1 All Aluminum Conductor, Bare Construction Aluminum alloy 1350-H19 wires, concentrically stranded. Specifications Meets or exceeds the following ASTM specifications: B-230 Aluminum Wire, 1350-H19 for Electrical Purposes B-231 Aluminum Conductors, Concentric-Lay-Stranded Applications Classes* AA and A are used primarily for overhead transmission and primary and secondary distribution where ampacity must be maintained and a lighter conductor (compared to ACSR) is desired, when conductor strength is not a critical factor. Classes B and C are used primarily as bus, apparatus connectors and jumpers where additional flexibility is required. *Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible. See referenced page in the Hardware & Supplies section: Suggested Prep Tool Cable End Strippers 2x2, 4x4 - I-9 Code Word Size (AWG or kcmils) No. of Wires Class Individual Wire Dia. (in) Complete Cable Dia. (in) DC @ 20˚C AC @ 20˚C Allowable Ampacity (amps) Iris 2 7 AA, A .0974 .292 .26000 .31800 185 Poppy 1/0 7 AA, A .1228 .368 .16400 .20000 247 Aster 2/0 7 AA, A .1379 .414 .13000 .15900 286 Phlox 3/0 7 AA, A .1548 .464 .10300 .12600 331 Oxlip 4/0 7 AA, A .1739 .522 .08170 .09990 383 Laurel 266.8 19 A .1185 .592 .06480 .07930 444 Tulip 336.4 19 A .1331 .665 .05140 .06300 513 Daffodil 350 19 A .1357 .679 .04940 .06050 526 Canna 397.5 19 AA, A .1446 .723 .04350 .05340 570 Cosmos 477 19 AA .1584 .792 .03620 .04450 639 Dahlia 556.5 19 AA .1711 .856 .03110 .03820 703 Mistletoe 556.5 37 AA .1226 .858 .03110 .03820 704 Meadowsweet 600 37 AA .1273 .891 .02280 .03550 738 Orchid 636 37 AA, A .1311 .918 .02720 .03550 765 Petunia 750 37 AA .1424 .997 .02300 .02860 847 Arbutus 795 37 AA .1466 1.026 .02170 .02700 878 Magnolia 954 37 AA .1606 1.124 .01810 .02260 982 Bluebell 1033.5 37 AA .1671 1.170 .01670 .02100 1031 Narcissus 1272 61 AA, A .1444 1.300 .01360 .01730 1169 Coreopsis 1590 61 AA .1614 1.453 .01090 .01410 1333 Lupine 2500 91 A .1657 1.823 .00698 .00969 1706 Stranding Resistance (Ohms/M-ft) Other cables not listed here may be available upon request. Information based on Southwire specs. AAC www.ptsupply.com [email protected] 800-238-7514

All Aluminum Conductor, Bare 800-238-7514

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: All Aluminum Conductor, Bare 800-238-7514

1

All Aluminum Conductor, BareConstructionAluminum alloy 1350-H19 wires, concentrically stranded.

SpecificationsMeets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical PurposesB-231 Aluminum Conductors, Concentric-Lay-Stranded

ApplicationsClasses* AA and A are used primarily for overhead transmission and primary and secondary distribution where ampacity must be maintained and a lighter conductor (compared to ACSR) is desired, when conductor strength is not a critical factor. Classes B and C are used primarily as bus,

••

apparatus connectors and jumpers where additional flexibility is required.

*Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Code WordSize (AWG or kcmils) No. of Wires Class

Individual Wire Dia. (in)

Complete Cable Dia. (in) DC @ 20˚C AC @ 20˚C

Allowable Ampacity (amps)

Iris 2 7 AA, A .0974 .292 .26000 .31800 185

Poppy 1/0 7 AA, A .1228 .368 .16400 .20000 247

Aster 2/0 7 AA, A .1379 .414 .13000 .15900 286

Phlox 3/0 7 AA, A .1548 .464 .10300 .12600 331

Oxlip 4/0 7 AA, A .1739 .522 .08170 .09990 383

Laurel 266.8 19 A .1185 .592 .06480 .07930 444

Tulip 336.4 19 A .1331 .665 .05140 .06300 513

Daffodil 350 19 A .1357 .679 .04940 .06050 526

Canna 397.5 19 AA, A .1446 .723 .04350 .05340 570

Cosmos 477 19 AA .1584 .792 .03620 .04450 639

Dahlia 556.5 19 AA .1711 .856 .03110 .03820 703

Mistletoe 556.5 37 AA .1226 .858 .03110 .03820 704

Meadowsweet 600 37 AA .1273 .891 .02280 .03550 738

Orchid 636 37 AA, A .1311 .918 .02720 .03550 765

Petunia 750 37 AA .1424 .997 .02300 .02860 847

Arbutus 795 37 AA .1466 1.026 .02170 .02700 878

Magnolia 954 37 AA .1606 1.124 .01810 .02260 982

Bluebell 1033.5 37 AA .1671 1.170 .01670 .02100 1031

Narcissus 1272 61 AA, A .1444 1.300 .01360 .01730 1169

Coreopsis 1590 61 AA .1614 1.453 .01090 .01410 1333

Lupine 2500 91 A .1657 1.823 .00698 .00969 1706

StrandingResistance (Ohms/M-ft)

Other cables not listed here may be available upon request. Information based on Southwire specs.

AAC

[email protected] 800-238-7514

Page 2: All Aluminum Conductor, Bare 800-238-7514

2

Aluminum Conductor, Steel ReinforcedConstructionAluminum alloy 1350-H19 wires, concentrically stranded about a steel core. Core wire for ACSR is available with class A, B or C galvanizing; "aluminized" aluminum coated (AZ); or aluminum-clad (AW). Additional corrosion protection is available through the application of grease to the core or infusion of the complete cable with grease.

SpecificationsMeets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical PurposesB-231 Aluminum Conductors, Concentric-Lay-StrandedB-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced for ACSRB-341 Aluminum-Coated Steel Core Wire for ACSR/AZB-498 Zinc-Coated Steel Core Wire for ACSRB-802 Zinc-5% Aluminum-Mischmetal Alloy-Coated Steel Core Wire for ACSR

ApplicationsUsed as bare overhead transmission cable and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enables desired strength to be achieved without sacrificing ampacity.

••••••

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Code Word AWGStranding (Alum./Stl.) AIum. Steel

Steel Core

Complete Cable

Weight (lbs/M-ft) DC @ 20˚C AC @ 20˚C

Allowable Ampacity (amps)

Swanate 4 7/1 .0772 .1030 .1030 .257 67 .3990 .5190 140

Sparrow 2 6/1 .1052 .1052 .1052 .316 91 .2540 .3320 184

Sparate 2 7/1 .0974 .1298 .1298 .325 107 .2510 .3380 184

Raven 1/0 6/1 .1327 .1327 .1327 .398 145 .1590 .2170 242

Quail 2/0 6/1 .1489 .1489 .1489 .447 183 .1260 .1760 276

Pigeon 3/0 6/1 .1672 .1672 .1672 .502 230 .1000 .1440 315

Penguin 4/0 6/1 .1878 .1878 .1878 .563 291 .0795 .1190 357

Merlin 336.4 18/1 .1367 .1367 .1367 .684 365 .0510 .0625 519

Linnet 336.4 26/7 .1137 .0885 .2654 .720 462 .0505 .0618 529

Pelican 477 18/1 .1628 .1628 .1628 .814 517 .0360 .0442 646

Drake 795 26/7 .1749 .1360 .4080 1.107 1093 .0214 .0263 907

Resistance (Ohms/M-ft)

Individual Wire Dia. (in)

Diameter (in)

Other cables not listed here may be available upon request. Information based on Southwire specs.

ACSR

[email protected] 800-238-7514

Page 3: All Aluminum Conductor, Bare 800-238-7514

3

Covered Line Wire Aluminum ConductorConstructionAluminum alloy 1350-H19, 6201 or ACSR conductors, concentrically stranded. Covered with PE or XLP.

SpecificationsMeets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical PurposesB-231 Aluminum Conductors, Concentric-Lay-StrandedB-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)

•••

B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors

ApplicationsUsed primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor.

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Code WordSize

(AWG or kcmils) StrandingCover

Thickness (mils)Total Diameter

(mils) XLP Conv. Poly. Allowable Ampacity

6201 Aluminum Alloy

*Oilnut 1/0 7 60 518 159 159 250

*Waterash 2/0 7 60 567 195 195 290

*Planetree 4/0 7 60 683 297 297 385

All-Aluminum

Pear 4 1 30 264 47 47 135

Peach 2 7 45 373 84 84 180

Quince 1/0 7 60 477 136 136 240

Orange 2/0 7 60 522 167 167 280

Olive 4/0 7 60 626 253 253 370

Pomegranate 4/0 19 60 632 247 247 370

Mulberry 266.8 19 60 694 305 305 430

Annona 336.4 19 60 765 377 377 495

Huckleberry 477 37 80 931 538 538 610

Paw Paw 556.5 37 80 992 619 619 670

Breadfruit 636 61 95 1,081 715 715 720

Persimmon 795 61 95 1,186 877 877 825

Grapefruit 1,033.5 61 95 1,326 - 1,118 970

ACSR

Butternut 4 6/1 30 310 72 72 135

Hickory 4 7/1 30 317 83 83 135

Pignut 2 6/1 45 406 118 118 180

Almond 1/0 6/1 60 518 190 190 235

Pecan 2/0 6/1 60 567 233 233 270

Filbert 3/0 6/1 60 622 288 288 305

Buckeye 4/0 6/1 60 683 357 357 345

Weight (lbs/M-ft)

*AWG equivalent to ACSR construction or 1350 aluminum equivalent.Information based on Southwire specs.

Other cables not listed here may be available upon request.

Covered Line Wire, Aluminum

[email protected] 800-238-7514

Page 4: All Aluminum Conductor, Bare 800-238-7514

4

Duplex Service DropConstructionConductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either PE or XLP. Neutral messengers are concentrically stranded 6201, AAC or ACSR.

SpecificationsMeets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical PurposesB-231 Aluminum Conductors, Concentric-Lay-StrandedB-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)B-399 Concentric-Lay-Stranded 6201-T81 Aluminum Alloy Conductors

•••

•B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire

ApplicationsPrimarily used for 120V overhead service applications such as street lighting, outdoor lighting and temporary service for construction. To be used at voltages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75°C for PE insulated conductors or 90°C for XLP insulated conductors.

Code Word* AWG Stranding AWG Stranding XLP PE XLP PE

6201 Alloy Neutral-Messenger

Chihuahua 6 1 6 7 65 65 85 70

Vizsla 6 7 6 7 68 68 85 70

Harrier 4 1 4 7 99 99 115 90

Whippet 4 7 4 7 103 103 115 90

Schnauzer 2 7 2 7 157 157 150 120

Heeler 1/0 9 1/0 7 250 250 205 160

AAC Neutral-Messenger

Pekingese 6 1 6 7 61 61 85 70

Collie 6 7 6 7 64 64 85 70

Dachshund 4 1 4 7 92 92 115 90

Spaniel 4 7 4 7 96 96 115 90

Doberman 2 7 2 7 147 147 150 120

Malemute 1/0 9 1/0 7 234 234 205 160

ACSR Neutral-Messenger

Setter 6 1 6 6/1 72 72 85 70

Shepherd 6 7 6 6/1 75 75 85 70

Eskimo 4 1 4 6/1 110 110 115 90

Terrier 4 7 4 6/1 115 115 115 90

Chow 2 7 2 6/1 176 176 150 120

Bull 1/0 9 1/0 6/1 280 280 205 160

Phase Conductor

Bare Neutral Messenger

Weight (lbs/M-ft)

Allowed Ampacities

*Code word for XLP insulated products are formed by adding /XLP to the conventional code word (e.g. Chihuahua/XLP).

Information based on Southwire specs.

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Duplex Service Drop

[email protected] 800-238-7514

Page 5: All Aluminum Conductor, Bare 800-238-7514

5

Triplex Service DropConstructionConductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either PE or XLP. Neutral messengers are concentrically stranded 6201, AAC or ACSR.

SpecificationsMeets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical PurposesB-231 Aluminum Conductors, Concentric-Lay-StrandedB-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)B-399 Stranded 6201-T81 Aluminum Alloy ConductorsB-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire

Meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.

ApplicationsUsed to supply power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75°C for PE insulated conductors or 90°C for XLP insulated conductors.

•••••

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Code Word* AWG Stranding AWG Stranding XLP PE XLP PE

6201 Alloy Neutral-Messenger

Hippa 6 7 6 7 107 107 85 70

Barnacle 4 7 4 7 160 160 115 90

Shrimp 2 7 2 7 243 243 150 120

6201 Alloy Reduced Neutral-Messenger

Crab 4 7 6 7 143 143 115 90

AAC Neutral-Messenger

Patella 6 7 6 7 103 103 85 70

Oyster 4 7 4 7 154 154 115 90

ACSR Neutral-Messenger

Paludina 6 1 6 6/1 109 109 85 70

Whelk 4 1 4 6/1 - 164 115 90

Periwinkle 4 7 4 6/1 172 172 115 90

Neritina 1/0 7 1/0 6/1 420 420 205 160

Runcina 2/0 7 2/0 6/1 520 520 235 185

Zuzara 4/0 18 4/0 6/1 789 789 315 245

ACSR Reduced Neutral-Messenger

Strombus 4 7 6 6/1 151 151 115 90

Cockle 2 7 4 6/1 228 228 150 120

Janthina 1/0 7 2 6/1 366 366 205 160

Cerapus 4/0 18 2/0 6/1 681 681 315 245

Phase Conductor

Bare Neutral Messenger

Weight (lbs/M-ft)

Allowed Ampacity

*Code word for XLP insulated products are formed by adding /XLP to the conventional code word (e.g. Hippa/XLP).

Other cables not listed here may be available upon request.

Information based on Southwire specs.

Triplex Service Drop

[email protected] 800-238-7514

Page 6: All Aluminum Conductor, Bare 800-238-7514

6

Information based on Southwire specs.

*Code word for XLP insulated products are formed by adding /XLP to the con-ventional code word (e.g. Arabian/XLP).

Bare Neutral Messenger

Code Word*AWG or kcmils Stranding

AWG or kcmils Stranding XLP PE XLP PE

6201 Alloy Neutral-Messenger

Arabian 4 7 48.69 7 217 217 100 80

Belgian 2 7 77.47 7 328 328 135 105

Shetland 1/0 9 123.3 7 519 519 180 140

Thoroughbred 2/0 11 155.4 7 639 639 205 160

Walking 4/0 18 246.9 7 977 977 275 210

AAC Neutral-Messenger

Pinto 4 7 4 7 211 211 100 80

Mustang 2 7 2 7 318 318 135 105

Criollo 1/0 9 1/0 7 506 503 180 140

Percheron 2/0 11 2/0 7 619 619 205 160

Oldenburg 4/0 18 4/0 19 945 945 275 210

Lippizaner 336.4 19 336.4 19 1,519 1,519 370 280

ACSR Neutral-Messenger

Chola 6 7 6 6/1 153 153 75 60

Hackney 4 7 4 6/1 229 229 100 80

Palomino 2 7 2 6/1 347 347 135 105

Costena 1/0 9 1/0 6/1 549 549 180 140

Grullo 2/0 11 2/0 6/1 - 677 205 160

Suffolk 3/0 17 3/0 6/1 837 837 235 185

Appaloosa 4/0 18 4/0 6/1 1,038 1,038 275 210

Bronco 336.4 19 336.4 18.1 1,568 1,568 370 280

Weight (lbs/M-ft) Allowed

Ampacity

Phase Conductor

Quadruplex Service DropConstructionConductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either PE or XLP. Neutral messengers are concentrically stranded 6201, AAC or ACSR. Conductors are manufactured withridges for phase identification (one conductor one ridge, one conductor two ridges, one conductor plain).

SpecificationsMeets or exceeds the following ASTM specifications:

B-230 Aluminum Wire, 1350-H19 for Electrical PurposesB-231 Aluminum Conductors, Concentric-Lay-StrandedB-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR)B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors

••••

B-901 Compressed Round Stranded Aluminum Conductors Using Single Input WireMeets or exceeds all applicable requirements of ANSI/ICEA S-76-474.

ApplicationsUsed to supply three-phase power, usually from a pole-mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600V phase-to-phase or less and at conductor temperatures not to exceed 75°C for PE insulated conductors or 90°C for XLP insulated conductors.

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Other cables not listed here may be available upon request.

Quadruplex Service Drop

[email protected] 800-238-7514

Page 7: All Aluminum Conductor, Bare 800-238-7514

7

Triplex 600V Secondary UD HI-SCOREConstructionConductors are stranded, compressed 1350-H16/H26 aluminum, insulated with an XLP meeting the requirements of ANSI/ICEA S-81-570. Neutrals are triple yellow extruded stripe. Cables with "YES" neutrals have sequential footage markers. Conductors are durably surface printed for identification. Two-phase conductors and one neutral conductor are cabled to produce the triplex cable configuration. Conductors are also available paralleled.

SpecificationsMeets or exceeds the following applicable ASTM specifications:

B-231 Aluminum 1350 Conductors, Concentric-Lay-StrandedB-609 Aluminum 1350 Round Wire, Annealed and Intermidiate Tempers, for Electrical PurposesB-786 19 Wire Combination Unilay-Stranded Aluminum Conductors for Subsequent InsulationB-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire

HI-SCORE triplex or paralleled 600V secondary UD cable insulation meets or exceeds all grade and type require-ments of ANSI/ICEA S-81-570 and UL Standard 854 for Type USE-2.

ApplicationsUsed for secondary distribution and underground service at 600V or less, either direct burial or in ducts. Especially suited for applications requiring superior resistance to mechanical damage. Rated 90°C continuous operation, 130°C emergency overload and short circuit 250°C.

••••

Information based on Southwire specs.

Code WordAWG or kcmils Stranding

AWG or kcmils Stranding

Single Phase Conductor

Neutral Cond.

Complete Cable

Weight (lbs/M-ft)

Direct Burial

In Ducts

Vassar/HI-SCORE 4 7 4 7 345 345 745 192 125 90

Stephens/HI-SCORE 2 7 4 7 403 345 870 250 165 120

Ramapo/HI-SCORE 2 7 2 7 403 403 870 279 165 120

Brenau/HI-SCORE 1/0 9 2 7 512 403 1,106 387 215 160

Bergen/HI-SCORE 1/0 9 1/0 9 512 512 1,106 442 215 160

Converse/HI-SCORE 2/0 11 1 9 555 473 1,199 479 245 180

Hunter/HI-SCORE 2/0 11 2/0 11 555 555 1,199 535 245 180

Hollins/HI-SCORE 3/0 17 1/0 9 603 512 1,302 572 280 205

Sweetbriar/HI-SCORE 4/0 18 2/0 11 658 555 1,421 709 315 240

Monmouth/HI-SCORE 4/0 18 4/0 18 658 658 1,421 797 315 240

Pratt/HI-SCORE 250 26 3/0 17 732 603 1,581 856 345 265

Wesleyan/HI-SCORE 350 37 4/0 18 831 658 1,795 1,121 415 320

Newark/HI-SCORE 350 37 350 37 831 831 1,795 1,282 415 320

Rider/HI-SCORE 500 37 350 37 980 831 2,117 1,602 495 395

Fairfield/HI-SCORE 750 61 500 37 1,188 980 2,566 2,317 620 495

Phase Conductor Neutral Diameter (mils)

Allowed Ampacity

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9•

Triplex 600V

[email protected] 800-238-7514

Page 8: All Aluminum Conductor, Bare 800-238-7514

8

Information based on Southwire specs.

15kV Primary UD CableConstructionThe phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor, cov-ered by a semi-conducting XLP strand shield, a tree-retardant XLP primary insulation and a semi-conducting XLP insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires is applied over the insulation shield.

Size (AWG or kcmils) Stranding

No. of Wires AWG

Bare Phase Cond.

Over Insul.

Over Insul. Shield

Comp. Cable

Comp. Cable Weight

(lbs/M-ft)Direct Burial

In Ducts

Aluminum Conductor, .175" insulation, 100% insulation level Call for specs on cable with copper conductor

2 7 10 14* 283 678 758 886 356 168* 119*

1/0 19 16 14* 362 758 838 966 496 218* 155*

2/0 19 20 14* 406 800 880 1,008 589 248* 177*

3/0 19 25 14* 456 850 930 1,058 703 284* 201*

4/0 19 20 12* 512 908 988 1,149 852 324* 230*

250 37 16 10* 558 963 1,043 1,246 1,020 360* 257*

350 37 18 14** 660 1,063 1,163 1,291 866 389** 319**

500 37 25 14** 789 1,193 1,293 1,421 1,142 468** 384**

750 61 24 12** 968 1,383 1,483 1,644 1,613 569** 468**

1,000 61 20 10 1,117 1,530 1,630 1,834 2,055 642 542

Aluminum Conductor, .22" insulation, 133% insulation level Call for specs on cable with copper conductor

2 7 10 14* 283 770 850 978 403 168 119*

1/0 19 16 14* 362 850 930 1,058 547 218 155*

2/0 19 20 14* 406 893 973 1,101 642 248 177*

3/0 19 25 14* 456 943 1,023 1,151 760 284 201*

4/0 19 20 12* 512 1,000 1,080 1,242 912 324 230*

250 37 16 10* 558 1,055 1,155 1,359 1,101 360 257*

350 37 18 14** 660 1,155 1,255 1,383 936 389 319**

500 37 25 14** 789 1,285 1,385 1,513 1,219 468 384**

750 61 24 12** 968 1,475 1,575 1,737 1,702 569 468**

1,000 61 20 10 1,117 1,623 1,753 1,956 2,193 642 542

Allowed AmpacityDiameter (mils)

*Full neutral construction (ampacities assume - single phase circuit, one cable).**1/3 neutral cable (ampacities assume - three-phase circuit, three cables triplexed, multi-point grounding per ICEA methods).

SpecificationsMeets or exceeds the following applicable ASTM specifications:

B-3 Soft Annealed Copper WireB-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or SoftB-230 Aluminum, 1350-H19 Wire for Electrical Purposes

••

B-231 Aluminum 1350 Conductors, Concentric-Lay-StrandedB-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes

Manufactured to the latest edition of the following specifications and, in case of specification conflicts, in the order listed: ANSI/ICEA S-94-649, AEIC CS-8, RUS U-1.

ApplicationsPredominantly used for primary underground distribution; suitable for use in wet or dry locations, direct burial, underground duct and where exposed to sunlight. To be used at 15kV or less and at conductor temperatures not to exceed 90°C for normal operation.

Phase Conductor

Neutral

15kV HI-DRI UD

[email protected] 800-238-7514

Page 9: All Aluminum Conductor, Bare 800-238-7514

9

25kV Primary UD CableConstructionThe phase conductor is concentrically stranded, compressed soft copper or 1350-H16/26 aluminum alloy. The cable is composed of the conductor, covered by a semi-conducting XLP strand shield, a tree-retardant XLP pri-mary insulation and a semi-conducting XLP insulation shield. Conductors are available with either 100% or 133% insulation levels. A concentric neutral of bare copper wires is applied over the insulation shield.

SpecificationsMeets or exceeds the following applicable ASTM specifications:

B-3 Soft Annealed Copper WireB-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or SoftB-230 Aluminum, 1350-H19 Wire for Electrical PurposesB-231 Aluminum 1350 Conductors, Concentric-Lay-StrandedB-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes

Manufactured to the latest edition of the following specifications and, in case of specification conflicts, in the order listed: ANSI/ICEA S-94-649, AEIC CS-8, RUS U-1

ApplicationsPredominantly used for primary underground distribution; suitable for use in wet or dry locations, direct burial, underground duct and where exposed to sunlight. To be used at 25kV or less and at conductor temperatures not to exceed 90°C for normal operation.

•••••

Information based on Southwire specs.

Size (AWG or kcmils) Stranding

No. of Wires AWG

Bare Phase Cond.

Over Insul.

Over Insul. Shield

Comp. Cable

Comp. Cable Weight (lbs/M-ft)

Direct Burial

In Ducts

Aluminum Conductor, .26" insulation, 100% insulation level

1 19 13 14* 322 880 960 1,088 513 189* 134*

1/0 19 16 14* 362 920 1,000 1,128 590 214* 152*

2/0 19 20 14* 406 965 1,045 1,173 688 243* 173*

3/0 19 25 14* 456 1,015 1,095 1,223 808 278* 197*

4/0 19 20 12* 512 1,070 1,170 1,332 979 318* 225*

250 37 16 10* 558 1,125 1,225 1,429 1,153 353* 252*

350 37 18 14** 660 1,228 1,328 1,456 994 387** 320**

500 37 25 14** 789 1,358 1,458 1,586 1,284 466** 386**

750 61 24 12** 968 1,545 1,645 1,807 1,773 567** 475**

Copper Conduct, .26" insulation, 100% insulation level

1 19 20 14* 322 880 960 1,686 801 235* 168*

1/0 19 25 14* 362 920 1,000 1,128 937 268* 190*

2/0 19 20 12* 405 965 1,045 1,207 1,130 307* 220*

3/0 19 25 12* 456 1,015 1,095 1,257 1,363 351* 250*

4/0 19 20 10* 512 1,070 1,170 1,374 1,682 402* 287*

250 37 24 10* 558 1,125 1,225 1,429 1,959 445* 317*

350 37 18 12** 661 1,230 1,330 1,492 1,890 487** 403**

500 37 26 12** 790 1,358 1,458 1,619 2,575 575** 475**

Phase Conductor Neutral

Allowed AmpacityDiameter (mils)

*Full neutral construction (ampacities assume - single phase circuit, one cable).**1/3 neutral cable (ampacities assume - three-phase circuit, three cables triplexed, multi-point grounding per ICEA methods).

25kV HI-DRI UD

[email protected] 800-238-7514

Page 10: All Aluminum Conductor, Bare 800-238-7514

10

Bare Copper ConductorsConstructionBare copper, solid or stranded. Available in tempers hard, medium-hard, or soft. Stranded conductors are concentrically stranded in hard and medium-hard tempers and are Combination Unilay stranded in the soft-drawn temper.

SpecificationsMeets or exceeds the following applicable ASTM specifications:

B-1 Hard-Drawn Copper WireB-2 Medium-Hard Copper WireB-3 Soft or Annealed Copper WireB-787 19 Wire Combination Unilay-Stranded Soft Copper WireB-8 Concentric-Lay-Stranded Hard, Medium-Hard or Soft Copper Conductor

ApplicationsSolid and stranded (classes AA and A) bare copper are suitable for overhead transmission and distribution applications. Stranded conductor of greater flexibility (classes B and C) are suitable for uninsulated hook up, jumpers and grounds in electrical construction. Soft drawn copper is unilay construction.

•••••

AWGWeight

(lbs/M-ft)Diameter

(mils) Hard DrawnMedium

Hard DrawnSoft Drawn (Annealed)

Allowable Ampacity

Solid

14 12.4 64.1 2.626 2.613 2.525 -

12 19.8 80.8 1.652 1.643 1.588 -

10 31.4 101.9 1.039 1.033 .999 -

8 50 128.5 .653 .650 .628 95

6 79.4 162 .411 .409 .395 125

4 126.3 204.3 .258 .257 .249 170

2 200.9 257.6 .163 .162 .156 225

DC Resistance (Ohms/M-ft @ 20˚C)

Size (AWG or kcmils) Stranding

Stranding Class

Weight (lbs/M-ft)

Indv. Wires

Complete Cables Hard Drawn

Medium Hard Drawn

Soft Drawn (Annealed)

Allowable Ampacity

Stranded

8 7 B 51 49 146 .66630 .66290 .64080 95

6 7 B 81 61 184 .41910 .41690 .40300 130

4 7 A, B 128.9 77 232 .26360 .26220 .25340 170

2 7 A, B 204.9 97 292 .16600 .16500 .15780 230

1/0 7 A, AA 326.1 123 368 .10420 .10370 .10020 310

2/0 7 A, AA 410.9 138 414 .08627 .08224 .07949 355

3/0 7 A, AA 518.1 155 464 .06556 .06522 .06304 410

4/0 7 A, AA 653.3 174 522 .05199 .05172 .04999 480

4/0 19 B 653.3 106 528 .05199 .05172 .04999 480

250 19 A 771.9 115 574 .04400 .04378 .04231 530

350 19 A 1080.6 136 679 .03143 .03127 .03022 650

500 37 A, B 1543.8 116 814 .02200 .02189 .02116 810

DC Resistance (Ohms/M-ft @ 20˚C)Diameter (in)

Information based on Southwire specs.

Other cables not listed here may be available upon request.

Other cables not listed here may be available upon request.

Bare Copper

[email protected] 800-238-7514

Page 11: All Aluminum Conductor, Bare 800-238-7514

11

Covered Line Wire Copper ConductorConstructionConductors are hard or medium-hard concentrically stranded copper. Covered with black PE or XLP.

SpecificationsMeets or exceeds the following ASTM specifications:

B-1 Hard-Drawn Copper WireB-3 Medium Hard-Drawn Copper WireB-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft

Meets all applicable requirements of ANSI/ICEA S-70-547.

ApplicationsUsed primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor.

•••

Information based on Southwire specs.

Size (AWG or kcmils) Stranding

O.D. Covered (mils)

Weight (lbs/M-ft)

DC Resistance (ohms/M-ft @ 20˚C)

Allowable Ampacity

Solid

6 1 222 86.7 .411 130

4 1 264 135.3 .258 170

3 1 319 174.9 .205 195

2 1 348 218.1 .163 225

Stranded

6 7 238 90.3 .503 130

4 7 285 140.8 .316 175

2 7 373 227.1 .199 230

1/0 7 477 363.3 .125 305

2/0 7 522 453.3 .0992 350

3/0 7 570 565.6 .0788 405

4/0 7 626 707.6 .0625 465

250 19 677 825.4 .0530 520

300 19 729 984.6 .0442 580

350 19 779 1,144.5 .0380 640

500 37 950 1,637.2 .0278 785

750 61 1,128 2,422.8 .0182 995

1,000 61 1,307 3,234 .0140 1,180

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Covered Line Wire, Copper

[email protected] 800-238-7514

Page 12: All Aluminum Conductor, Bare 800-238-7514

12

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

Information based on Southwire specs.

Transformer Riser WireConstructionConductors are solid or stranded soft copper. Stranded conductors are concentrically stranded, compressed. The covering is high molecular weight PE, black.

SpecificationsMeets or exceeds the following ASTM specifications:

B-3 Soft or Annealed Copper WireB-8 Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard or Soft

••

AWG Stranding Bare CoveredWeight

(lbs/M-ft)

8 Solid 128.5 348.5 83

6 Solid 162 382 117

4 Solid 204.3 424.3 170

Diameter (mils)

ApplicationsUsed as uninsulated transformer risers at voltages up to and includ-ing 13.2kV. Although not treated as an insulation, the covering on transformer riser wire does reduce faults due to atmospheric conditions, shorts caused by excessive vibrations and faulting caused by objects crossing the leads.

Transformer Riser Wire

[email protected] 800-238-7514

Page 13: All Aluminum Conductor, Bare 800-238-7514

13

Copper Conductors

Conductor Shield

XLP Insulation

Insulation Shield

Copper Tape Shield

PVC Jacket

5kV, 5kVU Type MV-90 XLP, TS, PVCConstructionSingle conductor XLP insulated, shielded, thermoplastic jacket power cable. Proven XLP insulation, 90°C continuous conductor operating temperature, 100% copper tape shield coverage, fast stripping thermosetting insulation shield and it is triple extruded. Cable is sunlight resistant, suitable for direct burial. Also available listed for cable tray use in sizes 250 kcmils and larger upon request.

SpecificationsManufactured and tested in accordance with the latest revisions of the following standards and specification:

UL 1072 - Medium Voltage Power CablesICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for Use in the Transmission & Distribution of Electric Energy

Certified qualification tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully met the qualification testing requirements of AEIC CS-8.

ApplicationsFor use in aerial, direct burial, conduit, and underground duct installations as permitted by the NEC®. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal opera-tion, 130°C for emergency overload conditions and 250°C for short circuit conditions and are rated at 5kV, 100% (grounded system) and 133% insulation level (ungrounded system).

••

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

WS 5 End Stripper - I-9•

Information based on Southwire specs.

Size (AWG or kcmils)

Conductor Diameter (in)

Mininum Point Jacket

Thickness (in)Approx. Overall

Diameter (in)

Approx. Net Weight (lbs/M-ft) Duct

Conduit in Air

4 .225 .055 .654 309 110 97

2 .283 .055 .709 406 145 130

1 .322 .055 .749 474 170 155

1/0 .362 .055 .789 557 195 180

2/0 .405 .070 .860 681 220 205

3/0 .456 .070 .910 809 250 240

4/0 .512 .070 .965 968 290 280

250 .558 .070 1.020 1,108 320 315

350 .661 .070 1.125 1,462 385 385

500 .790 .070 1.250 1,977 470 475

750 .968 .070 1.437 2,826 585 600

1,000 1.117 .070 1.582 3,654 670 690

Allowable Ampacity

Type MV-90

[email protected] 800-238-7514

Page 14: All Aluminum Conductor, Bare 800-238-7514

14

Copper Conductors

Conductor Shield

XLP Insulation

Insulation Shield

Copper Tape Shield

PVC Jacket

15kV Type MV-90 XLP, TS, PVCConstructionSingle conductor XLP insulated, shielded, thermoplastic jacket power cable. Proven XLP insulation, 90°C continuous conductor operating temperature, 100% copper tape shield coverage, fast stripping thermosetting insulation shield and it is triple extruded. Cable is sunlight resistant, suitable for direct burial. Also available listed for cable tray use in sizes 250 kcmils and larger upon request.

SpecificationsManufactured and tested in accordance with the latest revisions of the following standards and specification:

UL 1072 - Medium Voltage Power CablesICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for Use in the Transmission & Distribution of Electric Energy

Certified qualification tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully met the qualification testing requirements of AEIC CS-8.

ApplicationsFor use in aerial, direct burial, conduit and underground duct installations as permitted by the NEC®. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal opera-tion, 130°C for emergency overload conditions and 250°C for short circuit conditions and are rated at 15kV, 100% insulation level (grounded system).

••

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

WS 5 End Stripper - I-9•

Information based on Southwire specs.

Size (AWG or kcmils)

Conductor Diameter (in)

Mininum Point Jacket

Thickness (in)Approx. Overall

Diameter (in)

Approx. Net Weight (lbs/M-ft) Duct

Conduit in Air

2 .283 .07 .905 531 155 150

1 .322 .07 .945 603 175 170

1/0 .362 .07 .985 692 200 195

2/0 .405 .07 1.025 797 230 225

3/0 .456 .07 1.075 930 260 260

4/0 .512 .07 1.130 1,095 295 295

250 .558 .07 1.185 1,241 325 330

350 .661 .07 1.290 1,605 390 395

500 .790 .07 1.415 2,132 65 480

750 .968 .07 1.602 3,002 565 585

1,000 1.117 .10 1.810 3,948 640 675

Allowable Ampacity (amps)

Type MV-90

[email protected] 800-238-7514

Page 15: All Aluminum Conductor, Bare 800-238-7514

15

Copper Conductors

Conductor Shield

XLP Insulation

Insulation Shield

Copper Wire Shield

PVC Jacket

Binder Tape

5kV, 5kVU Type MV-90 XLP, WS, PVCConstructionSingle conductor XLP insulated, shielded, thermoplastic jacket power cable. Proven XLP insulation, 90°C continuous conductor operating temperature, fast stripping thermosetting insulation shield and it is triple extruded. Cable is sunlight resistant, suitable for direct burial.

SpecificationsManufactured and tested in accordance with the latest revisions of the following standards and specification:

UL 1072 - Medium Voltage Power CablesICEA S-93-639 (NEMA WC 74) - 5-46kV Shielded Power Cable for Use in the Transmission & Distribution of Electric Energy

Certified qualification tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully met the qualification testing requirements of AEIC CS-8.

ApplicationsFor use in aerial, direct burial, conduit and underground duct installations as permitted by the NEC®. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal opera-tion, 130°C for emergency overload conditions and 250°C for short circuit conditions and are rated at 5kV, 100% (grounded system) and 133% insulation level (ungrounded system).

••

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

WS 5 End Stripper - I-9•

Information based on Southwire specs.

Size (AWG or kcmils)

Conductor Diameter (in)

Mininum Point Jacket

Thickness (in)Approx. Overall

Diameter (in)

Approx. Net Weight (lbs/M-ft) Duct

Conduit in Air

1 .322 .055 .777 442 170 155

1/0 .362 .07 .848 546 195 180

2/0 .405 .07 .888 646 220 205

3/0 .456 .07 .938 772 250 240

4/0 .512 .07 .993 926 290 280

250 .558 .07 1.048 1,065 320 315

350 .661 .07 1.153 1,412 385 385

500 .790 .07 1.278 1,920 470 475

750 .968 .07 1.465 2,759 585 600

1,000 1.117 .07 1.610 3,579 670 690

Allowable Ampacity (amps)

Type MV-90

[email protected] 800-238-7514

Page 16: All Aluminum Conductor, Bare 800-238-7514

16

Copper Conductors

Conductor Shield

XLP Insulation

Insulation Shield

Copper Wire Shield

PVC Jacket

Binder Tape

15kV Type MV-90 XLP, WS, PVCConstructionSingle conductor XLP insulated, shielded, thermoplastic jacket power cable. Proven XLP insulation, 90°C continuous conductor operating temperature, fast-stripping thermosetting insulation shield and it is triple extruded. Cable is sunlight resistant, suitable for direct burial.

SpecificationsManufactured and tested in accordance with the latest revisions of the following standards and specification:

UL 1072 - Medium Voltage Power CablesICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for Use in Transmission & Distribution of Electric Energy

Certified qualification tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully met the qualification testing requirements of AEIC CS-8.

ApplicationsFor use in aerial, direct burial, conduit and underground duct installations as permitted by the NEC®. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal opera-tion, 130°C for emergency overload conditions and 250°C for short circuit conditions and are rated at 15kV, 100% insulation level (grounded system).

••

See referenced page in the Hardware & Supplies section: Suggested Prep ToolWS 5 End Stripper - I-9

Information based on Southwire specs.

Size (AWG or kcmils)

Conductor Diameter (in)

Minimum Point Jacket

Thickness (in)Approx. Overall

Diameter (in)

Approx. Net Weight (lbs/M-ft) Duct

Conduit in Air

2 .283 .07 .933 494 155 150

1 .322 .07 .973 563 175 170

1/0 .362 .07 1.013 651 200 195

2/0 .405 .07 1.053 753 230 225

3/0 .456 .07 1.103 884 260 260

4/0 .512 .07 1.170 1,119 295 295

250 .558 .07 1.225 1,266 325 330

350 .661 .07 1.330 1,633 390 395

500 .790 .07 1.455 2,162 465 480

750 .968 .07 1.642 3,034 565 585

1,000 1.117 .10 1.850 3,985 640 675

Allowable Ampacity

Type MV-90

[email protected] 800-238-7514

Page 17: All Aluminum Conductor, Bare 800-238-7514

17

2.4kV Type MV-90 EPR Heavy Wall, N/SConstructionSingle conductor EPR insulated, PVC jacket power cable. Flexible, easy bending insulation, easy cable preparation, 90°C continuous operating temperature, resistance to moisture. Flame-retardant. Also available listed for cable tray use in sizes 1/0 and larger.

SpecificationsManufactured and tested in accordance with the latest revisions of the following standards and specification:

UL 1072 - Medium Voltage Power CablesICEA S-96-659 (NEMA WC 71) - Unshielded Cables Rated 2001-5000 Volts for Use in the Distribution of Electric Energy

ApplicationsFor use primarily in raceways in industrial applications as specified by the NEC®. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload condi-tions and 250°C for short circuit conditions and are rated at 2.4kV in wet or dry locations.

••

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

WS 5 End Stripper - I-9•

Copper Conductors

Conductor Shield

EPR Insulation

PVC Jacket

Information based on Southwire specs.

Size (AWG or kcmils)

Conductor Diameter (in)

Jacket Thickness (in)

Approx. Overall Diameter (in)

Approx. Net Weight (lbs/M-ft) Duct

Conduit in Air

6 .178 .080 .645 253 85 75

4 .225 .080 .692 321 110 97

2 .283 .080 .750 422 145 130

1 .322 .080 .789 489 170 155

1/0 .362 .080 .829 574 195 180

2/0 .405 .080 .871 676 220 205

3/0 .456 .095 .954 834 250 240

4/0 .512 .095 1.010 995 290 280

250 .558 .110 1.127 1,199 320 315

350 .661 .110 1.229 1,560 385 385

500 .790 .110 1.357 2,088 470 475

750 .968 .125 1.608 3,044 585 600

1,000 1.117 .125 1.756 3,897 670 690

Allowable Ampacity

Type MV-90

[email protected] 800-238-7514

Page 18: All Aluminum Conductor, Bare 800-238-7514

18

5kVU, 8kV Type MV-105 TS, PVC, CT RatedConstructionSingle conductor EPR insulated, shielded, thermoplastic jacketed power cable. Flexible, easy bending insulation, easy cable preparation, fast strip-ping thermosetting insulation shield, 105°C continuous operating tem-perature, 100% shield coverage and it is triple extruded. Cable is sunlight resistant, suitable for direct burial and listed for cable tray use in sizes 1/0 and larger.

SpecificationsManufactured and tested in accordance with the latest revisions of the following standards and specifications:

UL 1072 - Medium Voltage Power Cables ICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for Use in the Transmission & Distribution of Electric Energy

••

ICEA S-97-682 (when requested) 5-46 kV Standard for Utility Shielded Power CableUL 1685 - (AWG 1/0 and larger) -UL Flame Exposure TestIEEE 1202 - Flame Test (70,000 Btu/hr Vertical Tray Test)

Certified qualification tests were performed in accordance with the requirements of ICEA CS-6. Cable has fully met the qualification testing requirements of ICEA CS-6.

ApplicationsFor use in aerial, direct burial, cable trays, conduit and underground duct installations as permitted by the NEC®. These cables are capable of operating continuously at a conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload conditions and 250°C for short circuit conditions and are rated at 5kV, 133% (ungrounded system) and 8kV 100% insulation level (grounded system).

•••

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

WS 5 End Stripper - I-9•

Conductor Shield

EPR Insulation

Insulation Shield

Copper Tape Shield

PVC Jacket

Copper Conductors

Information based on Southwire specs.

Size (AWG or kcmils)

Conductor Diameter (in)

Min. Point Jacket Thickness (in)

Approx. Overall Diameter (in)

Approx. Net Weight (lbs/M-ft) Duct

Conduit in Air

6 .178 .055 .656 282 92 84

4 .225 .055 .701 351 120 110

1 .322 .055 .799 525 180 175

1/0 .362 .070 .870 641 210 200

2/0 .405 .070 .910 745 235 225

3/0 .456 .070 .960 877 270 270

4/0 .512 .070 1.015 1,036 310 305

250 .558 .070 1.070 1,181 345 355

350 .661 .070 1.175 1,543 415 430

500 .790 .070 1.300 2,067 505 530

750 .968 .070 1.487 2,932 630 665

1,000 1.117 .070 1.632 3,771 720 770

Allowable Ampacity

Type MV-105

[email protected] 800-238-7514

Page 19: All Aluminum Conductor, Bare 800-238-7514

19

5kV, 5kVU Type MV-105 TS, GW, PVC, CT RatedConstructionThree conductor EPR insulated, shielded, thermoplastic jacketed power cables with grounding conductor. Alternate constructions available.

SpecificationsManufactured and tested in accordance with the latest revisions of the following standards and specifications:

UL 1072 - Medium Voltage Power CablesICEA S-93-639 (NEMA WC 74) - 5-46 kV Shielded Power Cable for use in the Transmission & Distribution of Electric EnergyICEA S-97-682 (when requested) 5-46 kV Standard for Utility Shielded Power CableUL 1685 - UL Flame Exposure TestIEEE 1202 (Sizes 4 AWG and larger) - Flame Test (70,000 Btu/hr Vertical Tray Test)

Certified qualification tests were performed in accordance with the requirements of AEIC CS-8. Cable has fully met the qualification testing requirements of AEIC CS-8.

ApplicationsFor use in aerial installations, direct buried, cable trays, troughs or raceway. These cables are capable of operating continuously at a maximum conductor temperature of 105°C for normal operation, 140°C for emergency overload conditions and 250°C for short circuit conditions and are rated at 5kV, 100% (grounded system) and 133% insulation levels (ungrounded system).

••

••

See referenced page in the Hardware & Supplies section: Suggested Prep ToolWS 5 End Stripper - I-9

PVC Jacket

Copper Conductors

Conductor ShieldEPR Insulation

Insulation ShieldCopper Tape Shield

Core Binder Tape

Fillers

Ground Conductor

Information based on Southwire specs.

Size (AWG or kcmils)

Conductor Diameter (in)

Ground Conductor

(AWG)Min. Point Jacket

Thickness (in)Approx. Overall

Diameter (in)

Approx. Net Weight (lbs/M-ft) Duct

Conduit in Air

2 .283 6 .070 1.443 1,447 145 135

1 .322 4 .070 1.529 1,730 165 155

1/0 .362 4 .070 1.616 1,987 190 185

2/0 .405 4 .100 1.765 2,421 220 210

3/0 .456 3 .100 1.873 2,869 250 245

4/0 .512 3 .100 1.992 3,384 285 285

250 .558 3 .100 2.123 3,868 315 315

350 .661 2 .100 2.349 5,056 380 390

500 .790 1 .100 2.619 6,770 460 475

750 .968 1/0 .125 3.077 9,722 570 585

Allowable Ampacity (amps)

Type MV-105

[email protected] 800-238-7514

Page 20: All Aluminum Conductor, Bare 800-238-7514

20

Type TC Power Cable 600V THHN/PVC, GWConstructionAvailable in sizes 8 AWG through 750 kcmils and is manufactured using Type THHN or THWN conductors. Individual conductors are bare annealed copper covered with a PVC insulation over which a nylon (polyamide) or UL listed equal jacket is applied. The overall jacket consists of a flame- retardant, moisture- and sunlight-resistant PVC jacket. Non-halogen jacket available upon request.

SpecificationsMeets or exceeds the applicable requirements of the following standards and specifications:

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

Cable End Strippers 2x2, 4x4 - I-9

ASTM - (All applicable standards)UL 1277 - Electrical Power and Control Tray CablesUL 1581 - Electrical Wires, Cables and Flexible CordsICEA S-58-679 - Control Cable Conductor Identification. (Method 4 - single color compounds with surface printing of numbers)UL 1685 - UL Flame Exposure Test (70,000 Btu/hr)ICEA T-29-520 - Vertical Cable Tray Flame Test (210,000 Btu/hr)IEEE 1202 - Flame Testing of Cables for Use in Cable Tray in Industrial and Commercial Occupancies (70,000 Bth/hr)

ApplicationsUsed to supply power to motors or for connection to other power devices in industrial settings. Primary installa-tions include cable trays, raceways and outdoor locations where supported by a messenger wire. Type TC Power Cable is listed for direct burial and for use in Class 1, Division 2 hazardous locations and Class 1 control circuits. This cable may be used at temperatures not to exceed 75°C in wet locations and 90°C in dry locations. 6 and 8 AWG constructions with insulated grounds (standard) and 4 AWG and larger with bare or insulated ground are UL Listed for exposed runs (ER) per NEC® 336.10.

••••

•••

Copper Conductors

PVC Insulation with Nylon Jacket

Ground Conductor

Ground Conductor

PVC Jacket

Information based on Southwire specs.

Size (AWG or kcmils) Stranding

Ground Conductor

(AWG)Average Overall

Diameter (in)Approx. Weight

(lbs/M-ft) 75˚C 90˚C

8 7 10 .625 295 50 55

6 7 8 .710 433 65 75

4 7 8 .795 605 85 95

2 7 6 .958 940 115 130

1 19 6 1.100 1,193 130 150

1/0 19 6 1.184 1,442 150 170

2/0 19 6 1.281 1,730 175 195

3/0 19 4 1.391 2,159 200 225

4/0 19 4 1.508 2,613 230 260

250 37 4 1.659 3,065 255 290

350 37 3 1.942 4,270 310 350

500 37 2 2.220 5,899 380 430

750 61 1 2.652 8,600 475 535

Ampacity

Type TC

[email protected] 800-238-7514

Page 21: All Aluminum Conductor, Bare 800-238-7514

21

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

Cable End Strippers 2x2, 4x4 - I-9

Type TC Composite Cable 600V, TFFN or VW-1 THHN/THWNConstructionMulticonductor cables have TFFN or VW-1 THHN/THWN (PVC/Nylon) conductors with an overall gas/vapor-tight PVC jacket. Three power conductors and four or six control conductors.

SpecificationsConforms to the following standards and specifications:

NEC® Article 392 Cable Trays and 336 Power and Control Cable Type TCStandard 1277 of Underwriters Laboratories, Inc.ICEA T-30-520 - Flame TestICEA T-29-520 - Vertical Cable Tray Flame Test (210,000 Btu/hr)IEEE-383 - 70,000 BTU Cable Tray Propagation TestIEEE 1202 - 70,000 BTU Flame TestsCSA FT4UL E60749

ApplicationsFor supplying power and control signals to motors or providing connection to other power devices utilizing remote control circuits. Specifically approved for direct burial, wet or dry locations and outdoors in cable trays where a sunlight-resistant rating is required. UL Listed and OSHA acceptable. Recognized for use in Class 1 or 2, Division 2 hazardous locations and for installation in trays, wireways, troughs, channels, ducts and conduit.

••••••••

Stranded Bare Copper

High Dielectric Strength PVC Insulation

Conductor Jacket

Tape Binder (optional)

PVC Jacket

Note: Stranding is Class B, 2-14 AWG

Information based on AIW specs.

No. of Conductors AWG

No. of Conductors AWG

Overall Jacket Thickness (mils)

Approx. O.D. (in)

Approx. Weight (lbs/M-ft)

3 12 4 14 45 .470 192

3 10 4 14 45 .515 265

3 8 4 14 60 .650 356

3 6 4 14 60 .715 458

3 4 4 14 80 .880 702

3 2 4 14 80 1.005 982

Power Conductors Control Conductors

Type TC

[email protected] 800-238-7514

Page 22: All Aluminum Conductor, Bare 800-238-7514

22

Copper Conductors

PVC Insulation with Nylon Jacket

Ground Conductor

Filler

PVC Jacket

Binder String

Type TC Power Cable 600V, XHHW/PVC, GWConstructionAvailable in sizes 8 AWG through 750 kcmils and is manufactured using Type XHHW-2 conductors. Individual conductors are bare annealed copper covered with XLP insulation. The overall jacket consists of a flame-retardant, moisture- and sunlight-resistant PVC jacket. Non-halogen jacket available upon request.

SpecificationsMeets or exceeds the applicable requirements of the following standards and specifications:

ASTM - (All applicable standards)UL 44UL 1277 - Electrical Power and Control Tray Cables. UL 1581 - Electrical

•••

Wires, Cables and Flexible CordsICEA S-58-679 - Control Cable Conductor Identification. (Method 4 - single color (black) compounds with surface printing of numbers)UL 1685 - Flame Exposure Test (70,000 Btu/hr)ICEA T-29-520 - Vertical Cable Tray Flame Test (210,000 Btu/hr)IEEE 1202 - Flame Testing of Cables for Use in Cable Tray in Industrial and Commercial Occupancies (70,000 Bth/hr)

Meets and exceeds all construction requirements of ICEA S-95-658 (NEMA WC 70) - Unshielded 0 - 2 kV Cables, with testing frequencies based on UL requirements. ApplicationsFor supplying power to motors or for connection to other power devices in industrial settings. Primary installa-tions include cable trays, raceways and outdoor locations where supported by a messenger wire. Type TC Power Cable is listed for direct burial or in underground ducts and for use in Class 1, Division 2 hazardous locations and Class 1 control circuits. This cable may be used in wet and dry locations at temperatures not to exceed 90°C. 6 and 8 AWG constructions with insulated grounds (standard) and 4 AWG and larger with bare or insulated ground are UL Listed for exposed runs (ER) per NEC® 336.10°C.

•••

Size (AWG or kcmils) Stranding

Ground Conductor

(AWG)Average Overall

Diameter (in)Approx. Weight

(lbs/M-ft)Ampacity 90˚C

8 7 10 .681 330 55

6 7 8 .766 468 75

4 7 8 .797 606 95

2 7 6 .960 954 130

1 19 6 1.100 1,173 150

1/0 19 6 1.186 1,421 170

2/0 19 6 1.279 1,704 195

3/0 19 4 1.385 2,135 225

4/0 19 4 1.506 2,580 260

250 37 4 1.653 3,021 290

300 37 3 1.827 3,684 320

350 37 3 1.935 4,219 350

400 37 3 2.032 4,747 380

500 37 2 2.214 5,838 430

750 61 1 2.663 8,543 535

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

Cable End Strippers 2x2, 4x4 - I-9

Information based on Southwire specs.

Type TC

[email protected] 800-238-7514

Page 23: All Aluminum Conductor, Bare 800-238-7514

23

RHH/RHW Power Cable 600V CT RatedConstructionRHH or RHW-2 or USE-2 copper conductors are annealed (soft) copper. Insulation is an abrasion-, moisture-, heat-resistant and flame-retardant XLP. This product is sunlight resistant and rated for cable tray use.

SpecificationsMeets or exceeds the applicable requirements of the following standards and specifications:

UL 44 - Thermoset-Insulated Wires and CablesUL 1581 - UL Flame Exposure Test (VW-1)UL 854 - Service Entrance CablesUL 1685 - UL Flame Exposure TestICEA S-95-658 (NEMA WC70) Unshielded Power Cables 2000 Volts or Less for the Distribution of Electrical EnergyIEEE 1202 Flame Test (4/0 and Larger)

Type RHH or RHW-2 or USE-2 meets and exceeds all construction requirements of ICEA S-95-658 (NEMA WC 70) - Unshielded 0 - 2kV cables, with testing frequencies based on UL requirements. ApplicationsFor use in conduit or cable tray as specified in the NEC®. When used as Type USE-2 conductor is suitable for use as underground service entrance cable for direct burial at conductor temperatures not to exceed 90°C. When used as RHH or RHW-2, conductor temperatures shall not exceed 90°C in wet or dry locations. Voltage rating for RHH or RHW-2 or USE-2 conduc-tors is 600V.

•••••

See referenced page in the Hardware & Supplies section: Suggested Prep Tool

Cable End Strippers 2x2, 4x4 - I-9

Size (AWG or kcmils)

No. of Strands

Approx. Overall Diameter (in)

Approx. Weight (lbs/M-ft) Conduit Free Air

1/0 19 .525 390 170 260

2/0 19 .568 481 195 300

3/0 19 .619 597 225 350

4/0 19 .675 741 260 405

250 37 .751 880 290 455

350 37 .854 1,207 350 570

500 37 .983 1,693 430 700

750 61 1.191 2,516 535 885

1,000 61 1.340 3,315 615 1,055

Allowable Ampacities (amps)

Information based on Southwire specs.

RHH/RHW

[email protected] 800-238-7514

Page 24: All Aluminum Conductor, Bare 800-238-7514

24

Welding Cable

105˚C, BlackConstructionBare, annealed copper per ASTM B-3. 30 AWG rope lay stranded per ASTM B-172. Jacket is black thermoset EPDM. 105°C to -55°C. RoHS compliant.

ApplicationsDesigned for welding cable use where resistance to cuts, tears and abrasion is required.

90˚C, OrangeConstructionBare, annealed copper per ASTM B-3. 34 AWG rope lay stranded per ASTM B-172 (Class M #34 stranding). Jacket is oil-resistant, thermoset CPE per ASTM D-4313. Rated 90°C to -55°C.

ApplicationsDesigned for welding cable use where resistance to cuts, tears and abra-sion is required.

Size (AWG or kcmils) Stranding Nominal O.D. (in) Amps*

Shipping Weight (lbs/M-ft)

6 665 x 34 .395 105 134

4 1,045 x 34 .450 140 191

2 1,650 x 34 .515 190 286

1 2,090 x 34 .545 220 350

1/0 2,640 x 34 .600 260 454

2/0 3,300 x 34 .685 300 530

3/0 4,180 x 34 .755 350 658

4/0 5,225 x 34 .825 405 839

*Ampacity ratings are based on cable in free air at 30˚C. Ampacities will be greater when used for intermittent welding applications.

Size (AWG or kcmils) Stranding Nominal O.D. (in) Amps*

Shipping Weight (lbs/M-ft)

6 259 x 30 .320 115 125

4 413 x 30 .375 150 182

2 651 x 30 .440 205 271

1 826 x 30 .505 240 360

1/0 1,044 x 30 .570 285 444

2/0 1,308 x 30 .605 325 535

3/0 1,653 x 30 .670 380 667

4/0 2,071 x 30 .720 440 809

*Ampacity ratings are based on cable in free air at 30˚C. Ampacities will be greater when used for intermittent welding applications.

Information based on AIW specs.

Information based on AIW specs.

Separator

Thermoset Insulation

Class K (#30) Rope Lay Stranding

Welding Cable

[email protected] 800-238-7514

Page 25: All Aluminum Conductor, Bare 800-238-7514

25

Type SOOW Cable 90°C, 600VConstructionStranded bare copper, EPR insulation, suitable fillers, separator, oil- and weather-resistant, black CPE jacket.

SpecificationsMeets or exceeds all applicable requirements of:

UL 62 (Flexible Cord and Fixture Wire)CSA Standard 22.2 No. 49 (Flexible Cords and Cables)Mine Safety and Health Administration (MSHA) flame resistance for Mining Applications

This product complies with the requirements of Federal and Military Specification JC-580B, NEC® Article 400 and is OSHA acceptable.

•••

ApplicationsPermitted for use as specified by Article 400 and related articles of the NEC®. Some typical applications for Type SOOW Cords include wiring for industrial machinery, motors and associated equipment, portable tools and equipment, and temporary electrical power and lighting installations for construction sites. Type SOOW Cords are suitable for use in (i) dry locations not to exceed minimum -40°C or maximum 90°C or (ii) wet locations or other applicable locations. When exposed to oil or coolant at temperatures not to exceed 60°C. Type SOOW cords are ideal for flex applications in harsh environments where the highest degree of oil resistance and extended service life are essential.

AWG StrandingNominal Insul.

Thickness (mils)

Nom. Overall

Dia. (mils)Weight

(lbs/M-ft) Ampacity

18/2 16 x 30 30 345 70 10

18/3 16 x 30 30 365 80 7

18/4 16 x 30 30 390 95 5.6

16/2 26 x 30 30 370 80 13

16/3 26 x 30 30 390 95 10

16/4 26 x 30 30 420 115 8

14/2 41 x 30 45 510 135 18

14/3 41 x 30 45 535 170 15

14/4 41 x 30 45 575 205 12

12/2 65 x 30 45 570 195 25

12/3 65 x 30 45 595 225 20

12/4 65 x 30 45 650 270 16

10/2 104 x 30 45 620 250 30

10/3 104 x 30 45 660 290 25

10/4 104 x 30 45 715 355 20

AWG StrandingNominal Insul.

Thickness (mils)

Nom. Overall

Dia. (mils)Weight

(lbs/M-ft) Ampacity

8/2* 65 x 26 50 660 290 40

8/3* 65 x 26 50 720 365 35

8/4* 65 x 26 50 780 500 28

8/5* 65 x 26 50 860 545 28

6/3* 101 x 26 50 800 515 45

6/4* 101 x 26 50 845 620 36

6/5* 101 x 26 50 945 750 36

4/2* 119 x 25 50 890 500 70

4/3* 119 x 25 50 940 670 60

4/4* 119 x 25 50 1,010 835 48

4/5* 119 x 25 50 1,135 1,065 48

2/3* 133 x .0211 55 1,090 1,030 80

2/4* 133 x .0211 55 1,170 1,285 64

2/5* 133 x .0211 55 1,435 1,620 64

*Not UL or CSA, but manufactured to acceptable commercial standards. 2-8 AWG are non-UL and non-CSA, but the option is available.

See referenced pages in the Hardware & Supplies sectionSuggested Prep Tools

Cable End Strippers 2x2, 4x4 - I-9MKO1A Jacket Stripper - I-11721 Multi-Wire Stripper/Cutter - I-9

•••

For SDN® Flexible Control Cable see page 16 in the

Instrumentation & Tray section

Flexible Bunch Stranded Bare Copper Conductors

Synthetic Rubber Insulation (EPDM)

Separator

Thermoset CPE Jacket

Information based on AIW specs.

Type SOOW

[email protected] 800-238-7514

Page 26: All Aluminum Conductor, Bare 800-238-7514

26

Type SOW Industrial Motor Lead Cable

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolCable End Strippers 2x2, 4x4 - I-9

AWG Stranding Conductor O.D. (in)Insulation

Thickness (in)Jacket

Thickness (in) Nominal O.D. (in) AmpsShipping Weight

(lbs/M-ft)

16 26 x .01 .060 .030 .03 .186 13 25

14 41 x .01 .075 .045 .03 .233 18 48

12 65 x .01 .095 .045 .03 .253 25 51

10 104 x .01 .120 .045 .03 .278 30 66

90°C, 600VConstructionStranded, annealed bare copper conductor, EPDM insulation, heavy-duty, oil-resistant thermoset jacket. ApplicationsDesigned for use as motor and power leads where flexibility and portability are required.

For SDN® Flexible Control Cable see page 16 in the

Instrumentation & Tray section

Information based on AIW specs.

Stranded Copper Conductor

EPDM Insulation

Thermoset Jacket

Type SOW

[email protected] 800-238-7514

Page 27: All Aluminum Conductor, Bare 800-238-7514

27

See referenced pages in the Hardware & Supplies section:

Suggested Prep ToolsMK01A Jacket Stripper - I-11MK04 Jacket Stripper - I-11

••

Type G & G-GC Round 90°C, 2kV & 600V/2kVConstructionManufactured with rope-lay stranded, bunched members, annealed copper conductors which are insulated with a premium-grade EPDM. The three or four insulated conductors are assembled round with non-wicking rubber fillers as needed and are covered with a black jacket rated -40°C - 90°C (90°C dry locations, 75°C wet locations).

SpecificationsUL ListedCSA and MSHA approved

••

RoHS compliantMeets FT-5 Flame Test

••

Size (AWG or kcmils)

Cond. Strand

Ground Check AWG

Ground Cond. AWG

Nom. Insulation Thick. (in)

Nominal O.D. (in)

Current Amps

Approx. Net Weight (lbs/M-ft)

3 Conductor Type G-GC 2kV

8 133 10 2#10 .060 .965 65 665

6 259 10 2#10 .060 1.050 87 830

4 259 10 2#8 .060 1.105 114 1,145

2 259 10 2#7 .080 1.300 152 1,485

1 259 8 2#6 .080 1.465 177 2,100

1/0 259 8 2#5 .080 1.605 205 2,550

2/0 259 8 2#4 .080 1.750 237 3,020

3/0 259 8 2#3 .080 1.860 274 3,660

4/0 259 8 2#2 .080 1.940 316 4,410

250 627 8 2#2 .095 2.390 352 6,060

350 855 8 2#1/0 .095 2.680 433 7,400

500 1,235 8 2#2/0 .095 3.030 536 10,100

4 Conductor Type G 600V/2kV

8 133 4#12 - .060 1.045 52 635

6 259 4#12 - .060 1.125 70 900

4 259 4#10 - .060 1.210 91 1, 280

2 259 4#9 - .080 1.435 122 2,000

1 259 4#8 - .080 1.650 142 2,660

1/0 259 4#7 - .080 1.720 164 3,140

2/0 259 4#6 - .080 1.860 190 3,780

3/0 259 4#5 - .080 2.075 219 4,500

4/0 259 4#4 - .080 2.155 253 5,520

ApplicationsFor use in industrial and light- to medium-duty mining applications, heavy-duty service as power supply cable, power cable for mobile and portable electrical equipment at continuous conductor temperature of 90°C. Type G cables are suitable for use on three-phase AC systems where 3 or 4 conductors are needed and grounding is required. Excellent flexibility, resistance to oils, solvents, ozone, aging and abrasion.

Color Coding: 3-conductor White/Black/Red4-conductor White/Black/Red/Orange

Information based on Southwire specs.

Industrial Grade Cable

[email protected] 800-238-7514

Page 28: All Aluminum Conductor, Bare 800-238-7514

28

Mine Power Feeder Cable 90°C, 5kV/8kV/15kVConstructionBare stranded copper, extruded semi-conductor shield, XLP insulation, extruded insulation shield, ground and ground check conductors, jute fillers, cable reinforcement and black PVC jacket.

SpecificationsUL ListedOSHA and MSHA acceptable

••

Passes MSHA Flame TestMeets ICEA requirements

••

ApplicationsFor use in high-voltage distribution circuits for permanent or semi-portable installations in bore holes, shafts, open pits, strip mines and tunnels.

AWG or kcmils

No. of Strands

Insulation Thickness (in) AWG Strands AWG

Insulation Thickness (in)

Nominal O.D.(in) Amps

Approx. Ship. Weight (lbs/M-ft)

5kV - 100% & 133% Insulation Level - ES-13139

6 7 .09 10 7 x .0385 10 .030 1.235 93 991

4 7 .09 8 7 x .0486 8 .045 1.320 122 1,197

2 7 .09 6 7 x .0612 8 .045 1.460 159 1,653

2/0 19 .09 3 7 x .0867 8 .045 1.690 243 2,591

4/0 19 .09 1 19 x .0664 8 .045 1.950 321 3,806

250 37 .09 1/0 19 x .0745 8 .045 2.075 355 4,660

350 37 .09 2/0 19 x .0837 8 .045 2.285 435 6,130

500 37 .09 4/0 19 x .1055 8 .045 2.550 536 8,240

8kV - 100% Insulation Level - ES-13140

6 7 .115 10 7 x .0385 10 .030 1.350 93 1,077

4 7 .115 8 7 x .0486 8 .045 1.445 122 1,290

2 7 .115 6 7 x .0612 8 .045 1.565 159 1,710

1 19 .115 5 7 x .0688 8 .045 1.630 184 1,996

2/0 19 .115 3 7 x .0867 8 .045 1.850 243 2,857

4/0 19 .115 1 19 x .0664 8 .045 2.070 321 3,946

250 37 .115 1/0 19 x .0745 8 .045 2.190 355 4,980

350 37 .115 2/0 19 x .0837 8 .045 2.400 435 6,280

500 37 .115 4/0 19 x .1055 8 .045 2.700 536 8,470

15kV - 100% Insulation Level - ES-13141

2 7 .175 6 7 x .0612 8 .045 1.875 164 2,117

1 19 .175 5 7 x .0688 8 .045 1.940 187 2,477

1/0 19 .175 4 7 x .0772 8 .045 2.025 215 2,742

2/0 19 .175 3 7 x .0867 8 .045 2.110 246 3,130

4/0 19 .175 1 19 x .0664 8 .045 2.330 325 4,385

250 37 .175 1/0 19 x .0745 8 .045 2.450 359 5,400

350 37 .175 2/0 19 x .0837 8 .045 2.700 438 6,730

500 37 .175 4/0 19 x .0940 8 .045 3.050 502 8,515

Ground CheckGrounding

ConductorsPower Conductor

Information based on AIW specs.

Uninsulated Ground Wire

Insulation Shield

XLP Insulation

Conductor Shield

Bare Copper Conductors

Insulated Ground Check

PVC Jacket

Open Reinforcement

Industrial Grade Cable

[email protected] 800-238-7514

Page 29: All Aluminum Conductor, Bare 800-238-7514

29

Type W Portable Power Cable 90°C, 2kVConstructionManufactured with rope-lay stranded, bunched members, annealed copper conductors. A polyester or paper tape separates the copper conductors from the EP rubber insula-tion. The insulated conductors are assembled round with fillers as needed. The cable is covered with a black CPE rubber jacket. The jacket may be applied in two layers. Two-layer jackets are reinforced by a braid of synthetic material. The reinforcing is between the layers.

SpecificationsConductors are manufactured in accordance with ASTM B-33 and B-172Made in accordance with ICEA S-75-381 - Portable and Power Feeder Cables for Use in Mines and Similar LocationsMSHA accepted, P-7K-123049 LR27151UL Listed as Type RHH-RHW-2 per UL 44CSA ApprovedMeets FT-5 Flame Test

ApplicationsFor use in mining machines, locomotives, power supply leads on A.C. welders, motor leads, entertainment, generator leads and grounding cable at continuous conductor temperature of 90°C. Type W cables also are suitable for continuous immersion in shallow water. Excellent flexibility, resistance to oils, solvents, ozone, aging, and abrasion.

••

••••

See referenced pages in the Hardware & Supplies section:

Suggested Prep ToolsMK01A Jacket Stripper - I-11MK04 Jacket Stripper - I-11

••

Bare Copper Conductor

Fillers

Open Reinforcement

Separator

EPDM Insulation

CPE Jacket

No. of Conductors

Size (AWG or kcmils)

Cond. Strand

Nom. Insulation Thick. (in)

Nominal O.D. (in)

Current Amps

Approx. Net Weight (lbs/M-ft)

1 8 133 .060 .485 74 160

1 6 259 .060 .565 99 220

1 4 259 .060 .605 130 290

1 2 259 .080 .680 174 395

1 1 259 .080 .765 202 490

1 1/0 259 .080 .810 234 575

1 2/0 259 .080 .885 271 700

1 3/0 259 .080 .930 313 820

1 4/0 259 .080 .980 361 1,000

1 250 627 .095 1.045 402 1,170

1 350 855 .095 1.145 495 1,520

1 500 1,235 .095 1.310 613 2,090

Also available in 2, 3, 4, 5 conductor. Call for specifications. Information based on Southwire specs.

Industrial Grade Cable

[email protected] 800-238-7514

Page 30: All Aluminum Conductor, Bare 800-238-7514

30

FAA L-824 Type C 5kVConstructionShielded or unshielded, single conductor cable with stranded, bare copper conductor, XLP insulation and PVC jacket on shielded cable.

SpecificationsMeets ICEA S-96-659 for unshielded and ICEA S-93-639 for shielded. ApplicationsFor installation in ducts, conduit or direct burial for use in airport lighting and control circuits.

AWGConductor

StrandsInsulation Thick. (in)

Approx.O.D. (in)

Approx. Weight (lbs/M-ft)

Unshielded

8 7 .11 .375 94

6 7 .11 .415 130

4 7 .11 .460 189

Shielded

8 7 .09 .610 175

6 7 .09 .645 240

4 7 .09 .695 305

See referenced page in the Hardware & Supplies section:

Suggested Prep ToolWS 49 Airport Lighting Cable End Stripper/Penciller - I-9

Information based on AIW specs.

Stranded Bare Copper

Opaque Separator (or Conductor Shield for Shielded Cable)

XLP Insulation

Bare Copper Tape Shield*

PVC Jacket*

Semi-conducting Insulation Shield*

*Shielded cable only.

Airport Lighting Cable

[email protected] 800-238-7514