28
New range - 5 sizes, 20 models! 1 2 3 4 AIR HANDLING UNITS RIS P EKO 3.0 Efficiency up to 94%! Extremely low height ! Efficient EC fans!

AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

New range - 5 sizes, 20 models!

1 2 3 4

AIR HANDLING UNITS

RIS P EKO 3.0

E f f i c i e n c y up to 94%!

E x t r e m e l y low height !

Efficient ECfans!

Page 2: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger
Page 3: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

Contents

Basic features 4

RIS P EKO 3.0 full range 5

RIS 400P EKO 3.0 6

RIS 700P EKO 3.0 9

RIS 1200P EKO 3.0 12

RIS 1900P EKO 3.0 15

RIS 2500P EKO 3.0 18

Accessories 21

Installation assembly 23

Controls 24

Type name codes 26

Article numbers of new AHU range 26

Page 4: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

4

Basic features

Air handling units RIS P EKO are equipped with high efficiency cross - coun-

ter flow heat exchanger and EC motors. AHU range is used for ventilation of

houses, offices or other heated premises: classrooms, apartments, confer-

ence rooms and other.

•Air output range 200 - 2500 m3/h.

•Wide range – 5 sizes, 20 models !

•Extremely low height !

•EnergysavingandlownoiseECfanscompliantwithErPdirective2009/125/EC.

•Efficiencyofheatexchangerupto94%.

•Integrated electrical heater or optional water heater/cooler on the duct.

•Motorized 100% by-pass damper.

•EfficientandlowpressurelosspanelfiltersF7/F5.

•Designed for installation under the ceiling.

•FullintegratedPlug&Playcontrolsystem.

Construction

•Framelessconstructionfromdoubleskinnedpanels.

•Acoustic and thermal insulation of the walls - RIS 400 - 2500P EKO - 30/50 mm.

•RIS 400P - 700P EKO housing: powder coated white colour painting RAL 9016,

RIS 1200P – 2500P EKO - grey colour RAL 7040.

•Easyremovableorpluginelectricalheater(Plug&Play).

•Accesstointernalcomponentsbyhingeddoorwithlocks(removabledoorsalso).

•QuickandeasyaccesstocontrolboardandPlug&Playbyopeningseparate

compartment on the side of the unit.

•Stainless steel condensate tray.

•Fittedwithmountingbrackets.

Page 5: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

5

Air flow [m3/h]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

600

800

RIS 400P EKO 3.0

RIS 700P EKO 3.0

RIS 1200P EKO 3.0

RIS 1900P EKO 3.0

RIS 2500P EKO 3.0

PerformancePower consumption

400P EKO 3.0

700P EKO 3.0

1200P EKO 3.0

1900P EKO 3.0

2500P EKO 3.0

RIS P EKO 3.0 full range

Page 6: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

6

DimensionsRIS 400P EKO 3.0

1014

1300

1361

200

712

670

330

148

31

304

148

Page 7: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

7

0.9 EKO 3.0 1.6 EKO 3.0 3.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~1, 230 ~3, 400

-power consumption [kW] 0,9 1,6 3,0Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,125 / 1,17-speed [min-1] 3490

supply -power/current [kW/A] 0,134 / 1,18-speed [min-1] 3490

Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 1,16 / 6,39 1,86 / 9,39 3,26/15,39Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 30Weight [kg] 74,0ComplywithERP2013 +

RIS 400PE EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

160

140

120

100

80

60

40

20

0

160

140

120

100

80

60

40

20

0

Viewfrominspectionside

RIS 400PE EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

Technical data

RIS 400PE EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 67 54 59 64 58 57 54 47Extract 58 48 50 53 51 48 46 41Surrounding 51 40 43 46 45 40 39 36Measured at 443 m3/h, 100 Pa

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

Page 8: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

8

Technical data

400PW EKO 3.0Heater -phase/voltage [50Hz/VAC] AVS200-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,125/1,17-speed [min-1] 3490

supply -power/current [kW/A] 0,134/1,18-speed [min-1] 3490

Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 0,26/2,39Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 30Weight [kg] 73,0ComplywithERP2013 +

RIS 400PW EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

160

140

120

100

80

60

40

20

0

160

140

120

100

80

60

40

20

0

Viewfrominspectionside

RIS 400PW EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

RIS 400PW EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 67 54 59 64 58 57 54 47Extract 58 48 50 53 51 48 46 41Surrounding 51 40 43 46 45 40 39 36Measured at 443 m3/h, 100 Pa

Page 9: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

9

DimensionsRIS 700P EKO 3.0

35

8

1461

241,7 486,6

1074

16

0

48

6,6

72

8,3

1422

97

0

85

6,6

Page 10: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

10

Technical data

RIS 700PE EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

300

250

200

150

100

50

0

300

250

200

150

100

50

0

Viewfrominspectionside

RIS 700PE EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

RIS 700PE EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 75 64 66 68 70 66 60 59Extract 62 53 55 57 56 52 49 45Surrounding 56 45 47 50 50 47 43 42Measured at 764 m3/h, 100 Pa

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

1.2 EKO 3.0 3.0 EKO 3.0 4.5 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~1, 230 ~3, 400

-power consumption [kW] 1,2 3,0 4,5Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,218/1,9-speed [min-1] 3380

supply -power/current [kW/A] 0,237/2,07-speed [min-1] 3380

Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 1,66/5,51 3,46/19,0 4,96/9,85Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 95,0ComplywithERP2013 +

Page 11: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

11

RIS 700PW EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

300

250

200

150

100

50

0

300

250

200

150

100

50

0

Viewfrominspectionside

RIS 700PW EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

RIS 700PW EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 75 64 66 68 70 66 60 59Extract 62 53 55 57 56 52 49 45Surrounding 56 45 47 50 50 47 43 42Measured at 764 m3/h, 100 Pa

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

700PW EKO 3.0Heater -phase/voltage [50Hz/VAC] AVS200-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,218/1,9-speed [min-1] 3380

supply -power/current [kW/A] 0,237/2,07-speed [min-1] 3380

Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 0,46/2,5Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 95,0ComplywithERP2013 +

Technical data

Page 12: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

12

DimensionsRIS 1200P EKO 3.0

500

686

39

1

355,5

25

0

51,5

1439

1653

1550

1319

17

2

13

25

90

90

100

1497

1439

1397

Page 13: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

13

3.0 EKO 3.0 6.0 EKO 3.0 9.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~3, 400 ~3, 400

-power consumption [kW] 3,0 6,0 9,0Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,37/2,5-speed [min-1] 3400

supply -power/current [kW/A] 0,45/2,95-speed [min-1] 3400

Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 3,82/18,49 6,82/14,49 9,82/18,49Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 168,0ComplywithERP2013 +

RIS 1200PE EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

Viewfrominspectionside

RIS 1200PE EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

Technical data

RIS 1200PE EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 76 58 69 71 69 67 64 56Extract 64 52 56 61 56 50 45 42Surrounding 56 42 48 50 49 48 46 40Measured at 1298 m3/h, 100 Pa

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

Page 14: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

14

RIS 1200PW EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

Viewfrominspectionside

RIS 1200PW EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

Technical data

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

1200PW EKO 3.0Heater -phase/voltage [50Hz/VAC] SVS500x250-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,37/2,5-speed [min-1] 3400

supply -power/current [kW/A] 0,45/2,95-speed [min-1] 3400

Motor protection class IP-44Thermalefficiency 90%Max power consumption [kW/A] 0,82/5,49Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 168,0ComplywithERP2013 +

RIS 1200PW EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 76 58 69 71 69 67 64 56Extract 64 52 56 61 56 50 45 42Surrounding 56 42 48 50 49 48 46 40Measured at 1298 m3/h, 100 Pa

Page 15: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

15

DimensionsRIS 1900P EKO 3.0

88

30

0

39

9

44

44

0

18

92

10

6

Page 16: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

16

Technical data

RIS 1900PE EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

600

500

400

300

200

100

0

600

500

400

300

200

100

0

Viewfrominspectionside

RIS 1900PE EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

RIS 1900PE EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 77 53 64 69 73 70 65 61Extract 68 42 58 64 62 61 58 55Surrounding 60 50 52 54 54 50 48 41Measured at 1938 m3/h, 100 Pa

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

3.0 EKO 3.0 6.0 EKO 3.0 12.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~1, 230 ~3, 400 ~3, 400

-power consumption [kW] 3,0 6,0 12,0Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,488/3,16-speed [min-1] 2540

supply -power/current [kW/A] 0,485/3,12-speed [min-1] 2540

Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 4,11/19,98 7,02/14,7 13,31/24,03Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 269,0 270,0 272,00ComplywithERP2013 +

Page 17: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

17

Technical data

RIS 1900PW EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

600

500

400

300

200

100

0

600

500

400

300

200

100

0

Viewfrominspectionside

RIS 1900PW EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

RIS 1900PW EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 77 53 64 69 73 70 65 61Extract 68 42 58 64 62 61 58 55Surrounding 60 50 52 54 54 50 48 41Measured at 1938 m3/h, 100 Pa

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

1900PW EKO 3.0Heater -phase/voltage [50Hz/VAC] SVS700x400-power consumption [kW]Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,488/3,16-speed [min-1] 2540

supply -power/current [kW/A] 0,485/3,12-speed [min-1] 2540

Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 1,21/5,03Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 265,0ComplywithERP2013 +

Page 18: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

18

DimensionsRIS 2500 P EKO 3.0

481

185060

625,7 557,5 625,7

60

20

50

6,5

290

625,7 557,5 625,7

19

92

715 415,5715

10

5

40

0

145 700 261 700 145

18

8

44

49

9

Page 19: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

19

RIS 2500PE EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

Viewfrominspectionside

RIS 2500PE EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

Technical data

RIS 2500PE EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 80 60 68 72 75 74 71 65Extract 69 56 60 64 63 60 58 41Surrounding 62 46 54 56 57 54 50 45Measured at 2548 m3/h, 102 Pa

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

4.5 EKO 3.0 9.0 EKO 3.0 18.0 EKO 3.0Heater -phase/voltage [50Hz/VAC] ~3, 400 ~3, 400 ~3, 400

-power consumption [kW] 4,5 9,0 18,0Fans -phase/voltage [50Hz/VAC] ~1, 230

exhaust -power/current [kW/A] 0,725/3,24-speed [min-1] 2800

supply -power/current [kW/A] 0,675/3,0-speed [min-1] 2800

Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 12,5/5,87 19,5/10,7 33,1/19,7Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 316,0 320,0 322,0ComplywithERP2013 +

Page 20: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

20

RIS 2500PW EKO 3.0Performance

Power consumption

Extract airExhaust air Freshair Supply air

Temperature efficiency Airflow[l/s]

η[%

]

Airflow[m3/h]

Staticpressure[Pa]

Airflow[m3/h]

Airflow[l/s]

Power[W

]

Exhaust air

Specific fan power

Airflow[m3/h]

Staticpressure[Pa]

Airflow[l/s]

Power[W

]

Supply air

Airflow[l/s]

Staticpressure[Pa]

Airflow[m3/h]totalpowerforsupply&exhaustfanskWairflowm3/h x 3600SFP=

Viewfrominspectionside

RIS 2500PW EKO 3.0

Airflowtemperaturerangefrom-7°Cto+40°CDesigned for operation indoors only

Technical data

Extractair=20°C/60%RH-Outdoorair=-7°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=2°C/90%RHBalancebetweensupplyair/extractair=1.0

Extractair=20°C/60%RH-Outdoorair=7°C/90%RHBalancebetweensupplyair/extractair=1.0

RIS 2500PW EKO 3.0 Lwa total, dB(A)

LWA,dB(A)125 Hz 250 Hz 500 Hz 1kHz 2kHz 4kHz 8kHz

Supply 80 60 68 72 75 74 71 65Extract 69 56 60 64 63 60 58 41Surrounding 62 46 54 56 57 54 50 45Measured at 2548 m3/h, 102 Pa

2500PW EKO 3.0Heater -phase/voltage [50Hz/VAC]

SVS700x400-power consumption [kW]

Fans -phase/voltage [50Hz/VAC] ~1, 230exhaust -power/current [kW/A] 0,725/3,24

-speed [min-1] 2800supply -power/current [kW/A] 0,675/3,0

-speed [min-1] 2800Motor protection class IP-54Thermalefficiency 90%Max power consumption [kW/A] 6,7/1,4Automatic control integratedFilterclass-exhaust F7 -supply M5Thermal insulation [mm] 50Weight [kg] 313,0ComplywithERP2013 +

Page 21: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

21

2

5

1

7 10

4

8

3

1 - exhaust air fan2 - supply air fan3 - plate plate exchanger4 - filterforsupplyair5 - filterforextractair

6 - electrical heater7 - actuator of by-pass damper8 - temperature sensor for fresh air9 - humidity + temperature sensor

10 - control box

Accessories

6

9

View from inspection side

exhaust air fresh air

extract air supply air

Page 22: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

22

Type Accessories

TPCUNI PROFLEX

1141RC02-F2KFF-U

SSB PS SupplySP

ExhaustSP

SVS SSK SKS RMG VVP/VXP SKG

AKS

AP

AVS

AVA

EKA

RIS 400PE EKO + + - LM230A-TP LM230A-TP - - - - - 200 200

RIS 400PW EKO + + 61 - NF230A LM230A-TP - - - + + 200 200

RIS 700PE EKO + + - LM230A-TP LM230A-TP - - - - - 250 250

RIS 700PW EKO + + 61 - NF230A LM230A-TP - - - + + 250 250

RIS 1200PE EKO + + int LM230A-TP LM230A-TP - 500x250 500x250 - - - -

RIS 1200PW EKO + + 61 int NF230A LM230A-TP 500x250 500x250 500x250 + + - -

RIS 1900PE EKO + + int LM230A-TP LM230A-TP - 700x400* 700x400 - - - -

RIS 1900PW EKO + + 61 int NF230A LM230A-TP 700x400* 700x400* 700x400 + + - -

RIS 2500PE EKO + + int LM230A-TP LM230A-TP - 700x400 700x400 - - - -

RIS 2500PW EKO + + 61 int NF230A LM230A-TP 700x400 700x400 700x400 + + - -

Remote controller

Differential pressureswitch

Circular duct silencer

2-3-way valve Shut-off damper

Pressure transmitterRemote controller CO2 transmitter

Thermic water valve actuator

Mounting clips

Water heater coil

Heating coil

Damper for rectangular duct

Circular ductwater cooler

Rectangular duct silencer

Electrical duct heater

1141 FLEX RC02-F2 KFF-U

Duct humidity sensorProgrammablecontroller

Programmablecontroller

UNI

PS

AKS

PRO TPC

Actuator for dampers

SP

SSB

AP

SVS

AVS

SSK

AVA

SKS

EKA

Mixing point

RMG VVP/VXP SKG

Page 23: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

23

•Easyandquickinstallation.

•Ceilingmounted,suppliedwithrubbergaskets–vibrationabsorbers.

•Mounting position is shown above, another position mounting is prohibited.

•Unit designed for indoor installation only.

•RISPEKO3.0rangeequippedwithnewPRVV2.2controlboard.

•RISPEKO3.0versionscanbecontrolledwithUNI,PRO,TPCandFlexremotecontroldevices.

•Two RS485 ports – for remote controller and for MODBUS communication.

•The heat exchanger frost point is detected in two levels: temperature-controlled and pressure-controlled.

•Automaticdefrostingbyadjustmentofthefreshairfloworstoppingtheunitifnecessary.

•Optionalself-regulatingelectricalpre-heaterontheductforefficientfrostprotection.

•Accurateandefficientpulse-widthmodulation(PWM)electricalheatercontrol.

YES NO NO NO

Installation assembly

Controls

Page 24: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

24

FUNCTIONS

Descriptions of the functionsPRV V2.2E W

Main functions and control of functional unitsUser and servicing control level

Week timer + Holidays + Digital timer channels8 events for each day or weekday group* per week.*1-7 entire week, 1-5 working days, 6-7 weekend.

START/STOP function,,START/STOP“ function for starting or stopping operation of the heat recovery unit. „STOP“ signisindicatedonaremotecontrol(Flex).Itcanbeusedwithdoorlock,motionsensor(PIR),outsideswitchorotherexternaldigitalsignal(potential-freecontacts).On a position ,,START“ heat recovery unit operates according to the last remote controller settings.

Year-round optimization of recovery unit regulationWinter –heat recovery; Summer – cold recovery; Autumn and spring – low rotor speed/half by-pass opened.

Free Cooling functionThe premises are cooled down by supplying fresh air, when exhaust air temperature is higher thenfreshair.(Nightcoolingfunction)

Cool recoveryThe heat exchanger recovers cold air from exhaust air when premises temperature is lower than outside.

ON/OFF rotor motor control0-10V DC rotor motor speed control

By-pass ON/OFFBy-pass three-positional control

Minimum and maximum limits for supply air temperatureByactivatingtemperaturecontrolaccordingtoextractedairsensor(Min.-15°C,Max.+40°Cadjustableinservicemenu).

ON/OFF control of electric post-heaterPulse-width modulation (PWM) control of electrical heater

Accuracyof0,5°Cforsupplyairtemperature.Electric heater’s control by stages

Forthebiggercapacityelectricheaters.ON/OFF control of DX coolers

Water cooler control with three-positional valve actuatorON/OFF control of circulation pump

Fans’ speed synchronous 0-10V controlSeparate fans’ speed asynchronous 0-10V control

4 speeds for easy end-user control.“Stop” – the unit is stopped; “Low”, “Medium”, and “High”. Service menu allows adjusting each speed individually.

BOOST functionFansoperateathighspeed(setinservicemenu).Operationtimeisalsosetinservicemenu.„Boost“functionisreflectedinFLEXremote.

CO2, constant pressure, humidity controlFanspeedcontrolonly.

CO2, constant pressure controlPossibilitytoconnectCO2ortwopressuretransmitters.

Supply air temperature control according to the extract air sensorExhaust air damper control

Supply air damper controlRemote control ModBus input

Web-based software control.Remote controller input

Page 25: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

25

FUNCTIONS

Descriptions of the functionsPRV V2.2E W

Safety/emergency signal indicationsOverheat protection

Additional electrical heater overheat protection (software).Rotor fail alarm signal

Incaseofrotorbeltbreak-uporrotoroperationstoppingindication„RotorFail“appearsonFLEXremotecontroller.

Fire alarm signalFire and smoke alarm input

TheAHUstopstillserviceisrestoredinFLEXremotecontroller.Fans’ overheating alarm signal

Filter pollution indicator by pressure drop transmitterFilter pollution indicator by working hours

A possibility to choose period of time after which indication informs about necessity to changethefilters.(Min.168h,Max.6482h)Numberofworkinghourssetasdefault-2160h.Other indications

FanRun functionUnit in operation signal.

FanFail functionUnitoffoperationsignal.

Extracted air temperature sensorExhaust air temperature sensor

Returning water temperature sensorExtracted air relative humidity converter

Fresh air temperature sensorSupplied air temperature sensor

ControllersFLEX controller

Adjustmentofthenewcontrollerwithcontrolautomatics–Fullcontrol(servicecontrolincluded).

UNI PRO TPC*

• Absentcontrolfunctions:• Boostconfigurationmenu(time,fanspeed,nightcooling),temperatureandtimeconfiguration

ofwaterheater);• Servicemenu-PIconfiguration;• Reviewofseparatealarmsatonetime;• DXcoolingconfigurationpossibility;• Nightcoolingfastbuttonsetting;• Supplyandextractairfans’speedcontrol(3speedcanbeconfigured);• Functionalcomponents’typechoice.

DCV systems controlDemand-ControlledVentilationforextractedair.UsingonepressureoroneCO2transmitter.

DCV systems controlDemand-ControlledVentilationforextractedandsuppliedair.TwopressureoroneCO2transmitter.

UNI PRO TPC

Page 26: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

26

RIS 400 P E 0.9 EKO 3.0EquippedwithnewPRVV2.2controlboard

AHUwithECmotorsandefficientcross-counterflowheatexchanger

ElectricalheaterpowerinkW

Heatertype(E-integratedelectricalheater;W-optionalwaterheater)

Housingtype(P-under-ceiling)

AHUsizeaccordingtoairflowrangem3/h

AHU with plate heat-exchanger

New control boardArticle No. RIS Date

GAGRIS1747_0017A 400 PE 0.9 EKO 3.0

From

01.10

.201

3

GAGRIS1746_0017A 400 PE 1.6 EKO 3.0

GAGRIS1692_0016A 400 PE 3.0 EKO 3.0GAGRIS1748_0019A 400 PW EKO 3.0GAGRIS1737_0008A 700 PE 1.2 EKO 3.0GAGRIS1736_0007A 700 PE 3.0 EKO 3.0GAGRIS1693_0005B 700 PE 4.5 EKO 3.0GAGRIS1738_0009A 700 PW EKO 3.0GAGRIS1744_0022A 1200 PE 3.0 EKO 3.0GAGRIS1745_0021B 1200 PE 6.0 EKO 3.0GAGRIS1701_0020B 1200 PE 9.0 EKO 3.0GAGRIS1721_0023A 1200 PW EKO 3.0GAGRIS1751_0025A 1900 PE 3.0 EKO 3.0GAGRIS1752_0024B 1900 PE 6.0 EKO 3.0GAGRIS1706_0001B 1900PE 12.0 EKO 3.0GAGRIS1753_0026A 1900 PW EKO 3.0GAGRIS1754_0027B 2500 PE 4.5 EKO 3.0GAGRIS1755_0028B 2500 PE 9.0 EKO 3.0GAGRIS1707_0015B 2500 PE 18.0 EKO 3.0GAGRIS1756_0029A 2500 PW EKO 3.0

Type name codes

Article numbers of new AHU range

http://new.salda.lt/en/selection/ahu/

Page 27: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

Notes

Page 28: AIR HANDLING UNITS RIS P EKO 3 - SALDA - Salda range RIS P EKO 3.0 Presentation.pdf · Air handling units RIS P EKO are equipped with high efficiency cross - coun-ter flow heat exchanger

UAB SALDA

Ragainės g. 100 LT-78109, Šiauliai Lithuania

Tel. +370 41 54 04 15 Fax. +370 41 54 04 17

www.salda.lt [email protected]