Vicot Air Conditioning Co., Ltd.Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, ChinaTel: 0531-8235 5568Fax: 0531-8235 7911Web: www.vicot.com.cn

Vicot Air Conditioning Co., Ltd.Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, ChinaTel: 0531-8235 5568Fax: 0531-8235 7911Web: www.vicot.com.cn

Vicot Air Conditioning Co., Ltd.Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, ChinaTel: 0531-8235 5568Fax: 0531-8235 7911Web: www.vicot.com.cn

V i c o t A i r C o n d i o n i n g C o . , L t d .Vicot Air Handling Unit

Vicot Air Conditioning Co., Ltd.Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, ChinaTel: 0531-8235 5568Fax: 0531-8235 7911Web: www.vicot.com.cn

V i c o t A i r C o n d i o n i n g C o . , L t d .Vicot Air Handling Unit

Air Handling Unit

Page 2: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nitAir Handling Unit

Page 3: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nit

01 02

Introduc onVAQ series air handling units was developed and manufactured for years, with advanced Italian technology to meet the

requirement of clients. The unit features novel structure, a rac ve appearance and flexible assembly, stable opera on, complete

func on and easy installa on & maintenance. The parts all u lize famous brands. The moulds and equipment are all exported from

Italy.

The units have many func onal sec ons: air supply, cooling, hea ng, humidify, dehumidify, air purify and silencing. The units are

widely used in the air system of many industries like mechanical, electronic, tex le, medical, metallurgy, chemical, energy and food,

etc. The units are also ideal for restaurants, office buildings, hospitals, theaters, and supermarkets etc. The use can choose the most

economic and op mized func ons with so ware according to clients requirement.

Features

A. The components was standardized, and common in applica on, it makes convenient in assembly and maintenance, 200mm is the

basic value for each module ( Refers a “M” in following) , the machine dimension can be changed with flexibility to meet the clients’

requirement to maximum limit. We provide the users with 26 standard and 30 non-standard configura ons, 56 kinds of models, 280

kinds of specifica on, air flow from 3000~240000m3/h for op on, and there are more than 20 types of func onal sec ons for each

model.

B. It’s framework construc on, and can be flexibly assembled at site. The site assembly, maintenance and dismantle is convenient for it

scien fic modular design, especially for units of large or extra large size.

◆ Modular design

The unit adopts aluminum alloy frame and compound aluminum alloy of high strength.

1. The frame, with harden and polished surface, has features of high strength, exact dimension, elegant appearance, light in weight, etc.

2. Anodizing protec on film on the aluminum makes the shell more elegant and an -corrosive.

3. Its compound aluminum alloy frame and no-cold-bridge design guarantee great air ghtness and heat isola on performance.

4. Easy to assemble, disassemble and maintain.

5. PVC sealing.

◆ Excellent performance

A. Aluminum alloy frame

B. Insula on panel

1. The plenum panel is double skinned type, polystyrene or polyurethane with two steel sheets on both sides, or fire proof polyurethane

made by high pressure foaming equipment, guarantees perfect heat insula on performance.

2. For high pressure foamed polyurethane panel, the exterior is colored steel or sprayed plas c steel of 0.5mm or 0.6mm, interior is same as

exterior or galvanized sheet, the sound & heat insula on performance is be er than other normal insula on material, and its heat conduc ng

coefficient≤0.55W/M2.K, which meets Europe air handling unit standard EN1866T2. It has the best performance on heat and noise insula on,

fire proof, strength, rigidity, cleanness, etc.

C. Cooling coil

1. The coil is made of copper tubes and corrugated aluminum fins.

2. Water eliminator can be galvanized sheet, aluminium alloy, stainless steel, ABS, fiberglass or wet film type.

3. Dry drain pan.

D. Fan motor

1. Three phase asynchronous motor, IP54 protec on, and F class insula on.

2. High efficiency, low noise.

E. Filter

Many kinds of different filters for op on: G3/G4 plate prefilter, F5/F6/F7/F8 bag medium filter, F9/H10 plate sub HEPA filter.

Page 4: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nit

03 04

Normal approach

VICOT approach

This structure is to put colored steel on aluminum profile frame and fix

them with bolts, which is a metal to metal contact. Due to air pressure, the

panels and frame are easy to separate from each other. The appearance is not

a rac ve due to the outside bolts.

In order to avoid such situa on, Vicot developed its maze like sealing

structures to eliminate the metal to metal contact between panel and

framework, reducing air leakage.

The frame is made of aluminum alloy. The panels and frame is sealed

with PVC. The cabinet has no cold bridge. The cold bridge defending ability

reaches European TB1. The special double door sealing ensures air ght

environment.

The thermal conduc vity U(W/m2.k) in the following table is measured under 20K stable temperature differentce.

EN1886: European New StandardThermal conduc vity

Class T1

Class T2

Class T3

Class T4

Class T5

U≤0.5

0.5<U≤1

1<U≤1.4

1<U≤2

No requirement

Class TB1

Class TB2

Class TB3

Class TB4

Class TB5

0.75<Kb≤1 

0.6<Kb≤0.75 

0.45<Kb≤0.6 

0.3<Kb≤0.45 

No requirement

In the formular Kb=tmin/tair, tmin is the temperature difference between unit inside temperature and external wall temprature; tair is

ambient temperature.

An -cold bridge coefficient

3A

A

B

C

5.7

1.9

0.63

<0.63

The rate is measured when pressure inside of unit is 700Pa posi ve pressure.

Air leakage rate

Nomenclature VAQ 04 05 H C Z B R S L J X F

VICOT air handling unit

Nos. of modules in height

Nos. of modules in width

Pre-filter sec on

Medium filter sec on

Mixing box sec on

Fan sec on

Silencing sec on

Middle sec on

Air balancing sec on

Humidifica on sec on

Cooling coil sec on

Hea ng sec on

Op onal accessories◎ Control system is op onal and can be designed according to the clients’ requirements, such as: temperature and humidity control of

supply air and return air, an -freezing control, filter pressure differen al control, fresh air damper and fan motor coordinated control,

indoor/outdoor temperature difference compensa on energy saving control, building management system, etc.

◎ Variable air volume func on

VICOT can use asynchronous three phase motor with characteris c of pressure adjustment and speed change to achieve AHUs’ air flow

regula on and energy-saving by the inverter speed adjuster, which has so starter to reduce the impact to electricity facility and can do

stepless adjustment according to indoor temperature/humidity detected by sensors. Inverter brand can be DANFOSS,ABB,SIEMENS, etc.

According to the design, control-box can be equipped, which has the following func ons: total pressure and delta-star start and stop,

phase/overload protec on, motor overheat/over current protec on, and malfunc on alarm etc.

Note: Unit height = nos. of modules in height×200+K Unit width = nos. of modules in width×200+K

K: 80mm for unit with 30mm thickness panel; 120mm for unit of 50mm thickness panel

◆ Perfect sealing structure

Page 5: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nit

05 06

Technical Parameters1. Unit model and air flow

2. Simplified diagram of different sec ons

Range table of quick model selec on

ModelNominal air

flow (m3/h)

Air flow (m3/h)Face velocity (m2)

VAQ0404 3000 2423 2726 3029 3332 3635 0.34 VAQ0405 4000 3338 3755 4172 4589 5006 0.46

VAQ0406 5000 4252 4783 5315 5846 6378 0.59 VAQ0505 6000 4406 4956 5507 6058 6608 0.61

VAQ0506 8000 5613 6314 7016 7717 8419 0.78 VAQ0606 10000 6973 7845 8717 9588 10460 0.97

VAQ0607 12000 8473 9532 10591 11650 12709 1.18 VAQ0609 15000 11472 12906 14340 15774 17208 1.59

VAQ0709 18000 13680 15390 17100 18810 20520 1.90 20000 15480 17415 19350 21285 23220 2.15 VAQ0710VAQ0811 25000 19060 21442 23825 26207 28590 2.65 VAQ1011 30000 24707 27795 30884 33972 37061 3.43

VAQ1012 35000 27267 30676 34084 37493 40901 3.79 VAQ1013 40000 29828 33556 37285 41013 44742 4.14 VAQ1212 45000 33506 37694 41883 46071 50259 4.65 VAQ1213 50000 36652 41234 45815 50397 54978 5.09 60000 42937 48304 53671 59038 64405 5.96 VAQ1215VAQ1415 70000 50319 56609 62899 69189 75479 6.99 VAQ1417 80000 57692 64904 72115 79327 86538 8.01

VAQ1419 90000 65065 73198 81331 89464 97597 9.04

VAQ1421 100000 72438 81492 90547 99602 108657 10.06

VAQ1820 120000 83704 94167 104630 115093 125556 11.63 VAQ1824 150000 103058 115940 128822 141705 154587 14.31 VAQ2126 180000 132866 149474 166082 182691 199299 18.45

VAQ2128 200000 144271 162305 180338 198372 216406 20.04 VAQ2230 240000 174545 196363 218182 240000 261818 24.24

2.0m/s 2.25m/s 2.5m/s 2.75m/s 3.0m/s

Height (m

m)

800 3000 4000 5000 6500

800 1000 1200 1400 1800 2000 2200 2400 2600 3000 3400 3800 4200

1000 4000 6000 8000 8500 11500 130001200 5000 7000 10000 12000 15000 17000 200001400 11500 13500 18000 20000 23000 25000

1600 16000 20000 22500 25000 27000 30000 37000

2000 27000 30000 35000 40000 45000 530002400 36000 40000 45000 50000 60000 65000 74000 85000

2800 48000 55000 60000 70000 80000 90000 100000

Note: Navy bule area is VICOT’s standard product, light color area is op onal nonstandard product.

NO. Sec ons Symbol Diagram Length (M = 200mm) Remark

1 Top air inlet CCJFS

(0404-1011)3M

(1012-1215)4M

(1415-1421)5M(1820-2230)7M

(0404-1011)3M(1012-1215)4M

(1415-1421)5M

(1820-2230)7M

(0404-1011)3M

(1012-1215)4M

(1415-1421)5M

(1820-2230)7M

1M

3M

(0404-1011)3M

(1012-1215)4M

(1415-2230)5M

Damper is op onal

Damper is op onal

Damper is op onal

Filter class: G3

Having access door before it

Filter class: F5

Having access door before it

2 Horizontal air inlet JFP

3 Mixing box JFH

4 Horizontal plug-in filter WXP

5 Top plug-in filter WXS

6 Pre-filter GLC

7 Medium filter GLZ

8 Combined filters GLH3M

Filter class: G3+F5

Having access door before it

Width (mm)Air flow (m3/h)

It doesn’t occupy space

in the machine

Page 6: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nit

07 08

NO. Sec ons Symbol Diagram Length (M=200mm) Remark

(0404-1011)3M+4M

(1012-1215)4M+5M

(1415-1421)5M+6M

(1820-2230)7M+8M

2M

1M

1M

4M

3M

4M Water eliminator is op onal

In the same sec on with

cooling coil

Filter class: F9

Having access door before it9 Sub HEPA filter GLY

10 Air distribu on FL

11 Middle sec on ZJ

12 Cooling coil BL

13 Hea ng coil JRS

14 Steam hea ng JRQ

15 Electric heater JRD

16 Direc on drain JSM

wet film humidifica on

Note: 1. Electric heater sec on is determined by hea ng power.

2. Above sec ons are standard sec on. Real sec ons may have some changes.

3. Other sepcial requirements can be sent to us for special design.

4M

2M18 Dry steam humidifica on JSQ

NO. Sec ons Symbol Diagram Length (M=200mm) Remark

27 Horizontal air discharge CFP

(0404-1011)3M

(1012-1215)4M(1415-1421)5M(1820-2230)7M

(0404-1011)3M

(1012-1215)4M

(1415-2230)5M

2M-4M

3M-4M

3M-5M

3M

See fan sec on

See fan sec on

See fan sec on

Near to cooling coil and

sharing the same drain

pan and water eliminator

19 High pressure atomized JSW

humidifica on

2 Electrode humidifica on JSD

21 Return air fan FJH

22 Middle fan FJZ

23 Supply air fan FJS

24 Air balancing sec on JL

25 Noise silencing sec on XS

26 Top air discharge CFS

16 Circula ng water JSH

wet film humidifica on

Page 7: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nit

09 10

Cooling performance (fresh air condi on)

1) Cooling and/or hea ng coil sec on

Cooling performance (return air condi on)

3. Func onal sec ons specifica ons

ModelRated

air flow (m3/h)

4 rows 6 rows 8 rowsCooling capacity

(kW)

Water flow (m3/h)

Resistance (kPa)

DiameterDN

VAQ0404 3000 17.6 3.03 2.31 40 22.7 3.91 5.13 40 27.7 4.76 7.56 40

VAQ0405 4000 23.6 4.05 3.71 40 30.4 5.23 7.66 40 36.8 6.33 11.9 40

VAQ0406 5000 29.5 5.07 5.40 40 38.3 6.58 10.7 40 46.0 7.91 16.8 40

VAQ0505 6000 35.5 6.10 4.81 40 45.8 7.87 9.40 40 55.1 9.48 14.2 50

VAQ0506 8000 47.2 8.12 7.40 40 60.7 10.4 12.8 40 72.8 12.5 22.6 50

VAQ0606 10000 58.9 10.1 8.45 40 75.8 13.0 14.7 50 91.8 15.8 22.7 50

VAQ0607 12000 70.8 12.2 9.58 40 91.8 15.8 18.2 50 111 19.0 30.4 50

VAQ0609 15000 88.5 15.2 14.5 40 115 19.8 25.3 50 139 23.9 33.7 50

VAQ0709 18000 106 18.3 14.1 50 138 23.8 24.0 50 165 28.4 37.3 65

VAQ0710 20000 118 20.3 16.6 50 153 26.3 29.8 50 184 31.6 44.8 65

VAQ0811 25000 148 25.5 20.4 65 190 32.7 35.9 65 230 39.6 49.6 65

VAQ1011 30000 179 30.7 18.1 65 230 39.5 18.4 65 276 47.5 19.1 65

VAQ1012 35000 207 35.6 22.5 65 267 46.0 22.2 65 322 55.4 23.5 65

VAQ1013 40000 237 40.7 28.8 65 306 52.7 28.5 65 370 63.7 28.5 65

VAQ1212 45000 267 46.0 25.6 65 343 58.9 25.4 65 414 71.3 25.3 65

VAQ1213 50000 295 50.7 28.7 65 381 65.6 27.1 65 458 78.8 29.6 65

VAQ1215 60000 357 61.3 30.3 65 459 78.8 39.5 65 551 94.7 37.8 65

VAQ1415 70000 417 71.7 21.8 80 539 92.7 23.3 80 642 110 22.8 80

VAQ1417 80000 479 82.4 26.5 80 615 106 27.4 80 733 126 27.8 80

VAQ1419 90000 538 92.5 32.7 80 693 119 33.5 80 827 142 31.5 80

VAQ1421 100000 599 103 38.5 80 775 133 39.2 80 925 159 37.4 80

VAQ1820 120000 715 123 39.7 65 914 157 42.2 65 1114 192 48.8 65

VAQ1824 150000 899 155 40.3 65 1147 197 48.3 65 1377 237 52.6 65

VAQ2126 180000 1079 186 41.2 65 1382 238 51.1 80 1667 287 55.7 80

VAQ2128 200000 1196 206 44.5 65 1531 263 58.7 80 1846 317 63.2 80

VAQ2230 240000 1432 246 49.6 80 1834 315 64.3 80 2198 378 68.3 80

Note: 1. Air inlet temperature: 27oC DB/19.5oC WB. 2. Water inlet/outlet temperature: 7oC/12oC. 3. Maximum working pressure of coil is 1.6MPa. 4. Eliminator should be used when face velocity is more than 2.5m/s.

VAQ0404 3000 38.5 6.62 7.75 40 49.1 8.44 7.10 40 54.3 9.33 11.7 40

VAQ0405 4000 51.0 8.77 12.3 40 65.1 11.2 11.5 40 71.6 12.3 18.5 40

VAQ0406 5000 63.4 10.9 17.8 40 81.5 14.0 15.7 40 88.9 15.3 23.4 40

VAQ0505 6000 76.7 13.2 15.9 40 98.0 16.9 14.7 40 107 18.4 21.3 50

VAQ0506 8000 101 17.5 24.2 40 129 22.2 18.6 40 141 24.2 32.1 50

VAQ0606 10000 127 21.8 27.7 40 161 27.7 21.4 50 177 30.5 35.0 50

VAQ0607 12000 152 26.1 33.8 40 195 33.5 27.5 50 213 36.6 43.8 50

VAQ0609 15000 188 32.4 38.5 40 243 41.8 40.4 50 265 45.6 53.5 50

VAQ0709 18000 226 38.8 38.9 50 291 50.1 37.9 50 316 54.4 54.4 65

VAQ0710 20000 251 43.2 44.1 50 322 55.4 45.3 50 351 60.3 62.6 65

VAQ0811 25000 314 54.1 48.6 65 400 68.8 54.3 65 439 75.5 68.8 65

VAQ1011 30000 379 65.1 52.3 65 483 83.1 28.2 65 527 90.7 26.4 65

VAQ1012 35000 438 75.3 55.4 65 561 96.6 34.0 65 613

65

105 34.7 65

VAQ1013 40000 500 86.0 56.9 642 110 44.0 65 704 121 40.6 65

VAQ1212 45000 565 97.2 54.4 65 720 124 38.9 65 789 136 36.3 65

VAQ1213 50000 622 107 57.1 65 800 137 41.7 65 871 150 42.8 65

VAQ1215 60000 752 129 62.4 65 960 165 59.8 65 1045 180 56.9 65

VAQ1415 70000 884 152 41.0 80 1134 195 35.0 80 1224 210 31.7 80

VAQ1417 80000 1013 174 49.6 80 1291 222 41.5 80 1395 240 39.7 80

VAQ1419 90000 1135 195 54.8 80 1452 250 48.7 80 1572 270 46.7 80

VAQ1421 100000 1261 217 61.3 80 1622 279 56.9 80 1754 302 55.4 80

VAQ1820 120000 1513 260 75.6 65 1920 330 61.3 65 2120 365 72.3 65

VAQ1824 150000 1896 326 71.4 65 2403 413 70.2 65 2615 450 77.9 65

VAQ2126 180000 2274 391 78.5 65 2894 498 74.2 80 3162 544 82.5 80

VAQ2128 200000 2517 433 82.1 65 3202 551 85.3 80 3499 602 93.6 80

VAQ2230 240000 3011 518 84.6 80 3832 659 93.4 80 4165 716 96.8 80

Cooling capacity

(kW)

Cooling capacity

(kW)

Water flow (m3/h)

Water flow (m3/h)

Resistance (kPa)

Resistance (kPa)

DiameterDN

DiameterDN

DiameterDN

DiameterDN

DiameterDN

Resistance (kPa)

Model Resistance (kPa)

Resistance (kPa)

Water flow (m3/h)

Water flow (m3/h)

Water flow (m3/h)

Cooling capacity

(kW)

Cooling capacity

(kW)

Cooling capacity

(kW)

Rated air flow (m3/h)

4 rows 6 rows 8 rows

Note: 1. Air inlet temperature: 27oC DB/19.5oC WB. 2. Water inlet/outlet temperature: 7oC/12oC. 3. Maximum working pressure of coil is 1.6MPa. 4. Eliminator should be used when face velocity is more than 2.5m/s.

Page 8: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nit

1 1 12

Hea ng performance (return air condi on) Hea ng performance (fresh air condi on)

ModelRated

air flow (m3/h)

4 rows 6 rows 8 rowsHea ng capacity

(kW)

Water flow (m3/h)

Resistance (kPa)

DiameterDN

VAQ0404 3000 34.0 2.92 2.2 40 40.9 3.52 3.7 40 48.8 4.19 5.9 40

VAQ0405 4000 45.1 3.88 2.8 40 54.4 4.68 6.0 40 64.7 5.56 9.4 40

VAQ0406 5000 56.4 4.85 4.1 40 68.3 5.87 8.2 40 81.3 6.99 11.9 40

VAQ0505 6000 68.0 5.85 3.7 40 81.3 6.99 7.7 40 98.0 8.43 10.8 50

VAQ0506 8000 90.3 7.76 5.6 40 110 9.45 9.8 40 130 11.2 16.3 50

VAQ0606 10000 113 9.69 6.5 40 137 11.8 11.2 50 162 14.0 17.8 50

VAQ0607 12000 136 11.7 7.4 40 164 14.1 14.4 50 194 16.7 22.2 50

VAQ0609 15000 170 14.6 11.0 40 205 17.6 21.2 50 244 21.0 27.1 50

VAQ0709 18000 204 17.6 10.9 50 246 21.1 19.9 50 293 25.2 27.6 65

VAQ0710 20000 226 19.5 13.2 50 273 23.5 23.8 50 325 27.9 31.8 65

VAQ0811 25000 283 24.3 17.1 65 342 29.4 28.5 65 407 35.0 34.9 65

VAQ1011 30000 339 29.1 15.0 65 412 35.4 14.8 65 489 42.0 13.4 65

VAQ1012 35000 394 33.9 17.6 65 476 41.0 17.8 65 569 48.9 17.6 65

VAQ1013 40000 453 38.9 23.4 65 544 46.8 23.1 65 650 55.9 20.9 65

VAQ1212 45000 506 43.5 21.0 65 609 52.4 20.4 65 732 63.0 18.7 65

VAQ1213 50000 563 48.4 22.6 65 677 58.2 21.9 65 814 70.0 22.0 65

VAQ1215 60000 678 58.3 24.9 65 814 70.0 31.4 65 978 84.1 29.3 65

VAQ1415 70000 791 68.0 18.2 80 956 82.2 18.4 80 1142 98.2 16.3 80

VAQ1417 80000 907 78.0 19.9 80 1089 93.6 21.8 80 1298 112 20.4 80

VAQ1419 90000 1018 87.5 25.4 80 1233 106 25.5 80 1460 126 24.0 80

VAQ1421 100000 1132 97.3 29.3 80 1378 118 29.9 80 1631 140 28.5 80

VAQ1820 120000 1355 116 30.2 65 1628 140 32.1 65 1946 167 37.2 65

VAQ1824 150000 1700 146 30.7 65 2035 175 36.8 65 2431 209 40.1 65

VAQ2126 180000 2028 174 31.4 65 2462 212 38.9 80 2936 252 42.4 80

VAQ2128 200000 2260 194 33.9 65 2723 234 44.7 80 3246 279 48.1 80

VAQ2230 240000 2705 233 37.8 80 3263 281 49.0 80 3895 335 52.0 80

Note: 1. Air inlet temperature 15oC; 2. Water inlet/outlet temperature 60oC/50oC; 3. Maximum working pressure of coil is 1.6MPa.

VAQ0404 3000 40.7 3.50 2.88 40 50.0 4.30 5.93 40 58.1 4.99 8.14 40

VAQ0405 4000 53.9 4.63 4.57 40 66.3 5.70 8.76 40 76.9 6.61 12.7 40

VAQ0406 5000 67.2 5.78 6.63 40 83.0 7.13 12.2 40 96.4 8.29 18.0 40

VAQ0505 6000 81.2 6.98 5.94 40 98.9 8.50 10.6 40 116 10.0 15.4 50

VAQ0506 8000 108 9.25 9.05 40 133 11.5 14.8 40 154 13.3 24.7 50

VAQ0606 10000 134 11.5 10.3 40 167 14.3 17.0 50 193 16.6 24.5 50

VAQ0607 12000 162 13.9 11.8 40 199 17.1 20.5 50 230 19.8 32.2 50

VAQ0609 15000 202 17.4 17.8 40 248 21.3 28.3 50 289 24.8 35.9 50

VAQ0709 18000 242 20.8 17.3 50 297 25.5 26.9 50 346 29.8 40.1 65

VAQ0710 20000 269 23.1 20.3 50 330 28.4 33.5 50 384 33.0 48.0 65

VAQ0811 25000 335 28.8 24.6 65 413 35.6 40.9 65 481 41.4 53.1 65

VAQ1011 30000 402 34.5 21.8 65 497 42.8 20.8 65 577 49.6 20.4 65

VAQ1012 35000 467 40.2 27.2 65 575 49.4 24.8 65 672 57.8 25.1 65

VAQ1013 40000 536 46.1 35.0 65 656 56.4 31.7 65 767 66.0 30.1 65

VAQ1212 45000 600 51.6 30.7 65 735 63.2 28.3 65 865 74.4 27.0 65

VAQ1213 50000 667 57.4 34.8 65 817 70.2 30.1 65 961 82.6 31.8 65

VAQ1215 60000 802 69.0 36.4 65 981 84.3 43.8 65 1154 99.2 40.6 65

VAQ1415 70000 938 80.6 26.2 80 1154 99.3 25.9 80 1349 116 24.6 80

VAQ1417 80000 1075 92.5 31.7 80 1314 113 30.3 80 1533 132 29.7 80

VAQ1419 90000 1205 104 39.0 80 1487 128 35.7 80 1723 148 36.0 80

VAQ1421 100000 1340 115 44.6 80 1661 143 41.7 80 1924 165 42.3 80

VAQ1820 120000 1606 138 49.2 65 1961 169 46.7 65 2294 197 55.1 65

VAQ1824 150000 2013 173 54.4 65 2449 211 53.5 65 2864 246 59.4 65

VAQ2126 180000 2400 206 59.8 65 2963 255 56.6 80 3460 297 62.9 80

VAQ2128 200000 2674 230 62.5 65 3275 282 65.0 80 3824 329 71.3 80

VAQ2230 240000 3199 275 65.8 80 3923 337 71.2 80 4587 394 73.7 80

Hea ng capacity

(kW)

Hea ng capacity

(kW)

Hea ng capacity

(kW)

Hea ng capacity

(kW)

Hea ng capacity

(kW)Water flow

(m3/h)Water flow

(m3/h)

Water flow (m3/h)

Water flow (m3/h)

Water flow (m3/h)Resistance

(kPa)Resistance

(kPa)

Resistance (kPa)

Resistance (kPa)

Resistance (kPa)Diameter

DNDiameter

DN

DiameterDN

DiameterDN

DiameterDN

ModelRated

air flow (m3/h)

4 rows 6 rows 8 rows

Note: 1. Air inlet temperature 7oC; 2. Water inlet/outlet temperature 60oC/50oC; 3. Maximum working pressure of coil is 1.6MPa.

Page 9: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air

Han

dlin

g U

nit A

ir Handling U

nit

13 14

2) Steam hea ng sec on 3) Electric heater sec on

Humidifica on methods

4) Humidifica on sec on

This sec on is designed and added according to users’ requirements.Steam hea ng coil adopts galvanized steel pipe rolled with aluminum sheet or steel pipe rolled with steel sheet. Its maximum

working pressure is 0.4MPa, and it can be 2 or 3 rows.

Performance table

Note: 1. Air inlet temperature 7oC;

2. Steam pressure 0.2 MPa;

3. Parameters in above table are data of steel pipe rolled with aluminum sheet type;

4. Pararmeters in different face veloci es are 1.04 mes of above.

5. Please contact with VICOT for parameters in different steam pressures.

1. There must be one interlock device between fan motor and electric heater. Electric heater must be turned on a er fan motor starts up and

turned off before the fan motor stops.

2. The casing of electric heater must be earthed.

3. Insula ng resistance must be checked before the first opera on. The heater can be used only when the resistance is higher than 1MΩ. If

the ressistance decreases due to no use for a long me or uncared maintenance, it should be heated or electrified to recover its insula on. If

it cannot be recovered, it should not be used.

4. Check its insula ng resistance periodically.

5. Turn off the power before maintenance.

◎ Wet-film humidifica on: equal-enthalpy humidifica on, high satura on efficiency, saving space, sharing same sec on

with cooling coil to reduce the total length, no water treatment.

◎ Dry-steam humidifica on: isothermal humidifica on, high efficiency, stainless steel material, an -corrosion, having

mul -spraying rods structure or mul ple parallel.

◎ High pressure atomized humidifica on: equal-enthalpy humidifica on, stainless steel water distribu ng pipe, special

ceramic nozzle with high efficiency, an -corrosion and wear resistance, automa c an -blocking func on.

◎ Electrode humidifica on: high precise humidifica on, microprocessor controller, mul control mode.

Model Rated air flow (m3/h) Rows Hea ng capacity (kW) Model Rated air flow (m3/h) Rows Hea ng capacity (kW)

VAQ0404 30002 20.5

VAQ1013 400002 252

3 31.5 3 387

VAQ0405 40002 28.2

VAQ1212 450002 283

3 43.4 3 435

VAQ0406 50002 36.1

VAQ1213 500002 310

3 55.2 3 476

VAQ0505 60002 39.3

VAQ1215 600002 364

3 65.4 3 558

VAQ0506 80002 47.5

VAQ1415 700002 426

3 72.9 3 654

VAQ0606 100002 59.4

VAQ1417 800002 489

3 90.6 3 749

VAQ0607 120002 71.7

VAQ1419 900002 551

3 110 3 845

VAQ0609 15000 2 97.1 VAQ1421 100000 2 614 3 149 3 940

VAQ0709 180002 116

VAQ1820 1200002 708

3 178 3 1087

VAQ0710 200002 131

VAQ1824 1500002 872

3 201 3 1338

VAQ0811 250002 161

VAQ2126 1800002 1124

3 248 3 1725

VAQ1011 300002 209

VAQ2128 2000002 1220

3 321 3 1874

VAQ1012 350002 231

VAQ2230 2400002 1477

3 354 3 2267

Page 10: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

15 16

Wet-film humidifier

Dry steam humidifier

It humidifies air through natural evapora on of water. Its basic medium is plant fiber. The plant fiber is sintered to form overlapping

corrugated plate polymer composites a er special process, which have strong water absorp on, good self-cleaning ability, non-toxic,

acid resistance, mold resistance and fire-retardant. Its structure can provide the maximum contact surface with air and body of 1 square

meter has contact area of 500-600m2. When dry air passes the wet-film, water molecules will absorb heat from the air, vaporize and

evaporate, which inceases the air humidity. It can use running water or domes c water. Its features are as floows:

Its process is that filtered saturated steam enters into the humidifier, flows axially in the steam sleeving rods and heats the center

spraying rods by the latent heat of steam for ensuring to spray pure dry steam (without condensed water). Then, the saturated steam

enters into steam water separator chamber through steam sleeving rods; in the chamber is annular baffles; when the steam passed it,

it will rotate and flow upward ver cally to separate steam and condensate; the separated condensate is discharged through the trap.

When air needs to be humidified, the regula ng valve will be opened and dry steam enters into center sparying rod and is sprayed out

for humidifica on.

◎ Cleaning equal-enthalpy humidifica on: wet-film cooling humidifica on,without “white powder” phenomenon.

◎ Short humidifying distance: only wet-film body’s thickness.

◎ High satura on effciency: up to 80%.

◎ Safe and reliable: with an bacterial ingredients, good mold resistance.

◎ Advanced steam water separa on technology and structure, ensuring the separa on completely and thoroughly.

◎ Isothermal humidifica on, high efficiency, up to 95%.

◎ Unique muffler structure, no whistle and noise.

◎ Electric or magnCe c dry steam integra on, achieving precise remote control.

Humidifica on capacity of wet-film humidifier

ModelRated air flow

(m3/h)

Fresh air condi on (kg/h) Return air condi on (kg/h)

35%

efficiency

60% 75% 85% 35% 60% 75% 85%

VAQ0404 3000 7 13 20 23 6 11 17 19

VAQ0405 4000 10 19 28 32 8 15 23 26

VAQ0406 5000 12 24 35 40 10 19 29 33

VAQ0505 6000 13 24 37 42 11 20 30 34

VAQ0506 8000 16 31 47 53 13 26 39 44

VAQ0606 10000 20 39 58 66 17 32 48 54

VAQ0607 12000 25 47 71 80 20 39 58 66

VAQ0609 15000 33 64 96 108 28 52 79 89

VAQ0709 18000 40 76 114 129 33 63 94 107

VAQ0710 20000 45 86 129 146 37 71 106 121

VAQ0811 25000 56 106 159 180 46 87 131 148

VAQ1011 30000 72 137 206 233 59 113 170 192

VAQ1012 35000 80 151 227 258 66 125 187 212

VAQ1013 40000 87 166 249 282 72 136 205 232

VAQ1212 45000 98 186 279 316 80 153 230 261

VAQ1213 50000 107 204 305 346 88 168 252 285

VAQ1215 60000 125 239 358 406 103 196 295 334

VAQ1415 70000 147 280 419 475 121 230 345 391

VAQ1417 80000 168 321 481 545 139 264 396 449

VAQ1419 90000 190 361 542 615 156 298 447 506

VAQ1421 100000 211 402 604 684 174 331 497 563

VAQ1820 120000 244 465 698 791 201 383 575 651

VAQ1824 150000 301 573 859 973 248 472 707 802

VAQ2126 180000 388 738 1107 1255 319 608 912 1034

VAQ2128 200000 421 802 1202 1363 347 660 990 1122

VAQ2230 240000 509 970 1455 1648 419 799 1198 1358

efficiency efficiency efficiency efficiency efficiency efficiency efficiency

Note: fresh air condi on: 30oC DB & 10% RH; return air condi on: 27oC DB & 30% RH.

Comparison of different humidifica on methods

TypeUsing condi ons

Ambient temperature Humidity

Cri cal wind velocity (m/s) Water quality

Water/steam temperature

Water/steam pressure

Length (mm)

Wet-film type 5~70oC <90% <4.0 Running water or same 5~40oC 0.15~0.75 With coil

Dry steam type / / / Steam 0~240oC 0.02~0.4 600

High pressure atomized type 1~40oC <85% 0.5~3.5

Running water, purified water or same 4~55oC 0.1~0.5 1000

Electrode 0~40oC <80% / Running water or demineralized water 0~40oC 0.1~1.0 600

Electrothermal type 0~40oC <80% /Demineralized water, deionized water or reverse osmosis water 0~40oC 0.05~0.4 600

Page 11: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

17 18

Comparison of filter efficiency

Comparison table of filter efficiency and classifica ons of China, USA and EU

Pre-filter≥5μm Medium≥1μm High medium≥1μm Sub HEPA≥0.5μm HEPA≥0.5μmChina GB/T14295 80%>Efficiency≥20% 70%>EfficiencyC≥20% 99%>Efficiency≥70% 99.9%>EfficiencyC≥95% Efficiency>99.99%

European new standard

USA ASHRAE C1 C2~C4 L5 L6 L7 L8 M9 M10 M11 M12 M13 M14 H12~H16 VH17 VH18 VH19 VH20

G1 G2 G3 G4 F5 F6 F7 F8 F9 H10 H11 H12 H13 H14 V15,V17

65% 80% 80-90% >90% 40% 60% 80% 90% 85% 95% 99% 99.9% 99.995% 99.995% 99.9995%European

old standard EU1 EU2 EU3 EU4 EU5 EU6 EU7 EU8 EU9 EU10 EU11 EU12 EU13 EU14

欧洲规格Europe

U17

U16

U15

H14

H13

H12

H11

H10

F9

F8

F7

F6

F5

G490%

计重法Arrestance

80%

65%

G3

G2

G1

MPPS最易穿透粒径

中国传统分类 钠焰法

Chinese Classifica on Sodium Flame

EN77

9:20

02CE

N E

N18

22-1

EN77

9:20

02,0

.4μm

平均

AN

SI/A

SHRA

E 52

.1-1

992

AN

SI/A

SHRA

E 52

.1-1

992

GB1

2218

-89 大

气尘计数法

GB1

3554

-92

GB1

3554

-92

BS39

28,G

B616

5-85

AN

SI/A

SHRA

E 52

.2-1

999

99.5%

99.95%

99.995%

99.9995%

99.99995%

99.999995%

95%

85%

85%

90%

40%

60%

80%

比色法Dust-spot

99.9%(0.5μm)

95%(0.5μm)99%(1μm)

70%(1μm)

20%(1μm)

20%(5μm)

80%(5μm)

V类 亚高效

高效99.999%

欧洲旧规格

美国规格

ASHRAE52.2

Eurovent

Eu14

Eu13

Eu12

Eu11

Eu10

Eu9

Eu8

Eu7

Eu6

Eu5

Eu4

Eu3

Eu2

Eu1 MERV1

MERV2-4

MERV5MERV6MERV7MERV8MERV9MERV10MERV11MERV12

MERV13

MERV14

MERV15

MERV16

MERV17MERV18

MERV19

MERV20

99.99%99.97%

99.9%

95%

HEPA

高中效

Sub-HEPA

High-

medium

Medium

Coarse

中效

粗效

IV类

Ⅲ类

Ⅱ类

Ⅰ类

5) Filter sec on

Dimension table of built-in filter

Standard filter class: plate pre-filter of G3, medium bag filter of F5 and sub HEPA bag filter of F9.

Besides above filters, we can also provide other filters according to users’ requirements.

ModelDimension of built-in filter (mm)

592×592 592×490 490×490 592×390 490×390 390×390 592×287 490×287 390×287 287×287VAQ0404 / 

/ /  / 

/ /  /  / 

/ 

/  / 

/ / / 

/ 

/ 

/ / / 

/ 

/ / 

/ 

/ 

/ / 

/ / /  / 

/ 

/ / / 

/ 

/ / / / / / 

/ / 

/ 

/ / / 

/ / 

/ 

/ 

/ 

/ 

/ / / / 

/ / 

/ / 

/ / 

/ 

/ 

/ / / / / / / 

/ / 

/ 

/ 

2 2  

VAQ0405 1 1 1 1  

VAQ0406 1 1 1 1    

VAQ0505   1 2 1    

VAQ0506 1 1 1 1    

VAQ0606 1 2 1    

VAQ0607 2 2   1 1    

VAQ0609 2 3 1        

VAQ0709 4 2 2 1    

VAQ0710   4   2 2 2 1 1VAQ0811 3 3   3 1 1 1  

VAQ1011 3 3 6 1 1 2  

VAQ1012 3 4 1 6 2 3    

VAQ1013 2 4 2 4 4 1 1 2  

VAQ1212 9 3 3 1      

VAQ1213 6 6 4   3   1  

VAQ1215 12 3 4 1      

VAQ1415 12 3 8 2      

VAQ1417 9 9 6 6      

VAQ1419 12 6   8 4   3   2  

VAQ1421 18 3   12 2          

Note: 1. Pre-filter: plate type, 2 inches width of frame, folded washable filter, non-woven fabric materials, filtra on efficiency G3 (80%-90% Arrestance).

2. Medium filter: bag type, 1 inch width of frame, 20 inches length of bag, non-woven fabric materials, filtra on efficiency F5 (40-60% Dust-spot).

3. High medium / sub HEPA filter: ultra-fine glass fiber filter, filtra on efficiency F7-F9 (80-95% Dust-spot).

4. HEPA filter: please contact with VICOT if users want to add sub HEPA or HEPA filter.

5. Filter resistance is between ini al resistance and final resistance. Ini al resistance refers to the resistance when the filter has non-dust pollu on; final resistance

refers to the resistance when the filter has been dust pollu on and needs to be washed or replaced a er a certain me. It is not a fixed value and is determined by indoor

requirements to cleanliness and outdoor air pollu on.

6. VICOT can provide op onal differen al pressure gauge and switch for filter. The pressure switch can control differen al pressure alarm forC alarming.

/ / / / / / /  / 

/ / / 

/ 

/ 

/ / 

/ 

/ 

/ / / 

/ / / / / / 

/ / / 

/ / / / / 

/ / / / / / 

Page 12: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

19 20

6) Noise silencing sec on

Drag coefficiency

This sec on uses damped muffler, which consists of preforated plate with built-in sound-absorbing co on and has good noise

reduc on effect in a wide frequency range. The silencer can be made of galvanized steel sheet(standard), aluminium sheet or s anless

steel plate, with features of li le internal resistance, low noise, heat-resistant, humidity resistant, easy to clean, etc. Sound absorp on

band can be changed through changing perfora on diameter and rate.

ModelRated air flow

(m3/h)

Sound deadening capacity (dB(A)) Air resistance (Pa)

Silencer length (mm)/sec on length Silencer length (mm)/sec on length600/4M 900/5M 1200/6M 600/4M 900/5M 1200/6M

VAQ0404 3000 17 20 23 20 21 23 VAQ0405 4000 17 20 23 19 20 21 VAQ0406 5000 17 20 23 18 19 20 VAQ0505 6000 17 20 23 25 26 27 VAQ0506 8000 17 20 23 27 28 30 VAQ0606 10000 17 20 23 27 29 30 VAQ0607 12000 17 20 23 27 28 30

VAQ0609 15000 17 20 23 23 24 25

VAQ0709 18000 17 20 23 23 24 25 VAQ0710 20000 17 20 23 22 23 25 VAQ0811 25000 17 20 23 23 24 25 VAQ1011 30000 17 20 23 20 21 22 VAQ1012 35000 17 20 23 22 23 24 VAQ1013 40000 17 20 23 24 25 26 VAQ1212 45000 17 20 23 24 25 27 VAQ1213 50000 17 20 23 25 26 27 VAQ1215 60000 17 20 23 26 27 29 VAQ1415 70000 17 20 23 26 27 29 VAQ1417 80000 17 20 23 26 27 28 VAQ1419 90000 17 20 23 25 27 28 VAQ1421 100000 17 20 23 25 27 28 VAQ1820 120000 17 20 23 27 29 30 VAQ1824 150000 17 20 23 28 30 31 VAQ2126 180000 17 20 23 24 26 27 VAQ2128 200000 17 20 23 26 27 28 VAQ2230 240000 17 20 23 25 26 28

Silencer length (mm) 600 900 1200 1500 1800 2100 2400Drag coefficiency (ζ) 5.531 5.834 6.137 6.440 6.720 7.000 7.280

Calcula on of silencer pressure loss

ΔP=ζρυ2/2 ΔP: pressure loss ζ: drag coefficiency ρ: air density υ: silencer sec onal wind velocity

7) Fan sec on

Table of fan power

According to air flow and external sta c pressure, select forward or backward fan. The fan is F class insula on, IP54 protec on, and

380V/3Ph/50Hz power or others. Fan and motor are mounted on the same frame. There are spring shock absorbers between the frame and

unit. And, the outlet of fan has flexible joint for reducing shocking.

ModelAir pressure (Pa)

600 700 800 900 1000 1100 1200/

1400 1500 1600 1800 2000VAQ0404 3000 1.5 1.5 2.2 2.2 2.2 3 3        

VAQ0405 4000 1.5 2.2 2.2 2.2 3 3 3          

VAQ0406 5000 1.5 2.2 2.2 2.2 3 3 3          

VAQ0505 6000 2.2 2.2 3 3 4 4 4 4 4 5.5 5.5 5.5VAQ0506 8000 3 4 4 5.5 5.5 7.5 5.5 5.5 5.5 7.5 7.5 7.5VAQ0606 10000 4 4 5.5 5.5 7.5 7.5 5.5 7.5 7.5 7.5 11 11VAQ0607 12000 4 4 5.5 5.5 7.5 7.5 7.5 7.5 11 11 11 11

VAQ0609 15000 5.5 5.5 7.5 7.5 7.5 11 11 11 11 11 15 15

VAQ0709 18000 5.5 7.5 7.5 11 11 11 11 11 15 15 15 15

VAQ0710 20000 5.5 7.5 7.5 11 11 11 11 15 15 15 15 18.5VAQ0811 25000 7.5 11 11 11 15 15 15 15 15 18.5 18.5 22VAQ1011 30000 11 11 15 15 15 15 185 18.5 18.5 22 22 30VAQ1012 35000 11 15 15 15 15 18.5 18.5 22 22 30 30 30VAQ1013 40000 15 15 15 18.5 18.5 18.5 22 30 30 30 30 37VAQ1212 45000 18.5 18.5 18.5 22 22 22 30 30 30 30 37 37VAQ1213 50000 18.5 18.5 22 22 30 30 30 30 37 37 37 45VAQ1215 60000 18.5 22 22 30 30 30 30 37 37 45 45 55

VAQ1415 70000 30 30 30 30 37 37 37 45 45 45 55 55

VAQ1417 80000 30 30 37 37 37 45 45 55 55 55 75 75VAQ1419 90000 37 37 37 45 45 45 55 55 55 55 75 75VAQ1421 100000 37 37 45 45 45 55 55 75 75 75 75 75VAQ1820 120000 18.5×2 22×2 22×2 30×2 30×2 30×2 30×2 37×2 37×2 45×2 45×2 55×2VAQ1824 150000 30×2 30×2 37×2 37×2 37×2 45×2 45×2 55×2 55×2 55×2 75×2 75×2VAQ2126 180000 37×2 37×2 37×2 45×2 45×2 45×2 55×2 55×2 55×2 55×2 75×2 75×2VAQ2128 200000 37×2 37×2 45×2 45×2 45×2 55×2 55×2 75×2 72×2 75×2 75×2 75×2VAQ2230 240000 45×2 45×2 55×2 55×2 75×2 75×2 75×2 90×2 90×2 110×2 110×2 110×2

Note: Above table is suitable for supply fan, return fan and middle fan all.

Rated air flow

(m3/h)

//

///

/

//

///

///

Page 13: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

21 22

6. Air resistance of wet film humidifier5. Air resistance of filter (Pa)

300mm

3.43.232.82.62.42.2

250mm

200mm

150mm

100mm

50mm

Face velocity (m/s)

Air

resi

stan

ce (P

a)

140120100

806040200

Dimension1. Unit dimension

1. Correc on coefficiency of cooling capacity, hea ng

capacity and water flow

3. Correc on coefficiency of air resistance of

cooling coil

2. Correc on coefficiency of water resistance of

cooling coil

Performance in different condi ons

4. Correc on coefficiency of air resistance of

water eliminator

245

220

195

170

145

120

95

70

45

20

2.2 2.4 2.6 2.8 3.0 3.2 3.4

Sub HEPA filter:

plate type,

H10, 85%

Sub HEPA filter:

plate type,

F9, 95%

Sub HEPA filter:

bag type,

F9, 95%

Medium filter

(high): bag

type, F8, 90%

Medium filter

(high): bag

type, F7, 80%

Medium filter

(high): bag

type, F6, 60%

Medium filter

(high): bag

type, F5, 40%

Prefilter: bag

type, G4, 90%

Prefilter: bag

type, G3, 80%

Prefilter: plate

type, G4, 90%

Prefilter: plate

type, G3, 80%

Face velocity (m/s)

Air

resi

stan

ce (P

a)

Face velocity (m/s)

Corr

econ

coe

ffici

ency

Face velocity (m/s)

Face velocity (m/s)Face velocity (m/s)

Wat

er r

esis

tanc

e (P

a)

Resi

stan

ce (P

a)

Resi

stan

ce (P

a)

1

2

4

6

8

Rows

Page 14: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

23 24

2. Sec ons’ dimension1) Air inlet, air outlet and air distribu on sec on

Model Rated air flow (m3/h) L1 L2 A×B

VAQ0404 3000 600 800 320×400

VAQ0405 4000 600 800 400×400

VAQ0406 5000 600 800 400×500VAQ0505 6000 600 800 400×600VAQ0506 8000 600 800 600×600VAQ0606 10000 600 800 600×600VAQ0607 12000 600 800 600×800VAQ0609 15000 600 800 600×1000VAQ0709 18000 600 800 600×1200VAQ0710 20000 600 800 600×1400VAQ0811 25000 600 800 600×1400VAQ1011 30000 600 800 600×1600VAQ1012 35000 800 1000 800×1400VAQ1013 40000 800 1000 800×1600VAQ1212 45000 800 1000 800×1800VAQ1213 50000 800 1000 800×2000VAQ1215 60000 800 1000 800×2400VAQ1415 70000 1000 1200 1000×2400VAQ1417 80000 1000 1200 1000×2600VAQ1419 90000 1000 1200 1000×2800VAQ1421 100000 1000 1200 1000×2800VAQ1820 120000 1400 1600 1400×2800VAQ1824 150000 1400 1600 1400×3600VAQ2126 180000 1400 1600 1400×4000VAQ2128 200000 1400 1600 1400×4000VAQ2230 240000 1400 1600 1400×4800

Model Rated air flow (m3/h)30mm thickness of panel 50mm thickness of panel

H(mm) W(mm) H(mm) W(mm)

VAQ0404 3000 880 880 920 920

VAQ0405 4000 880 1080 920 1120

VAQ0406 5000 880 1280 920 1320

VAQ0505 6000 1080 1080 1120 1120

VAQ0506 8000 1080 1280 1120 1320

VAQ0606 10000 1280 1280 1320 1320

VAQ0607 12000 1280 1480 1320 1520

VAQ0609 15000 1280 1880 1320 1920

VAQ0709 18000 1480 1880 1520 1920

VAQ0710 20000 1480 2080 1520 2120

VAQ0811 25000 1680 2280 1720 2320

VAQ1011 30000 2080 2280 2120 2320

VAQ1012 35000 2080 2480 2120 2520

VAQ1013 40000 2080 2680 2120 2720

VAQ1212 45000 2480 2480 2520 2520

VAQ1213 50000 — — 2520 2720

VAQ1215 60000 — — 2520 3120

VAQ1415 70000 — — 2920 3120

VAQ1417 80000 — — 2920 3520

VAQ1419 90000 — — 2920 3920

VAQ1421 100000 — — 2920 4320

Note: 1. Above heights don’t include the height of base “T”.

2. The base height T of units under air flow of 45000m3/h is 80mm and panel thickness 30mm; above 45000m3/h is 100mm and 50mm.

3. Units adopt three-dimensional modular design and1M=200mm.

4. Package length=length modules nos×200+packing quan ty×K Width=width modules nos×200+K Height=height modules nos×200+T+K.

K: 80mm for units of 30mm thickness of panel; 120mm for units of 50mm thickness of panel.

Horizontal air inlet/outlet sec on

Top air inlet/outlet sec on

Mixing box sec on

Air distribu on sec on

Page 15: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

25 26

3) Fan sec on

ModelRated air flow

(m3/h)Total pressure (Pa)

E×F600 700 800 900 1000 1100 1200 1400 1500 1600 1800 2000

VAQ0404 3000 6M 6M 6M 6M 6M 6M 6M   400×400VAQ0405 4000 6M 6M 6M 6M 6M 6M 6M   400×400VAQ0406 5000 6M 6M 6M 6M 6M 6M 6M   400×400VAQ0505 6000 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 500×500VAQ0506 8000 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 500×500VAQ0606 10000 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 600×600VAQ0607 12000 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 600×600VAQ0609 15000 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 600×600VAQ0709 18000 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 700×700VAQ0710 20000 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 6M 700×700

VAQ0811 25000 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 7M 800×800

VAQ1011 30000 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 8M 800×800VAQ1012 35000 9M 9M 9M 9M 9M 9M 9M 9M 9M 9M 9M 9M 1000×1000VAQ1013 40000 9M 9M 9M 9M 9M 9M 9M 9M 9M 9M 9M 9M 1000×1000VAQ1212 45000 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 1100×1100VAQ1213 50000 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 1100×1100VAQ1215 60000 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 10M 1200×1200VAQ1415 70000 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 1300×1300VAQ1417 80000 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 1400×1400VAQ1419 90000 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 1400×1400VAQ1421 100000 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 12M 1500×1500

Note: According to real air flow and air pressure, dimensions of E&F will be adjusted.

ModelRated air flow

(m3/h) Coil quan tyA B C E

ΦDmm mm mm mm

VAQ0404 3000 1 170 600

0

96 DN25

VAQ0405 4000 1 170 600VAQ0406 5000 1 170 600VAQ0505 6000 1 170 800VAQ0506 8000 1 170 800VAQ0606 10000 1 175 1005VAQ0607 12000 1 175 1005VAQ0609 15000 1 175 1005VAQ0709 18000 1 175 1210VAQ0710 20000 1 175 1210VAQ0811 25000 2 185 622 98VAQ1011 30000 2 185 825 98VAQ1012 35000 2 185 825 98VAQ1013 40000 2 185 825 98

100

DN32

VAQ1212 45000 2 185 1028 98 VAQ1213 50000 2 185 1028 98

120

VAQ1215 60000 2 185 1028 98VAQ1415 70000 2 190 1180 130VAQ1417 80000 2 190 1180 130VAQ1419 90000 2 190 1180 130VAQ1421 100000 2 190 1180 130VAQ1820 120000 3 203 1020 105

123 DN40VAQ1824 150000 3 203 1020 105VAQ2126 180000 3 208 1220 130VAQ2128 200000 3 208 1220 130VAQ2230 240000 3 208 1380 130

///

///

///

///

///

2) Cooling/hea ng coil sec on

Upper horizontal supply fan

Lower horizontal supply fan

Top supply fan (A) Top supply fan (B) Middle fan Horizontal return fan Top return fan

Page 16: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

27 28

4. Sec ons weight

Model VAQ0404 VAQ0405 VAQ0406 VAQ0505 VAQ0506 VAQ0606 VAQ0607 VAQ0609 VAQ0709 VAQ0710 VAQ0811

Air inlet sec on

Mixing box 38 45 54 52 65 78 73 88 80 89 99

Mixing box with filter 61 70 84 95 107 128 120 144 146 164 181

Top(horizontal) air in 35 42 50 49 61 73 70 84 76 85 73

Filter sec on

Plate type 37 41 49 55 61 73 73 88 87 98 107

Bag type 50 53 64 69 76 91 90 108 106 118 129

Combined type 58 63 76 88 96 115 117 140 143 161 176

Cooling/hea ng coil sec on

4 rows with eliminator 51 58 69 81 101 121 125 137 149 182 206

6 rows with eliminator 60 66 79 94 117 140 146 161 175 215 248

8 rows with eliminator 66 74 89 106 133 160 167 184 202 248 289

Steam hea ng sec on

1 row 31 39 47 54 69 83 88 106 107 130 150

2 rows 55 61 73 87 115 138 149 179 185 228 266

Dry steam humidity sec on 42 52 51 61 60 57 68 64 77 69 78

Middle sec on 30 33 33 40 36 39 47 43 52 46 53

Air balancing sec on 33 38 39 47 48 51 61 59 71 67 82

Noise silencing sec on 58 72 76 91 95 119 143 142 170 170 218

Air outlet sec on 36 44 42 50 49 61 73 70 84 76 73

Fan sec on

600Pa 154 171 205 216 226 271 334 401 377 504 662

700Pa 154 182 213 216 244 271 334 401 422 529 682

800Pa 165 182 213 224 244 293 348 418 442 529 682

900Pa 165 182 213 224 265 293 348 418 485 556 682

1000Pa 165 189 220 232 265 310 388 418 485 556 712

1100Pa 170 189 220 232 278 310 388 468 485 556 712

1200Pa 170 189 220 249 286 352 402 477 510 595 731

1400Pa 249 286 352 402 477 510 620 731

1500Pa 249 286 352 436 477 543 647 731

1600Pa 273 293 352 436 477 543 647 765

1800Pa 273 293 378 436 498 543 647 765

2000Pa 273 293 378 436 498 543 677 794

Note: Opera ng weight is more than 10%-15% of net weight.

3. Usual func onal sec ons applica on

/

//

/

/

///

/

/

///

/

/

Mixing box

Silencer Return fan Air distribu onPlate pre-filter

Cooling coil 2nd return

airHea ng coil

Supply fan Air balancing

SilencerMiddle sec on

Medium bag filter

Air discharge

Return fan Air distribu on Pre&mediumfilter

Cooling coil Middle sec on

Hea ng coil

Dry steam humidifier

Supply fan

Mixing box Plate pre-filter

Cooling coil with wet film

Middle sec on

Hea ng coil

Supply fan Air balancing

Silencer Middle sec on

Medium bag filter

Air discharge

Mixing box Pre & mediumfilter

Cooling coil Middle sec on

Hea ng coil with

humidifier

Supply fan

Mixing boxPlate pre-filter

Cooling coil Supply fan

Page 17: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

29 30

Wiring at site

Notes:

1. Users should provide electric components

and wiring in broken line.

2. This method is suitable for fan motor of

more than 15kW (including 15kW); that of

less than 11kW can be started directly.

3. Users can use other startup method

according to real situa on.

Note: Opera ng weight is more than 10-15% of unit net weight.

Model VAQ1011 VAQ1012 VAQ1013 VAQ1212 VAQ1213 VAQ1215 VAQ1415 VAQ1417 VAQ1419 VAQ1421

Air inlet sec on

Mixing box 130 139 152 187 200 211 262 275 295 318

Mixing box with filter 226 252 275 304 331 365 413 445 471 512

Top (horizontal) air in 126 135 149 186 200 213 265 281 300 345

Filter sec on

Plate type 124 143 153 245 180 205 218 241 254 311

Bag type 148 164 180 183 206 230 245 270 285 366

Combined type 207 238 258 267 305 350 373 416 438 498

Cooling/hea ng coil sec on

4 rows with eliminator 236 273 314 626 694 777 850 923 994 1125

6 rows with eliminator 284 328 380 755 838 939 1028 1118 1207 1320

8 rows with eliminator 332 384 445 884 981 1100 1206 1313 1419 1542

Steam hea ng sec on

1 rows 177 204 235 271 308 344 385 425 466 532

2 rows 316 370 429 489 558 629 705 782 859 966

Dry steam humidity sec on 84 84 89 95 96 102 106 112 118 138

Middle sec on 58 58 61 65 58 65 66 70 125 167

Air balancing sec on 86 86 99 103 107 114 123 127 191 288

Noise silencing sec on 248 248 303 341 367 386 409 432 506 599

Air outlet sec on 126 126 135 149 186 200 213 265 281 355

Fan sec on

600Pa 699 720 767 1073 1113 1128 1333 1374 1411 1523

700Pa 699 750 767 1073 1123 1143 1333 1374 1411 1523

800Pa 729 750 767 1073 1203 1143 1333 1389 1411 1658

900Pa 729 750 787 1108 1203 1143 1333 1389 1522 1658

1000Pa 729 750 832 1108 1138 1208 1348 1389 1522 1658

1100Pa 729 796 832 1108 1228 1208 1348 1414 1522 1790

1200Pa 766 796 877 1213 1228 1233 1348 1414 1654 1790

1400Pa 766 825 1033 1213 1228 1303 1395 1549 1654 1930

1500Pa 766 825 1033 1213 1244 1303 1395 1549 1654 1930

1600Pa 811 922 1033 1213 1244 1386 1395 1549 1654 1930

1800Pa 811 922 1244 1388 1244 1386 1510 1686 1770 1930

2000Pa 811 922 1244 1388 1291 1477 1510 1686 1770 1930

1. Before installing unit, check unit’s model, parts and appearance, etc. according to manual and packing list. Then, open the

access door and turn blades of fan by hand to check if there is any metal grinding noise; if it is, solve it.

2. Unit should be installed on a flat base, which can be concrete type or made by steel channel and should be 160mm higher than

ground at least. There should be drainage ditch and floor drain around the base, for draining the condensate and sewage. And,

there should be enough space for maintenace.

3. The pipe below of heat exchanger is water inlet and above is outlet. Pipings should have their own brackets for bearing their

weight and avoiding unit to bear load. Install check valve for adjus ng water flow and maintenance, and Y-stainer for filtering

impuri es on the water inlet pipe; install air vent at the highest point of system and drain valve at the lowest point. Due to

nega ve pressure, the condensate pipe should be connected to a U-shaped water trap first and then to the sewer (See diagram

of water seal).

4. There should be flexible joint between unit and air duct. Air duct should have its own brackets for bearing the weight.

5. The power is 380V/50Hz/3Ph. A er electrifying, check fan’s rota ng direc on; if it is reverse, change phase sequence of power.

6. Motor should be connected to power with protec on device. Case of unit should be grounded. Motor of more than 15kW

shoud adopt reducing voltage start.

7. Power controller should have phase protec on and overload protec on.

8. There should be enough space for maintenance.

Installa on, opera on and maintenanceInstalla on

Page 18: Air Handling Unit - Vikotvikot.net/data/documents/1VikoT-Air-Handling-Unit.pdf · Vicot Air Conditioning Co., Ltd. Add: Hongdu Road, Dezhou Economic Development Zone, Shandong, China

Air H

andling UnitA

ir H

andl

ing

Uni

t

31 321. In the seasons (except winter) that heat exchanger isn’t used, fill it with water fully for an -corrosion.

2. In winter, if the unit isn’t used, drain all water in the heat exchanger and blow the remaining water by compressed air for

an -fros ng.

3. When the unit isn’t used for a long me, close fresh air damper, drain water in heat exchanger, loosen belt, and add lubrica ng

oil.

4. Water in the system must be clean and demineralized water is be er.

Maintenance

When it is nega ve pressure, A=B≥P/10+20mm

When posi ve pressure, A>P/10+20 mm B≥30 mm

P is the air pressure value at this posi on.

About Vicot Group1. Before star ng the unit, check each manual/electric valve.

2. Check fan’s bolts, belt and blades.

3. Check air duct’s valves, water pipings, electric system, controll components and wiring.

4. Exhaust the air in the unit and system.

5. Filters should be washed or replaced periodically.

6. The fan and motor parts should be lubricated regularly according to environmental condi ons.

7. The unit should be operated by professional persons. Check unit’s opera on regularly and remove the abnormal situa on.

8. Ensuring the insula on of ven la on system and water system is good enough.

9. During the using, if there is any damage or aging, like canvas, repair or replace it immediately.

10. In cold area, open the heat resouce 5-10 minutes before star ng the fan in order to avoiding cold air to form ice jam. When stoping

the unit, a small amount of hot water should circulate in the coil to prevent rust and frost.

Vicot Group is a high-tech corpora on specialized in R&D,

produc on, sales and service of renewable energy products. The

corpora on has almost 2000 staff and seven business divisions

and/or centers.

Our produc on base locates in Solar City, Dezhou, China, it

covers an area of 150,000 square meters with modern workshops

and office buildings of more than 80,000 square meters. Annual

yield capabili es are as follows: 100,000 electrical AC units; 10,000

gas fired AC units; 200,000 square meters of collectors; 100,000

pieces of tubes; Designed annual produc on value reaches

RMB5billion.

With the mission of “The same breath, energy saving

together”, the corpora on realizes energy saving and environment

protec on by focusing on effec ve u liza on of solar energy, air

source energy, geothermal energy and other renewable energies in

cooling, hea ng and domes c hot water fields.

With a total investment of RMB 16 million in April 2008, a er 3

years’ collabora on with more than 20 global universi es and

research ins tutes in sequence, Vicot successfully and innova vely

launched solar absorp on chiller and heat pump, solar absorp on,

central hea ng system, solar absorp on central hot water system,

solar boiler system, having more than 150 patents, large scale

produc on of them has been realized. It places China at the world

top level in solar medium temperature applica on field.

In the mean me of developing the technology of world leading

new energy product, the corpora on is operated with global

advanced ERP technique, UPDI\WMS barcode storage system and

ABC cost control system. Informa on, logis cs and cash flow are

highly integrated.

The corpora on has been awarded as “High and New

Technology Corpora on in Shandong Province”, “Energy-saving and

Innova ve Technology Award in China Refrigera on Industry”, etc..

It has ISO9001 and ISO14001 cer fica on, implements CE and

EUROVENT standards and guarantees its products of world level

quality with strict process control and comprehensive quality

management system.

Condensate pipe

AHU

Water discharge

Diagram of water seal

A

B

Opera on