66
MODEL VDC CONDENSER AND MODEL VDCF FLUID COOLER VDC 66 MODELS R-22, R-134A, R-404A, R-407C, R-410A, R-507A NOMINAL HEAT REJECTION CAPACITY 175 MBH THROUGH 2280 MBH VDCF 22 MODELS WATER, ETHYLENE GLYCOL, PROPYLENE GLYCOL NOMINAL HEAT REJECTION CAPACITY 65 MBH THROUGH 2890 MBH ISSUE DATE: October 12, 2020 AIR-COOLED CONDENSER AND FLUID COOLER INSTALLATION, OPERATION, MAINTENANCE Supersedes 195.29-NM1 (615) Form 195.29-NM1 (1020) 035 23478 100

AIR-COOLED CONDENSER AND FLUID COOLER

  • Upload
    others

  • View
    30

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AIR-COOLED CONDENSER AND FLUID COOLER

MODEL VDC CONDENSER AND

MODEL VDCF FLUID COOLER

VDC 66 MODELS R-22, R-134A, R-404A, R-407C, R-410A, R-507A

NOMINAL HEAT REJECTION CAPACITY 175 MBH THROUGH 2280 MBH

VDCF 22 MODELSWATER, ETHYLENE GLYCOL, PROPYLENE GLYCOL

NOMINAL HEAT REJECTION CAPACITY65 MBH THROUGH 2890 MBH

ISSUE DATE: October 12, 2020

AIR-COOLED CONDENSER AND FLUID COOLER

INSTALLATION, OPERATION, MAINTENANCE Supersedes 195.29-NM1 (615) Form 195.29-NM1 (1020)

035 23478 100

Page 2: AIR-COOLED CONDENSER AND FLUID COOLER

This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain com-ponents or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, instal-lation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in

IMPORTANT!READ BEFORE PROCEEDING!

GENERAL SAFETY GUIDELINES

which it is situated, as well as severe personal injury or death to themselves and people at the site.

This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This in-dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question.

SAFETY SYMBOLS

The following symbols are used in this document to alert the reader to specific situations:

Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken.

Indicates a potentially hazardous situa-tion which will result in possible injuries or damage to equipment if proper care is not taken.

Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollu-tion if proper care is not taken or instruc-tions and are not followed.

Highlights additional information useful to the technician in completing the work being performed properly.

External wiring, unless specified as an optional connection in the manufacturer’s product line, is not to be connected inside the control cabinet. All wiring must be in accordance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer’s warranty and cause serious damage to property or personal injury.

JOHNSON CONTROLS2

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

Page 3: AIR-COOLED CONDENSER AND FLUID COOLER

CHANGEABILITY OF THIS DOCUMENTIn complying with Johnson Controls’ policy for con-tinuous product improvement, the information con-tained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office or accessing the John-son Controls Knowledge Exchange website at https://docs.johnsoncontrols.com/chillers/

It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rig-ging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller.

REVISION NOTESRevisions made to this document are indicated in the following table. These revisions are to technical information, and any other changes in spelling, grammar, or formatting are not included.

AFFECTED PAGES DESCRIPTION

3 Conditioned Based Maintenance program information added

CONDITIONED BASED MAINTENANCE Traditional chiller maintenance is based upon assumed and generalized conditions. In lieu of the traditional maintenance program, a Johnson Controls YORK Conditioned Based Maintenance (CBM) program can be substituted. This CBM service plan is built around the specific needs for the chiller, operating conditions, and annualized impact realized by the chiller. Your lo-cal Johnson Controls Branch can propose a customized

Planned Service Agreement that leverages real time and historical data, delivering performance reporting, corrective actions required and data enabled guidance for optimal operation and lifecycle assurance. The pro-gram will include fault detection diagnostics, operation code statistics, performance based algorithms and ad-vance rules based rationale delivered by the Johnson Controls Connected Equipment Portal.

JOHNSON CONTROLS 3

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

Page 4: AIR-COOLED CONDENSER AND FLUID COOLER

BASE MODELVDC = Vertical Up AirflowHDC = Horizontal Airflow

DUTY“–“ = CondenserF = Fluid Cooler

FANS IN LINE1 = 1 Fan Long (Single-Wide only)2 = 2 Fans Long3 = 3 Fans Long4 = 4 Fans Long5 = 5 Fans Long6 = 6 Fans Long

FINS PER INCH8 = 8 FPI (Condensers only)0 = 10 FPI (Standard)2 = 12 FPI (3 and 4 row Condensers only)4 = 14 FPI (3 and 4 row Condensers only)

COIL CONSTRUCTIONB = 5/8 in. OD Tube

(1- through 6-Fan, Single-Wide Fluid Coolers)(4-, 6-, 8-, 10- & 12-Fan, Double-Wide Fluid Coolers)

C = 1/2 in. OD Tube(5- and 6-Fan, Single-Wide Condensers)(10- and 12-Fan, Double-Wide Condensers)

D = 3/8 in. OD Tube(1- through 4-Fan, Single-Wide Condensers)(4-, 6- and 8-Fan, Double-Wide Condensers)

COIL ROWS DEEP3 = 3 Rows (Condenser and 1-Fan Fluid Cooler)4 = 4 Rows6 = 6 Rows8 = 8 Rows (Fluid Cooler only)

V D C - 2 2 4 D 6 0

MOTOR HORSEPOWER, FAN SPEED1 = 1.0 HP, 840 RPM (60 Hz) 6 = 2.0 HP, 1150 RPM (60 Hz)7 = 1.0 HP, 700 RPM (50 Hz) 9 = 2.0 HP, 950 RPM (50 Hz)

CONDENSER AND FLUID COOLER NOMENCLATURE

X XX P G

FANS WIDE1 – Single-Wide Model2 – Double-Wide Model

COIL COATX = Not CoatedE = ElectroFiny Coated

FIN MATERIALX = AluminumH = Holly Gold Coated Aluminum(3/8 in. OD tube only)

C = Copper (3/8 in. OD tube only)

COIL CIRCUITX = CondenserB = 4-Pass Fluid CoolerC = 6-Pass Fluid Cooler

HOUSINGP = Painted

MOTOR POWER AND TYPETEAO with ATO, Inverter Duty Rated:

A = 200/3/60 C = 230/3/60H = 380/400/415/3/50G = 460/3/60J = 575/3/60

3

NOTE:TEAO – Totally Enclosed Air OverATO – Automatic Thermal Overload (Integral)

JOHNSON CONTROLS

J

FAN CONTROL TYPEW = Without Fan CyclingS = Temperature ControlledK = Temperature Controlled (VDCF only)J = Pressure ControlledI = VSD-Ready, Variable Speed Control

Double-Wide Units, Individual Fan BanksU = Temperature ControlledL = Temperature Controlled (VDCF only)Z = Pressure Controlled

JOHNSON CONTROLS4

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

Page 5: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE OF CONTENTS

SECTION 1 - GENERAL INFORMATION..............................................................................................................9Mechanical Specifications ................................................................................................................................9

Overview .................................................................................................................................................9Legs ........................................................................................................................................................9Coil ..........................................................................................................................................................9Headers ...................................................................................................................................................9Housing ...................................................................................................................................................9Fan Guards .............................................................................................................................................9Fans ........................................................................................................................................................9Motors .....................................................................................................................................................9Motor Mounts ........................................................................................................................................10Basic Factory Wiring (Standard) ...........................................................................................................10Basic Motor Control (Standard) .............................................................................................................10Shipping ................................................................................................................................................10Lifting .....................................................................................................................................................10

SECTION 2 - PRODUCT DESCRIPTION ............................................................................................................ 11Accessories and Options ................................................................................................................................ 11

Special Coils .......................................................................................................................................... 11Sealtite Conduit™ ................................................................................................................................. 11Manifold Kit ............................................................................................................................................ 11Motor Wiring Options for Fan Control .................................................................................................... 11Fan Cycling Options .............................................................................................................................. 11

SECTION 3 - HANDLING AND STORAGE .........................................................................................................13Preface ...........................................................................................................................................................13Shipping Inspection ........................................................................................................................................13Coil Inspection ................................................................................................................................................13Safety Requirements ......................................................................................................................................13

SECTION 4 - INSTALLATION ..............................................................................................................................15Mounting .........................................................................................................................................................15Crane Rigging Instructions .............................................................................................................................15Location ..........................................................................................................................................................16

Indoor Applications ................................................................................................................................16Outdoor Applications .............................................................................................................................16

Wiring .............................................................................................................................................................17Corrosive Environment ...................................................................................................................................17Electric Power Supply ....................................................................................................................................17Refrigerant Piping - Condenser ......................................................................................................................17Refrigerant Line Sizing ...................................................................................................................................17

Chiller Below Condenser .......................................................................................................................18Condenser Below Chiller .......................................................................................................................18

Oil Traps .........................................................................................................................................................18Refrigerant Piping Reference .........................................................................................................................18

R-410A Copper Line Sizing ...................................................................................................................18YCRL Line Sizing Notes ........................................................................................................................18Suggested Field Piping Arrangements ..................................................................................................18

JOHNSON CONTROLS 5

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

Page 6: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE OF CONTENTS (CONT’D)

Recommended Refrigeration Line Sizes ........................................................................................................19Receiver Location (if Required for Refrigerant Storage) ................................................................................21Refrigerant Charge .........................................................................................................................................22

SECTION 5 - TECHNICAL DATA .........................................................................................................................23Dimensions - Condenser ................................................................................................................................23Dimensions - Fluid Cooler ..............................................................................................................................24VDC Charge Calculation ................................................................................................................................25Physical Data .................................................................................................................................................26Wiring Diagrams .............................................................................................................................................48

SECTION 6 - COMMISSIONING ..........................................................................................................................57Unit Identification ............................................................................................................................................57Start-Up ..........................................................................................................................................................57

SECTION 7 - UNIT OPERATION .........................................................................................................................59Standard Fan Cycling .....................................................................................................................................59VDC Pressure Setting Guidelines ..................................................................................................................60

Two-stage units (2-fan single-wide, 4-fan double-wide VDC) ..........................................................................................60Three-stage units (3-fan single-wide, 6-fan double-wide VDC) ..........................................................................................60Four-stage units (4-fan single-wide, 8-fan double-wide VDC) ..........................................................................................60

Low Ambient Operation ..................................................................................................................................60Low Ambient Control Options .........................................................................................................................60

Fan Cycling Control ...............................................................................................................................60A99 Temperature Sensor Description and Mounting ......................................................................................61

Description ............................................................................................................................................61Accessories ...........................................................................................................................................61Operation ...............................................................................................................................................61Temperature Sensor Mounting - VDC ...................................................................................................62Temperature Sensor Mounting - VDCF .................................................................................................62Mounting Using an Immersion Well - VDCF ..........................................................................................62Temperature Sensor Replacement Parts ..............................................................................................63

Pressure Transducers Mounting ....................................................................................................................63VSD Inverter Wiring ........................................................................................................................................64

VSD Inverter Installation Checklist ........................................................................................................64

SECTION 8 - MAINTENANCE .............................................................................................................................65General ...........................................................................................................................................................65Cleaning .........................................................................................................................................................65Recommended Spare Parts ...........................................................................................................................65

JOHNSON CONTROLS6

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

Page 7: AIR-COOLED CONDENSER AND FLUID COOLER

LIST OF FIGURES

FIGURE 1 - Unit Components ................................................................................................................................10FIGURE 2 - Rigging And Leg Mounting Drawing ....................................................................................................15FIGURE 3 - Condenser, Compressor And Receiver On Same Level .....................................................................18FIGURE 4 - Capacity Controlled Systems ..............................................................................................................19FIGURE 5 - Condenser Higher Than Compressor And Receiver ...........................................................................19FIGURE 6 - Two Or More Condensers Connected To One Compressor ..............................................................19FIGURE 7 - Typical Piping Arrangement - VDC .....................................................................................................20FIGURE 8 - Refrigerant Connections - VDC ..........................................................................................................21FIGURE 9 - Liquid Connections - VDCF ................................................................................................................22FIGURE 10 - Basic Factory Wiring - Standard, 1-6 Fans Long - VDC and VDCF .................................................48FIGURE 11 - Temp-Controlled Fan Cycling, 2-6 Fans Long - VDC ........................................................................49FIGURE 12 - Temp-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Individually - VDC ..........50FIGURE 13 - Temp-Controlled Fan Cycling, 2-6 Fans Long - VDCF .....................................................................51FIGURE 14 - Temp-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Individually - VDCF .......52FIGURE 15 - Pressure-Controlled Fan Cycling, 2-5 Fans Long - VDC ..................................................................53FIGURE 16 - Pressure-Controlled Fan Cycling, 6 Fans Long - VDC .....................................................................54FIGURE 17 - Pressure-Controlled Fan Cycling, 2-6 Fans Long, Double-Wide, Fans Wired Indivdualy - VDC ......55FIGURE 18 - VSD-Controlled Fans, 2-6 Fans Long, Double-Wide Fans Wired in Pairs - VDC and VDCF ...........56FIGURE 19 - ID Plate Information, VDC - Monterrey, Mexico ................................................................................57FIGURE 20 - ID Plate Information, VDCF - Monterrey, Mexico ..............................................................................57FIGURE 21 - ID Plate Information, VDC - San Antonio, TX ...................................................................................57FIGURE 22 - ID Plate Information, VDCF - San Antonio, TX .................................................................................57FIGURE 23 - A99B Temperature Sensors ..............................................................................................................61FIGURE 24 - A99B Sensor Accessories .................................................................................................................61FIGURE 25 - A99B Sensor Dimensions .................................................................................................................61FIGURE 26 - Installing The Immersion Well ...........................................................................................................62FIGURE 27 - Insert Sensor, Spring And Bushing ...................................................................................................62FIGURE 28 - P499 Electronic Pressure Transducers .............................................................................................63FIGURE 29 - Pressure Transducer Wiring .............................................................................................................63

JOHNSON CONTROLS 7

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

Page 8: AIR-COOLED CONDENSER AND FLUID COOLER

LIST OF TABLES

TABLE 1 - Receiver And Heater Data ....................................................................................................................21TABLE 2 - Unit Dimensions - Condensers .............................................................................................................23TABLE 3 - Unit Dimensions - Fluid Coolers ...........................................................................................................24TABLE 4 - VDC Charge Calculation .......................................................................................................................25TABLE 5 - VDC Condenser 2.0 HP Rating And Physical Data ..............................................................................26TABLE 6 - VDC Condenser 1.0 HP Rating And Physical Data ..............................................................................31TABLE 7 - VDCF Fluid Cooler 2.0 HP Rating And Physical Data ..........................................................................36TABLE 8 - VDCF Fluid Cooler 1.0 HP Rating And Physical Data ..........................................................................41TABLE 9 - Lug Data ...............................................................................................................................................46TABLE 10 - Minimum Ambient Temperatures For Fan Cycling Control .................................................................59TABLE 11 - Temperature Settings For Fan Cycling ................................................................................................59TABLE 12 - Resistance vs. Temperature ...............................................................................................................62TABLE 13 - Replacement Temperature Sensor Product Code Numbers ...............................................................63TABLE 14 - Pressure vs. Voltage ...........................................................................................................................64TABLE 15 - VSD Inverter Connections ..................................................................................................................64

JOHNSON CONTROLS8

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

Page 9: AIR-COOLED CONDENSER AND FLUID COOLER

MECHANICAL SPECIFICATIONS

OverviewYORK Air-Cooled Condensers, Models VDC-113D10 through VDC-266C60, are available in 66 standard model sizes for air conditioning and refrigeration ap-plications, and may be used with any type of compres-sor for halocarbon refrigerants.

YORK Air-Cooled Fluid Coolers, Models VD-CF113B10 through VDCF268B60, are available in 22 standard model sizes for commercial and industrial fluid cooling and may be used with water or glycol. Contact Johnson Controls for special applications, for example, winter-weather chiller economizer duty or cooling industrial fluids.

Air-cooled condensers’ and fluid coolers’ air-sides op-erate dry (requiring a minimum of maintenance) and do not require pump and water piping installation ex-cept for fluid-side fluid cooling. Vertical airflow units are standard design for low silhouette applications.

Legs Made from heavy-gauge galvanized steel with foot pads and mounting holes on the bottom of each leg.

CoilSeamless copper tubes are expanded into full-col-lar aluminum fins. Fins have a corrugated surface to enhance heat transfer. Fin edges are rippled to work harden and stiffen material for resistance to mechani-cal damage. Return bends and headers are brazed with highly ductile silver-bearing copper alloy. Coil cas-ings and tubesheets are manufactured from galvanized steel. The tubesheets include aluminum inserts to pre-vent wear at the juncture of the tubes and tubesheets.

Prior to shipment, coils are strength and leak tested at design pressure, dehydrated, evacuated, pressurized with dry air or nitrogen, and sealed for shipment.

Condenser coils up to four fan lengths use 3/8 in. OD internally enhanced microfin tubes for optimum per-formance. Five- and six-fan length coils use 1/2 in. OD tubes. Fluid coolers use 5/8 in. OD tubes for low pres-sure drop.

For R-22, R-134a, R-407C, R-404A, and R-507A con-densing, the 3/8 in. and 1/2 in. OD tube coils have a 420 psig (29 barg) design pressure at 250°F (121°C)

for up to a 140°F (60°C) condensing temperature. For R-410A, the 3/8 in. OD tube coils have a 650 psig (44.8 barg) design pressure at 250°F (121°C) for up to a 140°F (60°C) condensing temperature.

For fluid coolers the 5/8 in. OD tube coils have a 250 psig (17.25 barg) design pressure for up to 145°F (62.8°C) entering fluid temperature.

HeadersHeavy-wall copper tube headers are designed for low pressure loss and proper refrigerant distribution. Dou-ble-wide units feature completely separate headers for each system circuit so there is no danger of refrigerant leakage between circuits. Inlet and outlet connections are provided. Integral subcooling is available for con-densers.

HousingThe unit structure is comprised of heavy-gauge galva-nized steel panels coated with baked-on champagne-colored powder paint, which, when subjected to ASTM B117 1000 hour salt spray testing, yields a minimum ASTM 1654 rating of "6". These panels are assembled with high-tensile strength fasteners. Fan panels have long, smooth-radius outlet orifices to ensure high en-ergy efficiency and low noise level. Each fan section is fully compartmentalized to prevent fan windmilling.

Fan GuardsHeavy-gauge OSHA-accepted fan guard design uses corrosion resistant, coated-steel wire.

FansHigh-efficiency, high-strength airfoil-profile blade fans are used for low noise and energy-efficient per-formance.

MotorsTotally enclosed air-over (TEAO) motors have built-in thermal overload (ATO) protection and are inverter duty ready. They feature ball bearings that are double-sealed and permanently lubricated. Standard motor is 2.0 hp, 3-phase, 60 Hz, 200, 230, 460, or 575 volts. Optional 1.0 hp, 3-phase, 60 Hz, 200, 230, 460, or 575 volts and 2.0 or 1.0 hp, 3-phase, 50 Hz, 380, 400, or 415 volts are also available.

SECTION 1 - GENERAL INFORMATION

JOHNSON CONTROLS 9

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

1

Page 10: AIR-COOLED CONDENSER AND FLUID COOLER

Motor MountsHeavy-gauge galvanized steel channels are used to mount motors.

Basic Factory Wiring (Standard)Motors are wired to contactors located in a UL-listed NEMA 4, weather-resistant enclosure, which includes a non-fused disconnect switch for single point power wiring, motor fuses, contactors, and an integral 115 volt control transformer. Enclosure is painted to match unit housing, and it ships mounted.

FIGURE 1 - UNIT COMPONENTS

LD16237a

FAN DECKCONTROL PANEL

LOCKING HANDLE

UNIT COIL CONNECTIONS1 UNIT LEG

COIL HEADERS

Note1: Fluid cooler inlet is horizontal

Basic Motor Control (Standard)Basic motor control does not support fan cycling. To include fan cycling, select an optional motor control.

ShippingAll units are shrink-wrapped with heavy sheet plastic wraps to protect the unit from road debris and tempo-rary storage.

LiftingUnits must be crane lifted off shipping truck and to fi-nal location.

JOHNSON CONTROLS10

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 1 - GENERAL INFORMATION

Page 11: AIR-COOLED CONDENSER AND FLUID COOLER

ACCESSORIES AND OPTIONS

Special CoilsWhile standard aluminum fins are compatible with most environments, when a unit is subjected to an es-pecially corrosive atmosphere, such as coastal air with a high concentration of salt, special fin treatment may be required. The following options are available for these applications.

Holly Gold Coat – This gold-colored, corrosion-re-sistant, polyester-polymer-coated aluminum fin passes 1000 hours of ASTM B117 salt spray testing. Available only with 3/8 in. OD tube coils.

ElectroFin™ Coat – ElectroFin™ Coat is applied to the completed coil, protecting the tubes, fins, headers, and galvanized steel casing with a coating that passes 5000 hours of ASTM B117 salt spray testing. Does not include shipped loose manifold kit.

Copper-Finned Coils – Copper-finned coils are avail-able for applications where the environment may cause galvanic corrosion of aluminum fins. Available only with 3/8 in. OD tube coils.

Sealtite Conduit™All fan motor wiring enclosed in sealed conduit.

Manifold KitTies dual inlet and outlet connections together on dou-ble-wide units for a single field connection (shipped loose for field installation). Typically used on double-wide condensers for use with a single chiller circuits or double-wide fluid coolers. Not available from factory on units with 4 1/8 in. OD connections.

Motor Wiring Options for Fan ControlMotors are wired to contactors located in a UL-listed NEMA 4, weather-resistant enclosure, which includes a non-fused disconnect switch, motor fuses, contac-tors, and an integral 115 volt control transformer. See Table 10 on page 59 and Table 11 on page 59, for fan-cycling control settings or contact Application Engineering for support. Enclosure ships mounted. If there is a concern about noise due to fan cycling, it is recommended that Head Pressure Control (Variable Speed Drive (VSD) Ready) be used.

Double-Wide Unit Fan Cycling Fan Cycling Options for Double-Wide Units are available with fans cycling in pairs or, for temperature-controlled and pressure-controlled fan cycling, with individual fan-bank fan cycling so the VDC can serve individual chiller cir-cuits.

Fan Cycling Options

Head Pressure Control by TemperatureMotors are wired for temperature-controlled fan cy-cling.

A temperature sensor, supplied with a clip for mount-ing in condenser’s air stream or a bulb well for installa-tion in fluid cooler’s leaving fluid piping, must be field installed. Fans next to the header are always running when unit is activated by run signal. Receivers are not required.

For fluid coolers, the lowest allowable leaving fluid temperature is -13°F (-25.0°C) which can be safely done with 50% Ethylene Glycol or 50% Propylene Glycol and a minimum ambient of -20°F (-28.9°C).

When a glycol heat transfer fluid is used in the YORK VDCF fluid cooler ensure that the fluid maintains the correct design glycol concentration. It is imperative to maintain a high enough concentration to prevent the fluid cooler from experiencing a solution freeze that can permanently damage the coil. Johnson Controls recommends that the fluid be checked to verify that the correct concentration is maintained at the beginning of seasonal cold weather or any time the system is opened or a leak is discovered.

It is also important that the unit is rated for the concen-tration of glycol that will be used. Higher concentra-tions than required will reduce the unit's heat transfer capacity and increase fluid pump horsepower.

The concentration required for the given application will depend on the particular glycol-based heat transfer fluid used and the lowest expected temperature. Differ-ent fluids have different specific gravity, specific heat, viscosity and thermal conductivity at different percent-ages and temperatures. Typically the system should be protected to 15 degrees below the lowest anticipated temperature. The fluid manufacturer's recommenda-

SECTION 2 - PRODUCT DESCRIPTION

JOHNSON CONTROLS 11

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

2

Page 12: AIR-COOLED CONDENSER AND FLUID COOLER

tions should be closely followed for your particular ap-plication.

The A350 controller and stage module are supplied with this option to control the fans.

Head Pressure Control by PressureRequired when selecting a VDC for use as a remote condenser for a YCRL chiller. Motors are wired for pressure-controlled fan cycling. Included pressure transducer(s) must be field installed. Fans next to the header are always running when unit is activated by run signal. Receivers are not required.

The P470 controller and stage module are supplied with this option to control the fans.

Head Pressure Control (VSD Ready)Motors are wired for variable speed fan control. VSD bypass control circuit is included, but inverter drive (VSD) is not included. Temperature or pressure sensor(s) for control must be field provided and in-stalled, if desired.

Field-installed inverter drives (VSDs) shall be mounted on or in close proximity to the VDC unit. The inverter drive shall be equipped with load reactors for installa-tions that require more than 25 feet of wire between the inverter and the VDC unit or whenever distortion is a concern to prevent voltage spikes that can damage the fan motors and void the VDC motor warranty. Motor damage caused by an improperly installed VSD is not warranted.

The VSD’s switching frequency shall not exceed 4 KHz.

When this option is selected, the option Sealtite™ Conduit on page 11 shall also be selected to ensure that the motor wire is shielded from voltage spikes. Grounding of conduit and all wiring is of extreme im-portance. See Figure 18 on page 56 and VSD Invert-er Wiring on page 64.

JOHNSON CONTROLS12

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 2 - PRODUCT DESCRIPTION

Page 13: AIR-COOLED CONDENSER AND FLUID COOLER

SECTION 3 - HANDLING AND STORAGE

PREFACEYour Johnson Controls Air-Cooled Condenser or Fluid Cooler incorporates the finest in engineering design, materials, and corrosion protection to provide a rugged long lasting unit. Proper installation, care and mainte-nance of your unit are essential to good performance and long life. Before rigging or beginning work on the unit, Johnson Controls recommends that experienced refrigeration contractors, operators, and maintenance technicians are formally trained on the Johnson Con-trols Air-Cooled Condenser features.

Reading this manual is a minimum re-quirement.

Before installing your unit, we suggest that you read the following instructions carefully and keep them handy for ready reference.

After installation, the unit must be properly connected to appropriately designed and installed refrigeration systems. The engineering plans, piping layouts, etc., for the Johnson Controls Air-Cooled Condenser or Fluid Cooler and associated system components must be detailed in accordance with local/governing codes and the best industry standards and practices such as those outlined in current industry literature. Reference the DX Piping Guide, Form 50.40-ES2 and the 2010 ASHRAE Refrigeration Handbook, Chapter 1, espe-cially noting the Safety Requirements section for high pressure refrigerants on page 1.35.

SHIPPING INSPECTIONCarefully examine the unit and notify the transporta-tion agent of any missing parts or damage. It is advis-able to inspect the unit as soon as received and to make a record of the serial number, and motor data.

The unit shipment should be checked on arrival to ensure that all major pieces, boxes and crates are re-ceived. The unit should be checked on the trailer or rail car before unloading, for any visible signs of dam-age. Any damage or signs of possible damage should be reported to the transportation company immediately for their inspection. Contact the Johnson Controls Re-gional or District office in order for a Johnson Controls Representative to assist in filing damage claims.

Johnson Controls will not be responsible for any damage in shipment or at job site, or loss of parts, if these shipping inspection instructions are not followed. (Refer to BOS Document Submitting and Processing Claims for materials lost or damaged in transit. 13-91.202-BEHQ)

Once received at the job site, all containers should be opened and contents checked against the packing list. Any material shortage should be reported to Johnson Controls immediately. (Refer to Shipping Damage Claims, Form 50.15-NM.)

COIL INSPECTIONThe refrigerant coil has a low pressure charge from the factory. Check the coil to see that the holding charge is intact. To do this, remove the 1/4 inch cap and briefly depress the Schrader valve located on the liquid or suc-tion header of each circuit to verify pressure. The charge must be maintained until refrigerant or fluid piping is connected to the unit. A coil that does not have a charge may have been damaged during transit. If the charge is not present when the unit is received, the coil must be pressure tested to 100 psig with dry nitrogen gas to confirm that it is leak free. Contact Johnson Con-trols before installing any air-cooled condenser or fluid cooler unit that has lost the factory charge. When com-municating with the factory, refer to the model and se-rial numbers which are located on the unit nameplate.

SAFETY REQUIREMENTSOnly experienced, qualified personnel should install, operate and maintain re-frigeration equipment.

Perform frequent visual inspections and continuously monitor a condenser to prevent the escape of refrig-erant. Use electronic refrigerant detectors in the unit proximity for continuous monitoring and detection of the presence of refrigerant in the atmosphere.

JOHNSON CONTROLS 13

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

3

Page 14: AIR-COOLED CONDENSER AND FLUID COOLER

THIS PAGE INTENTIONALLY LEFT BLANK.

JOHNSON CONTROLS14

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 3 - HANDLING AND STORAGE

Page 15: AIR-COOLED CONDENSER AND FLUID COOLER

SECTION 4 - INSTALLATION

MOUNTINGOnce the unit is placed in the desired location, secure legs to floor or steel work with 3/4" diameter bolts to prevent movement. The top should be level and the unit should be supported along its entire length (i.e., every leg should be secured). Use of vibration pads or isola-tors is recommended. The supporting structure must be strong enough to support the weight of the unit.

CRANE RIGGING INSTRUCTIONSAll units are designed for removal from the truck by crane only. Use lifting brackets shown on Figure 2 on page 15. Be careful to lift units evenly and balanced to avoid undue stress on the equipment.

Refer to customer submittal drawings for dimensional data and weight before installing units.

FIGURE 2 - RIGGING AND LEG MOUNTING DRAWINGLD14082

JOHNSON CONTROLS 15

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

4

Page 16: AIR-COOLED CONDENSER AND FLUID COOLER

LOCATIONJohnson Controls remote Air-Cooled Condensers and Fluid Coolers are designed to meet practically any requirement for mounting either indoors or outdoors. Care should be taken not to mount the unit where it is continually exposed to loose dirt or foreign matter which might clog the coil surface. The unit must be mounted in a level position, both front-to-back and side-to-side.

An important consideration when locating the con-denser is providing for adequate airflow to and from the unit. A minimum distance of four feet is recom-mended on all sides of the unit, with eight feet mini-mum recommended between adjacent air-cooled con-densers. The capability and performance of the unit is dependent upon the unimpeded flow of ambient air over the extended surface for removal of heat from the refrigerant discharge gas within the coil.

Solar effect has negligible bearing on the performance of the air-cooled condenser.

Indoor ApplicationsWhen the condenser or fluid cooler is mounted indoors, the air leaving the unit must be discharged to the out-doors to prevent recirculation of heated air through the unit. Provision must also be made for sufficient fresh air intake into the area where the unit is located.

When a discharge duct is used with a propeller fan, the duct's added static pressure leaves the unit subject to diminished heat transfer capacity because of a reduc-tion in airflow. The unit's rated capacity can be pre-served by designing the duct for negligible pressure loss, by the addition of an external fan to overcome the duct's static pressure, or by a combination of the two.All fan guards should be removed and access provid-ed in the duct to allow for servicing the fan and drive assemblies. A flexible duct connection will minimize noise transmission.

If louvers are to be installed on the duct outlet, the free open area should equal the duct cross sectional area.

For ducts of greater or lesser cross sectional area, spe-cial fans and motors can be furnished by Johnson Con-trols. Consult the factory for specific recommendations and pricing.

If inlet ducts are not provided, unrestricted flow of fresh air to the unit must be ensured. Care must be tak-en to ensure that the fresh air supplied is at the ambient air temperature. If air is taken from an area where the heat exceeds the ambient air temperature, the unit’s ca-pacity will be reduced. The arrangement must ensure that heated condenser discharge air is not re-circulated to the air intake of the unit.

Outdoor ApplicationsYour Johnson Controls Air-Cooled Condenser or Fluid Cooler has the fan motor(s) located inside the casing and requires no special provisions for weather protec-tion.

Multiple units should be installed so that the discharge of one unit is not directed into the intake of another unit.

A vertical airflow unit may be located without regard to prevailing wind. These units minimize fan noise and allow greater flexibility of location in relation to sur-rounding structures.

When installing condensers and fluid coolers, a loca-tion should be chosen so that at least three sides of the unit have unrestricted airflow. The fan should have free flow unrestricted by any overhanging structures.

The unit may be placed close to a building on one side with a minimum clearance of eight feet. In the case of multiple unit installations, units may be placed end-to-end without penalty and side-by-side with a minimum of four feet apart for single-wide and eight feet apart for double-wide units. Where located on a roof, it is best to mount the unit with the longer side parallel to the roof edge to minimize the potential for drawing heated air from the roof surfaces.

The rugged mounting legs of the Johnson Controls Air-Cooled Condensers and Fluid Coolers are designed to provide sufficient height for any operating condition. Mounting pads should be located for ground level in-stallation. When the unit will be located where an ex-cessive buildup of superheated air is expected, the unit should be mounted in a structural open frame.

JOHNSON CONTROLS16

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 4 - INSTALLATION

Page 17: AIR-COOLED CONDENSER AND FLUID COOLER

WIRINGA disconnect, as required by local codes, should be provided for each motor circuit. The motors have in-ternal thermal overload protection; therefore, multiple motors may be started from each circuit. See SECTION 5 - TECHNICAL DATA for wiring diagrams.

With factory wired motors, verify that the supply volt-age is the same as the motor nameplate voltage.

For field wiring, check the wiring terminals inside the motor to ensure that they are wired for proper power supply voltage. The wiring diagram is attached to the motor housing. Also, confirm fan rotation direction as indicated by the fan blades.

CORROSIVE ENVIRONMENTThese units must not be installed in environments that may be corrosive to the materials of construction. This could result in reduced performance, condenser fin de-terioration and coil leaks not covered by warranty.

ELECTRIC POWER SUPPLYCheck the electrical characteristics on the unit name-plate to make sure the power supply is the same. Only qualified electricians should install the power supply. All work should be done in conformance with prevail-ing codes and regulations.

Do not remove safety equipment or warn-ing labels from equipment. Removal could result in serious injury or death.

Disconnect the power supply to the unit before performing any service or mainte-nance. The disconnect should be locked in the “OFF” position following proper lockout tagging procedures.

REFRIGERANT PIPING - CONDENSERSpecial care must be taken to ensure adequate sizing of refrigerant piping for Johnson Controls Air-Cooled Condensers. Applicable standards should be consulted in this regard. The copper tubing should be de-oxi-dized and dehydrated Type L refrigeration tubing with wrought copper fittings employed. Keep all piping clean, and clean all pipe connections with a wire brush or the equivalent. Braze with 5% silver braze material with the recommended flux. Use a wet rag around the next solder joint when brazing.

Piping systems with halocarbon refrigerants must be properly evacuated to remove noncondensables and moisture prior to the introduction of refrigerant. A vac-uum of 750 microns is the minimum requirement to remove moisture.

The liquid drain line should not be exposed to high temperatures, and therefore should be insulated if it passes through an environment where temperatures exceed 120˚F. All refrigerant piping must be well sup-ported and protected from vibration. The condenser piping connections should not be left open to the atmo-sphere for any longer than required for solder connec-tions to be made.

Install a shut-off valve at the receiver inlet (if used). Install a purge valve or fitting at the highest point in the discharge gas piping.

In order to prevent condensed liquid refrigerant from causing damage to the compressor(s), install a trap in the vertical discharge piping at the compressor(s). The height of the trap should be 6 inches for every 10 feet of vertical discharge piping. If the height of the vertical piping makes this impractical, the trap may be replaced by a check valve.

When installing refrigeration piping, make certain that it is well supported. Make sure the vibrations from the compressor, condenser and piping are not transmitted to the building. The use of a discharge muffler may be necessary to prevent noises due to refrigerant pulsa-tions; particularly with high speed compressors.

REFRIGERANT LINE SIZINGRefrigerant piping systems must be designed to pro-vide practical line sizes without excessive pressure drops to prevent compressor oil from being "trapped" in the refrigerant piping, and to ensure proper flow of liquid refrigerant to the thermal expansion valve. Be sure to review DX Piping Guide, Form 50.40-ES2. Considerations should be given to:

1. Discharge line pressure drop due to refrigerant flow.

2. Discharge line refrigerant velocity for oil return.

3. Liquid line pressure drop due to refrigerant flow.

4. Liquid line pressure drop (or gain) due to vertical rise of the liquid line.

5. Pressure rating of brazed Type L Copper tubing with high pressure refrigerants.

JOHNSON CONTROLS 17

SECTION 4 - INSTALLATIONFORM 195.29-NM1 ISSUE DATE: 10/12/2020

4

Page 18: AIR-COOLED CONDENSER AND FLUID COOLER

To ensure a solid column of liquid refrigerant to the ex-pansion valve, the total liquid line pressure drop should never exceed 40 PSI (276 kPa). Refrigerant vapor in the liquid line will measurably reduce valve capacity and poor system performance can be expected.

To allow adequate oil return to the compressor, dis-charge risers should be sized for a minimum of 1000 FPM (5.08 m/s) while the system is operating at mini-mum capacity to ensure oil return up the suction riser.

Chiller Below CondenserOn a system where the chiller is located below the condenser, the discharge line must be sized for both pressure drop and oil return. In some cases a double discharge riser must be installed to ensure reliable oil return at reduced loads.

Condenser Below ChillerWhen the condenser is located below the chiller, the liquid line must be designed for both friction loss and static head loss due to the vertical rise. The value of static head loss of 5 PSI/ft. (3.4 kPa/30 cm) must be added to the friction loss pressure drop in addition to all pressure drops due to driers, valves, etc.

OIL TRAPSAll horizontal discharge lines should be pitched at least 1/4" per foot (2 cm/m) in the direction of the refriger-ant flow to aid in the return of oil to the chiller. All discharge lines with a vertical rise exceeding 3 feet (.91 meters) should have a "P" trap at the bottom and top of the riser. Discharge lines with a vertical rise exceeding 25 feet (7.6 meters) should be trapped every 15 feet (4.6 meters).

REFRIGERANT PIPING REFERENCE

R-410A Copper Line SizingWhen selecting pipe diameter and material for remote condenser piping R-410A systems, it is recommended that ASTM B280 material is used.

YCRL Line Sizing NotesIf the VDC is used in conjunction with a YCRL chiller with a design pressure of 650 psig, a mechanical high pressure cutout to shut the unit off at 585 psig, and (the unit) is rated at 650 psig, the maximum discharge pipe diameter that can be used is 1-5/8".

For more details, refer to the 2014 ASHRAE Refrigera-tion Handbook, Chapter 1, and note that brazing re-duces the strength of the heated pipe material to that of annealed material.

Suggested Field Piping ArrangementsThis section shows four field piping arrangements for remote air-cooled condensers in field erected systems using receivers.

Receivers are shown in Figures 3 through 6 for convenience. Many applications do not require receivers when the volume of the refrigerant charge does not ex-ceed 80% of the condenser coil internal volume and can be stored entirely in the condenser coil.

Discharge LineLoop

Trap

Compressor Liquid Line Receiver

Condenser

FIGURE 3 - CONDENSER, COMPRESSOR AND RECEIVER ON SAME LEVEL

LD16218

Figure 3 on page 18 covers a common application where the air- cooled condenser is located on the same elevation as the compressor and receiver. The discharge line in this case is not too critical. The main problem usually associated with this arrangement is insufficient vertical height to allow free draining of the liquid re-frigerant from the condenser coil to the receiver.

To prevent gas binding in the receiver and liquid build-up in the condenser coil, locate the receiver as far be-low the condenser outlet as possible. Liquid lines must be free of any loops or traps and horizontal runs must be pitched toward the receiver.

JOHNSON CONTROLS18

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 4 - INSTALLATION

Page 19: AIR-COOLED CONDENSER AND FLUID COOLER

LD16219

Condenser

Discharge Line A

Trap

Compressor

Liquid Line

Receiver

Discharge Line B

Loop

FIGURE 4 - CAPACITY CONTROLLED SYSTEMS

Figure 4 on page 19 shows the recommended con-figuration for applications of capacity controlled sys-tems. Discharge line A is sized for the maximum load conditions. Discharge line B is sized for the minimum loading conditions at sufficient velocity to carry the oil to the condenser at the reduced capacity.

LD16220

Condenser

Discharge Line

Trap

Compressor

Liquid Line

Receiver

FIGURE 5 - CONDENSER HIGHER THAN COM-PRESSOR AND RECEIVER

Figure 5 on page 19 illustrates a typical piping arrange-ment where the remote air-cooled condenser is located on a higher elevation than the compressor or receiver. In this arrangement, the design of the discharge line is very criti-cal and should be modified to the arrangement in diagram Figure 4, unless a very constant and steady load is main-tained.

LD16221

CondenserCondenser

Discharge Line

Trap

Compressor

Liquid Line

Receiver

Loop

FIGURE 6 - TWO OR MORE CONDENSERS CON-NECTED TO ONE COMPRESSOR

Figure 6 on page 19 illustrates another common ap-plication where two or more separate air-cooled con-densers are interconnected to a single compressor. In this case, each condenser must have both equal ca-pacity and equal pressure drop. The piping must also be arranged to ensure equal lengths to and from each condenser. If unlike piping and/or unequal condensers are used, the unequal pressure drop will cause liquid to build up in one of the condensers, reducing its effective capacity.

RECOMMENDED REFRIGERATION LINE SIZESThe recommended refrigerant line sizes (discharge line-compressor to condenser and liquid line-condens-er to receiver) can be determined from the DX Piping Guide, Form 50.40-ES2, while exercising care with regards to internal working pressure of copper piping with brazed joints for use with high-pressure refriger-ants.

JOHNSON CONTROLS 19

SECTION 4 - INSTALLATIONFORM 195.29-NM1 ISSUE DATE: 10/12/2020

4

Page 20: AIR-COOLED CONDENSER AND FLUID COOLER

FIGURE 7 - TYPICAL PIPING ARRANGEMENT - VDC

LD14090A

7

2

6

4

15

3

8

LEGEND1. YORK YCRL Chiller2. YORK Solution Air Handler3. Subcooler Liquid Plumbing4. Chilled Liquid Pump5. Discharge Line Muffler6. Fused Disconnect Switch7. Starter8. Purge Valve

JOHNSON CONTROLS20

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 4 - INSTALLATION

Page 21: AIR-COOLED CONDENSER AND FLUID COOLER

RECEIVER LOCATION (IF REQUIRED FOR REFRIGERANT STORAGE)It is preferable that the receiver be located in an ambient temperature above 65°F. When located in a lower ambi-ent temperature, provision should be made to heat and insulate the receiver, especially if long off-cycles are en-countered. Table 1 on page 21 shows suggested receiv-er and heater sizes. The receiver should be insulated with 1-inch thick Armaflex insulation or equivalent. Before applying the receiver insulation, the heater cable should be wrapped around the receiver throughout the length for even heat distribution. The heater must be field connected to the proper voltage and controlled so that it is energized on system shutdown.

TABLE 1 - RECEIVER AND HEATER DATA

RECEIVER HEATER WATTS RECEIVER HEATER

WATTS8" x 4' 210 14" x 8' 4208" x 6' 210 14" x 10' 4208" x 8' 210 16" x 6' 420

10" x 6' 210 16" x 8' 42010" x 8' 280 16" x 10' 560

10" x 10' 420 18" x 8' 56012" x 6' 280 18" x 10' 56012" x 8' 420 18" x 12' 700

12" x 10' 420 20" x 8' 56014" x 6' 280 20" x 10' 700

Notes: 1. Two Standard YORK single-wide condensers with single-circuit coils, one condenser used with each compressor.2. One Standard YORK double-wide condenser with one dual-circuit coil, one circuit used with each compressor. Available with individual

fan-bank fan cycling.3. Two Standard YORK double-wide condensers with dual-circuit coils, one condenser used with each compressor, shown with optional

manifolds (shipped loose).

FIGURE 8 - REFRIGERANT CONNECTIONS - VDC

LD16222

JOHNSON CONTROLS 21

SECTION 4 - INSTALLATIONFORM 195.29-NM1 ISSUE DATE: 10/12/2020

4

Page 22: AIR-COOLED CONDENSER AND FLUID COOLER

FIGURE 9 - LIQUID CONNECTIONS - VDCF

������������������������������

�����������

������������

�����������

������������

������������������� ������� ���������������������������������������

Notes:1. Standard YORK fluid cooler with one single-circuit coil.2. Standard YORK fluid cooler with two single-circuit coils, shown with optional manifolds (shipped loose), not available from factory on units

with 4 1/8 in. OD connections.

LD16223

REFRIGERANT CHARGEThe chiller is charged and shipped with a dry nitro-gen holding charge. The chiller and the remote piping condenser must be evacuated and the operating charge for the chiller, remote condenser and refrigerant pip-ing must be weighed in after all refrigerant piping is installed, leak checked, and evacuated. A minimum of 70% of the calculated complete system charge must be installed before attempting to operate a system. Final adjustment of refrigerant charge should be verified by subcooling values.

Use of refrigerant other than that stamped on the nameplates may cause damage to the refrigeration coils. Coil must not be subject to higher pressure than design pressure stamped on the nameplate.

The total system refrigerant charge is the sum of the operating charges of the evaporator, condenser and re-frigerant piping. The Refrigerant charge for discharge lines and liquid lines may be found in Tables 15 and 16 respectively on pages 28 and 29 of the DX Piping Guide, Form 50.40-ES2. The pump down capacity of the condenser should be equal to or greater than the total refrigerant charge required. Pumpdown capacity is normally the sum of the evaporator, condenser and refrigerant piping charges multiplied by 1.25.

JOHNSON CONTROLS22

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 4 - INSTALLATION

Page 23: AIR-COOLED CONDENSER AND FLUID COOLER

SECTION 5 - TECHNICAL DATA

A

W

C D

9.00

E

INLET1 REQUIRED

OUTLET1 REQUIRED

Electrical Enclosure

L

A

W 9.00

HEADER END

21.75

INLET2 REQUIRED

OUTLET2 REQUIRED

DOUBLE WIDE

SINGLE WIDE

G Holes for3

4" Bolts

H

4 x 4Mounting Pad

B9.50

SINGLE WIDEDOUBLE WIDE

L

6.000 2.000 TYP

REMOVEABLESHIPPING SKID

SHIPS ON SIDELEGS SHIP LOOSE

42.0042.00

AIRFLOWAIRFLOW

TABLE 2 - UNIT DIMENSIONS - CONDENSERSMODEL

NUMBERDIMENSIONS

L W H (1) A B C D E GVDC-11 60.5 46.4 53.8 38.3 50.5 --- --- --- 4VDC-12 113.5 46.4 53.8 38.3 103.5 --- --- --- 4VDC-13 166.5 46.4 53.8 38.3 156.5 53.0 103.5 --- 6VDC-14 219.5 46.4 53.8 38.3 209.5 106.0 103.5 --- 6VDC-15 272.5 46.9 53.8 38.3 262.5 106.0 103.5 53.0 8VDC-16 325.5 46.9 53.8 38.3 315.5 106.0 103.5 106.0 8VDC-22 113.5 88.6 53.8 80.5 103.5 --- --- --- 4VDC-23 166.5 88.6 53.8 80.5 156.5 53.0 103.5 --- 6VDC-24 219.5 88.6 53.8 80.5 209.5 106.0 103.5 --- 6VDC-25 272.5 89.6 53.8 81.5 262.5 106.0 103.5 53.0 8VDC-26 325.5 89.6 53.8 81.5 315.5 106.0 103.5 106.0 8

(1) Add 5.0 to the height on VDC-156, -166, -256, and -266.Note: Dimensions are in inches and for reference only.

DIMENSIONS - CONDENSER

NOTE: Johnson Controls recommends the minimum distance between the condenser and walls be 8 ft. The minimum distance between adjacent condenser should be 4 ft for single-wide units and 8 ft for double-wide units. This will prevent condenser air recirculation and faulty operation.

LD17329

JOHNSON CONTROLS 23

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 24: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 3 - UNIT DIMENSIONS - FLUID COOLERSMODEL

NUMBERDIMENSIONS

L W H (1) A B C D E GVDCF11 60.5 46.9 53.8 38.3 50.5 --- --- --- 4VDCF12 113.5 46.9 53.8 38.3 103.5 --- --- --- 4VDCF13 166.5 46.9 53.8 38.3 156.5 53.0 103.5 --- 6VDCF14 219.5 46.9 53.8 38.3 209.5 106.0 103.5 --- 6VDCF15 272.5 46.9 53.8 38.3 262.5 106.0 103.5 53.0 8VDCF16 325.5 46.9 53.8 38.3 315.5 106.0 103.5 106.0 8VDCF22 113.5 89.6 53.8 81.5 103.5 --- --- --- 4VDCF23 166.5 89.6 53.8 81.5 156.5 53.0 103.5 --- 6VDCF24 219.5 89.6 53.8 81.5 209.5 106.0 103.5 --- 6VDCF25 272.5 89.6 53.8 81.5 262.5 106.0 103.5 53.0 8VDCF26 325.5 89.6 53.8 81.5 315.5 106.0 103.5 106.0 8

(1) Add 5.0 to the height on fluid cooling units with 6 and 8 row coilsNote: Dimensions are in inches and for reference only and expressed in inches.

A

W

C D

9.00

E

INLET1 REQUIRED

OUTLET1 REQUIRED

Electrical Enclosure

L

A

W 9.00

HEADER END

21.75

INLET2 REQUIRED

OUTLET2 REQUIRED

DOUBLE WIDE

SINGLE WIDE

G Holes for3

4" Bolts

H

4 x 4Mounting Pad

B9.50

SINGLE WIDEDOUBLE WIDE

L

6.000 2.000 TYP

REMOVEABLESHIPPING SKID

SHIPS ON SIDELEGS SHIP LOOSE

42.0042.00

AIRFLOWAIRFLOW

NOTE: Johnson Controls recommends the minimum distance between the fluid cooler and walls be 8 ft. The minimum distance between adjacent fluid coolers should be 4 ft for single-wide units and 8 ft for double-wide units. This will prevent air recirculation and faulty operation.

DIMENSIONS - FLUID COOLER

LD17330

JOHNSON CONTROLS24

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 25: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 4 - VDC CHARGE CALCULATIONEXAMPLE BASIS

Model VDC-244D60Refrigerant circuits oneInternal condenser tube volume shown below 4.9 cu ft

OPERATING CHARGETotal operating charge = coil vol (cu ft) x rfr density (lb/cu ft) x 0.24Total operating charge (R-22) = 4.9 x 70.3 x 0.24 = 83 IbsTotal operating charge (R-134a) = 4.9 x 71.4 x 0.24 = 84 IbsTotal operating charge (R-404A) = 4.9 x 60.0 x 0.24 = 71 IbsTotal operating charge (R-407C) = 4.9 x 66.5 x 0.24 = 78 IbsTotal operating charge (R-410A) = 4.9 x 60.7 x 0.24 = 71 IbsTotal operating charge (R-507 A) = 4.9 x 60.1 x 0.24 = 71 Ibs

PUMPDOWN STORAGE CAPACITYTotal pumpdown capacity = coil vol (cu ft) x rfr density (Ib/cu ft) x 0.8Total pumpdown capacity (R-22) = 4.9 x 70.3 x 0.8 = 276 IbsTotal pumpdown capacity (R-134a) = 4.9 x 71.4 x 0.8 = 280 IbsTotal pumpdown capacity (R-404A) = 4.9 x 60.0 x 0.8 = 235 IbsTotal pumpdown capacity (R-407C) = 4.9 x 66.5 x 0.8 = 261 IbsTotal pumpdown capacity (R-410A) = 4.9 x 60.7 x 0.8 = 238 IbsTotal pumpdown capacity (R-507A) = 4.9 x 60.1 x 0.8 = 236 Ibs

Note: Refrigerant temperature for this example is 105°F. Use the density of the refrigerant at the most appropriate temperature for the application.

VDC CHARGE CALCULATIONThe following is an example of how to determine the operating charge and pumpdown storage capacity for the VDC condensers.

JOHNSON CONTROLS 25

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 26: AIR-COOLED CONDENSER AND FLUID COOLER

PHYSICAL DATA

TABLE 5 - VDC CONDENSER 2.0 HP RATING AND PHYSICAL DATA

MODELCOIL(1)

INTERNAL VOLUME (CU FT)

APPROXIMATE UNIT WEIGHT

(LBS)

FANS 50 HZ POWER INPUT

(KW)

60 HZ POWER INPUT

(KW)QUAN-TITY

NOMINAL HP

VDC-113D60 0.52 4701 2.0 1.81 1.96VDC-114D60 0.66 489

VDC-116D60 0.96 528VDC-123D60 0.95 828

2 2.0 3.62 3.92VDC-124D60 1.24 866VDC-126D60 1.82 944VDC-133D60 1.44 1,189

3 2.0 5.43 5.88VDC-134D60 1.87 1,246VDC-136D60 2.72 1,363VDC-143D60 1.86 1,546

4 2.0 7.24 7.84VDC-144D60 2.43 1,621VDC-146D60 3.56 1,777VDC-153C60 3.08 2,027

5 2.0 9.05 9.80VDC-154C60 4.06 2,167VDC-156C60 6.00 2,529VDC-163C60 3.75 2,414

6 2.0 10.86 11.76VDC-164C60 4.92 2,582VDC-166C60 7.25 3,015VDC-223D60 1.91 1,405

4 2.0 7.24 7.84VDC-224D60 2.49 1,481VDC-226D60 3.65 1,636VDC-233D60 2.89 2,034

6 2.0 10.86 11.76VDC-234D60 3.75 2,147VDC-236D60 5.45 2,380VDC-243D60 3.73 2,653

8 2.0 14.48 15.68VDC-244D60 4.87 2,804VDC-246D60 7.13 3,115VDC-253C60 6.17 3,521

10 2.0 18.10 19.60VDC-254C60 8.12 3,801VDC-256C60 12.01 4,500VDC-263C60 7.51 4,202

12 2.0 21.72 23.52VDC-264C60 9.84 4,537VDC-266C60 14.51 5,374

NOTE: 1. Coil internal volume includes header internal volume.

JOHNSON CONTROLS26

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 27: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS)(2)

200/3/60 230/3/60 460/3/60 575/3/60FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D607.6 12.0 15.0 6.6 10.6 15.0 3.4 5.6 6.0 2.7 4.4 6.0VDC-114D60

VDC-116D60VDC-123D60

15.2 19.6 25.0 13.2 17.2 20.0 6.8 9.0 10.0 5.4 7.1 10.0VDC-124D60VDC-126D60VDC-133D60

22.8 27.2 30.0 19.8 23.8 30.0 10.2 12.4 15.0 8.1 9.8 10.0VDC-134D60VDC-136D60VDC-143D60

30.4 34.8 40.0 26.4 30.4 35.0 13.6 15.8 20.0 10.8 12.5 15.0VDC-144D60VDC-146D60VDC-153C60

38.0 42.4 50.0 33.0 37.0 40.0 17.0 19.2 20.0 13.5 15.2 20.0VDC-154C60VDC-156C60VDC-163C60

45.6 50.0 50.0 39.6 43.6 50.0 20.4 22.6 25.0 16.2 17.9 20.0VDC-164C60VDC-166C60VDC-223D60

30.4 36.7 40.0 26.4 32.0 35.0 13.6 16.6 20.0 10.8 13.2 15.0VDC-224D60VDC-226D60VDC-233D60

45.6 51.9 60.0 39.6 45.2 50.0 20.4 23.4 25.0 16.2 18.6 20.0VDC-234D60VDC-236D60VDC-243D60

60.8 67.1 70.0 52.8 58.4 60.0 27.2 30.2 35.0 21.6 24.0 25.0VDC-244D60VDC-246D60VDC-253C60

76.0 82.3 90.0 66.0 71.6 80.0 34.0 37.0 40.0 27.0 29.4 30.0VDC-254C60VDC-256C60VDC-263C60

91.2 97.5 100.0 79.2 84.8 90.0 40.8 43.8 45.0 32.4 34.8 35.0VDC-264C60VDC-266C60

NOTE:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 5 - VDC CONDENSER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS 27

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 28: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(2)

380/3/50 400/3/50 415/3/50FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D604.5 7.1 10.0 4.4 7.0 10.0 4.3 6.9 10.0VDC-114D60

VDC-116D60VDC-123D60

9.0 11.6 15.0 8.8 11.4 15.0 8.6 11.2 15.0VDC-124D60VDC-126D60VDC-133D60

13.5 16.1 20.0 13.2 15.8 20.0 12.9 15.5 20.0VDC-134D60VDC-136D60VDC-143D60

18.0 20.6 25.0 17.6 20.2 25.0 17.2 19.8 20.0VDC-144D60VDC-146D60VDC-153C60

22.5 25.1 30.0 22.0 24.6 25.0 21.5 24.1 25.0VDC-154C60VDC-156C60VDC-163C60

27.0 29.6 30.0 26.4 29.0 30.0 25.8 28.4 30.0VDC-164C60VDC-166C60VDC-223D60

18.0 21.8 25.0 17.6 21.3 25.0 17.2 20.9 25.0VDC-224D60VDC-226D60VDC-233D60

27.0 30.8 35.0 26.4 30.1 35.0 25.8 29.5 30.0VDC-234D60VDC-236D60VDC-243D60

36.0 39.8 40.0 35.2 38.9 40.0 34.4 38.1 40.0VDC-244D60VDC-246D60VDC-253C60

45.0 48.8 50.0 44.0 47.7 50.0 43.0 46.7 50.0VDC-254C60VDC-256C60VDC-263C60

54.0 57.8 60.0 52.8 56.5 60.0 51.6 55.3 60.0VDC-264C60VDC-266C60

NOTE:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 5 - VDC CONDENSER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS28

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 29: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS)(3)

200/3/60 230/3/60 460/3/60 575/3/60FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D607.6 12.6 15.0 6.6 11.1 15.0 3.4 5.9 6.0 2.7 4.6 6.0VDC-114D60

VDC-116D60VDC-123D60

15.2 22.1 25.0 13.2 19.4 20.0 6.8 10.1 15.0 5.4 8.0 10.0VDC-124D60VDC-126D60VDC-133D60

22.8 31.6 35.0 19.8 27.6 30.0 10.2 14.4 15.0 8.1 11.4 15.0VDC-134D60VDC-136D60VDC-143D60

30.4 41.1 45.0 26.4 35.9 40.0 13.6 18.6 20.0 10.8 14.8 15.0VDC-144D60VDC-146D60VDC-153C60

38.0 50.6 60.0 33.0 44.1 45.0 17.0 22.9 25.0 13.5 18.1 20.0VDC-154C60VDC-156C60VDC-163C60

45.6 60.1 70.0 39.6 52.4 60.0 20.4 27.1 30.0 16.2 21.5 25.0VDC-164C60VDC-166C60VDC-223D60

30.4 41.1 45.0 26.4 35.9 40.0 13.6 18.6 20.0 10.8 14.8 15.0VDC-224D60VDC-226D60VDC-233D60

45.6 60.1 70.0 39.6 52.4 60.0 20.4 27.1 30.0 16.2 21.5 25.0VDC-234D60VDC-236D60VDC-243D60

60.8 79.1 80.0 52.8 68.9 70.0 27.2 35.6 40.0 21.6 28.3 30.0VDC-244D60VDC-246D60VDC-253C60

76.0 98.1 100.0 66.0 85.4 90.0 34.0 44.1 45.0 27.0 35.0 35.0VDC-254C60VDC-256C60VDC-263C60

91.2 117.1 125.0 79.2 101.9 110.0 40.8 52.6 60.0 32.4 41.8 45.0VDC-264C60VDC-266C60

NOTE:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

TABLE 5 - VDC CONDENSER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS 29

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 30: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(3)

380/3/50 400/3/50 415/3/50FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D604.5 7.5 10.0 4.4 7.4 10.0 4.3 7.3 10.0VDC-114D60

VDC-116D60VDC-123D60

9.0 13.1 15.0 8.8 12.9 15.0 8.6 12.6 15.0VDC-124D60VDC-126D60VDC-133D60

13.5 18.8 20.0 13.2 18.4 20.0 12.9 18.0 20.0VDC-134D60VDC-136D60VDC-143D60

18.0 24.4 25.0 17.6 23.9 25.0 17.2 23.4 25.0VDC-144D60VDC-146D60VDC-153C60

22.5 30.0 30.0 22.0 29.4 30.0 21.5 28.8 30.0VDC-154C60VDC-156C60VDC-163C60

27.0 35.6 40.0 26.4 34.9 35.0 25.8 34.1 35.0VDC-164C60VDC-166C60VDC-223D60

18.0 24.4 25.0 17.6 23.9 25.0 17.2 23.4 25.0VDC-224D60VDC-226D60VDC-233D60

27.0 35.6 40.0 26.4 34.9 35.0 25.8 34.1 35.0VDC-234D60VDC-236D60VDC-243D60

36.0 46.9 50.0 35.2 45.9 50.0 34.4 44.9 45.0VDC-244D60VDC-246D60VDC-253C60

45.0 58.1 60.0 44.0 56.9 60.0 43.0 55.6 60.0VDC-254C60VDC-256C60VDC-263C60

54.0 69.4 70.0 52.8 67.9 70.0 51.6 66.4 70.0VDC-264C60VDC-266C60

NOTE:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

TABLE 5 - VDC CONDENSER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS30

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 31: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 6 - VDC CONDENSER 1.0 HP RATING AND PHYSICAL DATA

MODELCOIL(1)

INTERNAL VOLUME (CU FT)

APPROXIMATE UNIT WEIGHT

(LBS)

FANS 60 HZ POWER INPUT (KW)

50 HZ POWER INPUT (KW)QUANTITY NOM HP

VDC-113D10 0.52 4701 1.0 1.01 1.05VDC-114D10 0.66 489

VDC-116D10 0.96 528VDC-123D10 0.95 828

2 1.0 2.02 2.10VDC-124D10 1.24 866VDC-126D10 1.82 944VDC-133D10 1.44 1,189

3 1.0 3.03 3.15VDC-134D10 1.87 1,246VDC-136D10 2.72 1,363VDC-143D10 1.86 1,546

4 1.0 4.04 4.20VDC-144D10 2.43 1,621VDC-146D10 3.56 1,777VDC-153C10 3.08 2,027

5 1.0 5.05 5.25VDC-154C10 4.06 2,167VDC-156C10 6.00 2,529VDC-163C10 3.75 2,414

6 1.0 6.06 6.30VDC-164C10 4.92 2,582VDC-166C10 7.25 3,015VDC-223D10 1.91 1,405

4 1.0 4.04 4.20VDC-224D10 2.49 1,481VDC-226D10 3.65 1,636VDC-233D10 2.89 2,034

6 1.0 6.06 6.30VDC-234D10 3.75 2,147VDC-236D10 5.45 2,380VDC-243D10 3.73 2,653

8 1.0 8.08 8.40VDC-244D10 4.87 2,804VDC-246D10 7.13 3,115VDC-253C10 6.17 3,521

10 1.0 10.10 10.50VDC-254C10 8.12 3,801VDC-256C10 12.01 4,500VDC-263C10 7.51 4,202

12 1.0 12.12 12.60VDC-264C10 9.84 4,537VDC-266C10 14.51 5,374

NOTE: 1. Coil internal volume includes header internal volume.

JOHNSON CONTROLS 31

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 32: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS)(2)

200/3/60 230/3/60 460/3/60 575/3/60FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D105.7 9.6 15.0 4.8 8.3 10.0 2.4 4.3 6.0 1.9 3.4 6.0VDC-114D10

VDC-116D10VDC-123D10

11.4 15.3 20.0 9.6 13.1 15.0 4.8 6.7 10.0 3.8 5.3 6.0VDC-124D10VDC-126D10VDC-133D10

17.1 21.0 25.0 14.4 17.9 20.0 7.2 9.1 10.0 5.7 7.2 10.0VDC-134D10VDC-136D10VDC-143D10

22.8 26.7 30 19.2 22.7 25 9.6 11.5 15 7.6 9.1 10.0VDC-144D10VDC-146D10VDC-153C10

28.5 32.4 35.0 24.0 27.5 30.0 12.0 13.9 15.0 9.5 11.0 15.0VDC-154C10VDC-156C10VDC-163C10

34.2 38.1 40.0 28.8 32.3 35.0 14.4 16.3 20.0 11.4 12.9 15.0VDC-164C10VDC-166C10VDC-223D10

22.8 28.2 30.0 19.2 23.9 25.0 9.6 12.1 15.0 7.6 9.6 10.0VDC-224D10VDC-226D10VDC-233D10

34.2 39.6 40.0 28.8 33.5 35.0 14.4 16.9 20.0 11.4 13.4 15.0VDC-234D10VDC-236D10VDC-243D10

45.6 51.0 60.0 38.4 43.1 45.0 19.2 21.7 25.0 15.2 17.2 20.0VDC-244D10VDC-246D10VDC-253C10

57.0 62.4 70.0 48.0 52.7 60.0 24.0 26.5 30.0 19.0 21.0 25.0VDC-254C10VDC-256C10VDC-263C10

68.4 73.8 80.0 57.6 62.3 70.0 28.8 31.3 35.0 22.8 24.8 25.0VDC-264C10VDC-266C10

NOTE:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 6 - VDC CONDENSER 1.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS32

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 33: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(2)

380/3/50 400/3/50 415/3/50FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D602.8 5.0 6.0 2.7 4.9 6.0 2.6 4.8 6.0VDC-114D60

VDC-116D60VDC-123D60

5.6 7.8 10.0 5.4 7.6 10.0 5.2 7.4 10.0VDC-124D60VDC-126D60VDC-133D60

8.4 10.6 15.0 8.1 10.3 15.0 7.8 10.0 10.0VDC-134D60VDC-136D60VDC-143D60

11.2 13.4 15.0 10.8 13.0 15.0 10.4 12.6 15.0VDC-144D60VDC-146D60VDC-153C60

14.0 16.2 20.0 13.5 15.7 20.0 13.0 15.2 20.0VDC-154C60VDC-156C60VDC-163C60

16.8 19.0 20.0 16.2 18.4 20.0 15.6 17.8 20.0VDC-164C60VDC-166C60VDC-223D60

11.2 14.1 15.0 10.8 13.7 15.0 10.4 13.2 15.0VDC-224D60VDC-226D60VDC-233D60

16.8 19.7 20.0 16.2 19.1 20.0 15.6 18.4 20.0VDC-234D60VDC-236D60VDC-243D60

22.4 25.3 30.0 21.6 24.5 25.0 20.8 23.6 25.0VDC-244D60VDC-246D60VDC-253C60

28.0 30.9 35.0 27.0 29.9 30.0 26.0 28.8 30.0VDC-254C60VDC-256C60VDC-263C60

33.6 36.5 40.0 32.4 35.3 40.0 31.2 34.0 35.0VDC-264C60VDC-266C60

NOTE:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 6 - VDC CONDENSER 1.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS 33

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 34: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS)(3)

200/3/60 230/3/60 460/3/60 575/3/60FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D105.7 10.3 15.0 4.8 8.9 10.0 2.4 4.6 6.0 1.9 3.6 6.0VDC-114D10

VDC-116D10VDC-123D10

11.4 17.4 20.0 9.6 14.9 15.0 4.8 7.6 10.0 3.8 6.0 6.0VDC-124D10VDC-126D10VDC-133D10

17.1 24.5 25.0 14.4 20.9 25.0 7.2 10.6 15.0 5.7 8.4 10.0VDC-134D10VDC-136D10VDC-143D10

22.8 31.6 35 19.2 26.9 30.0 9.6 13.6 15.0 7.6 10.8 15.0VDC-144D10VDC-146D10VDC-153C10

28.5 38.8 40.0 24.0 32.9 35.0 12.0 16.6 20.0 9.5 13.1 15.0VDC-154C10VDC-156C10VDC-163C10

34.2 45.9 50.0 28.8 38.9 40.0 14.4 19.6 20.0 11.4 15.5 20.0VDC-164C10VDC-166C10VDC-223D10

22.8 31.6 35.0 19.2 26.9 30.0 9.6 13.6 15.0 7.6 10.8 15.0VDC-224D10VDC-226D10VDC-233D10

34.2 45.9 50.0 28.8 38.9 40.0 14.4 19.6 20.0 11.4 15.5 20.0VDC-234D10VDC-236D10VDC-243D10

45.6 60.1 70.0 38.4 50.9 60.0 19.2 25.6 30.0 15.2 20.3 25.0VDC-244D10VDC-246D10VDC-253C10

57.0 74.4 80.0 48.0 62.9 70.0 24.0 31.6 35.0 19.0 25.0 25.0VDC-254C10VDC-256C10VDC-263C10

68.4 88.6 90.0 57.6 74.9 80.0 28.8 37.6 40.0 22.8 29.8 30.0VDC-264C10VDC-266C10

NOTE:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

TABLE 6 - VDC CONDENSER 1.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS34

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 35: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(2)

380/3/50 400/3/50 415/3/50FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDC-113D602.8 5.4 6.0 2.7 5.3 6.0 2.6 5.1 6.0VDC-114D60

VDC-116D60VDC-123D60

5.6 8.9 10.0 5.4 8.6 10.0 5.2 8.4 10.0VDC-124D60VDC-126D60VDC-133D60

8.4 12.4 15.0 8.1 12.0 15.0 7.8 11.6 15.0VDC-134D60VDC-136D60VDC-143D60

11.2 15.9 20.0 10.8 15.4 20.0 10.4 14.9 15.0VDC-144D60VDC-146D60VDC-153C60

14.0 19.4 20.0 13.5 18.8 20.0 13.0 18.1 20.0VDC-154C60VDC-156C60VDC-163C60

16.8 22.9 25.0 16.2 22.1 25.0 15.6 21.4 25.0VDC-164C60VDC-166C60VDC-223D60

11.2 15.9 20.0 10.8 15.4 20.0 10.4 14.9 15.0VDC-224D60VDC-226D60VDC-233D60

16.8 22.9 25.0 16.2 21.8 25.0 15.6 21.4 25.0VDC-234D60VDC-236D60VDC-243D60

22.4 29.9 30.0 21.6 28.9 30.0 20.8 27.9 30.0VDC-244D60VDC-246D60VDC-253C60

28.0 36.9 40.0 27.0 35.6 40.0 26.0 34.4 35.0VDC-254C60VDC-256C60VDC-263C60

33.6 43.9 45.0 32.4 42.4 45.0 31.2 40.9 45.0VDC-264C60VDC-266C60

NOTE:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

TABLE 6 - VDC CONDENSER 1.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS 35

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 36: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 7 - VDCF FLUID COOLER 2.0 HP RATING AND PHYSICAL DATA

MODELCOIL(1)

INTERNAL VOLUME (CU FT)

APPROXIMATE UNIT WEIGHT

(LBS)

FANS 60 HZ POWER INPUT (KW)

50 HZ POWER INPUT (KW)QUANTITY NOM HP

VDCF113B60XXB 1.07 519

1 2.0 1.81 1.96

VDCF113B60XXC 1.07 537VDCF114B60XXB 1.45 557VDCF116B60XXB 2.27 658VDCF116B60XXC 1.98 649VDCF118B60XXB 2.80 728VDCF124B60XXB 2.43 987

2 2.0 3.62 3.92VDCF126B60XXB 3.75 1,168VDCF126B60XXC 3.46 1,160VDCF128B60XXB 4.78 1,304VDCF134B60XXB 3.42 1,415

3 2.0 5.43 5.88VDCF136B60XXB 5.23 1,679VDCF136B60XXC 4.94 1,671VDCF138B60XXB 6.75 1,881VDCF144B60XXB 4.41 1,846

4 2.0 7.24 7.84VDCF146B60XXB 6.71 2,189VDCF146B60XXC 6.43 2,181VDCF148B60XXB 8.73 2,457VDCF154B60XXB 5.40 2,275

5 2.0 9.05 9.80VDCF156B60XXB 8.19 2,699VDCF156B60XXC 7.91 2,691VDCF158B60XXB 10.70 2,033VDCF164B60XXB 6.38 2,704

6 2.0 10.86 11.76VDCF166B60XXB 9.67 3,210VDCF166B60XXC 9.39 3,202VDCF168B60XXB 12.68 3,609VDCF224B60XXB 4.86 1,736

4 2.0 7.24 7.84VDCF226B60XXB 7.50 2,074VDCF226B60XXC 6.92 2,071VDCF228B60XXB 9.56 2,346VDCF234B60XXB 6.84 2,499

6 2.0 10.86 11.76VDCF236B60XXB 10.46 2,998VDCF236B60XXC 9.88 2,995VDCF238B60XXB 13.50 3,402VDCF244B60XXB 8.82 3,267

8 2.0 14.48 15.65VDCF246B60XXB 13.42 3,919VDCF246B60XXC 12.86 3,916VDCF248B60XXB 17.46 4,455VDCF254B60XXB 10.80 4,030

10 2.0 18.10 19.60.VDCF256B60XXB 16.38 4,840VDCF256B60XXC 15.82 4,837VDCF258B60XXB 21.40 5,508VDCF264B60XXB 12.76 4,795

12 2.0 21.72 23.52VDCF266B60XXB 19.34 5,764VDCF266B60XXC 18.78 5,761VDCF268B60XXB 25.36 6,562

NOTE:1. Coil internal volume includes header internal volume.

JOHNSON CONTROLS36

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 37: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS)(2)

200 VOLTS 230 VOLTS 460 VOLTS 575 VOLTSFLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B60XXB

7.6 12.0 15.0 6.6 10.6 15.0 3.4 5.6 6.0 2.7 4.4 6.0

VDCF113B60XXCVDCF114B60XXBVDCF116B60XXBVDCF116B60XXCVDCF118B60XXBVDCF124B60XXB

15.2 19.6 25.0 13.2 17.2 20.0 6.8 9.0 10.0 5.4 7.1 10.0VDCF126B60XXBVDCF126B60XXCVDCF128B60XXBVDCF134B60XXB

22.8 27.2 30.0 19.8 23.8 30.0 10.2 12.4 15.0 8.1 9.8 10.0VDCF136B60XXBVDCF136B60XXCVDCF138B60XXBVDCF144B60XXB

30.4 34.8 40.0 26.4 30.4 35.0 13.6 15.8 20.0 10.8 12.5 15.0VDCF146B60XXBVDCF146B60XXCVDCF148B60XXBVDCF154B60XXB

38.0 42.4 50.0 33.0 37.0 40.0 17.0 19.2 20.0 13.5 15.2 20.0VDCF156B60XXBVDCF156B60XXCVDCF158B60XXBVDCF164B60XXB

45.6 50.0 50.0 39.6 43.6 50.0 20.4 22.6 25.0 16.2 17.9 20.0VDCF166B60XXBVDCF166B60XXCVDCF168B60XXBVDCF224B60XXB

30.4 36.7 40.0 26.4 32.0 35.0 13.6 16.6 20.0 10.8 13.2 15.0VDCF226B60XXBVDCF226B60XXCVDCF228B60XXBVDCF234B60XXB

45.6 51.9 60.0 39.6 45.2 50.0 20.4 23.4 25.0 16.2 18.6 20.0VDCF236B60XXBVDCF236B60XXCVDCF238B60XXBVDCF244B60XXB

60.8 67.1 70.0 52.8 58.4 60.0 27.2 30.2 35.0 21.6 24.0 25.0VDCF246B60XXBVDCF246B60XXCVDCF248B60XXBVDCF254B60XXB

76.0 82.3 90.0 66.0 71.6 80.0 34.0 37.0 40.0 27.0 29.4 30.0VDCF256B60XXBVDCF256B60XXCVDCF258B60XXBVDCF264B60XXB

91.2 97.5 100.0 79.2 84.8 90.0 40.8 43.8 45.0 32.4 34.8 35.0VDCF266B60XXBVDCF266B60XXCVDCF268B60XXB

NOTE:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 7 - VDCF FLUID COOLER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS 37

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 38: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(2)

380 VOLTS 400 VOLTS 415 VOLTSFLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B60XXB

4.5 7.1 10.0 4.4 7.0 10.0 4.3 6.9 10.0

VDCF113B60XXCVDCF114B60XXBVDCF116B60XXBVDCF116B60XXCVDCF118B60XXBVDCF124B60XXB

9.0 11.6 15.0 8.8 11.4 15.0 8.6 11.2 15.0VDCF126B60XXBVDCF126B60XXCVDCF128B60XXBVDCF134B60XXB

13.5 16.1 20.0 13.2 15.8 20.0 12.9 15.5 20.0VDCF136B60XXBVDCF136B60XXCVDCF138B60XXBVDCF144B60XXB

18.0 20.6 25.0 17.6 20.2 25.0 17.2 19.8 20.0VDCF146B60XXBVDCF146B60XXCVDCF148B60XXBVDCF154B60XXB

22.5 25.1 30.0 22.0 24.6 25.0 21.5 24.1 25.0VDCF156B60XXBVDCF156B60XXCVDCF158B60XXBVDCF164B60XXB

27.0 29.6 30.0 26.4 29.0 30.0 25.8 28.4 30.0VDCF166B60XXBVDCF166B60XXCVDCF168B60XXBVDCF224B60XXB

18.0 21.8 25.0 17.6 21.3 25.0 17.2 20.9 25.0VDCF226B60XXBVDCF226B60XXCVDCF228B60XXBVDCF234B60XXB

27.0 30.8 35.0 26.4 30.1 35.0 25.8 29.5 30.0VDCF236B60XXBVDCF236B60XXCVDCF238B60XXBVDCF244B60XXB

36.0 39.8 40.0 35.2 38.9 40.0 34.4 38.1 40.0VDCF246B60XXBVDCF246B60XXCVDCF248B60XXBVDCF254B60XXB

45.0 48.8 50.0 44.0 47.7 50.0 43.0 46.7 50.0VDCF256B60XXBVDCF256B60XXCVDCF258B60XXBVDCF264B60XXB

54.0 57.8 60.0 52.8 56.5 60.0 51.6 55.3 60.0VDCF266B60XXBVDCF266B60XXCVDCF268B60XXB

NOTE:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 7 - VDC CONDENSER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS38

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 39: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 60 HZ AT STANDARD AIR (AMPS)(3)

200/3/60 230/3/60 460/3/60 575/3/60FLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B60XXB

7.6 12.6 15.0 6.6 11.1 15.0 3.4 5.9 6.0 2.7 4.6 6.0

VDCF113B60XXCVDCF114B60XXBVDCF116B60XXBVDCF116B60XXCVDCF118B60XXBVDCF124B60XXB

15.2 22.1 25.0 13.2 19.4 20.0 6.8 10.1 10.0 5.4 8.0 10.0VDCF126B60XXBVDCF126B60XXCVDCF128B60XXBVDCF134B60XXB

22.8 31.6 35.0 19.8 27.6 30.0 10.2 14.4 15.0 8.1 11.4 15.0VDCF136B60XXBVDCF136B60XXCVDCF138B60XXBVDCF144B60XXB

30.4 41.1 45.0 26.4 35.9 40.0 13.6 18.6 15.0 10.8 14.8 15.0VDCF146B60XXBVDCF146B60XXCVDCF148B60XXBVDCF154B60XXB

38.0 50.6 60.0 33.0 44.1 45.0 17.0 22.9 20.0 13.5 18.1 20.0VDCF156B60XXBVDCF156B60XXCVDCF158B60XXBVDCF164B60XXB

45.6 60.1 70.0 39.6 52.4 60.0 20.4 27.1 25.0 16.2 21.5 25.0VDCF166B60XXBVDCF166B60XXCVDCF168B60XXBVDCF224B60XXB

30.4 41.1 45.0 26.4 35.9 40.0 13.6 18.6 15.0 10.8 14.8 15.0VDCF226B60XXBVDCF226B60XXCVDCF228B60XXBVDCF234B60XXB

45.6 60.1 70.0 39.6 52.4 60.0 20.4 27.1 25.0 16.2 21.5 25.0VDCF236B60XXBVDCF236B60XXCVDCF238B60XXBVDCF244B60XXB

60.8 79.1 80.0 52.8 68.9 70.0 27.2 35.6 30.0 21.6 28.3 30.0VDCF246B60XXBVDCF246B60XXCVDCF248B60XXBVDCF254B60XXB

76.0 98.1 100.0 66.0 85.4 90.0 34.0 44.1 35.0 27.0 35.0 35.0VDCF256B60XXBVDCF256B60XXCVDCF258B60XXBVDCF264B60XXB

91.2 117.1 125.0 79.2 101.9 110.0 40.8 52.6 45.0 32.4 41.8 55.0VDCF266B60XXBVDCF266B60XXCVDCF268B60XXB

NOTE:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

TABLE 7 - VDCF FLUID COOLER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS 39

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 40: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 7 - VDC CONDENSER 2.0 HP RATING AND PHYSICAL DATA (CONT'D)

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(2)

380 VOLTS 400 VOLTS 415 VOLTSFLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B60XXB

4.5 7.5 10.0 4.4 7.4 10.0 4.3 7.3 10.0

VDCF113B60XXCVDCF114B60XXBVDCF116B60XXBVDCF116B60XXCVDCF118B60XXBVDCF124B60XXB

9.0 13.1 15.0 8.8 12.9 15.0 8.6 12.6 15.0VDCF126B60XXBVDCF126B60XXCVDCF128B60XXBVDCF134B60XXB

13.5 18.8 20.0 13.2 18.4 20.0 12.9 18.0 20.0VDCF136B60XXBVDCF136B60XXCVDCF138B60XXBVDCF144B60XXB

18.0 24.4 25.0 17.6 23.9 25.0 17.2 23.4 25.0VDCF146B60XXBVDCF146B60XXCVDCF148B60XXBVDCF154B60XXB

22.5 30.0 30.0 22.0 29.4 30.0 21.5 28.8 30.0VDCF156B60XXBVDCF156B60XXCVDCF158B60XXBVDCF164B60XXB

27.0 35.16 40.0 26.4 34.9 35.0 25.8 34.1 35.0VDCF166B60XXBVDCF166B60XXCVDCF168B60XXBVDCF224B60XXB

18.0 24.4 25.0 17.6 23.9 25.0 17.2 23.4 25.0VDCF226B60XXBVDCF226B60XXCVDCF228B60XXBVDCF234B60XXB

27.0 35.6 40.0 26.4 34.9 35.0 25.8 34.1 35.0VDCF236B60XXBVDCF236B60XXCVDCF238B60XXBVDCF244B60XXB

36.0 46.9 45.0 35.2 45.9 50.0 34.4 44.9 45.0VDCF246B60XXBVDCF246B60XXCVDCF248B60XXBVDCF254B60XXB

45.0 58.1 60.0 44.0 56.9 60.0 43.0 55.6 60.0VDCF256B60XXBVDCF256B60XXCVDCF258B60XXBVDCF264B60XXB

54.0 69.4 70.0 52.8 67.9 70.0 51.6 66.4 70.0VDCF266B60XXBVDCF266B60XXCVDCF268B60XXB

NOTE:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

JOHNSON CONTROLS40

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 41: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 8 - VDCF FLUID COOLER 1.0 HP RATING AND PHYSICAL DATA

MODELCOIL(1)

INTERNAL VOLUME (CU FT)

APPROXIMATE UNIT WEIGHT

(LBS)

FANS 60 HZ POWER INPUT (KW)

50 HZ POWER INPUT (KW)QUANTITY NOM HP

VDCF113B10XXB 1.07 519

1 1.0 1.01 1.05

VDCF113B10XXC 1.07 537VDCF114B10XXB 1.45 557VDCF116B10XXB 2.27 658VDCF116B10XXC 1.98 649VDCF118B10XXB 2.80 728VDCF124B10XXB 2.43 987

2 1.0 2.02 2.10VDCF126B10XXB 3.75 1,168VDCF126B10XXC 3.46 1,160VDCF128B10XXB 4.78 1,304VDCF134B10XXB 3.42 1,415

3 1.0 3.03 3.15VDCF136B10XXB 5.23 1,679VDCF136B10XXC 4.94 1,671VDCF138B10XXB 6.75 1,881VDCF144B10XXB 4.41 1,846

4 1.0 4.04 4.20VDCF146B10XXB 6.71 2,189VDCF146B10XXC 6.43 2,181VDCF148B10XXB 8.73 2,457VDCF154B10XXB 5.40 2,275

5 1.0 5.05 5.25VDCF156B10XXB 8.19 2,699VDCF156B10XXC 7.91 2,691VDCF158B10XXB 10.70 2,033VDCF164B10XXB 6.38 2,704

6 1.0 6.06 6.30VDCF166B10XXB 9.67 3,210VDCF166B10XXC 9.39 3,202VDCF168B10XXB 12.68 3,609VDCF224B10XXB 4.86 1,736

4 1.0 4.04 4.20VDCF226B10XXB 7.50 2,074VDCF226B10XXC 6.92 2,071VDCF228B10XXB 9.56 2,346VDCF234B10XXB 6.84 2,499

6 1.0 6.06 6.30VDCF236B10XXB 10.46 2,998VDCF236B10XXC 9.88 2,995VDCF238B10XXB 13.50 3,402VDCF244B10XXB 8.82 3,267

8 1.0 8.08 8.40VDCF246B10XXB 13.42 3,919VDCF246B10XXC 12.86 3,916VDCF248B10XXB 17.46 4,455VDCF254B10XXB 10.80 4,030

10 1.0 10.10 10.50VDCF256B10XXB 16.38 4,840VDCF256B10XXC 15.82 4,837VDCF258B10XXB 21.40 5,508VDCF264B10XXB 12.76 4,795

12 1.0 12.12 12.60VDCF266B10XXB 19.34 5,764VDCF266B10XXC 18.78 5,761VDCF268B10XXB 25.36 6,562

NOTES: 1. Coil internal volume includes header internal volume.

JOHNSON CONTROLS 41

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 42: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT, 30 PH, 60 HZ DRAW AT STANDARD AIR (AMPS)(2)

200 VOLTS 230 VOLTS 460 VOLTS 575 VOLTSFLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B10XXB

5.7 9.6 15.0 4.8 8.3 10.0 2.4 4.3 6.0 1.9 3.4 6.0

VDCF113B10XXCVDCF114B10XXBVDCF116B10XXBVDCF116B10XXCVDCF118B10XXBVDCF124B10XXB

11.4 15.3 20.0 9.6 13.1 15.0 4.8 6.7 10.0 3.8 5.3 6.0VDCF126B10XXBVDCF126B10XXCVDCF128B10XXBVDCF134B10XXB

17.1 21.0 25.0 14.4 17.9 20.0 7.2 9.1 10.0 5.7 7.2 10.0VDCF136B10XXBVDCF136B10XXCVDCF138B10XXBVDCF144B10XXB

22.8 26.7 30 19.2 22.7 25 9.6 11.5 15 7.6 9.1 10VDCF146B10XXBVDCF146B10XXCVDCF148B10XXBVDCF154B10XXB

28.5 32.4 35.0 24.0 27.5 30.0 12.0 13.9 15.0 9.5 11.0 15.0VDCF156B10XXBVDCF156B10XXCVDCF158B10XXBVDCF164B10XXB

34.2 38.1 40.0 28.8 32.3 35.0 14.4 16.3 20.0 11.4 12.9 15.0VDCF166B10XXBVDCF166B10XXCVDCF168B10XXBVDCF224B10XXB

22.8 28.2 30.0 19.2 23.9 25.0 9.6 12.1 15.0 7.6 9.6 10.0VDCF226B10XXBVDCF226B10XXCVDCF228B10XXBVDCF234B10XXB

34.2 39.6 40.0 28.8 33.5 35.0 14.4 16.9 20.0 11.4 13.4 15.0VDCF236B10XXBVDCF236B10XXCVDCF238B10XXBVDCF244B10XXB

45.6 51.0 60.0 38.4 43.1 45.0 19.2 21.7 25.0 15.2 17.2 20.0VDCF246B10XXBVDCF246B10XXCVDCF248B10XXBVDCF254B10XXB

57.0 62.4 70.0 48.0 52.7 60.0 24.0 26.5 30.0 19.0 21.0 25.0VDCF256B10XXBVDCF256B10XXCVDCF258B10XXBVDCF264B10XXB

68.4 73.8 80.0 57.6 62.3 70.0 28.8 31.3 35.0 22.8 24.8 25.0VDCF266B10XXBVDCF266B10XXCVDCF268B10XXB

NOTES:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 8 - VDCF FLUID COOLER 1.0 HP RATING AND PHYSICAL DATA

JOHNSON CONTROLS42

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 43: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(2)

380 VOLTS 400 VOLTS 415 VOLTSFLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B10XXB

2.8 5.0 6.0 2.7 4.9 6.0 2.6 4.8 6.0

VDCF113B10XXCVDCF114B10XXBVDCF116B10XXBVDCF116B10XXCVDCF118B10XXBVDCF124B10XXB

5.6 7.8 10.0 5.4 7.6 10.0 5.2 7.4 10.0VDCF126B10XXBVDCF126B10XXCVDCF128B10XXBVDCF134B10XXB

8.4 10.6 15.0 8.1 10.3 15.0 7.8 10.0 10.0VDCF136B10XXBVDCF136B10XXCVDCF138B10XXBVDCF144B10XXB

11.2 13.4 15.0 10.8 13.0 15.0 10.4 12.6 15.0VDCF146B10XXBVDCF146B10XXCVDCF148B10XXBVDCF154B10XXB

14.0 16.2 20.0 13.5 15.7 20.0 13.0 15.2 20.0VDCF156B10XXBVDCF156B10XXCVDCF158B10XXBVDCF164B10XXB

16.8 19.0 20.0 16.2 18.4 20.0 15.6 17.8 20.0VDCF166B10XXBVDCF166B10XXCVDCF168B10XXBVDCF224B10XXB

11.2 14.1 15.0 10.8 13.7 15.0 10.4 13.2 15.0VDCF226B10XXBVDCF226B10XXCVDCF228B10XXBVDCF234B10XXB

16.8 19.7 20.0 16.2 19.1 20.0 15.6 18.4 20.0VDCF236B10XXBVDCF236B10XXCVDCF238B10XXBVDCF244B10XXB

22.4 25.3 30.0 21.6 24.5 25.0 20.8 23.6 25.0VDCF246B10XXBVDCF246B10XXCVDCF248B10XXBVDCF254B10XXB

28.0 30.9 35.0 27.0 29.9 30.0 26.0 28.8 30.0VDCF256B10XXBVDCF256B10XXCVDCF258B10XXBVDCF264B10XXB

33.6 36.5 40.0 32.4 35.3 40.0 31.2 34.0 35.0VDCF266B10XXBVDCF266B10XXCVDCF268B10XXB

NOTES:2. For Temperature-Controlled Fan Cycling and Pressure-Controlled Fan Cycling.

TABLE 8 - VDC CONDENSER 1.0 HP RATING AND PHYSICAL DATA (CONT'D)

JOHNSON CONTROLS 43

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 44: AIR-COOLED CONDENSER AND FLUID COOLER

MODELMOTOR CURRENT DRAW, 30 PH, 50 HZ AT STANDARD AIR (AMPS)(3)

200 VOLTS 230 VOLTS 460 VOLTS 575 VOLTSFLA MCA MOP FLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B10XXB

5.7 10.3 15.0 4.8 8.9 10.0 2.4 4.6 6.0 1.9 3.6 6.0

VDCF113B10XXCVDCF114B10XXBVDCF116B10XXBVDCF116B10XXCVDCF118B10XXBVDCF124B10XXB

11.4 17.4 20.0 9.6 14.9 15.0 4.8 7.6 10.0 3.8 6.0 6.0VDCF126B10XXBVDCF126B10XXCVDCF128B10XXBVDCF134B10XXB

17.1 24.5 25.0 14.4 20.9 25.0 7.2 10.6 15.0 5.7 8.4 10.0VDCF136B10XXBVDCF136B10XXCVDCF138B10XXBVDCF144B10XXB

22.8 31.6 35.0 19.2 26.9 30.0 9.6 13.6 15.0 7.6 10.8 15.0VDCF146B10XXBVDCF146B10XXCVDCF148B10XXBVDCF154B10XXB

28.5 38.8 40.0 24.0 32.9 35.0 12.0 16.6 20.0 9.5 13.1 15.0VDCF156B10XXBVDCF156B10XXCVDCF158B10XXBVDCF164B10XXB

34.2 45.9 50.0 28.8 38.9 40.0 14.4 19.6 20.0 11.4 15.5 20.0VDCF166B10XXBVDCF166B10XXCVDCF168B10XXBVDCF224B10XXB

22.8 31.6 35.0 19.2 26.9 30.0 9.6 13.6 15.0 7.6 10.8 15.0VDCF226B10XXBVDCF226B10XXCVDCF228B10XXBVDCF234B10XXB

34.2 45.9 50.0 28.8 38.9 40.0 14.4 19.6 20.0 11.4 15.5 20.0VDCF236B10XXBVDCF236B10XXCVDCF238B10XXBVDCF244B10XXB

45.6 60.1 70.0 38.4 50.9 60.0 19.2 25.6 30.0 15.2 20.3 25.0VDCF246B10XXBVDCF246B10XXCVDCF248B10XXBVDCF254B10XXB

57.0 74.4 80.0 48.0 62.9 70.0 24.0 31.6 35.0 19.0 25.0 25.0VDCF256B10XXBVDCF256B10XXCVDCF258B10XXBVDCF264B10XXB

68.4 88.6 90.0 57.6 74.9 80.0 28.8 37.6 40.0 22.8 29.8 30.0VDCF266B10XXBVDCF266B10XXCVDCF268B10XXB

NOTES:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

TABLE 8 - VDCF FLUID COOLER 1.0 HP RATING AND PHYSICAL DATA

JOHNSON CONTROLS44

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 45: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 8 - VDC CONDENSER 1.0 HP RATING AND PHYSICAL DATA (CONT'D)

MODELMOTOR CURRENT DRAW, 3 PH, 50 HZ AT STANDARD AIR (AMPS)(2)

380 VOLTS 400 VOLTS 415 VOLTSFLA MCA MOP FLA MCA MOP FLA MCA MOP

VDCF113B10XXB

2.8 5.4 6.0 2.7 5.3 6.0 2.6 5.1 6.0

VDCF113B10XXCVDCF114B10XXBVDCF116B10XXBVDCF116B10XXCVDCF118B10XXBVDCF124B10XXB

5.6 8.9 10.0 5.4 8.6 10.0 5.2 8.4 10.0VDCF126B10XXBVDCF126B10XXCVDCF128B10XXBVDCF134B10XXB

8.4 12.4 15.0 8.1 12.0 15.0 7.8 11.6 15.0VDCF136B10XXBVDCF136B10XXCVDCF138B10XXBVDCF144B10XXB

11.2 15.9 20.0 10.8 15.4 20.0 10.4 14.9 15.0VDCF146B10XXBVDCF146B10XXCVDCF148B10XXBVDCF154B10XXB

14.0 19.4 20.0 13.5 18.8 20.0 13.0 18.1 20.0VDCF156B10XXBVDCF156B10XXCVDCF158B10XXBVDCF164B10XXB

16.8 22.9 25.0 16.2 22.1 25.0 15.6 21.4 25.0VDCF166B10XXBVDCF166B10XXCVDCF168B10XXBVDCF224B10XXB

11.2 15.9 20.0 10.8 15.4 20.0 10.4 14.9 15.0VDCF226B10XXBVDCF226B10XXCVDCF228B10XXBVDCF234B10XXB

16.8 22.9 25.0 16.2 22.1 25.0 15.6 21.4 25.0VDCF236B10XXBVDCF236B10XXCVDCF238B10XXBVDCF244B10XXB

22.4 29.9 30.0 21.6 28.9 30.0 20.8 27.9 30.0VDCF246B10XXBVDCF246B10XXCVDCF248B10XXBVDCF254B10XXB

28.0 36.9 40.0 27.0 35.6 40.0 26.0 34.4 35.0VDCF256B10XXBVDCF256B10XXCVDCF258B10XXBVDCF264B10XXB

33.6 43.9 45.0 32.4 42.4 45.0 31.2 40.9 45.0VDCF266B10XXBVDCF266B10XXCVDCF268B10XXB

NOTES:3. For VSD-ready for Variable Speed Fan Control and Standard Control without Fan Cycling.

JOHNSON CONTROLS 45

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 46: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 9 - LUG DATA

VDC AND VDCF MODELS VDC AND VDCF VOLTAGEDISCONNECT WIRE RANGE1 HP 2 HP

VDC-11 AND VDCF11

200

#14-10 AWG #14-10 AWG230

380/400/415460575

VDC-12 AND VDCF12

200

#14-10 AWG #14-10 AWG230

380/400/415460575

VDC-13 AND VDCF13

200

#14-10 AWG

#10-3 AWG230

380/400/415#14-10 AWG460

575

VDC-14 AND VDCF14

200

#14-10 AWG

#10-3 AWG230

380/400/415#14-10 AWG460

575

VDC-15 AND VDCF15

200#10-3 AWG #14-2/0 AWG

230380/400/415

#14-10 AWG#10-3 AWG

460575 #14-10 AWG

VDC-16 AND VDCF16

200#10-3 AWG #14-2/0 AWG

230380/400/415

#14-10 AWG #10-3 AWG460575

VDC-22 AND VDCF22

200

#14-10 AWG

#10-3 AWG230

380/400/415#14-10 AWG460

575

VDC-23 AND VDCF23

200#10-3 AWG #14-2/0 AWG

230380/400/415

#14-10 AWG #10-3 AWG460575

JOHNSON CONTROLS46

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 47: AIR-COOLED CONDENSER AND FLUID COOLER

VDC AND VDCF MODELS VDC AND VDCF VOLTAGEDISCONNECT WIRE RANGE1 HP 2 HP

VDC-24 AND VDCF24

200#14-2/0 AWG #14-2/0 AWG

230380/400/415

#10-3 AWG#10-3 AWG460

575 #14-10 AWG

VDC-25 AND VDCF25

200#14-2/0 AWG #6-3/0 AWG

230380/400/415

#10-3 AWG#14-2/0 AWG

460575 #10-3 AWG

VDC-26 AND VDCF26

200#14-2/0 AWG #6-3/0 AWG

230380/400/415

#10-3 AWG#14-2/0 AWG

460575 #10-3 AWG

TABLE 9 - LUG DATA (CONT'D)

JOHNSON CONTROLS 47

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 48: AIR-COOLED CONDENSER AND FLUID COOLER

WIRING DIAGRAMSAll electrical wiring connections should be made by a licensed electrical contractor in conformance with the national electri-cal code and local regulations which may apply.

Components:SD - Non-fused safety disconnect (handle on door)MC - Motor contractorsSS - Motor contractor surge suppressorsFUM - Motor fusesTR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocks

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 475 votls).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold.

FIGURE 10 - BASIC FACTORY WIRING - STANDARD, 1-6 FANS LONG - VDC AND VDCF

LD16230a

Legend Power Wiring Control Wiring

JOHNSON CONTROLS48

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 49: AIR-COOLED CONDENSER AND FLUID COOLER

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold.

Components:SD - Non-fused safety disconnect (handle on door)SWA - System 350 control switch (temperature type)SWB - System 350 stage modules (temperature type)Y350R - Power moduleSL - Outside Air SensorMC - Motor contractorsSS - Motor contractor surge suppressors

FUM - Motor fusesTR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocksSMC - Surface mount clip (Ships loose)

FIGURE 11 - TEMP-CONTROLLED FAN CYCLING, 2-6 FANS LONG - VDC

LD16231a

Legend Power Wiring Control Wiring

JOHNSON CONTROLS 49

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 50: AIR-COOLED CONDENSER AND FLUID COOLER

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.

Components:SD - Non-fused safety disconnect (handle on door)SWA - System 350 control switch (temperature type)SWB - System 350 stage modules (temperature type)Y350R - Power moduleSL - Outside air sensorMC - Motor contractorsSS - Motor contractor surge suppressors

FUM - Motor fusesTR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocksSMC - Surface Mount clip (Ships loose)

FIGURE 12 - TEMP-CONTROLLED FAN CYCLING, 2-6 FANS LONG, DOUBLE-WIDE, FANS WIRED INDIVIDU-ALLY - VDC

LD16232a

Legend Power Wiring Control Wiring

JOHNSON CONTROLS50

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 51: AIR-COOLED CONDENSER AND FLUID COOLER

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold.

Components:SD - Non-fused safety disconnect (handle on door)SWA - System 350 control switch (temperature type)SWB - System 350 stage modules (temperature type)Y350R - Power moduleSL - Outside air sensor (sensing fluid leaving temperature)MC - Motor contractorsSS - Motor contractor surge suppressors

FUM - Motor fusesTR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocksIM - Imersion well 11A-601R (ships loose)

FIGURE 13 - TEMP-CONTROLLED FAN CYCLING, 2-6 FANS LONG - VDCF

LD16238a

Legend Power Wiring Control Wiring

JOHNSON CONTROLS 51

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 52: AIR-COOLED CONDENSER AND FLUID COOLER

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.

Components:SD - Non-fused safety disconnect (handle on door)SWA - System 350 control switch (temperature type)SWB - System 350 stage modules (temperature type)Y350R - Power moduleSL - Outside air sensor (sensing fluid leaving Temperature)MC - Motor contractorsSS - Motor contractor surge suppressors

FUM - Motor fusesTR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocksIM - Imersion well 11A-601R (ships loose)

FIGURE 14 - TEMP-CONTROLLED FAN CYCLING, 2-6 FANS LONG, DOUBLE-WIDE, FANS WIRED INDIVIDU-ALLY - VDCF

LD16239a

Legend Power Wiring Control Wiring

JOHNSON CONTROLS52

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 53: AIR-COOLED CONDENSER AND FLUID COOLER

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold.

Components:SD - Non-fused safety disconnect (handle on door)P470 - JCI P470 control switch (pressure type)PT - Electronic pressure transducerMC - Motor contractorsSS - Motor contractor surge suppressorsFUM - Motor fuses

TR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocksNUT - 1/4" Flare x 1/4" OD solder (ships loose)

FIGURE 15 - PRESSURE-CONTROLLED FAN CYCLING, 2-5 FANS LONG - VDC

LD16233a

Legend Power Wiring Control Wiring

JOHNSON CONTROLS 53

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 54: AIR-COOLED CONDENSER AND FLUID COOLER

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.6. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold.

Components:SD - Non-fused safety disconnect (handle on door)P470 - JCI P470 control switch (pressure type)PT - Electronic pressure transducerMC - Motor contractorsSS - Motor contractor surge suppressorsFUM - Motor fuses

TR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocksNUT - 1/4" Flare x 1/4" OD solder (ships loose)

FIGURE 16 - PRESSURE-CONTROLLED FAN CYCLING, 6 FANS LONG - VDC

LD16234a

Legend Power Wiring Control Wiring

JOHNSON CONTROLS54

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 55: AIR-COOLED CONDENSER AND FLUID COOLER

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC con-

densers to operate when the chiller compressor starts.3. Standard motors are 2.0 hp, 1150 rpm, 3 phase, 60 Hz with built-in thermal overload protection.4. Supply voltage must be specified on purchase order.5. All field wiring must meet NEC and local codes.

Components:SD - Non-fused safety disconnect (handle on door)P470 - JCI P470 control switch (pressure type)PT - Electronic pressure transducerMC - Motor contractorsSS - Motor contractor surge suppressorsFUM - Motor fuses

TR - Control circuit transformerFUT - Transformer fusesFUC - Control circuit fuseTB - Terminal blocksNUT - 1/4" Flare x 1/4" OD solder (ships loose)

FIGURE 17 - PRESSURE-CONTROLLED FAN CYCLING, 2-6 FANS LONG, DOUBLE-WIDE, FANS WIRED INDI-VDUALY - VDC

LD16235a

JOHNSON CONTROLS 55

SECTION 5 - TECHNICAL DATAFORM 195.29-NM1 ISSUE DATE: 10/12/2020

5

Page 56: AIR-COOLED CONDENSER AND FLUID COOLER

Components:SD - Non-fused safety disconnect (handle on door)MC - Motor contractorsSS - Motor contractor surge suppressorsFUM - Motor fusesTR - Control circuit transformerFUT - Transformer fuses

FUC - Control circuit fuseTB - Terminal blocksIC - Inverted contractorBP - Bypass contractorSS1 - VSD Bypass switch on doorRR - Run relay

NOTES:1. Power supply (by others) to be 3-phase, 60 Hz (200, 230, 460, or 575 volts) or 50 Hz (380, 400, or 415 volts).2. Compressor Interlock (by other) is 115 volts with 200, 230, 380, 400, 415, 460, or 575 volt supply. It allows the VDC condensers to operate

when the chiller compressor starts.3. Standard inverter-duty motors are 2.0 hp, 1150 rpm, 3-phase, 60 Hz with built-in thermal overload protection.4. VSD controller is not included and must be field provided.5. Temperature or pressure sensors for controls must be field provided and installed, if desired.6. Supply voltage must be specified on purchase order.7. All field wiring must meet NEC and local codes.8. Double-wide units with motors wired in pairs require the optional manifold kit or a customer-supplied manifold.9. WARNING – DO NOT connect Incoming AC power to output terminals. Severe damage to the drive will result.

FIGURE 18 - VSD-CONTROLLED FANS, 2-6 FANS LONG, DOUBLE-WIDE FANS WIRED IN PAIRS - VDC AND VDCF

JOHNSON CONTROLS56

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 5 - TECHNICAL DATA

Page 57: AIR-COOLED CONDENSER AND FLUID COOLER

SECTION 6 - COMMISSIONING

UNIT IDENTIFICATIONA nameplate permanently attached to the unit identi-fies air-cooled condenser unit information. Figures 19 through 22 on page 57 shows the information pro-vided. We recommend that the nameplate data be en-tered on the ID Plate Information graphic, Figures 19 through 22 on page 57, for reference when ordering parts.

Provide the MODEL and SERIAL NUM-BER from the nameplate and installation date when making inquiries about the unit or ordering replacement parts. If failure occurs provide the date of the failure.

START-UPCheck that the fan(s) are rotating in the right direction for draw through operation. If it is necessary to reverse rotation of the three phase motors, interchange any two electrical leads at the condenser fan contactor or main disconnect switch.

Be sure that all noncondensable gases are purged from each refrigerant circuit.

LD16226

FIGURE 19 - ID PLATE INFORMATION, VDC - MONTERREY, MEXICO

LD16228

FIGURE 20 - ID PLATE INFORMATION, VDCF - MONTERREY, MEXICO

LD16227

FIGURE 21 - ID PLATE INFORMATION, VDC - SAN ANTONIO, TX

LD16229

FIGURE 22 - ID PLATE INFORMATION, VDCF - SAN ANTONIO, TX

JOHNSON CONTROLS 57

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

6

Page 58: AIR-COOLED CONDENSER AND FLUID COOLER

THIS PAGE INTENTIONALLY LEFT BLANK.

JOHNSON CONTROLS58

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 6 - COMMISSIONING

Page 59: AIR-COOLED CONDENSER AND FLUID COOLER

SECTION 7 - UNIT OPERATION

STANDARD FAN CYCLINGAir-cooled condensers must operate at lower than de-sign ambient dry bulb temperature. A minimum oper-ating pressure must be maintained under all ambient operating conditions to ensure sufficient pressure and satisfactory system operation. Therefore, if air-cooled condenser operation below 40°F ambient temperature is required, refer to Fan Cycling Options on page 11 and Low Ambient Control Options on page 60.

The capacity of an air-cooled condenser is directly pro-portional to the TD, which is the temperature difference between the condensing temperature and the air dry bulb entering the condenser. A condenser is normally selected to operate on a “TD” suitable for summer am-bient temperature conditions. The capacity of this con-denser, however, is substantially increased when oper-ated with low ambient temperatures. The result of the increase in condenser capacity is to reduce the system head pressure. When the ambient temperature drops below a certain value, the head pressure falls below the point where the expansion valve cannot properly feed the evaporator and very poor or unsatisfactory system operation results.

On multiple fan units, individual fan sections can be cycled to not exceed nominal condenser capacity at low ambient conditions. Table 10 on page 59 provides minimum ambient temperatures for this method of con-trol. Table 11 on page 59 gives individual thermostat settings for all units referenced to various design tem-perature differences. In lieu of thermostats, fan cycling can be controlled by pressure switches connected to condenser inlet (hot gas) headers. This is recommend-ed for process applications. Contact Johnson Controls for special pricing.

TABLE 10 - MINIMUM AMBIENT TEMPERATURES FOR FAN CYCLING CONTROL

Type Of Condenser

Minimum Outside Temperature For 100% Capacity

Single Wide

No. Of Fans

Double Wide No. Of Fans

Design Temperature Difference (TD °F)

10 15 20 25 30

1, 2 4 71 62 53 43 363 6 62 49 37 25 144 8 54 38 22 8 05 10 45 26 5 0 06 12 38 15 0 0 0

TABLE 11 - TEMPERATURE SETTINGS FOR FAN CYCLINGSingle-Wide Double-Wide Temp

Settings (Stage)

Design temperature Difference (TD °F)Number of

FansNumber of

Fans 10 15 20 25 30

2 4 Setpoint (l) 77 72 67 62 57

3 6Setpoint (2) 72 64 58 51 44Offset (1) 5 8 9 11 13

4 8Setpoint (3) 67 58 49 40 32Offset (2) 7 9 11 15 17Offset (1) 10 14 18 22 25

5 10

Setpoint (4) 62 51 40 30 20Offset (3) 8 11 14 17 20Offset (2) 12 17 22 26 31Offset (1) 15 21 27 32 37

6 12

Setpoint (5) 58 44 32 20 9Offset (4) 9 14 17 20 23Offset (3) 14 20 26 31 35Offset (2) 17 25 31 38 43Offset (I) 19 28 35 42 48

JOHNSON CONTROLS 59

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

7

Page 60: AIR-COOLED CONDENSER AND FLUID COOLER

VDC PRESSURE SETTING GUIDELINESWhen a YORK VDC is used as a remote condenser with a YCRL chiller, the VDC must be ordered and installed with the “Head Pressure Control by Pressure” option, which provides Johnson Controls model P470 pressure controllers factory mounted in the VDC con-trol panel. P470 controller operating manuals, included in the VDC control panel, provide guidance for field fan-staging setup.

Johnson Controls recommends the following pressure set points for general use; if excessive fan cycling is noted the final stage of cycling should be adjusted (deadband increased). The deadband proposed in these guidelines is set to 125 psi, which is the standard set-ting for Johnson Controls air-cooled R-410A units (YLAA, YCAL and YCRL).

Two-stage units (2-fan single-wide, 4-fan double-wide VDC)

• Stage 1, ON when any compressor is ON.

• Stage 2, ON at 380 psig, OFF at 255 psig.

Three-stage units (3-fan single-wide, 6-fan double-wide VDC)

• Stage 1, ON when any compressor is ON.

• Stage 2, ON at 380 psig, OFF at 255 psig.

• Stage 3, ON at 405 psig, OFF at 280 psig.

Four-stage units (4-fan single-wide, 8-fan double-wide VDC)

• Stage 1, ON when any compressor is ON.

• Stage 2, ON at 380 psig, OFF at 255 psig.

• Stage 3, ON at 405 psig, OFF at 280 psig.

• Stage 4, ON at 430 psig, OFF at 305 psig.

Compressor will unload when the discharge pressure reaches 565 psig.

LOW AMBIENT OPERATIONSince air-cooled condensers are often required to oper-ate over a wide range of ambient air temperatures and variable loading conditions, provision must be made to maintain the overall system balance. Any air-cooled condenser tends to run at a low head pressure when operating in a low ambient air temperature. Low head pressures can result in poor expansion valve operation, which will in turn cause poor system operation.

Within limits, air conditioning applications allow the operating head pressure to vary with the ambient air temperature without adversely affecting the system op-eration. The head pressure lower limit depends upon the required pressure drop across the thermostatic expan-sion valve. For normal air conditioning applications, the low pressure limit should correspond to a condens-ing temperature of 65° to 70°F. This corresponds to an ambient air temperature lower limit of approximately 55° to 60°F. Air conditioning may not be required at or below these ambient temperatures. However, to ensure sufficient receiver pressure during compressor start-up, it is recommended that a high-pressure cut-in switch be used to allow the head pressure to rise before the condenser fan starts.

Many applications, such as commercial refrigera-tion, require operation below the above ranges (55° to 60°F). Johnson Controls offers fan cycling to maintain a desired condensing pressure.

LOW AMBIENT CONTROL OPTIONS

Fan Cycling ControlOn multiple fan units, individual fan sections can be controlled to prevent exceeding nominal condenser capacity at low ambient conditions. Table 10 on page 59 provides minimum ambient temperatures for ef-fective fan cycle control. Lower ambient temperatures than listed are not recommended for this method of control. Table 11 on page 59 gives temperature set-tings for all units referenced to various design tempera-ture differences.

Head Pressure Control by Temperature on page 11 for VDCs and VDCFs and Head Pressure Control by Pressure on page 12 for VDCs can be used to con-trol individual fans in single-wide models and individ-ual fans or pairs of fans in double-wide models.

Head Pressure Control (VSD Ready) on page 12 for VDCs and VDCFs can be used to vary speeds of all fans in unison.

JOHNSON CONTROLS60

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 7 - UNIT OPERATION

Page 61: AIR-COOLED CONDENSER AND FLUID COOLER

A99 TEMPERATURE SENSOR DESCRIPTION AND MOUNTING

Description

LD14536

FIGURE 23 - A99B TEMPERATURE SENSORS

The A99B Series Temperature Sensors are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors are splashproof and are designed to measure temperature in a variety of refrigeration applications. Several accessories allow easy tailoring of the temper-ature sensor to various mounting configurations.

Applications include temperature sensing for freezers and coolers, as well as in defrost termination sensing, space and return air temperature sensing, and condens-er fan cycling.

AccessoriesSee Figure 24 on page 61 for A99B series acces-sories.

All accessories are available through local Johnson Control/Penn representatives using part numbers shown.

OperationThe A99B sensor incorporates a PTC silicon sensing element whose resistance increases with an increase in temperature. The sensor has a reference resistance of 1035 ohms at 77°F (25°C). Each element is calibrated according to a standard graph, as shown in Table 12 on page 62.

LD14535

in.(mm)

1/4 (6)

2 (50)

FIGURE 25 - A99B SENSOR DIMENSIONS

FIGURE 24 - A99B SENSOR ACCESSORIES

4 1/2(113.5)

1 11/16(42) 1 3/8

(35)

EMTConduitAdapter

ADP11A-600R1/2(13)

Sun ShieldSHL10A-603R

9 1/8(229)

1 3/4 (44)

4 5/16(110)

PVC EnclosureBOX10A-600R

3(76) Dia.

3/8(9.3)

4 3/4(119)

7/8(23)

1(25.4)

1(25.4)

Surface Mount ClipA99-CLP-1

1/4 (6)

Immersion WellWEL 11A-601R

LD14537

JOHNSON CONTROLS 61

SECTION 7 - UNIT OPERATIONFORM 195.29-NM1 ISSUE DATE: 10/12/2020

7

Page 62: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 12 - RESISTANCE VS. TEMPERATURE

°F (°C) RESISTANCE IN OHMS °F (°C) RESISTANCE

IN OHMS-40 (-40) 613 113 (45) 1195-31 (-35) 640 122 (50) 1237-22 (-30) 668 131 (55) 1279-13 (-25) 697 140 (60) 1323-4 (-20) 727 149 (65) 13685 (-15) 758 158 (70) 1413

14 (-10) 789 167 (75) 145923 (-5) 822 176 (80) 150632 (0) 855 185 (85) 155441 (5) 889 194 (90) 1602

50 (10) 924 203 (95) 165259 (15) 960 212 (100) 170268 (20) 997 221 (105) 175377 (25) 1035 230 (110) 180486 (30) 1074 239 (115) 185695 (35) 1113 248 (120) 1908

104 (40) 1153

Temperature Sensor Mounting - VDCAir-cooled condenser ambient air temperature sensor mounting should use the surface mounting clip pro-vided inside the control box and observe the following guidelines:

• Sensor can be mounted in any position.• Locate in an area that represents a steady tempera-

ture and air mixing.• Do not mount near excessive vibration or electri-

cal noise.• For outdoor applications avoid mounting in direct

sunlight. Mounting on the north side of the unit is preferred, but if not possible use a sun shield.

Temperature Sensor Mounting - VDCFFluid coolers sensing liquid outlet temperature use the immersion well provided inside the control box and observe the following guidelines:

• Select a location in the outlet pipe line. A 1/2 in. opening is required to braze the immersion well. The pipe diameter must be greater than 3 in.

• Perform a leak test on the braze joint before put-ting system into operation.

• Use thermally conductive paste inside the immer-sion well.

• Loosen the set screw in the immersion well and thread the spring, then the bushing, onto the sen-sor lead.

• At least one-half of the bushing is inserted into the immersion well (bushing will compress spring) and tighten the set screw against the bushing.

Mounting Using an Immersion Well - VDCF1. Select the mounting location in the pipe line. A

1/2", 14 NPT, opening is required to properly in-stall the immersion well (WEL11A-601R). The pipe’s diameter must be greater than the length of the well probe.

2. Insert an appropriate amount of thermally con-ductive paste in the well.

3. Install the immersion well. Tighten hex nut se-curely using a wrench.

Tightenwith Wrench

1/2 inch 14 NPTOpening

LD14539

FIGURE 26 - INSTALLING THE IMMERSION WELL

4. Using a straight slot screwdriver, loosen the set screw at top of the immersion well.

5. Thread the spring, then the bushing, onto the sen-sor lead.

Sensor Lead.

LD14538

FIGURE 27 - INSERT SENSOR, SPRING AND BUSHING

6. Insert sensor, spring, and bushing into well so that at least one-half of the bushing is inserted into the well, as shown in Figure 27 on page 62 (bush-ing will compress the spring).

7. Tighten the set screw against the bushing.

JOHNSON CONTROLS62

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 7 - UNIT OPERATION

Page 63: AIR-COOLED CONDENSER AND FLUID COOLER

Temperature Sensor Replacement PartsSee Table 13 on page 63 for temperature sensor product code numbers.

PRESSURE TRANSDUCERS MOUNTING

LD14541

FIGURE 28 - P499 ELECTRONIC PRESSURE TRANSDUCERS

Condensers sensing inlet pressure use the 1/4" SAE flare nut provided inside the control box and observe the following guidelines:

• Select a location in the inlet pipe line and braze the 1/4" SAE flare nut.

• Hand thread the transducer to the pressure tap point.

• Tighten the connection using the wrench flats on the transducer to avoid damaging it.

• Perform a leak test on the braze joint before put-ting system into operation.

• Use only the shielded wire harness provided.

Red Wire = SUPPLY

White Wire = OUTPUTBlack Wire = COMMON

24VCOM

VDC

SEN

CONTROLLER LD14540

FIGURE 29 - PRESSURE TRANSDUCER WIRING

TABLE 13 - REPLACEMENT TEMPERATURE SENSOR PRODUCT CODE NUMBERSPRODUCT

CODE NUMBER

DESCRIPTION

A99BA-200C PTC Silicon Sensor with Shielded Cable; Cable length: 6-1/2 ft (2 m); Range: -40 to 212°F (-40 to 100°C).A99BB-25C PTC Silicon Sensor with PVC Cable; Cable length: 9-3/4 in. (0.25 m); Range: -40 to 212°F (-40 to 100°C).

A99BB-200C PTC Silicon Sensor with PVC Cable; Cable length: 6-1/2 ft (2 m); Range: -40 to 212°F (-40 to 100°C).

A99BB-200D PTC Silicon Sensor with PVC Cable Bulk Pack; contains 100 A99BB-200 sensors. Individual sensor cable length: 6-1/2 ft (2 m); Range: -40 to 212°F (-40 to 100°C).

A99BB-300C PTC Silicon Sensor with PVC Cable; Cable length: 9-3/4 ft (3 m); Range: -40 to 212°F (-40 to 100°C).A99BB-500C PTC Silicon Sensor with PVC Cable; Cable length: 16-3/8 ft (5 m); Range: -40 to 212°F (-40 to 100°C).A99BB-600C PTC Silicon Sensor with PVC Cable; Cable length: 19-1/2 ft (6 m); Range: -40 to 212°F (-40 to 100°C).

A99BC-25C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length: 9-3/4 in. (0.25 m); Range: -40 to 248°F (-40 to 120°C).

A99BC-300C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length: 9-3/4 ft (3 m); Range: -40 to 248°F (-40 to 120°C).

A99BC-1500C PTC Silicon Sensor with High Temperature Silicon Cable; Cable length: 49 ft (15 m); Range: -40 to 248°F (-40 to 120°C).

Note: All sensors are available through local Johnson Controls / Penn representatives using part numbers shown.

JOHNSON CONTROLS 63

SECTION 7 - UNIT OPERATIONFORM 195.29-NM1 ISSUE DATE: 10/12/2020

7

Page 64: AIR-COOLED CONDENSER AND FLUID COOLER

TABLE 14 - PRESSURE VS. VOLTAGEP499 RCP-105C (0-500PSIG) TRANSDUCER P499 RCP-107C (0-700PSIG) TRANSDUCER

VOLTAGE (VDC) PRESSURE (PSIG) VOLTAGE (VDC) PRESSURE (PSIG)0.5 0 0.5 01.0 62.5 1.0 93.751.5 125 1.5 187.52.0 187.5 2.0 281.252.5 250 2.5 3753.0 312.5 3.0 468.753.5 375 3.5 562.54.0 437.5 4.0 656.254.5 500 4.5 750

VSD INVERTER WIRINGReference WIRING DIAGRAMS FIGURE 18: Three-phase power supplied to the inverter, LINE TO VSD, shall be run in a conduit separate from the power out-put conduit, LOAD FROM VSD. Each conduit shall

contain only the three-phase power wires and a ground wire with no additional wiring. The VSD ground wire in each conduit shall be grounded to its own ground lug located in the VDC motor control panel.

TABLE 15 - VSD INVERTER CONNECTIONSVDC CONTROL PANEL TERMINAL BLOCK, TB3

TERMINAL BLOCK LUGSU1, V1, W1 U2, V2, W2

DRIVE MANUFACTURER INPUT TERMINALS OUTPUT TERMINALSABB U1, V1, W1 U2, V2, W2

Eaton L1, L3, L3 U, V, WDanfoss L1, L3, L3 U, V, W

Schneider L1, L3, L3 U, V, W

Note: 1. Connect VSD inverter drive terminals to the appropriate control panel terminal block lug.

�� The input power, motor and control wiring are through separate conduit runs.

�� NO power factor compensation capacitors are in the motor cable.

�� NO tools or foreign objects (such as drill shav-ings) are inside the drive.

�� NO alternate power source for the motor is con-nected, and no voltage is applied to the output of the drive.

�� All connections are tightened per specification, and all wiring is correct.

VSD Inverter Installation Checklist�� Installation environment conforms to the drive’s specifications for ambient conditions.

�� The drive is mounted securely.

�� The drive has adequate ventilation.

�� The motor and driven equipment are ready to be run.

�� The correct RFI filter screws for the power source are used.

�� The drive and motor are properly grounded.

�� The input voltage matches the drive’s rating.

JOHNSON CONTROLS64

FORM 195.29-NM1 ISSUE DATE: 10/12/2020SECTION 7 - UNIT OPERATION

Page 65: AIR-COOLED CONDENSER AND FLUID COOLER

SECTION 8 - MAINTENANCE

GENERALWhen our Johnson Controls remote Air-Cooled Con-denser or Fluid Cooler has been properly installed, it will require little in the way of regular service or main-tenance. A regular schedule of periodic maintenance should be established, which includes a complete an-nual checkup.

Motors are equipped with sealed bearings; no motor grease is required.

CLEANINGWhen visual inspection so indicates, the condenser coil should be cleaned with a vacuum cleaner, compressed air or brush to clear dust and debris which will impede

performance. A clean coil saves energy. Consult the material Safety Data Sheet to determine a cleaning so-lution that is compatible with all parts of the unit. If the unit's casing shows signs of rust, the rust spots should be cleaned and sprayed with a rust preventative.

RECOMMENDED SPARE PARTSSee Renewal Parts Guide, Form 195.29-RP1 for re-placement and recommended spare parts for earlier as well as current models.

JOHNSON CONTROLS 65

FORM 195.29-NM1 ISSUE DATE: 10/12/2020

8

Page 66: AIR-COOLED CONDENSER AND FLUID COOLER

5000 Renaissance Drive, New Freedom, Pennsylvania USA 17349 1-800-524-1330 Subject to change without notice. Printed in USACopyright © by Johnson Controls 2020 www.johnsoncontrols.com ALL RIGHTS RESERVEDForm 195.29-NM1 (1020)Issue Date: October 12, 2020 Supersedes: 195.29-NM1 (615)