35
Air Conditioning Technical Data EEDEN14-131 AZQS-BV1

Air Conditioning Technical Data - Tinlavir€¦ · • Outdoor Unit • AZQS-BV1 1 2 • Split - Sky Air • AZQS-BV1 1 Features k i S n U - 1 r V o tB o - i d S l t Q upZ OSA•

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • Air Conditioning

    Technical Data

    EEDEN14-131

    AZQS-BV1

  • • Split - Sky Air • AZQS-BV1 1

    • Outdoor Unit • AZQS-BV1

    TABLE OF CONTENTSAZQS-BV1

    1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Nominal Capacity And Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    4 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    5 Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    6 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Cooling Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Heating Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Capacity Correction Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    7 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    8 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    9 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    10 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Wiring Diagrams - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    11 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Sound Pressure Spectrum - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Sound Pressure Spectrum - Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Sound Pressure Spectrum Quiet Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    12 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    13 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

  • • Outdoor Unit • AZQS-BV1

    1

    2

    1 Features

    door Uni it - Sk S-BV1

    Out Spl AZQ • Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall

    • Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency

    • Outdoor units for pair application

    • Seasonal efficiency, optimized for all seasons.

    • Seasonal efficiency gives an indication on how efficient an air conditioner operates over an entire heating or cooling season.

    Inverter Auto cooling-heating

    changeover

    • Split - Sky Air • AZQS-BV1

  • 3

    2

    • Outdoor Unit • AZQS-BV1

    2 Specifications

    Notes

    (1) EER/COP according to Eurovent 2012

    Notes

    (1) EER/COP according to Eurovent 2012

    2-1 Nominal Capacity And Nominal Input *ACQ71C/AZQS71BV1 ACQ100C/AZQS100BV1 ACQ125C/AZQS125BV1Cooling capacity Nom. kW 6.8 9.5 12.1Heating capacity Nom. kW 7.50 10.80 13.5Seasonal efficiency (according to EN14825)

    Cooling Energy label B B -Pdesign kW 6.33 9.50 -SEER 4.65 4.65 -Annual energy consumption

    kWh 476 716 -

    Heating (Average climate)

    Energy label A A -Pdesign kW 6.33 7.60 -SCOP 3.80 3.80 -Annual energy consumption

    kWh 2,332 2,800 -

    Nominal efficiency (cooling at 35°/27° nominal load, heating at 7°/20° nominal load)

    EER 3.31 3.21 3.01COP 3.61 3.61 3.41Annual energy consumption kWh 1,027 1,480 2,010Energy label Cooling A A B

    Heating A A B

    2-2 Nominal Capacity And Nominal Input ABQ71B/AZQS71BV1Cooling capacity Nom. kW 6.8 (3)Heating capacity Nom. kW 7.5 (4)Seasonal efficiency (according to EN14825)

    Cooling Energy label BPdesign kW 6.80SEER 4.65Annual energy consumption

    kWh 512

    Heating (Average climate)

    Energy label APdesign kW 6.33SCOP 3.41Annual energy consumption

    kWh 2,599

    Nominal efficiency (cooling at 35°/27° nominal load, heating at 7°/20° nominal load)

    EER 3.01COP 3.61Annual energy consumption kWh 1,130Energy label Cooling B

    Heating A

    2-3 Nominal Capacity And Nominal Input ABQ125A/AZQS125BV1 ABQ140A/AZQS140BV1Cooling capacity Nom. kW 12.1 13.0Heating capacity Nom. kW 13.5 15.5Seasonal efficiency (according to EN14825)

    Cooling Energy label -Pdesign kW -SEER -Annual energy consumption

    kWh -

    Heating (Average climate)

    Energy label -Pdesign kW -SCOP -Annual energy consumption

    kWh -

    • Split - Sky Air • AZQS-BV1 3

  • • Outdoor Unit • AZQS-BV1

    2

    4

    2 Specifications

    Notes

    (1) EER/COP according to Eurovent 2012

    Notes

    (1) EER/COP according to Eurovent 2012

    Nominal efficiency (cooling at 35°/27° nominal load, heating at 7°/20° nominal load)

    EER 2.91 3.01COP 3.41Annual energy consumption kWh 2,079 2,159Energy label Cooling C B

    Heating B

    2-4 Nominal Capacity And Nominal Input AHQ71C/AZQS71BV1 AHQ100C/AZQS100BV1 AHQ125C/AZQS125BV1 AHQ140C/AZQS140BV1Cooling capacity Nom. kW 6.8 9.5 12.1 13.0Heating capacity Nom. kW 7.5 10.8 13.5 15.5Seasonal efficiency (according to EN14825)

    Cooling Energy label B -Pdesign kW 6.80 9.50 -SEER 4.65 4.60 -Annual energy consumption

    kWh 511 723 -

    Heating (Average climate)

    Energy label A -Pdesign kW 6.33 7.60 -SCOP 3.80 -Annual energy consumption

    kWh 2,332 2,800 -

    Nominal efficiency (cooling at 35°/27° nominal load, heating at 7°/20° nominal load)

    EER 3.03 2.62 2.63 3.01COP 3.05 3.41 3.61 3.41Annual energy consumption kWh 1,120 1,810 2,300 2,159Energy label Cooling B D B

    Heating D B A B

    2-5 Technical Specifications AZQS71BV1 AZQS100BV1 AZQS125BV1 AZQS140BV1Capacity control Method Inverter controlledCasing Colour - Ivory white

    Material - Painted galvanized steel plateDimensions Unit Height mm 770 990 1,430

    Width mm 900 940Depth mm 320

    Packed unit Height mm 900 1,170 1,610Width mm 980 1,015Depth mm 420 422

    Weight Unit kg 67 81 102Packed unit kg 71 88 108

    Heat exchanger Length mm 857 -Rows Quantity 2 -Fin pitch mm 1.4 -Passes Quantity 8 -Face area m² 0.641 -Stages Quantity 34 -Empty tubeplate hole

    Quantity 0 -

    Tube type Hi-XSS (8) -Fin Type WF fin

    Treatment Anti-corrosion treatment (PE)

    2-3 Nominal Capacity And Nominal Input ABQ125A/AZQS125BV1 ABQ140A/AZQS140BV1

    • Split - Sky Air • AZQS-BV1

  • 3

    2

    • Outdoor Unit • AZQS-BV1

    2 Specifications

    Compressor Quantity 1Model 2YC63DXD -Type Hermetically sealed swing compressorOutput W 1,700.0 -Starting method Inverter driven -

    Fan Type Propeller fanDischarge direction HorizontalQuantity 1 2Air flow rate Cooling Nom. m³/min 52.0 76 77 83

    Super low

    m³/min -cfm -

    Heating Nom. m³/min 48.0 83 62Super low

    m³/min -cfm -

    Fan motor Quantity 1 2Model KFD-325-70-8A Brushless DC motorOutput W 70 200 94Drive Direct driveSpeed Steps 8 -

    Cooling Nom. rpm 800 -Super low

    rpm -

    Heating Nom. rpm 745 -Super low

    rpm -

    Sound power level Cooling Nom. dBA 64 70 71 70Sound pressure level Cooling Nom. dBA 48 53 54 53

    Silent operation dBA 43 -Heating Nom. dBA 50 57 58 54Night quiet mode Level 1 dBA - 49

    Operation range Cooling Ambient

    Min. °CDB -5.0Max. °CDB 46.0

    Heating Ambient

    Min. °CWB -15.0Max. °CWB 15.5

    Refrigerant Type R-410ACharge kg 2.75 2.9 4.0Control Expansion valve (electronic type)GWP 1,975Circuits Quantity 1

    Refrigerant oil Type FVC50KCharged volume l 0.75 0.9 1.35

    2-5 Technical Specifications AZQS71BV1 AZQS100BV1 AZQS125BV1 AZQS140BV1

    • Split - Sky Air • AZQS-BV1 5

  • • Outdoor Unit • AZQS-BV1

    2

    6

    2 Specifications

    Notes

    (1) See separate drawings for electrical data (2) Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 61000-3-12: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current \>16A and ≤ 75A per phase (3) PED unit category: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (4) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (5) Short-circuit power (6) RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (7) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).

    Piping connections Liquid Quantity 1Type Flare connectionOD mm 9.52

    Gas Quantity 1Type Flare connectionOD mm 15.9

    Drain Quantity 3 5Type HoleID mm -OD mm 26

    Piping length OU - IU Min. m 5Max. m 30 50

    System Equivalent

    m 40 70

    Chargeless

    m 30

    Additional refrigerant charge kg/m See installation manualLevel difference IU - OU Max. m 15.0 30.0

    IU - IU Max. m - 0.5Heat insulation Both liquid and gas pipes

    Defrost method Pressure equalising Reversed cycleDefrost control Sensor for outdoor heat exchanger temperatureSafety devices Item 01 High pressure switch

    02 Fan motor thermal protection03 Fuse

    2-6 Electrical Specifications AZQS71BV1 AZQS100BV1 AZQS125BV1 AZQS140BV1Power supply Name V1

    Phase 1~Frequency Hz 50Voltage V 220-240Voltage range Min. % -10

    Max. % 10Current Nominal running

    current (RLA)Cooling A 16.20 -

    Zmax List Complies to EN6100-3-3

    Complies to EN61000-3-12

    Recommended fuses A 20 32Current - 50Hz Maximum fuse amps (MFA) A 20 -Current - 60Hz Maximum fuse amps (MFA) A -Wiring connections For power supply Remark - See installation manual outdoor unit

    For connection with indoor

    Remark - See installation manual outdoor unit

    Power supply intake Outdoor unit only

    2-5 Technical Specifications AZQS71BV1 AZQS100BV1 AZQS125BV1 AZQS140BV1

    • Split - Sky Air • AZQS-BV1

  • 3

    3

    • Outdoor Unit • AZQS-BV1

    3 Electrical data3 - 1 Electrical Data

    • Split - Sky Air • AZQS-BV1 7

  • • Outdoor Unit • AZQS-BV1

    4

    8

    4 Options4 - 1 Options

    • Split - Sky Air • AZQS-BV1

  • 3

    5

    • Outdoor Unit • AZQS-BV1

    5 Combination table5 - 1 Combination Table

    • Split - Sky Air • AZQS-BV1 9

  • • Outdoor Unit • AZQS-BV1

    6

    10

    6 Capacity tables6 - 1 Cooling Capacity Tables

    • Split - Sky Air • AZQS-BV1

  • 3

    6

    • Outdoor Unit • AZQS-BV1

    6 Capacity tables6 - 1 Cooling Capacity Tables

    • Split - Sky Air • AZQS-BV1 11

  • • Outdoor Unit • AZQS-BV1

    6

    12

    6 Capacity tables6 - 1 Cooling Capacity Tables

    • Split - Sky Air • AZQS-BV1

  • 3

    6

    • Outdoor Unit • AZQS-BV1

    6 Capacity tables6 - 1 Cooling Capacity Tables

    • Split - Sky Air • AZQS-BV1 13

  • • Outdoor Unit • AZQS-BV1

    6

    14

    6 Capacity tables6 - 2 Heating Capacity Tables

    • Split - Sky Air • AZQS-BV1

  • 3

    6

    • Outdoor Unit • AZQS-BV1

    6 Capacity tables6 - 2 Heating Capacity Tables

    • Split - Sky Air • AZQS-BV1 15

  • • Outdoor Unit • AZQS-BV1

    6

    16

    6 Capacity tables6 - 2 Heating Capacity Tables

    • Split - Sky Air • AZQS-BV1

  • 3

    6

    • Outdoor Unit • AZQS-BV1

    6 Capacity tables6 - 2 Heating Capacity Tables

    • Split - Sky Air • AZQS-BV1 17

  • • Outdoor Unit • AZQS-BV1

    6

    18

    6 Capacity tables6 - 3 Capacity Correction Factor

    • Split - Sky Air • AZQS-BV1

  • 3

    7

    • Outdoor Unit • AZQS-BV1

    7 Dimensional drawings7 - 1 Dimensional Drawings

    • Split - Sky Air • AZQS-BV1 19

  • • Outdoor Unit • AZQS-BV1

    7

    20

    7 Dimensional drawings7 - 1 Dimensional Drawings

    • Split - Sky Air • AZQS-BV1

  • 3

    8

    • Outdoor Unit • AZQS-BV1

    8 Centre of gravity8 - 1 Centre of Gravity

    • Split - Sky Air • AZQS-BV1 21

  • • Outdoor Unit • AZQS-BV1

    8

    22

    8 Centre of gravity8 - 1 Centre of Gravity

    • Split - Sky Air • AZQS-BV1

  • 3

    9

    • Outdoor Unit • AZQS-BV1

    9 Piping diagrams9 - 1 Piping Diagrams

    • Split - Sky Air • AZQS-BV1 23

  • • Outdoor Unit • AZQS-BV1

    10

    24

    10 Wiring diagrams10 - 1 Wiring Diagrams - Single Phase

    • Split - Sky Air • AZQS-BV1

  • 3

    10

    • Outdoor Unit • AZQS-BV1

    10 Wiring diagrams10 - 1 Wiring Diagrams - Single Phase

    • Split - Sky Air • AZQS-BV1 25

  • • Outdoor Unit • AZQS-BV1

    11

    26

    11 Sound data11 - 1 Sound Power Spectrum

    • Split - Sky Air • AZQS-BV1

  • 3

    11

    • Outdoor Unit • AZQS-BV1

    11 Sound data11 - 2 Sound Pressure Spectrum - Cooling

    • Split - Sky Air • AZQS-BV1 27

  • • Outdoor Unit • AZQS-BV1

    11

    28

    11 Sound data11 - 3 Sound Pressure Spectrum - Heating

    • Split - Sky Air • AZQS-BV1

  • 3

    11

    • Outdoor Unit • AZQS-BV1

    11 Sound data11 - 4 Sound Pressure Spectrum Quiet Mode

    • Split - Sky Air • AZQS-BV1 29

  • • Outdoor Unit • AZQS-BV1

    12

    30

    12 Installation12 - 1 Installation Method

    • Split - Sky Air • AZQS-BV1

  • 3

    12

    • Outdoor Unit • AZQS-BV1

    12 Installation12 - 1 Installation Method

    • Split - Sky Air • AZQS-BV1 31

  • • Outdoor Unit • AZQS-BV1

    13

    32

    13 Operation range13 - 1 Operation Range

    3D076504

    ZQS-

    Out

    door

    tem

    p.(°

    CDB)

    Ope

    ratio

    nra

    nge

    Allo

    wab

    lera

    nge

    ofop

    erat

    ion

    (pul

    l-dow

    n)

    Indoor temp. (°CWB)

    (Cooling)

    (Heating)

    Indoor temp. (°CDB)

    Out

    door

    tem

    p.(°

    CWB)

    Ope

    ratio

    nra

    nge

    Allo

    wab

    lera

    nge

    ofop

    erat

    ion

    (war

    min

    g-up

    )

    Notes:1 Depending on operation and installation conditions, the indoor unit can change over to

    freeze-up operation (indoor de-icing).2 To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install

    the outdoor unit in a location not exposed to wind.3 In case of high humidity conditions (>92%) in this operation area, an RZQG model

    should be used instead of an RZQSG model. This to avoid freeze-up of the outdoor unit.

    A BV1

    • Split - Sky Air • AZQS-BV1

  • Daikin Europe N.V. participates in the Eu-rovent Certification programme for LiquidChilling Packages (LCP), Air handling units(AHU) and Fan coil units (FCU), Check on-going validity of certificate online: www.eu-rovent-certification.com or using:www.certiflash.com

    EED

    EN

    14-1

    31

    • 12/

    13 •

    Cop

    yrig

    ht D

    aiki

    n Th

    e pr

    esen

    t pub

    licat

    ion

    supe

    rsed

    es E

    EDEN

    13-1

    31The present leaflet is drawn up by way of information only and does notconstitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V.has compiled the content of this leaflet to the best of its knowledge. Noexpress or implied warranty is given for the completeness, accuracy, re-liability or fitness for particular purpose of its content and the productsand services presented therein. Specifications are subject to changewithout prior notice. Daikin Europe N.V. explicitly rejects any liability forany direct or indirect damage, in the broadest sense, arising from or re-lated to the use and/or interpretation of this leaflet. All content is copy-righted by Daikin Europe N.V.

    BARCODE Daikin products are distributed by:

    Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

    Air ConditioningTechnical DataAZQS-BV1

    1 Features2 Specifications2-1 Nominal Capacity And Nominal Input2-2 Nominal Capacity And Nominal Input2-3 Nominal Capacity And Nominal Input2-4 Nominal Capacity And Nominal Input2-5 Technical Specifications2-6 Electrical Specifications

    3 Electrical data4 Options5 Combination table6 Capacity tables6 - 1 Cooling Capacity Tables6 - 2 Heating Capacity Tables6 - 3 Capacity Correction Factor

    7 Dimensional drawings8 Centre of gravity9 Piping diagrams10 Wiring diagrams10 - 1 Wiring Diagrams - Single Phase

    11 Sound data11 - 1 Sound Power Spectrum11 - 2 Sound Pressure Spectrum - Cooling11 - 3 Sound Pressure Spectrum - Heating11 - 4 Sound Pressure Spectrum Quiet Mode

    12 Installation12 - 1 Installation Method

    13 Operation range