Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Model PUHY-P250YHM-APFD-P250VM-EPFD-P500VM-E
DATA BOOK
AIR CONDITIONERS
CONTENTS
1. Specifications1-1 Main Features1-2 List of Possible Combinations of Indoor and Outdoor Units1-3 Unit Specifications
2. Capacity Curves2-1 Cooling Capacity2-2 Cooling Input2-3 Part Load Performance2-4 SHF Curves2-5 Correction by refrigerant piping length2-6 Operation limit
3. Sound Levels3-1 Noise Level3-2 NC Curves3-3 Fan Characteristics Curves
4. External Dimensions 5. Electrical Wiring Diagrams 6. Refrigerant Circuit Diagram And Thermal Sensor 7. System Design
7-1 Refrigerant Piping System7-2 Control Wiring7-3 Types of switch settings and setting methods7-4 Sample System Connection7-5 External input/output specifications7-6 System Rotation Control7-7 Notes on the use of optional accessories
8. Air Conditioning the Computer Room8-1 Main Features of the Floor-Duct Air Conditioners8-2 Features of air-conditioner for computer room8-3 Step-by-Step Plan for the Implementation of the Air-Conditioning8-4 Conditions for the Installation of Computer-Room Air Conditioners 8-5 Setting the Air conditioners8-6 Automatic Control of the Computer Room
9. Maintenance/Inspection9-1 Maintenance/Inspection Schedule
1123 4445688 991011 12 15 18 2020212224293434
35353536373840
4141
Close controlPUHY-P-YHM-APFD-P-VM-E
····························································································································
······························································
···········································································································································································
··········································································································
·····················································································
·········································································································································································································
···········································
···········································
·································································
······················································
···
···············································································································
····························································
··············································································
·····················
······················
···································
···································································
··············································································
1. Specifications1-1.Main Features
1
(1) List of Models
<10HP System>
<20HP System>
PUHY-P250YHM-A
10HP(Down flow): PFD-P250VM-E20HP(Down flow): PFD-P500VM-E
✻ PFD-type indoor units cannot be connected to outdoor units other than the ones specified above.✻ PFD-type indoor units and other types of indoor units cannot coexist in the same refrigerant system.✻ It is necessary to change pulley and V-belt when using it by the power supply frequency 60Hz.✻ For restrictions when the PFD-type indoor units are connected (related to the system), see P20.
When using a PFD-P250VM-E as an indoor unit, connect an outdoor unit PUHY-P250YHM-A to eachindoor unit and operate with a built-in remote control for the indoor unit.✻1: Bold line indicates refrigerant piping (gas/liquid). This system consists of single refrigerant circuit.✻2: Indicates TB3-type transmission line that connects the indoor and outdoor units.
This system consists of single refrigerant circuit.✻3: Indicates TB7-Type transmission line that allows the unit to communicate with the controller.
Outdoor Unit
} Indoor Unit
Outdoor Unit
G-50APUHY-P250YHM-A
Indoor Unit
PFD-P250VM-E
TB7 TB3 ✻2✻3
✻112V DC
M-NET
PAC-SC50KUA
UP
POWER RATING
MODEL
WEIGHT
SERIAL No.
2.11kg
POWER SUPPLY UNIT
MITSUBISHI ELECTRIC CORPORATION
PAC-SC50KUA
When using a PFD-P500VM-E as an indoor unit, connect 2 PUHY-P250YHM-A outdoor units toeach indoor unit and operate with a built-in remote control for the indoor unit.At factory shipment, this model of indoor unit is designed and set to accommodate a single refriger-ant circuit. Connection of two refrigerant circuits to the indoor unit requires setting change and pipe work.✻1: Bold line indicates refrigerant piping (gas/liquid). This system consists of two refrigerant circuits.✻2: Indicates TB3-type transmission line that connects the indoor and outdoor units.
This system consists of two refrigerant circuits.✻3: Indicates TB7-type transmission line that allows the unit to communicate with the controller.
Outdoor Unit
PUHY-P250YHM-A
Indoor UnitPFD-P500VM-E
TB7 TB3 ✻2
✻1
TB3
PUHY-P250YHM-A
TB7✻3
G-50A
12V DC
M-NET
PAC-SC50KUA
UP
POWER RATING
MODEL
WEIGHT
SERIAL No.
2.11kg
POWER SUPPLY UNIT
MITSUBISHI ELECTRIC CORPORATION
PAC-SC50KUA
Two refrigerant circuits
2
1-2. List of Possible Combinations of Indoor and Outdoor Units
✻1: Refer to the following pages for detailed specifications of each unit.✻2: They were measured at operation under the following conditions:
<Cooling> Indoor:27˚CDB/19˚CWB Outdoor:35˚CDB<Heating> Indoor:20˚CDB Outdoor: 7˚CDB/6˚CWB
Pipe length:7.5m, Height difference:0m
Model Name Indoor unit
Outdoor unit
Cooling Heating
System capacity kW 28.0 31.5
System Power input kW 9.3 9.1
System current A 16.7/15.9/15.4 16.4/15.5/15.1
10HP system
PFD-P250VM-E
PUHY-P250YHM-A
Cooling Heating
56.0 63.0
18.6 18.2
32.3/30.8/29.7 31.7/30.0/29.1
20HP system
PFD-P500VM-E
PUHY-P250YHM-A x 2
(2) Indoor Unit
3
1-3. Unit Specifications
28.0 31.53N ~ 380/400/415V 50/60Hz
Capacity
Model name
kWPower source
✻ 1
✻ 2
kWA
m3/minkW
kWkW
mm
dB(A)kg
Power inputCurrentFan
Airflow rateType ✕ Quantity
Motor outputTypeMotor outputCrankcase heater
Compressor
Refrigerant / LubricantExternal finish
High pressure protection
Inverter circuit (COMP./FAN)
CompressorFan
External dimension H x W x DProtectiondevices
Refrigerant piping diameter
High press. pipeLow press. pipe
Noise levelNet weight
1,710 (without legs 1,650) x 920 x 760
Propeller fan x 11850.46
Hermetic6.7
0.035 x 1
R410A/MEL32Heat exchanger Salt resistant fin
Over-heat protection, Over current protection ø9.52 Brazed (ø12.7 for over 90m)
ø22.2 Brazed
Pre-coated galvanized steel sheets (+ powder coating for -BS type) <MUNSEL 5Y 8/1 or similar>
High pres. Sensor & High pres. Switch at 4.15MPa
200
6.66.811.1/10.5/10.211.4/10.9/10.5
PUHY-P250YHM-A (-BS)connected with PFD series
Over heat protectionThermal switch
57
Cooling Heating
Note: *1. Cooling/Heating capacity indicates the maximum value at operation under the following condition.
*2. It is measured in anechoic room.** Installation/foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items shall be referred to the Installation Manual.
Indoor : 27˚CDB / 19˚CWBIndoor : 20˚CDBPipe length : 7.5m
Outdoor :Outdoor :Height difference : 0m
35˚CDB7˚CDB / 6˚CWB
<Cooling><Heating>
3N~380/400/415V(50Hz), 400/415V(60Hz)
PFD-P500VM-E
5.0Power source
kW
-
Power input
System capacity
A
m3/minPa
kg
dB(A)m
mm
Current
Heat exchanger
Fan
RefrigerantExternal finish
Type x QuantityAirflow rateExternal static pressure
kWMotor Output
Air filter
Refrigerant piping diameter✻ 2
Refrigerant piping allowable length
Gas pipeLiquid pipe
Cross fin (Aluminum plate fin and copper tube)
Sirocco fan x 2Sirocco fan x 1
ø 9.52 Brazed (ø 12.7 for over 90m)ø 22.2 Brazed
Single refrigerantcircuitTwo refrigerantcircuit
320
1,950 x 1,380 x 780
9.5/9.0/8.7
PFD-P250VM-E
2.5
kW 28.0 31.5 56.0 63.0
5.3/5.0/4.9
1601201204.42.2
380
59150
Gas pipeLiquid pipe ø 15.88 Brazed
ø 28.58 Brazed
Gas pipeLiquid pipe ø 9.52 Brazed (ø 12.7 for over 90m)
ø 22.2 Brazed
520
63150
R410AGalvanized steel plate (with polyester coating)
<MUNSEL 2.9GY 8.6/0.3(White) 7.2GB 3.2/5.3(Blue) or similar>
PP Honeycomb fabric (washable)
Thermal switch1,950 x 1,980 x 780
Protection devices (Fan)External dimensions H x W x D
Model name
Noise level
Net weight
Cooling Heating ✻ 1 ✻ 1Cooling Heating
Note: *1. Heating can be used only by the indoor warming-up.*2. At factory shipment, this model of indoor unit is designed and set to accommodate a single refrigerant circuit.
Connection of two refrigerant circuits to the indoor unit requires setting change and pipe work.** Installation/foundation work, electric connection work, duct work, insulation work, power source switch and other items are
not specified in the specifications.
(1) Outdoor Unit
4
2. Capacity Curves2-1. Cooling Capacity
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
-15 -10 -5 0 5 10 15 20 25 30 35 40 45
Indoor unit inlet temperature (˚CWB)
Indoor unit inlet temperature (˚CWB)
19
15
12
24
0.7
0.8
0.9
1.0
1.1
1.2
1.3
19
24
15
12
-15 -10 -5 0 5 10 15 20 25 30 35 40 45
Cap
acity
cor
rect
ion
coef
ficie
ntIn
put C
orre
ctio
n C
oeffi
cien
t
Outdoor unit inlet temperature (˚CDB)
Outdoor unit inlet temperature (˚CDB)
2-2. Cooling Input
✻ The correction curves indicate the values measured at the point where the compressor wasoperated at its maximum capacity.
✻ indicates the standard value.
2-3. Part Load Performance
5
10HP SystemIndoor Unit : PFD-P250VM-EOutdoor Unit : PUHY-P250YHM-A
CoolingCapacity (kW)
100%Capacity
90%Capacity
80%Capacity
70%Capacity
60%Capacity
50%Capacity
40%Capacity
40 ˚C 26.6 10.05 8.75 7.68 6.79 6.08 5.50 5.0435 ˚C 28.0 9.30 8.11 7.18 6.41 5.82 5.13 4.6030 ˚C 29.4 8.65 7.61 6.81 6.17 5.50 4.94 4.5225 ˚C 30.2 8.10 7.21 6.56 6.00 5.38 4.89 4.5020 ˚C 31.1 7.72 6.92 6.26 5.74 5.27 4.85 4.4715 ˚C 31.6 7.54 6.87 6.31 5.80 5.35 4.94 4.56
* Indoor air temperature condition: 27˚CDB/19˚CWB
20HP SystemIndoor Unit : PFD-P500VM-EOutdoor Unit : PUHY-P250YHM-A ✕ 2
CoolingCapacity (kW)
100%Capacity
90%Capacity
80%Capacity
70%Capacity
60%Capacity
50%Capacity
40%Capacity
30%Capacity
40 ˚C 53.2 20.09 17.46 15.24 13.49 12.08 10.94 10.07 8.3735 ˚C 56.0 18.60 16.19 14.30 12.77 11.51 10.11 9.05 8.0630 ˚C 58.8 17.30 15.24 13.58 12.24 10.79 9.76 8.92 7.6825 ˚C 60.5 16.19 14.47 13.06 11.79 10.59 9.67 8.79 7.5520 ˚C 62.2 15.44 13.88 12.53 11.42 10.48 9.64 8.52 7.4915 ˚C 63.3 15.07 13.83 12.63 11.58 10.67 9.84 8.62 7.64
* Indoor air temperature condition: 27˚CDB/19˚CWB
Outdoor unit inlettemp. (˚CDB)
System Power input (kW)
Outdoor unit inlettemp. (˚CDB)
System Power input (kW)
6
2-4. SHF Curves
Operation Temparature Range: Indoor : 12˚CWB~24˚CWB Outdoor : -15˚CDB~43˚CDB (RH : 30~80%)
Standard Point " " : Indoor : 27˚CDB/19˚CWB Outdoor : 35˚CDB/-
0.4
0.5
0.6
0.7
0.8
0.9
1
30 40 50 60 70 80
RH (%)
SH
F
130% 120%110%100% 90% 80% 70%
Standard Capacity Ratio
Standard Capacity Ratio
0.93
0.4
0.5
0.6
0.7
0.8
0.9
1
30 40 50 60 70 80
RH (%)
SH
F
130% 120%110%100% 90% 80% 70%
35 45 55 65 75
Indoor Temperature 27˚CDB
35 45 55 65 75
Indoor Temperature 24˚CDB
7
Operation Temparature Range: Indoor: 12˚CWB~24˚CWBOutdoor: -15˚CDB~43˚CDB(RH: 30~80%)
0.4
0.5
0.6
0.7
0.8
0.9
1
30 40 50 60 70 80
RH (%)
SH
F
120% 110% 100% 90% 80% 70%
Standard Capacity Ratio
Standard Capacity Ratio
0.4
0.5
0.6
0.7
0.8
0.9
1
30 40 50 60 70 80
RH (%)
SH
F
120% 110%100% 90% 80% 70%
35 45 55 65 75
Indoor Temperature 22˚CDB
35 45 55 65 75
Indoor Temperature 20˚CDB
8
2-5. Correction by refrigerant piping length
To obtain a decrease in cooling/heating capacity due to refrigerant piping extension, multiply by the capacitycorrection factor based on the refrigerant piping equivalent length in the table below.
• Cooling
Equivalent length = (Actual piping length to the farthest indoor unit) + (0.50 ✕ number of bent on the piping)m• How to obtain piping equivalent length
Piping equivalent length (m)
Cap
acity
cor
rect
ion
coef
ficie
nt
0.7
0.8
0.9
1
0 20 40 60 80 100 120 140 160 180
2-6. Operation limit
Indo
or te
mpe
ratu
re (
˚CW
B)
-15 0-5-10 5 10 15 20 25 30 35 40 451012
15
20
25
30
* The height between the Outdoor PUHY-P-YHM-A and Indoor could make the running temperature range narrow. For details refer to P19, 7-1 Refrigerant Piping System.
Outdoor temperature (˚CDB)
• Heating
Outdoor temperature (˚CWB)
Indo
or te
mpe
ratu
re (
˚CD
B)
30
25
20
15
10
5-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
9
3. Sound Levels3-1. Noise Level
1m
1m
Measurementlocation
SeriesNoise Level
(dB [Type A])
PFD-P250VM-E 59
PFD-P500VM-E 63
(1) Outdoor Unit
(2) Indoor Unit
Measurement location
1m
1m
SeriesNoise Level
(dB [Type A])
PUHY-P250YHM-A 57
10
3-2. NC Curves
PUHY-P250YHM-A
PFD-P250VM-E (External static pressure 120Pa) PFD-P500VM-E (External static
pressure 120Pa)63Hz 125Hz 250Hz 500Hz 2000Hz1000Hz 4000Hz 8000Hz dB(A)
82.8 70.5 65.6 57,0 55.1 51.1 44.7 37.9 63
(External static pressure 0Pa)
63Hz 125Hz 250Hz 500Hz 2000Hz1000Hz 4000Hz 8000Hz dB(A)
70.6 62.7 60.5 56.1 54.8 45.7 39.7 32.9 59
63Hz 125Hz 250Hz 500Hz 2000Hz1000Hz 4000Hz 8000Hz dB(A)
10
20
30
40
50
60
70
80
90
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz10
20
30
40
50
60
70
80
90
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
10
20
30
40
50
60
70
80
90
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OC
TAV
E B
AN
D P
RE
SS
UR
E L
EV
EL
(dB
) 0
dB =
20µ
Pa
OCTAVE BAND CENTER FREQUENCIES (Hz)
OC
TAV
E B
AN
D S
OU
ND
LE
VE
L (d
B)
OCTAVE BAND CENTER FREQUENCIES (Hz)
OC
TAV
E B
AN
D P
RE
SS
UR
E L
EV
EL
(dB
) 0
dB =
20µ
Pa
OCTAVE BAND CENTER FREQUENCIES (Hz)
Approximate minimum audible limit on continuous noise
Approximate minimum audible limit on continuous noise
Approximate minimum audible limit on continuous noise
Standard 35.0 57.0
NightMode 44.0 When Night Mode is set,the A/C system's capacity is limited. The system could return to normal operation from ���ht Mode automaticall in the case that the operation condition is severe.
50/60Hz
50/60Hz
59.0 62.0 60.0 54.0 50.5 46.0 41.024.558.0 53.5 44.0 39.0 36.5 32.5 31.0
Standard 50/60HzNight Mode 50/60Hz
11
3-3. Fan Characteristics Curves
PFD-P250VM-E
PFD-P500VM-E
: 50/60Hz, standard
: 50/60Hz, standard
0
100
200
300
400
500
600
700
800
900
1000
130 140 150 160 170 180 190
)a
P(er
usser
pcit
atsla t
oT
Fan rotation speed
Internalresistance
1200rpm
1100rpm
1000rpm
900rpm
800rpm
Output 3.7kW
136 184
Air volume (m3/min)
Air volume (m3/min)
✻ Pulley and V-belt is procured on site.
✻ Pulley and V-belt is procured on site.
290 310 330 350318 345
250
0
100
200
300
400
500
600
700
800
270
)a
P(er
usser
pcit
atslat
oT
272
800rpm800rpmInternal resistance
Fan rotation speedOutput 5.5kW
StandardStandard
1000rpm
1100rpm
1000rpm
900rpm900rpm
12
34
5
6
7
8
9
3
4
5
6
7
8
9
2
6
No.
3
4
5
6
7
8
9
No.
1
3
4
5
7
8
9
1170114010801040973930845797748
Rotational speed (rpm)
113510701015978905850803
Rotational speed (rpm)
ø315-B-2-42ø315-B-2-42
ø250-B-2-42ø250-B-2-42ø280-B-2-42
50Hz
Motor pulley Fan pulley
ø170-B-2-38
ø180-B-2-38ø170-B-2-38
ø180-B-2-38ø180-B-2-38
ø160-B-2-38
ø170-B-2-38
ø236-B-2-42ø250-B-2-42
50Hz
Motor pulley Fan pulley
ø160-B-2-28
ø160-B-2-28
ø170-B-2-28
ø165-B-2-28ø165-B-2-28ø165-B-2-28ø165-B-2-28ø170-B-2-28ø160-B-2-28
ø315-B-2-42
ø280-B-2-42
ø200-B-2-42ø212-B-2-42ø224-B-2-42ø236-B-2-42
ø280-B-2-42
ø315-B-2-42
ø250-B-2-42
B48B49B50B51B52B54B54B57B56
V-belte
B51B51B51B50B53B56B55
V-belte
60Hz
Motor pulley Fan pulley
ø280-B-2-42
ø165-B-2-28
ø165-B-2-28ø165-B-2-28
ø180-B-2-28ø170-B-2-28
ø355-B-2-42
ø250-B-2-42ø280-B-2-42ø280-B-2-42
-ø160-B-2-28
ø160-B-2-28ø170-B-2-28
ø300-B-2-42ø315-B-2-42
ø355-B-2-42-
ø300-B-2-42ø180-B-2-38
ø355-B-2-42ø355-B-2-42ø160-B-2-38
60Hz
Fan pulleyMotor pulley
ø160-B-2-38 ø250-B-2-42
ø280-B-2-42ø300-B-2-42
ø170-B-2-38
ø160-B-2-38ø160-B-2-38ø160-B-2-38 ø315-B-2-42
B52B56B54B54B55B56B60B59
-
V-belte
B50B55B52B54B55B58B58
V-belte
12
4. External Dimensions
PUHY-P250YHM-A(-BS) Unit : mm
172
142
BA
ø22
.2 B
raze
dø
9.52
Bra
zed
Gas
Liqu
idG
asLi
quid
Con
nect
ion
spec
ifica
tions
for
the
refri
gera
nt s
ervi
ce v
alve
PUHY
-P25
0YHM
Pos
ition
dim
ensi
ons
for
the
refr
iger
ant
serv
ice
valv
eM
odel
Con
nect
ing
pipe
spe
cific
atio
ns
Ref
riger
ant s
ervi
ceva
lve
<ga
s>
Ref
riger
ant s
ervi
ceva
lve
<liq
uid>
ø34
Kno
ckou
t hol
eø
52 K
nock
out h
ole
ø52
or
ø27
Kno
ckou
t hol
eø
65 o
r ø
40 K
nock
out h
ole
150X
92 K
nock
out h
ole
102X
72 K
nock
out h
ole
Fron
t thr
ough
hol
eBo
ttom
thro
ugh
hole
Fron
t thr
ough
hol
eFr
ont t
hrou
gh h
ole
Botto
m th
roug
h ho
leFr
ont t
hrou
gh h
ole
For t
rans
mis
sion
cab
les
For
wire
s
For
pip
es
Spe
cific
atio
nsU
sage
NO
.
Not
e1.P
leas
e re
fer
to th
e ne
xt p
age
for
info
rmat
ion
rega
rdin
g ne
cess
ary
spac
ing
arou
nd th
eun
it an
d fo
unda
tion
wor
k.2.
The
det
acha
ble
leg
can
be r
emov
ed a
t site
.3.
At b
razi
ng o
f pip
es,w
rap
the
refr
iger
ant s
ervi
ce v
alve
w
ith w
et c
loth
and
kee
p th
e te
mpe
ratu
re o
f re
frig
eran
t ser
vice
val
ve u
nder
120
˚C.
<A
cces
sorie
s>C
onne
ctin
g pi
pe
<G
as>
·
Elb
ow(I
D25
.4X
OD
25.4
)···P
250
· P
ipe
(ID
25.4
XO
D22
.2)·
··P25
0
<
Liqu
id>
· P
ipe
(ID
9.52
XO
D9.
52)·
··P25
0
*1
*1 C
onne
ct b
y us
ing
the
conn
ectin
g pi
pes
(for
bot
tom
pip
ing
a
nd fr
ont p
ipin
g) th
at a
re s
uppl
ied.
(fro
nt a
nd b
ack,
2 po
ints
)N
ote
2*
555560
60
760
A
B 60
Det
acha
ble
leg60
1710
72
Con
trol
box
132
64 3
1
1 2 3 4 5 625
Inta
keai
r
90
204
102
251
240
Inta
keai
r
Ser
vice
pane
l
1410
1650
760
920
88
25
54Inta
keai
r
Dis
char
ge a
ir
98
Fro
nt v
iew
Left
side
vie
w
Top
vie
w1p
c.1p
c.
1pc.
221
150
(Mounting pitch)
(Mou
ntin
g pi
tch)
Ref
riger
ant s
ervi
ce
valv
e <g
as>
Ref
riger
ant s
ervi
ceva
lve
<liq
uid>
2X2-
14X
20 O
val h
ole
14583
760
8076
080
18724(721 727)18
9286
131
251
186
52
145
Bot
tom
vie
w
13
PFD-P250VM-E Unit : mm390
50
50
100
Not
e1.
Be
sure
to s
et u
p a
trap
for
Em
erge
ncy
drai
n pi
ping
.(T
rap
heig
ht:b
eyon
d 10
0mm
)(T
rap
is n
ot n
eces
sary
for
mai
n dr
ain
pipi
ng.)
2.A
ppro
ve th
is fi
gure
bec
ause
it is
ref
used
for
the
impr
ovem
ent a
nd s
peci
ficat
ion
subj
ect t
o ch
ange
with
out n
otic
e.3.
Am
puta
te a
gas
pip
e/liq
uid
pipe
in th
e fix
ed h
eigh
t at t
he ti
me
of 2
ref
riger
ant
circ
uit c
onne
ctio
n, a
nd c
onne
ct it
with
the
loca
l pip
e.
Dra
in p
ipin
g co
nnec
tion
for
hum
idifi
er
Air
inle
t
500
or m
ore
200
or m
ore
400 or more
800 or more
Indo
or u
nit
Ser
vice
spa
ce
Uni
t sur
face
figur
e
Pip
e ex
ecut
ion
spac
e
Uni
t fro
ntfig
ure
Indo
or u
nit
Ser
vice
spa
ce
Hol
e fo
r th
e co
ntro
l wiri
ng
Lifti
ng b
olts
<2-
ø32
kno
ck o
utho
le>
Hol
e fo
r th
e po
wer
supp
ly(B
ody)
<N
omal
/Loc
al>
1380
Rem
ote
cont
rolle
r
A
Ref
rig. p
ipin
g <
gas>
ø22
.2 b
raze
Pow
er s
uppl
y:W
hite
Ope
ratin
g:G
reen
Che
ck:Y
ello
wF
ailu
re:R
ed(A
cces
sory
)F
ilter
Lam
p
<vi
ew fr
om A
>
320220
1950
20
100
462
580
Pan
el
<ø
32 k
nock
out
hol
e>
Air
inle
t
Con
trol
box
50
140
Hol
e fo
r th
e co
ntro
l wiri
ng <
ø32
kno
ck o
ut h
ole>
Mai
n dr
ain
pipi
ng c
onne
ctio
n <
Rp1
-1/4
>
<A
cces
sory
>· L
iftin
g bo
lts···
···4p
c.· F
ront
pan
el o
peni
ng a
nd c
losi
ng k
ey···
···1p
c.
100
Air
outle
t
Ref
rig. p
ipin
g <
liqui
d> ø
9.52
bra
ze
Hol
e fo
r th
e po
wer
sup
ply
<ø
32 k
nock
out
hol
e>
260
68
100
1180
780
1340
Hol
e fo
r th
e co
ntro
l wiri
ng(ø
60)
410
68
Hol
e fo
r th
e po
wer
sup
ply(
ø60
)32
1
220
Hol
e fo
r ga
s pi
pe c
onne
ctin
g(ø
42)
Air
outle
t
20
Bol
t hol
es:8
-ø18
140
305
100
518
Hol
e fo
r liq
uid
pipe
con
nect
ing(
ø24
)
65
<R
p1-1
/4>
Hol
e fo
r liq
uid
pipe
con
nect
ing(
ø24
)
87
186
20
Em
erge
ncy
drai
n pi
ping
con
nect
ion
<R
p1-1
/4>
Hol
e fo
r ga
s pi
pe c
onne
ctin
g(ø
42)
Cha
ngeo
ver
switc
h (S
W9)
340
100
150
260
171
20
401
740
14
PFD-P500VM-E Unit : mm
5010
0140
5050 390 10
0
68124
135
Not
e1.
Be
sure
to s
et u
p a
trap
for
Em
erge
ncy
drai
n pi
ping
.(T
rap
heig
ht:b
eyon
d 10
0mm
)(T
rap
is n
ot n
eces
sary
for
mai
n dr
ain
pipi
ng.)
2.A
ppro
ve th
is fi
gure
bec
ause
it is
ref
used
for
the
impr
ovem
ent a
nd s
peci
ficat
ion
subj
ect t
o ch
ange
with
out n
otic
e.3.
Am
puta
te a
gas
pip
e/liq
uid
pipe
in th
e fix
ed h
eigh
t at t
he ti
me
of 2
ref
riger
ant
circ
uit c
onne
ctio
n, a
nd c
onne
ct it
with
th
e lo
cal p
ipe.
Ref
rig. p
ipin
g <
liqui
d> in
2 r
efrig
. circ
uit s
yste
m ø
9.5
2 br
aze
No.
1
Ref
rig. p
ipin
g <
gas>
in 2
ref
rig. c
ircui
t sys
tem
type
P45
0:ø
19.
05 b
raze
, typ
e P
560:
ø 2
2.2
braz
e N
o.1
Ref
rig. p
ipin
g <
liqui
d> ø
15.
88 b
raze
Ref
rig. p
ipin
g <
gas>
ø 2
8.58
bra
ze
Hol
e fo
r N
o.2
gas
pipe
conn
ectin
g(ø
42)
in 2
re
frig
. circ
uit s
yste
m
Hol
e fo
r N
o.2
liqui
d pi
peco
nnec
ting(
ø 2
4) in
2
refr
ig. c
ircui
t sys
tem
Hol
e fo
r liq
uid
pipe
con
nect
ing(
ø 3
4)
Hol
e fo
r N
o.1
liqui
d pi
pe c
onne
ctin
g(ø
24)
in 2
ref
rig. c
ircui
t sys
tem
Bol
t hol
es:8
-ø 1
8
Hol
e fo
r N
o.1
gas
pipe
con
nect
ing(
ø 4
2)in
2 r
efrig
. circ
uit s
yste
m
Hol
e fo
r ga
s pi
pe c
onne
ctin
g(ø
48)
Mai
n dr
ain
pipi
ng c
onne
ctin
g<R
p1-1
/4>
Dra
in p
ipin
g co
nnec
tion
for
hum
idifi
er
<A
cces
sory
>· L
iftin
g bo
lts···
···4p
c.· F
ront
pan
el o
peni
ng a
nd c
losi
ng k
ey···
···1p
c.
Air
inle
t
Ser
vice
spa
ce
Indo
or u
nit
Pip
e ex
ecut
ion
spac
e
Pan
el o
peni
ngan
d cl
osin
g di
men
sion
Indo
or u
nit
Uni
t sur
face
figur
e
Ser
vice
spa
ce
400 or more
Uni
t fro
ntfig
ure
1000 or more ✻1
200
or m
ore
✻1.
It is
nec
essa
ry fo
r th
e re
mov
al
of th
e pa
nel b
eyon
d 60
0mm
.
500
or m
ore
710R
efrig
. pip
ing
<ga
s> in
2 r
efrig
. circ
uit s
yste
mty
pe P
450:
ø 1
9.05
bra
ze,
type
P56
0:ø
22.
2 br
aze
No.
2
680
<2-ø
32
knoo
k ou
tho
le>
<ø
32
knoo
k ou
t hol
e>
Air
outle
t
Air
inle
t
Pow
er s
uppl
y:W
hite
Ope
ratin
g:G
reen
Che
ck:Y
ello
wF
ailu
re1
:Red
Fai
lure
2:R
ed
<N
orm
al/L
ocal
>
(Acc
esso
ry)
<vi
ew fr
om A
>
<R
p1-1
/4>
Air
outle
t
Hol
e fo
r liq
uid
side
pip
e co
nnec
ting
or N
o.1
gas
side
pip
e co
nnec
ting(
ø 4
2)in
2 r
efrig
. circ
uit s
yste
m
Hol
e fo
r N
o.2
gas
side
pip
e co
nnec
ting(
ø 4
2)in
2 r
efrig
. circ
uit s
yste
m
100
100
1780
1940
100
2020
20
65
321
100
410
359
241
740
359
580
305
320220
370
20
Em
erge
ncy
drai
n pi
ping
con
nect
ion
<R
p1-1
/4>
Hol
e fo
r N
o.1
liqui
d si
de p
ipe
conn
ectin
g(ø
24)
in 2
ref
rig. c
ircui
t sys
tem
Hol
e fo
r th
e po
wer
sup
ply(
ø 6
0)
1950
780
Hol
e fo
r ga
s si
de p
ipe
conn
ectin
g or
N
o.2
liqui
d si
de p
ipe
conn
ectin
g(ø
48)
in 2
ref
rig. c
ircui
t sys
tem
440
Air
outle
t
185
379
135
Ref
rig. p
ipin
g <
liqui
d> in
2 r
efrig
. circ
uit
syst
em ø
9.5
2 br
aze
No.
2
68
120
Hol
e fo
r th
e co
ntro
l wiri
ng <
ø 3
2 kn
ook
out h
ole>
Hol
e fo
r th
e po
wer
sup
ply
<ø
32
knoo
k ou
t hol
e>
220
150
81
Hol
e fo
r th
e co
ntro
l wiri
ng(ø
60)
Pan
el
68
Lifti
ng b
olts
171
A
Con
trol
box
Lam
p
Filt
er
Rem
ote
cont
rolle
r
838
Hol
e fo
r th
e co
ntro
l wiri
ng
1980
124
68
Hol
e fo
r the
pow
ersu
pply
(Bod
y)
Cha
ngeo
ver
switc
h (S
W9)
15
5. Electrical Wiring DiagramsPUHY-P250YHM-A
For
ope
ning
/clo
sing
the
bypa
ssci
rcui
t
Out
door
uni
t hea
t exc
hang
erca
paci
ty c
ontr
ol
Sol
enoi
dva
lve
Con
trol
box
inte
rnal
tem
pera
ture
TH
BO
X
Pip
e te
mpe
ratu
re
Z24
,25
The
rmis
tor
Sub
cool
byp
ass
outle
tte
mpe
ratu
re
Dis
char
ge p
ipe
tem
pera
ture
AC
C in
let p
ipe
tem
pera
ture
Sub
cool
ed li
quid
ref
riger
ant
tem
pera
ture
OA
tem
pera
ture
IGB
T te
mpe
ratu
reF
unct
ion
setti
ng c
onne
ctor
TH
HS
TH
7
TH
6T
H5
TH
4T
H3
TH
2
Pow
er s
uppl
y
Exp
lana
tion
Indo
or/O
utdo
or tr
ansm
issi
onca
ble
Cen
tral
con
trol
tran
smis
sion
cabl
e
Ter
min
albl
ock
TB
7
TB
3T
B1Sym
bol
Pre
ssur
e co
ntro
l,Ref
riger
ant f
low
rate
con
trol
DC
rea
ctor
DC
L
SV
1a
LEV
2a,b
LEV
1Li
near
expa
nsio
nva
lve
Sol
enoi
dva
lve
HIC
byp
ass,
Con
trol
s re
frig
eran
tflo
w in
HIC
circ
uit
CT
12,2
2,3
CH
11C
rank
case
hea
ter(
for
heat
ing
the
com
pres
sor)
Cur
rent
sen
sor(
AC
)M
agne
tic r
elay
(inve
rter
mai
n ci
rcui
t)72
CLo
w p
ress
ure
Dis
char
ge p
ress
ure
Hig
h pr
essu
re p
rote
ctio
n fo
r th
eou
tdoo
r un
itP
ress
ure
switc
hP
ress
ure
sens
or63
LS
63H
1
Sym
bol
Exp
lana
tion
4-w
ay v
alve
21S
4a,b
For
ope
ning
/clo
sing
the
bypa
ssci
rcui
t und
er th
e O
/SS
V5b
SV
9
63H
S1
<S
ymbo
l exp
lana
tion>
*1.S
ingl
e-do
tted
lines
indi
cate
wiri
ng
not
sup
plie
d w
ith th
e un
it.*2
.Dot
-das
h lin
es in
dica
te th
e co
ntro
l
box
bou
ndar
ies.
*3.R
efer
to th
e D
ata
book
for
conn
ectin
g
inpu
t/out
put s
igna
l con
nect
ors.
*4.D
aisy
-cha
in te
rmin
als
(TB
3) o
n th
e
out
door
uni
ts in
the
sam
e re
frig
eran
t
sys
tem
toge
ther
.*5
.Fas
ton
term
inal
s ha
ve a
lock
ing
fu
nctio
n.M
ake
sure
the
term
inal
s
are
sec
urel
y lo
cked
in p
lace
afte
r
inse
rtio
n.P
ress
the
tab
on th
e
term
inal
s to
rem
oved
them
.*6
.Con
trol
box
hou
ses
high
-vol
tage
par
ts.
B
efor
e in
spec
ting
the
insi
de o
f the
c
ontr
ol b
ox,tu
rn o
ff th
e po
wer
,kee
p
the
unit
off f
or a
t lea
st 1
0 m
inut
es,
a
nd c
onfir
m th
at th
e vo
ltage
bet
wee
n
FT
-P a
nd F
T-N
on
INV
Boa
rd h
as d
ropp
ed
to D
C20
V o
r le
ss.
M1
M2
SV
1a
Z3
21
M-N
ET
pow
ersu
pply
circ
uit
C5
LED
3:C
PU
in
ope
ratio
n
LED
1:N
orm
al
ope
ratio
n
SC
-L1
SC
-L2
12
WU
SC
-W
1
Z5
R1
R2
R3C
3
C2F3
F2
F1
Z1
Z2
R5
D1
R4
R6
C17
Dio
deB
ridge
C7
C8
C9
C10
C4
C1
C6
Pow
er S
ourc
e3N 50
/60H
z38
0/40
0/41
5VN
L3L2
L1
TB
1N
L3L2
L1
L
F4
AC
250V
6.3A
T
blac
k
whi
te
red 31 C
N3
gree
n
TB
24
N
TB
23
L3 TB
22
L2 TB
21
L1
CN
1B4
13
1C
N1A
UU
U
F1,
F2,
F3
AC
250V
6.3A
TUZ4
DS
A
CN
2
6 5 3 1
Noi
seF
ilter
UZN
R01
U
31
CN
5re
d3
CN
4bl
ue1
47 1 CN
INV
CN
VD
C
4 1FA
N B
oard
F01
DC
700V
4A T
C63
0C
631
R63
1
R63
0IP
M
CN
18V
blue
CN
4re
dC
N5
21
13
12
234 1
CN
21bl
ue
CN
22re
d
6 5 4 3
TH
BO
X
LED
2:E
rror
Fan
mot
or(H
eat e
xcha
nger
)
M 3V
DC
LR
1R
5*5 bl
ack
red
C10
0
2 431
72C bl
ack
red
SC
-P1
SC
-P2
4
CN
1
1
LED
1 N
orm
al o
pera
tion(
lit)
/Err
or(b
link)C
N5V
yello
wC
N6
21
3
3
1C
N4
12
CN
2
15 27 1C
NT
YP
C1
RS
H1
TH
HS
*6 FT
-P
FT
-N
P N
INV
Boa
rd
R34
C30
C32
C34
C36
R30
R32
C31
C33
C35
C37
R31
R33
blac
k
whi
te
red
R35
CT
3S
C-L
3
IGB
T
SC
-U
SC
-V
CT
12C
T22
red
whi
tebl
ack
blac
kw
hite
red U
VW
MS
3
M
otor
(Com
pres
sor)
Cen
tral
con
trol
tran
smis
sion
cabl
e
Indo
or/O
utdo
ortr
ansm
issi
onca
ble
Indo
or/O
utdo
ortr
ansm
issi
onca
ble
*4
TP
2T
P1
TB
7S
M2
M1TB
3
M-N
ET
Boa
rd
13
CN
04re
d
LED
1:P
ower
sup
ply
to In
door
/Out
door
tran
smis
sion
line
CN
102
43
21
CN
S2
yello
w
21
54
32
CN
ITre
d
1
63H
1P
LEV
2bM
LEV
2aMM
LEV
1123456
CN
LVA
CN
LVB
red
123456
5 4 3 2 16
CN
LVC
red
3 1C
NT
YP
2bl
ack
Z24
3 2 1
Z25
CN
TY
P5
gree
n
CN
TY
P4
gree
n
4 3 2 1
CN
213
red
CN
212
2 1
CN
990
2 1
TH
6
TH
7
TH
3
TH
5
21 363
LS
63H
S1
21 3
TH
2
TH
4
3 2 1C
N20
2re
d
CN
201
23 1
CN
215
blac
k2 1
CN
211
21re
dC
NIT
yello
wC
NS
25
12
34
OF
F
ON
12
34
12
34
CN
41
CN
40
CN
102 4
32
1C
N3D 1
23
red
CN
3S 12
3
blue
CN
3N 12
3
*3
yello
wC
N3K 1
2C
NA
Cre
d2
13
F01
AC
250V
3.15
A T
6 5 3 1
SV
9
X09
X10
CN
508
blac
k
X08
X07
1356
CN
507
red
6 5 3 1
SV
5bC
N50
6
X06
X05
3 121
S4a
CN
504
gree
nX
04
X03
CH
11
3 1C
N50
3bl
ue
2 1C
N50
2X
02
X01
21S
4b
1 1C
N50
1
2 3
CN
AC
2bl
ack
65 72C
12C
N72
red
31
CN
DC
pink
12
CN
T01
13
12
21
21
CN
801
yello
wC
NT
02C
N33
2bl
ueC
N4
CN
2
7 5 2 1
CP
U p
ower
supp
ly c
ircui
t
Pow
er fa
ilure
dete
ctio
n ci
rcui
t
Con
trol
Boa
rdLE
D1
SW
1
ON
OF
F1
10S
W2
ON
OF
F1
10S
W3
ON
OF
F1
10S
W4
ON
OF
F1
10
ON
OF
F1
10S
W5
543
12V
1
CN
51
*3
SW
U2
SW
U1
10's
digi
t1'
sdi
git
Uni
t add
ress
setti
ngLE
D1
Dis
play
setti
ngF
unct
ion
setti
ng
Com
pres
sor
ON
/OF
F o
utpu
tE
rror
det
ectio
n ou
tput
TB
7 P
ower
sele
ctin
gco
nnec
tor
LED
3:Li
t whe
n po
wer
ed
LED
2:C
PU
in o
pera
tion
blac
kt t t t
t
t
t t
16
PFD-P250VM-E
u
Not
e: 1
. The
dot
ted
lines
sho
w fi
eld
wiri
ng.
2.
The
add
ress
set
ting
of th
e in
door
uni
t sho
uld
alw
ays
be o
dd.
3.
The
out
door
uni
t to
whi
ch th
e in
door
uni
t is
conn
ecte
d w
ith th
e tra
nsm
issi
on li
ne,
the
addr
ess
of th
e ou
tdoo
r uni
t sho
uld
be th
e in
door
uni
t +50
.
4. M
ark
i
ndic
ates
term
inal
bed
,
con
nect
or,
b
oard
inse
rtion
con
nect
or
or
fast
enin
g co
nnec
tor o
f con
trol b
oard
.
0F E D CBA9
09 8 7 6
54321
91 2 3 4
5678
0 87
654321
21
21
71
23
45
6
CN7V
CN24
CN25
X11
SW8
SW4
SW11
(1st
digit)
SW12
(2nd
digi
t)SW
14
SW7
SW2
SW1
SW3
SWC
SW5
Add
ress
(odd
)
12
34
56
12
32
12
12
12
11
2
T
CN3T
3
CN28
CN31
CN29
CN20
CN21
CN60
CN22
Z3
33P1
97
51
31
31
31
1
CNT
CND
CN90
CN33
CNP
54
32
16
54
32 CN
51
1
CN52
Deh
umid
ify
ZNR9
01DS
A1
CN3A
ZNR1
F901
X06
X05X
04
321 2
CN32
321X0
1
CN2MI.B
.
1
X07 Z1
Insi
de s
ectio
n of
con
trol b
ox
RC
21
21
TB15
Failu
re o
utpu
t
Dis
tant
loca
tion
on/o
ff<n
o vo
ltage
or c
urre
nt>
Sta
tus
outp
ut
Dis
tant
loca
tion
on/o
ff<w
ith v
olta
ge a
nd c
urre
nt>
Powe
r sup
ply
DC30
V, A
C100
/200
V
Sw
itch(
norm
al/lo
cal)
Pow
er s
uppl
y D
C12
~24V
Pow
er s
uppl
y
380/
400/
415V
(50H
z)
400
/415
V(6
0Hz)
DC
24~3
0V
Indo
or u
nit
Con
trol w
iring
LED
dis
play
(failu
re)
LED
dis
play
(sta
tus)
LED
dis
play
(pow
er s
uppl
y)
3N~
LED
dis
play
(che
ck)
SW
9
2 3 4 5154321
B2B1BCA2A1AC 54321C
IFB
3
L3A1S B1 L2L1 X1
11 22 1 6 5 1 2
PE
N
F1
3 4 5 6
31ZN
R1
31CN1
DSA1
PE
TB23
TB21
LL
TB22
CN53
TB2
S.B
.
CN54
L3
TB5
SH
IELD
L2L1 L4
FAN
over
cur
rent
dete
ctio
n
51F
Z1
ZNR2
52F
Z3
51F
52F
MF
TH24
TH21
TH22
TH23
6 5 4 3 2 1
LEV
SY
MB
OL
NA
ME
DS
A1
Sur
ge a
bsor
ber
LED
dis
play
(po
wer
sup
ply)
F90
1
ZNR1
, ZNR
2, ZN
R901
MF
I.B.
S.B
.IF
BT
B2
TB
5T
B15
TB
21
TB
22T
B23
F1
T LEV
52F
51F
33P
1
RC
L4L3L2L1Z3
Z1
X11
SW
C(I
.B.)
SW
14(I
.B.)
SW
12(I
.B.)
SW
11(I
.B.)
SW
9S
W4(
I.B.)
SW
3(I.B
.)S
W2(
I.B.)
SW
1(I.B
.)
Sur
ge a
bsor
ber
boar
d
Sw
itch
(out
let/i
nlet
tem
p.co
ntro
l)
Flo
at s
witc
h
Fus
e<6-
3/6A
>
Var
isto
r
Tran
sfor
mer
Ele
ctro
nic
linea
r ex
pan.
valv
eC
onta
ctor
(fan
I/D
)O
ver
curr
ent r
elay
(fa
n I/D
)
Fus
e<5A
>
The
rmis
tor
(inle
t tem
p.de
tect
ion)
Sw
itch
(con
nect
ion
No.
set)
Sw
itch
(for
mod
e se
lect
ion)
Sw
itch
(for
cap
acity
cod
e)S
witc
h (f
or m
ode
sele
ctio
n)S
witc
h (f
or m
odel
sel
ectio
n)
Aux
iliar
y re
lay(
chec
k)
LED
dis
play
(fa
ilure
)LE
D d
ispl
ay (
stat
us)
LED
dis
play
(ch
eck)
Sw
itch
(nor
mal
/loca
l)
TH
24T
H23
TH
22T
H21
Sw
itch
(1st
dig
it ad
dres
s se
t)S
witc
h (2
nd d
igit
addr
ess
set)
Fan
mot
orIn
door
con
trol
ler
boar
d
Pow
er s
ourc
e te
rmin
al b
edTr
ansm
issi
on te
rmin
al b
ed
Ext
erna
l inp
ut/o
utpu
t boa
rd
Tran
smis
sion
term
inal
bed
MA
Rem
ote
cont
rolle
r
Term
inal
bed
for
dist
ant l
ocat
ion
on/o
ff<
With
vol
tage
and
cur
rent
>
Term
inal
bed
for
dist
ant l
ocat
ion
on/o
ff<
No
volta
ge o
r cu
rren
t>
Aux
iliar
y re
lay(
fan
failu
re d
etec
tion)
Aux
iliar
y re
lay(
fan)
The
rmis
tor
(pip
ing
tem
p.de
tect
ion/
gas)
The
rmis
tor
(pip
ing
tem
p.de
tect
ion/
liqui
d)
The
rmis
tor
(out
let t
emp.
dete
ctio
n)
Term
inal
bed
for
dist
ant l
ocat
ion
disp
lay
Ext
erna
l inp
ut a
dapt
er
(PA
C-S
A88
HA
)
CN
525(
gree
n)
1(br
own)
Z
Indo
or u
nit
cont
rol b
oard
Rel
ay c
ircui
t
The
sign
al in
put o
f the
deh
umid
ify o
rder
is to
conn
ect w
iring
refe
rrin
g to
the
botto
m fi
gure
.
SW
Pow
er
Dis
tant
con
trol p
anel
SW
:Def
umid
ify o
rder
(fiel
d su
pply
and
con
stru
ctio
n)
Z
Z:R
elay
(Con
tact
: M
inim
um a
pplic
able
load
DC
12V
1m
A or
less
)
u
u
u
t t t t
17
PFD-P500VM-E
� � � � � � � �
�����
������
���
���
���
��
��
����
�
��
���
��
�����
���
�������
�����
���
������
��
��
������
��
����
��
�����
�����
��
���
��
���
��!��
����
���
��!
"�����
���
���
���
���
��"�"!�
���
��!�
���
�����
��
���
���
#����
���
����
�!�
#���
���
���!�
���
�����
��
���
���
#����
���
��$��
�!�
#���
%!��
���!�
���
�����
��
����
��
���
#����
���
��
���
#����
&��
�����
�!��
���!��
��
�"
���
��
����!��
�"����"��
�
��
���
������
���
��
����
������
��
����
��!��
���!��
���!�
#�
���
�����!��
&'(�
'�)
��*
��"
���
���
���
�#���
"����"��
��#����
������
�"����"��
�����
���
��
�"����"��
���"�����#����
�
����
+
��,
���
��-
���
���
��'
(. / 0�%12
(2 , -
3'
���
�2
�
� � �'
3
-,
( ,-
3'����
3'
-�
��
��
���
��
�'
��
��
4��
��
-5
1����
����
��
����
����
��
� ��
����
���
��
����
����
��
'��
�'�
0��!�
���
��
�'
� ��
�'
�
6�72
(�0�
1�
6�7�
.2(�
4(3
4('
4(�
4(�
4(-
��
�1
��
��
��
�)
��%
��
��� � ����
'2
�'
��
-�
����
��0
��2(
��
����
��8
��
6�
���
���
��
��,
��
��
�� ��
��
��
��2
��
��
��
��
��(
��
���
�3(
��
�� ��
3'
�
6�
��8�
���
���
�9
��:�
�9
��:�
�9
��:�
�9
��:�
;/5
�
;/5
�
����'33 ' � � � �
10
�%�
3'
��
��
3'
��
��
3'
��
��
;/5�
1;/
5�%
;/5�
��
���
��
��"�
��
��"�
����#
�<
7�
��
�%�'
1�� %�
� � 3 '
0�
��=�(5
����
������!��
������
��
�
;/
0��
��
���
���
��!
��
;/
0��
��
����
��!
�
�%':
�
�9
�/;0
;�;�
� �
6�7
�
����
�
0�1
�
��%
�
�
;�;�;�
� �
�
.�
8�
���!
���
��
=�,(>�
((>�
�'5
�'(9
? �((>�
�'5
�3(9
?
;/
0��
��
����
���!
���
8/�%
�
;'
� � ' 3�
�"
���
���
�>
�"�
��
2
����.
�!
���!��
!�
0�
�����
"���
���>�
��@��
$���
��
��"!
�����A
�����
���!
��!��
!�
0�
�����
"���
���>�
��@
��$�
����
���
"!�����A
�����
���!
��!��
!�
����.
�!
���!��
!�
8�
���!
���
0�
�(5�1
��((>�
((5
8�
���!
���
0�
��=��5
;/
0��
��
���
���
��!
��
0�
��=�(5
����
������!��
������
��
�
;/
0��
��
��"�
�"*
;�;�;;
; ;
'����
� 1�%�%�%�%�1�1�1� '�����
�.%��
'��%
��
��'�
�%��
�%�� �
9�/
;0
�%':
� ��
4��
� �
8/
4��
@���
��A
���1
���
�)
� � ���
��
�� ��
������%
��'
��
��
��
'�
'�
��
�
��
'�
0��!�
���
6�72
(�
.2(�
6�7� 0�1�
4(�
4(-
4(�
4('
4(3
��8
����
��2(
��0
���
��
���
��
���
��
���
��( �
��
��
��2 �
��
��
��
���
���
�,'
��
��
3(�
��
�'
3�
��
�-
��
'�
��
2
6�
@����
�A
��8�
�
6���
�'�
���
��
��
-5
��
��
'3
-
��
4��
��'
���
����
����
��
� ��
����
���
��
��,
1����
����
��
���
���
���
��-
���
����
(. / 0�%12
(2 , -
3'
���
�2
�
� � �'
3
-,
( ,-
3'����
����
.1�
�$�
�"!
�����
����
"��
�
'�.
6�
6�7
�
6�
'�.
6�
�9
��:�
�9
��:�
�9
��:�
�9
��:�
'�.
'�.
).
�1
)/
�B
)%
C;
�!��
��#���#
��
0�
1�
;'
6�
7��6�
7��6�
72(�
;/
0��
��
���
���
��!
��
;/
0��
��
���
���!
�
;/
0��
��
��"
��"*
;/
0��
��
���
�
���!���
)1
7��
���
"������
�7
�
�%
��
�%
�'
�%
':�
�:�
�%
�
�.%
��%
�
10
�%�
��%
�����%
��
).
�!��
��#���#
��#����
�
�"�
��!���>�
����
���"
�����
.�
���
�"�
5�����
�
���
����
����
/�
"����"
�����<����$
�$
�
�����
"��
����
��>0
C$��"!�������
��
����
�>0
�����
���
����
���
����
���
"���
�
�"�
�"����"���
����
��
�
�"�
�����
���
���
"���
�
�"�
����"���"��
"���
�
�"�
�����
���
���
"���
�
�"�
�����
������
"���
1!<
���
���
��"
��"*
;/
0��
��
���
���
��!
��
�
�"�
�����
�>�
"�
�9
��:�
��9
��:�
��
����%
�
��
����%
�
��
����%
�
��
����%
�
��
�����%
�
��
�����%
�
��
�����%
�
��
����%
�
4���4
��
6��6�
6�
;�
;�
;�
;�
��
2
�9
��:�
��9
��:�
�9
��:�
��9
��:�
�9
��:�
��9
��:�
��8
����8
�
'�.
'�.
;/
5���
�.�
.2(�
�%
��
�%
��
�
�"�
������
������
��
���
�
�"�
����
��
������
��
���
.��
����
�
������"������
�#����
1�����
�#����
8�
����!�"
���
���
�#��
���
���
���
���
���
�#��
/<��
����
�!�>�!��
!�#����
���
���
���
���
���
�#��
����
��#��
�����
�����
"����
��>�
��
@�
��
$�����
���
"!�����A
����
��#��
�����
�����
"����
��>�
��@�
�$�����
��"!�����A
1!<
���
���
�����
��!
������
"���
1!<
���
���
�����
�����
���
���
��
���
����
���
"���>�
��
�����
���
���
��
���
����
���
"���>D
!�
�����
���
���
!�����
����
���
"���
����
��#��
�����
�����
"����
��
��
�
.!��
@3��
>31
A
.!��
@'1
A
���
��!
���
���
"����
�!"�
��
8�
��
��
������!��
"�����#
����
6��#
��
�
'��
����
��
'�
���
����
��!�����
����!�
���
���
���
��"�
���"�
��
���
�����
���
���
#�����
��!��
�
7��
�"
�"!�
/<�
���
�
��!�������
�
�81
�:�
1,,9
1
��
+0��!
��
�����
��
6+7
��
���
����
"�+)
��
!�
���"
�#�
���
0�
��5
��
1���
��
0�
����"�
�����
���
6
9�
��"�
���"�
�"�
�����
�����
���
��"
�"!��
7��
�$�
���
;/
5�%
"����"�
��
����
10
�%�#����
����
"����"�
���
��
3(
��
��%
��#����
�
�����"�
�"�
���"�
����
��
�1
��
��)
����%
��#����
�
@����
�A
3 ' � � � �
��
3(
3'
��
��
��
�1
��
�)
��%
��
� � � � �
;/5�
@����
�A
9�
����
�!�
���
�������
���
"���
���
�����
���
��"
�"!�
8.0
:8'((5
):/
�����
���
�����
���
�
C�
3'
��
��
C�
3'
��
��
�(
2,
-
C�
'�
��
� C�
'�
��
��(
2,
-
C�
3'
��
��
C�
3'
��
��
���
���
���
��
"�"
!�
���
���
���
��
"�"
!�
��
��
��
��
�
/<��
����
�!�:�!��
!�
#����
��.%
���
"���
��
��:$
�����
��!����1
���
"���
����:$
�����
��!�
����
%
����
!��
���
��<��
����
�!��!
�"���
��
���
�����!��
�����
"����"��
���
��
�:�
����
���
��"�"!��"����"���
�
�����:"
�"!�
��
����
���
�!���
�
��
���
!��
����
�
�����
�����
����
���
��
���
�<��
����
�!�:�!��
!�#����
�
1�
1�
1�
%�
%�
%�
1 %
�%
��
�%
��
!
!
!
!
!
!
18
6. Refrigerant Circuit Diagram And Thermal SensorOutdoor Unit : PUHY-P250YHM-A
SC
C(H
IC C
ircui
t)LE
V1
SV
1a
63H
1
21S
4a
ST
3
ST
6
63H
S1
CJ2
ST
7
AC
CT
H4
TH
2
TH
3
TH
7
TH
6
21S
4b
TH
5
CP
1
CJ1
63LS
SV
5b
CV
1
LEV
2a
LEV
2b
ST
1
ST
2
BV
1
SV
9C
P2
BV
2
O/S
CO
MP
TH
23
TH
22
Indoor Unit : PFD-P250VM-E
19
Outdoor Unit : PUHY-P250YHM-A x 2Indoor Unit : PFD-P500VM-E
SCC(HIC circuit)
SCC(HIC circuit)
LEV1
SV1a
63H1
21S4a
ST3
ST6
63HS1 CJ2
ST7
ACCTH4
TH2
TH3
TH7
21S4b
TH5
CP1
CJ1
63LS
SV5b
CV1
LEV2a
LEV2b
ST1
ST2
BV1
SV9 CP2
BV2
O/S
COMP
LEV1
SV1a
63H1
21S4a
ST3
ST6
63HS1 CJ2
ST7
ACCTH4
TH6
TH6
TH2
TH3
TH7
21S4b
TH5
CP1
CJ1
63LS
SV5b
CV1
LEV2a
LEV2b
ST1
ST2
BV1
SV9 CP2
BV2
O/S
COMP
TH23-1
TH22-1 TH22-2
TH23-2
20
7. System Design7-1.Refrigerant Piping System
■ Sample connection
■ Pipe selection
■ Amount of refrigerant charge
Refrigerant for extension piping is not included at factory shipment. Add an appropriate amount of refrigerant for each system on site. Write down the size and the length of the piping in each system as well as the amount of added refrigerant on the outdoor unit as a reference for servicing.
■ Calculating the amount of refrigerant to be added
• The amount of refrigerant that is necessary for extension piping is calculated based on the size and the length of the liquid piping.
• Use the following formula to figure out the amount of refrigerant to be added.• Round up the calculation result to the nearest 0.1 kg. (e.g., If the result is 16.08 kg, round up the .08 to .1 , which
yields 16.1 kg.)
CautionCharge Liquid Refrigerant
Filling the equipment with gas refrigerant will result in a power loss due to transformation of refrigerant in the tank.
✻ Refrigerant charge calculation
✻ Amount of charged refrigerant at factory shipment ✻Sample calculation
Outdoor unit model
Chargedrefrigerant amount(kg)
9.0P250
Outdoor unit
L
L
H
A
Outdoor unit
L
H
A
Indoor unit Indoor unit
Liquid pipe size
Total length of the ø 12.7 pipes x 0.12
Liquid pipe size
Total length of the ø 9.52 pipes x 0.06
(m) x 0.12(kg/m)
+(m) x 0.06(kg/m)
+
Total capacity of connected indoor units Amount for the indoor unit
P250 model 2.0kg
✻ 2 kg x 2 when connected to a system with two outdoor units
P500 model4.0kg
500 model indoor unit : When ø 9.52 pipes are used and the piping length is 80 m80(m) x 0.06(kg/m)+2.0kg=6.8kg
(Amount for the extension pipe to each outdoor unit)
<Connection to a system with two outdoor unit>
Farthest piping length(L)
Height difference between indoor and outdoor units (H)
50 m or less (40 m if outdoor unit is below indoor unit, 15 m if outside temperature is 10˚C or below)
165 m or less in actual lengthAllowable piping lengthAllowable height difference
<Refrigerant system with one outdoor unit>
<Amount of refrigerant to be added>
<Refrigerant system with two outdoor units>
Outdoor unit model Liquid pipe size Gas pipe sizeP250
✻1 Use ø 12.7 pipes when the pipe length exceeds 90 m.ø 9.52 ✻1 ø 22.2
21
7-2.Control Wiring
Restrictions when the PFD-type indoor units are connected (related to the system)
(1) Specifications of control wiring and maximum length of wiring
Transmission line is a type of control line. When the source of noise is located adjacent to the unit, theuse of shield cable as well as moving the unit as far away from the noise source are recommended.
1 Transmission line (M-NET transmission line)
For multiple-refrigerant system
Length of transmission line
Facility type(noise level measurement)
No. of cable 2-core cable
Diameter Over 1.25mm2
Wiring specifications
All types of facilities
n/a
Shield cableCVVS · CPEVS · MVVS
System component
Maximum length: 200mMaximum length of centralized control transmission line and Indoor/Outdoortransmission line via indoor/outdoor units: 500m maximum
Total length of indoor/outdoor transmission line
Cable type
(1) The PFD-type indoor units cannot be connected to the ME remote controller.(2) The address settings must be made on this system.(3) The following functions cannot be selected on the PFD-type indoor units.
1) Switching between automatic power recovery Enabled/Disabled (Fixed to "Enabled" in thePFD-type indoor units)
2) Switching between power source start/stop (Fixed to "Disabled" in the PFD-type indoor units)(4) The PFD-type indoor units and other types of indoor units cannot be grouped.(5) The following functions are limited when the system controller (such as G-50A) is connected.
1) To perform group operation in the system with two refrigerant circuits (combination of two out-door units and one indoor unit: P500 model only), the addresses of the controller boards No.1and No.2 on a indoor unit must be set within a group.
2) The local operation cannot be prohibited with the system controller.3) When the switches of the PFD-type indoor units are set as follows, the unit ON/OFF operation
cannot be made with the system controller.· When the Normal/Local switching switch is set to "Local"· When the DipSW1-10 on the control circuit board is set to "ON"
4) The PFD type indoor units cannot be grouped with other types of indoor units.
22
(1) Address setting
7-3.Types of switch settings and setting methodsWhether a particular system requires switch settings depends on its components. Refer to the section “7-4 Sample System Connection” before conducting electrical work.Keep the power turned off while setting the switches. If settings are changed while being powered, thechanged settings will not register, and the unit may malfunction.
Symbol
Outdoor unit OC
Indoor unit
✻ 10HP has only the main controller
Main/sub controllers ✻ IC
Turn off the power to
Outdoor unit
Indoor and outdoor units
Unit
2 Remote control wiring
MA remote controller ✻ 1
No. of cable 2-core cable
Diameter0.3~1.25mm2
(0.75~1.25mm2)✻ 2✻ 3
Wiring specifications
VCTF · VCTFK · CVV · CVS · VVR · VVF · VCT
Maximum length: 200 mTotal Length
✻ 1: “MA remote controller” includes MA remote controller, Simple MA controller, and wireless remote controller.✻ 2: Cables with a diameter of 0.75mm2 or smaller recommended for easier handling.✻ 3: When connecting to Simple MA controller terminal, use a cable with a diameter within the range shown in
the parenthesis.
Cable type
The need for address settings and the range of address setting depend on the configuration of the sys-tem. Refer to “Sample System Connection”.
SymbolUnit or controller
Main · SubIndoor unit
MA remote controller
Addresssetting range
IC01~50
(Note 1)
Address setting methodFactory setting
No address setting required.
00
00
MA
Outdoor unit OC
Main
51~100
Model
In case of 10HP system, assign an odd number starting with "01". In case of 20HP system with two refrigerant circuits, assign a sequential odd number starting with "01" to the upper indoor controller, and assign "the address of the upper indoor controller + 1" to the lower indoor controller.(For the system with one refrigerant circuit, the lower circuit board is not used.)
Add 50 to the address assigned to the indoor unit connected the system with one outdoor unit.
(The main/sub switch must be configured if two remote controllers are connected to the system or if the indoor units are connected to different outdoor units.)
(Note1) If a given address overlaps any of the addresses that are assigned to other outdoor units, use a different, unused address within the setting range.
23
(5) Connection of two refrigerant circuits
When two refrigerant circuits are connected on site, make the switch settings on the controller circuitboard following the instructions described in the installation manual for the indoor unit.
(4) Setting the MA “Sub” controller
When using two remote controllers or running two indoor units as a group, one of the controllers must beset to “Sub” controller.✻ No more than two remote controllers can be connected to a group.
(Factory setting: “Main”)Set the controller according to the following procedure. Refer also to the instructions manual supplied withthe MA remote controller.
Remote controller bodyDip switches
1
ON
2 3 4
Screwdriver
Remove the cover on the remote controller
Set Dip Switch No.1 on the remotecontroller to “OFF” (Main to Sub)
Insert a flat-head screwdriver in the groove shown in the picture, and move the screwdriver in the direction shown in the arrow.
(3) Choosing the temperature detection spot by indoor unit (Factory Setting: SWC “Standard”)
When using the suction temperature sensor, set SWC to “Option.”(The discharge temperature sensor is supplied as standard specification.)
(2) Power supply switch connector connection on the outdoor unit (Factory setting: The male power supply switch connector is connected to CN41.)
Systemconfiguration
Power supply switch connector connection
Not connectedNot grouped
Grouped
Required
Grouped/Not grouped
Grouped/Not grouped
Grouped/Not grouped
Not required
Leave the male connector on CN41 as it is. (Factory setting)
Leave the male connector on CN41 as it is. (Factory setting)
System in which indoor units connected to one
outdoor unit
Connection to the system controller
With connection to indoor-outdoor transmission line
With connection to transmission
line for centralized control
Power supply unit for transmission
lines
Not required (Powered from
the outdoor unit)
Grouping the indoor units connected to different outdoor
units
System in which indoor units connected to
multiple outdoor unitsDisconnect the male connector from the female power supply switch connector (CN41) and connect it to the female power supply switch connector (CN40) on only one of the outdoor units (OC).*Connect the S (shielded) terminal on the terminal block (TB7) on the outdoor unit whose male connector on CN41 was disconnected and connected to CN40 to the earth terminal ( ) on the control box.
✻ When the system controller is connected to the indoor/outdoor transmission line and the power is supplied from the outdoor unit, do not to turn off the outdoor unit. If its power supply is cut, the power is not supplied to the system controller, and the functions will not work.
24
7-4.Sample System Connection
(1) An example of a system to which an MA remote controller is connected
Control Wiring Diagram
Notes Maximum Allowable Length
Wiring and Address Setting
OC
TB3TB7M1 M2 M1 M2S
51
IC
TB5-1A1 B1 S
01
TB5-2A2 B2 S
02
A B
TB151 2
MA
L1Leave the male connector on CN41 as it is.
1. Leave the male connector on the female power supply switch connector (CN41) as it is.2. Grounding to S terminal on the terminal block for transmission line for centralized
control (TB7) is not required.3. Although two indoor controllers (controller circuit boards) are equipped inside the
indoor unit (20HP), the board on No.2 side (lower side) is not used. Do not connect wiring to the lower controller circuit board.
4. The outdoor unit cannot be connected to the units other than the PFD series indoor units.
<a. Indoor/Outdoor transmission line>Connect M1, M2 terminals of the indoor/outdoor transmission line terminal block (TB3) on the outdoor unit (OC) and A1, B1 terminals of the indoor/outdoor terminal block (TB5-1) on the indoor unit (IC). (Non-polarized 2-core cable) *Only use shielded cables.[Shielded cable connection]Connect the earth terminal of the OC and S terminal of the IC terminal block (TB5-1).
<b. Switch setting>Address setting is required as follows.
Main Controller
Sub Controller Settings to be made with the sub/main switch
IC
IC
OC
1
2
Notes
3MA
MA
51~100
01~50
01~50
00
00
Setting not required.
Sub Controller
✻ One indoor controller (controller circuit board) is equipped in the indoor unit (10HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (20HP).
<a. Indoor/Outdoor transmission line>Maximum Length (1.25mm2 or more)
L1 200m
Ste
ps Unit or controller
Main
Sub
Indoorunit
MAremotecontroller
Addresssetting range
Address setting method
Outdoor unit
Factorysetting
Main
Assign a sequential odd number starting with "01" to the upper indoor controller.
Add 50 to the address assigned to the indoor unit connected to the system with one outdoor unit.
Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +1)
1 System connected to one outdoor unit
25
Control Wiring Diagram
Notes Maximum Allowable Length
Wiring and Address Setting
Leave the male connector on CN41 as it is.
1. Assign a sequential number to the outdoor unit.2. Do not connect the terminal blocks (TB5) of the indoor units connected to different
outdoor units.3. Disconnect the male connector on the controller board from the female power supply
switch connector (CN41), and connect it to the female power supply switch connector (CN40) on only one of the outdoor units.
4. Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor units.
5. When the power supply unit is connected to the transmission line for centralized control, leave the male connector on the female power supply switch connector (CN41) as it is at factory shipment.
6. The outdoor unit cannot be connected to the units other than the PFD series indoor units.
<a. Indoor/Outdoor transmission line>Connect M1, M2 terminals of the indoor/outdoor transmission line terminal block (TB3) on the outdoor unit (OC) and A1, B1 terminals of the indoor/outdoor terminal block (TB5-1) on the indoor unit (IC). (Non-polarized 2-core cable) *Only use shielded cables.[Shielded cable connection] Connect the earth terminal of the OC and S terminal of the IC terminal block (TB5-1).
<b. Transmission line for centralized control> Daisy-chain terminals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on each outdoor unit (OC).Disconnect the male connector on the controller board from the female power supply switch connector (CN41), and connect it to the female power supply switch connector (CN40) on only one of the outdoor units. *Only use shielded cables.[Shielded cable connection] To ground the shielded cable, daisy-chain the S-terminals on the terminal block (TB7) on each of the outdoor
units. Connect the S (shielded) terminal on the terminal block (TB7) on the outdoor unit whose male connector on CN41 was disconnected and connected to CN40 to the earth terminal ( ) on the electric box.
<c. Switch setting>Address setting is required as follows.
Main Controller
Sub Controller Settings to be made with the sub/main switch
IC
IC
OC
1
2
Notes
3MA
MA
51~100
01~50
01~50
00
00
Setting not required.
Sub Controller
✻ One indoor controller (controller circuit board) is equipped in the indoor unit (10HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (20HP).
<a. Indoor/Outdoor transmission line>Maximum Length (1.25mm2 or more)
L1, L2 200m<b. Transmission line for centralized control>
Maximum Length via outdoor unit (1.25mm2 or more)L1 + L31 + L2 500m
Ste
ps Unit or controller
Main
Sub
Indoorunit
MAremotecontroller
Addresssetting range
Address setting method
Outdoor unit
Factorysetting
Main
Assign a sequential odd number starting with "01" to the upper indoor controller.
Add 50 to the address assigned to the indoor unit connected to the system with one outdoor unit.
Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +1)
OC
TB3TB7M1 M2M1M2 S
51
IC
TB5-1A1 B1 S
01
TB5-2A2B2 S
02
OC
TB3TB7M1M2M1M2 S
52
A B
TB151 2
MA
L31
L1
L2
Connection
Disconnect the male power supply connector from CN40 and connect it to CN41.
not connect
(1) An example of a system to which an MA remote controller is connected2 System connected to two outdoor units
26
(1) An example of a system to which an MA remote controller is connected
Control Wiring Diagram
Notes Maximum Allowable Length
Wiring and Address Setting
Leave the male connector on CN41 as it is. OC
TB3TB7M1 M2M1 M2 S
51
IC
TB5-1A1 B1 S
01
TB5-2A2 B2 S
02
A B
TB151 2
MA(Main)
A B
MA(Sub)
L1
A1 B2
MA
m1m2
1. Leave the male connector on the female power supply switch connector (CN41) as it is.2. Grounding to S terminal on the terminal block for transmission line for centralized
control (TB7) is not required.3. Although two indoor controllers (controller circuit boards) are equipped inside the
indoor unit, the board on No.2 side (lower side) is not used. Do not connect wiring to the lower controller circuit board.
4. No more than two MA remote controllers (including both main and sub controllers) can be connected to a group of indoor units. If three or more MA remote controllers are connected, remove the wire for the MA remote controller from the terminal block (TB15).
5. The outdoor unit cannot be connected to the units other than the PFD series indoor units.
<a. Indoor/Outdoor transmission line>Same as (1) 1.
<b. MA remote controller wiring>[When two remote controllers are connected to the system]When two remote controllers are connected to the system, connect terminals 1 and 2 of the terminal block (TB15) on the indoor unit (IC) to the terminal block on the MA remote controllers (option).*Set the Main/Sub switch on the connected MA remote controllers (option) to SUB.(See the installation manual for the MA remote controller for the setting method.)
<c. Switch setting>Address setting is required as follows.
Main Controller
Sub Controller Settings to be made with the sub/main switch
IC
IC
OC
1
2
Notes
3MA
MA
51~100
01~50
01~50
00
00
Setting not required.
Sub Controller
✻ One indoor controller (controller circuit board) is equipped in the indoor unit (10HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (20HP).
<a. Indoor/Outdoor transmission line>Same as (1) 1.
<b. MA remote controller wiring>Maximum overall length (0.3-1.25mm2 or more)
m1 + m2 200m
Ste
ps Unit or controller
Main
Sub
Indoorunit
MAremotecontroller
Addresssetting range
Address setting method
Outdoor unit
Factorysetting
Main
Assign a sequential odd number starting with "01" to the upper indoor controller.
Add 50 to the address assigned to the indoor unit connected to the system with one outdoor unit.
Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +1)
3 System in which two MA remote controllers are connected to one indoor unit
27
Control Wiring Diagram
Notes Maximum Allowable Length
Wiring and Address Setting
1. Leave the male connector on the female power supply switch connector (CN41) as it is.2. Grounding to S terminal on the terminal block for transmission line for centralized
control (TB7) is not required.3. Although two indoor controllers (controller circuit boards) are equipped inside the
indoor unit, the board on No.2 side (lower side) is not used. Do not connect wiring to the lower controller circuit board.
4. No more than two MA remote controllers (including both main and sub controllers) can be connected to a group of indoor units. If three or more MA remote controllers are connected, remove the wire for the MA remote controller from the terminal block (TB15).
5. The outdoor unit cannot be connected to the units other than the PFD series indoor units.
<a. Indoor/Outdoor transmission line>Same as (1) 1.
<b. MA remote controller wiring>[Group operation of indoor units]To perform a group operation of indoor units (IC), daisy-chain terminals 1 and 2 on the terminal block (TB15) on all indoor units (IC). (Non-polarized 2-core cable)*Set the Main/Sub switch on one of the MA remote controllers to SUB.
<c. Switch setting>Address setting is required as follows.
Main Controller
Sub Controller Settings to be made with the sub/main switch
IC
IC
OC
1
2
Notes
3MA
MA
51~100
01~50
01~50
00
00
Setting not required.
Sub Controller
✻ One indoor controller (controller circuit board) is equipped in the indoor unit (10HP), and two indoor controllers (controller circuit boards) are equipped in the indoor unit (20HP).
Ste
ps Unit or controller
Main
Sub
Indoorunit
MAremotecontroller
Addresssetting range
Address setting method
Outdoor unit
Factorysetting
Main
Assign a sequential odd number starting with "01" to the upper indoor controller.
Add 50 to the address assigned to the indoor unit connected to the system with one outdoor unit.
Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +1)
OC
TB3TB7M1M2M1M2 S
51
IC
TB5-1A1 B1 S
01
TB5-2A2 B2 S
02
A B
TB151 2
MA(Main) MA(Sub)
L1Leave the male connector on CN41 as it is. OC
TB3TB7M1M2M1 M2 S
53
IC
TB5-1A1B1 S
03
TB5-2A2 B2 S
04
A B
TB151 2
L1Leave the male connector on CN41 as it is.
m1 m2
m3
<a. Indoor/Outdoor transmission line>Same as (1) 1.
<b. MA remote controller wiring>Maximum overall length (0.3-1.25mm2 or more)
m1 + m2 + m3 200m
(1) An example of a system to which an MA remote controller is connected4 System in which two indoor units are grouped with the MA remote controller
28
(2) System with MA remote controller and G-50A
Control Wiring Diagram
Notes Maximum Allowable Length
Wiring and Address Setting
1. Be sure to use odd numbers to set the address for indoor units (10 HP and 20HP connected to the one outdoor unit).
2. To set the indoor unit address for 20 HP connected to two outdoor units, use odd numbers for the top controllers and use even numbers for the bottom controllers (Main controller plus 1).
3. Use the power supply switch connector (CN41) on the outdoor unit as is.4. It is not necessary to ground the S terminal of transmission line terminal board for
centralized controller on the outdoor unit.5 No more than two main/sub remote controllers can be connected to the indoor unit in
the same group. When more than two remote controllers are present in the system, disconnect MA remote controller from TB15 in the indoor unit.
6. Put both types of the addresses for P500-type indoor units in the same group when setting groups for indoor units with system controller (ex. G-50A).
<a. Indoor/Outdoor transmission line>Same as (1) 1.
<b. Transmission line for centralized control> Daisy-chain terminals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on each outdoor unit (OC).*Only use shielded cables.[Shielded cable connection]To ground the shielded cable, daisy-chain the S-terminals on the terminal block (TB7) on each of the outdoor units.
<c. Switch setting>Address setting is required as follows.
<a. Indoor/Outdoor transmission line>L1, L2, L3 200m
<b. Transmission Line for Centralized Control >L31 + L32 + L33 + L34 + L3 500mL1 + L31 + L34 + L3 500m
<c. MA Remote Controller Line >Total Length (0.3 ~ 1.25mm2)
m1 200m
Main Controller
Sub Controller Settings to be made with the sub/main switch
IC
IC
OC
1
2
Notes
3MA
MA
51~100
01~50
01~50
00
00
Setting not required.
Sub Controller
Ste
ps Unit or controller
Main (10HP, 20HP)
Sub(20HP)
Indoorunit
MAremotecontroller
Addresssetting range
Address setting method
Outdoor unit
Factorysetting
Main
Assign a sequential odd number starting with "01" to the upper indoor controller.
Add 50 to the address assigned to the indoor unit connected to the system with one outdoor unit.
Assign sequential numbers starting with the address of the main unit in the same group. (Main unit address +1)
MA
TB151 2
A B
OC
TB3TB7M1M1M2S
53
IC
MA
TB5-1A1 B1 S
03
TB5-2A2 B2 S
TB151 2
A B
04
OC
TB3TB7M1M2M1M2 S
54
OC
TB3TB7M1M2 M2M1M2S
51
IC
TB5-1A1 B1S
01
L1Use CN41 as is.
PowerSupply
A B S
G-50A
A B S
L32
L33
Option
DC power supply line(DC12V)
L34
m1
L2
L3
m1
Use CN41 as is.
Use CN41 as is.
✻There is one indoor controller board inside indoor unit.
✻There are two indoor controller boards inside indoor unit.
L31
not connect
not connect
1 System with multiple indoor units (10HP, 20HP)
29
7-5.External input/output specifications
(1) Input/output specifications
Function Usage Signals
Function Usage Signal
Input
Start/stop Turning ON/OFF the indoor unit
· Pulse [Factory setting: Dip SW1-9 ON](a-contact with voltage/without voltage) ✻1
<With voltage> Power Source: DC12~24V Electrical Current: Approximately 10mA (DC12V)
<Standard Pulse>
Sending a command to perform dehumidifi-cation with priority
LevelRefer to the wiring diagram <Dehumidification command> shown on the page31.
· Level [Dip SW1-9 OFF]
Output
No.1OperationStatus
Obtaining signals indicating operation status of indoor units in each refrigerant circuit.
Relay a-contact output DC 30V or AC 220~240V
Standard Current : 1AMinimum Current : 1mA
No. 1Error Status
Obtaining signals indicating error status of indoor units in each refrigerant circuit.
No. 2OperationStatus
Obtaining signals indicating operation status of indoor units in each refrigerant circuit.
No. 2Error Status
✻
✻
✻ 20HP only
Obtaining signals indicating error status of indoor units in each refrigerant circuit.
over 200ms(Pulse powering time)
over 200ms(Pulse interval)
✻1 Use minute-current contact (DC12V 1mA)
Dehumidi-fication signal
Short: operateOpen: stop
30
(2) Wiring
External input/output board
Power Source for Display
No.1 Operation Status
No.1 Error Status
✻ No.2 Operation Status
✻ 20HP only
✻ No.2 Error Status
Common
Stop/Start
Input with voltage
Input without voltage
Relay Contact Point Output
Stop/Start
External power source
Connection to terminal board Connection with connectors
(✻1) For instructions on how to install the short-circuit plate, refer to "Caution on using the external input function" shown on the next page. Wiring distance 100 m or less.
SW12
L1
L2
L3
L4
(*1) Short circuit plate
(*1) Short circuit plate
SW11
CN53
1
2
3
4
5
1
2
3
4
5
TB21
TB22
TB23
XA
XB
XC
XE
XD
XE
XD
XC
XB
XA
COM
1
2
BC
B1
B2
AC
A1
A2
3
4
5
CN54
<Input with Applied Voltage>DC12~24VElectrical current input (per contact)Approximately 10mA (DC12V)
SW12Remote start/stop switchEach pressing of the SW (Pulse input) switches between ON and OFF.
Remote start/stop✻ Each pressing of the SW (Pulse input) switches
between ON and OFF.
External powersource
<Input without voltage applied>
Contact: Minimum applicable load DC12V 1mAContact rating DC12V 0.1A and over
SW11
<Relay contact output>DC30V or less 1AAC220-240V 1A
No.1 Operation Status Indicator LampL1
No.1 Error Status Indicator LampL2
Power supplyfor displays
No.2 Operation Status Indicator LampL3
No.2 Error Status Indicator LampL4
Relay(Permissible Electrical Current: 10mA~1A)
XA~XE
● Setting on the Indoor UnitConfirm the following setting when using external input.1 No.1, No.2 Controller board Dip SW 3-8: ON (Factory Setting: ON; External input will not be available when OFF.)2 No.1, No.2 address board Dip SW 1-10: OFF (Factory Setting: OFF; External input will not be available when ON.)3 Normal/Local switch inside the unit controller box is set to “Normal.” (Factory Setting: Normal; External input will not be
available when it is set to “Local.”)
31
● Caution on using the external input function (20HP only)
54321COMB2B1BCA2A1AC
TB23 TB21 TB22
CN53 CN54
External input-output board
Short-circuit plate
External input-output board
54321COMB2B1BCA2A1AC
TB23 TB21 TB22
CN53 CN54
Short-circuit plate
External input
<The case of with-voltage input>
· Connecting the short-circuit plate
<The case of no-voltage input>
External input
When using the external input function on the indoor unit that is connected to a two-refrigerant circuit, connect the short-circuit plate that is supplied with the unit to the appropriate terminals on the external input-output board.Without the short-circuit plate, the unit will not function properly.Don’t connect the short-circuit plate in case of a one-refrigerant circuit.
Caution
1 Brown
SW: Dehumidification command Z : Relay
Contact: Minimum applicable load DC12V 1mAContact rating DC12V 0.1A and over
Relay power supply
Indoor unitcontroller circuit board
Adapter forremote display(PAC-SA88HA) Relay circuit Remote controller board
Z SW
CN52
5 Green
Z
<Dehumidification command>
32
(3) Wiring Method
1 Check the indoor unit setting (Refer to 7-5.(2) Wiring )2 When using the external output function, connect each signal line to External output Terminal (TB22)
on the unit, depending on the usage.3 When using external input function, peal the outer layer of the signal line off, and connect it to external
input terminal (TB21 or TB23) on the unit, depending on the usage.
54
32
1CO
MB2
B1BC
A2A1
AC
TB23TB21
TB22
CN
53C
N54
✻1
✻1
Fix the wire on the high-voltage (AC220-240V) clamp. Pull the wire through the hole for transmission line to outside the unit. ✻3
Fix the wire on the low-voltage (below DC30V) clamp. Pull the wire through the hole for transmission line to outside the unit. ✻2
To CN51 of No.1 board
To CN51 of No.2 board
Wiring inside the unit
Wiring On Site
✻1 For instructions on how to install the short circuit plate on the 20HP indoor unit, refer to "Caution on using theexternal input function" shown on the previous page.
✻2 Do not bundle with high-voltage (AC220-240V) wire, since noise interference from such wire may cause theunit to malfunction.
✻3 Do not bundle with minute-voltage (DC30V or below) wire, since noise interference from such wire may causethe unit to malfunction.
Caution1) Wiring should be covered by insulation tube with supplementary insulation.2) Use relays or switches with IEC or equivalent standard.3) The electric strength between accessible parts and control circuit should have 2750V or more.4) TB21 is a terminal specifically for No-voltage contact point input. Do not apply voltage to TB21, since it
must result in malfunction of indoor unit controller board.5) TB23 is specifically for contact point input with voltage. Check the polarity before connecting to avoid
damage to the unit.6) Keep the wires on the input side and on the output side away from each other when using AC220-
240V as a power source for displays.7) Keep the length of the extension part of external signal line under 100m.8) 20HP is shipped with B1 and B2 terminals of TB21 and A1 and A2 terminals of TB23 short-circuited
respectively. Do not eliminate this feature. If it is eliminated, the units in one of the two refrigerant circuits may not operate.
33
(4) Switch setting
● The suction/discharge temperature control of the indoor unit.
Either suction temperature control or discharge temperature control can be selected .The suction/discharge temperature control can be switched by the switches (SWC) on the controller circuitboard inside the controller of the indoor unit. The discharge temperature control is selected at factory shipment. (SWC is set to “Standard.”) To switch the control, set SWC on two controller circuit boards inside the controller as follows.
To perform suction temperature control: Set SWC to “Option (OP)” To perform discharge temperature control: Set SWC to “Standard”
The setting for the SWC on the two controller circuit boards must be the same (applicable only when con-necting to a two-refrigerant circuit). *Only the suction temperature control is performed in the heating mode regardless of the SWC setting.
(5) Dehumidification priority control
This unit can be operated in the dehumidification priority control by receiving external signals (CN52 onindoor unit). The unit goes into the dehumidification priority control when dehumidification signal is received for 10 con-tinuous minutes during cooling operation. The unit resumes normal operation when the signal goes off orwhen the suction temperature reaches 13˚C or below. When the unit is in this control, the unit is operated at the maximum capacity regardless of the actual set-ting, so the room temperature may reach below the preset temperature. If this is a problem, install a circuit that turns off the dehumidification signal based on the room temperature. The model of units described in this manual does not support the reheat function, so it does not allow boththe temperature and humidity to be controlled simultaneously.
(6) Normal/Local switching switch (SW9)
When selecting the “Local” mode using the Normal/Local switching switch beside the MA remote controlleron indoor unit, the local operation is enabled, and the remote ON/OFF operation (external input or systemcontroller) is disabled.If no external input is available, the local operation is enabled in both “Nomal” and “Local” modes.The occurred error is not reported to the upper system, such as building management system including sys-tem controller. (If an error occurs during inspection, the occurred error is reported only to the units, and theerror history remains on the units.)
34
Only use optional parts recommended by Mitsubishi Electric. These parts should only be installed by a qualified technician. Improper installation may result in water leakage, electric shock, or fire.
WARNING
7-7.Notes on the use of optional accessories
7-6.System Rotation Control
Applicable UnitsIndoor units: PFD-P250, 500VM-EOutdoor unit: PUHY-P250YHM-A(-BS)
CAUTION To enable this control function, the following wiring and settings are required at installation.1) Daisy-chain terminals M1 and M2 on the terminal block for transmission line for
centralized control (TB7) on all applicable outdoor units.Move the power jumper connected to CN41 to CN40 on only one of the outdoor units.To supply power to the outdoor unit from a power supply unit, leave the power jumperconnected to CN41as it is (factory setting).
2) Check that the label on the indoor unit circuit board reads KE90D352, if it does not,replace the circuit board.
3) Set the SW1-9 and SW1-10 on indoor units as follows to enable the external input:(SW1-9: ON; SW1-10: OFF).
4) Assign sequential addresses to the units as shown below (Figure 1).(Only use odd numbers for the 10HP system.)
5) Make the rotation group settings by setting the appropriate switches on the outdoor units.
1. General Descriptions• Each group can consist of a maximum of 5 systems and a minimum of 2 systems.•With the use of this control function, one system in a given group serves as a backup andremains stopped.
•The unit designated as the control unit (System 1 in Figure 1) sends command signals to otherunits in the group to start or stop, and rotates the backup unit every 480 hours.
•Rotation sequence is in the ascending order of address, starting from the lowest address afterthe control unit address.(e.g., System 2→System 3→System 4→System 5→System 1 in Figure 1 below)
•If other units in the group detect an error or if there is a communication failure between thesystems, this control is terminated, and the backup unit goes into operation.
OC51
IC01
MA
Figure 1 Sample 20HP system group
OC52
IC02
OC53
IC03
MA
System 2
Backup unit
OC54
IC04
OC55
IC05
MA
System 3
OC56
IC06
OC57
IC07
MA
System 4
OC58
IC08
OC59
IC09
MA
System 5
OC60
IC10
System 1(Control unit)
TB7
TB3TB5
TB15
TB7
TB3TB5
TB15
35
8. Air Conditioning the Computer Room8-1 Main Features of the Floor-Duct Air Conditioners
8-2 Features of air-conditioner for computer room
Filter
Free-access top floor
Ceiling
Com
pute
r
This system is installed by building a floor over an existing floor and using the space between these two floors as an air-conditioning duct. This system has the following characteristics:
1 The temperature and humidity can efficiently and reliably be controlled, since the air-conditioned air issent directly to the machine.
2 It provides a comfortable environment for the operator, since the air can be conditioned to best suit theneeds of the operator and machines.
3 It is favorable in terms of appearance because the air-conditioning duct is out of sight.
4 The location of the duct is irrelevant when considering adding new machines or rearranging the existingmachines, since the entire floor serves as the air duct.
(1) Unlike plenum ventilation and overhead-duct type conditioners, since the conditioned air is not mixedwith the air in the room, the air that comes out of the unit has to meet the predetermined conditions(constant temperature/constant humidity) at the time the air exits the unit.Close attention must be paid to the auto-controlling system.
(2) Dust in the duct space (between the free-access top floor and the existing floor) must be thoroughlyremoved before installing the unit.
(3) Since the existing floor is cooled by the unit, it may produce dews on the ceiling of the room downbelow.
Air-conditioner for computer room is designed to maintain a constant room temperature and humidity. Forunderfloor air supply systems, providing air that meets predetermined requirements is a must. The com-pressor installed in this unit runs year around. The capacity controlled compressor regulates the outlet airtemperature (or inlet air temperature) depending on the load change. The humidifier (Configure to Order)installed in this unit humidifies a room to a target humidity, and regulates the humidity. With priority dehu-midification control (a dehumidifier must be installed on site), a room is dehumidified to a target humidity.Since the reheat function is not equipped, the room temperature may drop below the predetermined tem-perature due to a load inside the room. Therefore, the absolute humidity drops whereas the relativehumidity may not drop to a target humidity.
Caution
36
8-3 Step-by-Step Plan for the Implementation of the Air-Conditioning
Basic Conditions
Securing Necessary Rooms
Decision to Install the Air-Conditioning System
Selecting the Air-Conditioner Model
Selecting the Controllers
Total System Air-conditioning operation panel (secure individual operation circuit), Auto Controller (temperature and humidity indicator/recorder), management, safety, laws, maintenance, earthquake proof, anti-vibration (floor load, anti-vibration device), noise control, etc.
Calculating the Load
Setting the Conditions for the Room
Temperature/humidity Condition
Purpose Making decisions on the computer system
Accommodates possible future expansion (ensuring the acquisition route)
Operation schedule
Back-up system (in case of breakdowns, power outage, water-supply cut offs etc.)
Air conditioning methods (continuous, floor-duct type etc.)
Computer room, CVCF room, MT Disk Storage room
Supplementary computer room, system surveillance room
Programmer room, operator room
Battery room, transformer room
37
8-4 Conditions for the Installation of Computer-Room Air Conditioners
Computer
Fan
Air conditioner
Air intake
Free-accessfloor
Air discharge
(1) Outdoor Temperature and Humidity
Generally the values set for general air conditioners are used, although the value higher than the maxi-mum outdoor temperature and humidity may be set for devices like computer-room air conditioners thatmust keep the air temperature and humidity under predetermined levels.
(2) Indoor Temperature and Humidity
There is a wide range of conditions set by different computer manufacturers, and the conditions need tobe set in consultation with the manufacturers. The most basic conditions include keeping dew condensa-tion and static electricity from forming. It is also necessary to keep the room free of dust to ensure asmooth operation of the computer.
(3) Matching the Volume of Air Flow
It is possible to use the fan on the computer to cool the room. This controlling method requires a certainvolume of cold air in proportion to the amount of heat produced by the device. The inlet panel is located atthe bottom of the unit, and the exhaust pipe is located either on the ceiling, front and back, or on the side.
(4) Considering a Back-up Air Conditioning System
When the system is not allowed to stop at all, a back-up system is necessary. There are several different options for a back-up as the following:
1 Installing two sets of air conditioning systems necessary for the computer.2 Utilizing regular office air conditioners (for people)3 Using one of the units as a back-up
1 is used infrequently due to high costs involved. 2 involves many technical problems such as the difference between preset conditions for computer rooms and office rooms. In general, 3 is a preferredmethod. If 3 is chosen, the unit method (package method) is more economical than the central method.
38
8-5 Setting the Air conditioners
20.9kW
5
20W/m2
60Hz
Computer-generated heat
Number of workers
Lighting
Temperature and humidity
Frequency
Indoor ˚CDB/Indoor WBT : 24˚C/17˚C˚CDB of the air going into the computer : 18˚C
(1) Air-Conditioning Load
(2) Sample Selection of Air Conditioners
(2-1) Conditions
Windows
Inside Measurement
Surroundings
(W: 4.5m, H: 1.5m) ✕ 2
Ceiling height 2.2m
Upstairs room, downstairs room, heat and air conditioning
(2-2) Building Conditions
1 Coefficient of Overall Heat Transmission U (W/m2 ·K)
Summer 3.6, Winter 3.8
2.05
Summer 5.93, Winter 6.5
Floor (free access)
Outer Walls
Inner Walls
Ceiling
Floor
Windows
Downward convection 3.36, upward convection 3.3
Downward convection 3.05, upward convection 4.56
Downward convection 2.42, upward convection 3.3
2 Internal Load
1 Once the floor plan is made and the conditions for the air-conditioning system are set, air conditioningcapacity has to be determined by calculating the load.
2 Unlike the outdoor air, computer load remains constant throughout the year. However, it is possiblethat there are considerable fluctuations within a day. This is due to the fact that, depending on the timeof the day, there are changes in the number of computers that are turned on and that the differentcomputer systems are in operation.
3 If there is a plan to expand the current computer system in the future, it is important to include theload for the units to be added in the future when calculating the thermal load because it is practicallyimpossible to keep the computers off for days on end during the installation of the new units.
4 The following items need to be checked before calculating the unit capacity:· Floor area of the computer room (m2)· Total quantity of heat generated by computers
Number of People in the Room 5 Lighting 20W/m2
Calculator 20.9kWDraft 0.2 times/h
3 Volume of Outdoor Air Intake
25m3/h·person
Window
39
(2-3) Calculating the Load and Selecting a Model
1 Load (in the summer with air-conditioning)
2 Necessary Air Circulation
3 Model Selection
< Sensible Heat > SH
< Latent Heat > LH
Total load is 28.8kW
Computer
Lighting
Number of people in the room
Infiltration draft
Outer wall (heat transmission)
Windows (radiation)
Windows (heat transmission)
Inner wall(heat transmission)
Outside air
1,800W
5 persons ✕ 64 (U)
(0.2 times/h) 39.6m3 ✕ 0.336 ✕ 8
8.5m2 ✕ 3.6 ✕ 8
13.5m2 ✕ 0.65 ✕ 188
13.5 ✕ 5.93 ✕ 8
61.6 ✕ 2.05 ✕ 4
125m3 ✕ 0.336 ✕ 8
20.9 kW
1.8 kW
0.32 kW
0.11 kW
0.25 kW
1.91 kW
0.64 kW
0.5 kW
0.34 kW
26.8 kWTotal
Infiltration draft
Number of people in the room
Outside air
39.6 ✕ 834 ✕ 0.0117
5 persons ✕ 82
125m3 ✕ 834 ✕ 0.0117
0.39 kW
0.41 kW
1.22 kW
2.0 kWTotal
26800
0.336 ✕ (24 -18)V = ÷ 60 = 221m3/min
Calculate the temperature difference by setting the outdoor temperature; then, calculate hourly loads.The chart shows the result of a calculation, supposing that the system reaches its highest load at 12 o'clock.Outdoor temperatures in this example Summer : 32˚CDB relative humidity 60%
Winter : -2˚CDB relative humidity 42%
PUHY-P250YHM-A ✕ 2, PFD-P500VM-E typeIndoor ˚CDB 24˚C / Indoor ˚CWB 17˚C outdoor ˚CDB 32˚CCapacity of the Moment 54.3kW SHF = 0.92Capacity of Sensible Heat 54.3 ✕ 0.92 = 49.9/kWStandard Air-Flow Volume: 320m3/min can be accommodated with PUHY-P250YHM-A ✕ 2 and PFD-P500VM-E.
40
8-6 Automatic Control of the Computer Room
✻1✻2
< Outdoor Unit >
Free-Access Floor
< Indoor unit >
Suctiontemperaturesensor
Discharge temperature sensor
RA
SA
TB3 TB3
Controller
Terminal Bed forExternal Input/Output
Remote Controller
ExamplePFD-P500VM-E automatically controls the cooling temperature with a built-in controller. (suction temperature or discharge temperature control)This unit is designed for high sensible-heat specifications, and it does not include a humidifier or a dehumidi-fier. Install such components as necessary.
✻1 Bold lines in the diagram indicate refrigerant piping (gas/liquid).This system consists of two refrigerant circuit.
✻2 Indicates TB3-type transmission line used to communicate with the indoor unit.This system is made up of two circuit.
41
9. Maintenance/Inspection9-1. Maintenance/Inspection Schedule
Indo
orO
utdo
or
Fan Motor 6 months 40000 hours Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
YesYes
Bearing 6 months 40000 hours
Fan Belt 6 months 8000 hours
Air Filter 3 months 5 years Yes
Drain Pan 6 months 8 years
Add lubricant once a year
Disposable parts
Maintenance schedule changes depending on the local conditions
Drain Hose 6 months 8 years
Linear Expansion Valve 1 year 25000 hours
Heat Exchanger 1 year 5 years
Float Switch 6 months 25000 hours
Display Lamp (LED) 1year 25000 hours
Compressor 6 months 40000 hours
Fan motor 6 months 40000 hours
Linear Expansion Valve1 year 25000 hours
Heat Exchanger 1 year 5 years
Pressure Switch 1 year 25000 hours
PartsCheck every
Replace after
Daily check
Periodically check Remarks
Yes
4-way valve
1 year 25000 hours
Unit
Having the units inspected by a specialist on a regular basis, in addition to regular maintenance such aschanging the filters, will allow the users to use them safely and in good condition for an extended period oftime.The chart below indicates standard maintenance schedule.
(1) Approximate Long evity of Various Parts
The chart shows an approximate longevity of parts. It is an estimation of the time when old parts mayneed to be replaced or repairs need to be made.It does not mean that the parts must absolutely be replaced (except for the fan belt).Please note that the figures in the chart do not mean warranty periods.
(2) Notes
The above chart shows a maintenance schedule for a unit that is used under the following conditions:A. Less than 6 times per hour of compressor stoppageB. The unit stays on 24 hours a day.
Shortening the inspection cycle may need to be considered when the following conditions apply:When used in high temperature/high humidity area or when used in a place where the temperatureand/or humidity fluctuate greatlyWhen plugged into an unstable power source (sudden change in voltage, frequency, wave distor-tions) (Do not exceed the maximum capacity.)When the unit is installed in a place where it receives vibrations or major impacts.When used in a place with poor air quality (containing dust particles, salt, poisonous gas such assulfuric acid gas and sulfuric hydrogen gas, oil mist).
Even when the above maintenance schedule is followed, there could be unexpected problems thatcannot be predicted.
Holding of PartsWe will hold parts for the units for at least 9 years after the termination of the production of the unit,following the standards set by the ministry of economics and industries.
1
2
3
4
42
(3) Details of Maintenance/Inspection
. Check for unusual noise
. Measure the insulation resistance
. Check for excessive slack . Check for wear and tear . Check for unusual noise
. Check for unusual noise
. Free of unusual noise
. Insulation resistance over 1M
. Resistance (30~40N/belt) . Adequate amount of slack=5mm. Belt length=no longer than 102% of the original length
. Free of wear and tear
. Free of unusual noise
. Free of unusual noise
Replace when insulation resistance is under 1M
. Check for clogging of the drainage system
. Check for loosened bolts
. Check for corrosion
. Check for clogging of the drainage system
. Chec
. Check the drainage of the drain trap
k for corrosion
. Clean, free of clogging
. Free of loose screws
. No major disintegration
Clean if dirty or cloggedTighten boltsReplace if extremely worn
. Perform an operation check using the operation data
. Adequately controls the air temperature
Replace if malfunctioning
. Check for torn wire, fraying, and unplugged connectors
. Check insulation resistance
. No frayed or cut wires or unplugged connectors
. Insulation resistance over 1M
Replace when cut or shorted, when the insulation resistance goes below 1M , or if there is a history of abnormal operation
. Perform an operation check using the operation data
. Adequately controls the air temperature
Replace if malfunctioning
. Check for clogging, dirt, and damage
. Clean, free of clogging or damage
Clean
. Check for unusual noise
. Measure insulation resistance
. Free of unusual sound
. Insulation resistance over 1MReplace if insulation resistance goes below 1M
. Make sure the lamp comes on . Comes on when the output is . Rapid drop in brightness
on Replace if the light does not come on when the power is on
. Perform an operation check using the operation data
. Adequately controls the refrigerant temperature when the valve is switched (Check temperature change when cooling/heating is switched.)
Replace if malfunctioning
. Check for clogging and tear
. Clean the filter
. Clean, free of damage Clean the filterReplace if extremely dirty or damaged
. Check the outer appearance
. Make sure its free of foreign objects
. Free of frayed or cut wires
. Free of foreign objectsReplace if damaged or extremely wornRemove foreign objects
. Clean, free of clogging
. Free of wear and tearClean if dirty or cloggedReplace if ePour water into the drain trap
xtremely worm
. Check for unusual noise
. Check insulation resistance
. Check for loosened terminals
. Free of unusual sound
. Insulation resistance over 1M
. Free of loosened terminals
Replace if insulation resistance goes below 1M (under the condition that the refrigerant is not liquefied)Tighten loosened bolts
Adjust the beltReplace if the belt length exceeds 2% of the original length, worn, or used over 8000 hours
If the noise doesn't stop after lubrication, change the oil. Add lubricant once a year.
. Check for clogging, dirt, and damage
. Clean, free of clogging or damage
Clean
Parts
Fan motor
Bearing
Fan belt
Air filter
Linear expansion valve
Display lamp
Compressor
Fan motor
Linear expansion valve
6 months
6 months
6 months
6 months
3 months
Check pointsInspection
CycleUnit What to doAssessment
Drain pan
Drain hose
Float switch
Heat exchanger
Pressure switch
4-way valve
Indo
orO
utdo
or
1 year
1 year
1 year
Heat exchanger
(LED)
DATA BOOK PUHY-P250YHM-APFD-P250VM-EPFD-P500VM-E
Issued in June 2008 MEE07K622Printed in Japan
New publication effective June 2008.Specifications subject to change without notice.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN