AGENDA NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 First Draft Meeting Wednesday, July 29, 2015 InterContinental Milwaukee Milwaukee, WI Adobe Connect remote access available at: http://nfpa.adobeconnect.com/kbmeeting/ Voice available via telephone at: US (Toll): 1-719-867-1571 US/Canada (Toll Free): 1-877-860-3058 Participant Code: 955879 1. Call to order. Call meeting to order by Chair Henry Paszczuk at 8:00 a.m. on July 29, 2015 at the InterContinental Milwaukee Hotel, Milwaukee, WI. 2. Introduction of committee members and guests. For a current committee roster, see page 02. 3. Approval of May 23, 2013 second draft meeting minutes. See page 004. 4. The process staff PowerPoint presentation. See page 07. 5. Correlating committee minutes with direction for 2018 editions. See page 24. 6. NFPA 101 First Draft preparation. For Public Input, see page 39. 7. NFPA 5000 First Draft preparation. For Public Input, see page 100. 8. Other business. 9. Future meetings. 10. Adjournment. Enclosures Page 1 of 171

AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

AGENDA

NFPA Technical Committee on Interior Finish and Contents

NFPA 101 and NFPA 5000 First Draft Meeting Wednesday, July 29, 2015

InterContinental Milwaukee

Milwaukee, WI

Adobe Connect remote access available at: http://nfpa.adobeconnect.com/kbmeeting/

Voice available via telephone at:

US (Toll): 1-719-867-1571

US/Canada (Toll Free): 1-877-860-3058

Participant Code: 955879

1. Call to order. Call meeting to order by Chair Henry Paszczuk at 8:00 a.m. on July 29,

2015 at the InterContinental Milwaukee Hotel, Milwaukee, WI.

2. Introduction of committee members and guests. For a current committee roster, see

page 02.

3. Approval of May 23, 2013 second draft meeting minutes. See page 004.

4. The process – staff PowerPoint presentation. See page 07.

5. Correlating committee minutes with direction for 2018 editions. See page 24.

6. NFPA 101 First Draft preparation. For Public Input, see page 39.

7. NFPA 5000 First Draft preparation. For Public Input, see page 100.

8. Other business.

9. Future meetings.

10. Adjournment.

Enclosures

Page 1 of 171

Page 2: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Address List No PhoneInterior Finish and Contents SAF-INT

Safety to Life

Kristin Bigda07/09/2015

SAF-INT

Henry Paszczuk

ChairConnecticut Department of Public Safety102 Jeffrey LaneBerlin, CT 06037Alternate: Joseph Kingston

E 4/15/2004SAF-INT

Kristin Bigda

Secretary (Staff-Nonvoting)National Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

6/29/2007

SAF-INT

Vytenis Babrauskas

PrincipalFire Science and Technology Inc.9000 - 300th Place SEIssaquah, WA 98027-8832

SE 10/1/1993SAF-INT

Patrick Boyer

PrincipalState Farm Insurance Company1501 Rhodes LaneBloomington, IL 61704

I 08/09/2012

SAF-INT

Matthew Carrigan

PrincipalMontgomery County Fire Rescue Service100 Edison Park Drive, 2nd FloorGaithersburg, MD 20878International Association of Fire FightersAlternate: Rick J. Daughtery

L 07/29/2013SAF-INT

Peter S. Cutrer

PrincipalRochester Fire Department37 Wakefield StreetRochester, NH 03867

E 10/29/2012

SAF-INT

Nicholas A. Dawe

PrincipalCobb County Fire Marshal’s Office1595 County Services ParkwayMarietta, GA 30008

E 10/20/2010SAF-INT

William E. Fitch

PrincipalPhyrefish.com31 SE 5th Street, Suite 3815Miami, FL 33131-2528

SE 1/1/1991

SAF-INT

Marcelo M. Hirschler

PrincipalGBH International2 Friar’s LaneMill Valley, CA 94941Alternate: Timothy Earl

SE 1/1/1991SAF-INT

James K. Lathrop

PrincipalKoffel Associates, Inc.81 Pennsylvania AvenueNiantic, CT 06357Bobrick Washroom Equipment, Inc.Alternate: Alan Gettelman

M 07/29/2013

SAF-INT

Richard T. Long, Jr.

PrincipalExponent, Inc.17000 Science Drive, Suite 200Bowie, MD 20715-4427Upholstered Furniture Action Council

M 10/18/2011SAF-INT

Thomas W. McKeon

PrincipalEverest National Insurance6600 Boulevard EastSuite 10EWest New York, NY 07093

I 04/08/2015

SAF-INT

C. Anthony Penaloza

PrincipalIntertek Testing Services16015 Shady Falls RoadElmendorf, TX 78112

RT 3/21/2006SAF-INT

Milosh T. Puchovsky

PrincipalWorcester Polytechnic InstituteDepartment of Fire Protection Engineering100 Institute RoadWorcester, MA 01609

SE 10/20/2010

1

Page 2 of 171

Page 3: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Address List No PhoneInterior Finish and Contents SAF-INT

Safety to Life

Kristin Bigda07/09/2015

SAF-INT

Shelley Siegel

PrincipalUniversal Design & Education Network9268 Palomino DriveLake Worth, FL 33467-1024American Society of Interior Designers

U 7/20/2000SAF-INT

Dwayne E. Sloan

PrincipalUL LLC12 Laboratory DrivePO Box 13995Research Triangle Park, NC 27709-3995Alternate: Randall K. Laymon

RT 7/26/2007

SAF-INT

Rick J. Daughtery

AlternateCity of Fort Thomas Fire Department1904 Appeals CourtIndependence, KY 41051International Association of Fire FightersPrincipal: Matthew Carrigan

L 07/29/2013SAF-INT

Timothy Earl

AlternateGBH International6862 Shallowford WayPortage, MI 49024Principal: Marcelo M. Hirschler

SE 8/9/2011

SAF-INT

Alan Gettelman

AlternateBobrick Washroom Equipment Inc.1161 Hart StreetNorth Hollywood, CA 91605Principal: James K. Lathrop

M 08/11/2014SAF-INT

Joseph Kingston

AlternateConnecticut Office of State Fire Marshal1111 Country Club RoadMiddletown, CT 06451Principal: Henry Paszczuk

E 03/05/2012

SAF-INT

Randall K. Laymon

AlternateUL LLC333 Pfingsten RoadNorthbrook, IL 60062-2096Principal: Dwayne E. Sloan

RT 7/26/2007SAF-INT

Kristin Bigda

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

6/29/2007

2

Page 3 of 171

Page 4: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting

MINUTES

Thursday, May 23, 2013 DoubleTree by Hilton Hotel San Diego Downtown

1646 Front Street San Diego, California

1. Call to Order. The meeting was called to order by Chair, Henry Paszczuk, at 8:00 a.m. on May 23, 2013 at the Double Tree by Hilton Hotel, San Diego, California.

Introduction of Committee Members and Guests.

TECHNICAL COMMITTEE MEMBERS PRESENT

NAME COMPANY Henry Paszczuk, Chair Connecticut Department of Public Safety Kristin Bigda, Secretary NFPA Peter Cutrer, Principal Sanford Fire Department Nicholas Dawe, Principal Marcelo Hirschler, Principal GBH International Milosh Puchovsky, Principal Worcester Polytechnic Institute Shelley Siegel, Principal Universal Design & Education Network

Rep.: American Society of Interior Designers James Lathrop, Voting Alternate Koffel Associates, Inc.

Rep: The Carpet and Rug Institute

GUESTS

NAME COMPANY Alan Gettelman Bobrick Washroom Equipment

Page 4 of 171

Page 5: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

TECHNICAL COMMITTEE MEMBERS NOT PRESENT

NAME COMPANY Vytenis Babrauskas, Principal Fire Science and Technology Inc. Patrick Boyer, Principal State Farm Insurance Company William Fitch, Principal Phyrefish.com Richard Long, Principal Exponent, Inc.

Rep.: Upholstered Furniture Action Council C. Penaloza, Principal Intertek Testing Services Dwayne Sloan, Principal Underwriters Laboratories Inc.

3. Approval of Previous Meeting Minutes. The May 23, 2012 meeting minutes were approved as written and distributed.

4. The New Process Review. Staff Liaison Kristin Bigda used the PowerPoint presentation included in the agenda to discuss the Second Draft phase of the new codes and standards development process.

5. Definitions Task Group Report. Marcelo Hirschler volunteered to represent BLD/SAF-INT on the definitions task group.

6. Hazardous Materials Task Group. Chapter 10 in NFPA 101 and 5000 do not contain

provisions related to hazardous materials therefore the Committee did not have any direct input for the Correlating Committee at this time.

7. NFPA 101 Second Draft (formerly ROC) Review. All public comments, correlating

notes, and committee inputs were addressed. Additional Second Revisions were developed as needed. See Second Draft ballot package and draft.

8. NFPA 5000 Second Draft (formerly ROC) Review. All public comments, correlating notes, and committee inputs were addressed. Additional Second Revisions were developed as needed. See Second Draft ballot package and draft.

9. Other Business.

Review of proposed fire test document The committee reviewed the proposal for a new fire test standard that would provide a test method to evaluate fire/ignition resistance of upholstered furniture subject to a flaming ignition source. The committee was in support of the proposal.

10. Future Meetings. The BLD/SAF-INT committee has completed its meetings for the 2015 revision cycle. The next meeting of the committee will be held sometime in the summer of 2016.

11. Adjournment. The meeting was adjourned by Chair Henry Paszczuk at 11:15 am on Thursday, May 23, 2013.

Page 5 of 171

Page 6: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Meeting Minutes Prepared By:

Kristin Bigda, NFPA Staff

Page 6 of 171

Page 7: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

1

NFPA 101 / 5000 First Draft Meetings

InterContinental HotelMilwaukee, Wisconsin

July 27-31 and August 24-28, 2015

NFPA First Draft Meeting

nfpa.org 2

At this and all NFPA committee meetings we are concerned with your safety

If the fire alarm sounds, please egress the building

Page 7 of 171

Page 8: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

2

NFPA First Draft Meeting

• Please verify/update your contact information on roster attached to sign-in list

• Members categorized in any interest category who have been retained to represent the interests of ANOTHER interest category (with respect to issues addressed by the TC) shall declare those interests to the committee and refrain from voting on those issues throughout the process

nfpa.org 3

Members

NFPA First Draft Meeting

• All guests are required to sign in and identify their affiliations

• Participation is limited to TC members or those individuals who have previously requested time to address the committee

• Participation by other guests is permitted at the Chair’s discretion

nfpa.org 4

Guests

Page 8 of 171

Page 9: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

3

NFPA First Draft Meeting

• Use of audio recorders or other means capable of reproducing verbatim transcriptions of this meeting is not permitted

nfpa.org 5

Members and Guests

Annual 2017 Revision Cycle – Key Dates

• Public Input Stage (First Draft): First Draft Meeting: July 27-31 and August 24-28, 2015 Posting of First Draft for Balloting Date: before October 26, 2015 Posting of First Draft for Public Comment: March 7, 2016

• Comment Stage (Second Draft): Public Comment Closing Date: May 16, 2016 Second Draft Meeting Period: TBD - June 1 to July 25, 2016 Posting of Second Draft for Balloting Date: September 5, 2016 Posting of Second Draft for NITMAM: January 16, 2017

• Tech Session Preparation: NITMAM Closing Date: February 20, 2017 NITMAM / CAM Posting Date: April 17, 2017 NFPA Annual Meeting: June 4-7, 2017 (Boston)

• Standards Council Issuance: Issuance of Documents with CAM: August 10, 2017

nfpa.org 6

Page 9 of 171

Page 10: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

4

NFPA First Draft Meeting

• Either Principal or Alternate can vote; not both

• All Principals are encouraged to have an Alternate

• Voting (simple majority) during meeting is used to establish a sense of agreement on First Revisions

• Voting (simple majority) during meeting is also used to establish Public Input resolution responses and to create Committee Inputs

nfpa.org 7

Voting During the First Draft Meeting

NFPA First Draft Meeting

• Follow Robert’s Rules of Order

• Discussion requires a motion

nfpa.org 8

General Procedures

Page 10 of 171

Page 11: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

5

NFPA First Draft Meeting

• Not in order when another member has the floor

• Requires a second

• Not debatable and DOES NOT automatically stop debate

• 2/3 affirmative vote immediately closes debate, returns to the original motion

• Less than 2/3 allows debate to continue

nfpa.org 9

Motion to End Debate, Previous Question, or to “Call the Question”

NFPA First Draft Meeting

• Member addresses the chair

• Receives recognition from the chair

• Member introduces the motion

• Another member seconds the motion

nfpa.org 10

Committee member actions:

Page 11 of 171

Page 12: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

6

NFPA First Draft Meeting

• Restates the motion

• Calls for discussion

• Ensures all issues have been heard

• Calls for a vote

• Announces the vote result

nfpa.org 11

Committee chair actions:

12nfpa.org

Page 12 of 171

Page 13: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

7

NFPA First Draft Meeting

• Resolve Public Input (PI)

• Create a First Revision (FR)

• Create a Committee Input (CI) – a placeholder used to solicit Public Comments and permit further work at Second Draft stage

nfpa.org 13

Committee Actions and Motions:

NFPA First Draft Meeting

• Committee develops a Committee Statement (CS) to respond to (i.e., resolve) a Public Input

• Committee indicates in CS its reasons for not accepting the recommendation and/or points to a relevant First Revision

• PI does not get balloted

nfpa.org 14

Resolve a Public Input (PI)

Page 13 of 171

Page 14: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

8

NFPA First Draft Meeting

• FR is created to change current text or add new text

• Committee Statement (CS) is developed to substantiate the change

• Associated PIs get a committee response, often simply referring to the relevant FR

• Each FR gets balloted

nfpa.org 15

Create a First Revision (FR)

NFPA First Draft Meeting

• Committee is not ready to incorporate a change into the First Draft but wants to receive Public Comment on a topic that can be revisited at Second Draft stage

• Committee Statement (CS) is developed to explain committee’s intent

• CI is not balloted

nfpa.org 16

Create a Committee Input (CI)

Page 14 of 171

Page 15: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

9

NFPA First Draft Meeting

• All Public Input must receive a Committee Statement

• Provide a valid technical reason

• Do not use vague references to “intent”

• Explain how the submitter’s substantiation is inadequate

• Reference a First Revision if it addresses the intent of the submitter’s Public Input

nfpa.org 17

Committee Statements (Substantiation):

NFPA First Draft Meeting

• In-meeting votes establish a sense of agreement on the development of First Revisions (FR)

• FRs are secured by electronic balloting (≥2/3 of completed ballots affirmative, and affirmative by ≥1/2 voting members)

• Only the results of the electronic ballot determine the official position of the committee on the First Draft

nfpa.org 18

Formal Voting on First Revisions

Page 15 of 171

Page 16: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

10

NFPA First Draft Meeting

• Only First Revisions (FR) are balloted

Public Inputs and Committee Statements not balloted

Reference materials are available

• First Draft, PI, CI, and CS

• Voting options:

Affirmative on all FRs

Affirmative on all FRs with exceptions specifically noted

• Ballot provides option to vote affirmative with comment

• Vote to reject or abstain requires a reason

nfpa.org 19

Ballots

NFPA First Draft Meeting

• Web-based balloting system

• Alternates are encouraged to return ballots

• Ballot session will time out after 90 minutes

• Use “submit” to save your work – ballots can be revised until the balloting period is closed

nfpa.org 20

Electronic Balloting

Page 16 of 171

Page 17: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

11

NFPA First Draft Meeting

nfpa.org 21

• Click link provided in ballot email

• Sign in with NFPA.org username and password

NFPA First Draft Meeting

nfpa.org 22

• Select either ‘Affirmative All’ or ‘Affirmative with Exception(s)’

Page 17 of 171

Page 18: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

12

NFPA First Draft Meeting

nfpa.org 23

• Use “See FR- #” link to review all First Revisions

• Use “edit election” to change individual votes or to modify vote after submitting ballot

NFPA First Draft Meeting

nfpa.org 24

• Make selection: Affirmative with Comment, Negative, or Abstain

• No selection defaults to affirmative

• Must include comment (reason) on each vote other than Affirmative

Page 18 of 171

Page 19: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

13

NFPA First Draft Meeting

nfpa.org 25

• To complete ballot click Participant Consent and Submit

• Return to edit any votes by ballot due date

NFPA First Draft Meeting

• Initial ballot

• Circulation of negatives and comments – electronic balloting is re-opened to permit members to change votes

• Any First Revision that fails ballot becomes a Committee Input (CI)

nfpa.org 26

Balloting

Page 19 of 171

Page 20: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

14

Legal

• Must comply with state and federal antitrust laws

• Participants are to conduct themselves in strict accordance with these laws

• Read and understand NFPA’s Antitrust Policy which can be accessed at nfpa.org/regs

nfpa.org 27

Antitrust Matters

Legal

• Participants must avoid any conduct, conversation or agreement that would constitute an unreasonable restraint of trade

• Conversation topics that are off limits include: Profit, margin, or cost data

Prices, rates, or fees

Selection, division or allocation of sales territories, markets or customers

Refusal to deal with a specific business entity

nfpa.org 28

Antitrust Matters (cont’d)

Page 20 of 171

Page 21: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

15

Legal

• NFPA’s standards development activities are based on openness, honesty, fairness and balance

• Participants must adhere to the Regulations Governing the Development of NFPA Standards and the Guide for the Conduct of Participants in the NFPA Standards Development Process which can accessed at nfpa.org/regs

• Follow guidance and direction from your employer or other organization you may represent

nfpa.org 29

Antitrust Matters (cont’d)

Legal

• Manner is which standards development activity is conducted can be important

• The Guide of Conduct requires standards development activity to be conducted with openness, honesty and in good faith

• Participants are not entitled to speak on behalf of NFPA

• Participants must take appropriate steps to ensure their statements whether written or oral and regardless of the setting, are portrayed as personal opinions, not the position of NFPA

• Be sure to ask questions if you have them

nfpa.org 30

Antitrust Matters (cont’d)

Page 21 of 171

Page 22: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

16

Legal

• Disclosures of essential patent claims should be made by the patent holder

• Patent disclosures should be made early in the process

• Others may also notify NFPA if they believe that a proposed or existing NFPA standard includes an essential patent claim

• NFPA has adopted and follows ANSI’s Patent Policy

• It is the obligation of each participant to read and understand NFPA’s Patent Policy which can accessed at nfpa.org/regs

nfpa.org 31

Patents

TC Struggles with an Issue

• TC needs data on a new technology or emerging issue

• Two opposing views on an issue with no real data

• Data presented is not trusted by committee

Code Fund Lends a Hand

• TC rep and/or staff liaison submits a Code Fund Request

• Requests are reviewed by a Panel and chosen based on need / feasibility

Research Project Carried Out

• Funding for project is provided by the Code Fund and/or industry sponsors

• Project is completed and data is available to TC

www.nfpa.org/codefund

Page 22 of 171

Page 23: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 / 5000 First Draft MeetingsMilwaukee, Wisconsin

17

Document Information PagesAbout

• Document scope• Table of contents• Articles• Research and

statistical reports• Latest codes and

standards news on NFPA Today blog feed

• Free access

Current and Previous Editions

• Issued TIAs, FIs, Errata

• Archived revision information such as meeting and ballot information, First Draft Reports (previously ROPs), Second Draft Reports (previously ROCs), and Standards Council and NITMAM information

Next Edition

• Revision cycle schedule

• Posting & closing dates

• Submit public input/comments via electronic submission system.

• Meeting and ballot information

• First Draft Report and Second Draft Report

• NITMAM information• Standard Council

Decisions• Private TC info (*red

asterisk)• Ballot circulations,

informational ballots and other committee info

Technical Committee

• Committee name and staff liaison

• Committee scope and responsibility

• Committee list with private information

• Committee documents (codes & standards) in PDF format

• Committees seeking members

• Online committee membership application

Have a

productive

meeting

Page 23 of 171

Page 24: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

MINUTES Joint Teleconference / Adobe Connect Meeting of

NFPA Correlating Committee on Building Code (BLD-AAC) NFPA Correlating Committee on Safety to Life (SAF-AAC)

March 10, 2015

1. Call to Order. Teleconference / Adobe Connect meeting called to order by SAF-

AAC Chair Bill Koffel at 11:00 a.m. Eastern on March 10, 2015. BLD-AAC Chair

Jim Quiter was unable to attend.

2. Attendance Roll Call. Staff called the roll of BLD-AAC and SAF-AAC and recorded

the members who responded as being present.

The following members were in attendance:

NAME COMPANY BLD-AAC SAF-AAC William Koffel Koffel Associates, Inc. Non-Voting

Member

Chair

Jerry Wooldridge Reedy Creek Improvement District Secretary

Chad Beebe ASHE – AHA

Rep.: TC on Board and Care

Facilities

Non-Voting

Member

Non-Voting

Member

Wayne Carson Carson Associates, Inc.

Rep.: TC on Fundamentals

Non-Voting

Member

Non-Voting

Member

Shane Clary Bay Alarm Company

Rep.: Signaling Systems Correlating

Committee

Principal: Wayne Moore

Alternate to

Non-Voting

Member

David Collins The Preview Group, Inc.

Rep.: TC on Means of Egress

Non-Voting

Member

Non-Voting

Member

John Devlin Aon Fire Protection Engineering

Corp.

Rep.: TC on Fire Protection Features

Non-Voting

Member

Non-Voting

Member

Salvatore DiCristina Rutgers, The State University of

New Jersey

Rep.: Bulding Code Development

Committee

Principal

Victor Dubrowski Code Consultants, Inc.

Re.: TC on Educational and Day-

Care Occupancies

Non-Voting

Member

Non-Voting

Member

Page 24 of 171

Page 25: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NAME COMPANY BLD-AAC SAF-AAC David Frable US General Services Administration Principal

Randy Gaw Rep.: TC on Detention &

Correctional Occupancies

Non-Voting

Member

Non-Voting

Member

John Harrington FM Global Principal

Howard Hopper UL LLC Principal Principal

Stephen Hrustich Gwinnett County Fire & Emergency

Services

Rep.: International Association of

Fire Chiefs

Principal

Jonathan Humble American Iron and Steel Institute Principal

Gerald Jones Rep: Building Seismic Safety

Council/Code Resource Support

Committee

Principal

J. Edmund Kalie Jr. Prince George’s County Government Principal

Gary Keith FM Global

Principal: John Harrington

Alternate

David P. Klein US Department of Veteran Affairs

Rep.: TC on Health Care

Occupancies

Non-Voting

Member

Non-Voting

Member

Amy Murdock Code Consultants, Inc.

Rep.: TC on Mercantile & Business

Occupancies

Non-Voting

Member

Non-Voting

Member

Isaac Papier Honeywell, Inc.

Rep.: National Electrical

Manufacturers Association

Principal

Henry Paszczuk Connecticut Dept. of Public Safety

Rep.: TC on Interior Finish &

Contents

Non-Voting

Member

Non-Voting

Member

Ronald Reynolds Virginia State Fire Marshal’s Office

Rep.: International Fire Marshals

Association

Principal

Eric Rosenbaum Jensen Hughes

Rep.: American Health Care

Association

Principal

Faimeen Shah Vortex Fire Engineering

Consultancy

Principal

Jeffrey Tubbs Arup

Rep.: TC on Assembly Occupancies

Non-Voting

Member

Non-Voting

Member

Robert Upson National Fire Sprinkler Association

Principal: Jeffrey Hugo

Alternate

Joseph Versteeg Versteeg Associates

Rep.: TC on Alternative Approaches

to Life Safety

Non-Voting

Member

Non-Voting

Member

Leon Vinci Health Promotion Consultants

Rep: American Public Health

Association

Principal: Jake Pauls

Alternate

Page 25 of 171

Page 26: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

The following members were not in attendance:

NAME COMPANY BLD-AAC SAF-AAC James Quiter Arup Chair Principal

Sam Francis American Wood Council Principal

Raymond Hansen US Department of the Air Force Principal

John Kampmeyer, Sr. Triad Fire Protection Engineering

Corp.

Principal

Russell Leavitt Telgian Corporation

Rep.: American Fire Sprinkler

Association

Principal

Michael Newman Johnson & Johnson

Rep.: NFPA Industrial Fire

Protection Section

Principal

Daniel O’Connor Aon Fire Protection Engineering

Rep.: American Hotel & Lodging

Association

Principal

Richard Jay Roberts Honeywell Life Safety

Rep.: National Electrical

Manufacturers Association

Principal

The following guests were in attendance:

NAME COMPANY Kristin Bigda National Fire Protection Association

Ron Coté National Fire Protection Association

Allan Fraser National Fire Protection Association

Daniel Gorham National Fire Protection Association

Gregory Harrington National Fire Protection Association

Robert Solomon National Fire Protection Association

3. Minutes Approval. Minutes of the BLD-AAC November 8, 2013 and SAF-AAC

November 7, 2013 meetings were approved as distributed.

4. Liaison Reports. Sprinkler Project. Bill Koffel presented the sprinkler project liaison report. There

were no significant changes being made to NFPA 13, 13D and 13R (vis a vis NFPA

101/5000) in the current revision cycle (Annual 2015). NITMAMS are awaited. The

NFPA 13 revisions include re-inserting the sprinkler exemption for apartment unit

bathrooms.

Fire Alarm Project. Shane Clary presented the fire alarm project liaison report.

There were no significant changes being made to NFPA 72 (vis a vis NFPA

101/5000) in the current revision cycle (Annual 2015). NITMAMS are awaited.

Page 26 of 171

Page 27: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

5. Supplemental Operating Procedures. SAF-AAC Chair Bill Koffel advised that he

and BLD-AAC chair Jim Quiter will appoint a task group to review the supplemental

operating procedures; compare its features to the NFPA Regulations Governing the

Development of NFPA Standards (Regs); and determine what, if anything, needs to

be retained in some form. Correlating committee members were asked to review the

procedures; identify any items that need to be retained; and communicate such to

staff.

6. Hazardous Materials – NFPA 101. The NFPA 101 Hazardous Materials Task

Group report was noted as received. Task Group Chair Jeff Tubbs was asked to

submit the proposed changes as official Public Input, on behalf of the task group, by

the July 6 closing date. Staff advised that the SAF-FUN, SAF-MEA, and SAF-FIR

technical committees would each address the portion of the recommended changes

that apply to their assigned chapters. Proposed new Annex C (a repository for

information on the NFPA documents that address hazardous materials) would be

addressed by SAF-FUN. The Correlating Committee would perform any needed

correlation among the technical committee actions.

7. NFPA 101/5000 2018-Edition Work Areas. The activity / plans updates from the

technical committee chairs and the development of subject areas for focus during the

2018 edition revision cycle were handled together. The resulting issues, for

consideration by the technical committees, follow:

SUBJECT NOTES NFPA 101 NFPA 5000

Glossary of Terms Direction needed on how to

proceed with definitions (on-

going)

All TCs based

on definition

assignments

All TCs based

on definition

assignments

Resilient design

concepts

Emerging topic but may pilot

a project for BLD/SAF-HEA

in 2015

HEA

Other TCs

might

consider

HEA

Other TCs

might

consider

Hazardous materials in

NFPA 101

How should code regulate

egress provisions related to

health hazards and not just

fire? (Jeff Tubbs Task

Group)

FUN, MEA,

FIR with AAC

review

Hazardous materials in

NFPA 5000

Review Chapter 34

provisions for things like

dead ends and common path

of travel

IND

Smoke compartment

size increase in health

care

Conditions needed to allow

larger compartment size in

hospitals/nursing homes

HEA HEA

CO detection in Only residential occupancy BCF BCF

Page 27 of 171

Page 28: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

SUBJECT NOTES NFPA 101 NFPA 5000

residential B&C without CO provisions;

Correlating Committee asked

earlier for a TIA

Security/safety/code

conflicts (re: schools,

in particular)

Should have content to

review from 12/2014 School

Security/Safety Workshop

FUN re: doc

Scope

expansion;

MEA, END;

Other TCs

might

consider re:

active shooter

FUN re: doc

Scope

expansion;

MEA, END;

Other TCs

might

consider re:

active shooter

Elevator use Incorporate the latest and

greatest information from

ASME

MEA, FUN BSY, MEA,

FUN

Home health care May consider joint NFPA

99/NFPA 101 project to

address durable medical

equipment (DME), safety

measures, and backup power

HEA, possible

co-ordination

w/ RES

Means of egress

remoteness

How is remoteness of exit

access potentially impacted

by vertical openings?

MEA, FIR MEA, FIR

Exterior wall

assemblies and NFPA

285

Review FPRF report (June

2014) and determine if

changes needed for NFPA

5000

BLC, SCM

“Life safety” sprinkler

systems

Introduce discussion on

scope, use and limitations of

NFPA 13D and NFPA 13R

for:

- Other than residential

occupancies

- 5- and 6-story buildings

integrating ‘pedestal

construction’ (13R)

BCF, RES BCF, RES,

BLC

NFPA 13R attic

protection

What is expected

performance level? Lives

saved but building lost

RES, BCF RES, BCF

Buildings under

construction

Evaluate application of

NFPA 241 to systems and

buildings

FUN FUN

Term “temporary” Expand definition to consider

use of temporary systems as

well as buildings/structures

FUN FUN

Page 28 of 171

Page 29: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

SUBJECT NOTES NFPA 101 NFPA 5000

Location, design,

hardening of egress

stairs based on wind

hazard

Avoid stair designs that utilize

glass on exterior walls.

Alternatively, look at use of

ASTM E1886, Standard Test

Method for Performance of

Exterior Windows, Curtain

Walls, Doors, and Impact

Protective Systems Impacted

by Missile(s) and Exposed to

Cyclic Pressure Differentials,

and/or ASTM E1996,

Standard Specification for

Performance of Exterior

Windows, Curtain Walls,

Doors, and Impact Protective

Systems Impacted by

Windborne Debris in

Hurricanes. See NIST NCST

report on Joplin, MO tornado.

FIR, MEA FIR, MEA,

SCM

In-building storm

shelter spaces

Add scoping and reference to

ANSI/NSSA/ICC 500 for

certain occupancies.

Various – incl

FUN (Scope);

AXM, END,

MER

Various – incl

FUN (Scope);

AXM, END,

MER, BLC,

SCM

Stair descent devices Add scoping, how many and

where

MEA,

Various

occupancies

BSY, MEA,

Various

occupancies

UMC technical review Close review for “conflicts”

with 90A, 90B, and other

NFPA documents (e.g.,

flexible air duct/connector

length)

BSF BSY

Roof egress New section on egress

requirements for roofs with

mechanical equipment

MEA MEA

Private

homes/dwellings

rented as B&Bs

Trend of private homeowners

advertising their home for

short stay rentals

(airbnb.com) but not licensed

or regulated in any way.

Might be more of a Pub Ed

issue.

RES RES

Life Safety Evaluation

for assembly

Continue the upgrading effort AXM AXM

Page 29 of 171

Page 30: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

SUBJECT NOTES NFPA 101 NFPA 5000

occupancies

Falls over guards in

arenas and stadia

FPRF report AXM AXM

Opening protectives

(door, windows)

ratings

Chair convened a task group FIR FIR

Inspection, testing,

maintenance (ITM) of

fire escape stairs

Consider National Fire

Escape Assn materials

MEA MEA

Day-care age for self-

preservation

FPRF report END END

Ambulatory health care

occupant load factor

2 FPRF reports HEA HEA

Apartments for the

elderly

Is there a special risk or is

special protection needed?

Revisit 1981 edition of

NFPA 101

RES RES

Open malls Chair convened a task group MER MER

Evacuation chairs Scoping and use of RESNA

standard

BSY

Accessibility reference

updating

2010 ADA; expected update

of ANSI A117.1

BSY

Green roofing systems FM Global has installation

data sheet and approval

standard

SCM

Tall timber buildings FPRF report BLC

Height and area FPRF compilation, but no

objective criteria developed

BLC

8. Other Business. No other business was raised.

9. Next Meeting. The BLD-AAC and SAF-AAC correlating committees will meet to

address NFPA 5000/101 First Draft correlation issues in December 2015 or early

January 2016.

10. Adjournment. The meeting was adjourned at 12:00 p.m. Eastern.

Minutes prepared by Ron Coté and Kelly Carey

Page 30 of 171

Page 31: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 264-NFPA 101-2015 [ Section No. 3.3.51 ]

3.3.51 * Critical Radiant Flux.

The level of incident radiant heat energy in units of W/cm2 on a floor-covering system at themost distant flameout point. (SAF-INT)

Statement of Problem and Substantiation for Public Input

Errata: asterisk missing in spite of annex note

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 263-NFPA 101-2015 [Section No. A.3.3.51]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 14:02:40 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 618 7/7/2015 8:49 AMPage 31 of 171

Page 32: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 185-NFPA 101-2015 [ Section No. 3.3.92.4 ]

3.3.92.4 * Interior Wall Finish.

The interior finish of columns, fixed or movable walls, and fixed or movable partitions.(SAF-INT)

A.3.3.92.4 Such partitions are intended to include washroom water closet partiitons.

Statement of Problem and Substantiation for Public Input

This annex note somehow ended up (after revisions in the code) in A.10.2.1.5 but it belongs here.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 186-NFPA 101-2015 [Section No. A.10.2.1.5]

Public Input No. 187-NFPA 101-2015 [New Section after A.3.3.92.3]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 24 19:13:11 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 618 7/7/2015 8:49 AMPage 32 of 171

Page 33: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 263-NFPA 101-2015 [ Section No. A.3.3.51 ]

A.3.3.51 Critical Radiant Flux.

Critical radiant flux is the property determined by the test procedure of NFPA 253, StandardMethod of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant HeatEnergy Source or by ASTM E648Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source . The unit of measurement of critical

radiant flux is watts per square centimeter (W/cm2).

(Also add ASTM E648 (2014c) to the annex on informational ASTM references)

Statement of Problem and Substantiation for Public Input

This just adds the equivalent ASTM standard, consistent with other references to NFPA 253.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 264-NFPA 101-2015 [Section No. 3.3.51]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jul 02 13:59:52 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

518 of 618 7/7/2015 8:49 AMPage 33 of 171

Page 34: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 180-NFPA 101-2015 [ Section No. 10.2 ]

10.2 *

Interior Finish.

10.2.1 *

General

.

10.2.1.1

Classification of interior finish materials shall be in accordance with tests made underconditions simulating actual installations, provided that the authority having jurisdiction ispermitted to establish the classification of any material for which classification by a standardtest is not available

, unless otherwise provided in 10.

2.1.2 or 10.2.1.4 .

10.2.1.2

The provisions of 10.2.1.1 shall not apply to materials having a total thickness of less than 1 ⁄ 28in. (0.9 mm) that are applied directly to the surface of walls and ceilings where both of the followingconditions are met:

(1) The wall or ceiling surface is a noncombustible or limited-combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish whentested in accordance with 10.2.3 , using fiber cement board as the substrate material.

10.2.1.3

If a material having a total thickness of less than 1 ⁄ 28 in. (0.9 mm) is applied to a surface that isnot noncombustible or not limited-combustible, the provisions of 10.2.1.1 shall apply.

10.2.1.4

Approved existing installations of materials applied directly to the surface of walls and ceilings in a

total thickness of less than 1 ⁄ 28 in. (0.9 mm) shall be permitted to remain in use, and theprovisions of 10.2.2 through 10.2.3.7.2 shall not apply.

10.2.1.5*

Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied structurallyor for decoration, acoustical correction, surface insulation, or other purposes shall be consideredinterior finish and shall not be considered decorations or furnishings.

10.2.1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 17 7/8/2015 4:07 PMPage 34 of 171

Page 35: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

6 3 Lockers constructed of combustible materials shall be considered interior finish.

10.2. 1.4 For fire-retardant coatings, see 10. 2

* .6.

10.2.2* Use of Interior Finishes.

10.2.2.1

Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies (see Chapter 7 andChapters 11 through 43 )

(2) As specified in 10.2.3 through 10.2.6 .

10.2.2.2 *

Interior floor finish shall comply with 10.2.7 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in the Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent to

floor finishes with a critical radiant flux of at least 0.1 W/cm 2

10.2.3 *

Interior Wall or Ceiling Finish Testing and Classification.

InteriorWhen interior wall or ceiling finish

thatis required elsewhere in this Code to be

Class A, Class B, or Class C shall be classified based on test results from ASTM E 84, StandardTest Method for Surface Burning Characteristics of Building Materials , or ANSI/UL 723, Standardfor Test for Surface Burning Characteristics of Building Materials , except as indicated inclassified for fire performance and smoke development it shall be classified in accordance with10.2.3.1 or 10.2.3. 3, except as indicated in sections 10. 2 . 4.

10.2.3.1

Exposed portions of structural members complying with the requirements for Type IV(2HH)construction in accordance with NFPA 220, Standard on Types of Building Construction , or with thebuilding code shall be exempt from testing and classification in accordance with ASTM E 84,Standard Test Method for Surface Burning Characteristics of Building Materials , or ANSI/UL 723,Standard for Test for Surface Burning Characteristics of Building Materials .

10.2.3.2

Interior wall and ceiling finish materials tested in accordance with NFPA 286. Interior walland ceiling finish

testedmaterials shall be classified in accordance with NFPA 286, Standard Methods of Fire Tests for

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 17 7/8/2015 4:07 PMPage 35 of 171

Page 36: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth , and

meeting the conditions ofcomply with Section 10.2.3.

7.2 shall be permitted to be used where interior wall and ceiling finish is required to be Class A inaccordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials , or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials .2. Materials tested in accordance with section 10.2.3.1 and complying with Section 10.2.3.2shall be considered also to comply with the requirements of a Class A, Class B or Class C inaccordance with Section 10.2.3.3.

10.2.3.

3

For fire-retardant coatings, see 10.2.6 .

2 Acceptance criteria for NFPA 286. The interior finish shall comply with the following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. For new installations, the total smoke released throughout the test shall not exceed 1,000

m 2 .

10.2.3.

4 * Products required to be3* Interior wall and ceiling finish materials tested in accordance with ASTM E84 orANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance withASTM E 84 , Standard Test Method for Surface Burning Characteristics of BuildingMaterials , or ANSI/UL 723 , Standard for Test for Surface Burning Characteristics ofBuilding Materials ,

shall be grouped in the classes described inexcept as indicated in Sections 10.2.3.4

.1 throughand 10.2.3.

4.3 in5 . Such interior finish materials shall be grouped in the following classes in accordance withtheir flame spread

indexand smoke

developed index, except as indicated in 10.2.3.4.4 .

10.2.3.4.1 Class A Interior Wall and Ceiling Finish.

Class A interior wall and ceiling finishes shall be those finishes with a flame spread index of 0–25and a smoke developed index of 0–450 and shall include any material classified at 25 or less onthe flame spread index test scale and 450 or less on the smoke developed index test scale.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

3 of 17 7/8/2015 4:07 PMPage 36 of 171

Page 37: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.3.4.2 Class B Interior Wall and Ceiling Finish.

Class B interior wall and ceiling finishes shall be those finishes with a flame spread index of 26–75and a smoke developed index of 0–450 and shall include any material classified at more than 25but not more than 75 on the flame spread index test scale and 450 or less on the smoke developedindex test scale.

10.2.3.4.3 Class C Interior Wall and Ceiling Finish.

Class C interior wall and ceiling finishes shall be those finishes with a flame spread index of76–200 and a smoke developed index of 0–450 and shall include any material classified at morethan 75 but not more than 200 on the flame spread index test scale and 450 or less on the smokedeveloped index test scale.

-developed indexes .

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.

43 .

4 1 Existing interior finish shall be exempt from the smoke developed index criteria of 10.2.3.

4.1 through3.

10.2.3.

4.3 .

10.2

.3.5 The classification of interior finish specified in 10.2.3.

43 shall be that of the basic material used by itself or in combination with other materials.

10.2.3.

6 3.3 Wherever the use of Class C interior wall and ceiling finish is required, Class A or Class Bshall be permitted. Where Class B interior wall and ceiling finish is required, Class A shall bepermitted.

10.2.3.

7 * Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for EvaluatingRoom Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panelsand Walls , shall comply with the criteria of4 Materials complying with the requirements of Section 10.2.3.

7.1. Products1 shall not be required to be tested in accordance with

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

4 of 17 7/8/2015 4:07 PMPage 37 of 171

Page 38: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling InteriorFinish to Room Fire Growth , shall comply with the criteria of10.2.3.

73 .

2.

10.2.3.

7.1 * The interior finish shall comply with all of the following when tested using method B of thetest protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire GrowthContribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls :

During the 40 kW exposure, flames shall not spread to the ceiling.

The flame shall not spread to the outer extremities of the samples on the 8 ft × 12 ft (2440 mm ×3660 mm) walls.

Flashover, as described in NFPA 265, shall not occur.

For new installations, the total smoke released throughout the test shall not exceed 1000 m 2

5 Materials described in sections 10.2.4 shall be tested as described in the correspondingsections .

10.2.

3.7.2

The interior finish shall comply with all of the following when tested using the test protocol of NFPA286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finishto Room Fire Growth :

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

(3) Flashover, as described in NFPA 286, shall not occur.

(4) The peak heat release rate throughout the test shall not exceed 800 kW.

(5) For new installations, the total smoke released throughout the test shall not exceed 1000

m 2 .

4* Interior wall and ceiling finish materials with special requirements. The materialsindicated in Sections 10.2.4.1 through 10.2.4

* Specific Materials..16 shall be tested as indicated in the corresponding sections.

10.2.4.1

* Textile Wall and Textile Ceiling Materials. The use of textile materials on walls or ceilings shallcomply with oneThickness exemption. The provisions of 10.2.3 shall not apply to materials having a totalthickness of less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls andceilings where both of the following conditions

:

Textile materials meeting the requirements of Class A when tested in accordance with1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

5 of 17 7/8/2015 4:07 PMPage 38 of 171

Page 39: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

ASTM E 84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials , or ANSI/UL 723, Standard for Test for Surface Burning Characteristics ofBuilding Materials , using the specimen preparation and mounting method of ASTM E 2404,Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric(Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended tobe Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics (see10.2.3.4 ), shall be permitted on the walls or ceilings of rooms or areas protected by anapproved automatic sprinkler system.

Textile materials meeting the requirements of Class A when tested in accordance withASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method ofASTM E 2404 (see 10.2.3.4 ), shall be permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever isless.

2.

Textile materials meeting the requirements of Class A when tested in accordance withASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method ofASTM E 2404 (see 10.2.3.4 ) , shall be permitted to extend not more than 48 in. (1220mm) above the finished floor on ceiling-height walls and ceiling-height partitions.

3.

Previously approved existing installations of textile material meeting the requirements ofClass A when tested in accordance with ASTM E 84 or ANSI/UL 723 (see 10.2.3.4 ) shallbe permitted to be continued to be used.

4.

Textile materials shall be permitted on walls and partitions where tested in accordance withNFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contributionof Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls . (See10.2.3.7 .)

5.

Textile materials shall be permitted on walls, partitions, and ceilings where tested inaccordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution ofWall and Ceiling Interior Finish to Room Fire Growth . (See 10.2.3.7 .)

6.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

6 of 17 7/8/2015 4:07 PMPage 39 of 171

Page 40: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.2 * Expanded Vinyl Wall and Expanded Vinyl Ceiling Materials.

The use of expanded vinyl wall or expanded vinyl ceiling materials shall comply with one of thefollowing conditions:

(1) Materials meeting the requirements of Class A when tested in accordance with ASTM E 84,Standard Test Method for Surface Burning Characteristics of Building Materials , or ANSI/UL723, Standard for Test for Surface Burning Characteristics of Building Materials , using thespecimen preparation and mounting method of ASTM E 2404 , Standard Practice forSpecimen Preparation and Mounting of Textile, Paper, or Polymeric (Including Vinyl) Wall orCeiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over aWood Substrate, to Assess Surface Burning Characteristics (see 10.2.3.4 ), shall bepermitted on the walls or ceilings of rooms or areas protected by an approved automaticsprinkler system.

(2) Materials meeting the requirements of Class A when tested in accordance with ASTM E 84or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E 2404(see 10.2.3.4 ), shall be permitted on partitions that do not exceed three-quarters of thefloor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less.

(3) Materials meeting the requirements of Class A when tested in accordance with ASTM E 84or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E 2404(see 10.2.3.4 ), shall be permitted to extend not more than 48 in. (1220 mm) above thefinished floor on ceiling-height walls and ceiling-height partitions.

(4) Previously approved existing installations of materials meeting the requirements for theoccupancy involved, when tested in accordance with ASTM E 84 or ANSI/UL 723 (see10.2.3.4 ), shall be permitted to be continued to be used.

(5) Materials shall be permitted on walls and partitions where tested in accordance with NFPA265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution ofTextile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls. (See 10.2.3.7 .)

(6) Materials shall be permitted on walls, partitions, and ceilings where tested in accordancewith NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall andCeiling Interior Finish to Room Fire Growth. (See 10.2.3.7 .)

10.2.4.3 Cellular or Foamed Plastic.

are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish whentested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.1 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to asurface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shallapply.

10.2.4.1.2 Approved existing installations of materials applied directly to the surface of wallsand ceilings in a total thickness of less than 1⁄28 in. (0.9 mm) shall be permitted to remain inuse, and the provisions of 10.2.3 shall not apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural memberscomplying with the requirements for Type IV (2HH) construction in accordance with NFPA 220,Standard on Types of Building Construction , or with the building code shall be exempt from

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

7 of 17 7/8/2015 4:07 PMPage 40 of 171

Page 41: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be usedas interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2 . Therequirements of 10.2.4.3

through 10.2.4.3.2shall apply both to exposed foamed plastics and to foamed plastics used in conjunction with atextile or vinyl facing or cover.

10.2.4.3.1 *

Cellular or foamed plastic materials shall be permitted where subjected to large-scale fire teststhat substantiate their combustibility and smoke release characteristics for the use intendedunder actual fire conditions.

10.2.4.3.1.1

One of the following fire tests shall be used for assessing the combustibility of cellular orfoamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall andCeiling Interior Finish to Room Fire Growth , with the acceptance criteria of 10.2.3.

7.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material (including smoke

measurements, with total smoke release not to exceed 1000 m 2 )

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction

(4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall andRoof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels,Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2 *

The tests shall be performed on a finished foamed plastic assembly related to the actualend-use configuration, including any cover or facing, and at the maximum thickness intendedfor use.

10.2.4.3.2

Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent of the specific

wall or ceiling area to which it is applied, provided that it is not less than 20 lb/ft 3 (320

kg/m 3 ) in density, is limited to

1 ⁄ 21⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in width, and complies with the requirementsfor Class A or Class B interior wall and ceiling finish as described in 10.2.3.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

8 of 17 7/8/2015 4:07 PMPage 41 of 171

Page 42: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

43 ; however, the smoke developed index shall not be limited.

10.2.4.4 *

Light-Transmitting Plastics. Light-transmitting plastics shall be permitted to beTextile wall coverings. Where used as interior wall

and ceiling finish if approved by the authority having jurisdiction.finish materials, textile materials shall be tested in the manner intended for use, using theproduct mounting system, including adhesive, and shall comply with the requirements of one ofthe following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.

5 Decorations and Furnishings.

Decorations and furnishings that do not meet the definition of interior finish, as defined in 3.3.92.2 ,shall be regulated by the provisions of Section 10.3 .

10.2.4.6 Metal Ceiling and Wall Panels.

Listed factory finished metal ceiling and wall panels meeting the requirements of4.1 * Products tested in accordance with NFPA 265, Standard Methods of Fire Tests forEvaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings onFull Height Panels and Walls , shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested usingmethod B of the test protocol of NFPA 265, Standard Methods of Fire Tests for EvaluatingRoom Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full HeightPanels and Walls :

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft. (2440mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) For new installations, the total smoke released throughout the test shall not exceed 1000

m 2 .

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordancewith ASTM E84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials , or ANSI/UL 723, Standard for Test for Surface Burning Characteristics ofBuilding Materials , using the specimen preparation and mounting method of ASTM E2404,Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric(Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to beApplied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall bepermitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do notexceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions.

(4) Previously approved existing installations of textile material meeting the requirements of

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

9 of 17 7/8/2015 4:07 PMPage 42 of 171

Page 43: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Class A when tested in accordance with ASTM E84 or ANSI/UL 723 shall be permitted to becontinued to be used.

10.2.4.5* Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,expanded vinyl wall coverings shall be tested in the manner intended for use, using the productmounting system, including adhesive, and shall comply with the requirements of one of thefollowing: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textilematerials shall be tested in the manner intended for use, using the product mounting system,including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, StandardTest Method for Surface Burning Characteristics of Building Materials , or ANSI/UL 723,Standard for Test for Surface Burning Characteristics of Building Materials , using thespecimen preparation and mounting method of ASTM E2404, Standard Practice for SpecimenPreparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall orCeiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics , andshall be permitted on the ceilings of rooms or areas protected by an approved automaticsprinkler system .

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,expanded vinyl materials shall be tested in the manner intended for use, using the productmounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM

E 84E84 , Standard Test Method for Surface Burning Characteristics of Building Materials , orANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials

(see, using the specimen preparation and mounting method of ASTM E2404, Standard Practice forSpecimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and WoodWall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics ,and shall be permitted on the ceilings of rooms or areas protected by an approved automaticsprinkler system .

10.2.

3.4), shall be permitted to be finished with one additional application of paint. Such painted panelsshall be permitted for use in areas where Class A interior finishes are required. The total paint

thickness shall not exceed 1 ⁄ 28 in. (0.9 mm).4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materials otherthan wood are used, the lockers shall be considered interior finish and shall comply withSection 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustible

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

10 of 17 7/8/2015 4:07 PMPage 43 of 171

Page 44: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

materials shall be permitted to be used in any location where interior finish materials arerequired to meet a Class C classification in accordance with 10.2.3.

10.2.4.

7 9 Polypropylene (PP) and High-Density Polyethylene (HDPE).

Polypropylene and high-density polyethylene materials shall not be permitted as interior wallor ceiling finish unless the material complies with the requirements of 10.2.3.

7

1 .

2.

The tests shall be performed on a finished assembly and on the maximum thickness intendedfor use.

10.2.4.

8

10 Site-Fabricated Stretch Systems.

For new installations, site-fabricated stretch systems containing all three componentsdescribed in the definition in Chapter 3 shall be tested in the manner intended for use andshall comply with the requirements of 10.2.3 .1 or 10.2.3.

2

3 . If the materials are tested in accordance with ASTM

E 84

E84 , Standard Test Method for Surface Burning Characteristics of Building Materials , orANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with ASTM

E 2573

E2573 , Standard Practice for Specimen Preparation and Mounting of Site-FabricatedStretch Systems to Assess Surface Burning Characteristics .

10.2.4.

9

11 Reflective Insulation Materials.

Reflective insulation materials shall be tested in the manner intended for use and shall complywith the requirements of 10.2.3 . 1 or 10.2.3.3. If the materials are tested in accordance withASTM

E 84

E84 , Standard Test Method for Surface Burning Characteristics of Building Materials , orANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with ASTM

E 2599

E2599 , Standard Practice for Specimen Preparation and Mounting of Reflective Insulation,Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to AssessSurface Burning Characteristics .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

11 of 17 7/8/2015 4:07 PMPage 44 of 171

Page 45: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.

5

4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall panelsmeeting the requirements of Class A in accordance with 10.2.3, shall be permitted to befinished with one additional application of paint. Such painted panels shall be permitted foruse in areas where Class A interior finishes are required. The total paint thickness shall notexceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate . Laminatedproducts factory-produced with a wood substrate shall be tested in the manner intended foruse and shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are testedin accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics ofBuilding Materials , or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials , specimen preparation and mounting shall be inaccordance with ASTM E2579, Standard Practice for Specimen Preparation and Mounting ofWood Products to Assess Surface Burning Characteristics , using the product-mountingsystem (including adhesive) of actual use.

10.2.4.14 Facings or wood veneers intended to be applied on site over a wood substrate.Facings or veneers intended to be applied on site over a wood substrate shall be tested in themanner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If thematerials are tested in accordance with NFPA 286, Standard Methods of Fire Tests forEvaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they shalluse the product-mounting system, including adhesive, described in Section 5.8.9 of NFPA 286.If the materials are tested in accordance with ASTM E84, Standard Test Method for SurfaceBurning Characteristics of Building Materials , or ANSI/UL 723, Standard for Test forSurface Burning Characteristics of Building Materials , specimen preparation and mountingshall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation andMounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling CoveringsFacings and Veneers, to Assess Surface Burning Characteristics .

10.2.4.15* Light-Transmitting Plastics. Light-transmitting plastics shall be permitted tobe used as interior wall and ceiling finish if approved by the authority having jurisdiction.

10.2.4.16 Decorations and Furnishings. Decorations and furnishings that do not meet thedefinition of interior finish, as defined in 3.3.92.2, shall be regulated by the provisions ofSection 10.3.

10.2.5 Trim and Incidental Finish.

10.2.5.1

General.

Interior wall and ceiling trim and incidental finish, other than wall base in accordance with10.2.5.2 and bulletin boards, posters, and paper in accordance with 10.2.5.3 , not in excess of

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

12 of 17 7/8/2015 4:07 PMPage 45 of 171

Page 46: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10 percent of the specific wall and ceiling areas of any room or space to which it is appliedshall be permitted to be Class C materials in occupancies where interior wall and ceiling finishof Class A or Class B is required.

10.2.5.2

Wall Base.

Interior floor trim material used at the junction of the wall and the floor to provide afunctional or decorative border, and not exceeding 6 in. (150 mm) in height, shall meet therequirements for interior wall finish for its location or the requirements for Class II interiorfloor finish as described in 10.2.7.4 using the test described in 10.2.7.3 . If a Class I floorfinish is required, the interior floor trim shall be Class I.

10.2.5.3

Bulletin Boards, Posters, and Paper.

10.2.5.3.1

Bulletin boards, posters, and paper attached directly to the wall shall not exceed 20 percent ofthe aggregate wall area to which they are applied.

10.2.5.3.2

The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in sprinklerededucational or day-care occupancies in accordance with 14.7.4.3 (2), 15.7.4.3 (2), 16.7.4.3 (2),or 17.7.4.3 (2).

10.2.6 *

Fire-Retardant Coatings.

10.2.6.1 *

The required flame spread index or smoke developed index of existing surfaces of walls,partitions, columns, and ceilings shall be permitted to be secured by applying approvedfire-retardant coatings to surfaces having higher flame spread index values than permitted.Such treatments shall be tested, or shall be listed and labeled for application to the material towhich they are applied, and shall comply with the requirements of NFPA 703, Standard forFire Retardant–Treated Wood and Fire-Retardant Coatings for Building Materials .

10.2.6.2 *

Surfaces of walls, partitions, columns, and ceilings shall be permitted to be finished withfactory-applied fire-retardant

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

13 of 17 7/8/2015 4:07 PMPage 46 of 171

Page 47: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

-

coated products that have been listed and labeled to demonstrate compliance with therequirements of ASTM

E 2768

E2768 , Standard Test Method for Extended Duration Surface Burning Characteristics ofBuilding Materials, on the coated surface.

10.2.6.3

Fire-retardant coatings or factory-applied fire

-

retardant coated assemblies shall possess the desired degree of permanency and shall bemaintained so as to retain the effectiveness of the treatment under the service conditionsencountered in actual use.

10.2.7 *

Interior Floor Finish Testing and Classification.

10.2.7.1 *

Carpet and

carpetlike

carpet like interior floor finishes shall comply with ASTM

D 2859

D2859 , Standard Test Method for Ignition Characteristics of Finished Textile FloorCovering Materials.

10.2.7.2 *

Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for fire

performance, shall have a minimum critical radiant flux of 0.1 W/cm 2 .

10.2.7.3 *

Interior floor finishes shall be classified in accordance with 10.2.7.4 , based on test resultsfrom NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor CoveringSystems Using a Radiant Heat Energy Source, or ASTM

E 648

E648 , Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using aRadiant Heat Energy Source.

10.2.7.4

Interior floor finishes shall be grouped in the classes specified in 10.2.7.4.1 and 10.2.7.4.2 in

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

14 of 17 7/8/2015 4:07 PMPage 47 of 171

Page 48: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

accordance with the critical radiant flux requirements.

10.2.7.4.1

Class I Interior Floor Finish.

Class I interior floor finish shall have a critical radiant flux of not less than 0.45 W/cm 2 , asdetermined by the test described in 10.2.7.3 .

10.2.7.4.2

Class II Interior Floor Finish.

Class II interior floor finish shall have a critical radiant flux of not less than 0.22 W/cm 2 , but

less than 0.45 W/cm 2 , as determined by the test described in 10.2.7.3 .

10.2.7.5

Wherever the use of Class II interior floor finish is required, Class I interior floor finish shallbe permitted.

10.2.8

Automatic Sprinklers.

10.2.8.1

Other than as required in 10.2.4 , where an approved automatic sprinkler system is installedin accordance with Section 9.7 , Class C interior wall and ceiling finish materials shall bepermitted in any location where Class B is required, and Class B interior wall and ceilingfinish materials shall be permitted in any location where Class A is required.

10.2.8.2

Where an approved automatic sprinkler system is installed in accordance with Section 9.7 ,throughout the fire compartment or smoke compartment containing the interior floor finish,Class II interior floor finish shall be permitted in any location where Class I interior floorfinish is required, and where Class II is required, the provisions of 10.2.7.2 shall apply.

Additional Proposed Changes

File Name Description Approved

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

15 of 17 7/8/2015 4:07 PMPage 48 of 171

Page 49: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA_101_10.2_proposed_2018_complete_with_veneers_clean.docxComplete rewrite of section 10.2 - clean

NFPA_101_10.2_proposed_2018_complete_with_veneers.docx

Complete rewrite of section 10.2 with underline and strike out

Statement of Problem and Substantiation for Public Input

This reorganizes section 10.2 for a more logical organization but it does not change any of the requirements. The attachments show the way the sections will read if approved by the committee. The key issue is to recognize that the default test for assessing interior finish fire safety requirements is NFPA 286 (room-corner test) because any interior finish material is allowed to be tested to NFPA 286, while not all materials are allowed to be tested to ASTM E84 or to NFPA 265. In fact, foam plastics, HDPE and PP are not allowed to be tested to ASTM E84. Moreover, both textile wall and ceiling coverings and expanded vinyl wall coverings and ceiling coverings are only allowed to be tested to ASTM E84 under certain conditions. Also,while textile and expanded vinyl wall coverings are allowed to be tested to NFPA 265, neither textile nor expanded vinyl ceiling coverings are permitted to be tested to NFPA 265. Also, several materials are required to use special mounting methods in order to be tested to ASTM E84. Finally, this reorganization does incorporate both the very thin linings (< 1/28 of an inch) and the exposed portions of structural members in the same sections as all other products, while not changing the requirements.

As proposed in separate public inputs, new sections are proposed to be added dealing with "Laminated products factory-produced with a wood substrate" and "Facings or wood veneers intended to be applied on site over a wood substrate", which places into the code requirements that have been developed within ASTM committee E05 on Fire Standards in new sections on ASTM E84 mounting practices (ASTM E2579 and ASTM E2404, respectively). They are proposed as sections 10.2.4.13 and 10.2.4.14, respectively.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 123-NFPA 101-2015 [New Section after 10.2.4]

Public Input No. 124-NFPA 101-2015 [New Section after 10.2.4]

Public Input No. 188-NFPA 101-2015 [Section No. A.10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jun 21 17:47:00 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

16 of 17 7/8/2015 4:07 PMPage 49 of 171

Page 50: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

17 of 17 7/8/2015 4:07 PMPage 50 of 171

Page 51: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 – Sections 10.2 (2018)

10.2*

10.2.1* General

10.2.1.1 Classification of interior finish materials shall be in accordance with tests made

under conditions simulating actual installations, provided that the authority having

jurisdiction is permitted to establish the classification of any material for which classification

by a standard test is not available.

10.2.1.2* Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied

structurally or for decoration, acoustical correction, surface insulation, or other purposes

shall be considered interior finish and shall not be considered decorations or furnishings.

10.2.1.3 Lockers constructed of combustible materials shall be considered interior finish.

10.2.1.4 For fire-retardant coatings, see 10.2.6.

10.2.2* Use of Interior Finishes.

10.2.2.1 Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies (see Chapter 7 and Chapters 11 through 43) (2) As specified in 10.2.3 through 10.2.6.

10.2.2.2* Interior floor finish shall comply with 10.2.7 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in the Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent to

floor finishes with a critical radiant flux of at least 0.1 W/cm2

10.2.3* Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified for fire

performance and smoke development it shall be classified in accordance with 10.2.3.1 or

10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1 Interior wall and ceiling finish materials tested in accordance with NFPA 286.

Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286,

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and comply with Section 10.2.3.2. Materials tested in

accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be considered also

to comply with the requirements of a Class A, Class B or Class C in accordance with Section

10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with the

following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. For new installations, the total smoke released throughout the test shall not exceed 1,000

m2.

10.2.3.3* Interior wall and ceiling finish materials tested in accordance with ASTM E84 or

ANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance with

ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building

Page 51 of 171

Page 52: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, except as indicated in Sections 10.2.3.4 and 10.2.3.5. Such interior finish

materials shall be grouped in the following classes in accordance with their flame spread and

smoke-developed indexes.

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 Existing interior finish shall be exempt from the smoke developed index criteria of

10.2.3.3.

10.2.3.3.2 The classification of interior finish specified in 10.2.3.3 shall be that of the basic

material used by itself or in combination with other materials.

10.2.3.3.3 Wherever the use of Class C interior wall and ceiling finish is required, Class A or

Class B shall be permitted. Where Class B interior wall and ceiling finish is required, Class

A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not be required

to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

corresponding sections.

Page 52 of 171

Page 53: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4* Interior wall and ceiling finish materials with special requirements. The materials

indicated in Sections 10.2.4.1 through 10.2.4.16 shall be tested as indicated in the

corresponding sections.

10.2.4.1 Thickness exemption. The provisions of 10.2.3 shall not apply to materials having a

total thickness of less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls

and ceilings where both of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.1 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shall

apply.

10.2.4.1.2 Approved existing installations of materials applied directly to the surface of walls

and ceilings in a total thickness of less than 1⁄28 in. (0.9 mm) shall be permitted to remain in

use, and the provisions of 10.2.3 shall not apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural members

complying with the requirements for Type IV (2HH) construction in accordance with NFPA

220, Standard on Types of Building Construction, or with the building code shall be exempt

from testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be used as

interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2. The

requirements of 10.2.4.3 shall apply both to exposed foamed plastics and to foamed plastics

used in conjunction with a textile or vinyl facing or cover.

10.2.4.3.1* Cellular or foamed plastic materials shall be permitted where subjected to large-

scale fire tests that substantiate their combustibility and smoke release characteristics for

the use intended under actual fire conditions.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibility of

cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material (including smoke

measurements, with total smoke release not to exceed 1000 m2)

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction (4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2* The tests shall be performed on a finished foamed plastic assembly related to

the actual end-use configuration, including any cover or facing, and at the maximum

thickness intended for use.

Page 53 of 171

Page 54: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent of

the specific wall or ceiling area to which it is applied, provided that it is not less than 20 lb/ft3

(320 kg/m3) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in width,

and complies with the requirements for Class A or Class B interior wall and ceiling finish as

described in 10.2.3.3; however, the smoke developed index shall not be limited.

10.2.4.4* Textile wall coverings. Where used as interior wall finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting system,

including adhesive, and shall comply with the requirements of one of the following: section

10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1* Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using method

B of the test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.

(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) For new installations, the total smoke released throughout the test shall not exceed 1000

m2.

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordance

with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E2404,

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall

be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do not

exceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-

height partitions.

(4) Previously approved existing installations of textile material meeting the requirements of

Class A when tested in accordance with ASTM E84 or ANSI/UL 723 shall be permitted to be

continued to be used.

10.2.4.5* Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,

expanded vinyl wall coverings shall be tested in the manner intended for use, using the

product mounting system, including adhesive, and shall comply with the requirements of one

of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

Page 54 of 171

Page 55: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting system,

including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,

expanded vinyl materials shall be tested in the manner intended for use, using the product

mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materials other

than wood are used, the lockers shall be considered interior finish and shall comply with

Section 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustible

materials shall be permitted to be used in any location where interior finish materials are

required to meet a Class C classification in accordance with 10.2.3.

10.2.4.9 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropylene and

high-density polyethylene materials shall not be permitted as interior wall or ceiling finish

unless the material complies with the requirements of 10.2.3.1. The tests shall be performed

on a finished assembly and on the maximum thickness intended for use.

10.2.4.10 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretch

systems containing all three components described in the definition in Chapter 3 shall be

tested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or

10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics.

Page 55 of 171

Page 56: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.11 Reflective Insulation Materials. Reflective insulation materials shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting

shall be in accordance with ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics.

10.2.4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall panels

meeting the requirements of Class A in accordance with 10.2.3, shall be permitted to be

finished with one additional application of paint. Such painted panels shall be permitted for

use in areas where Class A interior finishes are required. The total paint thickness shall not

exceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate. Laminated products

factory-produced with a wood substrate shall be tested in the manner intended for use and

shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are tested in

accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with ASTM

E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, using the product-mounting system (including

adhesive) of actual use.

10.2.4.14 Facings or wood veneers intended to be applied on site over a wood substrate.

Facings or veneers intended to be applied on site over a wood substrate shall be tested in the

manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If

the materials are tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they shall

use the product-mounting system, including adhesive, described in Section 5.8.9 of NFPA

286. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics.

10.2.4.15* Light-Transmitting Plastics. Light-transmitting plastics shall be permitted to be

used as interior wall and ceiling finish if approved by the authority having jurisdiction.

10.2.4.16 Decorations and Furnishings. Decorations and furnishings that do not meet the

definition of interior finish, as defined in 3.3.92.2, shall be regulated by the provisions of

Section 10.3.

10.2.5 Trim and Incidental Finish.

10.2.5.1 General. Interior wall and ceiling trim and incidental finish, other than wall base in

accordance with 10.2.5.2 and bulletin boards, posters, and paper in accordance with 10.2.5.3,

Page 56 of 171

Page 57: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

not in excess of 10 percent of the specific wall and ceiling areas of any room or space to which

it is applied shall be permitted to be Class C materials in occupancies where interior wall

and ceiling finish of Class A or Class B is required.

10.2.5.2 Wall Base. Interior floor trim material used at the junction of the wall and the floor

to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height, shall

meet the requirements for interior wall finish for its location or the requirements for Class II

interior floor finish as described in 10.2.7.4 using the test described in 10.2.7.3. If a Class I

floor finish is required, the interior floor trim shall be Class I.

10.2.5.3 Bulletin Boards, Posters, and Paper.

10.2.5.3.1 Bulletin boards, posters, and paper attached directly to the wall shall not exceed

20 percent of the aggregate wall area to which they are applied.

10.2.5.3.2 The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in

sprinklered educational or day-care occupancies in accordance with 14.7.4.3(2), 15.7.4.3(2),

16.7.4.3(2), or 17.7.4.3(2).

10.2.6* Fire-Retardant Coatings.

10.2.6.1* The required flame spread index or smoke developed index of existing surfaces of

walls, partitions, columns, and ceilings shall be permitted to be secured by applying approved

fire-retardant coatings to surfaces having higher flame spread index values than permitted.

Such treatments shall be tested, or shall be listed and labeled for application to the material

to which they are applied, and shall comply with the requirements of NFPA 703, Standard

for Fire Retardant–Treated Wood and Fire-Retardant Coatings for Building Materials.

10.2.6.2* Surfaces of walls, partitions, columns, and ceilings shall be permitted to be finished

with factory-applied fire-retardant coated products that have been listed and labeled to

demonstrate compliance with the requirements of ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on the coated

surface. 10.2.6.3 Fire-retardant coatings or factory-applied fire retardant coated assemblies shall

possess the desired degree of permanency and shall be maintained so as to retain the

effectiveness of the treatment under the service conditions encountered in actual use.

10.2.7* Interior Floor Finish Testing and Classification.

10.2.7.1* Carpet and carpet like interior floor finishes shall comply with ASTM D2859,

Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. 10.2.7.2* Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for

fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2.

10.2.7.3* Interior floor finishes shall be classified in accordance with 10.2.7.4, based on test

results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source.

Page 57 of 171

Page 58: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.7.4 Interior floor finishes shall be grouped in the classes specified in 10.2.7.4.1 and

10.2.7.4.2 in accordance with the critical radiant flux requirements.

10.2.7.4.1 Class I Interior Floor Finish. Class I interior floor finish shall have a critical

radiant flux of not less than 0.45 W/cm2, as determined by the test described in 10.2.7.3.

10.2.7.4.2 Class II Interior Floor Finish. Class II interior floor finish shall have a critical

radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the test

described in 10.2.7.3.

10.2.7.5 Wherever the use of Class II interior floor finish is required, Class I interior floor

finish shall be permitted.

10.2.8 Automatic Sprinklers.

10.2.8.1 Other than as required in 10.2.4, where an approved automatic sprinkler system is

installed in accordance with Section 9.7, Class C interior wall and ceiling finish materials

shall be permitted in any location where Class B is required, and Class B interior wall and

ceiling finish materials shall be permitted in any location where Class A is required.

10.2.8.2 Where an approved automatic sprinkler system is installed in accordance with

Section 9.7, throughout the fire compartment or smoke compartment containing the interior

floor finish, Class II interior floor finish shall be permitted in any location where Class I

interior floor finish is required, and where Class II is required, the provisions of 10.2.7.2 shall

apply.

Page 58 of 171

Page 59: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 101 – Sections 10.2 (2018)

10.2.1* General

10.2.1.1 Classification of interior finish materials shall be in accordance with tests made

under conditions simulating actual installations, provided that the authority having

jurisdiction is permitted to establish the classification of any material for which classification

by a standard test is not available, unless otherwise provided in 10.2.1.2 or 10.2.1.4.

10.2.1.2 The provisions of 10.2.1.1 shall not apply to materials having a total thickness of less

than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings where both

of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.1.3 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.1.1 shall

apply.

10.2.1.4 Approved existing installations of materials applied directly to the surface of walls

and ceilings in a total thickness of less than 1⁄28 in. (0.9 mm) shall be permitted to remain in

use, and the provisions of 10.2.2 through 10.2.3.7.2 shall not apply.

10.2.1.2 10.2.1.5* Fixed or movable walls and partitions, paneling, wall pads, and crash pads

applied structurally or for decoration, acoustical correction, surface insulation, or other

purposes shall be considered interior finish and shall not be considered decorations or

furnishings.

10.2.1.3 10.2.1.6 Lockers constructed of combustible materials shall be considered interior

finish.

10.2.1.4 For fire-retardant coatings, see 10.2.6.

Section 10.2.2: No changes –

Section 10.2.3 and 10.2.4 – Delete in their entirety and replace by wording below

10.2.3* Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified for fire

performance and smoke development it shall be classified in accordance with 10.2.3.1 or

10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1 Interior wall and ceiling finish materials tested in accordance with NFPA 286.

Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286,

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and comply with Section 10.2.3.2. Materials tested in

accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be considered also

to comply with the requirements of a Class A, Class B or Class C in accordance with Section

10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with the

following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

Page 59 of 171

Page 60: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

5. The total smoke released throughout the test shall not exceed 1,000 m2.

10.2.3.3 Interior wall and ceiling finish materials tested in accordance with ASTM E84 or

ANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance with

ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, except as indicated in Sections 10.2.3.4 and 10.2.3.5. Such interior finish

materials shall be grouped in the following classes in accordance with their flame spread and

smoke-developed indexes.

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 Existing interior finish shall be exempt from the smoke developed index criteria of

10.2.3.3.

10.2.3.3.2 The classification of interior finish specified in 10.2.3.3 shall be that of the basic

material used by itself or in combination with other materials.

10.2.3.3.3 Wherever the use of Class C interior wall and ceiling finish is required, Class A or

Class B shall be permitted. Where Class B interior wall and ceiling finish is required, Class

A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not be required

to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

corresponding sections.

Page 60 of 171

Page 61: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4 Interior wall and ceiling finish materials with special requirements. The materials

indicated in Sections 10.2.4.1 through 10.2.4.15 shall be tested as indicated in the

corresponding sections.

10.2.4.1 Thickness exemption. The provisions of 10.2.3 shall not apply to materials having a

total thickness of less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls

and ceilings where both of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.1 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shall

apply.

10.2.4.1.2 Approved existing installations of materials applied directly to the surface of walls

and ceilings in a total thickness of less than 1⁄28 in. (0.9 mm) shall be permitted to remain in

use, and the provisions of 10.2.3 shall not apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural members

complying with the requirements for Type IV (2HH) construction in accordance with NFPA

220, Standard on Types of Building Construction, or with the building code shall be exempt

from testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be used as

interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2. The

requirements of 10.2.4.3 shall apply both to exposed foamed plastics and to foamed plastics

used in conjunction with a textile or vinyl facing or cover.

10.2.4.3.1* Cellular or foamed plastic materials shall be permitted where subjected to large-

scale fire tests that substantiate their combustibility and smoke release characteristics for

the use intended under actual fire conditions.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibility of

cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material (including smoke

measurements, with total smoke release not to exceed 1000 m2)

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction (4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2* The tests shall be performed on a finished foamed plastic assembly related to

the actual end-use configuration, including any cover or facing, and at the maximum

thickness intended for use.

Page 61 of 171

Page 62: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent of

the specific wall or ceiling area to which it is applied, provided that it is not less than 20 lb/ft3

(320 kg/m3) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in width,

and complies with the requirements for Class A or Class B interior wall and ceiling finish as

described in 10.2.3.3; however, the smoke developed index shall not be limited.

10.2.4.4 Textile wall coverings. Where used as interior wall finish materials, textile materials

shall be tested in the manner intended for use, using the product mounting system, including

adhesive, and shall comply with the requirements of one of the following: section 10.2.3.1,

section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1 * Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using method

B of the test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.

(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) For new installations, the total smoke released throughout the test shall not exceed 1000

m2.

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordance

with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E2404,

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall

be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do not

exceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-

height partitions.

(4) Previously approved existing installations of textile material meeting the requirements of

Class A when tested in accordance with ASTM E84 or ANSI/UL 723 shall be permitted to be

continued to be used.

10.2.4.5 Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,

expanded vinyl wall coverings shall be tested in the manner intended for use, using the

product mounting system, including adhesive, and shall comply with the requirements of one

of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

Page 62 of 171

Page 63: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting system,

including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,

expanded vinyl materials shall be tested in the manner intended for use, using the product

mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.8 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropylene and

high-density polyethylene materials shall not be permitted as interior wall or ceiling finish

unless the material complies with the requirements of 10.2.3.1. The tests shall be performed

on a finished assembly and on the maximum thickness intended for use.

10.2.4.9 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretch

systems containing all three components described in the definition in Chapter 3 shall be

tested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or

10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics.

10.2.4.10 Reflective Insulation Materials. Reflective insulation materials shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting

shall be in accordance with ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics.

Page 63 of 171

Page 64: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.11 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall panels

meeting the requirements of Class A in accordance with 10.2.3, shall be permitted to be

finished with one additional application of paint. Such painted panels shall be permitted for

use in areas where Class A interior finishes are required. The total paint thickness shall not

exceed 1⁄28 in. (0.9 mm).

10.2.4.12 Laminated products factory-produced with a wood substrate. Laminated products

factory-produced with a wood substrate shall be tested in the manner intended for use and

shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are tested in

accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with ASTM

E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, using the product-mounting system (including

adhesive) of actual use.

10.2.4.13 Facings or wood veneers intended to be applied on site over a wood substrate.

Facings or veneers intended to be applied on site over a wood substrate shall be tested in the

manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If

the materials are tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they shall

use the product-mounting system, including adhesive, described in Section 5.8.9 of NFPA

286. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics.

10.2.4.14 Light-Transmitting Plastics. Light-transmitting plastics shall be permitted to be

used as interior wall and ceiling finish if approved by the authority having jurisdiction.

10.2.4.15 Decorations and Furnishings. Decorations and furnishings that do not meet the

definition of interior finish, as defined in 3.3.92.2, shall be regulated by the provisions of

Section 10.3.

10.2.5 Trim and Incidental Finish.

10.2.5.1 General. Interior wall and ceiling trim and incidental finish, other than wall base in

accordance with 10.2.5.2 and bulletin boards, posters, and paper in accordance with 10.2.5.3,

not in excess of 10 percent of the specific wall and ceiling areas of any room or space to which

it is applied shall be permitted to be Class C materials in occupancies where interior wall

and ceiling finish of Class A or Class B is required.

10.2.5.2 Wall Base. Interior floor trim material used at the junction of the wall and the floor

to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height, shall

meet the requirements for interior wall finish for its location or the requirements for Class II

interior floor finish as described in 10.2.7.4 using the test described in 10.2.7.3. If a Class I

floor finish is required, the interior floor trim shall be Class I.

Page 64 of 171

Page 65: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.5.3 Bulletin Boards, Posters, and Paper.

10.2.5.3.1 Bulletin boards, posters, and paper attached directly to the wall shall not exceed

20 percent of the aggregate wall area to which they are applied.

10.2.5.3.2 The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in

sprinklered educational or day-care occupancies in accordance with 14.7.4.3(2), 15.7.4.3(2),

16.7.4.3(2), or 17.7.4.3(2).

10.2.6* Fire-Retardant Coatings.

10.2.6.1* The required flame spread index or smoke developed index of existing surfaces of

walls, partitions, columns, and ceilings shall be permitted to be secured by applying approved

fire-retardant coatings to surfaces having higher flame spread index values than permitted.

Such treatments shall be tested, or shall be listed and labeled for application to the material

to which they are applied, and shall comply with the requirements of NFPA 703, Standard

for Fire Retardant–Treated Wood and Fire-Retardant Coatings for Building Materials.

10.2.6.2* Surfaces of walls, partitions, columns, and ceilings shall be permitted to be finished

with factory-applied fire-retardant coated products that have been listed and labeled to

demonstrate compliance with the requirements of ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on the coated

surface. 10.2.6.3 Fire-retardant coatings or factory-applied fire retardant coated assemblies shall

possess the desired degree of permanency and shall be maintained so as to retain the

effectiveness of the treatment under the service conditions encountered in actual use.

10.2.7* Interior Floor Finish Testing and Classification.

10.2.7.1* Carpet and carpet like interior floor finishes shall comply with ASTM D2859,

Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. 10.2.7.2* Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for

fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2.

10.2.7.3* Interior floor finishes shall be classified in accordance with 10.2.7.4, based on test

results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source. 10.2.7.4 Interior floor finishes shall be grouped in the classes specified in 10.2.7.4.1 and

10.2.7.4.2 in accordance with the critical radiant flux requirements.

10.2.7.4.1 Class I Interior Floor Finish. Class I interior floor finish shall have a critical

radiant flux of not less than 0.45 W/cm2, as determined by the test described in 10.2.7.3.

10.2.7.4.2 Class II Interior Floor Finish. Class II interior floor finish shall have a critical

radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the test

described in 10.2.7.3.

Page 65 of 171

Page 66: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.7.5 Wherever the use of Class II interior floor finish is required, Class I interior floor

finish shall be permitted.

10.2.8 Automatic Sprinklers.

10.2.8.1 Other than as required in 10.2.4, where an approved automatic sprinkler system is

installed in accordance with Section 9.7, Class C interior wall and ceiling finish materials

shall be permitted in any location where Class B is required, and Class B interior wall and

ceiling finish materials shall be permitted in any location where Class A is required.

10.2.8.2 Where an approved automatic sprinkler system is installed in accordance with

Section 9.7, throughout the fire compartment or smoke compartment containing the interior

floor finish, Class II interior floor finish shall be permitted in any location where Class I

interior floor finish is required, and where Class II is required, the provisions of 10.2.7.2 shall

apply.

Page 66 of 171

Page 67: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 123-NFPA 101-2015 [ New Section after 10.2.4 ]

10.2.4.10 Laminated products factory-produced with a wood substrate . Laminatedproducts factory-produced with a wood substrate shall be tested in the manner intended foruse and shall comply with the requirements of 10.2.3. If the materials are tested in accordancewith ASTM E84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics ofBuilding Materials (see 10.2.3.4) , specimen preparation and mounting shall be inaccordance with ASTM E2579, Standard Practice for Specimen Preparation and Mounting ofWood Products to Assess Surface Burning Characteristics , using the product-mountingsystem (including adhesive) of actual use.

Statement of Problem and Substantiation for Public Input

ASTM has developed mounting methods for both "facings or wood veneer intended to be applied on site over a wood substrate" and laminated products that are factory produced and have a wood substrate. The concept is that facings that are produced as part of a commercial (factory-produced) panel are finished products and the manufacturer should be responsible to ensure that the product itself (the full panel) is safe and there is no need to discuss a substrate. It has been shown that, when veneers are applied over a wood substrate the resulting flame spread is much higher than when applied over gypsum board or over a noncombustible substrate. Therefore the requirement in ASTM E2579 is that the testing be done with the full product and, thus, there will no need to retest for different substrates. Similarly, NFPA 286 contains a section that addresses testing of wall covering materials, including facings applied on site and laminated products produced in the factory. Facings applied on site over wood substrates are tested using ASTM E2404.

Note that this public input is not intended to replace an existing section but to be incorporated after the last section in 10.3. Note also that the public input to add a clarification of the requirements for facings or wood veneers intended to be applied on site over a wood substrate is also intended to be incorporated as a new section between.

NFPA 286 language 5.8 Wall or Ceiling Covering Materials. 5.8.2 Where the wall or ceiling covering system is a factory produced wall panel, the adhesive shall be the same one used in the manufacture of the factory-produced wall or ceiling panel. ASTM E2579 - Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics 1. Scope 1.1 This practice describes procedures for specimen preparation and mounting when testing wood products to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to laminated products factory produced with a wood substrate (see 8.6). This practice does not apply to wood veneers or facings intended to be applied on site over a wood substrate, which are covered by Practice E2404. 1.3 Testing is conducted with Test Method E84.

ASTM E2404 – Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics 1. Scope 1.1 This practice describes procedures for specimen preparation and mounting when testing textile, paper or polymeric (including vinyl and expanded vinyl) wall or ceiling covering materials to assess flame spread

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 7/8/2015 4:15 PMPage 67 of 171

Page 68: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

and smoke development as surface burning characteristics using Test Method E84. 1.2 This practice applies also to facings or wood veneers intended to be applied on site over a wood substrate (see 8.7). This practice does not apply to laminated products factory produced with a wood substrate, which are covered by Practice E2579. 1.3 Testing is conducted with Test Method E84.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 124-NFPA 101-2015 [New Section after 10.2.4]

Public Input No. 180-NFPA 101-2015 [Section No. 10.2]

Public Input No. 188-NFPA 101-2015 [Section No. A.10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 05 18:40:13 EDT 2015

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 7/8/2015 4:15 PMPage 68 of 171

Page 69: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 124-NFPA 101-2015 [ New Section after 10.2.4 ]

10.2.4.11 Facings or wood veneers intended to be applied on site over a wood substrate.Facings or veneers intended to be applied on site over a wood substrate shall be tested inthe manner intended for use and shall comply with the requirements of 10.2.3. If thematerials are tested in accordance with NFPA 286, Standard Methods of Fire Tests forEvaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth (see10.2.3.2), they shall use the product-mounting system, including adhesive, described inSection 5.8.9 of NFPA 286. If the materials are tested in accordance with ASTM E84,Standard Test Method for Surface Burning Characteristics of Building Materials , orANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials (see 10.2.3.4), specimen preparation and mounting shall be in accordance withASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile,Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings andVeneers, to Assess Surface Burning Characteristics .

Statement of Problem and Substantiation for Public Input

ASTM has developed mounting methods for both "facings or wood veneer intended to be applied on site over a wood substrate" and laminated products that are factory-produced and have a wood substrate. The concept is that these facings (applied on site) are basically the same as wall coverings and the manufacturer should be responsible for the facing only and needs to ensure that the material is safe and should test over the appropriate substrate. It has been shown that, when veneers are applied over a wood substrate the resulting flame spread is much higher than when applied over gypsum board or over a non-combustible substrate. Therefore the requirement in ASTM E2404 is that the testing be done over a standard wood substrate and, thus, there will no need to retest for different types of wood.

Similarly, NFPA 286 contains a section that addresses testing of wall covering materials, including facings applied on site and laminated products produced in the factory. Panels including factory applied facings with wood substrates are tested using ASTM E2579. Note that this public input is not intended to replace an existing section but to be incorporated at the end of the 10.2.4 sections. Note also that the public input to add a clarification of the requirements for laminated products factory-produced with a wood substrate is also intended to be incorporated as a new section within 10.2.4.

NFPA 286 language5.9 Laminated Products with Wood Substrates.5.9.1 Laminated products shall be tested as they are intended to be installed.5.9.1.1 The test specimens shall consist of the finished product, namely the combination of the facing or veneer, the adhesives or fasteners used, and the specific wood substrate that will be used.5.9.2 If the laminated product consists of a facing or veneer intended to be applied on-site over a wood substrate, the facing or veneer shall be tested as described in 5.9.2.1 and 5.9.2.2.5.9.2.1* The test specimens shall comply with the following:(1) Specimens shall consist of the facing or veneer mounted on the "A" face of nominal 12 mm (15⁄32 in.) untreated plywood with a face veneer of Douglas fir.(2) The plywood shall comply with NIST Voluntary Product Standard PS 1, Structural Plywood.(3) The plywood shall carry one of the following grade stamps: (a) APA-The Engineered Wood Association (b) TECO, indicating that the plywood has been graded PS 1 A-B and is for exterior exposure (c) CSA Standard O121, Douglas Fir Plywood.5.9.2.2 The adhesive used to attach the facing or veneer to the wood substrate in 5.9.2.1 shall be that specified by the manufacturer of the facing or veneer and applied in accordance with manufacturer's application instructions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 3 7/8/2015 4:17 PMPage 69 of 171

Page 70: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Also, for information, from NFPA 286:5.8.9 Wall or Ceiling Coverings Intended to Be Applied over a Wood Substrate. If the wall or ceiling coverings are intended to be applied over a wood substrate, the specimens shall consist of the wall or ceiling covering mounted on untreated plywood, with a face veneer of Douglas fir. The plywood shall have the same thickness as the wood substrate used in actual installations, and shall comply with NIST Voluntary Product Standard PS 1-07, Structural Plywood. The plywood shall be marked with a grade stamp indicating that the plywood has been graded PS 1-07 A-B and is for exterior exposure. The grade stamp shall be issued by a quality control agency. Alternatively, the plywood shall be permitted to be stamped as conforming to CSA Standard O121, Douglas Fir Plywood.

ASTM E2404 – Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing textile, paper or polymeric (including vinyl and expanded vinyl) wall or ceiling covering materials to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to facings or wood veneers intended to be applied on site over a wood substrate (see 8.7). This practice does not apply to laminated products factory produced with a wood substrate, which are covered by Practice E2579.1.3 Testing is conducted with Test Method E84.

ASM E2579 - Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing wood products to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to laminated products factory produced with a wood substrate (see 8.6). This practice does not apply to wood veneers or facings intended to be applied on site over a wood substrate, which are covered by Practice E2404.1.3 Testing is conducted with Test Method E84.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 123-NFPA 101-2015 [New Section after 10.2.4]

Public Input No. 180-NFPA 101-2015 [Section No. 10.2]

Public Input No. 188-NFPA 101-2015 [Section No. A.10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 05 19:00:01 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 3 7/8/2015 4:17 PMPage 70 of 171

Page 71: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

3 of 3 7/8/2015 4:17 PMPage 71 of 171

Page 72: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 122-NFPA 101-2015 [ New Section after 10.2.5 ]

10.2.4.10 Laminated products factory-produced with a wood substrate . Laminatedproducts factory-produced with a wood substrate shall be tested in the manner intended foruse and shall comply with the requirements of 10.2.3. If the materials are tested in accordancewith ASTM E84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials , or ANSI/UL 723, Standard for Test for Surface Burning Characteristics ofBuilding Materials (see 10.2.3.3) , specimen preparation and mounting shall be in accordancewith ASTM E2579, Standard Practice for Specimen Preparation and Mounting of WoodProducts to Assess Surface Burning Characteristics , using the product-mounting system(including adhesive) of actual use.

Statement of Problem and Substantiation for Public Input

ASTM has developed mounting methods for both "facings or wood veneer intended to be applied on site over a wood substrate" and laminated products that are factory produced and have a wood substrate. The concept is that facings that are produced as part of a commercial (factory-produced) panel are finished products and the manufacturer should be responsible to ensure that the product itself (the full panel) is safe and there is no need to discuss a substrate. It has been shown that, when veneers are applied over a wood substrate the resulting flame spread is much higher than when applied over gypsum board or over a noncombustible substrate. Therefore the requirement in ASTM E2579 is that the testing be done with the full product and, thus, there will no need to retest for different substrates. Similarly, NFPA 286contains a section that addresses testing of wall covering materials, including facings applied on site and laminated products produced in the factory. Facings applied on site over wood substrates are tested using ASTM E2404.Note that this public input is not intended to replace an existing section but to be incorporated after the last section in 10.3. Note also that the public input to add a clarification of the requirements for facings or wood veneers intended to be applied on site over a wood substrate is also intended to be incorporated as a new section between.

NFPA 286 language5.8 Wall or Ceiling Covering Materials.5.8.2 Where the wall or ceiling covering system is a factory produced wall panel, the adhesive shall be the same one used in the manufacture of the factory-produced wall or ceiling panel.

ASTM E2579 - Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing wood products to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to laminated products factory produced with a wood substrate (see 8.6). This practice does not apply to wood veneers or facings intended to be applied on site over a wood substrate, which are covered by Practice E2404.1.3 Testing is conducted with Test Method E84.

ASTM E2404 – Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing textile, paper or polymeric (including vinyl and expanded vinyl) wall or ceiling covering materials

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 2 7/8/2015 4:19 PMPage 72 of 171

Page 73: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to facings or wood veneers intended to be applied on site over a wood substrate (see 8.7). This practice does not apply to laminated products factory producedwith a wood substrate, which are covered by Practice E2579.1.3 Testing is conducted with Test Method E84.

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 05 18:27:43 EDT 2015

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 2 7/8/2015 4:19 PMPage 73 of 171

Page 74: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 133-NFPA 101-2015 [ Section No. 10.3.4 ]

10.3.4* Where required by the applicable provisions of this Code , mattresses, unless themattress is located in a building protected throughout by an approved automatic sprinkler system,shall comply with 10.3.4.1 or with 10.3.4.2.

10.3.4.1 The mattress shall have limited rates of heat release when tested in accordance withASTM E 1590, Standard Test Method for Fire Testing of Mattresses , as follows:

(1) The peak rate of heat release for the mattress shall not exceed 100 kW.

(2) The total heat released by the mattress during the first 10 minutes of the test shall not exceed25 MJ.

10.3.4.2 The mattress shall have a mass loss of no more than 15 percent of the initial mass of themattress when tested in accordance with the fire test in Annex A3 of ASTM F1085, StandardSpecification for Mattress and Box Springs for Use in Berths in Marine Vessels.

Statement of Problem and Substantiation for Public Input

The test in Annex 3 of ASTM F1085 is a very simple test that predicts fairly will the results of ASTM F1590 and is, in fact, more severe than ASTM E1590 because mattresses that melt cannot run away from the flame.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 188-NFPA 101-2015 [Section No. A.10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 11 15:45:52 EDT 2015

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 7/8/2015 4:20 PMPage 74 of 171

Page 75: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 134-NFPA 101-2015 [ Section No. 10.3.4 ]

10.3.4 * Where required by the applicable provisions of this Code , mattresses shall comply with10.3.4.1 or with 10.3.4.2 , unless the mattress is located in a building protected throughout by anapproved automatic sprinkler system , .

10.3.4.1 The mattress shall have limited rates of heat release when tested in accordance withASTM E 1590 E1590 , Standard Test Method for Fire Testing of Mattresses , as follows:

(1) The peak rate of heat release for of the mattress shall not exceed 100 kW.

(2) The total heat released by the mattress during the first 10 minutes of the test shall not exceed25 MJ.

10.3.4.2 The mattress shall have a mass loss not exceeding 15 percent when tested in accordancewith the fire test in Appendix A3 of ASTM F1085, Standard Specification for Mattress and BoxSprings for Use in Berths in Marine Vessels.

Also, add into the section on referenced ASTM standards a reference to ASTM F1085, StandardSpecifcation for Mattress and Box Springs for Use in Berths in Marine Vessels (2014).

Statement of Problem and Substantiation for Public Input

This public input does not require a change in the testing but simply provides an alternative. As an option, the fire test in Annex A3 of ASTM F1085 is being recommended as an optional alternative to the test in ASTM E1590. The existing test in ASTM E1590 (and its pass/fail criteria) are not being modified.

The test method in Annex A3 of ASTM F1085 was developed originally for use in detention and correctional occupancies and it is a very severe test that is a reasonable (and less expensive) alternative to ASTM E1590.

This test is very simple and can be conducted at any facility and does not require the use of an instrumented fire test lab. The test can be described in a few words: it involves rolling up a mattress, placing it at an angle (for example by holding it with a brick), introducing newspaper into the volume surrounding the rolled up mattress and igniting the newspaper with a match.

One of the advantages of using the ASTM F1085 Annex A3 test is that if the mattress materials melt away from the flame with flaming drips they may “pass” the ASTM E1590 test but melting will not allow a mattress to pass this test. In this test the material that flames on the floor will keep burning the mattress itself.

The following table shows the results using the ASTM F1085 Annex A3 test for a number of mattresses in two studies (one in 1980 and one in 2003) and it also shows whether the mattresses meet the ASTM E1590 requirements in the IFC code. It is clear from the table that mattresses usually burn up almost completely or lose very little mass and that the ASTM F1085 test will not pass mattresses that fail the IFC code requirements.

Mattress ASTM F1085 Mass Loss % NFPA 101 Pass: Yes or No1 (2003) 1.22 Yes2 (2003) 9.47 Yes3 (2003) 3.30 Yes4 (2003) 100 No5 (2003) 100 No1 (1980) 100 No2 (1980) 100 No3 (1980) 98.5 No

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 4 7/8/2015 4:21 PMPage 75 of 171

Page 76: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

4 (1980) 91.1 No5 (1980) 91 No6 (1980) 83.1 No7 (1980) 44.7 No8 (1980) 3.0 Yes

As another example of the usefulness of this test, two mattresses, both of which pass the ASTM E1590 test requirements, were recently tested to the ASTM F1085 Annex A3 test. One of the mattresses gave a mass loss of 1% while the other one melted and burnt virtually completely.

Test/Results Polychloroprene Mattress FR Polyester MattressASTM F1085 Annex A3 1% weight loss (pass) >90% weight loss (fail)ASTM E1590 Pass (Peak HRR: 25 kW) Pass

The test method from Annex A3 of ASTM F1085 is also described (albeit without enough details to conduct the test in a standard fashion) in section 10.2 of ASTM F1870 (Standard Guide for Selection of Fire Test Methods for the Assessment of Upholstered Furnishings in Detention and Correctional Facilities) as a test method “Designed for Detention and Correction Facilities”. ASTM F1870 is already in the Annex of NFPA 101.

Relevant parts of the text of Annex A3 of ASTM F1085 follows:A3.1 BackgroundA3.1.1 This optional test method provides a means for evaluating mattresses, and mattress inserts, for the weight loss, and fire behavior they exhibit under specified exposure conditions.A3.1.2 Results of this test method are likely to be reasonably predictive of the results of the test method in Annex A1, in terms of being able to differentiate between mattresses (or mattress inserts) of various degrees of fire performance.A3.1.3 This test method is capable of subdividing mattresses (or mattress inserts) into several categories depending on their response to the ignition source applied: some mattresses (or mattress inserts) will burn up completely, while some others will lose small fractions of the initial weight, with a series of intermediate fire-test responses also likely.A3.2 Test SpecimenA3.2.1 Use as the test specimen an actual manufactured mattress, mattress insert, or prototype thereof, in the configuration of its intended use.A3.2.2 If an actual manufactured mattress, or mattress insert, is not supplied, the size of the default mattress to be tested has the following dimensions: 0.76 by 1.90 m by at least 76 mm thick (30.0 by 75 in. by at least 3 in. thick). Whenever possible an actual mattress shall be used.A3.2.3 The test specimen used shall be the size representative of the intended use of the product to be tested. Report the actual dimensions of the test specimen used.A3.2.4 The test specimen, shall, in all respects, reflect the construction of the actual mattress, or mattress insert, that it is intended to represent.A3.5 ProcedureA3.5.1 Conduct the tests in a room equipped with appropriate exhausts to ensure that the resulting smoke can be vented. The so-called “ASTM room” (2.4 by 3.7 by 2.4 m high; 8 by 12 by 8 ft high) described in Test Method E1590 is an example of a room deemed satisfactory for this test. Rooms of other dimensions are also suitable.A3.5.2 Weigh 8 double sheets of black print newspaper (not tabloid size) and record the weight, to an accuracy of no less than 1.0 g.A3.5.3 Weigh the conditioned mattress, or mattress insert, and record the weight, to an accuracy of no less than 50 g. This shall be considered the initial mattress or mattress insert weight. Test within 30 min of weighing the mattress.A3.5.4 Use a pipe approximately 0.6-1.0 m (24-39 in.) long and 230-250 mm (9-10 in.) in internal diameter for rolling the mattress, or mattress insert.A3.5.5 Roll the long dimension of the test specimen (mattress, mattress prototype, mattress insert or mattress cushioning material), completely around the pipe. Retain the test specimen in place by using steel poultry netting or a minimum of three steel wire ties. This configuration creates a “chimney effect.”

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 4 7/8/2015 4:21 PMPage 76 of 171

Page 77: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Remove the pipe after the roll containing the test specimen has been secured and has formed a test specimen roll.A3.5.5.1 If the mattress, or mattress insert, is asymmetrical, inasmuch as the top and bottom surfaces are different, tests shall be conducted on both sides. If results differ depending on the side exposed to the ignition source, the appropriate results are those from the test that is shown to be more severe.A3.5.6 Position the test specimen roll such that it is both: (1) secure from falling and (2) tilted to one side at an angle of 75-80 degrees to the floor. This is achievable: (a) by propping up the test specimen roll on one side, with two 70-80 mm (3 in.) steel angle irons or two bricks, with 70-100 mm separation between them, and securing the test specimen roll from tipping over during testing by attaching 3 wires to the steel netting,with the wires suspended from up high (for example from the ceiling) or (b) by leaning the mattress against a non combustible support at the required angle. The angled configuration is needed to allow air to enter at the bottom of the chimney formed by the test specimen roll.A3.5.7 Crumple up the sheets of newspaper, loosely, into individual balls approximately 150 mm (6 in.) in diameter and place them in the inside of the chimney.A3.5.8 Ignite the crumpled newspaper, from the top, with a single match, ensuring that the newspaper is well lit.Note: A rather intense fire lasting 90-100 s is likely to result.A3.5.9 Allow free burning of the test specimen roll until the first of the following conditions is reached: (a) All burning has ceased. (b) Flashover in the test room appears inevitable. In this case, extinguish the test specimen fire manually and report the result as a flashover. Weighing of the test specimen remains is not necessary in this case.A3.5.10 Conclude the test after visible flames have ceased, unless the mattress, or mattress insert, is still smoldering. At the test conclusion, let the mattress, or mattress insert, cool to room temperature and check to ensure that there is no visible smoke and that the mattress, or mattress insert, is not smoldering.A3.5.11 If the mattress, or mattress insert, is smoldering when visible flames have ceased, do not conclude the test but continue the test until 60 minutes have elapsed and then terminate the test. Report the time at which visible flames have ceased and the time at which smoldering has ceased, unless smoldering has continued until the test has been externally terminated. Report the method of test termination and check to ensure that there is no more smoldering, no visible smoke and that the mattress is dry (if water was used).A3.5.12 Any molten mattress material or molten material that has solidified after cooling shall be excluded from the final test specimen weight. If molten material is all that remains of the test specimen the weight loss shall be reported as 100%.A3.5.13 Upon completion of the test, the mattress, or mattress insert, remains, if any, shall be weighed, after placing them in a pre-weighed non combustible container. The mattress, or mattress insert, remains shall include any portion of the test specimen that has fallen off, during or after the test.A3.5.14 Clean the test room so that no charred residues remain. Then, safely discard all mattress residues, preferably in sealed containers.A3.5.15 Conduct the test in duplicate. Conduct each burn on an untested specimen.

Clarification:TerraView appears to show that the entire text is new. In fact, however, NFPA 101 (2015) reads as follows:10.3.4* Where required by the applicable provisions of this Code, mattresses, unless the mattress is located in a building protected throughout by an approved automatic sprinkler system, shall have limited rates of heat release when tested in accordance with ASTM E 1590, Standard Test Method for Fire Testing of Mattresses, as follows:(1) The peak rate of heat release for the mattress shall not exceed 100 kW.(2) The total heat released by the mattress during the first 10 minutes of the test shall not exceed 25 MJ.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 188-NFPA 101-2015 [Section No. A.10.2]

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

3 of 4 7/8/2015 4:21 PMPage 77 of 171

Page 78: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 11 16:02:50 EDT 2015

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

4 of 4 7/8/2015 4:21 PMPage 78 of 171

Page 79: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 187-NFPA 101-2015 [ New Section after A.3.3.92.3 ]

A.3.3.92.4 Such partitions are intended to include washroom water closet partitions.

Statement of Problem and Substantiation for Public Input

This belongs here and not in A.10.2.1.5

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 186-NFPA 101-2015 [Section No. A.10.2.1.5]

Public Input No. 185-NFPA 101-2015 [Section No. 3.3.92.4]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 24 19:19:28 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

519 of 618 7/7/2015 8:49 AMPage 79 of 171

Page 80: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 188-NFPA 101-2015 [ Section No. A.10.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 5 7/9/2015 8:47 AMPage 80 of 171

Page 81: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

A.10.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

2 of 5 7/9/2015 8:47 AMPage 81 of 171

Page 82: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

The requirements pertaining to interior finish are intended to restrict the spread of fire over thecontinuous surface forming the interior portions of a building.

Table A.10.2 shows the fire test methods and classification criteria that apply to different interiorfinish materials.

Table A.10.2 Fire Testing of Interior Finish Materials

Material Test Method Acceptance Criterion Application Requirement Section Interior wall and ceilingfinish materials, except as shown in this table ASTM E 84 or ANSI/UL 723 Class A, in accordancewith 10.2.3.4(1) As required by relevant sections 10.2.3 ASTM E 84 or ANSI/UL 723 Class B, inaccordance with 10.2.3.4(2) As required by relevant sections 10.2.3 ASTM E 84 or ANSI/UL723 Class C, in accordance with 10.2.3.4(3) As required by relevant sections 10.2.3 NFPA 286 Inaccordance with 10.2.3.7.2 Permitted where Class A, B, or C is required by relevant

sections 10.2.3.2 Materials having thickness < 1 ⁄ 28 in. (<0.90 mm) applied directly to anoncombustible or limited-combustible surface of walls or ceilings No testingrequired 10.2.1.2 Exposed portions of structural members complying with requirements forbuildings of Type IV (2HH) construction in accordance with NFPA 220 No testingrequired 10.2.3.1 Cellular or foamed plastics (exposed foamed plastics and foamed plastics usedin conjunction with textile or vinyl facing or cover) NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A, B, or C is required by relevantsections 10.2.4.3.1.1(1) ANSI/UL 1715 Pass Permitted where Class A, B, or C is required byrelevant sections 10.2.4.3.1.1(2) ANSI/UL 1040 Pass Permitted where Class A, B, or C is requiredby relevant sections 10.2.4.3.1.1(3) FM 4880 Pass Permitted where Class A, B, or C is required byrelevant sections 10.2.4.3.1.1(4) Suitable large-scale fire test that substantiates combustibilitycharacteristics for use intended under actual fire conditions Pass Permitted where Class A, B, or Cis required by relevant sections 10.2.4.3.1 Textile wall coverings NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A, B, or C is required by relevant sections 10.2.4.1(6) NFPA 265,Method B In accordance with 10.2.3.7.1 Permitted on walls and partitions 10.2.4.1(5) ASTM E 84or ANSI/UL 723 Class A, in accordance with 10.2.3.4(1) Permitted on walls, but also requiressprinklers per Section 9.7 10.2.4.1(1) ASTM E 84 or ANSI/UL 723 Class A, in accordance with10.2.3.4(1) Permitted on partitions not exceeding three-quarters of the floor-to-ceiling height or notexceeding 8 ft (2440 mm) in height, whichever is less 10.2.4.1(2) ASTM E 84 or ANSI/UL723 Class A, in accordance with 10.2.3.4(1) Permitted to extend not more than 48 in. (1220 mm)above finished floor on ceiling-height walls and ceiling-height partitions 10.2.4.1(3) ASTM E 84 orANSI/UL 723 Class A, in accordance with 10.2.3.4(1) Previously approved existing installations oftextile material meeting the requirements of Class A permitted to be continued to beused 10.2.4.1(4) Expanded vinyl wall coverings NFPA 286 In accordance with 10.2.3.7.2 Permittedwhere Class A, B, or C is required by relevant sections 10.2.4.2(6) NFPA 265, Method B Inaccordance with 10.2.3.7.1 Permitted on walls and partitions 10.2.4.2(5) ASTM E 84 or ANSI/UL723 Class A, in accordance with 10.2.3.4(1) Permitted on walls, but also requires sprinklers perSection 9.7 10.2.4.2(1) ASTM E 84 or ANSI/UL 723 Class A, in accordance with10.2.3.4(1) Permitted on partitions not exceeding three-quarters of the floor-to-ceiling height or notexceeding 8 ft (2440 mm) in height, whichever is less 10.2.4.2(2) ASTM E 84 or ANSI/UL723 Class A, in accordance with 10.2.3.4 (1) Permitted to extend not more than 48 in. (1220 mm)above finished floor on ceiling-height walls and ceiling-height partitions 10.2.4.2(3) ASTM E 84 orANSI/UL 723 Class A, B, or C, in accordance with 10.2.3.4 Existing installations of materials withappropriate wall finish classification for occupancy involved, and with classification in accordancewith the provisions of 10.2.3.4 10.2.4.2(4) Textile ceiling coverings NFPA 286 In accordance with10.2.3.7.2 Permitted where Class A, B, or C is required by relevant sections 10.2.4.1(6) ASTM E84 or ANSI/UL 723 Class A, in accordance with 10.2.3.4(1) Permitted on walls, but also requiressprinklers per Section 9.7 10.2.4.1(1) ASTM E 84 or ANSI/UL 723 Class A, in accordance with10.2.3.4(1) Previously approved existing installations of textile material meeting the requirements ofClass A permitted to be continued to be used 10.2.4.1(4) Expanded vinyl ceiling coverings NFPA286 In accordance with 10.2.3.7.2 Permitted where Class A, B, or C is required by relevantsections 10.2.4.2(6) ASTM E 84 or ANSI/UL 723 Class A, in accordance with 10.2.3.4(1) Permittedon walls, but also requires sprinklers per Section 9.7 10.2.4.2(1) ASTM E 84 or ANSI/UL

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

3 of 5 7/9/2015 8:47 AMPage 82 of 171

Page 83: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

723 Class A, B, or C, in accordance with 10.2.3.4 Existing installations of materials with appropriatewall finish classification for occupancy involved, and with classification in accordance with theprovisions of 10.2.3.4 10.2.4.2(4) Interior trim, other than foamed plastic and other than wallbase ASTM E 84 or ANSI/UL 723 Class C, in accordance with 10.2.3.4 Interior wall and ceiling trimand incidental finish, other than wall base not in excess of 10 percent of the specific wall and ceilingareas of any room or space to which it is applied where interior wall and ceiling finish of Class A orClass B is required 10.2.5.1 NFPA 286 In accordance with 10.2.3.7.2 Permitted where Class A, B,or C is required by relevant sections 10.2.3.2 Foamed plastic used as interior trim ASTM E 84 or

ANSI/UL 723 Flame spread index = 75 (1) Minimum density of interior trim required to be 20 lb/ft 3

(320 kg/m 3 ) 10.2.4.3.2 (2) Maximum thickness of interior trim required to be 1 ⁄ 2 in. (13mm), and maximum width required to be 4 in. (100 mm) 10.2.4.3.2 (3) Interior trim not permittedto constitute more than 10 percent of the specific wall or ceiling area of a room or space to which itis applied 10.2.4.3.2 NFPA 286 In accordance with 10.2.3.7.2 Permitted where Class A, B, or C isrequired by relevant sections 10.2.3.2 Fire-retardant coatings NFPA 703 Class A, B, or C, whentested by ASTM E 84 or ANSI/UL 723, in accordance with 10.2.3.4 Required flame spread index orsmoke developed index values of existing surfaces of walls, partitions, columns, and ceilingspermitted to be secured by applying approved fire-retardant coatings to surfaces having higherflame spread index values than permitted; such treatments required to be tested or listed andlabeled for application to material to which they are applied 10.2.6.1 Factory-applied fire-retardant–coated assemblies (listed and labeled) ASTM E 2768 on the coated surface Pass Surfaces of walls.partitions, columns, and ceilings in new construction 10.2.6.2 Carpet and carpetlike interior floorfinishes ASTM D 2859 Pass All areas 10.2.7.1 Floor coverings, other than carpet, judged torepresent an unusual hazard (excluding traditional finish floors and floor coverings, such as wood

flooring and resilient floor coverings) NFPA 253 Critical radiant flux = 0.1 W/cm 2 Allareas 10.2.7.2 Interior floor finish, other than carpet and carpetlike materials NFPA 253 Class I:

Critical radiant flux = 0.45 W/cm 2 , in accordance with 10.2.7.4 As required by relevant

sections 10.2.7.3 NFPA 253 Class II: Critical radiant flux = 0.22 W/cm 2 , in accordance with10.2.7.4 As required by relevant sections 10.2.7.3 Wall base [interior floor trim material used atjunction of wall and floor to provide a functional or decorative border, and not exceeding 6 in. (150

mm) in height] NFPA 253 Class II: Critical radiant flux = 0.22 W/cm 2 , in accordance with

10.2.7.4 All areas 10.2.5.2 NFPA 253 Class I: Critical radiant flux = 0.45 W/cm 2 , in accordancewith 10.2.7.4 If interior floor finish is required to meet Class I critical radiant flux 10.2.5.2 Floor finishof traditional type, such as wood flooring and resilient floor coverings No testing required 10.2.2.2

The default requirements are based on fire testing to NFPA 286 (with the criteria of 10.2.3.2),which apply to all interior finish materials. Many interior finish materials are permitted to be testedbased on other fire tests (namely, based either on ASTM E84 or UL 723 or on NFPA 265), asshown in the relevant sections.

Table A.10.2 shows the fire test methods and classification criteria that apply to different interiorwall and ceiling finish materials.

Table A.10.2 Fire Testing of Interior Wall and Ceiling Finish Materials

(replace the table by the attached table)

Additional Proposed Changes

File Name Description Approved

101_A10.2_including_table_proposed_for_2018.docxRevised A.10.2, including revised table.

Statement of Problem and Substantiation for Public Input

The table is not longer correct and the revised table is based on the revisions proposed for section 10.2.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

4 of 5 7/9/2015 8:47 AMPage 83 of 171

Page 84: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

The sections on interior floor finish are proposed to be deleted as unnecessary. No requirements are being changed, other than adding the new requirements proposed for "Laminated products factory-produced with a wood substrate" and for "Facings or wood veneers intended to be applied on site over a wood substrate".

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 123-NFPA 101-2015 [New Section after 10.2.4]

Public Input No. 124-NFPA 101-2015 [New Section after 10.2.4]

Public Input No. 133-NFPA 101-2015 [Section No. 10.3.4]

Public Input No. 134-NFPA 101-2015 [Section No. 10.3.4]

Public Input No. 180-NFPA 101-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 24 19:46:07 EDT 2015

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

5 of 5 7/9/2015 8:47 AMPage 84 of 171

Page 85: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

A.10.2 The requirements pertaining to interior finish are intended to restrict the spread of fire over the continuous surface forming the interior portions of a building. The default requirements are based on fire testing to NFPA 286 (with the criteria of 10.2.3.2), which apply to all interior finish materials. Many interior finish materials are permitted to be tested based on other fire tests (namely, based either on ASTM E84 or UL 723 or on NFPA 265), as shown in the relevant sections. Table A.10.2 shows the fire test methods and classification criteria that apply to different interior wall and ceiling finish materials.

Table A.10.2 Fire Testing of Interior Wall and Ceiling Finish Materials

Material Test

Method Acceptance Criterion Application Requirement Paragraph

Base Requirement

All interior wall and ceiling finish materials

NFPA 286

In accordance with 10.2.3.2

Permitted anywhere, including where Class A, Class B or Class C in accordance with ASTM E84 or UL 723 is required by relevant sections

10.2.3.1

Alternate requirements for some interior wall and ceiling finish materials

Materials having a thickness less than 1⁄28 in. (0.9 mm) applied directly to a noncombustible or limited combustible surface of walls or ceilings

No testing required

10.2.4.1

Exposed portions of structural members complying with the requirements for buildings of Type IV (2HH) construction, in accordance with NFPA 220 or with the building code

No testing required

10.2.4.2

Cellular or foamed plastics (exposed foamed plastics and foamed plastics used in conjunction with a textile or vinyl facing or cover)

NFPA 286

In accordance with 10.2.3.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1

FM 4880 Pass Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1

Page 85 of 171

Page 86: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Material Test

Method Acceptance Criterion Application Requirement Paragraph

UL 1040 Pass Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1

UL 1715

Pass (plus smoke

measurements,

with total smoke

release not to

exceed 1000 m2)

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1

Textile wall coverings ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on walls, but also requires sprinklers. As required by relevant sections. Tested using specimen preparation and mounting per ASTM E2404

10.2.4.4

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less. Tested using specimen preparation and mounting per ASTM E2404

10.2.4.4

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted to extend not more than 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions. Tested using specimen preparation and mounting per ASTM E2404

10.2.4.4

NFPA 265 Method B

In accordance with 10.2.4.4.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.4.2

Expanded vinyl wall coverings

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on walls, but also requires sprinklers. As required by relevant sections Tested using specimen preparation and mounting per ASTM E2404

10.2.4.5

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less Tested using specimen preparation and mounting per ASTM E2404

10.2.4.5

Page 86 of 171

Page 87: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Material Test

Method Acceptance Criterion Application Requirement Paragraph

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted to extend not more than 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions Tested using specimen preparation and mounting per ASTM E2404

10.2.4.5

NFPA 265 Method B

In accordance with 10.2.4.4.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.5

Textile ceiling coverings ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on ceilings, but also requires sprinklers. Tested using specimen preparation and mounting per ASTM E2404

10.2.4.6

Expanded vinyl ceiling coverings

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on ceilings, but also requires sprinklers. Tested using specimen preparation and mounting per ASTM E2404

10.4.2.7

Interior trim, other than foamed plastic and other than wall base

ASTM E84 or UL 723

Class C, in accordance with 10.3.2.3

Interior wall and ceiling trim and incidental finish, other than wall base not in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it is applied in occupancies where interior wall and ceiling finish of Class A or Class B is required

10.2.5.1

Foamed plastic used as interior trim

ASTM E84 or UL 723

Flame spread index not exceeding75

(1) Minimum density of interior trim required to be 20 lb/ft3 (320 kg/m3)

10.2.4.3.2

(2) Maximum thickness of interior trim required to be 0.5 in. (13 mm), and maximum width permitted to be 8 in. (205 mm)

10.2.4.3.2

(3) Interior trim not permitted to constitute more than 10 percent of specific wall or ceiling area of a room or space to which it is applied.

10.2.4.3.2

Wall base Tested as interior

Shall not exceed 6 in. (150 mm) in height

10.2.5.2

Page 87 of 171

Page 88: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Material Test

Method Acceptance Criterion Application Requirement Paragraph

floor finish

Lockers

Tested as interior finish

10.2.4.8

Wood lockers ASTM E84 or UL 723

Class C, in accordance with 10.3.2.3

No testing required 10.2.4.8.2

Polypropylene and High density polyethylene

NFPA 286

In accordance with 10.2.3.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.9

Site-Fabricated Stretch Systems

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2573

10.2.4.10

Reflective Insulation Materials

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2599

10.2.4.11

Metal Ceiling and Wall Panels

10.2.4.12

Laminated products factory-produced with a wood substrate

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2579

10.2.4.13

Facings or wood veneers intended to be applied on site over a wood substrate

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2404

10.2.4.14

Light transmitting plastics 10.2.4.15

Fire retardant coatings Pass NFPA 703 10.2.6

Factory-applied fire retardant coated products listed and labeled for the application

ASTM E2768

Pass 10.2.6.3

Trim and incidental finish (not foamed plastic)

ASTM E84 or UL 723

Class C, in accordance with 10.3.2.3x

Interior trim not permitted to constitute more than 10 percent of specific wall or ceiling area of a room or space to which it is applied.

10.2.5.1

Bulletin boards, posters and paper

No testing required

Bulletin boards, posters, and paper attached directly to the wall shall not exceed 20 percent of the aggregate wall area to which they are applied.

10.2.5.3.1

No testing required The provision of 10.2.5.3.1 shall not apply to artwork and

10.2.5.3.2

Page 88 of 171

Page 89: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Material Test

Method Acceptance Criterion Application Requirement Paragraph

teaching materials in sprinklered educational or day-care occupancies in accordance with 14.7.4.3(2), 15.7.4.3(2), 16.7.4.3(2), or 17.7.4.3(2).

Page 89 of 171

Page 90: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 186-NFPA 101-2015 [ Section No. A.10.2.1.5 ]

A.10.2.1.5

Such partitions are intended to include washroom water closet partitions.

Statement of Problem and Substantiation for Public Input

This annex note does not belong here, probably due to revisions in the code) but it belongs with the definition of interior wall finish.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 185-NFPA 101-2015 [Section No. 3.3.92.4]

Public Input No. 187-NFPA 101-2015 [New Section after A.3.3.92.3]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 24 19:16:45 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

536 of 618 7/7/2015 8:49 AMPage 90 of 171

Page 91: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 184-NFPA 101-2015 [ Section No. A.10.2.3.7 ]

A.10.2.3.7

The methodology specified in NFPA 265, Standard Methods of Fire Tests for Evaluating RoomFire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels andWalls, includes provisions for measuring smoke obscuration. Such measurement is considereddesirable, but the basis for specific recommended values is not currently available. (SeeA.10.2.4.1.)

Statement of Problem and Substantiation for Public Input

The sentence proposed for deletion is obsolete as it refers to older editions of NFPA 265 and of the code.

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 24 14:20:51 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

537 of 618 7/7/2015 8:49 AMPage 91 of 171

Page 92: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 64-NFPA 5000-2015 [ Section No. 3.3.220.4 ]

3.3.220.4 * Interior Wall Finish.

The interior finish of columns, fixed or movable walls, and fixed or movable partitions.(BLD-INT)

(an annex section A.3.3.22.4 is proposed, to read as follows: Such partitions areintended to include washroom water closet partitions)

Statement of Problem and Substantiation for Public Input

The annex note to A.10.1.3 belongs to A.3.3.220.4.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 65-NFPA 5000-2015 [New Section after A.3.3.220.3]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 22 21:28:26 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 479 7/7/2015 12:51 PMPage 92 of 171

Page 93: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 53-NFPA 5000-2015 [ Section No. 10.2 ]

10.2 *

Interior Finish

.

10.2.1

General

.

10.2.1.1

Classification of interior finish materials shall be in accordance with tests made underconditions simulating actual installations, provided that the authority having jurisdiction ispermitted to establish the classification of any material for which a classification by astandard test is not available

, unless otherwise provided in 10.2.1.2 .

10.2.1.2

The provisions of 10.2.1.1 shall not.

10.2.1.2 Fixed or movable walls and partitions, paneling, wall pads, and crash padsapplied structurally or for decoration, acoustical correction, surface insulation, or otherpurposes shall be considered interior finish and shall not be considered decorations orfurnishings.

10.2.1.3 Lockers constructed of combustible materials shall be considered interior finish.

10.2.2* Use of Interior Finishes.

10.2.2.1 Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter 11and Chapters 15 through 31 and 33 through 34

(2) As specified in section 10.2.3 through 10.2.5.

10.2.2.2 * Interior floor finish shall comply with 10.2.6 under any of the followingconditions:

(1) Where floor finish requirements are specified elsewhere in this Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent

to floor finishes with a critical radiant flux of at least 0.1 W/cm 2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

154 of 479 7/7/2015 12:51 PMPage 93 of 171

Page 94: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.3 Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified forfire performance and smoke development it shall be classified in accordance with 10.2.3.1 or10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1* Interior wall and ceiling finish materials tested in accordance with NFPA286. Interior wall and ceiling finish materials shall be classified in accordance with NFPA286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and CeilingInterior Finish to Room Fire Growth , and comply with Section 10.2.3.2. Materials testedin accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be consideredalso to comply with the requirements of a Class A, Class B or Class C in accordance withSection 10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with thefollowing:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. The total smoke released throughout the test shall not exceed 10,764 ft 2 ( 1,000 m 2 ).

10.2.3.3* Interior wall and ceiling finish materials tested in accordance with ASTM E84or ANSI/UL 723. Interior wall and ceiling finish materials shall be classified inaccordance with ASTM E 84 , Standard Test Method for Surface Burning Characteristicsof Building Materials , or ANSI/UL 723 , Standard for Test for Surface BurningCharacteristics of Building Materials , except as indicated in Sections 10.2.3.4 and10.2.3.5 . Such interior finish materials shall be grouped in the following classes inaccordance with their flame spread and smoke-developed indexes .

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 The classification of interior finish specified in 10.2.3.3 shall be that of thebasic material used by itself or in combination with other materials.

10.2.3.3.2 Wherever the use of Class C interior wall and ceiling finish is required, ClassA or Class B shall be permitted. Where Class B interior wall and ceiling finish is required,Class A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not berequired to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

155 of 479 7/7/2015 12:51 PMPage 94 of 171

Page 95: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

corresponding sections.

10.2.3.6 * Fire-retardant coatings shall not be used to obtain compliance with the interiorfinish requirements of this Code .

10.2.3.7 * Surfaces of walls, partitions, columns, and ceilings shall be permitted to befinished with factory-applied fire retardant-coated products that have been listed andlabeled to demonstrate compliance with the requirements of ASTM E2768, Standard TestMethod for Extended Duration Surface Burning Characteristics of Building Materials , onthe coated surface.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

156 of 479 7/7/2015 12:51 PMPage 95 of 171

Page 96: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4* Interior wall and ceiling finish materials with special requirements. Thematerials indicated in Sections 10.2.4.1 through 10.2.4.15 shall be tested as indicated in thecorresponding sections.

10.2.4.1 Thickness exemption.

10.2.4.1.1 The provisions of 10.2.3 shall not apply to materials having a total thicknessof less than

1 ⁄ 281⁄28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings where both ofthe following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited

-combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finishwhen tested in accordance with 10.

42 .

13, using fiber cement board as the substrate material.

10.2. 4. 1.

3 2 If a material having a total thickness of less than

1 ⁄ 281⁄28 in. (0.9 mm) is applied to a surface that is not noncombustible or not limited -combustible, the provisions of 10.2. 3 shall apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structuralmembers complying with the requirements for Type IV (2HH) construction in accordancewith 7.2.5 of this code shall be exempt from testing and classification in accordance with10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not beused as interior wall and ceiling finish unless specifically permitted by 10.2.4.3. 1

.1shall apply.or 10.2.4.3.2. The requirements of 10.2.4.3 shall apply both to exposed foamed plastics andto foamed plastics used in conjunction with a textile or vinyl facing or cover.

10.2. 4.3. 1 Cellular or foamed plastic materials meeting the definition of foamed plasticinsulation shall be permitted where subjected to large-scale fire tests that substantiatetheir combustibility and smoke release characteristics of the material for the use intendedunder actual fire conditions .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

157 of 479 7/7/2015 12:51 PMPage 96 of 171

Page 97: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

4

Fixed or movable walls and partitions, paneling, and wall pads and crash pads, appliedstructurally or for decoration, acoustical correction, surface insulation, or other purposes, shallbe considered interior finish and shall not be considered decorations or furnishings.

10.2.1.5

Lockers constructed of combustible materials shall be considered interior finish.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibilityof cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall andCeiling Interior Finish to Room Fire Growth , with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material [ (including smoke

measurements, with total smoke release not to exceed 10,764 ft 2 (1000 m 2 )]

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction

(4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Walland Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior BuildingPanels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2 The tests shall be performed on a finished foamed plastic assembly related tothe actual end-use configuration, including any cover or facing, and at the maximumthickness intended for use.

10.2.4.3.1.3 * Cellular or foamed plastic materials tested in accordance with ANSI/UL1040, Standard for Fire Test of Insulated Wall Construction , or FM 4880, ApprovalStandard for Class I Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, InteriorFinish Materials or Coating, and Exterior Wall Systems , shall also be tested for smokerelease using NFPA 286, with the acceptance criterion of 10.2.3.2.

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10percent of the specific wall or ceiling area to which it is applied, provided that it is not less

than 20 lb/ft 3 (320 kg/m 3 ) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in.(100 mm) in width, and complies with the requirements for Class A or Class B interior walland ceiling finish as described in 10.2.3.3; however, the smoke developed index shall not belimited.

10.2.4.4* Textile wall coverings. Where used as interior wall finish materials, textilematerials shall be tested in the manner intended for use, using the product mountingsystem, including adhesive, and shall comply with the requirements of one of the following:section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1 * Products tested in accordance with NFPA 265, Standard Methods of FireTests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl WallCoverings on Full Height Panels and Walls , shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

158 of 479 7/7/2015 12:51 PMPage 97 of 171

Page 98: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

method B of the test protocol of NFPA 265, Standard Methods of Fire Tests for EvaluatingRoom Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full HeightPanels and Walls :

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) The total smoke released throughout the test shall not exceed 10,764 ft 2 (1000 m 2 ).

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested inaccordance with ASTM E84, Standard Test Method for Surface Burning Characteristics ofBuilding Materials , or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials , using the specimen preparation and mountingmethod of ASTM E2404, Standard Practice for Specimen Preparation and Mounting ofTextile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings andWood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess SurfaceBurning Characteristics, shall be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do notexceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls andceiling-height partitions.

10.2.4.5 Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,expanded vinyl wall coverings shall be tested in the manner intended for use, using theproduct mounting system, including adhesive, and shall comply with the requirements ofone of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textilematerials shall be tested in the manner intended for use, using the product mountingsystem, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84,Standard Test Method for Surface Burning Characteristics of Building Materials , orANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials , using the specimen preparation and mounting method of ASTM E2404,Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric(Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to AssessSurface Burning Characteristics , and shall be permitted on the ceilings of rooms orareas protected by an approved automatic sprinkler system .

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finishmaterials, expanded vinyl materials shall be tested in the manner intended for use, usingthe product mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

159 of 479 7/7/2015 12:51 PMPage 98 of 171

Page 99: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Standard Test Method for Surface Burning Characteristics of Building Materials , orANSI/UL 723, Standard for Test for Surface Burning Characteristics of BuildingMaterials , using the specimen preparation and mounting method of ASTM E2404,Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric(Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to AssessSurface Burning Characteristics , and shall be permitted on the ceilings of rooms orareas protected by an approved automatic sprinkler system .

10.2.4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materialsother than wood are used, the lockers shall be considered interior finish and shall complywith Section 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustiblematerials shall be permitted to be used in any location where interior finish materials arerequired to meet a Class C classification in accordance with 10.2.3.

10.2.4.9 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropyleneand high-density polyethylene materials shall not be permitted as interior wall or ceilingfinish unless the material complies with the requirements of 10.2.3.1. The tests shall beperformed on a finished assembly and on the maximum thickness intended for use.

10.2.4.10 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretchsystems containing all three components described in the definition in Chapter 3 shall betested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Methodfor Surface Burning Characteristics of Building Materials , or ANSI/UL 723, Standardfor Test for Surface Burning Characteristics of Building Materials , specimen preparationand mounting shall be in accordance with ASTM E2573, Standard Practice for SpecimenPreparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface BurningCharacteristics .

10.2.4.11 Reflective Insulation Materials. Reflective insulation materials shall be testedin the manner intended for use and shall comply with the requirements of 10.2.3.1 or10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Methodfor Surface Burning Characteristics of Building Materials , or ANSI/UL 723, Standardfor Test for Surface Burning Characteristics of Building Materials , specimen preparationand mounting shall be in accordance with ASTM E2599, Standard Practice for SpecimenPreparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl StretchCeiling Materials for Building Applications to Assess Surface Burning Characteristics .

10.2.4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wallpanels meeting the requirements of Class A in accordance with 10.2.3, shall be permitted tobe finished with one additional application of paint. Such painted panels shall be permittedfor use in areas where Class A interior finishes are required. The total paint thickness shallnot exceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate . Laminated

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

160 of 479 7/7/2015 12:51 PMPage 99 of 171

Page 100: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 54-NFPA 5000-2015 [ Section No. 10.3 ]

10.3 Use of Interior Finishes.

10.3.1

Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter11 and Chapters 15 through 31 and 33 through 34

(2) As specified in Section 10.5

10.3.2 * Use of Interior Finishes.

10.3.2.1

Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter11 and Chapters 15 through 31 and 33 through 34

(2) As specified in Section 10.4 through 10.6

10.3.2.2 *

Interior floor finish shall comply with Section 10.7 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in this Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent

to floor finishes with a critical radiant flux of at least 0.1 W/cm 2

Additional Proposed Changes

File Name Description Approved

NFPA_5000_sections_10.2_complete_proposed_for_2018_clean.docxComplete new proposed section 10.2

Statement of Problem and Substantiation for Public Input

This section, as well as sections 10.4 through 10.8 are proposed to be eliminated and incorporated into section 10.2, for parallelism with NFPA 101 (no change in requirements).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

165 of 479 7/7/2015 12:51 PMPage 100 of 171

Page 101: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jun 21 19:35:33 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

166 of 479 7/7/2015 12:51 PMPage 101 of 171

Page 102: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 5000 – Sections on Interior Finish - 10.2-10.8 (2018)

10.2* Interior Finish

10.2.1 General

10.2.1.1 Classification of interior finish materials shall be in accordance with tests made

under conditions simulating actual installations, provided that the authority having

jurisdiction is permitted to establish the classification of any material for which a

classification by a standard test is not available.

10.2.1.2 Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied

structurally or for decoration, acoustical correction, surface insulation, or other purposes

shall be considered interior finish and shall not be considered decorations or furnishings.

10.2.1.3 Lockers constructed of combustible materials shall be considered interior finish.

10.2.2* Use of Interior Finishes.

10.2.2.1 Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter 11

and Chapters 15 through 31 and 33 through 34 (2) As specified in section 10.2.3 through 10.2.5.

10.2.2.2* Interior floor finish shall comply with 10.2.6 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in this Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent

to floor finishes with a critical radiant flux of at least 0.1 W/cm2

10.2.3 Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified for

fire performance and smoke development it shall be classified in accordance with 10.2.3.1 or

10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1* Interior wall and ceiling finish materials tested in accordance with NFPA 286.

Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286,

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and comply with Section 10.2.3.2. Materials tested in

accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be considered

also to comply with the requirements of a Class A, Class B or Class C in accordance with

Section 10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with the

following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. The total smoke released throughout the test shall not exceed 10,764 ft2 (1,000 m2).

10.2.3.3* Interior wall and ceiling finish materials tested in accordance with ASTM E84 or

ANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance

Page 102 of 171

Page 103: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, except as indicated in Sections 10.2.3.4 and 10.2.3.5. Such interior

finish materials shall be grouped in the following classes in accordance with their flame

spread and smoke-developed indexes.

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 The classification of interior finish specified in 10.2.3.3 shall be that of the basic

material used by itself or in combination with other materials.

10.2.3.3.2 Wherever the use of Class C interior wall and ceiling finish is required, Class A

or Class B shall be permitted. Where Class B interior wall and ceiling finish is required,

Class A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not be

required to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

corresponding sections.

10.2.3.6* Fire-retardant coatings shall not be used to obtain compliance with the interior

finish requirements of this Code.

10.2.3.7* Surfaces of walls, partitions, columns, and ceilings shall be permitted to be

finished with factory-applied fire retardant-coated products that have been listed and

labeled to demonstrate compliance with the requirements of ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on

the coated surface.

Page 103 of 171

Page 104: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4* Interior wall and ceiling finish materials with special requirements. The materials

indicated in Sections 10.2.4.1 through 10.2.4.15 shall be tested as indicated in the

corresponding sections.

10.2.4.1 Thickness exemption.

10.2.4.1.1 The provisions of 10.2.3 shall not apply to materials having a total thickness of

less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings

where both of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.2 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shall

apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural members

complying with the requirements for Type IV (2HH) construction in accordance with 7.2.5

of this code shall be exempt from testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be used

as interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2.

The requirements of 10.2.4.3 shall apply both to exposed foamed plastics and to foamed

plastics used in conjunction with a textile or vinyl facing or cover.

10.2.4.3.1 Cellular or foamed plastic materials meeting the definition of foamed plastic

insulation shall be permitted where subjected to large-scale fire tests that substantiate

their combustibility and smoke release characteristics of the material for the use intended

under actual fire conditions.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibility of

cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material [(including smoke

measurements, with total smoke release not to exceed 10,764 ft2 (1000 m2)]

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction (4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2 The tests shall be performed on a finished foamed plastic assembly related to

the actual end-use configuration, including any cover or facing, and at the maximum

thickness intended for use.

10.2.4.3.1.3* Cellular or foamed plastic materials tested in accordance with ANSI/UL 1040,

Standard for Fire Test of Insulated Wall Construction, or FM 4880, Approval Standard for Class I Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish

Page 104 of 171

Page 105: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Materials or Coating, and Exterior Wall Systems, shall also be tested for smoke release

using NFPA 286, with the acceptance criterion of 10.2.3.2.

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent

of the specific wall or ceiling area to which it is applied, provided that it is not less than 20

lb/ft3 (320 kg/m3) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in

width, and complies with the requirements for Class A or Class B interior wall and ceiling

finish as described in 10.2.3.3; however, the smoke developed index shall not be limited.

10.2.4.4* Textile wall coverings. Where used as interior wall finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall comply with the requirements of one of the following:

section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1* Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using

method B of the test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.

(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) The total smoke released throughout the test shall not exceed 10,764 ft2 (1000 m2).

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordance

with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E2404,

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall

be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do not

exceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and

ceiling-height partitions.

10.2.4.5 Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,

expanded vinyl wall coverings shall be tested in the manner intended for use, using the

product mounting system, including adhesive, and shall comply with the requirements of

one of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

Page 105 of 171

Page 106: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,

expanded vinyl materials shall be tested in the manner intended for use, using the product

mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materials other

than wood are used, the lockers shall be considered interior finish and shall comply with

Section 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustible

materials shall be permitted to be used in any location where interior finish materials are

required to meet a Class C classification in accordance with 10.2.3.

10.2.4.9 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropylene and

high-density polyethylene materials shall not be permitted as interior wall or ceiling finish

unless the material complies with the requirements of 10.2.3.1. The tests shall be

performed on a finished assembly and on the maximum thickness intended for use.

10.2.4.10 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretch

systems containing all three components described in the definition in Chapter 3 shall be

tested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or

10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics.

Page 106 of 171

Page 107: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.11 Reflective Insulation Materials. Reflective insulation materials shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics.

10.2.4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall

panels meeting the requirements of Class A in accordance with 10.2.3, shall be permitted to

be finished with one additional application of paint. Such painted panels shall be permitted

for use in areas where Class A interior finishes are required. The total paint thickness shall

not exceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate. Laminated products

factory-produced with a wood substrate shall be tested in the manner intended for use and

shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are tested in

accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with

ASTM E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, using the product-mounting system (including

adhesive) of actual use.

10.2.4.14 Facings or wood veneers intended to be applied on site over a wood substrate.

Facings or veneers intended to be applied on site over a wood substrate shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they

shall use the product-mounting system, including adhesive, described in Section 5.8.9 of

NFPA 286. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, specimen

preparation and mounting shall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics.

10.2.4.15* Light transmitting plastics. Light-transmitting plastics used as interior wall and

ceiling finish shall be permitted based on large-scale fire tests that substantiate the

combustibility characteristics of the plastics for the use intended under actual fire

conditions. The tests shall be performed on a light transmitting plastic assembly related to

the actual end-use configuration and on the maximum thickness intended for use. (See Section 48.7.)

10.2.5 Trim and Incidental Finish.

Page 107 of 171

Page 108: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.5.1 General. Interior wall and ceiling trim and incidental finish, other than wall base

in accordance with 10.2.5.2 and bulletin boards and posters in accordance with 10.2.5.3, not

in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it

is applied shall be permitted to be Class C materials in occupancies where interior wall and

ceiling finish of Class A or Class B is required.

10.2.5.2 Wall Base. Interior floor trim material used at the junction of the wall and the floor

to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height,

shall meet the requirements for interior wall finish for its location or the requirements for

Class II interior floor finish as described in 10.2.6.4 using the test described in 10.2.6.3. If a

Class I floor finish is required, the interior floor trim shall be Class I.

10.2.5.3 Bulletin Boards and Posters.

10.2.5.3.1 Bulletin boards and posters attached directly to the wall shall not exceed 20

percent of the aggregate wall area to which they are applied.

10.2.5.3.2 The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in

sprinklered educational or day-care occupancies in accordance with 17.5.5.3, 18.5.5 or

18.6.5.

10.2.6* Interior Floor Finish Testing and Classification.

10.2.6.1* Carpet and carpet like interior floor finishes shall comply with ASTM D2859,

Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. 10.2.6.2* Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for

fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2.

10.2.6.3* Interior floor finishes shall be classified in accordance with 10.2.6.4, based on test

results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source. 10.2.6.4 Interior floor finishes shall be grouped in the classes specified in 10.2.6.4.1 and

10.2.6.4.2 in accordance with the critical radiant flux requirements.

10.2.6.4.1 Class I Interior Floor Finish. Class I interior floor finish shall have a critical

radiant flux of not less than 0.45 W/cm2, as determined by the test described in 10.2.6.3.

10.2.6.4.2 Class II Interior Floor Finish. Class II interior floor finish shall have a critical

radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the

test described in 10.2.6.3.

10.2.6.5Wherever the use of Class II interior floor finish is required, Class I interior floor

finish shall be permitted.

10.2.7 Automatic Sprinklers.

Page 108 of 171

Page 109: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.7.1 Other than as required in 10.5, where an approved automatic sprinkler system is

installed in accordance with Section 55.3, Class C interior wall and ceiling finish materials

shall be permitted in any location where Class B is required, and Class B interior wall and

ceiling finish materials shall be permitted in any location where Class A is required.

10.2.7.2 Where an approved automatic sprinkler system is installed in accordance with

Section 55.3, throughout the fire compartment or smoke compartment containing the

interior floor finish, Class II interior floor finish shall be permitted in any location where

Class I interior floor finish is required, and where Class II is required, the provisions of

10.2.6.2 shall apply.

Page 109 of 171

Page 110: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 55-NFPA 5000-2015 [ Section No. 10.4 ]

10.4 Interior Wall or Ceiling Finish Testing and Classification.

10.4.1 *

Interior wall or ceiling finish that is required elsewhere in this Code to be Class A, Class B, orClass C shall be classified based on test results from ASTM E 84, Standard Test Method ofSurface Burning Characteristics of Building Materials , or ANSI/UL 723, Standard for Test ofSurface Burning Characteristics of Building Materials , or except as indicated in 10.4.1.1 or10.4.1.2 .

10.4.1.1

Exposed portions of structural members complying with the requirements for Type IV(2HH)construction in accordance with 7.2.5 of this Code shall be exempt from the testing andclassification provisions of ASTM E 84 or ANSI/UL 723.

10.4.1.2

Interior wall and ceiling finish tested in accordance with NFPA 286, Standard Methods of FireTests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth , andmeeting the conditions of 10.4.5.2 , shall be permitted to be used where a Class Aclassification in accordance with ASTM E 84 or ANSI/UL 723 is required.

10.4.1.3 *

Fire-retardant coatings shall not be used to obtain compliance with the interior finishrequirements of this Code .

10.4.1.4 *

Surfaces of walls, partitions, columns, and ceilings shall be permitted to be finished withfactory-applied fire-retardant-coated products that have been listed and labeled to demonstratecompliance with the requirements of ASTM E 2768, Standard Test Method for ExtendedDuration Surface Burning Characteristics of Building Materials , on the coated surface.

10.4.2 *

Products required to be tested in accordance with ASTM E 84 or ANSI/UL 723 shall begrouped in the classes described in 10.4.2.1 through 10.4.2.3 in accordance with their flamespread index and smoke developed index, except as indicated in 10.4.1.2 .

10.4.2.1 Class A Interior Wall and Ceiling Finish.

Class A interior wall and ceiling finishes shall be those finishes with a flame spread index of0–25 and a smoke developed index of 0–450 and shall include any material classified at 25 orless on the flame spread index test scale and 450 or less on the smoke developed index testscale.

10.4.2.2 Class B Interior Wall and Ceiling Finish.

Class B interior wall and ceiling finishes shall be those finishes with a flame spread index of26–75 and a smoke developed index of 0–450 and shall include any material classified at morethan 25 but not more than 75 on the flame spread index test scale and 450 or less on thesmoke developed index test scale.

10.4.2.3 Class C Interior Wall and Ceiling Finish.

Class C interior wall and ceiling finishes shall be those finishes with a flame spread index of76–200 and a smoke developed index of 0–450 and shall include any material classified atmore than 75 but not more than 200 on the flame spread index test scale and 450 or less onthe smoke developed index test scale.

10.4.3

The classification of interior finish specified in 10.4.2 shall be that of the basic material usedby itself or in combination with other materials.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

167 of 479 7/7/2015 12:51 PMPage 110 of 171

Page 111: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.4.4

Wherever the use of Class C interior wall and ceiling finish is required, Class A or Class B shallbe permitted. Where Class B interior wall and ceiling finish is required, Class A shall bepermitted.

10.4.5 *

Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for EvaluatingRoom Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full HeightPanels and Walls , shall comply with the criteria of 10.4.5.1 . Products tested in accordancewith NFPA 286 shall comply with the criteria of 10.4.5.2 .

10.4.5.1 *

The interior finish shall comply with the following when tested using the Method B test protocolof NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution ofTextile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls :

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft by 12 ft(2440 mm by 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) The total smoke released throughout the test shall not exceed 1000 m 2 .

10.4.5.2

The interior finish shall comply with all of the following when tested using the test protocol ofNFPA 286:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

(3) Flashover, as described in NFPA 286, shall not occur.

(4) The peak heat release rate throughout the test shall not exceed 800 kW.

(5) The total smoke released throughout the test shall not exceed 10,764 ft 2 (1000 m 2 ).

Additional Proposed Changes

File Name Description Approved

NFPA_5000_sections_10.2_complete_proposed_for_2018_clean.docxProposed complete 10.2.

Statement of Problem and Substantiation for Public Input

This section, as well as sections 10.3 and 10.4 through 10.8 are proposed to be eliminated and incorporated into section 10.2, for parallelism with NFPA 101 (no change in requirements).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

168 of 479 7/7/2015 12:51 PMPage 111 of 171

Page 112: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jun 21 19:39:13 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

169 of 479 7/7/2015 12:51 PMPage 112 of 171

Page 113: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 5000 – Sections on Interior Finish - 10.2-10.8 (2018)

10.2* Interior Finish

10.2.1 General

10.2.1.1 Classification of interior finish materials shall be in accordance with tests made

under conditions simulating actual installations, provided that the authority having

jurisdiction is permitted to establish the classification of any material for which a

classification by a standard test is not available.

10.2.1.2 Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied

structurally or for decoration, acoustical correction, surface insulation, or other purposes

shall be considered interior finish and shall not be considered decorations or furnishings.

10.2.1.3 Lockers constructed of combustible materials shall be considered interior finish.

10.2.2* Use of Interior Finishes.

10.2.2.1 Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter 11

and Chapters 15 through 31 and 33 through 34 (2) As specified in section 10.2.3 through 10.2.5.

10.2.2.2* Interior floor finish shall comply with 10.2.6 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in this Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent

to floor finishes with a critical radiant flux of at least 0.1 W/cm2

10.2.3 Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified for

fire performance and smoke development it shall be classified in accordance with 10.2.3.1 or

10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1* Interior wall and ceiling finish materials tested in accordance with NFPA 286.

Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286,

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and comply with Section 10.2.3.2. Materials tested in

accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be considered

also to comply with the requirements of a Class A, Class B or Class C in accordance with

Section 10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with the

following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. The total smoke released throughout the test shall not exceed 10,764 ft2 (1,000 m2).

10.2.3.3* Interior wall and ceiling finish materials tested in accordance with ASTM E84 or

ANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance

Page 113 of 171

Page 114: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, except as indicated in Sections 10.2.3.4 and 10.2.3.5. Such interior

finish materials shall be grouped in the following classes in accordance with their flame

spread and smoke-developed indexes.

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 The classification of interior finish specified in 10.2.3.3 shall be that of the basic

material used by itself or in combination with other materials.

10.2.3.3.2 Wherever the use of Class C interior wall and ceiling finish is required, Class A

or Class B shall be permitted. Where Class B interior wall and ceiling finish is required,

Class A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not be

required to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

corresponding sections.

10.2.3.6* Fire-retardant coatings shall not be used to obtain compliance with the interior

finish requirements of this Code.

10.2.3.7* Surfaces of walls, partitions, columns, and ceilings shall be permitted to be

finished with factory-applied fire retardant-coated products that have been listed and

labeled to demonstrate compliance with the requirements of ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on

the coated surface.

Page 114 of 171

Page 115: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4* Interior wall and ceiling finish materials with special requirements. The materials

indicated in Sections 10.2.4.1 through 10.2.4.15 shall be tested as indicated in the

corresponding sections.

10.2.4.1 Thickness exemption.

10.2.4.1.1 The provisions of 10.2.3 shall not apply to materials having a total thickness of

less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings

where both of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.2 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shall

apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural members

complying with the requirements for Type IV (2HH) construction in accordance with 7.2.5

of this code shall be exempt from testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be used

as interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2.

The requirements of 10.2.4.3 shall apply both to exposed foamed plastics and to foamed

plastics used in conjunction with a textile or vinyl facing or cover.

10.2.4.3.1 Cellular or foamed plastic materials meeting the definition of foamed plastic

insulation shall be permitted where subjected to large-scale fire tests that substantiate

their combustibility and smoke release characteristics of the material for the use intended

under actual fire conditions.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibility of

cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material [(including smoke

measurements, with total smoke release not to exceed 10,764 ft2 (1000 m2)]

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction (4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2 The tests shall be performed on a finished foamed plastic assembly related to

the actual end-use configuration, including any cover or facing, and at the maximum

thickness intended for use.

10.2.4.3.1.3* Cellular or foamed plastic materials tested in accordance with ANSI/UL 1040,

Standard for Fire Test of Insulated Wall Construction, or FM 4880, Approval Standard for Class I Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish

Page 115 of 171

Page 116: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Materials or Coating, and Exterior Wall Systems, shall also be tested for smoke release

using NFPA 286, with the acceptance criterion of 10.2.3.2.

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent

of the specific wall or ceiling area to which it is applied, provided that it is not less than 20

lb/ft3 (320 kg/m3) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in

width, and complies with the requirements for Class A or Class B interior wall and ceiling

finish as described in 10.2.3.3; however, the smoke developed index shall not be limited.

10.2.4.4* Textile wall coverings. Where used as interior wall finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall comply with the requirements of one of the following:

section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1* Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using

method B of the test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.

(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) The total smoke released throughout the test shall not exceed 10,764 ft2 (1000 m2).

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordance

with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E2404,

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall

be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do not

exceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and

ceiling-height partitions.

10.2.4.5 Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,

expanded vinyl wall coverings shall be tested in the manner intended for use, using the

product mounting system, including adhesive, and shall comply with the requirements of

one of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

Page 116 of 171

Page 117: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,

expanded vinyl materials shall be tested in the manner intended for use, using the product

mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materials other

than wood are used, the lockers shall be considered interior finish and shall comply with

Section 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustible

materials shall be permitted to be used in any location where interior finish materials are

required to meet a Class C classification in accordance with 10.2.3.

10.2.4.9 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropylene and

high-density polyethylene materials shall not be permitted as interior wall or ceiling finish

unless the material complies with the requirements of 10.2.3.1. The tests shall be

performed on a finished assembly and on the maximum thickness intended for use.

10.2.4.10 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretch

systems containing all three components described in the definition in Chapter 3 shall be

tested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or

10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics.

Page 117 of 171

Page 118: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.11 Reflective Insulation Materials. Reflective insulation materials shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics.

10.2.4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall

panels meeting the requirements of Class A in accordance with 10.2.3, shall be permitted to

be finished with one additional application of paint. Such painted panels shall be permitted

for use in areas where Class A interior finishes are required. The total paint thickness shall

not exceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate. Laminated products

factory-produced with a wood substrate shall be tested in the manner intended for use and

shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are tested in

accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with

ASTM E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, using the product-mounting system (including

adhesive) of actual use.

10.2.4.14 Facings or wood veneers intended to be applied on site over a wood substrate.

Facings or veneers intended to be applied on site over a wood substrate shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they

shall use the product-mounting system, including adhesive, described in Section 5.8.9 of

NFPA 286. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, specimen

preparation and mounting shall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics.

10.2.4.15* Light transmitting plastics. Light-transmitting plastics used as interior wall and

ceiling finish shall be permitted based on large-scale fire tests that substantiate the

combustibility characteristics of the plastics for the use intended under actual fire

conditions. The tests shall be performed on a light transmitting plastic assembly related to

the actual end-use configuration and on the maximum thickness intended for use. (See Section 48.7.)

10.2.5 Trim and Incidental Finish.

Page 118 of 171

Page 119: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.5.1 General. Interior wall and ceiling trim and incidental finish, other than wall base

in accordance with 10.2.5.2 and bulletin boards and posters in accordance with 10.2.5.3, not

in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it

is applied shall be permitted to be Class C materials in occupancies where interior wall and

ceiling finish of Class A or Class B is required.

10.2.5.2 Wall Base. Interior floor trim material used at the junction of the wall and the floor

to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height,

shall meet the requirements for interior wall finish for its location or the requirements for

Class II interior floor finish as described in 10.2.6.4 using the test described in 10.2.6.3. If a

Class I floor finish is required, the interior floor trim shall be Class I.

10.2.5.3 Bulletin Boards and Posters.

10.2.5.3.1 Bulletin boards and posters attached directly to the wall shall not exceed 20

percent of the aggregate wall area to which they are applied.

10.2.5.3.2 The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in

sprinklered educational or day-care occupancies in accordance with 17.5.5.3, 18.5.5 or

18.6.5.

10.2.6* Interior Floor Finish Testing and Classification.

10.2.6.1* Carpet and carpet like interior floor finishes shall comply with ASTM D2859,

Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. 10.2.6.2* Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for

fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2.

10.2.6.3* Interior floor finishes shall be classified in accordance with 10.2.6.4, based on test

results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source. 10.2.6.4 Interior floor finishes shall be grouped in the classes specified in 10.2.6.4.1 and

10.2.6.4.2 in accordance with the critical radiant flux requirements.

10.2.6.4.1 Class I Interior Floor Finish. Class I interior floor finish shall have a critical

radiant flux of not less than 0.45 W/cm2, as determined by the test described in 10.2.6.3.

10.2.6.4.2 Class II Interior Floor Finish. Class II interior floor finish shall have a critical

radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the

test described in 10.2.6.3.

10.2.6.5Wherever the use of Class II interior floor finish is required, Class I interior floor

finish shall be permitted.

10.2.7 Automatic Sprinklers.

Page 119 of 171

Page 120: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.7.1 Other than as required in 10.5, where an approved automatic sprinkler system is

installed in accordance with Section 55.3, Class C interior wall and ceiling finish materials

shall be permitted in any location where Class B is required, and Class B interior wall and

ceiling finish materials shall be permitted in any location where Class A is required.

10.2.7.2 Where an approved automatic sprinkler system is installed in accordance with

Section 55.3, throughout the fire compartment or smoke compartment containing the

interior floor finish, Class II interior floor finish shall be permitted in any location where

Class I interior floor finish is required, and where Class II is required, the provisions of

10.2.6.2 shall apply.

Page 120 of 171

Page 121: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 48-NFPA 5000-2015 [ New Section after 10.5 ]

10.5.9 Laminated products factory-produced with a wood substrate . Laminated products factory-produced with a wood substrate shall be tested in the manner intended for use and shall complywith the requirements of 10.4. If the materials are tested in accordance with ASTM E84,Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,Standard for Test for Surface Burning Characteristics of Building Materials (see 10.4.2) ,specimen preparation and mounting shall be in accordance with ASTM E2579, Standard Practicefor Specimen Preparation and Mounting of Wood Products to Assess Surface BurningCharacteristics , using the product-mounting system (including adhesive) of actual use.

Statement of Problem and Substantiation for Public Input

ASTM has developed mounting methods for both "facings or wood veneer intended to be applied on site over a wood substrate" and laminated products that are factory produced and have a wood substrate. The concept is that facings that are produced as part of a commercial (factory-produced) panel are finished products and the manufacturer should be responsible to ensure that the product itself (the full panel) is safe and there is no need to discuss a substrate. It has been shown that, when veneers are applied over a wood substrate the resulting flame spread is much higher than when applied over gypsum board or over a noncombustible substrate. Therefore the requirement in ASTM E2579 is that the testing be done with the full product and, thus, there will no need to retest for different substrates. Similarly, NFPA 286 contains a section that addresses testing of wall covering materials, including facings applied on site and laminated products produced in the factory. Facings applied on site over wood substrates are tested using ASTM E2404. Note that this public input is not intended to replace an existing section but to be incorporated after the last section in 10.5. Note also that the public input to add a clarification of the requirements for facings or wood veneers intended to be applied on site over a wood substrate is also intended to be incorporated as a new section between.

NFPA 286 language5.8 Wall or Ceiling Covering Materials.5.8.2 Where the wall or ceiling covering system is a factory produced wall panel, the adhesive shall be the same one used in the manufacture of the factory-produced wall or ceiling panel.

ASTM E2579 - Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing wood products to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to laminated products factory produced with a wood substrate (see 8.6). This practice does not apply to wood veneers or facings intended to be applied on site over a wood substrate, which are covered by Practice E2404.1.3 Testing is conducted with Test Method E84.

ASTM E2404 – Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing textile,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

170 of 479 7/7/2015 12:51 PMPage 121 of 171

Page 122: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

paper or polymeric (including vinyl and expanded vinyl) wall or ceiling covering materials to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to facings or wood veneers intended to be applied on site over a wood substrate (see 8.7). This practice does not apply to laminated products factory produced with a wood substrate, which are covered by Practice E2579.1.3 Testing is conducted with Test Method E84.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 49-NFPA 5000-2015 [New Section after 10.5]

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 11 18:01:13 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

171 of 479 7/7/2015 12:51 PMPage 122 of 171

Page 123: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 49-NFPA 5000-2015 [ New Section after 10.5 ]

10.5.10 Facings or wood veneers intended to be applied on site over a wood substrate. Facingsor veneers intended to be applied on site over a wood substrate shall be tested in the mannerintended for use and shall comply with the requirements of 10.4. If the materials are tested inaccordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Walland Ceiling Interior Finish to Room Fire Growth (see 10.4.x), they shall use the product-mounting system, including adhesive, described in Section 5.8.9 of NFPA 286. If the materialsare tested in accordance with ASTM E84, Standard Test Method for Surface BurningCharacteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials (see 10.4.x), specimen preparation and mounting shall bein accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting ofTextile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings andVeneers, to Assess Surface Burning Characteristics .

Statement of Problem and Substantiation for Public Input

ASTM has developed mounting methods for both "facings or wood veneer intended to be applied on site over a wood substrate" and laminated products that are factory-produced and have a wood substrate. The concept is that these facings (applied on site) are basically the same as wall coverings and the manufacturer should be responsible for the facing only and needs to ensure that the material is safe and should test over the appropriate substrate. It has been shown that, when veneers are applied over a wood substrate the resulting flame spread is much higher than when applied over gypsum board or over a non-combustible substrate. Therefore the requirement in ASTM E2404 is that the testing be done over a standard wood substrate and, thus, there will no need to retest for different types of wood.

Similarly, NFPA 286 contains a section that addresses testing of wall covering materials, including facings applied on site and laminated products produced in the factory. Panels including factory applied facings with wood substrates are tested using ASTM E2579.

Note that this public input is not intended to replace an existing section but to be incorporated at the end of the 10.5 sections. Note also that the public input to add a clarification of the requirements for laminated products factory-produced with a wood substrate is also intended to be incorporated as a new section within 10.4.

NFPA 286 language5.9 Laminated Products with Wood Substrates.5.9.1 Laminated products shall be tested as they are intended to be installed.5.9.1.1 The test specimens shall consist of the finished product, namely the combination of the facing or veneer, the adhesives or fasteners used, and the specific wood substrate that will be used.5.9.2 If the laminated product consists of a facing or veneer intended to be applied on-site over a wood substrate, the facing or veneer shall be tested as described in 5.9.2.1 and 5.9.2.2.5.9.2.1* The test specimens shall comply with the following:(1) Specimens shall consist of the facing or veneer mounted on the "A" face of nominal 12 mm (15⁄32 in.) untreated plywood with a face veneer of Douglas fir.(2) The plywood shall comply with NIST Voluntary Product Standard PS 1, Structural Plywood.(3) The plywood shall carry one of the following grade stamps: (a) APA-The Engineered Wood Association (b) TECO, indicating that the plywood has been graded PS 1 A-B and is for exterior exposure (c) CSA Standard O121, Douglas Fir Plywood.5.9.2.2 The adhesive used to attach the facing or veneer to the wood substrate in 5.9.2.1 shall be that

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

172 of 479 7/7/2015 12:51 PMPage 123 of 171

Page 124: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

specified by the manufacturer of the facing or veneer and applied in accordance with manufacturer's application instructions.

Also, for information, from NFPA 286:5.8.9 Wall or Ceiling Coverings Intended to Be Applied over a Wood Substrate. If the wall or ceiling coverings are intended to be applied over a wood substrate, the specimens shall consist of the wall or ceiling covering mounted on untreated plywood, with a face veneer of Douglas fir. The plywood shall have the same thickness as the wood substrate used in actual installations, and shall comply with NIST Voluntary Product Standard PS 1-07, Structural Plywood. The plywood shall be marked with a grade stamp indicating that the plywood has been graded PS 1-07 A-B and is for exterior exposure. The grade stamp shall be issued by a quality control agency. Alternatively, the plywood shall be permitted to be stamped as conforming to CSA Standard O121, Douglas Fir Plywood.

ASTM E2404 – Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics 1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing textile, paper or polymeric (including vinyl and expanded vinyl) wall or ceiling covering materials to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to facings or wood veneers intended to be applied on site over a wood substrate (see 8.7). This practice does not apply to laminated products factory produced with a wood substrate, which are covered by Practice E2579.1.3 Testing is conducted with Test Method E84.

ASTM E2579 - Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics1. Scope1.1 This practice describes procedures for specimen preparation and mounting when testing wood products to assess flame spread and smoke development as surface burning characteristics using Test Method E84.1.2 This practice applies also to laminated products factory produced with a wood substrate (see 8.6). This practice does not apply to wood veneers or facings intended to be applied on site over a wood substrate, which are covered by Practice E2404.1.3 Testing is conducted with Test Method E84.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 48-NFPA 5000-2015 [New Section after 10.5]

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 11 18:11:24 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

173 of 479 7/7/2015 12:51 PMPage 124 of 171

Page 125: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 56-NFPA 5000-2015 [ Section No. 10.5 ]

10.5 * Specific Materials.

10.5.1 * Textile Wall and Textile Ceiling Materials.

The use of textile materials on walls or ceilings shall comply with one of the followingconditions:

(1) Textile materials meeting the requirements of Class A when tested in accordance withASTM E 84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials, or ANSI/UL 723, Standard for Test for Surface Burning, using the specimenpreparation and mounting method of ASTM E 2404, Standard Practice for SpecimenPreparation and Mounting of Textile, Paper or Polymeric (including Vinyl) Wall or CeilingCoverings, and of Facings and Wood Veneers Intended to be Applied on Site Over aWood Substrate, to Assess Surface Burning Characteristics, (see 10.4.2 ) , shall bepermitted on the walls or ceilings of rooms or areas protected by an approved automaticsprinkler system.

(2) Textile materials meeting the requirements of Class A when tested in accordance withASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method ofASTM E 2404 (see 10.3.2) , shall be permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height, or do not exceed 8 ft (2440 mm) in height,whichever is less.

(3) Textile materials meeting the requirements of Class A when tested in accordance withASTM E 84 or ANSI/UL 723, using the specimen preparation and mounting method ofASTM E 2404 ( see 10.3.2 ), shall be permitted to extend not more than 48 in. (1220mm) above the finished floor on ceiling-height walls and ceiling-height partitions.

(4) Textile materials shall be permitted on walls and partitions where tested in accordancewith NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire GrowthContribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels andWalls . ( See 10.3.5.)

(5) Textile materials shall be permitted on walls, partitions, and ceilings where tested inaccordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contributionof Wall and Ceiling Interior Finish to Room Fire Growth . (See 10.3.5.)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

174 of 479 7/7/2015 12:51 PMPage 125 of 171

Page 126: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.5.2 * Expanded Vinyl Wall and Ceiling Coverings.

The use of expanded vinyl wall or ceiling coverings shall comply with one of the followingconditions:

(1) Materials meeting the requirements of Class A when tested in accordance with ASTM E84 or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E2404 ( see 10.4.2 ), shall be permitted on the walls or ceilings of rooms or areasprotected by an approved automatic sprinkler system.

(2) Materials meeting the requirements of Class A when tested in accordance with ASTM E84 or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E2404 ( see 10.3.2 ), shall be permitted on partitions that do not exceed three-quarters ofthe floor-to-ceiling height, or do not exceed 8 ft (2440 mm) in height, whichever is less.

(3) Materials meeting the requirements of Class A when tested in accordance with ASTM E84 or ANSI/UL 723, using the specimen preparation and mounting method of ASTM E2404 ( see 10.3.2 ), shall be permitted to extend not more than 48 in. (1220 mm) abovethe finished floor on ceiling-height walls and ceiling-height partitions.

(4) Materials shall be permitted on walls and partitions where tested in accordance withNFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire GrowthContribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels andWalls . ( See 10.3.6 .)

(5) Materials shall be permitted on walls, partitions, and ceilings where tested inaccordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contributionof Wall and Ceiling Interior Finish to Room Fire Growth . ( See 10.3.5 .)

10.5.3 Cellular or Foamed Plastic.

Cellular or foamed plastic materials shall not be used as interior wall and ceiling finish, unlessspecifically permitted by 10.5.3.1 or 10.5.3.2 . This subsection shall apply to both exposedfoamed plastics and to foamed plastics used in conjunction with a textile or vinyl facing orcover.

10.5.3.1

Cellular or foamed plastic materials meeting the definition of foamed plastic insulation shall bepermitted where subjected to large-scale fire tests that substantiate the combustibility andsmoke release characteristics of the material for the use intended under actual fire conditions.

10.5.3.1.1

One of the following fire tests shall be used for assessing the combustibility of cellular orfoamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall andCeiling Interior Finish to Room Fire Growth , with the acceptance criteria of 10.4.5.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material [including smoke

measurements, with total smoke release not to exceed 10,764 ft 2 (1000 m 2 )]

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction

(4) FM 4880, Approval Standard for Class 1 Insulated Wall or Wall and Roof/CeilingPanels; Plastic Interior Finish Materials; Plastic Exterior Building Panels; Wall/CeilingCoating Systems; Interior or Exterior Finish Systems

10.5.3.1.2

The tests shall be performed on a finished foamed plastic assembly related to the actualend-use configuration, including any cover or facing, and at the maximum thickness intendedfor use.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

175 of 479 7/7/2015 12:51 PMPage 126 of 171

Page 127: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.5.3.1.3 *

Cellular or foamed plastic materials tested in accordance with ANSI/UL 1040, Standard for FireTest of Insulated Wall Construction , or FM 4880, Approval Standard for Class I Fire Rating ofInsulated Wall or Wall and Roof/Ceiling Panels, Interior Finish Materials or Coating, andExterior Wall Systems , shall also be tested for smoke release using NFPA 286, with theacceptance criterion of 10.4.5.2 .

10.5.3.2

Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent of the specific

wall or ceiling area to which it is applied, provided that it is not less than 20 lb/ft 3 (320 kg/m 3 )

in density, is limited to 1 ⁄ 2 in. (13 mm) in thickness and 4 in. (100 mm) in width, andcomplies with the requirements for Class A or Class B interior wall and ceiling finish, asdescribed in 10.4.2 ; however, the smoke developed index shall not be limited.

10.5.4 * Light-Transmitting Plastics.

Light-transmitting plastics used as interior wall and ceiling finish shall be permitted based onlarge-scale fire tests that substantiate the combustibility characteristics of the plastics for theuse intended under actual fire conditions. The tests shall be performed on a light-transmittingplastic assembly related to the actual end-use configuration and on the maximum thicknessintended for use. (See Section 48.7 .)

10.5.5 Metal Ceiling and Wall Panels.

Listed, factory-finished metal ceiling and wall panels meeting the requirements of Class A whentested in accordance with ASTM E 84 or ANSI/UL 723 ( see 10.4.2 ) shall be permitted to befinished with one additional application of paint. These painted panels shall be permitted foruse in areas where Class A interior finishes are required. The total paint thickness shall not

exceed 1 ⁄ 28 in. (0.90 mm).

10.5.6 Lockers.

10.5.6.1 Combustible Lockers.

Where lockers constructed of combustible materials other than wood are used, the lockersshall be considered interior finish and shall comply with Section 10.2 , except as permitted by10.5.6.2 .

10.5.6.2 Wood Lockers.

Lockers constructed entirely of wood and of noncombustible materials shall be permitted to beused in any location where interior finish materials are required to meet a Class C classificationin accordance with 10.4.1 .

10.5.7 Polypropylene (PP) and High Density Polyethylene (HDPE).

Polypropylene and high density polyethylene materials shall not be permitted to be used asinterior wall or ceiling finish, unless the material complies with the requirements of 10.4.5.2 .The tests shall be performed on a finished assembly and on the maximum thickness intendedfor use.

10.5.8 Site-Fabricated Stretch Systems.

Site-fabricated stretch systems containing all three components described in the definition inChapter 3 shall be tested in the manner intended for use and shall comply with therequirements of 10.4.1 or 10.4.1.2 . If the materials are tested in accordance with ASTM E 84or ANSI/UL 723, specimen preparation and mounting shall be in accordance with ASTM E2573.

10.5.9 Reflective Insulation Materials.

Reflective insulation materials shall be tested in the manner intended for use and shall complywith the requirements of 10.4.1 or 10.4.1.2 . If the materials are tested in accordance withASTM E 84 or ANSI/UL 723, specimen preparation and mounting shall be in accordance withASTM E 2599, Standard Practice for Specimen Preparation and Mounting of ReflectiveInsulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications toAssess Surface Burning Characteristics .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

176 of 479 7/7/2015 12:51 PMPage 127 of 171

Page 128: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Additional Proposed Changes

File Name Description Approved

NFPA_5000_sections_10.2_complete_proposed_for_2018_clean.docxproposed complete new 10.2

Statement of Problem and Substantiation for Public Input

This section, as well as sections 10.3, 10.4 and 10.6 through 10.8 are proposed to be eliminated and incorporated into section 10.2, for parallelism with NFPA 101 (no change in requirements).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jun 21 19:40:45 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

177 of 479 7/7/2015 12:51 PMPage 128 of 171

Page 129: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 5000 – Sections on Interior Finish - 10.2-10.8 (2018)

10.2* Interior Finish

10.2.1 General

10.2.1.1 Classification of interior finish materials shall be in accordance with tests made

under conditions simulating actual installations, provided that the authority having

jurisdiction is permitted to establish the classification of any material for which a

classification by a standard test is not available.

10.2.1.2 Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied

structurally or for decoration, acoustical correction, surface insulation, or other purposes

shall be considered interior finish and shall not be considered decorations or furnishings.

10.2.1.3 Lockers constructed of combustible materials shall be considered interior finish.

10.2.2* Use of Interior Finishes.

10.2.2.1 Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter 11

and Chapters 15 through 31 and 33 through 34 (2) As specified in section 10.2.3 through 10.2.5.

10.2.2.2* Interior floor finish shall comply with 10.2.6 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in this Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent

to floor finishes with a critical radiant flux of at least 0.1 W/cm2

10.2.3 Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified for

fire performance and smoke development it shall be classified in accordance with 10.2.3.1 or

10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1* Interior wall and ceiling finish materials tested in accordance with NFPA 286.

Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286,

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and comply with Section 10.2.3.2. Materials tested in

accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be considered

also to comply with the requirements of a Class A, Class B or Class C in accordance with

Section 10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with the

following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. The total smoke released throughout the test shall not exceed 10,764 ft2 (1,000 m2).

10.2.3.3* Interior wall and ceiling finish materials tested in accordance with ASTM E84 or

ANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance

Page 129 of 171

Page 130: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, except as indicated in Sections 10.2.3.4 and 10.2.3.5. Such interior

finish materials shall be grouped in the following classes in accordance with their flame

spread and smoke-developed indexes.

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 The classification of interior finish specified in 10.2.3.3 shall be that of the basic

material used by itself or in combination with other materials.

10.2.3.3.2 Wherever the use of Class C interior wall and ceiling finish is required, Class A

or Class B shall be permitted. Where Class B interior wall and ceiling finish is required,

Class A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not be

required to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

corresponding sections.

10.2.3.6* Fire-retardant coatings shall not be used to obtain compliance with the interior

finish requirements of this Code.

10.2.3.7* Surfaces of walls, partitions, columns, and ceilings shall be permitted to be

finished with factory-applied fire retardant-coated products that have been listed and

labeled to demonstrate compliance with the requirements of ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on

the coated surface.

Page 130 of 171

Page 131: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4* Interior wall and ceiling finish materials with special requirements. The materials

indicated in Sections 10.2.4.1 through 10.2.4.15 shall be tested as indicated in the

corresponding sections.

10.2.4.1 Thickness exemption.

10.2.4.1.1 The provisions of 10.2.3 shall not apply to materials having a total thickness of

less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings

where both of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.2 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shall

apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural members

complying with the requirements for Type IV (2HH) construction in accordance with 7.2.5

of this code shall be exempt from testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be used

as interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2.

The requirements of 10.2.4.3 shall apply both to exposed foamed plastics and to foamed

plastics used in conjunction with a textile or vinyl facing or cover.

10.2.4.3.1 Cellular or foamed plastic materials meeting the definition of foamed plastic

insulation shall be permitted where subjected to large-scale fire tests that substantiate

their combustibility and smoke release characteristics of the material for the use intended

under actual fire conditions.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibility of

cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material [(including smoke

measurements, with total smoke release not to exceed 10,764 ft2 (1000 m2)]

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction (4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2 The tests shall be performed on a finished foamed plastic assembly related to

the actual end-use configuration, including any cover or facing, and at the maximum

thickness intended for use.

10.2.4.3.1.3* Cellular or foamed plastic materials tested in accordance with ANSI/UL 1040,

Standard for Fire Test of Insulated Wall Construction, or FM 4880, Approval Standard for Class I Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish

Page 131 of 171

Page 132: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Materials or Coating, and Exterior Wall Systems, shall also be tested for smoke release

using NFPA 286, with the acceptance criterion of 10.2.3.2.

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent

of the specific wall or ceiling area to which it is applied, provided that it is not less than 20

lb/ft3 (320 kg/m3) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in

width, and complies with the requirements for Class A or Class B interior wall and ceiling

finish as described in 10.2.3.3; however, the smoke developed index shall not be limited.

10.2.4.4* Textile wall coverings. Where used as interior wall finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall comply with the requirements of one of the following:

section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1* Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using

method B of the test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.

(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) The total smoke released throughout the test shall not exceed 10,764 ft2 (1000 m2).

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordance

with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E2404,

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall

be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do not

exceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and

ceiling-height partitions.

10.2.4.5 Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,

expanded vinyl wall coverings shall be tested in the manner intended for use, using the

product mounting system, including adhesive, and shall comply with the requirements of

one of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

Page 132 of 171

Page 133: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,

expanded vinyl materials shall be tested in the manner intended for use, using the product

mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materials other

than wood are used, the lockers shall be considered interior finish and shall comply with

Section 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustible

materials shall be permitted to be used in any location where interior finish materials are

required to meet a Class C classification in accordance with 10.2.3.

10.2.4.9 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropylene and

high-density polyethylene materials shall not be permitted as interior wall or ceiling finish

unless the material complies with the requirements of 10.2.3.1. The tests shall be

performed on a finished assembly and on the maximum thickness intended for use.

10.2.4.10 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretch

systems containing all three components described in the definition in Chapter 3 shall be

tested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or

10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics.

Page 133 of 171

Page 134: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.11 Reflective Insulation Materials. Reflective insulation materials shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics.

10.2.4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall

panels meeting the requirements of Class A in accordance with 10.2.3, shall be permitted to

be finished with one additional application of paint. Such painted panels shall be permitted

for use in areas where Class A interior finishes are required. The total paint thickness shall

not exceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate. Laminated products

factory-produced with a wood substrate shall be tested in the manner intended for use and

shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are tested in

accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with

ASTM E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, using the product-mounting system (including

adhesive) of actual use.

10.2.4.14 Facings or wood veneers intended to be applied on site over a wood substrate.

Facings or veneers intended to be applied on site over a wood substrate shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they

shall use the product-mounting system, including adhesive, described in Section 5.8.9 of

NFPA 286. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, specimen

preparation and mounting shall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics.

10.2.4.15* Light transmitting plastics. Light-transmitting plastics used as interior wall and

ceiling finish shall be permitted based on large-scale fire tests that substantiate the

combustibility characteristics of the plastics for the use intended under actual fire

conditions. The tests shall be performed on a light transmitting plastic assembly related to

the actual end-use configuration and on the maximum thickness intended for use. (See Section 48.7.)

10.2.5 Trim and Incidental Finish.

Page 134 of 171

Page 135: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.5.1 General. Interior wall and ceiling trim and incidental finish, other than wall base

in accordance with 10.2.5.2 and bulletin boards and posters in accordance with 10.2.5.3, not

in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it

is applied shall be permitted to be Class C materials in occupancies where interior wall and

ceiling finish of Class A or Class B is required.

10.2.5.2 Wall Base. Interior floor trim material used at the junction of the wall and the floor

to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height,

shall meet the requirements for interior wall finish for its location or the requirements for

Class II interior floor finish as described in 10.2.6.4 using the test described in 10.2.6.3. If a

Class I floor finish is required, the interior floor trim shall be Class I.

10.2.5.3 Bulletin Boards and Posters.

10.2.5.3.1 Bulletin boards and posters attached directly to the wall shall not exceed 20

percent of the aggregate wall area to which they are applied.

10.2.5.3.2 The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in

sprinklered educational or day-care occupancies in accordance with 17.5.5.3, 18.5.5 or

18.6.5.

10.2.6* Interior Floor Finish Testing and Classification.

10.2.6.1* Carpet and carpet like interior floor finishes shall comply with ASTM D2859,

Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. 10.2.6.2* Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for

fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2.

10.2.6.3* Interior floor finishes shall be classified in accordance with 10.2.6.4, based on test

results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source. 10.2.6.4 Interior floor finishes shall be grouped in the classes specified in 10.2.6.4.1 and

10.2.6.4.2 in accordance with the critical radiant flux requirements.

10.2.6.4.1 Class I Interior Floor Finish. Class I interior floor finish shall have a critical

radiant flux of not less than 0.45 W/cm2, as determined by the test described in 10.2.6.3.

10.2.6.4.2 Class II Interior Floor Finish. Class II interior floor finish shall have a critical

radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the

test described in 10.2.6.3.

10.2.6.5Wherever the use of Class II interior floor finish is required, Class I interior floor

finish shall be permitted.

10.2.7 Automatic Sprinklers.

Page 135 of 171

Page 136: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.7.1 Other than as required in 10.5, where an approved automatic sprinkler system is

installed in accordance with Section 55.3, Class C interior wall and ceiling finish materials

shall be permitted in any location where Class B is required, and Class B interior wall and

ceiling finish materials shall be permitted in any location where Class A is required.

10.2.7.2 Where an approved automatic sprinkler system is installed in accordance with

Section 55.3, throughout the fire compartment or smoke compartment containing the

interior floor finish, Class II interior floor finish shall be permitted in any location where

Class I interior floor finish is required, and where Class II is required, the provisions of

10.2.6.2 shall apply.

Page 136 of 171

Page 137: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 57-NFPA 5000-2015 [ Section No. 10.6 ]

10.6 Trim and Incidental Finish.

10.6.1 General.

Interior wall and ceiling trim and incidental finish, other than wall base in accordance with10.6.2 and bulletin boards and posters in accordance with 10.6.3 , not in excess of 10 percentof the specific wall and ceiling areas of any room or space to which it is applied, shall bepermitted to be Class C materials in occupancies where interior wall and ceiling finish of ClassA or Class B is required

10.6.2 Wall Base.

Interior floor trim material used at the junction of the wall and the floor to provide a functional ordecorative border, and not exceeding 6 in. (150 mm) in height, shall meet the interior wall finishrequirements for its location or the requirements for Class II interior floor finish, as described in10.7.4 , using the test described in 10.7.3 . If a Class I floor finish is required, the interior floortrim shall be Class I.

10.6.3 Bulletin Boards and Posters.

10.6.3.1

Bulletin boards and posters attached directly to the wall shall not exceed 20 percent of theaggregate wall area to which they are applied.

10.6.3.2

The provision of 10.6.3.1 shall not apply to artwork and teaching materials in sprinklerededucational or day-care occupancies in accordance with 17.5.5.3 , 18.5.5 , or 18.6.5 .

Additional Proposed Changes

File Name Description Approved

NFPA_5000_sections_10.2_complete_proposed_for_2018_clean.docxproposed complete 10.2

Statement of Problem and Substantiation for Public Input

This section, as well as sections 10.3 through 10.5 and 10.7 through 10.8 are proposed to be eliminated and incorporated into section 10.2, for parallelism with NFPA 101 (no change in requirements).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

178 of 479 7/7/2015 12:51 PMPage 137 of 171

Page 138: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Zip:

Submittal Date: Sun Jun 21 19:42:18 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

179 of 479 7/7/2015 12:51 PMPage 138 of 171

Page 139: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 5000 – Sections on Interior Finish - 10.2-10.8 (2018)

10.2* Interior Finish

10.2.1 General

10.2.1.1 Classification of interior finish materials shall be in accordance with tests made

under conditions simulating actual installations, provided that the authority having

jurisdiction is permitted to establish the classification of any material for which a

classification by a standard test is not available.

10.2.1.2 Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied

structurally or for decoration, acoustical correction, surface insulation, or other purposes

shall be considered interior finish and shall not be considered decorations or furnishings.

10.2.1.3 Lockers constructed of combustible materials shall be considered interior finish.

10.2.2* Use of Interior Finishes.

10.2.2.1 Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter 11

and Chapters 15 through 31 and 33 through 34 (2) As specified in section 10.2.3 through 10.2.5.

10.2.2.2* Interior floor finish shall comply with 10.2.6 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in this Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent

to floor finishes with a critical radiant flux of at least 0.1 W/cm2

10.2.3 Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified for

fire performance and smoke development it shall be classified in accordance with 10.2.3.1 or

10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1* Interior wall and ceiling finish materials tested in accordance with NFPA 286.

Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286,

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and comply with Section 10.2.3.2. Materials tested in

accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be considered

also to comply with the requirements of a Class A, Class B or Class C in accordance with

Section 10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with the

following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. The total smoke released throughout the test shall not exceed 10,764 ft2 (1,000 m2).

10.2.3.3* Interior wall and ceiling finish materials tested in accordance with ASTM E84 or

ANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance

Page 139 of 171

Page 140: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, except as indicated in Sections 10.2.3.4 and 10.2.3.5. Such interior

finish materials shall be grouped in the following classes in accordance with their flame

spread and smoke-developed indexes.

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 The classification of interior finish specified in 10.2.3.3 shall be that of the basic

material used by itself or in combination with other materials.

10.2.3.3.2 Wherever the use of Class C interior wall and ceiling finish is required, Class A

or Class B shall be permitted. Where Class B interior wall and ceiling finish is required,

Class A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not be

required to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

corresponding sections.

10.2.3.6* Fire-retardant coatings shall not be used to obtain compliance with the interior

finish requirements of this Code.

10.2.3.7* Surfaces of walls, partitions, columns, and ceilings shall be permitted to be

finished with factory-applied fire retardant-coated products that have been listed and

labeled to demonstrate compliance with the requirements of ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on

the coated surface.

Page 140 of 171

Page 141: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4* Interior wall and ceiling finish materials with special requirements. The materials

indicated in Sections 10.2.4.1 through 10.2.4.15 shall be tested as indicated in the

corresponding sections.

10.2.4.1 Thickness exemption.

10.2.4.1.1 The provisions of 10.2.3 shall not apply to materials having a total thickness of

less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings

where both of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.2 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shall

apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural members

complying with the requirements for Type IV (2HH) construction in accordance with 7.2.5

of this code shall be exempt from testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be used

as interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2.

The requirements of 10.2.4.3 shall apply both to exposed foamed plastics and to foamed

plastics used in conjunction with a textile or vinyl facing or cover.

10.2.4.3.1 Cellular or foamed plastic materials meeting the definition of foamed plastic

insulation shall be permitted where subjected to large-scale fire tests that substantiate

their combustibility and smoke release characteristics of the material for the use intended

under actual fire conditions.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibility of

cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material [(including smoke

measurements, with total smoke release not to exceed 10,764 ft2 (1000 m2)]

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction (4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2 The tests shall be performed on a finished foamed plastic assembly related to

the actual end-use configuration, including any cover or facing, and at the maximum

thickness intended for use.

10.2.4.3.1.3* Cellular or foamed plastic materials tested in accordance with ANSI/UL 1040,

Standard for Fire Test of Insulated Wall Construction, or FM 4880, Approval Standard for Class I Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish

Page 141 of 171

Page 142: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Materials or Coating, and Exterior Wall Systems, shall also be tested for smoke release

using NFPA 286, with the acceptance criterion of 10.2.3.2.

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent

of the specific wall or ceiling area to which it is applied, provided that it is not less than 20

lb/ft3 (320 kg/m3) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in

width, and complies with the requirements for Class A or Class B interior wall and ceiling

finish as described in 10.2.3.3; however, the smoke developed index shall not be limited.

10.2.4.4* Textile wall coverings. Where used as interior wall finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall comply with the requirements of one of the following:

section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1* Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using

method B of the test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.

(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) The total smoke released throughout the test shall not exceed 10,764 ft2 (1000 m2).

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordance

with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E2404,

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall

be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do not

exceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and

ceiling-height partitions.

10.2.4.5 Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,

expanded vinyl wall coverings shall be tested in the manner intended for use, using the

product mounting system, including adhesive, and shall comply with the requirements of

one of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

Page 142 of 171

Page 143: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,

expanded vinyl materials shall be tested in the manner intended for use, using the product

mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materials other

than wood are used, the lockers shall be considered interior finish and shall comply with

Section 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustible

materials shall be permitted to be used in any location where interior finish materials are

required to meet a Class C classification in accordance with 10.2.3.

10.2.4.9 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropylene and

high-density polyethylene materials shall not be permitted as interior wall or ceiling finish

unless the material complies with the requirements of 10.2.3.1. The tests shall be

performed on a finished assembly and on the maximum thickness intended for use.

10.2.4.10 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretch

systems containing all three components described in the definition in Chapter 3 shall be

tested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or

10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics.

Page 143 of 171

Page 144: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.11 Reflective Insulation Materials. Reflective insulation materials shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics.

10.2.4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall

panels meeting the requirements of Class A in accordance with 10.2.3, shall be permitted to

be finished with one additional application of paint. Such painted panels shall be permitted

for use in areas where Class A interior finishes are required. The total paint thickness shall

not exceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate. Laminated products

factory-produced with a wood substrate shall be tested in the manner intended for use and

shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are tested in

accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with

ASTM E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, using the product-mounting system (including

adhesive) of actual use.

10.2.4.14 Facings or wood veneers intended to be applied on site over a wood substrate.

Facings or veneers intended to be applied on site over a wood substrate shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they

shall use the product-mounting system, including adhesive, described in Section 5.8.9 of

NFPA 286. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, specimen

preparation and mounting shall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics.

10.2.4.15* Light transmitting plastics. Light-transmitting plastics used as interior wall and

ceiling finish shall be permitted based on large-scale fire tests that substantiate the

combustibility characteristics of the plastics for the use intended under actual fire

conditions. The tests shall be performed on a light transmitting plastic assembly related to

the actual end-use configuration and on the maximum thickness intended for use. (See Section 48.7.)

10.2.5 Trim and Incidental Finish.

Page 144 of 171

Page 145: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.5.1 General. Interior wall and ceiling trim and incidental finish, other than wall base

in accordance with 10.2.5.2 and bulletin boards and posters in accordance with 10.2.5.3, not

in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it

is applied shall be permitted to be Class C materials in occupancies where interior wall and

ceiling finish of Class A or Class B is required.

10.2.5.2 Wall Base. Interior floor trim material used at the junction of the wall and the floor

to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height,

shall meet the requirements for interior wall finish for its location or the requirements for

Class II interior floor finish as described in 10.2.6.4 using the test described in 10.2.6.3. If a

Class I floor finish is required, the interior floor trim shall be Class I.

10.2.5.3 Bulletin Boards and Posters.

10.2.5.3.1 Bulletin boards and posters attached directly to the wall shall not exceed 20

percent of the aggregate wall area to which they are applied.

10.2.5.3.2 The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in

sprinklered educational or day-care occupancies in accordance with 17.5.5.3, 18.5.5 or

18.6.5.

10.2.6* Interior Floor Finish Testing and Classification.

10.2.6.1* Carpet and carpet like interior floor finishes shall comply with ASTM D2859,

Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. 10.2.6.2* Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for

fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2.

10.2.6.3* Interior floor finishes shall be classified in accordance with 10.2.6.4, based on test

results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source. 10.2.6.4 Interior floor finishes shall be grouped in the classes specified in 10.2.6.4.1 and

10.2.6.4.2 in accordance with the critical radiant flux requirements.

10.2.6.4.1 Class I Interior Floor Finish. Class I interior floor finish shall have a critical

radiant flux of not less than 0.45 W/cm2, as determined by the test described in 10.2.6.3.

10.2.6.4.2 Class II Interior Floor Finish. Class II interior floor finish shall have a critical

radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the

test described in 10.2.6.3.

10.2.6.5Wherever the use of Class II interior floor finish is required, Class I interior floor

finish shall be permitted.

10.2.7 Automatic Sprinklers.

Page 145 of 171

Page 146: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.7.1 Other than as required in 10.5, where an approved automatic sprinkler system is

installed in accordance with Section 55.3, Class C interior wall and ceiling finish materials

shall be permitted in any location where Class B is required, and Class B interior wall and

ceiling finish materials shall be permitted in any location where Class A is required.

10.2.7.2 Where an approved automatic sprinkler system is installed in accordance with

Section 55.3, throughout the fire compartment or smoke compartment containing the

interior floor finish, Class II interior floor finish shall be permitted in any location where

Class I interior floor finish is required, and where Class II is required, the provisions of

10.2.6.2 shall apply.

Page 146 of 171

Page 147: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 58-NFPA 5000-2015 [ Section No. 10.7 ]

10.7 * Interior Floor Finish Testing and Classification.

10.7.1 *

Carpet and carpetlike interior floor finishes shall comply with ASTM D 2859, Standard TestMethod for Ignition Characteristics of Finished Textile Floor Covering Materials .

10.7.2 *

Floor coverings, other than carpet for which 10.3.2 establishes requirements for fire

performance, shall have a minimum critical radiant flux of 0.1 W/cm 2 .

10.7.3 *

Interior floor finishes shall be classified in accordance with 10.7.4 , based on test results fromNFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Usinga Radiant Heat Energy Source , or ASTM E 648, Standard Test Method for Critical RadiantFlux of Floor Covering Systems Using a Radiant Heat Energy Source .

10.7.4

Interior floor finishes shall be grouped in the classes specified in 10.7.4.1 and 10.7.4.2 inaccordance with the critical radiant flux requirements.

10.7.4.1 Class I Interior Floor Finish.

Class I interior floor finish shall have a critical radiant flux of not less than 0.45 W/cm 2 , asdetermined by the test described in 10.7.3 .

10.7.4.2 Class II Interior Floor Finish.

Class II interior floor finish shall have a critical radiant flux of not less than 0.22 W/cm 2 , but

less than 0.45 W/cm 2 , as determined by the test described in 10.7.3 .

10.7.5

Wherever the use of Class II interior floor finish is required, Class I interior floor finish shall bepermitted.

Additional Proposed Changes

File Name Description Approved

NFPA_5000_sections_10.2_complete_proposed_for_2018_clean.docxproposed complete 10.2

Statement of Problem and Substantiation for Public Input

This section, as well as sections 10.3 through 10.6 and section 10.8 are proposed to be eliminated and incorporated into section 10.2, for parallelism with NFPA 101 (no change in requirements).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

180 of 479 7/7/2015 12:51 PMPage 147 of 171

Page 148: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jun 21 19:43:50 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

181 of 479 7/7/2015 12:51 PMPage 148 of 171

Page 149: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 59-NFPA 5000-2015 [ Section No. 10.8 ]

10.8 Automatic Sprinklers.

10.8.1

Other than as required in Section 10.5 , where an approved automatic sprinkler system isinstalled in accordance with Section 55.3 , Class C interior wall and ceiling finish materialsshall be permitted in any location where Class B is required, and Class B interior wall andceiling finish materials shall be permitted in any location where Class A is required.

10.8.2

Where an approved automatic sprinkler system is installed in accordance with Section 55.3throughout the fire compartment or smoke compartment containing the interior floor finish,Class II interior floor finish shall be permitted in any location where Class I interior floor finish isrequired; and where Class II is required, the provisions of 10.7.2 shall apply.

Additional Proposed Changes

File Name Description Approved

NFPA_5000_sections_10.2_complete_proposed_for_2018_clean.docxproposed complete 10.2

Statement of Problem and Substantiation for Public Input

This section, as well as sections 10.3 through 10.7 are proposed to be eliminated and incorporated into section 10.2, for parallelism with NFPA 101 (no change in requirements).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Sun Jun 21 19:45:19 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

182 of 479 7/7/2015 12:51 PMPage 149 of 171

Page 150: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

NFPA 5000 – Sections on Interior Finish - 10.2-10.8 (2018)

10.2* Interior Finish

10.2.1 General

10.2.1.1 Classification of interior finish materials shall be in accordance with tests made

under conditions simulating actual installations, provided that the authority having

jurisdiction is permitted to establish the classification of any material for which a

classification by a standard test is not available.

10.2.1.2 Fixed or movable walls and partitions, paneling, wall pads, and crash pads applied

structurally or for decoration, acoustical correction, surface insulation, or other purposes

shall be considered interior finish and shall not be considered decorations or furnishings.

10.2.1.3 Lockers constructed of combustible materials shall be considered interior finish.

10.2.2* Use of Interior Finishes.

10.2.2.1 Requirements for interior wall and ceiling finish shall apply as follows:

(1) Where specified elsewhere in this Code for specific occupancies as noted in Chapter 11

and Chapters 15 through 31 and 33 through 34 (2) As specified in section 10.2.3 through 10.2.5.

10.2.2.2* Interior floor finish shall comply with 10.2.6 under any of the following conditions:

(1) Where floor finish requirements are specified elsewhere in this Code

(2) Where the fire performance of the floor finish cannot be demonstrated to be equivalent

to floor finishes with a critical radiant flux of at least 0.1 W/cm2

10.2.3 Interior Wall or Ceiling Finish Testing and Classification.

When interior wall or ceiling finish is required elsewhere in this Code to be classified for

fire performance and smoke development it shall be classified in accordance with 10.2.3.1 or

10.2.3.3, except as indicated in sections 10.2.4.

10.2.3.1* Interior wall and ceiling finish materials tested in accordance with NFPA 286.

Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286,

Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, and comply with Section 10.2.3.2. Materials tested in

accordance with section 10.2.3.1 and complying with Section 10.2.3.2 shall be considered

also to comply with the requirements of a Class A, Class B or Class C in accordance with

Section 10.2.3.3.

10.2.3.2 Acceptance criteria for NFPA 286. The interior finish shall comply with the

following:

1. During the 40 kW exposure, flames shall not spread to the ceiling.

2. The flame shall not spread to the outer extremity of the sample on any wall or ceiling.

3. Flashover, as defined in NFPA 286, shall not occur.

4. The peak heat release rate throughout the test shall not exceed 800 kW.

5. The total smoke released throughout the test shall not exceed 10,764 ft2 (1,000 m2).

10.2.3.3* Interior wall and ceiling finish materials tested in accordance with ASTM E84 or

ANSI/UL 723. Interior wall and ceiling finish materials shall be classified in accordance

Page 150 of 171

Page 151: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

with ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, except as indicated in Sections 10.2.3.4 and 10.2.3.5. Such interior

finish materials shall be grouped in the following classes in accordance with their flame

spread and smoke-developed indexes.

Class A: Flame spread index 0-25; smoke developed index 0-450.

Class B: Flame spread index 26-75; smoke developed index 0-450.

Class C: Flame spread index 76-200; smoke developed index 0-450.

10.2.3.3.1 The classification of interior finish specified in 10.2.3.3 shall be that of the basic

material used by itself or in combination with other materials.

10.2.3.3.2 Wherever the use of Class C interior wall and ceiling finish is required, Class A

or Class B shall be permitted. Where Class B interior wall and ceiling finish is required,

Class A shall be permitted.

10.2.3.4 Materials complying with the requirements of Section 10.2.3.1 shall not be

required to be tested in accordance with 10.2.3.3.

10.2.3.5 Materials described in sections 10.2.4 shall be tested as described in the

corresponding sections.

10.2.3.6* Fire-retardant coatings shall not be used to obtain compliance with the interior

finish requirements of this Code.

10.2.3.7* Surfaces of walls, partitions, columns, and ceilings shall be permitted to be

finished with factory-applied fire retardant-coated products that have been listed and

labeled to demonstrate compliance with the requirements of ASTM E2768, Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials, on

the coated surface.

Page 151 of 171

Page 152: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4* Interior wall and ceiling finish materials with special requirements. The materials

indicated in Sections 10.2.4.1 through 10.2.4.15 shall be tested as indicated in the

corresponding sections.

10.2.4.1 Thickness exemption.

10.2.4.1.1 The provisions of 10.2.3 shall not apply to materials having a total thickness of

less than 1⁄28 in. (0.9 mm) that are applied directly to the surface of walls and ceilings

where both of the following conditions are met:

(1) The wall or ceiling surface is a noncombustible or limited combustible material.

(2) The materials applied meet the requirements of Class A interior wall or ceiling finish

when tested in accordance with 10.2.3, using fiber cement board as the substrate material.

10.2.4.1.2 If a material having a total thickness of less than 1⁄28 in. (0.9 mm) is applied to a

surface that is not noncombustible or not limited-combustible, the provisions of 10.2.3 shall

apply.

10.2.4.2 Exposed portions of structural members. Exposed portions of structural members

complying with the requirements for Type IV (2HH) construction in accordance with 7.2.5

of this code shall be exempt from testing and classification in accordance with 10.2.3.

10.2.4.3 Cellular or Foamed Plastic. Cellular or foamed plastic materials shall not be used

as interior wall and ceiling finish unless specifically permitted by 10.2.4.3.1 or 10.2.4.3.2.

The requirements of 10.2.4.3 shall apply both to exposed foamed plastics and to foamed

plastics used in conjunction with a textile or vinyl facing or cover.

10.2.4.3.1 Cellular or foamed plastic materials meeting the definition of foamed plastic

insulation shall be permitted where subjected to large-scale fire tests that substantiate

their combustibility and smoke release characteristics of the material for the use intended

under actual fire conditions.

10.2.4.3.1.1 One of the following fire tests shall be used for assessing the combustibility of

cellular or foamed plastic materials as interior finish:

(1) NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, with the acceptance criteria of 10.2.3.2

(2) ANSI/UL 1715, Standard for Fire Test of Interior Finish Material [(including smoke

measurements, with total smoke release not to exceed 10,764 ft2 (1000 m2)]

(3) ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction (4) ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems

10.2.4.3.1.2 The tests shall be performed on a finished foamed plastic assembly related to

the actual end-use configuration, including any cover or facing, and at the maximum

thickness intended for use.

10.2.4.3.1.3* Cellular or foamed plastic materials tested in accordance with ANSI/UL 1040,

Standard for Fire Test of Insulated Wall Construction, or FM 4880, Approval Standard for Class I Fire Rating of Insulated Wall or Wall and Roof/Ceiling Panels, Interior Finish

Page 152 of 171

Page 153: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Materials or Coating, and Exterior Wall Systems, shall also be tested for smoke release

using NFPA 286, with the acceptance criterion of 10.2.3.2.

10.2.4.3.2 Cellular or foamed plastic shall be permitted for trim not in excess of 10 percent

of the specific wall or ceiling area to which it is applied, provided that it is not less than 20

lb/ft3 (320 kg/m3) in density, is limited to 1⁄2 in. (13 mm) in thickness and 4 in. (100 mm) in

width, and complies with the requirements for Class A or Class B interior wall and ceiling

finish as described in 10.2.3.3; however, the smoke developed index shall not be limited.

10.2.4.4* Textile wall coverings. Where used as interior wall finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall comply with the requirements of one of the following:

section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

10.2.4.4.1* Products tested in accordance with NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls, shall comply with the criteria of 10.2.4.4.2.

10.2.4.4.2* The interior finish shall comply with all of the following when tested using

method B of the test protocol of NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels and Walls:

(1) During the 40 kW exposure, flames shall not spread to the ceiling.

(2) The flame shall not spread to the outer extremities of the samples on the 8 ft. × 12 ft.

(2440 mm × 3660 mm) walls.

(3) Flashover, as described in NFPA 265, shall not occur.

(4) The total smoke released throughout the test shall not exceed 10,764 ft2 (1000 m2).

10.2.4.4.3 Textile materials meeting the requirements of Class A when tested in accordance

with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, using the specimen preparation and mounting method of ASTM E2404,

Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) Wall or Ceiling Coverings, and of Facings and Wood Veneers Intended to be Applied on Site Over a Wood Substrate, to Assess Surface Burning Characteristics, shall

be permitted as follows:

(1) On the walls of rooms or areas protected by an approved automatic sprinkler system.

(2) On partitions that do not exceed three-quarters of the floor-to-ceiling height or do not

exceed 8 ft. (2440 mm) in height, whichever is less.

(3) On the lower 48 in. (1220 mm) above the finished floor on ceiling-height walls and

ceiling-height partitions.

10.2.4.5 Expanded Vinyl Wall Coverings. Where used as interior wall finish materials,

expanded vinyl wall coverings shall be tested in the manner intended for use, using the

product mounting system, including adhesive, and shall comply with the requirements of

one of the following: section 10.2.3.1, section 10.2.4.4.1 or section 10.2.4.4.3.

Page 153 of 171

Page 154: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.6 Textile ceiling coverings. Where used as interior ceiling finish materials, textile

materials shall be tested in the manner intended for use, using the product mounting

system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.7 Expanded Vinyl ceiling coverings. Where used as interior ceiling finish materials,

expanded vinyl materials shall be tested in the manner intended for use, using the product

mounting system, including adhesive, and shall either:

(1) comply with the requirements of the requirements of section 10.2.3.1 or

(2) meet the requirements of Class A when tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, using the

specimen preparation and mounting method of ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics, and shall be permitted on the ceilings of rooms or areas protected by an

approved automatic sprinkler system.

10.2.4.8 Lockers.

10.2.4.8.1 Combustible Lockers. Where lockers constructed of combustible materials other

than wood are used, the lockers shall be considered interior finish and shall comply with

Section 10.2.3, except as permitted by 10.4.8.2.

10.2.4.8.2 Wood Lockers. Lockers constructed entirely of wood and of noncombustible

materials shall be permitted to be used in any location where interior finish materials are

required to meet a Class C classification in accordance with 10.2.3.

10.2.4.9 Polypropylene (PP) and High-Density Polyethylene (HDPE). Polypropylene and

high-density polyethylene materials shall not be permitted as interior wall or ceiling finish

unless the material complies with the requirements of 10.2.3.1. The tests shall be

performed on a finished assembly and on the maximum thickness intended for use.

10.2.4.10 Site-Fabricated Stretch Systems. For new installations, site-fabricated stretch

systems containing all three components described in the definition in Chapter 3 shall be

tested in the manner intended for use and shall comply with the requirements of 10.2.3.1 or

10.2.3.3. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2573, Standard Practice for Specimen Preparation and Mounting of Site-Fabricated Stretch Systems to Assess Surface Burning Characteristics.

Page 154 of 171

Page 155: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.4.11 Reflective Insulation Materials. Reflective insulation materials shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and

mounting shall be in accordance with ASTM E2599, Standard Practice for Specimen Preparation and Mounting of Reflective Insulation, Radiant Barrier, and Vinyl Stretch Ceiling Materials for Building Applications to Assess Surface Burning Characteristics.

10.2.4.12 Metal Ceiling and Wall Panels. Listed factory finished metal ceiling and wall

panels meeting the requirements of Class A in accordance with 10.2.3, shall be permitted to

be finished with one additional application of paint. Such painted panels shall be permitted

for use in areas where Class A interior finishes are required. The total paint thickness shall

not exceed 1⁄28 in. (0.9 mm).

10.2.4.13 Laminated products factory-produced with a wood substrate. Laminated products

factory-produced with a wood substrate shall be tested in the manner intended for use and

shall comply with the requirements of 10.2.3.1 or 10.2.3.3. If the materials are tested in

accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, specimen preparation and mounting shall be in accordance with

ASTM E2579, Standard Practice for Specimen Preparation and Mounting of Wood Products to Assess Surface Burning Characteristics, using the product-mounting system (including

adhesive) of actual use.

10.2.4.14 Facings or wood veneers intended to be applied on site over a wood substrate.

Facings or veneers intended to be applied on site over a wood substrate shall be tested in

the manner intended for use and shall comply with the requirements of 10.2.3.1 or 10.2.3.3.

If the materials are tested in accordance with NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth, they

shall use the product-mounting system, including adhesive, described in Section 5.8.9 of

NFPA 286. If the materials are tested in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723,

Standard for Test for Surface Burning Characteristics of Building Materials, specimen

preparation and mounting shall be in accordance with ASTM E2404, Standard Practice for Specimen Preparation and Mounting of Textile, Paper or Polymeric (Including Vinyl) and Wood Wall or Ceiling Coverings Facings and Veneers, to Assess Surface Burning Characteristics.

10.2.4.15* Light transmitting plastics. Light-transmitting plastics used as interior wall and

ceiling finish shall be permitted based on large-scale fire tests that substantiate the

combustibility characteristics of the plastics for the use intended under actual fire

conditions. The tests shall be performed on a light transmitting plastic assembly related to

the actual end-use configuration and on the maximum thickness intended for use. (See Section 48.7.)

10.2.5 Trim and Incidental Finish.

Page 155 of 171

Page 156: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.5.1 General. Interior wall and ceiling trim and incidental finish, other than wall base

in accordance with 10.2.5.2 and bulletin boards and posters in accordance with 10.2.5.3, not

in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it

is applied shall be permitted to be Class C materials in occupancies where interior wall and

ceiling finish of Class A or Class B is required.

10.2.5.2 Wall Base. Interior floor trim material used at the junction of the wall and the floor

to provide a functional or decorative border, and not exceeding 6 in. (150 mm) in height,

shall meet the requirements for interior wall finish for its location or the requirements for

Class II interior floor finish as described in 10.2.6.4 using the test described in 10.2.6.3. If a

Class I floor finish is required, the interior floor trim shall be Class I.

10.2.5.3 Bulletin Boards and Posters.

10.2.5.3.1 Bulletin boards and posters attached directly to the wall shall not exceed 20

percent of the aggregate wall area to which they are applied.

10.2.5.3.2 The provision of 10.2.5.3.1 shall not apply to artwork and teaching materials in

sprinklered educational or day-care occupancies in accordance with 17.5.5.3, 18.5.5 or

18.6.5.

10.2.6* Interior Floor Finish Testing and Classification.

10.2.6.1* Carpet and carpet like interior floor finishes shall comply with ASTM D2859,

Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials. 10.2.6.2* Floor coverings, other than carpet for which 10.2.2.2 establishes requirements for

fire performance, shall have a minimum critical radiant flux of 0.1 W/cm2.

10.2.6.3* Interior floor finishes shall be classified in accordance with 10.2.6.4, based on test

results from NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source, or ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source. 10.2.6.4 Interior floor finishes shall be grouped in the classes specified in 10.2.6.4.1 and

10.2.6.4.2 in accordance with the critical radiant flux requirements.

10.2.6.4.1 Class I Interior Floor Finish. Class I interior floor finish shall have a critical

radiant flux of not less than 0.45 W/cm2, as determined by the test described in 10.2.6.3.

10.2.6.4.2 Class II Interior Floor Finish. Class II interior floor finish shall have a critical

radiant flux of not less than 0.22 W/cm2, but less than 0.45 W/cm2, as determined by the

test described in 10.2.6.3.

10.2.6.5Wherever the use of Class II interior floor finish is required, Class I interior floor

finish shall be permitted.

10.2.7 Automatic Sprinklers.

Page 156 of 171

Page 157: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

10.2.7.1 Other than as required in 10.5, where an approved automatic sprinkler system is

installed in accordance with Section 55.3, Class C interior wall and ceiling finish materials

shall be permitted in any location where Class B is required, and Class B interior wall and

ceiling finish materials shall be permitted in any location where Class A is required.

10.2.7.2 Where an approved automatic sprinkler system is installed in accordance with

Section 55.3, throughout the fire compartment or smoke compartment containing the

interior floor finish, Class II interior floor finish shall be permitted in any location where

Class I interior floor finish is required, and where Class II is required, the provisions of

10.2.6.2 shall apply.

Page 157 of 171

Page 158: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 47-NFPA 5000-2015 [ Section No. A.3.3.134 ]

A.3.3.134 Critical Radiant Flux.

Critical radiant flux is the property determined by the test procedure of NFPA 253, Standard Methodof Test for Critical Radiant Flux of Floor Covering Systems Using a Radiant Heat Energy Source or of ASTM E648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems Usinga Radiant Heat Energy Source . The unit of measurement of critical radiant flux is watts per

square centimeter (W/cm2).

Statement of Problem and Substantiation for Public Input

This simply adds the alternate equivalent (ASTM) standard, which is referenced throughout NFPA 5000 each time that NFPA 253 is mentioned, with this as an exception.

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 04 14:19:11 EDT 2015

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 7/9/2015 9:46 AMPage 158 of 171

Page 159: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 65-NFPA 5000-2015 [ New Section after A.3.3.220.3 ]

A.3.3.220.4 Such partitions are intended to include washroom water closet partitions.

Statement of Problem and Substantiation for Public Input

This is the annex note moved from A.10.1.3 and referring to interior wall finish.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 64-NFPA 5000-2015 [Section No. 3.3.220.4]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 22 21:33:45 EDT 2015

Copyright Assignment

I, MARCELO HIRSCHLER, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and fullrights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). Iunderstand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in which thisPublic Input in this or another similar or derivative form is used. I hereby warrant that I am the author of this Public Input and that Ihave full power and authority to enter into this copyright assignment.

By checking this box I affirm that I am MARCELO HIRSCHLER, and I agree to be legally bound by the above CopyrightAssignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating anelectronic signature that will, upon my submission of this form, have the same legal force and effect as a handwritten signature

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/FormLaunch?id=/TerraView/C...

1 of 1 7/9/2015 9:47 AMPage 159 of 171

Page 160: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 60-NFPA 5000-2015 [ Section No. A.10.1.3 ]

A.10.1.3

Such partitions are intended to include washroom water closet partitions.

Statement of Problem and Substantiation for Public Input

This reference is misapplied - it should refer to the definition of interior finish in chapter 3.

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 22 20:58:31 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

412 of 479 7/7/2015 12:51 PMPage 160 of 171

Page 161: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 61-NFPA 5000-2015 [ Section No. A.10.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

413 of 479 7/7/2015 12:51 PMPage 161 of 171

Page 162: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

A.10.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

414 of 479 7/7/2015 12:51 PMPage 162 of 171

Page 163: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

The requirements pertaining to interior finish are intended to restrict the spread of fire over thecontinuous surface forming the interior portions of a building.

Table A.10.2 shows the fire test methods and classification criteria that apply to differentinterior finish materials.

Table A.10.2 Fire Testing of Interior Finish Materials

Material Test Method Acceptance Criterion Application Requirement Paragraph Interior wall andceiling finish materials, except as shown below in this table Textile wall coverings ASTM E84 or UL 723 Class A, in accordance with 10.3.2.1 As required by relevantsections 10.3.1 ASTM E 84 or UL 723 Class B, in accordance with 10.3.2.2 As required byrelevant sections 10.3.1 ASTM E 84 or UL 723 Class C, in accordance with 10.3.2.3 Asrequired by relevant sections 10.3.1 NFPA 286 In accordance with 10.3.6.2 Permitted whereClass A, Class B, or Class C is required by relevant sections 10.3.1.2 Materials having a

thickness less than 1 ⁄ 28 in. (0.9 mm) applied directly to a noncombustible or limitedcombustible surface of walls or ceilings No testing required 10.1.2 Exposed portions ofstructural members complying with the requirements for buildings of Type IV (2HH)construction, in accordance with 7.2.5 No testing required 10.3.1.1 Cellular or foamedplastics (exposed foamed plastics and foamed plastics used in conjunction with a textile or vinylfacing or cover) NFPA 286 In accordance with 10.3.6.2 Permitted where Class A, Class B,or Class C is required by relevant sections 10.4.3.1, Section 48.5 FM 4880 Pass Permittedwhere Class A, Class B, or Class C is required by relevant sections 10.4.3.1, Section 48.5 UL1040 Pass Permitted where Class A, Class B, or Class C is required by relevantsections 10.4.3.1, Section 48.5 UL 1715 Pass Permitted where Class A, Class B, or Class C isrequired by relevant sections 10.4.3.1, Section 48.5 A suitable large-scale fire test thatsubstantiates their combustibility characteristics for the use intended under actual fireconditions Pass Permitted where Class A, Class B, or Class C is required by relevantsections 10.4.3.1, Section 48.5 NFPA 286 In accordance with 10.3.6.2 Permitted where ClassA, Class B, or Class C is required by relevant sections 10.3.1.2 Method B In accordance with10.3.6.1 Permitted on walls and partitions 10.4.1(4) ASTM E 84 or UL 723 Class A, inaccordance with 10.3.2.1 Permitted on walls, but also requires sprinklers per Section55.3 10.4.1(1) ASTM E 84 or UL 723 Class A, in accordance with 10.3.2.1 Permitted onpartitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft(2440 mm) in height, whichever is less 10.4.1(2) ASTM E 84 or UL 723 Class A, in accordancewith 10.3.2.1 Permitted to extend not more than 48 in. (1220 mm) above the finished floor onceiling-height walls and ceiling-height partitions 10.4.1(3) NFPA 286 In accordance with10.3.6.2 Permitted where Class A, Class B, or Class C is required by relevantsections 10.4.2(5) NFPA 265, Method B In accordance with 10.3.6.1 Permitted on walls andpartitions 10.4.2(4) ASTM E 84 or UL 723 Class A, in accordance with 10.3.2.1 Permitted onwalls, but also requires sprinklers per Section 55.3 10.4.2(1) ASTM E 84 or UL 723 Class A, inaccordance with 10.3.2.1 Permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less 10.4.2(2) ASTME 84 or UL 723 Class A, in accordance with 10.3.2.1 Permitted to extend not more than 48 in.(1220 mm) above the finished floor on ceiling-height walls and ceiling-heightpartitions 10.4.2(3) Textile ceiling coverings NFPA 286 In accordance with10.3.6.2 Permitted where Class A, Class B, or Class C is required by relevantsections 10.3.1.2 ASTM E 84 or UL 723 Class A, in accordance with 10.3.2.1 Permitted onwalls, but also requires sprinklers per Section 55.3 10.4.1(1) Expanded vinyl ceilingcoverings NFPA 286 In accordance with 10.3.6.2 Permitted where Class A, Class B, orClass C is required by relevant sections 10.4.2(5) ASTM E 84 or UL 723 Class A, inaccordance with 10.3.2.1 Permitted on walls, but also requires sprinklers per Section55.3 10.4.2(1) Interior trim, other than foamed plastic and other than wall base ASTM E84 or UL 723 Class C, in accordance with 10.3.2.3 Interior wall and ceiling trim and incidentalfinish, other than wall base not in excess of 10 percent of the specific wall and ceiling areas ofany room or space to which it is applied in occupancies where interior wall and ceiling finish ofClass A or Class B is required 10.5.1 NFPA 286 In accordance with 10.3.6.2 Permitted where

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

415 of 479 7/7/2015 12:51 PMPage 163 of 171

Page 164: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Class A, Class B, or Class C is required by relevant sections 10.3.1.2 Foamed plastic used asinterior trim ASTM E 84 or UL 723 Flame spread index =75 (1) Minimum density of

interior trim required to be 20 lb/ft 3 (320 kg/m 3 ) 10.5.1, 48.5.3 (2) Maximum thickness ofinterior trim required to be 0.5 in. (13 mm), and maximum width permitted to be 8 in. (205mm) 10.5.1, 48.5.3 (3) Interior trim not permitted to constitute more than 10 percent ofspecific wall or ceiling area of a room or space to which it is applied. 10.5.1, 48.5.3 NFPA286 In accordance with 10.3.6.2 Permitted where Class A, Class B, or Class C is required byrelevant sections 10.3.1.2 Carpet and carpetlike interior floor finishes ASTM D2859 Pass All areas 10.6.1 Floor coverings, other than carpet, that are judged to represent anunusual hazard (excluding traditional finish floors and floor coverings, such as wood flooring

and resilient floor coverings) NFPA 253 or ASTM E 648 CFR ≥ 0.1 W/cm 2 Allareas 10.6.2 Interior floor finish, other than carpet and carpetlike materials NFPA 253 or

ASTM E 648 Class I: CFR ≥ 0.45 W/cm 2 , in accordance with 10.6.4.1 As required by relevant

sections 10.6.3 NFPA 253 or ASTM E 648 Class II: CFR ≥ 0.22 W/cm 2 , in accordance with10.6.4.2 As required by relevant sections 10.6.3 Wall base [interior floor trim material used atthe junction of the wall and the floor to provide a functional or decorative border, and notexceeding 6 in. (150 mm) in height] NFPA 253 or ASTM E 648 Class I: CFR ≥ 0.45

W/cm 2 , in accordance with 10.6.4.1 All areas 10.5.2 NFPA 253 or ASTM E 648 Class II: CFR

≥ 0.22 W/cm 2 , in accordance with 10.6.4.2 If interior floor finish is required to meet Class ICFR 10.5.2 Floor finish of traditional type, such as wood flooring and resilient floorcoverings No testing required Section 10.6

The default requirements are based on fire testing to NFPA 286 (with the criteria of 10.2.3.2),which apply to all interior finish materials. Many interior finish materials are permitted to betested based on other fire tests (namely, based either on ASTM E84 or UL 723 or on NFPA265), as shown in the relevant sections.

Table A.10.2 shows the fire test methods and classification criteria that apply to differentinterior wall and ceiling finish materials.

Table A.10.2 Fire Testing of Interior Wall and Ceiling Finish Materials

(Replace the table by the attached table)

Additional Proposed Changes

File Name Description Approved

5000_A10.2_including_table_proposed_for_2018.docxRevised section A10.2 including revised table

Statement of Problem and Substantiation for Public Input

The table contains multiple errors that have been revised. The proposed new table is consistent with the proposed new text for 10.2. The sections of the table dealing with interior floor finish are being deleted because they are unnecessary as the text in the body is clear enough.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 53-NFPA 5000-2015 [Section No. 10.2]

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

416 of 479 7/7/2015 12:51 PMPage 164 of 171

Page 165: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 22 21:01:19 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

417 of 479 7/7/2015 12:51 PMPage 165 of 171

Page 166: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

A.10.2 The requirements pertaining to interior finish are intended to restrict the spread of fire over the continuous surface forming the interior portions of a building. The default requirements are based on fire testing to NFPA 286 (with the criteria of 10.2.3.2), which apply to all interior finish materials. Many interior finish materials are permitted to be tested based on other fire tests (namely, based either on ASTM E84 or UL 723 or on NFPA 265), as shown in the relevant sections. Table A.10.2 shows the fire test methods and classification criteria that apply to different interior wall and ceiling finish materials.

Table A.10.2 Fire Testing of Interior Wall and Ceiling Finish Materials

Material Test

Method Acceptance

Criterion Application Requirement Paragraph

Base Requirement

All interior wall and ceiling finish materials

NFPA 286

In accordance with 10.2.3.2

Permitted anywhere, including where Class A, Class B or Class C in accordance with ASTM E84 or UL 723 is required by relevant sections

10.2.3.1

Alternate requirements for some interior wall and ceiling finish materials

Materials having a thickness less than 1⁄28 in. (0.9 mm) applied directly to a noncombustible or limited combustible surface of walls or ceilings

No testing required

10.2.4.1

Exposed portions of structural members complying with the requirements for buildings of Type IV (2HH) construction, in accordance with 7.2.5

No testing required

10.2.4.2

Cellular or foamed plastics (exposed foamed plastics and foamed plastics used in conjunction with a textile or vinyl facing or cover)

NFPA 286

In accordance with 10.2.3.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1, Section 48.5

FM 4880 Pass Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1, Section 48.5

UL 1040 Pass Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1, Section 48.5

UL 1715 Pass Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.3.1, Section 48.5

Page 166 of 171

Page 167: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Material Test

Method Acceptance

Criterion Application Requirement Paragraph

Textile wall coverings ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on walls, but also requires sprinklers per Section 55.3. As required by relevant sections. Tested using specimen preparation and mounting per ASTM E2404

10.2.4.4

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less. Tested using specimen preparation and mounting per ASTM E2404

10.2.4.4

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted to extend not more than 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions. Tested using specimen preparation and mounting per ASTM E2404

10.2.4.4

NFPA 265 Method B

In accordance with 10.2.4.4.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.4.2

Expanded vinyl wall coverings

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on walls, but also requires sprinklers per Section 55.3. As required by relevant sections Tested using specimen preparation and mounting per ASTM E2404

10.2.4.5

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on partitions that do not exceed three-quarters of the floor-to-ceiling height or do not exceed 8 ft (2440 mm) in height, whichever is less Tested using specimen preparation and mounting per ASTM E2404

10.2.4.5

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted to extend not more than 48 in. (1220 mm) above the finished floor on ceiling-height walls and ceiling-height partitions Tested using specimen preparation and mounting per ASTM E2404

10.2.4.5

NFPA 265 Method B

In accordance with 10.2.4.4.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.5

Page 167 of 171

Page 168: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Material Test

Method Acceptance

Criterion Application Requirement Paragraph

Textile ceiling coverings ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on ceilings, but also requires sprinklers per Section 55.3 Tested using specimen preparation and mounting per ASTM E2404

10.2.4.6

Expanded vinyl ceiling coverings

ASTM E84 or UL 723

Class A, in accordance with 10.3.2.3

Permitted on ceilings, but also requires sprinklers per Section 55.3 Tested using specimen preparation and mounting per ASTM E2404

10.4.2.7

Interior trim, other than foamed plastic and other than wall base

ASTM E84 or UL 723

Class C, in accordance with 10.3.2.3

Interior wall and ceiling trim and incidental finish, other than wall base not in excess of 10 percent of the specific wall and ceiling areas of any room or space to which it is applied in occupancies where interior wall and ceiling finish of Class A or Class B is required

10.2.5.1

Foamed plastic used as interior trim

ASTM E84 or UL 723

Flame spread index not exceeding75

(1) Minimum density of interior trim required to be 20 lb/ft3 (320 kg/m3)

10.2.4.3.2, 48.5.3

(2) Maximum thickness of interior trim required to be 0.5 in. (13 mm), and maximum width permitted to be 8 in. (205 mm)

10.2.4.3.2, 48.5.3

(3) Interior trim not permitted to constitute more than 10 percent of specific wall or ceiling area of a room or space to which it is applied.

10.2.4.3.2 48.5.3

Wall base

Tested as interior floor finish

Shall not exceed 6 in. (150 mm) in height

10.2.5.2

Lockers Tested as interior finish

10.2.4.8

Wood lockers ASTM E84 or UL 723

Class C, in accordance with 10.3.2.3

No testing required 10.2.4.8.2

Polypropylene and High density polyethylene

NFPA 286

In accordance with 10.2.3.2

Permitted where Class A, Class B, or Class C is required by relevant sections

10.2.4.9

Site-Fabricated Stretch Systems

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2573

10.2.4.10

Page 168 of 171

Page 169: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Material Test

Method Acceptance

Criterion Application Requirement Paragraph

Reflective Insulation Materials

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2599

10.2.4.11

Metal Ceiling and Wall Panels

10.2.4.12

Laminated products factory-produced with a wood substrate

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2579

10.2.4.13

Facings or wood veneers intended to be applied on site over a wood substrate

ASTM E84 or UL 723

Tested using specimen preparation and mounting per ASTM E2404

10.2.4.14

Light transmitting plastics 10.2.4.15

Fire retardant coatings Not permitted for compliance 10.2.3.6

Factory-applied fire retardant coated products listed and labeled for the application

ASTM E2768

Pass 10.2.3.7

Page 169 of 171

Page 170: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 62-NFPA 5000-2015 [ Section No. A.10.4.5 ]

A.10.4.5

The methodology specified in NFPA 265, Standard Methods of Fire Tests for Evaluating RoomFire Growth Contribution of Textile or Expanded Vinyl Wall Coverings on Full Height Panels andWalls, includes provisions for measuring smoke obscuration. Such measurement is considereddesirable, but the basis for specific recommended values is not currently available. [SeeA.10.5.1 (4)(4).]

Statement of Problem and Substantiation for Public Input

The sentence struck out refers to older editions of NFPA 265 and older editions of the code, which were not clear about smoke measurements. The reference struck out was to an Annex section that no longer exists .

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 22 21:19:03 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

418 of 479 7/7/2015 12:51 PMPage 170 of 171

Page 171: AGENDA NFPA Technical Committee on Interior Finish and … · 2016-03-28 · NFPA Technical Committee on Interior Finish and Contents NFPA 101 and NFPA 5000 Second Draft Meeting MINUTES

Public Input No. 63-NFPA 5000-2015 [ Section No. A.10.4.5.1 ]

A.10.4.5.1

See A.10.4.5 and A . 10.5.1 (4).

Statement of Problem and Substantiation for Public Input

The referenced Annex section does not exist.

Submitter Information Verification

Submitter Full Name: MARCELO HIRSCHLER

Organization: GBH INTERNATIONAL

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 22 21:24:42 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

419 of 479 7/7/2015 12:51 PMPage 171 of 171