AE Guide PC57.127-D10.0 12-29-06

Embed Size (px)

Citation preview

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    1/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved.

    This is an unapproved IEEE Standards Draft, subject to change. 1

    Draft Guide for the Detection and Location ofAcoustic Emissions from Partial Discharges in Oil-Immersed Power Transformers and Reactors

    Sponsored by the

    Transformers Committee

    of the

    IEEE Power Engineering Society

    Copyright 2006 by the Institute of Electrical and Electronics Engineers, Inc.

    Three Park Avenue

    New York, New York 10016-5997, USA

    All rights reserved.

    This document is an unapproved draft of a proposed IEEE Standard. As such, this document is subject to change.

    USE AT YOUR OWN RISK! Because this is an unapproved draft, this document must not be utilized for any

    conformance/compliance purposes. Permission is hereby granted for IEEE Standards Committee participants to

    reproduce this document for purposes of IEEE standardization activities only. Prior to submitting this document to

    another standards development organization for standardization activities, permission must first be obtained from

    the Manager, Standards Licensing and Contracts, IEEE Standards Activities Department. Other entities seeking

    permission to reproduce this document, in whole or in part, must obtain permission from the Manager, StandardsLicensing and Contracts, IEEE Standards Activities Department.

    IEEE Standards Activities Department

    Standards Licensing and Contracts

    445 Hoes Lane, P.O. Box 1331

    Piscataway, NJ 08855-1331, USA

    Abstract: This guide is applicable to the detection and location of acoustic emissions from partial discharges and

    other sources in oil immersed power transformers and reactors. It is intended to provide a means of associating the

    relative magnitude and position of partial discharges and other sources with the acoustic signals obtained by

    strategically located transducers.

    Keywords:acoustic emission (AE), attenuation, burst, gas-in-oil analysis, low-amplitude discharges, partial

    discharge (PD), power transformers, reactors.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    2/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    2

    Introduction

    This introduction is not part of IEEE xxxxxx, Guide for the Detection and Location of Acoustic Emissions from

    Partial Discharges in Oil - Immersed Power Transformers and Reactors. The Guide is an expansion of PC57.127

    Trial Use Guide for the Detection of Acoustic Emissions from Partial Discharges in Oil-Immersed Power

    Transformers. It has been expanded to include more theory and signal interpretation information, newer techniques

    for detection and the concepts for location. Active workers in the field are constantly trying to improve their

    methods. More effective methods may appear in the future.

    Participants

    At the time this guide was completed, the Working Group on Acoustic Partial Discharge Tests in Transformers had

    the following membership:

    John W. Harley, Chair

    Donald Ayers

    Ron Barker

    Ray Bartnikas

    Barry BeasterJeff Benach

    Tord Bengtsson

    Paul Boman

    John Bosiger

    Carl Bush

    Alvaro Cancino

    William Carter

    Yunxiang Chen

    Bill Chiu

    Roy Colquitt

    Jerry Corkran

    John Crouse

    Alan Darwin

    Ron Daubert

    Fred Elliott

    Don Fallon

    Norman Field

    Michael Franchek

    Jim Fyvie

    Robert Ganser

    Andreas Garnitschnig

    Richard Graham

    William GriesackerSergio Guerrero

    Ernst Hanique

    Tom Harbaugh

    Peter Heinzig

    Keith Highton

    Thang Hochanh

    John Holland

    Anthony Jonatti

    Steve Jordan

    Samer Khaled

    Vladimir Khalin

    Emil Kowal

    John Lackey

    Robert Langan

    Mike Lau

    Eberhard Lemke

    Raymond Lortie

    Richard Lowe

    Andre Lux

    Tamyres Luiz Machado

    Jim McIver

    Martin Navarro

    Van Nhi NguyenArturo Nunez

    Mark Perkins

    Paul Pillitteri

    Bertrand Poulin

    Gustav Preininger

    George Reitter

    John Runski

    Dirk Russwurm

    Ewald Schweiger

    Hemchandra Shertukde

    James Smith

    Brian Sparling

    Charles Sweetser

    Ed Tenyenhuis

    Subhash Tuli

    Albert Walls

    Barry Ward

    Eduardo Garcia Wild

    Others who were active in the writing of this guide are:

    Pierre Boss

    Ed Cromer

    Michel Duval

    George Forrest

    Valery Godinez

    David Goodwin

    Lars-Erik Juhlin

    Stanley Lindgren

    Adrian Pollock

    Karen Weissman

    The following persons were on the balloting committee:

    (To be supplied by IEEE Standards Project Editor at time of publication)

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    3/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    3

    Patents

    Attention is called to the possibility that implementation of this standard may require use of subject matter covered

    by patent rights. By publication of this standard, no position is taken with respect to the existence or validity of any

    patent rights in connection therewith. The IEEE shall not be responsible for identifying patents or patent applications

    for which a license may be required to implement an IEEE standard or for conducting inquiries into the legal

    validity or scope of those patents that are brought to its attention. A patent holder or patent applicant has filed a

    statement of assurance that it will grant licenses under these rights without compensation or under reasonable rates

    and nondiscriminatory, reasonable terms and conditions to applicants desiring to obtain such licenses. The IEEE

    makes no representation as to the reasonableness of rates, terms, and conditions of the license agreements offered by

    patent holders or patent applicants. Further information may be obtained from the IEEE Standards Department.

    A Patent Letter of Assurance has been filed with the IEEE by the patent holder of the material presented in Clause

    6.7 Three sensor system.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    4/50

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    5/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    5

    10. Characterization of AE signals

    10.1 Introduction .

    10.2 General alternating current systems.

    10.3 Acoustic systems that record single events

    10.4 DSP workstations that record data over extended periods ...10.5 On-line (continuous) acoustic PD systems ......

    10.6 HVDC transformers and reactors ..

    10.7 Characteristics of PD from static electrification ....

    10.8 Acoustic activity from thermal faults, the core, mechanical noises and

    other sources...........................................................................................

    10.9 Comparison between electrical and acoustic signals

    25

    25

    25

    26

    2929

    30

    30

    31

    31

    11.

    12.

    Integrating AE results with data from oil analysis ..

    Acoustic activity interpretation ..

    33

    33

    Annex A (informative) Bibliography 35

    Annex B (informative) Signal processing . 39

    Annex C

    Annex D

    (informative) Wavelet signal processing theory

    (informative) Tutorial: detection and location of AE from PD

    40

    43

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    6/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    6

    IEEE Guide for the Detection and Location ofAcoustic Emissions from Partial Discharges inOil-Immersed Power Transformers and Reactors

    1. Overview

    1.1 Scope

    This guide is applicable to the detection and location of acoustic emissions from partial discharges and other sources

    in oil immersed power transformers and reactors. Both electrical sources (partial discharge) and mechanical sources

    (such as loose clamping, bolts or insulation parts) generate these emissions. There are descriptions of acoustic

    instrumentation, test procedures, and interpretation of results. When this guide is used with oil-immersed reactors, it

    must be understood that interpretation of signals may be different because of the construction of the reactor.

    Accuracy of location depends on the type of fault, configuration of tank, type of instrumentation and experience.

    1.2 Purpose

    This guide is intended to provide information that may be helpful in planning, installing and operating acoustic

    monitoring equipment and in meaningful interpretation of resulting data. Users are intended to be persons

    knowledgeable in this field such as utility engineers, consultants, academics and manufacturers.

    1.3 Safety warnings

    The safety warnings in this subclause apply only to work done on transformers installed in the field, not to factory

    testing. Refer to factory test codes for safety warnings for these situations.

    Partial discharge (PD) location should only be attempted by those technicians and engineers trained in working on

    high-voltage transformers and knowledgeable of the risks associated with this work.

    WARNINGS

    1. The transformer tank must be connected to a low resistance ground to limit the extremely highvoltages being induced into the ground circuit and the tank if a high voltage to ground failureoccurs. The personnel risk is very high if the transformer fails to ground. Even when grounded

    properly, the voltage on the tank to a different ground source may be LETHAL at the instant the

    failure occurs.

    2. If the transformer is being energized or de-energized, or there is another type of power systemvoltage, all personnel should maintain a reasonable distance from the transformer and

    equipment electrically connected to the tank due to the possibility of a failure. It is recommended

    that acoustic measurement equipment connected to the tank be electrically isolated from thetransformer tank, e.g., by optical means or by high-voltage electrical insulation, when measuring

    during transient events to eliminate the danger to the equipment or operators.

    3. It is preferable to make all connections to the tank with the transformer de-energized, but in no caseshould the transformer voltage be above normal voltage while the sonic measuring devices areinstalled. Personnel must not access areas where high voltages are within minimum approach

    distance, such as on top of energized transformers or in bushing compartments.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    7/50

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    8/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    8

    3. Detection and measurement of PD background information

    Since PD cannot be measured directly, its energy by-products such as electrical transients, chemical changes,

    electromagnetic emissions, vibration, sound, light, and heat must be measured. Each of these energy by-products,

    when measured, has advantages and disadvantages for identifying PD. The measurement methods are as follows:

    a) Radio frequency (RF) - VHF: the VHF measurement of radio waves is in the frequency range of 30 MHz -300 MHz. This VHF measurement is usually associated with aerial antennas, but not exclusively. Some

    window type receiver devices may also monitor the VHF range. The signal attenuation and noise reduction

    are similar but less compared to the UHF frequency.

    b) Radio frequency (RF) - UHF: the UHF measurement of radio waves is in the frequency range of 300 MHz -3 GHz. These measurements are often performed using a window style UHF receiver. UHF tests are less

    affected by external noise. The Corona type of PD emits only up to a frequency of approximately 300MHz.

    Signals are strongly attenuated when they pass through the bushings or travel longer distances within the

    oil. Cell phone and TV stations operate in the UHF band and might introduce strong noise. Discharges

    directly in the oil have an upper frequency limit of only a few hundred Kilohertz and can not be detected.

    c) RF current transformers (RFCT): RFCTs are designed to measure up to several tens or hundred MHz. Theycan be placed on ground returns and/or bushing taps. The RFCT by itself is generally considered non-

    intrusive; however, the RFCT may require an outage to be installed. It can be used both for off-line and on-

    line measurement states.

    d) Coupling capacitor (CC): the CC sensor interfaces directly with the voltage terminal. This is the methoddescribed in IEC 60270 [B36]. This is a common factory test method. Results are measured in pC. This

    measurement works well under a controlled noise-free environment, but may not work well in a field

    environment.

    For field measurements, this method can utilize either a user-supplied capacitor or the leakage current from

    a bushing tap, using the condenser layered bushing as the coupling capacitor. When the user supplies an

    external reference capacitor for on-line measurements, the measurement is considered intrusive. However,

    when a coupling capacitor is used, there is generally no limitation put on the frequency measurement range.

    e) Acoustic emission (AE): consists of one or more ultrasonic transducers that are sensitive to the AE

    generated by a PD source. Acoustic sound sources are wide-banded (> 1MHz). Due to the propagationcharacteristics of the insulation medium and apparatus structure, ultrasonic AE is measured in the 20 kHz

    to 500 kHz frequency range.

    f) Ultra violet light (UV): detects UV light generated by corona, external PD on surfaces, and arcing. Thismethod generally detects external events within line of sight. With the help of daylight blocking filter and

    very sensitive cameras, UV measurements can be obtained in direct sunlight.

    g) Dissolved gas analysis (DGA): In the case of PD in voids or gas bubbles, the main gas formed is hydrogentogether with significant amounts of methane (typically 10%) and minor amounts of the other gases.

    Variable amounts of the carbon oxides may also result from partial discharges in cellulose, although

    usually in lower quantities than the other gases. [B17, B18].

    In the case of discharges of the sparking-type in oil or in paper, significant amounts of all the hydrocarbons(including acetylene) are formed in addition to hydrogen.

    h) Power factor tip-up: PD produces a power loss, which is a function of applied voltage. If PD is present,losses increase and the power factor changes with applied voltage. The power factor difference between

    applied voltage levels is known as "tip-up".

    This guide focuses on the detection and location of PD using AE techniques. These techniques are sometimes

    combined with one or more of the above PD detection and measurement methods.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    9/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    9

    4. Introduction to acoustic PD systems

    PD detection and location work is carried out in the factory and in the field, the latter being done with the

    transformer either connected to the grid or supplied by a separate power source.

    Acoustic PD systems are most often used when PD has been identified as a result of other diagnostic procedures,

    such as dissolved gas analysis and electrical PD measurement.

    There are two general categories of acoustic location systems: all-acoustic systems and acoustic systems with an

    electrical PD trigger. In addition, on-line (continuous) acoustic monitoring systems are being used primarily to

    detect and trend emissions. Typical implementations of each of these types of systems are given below along with

    the respective advantages and limitations.

    4.1 The all-acoustic system

    The first category, the all-acoustic system, consists of one or more ultrasonic transducers that are sensitive to the AE

    generated by a PD event. The detection and coarse location of one or more sources can be accomplished by moving

    one or more externally mounted sensors to different locations on the transformer tank. A more precise location of a

    PD source may be determined by the relative arrival times of the acoustic signals at each of the sensors. No voltage

    or current readings are required on the transformer. This makes the all-acoustic system a suitable tool for source

    location on operating transformers in the field.

    The acoustic transducers can be mounted on the exterior of the transformer tank to detect the acoustic signal as it

    hits the tank wall, or inside the transformer to detect the signal in the oil.

    Benefits of the externally mounted sensors include the ability to reconfigure the sensors as necessary to obtain a

    clearer acoustic signal, the flexibility to move the system to another transformer, and the ease of retrofitting existing

    transformers. The disadvantage of the external configuration is that it is more sensitive to external noise sources.

    Benefits of the internally mounted sensors may include a clearer, louder measurement with a better signal-to-noise

    ratio. Disadvantages are that installation of the sensors is invasive to the transformer and, once installed, the sensors

    can not be moved around to achieve a clearer line of sight to the source, nor can they be easily removed and installed

    on another transformer.

    4.2 The acoustic system with an electrical PD trigger

    The second category, the acoustic system with an electrical PD trigger, pairs the array of acoustic sensors described

    above with a current or voltage measurement device that detects the PD signal electrically. The electric signal is

    usually considered as detected instantaneously. When using this assumption, the arrival time of the electric signal is

    used as time zero for the PD event. The difference in arrival times of the electric signal and an acoustic signal is the

    propagation time between the PD source and that sensor location. PD location is based on the absolute arrival time

    at each sensor, as opposed to the all-acoustic system described above which uses the difference in arrival time

    between sensors.

    The assumption of instantaneous detection of the electric signal is correct when it appears e.g. at the bushing tap of

    the transformer. At the most this delay is in the range of a few microseconds and therefore can be neglected.However, an acoustic system with an electrical PD trigger is processing the electrical signal first. Here the

    processing time may be taken into account in order to decrease location error. Table 1 shows the time lags due to the

    analog processing time measured in three different electrical PD detector types.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    10/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    10

    Table 1 - Time lag in electrical PD detectors

    Type of detector Time-lag to t0 Signal rise time

    (10-90%)

    Approximate location

    error in oil

    Wide-band with active

    Integrator (100-400 kHz)

    0.2 s 1.2 s Negligible (< 2 mm)

    Narrow-band at 1 MHz

    With 9 kHz bandwidth

    16 s 35 s 22 mm-70 mm (1 in. ~3 in.)

    Narrow-band at 1 MHzWith 4.5 kHz bandwidth

    16 s 50 s 22 mm-95 mm (1 in. ~4 in.)

    The numbers are provided only as an example. Other detectors from different manufacturers may have different time

    lags since this property is not specified in the standards. It can be seen that a narrow-band detector may introduce a

    time lag that may be taken into account if very accurate location measurements are desired.

    One advantage of the combined system is that the electrical measurement provides confirmation that the acoustic

    sensors are locating a PD event as opposed to another acoustic noise source. Furthermore, the electrical signal is a

    convenient trigger that can be used to start the data acquisition at the acoustic sensors.

    The major disadvantage of the combined system is that it may be difficult to obtain a clean electric PD measurement

    due to electrical noise in the field. Hence, the combined acoustic-electrical PD locator system is more suitable for

    use in the factory or plant than in the field.

    4.3 The on-line (continuous) acoustic monitoring system

    The main purpose of permanently installed on-line acoustic monitoring systems is to provide an early indication of

    an incipient fault to a remote location. These systems usually consist of multiple sensors, amplifier and data

    acquisition/processing modules. The sensors are placed at locations where faults may be anticipated based on past

    experience or highest probability of problems occurrence. The data acquisition/processing systems are able to

    transmit collected data and/or warning alerts to locations outside the substation.

    The data is often limited to activity levels rather than specific waveforms. Location information is often limited to

    knowledge of which sensor is most active.

    Some continuous monitoring systems use the signal from a split CT around the transformer case ground or an RFsignal from a sensor inside the transformer to identify the AE signal as an internal PD.

    Warning alerts caused by level of activity above a baseline or trend of activity are usually reason to take gas samples

    and perhaps perform more extensive acoustic or other testing.

    5. Acoustic signal and transmission characteristics

    5.1 Acoustic signal

    The energy creating the acoustic signal is from PD and mechanical and thermal sources inside and outside

    transformers and reactors.

    Figure 1a shows a waveform from an acoustic sensor mounted on the outside of a transformer tank. It is typical of

    one burst of PD. The sharp rise of the wave front indicates that a direct wave has impinged on the inside tank wall

    within the critical angle for a pressure wave.

    The horizontal axis shows time in microseconds. The burst had a length of 144 microseconds from the first threshold

    crossing to the last threshold crossing. The vertical axis is a dimensionless indication of amplitude. The number of

    acoustic bursts in a unit of time, usually one second, is a measure of acoustic activity.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    11/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    11

    Figure 1a - Typical acoustic emission burst

    Figure 1b is a detail of the waveform in Figure 1a. There are 16 oscillations (also called counts) at or above the

    indicated threshold of 100. The oscillations are shown below.

    Oscillations: 1 2 3 4 5 6789-10 11-12-13-14 15-16

    Figure 1b Oscillations in an acoustic emission burst

    AE detection systems may count bursts and/or oscillations.

    In order to count bursts, the oscillatory portion of the decaying burst must be removed by means of a demodulation

    circuit. This ensures that each emitted burst is recorded as a single discrete event. The bursts can then be recorded at

    a preset magnitude level over a one second time period. Also, a distribution of all the discrete AE burst magnitudes

    can be obtained by means of a pulse height analyzer, again over a one second time period. If the PD pulses occur

    faster than the ring-down time of the acoustic transducer or the time window used for pulse qualification in some

    automated systems, errors in burst rate count and burst height distribution will occur.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    12/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    12

    5.2 Acoustic signal propagation from source to tank wall

    Active PD sources in oil-filled transformers produce AE signals that propagate away from the source in all

    directions. The acoustic signals travel through the intervening material to eventually arrive at the transformer tank

    wall. The distance traveled in a particular medium is dependent on the time that it takes for an acoustic signal to

    complete this journey as shown in the equation below:

    distance traveled = acoustic wave speed x travel time

    Consequently, sensors placed at different locations on the tank wall, i.e. at different distances from the source, will

    experience different signal arrival times. For the case of the all-acoustic system, it is possible to detect the

    difference in signal arrival time at one sensor relative to another. This in turn allows for the estimation of the

    difference in the two propagation path distances. For the case of the combined acoustic-electric system, the time

    delay between the source and the sensor can be detected, and the absolute path length between the source and a

    given sensor can be determined. Each of these system types requires a slightly different procedure to locate the

    source, as described in the sections on Operating Procedures, Clauses 8 and 9.

    Acoustic PD source location commonly assumes that the acoustic signal travels a direct, straight-line route from the

    source to the sensor. Unfortunately, this is not always the case as the acoustic field inside the tank is very complex

    due to wave reflection, diffraction in different materials and other parameters. For example, if there is an

    obstruction blocking the line of sight between the source and the sensor location, the sound may travel around the

    obstruction. This results in a longer propagation time that would imply a greater distance between the source and

    the sensor than actually exists. Alternately, the sound may travel directly through the obstruction at a wave speed

    that is greater than in the oil. The resulting arrival time would be earlier, which would imply a shorter distance

    between the source and the sensor than actually exists. To help avoid these misinterpretations, it is important to

    confirm the estimated source location by repeating the distance calculations with several sensor locations.

    5.3 Acoustic signal propagation within the tank wall

    The propagation of the acoustic waves within the transformer wall is complex. However, using experimental

    evidence based on acoustic signals about 100 kHz and wall thickness about 10 mm, wave propagation velocity can

    be assigned a constant value and wave types can be regarded as similar to compression and shear waves. This

    empirical approach is used in this document.

    Structure-borne propagation paths within the tank wall present a further technical challenge. As the acoustic wavehits the tank wall, its frequency characteristics remain the same, but its mode of propagation and propagation speed

    change. In the example in Figure 2, the sensor is located on the far side of the tank, away from the source.

    Figure 2 - Illustration of typical propagation paths for the acoustic PD signal.

    Primary reflection wave propagation can take place within the confines of the tank as shown. The speed of sound for

    this wave depends on the media encountered by the sound wave.

    Acoustic

    sensor

    PD Source

    Transformer

    tank

    Direct acoustic path

    Structure-bornepath

    Primary

    reflection wave

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    13/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    13

    Acoustic waves hitting the nearby tank wall will create an alternate propagation path via the tank wall to the sensor

    on the other side. The wave speed in metal is greater than in oil. Therefore the wave traveling this structure-borne

    path may arrive at the sensor earlier than the wave traveling the direct acoustic path. If the distance calculations were

    based on the arrival time of the structure-borne wave using the wave speed in oil, this would imply an incorrect

    distance between the source and the sensor. It is crucial that distance calculations are based on the direct acoustic

    path. It is critical to confirm the estimated source location by using a variety of sensor locations.

    Another way to distinguish the structure-borne waves from the oil-borne waves is to analyze the mode of vibration.

    Fluids, such as oil, will only support pressure waves. Solids, such as steel, can support many types of wave motion.Waves in the oil give rise to both pressure waves and shear waves in the tank wall.

    Source

    Tank wall

    Detector

    Direct wave

    Pressure (Longitudinal) Waves

    Shear (Transversal) Waves

    Structure-borne waves

    shear wave

    Critical angle for:

    pressure wa ve

    Figure 3 - Illustration of the longitudinal and transversal waves in the enclosure and how they are

    created from direct waves.

    NOTE: the wavelengths in Figure 3 are not to scale.

    Two wave fronts will be seen in these cases, as illustrated in Figure 3. The shear wave has the largest amplitude and

    can be identified in this way. The pressure wave is faster and may arrive at the detector first.

    The problem of structure-borne waves is reduced significantly if the acoustic sensor is located inside the tank.

    5.4 Velocity of sound in oil

    For the calculation of distance of the PD source from the sensor, 1413 m/s at 20 C is typically used. Corrections to

    the speed of sound for temperature and moisture content are not generally made to increase accuracy because the

    uncertainties due to material propagation are usually much larger.

    Table 2 shows estimates of the velocity of sound in oil at other temperatures. The velocity will be different if there

    are other materials in the wave path and may change depending on the properties of the oil.

    Table 2 - Velocity of sound in transformer oil vs. temperature

    Temperature of oil - C Velocity m/s

    50 1300

    80 1200

    110 1100

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    14/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    14

    6. AE systems: equipment specifications

    6.1 Introduction

    Many different types of instrumentation are available for detection and location of AE. Several types of typical AE

    systems and sensors are described here that have been shown effective in certain transformer arrangements;

    however, other systems may be equally or more effective, depending on the transformer physical parameters and the

    location of the PD.

    6.2 Acoustic systems that record single events

    A typical system consists of the following components.

    a) A digital detection system. This may consist of one or more standard 4-channel digital oscilloscopes withsampling rate for each channel greater than 1 mega-sample/second and memory depth greater than 5000

    samples. Data acquisition units available for computers could be used if they fulfill these requirements.

    Features such as averaging, peak detection, zoom, measurements and storage are very useful.

    b) Sensors: As discussed in Clauses 6.5, 6.6 and 6.7 below.

    c) Cabling and power supply units for the sensors.

    6.3 Digital signal processing (DSP) workstations that record acoustic data over extendedperiods

    Transportable DSP workstation systems are used to automate the AE acquisition and interpretation process. These

    systems identify, qualify and locate AE sources using the signals from sensors in Clauses 6.5 and 6.6 below. The

    systems combine the acquisition and saving of multiple AE signals with the capability to

    a) Qualify the signal as PD by determining the fit of the AE waveform to parameters such as rise time,duration time, and asynchronicity with the excitation frequency, e.g. 60 Hz.

    b) Provide a relative measure of activity level by determining the energy level at the transducer face. This isdone by counting the number of bursts and the area beneath the burst envelope that is above the threshold

    setting. Note this does not provide the actual level of PD energy.

    c) Calculate the location of signal source(s).

    Results of tests can be displayed as graphs such as point plots, line graphs, bar graphs or cluster graphs with multiple

    parameters or waveforms or the results of summations of data. This same data is used to generate reports that give

    the hardware and software setup information, acquisition activity and location of the source(s) of the PD.

    6.4 On-line (continuous) acoustic PD monitoring systems

    There are two general types of systems for continuously monitoring PD.

    a) Permanently installed on-line acoustic monitoring systems to detect and trend AE signals and send thatinformation to a remote location. Data gathering personnel are not usually present during normal

    operation. These systems typically consist of multiple sensors, which are placed at locations where faults

    may be anticipated based on past experience or highest probability of problems occurring, and amplifier

    and data acquisition/processing systems that are able to transmit collected data and/or warning alerts to

    locations outside the substation. They usually do not perform remote location analysis of the AE. Supply

    of power from the station DC source or another uninterruptible supply may be specified. For long-term

    robustness, the systems require protection of inputs, outputs and grounds similar to electronic relays.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    15/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    15

    A test to establish the baseline data of acoustic activity on the transformer is performed during the

    installation process. This test provides information to establish the best hardware and software settings for

    permanent monitoring. It is helpful for gain settings to be the same as adjacent transformers in order to

    compare readings if signals are thought to be the result of network disturbances.

    Permanent mounting of sensors is desirable for long term installations. This may be accomplished with a

    thin coating of suitable epoxy and a mechanical holder. The epoxy should be chosen to avoid broken

    bonds due to differential thermal expansion between the sensor and the wall. The bonding agent is usually

    a suitable couplant.

    b) Systems that include acoustic sensors and a high frequency current transformer installed on the caseground connection or a special radio frequency transducer mounted inside the transformer. These systems

    utilize the concurrence of an acoustic event and an electrical or radio frequency signal to confirm that the

    acoustic signal is PD. In some systems, the time difference is used to give a measure of location.

    6.5 External sensor

    The sensor mounted on the external surface of the transformer tank is a piezo-electric displacement transducer

    operating in its compression mode. Different investigators are using sensors with a sensitive region ranging from

    about 20 kHz to 500 kHz.

    It has been shown [B10] that the main frequency of a partial discharge of about 150 pC magnitude is 100 kHz.Users typically choose sensors with resonant frequency (for longitudinal waves) of either 60 kHz or 150 kHz. For

    larger discharges, frequencies should decrease. Also, attenuation affects high frequencies more than low. These

    factors favor the sensor with the 60 kHz resonant frequency for factory and laboratory use. In the field, however,

    numerous noises or harmonics of noises are encountered in the 20 kHz to 60 kHz frequency range. Since the sensor

    is sensitive to pressure waves in its frequency range that may not be from a PD source, these noises may lead to false

    readings. A number of users favor the 150 kHz resonant frequency sensor for field applications for this reason.

    Being a piezo-electric device, the sensor will also respond to varying electromagnetic fields such as those found in

    substations. To minimize this effect, the transducer can be either a "differential" type utilizing two crystals

    (mounted out of phase for noise reduction) or a shielded single crystal transducer with an integral pre-amplifier

    circuit. The latter is the preferred and most common configuration because its comparatively high amplitude, low

    impedance output is less susceptible to degradation due to noise pick-up in the connecting cables.

    Acoustic couplant gel or grease should be applied to the face of the transducer or matching piece just prior to test.

    Gels or solids that retain high viscosity at the transformer wall at operating temperature are preferred because low

    viscosity couplants will not transfer shear stresses. Couplants produced for ultrasonic non-destructive testing

    purposes are generally suitable. Gelled glycerin and silicone grease are particularly efficient and are recommended.

    Silicone grease can be difficult to remove from the tank surface.

    6.6 Internal sensor

    The internal AE sensor or waveguide is a device immersed in the oil that couples acoustic energy from the oil to an

    externally mounted sensor. An example of a waveguide would be a solid fiberglass rod inserted through a seal into

    the transformer tank with a sensor mounted on the external end of the rod. Careful attention must be given to

    maintaining dielectric properties and dimensions. The waveguide is less directional than external tank wall-mounted

    sensors because the impedance of the steel tank wall is not a factor. It is less sensitive to external noise such asstorms or loose fittings. [B25].

    A new technique under development uses an optical interferometric technique. A laser light source is coupled to the

    sensing head through an optical fiber. The sensing head consists of an air gap and a thin silica glass diaphragm.

    The optical signal is a function of the air gap length. Variations in the length, caused by an acoustical pressure wave,

    are proportional to the intensity of the acoustic signal.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    16/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    16

    6.7 Three sensor system

    A transducer system has been developed to aid optimization of sensitivity and rejection of non-PD signals [B9]. It

    consists of three relatively closely placed acoustic sensors mounted in a rigid movable frame. An electric detector

    may be used to sense the time of origin of the PD, which allows determination of the total transit time of the wave

    front. This system is intended to be operated by an experienced person. In searching for possible PD signals and

    their origin, the detector frame is moved to selected positions on the transformer tank. At each position, a set of

    different trigger and time frame settings are studied on the evaluation unit, which may be a digital oscilloscope.

    Suitable algorithms in the evaluation unit determine the direction and possibly the distance to the discharge source.

    6.8 Band-pass filter

    The use of a band-pass filter is optional. Its purpose is to negate as many of the effects as possible of signals that are

    not associated with PDs. These include vibrations caused by the magnetostrictive action of the core (Barkhausen

    noise), pumps and fans. Most of these fall below 30 kHz; however, the Barkhausen noise emanating from the core

    has sometimes been found to be in the 50 kHz range. Hence, a 100 kHz high-pass section with a rapid, roll-off

    response characteristic is needed. The reasonably generous band-pass (200 kHz) allows for variations between

    different transducers, in so far as their resonant frequencies are concerned.

    The filter is a band-pass type with lower and upper cutoff frequencies of FL and FH. These are frequencies at which

    the response to a constant sinusoidal input voltage has fallen by 3 dB from the maximum value. When used with a

    150 kHz sensor, FL should be about 100 kHz and FH should be about 300 kHz. The roll-off characteristics of thefilter should be a minimum of 48 dB/octave (240 dB/decade) for the high-pass section. This means that, relative to

    the signal of interest (150 kHz), a 50 kHz signal would be attenuated by 48 dB. The low-pass filter should roll off at

    not less than 24 dB/octave (120 dB/decade) so that a 600 kHz signal would be attenuated by 24 dB.

    7. AE testing

    7.1 Personnel qualification and certification

    Formal qualification and certification for personnel doing acoustic testing and interpretation of test data is available.

    One such program is given by the American Society for Nondestructive Testing [B5].

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    17/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    17

    7.2 Field vs. factory test differences

    AE testing in factories or field situations has many differences. Some of the specific ones are shown in Table 3:

    Table 3 - AE testing: field vs. factory differences

    Field Factory

    Ambient Noise sources Limited control; e.g. noise from rain or

    hail. Signal processing or post test

    analysis can reduce or eliminate noise

    in some cases.

    Controllable

    Cooling Pumps May be required by system operating

    requirements.

    Can be shut off

    Weather Limited control, e.g. noise from rain.

    Signal processing or post test analysis

    can reduce or eliminate noise in some

    cases.

    Testing done indoors

    Power Supply Isolation, Filtering, and/or UPS

    required

    Clean power available

    Grounding Single point grounding for test object

    and equipment needs to be established.

    Appropriate grounding provisions

    built into test bay.

    Equipment Access Precautions needed for working near

    energized facilities.

    Precautions needed for working near

    energized facilities.

    Transformer Design Generally limited knowledge of what is

    inside the tank.

    Full design information available.

    Test Voltage Limited adjustment range unless a test

    power supply is taken to the

    transformer location

    Full control of voltage levels

    Gas blanket (air or nitrogen) Use care that sensors are mounted

    below oil level. Also, bubbles may be

    present during certain operating

    conditions.

    Use care that sensors are mounted

    below oil level.

    More information appropriate to the two environments is included in Clauses 8 and 9.

    7.3 General considerations on the application of sensors

    Transducer placement and mounting are critical to avoid attenuated or misleading signals [B6]. Some things to

    consider include the following:

    a) The contact between the transducer and the transformer tank is critical. Simply placing a transducer onthe transformer tank surface often produces a very weak signal. It is advisable to wipe the area free of

    dirt, oil, bugs, etc. and polish it with a mild abrasive or abrasive cloth before placing the transducer.

    b) An acoustic couplant is essential for enhancing the mechanical and acoustical coupling between thetransducer and the tank surface. It should be evenly applied to the clean mounting surface of the

    transducer before placement.

    c) A sound transmitting epoxy may have to be used if the mounting location is non-magnetic.

    d) Transducers mounted on the tank walls may detect both direct and wall-borne signals. Those mountedon a bolted cover or other gasketed surface may receive the direct signal more clearly, but the wall-borne

    signals may be distorted or dissipated because of the gasket.

    e) If possible, avoid locations where there is magnetic or non-magnetic tank shielding, which will causeextra signal attenuation

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    18/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    18

    f) On transformers built with double wall construction, transducers should be located on the welded ribs thatspan between the two tank walls to provide a strong signal. The air in the cavity between the walls

    attenuates acoustic signals.

    g) If possible avoid locations above gas spaces. This adds extra impedance in the transmission path, whichproduces additional attenuation. Signals may be difficult to resolve.

    h) Avoid mounting sensors on tank stiffeners unless the tank has a double-skin wall

    i) For safety reasons, do not locate sensors in areas of high voltage

    j) Provide sufficient spacing between sensors to insure independent signals. Distance depends on sensormodel

    k) Verify sensor operation, either the entire system or each sensor. Amplifiers should be set for similarsensitivity for all sensors.

    l) An acoustic verification rod may be helpful in determining an initial location for a sensor. The rod ismade of a solid sound-conducting insulation material, typically wood or fiberglass. It is used by placing

    one end against the transformer tank, the other end against ones ear and listening for sounds that could

    indicate PD.

    m) Avoid the ends of transformers that have cores with unwound return limbs.

    n) Aluminum or stainless steel walls are non-magnetic. Sensors may have to be placed using epoxy.

    o) Do not mount sensors on control boxes

    p) LTC operation contains a high electromechanical energy that usually propagates through the entiretransformer. Actions should be taken in order to identify operations during the test and distinguish them

    in post-test analysis to identify the source of AE.

    q) Shell-form transformers: locate the sensors on top (above the core) or bottom (below the core).

    r) Transient voltage protection must be applied to the input of test instruments/devices.

    s) Extraneous electrostatic and magnetic signals may cause false indications and damage equipment.

    8. AE field test procedure

    8.1 Introduction

    AE testing is usually done in response to gas-in-oil test results or noises that may indicate partial discharge activity.

    In most cases, the transformers are monitored while carrying load. This requires safety precautions when placing

    the transducers, assuring that minimum approach distances are not compromised. Refer to Clause 1.3 Safetywarnings.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    19/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    19

    8.2 Test setup

    Approximately two to three hours are usually required to prepare for monitoring after arrival at a site. This will

    depend on number of sensors to be installed and accessibility to the unit, power source, etc. If a test power supply is

    being used, extra time will be needed to setup and check out the power supply.

    Set up the test equipment at a convenient location for access to the transformer and the station service source.

    Establish a common point ground for all of the test equipment and the transformer.

    The transducers are connected to the test equipment with coaxial cables. Cable routings should be chosen to

    minimize interference pickup from bus work and grounding connections in the test area. Verify proper operation of

    the monitoring system.

    An operational test should be followed in order to assure the same sensitivity of all sensors. Many users verify

    transducer sensitivity by breaking the lead of a Number 2 pencil against the tank close to the transducer. Users

    advise this is limited to tanks with 19 mm (3/4") maximum wall thickness. Another technique is to activate an

    acoustic transducer to create a signal into the tank and measure the output of the other sensors. The signals recorded

    by the various transducers should be compared to see if they are reasonable and consistent.

    8.3 Sensor placement and initial scan

    Unless on-line PD monitoring is being used, there is usually no indication of where to look for the noise source.

    Therefore, a scan covering the complete transformer is the first step.

    a)For a three-phase core form transformer, install one sensor in the general area of the bottom connection ofeach bushing. Place additional sensors at approximately the center of each winding limb on the high and

    low voltage sides of the tank. If extra sensors are available, place them on the tank ends. See 7.2 m).

    b) Similarly, for a single-phase core form transformer, install one sensor in the general area of eachbushing bottom connection. Place additional sensors at approximately the center of each limb of the

    windings on each of the four sides of the transformer tank. See 7.2 m).

    c) If the transformer has a preventive autotransformer inside, consideration should be given to placing oneor two transducers close to its location.

    d) Using the same sensor locations and software settings when testing identical transformers permitsestablishing ambient baseline data for that particular design. The sensors may have to be moved to

    improve reception of signals from a specific source.

    e) Sufficient couplant gel is to be applied to the face of the transducer to ensure efficient transmission ofthe AE signal from the tank wall to the sensing crystal. Too much couplant will not be harmful (though

    wasteful), whereas too little couplant can seriously inhibit the transducers sensing capabilities.

    f) Magnetic shielding blocks the signal from the sensors. The location where shielding is installed isusually obtained by referring to pictures or notes from past experience with the transformer or from the

    manufacturer.

    g) In the case of transformers indicating PD, a high frequency split-core CT or ammeter (Rogowsky coiltype) around the transformer case ground can be used as a direct signal to the digitizer. This can be used

    as the trigger transducer to indicate time zero.

    The face of the transducer with its film of couplant should be brought into contact with the transformer tank wall

    with only sufficient pressure applied in order to get a good signal and hold it in position. It is necessary to hold the

    sensor steady so that no signals are generated due to relative movement between the sensor and tank wall. This can

    be achieved by means of a magnetic clamp, adhesive tape or epoxy.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    20/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    20

    The time period for the initial scan is dependent on the acoustic activity rate. Some users monitor for about four

    hours before changing transducer placement. This basically assures the emission patterns are consistent and

    repeatable. If activity rates are low or erratic overnight monitoring may be required.

    8.4 Monitoring techniques

    When the transformer is energized from the power system, voltage levels are fairly constant making inception and

    extinction levels of acoustic activity very difficult to determine.

    Techniques for varying system conditions to help characterize the AE source include:

    a) Varying transformer loading to see if the acoustic activity is load related

    b) Raising or lowering the bus voltage several kV by tap-changing and/or capacitor/reactor switching

    c) Moving the transformer on-load tap-changer(s) up or down a step at a time to see the impact on the

    acoustic activity

    If the transformer is energized from a test power supply, the test voltage can be raised and lowered at will for

    determination of acoustic activity inception and extinction levels.

    Signal sensitivity is unique to each particular AE monitoring system. Trigger level settings depend on the normal

    operating noise on the transformer to be tested (this depends on core type, pump/fan operation noise, etc.). The best

    initial settings are the least sensitive settings that give a clear AE pattern (avoiding the noise coming from the core,

    pumps/fans or other sources). The settings can then be optimized during the signal location process.

    A three dimensional layout can be constructed, for instance, using a convenient corner of the tank for zero

    coordinates. For tanks with rounded corners, consider squaring them off for reference. After sensor locations are

    plotted, the time delay in each transducer signal can be used to estimate the source location. Using the maximum

    number of sensors possible improves the accuracy and usability of this approach.

    8.5 Locating the source of the signal

    An approximate source location can be estimated based on relative timing of signal arrivals at the varioustransducers and assumptions about the speed of sound in oil. This is not a foolproof method because of the different

    types of material (insulation, steel, copper, oil, etc.) in the paths between the signal source and the various

    transducers. Also, there may be more than one signal source in the transformer.

    Reposition transducers to focus on the area of the transformer tank where the suspected source is located and

    continue the monitoring process. The sensors can be arbitrarily close as long as a time difference between them can

    be measured.

    Sometimes, even when transducers have been relocated to a suspected area, only one sensor detects the acoustic

    activity. This can happen either because the source detected is very low in intensity or highly attenuated or because

    there is a problem with the instrumentation. Care should be taken not to automatically disregard this activity as

    noise.

    The signal source location can be confirmed by a set of consistent signal timings. A clear consistent picture of the

    signal characteristic helps to identify the source type.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    21/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    21

    8.6 Reporting and follow-up

    Comparison of actual problems and the predictions from acoustic monitoring are important for building the

    knowledge base on the response of a particular monitoring system. This greatly enhances the usefulness of acoustic

    monitoring as a diagnostic tool.

    The investigation report should include information on the test setup, test procedures, test waveforms (if any), and

    predicted signal sources based on experience, internal assembly drawings and/or photographs of the transformer

    under test.

    Follow-up reporting may include comparison of the actual problem and the predictions from the investigation.

    Useful information includes:

    a) What was found

    b) Where was it located

    c) Differences between predicted and real locations

    d) How the problem was corrected

    Acoustic monitoring after repair allows comparison of before and after acoustic signatures and allows establishingthe new baseline data of the transformer.

    9. Factory test procedure using an electrical trigger

    9.1 Introduction

    An important difference between the factory test and the in-field test is the advantage of being able to use an

    electrical PD signal to trigger the acoustic data acquisition. This electrical trigger, occurring virtually

    instantaneously as the PD emissions leave their source, provides a convenient "time-zero" mark to use to measure

    the time differential between this signal and the acoustic signals, and hence calculate the distance from the acoustic

    sensors to the PD source.

    The input of the electrical PD detector is typically connected to the bushing capacitance tap. The output is

    connected to one of the channels of the acoustic location system. It is recommended to use an electrical apparent

    charge detector rather than a radio-influence voltage (RIV) meter since the frequency range of the former is much

    closer to that of the AE than the latter. However, either can be used for the trigger. The AE sensors are connected to

    the transformer tank wall. The outputs of the sensors are connected to the acoustic location system for viewing the

    acoustic signal and its time delay from the electrical signal.

    9.2 Initial sensor placement

    The initial placement of the AE sensors onto the tank wall can make the difference between an efficient location of

    the PD source and a more time consuming one. Guidance in making an informed estimate of where to initially place

    the sensors can come from the Induced Voltage Test. This test, in most cases, will indicate which phase of the

    transformer contains the PD source. If so, the sensors should then of course be placed in the area of the problemphase. Caution should be exercised because there has been at least one experience [B51] where the induced voltage

    test indicated the PD to be located in one phase and the acoustic test located it on a different phase, the latter being

    verified through internal inspection. A typical example would be a delta winding where each bushing is connected to

    two phases.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    22/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    22

    Another source of information is to examine the transformer internal assembly drawings and photographs if

    available. They may show likely areas of PD sources, and indicate whether the problem may be on the LV or HV

    side, or an end wall, and whether it is towards the top, middle, or bottom of the tank. An example of a simplified

    HV-Side transformer assembly is shown in Figure 4. A search for the problem PD source within such an assembly

    can include placing sensors along the windings, over each de-energized tap-changer, and/or along the high-voltage

    leads connecting each HV winding to its respective bushing.

    Figure 4 - Example of HV-side of three-phase transformer assembly

    Ideally, initial placement of sensors would resemble one of the three arrangements shown in Figures 5a, 5b, and 5c.

    Figures 5a and 5b are for the case when the problem phase is known; Figure 5c for when it is not known.

    Figure 5a - Sensor locations with PD source in center phase. Typically sensors are located oneach side wall.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    23/50

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    24/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    24

    Figure 6 - Transformer tank plan view

    Some creativity is therefore required, and the actual sensor placement may be significantly different from the

    arrangements shown in the previous figures. For example, due to the presence of radiators or internal wiring trays,

    the sensors for one phase might need to be placed on the opposite side-wall than the other two phases.

    Mounting the sensors on manhole or other covers may provide an AE signal path that is clear of tank wall - carried

    signal if the cover is isolated from the tank by flexible gaskets. The transformer oil must be in contact with the

    inside surface of the cover for the sensor to be effective.

    Shell form type transformer arrangement requires special mention owing to the shielding used inside the tank walls.

    It may only be possible to place sensors on the top of the tank or in areas where there is no shielding.

    9.3 Measurements and changing of sensor placement

    With the sensors in place, a simple check may be performed to ensure that they are indeed operational. Using low

    signal amplification setting, this check can be accomplished by gently tapping your fingertip on the tank wall

    immediately beside one of the sensors. This will create an acoustic signal, which should be detected by the sensor

    and displayed on the oscilloscope. Use this procedure to check each sensor in turn.

    Now, the first set of AE measurements is ready to be taken. To do so, energize the transformer in the same manner

    as during the routine Induced Voltage Test. Increase the voltage slowly until the electrical apparent charge detector

    measures sustained PD activity, or until the full test voltage level is reached that can be safely sustained

    continuously. (Do not raise the voltage level beyond this amount, as a higher voltage level, though possibly

    producing greater PD activity, unduly stresses the transformer insulation). At this voltage level, and with a medium

    acoustic signal amplification setting, the oscilloscope trigger sensitivity level must be calibrated to the

    corresponding electrical PD detector signal. Now, for every half-cycle of the voltage wave, the oscilloscope will be

    triggered to begin data acquisition from both the electrical PD detector and the acoustic emission PD sensors.

    "Time-zero" will be the instant in time that the data acquisition is triggered to begin. As many sensors as the

    oscilloscope will allow should be displayed at once. Data that invites analysis can be "frozen" on-screen and stored

    in memory using the digital oscilloscope.

    The interpretation of the acoustic signals displayed on the oscilloscope is done according to Clause 10.1 of thisguide. If none of the sensors indicate PD activity, increase their signal amplification slightly and repeat the test. If

    there are still no clear signs of activity, the sensors will have to be moved manually, perhaps by a displacement of

    half a meter either vertically or horizontally, and retested again. Another suggestion is to move some of the sensors

    to the opposite side of the tank. This is a trial-and-error process that continues until at least one of the sensors

    indicates the presence of PD activity. Again, this process can be expedited with the examination of the transformer

    internal assembly drawings and photographs.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    25/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    25

    When one or more of the sensors shows activity, assuming in the simplest case that only one problem PD source is

    present, the rest of the sensors may be manually moved into the vicinity of the active area. The objective is to obtain

    AE signals from all sensors, and to position them so as to minimize the time differential between "time-zero" and

    the beginning of the acoustically detected PD signal. Ideally, this minimum time difference will correspond to a

    maximum number of individual oscillations in the signal as measured by the counting circuit; however, this may not

    necessarily be so (refer to Clauses 4.2 and 5 for calculation of the distance from the sensors to the PD source).

    Using this procedure for sensor placement and AE measurement, the PD source can often be located to within 25 cm

    or less.

    10. Characterization of AE signals

    10.1 Introduction

    Characterizing whether an AE signal is PD is usually done by considering factors such as length of the burst,

    movement of the AE signal relative to the excitation frequency and rise time of the first oscillation to cross the

    threshold.

    Partial discharges obtained by conventional electrical methods use a threshold to predict severe activity. This level

    is generally about 300 pC to 500 pC. Because of variations in the acoustic signal caused by distance and interfering

    materials, there is no similar threshold for acoustic systems. A strong signal buried deep within a winding may be

    very weak by the time it reaches the acoustic sensor. Also, differences in amplifier gain settings cause differences in

    magnitude.

    10.2 General alternating current systems

    In general, two types of PD activity (other than zero) may be encountered: continuous and sporadic.

    By continuous, it is meant that PD bursts are present all the time, though they may have varying AE amplitude. This

    type of signal is typical of that produced by an energetic PD source.

    Sporadic activity can be further subdivided into two types.

    a. Sporadic AE from a continuous PD source: this is characterized by activity that is present most of the time,but short quiescent periods are also encountered. This type of signal may be produced by exposed sources

    on conductors and connectors, defects in insulation, worn tap changers, foreign objects or ungrounded

    hardware.

    b. Sporadic PD with lengthy quiescent periods (perhaps minutes) followed by short periods of very highactivity: this type of signal has been found to be associated with floating static shields, streaming

    electrification or other types of static discharges (see Clause 10.7) and bad contacts in tank wall shielding.

    Often short-lived arcs are associated with this type of fault, and these produce very energetic AE signals

    during active periods.

    As previously described, it is often possible to determine the position on the tank wall where the transducer is

    closest to the PD source. This does not give information as to the distance into the tank (from that location) to the

    source. However, observing the signal on an oscilloscope (a digital transient recorder is recommended), it is possibleto form an opinion regarding this. For example, the burst shown in Figure 1a has suffered very little attenuation.

    This is evidenced by the high rise rate of the leading edge of the burst envelope, resulting in the characteristic

    "arrow head" shape. To achieve this, the propagation path is almost entirely in oil with little solid insulation

    involved.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    26/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    26

    If the PD signal propagates through layers of solid materials (iron, copper, insulation, etc.), the resulting attenuation

    not only affects the overall amplitude, but also modifies the burst envelope by "rounding off" the leading edge. In

    the extreme, the burst envelope becomes "egg-shaped" or "ellipsoid-shaped" as shown in Figure 7 [B41]. By

    utilizing this phenomenon, it may be possible to estimate whether the source lies close to the surface or is buried

    well within the insulation system.

    Figure 7 Typical AE burst showing effect of attenuation

    The waveform beyond 200 microseconds is from reflections of the signal.

    The user should always be aware that the responding characteristics of the sensor may at times be more in evidence

    than the forcing characteristics of the PD signal.

    Some experts use signal length of 40 microseconds to 1 millisecond as an identification criterion for PD.

    PD usually has a correlation to the excitation frequency, e.g. 60 Hz, waveform, but is not synchronized to this

    frequency. Typically, there is a slight "jitter" back and forth from a constant position on the waveform.

    10.3 Acoustic systems that record single events

    The frequency range of a signal is between 50 kHz and 350 kHz. In [B10] the main frequency for an approximate

    150pC discharge is about 100 kHz with the expectation that for larger discharges, frequencies will decrease.

    The amplitude and time duration depend on the physical size of the transformer tank and the location of the sensors

    and their actual separation from the estimated PD source.

    The subsequent attenuation of the signals is due to the heterogeneous structure of the transformer core/coil

    assembly. Attenuation of the signal inside the tank affects high frequencies more than low. The attenuation of the

    signal also creates a lack of correlation of scaling factor between the acoustic signal and electrically measured

    apparent charge.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    27/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    27

    Some examples of signals are shown in the figures below.

    Figure 8 - A laboratory recorded direct PD signal (bottom) and its power spectrum (top)

    The signal in the lower trace of Figure 8 is in the time domain; the x-scale is seconds. The signal in the upper trace is

    in the frequency domain; the x-scale is hertz (Hz). The sensor used has its main sensitivity in the range 20 kHz to

    120 kHz, which is clearly visible in the spectrum. Note the sharp initial rise in the time frame; maximum amplitude

    is reached in the first oscillation. The second, more dilute, burst at about 0.7 ms is due to reflection.

    ttd1

    .7E-03 -0.6E-03 -0.4E-03 -0.3E-03 -0.2E-03 -0.1E-03 0. 0.1E-03 0.2E-0

    0.

    0.5

    FFT:ttd1

    . 0.2E+06 0.3E+06

    0.5

    1.

    Figure 9 - A laboratory recorded signal with clear signs of propagation in the tank wall, together

    with its power spectrum

    The time frame signal (lower trace, scale is seconds) in Figure 9 shows a typical two-step behavior. The longitudinal

    wave arrives first with lower amplitude than the transversal wave that comes about 0.04 ms later. The frequency

    content (upper trace in Hz) will be slightly dependent on the wall thickness, length of wall path etc., but is mainly

    unchanged from a direct signal as it is dominated by the sensor response which extends up to about 120 kHz.

    direct PD signal

    -0.1E-03 0. 0.1E-03 0.3E-03 0.4E-03 0.5E-03 0.6E-03 0.7E-03 0.8E-03

    -0.2

    -0.1

    0.0.1

    0.2

    0.3FFT:direct PD signal (f requency domain)

    -0.1E+06 0. 0.2E+06 0.3E+06 0.4E+06

    0.1

    0.2

    0.3

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    28/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    28

    time domain

    -0.001 -0.5E-03 0. 0.5E-03

    0.

    0.05

    FFT entire signal

    . 0.5E+05 0.1E+06

    0.05

    0.1

    FFT noise

    . 0.5E+05 0.1E+06

    0.05

    0.1

    Figure 10 - A weak time domain PD signal together with power spectra for entire signal (middle)

    and for the noise part (top)

    Comparison of the two FFT frequency domain spectra in Figure 10 reveals that the PD signal main amplitude is

    below 75 kHz. This is because the source is under paper insulation, which attenuates higher frequencies. The signalis just slightly larger than acquisition system noise.

    Signal

    -0.4E-03 -0.2E-03 -0.1E-03 0. 0.1E-03 0.2E-

    0.

    0.01

    Signal 256 averages

    -0.2E-03 -0.1E-03 0. 0.1E-03

    0.

    0.01

    Figure 11 - A clear signal with indications of wall propagation (bottom). These indications are

    confirmed by averaging (top)

    Averaging can be a very effective method to reduce noise, as illustrated in Figure 11. The trigger was in this case set

    on the high amplitude oscillation in the acoustic signal. A stable trigger and a high sample rate are required for

    averaging. Several independent averages should always be performed to avoid chance coincidences. If applicable,

    averaging is often the most effective method to reduce noise. Note, for example, the very weak indications of asignal appearing around -0.3 ms in the upper trace. Such observations are often the key to a successful localization.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    29/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    29

    signal

    -0.003 -0.002 -0.001 0.0.

    0.1

    FFT:signal

    . 0.1E+06 0.15E+06

    0.10.20.3

    Figure 12 - A PD signal that has passed from the high-voltage side to the low-voltage side of atransformer

    The wave front in the lower trace of Figure 12 is not sharply rising; it grows slowly (note time scale) and starts

    roughly at -1.5 ms in the figure. The power spectrum in the upper trace shows a strong peak around 35 kHz,

    indicating the passage of the signal through considerable amounts of attenuating material.

    10.4 DSP workstations that record acoustic data over extended periods

    Transportable DSP workstation systems process and graphically display the bursts from AE sensors and a number of

    signal characteristics vs. time, cumulative time or each other in two and three dimensional formats. This is done for

    multiple sensors simultaneously. Signal characteristics include amplitude, signal energy, PD hits, signal duration

    (microseconds), PD hits vs. the phase of the power frequency voltage, where phase information is available, and rise

    time.

    Software in these systems may take advantage of known PD characteristics in order to reduce false indications of

    PD. Characteristics include:

    a) Signal may be asynchronous relative to the excitation frequency, e.g. 60 Hz. If the signal is synchronous

    with the excitation frequency, e.g. 60 Hz, it is often noise [B68]

    b) Length of the burst

    c) Rise time of the first oscillation that crosses the threshold.

    Software with a PD locator algorithm uses data collected by the system and three dimensional details of the

    transformer tank to generate the best estimate of the PD location. This software may use wavelet transform methods

    to estimate the PD location (Annex C).

    10.5 On-line (continuous) acoustic partial discharge monitoring systems

    Monitoring systems that send information to remote locations are usually intended to alert maintenance and

    engineering personnel to possible problems, which can then be followed by more extensive field tests. The systemsoften have less processing capability than DSP workstation systems and may not be able to characterize whether the

    AE signal is PD. The information transmitted is usually limited to number of counts per unit time and a measure of

    energy that is undefined.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    30/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    30

    10.6 HVDC transformers and reactors

    PD detection and location devices are used in the same way during high voltage direct current (HVDC) transformer

    and reactor factory and field measurements as they are with normal ac equipment tests. If the transformers are

    energized without having the converter operating, there is no extra background noise and PD measurements are the

    same as ac equipment. However, in field measurements:

    a) EMI interference may be higher in an HVDC substation, requiring additional shielding of instrumentation,cables and wires. Due to commutation transients there is significant high frequency voltage difference

    between different parts of the ground system.

    b) The background noise level in HVDC transformers in operation is much higher than in normal actransformers and reactors due to the fast transients at converter operation (e.g. valve commutation). Higher

    trigger thresholds may compensate for this. If noise levels are too high, acoustic monitoring for PD is not

    useful.

    c) Acoustic monitoring during inverter operation may be more difficult than rectifier operation because of thefast transients from high capacitive currents at valve firing.

    d) A sensor of 150 kHz resonant frequency may reduce the noise level compared to one of 60 kHz resonantfrequency, but it will also reduce the sensitivity to PD sources under paper.

    Sensor location notes cited in other parts of this Guide should be observed. In addition, the acoustic signal may be

    attenuated in the area around the valve winding bushing turrets, possibly caused by the extra insulation barriers used

    around the bushing connection for resistivity grading. Better results in this location may be obtained by looking

    down into the turret by mounting the sensor on the bushing flange mounting surface.

    10.7 Characteristics of PD from static electrification

    The failures of a number of large power transformers have been attributed to accumulation of charge and subsequent

    flashover discharge. Field tests have indicated a correlation of the charge buildup, accompanied by an increasing

    level of PD activity, with oil temperatures below approximately 40 C and relatively high oil velocity [B16, B22,

    B47]. This phenomenon is called static electrification.

    It was expected that gases consistent with PD and flashover discharge would be formed; however, DGAs takenduring the field tests [B47] did not indicate any increase in levels of hydrogen or other gases. This was probably

    because of the relatively short period of time and sporadic occurrences of the static electrification.

    External sensor placement is mostly toward the top of the transformer using care to avoid internal shielding.

    However, the high energy discharges of advanced static electrification can be detected by sensors located at almost

    any location clear of shielding. These discharges can sometimes be heard as loud bangs by persons standing near the

    transformer.

    Static electrification discharges can be detected by acoustic methods well before they become damaging [B22].

    Field test experiences [B22, B52] have shown that the most critical situations where static electrification can occur

    is during start-up or lightly loaded operation in cold weather. Acoustic activity due to static electrification is

    gradually reduced as oil temperature is increased. It practically stops after reaching 50 C.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    31/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    31

    10.8 Acoustic activity from thermal faults, the core, mechanical noises and other sources

    AE techniques have typically been used only for the detection and location of PD/arcing in power transformers

    when an indication of a problem is pointed out by other techniques (usually gas-in-oil). However, it has been

    observed through the years that transformers without gassing history and/or no indication of an electrical problem

    produce acoustic activity when monitored over a fixed period of time [B52]. These signals must be differentiated

    from PD signals for the results to be effective. Some examples and their characteristics follow.

    a) Core magnetostriction noise (Barkhausen effect): the primary frequency occurs at twice the powerfrequency; the amplitude of this signal in both half cycles is about the same. Over fluxing may create

    considerable noise, which may have harmonics that reach to the 30 kHz to 40 kHz frequency range or above.

    b)Pumped liquid noise: the discharge from oil circulating pumps may interfere with PD signals withtransducers placed low on the transformer tank. They usually have no correlation with the 50 Hz or 60 Hz

    waveform.

    c)Loose nameplates, pipes hitting each other, fan noise, etc. may sometimes have repeatable waveforms closeto PD signals. The length of the signal is often much longer than the PD signal, which is characteristically

    under 150s.

    d) Loose shielding connections in the transformer tank wall may cause large PD indications, but not be

    detrimental to transformer operation. The location of the signals should be considered and correlated withtransformer design drawings.

    e)Wiring from the sensors to the amplifiers, if not properly shielded, will pick up spurious PD signals. Look atevery possible source before concluding there are major problems inside the transformer.

    f) Trucks, environmental noises (thunderstorms, rain, snow, hail, wind, etc.), and miscellaneous events near thetransformer tank may activate the acoustic sensors. These are random signals lasting longer than 1 ms.

    g)Switching and load tap changer movement are random signals.

    h)Thermal faults may cause random signals [B21, B46]

    The correlation of additional parameters of the transformer during the test (current, voltage, pump/fan current, oiltemperature, winding temperature, phase angle, etc.) with the AE data may assist in identification and separation of

    the different acoustic sources detected during a test [B45]. A sensor isolated from the transformer tank may be used

    as a reference for some environmental noises. If possible, a correlation with electrical PD detection can aid in

    distinguishing between PD and noise signals.

    10.9 Comparison between electrical and acoustic signals

    A PD exhibits, besides other phenomena, a fast transient electrical pulse and an acoustic "bang". Depending on the

    location of the PD and the coupling path between the event and the detector, the electric or acoustic signal can be

    used to detect the PD. Both methods have different detection ways and sensitivities for unwanted signals (noise).

    The acoustic PD detection is most useful for events within the line-of-sight of the acoustic transducers. This limits

    the detection range, but also the amount of noise.

    The electric PD detection covers a wider area, including e.g. bushing and tap changer. External noise will also be

    detected and is difficult to remove. The correlation between instrument reading and actual discharge magnitude is

    better than with the acoustic method. Several international standards exist that define the instrument response, which

    is the readout in pico-Coulomb or micro-Volt, allowing a better comparison between manufacturer and in-field

    measurements.

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    32/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    32

    Table 4 gives a rough overview of the comparison of electrical and acoustic PD signals.

    Table 4 - Comparison of electrical and acoustic PD signals

    Source Electrical

    Detection

    Acoustic

    Detection

    Remark

    PD generated within the transformerPD on the outside of the winding Yes Yes Best use for acoustic detector, location

    (triangulation)

    PD within the winding Yes unlikely Strong acoustic attenuation inside the

    winding.

    RIV-detector signal affected by circuit L-C

    resonance

    PD between winding and core Yes difficult acoustic signal reflection at the core

    required

    PD between core and tank Yes Yes PD location is often difficult

    Arcing / tracking of the oil surface Yes Yes

    Arcing / tracking of the bushing

    surface in the oil

    Yes Yes

    PD in the bushing Yes possiblea

    PD in the de-energized tap changer Yes Yes

    PD in the on-load tap changer Yes Yesbsensor placement on LTC compartment

    Noise sources

    PD outside the transformer, (e.g.

    corona on busbar, PD in switchgear)

    Yes Noc

    Strong tracking / leader discharge Yes possiblec,d

    Nearby lightning strokes Yes possiblec,dunlikely single events

    Nearby car ignition Yes Nocno relation to phase angle

    Switched electronic power supplies Yes Noc

    Radio stations, transmitter Yes No Electrical noise filter (band-stop) or shift in

    RIV frequency required

    Weather (rain, sleet, snow, hail) No Yes

    Other events

    Moisture / Degradation in the oil No No Use other diagnostic methods to supplement

    the PD detection (PF, DGA, etc.)

    a Field tests have proven [B42] that acoustic detection of PD in the bushing can be achieved if acoustic sensors are

    placed on the grounded flange of the bushing, close to the capacitance tap. See SAFETY WARNING Subclause 1.3.bSeveral cases have been reported [B41 B51 where PD/Arcing and/or tracking (carbon paths) have been detected

    inside LTC compartments, either on the insulating support bars or on the diverter switch cylinder.cSuccessful electrical PD detection requires noise suppression (e.g. gating together with an external noise antenna)

    and observation of the PD - phase pattern (fingerprint)dVery strong electrical signals can couple into the transducer or amplifier if the detector is not sufficiently screened

  • 8/12/2019 AE Guide PC57.127-D10.0 12-29-06

    33/50

    IEEE PC57.127/D10.0, December 29, 2006

    Copyright 2006 IEEE. All rights reserved

    This is an unapproved IEEE Standard subject to change

    33

    11. Integrating AE results with data from oil analysis

    Although AE data is useful in its own right, it becomes even more so when used in conjunction with dissolved gas-

    in-oil data. For example, if the problem has been present for some time, as is typical of situations that develop in the

    field, good correlation should be expected between gas analysis and AE data. As with any diagnostic tool, a baseline

    reading should be established before or at the start of monitoring AE signals. The increase and rate of increase of

    combustible gases from the baseline dissolved gas analysis (DGA) reading, in combination with events that occur on

    the transformer, then become relevant diagnostic data.

    PD and/or arcing in the presence of oil produce hydrogen (H2) and other gases. PD and the generation of H2due to

    PD, are the earliest (first) warning signals of most incipient faults known to the industry.

    If DGAs show a continuing increase of H2in combination with AE signals emanating from a source determined to

    be in a specific area, there is a good possibility that the partial discharge is taking place in the specific area. Refer to

    IEC 60599 [B37 and IEEE Standard C57.104 [B34 for more information.