Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Advances in Fixed-Area Expansion Devices
ACRCCR-20
For additional information:
Air Conditioning and Refrigeration Center University of Illinois Mechanical & Industrial Engineering Dept. 1206 West Green Street Urbana, II... 61801
(217) 333-3115
X.Fang
August 1999
The Air Conditioning and Refrigeration Center was founded in 1988 with a grant from the estate of Richard W. Kritzer, the founder of Peerless of America Inc. A State of Illinois Technology Challenge Grant helped build the laboratory facilities. The ACRC receives continuing support from the Richard W. Kritzer Endowment and the National Science Foundation. The following organizations have also become sponsors of the Center.
Amana Refrigeration, Inc. Brazeway, Inc. Carrier Corporation Caterpillar, Inc. Chrysler Corporation Copeland Corporation Delphi Harrison Thermal Systems Frigidaire Company General Electric Company Hill PHOENIX Honeywell, Inc. Hussmann Corporation Hydro Aluminum Adrian, Inc. Indiana Tube Corporation Lennox International, Inc. Modine Manufacturing Co. Peerless of America, Inc. The Trane Company Thermo King Corporation Visteon Automotive Systems Whirlpool Corporation York International, Inc.
For additional infonnation:
Air Conditioning & Refrigeration Center Mechanical & Industrial Engineering Dept. University of Illinois 1206 West Green Street Urbana IL 61801
2173333115
ADVANCES IN FIXED-AREA EXPANSION DEVICES
Xiande Fang
ABSTRACT
Fixed-area expansion devices are widely used in refrigerators, air-conditioners, and heat
pumps of up to 3.5 kW capacity with variable operating conditions. A fixed-area expansion
device falls into one of the three categories: an orifice, a short tube, and a capillary tube. The
earliest studies on orifices began in 1900s, with the interest in metering fluid flow rate. The
research on capillary tubes began to be active in 1940s. Since then, the study of fixed-area
expansion devices has been one of main activities in refrigerating. With the increasing need to
replace the ozone-depleting CFC and HCFC refrigerants, refrigerators, air-conditioners, and
heat pump systems have to be redesigned to accommodate new replacement refrigerants so
that research activities in fixed-area expansion devices have been intensified since early
1980s. This paper gives a detailed review of the literature on fixed-area expansion devices.
The main topics include the mass flow rate through orifices, the mass flow rate through short
tubes, rating capillary tubes, metastable flow, the friction factor and friction pressure drop,
and mathematical solution of fixed-area expansion device.
1 INTRODUCTION
A fixed-area expansion device can be categorized by its length-to-diameter ratio, LID.
According to its LID, a fixed-area expansion device falls into one of the three categories: an
orifice, a short tube, and a capillary tube. An orifice has an LID < 3. A short tube is defined as
having a length-to-diameter ratio of 3 < LID < 20 (Aaron and Domanski, 990). A capillary
1
tube has an LID > 20. This is an arbitrary categorization, but acceptable. Physically,
difference is in ratio offrictionallosses and it's effects on flow.
Every refrigerating unit requires a pressure-reducing device to meter the flow of
refrigerant to the low side in accordance with demands placed on the system. In 1931, a
hermetic system was introduced in Evansville, IN, utilizing a capillary tube as an expansion
device (Schulz, 1985). With the consideration of the safe, oil-soluble, halogenated
hydrocarbon as refrigerant in the early 1940s, the applicability of fixed-area expansion
devices increased. Gradually, They achieved popularity.
Fixed-area expansion devices have advantages such as low cost, elimination of moving
parts, a pressure equalization feature to reduce starting torque, and protection for compressor
motor overloading due to a maximum flow rate. On the other hand, the fixed geometry limits
the optimum operating conditions of a refrigerating cycle to only one point.
Among fixed-area expansion devices, the capillary tube is probably most widely used in
refrigerating systems. It is preferably used in smaller unitary hermetic equipment such as
household refrigerators and freezers, dehumidifiers, and conditioners. However, the use of the
capillary tube has been extended to include larger units such as unitary air conditioners in size
up to 10 tons (35 kW) capacity (ASHRAE Handbook - Equipment, 1988). The geometry of
the capillary tube used in small refrigeration systems is D = 0.64 - 2.0 mm and L = 1 - 6 m.
The most commonly used diameter of the capillary tube is 0.79 to 1.4 mm, and the length
manufacturers recommended is between 1.5 and 4.9 m (Schulz, 1985).
The short tube is mainly used in mobile air conditioners. In recent years, besides mobile
air conditioners, it has become widely used in residential air conditioners and heat pumps
(Aaron and Domanski, 1990).
The use of the orifice as an expansion device is relatively less compared with the
capillary tube and short tube. Benjamin and Miller (1941) conducted experiments of sharp
edged orifices of LID from 0.28 to 1 with saturated water at various upstream pressures. At an
upstream pressure of 14.1 bar, reducing downstream pressure from 14.1 to 1 bar, there was no
critical-pressure condition observed. This research suggests that a sharp-edged orifice with
2
LID <1 does not choke the flow at normal operating conditions, and therefore cannot be used
as an expansion device in vapor compression systems.
In large refrigerating systems, both the refrigerant mass flow rate and the pressure level
have to be maintained to within acceptable working limits. Numerous valve configurations
with adjustable throat areas have been developed to accomplish these controls. However, the
operation of these valves is based on sharp-edged orifices (Davies and Daniels, 1973).
Many investigations of fixed-area expansion devices have been carried out theoretically
and/or experimentally because the behavior of a fixed-area expansion device in a refrigeration
system is very complicated in spite of its simple construction. Henry (1970) summarized
several experimental observations as in Figure 1. For 0 ~ LID < 3, a superheated liquid jet is
surrounded by a vapor annulus and the pressure distribution is commensurate with the free
stream line flow of the liquid jet. For tubes between LID ~ 3 and LID ~ 12, the liquid jet
breaks up by shedding large bubbles at the surface and by forming vapor bubbles in the
middle of the jet. However, the pressure remains constant in this region. In the vicinity of LID
~ 12, the mixture takes on a thoroughly dispersed configuration.
L!C / / / {11 Vapor
Liquid _
p
~
Dispersed two-phase region
\\.---z O<UD<3 3 <UD <12 UD >12
Figure 1 Flow Patterns Characterizing the Discharge of Saturated or Subcooled Liquid through Sharp-Edged Orifices
The earliest studies on fixed-area expansion devices were related to orifices (Benjamin
and Miller, 1941; Rateau and Nostrand, 1905; and Stuart and Yarnall, 1936) with the interest
in metering fluid flow rates. The research on capillary tubes began to be active in 1940s
3
(Swart, 1946; Staebler, 1948; and Bolstad and Jordan, 1948). Since then, the study of fixed-
area expansion devices has been one of main research interests in refrigeration.
With the increasing need to replace ozone-depleting CFC and HCFC refrigerants,
refrigerators, air-conditioners, and heat pump systems have to be redesigned to accommodate
new replacement refrigerants. Consequently, research activities in fixed-area expansion
devices have been intensified recent two decades (Aaron and Domanski, 1990; Dirik et aI.,
1994; Kim and O'Neal, 1993, 1994a, and 1994b; Mei, 1982; Melo et aI., 1994 and 1995; and
Meyer and Dunn, 1996). It is the purpose of this paper to summarize activities published in
the literature regarding fixed-area expansion devices with emphases on the following topics:
• Mass flow rate through orifices;
• Mass flow rate through short tubes;
• Rating capillary tubes;
• Metastable flow;
• Friction factor and friction pressure drop;
• mathematical solution of fixed-area expansion device.
2 MASS FLOW RATE THROUGH ORIFICES
When liquid flows through an orifice without phase change, the mass flow rate equation
could be derived straight from the Berlouli equation. One form is given in ASHRAE
Handbook - Fundamentals (1997):
(1)
When the ratio of orifice diameter to conduit diameter p ::s; 0.2, the discharge coefficient
of sharp-edged orifices, Cd' is fitted based on the curve provided by ASHRAE Handbook -
Fundamentals (1997) as follows:
4
{0.9199 - 0.14256IogRe+ 0.016185(logRe)2
Cd = 0.6
(2)
The published papers about the mass flow rate of a fluid having partially evaporated at
upstream of, or during passage through an orifice are limited. Furthermore, the majority of
them are focused to the flow of steam-water mixtures through standard measuring orifices
(Benjamin and Miller, 1941; Burnell, 1947; Murdock, 1962; Romig et aI., 1966; Chisholm,
1967a, 1967b; and Collins, 1978). Work done in that area at ASHRAE will be presented soon.
Benjamin and Miller (1941) reported that the mass flow rate of saturated water through a
sharp-edged orifice could be calculated with sufficient accuracy by the formula used to
determine the flow of cold water through an orifice, and the discharge coefficient found for
saturated water was approximately the same as that generally used for cold water.
Some earlier researchers (Chisholm and Wastson, 1965; Romig et al., 1966; and Davies
and Daniels, 1973) thought that it was convenient to retain the form of Equation 1 when
dealing with two-phase situations. For a two-phase flow situation, partial vaporization takes
place at upstream of, during passage through, and/or at downstream of an orifice. The effect
of vapor-liquid composition on the flow rate was consequently reflected in the value of the
expansion factor. This approach yields
where y is defined as an expansion factor.
2p(Pup - Pc/own)
1- f34 (3)
The value of the expansion factor is unity if the flowing fluid has a constant density and
therefore no vaporization occurs during the whole flowing process. From the experimental
5
data with steam-water mixtures, Romig et al. (1966) correlated the following equation for the
expansion factor:
{ 0.968 + 0.112/3
y-0.94 + 0.20v'-0.0Iv'2
entirely liquid at upstream (4)
partially vaporized at upstream
Chisholm (1967a) developed a model for determining the expansion factor under the
condition where the density change of the gas or liquid through an orifice is negligible. The
theoretical development allows for the interfacial shear force between the phases. The model
can be used where the pressure drop over an orifice is small relative to the pressure at the
orifice. The difficulty of determining the expansion factor makes the Chisholm model less
usable. Davies and Daniels (1973) tried to use the Chisholm model for R-12 passing through
sharp-edged orifices, and no direct results were obtained from the Chisholm model. In the
case of the entirely liquid at upstream, they obtained the following equation based on
correlating experimental data:
y = 1-I.4xdown (5)
Equation 5 correlated the majority of the experimental data to within ±10%. Because the
data points are limited, the agreement of the predictions with the experimental data seems not
satisfied.
Studying boiling water flowing through nozzles, orifices and pipes, Burnell (1947)
proposed
(6)
6
where C is a surface-tension-dependent constant, which is
(7)
where K is an experimentally determined coefficient. In Burnell's study, K = 0.264.
Using more accurate values of water surface tension, Kinderman and Wales (1957)
proposed the following modification to Equation 7:
C=K~ (8) 0"200
where K = 0.284
Krakow and Lin (1988) observed that the mass flow rate of a refrigerant through an
orifice or a short tube, used as a throttling device in a heat pump, was primarily dependent on
the upstream not on the downstream conditions, that indicates choked flow conditions in their
data. The characteristics of the flow through an orifice were thus similar to those of the flow
through a capillary tube. Furthermore, observed mass flow rates were greater than those
calculated, assuming that the flow is sonic at a plane of the orifice. They developed the same
theoretical model for refrigerant flow through an orifice and a short tube based on the
assumption that when the upstream refrigerant is subcooled, the exit plane of the orifice is
saturated liquid, and when the upstream refrigerant is two-phase, the exit plane is sonic. Their
model is consistent with capillary tube models.
Obermeier (1990) developed theoretical equations for critical flow rates of refrigerants
flowing through tubes and orifices. They concluded that for a given thermodynamic state, not
one, but a range of critical flow rates existed.
7
We use the Aaron and Domanski (1990) model (see Equation 12) for R-134a flowing
through small orifices with diameters from 0.03 to 0.103 mm, and achieve success. The work
will be reported on another paper.
3 MASS FLOW RATE THROUGH SHORT TUBES
Bailey (1951) studied the flow of saturated and nearly saturated water through short
tubes with 5 < LID < 20. When keeping the upstream pressure to be constant and varying the
downstream pressure, he noted three distinct flow regimes as shown in Figure 2. Curve AB
represents the conventional single-phase flow relationship described by Equation 1, where the
fluid is subcooled at all points in the tube. Near point B, the pressure near the vena contracta
(the smallest flow area caused by sudden contraction) was at a value very close to Ps• When the
downstream pressure was varied near points B and C, Bailey observed an instability in the
flow and the operating points shifting back and forth from curve AB to CD. Further reduction
of the downstream pressure from point C to D, the flow relationship described by Equation 1
was reestablished. D is the point where the critical flow occurs. Continuing to decrease
downstream pressure from point D has no effect on the mass flow rate.
Zaloudek (1963) investigated water flowing through short tubes with LID < 6, and
reported the same findings as in Figure 2 except the stable operating points between curves
AB and CD, as represented by the dotted line. Observing no difference in the mass flow rate
from the transitional region between curves AB and CD, Zaloudek termed the phenomenon as
first-step critical flow or simply first-stage choking. The region from D to E, which Bailey
termed as critical flow, was termed as second-step critical flow or simply second-stage
choking by Zaloudek. Zaloudek suggested that the mass flow rate in the first-step critical
region could be calculated by
(9)
8
where Cd is approximately 0.61 to 0.64 for water.
D E
o~---------------------------Prssure differential across short tube
Figure 2 Operating Curves for a Short Tube at Constant Upstream Pressure, Bailey (1951)
Mei (1982) investigated the flow of initially subcooled R-22 flowing through short tubes
with 7.5 < LID <11.9. With experiments based on a three-ton split-system heat pump, he
observed that the first-stage choking occurred at the liquid subcooling temperature of 22.2 °C
and no second-stage choking took place. Utilizing Equation I as the model for AT < 22.2 °C,
and Equation 9 as the model for AT > 22.2 °C, Mei obtained the following equations based on
his own experimental data:
Cd = 0.4 - 0.007364(~Pup - Pt/own -.J1034.2) + 0.0108AT AT 5:. 22.2 (10)
and
Cd = 0.9175 -0.00585AT 22.2 < AT < 27.8 (11)
Aaron and Domanski (1990) adopted Equation I to short tubes with neglecting ~,
correcting Cd' and substituting Pf , the pressure before flashing occurs, for P down' Equation I is
9
used for incompressible flow. Using Pf instead of P down avoids violating the incompressible
flow assumption. They proposed the following equation as the mass flow rate model of short
tubes:
(12a)
which is in essence
(12b)
where Cd and Cs (or Pf) are correlated with experimental data.
Aaron and Domanski correlated their experimental data with R-22 in the range of 5 <
LID < 20, 1.09 < D < 1.7 mm, 5.6 < AT < 13.9 °C, 14.48 < Pup < 20.06 bar, 2.07 bar < Pdown
< Ps, and 0 ~ Depth < 0.508 mm, and obtained:
2 Cs = 1+ 12. 599Subl.293 - 0.122ge-o.0169(L I D) - 0.04753EvapO.6192 (13a)
and for sharp-edged and 45° chamfered geometries
Cd = 1+ 0.0551(LI D) 0.5844 (Depth 1 D)0.2967 (13b)
where
Sub = (Ts-Tup) 1 Ts (T in absolute temperatures, K)
Evap = (P s -P down) 1 P s (T in absolute pressures, K)
For sharp-edged tubes, Depth = 0, therefore Cd =1.
10
Aaron and Domanski claimed that their correlation described ninety-five percent of 929
experimental data to be within ±5%.
Using the same form of mass flow rate as Aaron and Domanki's, Kim and O'Neal
obtained the correlations of C for sharp-edged and 45° chamfered short tubes with R-22 s
(l994a)
(p J-O.485( )-0179 (P J2.7I6
1.005 + 5.7367 ;c'P ~. SUbcO.9948 + 0.268 ;c'P -Cs = (l4a)
2 0.226e -0.021(D I Dref)(L/ D) _ 0.092Evapc
Cd =1+0.02655(LI D) 0.70775 (Depth 1 D) 0.22684 (l4b)
and for sharp-edged short tubes with R-134a (l994b)
Cs = (
p J-O.3296( )-0.1758
1.0156 + 10.0612 ;c'P ~ SUbcl.0831 -(l5a)
2.9596 0.1802e -0.00214(DI Dref)(L/ D) _ 0.0754Evapc
I ])~
-04474 0.38210( .£ )
Cd = ~-2.6519X..{1+5.7705(~)· (1~:" ~;:J D (l5b)
where
Subc = (Ts-Tup) 1 Tc (T in absolute temperatures, K)
Evapc = (Pc-P down) 1 Pc (T in absolute pressures, K)
11
Some experimental conditions of Equations 14 and 15 are 5 <LID < 20, 1.092 ::::; D ::::;
1.717 mm, and ~T::::; 13.9 °C to "up::::; 0.1. For Equation 14, 14.48::::; Pup::::; 20.06 bar, and for
Equation 15, 8.96 bar ::::; Pup::::; 14.48 bar. The equations described approximately ninety-five
percent of their experimental data of the sharp-edged short tubes and ninety percent of those
of the 45° chamfered short tubes to be within ±5%.
Mei (1982) found first-stage choking phenomena in his experiments but pointed out that,
second-stage choking did not occur. Aaron and Domanski (1990) claimed second-stage
choking was repeated in their experiments but the flow was found to be slightly sensitive to
the downstream pressure once the critical pressure was reached. The mass flow rate typically
increased 3% to 8% from when the downstream pressure was near Ps to when the downstream
pressure was at the minimum value tested (about 200 kPa), and 100% choked flow was not
obtained. They used the term "choked flow" in order to maintain the same terminology as
customarily used in the previous literature on refrigerant flow through short tubes and
capillary tubes, where small flow dependency on downstream pressure has typically been
assumed negligible. For example, experimental data from Bolstad and Jordan (1948) and Pate
and Tree (1988) show that the flow of refrigerant through capillary tubes is not ideally
choked. Aaron and Domanski did not find the first-stage choking in their experiments. They
thought it was because their study concentrated on conditions where the downstream pressure
was below the saturation pressure. Kim and O'Neal (1994) also pointed out that the
refrigerant flow through short tubes did not satisfy ideal choked-flow conditions. They found
the mass flow rate increased 1% for LID=19 and 7% for LID=5.5, with the downstream
pressure reductions beyond Ps to the minimum downstream pressure (490 kPa).
4 RATING CAPILLARY TUBES
For mass flow through capillary tubes, no simple empirical correlations like those of
orifices and short tubes are found. Assuming adiabatic flow with saturated liquid or two-
12
phase fluid at the upstream and critical pressure at downstream, Whitesel (1957) developed a
formula for R -12 and R -22 flowing through capillary tubes
(16)
where
a=
[ J0.333
190 47.9 {1_XO.167)exp( ~p XO. 333 X 10-6] ~p up 47.9 up
[ JO.333
190 47.9 {1_xo.333 )2 exp(1.2Pup XO. 333 XI0-6] ~p up 47.9 up
for R-12
(17)
for R-22
Hopkins (1950) presented comprehensive ratings covering capillary tube refrigerant flow
capacities for R-12 and R-22. The rating curves presented cover the variables of tube
diameter, length, saturated condensing temperature, saturated evaporator temperature, amount
of liquid subcooling, and flow rate. The curves can be used to calculate flow rate directly
from a given capillary selection and flow condition or used to determine a capillary selection
from a flow condition and flow rate.
Based on the Hopkins' work (1950) for capillary tube selection, Whitesel (1957) and
Cooper et al. (1957) developed rating curves. Later, Rezk and Awn (1979) improved these
charts. Whitesel's work (1957) was later coupled with Hopkins' work, yielding the well
known ASHRAE rating curves for R-12 and R-22 (ASHRAE Handbook - Equipment, 1988).
13
5 METASTABLE FLOW
When an initially subcooled refrigerant flows through an expansion device in a
refrigerating system, the thermodynamic equilibrium flash point occurs not at but after the
point where the refrigerant pressure equals the saturation pressure corresponding to the
refrigerant temperature. In other words, the pressure at the point where flashing begins is
lower than the saturated pressure. This state of the fluid is classified as the metastable state, as
differentiated from a stable equilibrium state. The metastable phenomenon has remarkable
effect on the mass flow rate, and the downstream pressure and quality. Based on the
nucleation theory and experimental data of refrigerant-12, Chen et al. (1990) correlated the
following equation for calculation the underpressure of vaporization, (Ps-Pv):
(p p) fkT (v J ( J-O.208( )-3.18 8 - v '1/1\,.1 8 = 0.679 g ReO.914 AT8C ~
(]"3/2 V - v T D g 1 C
(18)
where D' is the reference length which is defmed as
(19)
Equation 18 is valid in the region of0.464xl04 < Re < 3.76x104, 0 < ATsc < 30.6 °C, and
0.66 < D <1.17 mm.
The Chen model has been used as a metastable model by several studies. Li et al. (1990)
used it to their mathematical model for capillary tubes with R-12. Dirik et al. (1994) and Yin
(1998) used it to their mathematical models for capillary tubes and short tubes with R-134a,
respectively. All of them reported the agreement of the model predictions with experimental
data.
14
Bittle and Pate (1996) incorporated Equation 18 into the flow model for predicting R-
134a, R-22, R-152a, and R-41Oa flowing through capillary tubes. They found it improved
mass flow rate predictions between 1 % and 5.5% for mass flux less than 0.42 kgl(s.m2) and
roughly within 1 % for mass flux greater than 0.42 kgl(s.m2). At the higher mass flux levels
measured with R-410a and R-22, the flow model consistently underpredicted the measured
data by 4% to 6%. They thought this was because the flow range went beyond that of the
Chen model.
Melo et a1. (1995a) compared predictions of Equation 18 with their own experimental
data with R-600a, R-134a, and R-12 flowing through capillary tubes of 0.606 :::;; D:::;; 1.05 mm
• in the range of ~ T = 2 -16°C, m = 2 - 6.5 kglh, and Re = 5300 - 9600. They found that the
predicted underpressures of vaporization varied only slightly with Re. However, the
experimental data appeared to vary randomly. The Chen model was unable to predict the
experimental data properly even allowing a relative error of ± 26%. Melo et a1. thought this
was due to the random variation of the reference length and was not related to the refrigerant
type.
Meyer and Dunn (1996 and 1998) examined experimentally the mass flow rate ofR-22
in an adiabatic capillary tube. They concluded that the metastable region of an operating
capillary tube was much more predictable than previously reported in the literature. Taking
the history of system operation into account, their experimental curves revealed a hysteresis
effect in the mass flow rate as the level of inlet subcooling is increased and decreased. As the
inlet level of subcooling is decreasing, it is possible to create and lengthen a metastable region
in which liquid flow exists where it might otherwise be two-phase. The longer liquid length
resulted in the higher mass flow rate. For their particular refrigerant-tube combination, the
mass flow rate for a given state point while the subcooling is decreasing can be as much as
about 10% higher than the same conditions while the subcooling is increasing. Meyer and
Dunn's contributions are helpful to understand the random variation of the mass flow rate at a
given state point.
15
Liu and Bullard (1997) observed that the mass flow hysteresis effect on a non-diabatic
capillary tube was as large as 7%, and the effect of capillary tube hysteresis on refrigerator
system thermodynamic cycle efficiency was as large as 3%.
6 FRICTION FACTOR AND FRICTION PRESSURE DROP
Two-phase friction pressure drop calculation is needed for studying fixed-area expansion
devices in many aspects (Hopkins, N. E., 1990; Mikol, E. P., 1963; and Meyer and Dunn,
1996). The common approach for calculating two-phase friction pressure drop is to utilize
single-phase friction factor models with some modifications. The single-phase friction factor
can be expressed as either the Darcy-Weisbach friction factor or the Fanning friction factor.
The former is four times of the latter.
6.1 Single-Phase Friction Factor
Many equations for the Darcy-Weisbach friction factor have been developed. The
Blasius' equation (20) and Filonenko's equation (21) are widely used for the turbulent flow in
smooth tubes (Zukauskas and Karni, 1989).
(20)
f = {1.821og Re-l.64y2 (21)
The "smooth" here means that the wall roughness elements are so small that their
influence does not extend beyond the laminar sublayer.
There are other opinions about the applicable Reynolds number range of Blasius'
equation (20) and Filonenko's equation (21). For example, Incropera and DeWitt (1996)
16
introduced Re :s; 2x104 for Blasius' equation (20) and 3000 :s; Re :s; 5x106 for Filonenko's
equation (21).
Moody and Princeton (1944) introduced Colebrook's equation. Colebrook, in
collaboration with C. M. White, developed an equation which agrees with two extremes of
roughness in transitional zone.
1 21 (8 2.51 J 10.5 =- og 3.7D + 10.5Re (22)
Since Colebrook's equation (22) cannot be solved explicitly for f, Althul has developed
an explicit formula for turbulent flow which was modified by Tsal (ASHRAE Handbook
Fundamentals, 1993)
/ =0.11('!"-+ 68)°·25 D Re
{/ 1= I = 0.0028 + 0.85/
(23)
if / ~ 0.018
if / < 0.018
Friction factors obtained from Althul's modified equation are within 1.6% of those
obtained by Colebrook's equation.
Churchill (1977) proposed an equation that combines laminar and turbulent regime and is
applicable to all relative roughness, which agrees with the Moody diagram (Moody and
Princeton, 1944)
17
{ }
11I2 12 16 16 -3/2
-8 8 + 2457ln 1 + 37,530 f - (RJ [(. (7!Re)" + 0.278/ D) (Re)] (24)
Figure 3 compares Blasius' equation (20), Filonenko's equation (21), Althul's modified
equation (23), and Churchill's equation (24). It is seen that Blasius' equation (20) can be valid
for Re <1.5x105, and Filonenko's equation (21) can be used within Re > 8xl03.
Althul's modified equation (23) has apparently lower prediction than Churchill's
equation (24) for large relative roughness conditions. When relative roughness & ID ~ 0.001,
the predictions by Althul's modified equation (23) and Churchill's equation (24) differ only
slightly. It is better to limit the application of Equation (23) to & ID ~ 0.001.
-...... 0.07
0.06
o t5 ~ 0.05 c o U 0.04 ·c u.
0.03
0.02
Relative roughness = 0.05
/ 0.01
-e-Blasius --*- Filonenko -tr-Churchill -Altshul's modified
O. 0 ~ 0'-::3~--'----L--'-"""""-'-'-.L...L...:---L---'---"-""""'~"",--="-....&.-.--'-....L-.JL.....L...JU:::W1 0 6
Reynolds number, Re
Figure 3 The Comparison of Friction Factor Equations
6.2 Two-Phase Friction Pressure Drop
18
Martinelli et a1. (1944) proposed the following equation for the pressure drop of
isothermal two-phase flow:
(25)
pressure drop per unit length which would exist if the gaseous phase is assumed to flow alone,
and ¢ g is a parameter which is a function of a dimensionless variable, I(, • The variable I(, is a
function of the ratio of mass flow rates of the liquid and gas, the ratio of densities of the
liquid and gas, the ratio of viscosities of the liquid and gas, and tube diameter.
Improving Equation (25), Lockhart and Martinelli (1949) proposed the following
equation for the pressure drop of isothermal two-phase flow:
(26)
where (~) I is the pressure drop per unit length which would exist if the liquid phase is
assumed to flow alone, and ¢l is a two-phase frictional multiplier which is a function of a
dimensionless variable, X, defined as
(27)
The variable X, similar to the variable 1(" is also a function of the ratio of mass flow rates
of the liquid and gas, the ratio of densities of the liquid and gas, the ratio of viscosities of the
19
liquid and gas, and tube diameter. The correlations of the variables X and X were given by the
authors (Martinelli et al. 1944; and Lockhart and Martinelli, 1949).
The Lockhart and Martinelli approach is successful for may flow conditions (Baroczy,
1966; Chen and Spedding, 1981; Chisholm, 1968; Davis, 1990; Dukler et aI., 1964; Marie,
1987; Lin et al., 1991; Souza et aI., 1993 and 1995; and Chang and Ro, 1996). Chisholm
(1967 -68) evaluated "Despite the large volume of work published in the field of two-phase
flow during the last 20 years, a recent investigation has shown that one of the earliest
procedures for predicting friction pressure gradient in two-phase flow, that of Lockhart and
Martinelli, remains the most successful."
Based on experimental data of air and liquids including benzene, kerosene, water, and
various oils in pipes varying in diameter from 1.5-25.8 mm, Lockhart and Martinelli provided
coordinates of ~ and f vs. Parameter X. De Souza et al. (1993, 1995) made some
improvements based on experimental data with refrigerants R-12, R-22, R-134a, MP-39, and
R-32/125. Li et al. (1990), Lin et al. (1991),and Chang and Ro (1996) presented different
models for the two-phase frictional multiplier, based on which we obtain a generalized
equation for the two-phase frictional multiplier as follows:
(28)
where two-phase friction factor ~ is calculated by a single-phase friction factor model with
the Reynolds number calculated by
Re= 4m PI D
Two-phase viscosity models reported in the published literature include
(i) the McAdams model (McAdams et al. 1942), given by
20
(29)
(ii)
1 1-x x -=--+-PI PI Pg
(iii) the Cicchitti model (Cicchitti et aI., 1960), given by
(iv)
(v) the Dukler model (Dukler et aI., 1964), given by
(vi)
xv g Pg + (1- x)v I PI PI = ---"'--~-----
vm
(30)
(31)
(32)
Another main approach for determining two-phase pressure drop due to the friction is
using the following equation (Niaz and de Vahl Davis; Bittle and Pate, 1996; and Wijaya,
1991):
(33)
where two-phase friction factor ~ is determined in the same way as just described.
Mikol (1963) analyzed that the inside diameters of refrigeration restrictor tubes were
large enough to be considered as "usual pipe", not "capillary" in the sense used by physicists
because even the smallest of the tube bores is approximately 100 or more times larger than the
mean free path of molecules. In other words, the friction factor correlations developed for
"usual pipes" are valid for refrigerant expansion devices. Mikol also pointed out that the
largest contributors to error in friction factors were tube inside diameter measurement and
21
mass flow rate measurement. A I % error in either measurements could result in ±5% and
±2% error in the friction factors, respectively.
6.3 Tube Roughness and Diameter Uncertainties
Tube roughness may cause a large uncertainty in the determination of friction factors. A
number of researchers (Mikol, 1963; Scott, 1976; and Sweedyk, 1981) suggested that short
tubes and capillary tubes made of drawn copper tubing of small bore, in general, could not be
considered smooth for purposes of friction factor selection.
Moody and Princeton (1944) estimated that the roughness of drawn brass and copper
tubing as of the order of 6xl0-5 in. Mikol (1963) experimentally determined the roughness of
0.055 inch drawn copper tubing to be 2.1xl0-5 in., which combined with the mean inside
diameter gives a relative roughness 3.8xl0-4. Sweedyk (1981) measured the roughnesses of
tubes from different manufacturers and different processes, and reported the roughnesses from
3.5x 10-6 to 7.3xl0-5 in. The variability is surprisingly large.
Meyer and Dunn (1996) implied that the Moody diagram (1944) would be successful in
giving an accurate surface roughness of a tube. In other words, the tube roughness can be
determined by measuring its single-phase friction factor and then reading the Moody diagram
according to the friction factor.
Liu and Bullard (1997) pointed out that it was necessary to determine actual diameters of
capillary tubes before analyzing the data from them because manufacturer's ± 0.001 inches of
tolerance in tube diameters could introduce up to ±10% uncertainty in cross sectional area and
mass flow rates.
7 MATHEMATICAL SOLUTION OF FIXED-AREA EXPANSION DEVICES
In the mathematical solution of engineering problems, one can identify three major levels
of approaches:
(1) Exact or rigorous solution
22
(2) Modeling
(3) Experimental correlation
7.1 Exact or Rigorous Solution
The term exact or rigorous solution in fluid mechanics is used for the exact solution of
the Navier-Stokes equation. Solutions of the Euler equation, that is, the Navier-Stokes
equation for zero viscosity are also considered exact solutions. Exact solutions of the Navier
Stokes equation are very rare and only simple problem can be solved exactly. The flow of
refrigerants through fixed-area expansion devices is generally turbulent and two-phase, where
the exact solution is not realistic therefore no related literature is searched.
7.2 Modeling
A two-phase flow is governed by equations representing conservation of mass,
conservation of momentum, and conservation of energy, the equation of state, the equation of
entropy (the second law of thermodynamics), and equations representing boundary conditions
such as the equation of critical mass flux (or the equation of sound velocity). Some
simplifications to the equations are needed in order to make a two-phase flow problem
tractable by analytical and numerical means. These simplifications will result in some kind of
approximations. Solving engineering problems by this approach is termed modeling. In the
quest for more accurate, but yet, sufficiently simple approaches to the solution of two-phase
flow problems, modeling is of utmost importance.
Approximated models for the modeling of fixed-area expansion devices range all the way
from homogeneous eqUilibrium model (HEM) to methods that attempt to represent all of the
non-equilibrium phenomena. In between are many hybrid models that treat some of the non
equilibrium aspects by using assumptions or empiricism. Among them, the HEM is the
earliest and most widely used one (Bolstad and Jordan, 1948; Marcy, 1949; Henry, 1970;
Leung et al., 1986, 1988, and 1990; Krakow and Lin, 1988; Lahey and Drew, 1990; Dirik et
al., 1994; Bansal and Rupasinghe, 1998; and Sami and Tribes, 1998).
23
There is no absolute criterion for a good model. It depends on the purpose of the model,
the accuracy needed, and the constraints such as time and cost to obtain a solution (Taite I and
Tel-Aviv, 1994). Hundreds of figures appear in the literature showing comparisons among
model predictions and/or experimental data. However there is no systematic evaluation of all
data to determined if quantitative criteria can be developed to guide the user who wishes to
know how accurate a certain estimate is likely to be under various circumstances (Wallis,
1980).
The HEM treats a two-phase mixture as a pseudo-fluid that can be described by the same
equations as an equivalent single-phase flow. The two phases are everywhere in equilibrium
with equal velocities and temperatures. Refrigerant properties such as quality, specific
volume, and enthalpy can be obtained from data tables or some general equations of state.
Nowadays, some standard software such as EES and REFPROP make the calculation of
refrigerant properties fairly easy.
Assuming that the flow is one-dimensional steady flow, gravity effect is negligible, no
shaft work exists, and D = constant, one can obtain the following equations of the HEM:
where
~G=O dz
du dP GA-=-A--r 7rD
dz dz W
24
conservation of mass (34)
conservation of momentum (35)
conservation of energy (36 )
(37)
The relation between the shearing force 'tw and the Darcy-Weisbach friction factor f is as
follows (Pai, 1981):
f=8~ pu2 (38)
Substituting the above expression into Equation 35, the momentum equation reduces to
G 2 d v m = _ dP _ G 2!, v m
dz dz 2D (39)
where
(40)
If ~q in energy equation (36) equals to zero, there is no heat conduction through the wall
of the expansion device. That is, the flow is adiabatic. Otherwise, it is non-adiabatic, and the
heat transfer equations representing the boundary condition must be given to solve the
problem.
The HEM works well for predicting the critical mass flux, Gc, in capillary tubes where
there is sufficient time for equilibrium to be achieved. However, little larger errors will occur
for short pipes and orifices, where there is insufficient time for the vapor formation to proceed
to equilibrium (Wallis, 1980). All of the two-phase critical flow theories are based on some
form of the single-phase critical flow rate equation:
(41)
25
The critical flow of a single-phase gas usually occurs when the Mach Number is equal to
one at the smallest cross-section. Even though speeds are high, molecular relaxation
phenomena are sufficiently rapid for the gas to be regarded as in thermodynamic equilibrium.
Two-phase critical flow is more complicated. The relaxation time for the formation of
new interfaces, heat, mass, and momentum transfer, and the evolution of flow patterns is
comparable with the time spent by the fluid in the "critical" region of rapid property change.
Although it may be possible to defme a mathematical condition of criticality at one location,
an entire region (that may include parts of the upstream system) plays a role in determining
how this condition is approached (Walls, 1980).
Just as the HEM is based on the ideal case of complete interphase equilibrium, it is
possible to derive a set of other models by making other limiting assumption, such as the
homogeneous frozen model (HFM) and the homogeneous isentropic model (HIM). This
avoids the necessity for taking any account of the details of the non-equilibrium phenomena.
7.3 Experimental Correlation
The approach of the experimental correlation, which uses equations correlated from
experimental data to solve engineering problems, is very attractive and useful. It is preferred
to correlate experimental data as a relation among dimensionless parameters so that the
relation is universally correct in the experimental range of the dimensionless parameters,
which may drastically reduce experimental load and difficulties. For example, the pressure
drop for a single-phase flow in a tube is of the form:
oP - = F(u,D,p,f-l,s) oz
In dimensionless form this relation can be replaced by
26
(42)
f = F(Re,&/ D) (43)
However, for some two-phase flow problems it is very difficult to obtain a dimensionless
relation because of the large number of parameters so that a dimensional relation has to be
chosen.
8 SUMMARY
Fixed-area expansion devices are widely used in refrigerators, air-conditioners, and heat
pumps of up to 3.5 kW capacity with variable operating conditions. A fixed-area expansion
device can be categorized by its length-to-diameter ratio, LID. An orifice has an LID < 3. A
short tube is defined as having a length-to-diameter ratio of3 < LID < 20. A capillary tube has
an LID > 20. This paper gives a detailed review of the literature on fixed-area expansion
devices with emphases on topics of the mass flow rate through orifices, the mass flow rate
through short tubes, metastable flow correction, the friction factor of single-phase flow, and
the pressure drop of two-phase flow.
Two-phase mass flow rate through an orifice can be calculated by Equation 3 and
Burnell's equation (6). Aaron and Domanski's equation (12) is a successful model for two
phase mass flow rate through a short tube.
For mass flow through capillary tubes, no simple empirical correlations like those of
orifices and short tubes are found. The rating charts are one of useful approach for capillary
tube selection.
The metastable phenomenon has remarkable effect on the mass flow rate, and the
downstream pressure and quality. The mass flow rate in the metastable region varies
randomly. The experimental curves reveal a hysteresis effect on the mass flow rate as the
level of inlet subcooling is increased and decreased. As the inlet level of subcooling is
decreasing, it is possible to create and lengthen a metastable region in which liquid flow
exists where it might otherwise be two-phase. The longer liquid length resulted in the higher
27
mass flow rate. The mass flow rate for a given state point while the subcooling is decreasing
can be as much as about 10% higher than the same conditions while the subcooling is
increasing. The Chen equation (18), developed from data for R-12, is the only model for
correcting metastable flow. It can improve mass flow rate predictions up to 5.5%. In some
flow range, the Chen equation (18) is not satisfied. Further research on metastable flow
correction is needed.
There are a number of equations for single-phase friction factor. Figure 3 compares
several single-phase friction factor equations. Churchill's equation 24 is complicated but has
the widest applicable range. There are two common approaches for determining two-phase
friction pressure drop. One is the Lockhart and Martinelli approach, which utilizes the two
phase frictional multiplier to calculate two-phase friction pressure drop. The other is similar to
single-phase pressure drop calculation method, where the two-phase friction factor is the
same form as the single-phase friction factor with Reynolds number calculated by two-phase
viscosity. The Lockhart and Martinelli approach is more successful. However, more studies
should be done to extend the Lockhart and Martinelli approach to wider refrigerant
application range.
In the mathematical solution of engineering problems, one can identify three major levels
of approaches: exact or rigorous solution, modeling, and experimental correlation. For
refrigerants flowing through expansion devices, the approach of the exact or rigorous solution
is not realistic, the approach of the modeling is of utmost importance, and the approach of the
experimental correlation is very useful in some aspects. Of the approximated models for the
modeling, the HEM is the earliest and most widely used one
The presentations provided here are by no means complete. The purpose here is just to
provide readers useful links to previous relative work. For more details, one has to consult the
original papers.
ACKNOWLEDGMENTS
28
The work is in the guidance of Professors Predrag S. Hrnjak and Clark W. Bullard, who
made many contributions to this paper. Their contributions are gratefully acknowledged.
NOMENCLATURE
Cd = discharge coefficient
C =P IP s f s
D = throttle diameter, m, except pointing out
D' = reference length
Dref = 1.35xlO-3 m
Depth = inlet chamfer depth, m, except pointing out
Evap = (Ps-Pout) / Ps
Evapc = (Pc-PouJ / Pc
(T in absolute pressures)
(T in absolute pressures)
f = Darcy-Weisbach fraction factor
ff = Fanning fraction factor
G = mass velocity (= density x velocity)
k = Boltzman's constant (= 1.380662xlO-23 JIK)
L = length, m, except pointing out
m = mass flow rate
P = pressure, Pa, except pointing out
Re = Reynolds number
Sub = (Ts-Tin) / Ts
Subc = (Ts-Tin) / Tc
(T in absolute temperatures, K)
(T in absolute temperatures, K)
T = Temperature, K, except pointing out
u = velocity
v = specific volume
v' = ratio of the actual specific volume at the upstream tap of the test orifice to the
29
specific volume of pure liquid at the upstream temperature.
x = refrigerant quality
X = two-phase flow modules defined by Equation 14
dP = pressure drop
( ~ ) g ~ pressure drop per unit length due to gas flowing at a rate ;" g with a density P,
(~} = pressure drop per unit length due to liquid flowing at a rate :nl with a density PI
( ~ ) t = pressure drop per unit length during two-phase flow
d T = subcooling
Greek Symbols
p = ratio of orifice diameter to conduit diameter
P = density
8 = roughness oftubes
'tw = shearing force
<J = surface tension
<J175 = liquid surface tension at 12.07xl05 Pa (175 psia)
<J200 = liquid surface tension at 13.79xl05 Pa (200 psia)
~ = two-phase frictional multiplier
X = two-phase flow modules
Subscripts
c = critical state, critical flow
down = downstream
f = at the point before flashing occurs
g = gas or vapor
I = liquid
30
m = average
s = saturated state
t = two-phase
up = upstream
v = vaporization
REFERENCES
Aaron, D. A. and Domanski, P. A., 990, Experimentation, analysis, and correlation of
refrigerant-22 flow through short tube restrictors, ASHRAE Transactions, Vol. 96, Part 1:
729-742.
ASHRAE Handbook - Equipment, 1988, Chapter 19, American Society of Heating,
Refrigerating, and Air-conditioning Engineers, Atlanta.
ASHRAE Handbook - Fundamentals, 1997, Chapter 2, American Society of Heating,
Refrigerating, and Air-conditioning Engineers, Atlanta.
ASHRAE Handbook - Fundamentals, 1993, Chapter 32, America Society of Heating,
Refrigerating, and Air-conditioning Engineers, Atlanta: 32.5.
Bailey, J. F., 1951, Metastable flow of saturated water, Transactions of the ASME, 73(Nov.):
1109-1116.
Bansal, P. K., and Rupasinghe, A. S., 1998, An homogeneous model for adiabatic capillary
tubes, Applied Thermal Engineering, 18(3-4): 207-219.
Baroczy, C. J., 1966, A simple frictional pressure drop calculation method, Int. J. Multiphase
Flow, 8:83-87.
Benjamin, M. W. and Miller, J. G., 1941, The flow of saturated water through throttling
Orifice, Transactions of the ASME, 63(5): 419-426.
Bittle, R. R. and Pate, M. B., 1996, A theoretical model for predicting adiabatic capillary tube
performance with alternative refrigerants, ASHRAE Transactions, Vol. 102, Part 2: 52-
64.
31
Bolstad, M. M., and Jordan, R. C., 1948, Theory and use of the capillary tube expansion
device, Refrigerating Engineering, 56(6): 519-523, 552.
Burnell, J. G., 1947, Flow of boiling water through nozzles, orifices and pipes, Engineering,
Vol. 164: 572-576.
Chang, S. D., and Ro, S. T., 1996, Pressure drop of pure HFC refrigerants and their mixtures
flowing in capillary tubes, Int. J. Multiphase Flow, 22(3): 551-561.
Chen, J. J. J., and Spedding, P. L., 1981, An extension of the Lockhart-Martinelli theory of
two-phase pressure drop and hold up, Int. J. Multiphase Flow, 7: 659-675.
Chen, Z-H., Li, R-Y, Lin, S., and Chen, Z-Y, 1990, A correlation for metastable flow of
refrigerant-12 through capillary tubes, ASHRAE Transactions, Vol. 96, Part 1: 550-554
Chisholm, D., 1967a, Flow of incompressible two phase mixtures through sharp-edged
orifices, J. Mechanical Engineering Science, 9(1): 72-78.
Chisholm, D., Dec. 1967b, Flow of compressible two-phase mixtures through throttling
devices, Chemical and Process Engineering Science: 73-78.
Chisholm, D., 1967-68, The influence of mass velocity on friction pressure gradients during
steam-water flow, Proc Instn Mech Engrs., 182(3H): 336-341.
Chisholm, D., and Watson, G. G. 1965, The flow of steam-water mixtures through sharp
edged orifices, Symposium on Two-Phase Flow, University of Exeter, Vol. 2 (June),
G201-G222:21-23.
Churchill, S. W., 1977, Friction-factor equation spans all fluid -flow regimes, Chemical
Engineering, No. 7:91-92.
Cicchitti, A., Lombardi, C., Silvestri, M., Soldaini, G., and Zavattarelli, 1960, Two-phase
cooling experiments-pressure drop, heat transfer, and burnout measurements, Energia
Nucleare, 7(6): 407-425.
Collins, R. L., May 1978, Choked expansion of subcooled water and I. H. E. flow model, J.
Heat Transfer, Vol. 100: 275 -280.
Cooper, L. Chu, C. K., and Bristen, 1957, Simple selection method for capillaries derived
from physical flow conditions, Refrigerating Engineering, 65(7): 37-46.
32
Davies, A, and Daniels, T. C., 1973, Single and two-phase flow of dichlorodifluoromethane,
(RI2), through sharp-edged orifices, ASHRAE Transactions, Vol. 79, Part 1: 109-123.
Davis, M. R., 1990, Wall friction for two-phase bubbly flow in rough and smooth tubes, Int.
J. Multiphase Flow, 16(5): 921-927.
Dirik, E., Inan, C., and Tanes, M. Y., 1994, Numerical and experimental studies on adiabatic
and nonadiabatic capillary tubes with HFC-134a, Proceedings of the International
Refrigeration Conference, Purdue University: 365-370.
Dukler A. E., Wicks, M., and Cleveland, R. G., 1964, Friction pressure drop in two-phase
flow, A. 1 Ch. E. 10(1): 38.
Henry, R. H., 1970, The two-phase critical discharge of initially saturated or subcooled
Liquid, Nuclear Science and Engineering, 41: 336-342.
Incropera, F. P. and DeWitt, D. P., 1996, Fundamentals of heat and mass transfer, John
Wiley & Sons, 4th Edition: 424, 445.
Kim, Y. and O'Neal, D. L., 1994b, An experimental study of two-phase flow ofHFC-134a
through short tube orifices, AES-Vol. 29, Heat Pump and Refrigeration Systems Design,
Analysis, and Applications, ASME: 1-8.
Kim, Y. and O'Neal, D. L., 1994a, Two-phase of R-22 through short tube orifices, ASHRAE
Transactions, Vol. 100, Part 1: 323-334.
Kim, Y. and O'Neal, D. L., 1994b, A semi-empirical model of two-phase flow of refrigerant-
134a through short tube orifices, Experimental Thermal and Fluid Science, 9(4): 426-
435.
Kinderman, W. J., and Wales, E. W., 1957, Fluid flow through two orifices in series III - the
parameters of metastable and stable flow of hot water, Transactions of the ASME,
79:183-190.
Krakow, K. I., and Lin, S, 1988, Refrigerant flow through orifices, ASHRAE Transactions,
Vol. 94, Part 1: 484-506.
33
Lahey, Jr., R. T., and Drew, D. A., 1990, The current state-of-the -art in the modeling of
vapor/liquid two-phase flows, In Proceedings of the ASME Winter Annual Meeting, 90-
WAIHT-13.
Leung, J. C., 1986, A generalized correlation for one-component homogeneous equilibrium
flashing choked flow, AIChE Journal, 32(10): 1743-1746.
Leung, J. C., and Grolmes, M. A., 1988, A generalized correlation for flashing choked flow of
initially subcooled liquid, AIChE Journal, 34(4): 688-691.
Leung, J. C., and Epstein M, 1990, A generalized correlation for two-phase nonflashing
homogeneous choked flow, Transactions of the ASME, Journal of Heat Transfer, 112:
528-530.
Li, R. Y., Lin, S., and Chen, Z. H., 1990, Numerical modeling of thermodynamic non
equilibrium flow of refrigerant through capillary tubes, ASHRAE Transactions, 96(1):
542-549.
Lin, S., Kwok, C. C. K., Li, R. Y., Chen, Z., H., and Chen, Z. Y., 1991, Local friction
pressure drop during vaporization of R-12 through capillary tubes, Int. J. Multiphase
Flow, 17(1): 95-102.
Liu, Y. and Bullard, C. W., 1997, An experimental and theoretical analysis of capillary tube
suction line heat exchangers, ACRC TR-I09, Department of Mechanical and Industrial
Engineering, University of Illinois at Urbana-Champaign
Lockhart, R. W. and Martinelli, R. C., 1949, Proposed correlation of data for isothermal two
phase, two-component flow in pipes, Chemical Engineering Progress, 45(1): 39-48.
Marcy, G. P., 1949, Pressure drop with change of phase in a capillary tube, Refrigerating
Engineering, 57(1): 53.
Marie, J. L., 1987, Modeling of the skin friction and heat transfer in turbulent two-component
bubbly flow in pipes, Int. J. Multiphase Flow, 13: 309-325.
Martinelli, R. C., Boelter, L. M., K., Taylor, T. H. M., Thomsen, E., G., and Morrin, E. H.,
1944, Isothermal pressure drop for two-phase two-component flow in a horizontal pipe,
Transactions of the ASME, 66(2): 139-151.
34
McAdams, W. H., Wood, W. K., and Bryan, R. L., 1942, Vaporization inside horizontal
tubes-II-Benzene-oil mixtures, Transactions of the ASME, 66(8): 671-684.
Melo, C., Ferreira, R. T. S., Neto, C. B., Goncalves, J. M., and Thiessen, M. R., 1994,
Experimental analysis of capillary tubes for CFC-12 and HFC-134a, Proceedings of
International Refrigeration Conference, Purdue University: 347-352.
Melo, C., Ferreira, R. T. S., Neto, C. B., and Goncalves, J. M., 1995a, Experimental and
analysis of refrigerant flow through adiabatic capillary tubes, AES-Vol. 34, Heat Pump
and Refrigeration Systems Design, Analysis, and Applications, ASME: 19-30.
Melo, C., Ferreira, R. T. S., Neto, C. B., and Goncalves, J. M., 1995b, Measuring pressure
and temperature profiles along capillary tubes, Proceedings of the 19'h International
Congress of Refrigeration, Vol. III a: 146-153.
Meyer, J. J., and Dunn, W. E., 1996, Alternative refrigerants in adiabatic capillary tubes,
ACRC TR-I08, University of Illinois at Urbana-Champaign, USA.
Meyer, J. J., and Dunn, W. E., 1998, New insights into the behavior of the metastable region
of an operating capillary tube, HVAC&R Research, 4(1): 105-115.
Mikol, E. P, 1963, Adiabatic single and two-Phase flow in small bore tubes, ASHRAE
Journal, 5(11): 75-86.
Moody, L. F. And Princeton, N. J., 1944, Friction factors for pipe flow, Transaction of the
ASME: 671-684.
Murdock, J. M., 1962, Two phase flow measurement with orifices, J. Basic Engineering,
84(4): 419-433.
Niaz, R. H., and G. De Vahl Davis, 1969, Adiabatic two-phase flow in a capillary tube,
Concurrent Gas-Liquid Flow, Symposium of the Canadian Society of Chemical
Engineers, University of Waterloo, Vol. 1: 259-269.
Obermeier, E., 1990, Two-phase critical flow-rates of refrigerants: thermodynamic limits of
flow-rates in tubes and orifices, Rev. Int. Froid, Vol. 13 (Sept): 301-307.
Pate, M. B., and Tree, D. R., 1987, An analysis of choked flow conditions in a capillary tube
suction line heat exchanger, ASHRAE Transactions, 93(1): 368-380.
35
Pai, S.-I., 1981, Modernfluid mechanics, Science Press, Beijing: 326.
Rateau, A., and Nostrand, D. V., 1905, Experimental researches on the flow of steam through
nozzles and orifices, New York: 62-74.
Rezk, A., and Awn, A., 1979, Investigation on flow of R12 through capillary tubes, In
Proceedings of the 15th International Congress of Refrigeration, Commission, B2, Vol.
2: 443-452.
Romig, R. P., Rothfus, R R, and Kermode, R I., 1966, Partial vaporization in orifices and
valves, I and EC Process design and development, 5(3): 73-78.
Sami, s. m., and Tribes, C., 1998, Numerical prediction of capillary tube behavior with pure
and binary alternative alternative refrigerants, Applied Thermal Engineering, 18(6): 491-
502.
Schulz, U. W., 1985, State of the art: the capillary tube for, and in, vapor compression
systems, ASHRAE Transactions, Vol. 91, Part 1: 92-103.
Scott, T. C., 1976, Flashing refrigerant flow in small bore tubes, Ph.D. Thesis, The
University of Michigan.
Souza, A. L., Chato, J. C., Wattelet, J. P., and Christofferson, B. R, 1993, Pressure drop
During two-phase flow of pure refrigerants and refrigerant-oil mixtures in horizontal
smooth tubes, ASME, Heat Transfer with Alternate Refrigerants, HTD-Vol. 243 :35-41.
Souza, A. L., and Pimenta, M. M., 1995, Prediction of pressure drop during horizontal two
phase flow of pure and mixed refrigerants, ASME, Cavitation and Multiphase Flow,
FED-Vol. 210: 161-171.
Staebler, L. A., 1948, Theory and use of a capillary tube for liquid refrigerant control,
Refrigerating Engineering, 55(1): 55-59 and 102-103.
Stuart M. c., and Yarnall, D. R, 1936, Fluid flow through two orifices in series, Mechanical
Engineering, 6 (Sept.): 14-19.
Swart, R H., 1946, Capillary tube heat exchangers, Refrigerating Engineering, 52(3): 221-
224 and 248-249.
36
Sweedyk, J. M., 1981, Capillary tubes - their standardization and use, ASHRAE Transactions,
87(1): 1069-1076.
Taitel, Y., and Tel-Aviv, U., 1994, Advances in two-phase modeling, SPE 27959.
Wallis, G. B., 1980, Critical two-phase flow, Int. J. Multiphase Flow, Vol. 16:97-112.
Whitesel, H. A., 1957a, Capillary two-phase flow, Refrigerating Engineering, 65(4): 42-44,
98-99.
Whitesel, H. A., 1957b, Capillary two-phase flow, part II, Refrigerating Engineering, 65(9):
35-40.
Wijaya, H., 1991, An experimental evaluation of adiabatic capillary tube performance for
HFC-134a and CFC-12, International CFC and Halon Alternatives Conference
Proceedings, Dec. 3-5, Baltimore, p. 474.
Yin, J. M., 1998, A theoretical model for predicting a adiabatic capillary tube performance: a
analysis and improvement, ACRC TR-139, University of Illinois at Urbana-Champaign.
Zaloudek, F. R., 1965, The critical flow of hot water through short tubes, USAEC Report,
HW-77594.
Zukauskas, A., and Kami, J., 1989, High-performance single-phase heat exchangers,
Hemisphere Publishing Corporation, New York: 381-382.
37