Addressable Fire Alarm Control Panel
Profile:
The addressable fire alarm control panel is a dual wire analog bus system, it can replace
the conventional fire alarm control system to save 50% or more cables.
Each detector, module, manual call point, horn, strobe ,hydrant has its own independent
address, the fireman or the guard can find the exact fire alarm location instead of a wide
area in conventional system.
The AW-AFP2100 series addressable fire alarm control panel is an advanced, perfect
and reliable system, it has been used in many countries.
Characters:
1. 32 bit MCU, embedded computer operation system, 7.4 inch LCD display (it is bigger
than most of other factories), PS/2 mouse and PC keyboard, Windows menu, user
friendly interface, nice looking.
2. Map display on both the panel and the computer monitor. (Most of the other factories
S h e n z h e n A s e n w a r e Te s t & C o n t r o l Te c h n o l o g y C o . , L t d .Address: D-26H,Shihong Bd.,Fanshen Rd.,Baoan,Shenzhen,China-518101Tel:+86-755-27663815 Fax:+86-755-27663915 Email:[email protected]
www.asenware.com
have only computer monitor map display function)
3. Detector sensitivity is adjustable.
4. Single point start/stop, self-test.
5. Max panels network capacity is 20.
6. Exact location configuration: zone-building-floor-room
Parameters:
1 Panel series:
Model No. Main characters
AW-AFP2100/40 LED indicator, 40 points address, wall
mounted panel
AW-AFP2100/396, 792,1188 LCD display, 396*n points address, wall
mounted panel
AW-AFP2100/1584, 1584+396*n LCD display, 296*n points address,
cabinet panel
1 396 points loop card: each loop card has 2 loops, each loop has 198 points address,
but the module points (MCP, horn, I/O modules and so on) should be less than 99 to
keep enough power in the loop.
2 Max points of one panel: 15840 points
3 Multi-line integrated fireman panel capacity: 4000 points
4 Bus integrated fireman panel capacity:4000 points
5 Panels network capacity : 20, by CAN bus.
6 Maximum loop length: 1500m
7 Loop cable: 2*1.5mm2 twisted pair cable
8 Maximum simultaneous alarm of each panel:
8.1 Fire alarm:500
8.2 Trouble:500
8.3 Feedback:500
9 Operating environment:
10 Temperature: -10 ~+55℃ ℃
11 Relative humidity: ≤95%(40 ,non-condensing℃ )12 Power:
12.1 AC power: 220VAC,50Hz,3A
12.2 DC power:24VDC
12.3 Battery:12V7.0Ah*2
Certification: CE