Addendum
I:\Offices\Roa\2014\5404-Union County Firearms Range\CA\Bidding\Addenda\Addendum 02\151230
Addendum 02.docx Page 1
ADDENDUM NO. 02
This Addendum forms a part of the Contract Documents and modifies and takes precedence over the
original Bid Documents for IFB#2016-014, Union County Sherriff’s Office Firing Range. Original
items of the Bid Documents not herein modified, amended, voided or suspended shall remain in
effect.
It is the responsibility of the Bidder to notify and/or distribute this Addendum to all sub-bidders.
Acknowledge receipt of this Addendum in the space provided on the Bid Form.
This Addendum consists of three pages, plus attached drawing sheets and specifications.
CHANGES TO DRAWINGS
1. Delete the following drawing sheets and replace with attached drawing sheets
incorporating revisions numbered “1” and dated 12/30/2015:
a. GI002 “APPENDIX B”
b. S-001 “LEGEND, NOTES, AND ABBREVIATIONS”
c. S-003 “GENERAL NOTES”
d. SB102 “FOUNDATION PLAN AREA B”
e. SB301 “FOUNDATION SECTIONS”
f. SB501 “TYPICAL FOUNDATION/SLAB DETAILS”
g. SF102 “ROOF FRAMING PLAN AREA B”
h. SF301 “FRAMING SECTIONS”
i. SF501 “TYPICAL FRAMING DETAILS”
j. AE101 “FLOOR PLAN AREA A”
k. AE102 “FLOOR PLAN AREA B”
l. AE103 “REFLECTED CEILING PLAN AREA A”
m. AE104 “REFLECTED CEILING PLAN AREA B”
n. AE105 “ROOF PLAN AND DETAILS”
213 South Jefferson, Suite 1011
Roanoke, VA 24011
Project: Union County Sheriff’s Office
Firing Range
Date: December 30, 2015
Project #: IFB#2016-014
Clark Nexsen Project No. 5404
Addendum
I:\Offices\Roa\2014\5404-Union County Firearms Range\CA\Bidding\Addenda\Addendum 02\151230
Addendum 02.docx Page 2
o. AE201 “ELEVATIONS”
p. AE202 “ELEVATIONS”
q. AE301 “BUILDING SECTIONS”
r. AE401 “ENLARGED PLANS”
s. AE501 “BALLISTIC DETAILS”
t. AE503 “DETAILS”
u. AE601 “SCHEDULES”
v. FP101 “FLOOR PLAN AREA A”
w. FP102 “FLOOR PLAN AREA B”
x. M-001 “ABBREVIATIONS LEGEND AND GENERAL NOTES”
y. M-101 “FLOOR PLANS - AREAS A AND B”
z. M-501 “DETAILS”
aa. M-601 “SCHEDULES”
bb. M-801 “CONTROL SEQUENCES DIAGRAMS AND POINT LISTS”
cc. M-802 “CONTROL SEQUENCES DIAGRAMS AND POINT LISTS”
CHANGES TO SPECIFICATIONS
1. Section 095113 - ACOUSTICAL PANEL CEILINGS:
a. Add the following article after article 2.3 and renumber subsequent articles:
“2.4 ACOUSTICAL PANELS: ACP – 2
A. Basis-of-Design Product: Subject to compliance with
requirements, provide Armstrong World Industries, Inc. “Fine
Fissured.”
B. Color: White.
C. Edge/Joint Detail: Square.
D. Modular Size: As indicated on Drawings.
E. Broad Spectrum Antimicrobial Fungicide and Bactericide
Treatment: Provide acoustical panels treated with
manufacturer's standard antimicrobial formulation that inhibits
fungus, mold, mildew, and gram-positive and gram-negative
bacteria and showing no mold, mildew, or bacterial growth
when tested according to ASTM D 3273 and evaluated
according to ASTM D 3274 or ASTM G 21.
F. Humidity Resistance: Resistant to sagging in high-humidity
conditions, including standing water and outdoor
applications.”
Addendum
I:\Offices\Roa\2014\5404-Union County Firearms Range\CA\Bidding\Addenda\Addendum 02\151230
Addendum 02.docx Page 3
2. Section 124816 – ENTRANCE FLOOR GRILLES:
a. Under 2.1 MANUFACTURERS add the following paragraph:
“B. Other Manufacturers:
1. Kadee Industries, “KDCP Aluminum Entrance Grid”.
3. Delete Section 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM and replace with
Section 283111 attached to this Addendum.
RESPONSES TO BIDDER QUESTIONS
The following are responses to questions received from Bidders that do not require modifications to
the Bid Documents. The following is provided as a courtesy so that all Bidders have access to the
same information.
1. Drawing Sheet AE503 - Question: Looking at details B4 and C4 on AE503, it appears a
portion of this vertical surface is open to the elements. Am I seeing this correctly, or is this
surface closed? If it is closed, what materials are being used to close it?
a. Response: Between the tops of the wood blocking assembly above the truss
bottom chords (Detail B4), and the bottom of the truss top chords (Detail C4) the
building is open to the exterior, through the webs of the trusses.
2. Specification Section 064116 – Question: Plastic laminate faced architectural cabinets
require AWI program labels. We have a supplier that does not participate in the AWI
programs, can this requirement be waived?
a. Response: No.
END OF ADDENDUM
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
53 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSMFKDEW
GI002
APPENDIX B
2
2012 APPENDIX BBUILDING CODE SUMMARY
FOR ALL COMMERCIAL PROJECTS
(EXCEPT 1 AND 2 FAMILY DWELLINGS AND TOWNHOUSES)
Name of Project: ________________________________________________________________
LEAD DESIGN PROFESSIONAL: __________________________________________
Address: ___________________________________________________ Zip Code: _________Proposed Use: __________________________________________________________________Owner/Authorized Agent: __________________ Phone #: ____________ _______________Owned By:Code Enforcement Jurisdiction:
DesignerArchitectural
2012 EDITION OF NC CODE FOR:EXISTING:CONSTRUCTED__________________ ORIGINAL USE(S)___________________RENOVATED __________________ CURRENT USE(S)___________________
PROPOSED USE(S)__________________
BASIC BUILDING DATA
CivilElectricalFire AlarmPlumbingMechanicalStructural
Construction Type:I-B
Sprinklers:Standpipes:Fire District:Building Height: (feet)
Gross Building Area:FLOOR EXISTING (SQ FT) NEW (SQ FT) SUBTOTAL6th Floor5th Floor4th Floor3rd Floor2nd FloorMezzanine1st FloorBasement
TOTAL
ALLOWABLE AREAOccupancy:
Assembly:Business:Educational:Factory:Hazardous:Institutional:
Mercantile:Residential:Storage:
Special Uses:
Special Provisions:
Mixed Occupancy:Incidental Use Separation (509)This separation is not exempt as a Non-Separated Use (see exceptions)Non-Separated Use (508.3.)The required type of construction for the building shall be determined by applying theheight and area limitations for each of the applicable occupancies to the entirebuilding. The most restrictive type of construction, shall apply to the entire building.Separated Use (508.4) - See below for area calculationsFor each story, the area of occupancy shall be such that the sum of the ratios of theactual floor area of each use divided by the allowable floor area for each use shall notexceed 1.
Actual Area of Occupancy A Actual Area of Occupancy BAllowable Area of Occupancy A Allowable Area of Occupancy B ≤ 1
≤ 1.00. . . . =
STORYNO.
DESCRIPTIONAND USE
(A)BLDG AREAPER STORY
(ACTUAL)
(B)TABLE 503
AREA
(C)AREA FORFRONTAGEINCREASE
(D)AREA FORSPRINKLERINCREASE
(E)ALLOWABLE
AREA ORUNLIMITED
(F)MAXIMUMBUILDING
AREA
1 - Frontage area increases from Section 506.2 are computed thus:a. Perimeter which fronts a public way or open space having 20 feet minimum width = ___________ (F)b. Total Building Perimeter = ___________ (P)c. Ratio (F/P) = ___________ (F/P)d. W=Minimum Width of Public Way = ___________ (W)e. Percent of frontage increase I = 100 [(F/P) - 0.25] x W/30 = ___________ (%)
2 - The sprinkler increase per Section 506.3 is as follows:a. Multi-story Building I = 200%b. Single story Building I = 300%
f
ss
3 - Unlimited area applicable under conditions of Section 507.
4 - Maximum Building Area = total number of stories in the building x E (506.4).
5 - The maximum area of parking garages must comply with 406.3.5. The maximum area of air traffic control towers mustcomply with Table 412.1.2.
New Construction
FIRE PROTECTION REQUIREMENTS
ALLOWABLE HEIGHT
Type of ConstructionBuilding Height in FeetBuilding Height in Stories
ALLOWABLE(TABLE 503)
INCREASEFOR
SPRINKLERS
SHOWN ONPLANS
CODEREFERENCE
Feet = H + 20' = _______
Stories + 1 = __________
Feet _________ (H)
Stories _______ (S)
Structural FrameIncluding Columns,Girders, Trusses
Bearing Walls
Exterior
North
East
West
South
InteriorNonbearing Walls andPartitions
BUILDING ELEMENTFIRE
SEPARATIONDISTANCE
(FEET)
RATING
REQ'D
Exterior
Interior walls and partitions
North
East
West
South
Floor ConstructionIncluding supportingbeams and joistsRoof ConstructionIncluding supportingbeams and joists
Shaft Enclosures - Exit
Shaft Enclosures - Other
Corridor Separation
Occupancy Separation
Party/Fire Wall Separation
Smoke Barrier Separation
Tenant Separation
Incidental Use Separation
PROVIDED(W/_____*REDUCTION)
DETAIL #AND
SHEET #
DESIGN #FOR
RATEDASSEMBLY
DESIGN # FORRATED
PENETRATION
DESIGN #FOR
RATEDJOINTS
* Indicate section number permitting reduction
LIFE SAFETY SYSTEM REQUIREMENTSEmergency Lighting:Exit Signs:Fire Alarm:Smoke Detection Systems:Panic Hardware:
STRUCTURAL DESIGNDESIGN LOADS:
ws
E
Ground Snow Load:
Wind Load:
SEISMIC DESIGN CATEGORY
1
LATERAL DESIGN CONTROL:
SOIL BEARING CAPACITIES:
PLUMBING FIXTURE REQUIREMENTS
EXISTING
USEURINALS
NEW
REQUIRED
WATER CLOSETS
MALE FEMALE
LAVATORIES
MALE FEMALESHOWERS /
TUBS
DRINKING FOUNTAINS
REGULAR ACCESSIBLE
ENERGY SUMMARY
ENERGY REQUIREMENTSThe following data shall be considered minimum and any special attribute required to meet the energycode shall also be provided. Each Designer shall furnish the required portions of the projectinformation for the plan data sheet. If energy cost budget method, state the annual energy cost budgetvs. allowable annual energy cost budget.
THERMAL ENVELOPE
Method of Compliance:
Roof/Ceiling Assembly (each assembly)
Exterior Walls (each assembly)
Walls below grade (each assembly)
Floors over unconditioned space (each assembly)
Floors slab on grade (each assembly)
MECHANICAL SUMMARY
MECHANICAL SYSTEMS, SERVICE SYSTEMS, AND EQUIPMENT
Thermal Zonewinter dry bulbsummer dry bulb
Interior design conditions
relative humidity
Building heating loadBuilding cooling loadMechanical Spacing Conditioning System
Unitarydescription of unitheating efficiencycooling efficiencysize category of unit
BoilerSize category. If oversized, state reason.
Chiller
List equipment efficiencies
Addition UpfitReconstruction Alteration Repair
II-B III-B V-BI-A II-A III-A V-AIV
No Partial Yes NFPA 13 NFPA 13R NFPA 13DNo Yes Class I Class II Class III Wet DryNo Yes Flood Hazard Area: No Yes
_________
I-1 I-2 I-3
A1 A2 A3
F-1 Moderate F-2 LowH-1 Detonate H-2 Deflagrate
I-4H-3 Combust H-4 Health H-5 HPM
R-1 R-2 R-3 R-4S-1 Moderate S-2 Low High-Piled
Utility and Miscellaneous:
402 403 404 405 406 407 408 409 410 411412 413 414 415 416 417 418 419 420 421
509.2 509.3 509.4 509.5 509.6 509.7 509.8
No Yes Separation: _____ Hhr Exception: _____________
City/County Private StateStateCity _____________ County ___________
No YesNo YesNo YesNo YesNo Yes
Wind (I )Snow (I )Seismic (I )
______________________________
RoofMezzanineFloor
Live Loads:
Importance Factors:
__________ psf__________ psf__________ psf__________ psf
Basic Wind SpeedExposure CategoryWind Base Shears (for MWFRS)
__________ mph (ASCE-7)__________Vx = __________ Vy = __________
Provide the following Seismic Design Parameters:B C D
Occupancy Category (Table 1604.5)Spectral Response AccelerationSite Classification (Table 1613.5.2)
Basic Structural System (check one)Bearing WallBuilding FrameMoment Frame
Dual with Special Moment FrameDual with Intermediate R/C or Special SteelInverted Pendulum
Seismic Base ShearAnalysis ProcedureArchitectural, Mechanical, Components anchored?
Ss = ____________ %g
Data Source:
S = ____________ %g
Field Test Presumptive Historical Data
Vx = __________ Simplified
Vy = __________ Modal Equivalent Lateral Force
Earthquake Wind
Field Test (provide copy of test report)Presumptive Bearing capacityPile size, type, and capacity
_________ psf_________ psf_________________________________________
Prescriptive (Energy Code)Performance (Energy Code)
Description of assemblyU-Value of total assemblyR-Value of insulationSkylights in each assembly
U-Value of skylightTotal square footage of skylights in each assembly
_______________________________________________________________________________________________________________________________________________________________________________
_____________________
Description of assemblyU-Value of total assemblyR-Value of insulationOpenings (windows or doors with glazing)
U-Value of assemblyShading coefficientProjection factorLow-E required, if applicable
Door R-Values
________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________________________________________________________
Description of assemblyU-Value of total assemblyR-Value of insulation
_________________________________________________________________________________________________________
Description of assemblyU-Value of total assemblyR-Value of insulation
_________________________________________________________________________________________________________
Description of assemblyU-Value of total assemblyR-Value of insulation
_________________________________________________________________________________________________________
Horizontal / vertical requirement ___________________________________Slab heated ___________________________________
_____________________________________________________________________________________________________________________________________________
winter dry bulbsummer dry bulb
_____________________________________________________________________________________________________________________________________________
______________________________________________________________________________________________
________________________________________________________________________________________________________________________________________________
________________________
Firm Name Lic. # EmailPhone #
I-3 Condition 1 2 3 4 5
A4 A5
5
1 2 3 4
Type _________ Type ___________
Stories _________
422 423
Partial _______
A
II III
IVI
SPACE
ELECTRICAL SUMMARY
ELECTRICAL SYSTEM AND EQUIPMENTMethod of Compliance:
Lighting Schedule
Equipment schedules with motors (not used for mechanical systems)
Prescriptive PerformanceEnergy Code:
Lamp type required in fixtureNumber of lamps in fixtureBallast type used in fixtureNumber of ballasts in fixtureTotal wattage per fixtureTotal interior wattage specified vs. allowed(whole building or space by space)Total exterior wattage specified vs. allowed
____________________________________________________________________________________________________________________________________________________________________________________
______________________________
Renovation
Accessory Occupancies:Assembly:Business:Educational:Factory:Hazardous:Institutional:
Mercantile:Residential:Storage:
I-1 I-2 I-3
A1 A2 A3
F-1 Moderate F-2 LowH-1 Detonate H-2 Deflagrate
I-4H-3 Combust H-4 Health H-5 HPM
R-1 R-2 R-3 R-4S-1 Moderate S-2 Low High-Piled
I-3 Condition 1 2 3 4 5
A4 A5
Parking Garage Open Enclosed Repair Garage
Utility and Miscellaneous:Parking Garage
Incidental UsesFurnace room where any piece of equipment is over 4000,000 Btu per hour input Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower Refrigerant machine room Hydrogen cut off rooms, not classified as Group HIncinerator roomsPaint shops, not classified as Group H, located in occupancies other than Group FLaboratories and vocational shops, not classified as Group H, located in a Group E or I-2occupancyLaundry rooms over 100 square feetGroup I-3 cells equipped with padded surfacesGroup I-2 commercial kitchensWaste and linen collection rooms over 100 square feetStationary storage battery systems having a liquid electrolyte capacity of more than 50gallons, or a lithiumion capacity of 1,000 pounds used for facility standby power,emergency power or uninterrupted power suppliesRooms containing fire pumpsGroup I-2 storage rooms over 100 square feetGroup I-2 commercial kitchensGroup I-2 laundries equal to or less than 100 square feetGroup I-2 rooms or spaces that contain fuel-fired heating equipment
424 425 426 427509.9
(Table 509):
LIFE SAFETY PLAN REQUIREMENTSLife Safety Plan Sheet #: ______________________
Fire and/or smoke rated wall locations (Chapter 7)Assumed and real property line locationsExterior wall opening area with respect to distance to assumed property lines (705.8) Existing structures within 30' of the proposed building Occupancy types for each area as it relates to occupant load calculation (Table 1004.1.1)Occupant loads for each areaExit access travel distance (1016)Common path of travel distances (1014.3 & 1028.8)
Dead end lengths (1018.4)Clear exit widths for each exit doorMaximum calculated occupant load capacity each exit door can accomodate based on egresswidth (1005.1)Actual occupant load for each exit doorA separate schematic plan indicating where fire rated floor/ceiling and/or roof structure isprovided for purposes of occupancy separationLocation of doors with panic hardware (1008.1.10)Location of doors with delayed egress locks and the amount of delay (1008.1.9.7)Location of doors with electromagnetic egress locks (1008.1.9.8)Location of doors equipped with hold-open devicesLocation of emergency escape windows (1029)The square footage of each fire area (902)The square footage of each smoke compartment (407.4)Note any code exceptions or table notes that may have been utilized regarding the items above
ACCESSIBLE PARKING
LOT ORPARKING AREA
TOTAL # OF PARKING SPACES
REQUIRED PROVIDED
# OF ACCESSIBLE SPACES PROVIDED
REGULAR WITH 5'ACCESS AISLE
VAN SPACES WITH8' ACCESS AISLE
TOTAL #ACCESSIBLEPROVIDED
TOTAL
(SECTION 1106)
B C DA E F
Yes No
(TABLE 2902.1)
3 4 5Climate Zone:
Prescriptive (ASHRAE 90.1)Performance (ASHRAE 90.1)
Size category. If oversized, state reason. ________________________
________________________
Prescriptive PerformanceASHRAE 90.1:
506.2.1 More Efficient Mechanical Equipment506.2.2 Reduced Lighting Power Density506.2.3 Energy Recovery Ventilation Systems506.2.4 Higher Efficiency Service Water Heating506.2.5 On-Site Supply of Renewable Energy506.2.6 Automatic Daylighting Control Systems
Open Enclosed Repair Garage
Yes NoSPECIAL INSPECTIONS REQUIRED:
UNION COUNTY SHERIFF'S OFFICE FIRING RANGEMILLS HARRIS ROAD, MARSHVILLE, NC
POLICE FIRING RANGECraig Fox 704-283-3868 [email protected]
-- 27,048 --
-- 27,048 27,048
Clark Nexsen JOHN SHIELDS 12471 540-982-0800 [email protected] Nexsen VINCE CHIRICHELLA 919-828-1876 [email protected] Nexsen MIKE PHILLIPS 704-377-8800 [email protected]
Clark Nexsen WES HORNE 40687 919-828-1876 [email protected] Nexsen JON DOVER 26841 757-455-5800 [email protected] Nexsen MARCUS WHITAKER 041510 704-377-8800 [email protected]
551
----
----
>30 0 -- -- -- ---- -- -- ---- -- -- ---- -- -- --
-- -- -- ---- -- -- ---- -- -- ---- -- -- --
-- - - - -- -- ---- -- -- -- -- -- ---- 1 0 -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- --
- - -- --
-- -- ---- -- -- -- -- -- -- --1 1 1 1 1 2 1 11 1 -- 1 1 -- 1 1
--
25 25 1 1 2
3,000
--
1.01.01.0
20N/A10010
--0.041
24NANA
NA
IIB
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- -- ---- -- -- -- -- -- --
-- 0 0 -- -- -- --
- - - - -- --
--23'-6"
1
IIB
28103
GI101
--
Clark Nexsen CHRIS BORN 22212 757-455-5800 [email protected]
27,048Firing Range-B 23,000 -- -- 40,2501 17,250---- -- -- -------- -- -- ---- ------ -- -- ---- ------ -- -- ---- --
895'895'
130'75
-- --
031441
90B
24k 114.6k
0.364 0.116
198k 263k
23'-6"
------------
--
--
--------
--
--
--------
--
See Schedule on EL501See Schedule on EL501
--
--0.072
14
NA
NANA
6
NA--
NA
NANANA
--
No
3A Charlotte, NC1891
707250
38.8 MBh
6 tons
packaged RTU HP
3.3 COP11.4 EER
>= 65,000 Btu/h and < 135,000 Btu/h
NA
NA
--
-- -- -- -- -- -- --
-
-- --
--
Clark NexsenClark Nexsen 919-828-1876Clark Nexsen 028914
Clark Nexsen 919-828-1876Clark NexsenClark Nexsen
----
----
-- -- -- ---- -- -- ---- -- -- ---- -- -- --
-- -- -- ---- -- -- ---- -- -- ---- -- -- --
-- - - - -- -- ---- -- -- -- -- -- ---- -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- ---- -- -- -- -- -- --
- - -- --
-- -- ---- -- -- -- -- -- -- --
-- --
--
3,000
Metal building with R-5 thermal block
-- -- -- -- -- -- --
-- -- -- -- -- -- --
-- -- -- -- -- ---- -- -- -- -- -- --
-- -- -- -- --
--
--
Clark Nexsen
--1---- -- -- -------- -- -- ---- ------ -- -- ---- ------ -- -- ---- --
Union
CLARK NEXSEN
-- --
24k 114.6k
------------
--
--
--------
--
--
--------
--
--
Metal building
NA
Unheated slabNot required
--
-- -- -- -- -- -- --
MAIN LOT
>30 0>30 0>30 0
0000
>30 0>30 0>30 0>30 0
0000
0 0
0 0
--
10 at slab edge
See Schedule on EL501See Schedule on EL501See Schedule on EL501
14,579 vs 19,002
783 vs 1,444
25 25 1 1 2
NA
Not required
1
No. Date Description1 12/30/2015 Revision 01
1
AFF ABOVE FINISHED FLOOR
BOC BOTTOM OF CONCRETE
BOS BOTTOM OF STEEL
BRG BEARING
CFS COLD-FORMED STEEL
AB ANCHOR BOLT
CJ SLAB CONSTRUCTION JOINT
CENTER LINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONN CONNECTION
CONC CONCRETE
CONT CONTINUOUS
DN DOWN
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATION
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
FFE FINISHED FLOOR ELEVATION
FOB FACE OF BRICK
FTG FOOTING
GALV GALVANIZED
HORIZ HORIZONTAL
HS HIGH STRENGTH
JBE JOIST BEARING ELEVATION
LG LONG
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MOW MIDDLE OF WALL
NTS NOT TO SCALE
OPP OPPOSITE
PJF PREMOLDED JOINT FILLER
PLATE
REQD REQUIRED
SF STEPPED FOOTING
SJ SLAB SAWED (CONTRACTION) JOINT
T&B TOP AND BOTTOM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF STEEL
TS THICKENED SLAB
TYP TYPICAL
VERT VERTICAL
WP WORKING POINT
WWF WELDED WIRE FABRIC
CL
PL
DIA, ø DIAMETER
POUNDS PER SQUARE FOOT
SIM SIMILAR
PSF
DWG DRAWING
KIP (k) 1000 LBS
POUNDS PER LINEAR FOOTPLF
UON UNLESS OTHERWISE NOTED
DCJ DOWELED CONSTRUCTION JOINT
ARCH ARCHITECTURAL
APPROX APPROXIMATELY
BD BAR DIAMETER
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
STD STANDARD
SD SLAB DEPRESSION
NO. NUMBER
NIC NOT IN CONTRACT
SCHED SCHEDULE
SOG SLAB-ON-GRADE
GA GAGE
LSH LONG SIDE HORIZONTAL
LSV LONG SIDE VERTICAL
OC ON CENTER
REINF REINFORCING
SL SLOPE(D)
PEMB PRE-ENGINEERED METAL BUILDING
PCM PRECAST CONCRETE MANUFATURER
SLOPE DIRECTION
CONCRETE
EARTH FILL
CONCRETE MASONRYUNIT (CMU)
POROUS FILL
INDICATES ELEVATIONREFERENCEDTO FINISHED FIRST FLOOR
DECK SPAN
KEYED CONSTRUCTION NOTE
COLUMN REFERENCE LINE(CENTERLINE OF COLUMN)
SPOT ELEVATION
JOIST BRIDGING
SLOPE DIRECTION
WALL TYPE
GROUT
SLAB DEPRESSION
DN
X
#
MOMENT CONNECTION
WELDED WIRE FABRIC
10k W24x55 [+X'-X"] 10k
END REACTIONS
BEAM SIZE
ELEVATION TOFINISH FLOOR
Wn
[X'-X"]
[X'-X"]
1. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL OTHER DRAWINGS. COORDINATE THE WORK OFOTHER TRADES INCLUDING, BUT NOT LIMITED TO THE REQUIREMENTS FOR SLEEVES, INSERTS, HOLES,HANGERS AND ANCHORS.
2. ELEVATIONS ON THE STRUCTURAL DRAWINGS ARE DENOTED AS [±X’-X”] REFERENCED TO THE FINISHED FIRSTFLOOR ELEVATION DATUM. REFER TO THE CIVIL DRAWINGS FOR ACTUAL DATUM ELEVATION.
3. REPORT DISCREPANCIES IN DIMENSIONS BETWEEN DIFFERENT DRAWINGS TO THE ARCHITECT AND ENGINEEROF RECORD PRIOR TO BEGINNING WORK IN AREAS THAT WILL BE AFFECTED.
4. DETAILS ENTITLED OR NOTED AS “TYPICAL” APPLY NOT ONLY WHERE SPECIFICALLY INDICATED ORREFERENCED, BUT ALSO IN ALL OTHER CASES WHERE THE NATURE OF THE CONSTRUCTION REQUIRES THEIRUSE. DETERMINE APPLICABILITY OF TYPICAL DETAILS FROM DESCRIPTIVE TITLES OR FROM THE SIMILARITY OFA CONSTRUCTION CONDITION TO ANOTHER CONDITION WHERE THE DETAIL IS SPECIFICALLY INDICATED ORREFERENCED.
5. THE STRUCTURAL DRAWINGS CONTAINED HEREIN REPRESENT THE FINISHED STRUCTURE. PROVIDE ALLTEMPORARY GUYING AND BRACING REQUIRED TO ERECT AND HOLD THE STRUCTURE IN PROPER ALIGNMENTUNTIL ALL STRUCTURAL WORK, INCLUDING CONNECTIONS, IS COMPLETE. THE ANALYSIS, DESIGN, SAFETY,ADEQUACY, AND INSPECTION OF ERECTION BRACING, SHORING, AND OTHER TEMPORARY SUPPORTS ARE THESOLE RESPONSIBILITY OF THE CONTRACTOR.
6. CONSTRUCTION MEANS, METHODS, TECHNIQUES, AND SEQUENCES AND SUPERVISION OF THE WORK ARE THESOLE RESPONSIBILITY OF THE CONTRACTOR.
7. REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP DRAWINGS UNDER ANYCIRCUMSTANCE.
GENERAL NOTES
1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES AND SPECIFICATIONS:
A. 2012 NORTH CAROLINA BUILDING CODE, EFFECTIVE SEPTEMBER 1, 2011
B. ASCE 7-05, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
C. AISC “SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS” DATED MARCH 9, 2005 (AISC 360-05)
D. AISC “CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES” DATED MARCH 18, 2005 (AISC 303-05)
E. ACI 318-08, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
2. DESIGN LOAD CRITERIA:
A. LIVE LOADS (UNIFORM)
ROOFGROUND FLOORSTORAGEMECHANICAL/ELECTRICAL ROOMS
NOTE: LIVE LOAD REDUCTION WAS NOT USED IN THE DESIGN OF THIS STRUCTURE
B. SNOW LOAD:
GROUND SNOW LOAD, PgSNOW EXPOSURE FACTOR, CₑTHERMAL FACTOR, CtSNOW LOAD IMPORTANCE FACTOR, IsFLAT ROOF SNOW LOAD, PfSLOPED ROOF SNOW LOAD, Ps
C. WIND LOADS:
BASIC WIND SPEED, VOCCUPANCY CATEGORYWIND IMPORTANCE FACTOR, IwWIND EXPOSURE CATEGORYGUST EFFECT FACTOR, GINTERNAL PRESSURE COEFFICIENTS, GCpi
DESIGN NOTES
DESIGN WIND PRESSURE FORWALL COMPONENTS (PSF)
DESIGN WIND PRESSURE FORROOF COMPONENTS (PSF)
DESIGN WIND PRESSURE FORPARAPETS (PSF)
WALL ZONE
1
2
3
1 - 20ROOF ZONE
21 - 100 101 +
+10.5
+10.5
+10.5
-19.1
-29.0
-41.3
+10.1
+10.1
+10.5
-18.8
-26.4
-35.0
+10.0
+10.0
+10.0
-17.9
-20.4
-20.4
4
5
COMPONENT TRIBUTARY AREA (FT²)
COMPONENT TRIBUTARY AREA (FT²)
1 - 20 21 - 100 101 +
+19.1
+19.1
-20.4
-20.4
+18.5
+18.5
-19.7
-22.8
+16.9
+16.9
-18.2
-19.7
WALL ZONE
4
5
STRENGTH
44.9
53.5
DEFLECTION
31.7
37.7
NOTES:1. POSITIVE AND NEGATIVE SIGNS SIGNIFY PRESSURES ACTING TOWARD AND
AWAY FROM THE SURFACES, RESPECTIVELY
2. BUILDING ZONES ARE DEFINED IN ASCE 7
1
2
0 - 20OVERHANG ZONE
21 - 100 101 +
COMPONENT TRIBUTARY AREA (FT²)
-27.8
-27.8
-27.4
-27.4
-26.5
-26.5
NOTES:1. STRENGTH DESIGN BASED ON 50-YEAR MEAN RECURRENCE INTERVAL
2. DEFLECTION (SERVICEABILITY) DESIGN BASED ON 10-YEAR MEANRECURRENCE INTERVAL
3. DEFLECTION CRITERIA FOR COLD FORMED STEEL STUDS IS H/600(SIMPLY SUPPORTED) AND H/300 (CANTILEVERED).
E. SEISMIC LOADS:
OCCUPANCY CATEGORY IISEISMIC IMPORTANCE FACTOR, Iₑ 1.0SPECTRAL RESPONSE ACCELERATION, S 0.364gSPECTRAL RESPONSE ACCELERATION, S 0.116gSPECTRAL RESPONSE COEFFICIENT, S 0.366gSPECTRAL RESPONSE COEFFICIENT, S 0.181gSITE CLASS CSEISMIC DESIGN CATEGORY BANALYSIS PROCEDURE EQUIVALENT LATERAL FORCEBASIC SEISMIC-FORCE-RESISTING SYSTEM SYSTEM 1 (LONG DIRECTION) SYSTEM 2 (SHORT DIRECTION) SYSTEM 3 (ADMINISTRATION PEMB)
"INTERMEDIATE PRECAST "ORDINARY COMPOSITE MOMENT "ORDINARY STEEL MOMENT FRAMES"SHEAR WALLS" FRAMES"
RESPONSE MODIFICATION FACTOR, R 4 3 3.5DESIGN BASE SHEAR, V=C W 0.122W 0.092W 0.105W
DESIGN NOTES (CONTINUED)
1. DESIGN RESPONSIBILITY FOR THE FOLLOWING ENGINEERED SYSTEMS AND COMPONENTS IS DELEGATEDTO A QUALIFIED SPECIALTY STRUCTURAL ENGINEER LICENSED IN THE STATE OF NORTH CAROLINA ANDSELECTED BY THE CONTRACTOR. THESE SYSTEMS AND COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO:
A. STRUCTURAL STEEL CONNECTIONS, INCLUDING BRACED FRAME CONNECTIONSB. COLD-FORMED STEEL FRAMING AND CONNECTIONSC. PRE-ENGINEERED METAL BUILDINGSD. PRECAST CONCRETE STRUCTURAL MEMBERS
2. DELEGATED ENGINEERED SYSTEMS AND COMPONENTS SHALL SATISFY ASCE 7-05 LOAD COMBINATIONS. SIGNEDAND SEALED CALCULATIONS AND DRAWINGS SHALL BE SUBMITTED TO THE ENGINEER OF RECORD.
3. COORDINATE WITH THE CONTRACT DOCUMENTS FOR PROFESSIONAL LICENSURE AND SEALINGREQUIREMENTS, DESIGN CRITERIA, DETAILS OF THE SYSTEM/COMPONENT INTERFACE WITH THE PRIMARYSTRUCTURE, SUBMITTAL REQUIREMENTS, AND CALCULATION REQUIREMENTS.
DELEGATED DESIGN NOTES
1. THE LATERAL LOAD-RESISTING SYSTEM AND STABILITY OF THE COMPLETED STRUCTURE IN THE SHORTAND LONG DIRECTIONS IS PROVIDED BY ORDINARY STEEL MOMENT FRAMES AND INTERMEDIATE PRECASTSHEAR WALLS, RESPECTIVELY. THE STEEL ROOF DECKING SERVES AS THE DIAPHRAGM AND TRANSFERSLATERAL FORCES TO THE MAIN FORCE-RESISTING MEMBERS.
LATERAL LOAD-RESISTING SYSTEM NOTES
D. COMPONENTS AND CLADDING WIND PRESSURES:
20 PSF100 PSF125 PSF125 PSF
10 PSF0.91.11.0
10 PSF10 PSF
90 MPHII
1.0B
0.85±0.55
+10.0
+10.0
+10.0
+10.0
+10.0
+10.0
s
1
Ds
D1
s
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:1
7 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
S-001
LEGEND, NOTES,AND
ABBREVIATIONS
34
STRUCTURAL ABBREVIATIONS
SYMBOL DESCRIPTION
STRUCTURAL LEGEND
SYMBOL DESCRIPTION
No. Date Description
1 12/30/15 Revision 01
1
STRUCTURAL PRECAST CONCRETE NOTES
1. ALL PRECAST CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THE AMERICANCONCRETE INSTITUTE "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE" (ACI 318-08) AND THEDESIGN RECOMMENDATIONS OF THE PRECAST CONCRETE INSTITUTE MANUAL, "PCI DESIGN BOOK - PRECAST ANDPRESTRESSED CONCRETE," SIXTH EDITION.
2. THE PRECAST CONCRETE MANUFACTURER (PCM) SHALL BE RESPONSIBLE FOR THE DESIGN OF ALL PRECASTCONCRETE ELEMENTS SHOWN ON THE CONTRACT DOCUMENTS. DESIGN ALL ELEMENTS AND CONNECTIONS TORESIST THE VERTICAL AND HORIZONTAL LIVE, DEAD, WIND, AND SEISMIC LOADINGS INDICATED IN THE DESIGNNOTES ON SHEET S-001.
3. THE PCM SHALL BE RESPONSIBLE FOR THE DESIGN OF ALL LATERAL LOAD RESISTANCE OF THE PRECASTCONCRETE STRUCTURAL SYSTEM. THE LATERAL LOAD RESISTING SYSTEMS FOR THE BUILDING SHALL BE ASFOLLOWS:
A. PRECAST CONCRETE WALL SHALL ACT AS SHEAR WALLS. THESE SHEAR WALLS WILL PROVIDE ALL OF THELATERAL LOAD RESISTANCE FOR THE LONG DIRECTION OF THE BUILDING.
4. PRECAST CONCRETE SHALL ATTAIN THE FOLLOWING MINIMUM 28-DAY COMPRESSIVE STRENGTHS (f'c):
A. ALL ELEMENTS 5000 PSI
5. CONCRETE DENSITY SHALL BE NORMAL WEIGHT UNLESS SPECIFICALLY OTHERWISE NOTED.
6. CONCRETE REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60.
7. PRESTRESSING STRAND SHALL BE UNCOATED, 7-WIRE, LOW-RELAXATION STRAND CONFORMING TOASTM A416/A416M, GRADE 270.
8. GALVANIZE ALL STEEL CONNECTION MATERIAL EXPOSED TO WEATHER OR BELOW GRADE.
9. DESIGN AND PROVIDE ALL EMBEDDED ITEMS SHOWN ON THE CONTRACT DOCUMENTS TO RESIST THE LOADSINDICATED. ALL LOADS INDICATED ARE SERVICE LOADS UNLESS OTHERWISE NOTED.
10. DESIGN ALL PRECAST CONCRETE TO MEET THE FIRE RATING REQUIREMENTS INDICATED IN THE CONTRACTDOCUMENTS.
11. COORDINATE ALL ARCHITECTURAL RECESSES, TEXTURES, OPENINGS, AND SIZES OF PRECAST CONCRETE ELEMENTSWITH THE ARCHITECTURAL DRAWINGS.
12. VERIFY AND COORDINATE THE REQUIREMENTS OF THE STRUCTURAL DRAWINGS WITH THE DRAWINGS OF ALL OTHERDISCIPLINES INCLUDING, BUT NOT LIMITED TO, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL. PROVIDE ALLSLEEVES AND PENETRATIONS THROUGH THE PRECAST CONCRETE.
Y
X
Z
APPLIED FORCE COORDINATE
SYSTEM FOR CONNECTIONS
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:1
7 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
S-003
GENERAL NOTES
36
No. Date Description
1 12/30/15 Revision 01
1
CF
3.5
34'-0"
10 11 12 13 14 15 16 17
SJ, TYP
SJ, TYP
17'-8
"17
'-4"
17'-4
"17
'-8"
SJ, TYP
20'-0"
380'-0"
F12.0x6.0 F8.0x4.5 F8.0x4.5 F8.0x4.5 F8.0x4.5 F8.0x4.5 F8.0x4.5
F12.0x6.0 F8.0x4.5 F8.0x4.5 F8.0x4.5 F8.0x4.5 F8.0x4.5 F8.0x4.5CF3.0 CF3.0 CF3.0
CF3.0
1'-6" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 30'-2"6"
17'-4" 16'-6"
SF
SF
CF3.0
3
18 19 19.5 20
C
D
B
E
14'-0
" T
YP
SJ, TYP
EDGE OF SLAB
EDGE OFSLAB
EDGEOF SLAB
70'-8
"
20'-4
"30
'-0"
20'-4
"
4'-0" 12'-6"
F5.0F3.5F3.0
F6.0 F6.0
F6.0 F6.0
F3.5F5.0
F3.0
1SB301
TYP
2
SB301
2
SB301
2
SB301
1SB301
TYP
4
TYP
5
2
3
SB301
13'-2"
6
( -1'-4" )
TOF
( -2'-8" )
TOF
3
15'-10"
SJ, TYP
1'-4"
4"4"
( -2'-8" )
TOF
SF
SF( -2'-0" )
TOF
5SB301
6SB301
( -2'-0" )
7
7
SB301
16x20PILASTERS
16x20PILASTERS
2
TOF
MA
TC
H L
INE
SE
E S
B10
1
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:1
8 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
SB102
FOUNDATIONPLAN AREA B
39
1/8" = 1'-0"FOUNDATION PLAN AREA B
A B
1/8" = 1' - 0"0 5' 10' 15' 30'
GRAPHIC SCALE(S)
KEY NOTES
KEY PLAN
1. ALL ELEVATIONS REFERENCED FROM FINISHED FIRST FLOOR ELEVATION,542.75' = [0'-0"].
2. TOP OF FOOTING ELEVATION SHALL BE [-1'-4"], UNLESS OTHERWISE NOTED.
3. SPREAD AND CONTINUOUS FOOTINGS ARE NOTED ON PLAN AS Fx AND CFx,RESPECTIVELY. SEE FOOTING SCHEDULE ON SHEET SB501 FOR SIZE ANDREINFORCING.
4. CENTER SPREAD FOOTINGS UNDER COLUMNS. CENTER CONTINUOUS FOOTINGSUNDER WALLS, UNLESS OTHERWISE NOTED.
5. FOR TYPICAL FOUNDATION DETAILS, SEE SHEET SB501.
6. FOR ALL UTILITIES PASSING UNDER FOOTINGS WITH A CLEAR DISTANCE FROMBOTTOM OF FOOTING TO TOP OF UTILITY OF LESS THAN 1'-2". STEP FOOTING SOUTILITIES PASS OVER THE TOP OF FOOTING AS PER TYPICAL DETAIL ON SB501.
7. COORDINATE ALL FOOTING LOCATIONS WITH CIVIL, PLUMBING, AND ELECTRICALDRAWINGS.
8. SLAB-ON-GRADE SHALL BE 6" THICK REINFORCED WITH 6x6-W2.9xW2.9 WWF PLACED1 1/2" BELOW TOP OF SLAB. PLACE SLAB ON CONTINUOUS BARRIER SYSTEM ASSHOWN IN TYPICAL DETAILS ON SHEET SB501, OVER 4" POROUS FILL.
9. ALL EXTERIOR WALLS ARE 8" SOLID PRECAST CONCRETE PANELS UNLESSOTHERWISE NOTED.
FOUNDATION PLAN NOTES
10. PILASTERS SHOWN AT COLUMN LINES ARE 16"x36" PRECAST CONCRETE, INTEGRALWITH THE 8" SOLID PRECAST WALL PANELS, UNLESS OTHERWISE NOTED.
11. FOUNDATIONS FOR PEMB ARE DESIGNED BASED ON PRELIMINARY COLUMN BASEREACTIONS. SUBMIT FINAL COLUMN BASE REACTIONS TO ENGINEER OF RECORDFOR RECONCILIATION OF FOUNDATION DESIGN WITH FINAL PEMB DESIGN.
12. STEPPED FOOTINGS (SF) ARE SHOWN AT APPROXIMATE LOCATIONS OF PRECASTCONCRETE WALL PANEL ENDS. LENGTH OF STEP IS WIDTH OF ENTIRE PRECASTPANEL. COORDINATE LOCATION OF STEPS WITH PCM.
1 COORDINATE LOCATION AND EXTENT OF SLAB DEPRESSION FORBULLET TRAP SYSTEM WITH ACTUAL EQUIPMENT INSTALLED. SEESHEET AE101 FOR ADDITIONAL INFORMATION
2 SLAB DEPRESSION, SEE TYPICAL DETAIL ON SHEET SB502. COORDINATEEXTENTS AND LOCATION WITH ARCHITECTURAL DRAWINGS
3 CHANNEL DRAIN, SEE DETAIL ON SB301
4 PRE-ENGINEERED METAL BUILDING COLUMN
5 HAIRPIN REINFORCING IN SLAB. SEE TYPICAL DETAIL ON SHEET SB502
6 SEE "TYPICAL SLAB AT EXTERIOR OPENING" DETAIL ON SHEET SB501
7 8" CMU WALL PARTITION. ANCHOR TO SLAB PER "TYPICAL CMU WALLANCHORAGE" DETAIL ON SB501
No. Date Description
1 12/30/15 Revision 01
X
11
1
1
1
1
1'-4"
1'-4
"
3'-4" NTS
[SEE PLAN]
TOC
1
2(2) #5 CONT
(1) #6 CONT
PEMB EXTERIORPANELING BEYOND #4 AT 12" OC
3/4"
CLR CONCRETE SLAB ON GRADE
COL
TT
/2
CONCRETE FOOTING
PEMB COLUMN
HAIRPIN REINFORCING BAR
CONCRETE SLAB-ON-GRADE
BASE PLATE PER PEMB MFR.COORDINATE LOCATION,
DIAMETER, AND NUMBER OFANCHOR HOLES WITH
ENGINEER OF RECORD
[SEE PLAN]
TOC
[SEE PLAN]
TOF
DOWELS WITH 90°STANDARD HOOK
1
2
4SB301
2'-0
"
2'-0"
GRID
TURNED DOWNSLAB EDGE
(10) #7 DOWELS WITH 90° STDHOOKS INTO FOOTING
24"x24"CONCRETE PIER
#3 CLOSED TIESAT 4" OC, TYP
18 19
6"
CONCRETE FOOTING
PEMB COLUMN
HAIRPIN REINFORCING BAR
CONCRETE SLAB-ON-GRADE
[SEE PLAN]
TOC
[SEE PLAN]
TOF
DOWELS WITH 90°STANDARD HOOK
1
2
CONCRETE SLAB ON GRADE
PRECAST CONCRETE WALL
4
SB301SIM
NOTE:SEE SECTION 2 THISSHEET FOR ITEMSNOT SPECIFIED.
EQ EQ
2" RIGID INSULATION
18 19
CONCRETE FOOTING
CONCRETE SLAB-ON-GRADE
[SEE PLAN]
TOC
[SEE PLAN]
TOF
CONCRETE SLAB ON GRADE
PRECAST CONCRETE WALL
3'-0" NTS
1
2
#4 AT 12" OC
2" RIGID INSULATION
SEE PLAN
1'-0"
1'-0" 6"
SLOPE
#4 CONT, TYP
[SEE PLAN]
TOF
CONCRETEFOOTING
PRECAST CONCRETEWALL PANEL, SEE PLAN
[SEE PLAN]
TOC
DOWELEDCONSTRUCTION JOINT.
SEE TYPICAL DCJ DETAILON SHEET SB501
SLOPED CHANNEL DRAIN.SEE PLUMBING DWG
SHEET PF001 AND PF002
MIN6"
VA
RIE
S
1'-6"
2'-4"
[SEE PLAN]
TOC
2
1
SLAB ON GRADE
SLOPED CHANNELDRAIN. SEE PLUMBING
DWG SHEET PF002DOWELEDCONSTRUCTION JOINT.SEE TYPICAL DCJDETAIL ON SHEET SB501
#4 CONT, TYP
MIN6"
VA
RIE
S
#3 BARS AT 12" OC
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:1
9 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
SB301
FOUNDATIONSECTIONS
40
3/4" = 1'-0"1
SECTION 3/4" = 1'-0"
2SECTION
1 1/2" = 1'-0"4
SECTION
3/4" = 1'-0"3
SECTION
3/4" = 1' - 0"0 1' 5'6" 2' 3' 4'
GRAPHIC SCALE(S)
1 1/2" = 1' - 0"0 6" 1' 2'3" 9"
3/4" = 1'-0"5
SECTION 3/4" = 1'-0"
6SECTION
1" = 1'-0"7
SECTION
No. Date Description
1 12/30/15 Revision 01
1
1
'A' AND'C' BARSCONT
'B' AND'D' BARS
L
(
CO
NT
)
PLAN AT WALL
WALL
'A' AND'C' BARS
'B' AND'D' BARS
PLAN AT COLUMN
COLUMN,WALL SIMILAR
W
L
SECTION
'B' BARS'A' BARS
'D' BARS'C' BARS
W
T
W
BOTTOM REINFORCINGCONTINUOUSTHROUGH JOINT
TIE BAR EACH SIDE OFCONSTRUCTION JOINT
2" C
LR T
OP
(3) #5x4'-0" TOPCENTERED ON JOINT
SE
E P
L AN
T
PREVIOUS POUR NEW POUR
T/3
T/3
T/3
4" 4" PLAN ATINTERSECTION
PLAN ATCORNER
NOTES:
1. WHERE THREE OR MORE BARS OCCUR,CENTER BAR(S) SHALL BE TREATED AS ANINNER FACE BAR.
2. 'B' AND 'D' BARS NOT SHOWN FORCLARITY.
SEE FOOTINGSCHEDULE ON THISSHEET FORREINFORCING (TYP)
1'-6"1'-6"
TYP
1'-6"0" TYP
0" T
YP
1'-6
"
8" STEP
16" MIN FOR
16" STEP
32" MIN FOR
TYP3" CLR
MIN
1'-0"
16"
MA
X
8" M
IN
24"
MA
X
8" M
IN
CONTINUOUS WALL FOOTINGREINFORCING, SEESCHEDULE, THIS SHEET
2
1
'Z' BARS SAME SIZE ANDNUMBER AS CONTINUOUSFOOTING REINFORCING,BEND AS SHOWN
'A' BARS
'B' BARS
CONTINUOUS WALLFOOTING REINFORCING
2
1
24" STEP
48" MIN FOR
CONCRETESLAB-ON-GRADE
VAPOR RETARDER
POROUS FILL
T
3/4" DIA x16" LONG SMOOTHDOWEL AT 12" OC, COATEDTO PREVENT BOND
WELDED WIREFABRIC (TYP)
APPLY LIQUID CURING COMPOUNDALONG ENTIRE FACE OF PREVIOUSPOUR TO PREVENT BOND
NOTES:
1. POSITION DOWELS PERPENDICULARTO JOINT AND PARALLEL TO TOP OFSLAB.
2. SUPPORT DOWELS INDEPENDENTLYOF REINFORCING.
[SEE PLAN]
TOC
SEE PLAN
3" CLR ENDOF WWF
PREVIOUS POUR NEW POUR
1 1
/2"
UO
N
T/2
T/2
1'-4"
2" CLR
3'-0
"
45°
SEE ARCH DWGS
WALL OPENING
PLAN
#4 AT 12" OC TOPWITH STD 180° HOOK
12" LAP MIN
CONCRETESLAB-ON-GRADE
(1) #4 AT RE-ENTRANTCORNER, MIDDLE OFSLAB, EACH SIDE
(1) #4 CONT
EDGEOF SLAB
WALL (TYP)
PAVING, SEECIVIL DWGS
CONCRETE SLAB-ON-GRADE
#4 AT 12" OC
#4 AT 24" OCWITH STD 90° HOOK
SECTION
FOOTING, SEE SCHEDULEON SHEET SB101 FORSIZE AND REINFORCING
0"
[SEE PLAN]
TOC
(1) #5 CONT
1'-0"
3/4" CLR
(2) #5 CONT
PRECAST CONCRETE WALL PANEL BEYOND
FACE OF WALL PANELAND TURN-DOWN
1
1
CL FOOTING AND WALL
SL 1/4:12
3/4
"
3'-0" NTS
[SEE PLAN]
TOF
3/4" DIA x 16" LONGDOWEL PER DCJ
DETAIL THIS SHEET
PAVING ORFINISHED GRADE,SEE CIVIL DWGS
CONCRETESLAB-ON-GRADE
1/2" PJF
FOOTING, SEE SCHEDULEFOR SIZE AND REINFORCING
[SEE PLAN]
TOF
[SEE PLAN]
TOC
NON-SHRINK GROUTAS REQUIRED
PRECAST CONCRETEWALL PANEL, SEE PLAN
CL WALL PANELAND FOOTING
DETAIL 'A'
NOTES:1. PAINT STEEL BELOW GRADE
WITH TWO (2) COATS OF COALTAR EPOXY.
2. DETAIL SIMILAR AT INTERIORWALL.
COL
3" CLR,TYP
EMBED PL- 5/8x10x1'-4" WITH(4) 3/4" DIA x8" LONG SHEARSTUDS WELDED TO UNDERSIDEOF PLATE. COORDINATELOCATION WITH PRECASTPANEL SHEAR CONNECTIONS.
L4x4x1/2 x0'-8". COORDINATELOCATION WITH PRECASTPANEL SHEAR CONNECTIONS.
PANEL SHEARCONNECTIONBY PCM
DETAIL 'A'
(1) #5 x3'-0" BAR SHALLBE PLACED IN THE SLABWHERE CONTROL JOINTINTERSECTIONS DONOT OCCUR AT SLABRE-ENTRANT CORNERS
PLAN
2"
11
72"
MIN
BA
R L
AP
EM
BE
D
8"
#5 BAR IN WALL ENDGROUTED CELL
THICKENEDCONCRETE SLAB EDGE
CMU WALL, SEE B1 ANDB2/AE503
#5 DOWELS. DRILL AND EPOXYINTO CONCRETE BASE SLABWITH POWERS FASTENERS'
PE1000+ ADHESIVE SYSTEM ORAPPROVED EQUAL
#4 AT 12" OC, EACH WAY
CONCRETESLAB-ON-GRADE
FACE OF EQUIPMENT
EQUIPMENT PAD. SEEELECTRICAL AND MECHANICALDWGS FOR SPECIFICS
3/4" CHAMFER (TYP)
[SEE PLAN]
TOC
2" C
LR
6"
1/2" PJF (TYP)
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:2
0 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
SB501
TYPICALFOUNDATION/SLAB
DETAILS
41NOT TO SCALE
TYPICAL FOOTING REINFORCING DIAGRAM AND SCHEDULESNOT TO SCALE
TYPICAL CONCRETEFOOTING CONSTRUCTION JOINT
NOT TO SCALE
TYPICAL CONTINUOUSFOOTING REINFORCING
FOOTING SCHEDULE - COLUMN
MARK
DIMENSIONS REINFORCING
W L T 'A' BARS 'B' BARS 'C' BARS 'D' BARS
F3.0 3'-0" 3'-0" 1'-4" 4-#6 4-#6 3-#6 3-#6
F3.5 3'-6" 3'-6" 1'-4" 5-#6 5-#6 4-#6 4-#6
F5.0 5'-0" 5'-0" 2'-0" 7-#7 7-#7 5-#6 5-#6
F6.0 6'-0" 6'-0" 2'-0" 8-#7 8-#7 6-#6 6-#6
F8.0x4.5 4'-6" 8'-0" 1'-6" 5-#7 8-#7 4-#6 6-#6
F12.0x6.0 6'-0" 12'-0" 1'-6" 6-#7 12-#7 5-#6 9-#6
NOT TO SCALE
TYPICAL STEPPED FOOTING
NOT TO SCALE
TYPICAL DOWELEDCONSTRUCTION JOINT (DCJ)
NOT TO SCALE
TYPICAL SLAB AT EXTERIOR OPENING
FOOTING SCHEDULE - WALL
MARK
DIMENSIONS REINFORCING
W T 'A' BARS 'B' BARS 'C' BARS 'D' BARS
CF3.0 3'-0" 1'-4" 4-#6 #6 AT 9" OC - -
CF3.5 3'-6" 1'-4" 5-#6 #6 AT 9" OC 4-#5 -
NOT TO SCALE
TYPICAL FOUNDATION DETAIL AT EXTERIOR PRECAST WALL
NOT TO SCALE
TYPICAL SLAB RE-ENTRANTCORNER REINFORCEMENT
NOT TO SCALE
TYPICAL CMU WALL ANCHORAGE
NOT TO SCALE
TYPICAL INTERIOR CONCRETESLAB-ON-GRADE EQUIPMENT PAD
No. Date Description
1 12/30/15 Revision 01
1
10 11 12 13 14 15 16 17
SLOPE DN SLOPE DN SLOPE DN SLOPE DN SLOPE DN SLOPE DN
F
A
SLOPE DN
1/4":1'-0"
SLOPE DN
1/4":1'-0"
5SF201
20'-0"
380'-2"
TR
US
S [+
22'-0
"]
TR
US
S [+
22'-0
"]
TR
US
S [+
22'-0
"]
TR
US
S [+
22'-0
"]
TR
US
S [+
22'-0
"]
TR
US
S [+
22'-0
"]
TR
US
S [+
22'-0
"]
TR
US
S [+
22'-0
"]
W14
X26
AT
5'-0
" O
C
71'-4
"
18 19 19.5 20
C
D
B
E
12 S
PA
AT
5'-0
" O
C =
60'
-0"
W12X19
(TYP, UON)
TOS [+15'-0"]
TOS [+22'-0"]
12 S
PA
AT
5'-0
" O
C =
60'
-0"
W12X19
(TYP, UON)
TOS [+15'-0"]
TOS [+22'-0"]
1
SF301
1
SF301
2SF301
2SF301
2
SF301
2
SF301
2
SF301
2
SF3013
SF301
3
SF301
1SF301
MA
TC
H L
INE
SE
E S
F10
1
3
3
1
2
3
3
INTERMEDIATE PEMBROOF MEMBERS NOT
SHOWN, TYP
1'-6"20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 30'-2" 17'-10"
20'-8
"30
'-0"
20'-8
"
TYPTYP
4
SF301TYP ATBEAM
BUILDING JOINT7
SF301
7
SF301
8SF301
TYP
AT SLOPED BEAMHIGH, TYP
AT SLOPED BEAMHIGH, TYP
AT SLOPED BEAMHIGH, TYP
AT SLOPED BEAMHIGH, TYP
AT SLOPED BEAMHIGH, TYP
AT SLOPED BEAMHIGH, TYP
AT STEEL BAFFLESLOWER, TYP
AT STEEL BAFFLESLOWER, TYP
[ 21'-4 5/8" ].
TOS TYP
4'-5
"4'
-5"
4'-5
"4'
-5"
, SLOPED , SLOPED
9
SF301TYP AT JOINT
1000 LBS
10
SF301HSS8X8X3/8 [+21'-11"]
HSS8X8X3/8 [+21'-11"]
HSS8X8X3/8 [+21'-11"]
2"
0"
17'-3
"17
'-3"
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:2
1 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
SF102
ROOF FRAMINGPLAN AREA B
44
1/8" = 1'-0"ROOF FRAMING PLAN AREA B
1/8" = 1' - 0"0 5' 10' 15' 30'
GRAPHIC SCALE(S)
KEY NOTES
KEY PLAN
FRAMING PLAN NOTES
A B
1 ROOF HATCH. COORDINATE SIZE AND LOCATION WITHARCHITECTURAL DRAWINGS
2 MECHANICAL EQUIPMENT. COORDINATE SIZE, LOCATION ANDREQUIRED ROOF PENETRATIONS WITH ARCHITECTURAL ANDMECHANICAL DRAWINGS. WEIGHTS SHOWN ARE BASED ON GENERALMODELS. IF WEIGHT OF FINAL EQUIPMENT SELECTED EXCEEDSWEIGHT SHOWN ON DRAWINGS BY MORE THAN 5%, INFORMENGINEER OF RECORD
3 PRE-ENGINEERED METAL BUILDING FRAME BY MANUFACTURER
1. ALL ELEVATIONS REFERENCED FROM FINISHED FLOOR ELEVATION [0'-0"].
2. ROOF CONSTRUCTION SHALL BE 1 1/2" DEEP STEEL ROOF DECK PER 'STEEL DECKNOTES' ON SHEET S-002, UNLESS OTHERWISE NOTED.
3. SEE SHEET SF201 FOR ELEVATION AND DETAILS OF STEEL TRUSS FRAMING.
4. TOP OF PRECAST WALL PANEL = [+23'-4"], UNLESS OTHERWISE NOTED.
5. STEEL ROOF DECK DIAPHRAGM PROVIDES THE PERMANENT LATERAL BRACING FORTHE TRUSS TOP AND BOTTOM CHORDS. THE CONTRACTOR SHALL PROVIDETEMPORARY LATERAL BRACING FOR THE TRUSSES UNTIL ALL DIAPHRAGMCONSTRUCTION IS COMPLETE, INCLUDING DIAPHRAGM CONNECTIONS TO THEPRECAST CONCRETE WALLS.
6. ALL EXTERIOR WALLS ARE 8" SOLID PRECAST CONCRETE PANELS UNLESSOTHERWISE NOTED.
7. PILASTERS SHOWN AT COLUMN LINES ARE 16"x36" PRECAST CONCRETE, INTEGRALWITH THE 8" SOLID PRECAST WALL PANELS, UNLESS OTHERWISE NOTED.
8. ALL STRUCTURAL STEEL SHALL BE COATED WITH HIGH PERFORMANCE PRIMER ANDPAINT PER "HIGH PERFORMANCE COATINGS" AND "STRUCTURAL STEEL FRAMING"SPECIFICATIONS. APPLY PRIMER PRIOR TO INSTALLATION OF STEEL ROOF DECK.
No. Date Description
1 12/30/15 Revision 01
X
1
1
1
CL TRUSS
[SEE PLAN]
TOS
STEEL TRUSS TOPCHORD MEMBER
STEEL TRUSSWEB MEMBER
STEEL BEAM, SEE PLAN
STEEL ROOFDECK
ROOFING,SEE ARCH
HIGH
LOW
STEEL TRUSSWEB MEMBER
PL 3/8x3x0'-3" BENT, CONT
[SEE SF201]
BOS
NOTE:SEE SHEET SF201 FOR TRUSSDETAILS AND MEMBER SIZES.
STEEL TRUSS BOTTOMCHORD MEMBER
STEEL BEAM, SEE PLAN
STEEL ROOF DECK
ROOFING, SEE ARCH
3/16
SLIP-CRITCAL CONNECTION
3/16 2-123/16 2-12
L3x2x1/4 (LLV) CONT
3/16 3-24
PL1/4x4x0'-4" BENT, CONT
1/4
L2x2x3/8 x 0'-8" @ 8'-0" OC
A
PRECASTCONCRETE WALL
EMBEDDED PLATE,CONT, WITH 3/4"ØTHREADED STUDSWELD TO FACE AT18" OC
SLOPED STEELBEAM, SEE
PLAN 7"
3/16 4-18
STEEL ROOF DECK
CL BEAM
L7x4x3/8 (LLH) CONTWITH VERT SLOTTED
HOLES AT 18" OC
NOTE:LOADS PER DIAGRAM IN #9 OF"STRUCTURAL PRECAST CONCRETENOTES" ON SHEET S-003 ARE AS FOLLOWS:
x = 0.4 k/fty = 0.48 k/ftz = 0.60 k/ft F
1/4" RANDOMORIENTED FIBER PAD
PRECASTCONCRETE WALL
EMBEDDEDPLATE AT 24" OC
F
[SEE PLAN]
TOC
[VARIES]
TOS
ROOFING, SEE ARCH
STEEL ROOF DECK 3/16 4-243/16 4-24
STEEL BEAM, SEE PLAN
L4x4x3/8 CONT
A
NOTE:LOADS PER DIAGRAM IN #9 OF"STRUCTURAL PRECAST CONCRETENOTES" ON SHEET S-003 ARE AS FOLLOWS:
x = 0.54 k/fty = 0.3 k/ftz = 1.1 k/ft
[SEE PLAN]
TOC
[SEE PLAN]
TOS BEAM END
PRECAST CONCRETEPANEL, SEE PLAN
STEEL ROOF DECK
ROOFING, SEE ARCH1/4 41/4 4
STEEL BEAM,SEE PLAN
BEARING PL1/2x6x0'-7" ON1" NON-SHRINK GROUTWITH (2) 5/8"Ø x 6" LONGHEADED STUDSEMBEDDED IN PRECASTCORBEL
PRECASTCONCRETE CORBEL,CONT
NOTE:LOADS PER DIAGRAM IN #9 OF"STRUCTURAL PRECAST CONCRETENOTES" ON SHEET S-003 ARE AS FOLLOWS:
x = 0.50 lb/fty = 1.15 k/ftz = 0.50 k/ft
[SEE PLAN]
TOS
PRECAST CONCRETEPANEL, SEE PLAN
PRECAST CONCRETECORBEL, CONT
EMBEDDED PLATEAT 24" OC
L4x4x3/8, CONT
3/16 4-243/16 4-24
ROOFING, SEE ARCH
STEEL ROOF DECK
STEEL BEAM BEYOND
NOTE:LOADS PER DIAGRAM IN #9 OF"STRUCTURAL PRECAST CONCRETENOTES" ON SHEET S-003 ARE ASFOLLOWS:
x = 0.15 k/fty = 0.20 k/ftz = 0.30 k/ft
2
CL TRUSS
STEEL BEAM,SEE PLAN
STEEL TRUSSWEB MEMBER
[SEE PLAN]
TOS
STEEL TRUSS TOPCHORD MEMBER
STEEL ROOFDECK
ROOFING,SEE ARCH
10" SOLID PRECASTWALL PANEL
EMBEDDED PL BY PCMAT 6'-0" OCY = 1k,Z = 3k
PROVIDE (2) 1/2" ØBOLTS PER 4' BAFFLE
PANEL (MIN)
BAFFLE SYSTEM
L3x3x5/16 (CONT) FORSUPPORT OF BAFFLESYSTEM, COORD WITHBAFFLE SYSTEM MFR
NOTE:SEE SHEET AE301 FORARCHITECTURAL DETAILS
A
3/16 1
NOTE:1. ENSURE THAT THE BAFFLE HANGERS
ARE PLUMB WITHIN A MAXIMUMTOLERANCE OF 1/2" HORIZONTAL PER1'-0" VERTICAL.
2. COORDINATE LOCATIONS OF STEELBRACKET SUPPORTS WITH BAFFLESYSTEM MFR.
BAFFLE SYSTEM
WIRE ROPE. 1750 LBCAPACITY (MIN)
WIRE ROPE ENDFITTING. 3500 LBCAPACITY (MIN)
[+13'-1"]
BOTTOM OF BAFFLESYSTEM
MAXIMUM SPACING BETWEEN WIRE ROPE = 10'-0"
STEEL BRACKET SUPPORTFOR UPPER CABLE, EACHSLOPED BEAM, BY BAFFLESYSTEM MFR
SLOPED STEEL BEAM,SEE PLAN
10 11
SEE PLAN
8"3/16 3-12
TYP
[SEE PLAN]
TOS TRUSS
STEEL TRUSS TOPCHORD MEMBER
3/16 3-12
PL3/8x8x CONT
ROOFING,SEE ARCH
STEELBEAM, SEE
PLAN
STEELTRUSS WEB
MEMBER
STEEL BEAM, SEE PLAN
[SEE PLAN]
TOS HSS
17
CL TRUSS
STEEL BEAM,SEE PLAN
STEEL TRUSSWEB MEMBER
[SEE PLAN]
TOS
STEEL BEAM,SEE PLAN
STEEL TRUSS TOPCHORD MEMBER
STEEL ROOFDECK
ROOFING,SEE ARCH
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:2
3 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
SF301
FRAMINGSECTIONS
46 3/4" = 1'-0"1
SECTION 1" = 1'-0"
2SECTION
1" = 1'-0"3
SECTION
1" = 1'-0"4
SECTION
1" = 1'-0"6
SECTION
1" = 1'-0"5
SECTION
3/4" = 1' - 0"0 1' 5'6" 2' 3' 4'
GRAPHIC SCALE(S)
1" = 1' - 0"0 6" 1' 3'2'
1 1/2" = 1'-0"7
SECTION
3/4" = 1'-0"8
SECTION
1" = 1'-0"9
SECTION 1" = 1'-0"
10SECTION
No. Date Description
1 12/30/15 Revision 01
1. ALL STRUCTURAL STEEL SHALL BE COATED WITHHIGH PERFORMANCE PRIMER AND PAINT PER"HIGH PERFORMANCE COATINGS" AND"STRUCTURAL STEEL FRAMING" SPECIFICATIONS.APPLY PRIMER PRIOR TO INSTALLATION OF STEELROOF DECK.
GENERAL NOTES
1
1
1
SIDE LAP FASTENERS,SEE SHEET S-002
PUDDLE WELD, TYP
WIDTH OF SHEET
VARIES
STEEL ROOF DECK,SEE PLAN
PUDDLE WELDSAROUND PERIMETEROF BUILDING, SEESHEET S-002 FORSIZE AND SPACING
NOTE:SEE SHEET S-002 FOR STEELDECK SIZE, GAGE, WELD SIZE,WELD PATTERN, AND SIDE LAPCONNECTIONS
CENTER LINEOF SUPPORT
CENTER LINEOF SUPPORT
BEAM, TYP
OPENING
L4x4x1/4 FRAMEAROUND OPENINGS, TYP
SEE FRAMING PLAN
SPACING
PLAN SECTION A-A
STEEL ROOFDECK, SEE PLAN
OPENING
L5x5x5/16x0'-5" LONGEACH END OF L4x4, TYP
AA
3/163/16
TYP
NOTE:SEE SHEET S-002 FOR STEEL DECKSIZE, GAGE, WELD SIZE, WELDPATTERN, AND SIDE LAP CONNECTIONS
SIDE LAP FASTENERS,SEE SHEET S-002
STEEL ROOFDECK, SEE PLAN
1 1
/2"
36/3 PATTERN
36/4 PATTERN
36/5 PATTERN
36/7 PATTERN
36" COVER WIDTH
AISC STANDARDSHEAR CONNECTION
GIRDER, SEE PLAN
[SEE PLAN]
TOS
BEAM, SEE PLAN
SIMILAR ATHSS BEAM
PARTIAL ROOF PLAN DECK PARALLEL TO MECHANICAL UNIT
1"
STEEL ROOFDECK
DECKSUPPORTANGLE
CL BEAM
MECH UNIT, SEEMECH DWGS
BEAM SUPPORTFOR MECH UNIT,SEE PLAN FOR SIZE
OUTSIDE EDGEOF CURB
STEEL ROOFDECK
CL BEAM
MECH UNIT, SEEMECH DWGS
BEAM SUPPORTFOR MECH UNIT,SEE PLAN FOR SIZE
NOTES:
1. WELD STEEL ROOF DECK TO DECKSUPPORT ANGLE AT 6" OC.
2. IF REQUIRED SPAN OF DECK SUPPORTANGLE EXCEEDS 10' - 0", CONTACTSTRUCTURAL ENGINEER OF RECORD.
OUTSIDE EDGEOF CURB
DECK SUPPORT ANGLE SIZE
0'-0" TO 6'-0" 6'-1" TO 10'-0"
BEAMS FOR MECH UNITCURB SUPPORT, SEEROOF PLAN FOR SIZE
ANGLE NOT REQUIREDIF 1' - 6" OR LESS
DECK SUPPORTANGLES, SEETABLE FOR SIZE
MECH ROOFTOP UNIT
MAIN ROOF BEAMS ORJOISTS, SEE PLAN FORSIZE AND SPACING
5"
BEAMS FOR MECH UNITCURB SUPPORT, SEEROOF PLAN FOR SIZE
TY
P
SE
E P
LAN
DECK SUPPORTANGLES, SEETABLE FOR SIZE
DECK PERPENDICULAR TO MECHANICAL UNIT
L3x3x1/4 L4x4x1/4
(2) 3/8Ø x 3 1/4" HEADEDSTUDS AT 12" OC
PRECAST CONCRETEINSULATED WALL PANEL
MC8x8.5 HOT DIPGALVANIZED
8"
NOTE:SEE SHEET AE601 FORHEADER CONDITION.
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
C:\U
sers
\mw
hitaker\
Docum
ents
\5404-U
nio
n C
o F
irin
g R
ange S
14_m
whitaker.
rvt
12/2
9/2
015 1
1:5
2:2
3 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
MBW
CTG
BSW
SF501
TYPICALFRAMINGDETAILS
47
NOT TO SCALE
TYPICAL ROOF DECK ATTACHMENTNOT TO SCALE
TYPICAL DECK SUPPORT AT ROOF OPENINGSNOT TO SCALE
STEEL ROOF DECKFASTENING REQUIREMENTS
NOT TO SCALE
TYPICAL BEAM-TO-GIRDERCONNECTION
NOT TO SCALE
TYPICAL ROOF MECHANICAL UNIT SUPPORT
No. Date Description
1 12/30/15 Revision 01
NOT TO SCALE
TYPICAL OVERHEADDOOR JAMB
1. ALL STRUCTURAL STEEL SHALL BE COATED WITHHIGH PERFORMANCE PRIMER AND PAINT PER"HIGH PERFORMANCE COATINGS" AND"STRUCTURAL STEEL FRAMING" SPECIFICATIONS.APPLY PRIMER PRIOR TO INSTALLATION OF STEELROOF DECK.
GENERAL NOTES
1
AE202C1
AE201A1
AE202B1
A2AE301
A2AE301
114C
C1AE301
C1AE301
380'-2"2 3 4 5 6 7 8 9
A
F
34' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0"
MATC
HLIN
EAE
102
14-LANERANGE
114
3
4
6
12
71' -
4"
109
LANE MARKINGS FORREFERENCE ONLY, NIC
12
34
56
78
910
1112
1314
114D
12
34
56
78
910
1112
1314
1
15
1
12
1314
12
34
56
78
910
1112
1314
12
34
56
78
910
1112
1314
12
34
56
78
910
1112
1314
12
34
56
78
910
1112
1314
10 10 10 10
3
3
TYP
12' - 0" 24' - 0" 30' - 0" 75' - 0"4' - 6"75'-0" TO 75YARD LINE
D2AE501
18
4' - 6"
17
26' - 0"15
22 TYP
TYP
19
SEE C5/AE501 FORBULLET RESISTANTDOOR DETAILS
145' - 8"
2' - 0"
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
26 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE101
FLOOR PLANAREA A
491/8" = 1' - 0"
0 5' 10' 15' 30'
A B
KEY PLAN
11 RECESSED HVAC/LIGHTING CONTROL PANEL, SEE DETAILB1/AE503
12 CONCRETE EQUIPMENT PAD, SEE SHEET CI10213 DUST COLLECTION UNIT14 SCREW CONVEYOR SYSTEM, SEE DETAIL C3/AE501 FOR
PRECAST WALL PENETRATION15 MECHANICAL EQUIPMENT17 TARGET LINE, 0 YARD LINE18 CONCRETE SIDEWALK, SEE SHEET CI10219 HEAVY DUTY CONCRETE PAVING, SEE SHEET CI10220 CHANNEL DRAIN, SEE DETAIL 7/SB30121 MB DOWNSPOUT22 PRECAST CONCRETE PILASTER
1 PRECAST CONCRETE WALL PANEL2 METAL BUILDING SYSTEM3 METAL DOWNSPOUT4 BULLET TRAP5 BOLLARD, SEE SHEET CI5016 CHANNEL DRAIN, SEE DETAIL 6/SB3017 EXPANSION JOINT, SEE DETAIL A3/AE5038 WATER HEATER9 4" WIDE X 12" LONG YELLOW PAINTED FIRING LINE WITH 8"
TALL YELLOW PAINTED LANE NUMBERS, CENTERED IN LANEAT 1.5 YARD LINE
10 4" WIDE YELLOW PAINTED FIRING LINE WITH 8" TALLYELLOW PAINTED LANE NUMBERS
1/8" = 1'-0"FLOOR PLAN AREA A
PLAN NOTES#GENERAL NOTES1. DOOR OPENINGS SHOWN IN PRECAST CONCRETE WALLS ARE OF
NOMINAL DIMENSIONS. MANUFACTURE WALL PANELS WITH OPENINGSSIZED TO ALLOW INSTALLATION OF DOOR AND FRAME.
2. SEE ELECTRICAL DRAWINGS FOR NOTES REGARDING ACCEPTABLELOCATIONS FOR SURFACE MOUNTED ELECTRICAL REACEWAYS ANDCONDUIT.
3. PROVIDE SEAL AT ALL PENETRATIONS OF EXTERIOR WALLS.SEE SHEETS GI003-GI004 FOR UL DETAILS FOR PENETRATIONSOF FIRE RATED WALLS.
No. Date Description1 12/30/2015 Revision 01
1
1
AE201C1
ARMORY110
LAUNDRY112
ELECTRICAL115
WOMEN111
MEN109
CORRIDOR102
WEAPONCLEANING
108
RANGESTORAGE
106
OFFICESTORAGE
105A
DATA107
COPYROOM
105
DIRECTOR'SOFFICE
103
VESTIBULE101
AGENCYOFFICE
104
14-LANERANGE
114
1
103104
105
106
105A
108
108A
110
109
111
112
115114B
114
114A
AE401A4
A1AE301
A1AE301
B1AE301
B1AE301
DW
380'-2"10 11 12 13 14 15 16 17
A
F
1' - 6" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0"
MATC
HLIN
EAE
101
AE202A1
23
45
67
89
1011
1213
14
FEC
FEC
10
11
8
7
7
621
30' - 2"
15
3
107
3' - 4
"10
' - 4"
4' - 0
"
MB STRUCTURE LINE
MB STRUCTURE LINE
PLUMBING113
113
15
12
34
56
78
910
1112
1314
10
D
C
18
18
B
E
20
20
33' - 10"
70' -
8"
12
19
19
6"
2
112
101A
1' - 10"
3' - 4" 3' - 4"
75' - 0"
18
18
19
18
18
12' - 0" 4' - 8" 6' - 6" 3' - 4" 7' - 4"
B1AE201
20
75'-0" TO 50 YARD LINE
FEB
FEB
18' - 4"
10' - 0" 8" 3' - 4"
MB STRUCTURE LINE
MB STRUCTURE LINE
3 TYP
TYP
20' -
4"30
' - 0"
20' -
4"
21
LANE MARKINGS FOR REFERENCE ONLY, NIC
4' - 0
"3'
- 4"
18' -
4"6'
- 4"
21' -
8"
21
21
5
4' - 8" 13' - 4"
1' - 8
"
ENTRANCE FLOORGRILLE
CONCRETE SLAB
SEE SHEET SB502 FOR SLABDEPRESSION DETAILS.COORDINATE DEPTH OF SLABDEPRESSION WITH FLOORGRILLE DEPTH
GROUT
2"ALIGN FRAME OF GRILLEWITH VCT
SEE A4/AE401 FORGRILLE DIMENSIONS
VCT
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
28 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE102
FLOOR PLANAREA B
50
1/8" = 1'-0"FLOOR PLAN AREA B
1/8" = 1' - 0"0 5' 10' 15' 30'
A BKEY PLAN
11 RECESSED HVAC/LIGHTING CONTROL PANEL, SEE DETAILB1/AE503
12 CONCRETE EQUIPMENT PAD, SEE SHEET CI10213 DUST COLLECTION UNIT14 SCREW CONVEYOR SYSTEM, SEE DETAIL C3/AE501 FOR
PRECAST WALL PENETRATION15 MECHANICAL EQUIPMENT17 TARGET LINE, 0 YARD LINE18 CONCRETE SIDEWALK, SEE SHEET CI10219 HEAVY DUTY CONCRETE PAVING, SEE SHEET CI10220 CHANNEL DRAIN, SEE DETAIL 7/SB30121 MB DOWNSPOUT22 PRECAST CONCRETE PILASTER
1 PRECAST CONCRETE WALL PANEL2 METAL BUILDING SYSTEM3 METAL DOWNSPOUT4 BULLET TRAP5 BOLLARD, SEE SHEET CI5016 CHANNEL DRAIN, SEE DETAIL 6/SB3017 EXPANSION JOINT, SEE DETAIL A3/AE5038 WATER HEATER9 4" WIDE X 12" LONG YELLOW PAINTED FIRING LINE WITH 8"
TALL YELLOW PAINTED LANE NUMBERS, CENTERED IN LANEAT 1.5 YARD LINE
10 4" WIDE YELLOW PAINTED FIRING LINE WITH 8" TALLYELLOW PAINTED LANE NUMBERS
1" = 1' - 0"0 6" 1' 3'2'
PLAN NOTES#
6" = 1'-0"D3FLOOR GRILLE DETAIL
No. Date Description1 12/30/2015 Revision 01
1
C1AE301
C1AE301
2 3 4 5 6 7 8 9
A
F
13'-0"
114
MATC
HLIN
EAE
104
7
4
SLOPE12 : 12
1
3
13'-0" SLOPE12 : 12
3
13'-0" SLOPE12 : 12
3
13'-0" SLOPE12 : 12
3
13'-0" SLOPE12 : 12
3
13'-0" SLOPE12 : 12
3
13'-0"
8
TYP
9
SLOPE12 : 12
9
SLOPE7 : 12
9
SLOPE7 : 12
3
10
20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0"
7 7 7 7 7 7 7
26' - 8" 7' - 0"
DIMENSIONS ARE TO LEADING EDGE OF EACH BAFFLE
18' - 8"
A3AE501
TYP
11
3 3 3 3 3 3
13TYP
8" X 4" X 1/4"BENT PLATE
CONT 1 5/8"SLOTTED CHANNEL
ARS BAFFLE
TARGET LIGHTFIXTURE
1' - 0"
PROVIDE SHEET OFSHREDDED RUBBER 1" THICKAND SAME DIMENSION AS THEBOTTOM OF THE FIXTUREMOUNTING PLATEARCHITECTURALJUNCTION BOX PROVIDEDWITH LIGHTING FIXTURE
38" X 6" X 1/4" STEEL PLATECONT 1 5/8" SLOTTED CHANNELARS CEILINGSOUND ABSORPTION PANELS
LIGHT FIXTURE
BOS13'-8"
CEILING13'-0"
PROVIDE SHEET OF SHREDDEDRUBBER 1" THICK AND SAMEDIMENSION AS THE BOTTOM OF THEFIXTURE MOUNTING PLATE
JUNCTION BOX
NOTE: SEE DETAIL 'C4' ON SHEET EL502 FOR TYPICAL INSTALLATION
JUNCTION BOX
XPPOWER 100W DLGSERIES LED DRIVER
FRONT VIEW TOP VIEW
CONT 1 5/8" SLOTTED CHANNELFASTENER
FASTENER
FASTENER
LIGHT FIXTUREJUNCTION BOX
JUNCTION BOX
XPPOWER 100W DLGSERIES LED DRIVER
LIGHT FIXTUREJUNCTION BOX
BOS13'-8"
FIXTURE MOUNTINGPLATE
LIGHTING FIXTURE
PROVIDE SHEET OF SHREDDEDRUBBER 1" THICK AND SAMEDIMENSION AS THE BOTTOM OFTHE FIXTURE MOUNTING PLATE
1/2" FLEX
JUNCTION BOX
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
29 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE103
REFLECTEDCEILING PLAN
AREA A
51 1/8" = 1'-0"REFLECTED CEILING PLAN AREA A
1/8" = 1' - 0"0 5' 10' 15' 30'
A B
KEY PLAN
1 2'X4' ACOUSTICAL PANEL CEILING2 2'X2' ACOUSTICAL PANEL CEILING3 ARS CEILING BAFFLE W / SOUND ABSORPTION PANEL4 LINE OF 180 DEGREE TURNING TURNING TARGET SYSTEM5 STEEL LADDER AND ROOF HATCH6 RADIAL DIFFUSER7 EXPOSED STRUCTURE8 TARGET LIGHTING, SEE DETAIL C2/AE1039 ARS CEILING BAFFLE10 LINE OF RUNNING MAN TARGET SYSTEM11 RANGE LIGHTING, SEE DETAL C1/AE10312 CLOSE GAP BETWEEN RADIAL DIFFUSER AND ADJACENT WALLS
USING MIN.029" THICK GALV STEEL SHEET FORMED TO MATCHPROFILE OF DIFFUSER. ATTACH WITH SHEET METAL SCREWS @6" OC MAX. PAINT TO MATCH DIFFUSER.
13 STROBE LIGHTING, SEE C3/AE103
REFLECTED CEILING PLAN NOTES#
1 1/2" = 1'-0"C2
TARGET LIGHT MOUNTINGDETAIL (TYPE D)
1 1/2" = 1'-0"C3LIGHT MOUNTING DETAIL (TYPE W)
1 1/2" = 1'-0"C1
RANGE LIGHT MOUNTINGDETAIL (TYPE F)
SHREDDED RUBBER SHEET: CONSISTING OFRECYCLED RUBBER PARTICLES IN ADHESIVEBINDER; SERVICE TEMPERATURE RANGE 10DEGREES F TO 150 DEGREES F; DUROMETERHARDNESS 50 TO 60, SHORE A; THICKNESS 1/2" TO3/4", BLACK COLOR
No. Date Description1 12/30/2015 Revision 01
1
B1AE301
B1AE301
9'-0"
9'-0"
9'-0"
9'-0"
9'-0" 9'-0"9'-0"
9'-0"
9'-0"
9'-0"9'-0"
9'-0"
9'-0"
108
102
103
101
104
107
105A
106
109
111
115112
110
105
10 11 12 13 14 15 16 17
A
F
114
MATC
HLIN
EAE
103
1
5
613'-0"
D
C
18
B
E
2019
D3AE104
7
7
2
13'-0" SLOPE12 : 12
3
13'-0" SLOPE12 : 12 13'-0" SLOPE
12 : 12
3
13'-0"
3
13'-0" SLOPE12 : 12
3
13'-0" SLOPE12 : 12
3
13'-0" SLOPE12 : 12
3
13'-0"
3
D2AE104
7777777
21' - 6" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 14' - 8" 13' - 4" 2' - 6"
11
TYP
DIMENSIONS ARE TO LEADINGEDGE OF BAFFLES
3333333
ACCESSPANEL
7
12
AE104D1
9'-0"
PROVIDE 3 1/2" SOUNDATTENUATING BLANKETS ABOVEACOUSTICAL PANEL CEILING INROOMS 103,104. DO NOT COVERLIGHT FIXTURES.
FINISH FLOOR0'-0"
ACOUSTICALPANEL CEILING
CORRIDOR CEILINGCONSTRUCTED ASWALL PER 2012NORTH CAROLINASTATE BUILDINGCODE ARTICLE 709.4,EXCEPTION 3.
S4R1S4R1
S4R1
SEE REFLECTEDCEILING PLAN FORHEIGHT
CEILING12'-0"
ACOUSTICALPANEL CEILING
CONT 2"X2"X3/16"STEEL ANGLE
ARS CEILING BAFFLE W/SOUND ABSORPTIONPANEL
+13'-0"
FRT 2X4 WDBLOCKING
METAL TRIM. PAINT PT-1
F
18CLOSE GAP BETWEEN RADIAL DIFFUSER ENDS ANDADJACENT WALL USING MIN .029" THICK GALVANIZEDSTEEL SHEET, FORMED TO MATCH DIFFUSER PROFILE.ATTACH TO DIFFUSER WITH SHEET METAL SCREWS AT6" OC MAX. PAINT CLOSURE TO MATCH DIFFUSER.
ACOUSTICAL PANEL CEILINGEXTRUDED ALUMINUM EDGE TRIM
ARS CEILING BAFFLEWITH SOUNDABPORPTION PANEL
ACOUSTICAL PANEL CEILING
LIGHT FIXTURERADIALDIFFUSER
OVERHEADCOILING DOOR
114A
8"
8"
8"
D2AE104
SOUND ABSORPTION PANEL
PRECAST CONCRETE WALL PANEL
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
32 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE104
REFLECTEDCEILING PLAN
AREA B
52
1/8" = 1'-0"REFLECTED CEILING PLAN AREA B
1/8" = 1' - 0"0 5' 10' 15' 30'
A B
KEY PLAN
3/8" = 1'-0"D3CORRIDOR CEILING DETAIL
1 1/2" = 1'-0"D2CEILING DETAIL
1 2'X4' ACOUSTICAL PANEL CEILING2 2'X2' ACOUSTICAL PANEL CEILING3 ARS CEILING BAFFLE W / SOUND ABSORPTION PANEL4 LINE OF 180 DEGREE TURNING TURNING TARGET SYSTEM5 STEEL LADDER AND ROOF HATCH6 RADIAL DIFFUSER7 EXPOSED STRUCTURE8 TARGET LIGHTING, SEE DETAIL C2/AE1039 ARS CEILING BAFFLE10 LINE OF RUNNING MAN TARGET SYSTEM11 RANGE LIGHTING, SEE DETAL C1/AE10312 CLOSE GAP BETWEEN RADIAL DIFFUSER AND ADJACENT WALLS
USING MIN.029" THICK GALV STEEL SHEET FORMED TO MATCHPROFILE OF DIFFUSER. ATTACH WITH SHEET METAL SCREWS @6" OC MAX. PAINT TO MATCH DIFFUSER.
13 STROBE LIGHTING, SEE C3/AE103
REFLECTED CEILING PLAN NOTES#
1/2" = 1'-0"D1CEILING DETAIL AT COILING DOOR
1
No. Date Description1 12/30/2015 Revision 01
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
A
FDS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
DS
37
6
3
C3AE503
D
C
18
B
E
20
1
SLOPE1 : 12SLOPE
TYP
191
8' - 0
"
SLOPE1/4 : 12
SLOPE1/4 : 127
8' - 0
"
8
4
2
7 7 7 7 7 7 7 7 7 7 7 7 77SLOPE1/4:12TYP
3
9
9
9
7
DS
DS
5 5 5 5
DS
DS
DS
DS
DS
DS
DS
DS
2' - 1"TYP
2' - 0
"22
' - 0"
22' -
0"2'
- 0"
1' - 4"
1' - 4"
10
11
13' -
0"
10' - 2"
NOTE: MB ROOFPENETRATION DETAILSPROVIDED BY MB MFR.
12
12
12
METAL DOWNSPOUT
METAL SCUPPER
3"4"
8"
9"
6" 1"
4"6"
4"8"
4"
METALCOLLECTOR BOX
12
EDGE OF CONCRETEPILASTER
4" X 6" OVERFLOWSCUPPER
ROOF PLANEBEYOND
METAL COLLECTORBOX
1' - 6"7"10"
4" X 6" SCUPPER
16'-1" AFF
4"
PRECASTCONCRETEWALL PANEL
SEALANT
METAL SCUPPER
EPDM SHEET FLASHINGEPDM
PT WD BLOCKINGEPDM
METALCOLLECTOR BOX
4"
SEALANT
METAL SCUPPER
EPDMEPDM SHEETFLASHING
EPDM
EPDM SHEETFLASHING
SEALANT
DRIP EDGE
2"2"
TOP OF WALL
1/2" DIA POST-INSTALLED ANCHORS,TYP OF 4
1' - 0
"
2' - 6"
2 1/2" X 1/2"STEEL BAR
SIDE ELEVATION PLAN
ALL COMPONENTS MINIMUM 2" X 3/8" STEELBAR, UNLESS OTHERWISE INDICATED
BEVEL ENDS, TYP
6"8"
1' - 4
"
WALL
SIDE RAIL ANDDIAGONAL BRACE
SIDE RAIL ANDDIAGONAL BRACE
EPDM SHEET FLASHINGEPDM1 12/" EPDM ROOFINGINSULATION
MIN
6"
PT WD BLOCKING
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
34 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE105
ROOF PLAN ANDDETAILS
53
1/16" = 1'-0"ROOF PLAN
1/16" = 1' - 0"0 5' 10' 20' 30' 60'
1 MB ROOFING2 30"X36" ROOF HATCH3 EPDM ROOFING4 MECHANICAL EQUIPMENT RTU-15 LADDER SUPPORT, SEE DETAIL C4/AE1056 ALUMINUM LADDER, SEE DETAIL C3/AE2027 TAPERED INSULATION CRICKET8 MB ROOF WALKWAY9 EXHAUST VENT10 PLUMBING VTR11 PLUMBING ROOF HYDRANT12 STEEL BEAM
ROOF PLAN NOTES#
3/4" = 1'-0"D1CONDUCTOR HEAD DETAIL
NO SCALED2
COLLECTOR BOX ANDOVERFLOW SCUPPER ELEVATION
1 1/2" = 1'-0"D3SCUPPER DETAIL
1 1/2" = 1'-0"D5
OVERFLOWSCUPPER DETAIL
1 1/2" = 1'-0"C4LADDER SUPPORT
1 1/2" = 1'-0"C2ROOF DETAIL
1
No. Date Description1 12/30/2015 Revision 01
1
1 1 1 1
1
FINISH FLOOR0'-0"
EAVE HEIGHT14'-0"
A1AE301
A1AE301
TOP OF PRECAST23'-4"
1011121314151617
2
4
5
6
7
11
5
16
17
18
15
AE105D2
7
1820 19
118 18
97
13
4
12
TYP
TYP
TYP
TYP
21TYP
TYP23
TYP
22
C3AE201
TYP
10' - 0" 10' - 0"8' - 6"6' - 8"
TYP WALL PANEL W/PILASTER, UON
TYP WALL PANEL W/OPILASTER, UON
5' - 8" 5' - 8"
23
2"
AIR INTAKE LOUVER
DRYER VENT
1
1
FINISH FLOOR0'-0"
A2AE301
A2AE301
TOP OF PRECAST23'-4"
23456789
4
16
518
1
1
7
9
17 TYP
TYP
TYP
TYP
TYP
23
TYP
24 25
9' - 0"LADDER SUPPORT.CENTER BETWEENPILASTER ANDPANEL JOINT, TYP
FINISH FLOOR0'-0"
EAVE HEIGHT14'-0"
B1AE301
B1AE301
TOP OF PRECAST23'-4"
AF
14
6 3
520
2 55
915
15
12
D C BE
1
13
8
9
8
2121 2122
9
8
9
8
10' - 8" 10' - 8"
PRECAST CONCRETEWALL PANEL
SAW-CUT REGLET
EXTERIOR
1/2"
JOINT SEALANT ANDBACKER ROD
1/2"
MECHANICALDUCT
JOINT SEALANT ANDBACKER ROD2"x2"x1/4" SS ANGLE ATTACHEDTO ALL 4 SIDES OF DUCT. SET INFULL BED OF JOINT SEALANT
SHE E
T M-
3 01
SEE
MECH
ANIC
AL
SS FLASHING AND SEALANTRoanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
37 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE201
ELEVATIONS
54
1/8" = 1'-0"B1NORTH ELEVATION AREA B
1/8" = 1'-0"A1NORTH ELEVATION AREA A
1/8" = 1' - 0"0 5' 10' 15' 30'
1/8" = 1'-0"C1EAST ELEVATION
1 PRECAST CONCRETE WALL PANEL - PROVIDE CONTINUOUSBITUMINOUS DAMPROOFING BELOW GRADE
2 MB WALL PANEL3 METAL ROOF EDGING4 METAL CONDUCTOR HEAD AND DOWNSPOUT5 MECHANICAL EQUIPMENT6 ALUMINUM LADDER SEE DETAIL C3/AE2027 HOLLOW METAL DOOR AND FRAME8 MB DOWNSPOUT9 METAL DOWNSPOUT BOOT10 OVERHEAD COILING DOOR11 EXPANSION JOINT12 CONCRETE FOOTING13 MB GUTTER14 METAL BOLLARD15 CONCRETE EQUIPMENT PAD16 ROOF PLANE BEYOND17 OVERFLOW SCUPPER18 LIGHT FIXTURE. SEE EL501 FOR MTG HEIGHT UON. CENTER
FIXTURES OVER DOORS OR SYMMETRICALLY FRAME DOOROR CENTER IN WALL PANELS UON.
19 BULLET RESISTANT DOOR AND FRAME20 ROOF HATCH21 EXHAUST VENT22 MB ROOF WALKWAY23 PRECAST CONCRETE PILASTER24 DUST COLLECTION UNIT25 SCREW CONVEYOR SYSTEM
ELEVATION NOTES#
3" = 1'-0"C3DUCT PENETRATION AT PRECAST
No. Date Description1 12/30/2015 Revision 01
1
1
1
1
FINISH FLOOR0'-0"
C1AE301
C1AE301
TOP OF PRECAST23'-4"
A F
3
518
5
16
4
9
1
4
9 15 15
12
C3AE201
C3AE201
10' - 8" 10' - 8"
FINISH FLOOR0'-0"
A2AE301
A2AE301
TOP OF PRECAST23'-4"
2 3 4 5 6 7 8 9
51
3
16
9
4
1818
17
1
15
12
19
23
TYP
9' - 0"
FINISH FLOOR0'-0"
EAVE HEIGHT14'-0"
A1AE301
A1AE301
TOP OF PRECAST23'-4"
10 11 12 13 14 15 16 17
4
9
5
14
3
7
10
1
7
2
56
18
16
18
12
17
18 2019
18
9
8
13
20
18
4
18 18
TYP
TYP
TYP
TYP
11
21TYP
23
TYP
C3AE201
VERI
FY
17' -
0"
5' - 10"9' - 4" 10' - 0"5' - 8"2"5' - 8" 10' - 0"10' - 0"
TYP WALL PANEL W/PILASTER, UON
TYP WALL PANEL W/OPILASTER, UON
COORDINATE LIGHT FIXTURE CONDUIT WITH COILING DOOR HOOD
TOP OF PRECAST23'-4"
ALUMINUM LADDERWITH GRATINGPLATFORM
BRACKETS @ 60" OC MAX W/(2) 1/2" DIA POST INSTALLEDANCHORS PER BRACKET, TYP
MB ROOFWALKWAY
3' - 6
"1'
- 0"
1' - 0
"
7"
7"
TYP
1' - 0
"1'
- 0"
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
40 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE202
ELEVATIONS
55
1/8" = 1'-0"C1WEST ELEVATION
1/8" = 1'-0"B1SOUTH ELEVATION AREA A
1/8" = 1'-0"A1SOUTH ELEVATION AREA B
1/8" = 1' - 0"0 5' 10' 15' 30'
1 PRECAST CONCRETE WALL PANEL - PROVIDE CONTINUOUSBITUMINOUS DAMPROOFING BELOW GRADE
2 MB WALL PANEL3 METAL ROOF EDGING4 METAL CONDUCTOR HEAD AND DOWNSPOUT5 MECHANICAL EQUIPMENT6 ALUMINUM LADDER SEE DETAIL C3/AE2027 HOLLOW METAL DOOR AND FRAME8 MB DOWNSPOUT9 METAL DOWNSPOUT BOOT10 OVERHEAD COILING DOOR11 EXPANSION JOINT12 CONCRETE FOOTING13 MB GUTTER14 METAL BOLLARD15 CONCRETE EQUIPMENT PAD16 ROOF PLANE BEYOND17 OVERFLOW SCUPPER18 LIGHT FIXTURE. SEE EL501 FOR MTG HEIGHT UON. CENTER
FIXTURES OVER DOORS OR SYMMETRICALLY FRAME DOOROR CENTER IN WALL PANELS UON.
19 BULLET RESISTANT DOOR AND FRAME20 ROOF HATCH21 EXHAUST VENT22 MB ROOF WALKWAY23 PRECAST CONCRETE PILASTER24 DUST COLLECTION UNIT25 SCREW CONVEYOR SYSTEM
ELEVATION NOTES#
1/2" = 1'-0"C4LADDER DETAIL
No. Date Description1 12/30/2015 Revision 01
1
1
FINISH FLOOR0'-0"
B1AE301
B1AE301
TOP OF PRECAST23'-4"
RANGESTORAGE
106
AGENCYOFFICE
104WEAPON
CLEANING108
ARMORY110
LAUNDRY112
AF
AE302A1
D C BE
FINISH FLOOR0'-0"
C1AE301
C1AE301
TOP OF PRECAST23'-4"
14-LANERANGE
114
AF
FINISH FLOOR0'-0"
EAVE HEIGHT14'-0"
AE302A3
A1AE301
A1AE301
TOP OF PRECAST23'-4"
AE302A4
WEAPONCLEANING
108
CORRIDOR102
14-LANERANGE
114
13' -
0"
9' - 0
"
10 11 12 13 14 15 16 17
ACOUSTICALPANELCEILING
18 2019
AE104D2
AE503C3
EXPANSIONJOINT
ARS CEILING BAFFLESWITH SOUND ABSORPTIONPANELS, TYP
EPDM ROOFING
CONCRETE SLABON GRADE
METAL BUILDING
75 100
SOUND ABSORPTIONPANELS TO 13'-0" AFFA3
AE503
4"X18" YELLOW PAINTEDFIRING LINES W/ 8" NUMBERS,BOTH SIDES OF RANGE, TYP
CHANNEL DRAIN,SEE DETAIL 7/SB301
ARS CEILINGBAFFLES WITHSOUND ABSORPTIONPANELS
FINISH FLOOR0'-0"
A2AE301
A2AE301
TOP OF PRECAST23'-4"
2 3 4 5 6 7 8 9
14 LANERANGE
11413' -
0" ARS CEILING BAFFLESWITH SOUND ABSORPTIONPANELS, TYP
EPDM ROOFINGAE503
C4
AE503B4
AE501A3
1
CONCRETE SLAB ON GRADE
2515731.5 50
SOUND ABSORPTIONPANELS TO 13'-0" AFF
TYP
TYP4"X18" YELLOW PAINTEDFIRING LINES W/ 8" NUMBERS,BOTH SIDES OF RANGE, TYP
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
44 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE301
BUILDINGSECTIONS
561/8" = 1' - 0"0 5' 10' 15' 30'
1/8" = 1'-0"A1TRANSVERSE SECTION ADMIN AREA
1/8" = 1'-0"A2TRANSVERSE SECTION
1/8" = 1'-0"B1LONGITUDINAL SECTION AREA B
1/8" = 1'-0"C1LONGITUDINAL SECTION AREA A
No. Date Description1 12/30/2015 Revision 01
1
T-1148"x48" FRPSPLASH GUARDON ALL WALLSADJ. TO SINK
MOP SINK
INSULATE ALLPIPING BENEATHLAVATORY TOP OF
SEAT
T-136" REAR
GRAB BAR
TYPICAL WATER COOLER
TYPICAL ACCESSIBLELAVATORY
TYPICALACCESSIBLE
URINAL
TYPICALACCESSIBLE
WATERCLOSET
WHEELCHAIRACCESSIBLE SPOUT
STANDINGHEIGHT SPOUT
SIDEFRONT
KNEE/TOECLEARANCEREQUIRED
FRONT SIDE
TYPICAL MOP SINK
T-242" SIDE GRAB
BAR
T-318" VERTICAL
GRAB BAR
T-4SANITARY
NAPKINDISPOSAL
T-5 T-6SOAP
DISPENSER
T-7DOUBLE TOILET
TISSUE
36"
34"
CL12" 24"
12" 42"
34"
40"
18"
40" 44"
CL
8" 28"
36" M
AX.
43"M
AX.
38" M
IN.
5" MAX. 15"MIN.
34"
KNEE/TOECLEARANCEREQUIRED 44
" MAX
.
15"
CL18"
19"M
AX.
17"M
IN.
TOWELDISPENSER
T-8ROBEHOOK
T-918" TOWEL
BAR
T-10SHOWER
CURTAIN, ROD,AND HOOKS
T-11MOP/BROOM
HOLDER
T-12FRAMEDMIRROR
60"
TYP.
48"
VARIES
76"
60"
40" M
AX. T
O
REFL
ECTI
VESU
RFAC
E
T-13SEAT COVERDISPENSER
MAX.
4' - 0
"
MAX
4' - 0
"8"
22"
AE502 C2
AE502
D2
2' - 0"
15' - 4" 5' - 4" 6' - 8"
15' - 4" 6' - 8"
3' - 6
"4'
- 0"
4' - 0
"
B2
B1AE301
B1AE301
A
F
1' - 4"1' - 4"
DIRECTOR'SOFFICE
103
COPYROOM
105
OFFICESTORAGE
105ADATA107
RANGESTORAGE
106
AGENCYOFFICE
104
VESTIBULE101
WEAPONCLEANING
108
ELECTRICAL115
WOMEN111
MEN109
ARMORY110
LAUNDRY112
CORRIDOR102
108
103104
112
110
108A
115
106
105
105A
114
111
109
GUNLOCKERS
T-11
T-6T-5
T-6T-5
D
W
EWC
2' - 4
"2'
- 10"
2' - 1
0"2'
- 4"
UNITHEATER
5'-0" X 4'-0"ENTRANCEFLOOR GRILLE
AE503A1
FEC
FEC
FD
S4R1
S4R1
S4
S4N
S4R1N
S4N
S4
S4R1
S4
S6R1
S4
12' - 2" 5' - 6" 3' - 3" 12' - 7"
6' - 2"
11' - 6"
AE401A2
AE503B1 UTILITY
SINK
D
C
18
B
E
S4
20
S4N
S4R1
11' -
6"21
' - 8"
16' -
1"11
' - 5"
11' -
5"7'
- 6"
8' - 7
"10
' - 5"
12' -
5"12
' - 4"
5' - 8
3/4" 5' - 0
"4'
- 10"
4' - 9" 10' - 4"19
D3AE104
WEAPONSCLEARINGSTATION
STAINLESS STEELCOUNTER, FIELDJOINT IN CENTEROF COUNTER RUN
6' - 8
"
19' -
2"
AE503A1 OH
107
113
S4R1
S4R1
S4R1N
S4
SE3
S4R1
S4R1
S4R1
S4R1
S4R1
S4
SE3
SE3
10' -
4"3'
- 4"
29' -
8"6'
- 4"
21' -
8"
1' - 6
"
S4
1' - 8" 3' - 0"
S6R1
SE3
WALL MOUNTEDUTILITY SHELVINGFOR RANGECONTROLCOMPUTER:PROVIDE FOUR12"x30"X3/4" HPDLFACED SHELVES,TWO ADJUSTABLEBRACKETS PERSHELF, AND TWO 72"SHELF STANDARDSMOUNTED @ 24"AFF.
EQ EQ
EQEQ
FD
FD
S4R1
S
S4R1S
S4R1
S
ACTIVE LEAF
ACTIVE LEAF
SE4
SE4
SE4
4' - 0"
A1AE501106A
S4
102
101
101A
CORNERGUARD,TYP
CONCRETE EQUIPMENT PAD
AE502A4
REF(NIC)
(NIC)
(NIC)
MIRROR
.
13' -
0"
T-9
T-6
T-5
T-8
T-2
T-3T-7
T-1
T-10
T-7T-3
T-1
T-2
T-4T-13
T-10
2' - 3
1/2"
T-6
T-12
T-12
T-5
T-13
T-9
MEN109
WOMEN111
3' - 3
1/2"
2' - 3
1/2"
5' - 8" 4' - 0"
3' - 1
"3'
- 1"
S4
S4
S4
S4N
109
111
C
5' - 8" 4' - 0"
20
2' - 1" 1' - 8" 1' - 8"
S4N
S4N
SE4
PLASTIC TOILETCOMPARTMENT
PLASTIC TOILETCOMPARTMENT
PLASTIC URINALSCREEN
3' - 3"
3' - 3"
5'-0" MIN CLEAR
5'-0" MIN CLEAR
S4NS4
S4R1
S4R1N
S4R1
SE4
S4
S4
3' - 3"
SLOPE FLOOR 1/4:12 TODRAIN - MOSAIC TILE CT-2
SLOPE FLOOR 1/4:12 TODRAIN - MOSAIC TILE CT-2
FD
FD
T-8
3/4" CHAMFER ON COUNTERTOP CORNER
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
47 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE401
ENLARGEDPLANS
58
1/4" = 1'-0"ACCESSORY MOUNTING HEIGHTS
1/4" = 1' - 0"0 5' 10' 15'1'
1/4" = 1'-0"A4ENLARGED PLAN
MARK DESCRIPTION MODEL NUMBER
T-1 36" STAINLESS STEEL GRAB BAR B-5806 X 36T-2 42" STAINLESS STEEL GRAB BAR B-5806 X 42T-3 18" STAINLESS STEEL GRAB BAR B-5806 X 18T-4 SANITARY NAPKIN DISPOSAL B-270T-5 RECESSED PAPER TOWEL DISPENSER AND WASTE
RECEPTACLEB-369 ClassicSeries
T-6 SOAP DISPENSER B-2111T-7 DOUBLE TOILET TISSUE DISPENSER B-273T-8 ROBE HOOK B-672T-9 18" STAINLESS STEEL TOWEL BAR B-398T-10 EXTRA HEAVY-DUTY SHOWER CURTAIN ROD, CURTAIN,
AND HOOKSB-6047, B-204-2, B-204-1
T-11 MOP/BROOM HOLDER B-223T-12 24"W x 42"H MIRROR WITH STAINLESS STEEL CHANNEL
FRAMEB-290
T-13 TOILET SEAT COVER DISPENSER B-221
1/2" = 1' - 0"0 1' 5'6" 2' 3' 4'
1/2" = 1'-0"A2ENLARGED FLOOR PLAN - RESTROOMS
TOILET ACCESSORY SCHEDULE
MODEL NUMBERS ARE FOR BASIS OF DESIGN BOBRICK ACCESSORIES
No. Date Description1 12/30/2015 Revision 01
1
TOE OF BULLET TRAP
CONTINUOUS TRENCHIN CONCRETE SLAB
1' - 0"
22'-0"
TO REAR WALL
3 1/2"
1" M
IN
PRECAST CONCRETE WALL PANEL
PAINTED 14 GAUGE METALFRAME ALL AROUND
1'-4" SQUARE OPENINGIN PRECAST. COORDINATEHEIGHT W / CONVEYOR MFR.
SCREW CONVEYOR SYSTEM
AIRTIGHT REMOVABLERUBBER SEAL
SUPPORT STRUT
SEALANT
SEALANT
3/8" ARSBENT PLATETARGET HOLDER
1/2" DIA STEEL T-BAR
12" DIA ARS TARGET
1"
6"
FIEL
D VE
RIFY
WIT
H US
ER
5'-0"
C L
3"1 1/2"
1"
2 3
CABLE HANGERSYSTEM, TYP
180 DEGREE TURNINGTARGET SYSTEM
RUNNING-MAN TARGET SYSTEM
REACTIVE TARGETSYSTEM, D3/AE501
ARS LOW-SLOPEBULLET TRAP
SCREWCONVEYORSYSTEM
1
AE501D2
22' - 0" 4' - 0" TARG
ET LI
NE
731.5
8'-0" ARS CEILING BAFFLE AT 45 DEGREESWITH SOUND ABSORPTION PANEL
8'-0" ARS CEILING BAFFLE AT 30 DEGREES(OMIT SOUND ABSORPTION PANEL)
6' - 8
"
ARS CEILING BAFFLE WITH SOUNDABSORPTION PANEL
AE503C4
SIM
7' - 0"8"
AE103C2
8' - 0
"
PRECAST CONCRETEWALL PANEL
BULLET-RESISTANTDOOR AND FRAME
ALUMINUM THRESHOLD -SET IN FULL BED OFSEALANT
CONCRETE SIDEWALK
TURNED DOWNCONCRETE SLABON GRADE
JOINT SEALANT ANDJOINT SEALANT BACKING
1/2" PJF
STEEL DOWEL,SEE SB501
BULLET-RESISTANTDOOR AND FRAME
BULLET-RESISTANTDOOR AND FRAME
3/8" ARS DEFLECTOR FROMFLOOR TO CEILING BEVEL
LEADINGEDGE OFPLATE 45DEGREES
FIRE ALARMPULL STATION
EXTERIOR INTERIOR
HEAD
SILL
JAMB ANCHOR
ALIG
N
5" 6"
4"
3"
DIRECTION OFBULLET TRAP
DIRECTION OFFIRING LINE
JAMB
45°
FINISH FLOOR0'-0"
TYP
1' - 0
"
MAX
1' - 0
"
S4R1
7"
ROOF HATCH
MB ROOF ASSEMBLY
STEEL LADDER2 1/2" X 2 1/2" X 1/4" STEEL ANGLES TYP
ATTACH TO TOP OF RATED CLGAT 12" OC
3" M
IN
S4R1S4
SCHEDULED CEILING
CORRIDOR102
RANGESTORAGE
106
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
49 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE501
BALLISTICDETAILS
59
1 1/2" = 1' - 0"0 6" 1' 2'3" 9"
1 1/2" = 1'-0"D2TOE OF BULLET TRAP
1 1/2" = 1'-0"C3AUGER PENETRATION DETAIL
1 1/2" = 1'-0"D3REACTIVE TARGET DETAIL
3" = 1' - 0"0 3" 6" 1'
1/4" = 1' - 0"0 5' 10' 15'1'
1/4" = 1'-0"A3BULLET TRAP SECTION
1 1/2" = 1'-0"C5BULLET RESISTANT DOOR DETAILS
3/4" = 1'-0"A1LADDER DETAIL
No. Date Description1 12/30/2015 Revision 01
1
B2AE503
SE3
SE3
RECESSEDHVAC/LIGHTINGCONTROL PANEL
PRECAST CONCRETEWALL PANEL3 HR FIRE BARRIER
4' - 0
"
1/2"
SEE
A2/E
L502
3' - 0
"
8" CMU WALL3 HR FIRE BARRIERUL DESIGN NO. U-904
SE3
SE3
SOLID MORTAR JOINTBETWEEN CMU ANDPRECAST WALLS WITHMASONRY TIES @ 16" OCVERTICALLY
S4
SOLID MORTAR JOINTBETWEEN CMU ANDPRECAST WALLS WITHMASONRY TIES @ 16" OCVERTICALLY
1/2"
3" GLASS FIBER BOARDINSULATION - MAINTAINCONTINUITY OFINSULATION & VAPORBARRIER
4' - 0
"
CLSE
3SE
3
CEILING ASSCHEDULED
CONDUIT
PENETRATIONFIRESTOPPINGUL DETAIL W-J-1042
4' - 0
"
SEE
A2/E
L502
1' - 8
"
7' - 4
"
RECESSEDHVAC/LIGHTINGCONTROL PANEL
PRECAST CONCRETEWALL PANEL3 HR FIRE BARRIER
SE3
8" CMU WALL3 HR FIRE BARRIERUL DESIGN NO. U-904
ACCESS DOOR
3" GLASS FIBER BOARDINSULATION
SOLID MORTAR JOINTBETWEEN CMU ANDPRECAST WALLS
10 11
PREFORMED JOINTSEAL BEYOND
EPDM
PT WD BLOCKING, TYP
EPDM SHEET FLASHING
CONT STEEL PLATE, BOTH SIDESOF JOINT, SEE SHEET SF301
1 1/2" EPDM ROOFING INSULATION
3/4" PT PLYWOOD
PT WOOD BLOCKINGCONT STEEL ANGLE, SEE 1/SF301
METAL DRIP EDGEEPDM TERMINATIONBAR BEYOND
EPDM
B3AE503
BELLOWS TYPE ROOFEXPANSION JOINT
2"
2"
STEEL BEAMEPDM SHEET FLASHING
6"
PRECAST CONCRETE WALLPANELS
3/8" ARS PLATE FROM FLOOR TOCEILING- BEVEL LEADING EDGE OFPLATE 45 DEGREES
POST INSTALLED ANCHORS @24" OC
PREFORMED JOINT SEALBOTH SIDES
6"1" SOUND ABSORPTION PANELS
2"
PRECAST CONCRETE WALLPANELS
PREFORMED JOINT SEAL2"
PT WD BLOCKING, TYP
EPDM SHEETEPDM SHEET FLASHINGBELLOWS TYPE ROOFEXPANSION JOINT
EXTERIOR SIDE
PRECAST CONCRETE WALLPANELS
3/8" ARS PLATE FROM FLOOR TOCEILING. BEVEL LEADING EDGE OFPLATE 45 DEGREES.
POST INSTALLED ANCHORS @24" OC
JOINT SEALANT AND JOINTSEALANT BACKING, BOTH SIDES
4"1" SOUND ABSORPTION PANELS
1/2"
NOTE: PROVIDE COVER PLATE AT EACH PRECAST WALL PANEL JOINTBETWEEN 100 YARD FIRING LINE AND BULLET TRAP, BOTH SIDES OF RANGE.
BOS13'-8"
3/4" PTPLYWOOD
EPDMSCUPPER
EPDM
PT WD 2X6AT 16" OC
METAL DRIP EDGE
STEEL TRUSS
EPDM ROOFINGINSULATION
EPDM SHEETFLASHING
2X PTBLOCKING OVERFLOW SCUPPER
2' - 4
"
TERMINATIONBAR BEYOND
EPDM
3/4" PT PLYWOOD
2X PT WOOD BLOCKING
PT WOOD BLOCKINGCONT STEEL ANGLE, SEE 1/SF301
METAL DRIP EDGE
1-1/2" EPDM ROOFING INSULATION
EPDM TERMINATIONBAR BEYOND
EPDM
A
18
B
PRECAST CONCRETEWALL PANEL
MB WALL PANEL
MB STRUCTURE LINE19
SE4
2" 3"
METAL FLASHINGSEALANT
SE3
6"
3" GLASS FIBERBOARD INSULATION
SEAL MB VAPORBARRIER TOGLASS FIBERBOARDINSULATION
BELLOWS-TYPE ROOFEXPANSION JOINT
EPDM SHEETFLASHING
EPDM SHEET
CONT MTL CLEATMTL ROOF EDGING
PT WD BLOCKING
PREFORMED JOINTSEAL- EXTEND UP 2"MIN BEHIND BELLOWS
SEAL OPEN END OFBELLOWSTERMINATION WITHFOAM FILLER
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
52 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE503
DETAILS
613" = 1' - 0"
0 3" 6" 1'1 1/2" = 1' - 0"
0 6" 1' 2'3" 9"
1 1/2" = 1'-0"B1PLAN DETAIL
1" = 1'-0"B2SECTION DETAIL
1 1/2" = 1'-0"C3ROOF EXPANSION JOINT
3" = 1'-0"A3EXPANSION JOINT
3" = 1'-0"B3PARAPET EXPANSION JOINT
3" = 1'-0"A4COVER PLATE DETAIL
1 1/2" = 1'-0"B4BOTTOM CHORD DETAIL
1 1/2" = 1'-0"C4TOP CHORD DETAIL
1 1/2" = 1'-0"A1PLAN DETAIL
1" = 1'-0"A2EXPANSION JOINT DETAIL
1
No. Date Description1 12/30/2015 Revision 01
1
1
F
SEE
SCHE
DULE
SEE SCHEDULE
FGSE
E SC
HEDU
LE
SEE SCHEDULE
SEE
SCHE
DULE
SEE SCHEDULE
OHCD
6" 6"
6"10
"
HG
SEE
SCHE
DULE
SEE SCHEDULE6" 6"
6"2'
- 6"
GL1
GL2
SEE
SCHE
DULE
2"
2"SEE SCHEDULE
2"
F1 F2 F3
5' - 8"
2"6'
- 10"
2"
2" 1' - 0"2"
3' - 0"2"
1' - 0" 2"
7' - 2
"
GL1 GL1
4' - 8"
2"6'
- 10"
2"
2" 3' - 0"2"
1' - 2" 2"
7' - 2
"
FIXED HM PANEL
7' - 0
"
STEEL CHANNEL -SEE JAMB DETAIL
HSS DOOR POST -SEE JAMB DETAIL
HM DOOR FRAME
F4
2"
10' - 0" 8"2"
3' - 0"2"
13' -
0"PRECAST CONCRETEWALL PANELSHIM AND SEALANT
3/8" STEEL PLATEWELDED
HEAD-DETAIL
HEAD-ISOMETRIC
BASE-ISOMETRIC
4"
HOLES FOR 1/2"BOLTS. FASTEN TOPOST-INSTALLEDTHREADED INSERTSIN CONCRETE.3/8" STEEL PLATEWELDED
4"
HSS 8X8X3/16
3/8" STEEL PLATEWELDED
SHIM 1/2" & GROUT(2) 1/2" POST-INSTALLED ANCHORS
OVERHEAD COILINGDOOR AND TRACK
HEAVY DUTY CONCRETE,SEE SHEET CI102
S7STEEL DOWEL,SEE SB501
JOINT SEALANT ANDJOINT SEALANT BACKING
1/2" PJF
PRECAST CONCRETEWALL PANEL
EMBEDDED STEEL CHANNELSEE SHEET SF501
FRAME ANCHOR W/COUNTERSUNK BOLT -DRILL & TAP STEELCHANNEL TO RECEIVEBOLT, TYP
HOLLOW METAL DOORAND FRAME
OVERHEAD COILINGDOOR AND TRACK
8"10
' - 0"
3' - 4
"
HSS 8X8X3/16 DOOR POST -SEE DOOR POST DETAILFOR HEAD ANDSILL ATTACHMENT
CL
COILING DOORASSEMBLY
ACOUSTICAL PANELCEILING EXTRUDEDALUMINUM TRIM
ACOUSTICAL PANELCEILING
8"
PRECAST CONCRETEWALL PANEL
1' - 0
"
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
g R
ange
A14
_pw
ard.
rvt
12/3
0/20
15 5
:01:
53 P
M
UN
ION
CO
UN
TY S
HER
IFF'
S O
FFIC
EFI
RIN
G R
ANG
EM
ILLS
HAR
RIS
RO
AD, M
ARSH
VILL
E, N
C
540411/17/2015JCSPAWDEW
AE601
SCHEDULES
62
DOOR SCHEDULEDOOR
NO.DOOR FRAME
FIRE RATING HARDWARE REMARKSTTL WIDTH HEIGHT THICKNESS TYPE MATERIAL TYPE MATERIAL HEAD JAMB SILL
101 3'-0" 7'-0" 1 3/4" F HM F3 HM H1 J1 S1 - 1101A 3'-0" 7'-0" 1 3/4" FG HM F2 HM H2 J3 - - 2102 3'-0" 7'-0" 1 3/4" F HM F3 HM H1 J1 S1 - 1103 3'-0" 7'-0" 1 3/4" HG WD F1 HM H2 J2 - 20 MIN 3 2104 3'-0" 7'-0" 1 3/4" HG WD F1 HM H2 J2 - 20 MIN 3 2105 3'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 - 20 MIN 3 2105A 3'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 - - 5106 6'-0" 7'-0" 1 3/4" F HM F1 HM H4 J5 S6 180 MIN 9106A 2'-8" 7'-0" 1 3/4" F HM F1 HM H2 J2 - - 5107 3'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 S4 20 MIN 3 2108 3'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 S2 20 MIN 3 2108A 3'-0" 7'-0" 1 3/4" F HM F1 HM H4 J5 S6 180 MIN 4109 3'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 S3 20 MIN 6 2110 3'-0" 7'-0" 1 3/4" F HM F1 HM H4 J5 S6 180 MIN 4111 3'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 S3 20 MIN 6 2112 3'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 S4 20 MIN 3 2113 6'-0" 7'-0" 1 3/4" F WD F1 HM H2 J2 S4 20 MIN. 7 2114 3'-0" 7'-0" 1 3/4" F HM F4 HM H3 J7 S5 - 10114A 10'-0" 13'-0" 1" OHCD STL F4 - H6 J7 S7 - - 1114B 3'-0" 7'-0" 1 3/4" F HM F1 HM H3 J4 S5 - 10114C 3'-0" 7'-0" 1 3/4" F HM F1 HM C5/AE501 C5/AE501 C5/AE501 - 11 3114D 3'-0" 7'-0" 1 3/4" F HM F1 HM H3 J4 S5 - 10115 3'-0" 7'-0" 1 3/4" F HM F1 HM H5 J6 S1 - 8
1/4" = 1'-0"DOOR TYPES
1/4" = 1'-0"DOOR FRAME TYPES
FINISH SCHEDULEROOM FLOOR BASE WALLS CEILING
REMARKSNO. NAME MATERIAL CODE MATERIAL CODE MATERIAL CODE MATERIAL CODE
101 VESTIBULE RESILIENT TILE VCT-1 RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1102 CORRIDOR RESILIENT TILE VCT-1 RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1103 DIRECTOR'S OFFICE RESILIENT TILE VCT-1 RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1104 AGENCY OFFICE RESILIENT TILE VCT-1 RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1105 COPY ROOM RESILIENT TILE VCT-1 RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1
105A OFFICE STORAGE RESILIENT TILE VCT-1 RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1106 RANGE STORAGE SEALED CONCRETE - RESILIENT RB-1 PAINT PT-2 EXPOSED STRUCTURE -107 DATA SEALED CONCRETE - RESILIENT RB-1 PAINT PT-2 EXPOSED STRUCTURE -108 WEAPON CLEANING RESINOUS FLOORING R-1 RESINOUS R-1 PAINT PT-2 GWB PT-1109 MEN CERAMIC TILE CT-1,CT-2 CERAMIC TILE CT-1 PAINT PT-2 GWB PT-1110 ARMORY RESILIENT TILE VCT-1 RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1111 WOMEN CERAMIC TILE CT-1,CT-2 CERAMIC TILE CT-1 PAINT PT-2 GWB PT-1112 LAUNDRY SEALED CONCRETE - RESILIENT RB-1 PAINT PT-2 ACOUSTIC CEILING PANELS ACP-1113 PLUMBING SEALED CONCRETE - RESILIENT RB-1 PAINT PT-2 EXPOSED STRUCTURE -114 14-LANE RANGE SEALED CONCRETE - - - SOUND ABSORPTION
PANELSSA-1 SOUND ABSORPTION PANELS,
ACOUSTIC CEILING PANELSSA-1,ACP-2
115 ELECTRICAL SEALED CONCRETE - RESILIENT RB-1 PAINT PT-2 EXPOSED STRUCTURE -
1/4" = 1' - 0"0 5' 10' 15'1'
FINISH LEGENDCODE MATERIAL DESCRIPTION / BASIS OF DESIGN PRODUCT
ACP-1 ACOUSTICAL CEILING PANEL ARMSTRONG; FINE FISSURED; COLOR: WHITE; SIZE: 24"X24"ACP-2 ACOUSTICAL CEILING PANEL ARMSTRONG; FINE FISSURED; COLOR: WHITE; SIZE: 24"X48"; HUMIDITY RESISTANTCT-1 CERAMIC QUARRY TILE AMERICAN OLEAN; QUARRY NATURALS; COLOR: PRAIRIE FLASH; SIZE 6"X6"X1/2"CT-2 CERAMIC MOSAIC TILE AMERICAN OLEAN; UNGLAZED COLORBODY PORCELAIN MOSAICS; COLOR: COCOA; SIZE 2”X2”X1/4"PT-1 PAINT SHERWIN WILLIAMS; COLOR: #SW6147 "PANDA WHITE"PT-2 PAINT SHERWIN WILLIAMS; COLOR: #SW6141 "SOFTER TAN"PT-3 PAINT SHERWIN WILLIAMS; COLOR: #SW2841 "WEATHERED SHINGLE"PL-1 PLASTIC LAMINATE PANOLAM; NEVAMAR HPL; COLOR:#VS2001 "VOUS FAWN"R-1 RESINOUS FLOORING STONHARD; STONSHIELD HRI; COLOR: ACORN; MEDIUM TEXTURE
RB-1 RESILIENT BASE JOHNSONITE; TRADITIONAL WALL BASE; COLOR: 76 CINNAMONSA-1 SOUND ABSORPTION PANELS AS SPECIFIEDTC-1 HDPE PLASTIC ACCURATE PARTITIONS SOLID PLASTIC (HDPE) TOILET COMPARTMENTS; COLOR: #9212 "MOCHA"
VCT-1 RESILIENT TILE ARMSTRONG; IMPERIAL TEXTURE STANDARD EXCELON; COLOR: #51839 "FORTRESS WHITE"; SIZE: 12"X12"X1/8"
1. PLASTIC LAMINATE FACED COUNTER SUPPORTS AND WALL MOUNTED SHELVES TO BE PL-1.2. LOCATE FLOOR TRANSITIONS BETWEEN ROOMS UNDER DOOR LEAF.3. PAINT METAL DOORS AND FRAMES PT-3.
1" = 1'-0"A2DOOR POST DETAIL
1" = 1' - 0"0 6" 1' 3'2'
1 1/2" = 1'-0"COILING DOOR DETAILS
J7
H6
REMARKS:1. PROVIDE ADDITIONAL DOOR CURTAIN HEIGHT TO ALLOW HOOD MOUNTING ABOVE CEILING.2. SMOKE AND DRAFT CONTROL DOOR ASSEMBLY3. BULLET RESISTANT DOOR AND FRAME.
No. Date Description1 12/30/2015 Revision 01
1
F
FF
14-LANERANGE
114
MA
TC
HLI
NE
FP
102
F
A
987654321
110
WP
WP
WP
(TYP.) LINEAR HEAT DETECTION CABLERUN WITHIN 20" OF ROOF PEAK
(TYP.) LINEAR HEAT DETECTION CABLERUN ABOVE CEILING BAFFLES
LINEAR HEAT DETECTION CABLERUN ABOVE CEILING BAFFLESWITHIN 20" OF ROOF DECK
FACP FIRE ALARM CONTROL PANEL
SMOKE DETECTOR, CEILING MOUNTED
STROBE UNIT WITH CANDELA RATING - WALLMOUNTED
HORN/STROBE UNIT WITH CANDELA RATING - WALLMOUNTED
MANUAL PULL STATION, MOUNT 4'-0" AFF
15F
15V
S
F
FIRE PROTECTION LEGEND
HORN/STROBE UNIT WITH CANDELA RATING - CEILINGMOUNTED
15
CF
STROBE UNIT WITH CANDELA RATING - CEILINGMOUNTED
C
15V
DUCT SMOKE DETECTORDAHU-1
WP WEATHERPROOF
HEAT DETECTOR, CEILING MOUNTEDH
FIRE ALARM MONITOR MODULEMM
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800
Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
\\corp
\dfs
\Offic
es\R
oa\2
014\5
404-U
nio
n C
ounty
Firearm
s R
ange\R
evit-U
nio
n C
o. F
irin
g R
ange\F
\5404-U
nio
n C
o F
irin
g R
ange F
14.r
vt
12/3
0/2
015 9
:26:4
9 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
KEF
EVA
RBA
FP101
FLOOR PLANAREA A
651/8" = 1' - 0"0 5' 10' 15' 30'
KEY PLAN 1/8" = 1'-0"FLOOR PLAN AREA A
A B
No. Date Description
1 12/30/15 Revision 01
1
1
1
FF
V
S
F
F
V
F F
FA
CP
F
F
F
F
FF
H
H
SS
S
SS
S
S
S
S
S
S
S
H
H
S
S
S
SF
F
F
H
ARMORY
110
LAUNDRY
112
ELECTRICAL
115
WOMEN
111
MEN
109
CORRIDOR
102
WEAPONCLEANING
108
RANGESTORAGE
106
OFFICESTORAGE
105A DATA
107
COPYROOM
105
DIRECTOR'SOFFICE
103
VESTIBULE
101
AGENCYOFFICE
104
14-LANERANGE
114
MA
TC
HLI
NE
FP
101
12
34
56
78
910
1112
1314
C
C
C 15
15
15
F
E
D
C
B
A
2019.519181716151413121110
15
15
15
15
C
110
30
C
DRTU-1
15C
15C
30C
110
WP
WP
WP
WP
WP
WP WP
LINEAR HEAT DETECTION CABLERUN ABOVE CEILING
(TYP.) LINEAR HEAT DETECTION CABLERUN WITHIN 20" OF ROOF PEAK
(TYP.) LINEAR HEAT DETECTION CABLERUN ABOVE CEILING BAFFLES
MM
FACP
NOTES
1. THE FIRE ALARM EQUIPMENT SUPPLIER IS RESPONSIBLE FOR PROVIDING ADDITIONAL INDICATING CIRCUITS AS REQUIRED TOPROPERLY OPERATE ALL AUDIO/VISUAL DEVICES.
2. ALL WIRING SHALL BE AS RECOMMENDED BY EQUIPMENT MANUFACTURER. ALL WIRING SHALL BE RUN IN CONDUIT.
3. FIRE ALARM RISER DIAGRAM IS SHOWN FOR REFERENCE ONLY. DEVICE LOCATIONS AND QUANTITIES SHALL BE AS SHOWN ON THEFLOOR PLANS. THE FIRE ALARM RISER DIAGRAM DOES NOT NECESSARILY INDICATE THE ACTUAL NUMBER OF ALARM NOTIFICATIONAPPLIANCE CIRCUITS. THE ACTUAL NUMBER OF APPLIANCE CIRCUITS NECESSARY IS DEPENDENT UPON THE EQUIPMENTMANUFACTURER.
4. PROVIDE A REMOTE LED TEST/INDICATOR LIGHT AND KEY SWITCH FOR EACH DUCT DETECTOR AND LABEL WHICH AHU IS SERVED.
5. PROVIDE SYNCHRONIZATION FOR AREAS WHERE MORE THAN ONE VISIBLE APPLIANCE IS LOCATED.
EP
F S F F F
FIRST FLOOR FIRST FLOOR
FFF FFF
6. MANUAL PULL STATIONS SHALL BE FLUSH-MOUNTED IN FINISHED AREAS AND SURFACE MOUNTED IN UNFINISHED AREAS.
FIRE ALARM RISER DIAGRAMNO SCALE
FV
F
1.
2.
DEVICE LOCATIONS SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURERSRECOMMENDATIONS AND EQUIPMENT LISTINGS. COORDINATE LOCATIONS WITH LIGHTING AND AIRHANDLING SYSTEMS. SMOKE DETECTORS SHALL BE LOCATED NO CLOSER THAN 3 FEET FROM ANYCEILING FAN BLADE TIPS OR SUPPLY AIR DIFFUSERS, AND NOT IN THE DIRECT AIR STREAM
3.
RISER DIAGRAM IS SHOWN FOR REFERENCE ONLY. DEVICE LOCATIONS AND QUANTITIES SHALL BE ASSHOWN ON THE FLOOR PLANS.
EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS, NORTH CAROLINABUILDING CODE, AND NFPA 72.
GENERAL NOTES
DACTTWO DEDICATED PHONELINES TO RECEIVING STATION
D SH
LINEAR HEATDETECTION
CABLE
MM
FIRE ALARM SYSTEM SEQUENCEOF OPERATION MATRIX
ACTION
INITIATION MANUALPULL
STATION
FACP MODULETROUBLE
ACTIVATE FIRE ALARM HORN & STROBE LIGHTS YES
DISPLAY ALARM INDICATOR AT FACP YES
NO
NO
TRANSMIT ALARM SIGNAL TO FIREDEPARTMENT
YES NO
RECORD INFORMATION ON FACP YES YES
DISPLAY SUPERVISORY CONDITION AT FACP NO NO
TRANSMIT SUPERVISORY SIGNAL TO FIREDEPARTMENT
NO NO
TRANSMIT TROUBLE SIGNAL TO FIREDEPARTMENT
NO YES
DISPLAY TROUBLE SIGNAL AT FACP NO YES
SMOKE ORHEAT
DETECTOR
YES
YES
YES
YES
NO
NO
NO
NO
LINEAR HEATDETECTION
CABLE
DUCTSMOKE
DETECTOR
SHUTDOWN ASSOCIATED HVAC UNIT NO NO NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
NO
NO
YES
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800
Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:
DATE:
DESIGN:
DRAWN:
REVIEW:
REVISIONS
SHEET OF 94
\\corp
\dfs
\Offic
es\R
oa\2
014\5
404-U
nio
n C
ounty
Firearm
s R
ange\R
evit-U
nio
n C
o. F
irin
g R
ange\F
\5404-U
nio
n C
o F
irin
g R
ange F
14.r
vt
12/3
0/2
015 9
:26:5
1 A
M
UN
ION
CO
UN
TY
SH
ER
IFF
'S O
FF
ICE
FIR
ING
RA
NG
EM
ILLS
HA
RR
IS R
OA
D, M
AR
SH
VIL
LE
, N
C
5404
11/17/2015
KEF
EVA
RBA
FP102
FLOOR PLANAREA B
66
1/8" = 1'-0"FLOOR PLAN AREA B
1/8" = 1' - 0"0 5' 10' 15' 30'
A B
KEY PLAN
1
1
1
1
No. Date Description
1 12/30/15 Revision 01
# CONSTRUCTION NOTE IDENTIFICATION
INDICATES ITEM TO BE PROVIDED
FLEXIBLE CONNECTOR
VERTICAL FIRE DAMPERVOLUME DAMPER
CEILING RETURN, EXHAUST OR TRANSFER GRILLE
CEILING SUPPLY DIFFUSER
MITERED ELBOW WITH TURNING VANES
RETURN DUCT TURNING UPRETURN DUCT TURNING DOWN
EXHAUST DUCT TURNING UPEXHAUST DUCT TURNING DOWN
SUPPLY DUCT TURNING UP (ROUND OR RECTANGULAR)
SUPPLY DUCT TURNING DOWN (ROUND OR RECTANGULAR)
10"x10" SQUARE OR RECTANGULAR DUCTWORK
THERMOSTAT
F10/6(CFM)
EXHAUST GRILLE DESIGNATIONWITH CFM INDICATED
A6(CFM)
CEILING DIFFUSER DESIGNATIONWITH CFM INDICATED
G20/20 RETURN GRILLE DESIGNATION
GENERAL
DUCTWORK
MOTORIZED CONTROL DAMPER
INDICATES ROUND DUCTWORKRETURN, EXHAUST OR TRANSFER AIR FLOWSUPPLY AIR FLOW
ACCESS DOORAD
ABOVE FINISHED FLOORAFF
ABOVE FINISHED GRADEAFG
DIAMETERDIA
MISCELLANEOUSMISC
TYPICALTYP
UNLESS OTHERWISE NOTEDUON
CONTROLSANALOG INPUT (TO PANEL)ANALOG OUTPUT (OUT OF PANEL)
BINARY INPUT (TO PANEL)BINARY OUTPUT (OUT OF PANEL)
CONTROL WIRING (SIGNAL PATH)
DIFFERENTIAL PRESSURE SENSOR
AI
BIBO
FLOW MEASURING SYSTEM
HIGH LIMIT TEMPERATURE SENSOR
LOW LIMIT TEMPERATURE SENSOR
MOTOR
MOTORIZED CONTROL DAMPER
MOTOR STARTER
SENSOR
STATIC PRESSURE SENSOR
SWITCH
TEMPERATURE SENSOR
CSR CURRENT SENSING RELAY
FLEXIBLE DUCT
LEGEND
M
M
M
AO
S
P
T
DPS
FMS
HL
LL
MS
S
T
VARIABLE FREQUENCY DRIVEVFD
CURRENT TRANSMITTER
ACOUSTICALLY LINED DUCT
ES
SDDAMPER END SWITCHDUCT SMOKE DETECTOR
CT
EXHAUST AIR
OUTSIDE AIRRETURN AIRSUPPLY AIR
DA
OARASA
EADISCHARGE AIR
RADIUS ELBOW
RD-1(CFM)
RADIAL DIFFUSER DESIGNATIONWITH CFM INDICATED
1.
2.
4.
5.
6.
11.
10.
9.
8.
7.
3.
12.
13.
14.
15.
GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACHMECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TOINDIVIDUAL MECHANICAL DRAWINGS WILL BE SHOWN ON THERESPECTIVE MECHANICAL DRAWING.
THE CONTRACTOR SHALL PROVIDE A COMPLETE HVAC SYSTEMTO INCLUDE ALL LABOR, MATERIALS, TOOLS, AND EQUIPMENTFOR A COMPLETE AND FUNCTIONAL SYSTEM INCLUDING ALLNECESSARY APPURTENANCES CUSTOMARILY INCLUDED IF NOTSPECIFICALLY CALLED OUT.
THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE ANDAPPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OFAPPLICABLE REGULATORY AGENCIES.
THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS,LICENSES, DOCUMENTS, AND SERVICES RELATED TOINSTALLATION OF THE WORK.
EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS MAY BEFURNISHED PROVIDED SUCH PROPOSED EQUIPMENT ISAPPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICE,CIRCUIT BREAKERS AND CONDUIT SIZES ARE APPROPRIATELYMODIFIED AT NO COST TO THE OWNER.
THE CONTRACTOR SHALL COORDINATE HIS WORK WITH THEOTHER TRADES IN ORDER TO RESOLVE ANY CONFLICT THATMIGHT ARISE DUE TO THE LOCATION OF EQUIPMENT OR THE USEOF SPACE.
RUN ALL HORIZONTAL DUCTWORK ABOVE CEILING UNLESSOTHERWISE NOTED.
ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESSOTHERWISE NOTED. WHERE SQUARE ELBOWS ARE SHOWN,INSTALL TURNING VANES.
MAKE DUCT PENETRATIONS OF ALL WALLS WITH SHEET METALDUCTS. FLEXIBLE DUCT PENETRATIONS OF WALLS ARE NOTACCEPTABLE.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOREXACT LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES.
DO NOT INSTALL EQUIPMENT OR DUCTWORK OVER ANYELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.
EXTEND DRAIN LINES TO NEAREST ROOF DRAIN OR ASINDICATED. ALL CONDENSATE DRAIN PIPING SHALL BE TRAPPEDAND PITCHED DOWN IN DIRECTION OF FLOW A MINIMUM OF 1"PER 10 FEET.
LAYOUT OF DUCTWORK IS DIAGRAMMATIC. RUN ALL EXPOSEDPIPING AND DUCTWORK AS HIGH AS POSSIBLE UNLESSOTHERWISE NOTED. ALLOW FOR RISES, DROPS AND OFFSETS ASREQUIRED.
DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS.
INSTALL MECHANICAL EQUIPMENT TO FACILITATE SERVICING,MAINTENANCE, AND REPAIR OR REPLACEMENT OF EQUIPMENTCOMPONENTS. AS MUCH AS PRACTICAL, CONNECT EQUIPMENT FOREASE OF DISCONNECTING, WITH A MINIMUM OF INTERFERENCE WITHOTHER INSTALLATIONS
16.
17.
18.
19.
MECHANICAL CONTRACTOR SHALL PROVIDE AUTOMATIC CONTROLDEVICES, SUCH AS TEMPERATURE SENSORS, RELAYS, PRESSURESWITCHES WHICH ARE ASSOCIATED WITH MECHANICAL EQUIPMENTAND ASSOCIATED CONTROL WIRING FROM STARTER TO THE CONTROLDEVICE. ELECTRICAL CONTRACTOR SHALL PROVIDE CONDUIT ANDWIRING FROM POWER SOURCE TO DISCONNECT SWITCH, FROMDISCONNECT SWITCH TO STARTER, AND FROM STARTER TO THEEQUIPMENT.
ALL CONTROL WIRING EXCEPT IN EQUIPMENT ROOMS SHALL BE RUNCONCEALED. WIRING IN WALLS SHALL BE IN CONDUIT. ALL WIRINGSHALL BE PLENUM RATED. CONTROL WIRING IN EXPOSED AREAS SHALLBE BUNDLED AND SECURED OR RUN IN CONDUIT. NO WIRING SHALL BESURFACE MOUNTED IN FINISHED SPACES. ALL ELECTRICAL WORKSHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE.
LOCATE THERMOSTATS AND TEMPERATURE SENSORS 54" ABOVEFINISHED FLOOR OR AS NOTED ON THE PLANS.
GENERAL NOTES
REFER TO ELECTRICAL DRAWINGS FOR VOLTAGE AND PHASEREQUIREMENTS FOR ALL EQUIPMENT REQUIRING AN ELECTRICALCONNECTION.
SPACE TYPE WINTER INDOORDB (°F) %RH
WINTER OUTDOORDB (°F) WB (°F)
SUMMER INDOOR SUMMER OUTDOORDB (°F) %RH DB (°F) WB (°F)
DESIGN CONDITIONS
ADMIN SPACES 70 - 72 50 94 7519 -
MOTORVOLTAGE/PHASE
120/1
MOTOR STARTER SCHEDULE
MAXHP
NEMA STARTERSIZE
208/3208/3
1/31-1/2
3
0 00 00
208/3 7-1/2 1460/3 2 0 0460/3 5 0460/3 10 1460/3 25 2460/3 50 3460/3 100 4
SYSTEM
SUPPLY AIR DUCTWORK:
DUCT CONSTRUCTION AND LEAKAGE SCHEDULETYPE OF
PRESSURE
RANGE VENTILATION SUPPLY
SEALCLASSIFICATION(PER SMACNA)
LEAKAGE CLASS(CFM/100 SQ FT AT
1 IN. WG)
TYPE OFDUCTWORK
RTU SUPPLY TO VAV TERMINALS
VAV TERMINALS TO SUPPLY OUTLETS
SMACNAPRESSURECLASS (IN
WG)
POSITIVE RECTANGULARROUND
63+3 A
RETURN AIR DUCTWORK:
RANGE VENTILATION RETURN NEGATIVE RECTANGULAR
RECTANGULAR
6
6-5 A
EXHAUST AND OUTSIDE AIR DUCTWORK:
DUCTWORK UNDER POSITIVE CONDITIONS
DUCTWORK UNDER NEGATIVE CONDITIONS
TRANSFER AND RELIEF DUCTWORK:
DUCTWORK UNDER POSITIVE CONDITIONS
DUCTWORK UNDER NEGATIVE CONDITIONS
POSITIVE RECTANGULAR 6A
POSITIVE RECTANGULAR 6+2 A
POSITIVE RECTANGULARROUND
63+2 A
POSITIVE RECTANGULARROUND
63+2 A
+2
-2NEGATIVE
NEGATIVE -2 A
RECTANGULAR
RECTANGULAR
6
6
RTU RETURN NEGATIVE -1 A
A
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
gR
ange
M14
_mja
rrett.
rvt
12/3
1/20
158:
46:2
6A
M
UN
ION
CO
UN
TYSH
ERIF
F'S
OFF
ICE
FIR
ING
RAN
GE
MIL
LSH
ARR
ISR
OAD
,MA
RSH
VILL
E,N
C
540411/17/2015JLDDRLEES
M-001
ABBREVIATIONSLEGEND AND
GENERAL NOTES
75
No. Date Description1 12/30/15 Revision 01
1
1
1
B3M-301
A1M-301
36"x12"OPENING INBOTTOM OFDUCT (TYP)
36"x12" OPENING INBOTTOM OF DUCT (TYP)
60"x44"
F-2
EF-2
60"x44"
14-LANERANGE
114
7
7
22"x22"
28"x28"
36"x32"
36"x44"
36"x44"
36"x32"
28"x28"
22"x22"
22"x22"
28"x28"
36"x32"
36"x44"
36"x44"
36"x32"
28"x28"
22"x22"
F-1
EF-1
FMS
FMS
P
P
1 2 3
F
A
A3M-301
LAUNDRY112
ELECTRICAL115
ARMORY110
WOMEN111
MEN109
WEAPONCLEANING
108
RANGESTORAGE
106
CORRIDOR102
COPYROOM
105DIRECTOR'S
OFFICE103
AGENCYOFFICE
104
14-LANERANGE
114
VESTIBULE101
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
20"ø
RD-13415(TYP)
RD-13415 (TYP)
T
T
T
T
T
T
T T
T
A8170
C8195
C8195
J8/8160
J8/6120
C6115
A10240
A10215
A8150G24/24
VAV-3
VAV-8
A10260
20"x16"
24"x14"
14"x12"12"x10"
12"x10"
VAV-2
VAV-5
VAV-6
VAV-7
VAV-4
52"x5
2"
SF-2
SF-1
UH-1
1
3
4
5
T
7
7
8
22"x22"
26"x26"
32"x30"
52"x52"
52"x52"
52"x5
2"
52"x52"
32"x30"
26"x26"
22"x22"22"x22"
26"x26"
32"x30"
52"x52"
52"x52"
32"x30"
26"x26"
22"x22"
52"x52"
B1M-301
FMS
FMS
P
P
G10/10G10/10
A8205
A6100
14"x12"
14"x12"
A6100
C8130
J8/6115
J8/6110
2
VAV-B
G10/10
G24/24
G10/10
J10/10
G10/10
10"ø
16 17 18 19 20
B
C
D
E
9
10"x8"
10"x8"12"x10"
10
11
14"x12"
12
10"ø
8"ø
DATA107
VAV-1
M
13
OA
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
gR
ange
M14
_mja
rrett.
rvt
12/3
1/20
158:
46:3
1A
M
UN
ION
CO
UN
TYSH
ERIF
F'S
OFF
ICE
FIR
ING
RAN
GE
MIL
LSH
ARR
ISR
OAD
,MA
RSH
VILL
E,N
C
540411/17/2015JLDAuthorEES
M-101
FLOOR PLANS -AREAS A AND B
No. Date Description1 12/30/15 Revision 01
CONSTRUCTION NOTES# KEY PLAN
GRAPHIC SCALE:
1 10X10 UP TO EF-3 ON ROOF.2 10X10 UP TO EF-4 ON ROOF.3 24X14 RA UP TO RTU-1 ON ROOF.4 32X16 SA UP TO RTU-1 ON ROOF.5 UP TO EF-5 ON ROOF.7 CONCRETE EQUIPMENT PAD; SEE DETAIL, SHEET CI102.8 FIRE RATED RETURN AIR PLENUM.9 4"Ø FLEXIBLE METALLIC DRYER EXHAUST DUCT (MAX
LENGTH = 8'-0") WITH WALL MOUNTED OUTLET.10 RTU-1 CONTROL PANEL.11 RANGE VENTILATION CONTROL PANEL RECESSED IN WALL.12 BMS PANEL.13 12X12 INTAKE LOUVER; SEE SHEET AE201 FOR LOCATION.
GENERAL NOTES1. OR GRILLE CONSTRUCTION NOTES ARE APPLICABLE
FOR SHEETS M-101 AND M-301.2. SEE SHEET GI101 FOR FIRE RATED PARTITIONS; SEE
SHEET GI004 FOR FOR FIRE RATED PARTITIONPENETRATION DETAILS.
3. SEE ROOF PLAN, AE105, FOR LOCATION OF ROOF-MOUNTED EQUIPMENT.
4. BRANCH DUCTS TO VAV TERMINALS SHALL BE SAMESIZE AS TERMNAL INLET.
5. RUNOUT DUCTS TO DIFFUSERS AND GRILLES SHALL BESAME SIZE AS DIFFUSER OR GRILLE NECK.
1/8" = 1'-0"FLOOR PLAN - AREA A
1/8" = 1'-0"FLOOR PLAN - AREA B
1/8" = 1' - 0"0 5' 10' 15' 30'
A B
1
1
1
RETURN AIRSUPPLY AIR
BRANCH DUCT
6"
MAIN DUCTMANUAL VOLUMEDAMPER
45°EXHAUST AIR
CLEANOUT
DRAIN LINE SHALL BE AT LEAST THE SAME SIZEAS THE CONNECTION ON THE EQUIPMENT
PITCH DOWNTOWARD DRAIN
DEPTH OF SEAL SHALL BE AMINIMUM = 0.5 X (FAN STATIC + 1")
CLEANOUT
EQUIPMENTCASING
MINIMUM = (1" XFAN STATIC +1")
(SECTION UNDER NEGATIVE PRESSURE)
DIMENSIONS INDICATEDIN PLAN VIEW AREINSIDE CLEAR
GRILLE
ACOUSTICALDUCT LINER
FIRE RATEDPARTITION
CEILING
ELEVATION VIEW
1 1/2 HOUR FIREDAMPER(DYNAMIC RATED)
8"MI
NIMU
MHE
IGHT
G24/24CEILING
ACOUSTICALLYLINED PLENUM
6" - 12"
24 PLENUM"
30"
FRONT VIEW SIDE VIEWRIGHT
30"
TOP VIEW
SEE DIFFUSERSCHEDULE
15"
1.375"4"
DOUBLE-WALLPERFORATED FACE
0.375"ØMOUNTING HOLE(TYP OF 5)
35"
4"
4" 4"
20"Ø30"20"36" MIN
30"
2"
1.375"21"
DOUBLE-WALL PERFORATED FRONT SECTION SHALL BE 0.050INCH ALUMINUM 3003-H14 AND SHALL WEIGH (PRIOR TOBEING PERFORATED) 0.713 POUNDS PER SQUARE FOOT. 0.050INCH ALUMINUM 3003-H14 PERFORATED FRONT SECTIONSHALL BE NON-COMBUSTIBLE, MOISTURE RESISTANT ANDDIMENSIONALLY STABLE. ALL PERFORATIONS SHALL BEROUND.
GENERAL CONSTRUCTION SHALL BE 22 GAUGE MINIMUMGALVANIZED SHEET METAL AND SHALL WEIGH 1.656 POUNDSPERSQUARE FOOT. GALVANIZED SHEET METAL SHALL BENON-COMBUSTIBLE, MOISTURE RESISTANT ANDDIMENSIONALLY STABLE.
DOUBLE WALL PERFORATED FRONT SECTION SHALL BEREMOVABLE TO GAIN ACCESS TO THE INTERIOR OF LAMINARAIRFLOW RADIAL DIFFUSER FOR ADJUSTMENT, INSPECTIONAND REQUIRED MAINTENANCE.
RADIAL DIFFUSER SPECIFICATIONS1.
2.
3.
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
gR
ange
M14
_mja
rrett.
rvt
12/3
1/20
158:
46:3
2A
M
UN
ION
CO
UN
TYSH
ERIF
F'S
OFF
ICE
FIR
ING
RAN
GE
MIL
LSH
ARR
ISR
OAD
,MA
RSH
VILL
E,N
C
540411/17/2015JLDDRLEES
M-501
DETAILS
78NO SCALE
TYPICAL BRANCH DUCTCONNECTION DETAIL
NO SCALECONDENSATION TRAP DETAIL
NO SCALETRANSFER DUCT DETAIL
NO SCALERETURN GRILLE PLENUM DETAIL
NO SCALELAMINAR AIRFLOW RADIAL DIFFUSER (RD-1) DETAIL
No. Date Description1 12/30/15 Revision 01
1
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
gR
ange
M14
_mja
rrett.
rvt
12/3
1/20
158:
46:3
3A
M
UN
ION
CO
UN
TYSH
ERIF
F'S
OFF
ICE
FIR
ING
RAN
GE
MIL
LSH
ARR
ISR
OAD
,MA
RSH
VILL
E,N
C
540411/17/2015JLDDRLEES
M-601
SCHEDULES
79
FAN SCHEDULE
MARK LOCATION TYPE SERVES CFMESP (IN
WG) BHP SONES DRIVEMOTOR
HP NOTESEF-1 GRADE CENTRIFUGAL
AIRFOILFIRING RANGE 37565 5.80 54.87 95 dBA BELT,
VFD60 1
EF-2 GRADE CENTRIFUGALAIRFOIL
FIRING RANGE 37565 5.80 54.87 95 dBA BELT,VFD
60 1
EF-3 ROOF CENTRIFUGAL,DOWN BLAST
MENS ROOM RM 109,WOMENS ROOM 111
280 0.30 0.03 4.6 DIRECT 1/6 3
EF-4 ROOF CENTRIFUGAL,DOWN BLAST
WEAPONS CLEANING RM108
225 0.25 0.02 3.6 DIRECT 1/6 3
EF-5 ROOF CENTRIFUGAL,DOWN BLAST
ELECTRICAL RM 115 150 0.20 0.02 3.7 DIRECT 1/60 4
SF-1 GRADE CENTRIFUGALAIRFOIL
FIRING RANGE 34150 2.25 26.29 87 dBA BELT,VFD
30 2
SF-2 GRADE CENTRIFUGALAIRFOIL
FIRING RANGE 34150 2.25 26.29 87 dBA BELT,VFD
30 2
FILTER SCHEDULE
Mark LOCATIONAIR
SYSTEM CFM
2" PLEATED PRE-FILTER HEPA
EFF.
APD (IN. WC)HEPA
EFFICIENCY
FACEAREA
(SQ FT)
HEPAFACE VEL
(FPM)
APD (IN. WC)
INITIAL FINAL INITIAL FINALF-1 GRADE EF-1 37565 MERV 13 0.25 1.0 99.97 80.0 500 1.5 3.0F-2 GRADE EF-2 37565 MERV 13 0.25 1.0 99.97 80.0 500 1.5 3.0
1. BASIS OF DESIGN: TRANE PRECEDENT MODEL WSC0722. ESP DOES NOT INCLUDE PRESSURE DROP OF FILTERS OR COILS WITHIN RTU3. REFRIGERANT: R-410A4. PROVIDE WITH MERV-8 DISPOSABLE FILTERS5. 0 - 100% ECONOMIZER WITH BAROMETRIC RELIEF
NOTES:
NOTE:1. BASIS OF DESIGN: TRANE MODEL UHAA.
NOTES:1. BASIS OF DESIGN: GREENHECK MODEL 40-AFSW-41. CW ROTATION, UPBLAST DISCHARGE.2. BASIS OF DESIGN: GREENHECK MODEL 40-AFSW-21, CW ROTATION, UPBLAST DISCHARGE.3. BASIS OF DESIGN: GREENHECK MODEL G-080-D.4. BASIS OF DESIGN: GREENHECK MODEL G-070-D.5. BASIS OF DESIGN: GREENHECK MODEL G-060-D.
NOTES:1. GALVANIZED STEEL, SIDE LOCK FILTER HOUSING WITH PRE-FILTER RACK AND 6 INCH BASE.
NOTES:1. BASIS OF DESIGN: PRICE MODEL SCD2. BASIS OF DESIGN: PRICE MODEL 80 TBP (PANEL MOUNTED)3. BASIS OF DESIGN: PRICE MODEL 80 BORDER STYLE TB4. BASIS OF DESIGN: PRICE MODEL 80, BORDER STYLE F, 1 1/4" FRAME5. BASIS OF DESIGN: RANGE VENTILATION DESIGN, INC., MODEL RD-3000.
ELECTRIC UNIT HEATER SCHEDULE
MARK LOCATION TYPE kWFANCFM
MTG HT(FT AFF)
UH-1 VESTIBULE RM 101 WALLMOUNTED
1.5 175 1'-0 "
PACKAGED ROOFTOP HEAT PUMP SCHEDULE
MARK LOCATION
SUPPLY FAN CAPACITY COOLING CAPACITY HEATING CAPACITY
MIN.COP
HEATINGCAPACITY FILTER PD (IN. WC)
SUPPLYAIR CFM
OACFM
ESP (INWG) BHP
TOTALCOOLING
(MBH)
SENSIBLECOOLING
(MBH)
ENTERING AIR(°F)
MINEER
REVERSE CYCLE HEATPUMP ELECTRIC
INITIAL FINALDB WBHEATING
(MBH) ENT AIRTEMP (°F) (KW)
RTU-1 ROOF 2075 775 0.8 0.77 76.5 58.2 81.5 66.6 11.4 38.8 60 3.3 18.0 0.25 1.0
BYPASS VARIABLE AIR VOLUME BOX SCHEDULE
MARK
MINIMUMINLET DIA
(IN.)
AIR FLOW(CFM)
NOTESMAX. MINVAV-1 6 240 145 1,2,4VAV-2 6 215 120 1,2,4VAV-3 6 150 50 1,2,4VAV-4 8 390 180 1,2,4VAV-5 6 170 105 1,2,4VAV-6 6 260 100 1,2,4VAV-7 6 245 135 1,2,4VAV-8 8 405 155 1,2,4VAV-B 14 X 12 1085 0 1,3,4
NOTES:1. BASIS OF DESIGN: TRANE VARITRAC.2. SINGLE-DUCT, COOLING ONLY TERMINAL.3. RECTANGULAR BYPASS TERMINAL.4. VAV TERMINALS ARE COMPONENTS OF A FACTORY
BY-PASS CONTROL SYSTEM FROM A SINGLEMANUFACTURER. PROVIDE ALL TERMINALS,SENSORS, CONTROLLERS, WIRING,TRANSFORMERS AND OTHER COMPONENTSNECESSARY FOR AN INTEGRATED BY-PASS VAVSYSTEMS. COORDIANATE WITH RTU AND DDCSYSTEM MANUFACTURER(S).
DIFFUSERS, REGISTERS AND GRILLES SCHEDULE
MARK ServiceCFM
RANGEMAX SP(IN WG)
NECK/COLLARSIZE (IN)
SHELLSIZE (IN) MOUNTING/TYPE
MAX THROW AT50 FPM (FT)
MAXNC NOTES
A6 SUPPLY AIR 0-120 0.04 6 24 X 24 LAY-IN LOUVER FACE 8 10 1A8 SUPPLY AIR 125-205 0.06 8 24 X 24 LAY-IN LOUVER FACE 12 16 1
A10 SUPPLY AIR 210-325 0.10 10 24 X 24 LAY-IN LOUVER FACE 15 22 1C6 SUPPLY AIR 0-120 0.04 6 24 X 24 SURFACE MOUNT LOUVER FACE 5 20 1C8 SUPPLY AIR 99-209 0.06 8 24 X 24 SURFACE MOUNT LOUVER FACE 12 16 1
G10/10 RETURN AIR 0-300 0.05 10 X 10 24 X 24 LAY-IN 1/2"X12"X12" EGGCRATE - 14 2G24/24 RETURN AIR 0-2000 -0.05 24 X 24 24 X 24 LAY-IN 1/2"X12"X12" EGGCRATE - 20 3
J8/6 EXHAUST AIR 95-145 0.07 8 X 6 24 X 24 SURFACE MOUNT 1/2"X1/2"X1/2"EGGCRATE
- 14 4
J8/8 EXHAUST AIR 150-230 0.07 8 X 8 24 X 24 SURFACE MOUNT 1/2"X1/2"X1/2"EGGCRATE
- 17 4
J10/10 RETURN AIR 0-300 0.05 10 X 10 24 X 24 SURFACE MOUNT 1/2"X1/2"X1/2"EGGCRATE
- 20 4
RD-1 SUPPLY AIR 3415 1.25 20 42 - - - 5
No. Date Description1 12/30/15 Revision 01
1
DDC CONTROL POINTS
POINT NAME AI AO BI BO TREND ALARMSHOWN
ONGRAPHIC
EXHAUST AIR DUCT LOW LIMIT STATIC PRESSUREEXHAUST AIR FLOW RATEEXHAUST AIR PRE-FILTER DIFFERENTIAL PRESSURE
EXHAUST FAN - START / STOPEXHAUST FAN STATUSEXHAUST FAN VFD SPEEDEXHAUST FAN VFD SPEED SETPOINT
X
X
XX
EXHAUST FAN VFD FAULT
EXHAUST AIR HEPA FILTER DIFFERENTIAL PRESSURE
X
XXXX
SUPPLY FAN - START / STOPSUPPLY FAN STATUSSUPPLY FAN VFD SPEEDSUPPLY FAN VFD SPEED SETPOINTSUPPLY FAN VFD FAULTSUPPLY AIR FLOW RATESUPPLY AIR DUCT HIGH LIMIT STATIC PRESSURERANGE CONTROL PANEL STATUSRANGE DOOR STATUS
MAINTENANCE DOOR STATUSRANGE STATUS
XXX
XX
X
X
X
X
X
XX
X
XX
X
XX
XX
X
XX
XX
XX
XX
XXXXX
XX
XX
RANGE VENTILATION SYSTEM
OVERVIEW:
THE RANGE VENTILATION SYSTEM SHALL BE CONTROLLED LOCALLY THROUGH THE RANGE CONTROLPANEL. THE RANGE CONTROL PANEL SHALL BE LOCATED IN A RECESSED ENCLOSURE AT THE BACK WALLOF THE RANGE (BEHIND THE FIRING LINE). THE SYSTEM SHALL OPERATE IN THREE MODES: "SAFE TOSHOOT", "RANGE SECURED" OR "UNOCCUPIED". THE SYSTEM CONSISTS OF TWO SUPPLY FANS (SF-1 & SF-2) AND TWO EXHAUST FANS (EF-1 & EF-2). ALL FANS SHALL OPERATE SIMULTANEOUSLY AS A SINGLESYSTEM.
RANGE VENTILATION CONTROL PANEL (RVCP):THE RANGE CONTROL PANEL SHALL ALLOW THE RANGE OPERATOR TO START OR STOP THE SYSTEMTHROUGH AN ON/OFF SWITCH. WHEN INDEXED TO “OFF”, THE SYSTEM SHALL BE UNDER FULL BASCONTROL. WHEN INDEXED TO “ON”, THE SYSTEM SHALL BE STARTED IN PREPARATION FOR LIVE FIRETRAINING. THE PANEL SHALL HAVE AN INTERACTIVE DISPLAY MODULE THAT REPORTS EQUIPMENT ANDSYSTEM STATUS, INCLUDING DOOR STATUSES, AS WELL AS ANY SYSTEM WARNINGS AND ALARMSREPORTED BY THE BAS. THE PANEL SHALL HAVE THE FOLLOWING LIGHTS WITH INDICATOR LABELS:
1. GREEN - “SAFE-TO-SHOOT”, ILLUMINATES ONLY AFTER THE VENTILATION SYSTEM IS BROUGHT TOOPERATIONAL LEVEL AND NO WARNINGS OR ALARMS ARE INDICATED.
2. RED - “RANGE SECURED”, ILLUMINATES ANY TIME THE SYSTEM IS NOT AT THE OPERATIONALLEVEL.3. YELLOW - “WARNING”, ILLUMINATES WHENEVER THE BAS REPORTS ANY MONITORED PARAMETERIS OUT OF RANGE.4. RED - “ALARM”, ILLUMINATES WHENEVER THE BAS REPORTS ANY EQUIPMENT FAILURE OR OTHER
ALARM CONDITION. THE PANEL SHALL HAVE AN AUDIBLE ALARM THAT ACTIVATES WHENEVER ANALARM CONDITION IS INDICATED AT THE PANEL.
SEE ELECTRICAL DRAWING, SHEET EL502, FOR RANGE VENTILATION PANEL DETAIL AND ADDITIONALINFORMATION.
INDICATOR LIGHTS ON THE RVCP SHALL ALSO BE USED TO INDICATE THE STATUS OF THE OVERHEADDOORS AND THE PERSONNEL DOORS THAT ENTER ONTO THE RANGE AND THE BULLET TRAPMAINTENANCE AREA DOORS. THE RVCP ALSO INTERACTS WITH FIRING RANGE INTERIOR AND EXTERIORWARNING LIGHTS. SPECIFICALLY, THE RVCP SHALL PERFORM THE FOLLOWING FUNCTIONS:1. PRIOR TO ACHIEVING “SAFE-TO-SHOOT” STATUS, ANY OPEN DOOR CONDITION SHALL PREVENT THE
RVCP FROM ACHIEVING “SAFE-TO-SHOOT” STATUS AND SHALL ILLUMINATE THE YELLOW WARNINGLIGHT ON THE RVCP. THE LIGHT SWITCH IN THE BULLET TRAP MAINTENANCE AREA IN THE “ON”POSITION INDICATING THAT SOMEONE MAY BE IN THE MAINTENANCE AREA ALSO PREVENTS THERVCP
FROM ACHIEVING “SAFE-TO-SHOOT” STATUS AND ILLUMINATES THE YELLOW WARNING LIGHTON THE RVCP.2. IN “SAFE-TO-SHOOT” MODE, IF THE BULLET TRAP MAINTENANCE AREA DOOR STATUS SWITCH
INDICATES A DOOR OPEN CONDITION, THE GREEN “SAFE-TO-SHOOT” LIGHT ON THE RVCP ISEXTINGUISHED, THE RED ALARM LIGHT ON THE RVCP ILLUMINATES, AND THE AMBER WARNING LIGHTON THE RANGE ILLUMINATES. THE VENTILATION SYSTEM OPERATIONAL STATUS REMAINSUNCHANGED.
3. IN “SAFE-TO-SHOOT” MODE, IF THE BULLET TRAP MAINTENANCE AREA LIGHT SWITCH IS IN THE “ON”POSITION, THE GREEN “SAFE-TO-SHOOT” LIGHT ON THE RVCP IS EXTINGUISHED, THE RED ALARM LIGHTON THE RVCP ILLUMINATES AND THE AMBER WARNING LIGHT ON THE RANGE ILLUMINATES. THEVENTILATION SYSTEM OPERATIONAL STATUS REMAINS UNCHANGED.
4. IN “SAFE-TO-SHOOT” MODE, IF ANY OF THE DOOR STATUS SWITCHES FOR DOORS THAT OPEN ONTOTHE RANGE INDICATES A DOOR OPEN CONDITION FOR LONGER THAN 2 MINUTES (ADJ.), THE GREEN“SAFE-TO-SHOOT” LIGHT ON THE RVCP IS EXTINGUISHED, THE RED ALARM LIGHT ON THE RVCPILLUMINATES AND THE AMBER WARNING LIGHT ON THE RANGE ILLUMINATES. THE VENTILATIONSYSTEM OPERATIONAL STATUS REMAINS UNCHANGED.
5. DOOR STATUS SWITCH AND MAINTENANCE AREA LIGHT SWITCH ALARM CONDITIONS SHALL CLEARAUTOMATICALLY. WHEN ALL ALARM CONDITIONS HAVE CLEARED, ALL WARNING LIGHTS ON THE RANGEARE EXTINGUISHED, THE RED ALARM LIGHT ON THE RVCP IS EXTINGUISHED AND THE GREEN“SAFE-TO-SHOOT” LIGHT IS ILLUMINATED.
6. UPON ACHIEVING “SAFE-TO-SHOOT” STATUS, THE RVCP SHALL ACTIVATE THE RED EXTERIOR WARNINGLIGHTS ON THE EXTERIOR OF THE FACILITY TO INDICATE THAT THE RANGE IS IN USE.
ENABLEMENT:1. PRIOR TO COMMENCING LIVE FIRE TRAINING ACTIVITIES, THE RANGE OPERATOR SHALL ENABLE
THE SYSTEM FROM THE RANGE CONTROL PANEL THROUGH THE SYSTEM ON/OFF SWITCH,UNLESS:A. THE SYSTEM IS MANUALLY SHUT DOWN, ORB. THE SYSTEM IS DIRECTED BY THE BAS TO SHUT DOWN
2. LOSS OF SIGNAL - IF AT ANYTIME THE BAS NETWORK LOSES CONTACT WITH THERANGE CONTROL PANEL:A. THE SYSTEM SHALL SHUT DOWN, ANDB. AN EQUIPMENT FAILURE ALARM CONDITION IS INDICATED AT THE RANGE CONTROL PANEL
RANGE SYSTEM ON/OFF SWITCH:1. ON - WHEN THE SYSTEM SWITCH IS INDEXED TO “ON”:
A. THE SUPPLY FANS AND EXHAUST FANS START AND RAMP UP TO THEIR OPERATING SPEEDSTHROUGH THEIR VARIABLE FREQUENCY DRIVES (VFD)
B. WHEN THE FANS ARE AT THEIR DESIGN AIR FLOW AS INDICATED BY THEIR RESPECTIVE AIRFLOW MEASURING STATIONS AND NO ALARM OR TROUBLE CONDITIONS ARE ACTIVATED, ASIGNAL SHALL BE SENT TO THE RANGE CONTROL PANEL TO DE-ENERGIZE THE RED “RANGESECURED” LIGHT AND ENERGIZE THE GREEN “READY TO SHOOT” LIGHT ON THE PANEL
C. IF ANY FAN OPERATION IS NOT VERIFIED BY A CURRENT SENSING RELAY ON ITS MOTORLEADS WITHIN 60 SECONDS OF ITS START SIGNAL OR AT ANY OTHER TIME WHEN IT ISSUPPOSED TO BE OPERATING, AN EQUIPMENT FAILURE ALARM IS ISSUED FOR THE FAN ANDTHE SYSTEM IS COMMANDED TO STOP.
D. IF ANY FAN HAS NOT REACH ITS DESIGN AIR FLOW WITHIN 5 MINUTES OF ITS START SIGNALOR AT ANY OTHER TIME WHEN IT IS SUPPOSED TO BE RUNNING AT DESIGN CAPACITY, ANEQUIPMENT FAILURE ALARM IS ISSUED FOR THE FAN AND THE SYSTEM IS COMMANDED TOSTOP.
E. FAILURE OF ANY OF THESE CONTROL POINTS TO BE SATISFIED SHALL ENERGIZE THE RED"RANGE SECURED" LIGHT ON THE RANGE CONTROL PANEL, ALARM AT THE BAS AND THERANGE CONTROL PANEL, SOUND AN ALARM HORN AFTER A 5-MINUTE (ADJUSTABLE) DELAYAND DE-ENERGIZE THE GREEN LIGHT.
2. OFF - WHEN THE SYSTEM SWITCH IS INDEXED TO “OFF”:A. THE GREEN “READY TO SHOOT” LIGHT IS DE-ENERGIZEDB. THE RED “RANGE SECURED” LIGHT IS ENERGIZED
OPERATION:1. “SAFE TO SHOOT” - UPON SYSTEM ACHIEVING “SAFE TO SHOOT” STATUS:
A. THE SUPPLY FAN VARIABLE SPEED DRIVE MODULATES THE SUPPLY FAN SPEED TOMAINTAIN DESIGN SUPPLY AIR FLOW
B. THE EXHAUST FAN VARIABLE SPEED DRIVE MODULATES THE EXHAUST FAN SPEED TOMAINTAIN 10% DIFFERENTIAL OF EXHAUST AIR FLOW ABOVE SUPPLY AIR FLOW
SAFETIES:1. VFD FAULT - IF A SUPPLY OR EXHAUST FAN VFD INDICATES A FAULT CONDITION:
A. THE SYSTEM IS SHUT DOWNB. AN EQUIPMENT FAILURE ALARM IS ISSUED, ANDC. THE CONDITION MUST BE MANUALLY RESET.
2. EQUIPMENT FAILURE ALARMS SHALL BE ISSUED AS FOLLOWS:A. FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFFB. FAN RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON
3. FILTER DIFFERENTIAL PRESSURE - UPON SENSING EXCESSIVE DIFFERENTIAL PRESSUREACROSS ANY OF THE FILTER MODULES:A. A WARNING SIGNAL IS SENT TO THE BAS AND TO THE RANGE CONTROL PANEL. SEE FILTER
SCHEDULE ON SHEET M-601 FOR RECOMMENDED FILTER FINAL PRESSURES.4. HIGH STATIC PRESSURE - UPON SENSING SUPPLY AIR DUCT STATIC PRESSURE ABOVE THE
HIGH LIMIT SET POINT (TO BE ESTABLISHED UPON COMPLETION OF TAB WORK):A. THE SYSTEM SHALL SHUT DOWNB. AN ALARM IS ISSUED TO THE BAS AND TO THE RANGE CONTROL PANEL, ANDC. THE CONDITION MUST BE MANUALLY RESET.
5. LOW STATIC PRESSURE - UPON SENSING EXHAUST AIR DUCT STATIC PRESSURE BELOW THELOW LIMIT SET POINT (TO BE ESTABLISHED UPON COMPLETION OF TAB WORK):A. THE SYSTEM SHALL SHUT DOWNB. AN ALARM IS ISSUED TO THE BAS AND TO THE RANGE CONTROL PANEL, ANDC. THE CONDITION MUST BE MANUALLY RESET.
M
VFDCT
AO
BOBI
AI AIBI
P FMS
AI
BI
BI
BI
RANGE VENTILATION SYSTEM CONTROL DIAGRAM
SUPPLY FAN
SA
RANGE PERSONNEL DOOR STATUS
MAINTENANCE DOOR STATUS
ROLL UP DOOR STATUS
M
CTVFD
BIAO
BO
DPS
AI AIAI
PBI
DPS
AI
FMS
AI
EA
EXHAUST FAN
OA
EA
PRE-FILTER HEPAFILTER
(EF-1, EF-2)
(SF-1, SF-2)
(TYPICAL FOR EF-1/SF-1 AND EF-2/SF-2)
S
S
S
RANGE PERSONNEL DOOR STATUS X X
X
1
ETHERNET
BACNET
CONTROL SYSTEM ARCHITECTURE
MAINBUILDING
CONTROLLER
SFCONTROLLER
EFCONTROLLER
RTU-1CONTROLLER
MISCELLANEOUSCONTROLLER
RANGECONTROL
PANEL
CHANGEOVERBYPASS
VAV SYSTEM
BUILDINGLAN
M
EXHAUST SYSTEM (EF-3 & EF-4)
SEQUENCE OF OPERATIONTHE EXHAUST FAN SHALL BE CONTROLLED BY THEBUILDING DDC SYSTEM. THE FAN SHALL BEINTERLOCKED TO RUN WHENEVER RTU-1 IS IN THEOCCUPIED MODE. WHEN ENERGIZED TO RUN, THEEXHAUST DAMPER SHALL OPEN. AFTER PROVINGOPEN, THE EXHAUST FAN SHALL START AND SHALLRUN CONTINUOUSLY. WHEN COMMANDED TO STOP,THE EXHAUST FAN SHALL STOP AND THE EXHAUSTDAMPER SHALL CLOSE AFTER A 30 SECOND DELAY.
EA
MS
CSR
BI
BO
M BO
ES
BI
EXHAUST SYSTEMDDC CONTROL POINTS
POINT NAME AI AO BI BO TREND ALARMSHOWN
ONGRAPHIC
EXHAUST FAN START/STOPEXHAUST FAN STATUSEXHAUST DAMPER OPEN / CLOSEEXHAUST DAMPER POSITIONEXHAUST FAN FAILUREEXHAUST DAMPER FAILURE
XX X
XX X
XX
M
EXHAUST SYSTEM (EF-5)
SEQUENCE OF OPERATIONTHE EXHAUST FAN SHALL BE CONTROLLED BY THEBUILDING DDC SYSTEM. ON A RISE IN SPACETEMPERATURE ABOVE 80°F (ADJ), THE INTAKE ANDEXHAUST DAMPERS SHALL OPEN. AFTER PROVINGOPEN, THE EXHAUST FAN SHALL START AND SHALLRUN CONTINUOUSLY. ON A FALL IN SPACETEMPERATURE BELOW 78°F (ADJ), THE FAN SHALLSTOP AND THE INTAKE AND EXHAUST DAMPERS SHALLCLOSE AFTER A 30 SECOND DELAY. FAN SHALLREMAIN OFF AT LEAST TEN MINUTES BEFORERESTARTING.AN ALARM SHALL BE GENERATED IF THESPACE TEMPERATURE RISES ABOVE 95°F (ADJ).
EA
MS
CSR
BI
M BO
ES
BI
EXHAUST SYSTEMDDC CONTROL POINTS
POINT NAME AI AO BI BO TREND ALARMSHOWN
ONGRAPHIC
EXHAUST FAN START/STOPEXHAUST FAN STATUSEXHAUST DAMPER OPEN / CLOSEEXHAUST DAMPER POSITIONEXHAUST FAN FAILUREEXHAUST DAMPER FAILURE
XX X
XX
XX
SPACE TEMPERATURESPACE TEMPERATURE SET POINT
HIGH SPACE TEMPERATURE
XX
X XX
X
T
AO
AI
BO
M ES
BIAO
X
INTAKE DAMPER OPEN/CLOSEINTAKE DAMPER POSITIONINTAKE DAMPER FAILURE
XX
X
X
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
gR
ange
M14
_mja
rrett.
rvt
12/3
1/20
158:
46:3
4A
M
UN
ION
CO
UN
TYSH
ERIF
F'S
OFF
ICE
FIR
ING
RAN
GE
MIL
LSH
ARR
ISR
OAD
,MA
RSH
VILL
E,N
C
540411/17/2015JLDDRLEES
M-801
CONTROLSEQUENCES
DIAGRAMS ANDPOINTS LISTS
80
No. Date Description1 12/30/15 Revision 01
1
TT
T
ROOFTOP AIR HANDLING UNIT (RTU-1) AND BYPASS VAV SYSTEM
DPS
AI
AI
M
BO
AI
AI
FMS AI
AO
AO
AI
BI
AI
OA
CSR
BI
RA
P
AI
DA
BYPASS DAMPER
AI
PANEL
AOAO
ZONE VAV TERMINAL
AO
CO2
AI
DX COIL AUX ELECHEAT
SA
(ROOM 103 ONLY)
CONTROLRTU
RTU-1 AIR HANDLING SYSTEM
OVERVIEW:
THE ROOF TOP AIR HANDLING UNIT (RTU) IS CONTROLLED BY A DEDICATED CENTRAL CONTROLPANEL (CCP) THAT IS PART OF A BYPASS VAV SYSTEM. ALL SYSTEM COMPONENTS (AIR HANDLINGUNIT, VAV TERMINALS AND CONTROLS) SHALL BE BY THE SAME SYSTEM MANUFACTURER. THE CCPIS CONNECTED TO THE BUILDING AUTOMATION SYSTEM. THE CCP SHALL PLACE THE UNIT INOCCUPIED OR UNOCCUPIED MODE BASED ON ITS USER DEFINABLE INTERNAL OCCUPANCYPROGRAM. THE CCP SHALL POLL THE ASSOCIATED ZONE TEMPERATURE SENSORS TO DETERMINEIF THE UNIT SHALL BE PLACED IN THE HEATING MODE OR COOLING MODE. THERE SHALL BE AMINIMUM 5°F DEAD-BAND BETWEEN HEATING AND COOLING MODES FOR THE UNIT. ALL CONTROLFUNCTIONALITY AND SUPERVISORY INFORMATION INCLUDING ALARMS AVAILABLE AT THE CCPSHALL ALSO BE AVAILABLE AT THE MAIN DDC CONTROL PANEL.
ENABLEMENT:
THE SYSTEM CENTRAL CONTROL PANEL ENABLES OR DISABLES THE RTU UNLESS THE CONTROLSAREMANUALLY SHUT DOWN, OR DIRECTED BY THE BAS TO SHUT DOWN. ONCE ENABLED, THE RTUOPERATES UNDER ITS FACTORY INSTALLED CONTROLS
OPERATION:
UNOCCUPIED MODE - IN THE UNOCCUPIED MODE: THE RTU SHALL BE DE-ENERGIZED, AND THEOUTDOOR AIR DAMPER SHALL BE CLOSED.
ZONE TEMPERATURE SET POINTS - UNOCCUPIED TEMPERATURE SET POINTS ARE ADJUSTABLEAND ARE INITIALLY AS FOLLOWS:
HEATING - 60°FCOOLING - 80°F
UNIT DISCHARGE AIR TEMPERATURE SET POINTS - DISCHARGE AIR TEMPERATURE SET POINTS AREADJUSTABLE AND ARE INITIALLY AS FOLLOWS:
HEATING - 90°FCOOLING - 57°F (DISABLED IN ECONOMIZER MODE)
HEATING REQUIRED - ON A CALL FOR HEATING (DETERMINED BY THE CCP POLLING ALL ASSOCIATEDZONE SENSORS TO SEE IF 50% OF THE SENSORS ARE AT LEAST 2°F BELOW THE UNOCCUPIEDTEMPERATURE SET POINT OR IF ANY INDIVIDUAL ZONE SENSOR IS BELOW 55°F), THE RTU FANCYCLES ON AND RUNS CONTINUOUSLY. THE OUTDOOR AIR DAMPER REMAINS CLOSED. THE HEATPUMP IS ENERGIZED AND THE UNIT OPERATES UNDER ITS FACTORY INSTALLED CONTROLS. UPONALL ZONES REPORTING SATISFIED UNOCCUPIED TEMPERATURE THE HEAT PUMP IS DISABLED ANDTHE UNIT CYCLES OFF. A BUILT-IN ANTI-SHORT-CYCLE TIMER SHALL PREVENT UNIT FROM CYCLINGON/OFF TOO FREQUENTLY.
COOLING REQUIRED - ON A CALL FOR COOLING (DETERMINED BY THE CCP POLLING ALL ASSOCIATEDZONE SENSORS TO SEE IF 50% OF THE SENSORS ARE AT LEAST 2°F ABOVE THE UNOCCUPIEDTEMPERATURE SET POINT OR IF ANY INDIVIDUAL ZONE SENSOR IS ABOVE 85°F) THE RTU FANCYCLES ON AND RUNS CONTINUOUSLY. THE OUTDOOR AIR DAMPER SHALL REMAIN CLOSED. THEUNIT OPERATES UNDER ITS FACTORY INSTALLED CONTROLS TO STAGE THE COMPRESSORS ASNECESSARY. UPON ALL ZONES REPORTING SATISFIED UNOCCUPIED TEMPERATURE COOLING ISDISABLED AND THE UNIT CYCLES OFF. BUILT-IN ANTI-SHORT-CYCLE TIMER SHALL PREVENT UNITFROM CYCLING ON/OFF TOO FREQUENTLY.
MORNING WARM-UP/COOL DOWN - PRIOR TO SCHEDULED OCCUPANCY PERIODS, THE SYSTEMSHALL BE PLACED IN WARM-UP OR COOL-DOWN MODE TO BRING SPACES TO THEIR OCCUPIEDTEMPERATURE SET POINTS. THIS SHALL BE ACHIEVED BY STAGING THE UNIT FOR HEATING ORCOOLING AS DETERMINED BY THE CENTRAL CONTROL PANEL. THE OUTDOOR AIR DAMPER SHALLREMAIN CLOSED DURING WARM-UP OR COOL- DOWN MODE.
ZONE TEMPERATURE SET POINTS -OCCUPIED TEMPERATURE SET POINTS ARE ADJUSTABLE ANDARE INITIALLY AS FOLLOWS:
HEATING - 70°FCOOLING - 72°F
UNIT DISCHARGE AIR TEMPERATURE SET POINTS - DISCHARGE AIR TEMPERATURE SET POINTS AREADJUSTABLE AND ARE INITIALLY AS FOLLOWS:
HEATING - 90°FCOOLING - 57°F (DISABLED IN ECONOMIZER MODE)
HEATING REQUIRED - WHEN THE SYSTEM IS IN HEATING MODE, THE FAN ISENERGIZED AND RUNS CONTINUOUSLY. THE HEAT PUMP IS ENERGIZED AND THE UNITOPERATES UNDER ITS FACTORY INSTALLED CONTROLS TO MAINTAIN THE LEAVINGAIR TEMPERATURE SET POINT. WHEN ALL ZONES ARE SATISFIED THE HEAT PUMPSHALL CYCLE OFF. A BUILT-IN ANTI-SHORT-CYCLE TIMER SHALL PREVENT THE HEATPUMP FROM CYCLING ON/OFF TOO FREQUENTLY.
COOLING REQUIRED - WHEN THE SYSTEM IS IN THE COOLING MODE, THE FAN ISENERGIZED AND RUNS CONTINUOUSLY. THE UNIT OPERATES UNDER ITS FACTORYINSTALLED CONTROLS TO STAGE THE COMPRESSORS AS NECESSARY TO MAINTAINTHE LEAVING AIR TEMPERATURE SET POINT. WHEN ALL ZONES ARE SATISFIED THECOMPRESSOR SHALL CYCLE OFF. A BUILT-IN ANTI-SHORT-CYCLE TIMER SHALLPREVENT THE COMPRESSORS FROM CYCLING ON/OFF TOO FREQUENTLY. IF ANYINDIVIDUAL ZONE TEMPERATURE SET POINT IS NOT SATISFIED WHEN ALL ZONE AIRVALVES ARE 100% OPEN, THEN THE AIR HANDLING UNIT LEAVING AIR TEMPERATURESHALL BE GRADUALLY RESET LOWER TO A MINIMUM OF 48°F AND THE UNITCONTROLS SHALL STAGE THE COMPRESSORS FOR MAXIMUM CAPACITY.
ECONOMIZER OPERATION:
RTU SHALL OPERATE IN ECONOMIZER MODE WHENEVER THE UNIT IS IN COOLINGMODE AND THE OUTDOOR TEMPERATURE IS LESS THAN 65°F. ECONOMIZER SHALLPROVIDE UP TO 100% OF THE DESIGN SUPPLY AIR QUANTITY AS OUTDOOR AIR FORCOOLING. ECONOMIZER SHALL AUTOMATICALLY REDUCE OUTDOOR AIR INTAKE TOTHE DESIGN MINIMUM WHEN OUTDOOR AIR INTAKE WILL NO LONGER SATISFYCOOLING DEMAND. ECONOMIZER MODE SHALL BE DISABLED AND MECHANICALCOOLING ENABLED WHENEVER THE UNIT IS IN THE COOLING MODE AND THEOUTDOOR TEMPERATURE IS GREATER THAN 65°F.
VAV TERMINALS SHALL OPERATE AS DESCRIBED HEREIN ON A CALL FOR COOLING.
AUXILIARY ELECTRIC HEAT
HEAT PUMP CONTROLS SHALL PREVENT SUPPLEMENTAL ELECTRIC HEATEROPERATION WHEN THE HEATING LOAD CAN BE MET BY THE HEAT PUMP ALONEDURING BOTH STEADY-STATE OPERATION AND SETBACK RECOVERY.SUPPLEMENTAL HEATER OPERATION IS PERMITTED DURING OUTDOOR COILDEFROST CYCLES.
SAFETIES:EQUIPMENT FAILURE - IF THE UNIT'S INTERNAL CONTROLS SHUT IT DOWN DUE TO AFAULT CONDITION:
AN EQUIPMENT FAILURE ALARM IS ISSUED, AND THE UNIT CONTROLS MUST BEMANUALLY RESET BEFORE IT IS ALLOWED TO RE-START
FILTER DIFFERENTIAL PRESSURE - UPON SENSING EXCESSIVE DIFFERENTIALPRESSURE SENSOR ACROSS THE AIR FILTERS:
A WARNING SIGNAL IS SENT TO THE CCP AND TO THE BAS
HIGH LIMIT LEAVING AIR TEMPERATURE - ON SENSING A SUPPLY AIR TEMPERATUREABOVE 110°F (ADJUSTABLE):
THE SYSTEM SHALL SHUT DOWN. AN ALARM IS ISSUED TO THE CCP AND BAS,AND THE CONDITION MUST BE RESET MANUALLY.
LOW LIMIT LEAVING AIR TEMPERATURE - ON SENSING A SUPPLY AIR TEMPERATUREBELOW 45°F (ADJUSTABLE):
THE SYSTEM SHALL SHUT DOWN. AN ALARM IS ISSUED TO THE CCP AND BAS,AND THE CONDITION MUST BE MANUALLY RESET.
DUCT SMOKE DETECTOR:
ON SENSING PRODUCTS OF COMBUSTION AT THE RETURN AIR DUCT SMOKEDETECTOR:
THE SYSTEM IS SHUT DOWN AND AN ALARM IS SENT TO THE CCP AND TO THEBAS. SMOKE DETECTION STATUS IS ALSO SENT TO THE BUILDING FIRE ALARMCONTRL PANEL.
BYPASS VAV SYSTEM
OVERVIEW:
THE SYSTEM IS A BYPASS VAV SYSTEM AND IS CONTROLLED BY THE DEDICATEDCENTRAL CONTROL PANEL (CCP) DESCRIBED ABOVE. ALL SYSTEM COMPONENTS(AIR HANDLING UNIT, VAV TERMINALS AND CONTROLS) SHALL BE BY THE SAMESYSTEM MANUFACTURER.
ENABLEMENT:
THE CENTRAL CONTROL PANEL ENABLES THE SYSTEM AND PLACES THE SYSTEM INOCCUPIED MODE OR UNOCCUPIED MODE ACCORDING TO THE USER DEFINABLEOCCUPANCY SCHEDULE UNLESS:
THE SYSTEM IS MANUALLY SHUT DOWN, OR DIRECTED BY THE BAS TO SHUTDOWN. OCCUPANCY OVERRIDE - ZONE TEMPERATURE SENSORS HAVE ANOCCUPANCY OVERRIDE PUSHBUTTON THAT TEMPORARILY PLACES THE SYSTEMIN THE OCCUPIED MODE FOR A MINIMUM OF 1 HOUR (ADJUSTABLE).
ZONE CONTROL DAMPERS ARE UNDER CONTROL OF THEIR RESPECTIVE ZONETEMPERATURE SENSORS.
OPERATION:
UNOCCUPIED MODE - IN THE UNOCCUPIED MODE:ALL ZONE DAMPERS ARE AT THEIR MINIMUM POSITIONS.BYPASS DAMPER IS AT 50% POSITION.
ZONE TEMPERATURE SET POINTS - UNOCCUPIED TEMPERATURE SET POINTS AREADJUSTABLE AND ARE INITIALLY AS FOLLOWS:
HEATING - 60°FCOOLING - 80°F
HEATING REQUIRED - WHENEVER THE CCP DETERMINES THAT HEATING IS REQUIRED(AS DESCRIBED ABOVE), THE ZONE DAMPER SHALL MODULATE OPEN UNTIL THEZONE TEMPERATURE IS SATISFIED.
COOLING REQUIRED - WHENEVER THE CCP DETERMINES THAT COOLING IS REQUIRED(AS DESCRIBED ABOVE), THE ZONE DAMPER SHALL MODULATE OPEN UNTIL THEZONE TEMPERATURE IS SATISFIED.
OCCUPIED MODE - IN THE OCCUPIED MODE:ZONE TEMPERATURE SET POINTS -OCCUPIED TEMPERATURE SET POINTS AREADJUSTABLE AND ARE INITIALLY AS FOLLOWS:
HEATING - 70°FCOOLING - 72°F
HEATING REQUIRED - ON A FALL IN ZONE TEMPERATURE BELOW THE OCCUPIED SETPOINT, THE ZONE DAMPER SHALL MODULATE OPEN UNTIL THE ZONE TEMPERATUREIS SATISFIED. ON A RISE IN ZONE TEMPERATURE ABOVE THE OCCUPIED SET POINT,THE REVERSE SHALL OCCUR.
COOLING REQUIRED - ON A RISE IN ZONE TEMPERATURE ABOVE THE OCCUPIED SETPOINT, THE ZONE DAMPER SHALL MODULATE OPEN UNTIL THE ZONE TEMPERATUREIS SATISFIED. ON A FALL IN ZONE TEMPERATURE BELOW THE OCCUPIED SET POINT,THE REVERSE SHALL OCCUR.
DUCT STATIC PRESSURE & BYPASS DAMPER
ON A RISE IN SUPPLY DUCT STATIC PRESSURE ABOVE THE SYSTEM SET POINT, THEBYPASS DAMPER MODULATES OPEN.
ON A FALL IN DUCT STATIC PRESSURE BELOW THE SET POINT MINUS 10%, THEREVERSE SHALL OCCUR.STATIC PRESSURE SENSOR SET POINT SHALL BE ESTABLISHED IN ACCORDANCEWITH THE SYSTEM EQUIPMENT MANUFACTURER'S WRITTEN RECOMMENDATIONS.
OCCUPANCY OVERRIDE - ZONE TEMPERATURE SENSORS HAVE AN OCCUPANCYOVERRIDE PUSHBUTTON THAT, WHEN INITIATED, TEMPORARILY PLACES THE SYSTEM INTHE OCCUPIED MODE FOR A MINIMUM OF 1 HOUR (ADJUSTABLE).
MORNING WARM-UP- WHEN THE CCP SCHEDULE PLACES THE SYSTEM IN MORNINGWARM-UP MODE:
ZONE TEMPERATURES ARE SET TO THE OCCUPIED MODE, HEATINGTEMPERATURE SET POINT,ZONE AIR VALVES MODULATE TO THEIR FULL OPEN POSITION. UPON ACHIEVINGTHE ZONE TEMPERATURE, THE ZONE AIR VALVE MODULATES TO ITS MINIMUM
POSITION.
MORNING COOL DOWN - WHEN THE CCP SCHEDULE PLACES THE SYSTEM IN MORNINGCOOL DOWN MODE:
ZONE TEMPERATURES ARE SET TO THE OCCUPIED MODE, COOLINGTEMPERATURE SET POINT,ZONE AIR VALVES MODULATE TO THEIR FULL OPEN POSITION. UPON ACHIEVINGTHE ZONE TEMPERATURE, THE ZONE AIR VALVE MODULATES TO ITS MINIMUM
POSITION
CARBON DIOXIDE (CO2) SENSOR - ON SENSING ZONE CO2 CONCENTRATION ABOVE1500-PPM (ADJUSTABLE), THE CORRESPONDING ZONE AIR VALVE MODULATES FULLYOPEN. ON A FURTHER RISE IN ZONE CO2 CONCENTRATION ABOVE 1750-PPM(ADJUSTABLE) THE CCP COMMANDS THE RTU OUTSIDE AIR DAMPER TO MODULATEOPEN UNTIL THE ZONE CONCENTRATION FALLS BELOW 1500-PPM. ON FURTHER RISE INZONE CO2 CONCENTRATION ABOVE 2000-PPM (ADJUSTABLE), AN AUDIBLE ALARM ISGENERATED AT THE ZONE CO2 SENSOR AND SENT TO THE CCP. THE ALARM SHALLAUTOMATICALLY RESET ON A FALL IN CO2 CONCENTRATION BELOW 1750-PPM.
SAFETIES:
HIGH ZONE TEMPERATURE - UPON SENSING A ZONE TEMPERATURE 10°F ABOVE ITS SETPOINT:
AN ALARM IS ISSUED TO THE CCP AND BAS, AND THE CONDITION MUST BE MANUALLYRESET.
LOW ZONE TEMPERATURE - UPON SENSING A ZONE TEMPERATURE 10°F BELOW ITSSET POINT:
AN ALARM IS ISSUED TO THE CCP AND BAS, AND THE CONDITION MUST BE MANUALLYRESET.
HIGH CO2 CONCENTRATION - UPON SENSING A ZONE CO2 CONCENTRATION ABOVE2000-PPM:
AN ALARM IS ISSUED AT THE CCP AND BAS, AND THE ALARM AT THE CCP AND BASMUST BE MANUALLY RESET.
RTU-1 DDC CONTROL POINTS
POINT NAME AI AO BI BO TREND ALARMSHOWN
ONGRAPHIC
RTU ENABLE XRTU STATUSRTU FAULT
OUTDOOR AIR DAMPER POSITION (0-100%)
X X
COOLING ENABLECOOLING STATUS
SUPPLY FAN STATUSSUPPLY AIR TEMPERATURESUPPLY AIR TEMPERATURE SETPOINTOUTDOOR AIR TEMPERATURE
X
XX
X
X
X
X
BYPASS VAV SYSTEM DDCCONTROL POINTS
POINT NAME AI AO BI BO TREND ALARMSHOWN
ONGRAPHIC
SUPPLEMENTAL ELECTRIC HEAT ENABLE
ZONE TEMPERATURE SETPOINTZONE AIR FLOWMINIMUM ZONE AIR FLOW SETPOINT
X
MAXIMUM ZONE AIR FLOW SETPOINTOUTDOOR AIR FLOWOCCUPANCY STATUSOCCUPANCY OVERRIDEDUCT STATIC PRESSURE
X X
X
X
AIR FILTER STATUS
HEAT ENABLE
DUCT STATIC PRESSURE SETPOINTBYPASS DAMPER AIRFLOW
X
XX
XX
XXXXX
X
X
X
X
X
X
XXXXX
X
X
XX
XX
XX
XX
XBYPASS DAMPER POSITION X X
AI
HL
AI
LL
AI
AI
COMMUNICATINGBYPASS CONTROLLER
CENTRALCONTROL
PANEL
BIBIBI BOBOBO
SD BI
OUTDOOR AIR DAMPER OPEN/CLOSE
SUPPLEMENTAL ELECTRIC HEAT STATUSSUPPLY AIR HIGH LIMIT TEMPERATURESUPPLY AIR LOW LIMIT TEMPERATURESUPPLY AIR HIGH LIMIT TEMPERATURE SETPOINTSUPPLY AIR LOW LIMIT TEMPERATURE SETPOINTRETURN DUCT SMOKE DETECTOR
XX
XX
X
XX
XX
ZONE TEMPERATURE XX XX
XX
TO/FROMDDC
SYSTEM
FILTER
M
CO2 CONCENTRATION X XX
1
1
1
Roanoke, VA 24011213 South Jefferson Avenue, Suite 1011
540.982.0800Clark Nexsen license number: C-1028
1 2 3 4 5
A
B
C
D
CN NO:DATE:DESIGN:DRAWN:REVIEW:
REVISIONS
SHEET OF 94
C:\R
evit
Proj
ects
\540
4-U
nion
Co
Firin
gR
ange
M14
_mja
rrett.
rvt
12/3
1/20
158:
46:3
5A
M
UN
ION
CO
UN
TYSH
ERIF
F'S
OFF
ICE
FIR
ING
RAN
GE
MIL
LSH
ARR
ISR
OAD
,MA
RSH
VILL
E,N
C
540411/17/2015JLDDRLEES
M-802
CONTROLSEQUENCES
DIAGRAMS ANDPOINTS LISTS
81
No. Date Description1 12/30/15 Revision 01
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 1
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Fire-alarm control unit.
2. Manual fire-alarm boxes.
3. System smoke detectors.
4. Heat detectors.
5. Linear heat detection cable.
6. Notification appliances.
7. Addressable interface device.
8. Digital alarm communicator transmitter.
1.3 DEFINITIONS
A. EMT: Electrical Metallic Tubing.
B. FACP: Fire Alarm Control Panel.
C. HLI: High Level Interface.
D. NICET: National Institute for Certification in Engineering Technologies.
E. PC: Personal computer.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product, including furnished options and accessories.
1. Include construction details, material descriptions, dimensions, profiles, and finishes.
2. Include rated capacities, operating characteristics, and electrical characteristics.
B. Shop Drawings: For fire-alarm system.
1. Comply with recommendations and requirements in the "Documentation" section of the
"Fundamentals" chapter in NFPA 72.
2. Include plans, elevations, sections, details, and attachments to other work.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 2
3. Include details of equipment assemblies. Indicate dimensions, weights, loads, required
clearances, method of field assembly, components, and locations. Indicate conductor
sizes, indicate termination locations and requirements, and distinguish between factory
and field wiring.
4. Detail assembly and support requirements.
5. Include voltage drop calculations for notification-appliance circuits.
6. Include battery-size calculations.
7. Include input/output matrix.
8. Include statement from manufacturer that all equipment and components have been tested
as a system and meet all requirements in this Specification and in NFPA 72.
9. Include performance parameters and installation details for each detector.
10. Verify that each duct detector is listed for complete range of air velocity, temperature,
and humidity possible when air-handling system is operating.
11. Include plans, sections, and elevations of heating, ventilating, and air-conditioning ducts,
drawn to scale; coordinate location of duct smoke detectors and access to them.
a. Show critical dimensions that relate to placement and support of sampling tubes,
detector housing, and remote status and alarm indicators.
b. Show field wiring required for HVAC unit shutdown on alarm.
c. Show field wiring and equipment required for HVAC unit shutdown on alarm.
d. Locate detectors according to manufacturer's written recommendations.
12. Include floor plans to indicate final outlet locations showing address of each addressable
device. Show size and route of cable and conduits and point-to-point wiring diagrams.
C. General Submittal Requirements:
1. Submittals shall be approved by authorities having jurisdiction prior to submitting them
to Architect.
2. Shop Drawings shall be prepared by persons with the following qualifications:
a. Trained and certified by manufacturer in fire-alarm system design.
b. NICET-certified, fire-alarm technician; Level II minimum.
c. Licensed or certified by authorities having jurisdiction.
1.5 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer.
B. Field quality-control reports.
1.6 Sample Warranty: For special warranty.
1.7 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For fire-alarm systems and components to include in
emergency, operation, and maintenance manuals.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 3
1. In addition to items specified in Section 017823 "Operation and Maintenance Data,"
include the following and deliver copies to authorities having jurisdiction:
a. Comply with the "Records" section of the "Inspection, Testing and Maintenance"
chapter in NFPA 72.
b. Provide "Fire Alarm and Emergency Communications System Record of
Completion Documents" according to the "Completion Documents" Article in the
"Documentation" section of the "Fundamentals" chapter in NFPA 72.
c. Complete wiring diagrams showing connections between all devices and
equipment. Each conductor shall be numbered at every junction point with
indication of origination and termination points.
d. Riser diagram.
e. Device addresses.
f. Record copy of site-specific software.
g. Provide "Inspection and Testing Form" according to the "Inspection, Testing and
Maintenance" chapter in NFPA 72, and include the following:
1) Equipment tested.
2) Frequency of testing of installed components.
3) Frequency of inspection of installed components.
4) Requirements and recommendations related to results of maintenance.
5) Manufacturer's user training manuals.
h. Manufacturer's required maintenance related to system warranty requirements.
i. Abbreviated operating instructions for mounting at fire-alarm control unit and each
annunciator unit.
B. Software and Firmware Operational Documentation:
1. Software operating and upgrade manuals.
2. Program Software Backup: On magnetic media or compact disk, complete with data files.
3. Device address list.
4. Printout of software application and graphic screens.
1.8 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective
covering for storage and identified with labels describing contents.
1. Lamps for Strobe Units: Quantity equal to 10 percent of amount installed, but no fewer
than one unit.
2. Smoke Detectors: Quantity equal to 10 percent of amount of each type installed, but no
fewer than one unit of each type.
3. Keys and Tools: One extra set for access to locked or tamper-proofed components.
4. Audible and Visual Notification Appliances: One of each type installed.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 4
1.9 QUALITY ASSURANCE
A. Installer Qualifications: Personnel shall be trained and certified by manufacturer for installation
of units required for this Project.
B. Use of Devices during Construction: Protect devices during construction unless devices are
placed in service to protect the facility during construction.
1.10 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace fire-alarm system equipment and
components that fail in materials or workmanship within specified warranty period.
1. Warranty Extent: All equipment and components not covered in the Maintenance Service
Agreement.
2. Warranty Period: Five years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 SYSTEM DESCRIPTION
A. Noncoded, addressable system, with multiplexed signal transmission and horn/strobe
evacuation.
B. Automatic sensitivity control of certain smoke detectors.
C. All components provided shall be listed for use with the selected system.
D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by
a qualified testing agency, and marked for intended location and application.
2.2 SYSTEMS OPERATIONAL DESCRIPTION
A. Fire-alarm signal initiation shall be by one or more of the following devices:
1. Manual stations.
2. Smoke detectors.
3. Heat detectors.
4. Linear heat detection cable.
B. Fire-alarm signal shall initiate the following actions:
1. Continuously operate alarm notification appliances.
2. Identify alarm and specific initiating device at fire-alarm control unit.
3. Transmit an alarm signal to the remote alarm receiving station.
4. Switch heating, ventilating, and air-conditioning equipment controls to fire-alarm mode.
5. Record events in the system memory.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 5
C. Supervisory signal initiation shall be by one or more of the following devices and actions:
1. Duct smoke detectors.
2. User disabling of zones or individual devices.
3. Loss of communication with any panel on the network.
D. System trouble signal initiation shall be by one or more of the following devices and actions:
1. Open circuits, shorts, and grounds in designated circuits.
2. Opening, tampering with, or removing alarm-initiating and supervisory signal-initiating
devices.
3. Loss of communication with any addressable sensor, input module, relay, control
module, remote annunciator, printer interface, or Ethernet module.
4. Loss of primary power at fire-alarm control unit.
5. Ground or a single break in internal circuits of fire-alarm control unit.
6. Abnormal ac voltage at fire-alarm control unit.
7. Break in standby battery circuitry.
8. Failure of battery charging.
9. Abnormal position of any switch at fire-alarm control unit or annunciator.
E. System Supervisory Signal Actions:
1. Initiate notification appliances.
2. Identify specific device initiating the event at fire-alarm control.
3. After a time delay of 200 seconds, transmit a trouble or supervisory signal to the remote
alarm receiving station.
4. Transmit system status to building management system.
2.3 FIRE-ALARM CONTROL UNIT
A. General Requirements for Fire-Alarm Control Unit:
1. Field-programmable, microprocessor-based, modular, power-limited design with
electronic modules, complying with UL 864.
a. System software and programs shall be held in nonvolatile flash, electrically
erasable, programmable, read-only memory, retaining the information through
failure of primary and secondary power supplies.
b. Include a real-time clock for time annotation of events on the event recorder and
printer.
c. Provide communication between the FACP and remote circuit interface panels,
annunciators, and displays.
d. The FACP shall be listed for connection to a central-station signaling system
service.
e. Provide nonvolatile memory for system database, logic, and operating system and
event history. The system shall require no manual input to initialize in the event of
a complete power down condition. The FACP shall provide a minimum 500-event
history log.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 6
2. Addressable Initiation Device Circuits: The FACP shall indicate which communication
zones have been silenced and shall provide selective silencing of alarm notification
appliance by building communication zone.
3. Addressable Control Circuits for Operation of Notification Appliances and Mechanical
Equipment: The FACP shall be listed for releasing service.
B. Alphanumeric Display and System Controls: Arranged for interface between human operator at
fire-alarm control unit and addressable system components including annunciation and
supervision. Display alarm, supervisory, and component status messages and the programming
and control menu.
1. Annunciator and Display: Liquid-crystal type, 80 characters, minimum.
2. Keypad: Arranged to permit entry and execution of programming, display, and control
commands.
C. Alphanumeric Display and System Controls: Arranged for interface between human operator at
fire-alarm control unit and addressable system components including annunciation and
supervision. Display alarm, supervisory, and component status messages and the programming
and control menu.
1. Annunciator and Display: Liquid-crystal type, two lines of 80 characters, minimum.
2. Keypad: Arranged to permit entry and execution of programming, display, and control
commands.
D. Initiating-Device, Notification-Appliance, and Signaling-Line Circuits:
1. Pathway Class Designations: NFPA 72, Class B.
2. Pathway Survivability: Level 0.
3. Install no more than 50 addressable devices on each signaling-line circuit.
4. Serial Interfaces:
a. One dedicated RS 485 port for central-station operation using point ID DACT.
b. One RS 485 port for remote annunciators, Ethernet module, or multi-interface
module (printer port).
c. One USB port for PC configuration.
E. Smoke-Alarm Verification:
1. Initiate audible and visible indication of an "alarm-verification" signal at fire-alarm
control unit.
2. Activate an approved "alarm-verification" sequence at fire-alarm control unit and
detector.
3. Sound general alarm if the alarm is verified.
4. Cancel fire-alarm control unit indication and system reset if the alarm is not verified.
F. Notification-Appliance Circuit:
1. Audible appliances shall sound in a three-pulse temporal pattern, as defined in NFPA 72.
2. Visual alarm appliances shall flash in synchronization where multiple appliances are in
the same field of view, as defined in NFPA 72.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 7
G. Transmission to Remote Alarm Receiving Station: Automatically transmit alarm, supervisory,
and trouble signals to a remote alarm station.
H. Primary Power: 24-V dc obtained from 120-V ac service and a power-supply module. Initiating
devices, notification appliances, signaling lines, trouble signals, supervisory signals, and digital
alarm communicator transmitters shall be powered by 24-V dc source.
1. Alarm current draw of entire fire-alarm system shall not exceed 80 percent of the power-
supply module rating.
I. Secondary Power: 24-V dc supply system with batteries, automatic battery charger, and
automatic transfer switch.
1. Batteries: Sealed lead calcium.
J. Instructions: Computer printout or typewritten instruction card mounted behind a plastic or
glass cover in a stainless-steel or aluminum frame. Include interpretation and describe
appropriate response for displays and signals. Briefly describe the functional operation of the
system under normal, alarm, and trouble conditions.
2.4 MANUAL FIRE-ALARM BOXES
A. General Requirements for Manual Fire-Alarm Boxes: Comply with UL 38. Boxes shall be
finished in red with molded, raised-letter operating instructions in contrasting color; shall show
visible indication of operation; and shall be mounted on recessed outlet box. If indicated as
surface mounted, provide manufacturer's surface back box.
1. Double-action mechanism requiring two actions to initiate an alarm, pull-lever type; with
integral addressable module arranged to communicate manual-station status (normal,
alarm, or trouble) to fire-alarm control unit.
2. Station Reset: Key- or wrench-operated switch.
2.5 SYSTEM SMOKE DETECTORS
A. General Requirements for System Smoke Detectors:
1. Comply with UL 268; operating at 24-V dc, nominal.
2. Detectors shall be [two-wire type.
3. Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
4. Base Mounting: Detector and associated electronic components shall be mounted in a
twist-lock module that connects to a fixed base. Provide terminals in the fixed base for
connection to building wiring.
5. Self-Restoring: Detectors do not require resetting or readjustment after actuation to
restore them to normal operation.
6. Integral Visual-Indicating Light: LED type, indicating detector has operated and power-
on status.
B. Photoelectric Smoke Detectors:
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 8
1. Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system and its sensitivity setting.
2. An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:
a. Primary status.
b. Device type.
c. Present average value.
d. Present sensitivity selected.
e. Sensor range (normal, dirty, etc.).
C. Duct Smoke Detectors: Photoelectric type complying with UL 268A.
1. Detector address shall be accessible from fire-alarm control unit and shall be able to
identify the detector's location within the system and its sensitivity setting.
2. An operator at fire-alarm control unit, having the designated access level, shall be able to
manually access the following for each detector:
a. Primary status.
b. Device type.
c. Present average value.
d. Present sensitivity selected.
e. Sensor range (normal, dirty, etc.).
3. Weatherproof Duct Housing Enclosure: NEMA 250, Type 4X; NRTL listed for use with
the supplied detector for smoke detection in HVAC system ducts.
4. Each sensor shall have multiple levels of detection sensitivity.
5. Sampling Tubes: Design and dimensions as recommended by manufacturer for specific
duct size, air velocity, and installation conditions where applied.
6. Relay Fan Shutdown: Fully programmable relay rated to interrupt fan motor-control
circuit.
2.6 HEAT DETECTORS
A. General Requirements for Heat Detectors: Comply with UL 521.
1. Temperature sensors shall test for and communicate the sensitivity range of the device.
B. Heat Detector, Fixed-Temperature Type: Actuated by temperature that exceeds a fixed
temperature of 155 deg F.
1. Mounting: Twist-lock base interchangeable with smoke-detector bases.
2. Integral Addressable Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
C. Linear Heat Detector Cable:
1. Detector Cable: Rated detection temperature 190 deg F . Listed for service in an outdoor
environment. Cable includes two steel actuator wires twisted together with spring
pressure, wrapped with protective tape, and finished with PVC outer sheath. Each
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 9
actuator wire is insulated with heat-sensitive material that reacts with heat to allow the
cable twist pressure to short circuit wires at the location of elevated temperature.
2. Signals to Fire-Alarm Control Unit: Any type of local system trouble shall be reported to
fire-alarm control unit as a composite "trouble" signal. Alarms on each detection zone
shall be individually reported to central fire-alarm control unit as separately identified
zones.
3. Addressable Monitor Module: Arranged to communicate detector status (normal, alarm,
or trouble) to fire-alarm control unit.
2.7 NOTIFICATION APPLIANCES
A. General Requirements for Notification Appliances: Individually addressed, connected to a
signaling-line circuit, equipped for mounting as indicated, and with screw terminals for system
connections.
B. General Requirements for Notification Appliances: Connected to notification-appliance signal
circuits, zoned as indicated, equipped for mounting as indicated, and with screw terminals for
system connections.
1. Combination Devices: Factory-integrated audible and visible devices in a single-
mounting assembly, equipped for mounting as indicated, and with screw terminals for
system connections.
C. Horns: Electric-vibrating-polarized type, 24-V dc; with provision for housing the operating
mechanism behind a grille. Comply with UL 464. Horns shall produce a sound-pressure level of
90 dBA, measured 10 feet from the horn, using the coded signal prescribed in UL 464 test
protocol.
D. Visible Notification Appliances: Xenon strobe lights complying with UL 1971, with clear or
nominal white polycarbonate lens mounted on an aluminum faceplate. The word "FIRE" is
engraved in minimum 1-inch-high letters on the lens.
1. Rated Light Output:
a. 15/30/75/110 cd, selectable in the field.
2. Mounting: Wall mounted unless otherwise indicated.
3. For units with guards to prevent physical damage, light output ratings shall be determined
with guards in place.
4. Flashing shall be in a temporal pattern, synchronized with other units.
5. Strobe Leads: Factory connected to screw terminals.
6. Mounting Faceplate: Factory finished, red.
2.8 ADDRESSABLE INTERFACE DEVICE
A. General:
1. Include address-setting means on the module.
2. Store an internal identifying code for control panel use to identify the module type.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 10
3. Listed for controlling HVAC fan motor controllers.
B. Monitor Module: Microelectronic module providing a system address for alarm-initiating
devices for wired applications with normally open contacts.
C. Control Module:
1. Operate notification devices.
2.9 DIGITAL ALARM COMMUNICATOR TRANSMITTER
A. Digital alarm communicator transmitter shall be acceptable to the remote central station and
shall comply with UL 632.
B. Functional Performance: Unit shall receive an alarm, supervisory, or trouble signal from fire-
alarm control unit and automatically capture two telephone lines and dial a preset number for a
remote central station. When contact is made with central station(s), signals shall be transmitted.
If service on either line is interrupted for longer than 45 seconds, transmitter shall initiate a local
trouble signal and transmit the signal indicating loss of telephone line to the remote alarm
receiving station over the remaining line. Transmitter shall automatically report telephone
service restoration to the central station. If service is lost on both telephone lines, transmitter
shall initiate the local trouble signal.
C. Local functions and display at the digital alarm communicator transmitter shall include the
following:
1. Verification that both telephone lines are available.
2. Programming device.
3. LED display.
4. Manual test report function and manual transmission clear indication.
5. Communications failure with the central station or fire-alarm control unit.
D. Digital data transmission shall include the following:
1. Address of the alarm-initiating device.
2. Address of the supervisory signal.
3. Address of the trouble-initiating device.
4. Loss of ac supply.
5. Loss of power.
6. Low battery.
7. Abnormal test signal.
8. Communication bus failure.
E. Secondary Power: Integral rechargeable battery and automatic charger.
F. Self-Test: Conducted automatically every 24 hours with report transmitted to central station.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 11
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and conditions for compliance with requirements for ventilation, temperature,
humidity, and other conditions affecting performance of the Work.
1. Verify that manufacturer's written instructions for environmental conditions have been
permanently established in spaces where equipment and wiring are installed, before
installation begins.
B. Examine roughing-in for electrical connections to verify actual locations of connections before
installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 EQUIPMENT INSTALLATION
A. Comply with NFPA 72, NFPA 101, and requirements of authorities having jurisdiction for
installation and testing of fire-alarm equipment. Install all electrical wiring to comply with
requirements in NFPA 70 including, but not limited to, Article 760, "Fire Alarm Systems."
1. Devices placed in service before all other trades have completed cleanup shall be
replaced.
2. Devices installed but not yet placed in service shall be protected from construction dust,
debris, dirt, moisture, and damage according to manufacturer's written storage
instructions.
B. Install wall-mounted equipment, with tops of cabinets not more than 78 inches above the
finished floor.
C. Manual Fire-Alarm Boxes:
1. Install manual fire-alarm box in the normal path of egress within 60 inches of the exit
doorway.
2. Mount manual fire-alarm box on a background of a contrasting color.
3. The operable part of manual fire-alarm box shall be between 42 inches and 48 inches
above floor level. All devices shall be mounted at the same height unless otherwise
indicated.
D. Smoke- or Heat-Detector Spacing:
1. Comply with the "Smoke-Sensing Fire Detectors" section in the "Initiating Devices"
chapter in NFPA 72, for smoke-detector spacing.
E. Install a cover on each smoke detector that is not placed in service during construction. Cover
shall remain in place except during system testing. Remove cover prior to system turnover.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 12
F. Duct Smoke Detectors: Comply with NFPA 72 and NFPA 90A. Install sampling tubes so they
extend the full width of duct. Tubes more than 36 inches long shall be supported at both ends.
1. Do not install smoke detector in duct smoke-detector housing during construction. Install
detector only during system testing and prior to system turnover.
G. Remote Status and Alarm Indicators: Install in a visible location near each smoke detector,
sprinkler water-flow switch, and valve-tamper switch that is not readily visible from normal
viewing position.
H. Audible Alarm-Indicating Devices: Install not less than 6 inches below the ceiling. Install bells
and horns on flush-mounted back boxes with the device-operating mechanism concealed behind
a grille. Install all devices at the same height unless otherwise indicated.
I. Visible Alarm-Indicating Devices: Install adjacent to each alarm bell or alarm horn and at least
6 inches below the ceiling. Install all devices at the same height unless otherwise indicated.
J. Device Location-Indicating Lights: Locate in public space near the device they monitor.
3.3 PATHWAYS
A. Pathways shall be installed in EMT, IMC, or RGS.
B. Exposed conduit shall be painted red enamel in unfinished spaces. In finished spaces, exposed
conduit shall be painted to match adjacent surface.
3.4 CONNECTIONS
A. Make addressable connections with a supervised interface device to the following devices and
systems. Install the interface device less than 36 inches from the device controlled. Make an
addressable confirmation connection when such feedback is available at the device or system
being controlled.
1. Alarm-initiating connection to activate emergency lighting control.
3.5 IDENTIFICATION
A. Identify system components, wiring, cabling, and terminals. Comply with requirements for
identification specified in Section 260553 "Identification for Electrical Systems."
B. Install framed instructions in a location visible from fire-alarm control unit.
3.6 GROUNDING
A. Ground fire-alarm control unit and associated circuits; comply with IEEE 1100. Install a ground
wire from main service ground to fire-alarm control unit.
B. Ground shielded cables at the control panel location only. Insulate shield at device location.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 13
3.7 FIELD QUALITY CONTROL
A. Field tests shall be witnessed by authorities having jurisdiction.
B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and
inspect components, assemblies, and equipment installations, including connections.
C. Perform tests and inspections.
D. Perform the following tests and inspections:
1. Visual Inspection: Conduct visual inspection prior to testing.
a. Inspection shall be based on completed record Drawings and system
documentation that is required by the "Completion Documents, Preparation" table
in the "Documentation" section of the "Fundamentals" chapter in NFPA 72.
b. Comply with the "Visual Inspection Frequencies" table in the "Inspection" section
of the "Inspection, Testing and Maintenance" chapter in NFPA 72; retain the
"Initial/Reacceptance" column and list only the installed components.
2. System Testing: Comply with the "Test Methods" table in the "Testing" section of the
"Inspection, Testing and Maintenance" chapter in NFPA 72.
3. Test audible appliances for the public operating mode according to manufacturer's written
instructions. Perform the test using a portable sound-level meter complying with Type 2
requirements in ANSI S1.4.
4. Test audible appliances for the public operating mode according to manufacturer's written
instructions.
5. Test visible appliances for the public operating mode according to manufacturer's written
instructions.
6. Factory-authorized service representative shall prepare the "Fire Alarm System Record of
Completion" in the "Documentation" section of the "Fundamentals" chapter in NFPA 72
and the "Inspection and Testing Form" in the "Records" section of the "Inspection,
Testing and Maintenance" chapter in NFPA 72.
E. Reacceptance Testing: Perform reacceptance testing to verify the proper operation of added or
replaced devices and appliances.
F. Fire-alarm system will be considered defective if it does not pass tests and inspections.
G. Prepare test and inspection reports.
H. Maintenance Test and Inspection: Perform tests and inspections listed for weekly, monthly,
quarterly, and semiannual periods. Use forms developed for initial tests and inspections.
I. Annual Test and Inspection: One year after date of Substantial Completion, test fire-alarm
system complying with visual and testing inspection requirements in NFPA 72. Use forms
developed for initial tests and inspections.
Firearms Training Range 5404
Union County, North Carolina
DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM 283111 - 14
3.8 MAINTENANCE SERVICE
A. Initial Maintenance Service: Beginning at Substantial Completion, maintenance service shall
include 12 months' full maintenance by skilled employees of manufacturer's designated service
organization. Include preventive maintenance, repair or replacement of worn or defective
components, lubrication, cleaning, and adjusting as required for proper operation. Parts and
supplies shall be manufacturer's authorized replacement parts and supplies.
1. Include visual inspections according to the "Visual Inspection Frequencies" table in the
"Testing" paragraph of the "Inspection, Testing and Maintenance" chapter in NFPA 72.
2. Perform tests in the "Test Methods" table in the "Testing" paragraph of the "Inspection,
Testing and Maintenance" chapter in NFPA 72.
3. Perform tests per the "Testing Frequencies" table in the "Testing" paragraph of the
"Inspection, Testing and Maintenance" chapter in NFPA 72.
3.9 SOFTWARE SERVICE AGREEMENT
A. Comply with UL 864.
B. Technical Support: Beginning at Substantial Completion, service agreement shall include
software support for two years.
C. Upgrade Service: At Substantial Completion, update software to latest version. Install and
program software upgrades that become available within two years from date of Substantial
Completion. Upgrading software shall include operating system and new or revised licenses for
using software.
3.10 DEMONSTRATION
A. Train Owner's maintenance personnel to adjust, operate, and maintain fire-alarm system.
END OF SECTION 283111