Addendum #1
Project: GJ Las Colonias Amphitheatre Addition
From Mike Nielsen
Project No: 20190529 Date: 04/07/2020
Summary of drawing changes: MH101 (See attached sheet)
1. Radon piping system updated to match architectural layout. 2. Radon exhaust fan indicated. 3. Existing exhaust fan ducts to be re-routed to roof.
ME601 (See attached sheet)
1. Radon exhaust fan schedule added. PL101 (See attached sheet)
1. Hot water recirculation balance valves indicated on plans reflecting specification requirements. 2. Water hammer arrestors indicated on plans reflecting specification requirements.
PE601 (See attached sheet)
1. Fixture specifications for Urinal ‘UR’ and sink “SS-1” added to plumbing fixture schedule. 2. Superfluous fixtures removed.
EP101 & EP601 (See attached sheets)
1. Provide electrical connection to new in-line exhaust fan. 2. Refer to updated mechanical equipment schedule.
End
T
T
A B C D
1
3
4
2
5
MECHANICAL
A111
ELECTRICAL
A112 STAR DRESSING
A109
OFFICE
A110
STAGING
STORAGE RIGHT
A102
SECURE
STORAGE
A103
CONCESSIONS
A128
MEN'S
A118
UNISEX
A120
STORAGE
A124
MOP
A122WOMENS
A116
IT
A113
STAGING
STORAGE LEFT
A114
STAR WC
A108
MEN'S
A131
WOMEN'S
A130
CROSSOVER
A105
CUSTODIAL
A104
UNISEX
A106A
WC 2
A107
DRESSING
A107A
GREEN ROOM
A106
PLATFORM
A101
MH101
2
(E)18"ø
(E)16"ø(E)16"ø
FCU-1
CU-1
C D
1
2
SECURE
STORAGE
A103
STAR WC
A108
MEN'S
A131
WOMEN'S
A130
CUSTODIAL
A104
UNISEX
A106A
WC 2
A107
DRESSING
A107A
GREEN ROOM
A106
(E)6
"ø
(E)6
"ø
(E)6
"ø
(E)8"ø(E)16"ø
(E)8
"ø
(E)6
"ø
(E)6
"ø
(E)6
"ø
(E)CEF-4(E)CEF-3 (E)CEF-2
(E)CEF-1
(E)CD145
(E)CD75
(E)CD95
(E)CD95
(E)14"ø
8"ø
8"ø
6"ø EA
14"x
12"
12"ø 12"ø
CD425
CD425
8"x8"
CG510
24"x
12"
CU-1
12"x
12"
18"x12"
1
6"ø
CD75
CD110
10"x8"
8"øFCU-1
L-1
2
(E)4"ø
(E)4
"ø
(E)4"ø
(E)4
"ø
(E)4
"ø
3
3
3 3
3
4
4
4
5
EF-1
EF-2
EF-3
IEF-46
74"ø
4"ø
4"ø
4"ø
7
4"ø
4"ø
4"ø
4"ø
4"ø
4 4
4"ø
4"ø
2
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
02.10.20
C:\U
se
rs\a
ra\D
ocum
ents
\20
190
52
9 M
EC
H C
EN
TR
AL
_ara
JW
VZ
G.r
vt
4/7
/20
20 2
:09
:17
PM MH101
MECHANICAL
PLANS
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
SHEET KEYNOTES
1 CONTRACTOR TO PROVIDE ACCESS PANEL AND MERV 8 FILTER.
2 EXISTING RADON EXHAUST FAN.
3 EXISTING PERFORATED PIPING UNDERSLAB CONTINUES THROUGH BUILDING.
4 EXTEND RESTROOM EXHAUST DUCT THROUGH ROOF. PATCH AND SEAL ROOFPER ROOF MANUFACTURER'S WARRANTY REQUIREMENTS.
5 EXTEND FURNACE COMBUSTION AIR AND VENT PIPING TO MANUFACTURER'SCONCENTRIC VENT KIT THROUGH ROOF. PATCH AND SEAL ROOF PENETRATIONPER ROOF MANUFACTURER'S WARRANTY REQUIREMENTS.
6 EXTEND RADON PIPING UP THROUGH WALL TO ABOVE CEILING INLINE FAN (SEEDETAIL).
7 CORRUGATED PERFORATED PVC PIPE BELOW FLOOR.
1/8" = 1'-0"1
STAGE LEVEL MECHANICAL PLAN
1/4" = 1'-0"2
ENLARGED MECHANICAL PLAN
RADON SYSTEM NOTES
1. RADON SYSTEM SHALL MEET ALL THE REQUIREMENTS OF COLORADO DEPARTMENT OF PUBLIC HEATH – URANIUM MILL TAILINGS MANAGEMENT PLAN (MAY 2015).
2. PROVIDE A 4” LAYER OF 1/2“ TO 3/4" CLEAN WASHED GRAVEL UNDER THE FLOOR SLAB.
3. PROVIDE 10 MIL HDPE SHEETING ON TOP OF GRAVEL AND BELOW CONCRETE FLOR SLAB. SHEETING SHALL EXTEND UP THE FOUNDATION WALLS AND SEAL TO WALL.
4. ALL PENETRATIONS THROUGH PLASTIC SHEETING SHALL BE SEALED WITH APPROVE TAPE.
5. UNDERFLOOR PIPING SHALL BE 4” CORRUGATED PERFORATED ADS PIPE. PERFORATED PIPE SHALL HAVE A MINIMUM OF TEN (10) 3/4” DIAMETER PERFORATIONS PER FOOT.
6. VENT PIPE SHALL BE SCHEDULE 40 DWV PVC PIPE.
7. ALL PENETRATIONS THROUGH FLOOR SHALL BE SEALED WITH POLYURETHANE CAULKING.
8. ALL COLD JOINTS IN CONCRETE FLOOR SHALL BE SEALED WITH POLYURETHANE CAULKING.
9. ALL SAWED CUT CONTROL JOINTS SHALL BE SEALED WITH POLYURETHANE CAULKING.
10. EXTEND VENT PIPE A MINIMUM OF 12” ABOVE ROOF. PROVIDE 1/2" BIRD SCREEN OVER OPENING OF PIPE.
11. RADON VENTILATION FAN SHALL BE LOCATE NEAR ROOF.
12. ALL EXPOSED PIPING SHALL BE PROPERLY APPROVED LABELED AS A RADON SYSTEM.
13. INSTALL A RADON U-TUBE MANOMETER ON VERTICAL EXPOSED VENT PIPE.
14. BUILDING SHALL BE RADON TESTED PRIOR TO OCCUPANCY.
2
2 ADD 1 04/08/2020
CEILING DIFFUSER, REGISTER & GRILLE SCHEDULE
SYMBOL DESCRIPTION
SIZES
ACCEPTABLEMANUFACTURERSNOMINAL SIZE
(NECK SIZE)AIR FLOW
(CFM)
CD
CEILING DIFFUSER:REMOVABLE PERFORATED FACEPLATE, 24" X 24" PANEL SIZE, 4-WAY PATTERN, ROUNDNECK, ALUMINUM CONSTRUCTIONNC-35 MAXIMUM, TESTED IN ACCORDANCE WITH ADC TEST 1062,OPTIONS & ACCESSORIES:BAKED ENAMEL WHITE FINISH. PROVIDE CEILING MOUNT TO MATCH CEILING TYPE.
6" DIA.8" DIA.10" DIA.12" DIA.14: DIA.
1202004007001000
KRUEGER 13SDTITUSPRICE
CG
CEILING GRILLE:REMOVABLE PERFORATED FACEPLATE, ALUMINUM, 24" X 24" PANEL SIZE, NC-35 MAXIMUM,TESTED IN ACCORDANCE WITH ADC TEST 1062,ROUND NECK OR SQUARE NECK, SEE DRAWINGS FOR NECK SIZE.OPTIONS & ACCESSORIES:BAKED ENAMEL WHITE FINISH. PROVIDE CEILING MOUNT TO MATCH CEILING TYPE.
6" DIA. (6" X 6")8" DIA. (8" X 8")
10" DIA. (10" X 10")12" DIA. (12" X 12")14: DIA. (14" X 14")
22" X 22"
12020042070010002000
KRUEGER 13SDTITUSPRICE
DUCT INSULATION REQUIREMENTS
DUCT SYSTEM DUCT LOCATION INSULATION MATERIAL
MINIMUM
THERMAL
RESISTANCE
("R")
FIELD APPLIEDJACKET
VAPORRETARDER
REQ'D
SUPPLY AIR
BUILDING INTERIOR, CONCEALED MINERAL-FIBER BLANKET 6.0 NONE NO
BUILDING INTERIOR, EXPOSED, OUTSIDE CONDITIONED SPACE MINERAL-FIBER BLANKET 6.0 NONE NO
BUILDING EXTERIOR (OUTSIDE BUILDING INSULATION) MINERAL-FIBER BLANKET 12.0 ALUMINUM NO
RETURN AIR
BUILDING INTERIOR, CONCEALED MINERAL-FIBER BLANKET 6.0 NONE NO
BUILDING INTERIOR, EXPOSED, OUTSIDE CONDITIONED SPACE MINERAL-FIBER BLANKET 6.0 NONE NO
BUILDING EXTERIOR (OUTSIDE BUILDING INSULATION) MINERAL-FIBER BLANKET 8.0 ALUMINUM NO
EXHAUST AIR ALL NONE --- --- ---
OUTSIDE AIR BUILDING INTERIOR, CONCEALED OR EXPOSED MINERAL-FIBER BLANKET 8.0 NONE NO
NOTES
(1) ALL DUCT INSUL ATION SHALL HAVE ALL SERVICE JACKET MANUFACTURED FROM KRAFT PAPER, REINFORCED SCRIM, ALUMI NUM FOIL OR VINYL FILM.
(2) DUCT INSULATION SHALL BE MECHANICAL FASTENED TO DUCTS WIDER THAN 24" AND SHALL BE AFFIXED TO BOTTOM OF DUCT WITH WELDED METAL PINS AND 2" WAHSERS AT 18" MAXIMUM
SPACING.
(3) DUCT LINER, WHERE SHOWN ON DRAWINGS, SHALL BE A MINIMUM OF 1" THICK AND SHALL HAVE A MINIMUM "R" VALUE OF 6.0.
(4) DUCT LINER SHALL NOT BE SUBSTITUTED FOR DUCT LINER UNLESS THE MINIMUM "R" VALUE OF THE DUCT LINER IS INCREASED TO A MINIMUM OF 6.0.
(5) DUCT DIMENSIONS SHOWN ON THE DRAWINGS ARE NET FREE AREA. WHERE DUCT LINER IS SHOWN, INCREASE METAL DUCT SIZE TO ALLOW FOR THICKNESS OF DUCT LINER.
(6) TOTAL LENGTH OF FLEXIBLE DUCT RUN SHALL NOT EXCEE D 3'-0". EXTEND SHEET METAL DUCT TO WITHIN 3'-0" OF THE AIR INLET OR AIR OUTLET DEVICE.
(7) OFFSET OF FLEXIBLE DUCT SHALL NOT EXCEED ONE-HALF (1/2) OF THE DUCT DIAMETER.
(8) ALL DUCT CHANGES IN DIRECTION SHALL BE MADE WITH RIGID ELBOWS OR OTHER RIGID METAL FITTINGS.
(9) INDOOR DUCT INSULATION AND RELATED MATERIALS SHALL HAVE A FLAME-SPREAD INDEX OF 25 OR LESS, AND SMOKE-DEVELOPED INDEX OF 50 OR LESS WHEN TESTED TO ASTM E 84.
(10) OUTDOOR DUCT INSULATION AND RELATED MATERIALS SHALL HAVE A FLAME-SPREAD INDEX OF 75 OR LESS, AND SMOKE-DEVELOPED INDEX OF 150 OR LESS WHEN TESTED TO ASTM 84.
(11) ALL DUCT COVERINGS AND LININGS SHALL NOT FLAME, GLOW, SMOLDER OR SMOKE WHEN TESTED IN ACCORDANCE WITH ASTM C 411.
(12) ALL MATERIALS USED AS INTERNAL INSULATION AND EXPOSED TO THE AIR STREAM IN DUCTS SHALL BE SHOWN TO BE DURABLE WHEN TESTED IN ACCORDANCE WITH UL 181.
FAN COIL & AC UNIT SCHEDULE
SYMBOL AREA SERVED MANUFACTURER MODEL NO.
BLOWER SECTION CAPACITY ELECTRICAL
SEERDIMENSIONS
(INCHES)NOTES
ARRANGEMENTSUPPLY
AIRFLOW(CFM)
E.S.P.TOTAL
COOLING(BTUH)
TOTALHEATING(BTUH)
MOTOR(HP)
V/PH/HZ
MCA MOCP
FCU-1 GREEN ROOM TRANE TUH1B040-SUB-1E HORIZONTAL 1050 0.5 -- 58,000 0.5 115/1/60 7.9 15 -- 36X19X31 (1-8)
CU-1 GREEN ROOM TRANE 4TWR4018G1000A CURB MOUNT N/A N/A 60,000 -- 0.125 208/3/60 12 20 15 33X32X30 (1-8)
ACCEPTABLE MANUFACTURERS NOTES
STULTZLEIBERTTRANE
(1) COOLING CAPACITY BASED UPON 72°F DB & 30% RH INDOOR & 95°F OUTDOOR DB(2) PROVIDE SINGLE SOURCE POWER OPTION(3) ESTABLISH CONTROL CONNECTION TO BMS TO MONITOR: STATUS, ALARM, ENABLE/DISABLE(4) PROVIDE REPLACEMENT MERV 8 FILTER AND REPLACEMENT FAN BELT WITH UNIT(5) REMOTE PROGRAMMABLE THERMOSTAT(6) ROUTE PRE-CHARGED REFRIGERANT PIPING FROM INDOOR TO OUTDOOR UNIT. PROVIDE UV RESISTIVE JACKET FOR EXPOSED PIPINGINSULATION.(7) CUSTOM FILTER BANK(8) MOUNT CONDENSING UNIT ON 6" CONCRETE PAD. ATTACHED WITH NEOPRENE VIBRATION ISOLATORS.
EXHAUST FAN SCHEDULESYMBOL AREA SERVED MANUFACTURER MODEL NO. CONFIG.
AIR FLOW(CFM)
STATICPRESSURE
(INCHES W.G.)
FANSPEED(RPM)
MOTOR MAXIMUMNOISE LEVEL
(SONES)
WEIGHT(LBS)
OPTIONS ANDACCESSORIES
CONTROLS NOTES / COMMENTSWATTS VOLTS PHASE HERTZ
EF-1 RESTROOM LOREN COOK GC-168 CEILING 150 0.35000 1160 46.1 120 1 60 3.50000 12 (1) (11) (101)
EF-2 RESTROOM LOREN COOK GC-168 CEILING 150 0.35000 1160 46.1 120 1 60 3.50000 12 (1) (11) (101)
EF-3 RESTROOM LOREN COOK GC-128 CEILING 50 0.25000 1160 23.0 120 1 60 3.50000 12 (1) (11) (101)
ACCEPTABLE MANUFACTURERS OPTIONS & ACCESSORIES CONTROLS NOTES & COMMENTS
LOREN COOK, TWIN CITY, PENN VENTILATOR, GREENHECK (1) GRAVITY BACKDRAFT DAMPER. (11) OPERATE DURING OCCUPIED MODE, PROVIDE TIMER. (101) ALL CAPACITIES AT JOB SITE ELEVATION
INLINE EXHAUST FAN (RADON) SCHEDULESYMBOL AREA SERVED
BASIS OF DESIGNMANUFACTURER
BASIS OFDESIGN
MODEL NO.
AIR FLOW(CFM)
STATICPRESSURE
(INCHES W.G.)
FANSPEED(RPM)
MOTOR MAXIMUMNOISE LEVEL
(SONES)
OPTIONS ANDACCESSORIES
CONTROLS NOTES / COMMENTSWATTS VOLTS PHASE HERTZ
IEF-4 RADON SYSTEM FANTECH HP 220 166 1.26 2886 152 120 1 60 10.0 (1)(2) (12) (A)
ACCEPTABLE MANUFACTURER OPTIONS & ACCESSORIES CONTROLS NOTES & COMMENTS
FANTECH (1) BACKDRAFT DAMPER(2) INTEGRAL THERMAL OVERLOAD PROTECTION(3) U-TUBE MANOMETER(4) RADON SYSTEM LABELS
(11) FAN TO RUN CONTINUOUSLY (A) CAPACITY AT JOB SITE ELEVATION.
LOUVER SCHEDULE
SYMBOL MANUFACTURER MODEL NO.OVERALLSIZE (IN.)
L x HTYPE
MINIMUMFREE AREA
(FT^2)CFM
ACCESSORIESAND REMARKS
L-1 RUSKIN ELFD6375 18 x 12 DRAINABLE 0.58 210 (1)(2)(3)
NOTES:
(1) EXTRUDED ALUMINUM CONSTRUCTION(2) GRAVITY BACKDRAFT DAMPER(3) COLOR BY ARCHITECT. PROVIDE FINISH SAMPLE FOR REVIEW
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
02.10.20
C:\U
se
rs\a
ra\D
ocum
ents
\20
190
52
9 M
EC
H C
EN
TR
AL
_ara
JW
VZ
G.r
vt
4/7
/20
20 2
:09
:11
PM ME601
MECHANICAL
SCHEDULES
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
2 ADD 1 04/08/2020
2
A B C D
1
3
4
2
5
MECHANICAL
A111
ELECTRICAL
A112 STAR DRESSING
A109
OFFICE
A110
STAGING
STORAGE RIGHT
A102
SECURE
STORAGE
A103
CONCESSIONS
A128
MEN'S
A118
UNISEX
A120
STORAGE
A124
MOP
A122WOMENS
A116
IT
A113
STAGING
STORAGE LEFT
A114
STAR WC
A108
MEN'S
A131
WOMEN'S
A130
CROSSOVER
A105
CUSTODIAL
A104
UNISEX
A106A
WC 2
A107
DRESSING
A107A
GREEN ROOM
A106
PLATFORM
A101
PL101
2
(E)4"øSS
(E)4"øRW
(E)2"øDCW
C D
1
2
SECURE
STORAGE
A103
STAR WC
A108
MEN'S
A131
WOMEN'S
A130
CUSTODIAL
A104
UNISEX
A106A
WC 2
A107
DRESSING
A107A
GREEN ROOM
A106
(E)4"øSS
(E)4"øRW
(E)2"øDCW
(E)4"øSS
1/2"øDHWR
2"øDCW
3/4"øDHW
FD
FD
(E)4"øSS
FD
SS-1
WCA LAV
LAV
LAV
WC
WC
UR
WCA
WCA
WC
LAV
LAV
FCO
1
2"øV
2"øDCW
1/2"øDHWR
4"øSS
3/4"øDHWR
(E)3"øSS
3/4"øDHW
4"øSS
1/2"øNG
(E)1 1/4"øNG
3"øSRW
3"øRW
3"øSRW
2
3
(E)4"øRW
(E)4"øSRW
(E)4"øRW
4
4
CO
2
2
5
CO
3/4"øDHW
5
3"øSS
2"øDCW
2
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
02.10.20
C:\U
se
rs\a
ra\D
ocum
ents
\20
190
52
9 M
EC
H C
EN
TR
AL
_ara
JW
VZ
G.r
vt
4/7
/20
20 2
:09
:22
PM PL101
PLUMBING
PLANS
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
SHEET KEYNOTES
1 BATHROOM GROUP SERVED BY WET VENT.
2 PRIMARY ROOF DRAIN PIPING UP TO PRIMARY ROOF DRAIN ON ROOF. BASIS OFDESIGN JR SMTIH 1010-AD-R-C. DRAINAGE COVERAGE: 950 SQFT: 20 GPM.EXISTING 4" LINE SERVES 2100 SQFT: 43.6 GPM, TOTAL: 63.6 GPM. MAXIMUMDRAINAGE CAPACITY ON A 4" LINE SLOPING AT 1/8" PER FT: 115 GPM.
3 SECONDARY ROOF DRAIN PIPING UP TO SECONDARY ROOF DRAIN ON ROOF.BASIS OF DESIGN JR SMTIH 1080-AD-R-C. DRAINAGE COVERAGE: 950 SQFT: 20GPM. EXISTING 4" LINE SERVES 2100 SQFT: 43.6 GPM, TOTAL: 63.6 GPM. MAXIMUMDRAINAGE CAPACITY ON A 4" LINE SLOPING AT 1/8" PER FT: 115 GPM.
4 CIRCUIT SETTER. SET AT 0.5 GPM. RECIRCULATION PIPING TO EXTEND TO LEVELOF STOP VALVES.
5 PROVIDE WATER HAMMER ARRESTOR. BASIS OF DESIGN SIOUX CHIEF 652-A FORSINGLE TOILET RESTROOM AND 652-C FOR MULTI TOILET RESTROOM.
1/8" = 1'-0"1
STAGE LEVEL PLUMBING PLAN
1/4" = 1'-0"2
ENLARGED PLUMBING PLAN
2 ADD 1 04/08/2020
2
PLUMBING FIXTURE SCHEDULESYMBOL FIXTURE TRAP WASTE VENT
DOMESTIC
COLD WATER
DOMESTIC
HOT WATERDESCRIPTION
BASIS OF DESIGN
MANUFACTURER AND MODELNOTES
WC WATER CLOSET INT. 3" 2" 1" ---- FLOOR MOUNTED, FLUSH VALVE, VITREOUS CHINA, ELONGATED, 1-1/2" TOP SPUD, 15" RIM HEIGHT, SIPHON JET, 2-1/8"MINIMUM TRAPWAY.DIAPHRAGM TYPE FLUSH VALVE, SENSOR ACTIVATED, DUAL FLUSH, 1.60/1.10 GALLONS PER FLUSH, POLISHEDCHROME PLATED BRASS, BATTERY, COURTESY FLUSH OVERRIDE BUTTON, VACUUM BREAKER.OPEN FRONT SEAT, LESS SEAT, HEAVY DUTY PLASTIC, ELONGATED, STAINLESS STEEL HINGE POSTS..
AMERICAN STANDARD 2234.001
SLOAN 111-1.6/1.1
BEMIS 1955C
MINIMUM MaP RATING = 1,000
WC-A WATER CLOSET(ACCESSIBLE ROOM)
INT. 3" 2" 1" ---- FLOOR MOUNTED, FLUSH VALVE, VITREOUS CHINA, ELONGATED, 1-1/2" TOP SPUD, 16-1/2" RIM HEIGHT, SIPHON JET,2-1/8" MINIMUM TRAPWAY.DIAPHRAGM TYPE FLUSH VALVE, SENSOR ACTIVATED, DUAL FLUSH, 1.60/1.10 GALLONS PER FLUSH, POLISHEDCHROME PLATED BRASS, BATTERY, COURTESY FLUSH OVERRIDE BUTTON, VACUUM BREAKER.OPEN FRONT SEAT, LESS SEAT, HEAVY DUTY PLASTIC, ELONGATED, STAINLESS STEEL HINGE POSTS..
AMERICAN STANDARD 3043.001
SLOAN 111-1.6/1.1
BEMIS 1955C
MINIMUM MaP RATING = 1,000
INSTALL FLUSH VALVE WITH HANDLE ON ACCESSIBLE SIDE
OF WATER CLOSET
UR URINAL (ACCESSIBLE) INT. 2" 2" 1" --- WALL MOUNTED, FLUSHING RIM, WASHOUT, VITREOUS CHINA. 3/4" TOP SPUD.ELECTRONIC, BATTERY POWERED, DIAPHRAGM TYPE FLUSH VALVE, 0.125 GALLON PER FLUSHPOLISHED CHROME PLATED BRASSFLOOR MOUNTED SUPPORT, FLOOR BEARING PLATE, TOP AND BOTTOM BEARING STUDS
KOHLER K-4904-ET
SLOAN ECOS 8186-0.125
J.R. SMITH 0615
SS-1 SINGLE BOWL 1-1/2" 1-1/2" 1-1/2" 1/2" 1/2" FIXTURE: SINGLE COMPARTMENT, 18 GAUGE, 304 STAINLESS STEEL, 19" X 18" X 7.5" BOWL.4" FAUCET LEDGE, SELF RIMMING.FAUCET: GOOSENECK SWING MOUNT, SINGLE HANDLE MIXING FAUCET, WRISTBLADE HANDLES, 8" CENTERSETAERATOR: POLISHED CHROME PLATED LEAD-FREE BRASS, LAMINAR FLOW, 1.5 GPM.DRAINS: STAINLESS STEEL CRUMB CUP STRAINER, REMOVABLE STAINLESS STEEL BASKET, 4" LONG TAILPIECE,CHROME PLATE BRASS CONDENSATE DRAIN TAILPIECE.TRAP: WHITE POLYVINYL CHLORIDE (PVC).STOPS: 1/2" I.P.S. X 3/8" O.D. COMPRESSION, POLISHED CHROME PLATED HEAVY PATTERN LEAD FREE BRASS ANGLEBALL VALVE.SUPPLIES: PEX TUBING, FORMED WITH FLANGE, RUBBER WASHER OR GASKET PLASTIC COMPRESSION SLEEVE,ASTM A112.18.6, ASTM F877.
ELKAY DSESR127224
ELKAY LK810GN05T6
OMIN A-400-05-LF
DEARBORN 701-1
POWERS LFe480-11
BRASSCRAFT KTCR19XC
BRASSCRAFT 1-15 C
INSINKERATOR BADGER '5'
CONFIRM CABINET SIZE PRIOR TO ORDER
LAV LAVATORY(ACCESSIBLE)
1-1/4" 1-1/2" 1-1/2" 1/2" 1/2" WALL MOUNTED, 20" x 18", VITREOUS CHING, ADA ACCEPTABLE, FAUCET LEDGE, 4" CENTER FAUCET HOLES.SINGLE LEVER FAUCET, CHROME PLATED LEAD FREE BRASS, CERAMIC COMPONENTS, DECK PLATE.LAMINAR FLOW AERATOR, POLISHED CHROME PLATED LEAD FREE BRASS, 0.5 GPM.COMBINATION TEMPERATURE & PRESSURE MIXING VALVE, CHROME PLATED LEAD FREE BRASS. INTEGRAL CHECKS,ASSE 1070 LISTED,CHROME PLATED BRASS GRID DRAIN,CHROME PLATED BRASS TAILPIECE, OFFSET TAILPIECEWHITE POLYVINYL CHLORIDE (PVC) TRAPANGLE BALL VALVE STOP, HEAVY DUTY, POLISHED CHROME PLATED LEAD FREE BRASS, 1/2" IPS x 3/8" O.D.COMPRESSION.POLISHED CHROME PLATED COPPER TUBING SUPPLY, 3/8" O.D, FORMED NOSEPIECE WITH FLANGE, WATER WASHEROR GASKET, COMPRESSION SLEEVE, ASTM A112.18.6.ENCLOSURE: RIGID POLYVINYL CHLORIDE ENCLOSURE, ADA ACCESSIBLE UL LISTEDSUPPORT: CONCEALED ARM, FLOOR MOUNTED, NARROW WALL, TUBULAR STEEL VERTICAL SUPPORTS, STEELFLOOR PLATES.
AMERICAN STANDARD 0355.012
SYMMONS SLS-2010OMIN A-400-05-LFPOWERS LFe480
MCQUIRE 155A
DEARBORN 9701-1
BRASSCRAFT KTCR19XC
BRASSCRAFT 1-15 C
TRUEBRO "LAV SHIELD" 2018
J.R. SMITH 0710-Z
SET DISCHARGE WATER TEMPERATURE AT 110 F.
PLUMBING FIXTURE SCHEDULE (CLEANOUTS)SYMBOL FIXTURE TRAP WASTE VENT
DOMESTICCOLD
WATER
DOMESTICHOT
WATERDESCRIPTION
BASIS OF DESIGNMANUFACTURER AND MODEL
NOTES
CO CLEANOUT --- SAME AS PIPE --- --- --- CAST IRON BLIND PLUG CHARLOTTE PIPE NH-50
FCO FLOOR CLEANOUT --- SAME AS PIPE --- --- --- HEAVY DUTY NICKEL BRONZE TOP, BRASS PLUG J. R. SMITH 4113S-NB
COTG CLEANOUT TO GRADE --- SAME AS PIPE --- --- --- HEAVY DUTY NICKEL BRONZE TOP, BRASS PLUG J. R. SMITH 4113S-NB
WCO WALL CLEANOUT --- SAME AS PIPE --- --- --- ROUND FLAT STAINLESS STEEL WALL PLATE J.R. SMITH 4532S
PLUMBING FIXTURE SCHEDULE (DRAINS)SYMBOL FIXTURE TRAP WASTE VENT
DOMESTICCOLD
WATER
DOMESTICHOT
WATERDESCRIPTION
BASIS OF DESIGNMANUFACTURER AND MODEL
NOTES
FD FLOOR DRAIN 2" 2" 2" --- --- LACQUER COATED CAST IRON BODY FLOOR DRAIN, FLASHING COLLAR,5" ROUND NICKEL BRONZE ADJUSTABLE STRAINER3.5" BARRIER TYPE TRAP PRIMER, ABS, NEOPRENE RUBBER DIAPHRAGM, ASSE STANDARD 1072-AF-GWDEEP SEAL P-TRAP
J. R. SMITH 2010-5AJ.R. SMITH 5A
SURESEAL SS 3509 INSTALL TRAP SEAL BEHIND STRAINER FACE
RD-4 ROOF DRAIN ---- 3" --- --- --- LACQUER COATED CAST IRON BODY,COMBINED FLASHING CLAMP AND GRAVEL STOP, SUMP RECEIVER, UNDERDECKCLAMP.
J. R. SMITH 1010-AD-R-C 3,760 SQ. FT. CAPACITY AT 2" PER HOUR RAINFALL AND1/8" PER FOOT SLOPE.
SRD-4 SECONDARY ROOF DRAIN --- 3" --- --- --- LACQUER COATED CAST IRON BODY,COMBINED FLASHING CLAMP AND GRAVEL STOP, 2" WATER DAM, SUMPRECEIVER, UNDERDECK CLAMP.
J. R. SMITH 1080-AD-R-C 3,760 SQ. FT. CAPACITY AT 2" PER HOUR RAINFALL AND1/8" PER FOOT SLOPE.
DSN-4 DOWNSPOUT NOZZLE --- 3" --- --- --- CAST BRONZE NOZZLE AND FLANGE J.R. SMITH 1771
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
02.10.20
C:\U
se
rs\a
ra\D
ocum
ents
\20
190
52
9 M
EC
H C
EN
TR
AL
_ara
JW
VZ
G.r
vt
4/7
/20
20 2
:09
:17
PM PE601
PLUMBING
SCHEDULES
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
2 ADD 1 04/08/2020
2
J
J
ST
ST
ST
ST
STST
ST
STST
ST
ST ST
J
J
JJ
J
J
JJ
J
J
ST
JJ
JJ
ST
STST
ST
W
W
W
W
W
W W
W
W
W
W
W
DF
W
W W W W W
W
A A A
"A""B"
"C""MDP"
400A200A
"CR"
MECHANICAL
A111
STAR WC
A108ELECTRICAL
A112
IT
A113
STAGING
STORAGE
LEFT
A114
GREEN
ROOM
A106
WC 2
A107STAR
DRESSING
A109
CUSTODIAL
A104OFFICE
A110
CROSSOVER
A105
STAGING
STORAGE
RIGHT
A102
SECURE
STORAGE
A103
PLATFORM
A101
UNISEX
A120
STORAGE
A124
MOP
A122
CONCESSIONS
A128
WOMENS
A116
MEN'S
A118
A
A
A
(ON ROOF)
UNISEX
A106A
DRESSING
A107A
MEN'S
A131
WOMEN'S
A130
5
4
3
2
1
A B C D
CEF-X1C-56
CEF-X2C-56
CEF-X3C-58
CU-1B-32,34,36
A
A
A
A
A
A
C- 46
C- 58
C- 56
C- 48
C- 50
C- 52
C- 54
1
1
1
1
1
C- 70
C- 60
C- 62
C- 64
C- 68
C- 66
FCU-1B-38
IEF-4C-60
1
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
E:\A
uto
de
sk\2
019
\20
19
052
9 E
LE
C C
EN
TR
AL
_td
s_
spe
ctr
um
-en
gin
ee
rs_co
m.r
vt
4/7
/20
20 1
:29
:11
PM EP101
STAGE LEVEL
POWER PLAN
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
GENERAL SHEET NOTES
SHEET KEYNOTES1 PROVIDE ELECTRICAL CONNECTIONS TO ELECTRIC HAND DRYERS. CIRCUIT WITH
2#10, #10G IN 0.75" CND. COORDINATE EXACT LOCATION AND REQUIREMENTS WITHTHE INSTALLERS PRIOR TO ROUGH-IN.
SCALE: 1/8" = 1'-0"1STAGE LEVEL POWER PLAN
1 ADD #01 4/7/2020
324 S. State St., Suite 400Salt Lake City, UT 84111
800-678-7077801-328-5151
fax: 801-328-5155www.spectrum-engineers.com
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
E:\A
uto
de
sk\2
019
\20
19
052
9 E
LE
C C
EN
TR
AL
_td
s_
spe
ctr
um
-en
gin
ee
rs_co
m.r
vt
4/7
/20
20 1
:29
:11
PM EP601
ELECTRICAL
SCHEDULES
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
EQUIPMENT SCHEDULEEQUIPMENT SCHEDULE KEY
E
Q
*
**
-
-
-
-
DIVISION 26
FURNISHED WITH EQUIPMENT
COORDINATE WITH THE DIVISION 23 TEMPERATURE CONTROL INSTALLER
AUTOMATIC CONTROL WIRING BY DIVISION 23
xxxxxxxx
MARK QTY ITEM DESCRIPTION
LOAD DATA
WIRE ANDCONDUIT SIZE
OVERCURRENTPROTECTION DISCONNECT STARTER
NOTES MARKHP kW MCA FLAVOL
T PH HzFURN
BY DEVICE LOCATIONFURN
BY DEVICE LOCATIONFURN
BY DEVICE SIZESSELECTOR
SWITCHPILOTLAMP
NORMALLYOPEN
CONTACT
NORMALLYCLOSED
CONTACT
PHASEFAILURERELAY
CEF-X1 1 CEILING EXHAUST FAN 1/6 - - 1 120 1 60 2 #12, #12 GR0.75" CND
E 20/1CB
C E TOGGLESWITCH
ADJ TOEQUIP
Q - - - - - - - CEF-X1
CEF-X2 1 CEILING EXHAUST FAN 1/6 - - 1 120 1 60 2 #12, #12 GR0.75" CND
E 20/1CB
C E TOGGLESWITCH
ADJ TOEQUIP
Q - - - - - - - CEF-X2
CEF-X3 1 CEILING EXHAUST FAN 1/6 - - 1 120 1 60 2 #12, #12 GR0.75" CND
E 20/1CB
C E TOGGLESWITCH
ADJ TOEQUIP
Q - - - - - - - CEF-X3
CU-1 1 CONDENSING UNIT - - 12 12 208 3 60 3 #10, #10 GR0.75" CND
E 30/3CB
B E 30A/3PFRS-20
ADJ TOEQUIP
Q - - - - - - - CU-1
FCU-1 1 FAN COIL UNIT - - - 7.9 120 1 60 2 #12, #12 GR0.75" CND
E 15/1CB
B E TOGGLESWITCH
ADJ TOEQUIP
Q - - - - - - - FCU-1
IEF-4 1 INLINE EXHAUST FAN 1/6 - - 1 120 1 60 2 #12, #12 GR0.75" CND
E 20/1CB
C E TOGGLESWITCH
ADJ TOEQUIP
Q - - - - - - - IEF-4
ALL OTHER LOADS @ 100% : 25.7 kVA -MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITHLARGEST MOTOR CALCULATED @ 125% PER NEC
RECEPTACLES: 12.2 kVA @ 91% = 11.1 kVA - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 102
LIGHTING & CONTINUOUS LOADS: - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 37
NEC DIVERSIFIED LOAD CALCULATIONS
CONNECTED AMPS PER PHASE 109 110 99 AVERAGE CONNECTED AMPS PER PHASE = 105
TOTALS: CONNECTED kVA PER PHASE 13 13 12 CONNECTED TOTAL kVA = 38
41 20 1 -- -- -- SPARE 0.0 6.7 -- -- -- -- -- -- 42
39 20 1 0.0 0.0 0.2 PWR: CONCESSIONS A128 0.2 6.7 -- -- -- -- -- -- 40
37 20 1 0.0 0.0 0.2 PWR: CONCESSIONS A128 0.2 6.7 PWR: ADA LIFT 0.0 20.0 0.0 3 100 38
35 20 1 0.0 0.0 0.9 PWR: STRG/CONCESSIONS A128 0.9 0.2 PWR: HAND DRYER 0.0 0.2 0.0 1 30 36
33 20 1 0.0 0.0 0.4 CO ROOM A120, A122 0.4 0.2 PWR: HAND DRYER 0.0 0.2 0.0 1 30 34
31 20 1 0.0 0.0 0.4 CO Room A118 0.4 0.2 PWR: HAND DRYER 0.0 0.2 0.0 1 30 32
29 20 1 0.0 0.0 0.2 CO ELECTRICAL A112 0.2 0.2 PWR: HAND DRYER 0.0 0.2 0.0 1 30 30
27 20 1 0.0 0.0 0.4 CO IT A113 0.4 0.2 PWR: HAND DRYER 0.0 0.2 0.0 1 30 28
25 20 1 0.0 0.0 0.4 CO IT A113 0.4 0.2 PWR: HAND DRYER 0.0 0.2 0.0 1 30 26
23 20 1 0.0 0.0 0.2 CO: IT A113 0.2 0.2 PWR: HAND DRYER 0.0 0.2 0.0 1 30 24
21 20 1 0.0 0.1 0.2 CO Room A106, A107 0.3 1.5 PWR: HAND DRYER 0.0 1.5 0.0 1 30 22
19 20 1 0.0 0.1 0.2 CO STAR WC A108 0.3 1.5 PWR: HAND DRYER 0.0 1.5 0.0 1 30 20
17 20 1 0.0 0.0 0.2 CO STAR DRESSING A109 0.2 0.3 -- -- -- -- -- -- 18
15 20 1 0.0 0.0 0.2 CO STAR DRESSING A109 0.2 0.3 -- -- -- -- -- -- 16
13 20 1 0.0 0.0 0.2 CO STAR DRESSING A109 0.2 0.3 PWR: OH DOOR 0.0 1.0 0.0 3 20 14
11 20 1 0.0 0.0 0.7 CO STAR DRESSING A109 0.7 0.5 CO: OUTSIDE STAGE RIGHT 0.5 0.0 0.0 1 20 12
9 20 1 0.0 0.1 0.9 CO Room A104, A103, A110, A111 1.0 0.5 CO: OUTSIDE STAGE FRONT RIGHT 0.5 0.0 0.0 1 20 10
7 20 1 0.0 0.0 0.7 CO STAGE RIGHT A102 0.7 0.5 CO: OUTSIDE STAGE FRONT LEFT 0.5 0.0 0.0 1 20 8
5 20 1 0.0 0.0 0.9 CO Room A102, A105, A114 0.9 0.7 CO STAGE A101 0.7 0.0 0.0 1 20 6
3 20 1 0.0 0.0 0.7 CO STAGE RIGHT A102 0.7 0.5 CO STAGE A101 0.5 0.0 0.0 1 20 4
1 20 1 0.0 0.0 0.9 CO STAGE LEFT A114 0.9 0.5 CO: OUTSIDE STAGE LEFT 0.5 0.0 0.0 1 20 2
NO AMP POLE LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG POLE AMP NO
CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT
ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING:
120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 225 AMPERE ELECTRICAL A112 SURFACE
VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: LOCATION: CABINET: NOTES:
PANEL: "A"
ALL OTHER LOADS @ 100% : 31.2 kVA -MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITHLARGEST MOTOR CALCULATED @ 125% PER NEC
RECEPTACLES: - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 103
LIGHTING & CONTINUOUS LOADS: 4.9 kVA @ 125% = 6.1 kVA - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 37
NEC DIVERSIFIED LOAD CALCULATIONS
CONNECTED AMPS PER PHASE 114 89 88 AVERAGE CONNECTED AMPS PER PHASE = 97
TOTALS: CONNECTED kVA PER PHASE 14 11 11 CONNECTED TOTAL kVA = 35
41 -- -- -- -- -- -- 0.3 0.1 PWR: DCP-1 0.0 0.1 0.0 1 20 42
39 20 2 0.0 0.7 0.0 PWR: AC-1b 0.3 0.1 PWR: WH-1 0.0 0.1 0.0 1 20 40
37 -- -- -- -- -- -- 1.6 1.0 PWR: FCU-1 0.0 1.0 0.0 1 15 38
35 30 2 0.0 3.1 0.0 PWR: AC-1a 1.6 1.4 -- -- -- -- -- -- 36
33 20 1 0.0 0.4 0.0 PWR: EF-2 0.4 1.4 -- -- -- -- -- -- 34
31 20 1 0.0 0.4 0.0 PWR: EF-1 0.4 1.4 PWR: CU-1 0.0 4.3 0.0 3 30 32
29 -- -- -- -- -- -- 0.6 0.0 SPARE -- -- -- 1 20 30
27 -- -- -- -- -- -- 0.6 0.0 SPARE -- -- -- 1 20 28
25 20 3 0.0 1.8 0.0 PWR: ERV-1 0.6 0.0 SPARE -- -- -- 1 20 26
23 20 1 0.0 0.5 0.0 PWR: F-4 0.5 0.0 SPARE -- -- -- 1 20 24
21 -- -- -- -- -- -- 2.3 0.0 SPARE -- -- -- 1 20 22
19 50 2 0.0 4.6 0.0 PWR: CU-4 2.3 0.0 SPARE -- -- -- 1 20 20
17 -- -- -- -- -- -- 1.8 0.0 SPARE -- -- -- 1 20 18
15 50 2 0.0 3.6 0.0 PWR: CU-3 1.8 0.0 SPARE -- -- -- 1 20 16
13 -- -- -- -- -- -- 2.3 0.0 SPARE -- -- -- 1 20 14
11 50 2 0.0 4.6 0.0 PWR: CU-2 2.3 0.5 LTG: STAGE HOUSE LIGHTS 0.0 0.0 0.5 1 20 12
9 -- -- -- -- -- -- 1.8 0.3 LTG: EXTERIOR 0.0 0.0 0.3 1 20 10
7 50 2 0.0 3.6 0.0 PWR: CU-1 1.8 0.9 LTG: RESTROOMS 0.0 0.0 0.9 1 20 8
5 20 1 0.0 0.5 0.0 PWR: F-3 0.5 1.0 LTG: ROOMS A106, A106A, A107A 0.0 0.0 1.0 1 20 6
3 20 1 0.0 0.5 0.0 PWR: F-2 0.5 1.2 LTG: ELEC/MECH 0.0 0.0 1.2 1 20 4
1 20 1 0.0 0.5 0.0 PWR: F-1 0.5 1.0 LTG: CORRIDOR 0.0 0.0 1.0 1 20 2
NO AMP POLE LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG POLE AMP NO
CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT
ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING:
120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 225 AMPERE ELECTRICAL A112 SURFACE
VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: LOCATION: CABINET: NOTES:
PANEL: "B"
ALL OTHER LOADS @ 100% : 10.7 kVA -MOTOR TOTALS INCLUDED IN ALL OTHER LOADS WITHLARGEST MOTOR CALCULATED @ 125% PER NEC
RECEPTACLES: 1.9 kVA @ 100% = 1.9 kVA - FIRST 10kVA @ 100%, REMAINDER @ 50% AVERAGE AMPS PER PHASE = 81
LIGHTING & CONTINUOUS LOADS: 13.2 kVA @ 125% = 16.5 kVA - 100% CONNECTED LOAD PLUS 25% DIVERSIFIED TOTAL kVA = 29
NEC DIVERSIFIED LOAD CALCULATIONS
CONNECTED AMPS PER PHASE 71 72 71 AVERAGE CONNECTED AMPS PER PHASE = 72
TOTALS: CONNECTED kVA PER PHASE 9 9 9 CONNECTED TOTAL kVA = 26
83 -- -- -- -- -- -- 0.1 0.1 -- -- -- -- -- -- 84
81 -- -- -- -- -- -- 0.1 0.1 -- -- -- -- -- -- 82
79 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.1 PWR: OUTDOOR... 0.0 0.2 0.0 3 40 80
77 -- -- -- -- -- -- 0.1 0.0 SPARE -- -- -- 1 20 78
75 -- -- -- -- -- -- 0.1 0.0 SPARE -- -- -- 1 20 76
73 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.0 SPARE -- -- -- 1 20 74
71 -- -- -- -- -- -- 0.1 0.0 SPARE -- -- -- 1 20 72
69 -- -- -- -- -- -- 0.1 0.2 CO: GREEN ROOM A106 0.2 0.0 0.0 1 20 70
67 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.2 CO: GREEN ROOM A106 0.2 0.0 0.0 1 20 68
65 -- -- -- -- -- -- 0.1 0.2 CO: GREEN ROOM A106 0.2 0.0 0.0 1 20 66
63 -- -- -- -- -- -- 0.1 0.2 CO: GREEN ROOM A106 0.2 0.0 0.0 1 20 64
61 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.2 CO: GREEN ROOM A106 0.2 0.0 0.0 1 20 62
59 -- -- -- -- -- -- 0.1 0.6 CO: GREEN ROOM A106 0.5 0.1 0.0 1 20 60
57 -- -- -- -- -- -- 0.1 0.3 CO: UNISEX A106A 0.2 0.1 0.0 1 20 58
55 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.6 CO: ROOM A130, A131 0.4 0.2 0.0 1 20 56
53 -- -- -- -- -- -- 0.1 1.5 PWR: HAND DRYER 0.0 1.5 0.0 1 20 54
51 -- -- -- -- -- -- 0.1 1.5 PWR: HAND DRYER 0.0 1.5 0.0 1 20 52
49 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 1.5 PWR: HAND DRYER 0.0 1.5 0.0 1 20 50
47 -- -- -- -- -- -- 0.1 1.5 PWR: HAND DRYER 0.0 1.5 0.0 1 20 48
45 -- -- -- -- -- -- 0.1 1.5 PWR: HAND DRYER 0.0 1.5 0.0 1 20 46
43 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 1.2 -- -- -- -- -- -- 44
41 -- -- -- -- -- -- 0.1 1.2 CR11 0.0 0.0 2.4 2 20 42
39 -- -- -- -- -- -- 0.1 1.2 -- -- -- -- -- -- 40
37 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 1.2 CR10 0.0 0.0 2.4 2 20 38
35 -- -- -- -- -- -- 0.1 0.9 -- -- -- -- -- -- 36
33 -- -- -- -- -- -- 0.1 0.9 CR9 0.0 0.0 1.8 2 20 34
31 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.9 -- -- -- -- -- -- 32
29 -- -- -- -- -- -- 0.1 0.9 CR8 0.0 0.0 1.8 2 20 30
27 -- -- -- -- -- -- 0.1 0.5 -- -- -- -- -- -- 28
25 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.5 CR7 0.0 0.0 1.0 2 20 26
23 -- -- -- -- -- -- 0.1 0.3 -- -- -- -- -- -- 24
21 -- -- -- -- -- -- 0.1 0.3 CR6 0.0 0.0 0.6 2 20 22
19 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.0 SPARE -- -- -- 1 20 20
17 -- -- -- -- -- -- 0.1 0.0 SPARE -- -- -- 1 20 18
15 -- -- -- -- -- -- 0.1 0.6 -- -- -- -- -- -- 16
13 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.6 CR4 0.0 0.0 1.2 2 20 14
11 -- -- -- -- -- -- 0.1 0.2 -- -- -- -- -- -- 12
9 -- -- -- -- -- -- 0.1 0.2 CR3 0.0 0.0 0.4 2 20 10
7 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.4 -- -- -- -- -- -- 8
5 -- -- -- -- -- -- 0.1 0.4 CR2 0.0 0.0 0.8 2 20 6
3 -- -- -- -- -- -- 0.1 0.4 -- -- -- -- -- -- 4
1 40 3 0.0 0.2 0.0 PWR: OUTDOOR... 0.1 0.4 CR1 0.0 0.0 0.8 2 20 2
NO AMP POLE LTG PWR CO DESCRIPTION A B C DESCRIPTION CO PWR LTG POLE AMP NO
CKT OCP LOAD (kVA) PHASE LOAD LOAD (kVA) OCP CKT
ACCESSORIES: PANEL DIRECTORY, IDENTIFICATION, GROUNDING BAR AIC RATING:
120/208V, 3 PH 4 WIRE 22" W x 6" D, BOLT-ON 225 AMPERE ELECTRICAL A112 SURFACE
VOLTS/PHASE/WIRE: PANEL SIZE & TYPE: MAIN SIZE AND TYPE: LOCATION: CABINET: NOTES:
PANEL: "C"
1 ADD #01 4/7/2020
1
C
1
2
2' - 10" 5' - 4 3/4" 5' - 5" 7 5/8"
04.0904.10
22.1622.16
10.2810.2810.2810.2810.29
09.09
26.11
23.02
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
AD101
Demolition
Plan
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
3/8" = 1'-0"A3 Enlarged Demolition Floor Plan
N
Keynote Legend
04.09 REMOVE CMU BLOCK ACCORDING TO DIMENSION SHOWN.REMOVE TO A HEIGHT OF 10'-0" ABOVE STAGE LEVEL.
04.10 REMOVE CMU BLOCK ACCORDING TO DIMENSION SHOWN.REMOVE TO A HEIGHT OF 7'-4" ABOVE STAGE LEVEL.
09.09 REMOVE EXISTING GRID CEILING IN THIS ROOM
10.28 REMOVE RESTROOM ACCESSORIES AND PATCH/REPAIRWALL AS REQUIRED
10.29 REMOVE HAND DRYER AND RELOCATE NEAR SHOWER. SEENEW FLOOR PLAN
22.16 REMOVE PLUMBING FIXTURES, CAP PLUMBING LINES ANDREPAIR DRYWALL
23.02 CONTRACTOR TO VERIFY LOCATIONS AND SIZES OFEXISTING PIPING, DUCTWORK, AND PLUMBING SYSTEMSFOR TIE INS. MINOR MODIFICATIONS ARE ANTICIPATED,CONTRACTOR TO MAKE THESE ADJUSTMENTSACCORDINGLY
26.11 EXISTING ELECTRICAL DEVICES AND EQUIPMENT IN THISAREA ARE TO BE REMOVED INCLUDING LIGHT FIXTURE,SWITCH, SENSOR, DUPLEX RECEPTACLE AND EXHAUST FANCONNECTION. REMOVE DEVICES AND CAP EXISTING BOXESTHAT REMAIN. MAINTAIN EXISTING CIRCUITING TO DEVICESAND CIRCUITS THAT REMAIN.
GENERAL NOTES - DEMOLITION
CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS, MATERIALS, FINISHES AND DIMENSIONS BEFORE AND AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT IF ANY UNFORESEEN CONDITIONS OCCUR.
CONTRACTOR SHALL PROTECT EXISTING STRUCTURE, ASSEMBLIES AND EQUIPMENT AS REQUIRED FROM DEMOLITION WORK. REPAIR, PATCH AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW CONSTRUCTION.
THE CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS, SOFFITS, ETC. AS REQUIRED IN THOSE AREAS NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS, BUT THAT ARE EFFECTED BY CONSTRUCTION.
CONTRACTOR TO PATCH/REPAIR ALL AREAS RESULTING FROM DEMOLITION AND PREPARE SUCH SURFACES TO RECEIVE SCHEDULED FINISHES.
REFER TO MECHANICAL, PLUMBING & ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION.
CONTRACTOR SHALL PROVIDE A 6 MIL. POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS & OBSTRUCTIONS AT ALL TIMES.
UPON COMPLETION OF CONSTRUCTION IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS AFFECTED BY CONSTRUCTION. THE GENERAL CONTACTOR SHALL CLEAN ALL FLOORING, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES, CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC.
CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY & EGRESS ROUTES FREE OF OBSTRUCTION AT ALL TIMES THROUGHOUT THE PROJECT.
CONTRACTOR TO PREVENT WATER BUILD UP AND/OR DAMAGE TO FOUNDATIONS ON THE CONSTRUCTION SITE OR ADJACENT AREAS.
1
1 Bid Addendum 01 4-7-20
4"
5/8
"
BOND BEAM PER STRUCTURAL
THRESHOLDPER HARDWARE SETS
BULLNOSE BLOCK AT DOOR JAMB & HEAD
JAMB ANCHOR
GROUT FULL
PLAN
SECTION
GROUT FULL
SCHEDULED DOOR
SEALANT AND BACKER ROD (BOTH SIDES)
6"
6"
HOLLOW METAL FRAME, PAINTED
SCHEDULED DOOR
HOLLOW METAL FRAME BEYOND
DOUBLE WOOD STUD HEADER, PROVIDE (2) WOOD STUDS AT DOOR TYP.
THRESHOLDPER HARDWARE SETS
PLAN
SECTION
SCHEDULED DOOR
HOLLOW METAL FRAME, PAINTED
GYP. BOARD (PAINTED)
HOLLOW METALFRAME (BEYOND)
HOLLOW METALDOOR (PAINTED)
HOLLOW METAL FRAME (PAINTED).
7 3/4"
1/2" 1/2"
SCHEDULED WALL
SCHEDULED WALL
AHM PAINTEDPNT-5
SEE SCHED
SE
E S
CH
ED
SOLID CORE WOOD
SE
E S
CH
ED
SEE SCHED
B
HM Painted Frame, PNT-5
2" 3' - 0" 2" 2" 3' - 0" 2"
4"
7' -
0"
HM Painted Frame,PNT-5
2"
7' -
0"
1 2
GYP BOARD
CORNER BEAD
METAL STUD WALL
STOREFRONT WINDOW SYSTEM
GLAZING, RE: SCHEDULE & WINDOW TYPES
BACKER ROD & SEALANT
SCHEDULED CMU WALL
BLOCKING
1/4"
STOREFRONT WINDOW SYSTEM
GLAZING, RE: SCHEDULE & WINDOW TYPES
BACKER ROD & SEALANT
CORNER BEAD
GYP BOARD
SCHEDULED CMU WALL
STUD WALL
BLOCKING4
' -
8"
8' - 0"
A2
AE601
Sim
B2
AE601
Sim
4' -
8"
6' - 0"
A2
AE601
Sim
B2
AE601
Sim
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
p h o n e : (8 0 1) 5 3 2 - 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS NOT INTENDED
FOR CONSTRUCTION, RECORDING PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS & MODELS
THEREOF, ARE PROPRIETARY & CAN NOT BE COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS WRITTEN PERMISSION FROM METHOD STUDIO
INC.
consultant:
project:
d
c
b
a
d
c
b
a
1 2 3 4 5
1 2 3 4 5
AE601
Door/Window
Schedules &
Types
19.0270February 10, 2020
Grand Junction, CO
LAS COLONIAS
AMPHITHEATER -
ADDITION
PERMIT SET
DOOR SCHEDULE
Door Frame
FrameMaterial Head Jamb Sill Fire Rating
HardwareSet CommentsNumber Width Height Thickness Type Door Material Door Finish
FrameType
FrameFinish
106 3' - 0" 7' - 0" 1 3/4" A HM PAINT 2 PAINT HM A3/A601 A3/A601 A3/A601 - 01
106A 3' - 0" 7' - 0" 1 3/4" A HM PAINT 2 PAINT HM A3/A601 A3/A601 A3/A601 - 04
107A 3' - 0" 7' - 0" 1 3/4" B SOLID CORE WOOD STAINED - - - - - - - 02
130 3' - 0" 7' - 0" 1 3/4" A HM PAINT 1 PAINT HM A4/A601 A4/A601 A4/A601 - 03
131 3' - 0" 7' - 0" 1 3/4" A HM PAINT 1 PAINT HM A4/A601 A4/A601 A4/A601 - 03
1 1/2" = 1'-0"A4
Typical HM Door @ CMU1 1/2" = 1'-0"
A3Typical HM Interior Door
1/4" = 1'-0"
Door Type1/4" = 1'-0"
Frame Type
1 Bid Addendum 01 4-7-20
1 1/2" = 1'-0"A2
Storefront Sill Detail
1 1/2" = 1'-0"B2
Storefront Header Detail
1/4" = 1'-0"C3
SF01 Glazing Type1/4" = 1'-0"
C2SF02 Glazing Type
1