Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
The results in this report only apply to the specimen that was tested Page 1 of 103
CONSTRUCTION
Acoustic Testing of CLT and Glulam Floor Assemblies
Nordic Engineered Wood Report No. A1-008253.1 19 August 2016
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 2 of 101
This page was
intentionally
left blank
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 3 of 101
Table of Contents
Summary ................................................................................................................................................................. 4
Summary Table of Full Floor Assemblies ................................................................................................................ 5
Summary Table of Flooring Patches Tested on Floor Assemblies ......................................................................... 8
Analysis ................................................................................................................................................................... 9
Bare CLT vs. bare glulam ........................................................................................................................... 9
Same toppings on CLT and glulam .......................................................................................................... 10
Precast concrete toppings vs. dry toppings .............................................................................................. 11
Precast concrete toppings vs. OSB raft topping vs. OSB raft topping with concrete topping .................. 12
Floor patches – improving impact ratings ................................................................................................. 13
Other Considerations ............................................................................................................................................. 14
Standard Test Reports........................................................................................................................................... 16
APPENDIX: ASTM E90-09 .................................................................................................................................. 100
APPENDIX: ASTM E492-09 ................................................................................................................................ 101
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 4 of 101
Summary
This report contains the transmission loss (TL) results measured in accordance with ASTM E90-09 and the normalized impact sound pressure level (NISPL) results measured in accordance with ASTM E492-09 of 13 cross-laminated timber (CLT) floor assemblies and 5 glulam floor assemblies. The report also contains the non-standard impact sound pressure level results measured on 6 different small patch specimens.
Summary tables containing the specimen number, sketch, short description, the sound transmission class (STC) and impact isolation class (IIC) ratings, as well as, the page number of the detailed test reports are provided starting on page 5.
A brief analysis of the floors tested as part of this test series is provided after the summary tables on page 9. The standard test reports of the tested floor assemblies begin on page 16.
The floor assemblies were built and tested between January and April 2016.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 5 of 101
Table of Full Floor Assemblies
Specimen ID Sketch and Short Description STC Rating
IIC Rating
Page Number
A1-008253-01F
Bare CLT 5 ply (131 mm)
39 22 16
A1-008253-02F
SonoDeck on CLT 5 ply (131 mm)
44 38 20
A1-008253-04F
Fermacell 2E31 on CLT 5 ply (131 mm)
48 41 24
A1-008253-06F
38 mm precast concrete slab on 25 mm SonusWave
placed on top of a CLT 5 ply (131 mm)
56 49 28
A1-008253-07F
70 mm precast concrete slab on 25 mm SonusWave
placed on top of a CLT 5 ply (131 mm)
56 46 32
A1-008253-10F
70 mm precast concrete slab on 32 mm Roxul ComfortBoard IS
placed on top of a CLT 5 ply (131 mm)
57 45 36
A1-008253-11F
Bare glulam decking (89 mm)
35 20 40
A1-008253-13F
Fermacell 2E31 on glulam decking (89 mm)
47 37 44
A1-008253-14F
70 mm precast concrete slab on 25 mm SonusWave
placed on top of a glulam decking (131 mm)
54 45 48
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 6 of 101
Specimen ID Sketch and Short Description STC Rating
IIC Rating
Page Number
A1-008253-25F
38 mm precast concrete slab placed directly on a
OSB wood raft with sand on top of a CLT 5 ply (131 mm)
64 53 52
A1-008253-26F
38 mm precast concrete slab on 17 mm SonusWave placed on a
OSB wood raft with sand on top of a CLT 5 ply (131 mm)
66 60 56
A1-008253-27F
OSB wood raft with sand on top of a CLT 5 ply (131 mm)
52 47 60
A1-008253-28F
Fermacell 2E31 placed on OSB wood raft with sand on
top of a CLT 5 ply (131 mm)
59 53 64
A1-008253-29F
SonoDeck placed on OSB wood raft with sand on
top of a CLT 5 ply (131 mm)
56 50 68
A1-008253-30F
38 mm precast concrete slab on 17 mm SonusWave placed on a
OSB wood raft (no sand) on top of a CLT 5 ply (131 mm)
59 54 72
A1-008253-31F
38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft
(no sand) with glass fiber batts on top of a CLT 5 ply (131 mm)
60 54 76
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 7 of 101
Specimen ID Sketch and Short Description STC Rating
IIC Rating
Page Number
A1-008253-33F
OSB wood raft with sand on top of glulam decking (89 mm)
51 47 80
A1-008253-34F
38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft
on top of glulam decking (89 mm)
65 59 84
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 8 of 101
Table of Flooring Patches Tested on Floor Assemblies
Specimen ID Sketch and Short Description STC Rating
IIC Rating
Page Number
A1-008253-21SF
Small patch of Fermacell 2E31 on 70 mm precast concrete slab on 25 mm
SonusWave placed on top of a CLT 5 ply (131 mm)
N/A 52 88
A1-008253-22SF
Small patch of laminate floor on AcoustiTech Premium on 70 mm precast
concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm)
N/A 51 90
A1-008253-23SF
Small patch of laminate floor on Roberts Soft Stride on 70 mm precast concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm)
N/A 51 92
A1-008253-24SF
Small patch of premium laminate floor on Roberts Soft Stride 70 mm precast
concrete slab on 32 mm Roxul ComfortBoard IS placed on top of a CLT 5 ply (131 mm)
N/A 51 94
A1-008253-32SF
Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete
slab on 17 mm SonusWave placed on a OSB wood raft (no sand) with glass fiber batts on top of a CLT 5 ply (131 mm)
N/A 58 96
A1-008253-35SF
Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete
slab on 17 mm SonusWave placed on a OSB wood raft on top of glulam decking (89 mm)
N/A 62 98
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 9 of 101
Analysis
The objective of this testing series was to obtain a set of floors with good airborne sound insulation rating (STC 50+) and good impact sound insulation rating (IIC 50+). A test matrix of CLT and glulam floors with various precast and dry toppings was established. This brief analysis section compares the 1/3-octave airborne transmission loss (TL) and normalized impact sound pressure levels (NISPL), as well as the single number ratings (STC and IIC) to identify toppings and coverings that perform the best on CLT and glulam floor assemblies.
Bare CLT vs. bare glulam
The TL and the NISPL of the bare 131 mm CLT and the bare 89 mm glulam floor assemblies are compared in Graph 1 and 2.
The blue curves in the above graphs show that the CLT outperforms the glulam bare floor assembly. Looking at the legend below the graphs, the CLT floor is 4 STC points and 2 IIC points better than the glulam floor.
The higher STC and IIC rating of the CLT floor correspond to the increase in the bare floor thickness and consequently a greater area density and stiffness.
10
20
30
40
50
60
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
Graph 1: Airborne TL Graph 2: Light Impact NISPL
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Norm
aliz
ed Im
pact
Sou
nd P
ress
ure
Leve
ls, N
ISPL
, in
dB
Frequency, f, in Hz
STC IIC1 39 222 35 20GLAM89 A1-008253-11F
Legend Specimen NumberCLT131 A1-008253-01F
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 10 of 101
Same toppings on CLT and glulam
The TL and the NISPL of the bare CLT, the bare glulam, the CLT with two toppings and the glulam with two toppings (38 mm precast concrete and OSB raft) are shown in Graph 3 and 4. In the above graphs, there are three pairs of curves which correspond to the pair of CLT and glulam floors with no topping, with the precast concrete topping and with the OSB raft. There are slight differences in the individual TL and NISPL curves of the CLT and the glulam with the same topping. The TL curves of the CLT base floor (aqua, green and blue) are above those with a glulam base floor (orange, purple and red respectively). The STC and IIC ratings of the CLT and glulam floors with the same topping (heavy and/or decoupled) achieve similar values (±1 STC or IIC) as seen in the legend below the graphs. Although the TL and NISPL curves of both type of floors with the same toppings follow the same trend, they are not superimposed. The single number ratings (STC and IIC) of both floor types with the same topping indicate that the rated overall performance is similar (±1 STC or IIC).
10
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
Graph 3: Airborne TL Graph 4: Light Impact NISPL
10
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000No
rmal
ized
Impa
ct S
ound
Pre
ssur
e Le
vels
, NIS
PL,
in d
B
Frequency, f, in Hz
STC IIC1 39 222 35 203 52 474 51 475 66 606 65 59
GLAM89 A1-008253-11F
Legend Specimen NumberCLT131 A1-008253-01F
OSB18_WB64(610)_RUB10_SAND50_CLT131 A1-008253-27FOSB18_WB64(610)_RUB10_SAND50_GLAM89 A1-008253-33FPCON38_SonusWave17_OSB18_WB64(610)_RUB10_SAND50_CLT13 A1-008253-26FPCON38_SonusWave17_OSB18_WB64(610)_RUB10_SAND50_GLAM A1-008253-34F
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 11 of 101
Precast concrete toppings vs. dry toppings
The TL and NISPL of CLT floor assemblies with a precast concrete topping (38 mm or 70 mm) and with dry panelized toppings are compared in Graph 5 and 6.
TL curves of the CLT floors with a concrete precast topping on a resilient membrane (blue, green and red) are higher that the curves of the CLT floors with dry panelized toppings (purple and aqua). The difference in TL between the different precast concrete thicknesses (blue vs red) or the type of interlayer (red vs green) is not significant. For the NISPL curves, the floors with the precast concrete topping (blue, green and red) are better than those with the dry panelized toppings (purple and aqua).
In terms of IIC rating, as shown in the legend below the graph, the best floor assembly is the one with the 38 mm precast concrete on the SonusWave 25 mm rubber mat with IIC 49. The mass of precast concrete toppings of 38 mm (98.6 kg/m2) and 70 mm (165.8 kg/m2) outweigh the mass of the SonoDeck (13.5 kg/m2) and that of the Fermacell (26.0 kg/m2). For poured or precast concrete slabs (06F vs. 07F), the increase from the 38 mm to the 70 mm precast is not noticeable for STC rating (STC 56 each) and has a unexpected, possibly unrepeatable, negative effect for the IIC rating (IIC 49 to 46).
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
Graph 5: Airborne TL Graph 6: Light Impact NISPL
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000No
rmal
ized
Impa
ct S
ound
Pre
ssur
e Le
vels
, NIS
PL,
in d
B
Frequency, f, in Hz
STC IIC1 56 492 56 463 57 454 44 385 48 41
PCON70_SonusWave25_CLT131 A1-008253-07F
Legend Specimen NumberPCON38_SonusWave25_CLT131 A1-008253-06F
PCON70_ComfortBoardIS32_CLT131 A1-008253-10FSonoDeck_CLT131 A1-008253-02FFermacell[2E31]_CLT131 A1-008253-04F
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 12 of 101
Precast concrete toppings vs. OSB raft topping vs. OSB raft topping with concrete topping
A set of CLT floors with precast concrete toppings and various OSB raft configurations are compared in Graph 7 and 8.
Comparing all the TL and NISPL results of the floors tested, the best floor assembly is the one with the OSB raft topping which includes a 38 mm precast concrete topping on top of 17 mm SonusWave (A1-008253-26F | the light blue curve) and achieves STC 66 and IIC 60 as shown in the legend below the graph. Removing the sand fill from the best assembly (26F) and substituting it with glass fiber batts (A1-008253-31F) or removing the SonusWave from the best assembly (26F) (A1-008253-25F) achieves lower TL and NISPL results.
The installation of the OSB raft is beneficial since it highly decouples the rigid CLT floor. The mass of the sand also increases the area density.
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
Graph 7: Airborne TL Graph 8: Light Impact NISPL
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000No
rmal
ized
Impa
ct S
ound
Pre
ssur
e Le
vels
, NIS
PL,
in d
B
Frequency, f, in Hz
STC IIC1 39 222 56 493 56 464 52 475 64 536 60 547 66 60
PCON38_SonusWave25_CLT131 A1-008253-06F
Legend Specimen NumberCLT131 A1-008253-01F
PCON70_SonusWave25_CLT131 A1-008253-07FOSB18_WB64(610)_RUB10_SAND50_CLT131 A1-008253-27FPCON38_OSB18_WB64(610)_RUB10_SAND50_CLT131 A1-008253-25FPCON38_SonusWave17_OSB18_WB64(610)_RUB10_GFB65_CLT131 A1-008253-31FPCON38_SonusWave17_OSB18_WB64(610)_RUB10_SAND50_CLT13 A1-008253-26F
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 13 of 101
Floor patches – improving impact ratings
The NISPL results of non-standard light impact tests of laminate flooring with panelized toppings on select CLT floor assemblies are shown in Graph 9.
The best CLT floor assembly (in purple) with the lowest NISPL curve is composed of a patch of laminate flooring on a 38 mm precast concrete topping on 17 mm SonusWave rubber membrane on top of the OSB raft. The addition of laminate flooring to the bare concrete surfaces improves the NISPL curves; moving from the blue to the red curve, or from the green to the purple curve. The IIC improves by 6 or 4 points respectively for those two set of curves as shown in the legend under the graph.
In general, the improvement of IIC ratings due to the addition of coverings will be more noticeable for floors where the IIC ratings are limited at mid to high frequencies and for reference floors that have lower IIC ratings.
Graph 9: Light Impact NISPL
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Norm
aliz
ed Im
pact
Sou
nd P
ress
ure
Leve
ls, N
ISPL
, in
dB
Frequency, f, in Hz
STC IIC1 57 452 N/A 513 60 544 N/A 58
PCON38_SonusWave17_OSB18_WB64(610)_RUB10_GFB65_CLT131 A1-008253-31F*Small Patch*LAM8_SoftStride_PCON38_SonusWave17_OSB18_WB A1-008253-32SF
Legend Specimen NumberPCON70_ComfortBoardIS32_CLT131 A1-008253-10F*Small Patch*LAM8_SoftStride_PCON70_ComfortBoardIS32_CLT13 A1-008253-23SF
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 14 of 101
Other Considerations Varying the thickness of the CLT or glulam floor
One CLT floor thickness (131 mm) and one glulam floor thickness (89 mm) were evaluated as part of this floor test series. As seen in Graph 3 and 4, the test results show that CLT or glulam floors with the same topping achieve similar TL and NISPL values as well as STC and IIC ratings (±2). It is expected that an increase in the thickness of the base floor assembly will not degrade the TL or NISPL values.
Precast vs. poured concrete toppings
As part of this test series, no comparisons were performed for precast vs. poured concrete toppings. In referring to report A1-006070.10 and the floor tests reported there, it is expected that STC ratings will remains the same or improve for poured toppings (vs. precast), whereas it is expected that IIC ratings will decrease. The improvement or deterioration of the STC and IIC is strongly dependent on the mass of the topping and the resiliency of the underlayment.
Specifications for sand fill
For this project, silica sand #71 was used as fill under the OSB raft but any other sand or fill with a density varying between 1400 kg and 1700 kg could be used as a substitute without significant change to IIC and STC ratings. It is important that the sand or fill be dry, remains loose and that only sand types approved to be installed in buildings are used.
In-situ vs. laboratory results
The laboratory sound insulation results measured according to ASTM E90 and ASTM E492 represent an upper limit of the direct sound insulation that can be measured in-situ. A number of factors influence the in-situ performance, for example: flanking sound transmission, specimen size, specimen coupling and construction workmanship.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 15 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 16 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Bare CLT 5 ply (131 mm)
Specimen ID A1-008253-01F
Construction Date: January 22, 2016
Specimen Description CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-01F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 131 1 343 69.5 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 17 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 18 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-003
Specimen ID: A1-008253-01F Date of Test: January 25, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 177.0 22.2 to 22.7 33.8 to 34.7 Area S of test specimen: 17.85 m2
Lower 176.9 17.8 to 18.7 35.4 to 38.1 Mass per unit area: 69.5 kg/m2
f (Hz)
Airborne TL (dB)
50 21
63 25
80 25
100 27
125 28
160 28
200 28
250 30
315 31
400 32
500 34
630 37
800 39
1000 41
1250 43
1600 46
2000 48
2500 51
3150 52
4000 53
5000 50
Sound Transmission
Class (STC) 39
Sum of Deficiencies (dB)
24 Max. Deficiency (dB)
6 dB at 400 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
1 2
4 6
5 3
2 1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 39
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 19 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-002
Specimen ID: A1-008253-01F Date of Test: January 12, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 177.0 21.8 to 21.9 31.3 to 31.5 Area S of test specimen: 17.85 m2
Lower 176.9 16.9 to 17.0 38.8 to 38.9 Mass per unit area: 69.5 kg/m2
f (Hz)
NISPL (dB)
50 76
63 72
80 72
100 75
125 79
160 81
200 82
250 83
315 84
400 86
500 87
630 87
800 88
1000 88
1250 87
1600 86
2000 82
2500 76
3150 66
4000 62
5000 59
Impact Insulation
Class (IIC)
22
Sum of Positive Differences (dB)
26 Max. Positive Difference (dB)
7 dB at 1600 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” with the exception that the temperature the lower room fell below 17 ºC. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
2 3
5 7
6
3
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 22
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 20 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen SonoDeck on CLT 5 ply (131 mm)
Specimen ID A1-008253-02F
Construction Date: January 29, 2016 to February 1, 2016
Specimen Description Topping: SonoDeck engineered acoustic panels from InsulFloor measuring 800 mm x 1220 mm x 25 mm (31.5” x 48” x 1”) are composed of two layers of 9.5 mm (3/8”) OSB glued together with 6 mm (1/4”) fiberglass mat on the bottom. The 25 mm (1”) overlapping joints of the panels were glued and stapled using 18 Ga. ¼” x ¾” narrow crown staples along the joints every 305 mm (12”). Each row of SonoDeck panels was offset by half a panel length (400 mm). The gap between the SonoDeck and the test frame was filled with closed cell polyethylene foam. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-02F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
25 mm SonoDeck engineered acoustic panels 25 261 13.5 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 156 1 604 83.0 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 21 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 22 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-006
Specimen ID: A1-008253-02F Date of Test: February 2, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.4 24.4 to 24.5 32.2 to 32.3 Area S of test specimen: 17.85 m2
Lower 176.9 18.2 to 18.2 40.9 to 41.0 Mass per unit area: 83.0 kg/m2
f (Hz)
Airborne TL (dB)
50 43
63 51
80 46
100 44
125 45
160 44
200 46
250 49
315 51
400 54
500 57
630 58
800 60
1000 62
1250 65
1600 68
2000 72
2500 77
3150 83
4000 87
5000 89
Sound Transmission
Class (STC) 44
Sum of Deficiencies (dB)
30 Max. Deficiency (dB)
8 dB at 200 and 250 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
4
8 8 6
4
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 44
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 23 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-005
Specimen ID: A1-008253-02F Date of Test: February 2, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.4 25.0 to 25.0 31.9 to 32.6 Area S of test specimen: 17.85 m2
Lower 176.9 18.3 to 18.3 40.9 to 40.9 Mass per unit area: 83.0 kg/m2
f (Hz)
NISPL (dB)
50 67
63 69
80 70
100 71
125 76
160 78
200 82
250 80
315 75
400 71
500 66
630 60
800 57
1000 53
1250 47
1600 41
2000 36
2500 30
3150 27 c
4000 25 c
5000 25 *
Impact Insulation
Class (IIC)
38
Sum of Positive Differences (dB)
21 Max. Positive Difference (dB)
8 dB at 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
2 4
8 6
1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 38
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 24 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Fermacell 2E31 on CLT 5 ply (131 mm)
Specimen ID A1-008253-04F
Construction Date: February 9, 2006 to February 10, 2016
Specimen Description Topping: Fermacell panels type 2E31 (EE20+WF10) measuring 500 mm wide x 1500 m long x 30 mm thick were installed on top of the CLT floor. The rabbeted edges of the Fermacell panels were glued using the Fermacell floor glue and screwed together using Fermacell floor screws 3.9 mm x 19 mm spaced at a minimum of 200 mm on centre along the joints. Each row of Fermacell panels was offset from the adjoining rows. Perimeter strips were installed all around the floor to decouple the Fermacell panels from the test frame. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-04F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
30 mm Fermacell 2E31 (EE20+WF10) 30 514 26.6 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 161 1 857 96.1 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 25 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 26 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-010
Specimen ID: A1-008253-04F Date of Test: February 9, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.8 21.5 to 22.0 40.0 to 42.1 Area S of test specimen: 17.85 m2
Lower 177.1 17.5 to 17.8 38.2 to 38.6 Mass per unit area: 96.1 kg/m2
f (Hz)
Airborne TL (dB)
50 25
63 30
80 29
100 30
125 32
160 32
200 33
250 35
315 38
400 42
500 45
630 49
800 53
1000 58
1250 62
1600 66
2000 69
2500 70
3150 73
4000 74
5000 73
Sound Transmission
Class (STC) 48
Sum of Deficiencies (dB)
28 Max. Deficiency (dB)
6 dB at 250 and 315 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
3 5
6 6 5
3
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 48
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 27 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-009
Specimen ID: A1-008253-04F Date of Test: January 12, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.8 23.1 to 23.1 29.1 to 30.1 Area S of test specimen: 17.85 m2
Lower 176.9 18.2 to 18.5 33.6 to 34.3 Mass per unit area: 96.1 kg/m2
f (Hz)
NISPL (dB)
50 69
63 65
80 66
100 69
125 73
160 74
200 76
250 76
315 76
400 75
500 74
630 70
800 67
1000 64
1250 60
1600 54
2000 50
2500 46
3150 41
4000 40
5000 39
Impact Insulation
Class (IIC)
41
Sum of Positive Differences (dB)
32 Max. Positive Difference (dB) 5dB at 200, 250, 315, 400 and 500Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
2 3
5 5 5 5 5
2
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 41
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 28 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 38 mm precast concrete slab on 25 mm SonusWave™ placed on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-06F
Construction Date: March 10, 2016 to March 11, 2016
Specimen Description Topping: A 38 mm (1-1/2”) precast concrete slab was placed on 25 mm Regupol® SonusWave™ which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-06F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 25 mm Regupol® SonusWave™ 25 261 13.5 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 194 3 508 181.6 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 29 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 30 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-016
Specimen ID: A1-008253-06F Date of Test: March 11, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.8 23.2 to 23.2 33.9 to 34.0 Area S of test specimen: 17.85 m2
Lower 176.9 21.6 to 21.7 36.9 to 37.2 Mass per unit area: 181.6 kg/m2
f (Hz)
Airborne TL (dB)
50 31
63 34
80 33
100 33
125 36
160 37
200 39
250 44
315 49
400 53
500 55
630 57
800 62
1000 68
1250 73
1600 79
2000 85 c
2500 88 *
3150 90 *
4000 91 *
5000 90 *
Sound Transmission
Class (STC) 56
Sum of Deficiencies (dB)
28 Max. Deficiency (dB)
7 dB at 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
4 6
7 5
3 2
1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 56
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 31 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-017
Specimen ID: A1-008253-06F Date of Test: March 11, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.8 23.6 to 23.7 33.8 to 34.3 Area S of test specimen: 17.85 m2
Lower 176.9 21.5 to 21.6 37.0 to 37.2 Mass per unit area: 181.6 kg/m2
f (Hz)
NISPL (dB)
50 58
63 59
80 67
100 66
125 67
160 67
200 66
250 64
315 64
400 64
500 63
630 63
800 61
1000 57
1250 54
1600 52
2000 50
2500 48
3150 44
4000 43
5000 43
Impact Insulation
Class (IIC)
49
Sum of Positive Differences (dB)
29 Max. Positive Difference (dB)
4 dB at 125 and 160 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
3 4 4
3 1 1
2 2 3
2 1
2 1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 49
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 32 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 70 mm precast concrete slab on 25 mm SonusWave™ placed on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-07F
Construction Date: February 29, 2016
Specimen Description Topping: A 70 mm (2-3/4”) precast concrete slab was placed on 25 mm Regupol® SonusWave™ which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-07F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
70 mm Precast Concrete Slab 70 3 202 165.8 kg/m2 25 mm Regupol® SonusWave™ 25 261 13.5 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 226 4 740 245.4 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 33 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 34 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-014
Specimen ID: A1-008253-07F Date of Test: March 1, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.5 19.3 to 19.4 32.2 to 32.3 Area S of test specimen: 17.85 m2
Lower 176.9 18.7 to 18.9 35.8 to 36.2 Mass per unit area: 245.4 kg/m2
f (Hz)
Airborne TL (dB)
50 33
63 37
80 37
100 36
125 39
160 38
200 41
250 45
315 45
400 49
500 53
630 58
800 61
1000 67
1250 72
1600 79
2000 86 c
2500 89 *
3150 89 *
4000 90 *
5000 91 c
Sound Transmission
Class (STC) 56
Sum of Deficiencies (dB)
31 Max. Deficiency (dB)
7 dB at 315 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
1
5 5 4
7 6
3
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 56
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 35 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-011
Specimen ID: A1-008253-07F Date of Test: February 29, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.5 19.5 to 19.6 32.3 to 32.8 Area S of test specimen: 17.85 m2
Lower 176.9 16.7 to 17.8 36.0 to 38.1 Mass per unit area: 245.4 kg/m2
f (Hz)
NISPL (dB)
50 51
63 46
80 50
100 53
125 55
160 61
200 61
250 61
315 65
400 64
500 64
630 65
800 65
1000 63
1250 59
1600 50
2000 46
2500 43
3150 36
4000 33
5000 31
Impact Insulation
Class (IIC)
46
Sum of Positive Differences (dB)
23 Max. Positive Difference (dB)
5 dB at 250 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” with the exception that the temperature in the lower room fell below 17 ºC. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
2 4
5 3
4
1 1 2
1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 46
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 36 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 70 mm precast concrete slab on 32 mm Roxul® ComfortBoard IS placed on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-10F
Construction Date: March 3, 2016
Specimen Description Topping: A 70 mm (2-3/4”) precast concrete slab was placed on Roxul® ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-10F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
70 mm Precast Concrete Slab 70 3 202 165.8 kg/m2 32 mm Roxul® ComfortBoard IS 32 78 4.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 233 4 623 239.4 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 37 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 38 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-015
Specimen ID: A1-008253-10F Date of Test: March 3, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.1 21.7 to 21.8 31.9 to 32.0 Area S of test specimen: 17.85 m2
Lower 176.9 19.4 to 19.4 34.8 to 34.9 Mass per unit area: 239.4 kg/m2
f (Hz)
Airborne TL (dB)
50 34
63 32
80 33
100 35
125 38
160 37
200 42
250 47
315 48
400 51
500 56
630 59
800 61
1000 65
1250 68
1600 75
2000 82
2500 86 c
3150 89 *
4000 91 *
5000 91 *
Sound Transmission
Class (STC) 57
Sum of Deficiencies (dB)
29 Max. Deficiency (dB)
7 dB at 160 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
3
7 5
3 5 5
1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 57
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 39 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-012
Specimen ID: A1-008253-10F Date of Test: March 3, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.1 22.2 to 22.2 31.7 to 32.5 Area S of test specimen: 17.85 m2
Lower 176.9 19.3 to 19.5 34.9 to 35.2 Mass per unit area: 239.4 kg/m2
f (Hz)
NISPL (dB)
50 66
63 65
80 65
100 70
125 67
160 69
200 67
250 67
315 65
400 67
500 63
630 64
800 65
1000 64
1250 63
1600 59
2000 55
2500 52
3150 48
4000 46
5000 44
Impact Insulation
Class (IIC)
45
Sum of Positive Differences (dB)
22 Max. Positive Difference (dB)
4 dB at 1250 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
3 2
1 2 2
4 3
2 2 1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 45
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 40 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Bare glulam decking (89 mm)
Specimen ID A1-008253-11F
Construction Date: January 26, 2016
Specimen Description Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15” x 3-1/2” x 153”). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2”) long common nails spaced 300 mm (12”) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam.
Cross-section of A1-008253-11F
Fastening details of glulam decking
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
89 mm Glulam Decking 89 971 50.2 kg/m2 Total 89 971 50.2 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 41 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 42 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-005
Specimen ID: A1-008253-11F Date of Test: January 28, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 177.4 22.5 to 22.5 38.1 to 38.5 Area S of test specimen: 17.85 m2
Lower 177.1 17.0 to 17.0 39.0 to 39.2 Mass per unit area: 50.2 kg/m2
f (Hz)
Airborne TL (dB)
50 17
63 21
80 25
100 25
125 22
160 26
200 26
250 29
315 29
400 32
500 33
630 34
800 35
1000 35
1250 35
1600 36
2000 37
2500 38
3150 41
4000 44
5000 40
Sound Transmission
Class (STC) 35
Sum of Deficiencies (dB)
23 Max. Deficiency (dB)
4 dB at 1250 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
2 2 2 2 2 3
4 3
2 1
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 35
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 43 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-004
Specimen ID: A1-008253-11F Date of Test: January 28, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 177.4 22.3 to 22.3 39.6 to 40.4 Area S of test specimen: 17.85 m2
Lower 177.1 17.0 to 17.0 39.2 to 39.4 Mass per unit area: 50.2 kg/m2
f (Hz)
NISPL (dB)
50 77
63 74
80 74
100 78
125 86
160 82
200 83
250 83
315 85
400 86
500 88
630 88
800 89
1000 90
1250 90
1600 88
2000 85
2500 80
3150 71
4000 65
5000 61
Impact Insulation
Class (IIC)
20
Sum of Positive Differences (dB)
29 Max. Positive Difference (dB)
7 dB at 1600 and 2000 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
1 3
6 7 7
5
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 20
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 44 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Fermacell 2E31 on glulam decking (89 mm)
Specimen ID A1-008253-13F
Construction Date: February 3, 2016
Specimen Description Topping: Fermacell panels type 2E31 (EE20+WF10) measuring 500 mm wide x 1500 mm long x 30 mm thick were installed on top of the glulam decking. The rabbeted edges of the Fermacell panels were glued using the Fermacell floor glue and screwed together using Fermacell floor screws 3.9 mm x 19 mm spaced at a minimum of 200 mm on centre along the joints. Each row of Fermacell panels was offset from the adjoining rows. Perimeter strips were installed all around the floor to decouple the Fermacell panels from the test frame. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15” x 3-1/2” x 153”). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2”) long common nails spaced 300 mm (12”) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam.
Cross-section of A1-008253-13F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
30 mm Fermacell 2E31 (EE20+WF10) 30 514 26.6 kg/m2 89 mm Glulam Decking 89 971 50.2 kg/m2 Total 119 1 485 76.8 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 45 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 46 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-009
Specimen ID: A1-008253-13F Date of Test: February 9, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.9 23.0 to 23.3 31.0 to 31.4 Area S of test specimen: 17.85 m2
Lower 177.1 18.5 to 18.9 40.1 to 40.7 Mass per unit area: 76.8 kg/m2
f (Hz)
Airborne TL (dB)
50 24
63 28
80 30
100 28
125 30
160 30
200 32
250 35
315 37
400 40
500 44
630 47
800 50
1000 54
1250 57
1600 59
2000 60
2500 62
3150 66
4000 69
5000 70
Sound Transmission
Class (STC) 47
Sum of Deficiencies (dB)
31 Max. Deficiency (dB)
6 dB at 315 and 400 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
1
4 5 5
6 6
3 1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 47
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 47 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-006
Specimen ID: A1-008253-13F Date of Test: February 8, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.9 24.2 to 24.3 31.8 to 33.2 Area S of test specimen: 17.85 m2
Lower 177.1 20.5 to 21.6 35.8 to 38.5 Mass per unit area: 76.8 kg/m2
f (Hz)
NISPL (dB)
50 64
63 64
80 67
100 70
125 72
160 75
200 77
250 78
315 78
400 78
500 77
630 76
800 74
1000 72
1250 68
1600 64
2000 59
2500 54
3150 50
4000 47
5000 45
Impact Insulation
Class (IIC)
37
Sum of Positive Differences (dB)
26 Max. Positive Difference (dB)
4 dB at 400, 500 and 630 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
2 3 3
4 4 4 3
2 1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 37
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 48 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 70 mm precast concrete slab on 25 mm SonusWave™ placed on top of a glulam decking (131 mm)
Specimen ID A1-008253-14F
Construction Date: February 17, 2016 to February 24, 2016
Specimen Description Topping: A 70 mm (2-3/4”) precast concrete slab was placed on 25 mm Regupol® SonusWave™ which was placed on the glulam decking. The edge of the precast concrete slab was filled with insulation and taped. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15” x 3-1/2” x 153”). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2”) long common nails spaced 300 mm (12”) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam.
Cross-section of A1-008253-14F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
70 mm Precast Concrete Slab 70 3 202 165.8 kg/m2 25 mm Regupol® SonusWave™ 25 195 10.1 kg/m2 89 mm Glulam Decking 89 971 50.2 kg/m2 Total 184 4 368 226.1 kg/m2
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 49 of 101
This page is intentionally left blank
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 50 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-011
Specimen ID: A1-008253-14F Date of Test: February 25, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.2 25.0 to 25.0 33.9 to 35.6 Area S of test specimen: 17.85 m2
Lower 177.1 21.0 to 21.3 37.4 to 37.7 Mass per unit area: 226.1 kg/m2
f (Hz)
Airborne TL (dB)
50 32
63 36
80 36
100 35
125 36
160 38
200 41
250 43
315 43
400 46
500 53
630 58
800 62
1000 67
1250 71
1600 76
2000 83
2500 87 c
3150 90 *
4000 91 *
5000 92 *
Sound Transmission
Class (STC) 54
Sum of Deficiencies (dB)
27 Max. Deficiency (dB)
7 dB at 315 and 400 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
2 3 3
4
7 7
1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 54
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 51 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-010
Specimen ID: A1-008253-14F Date of Test: February 26, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.2 23.9 to 24.0 29.4 to 30.7 Area S of test specimen: 17.85 m2
Lower 177.1 18.4 to 18.6 40.0 to 40.3 Mass per unit area: 226.1 kg/m2
f (Hz)
NISPL (dB)
50 55
63 57
80 62
100 67
125 71
160 73
200 73
250 72
315 72
400 70
500 66
630 65
800 63
1000 62
1250 59
1600 55
2000 51
2500 50
3150 47
4000 47
5000 47
Impact Insulation
Class (IIC)
45
Sum of Positive Differences (dB)
32 Max. Positive Difference (dB)
6 dB at 160 and 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
4 6 6
5 5 4
1 1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 45
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 52 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 38 mm precast concrete slab placed directly on a OSB wood raft with sand on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-25F
Construction Date: March 17, 2016 to March 21, 2016
Specimen Description Topping: A 38 mm (1-1/2”) precast concrete slab was installed directly on top of OSB sheeting. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2”) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-25F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 261 4 905 253.9 kg/m2 * The thickness of the sand is not included in the total specimen thickness.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 53 of 101
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 54 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-017
Specimen ID: A1-008253-25F Date of Test: March 22, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.6 24.9 to 24.9 31.4 to 31.6 Area S of test specimen: 17.85 m2
Lower 176.9 19.9 to 20.0 38.6 to 38.8 Mass per unit area: 253.9 kg/m2
f (Hz)
Airborne TL (dB)
50 35
63 36
80 36
100 37
125 41
160 45
200 48
250 54
315 56
400 62
500 65 c
630 63
800 68
1000 71
1250 77
1600 81
2000 86 c
2500 90 c
3150 91 c
4000 91 c
5000 90 c
Sound Transmission
Class (STC) 64
Sum of Deficiencies (dB)
29 Max. Deficiency (dB)
7 dB at 125 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
7 6 6
3 4
1 2
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 64
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 55 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-018
Specimen ID: A1-008253-25F Date of Test: March 22, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.6 24.9 to 24.9 31.8 to 32.1 Area S of test specimen: 17.85 m2
Lower 176.9 20.2 to 20.4 38.3 to 38.7 Mass per unit area: 253.9 kg/m2
f (Hz)
NISPL (dB)
50 58
63 60
80 59
100 61
125 61
160 61
200 61
250 58
315 58
400 54
500 54
630 56
800 56
1000 55
1250 52
1600 54
2000 50
2500 47
3150 42
4000 40
5000 39
Impact Insulation
Class (IIC)
53
Sum of Positive Differences (dB)
30 Max. Positive Difference (dB)
6 dB at 1600 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
2 2 2 2 1 1 1
6 5 5
3
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 53
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 56 of 101
Client: Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen: 38 mm precast concrete slab on 17 mm SonusWave™ placed on a OSB wood raft with sand on top of a CLT 5 ply (131 mm)
Specimen ID: A1-008253-26F
Construction Date: March 23, 2016
Specimen Description Topping: A 38 mm (1-1/2”) precast concrete slab was placed on 17 mm Regupol® SonusWave™ on top of OSB sheeting. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2”) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-26F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 17 mm Regupol® SonusWave™ 17 157 8.1 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 278 5 062 262.0 kg/m2 * The thickness of the sand is not included in the total specimen thickness.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 57 of 101
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 58 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-018
Specimen ID: A1-008253-26F Date of Test: March 23, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.3 24.7 to 24.8 42.4 to 43.8 Area S of test specimen: 17.85 m2
Lower 176.9 18.8 to 18.8 39.8 to 40.2 Mass per unit area: 262.0 kg/m2
f (Hz)
Airborne TL (dB)
50 33
63 34
80 38
100 40
125 44
160 46
200 49
250 55
315 57
400 63
500 68
630 70
800 72
1000 74
1250 79
1600 84
2000 90 c
2500 92 *
3150 92 c
4000 92 c
5000 92 c
Sound Transmission
Class (STC) 66
Sum of Deficiencies (dB)
31 Max. Deficiency (dB)
7 dB at 160 and 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
6 7 7
4 5
2
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 66
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 59 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-019
Specimen ID: A1-008253-26F Date of Test: March 23, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.3 24.9 to 26.1 26.8 to 47.5 Area S of test specimen: 17.85 m2
Lower 176.9 18.9 to 19.0 40.2 to 40.7 Mass per unit area: 262.0 kg/m2
f (Hz)
NISPL (dB)
50 58
63 60
80 59
100 61
125 61
160 61
200 61
250 58
315 58
400 54
500 54
630 56
800 56
1000 55
1250 52
1600 54
2000 50
2500 47 *
3150 42 *
4000 40 *
5000 39 *
Impact Insulation
Class (IIC)
60
Sum of Positive Differences (dB)
26 Max. Positive Difference (dB)
5 dB at 125, 160 and 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
3 5 5 5
3 4
1
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 60
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 60 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen OSB wood raft with sand on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-27F
Construction Date March 29, 2016
Specimen Description Topping: The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2”) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-27F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 223 3 000 155.3 kg/m2 * The thickness of the sand is not included in the total specimen thickness.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 61 of 101
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 62 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-019
Specimen ID: A1-008253-27F Date of Test: March 29, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.3 21.4 to 21.5 33.6 to 33.7 Area S of test specimen: 17.85 m2
Lower 176.9 18.5 to 18.5 41.0 to 41.1 Mass per unit area: 155.3 kg/m2
f (Hz)
Airborne TL (dB)
50 34
63 35
80 34
100 34
125 33
160 32
200 38
250 42
315 43
400 46
500 55
630 57
800 60
1000 62
1250 65
1600 67
2000 70
2500 75
3150 79
4000 80
5000 81
Sound Transmission
Class (STC) 52
Sum of Deficiencies (dB)
27 Max. Deficiency (dB)
7 dB at 160 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
3
7
4 3
5 5
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 52
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 63 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-020
Specimen ID: A1-008253-27F Date of Test: March 29, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.3 21.8 to 21.9 33.2 to 33.8 Area S of test specimen: 17.85 m2
Lower 176.9 18.5 to 18.5 41.4 to 41.8 Mass per unit area: 155.3 kg/m2
f (Hz)
NISPL (dB)
50 58
63 60
80 58
100 65
125 70
160 71
200 70
250 69
315 66
400 63
500 65
630 66
800 63
1000 58
1250 54
1600 51
2000 45
2500 41
3150 39
4000 35 c
5000 32 *
Impact Insulation
Class (IIC)
47
Sum of Positive Differences (dB)
29 Max. Positive Difference (dB)
6 dB at 160 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
5 6
5 4
1 2
4 2
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 47
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 64 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Fermacell 2E31 placed on OSB wood raft with sand on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-28F
Construction Date March 29, 2016
Specimen Description Topping: Fermacell panels type 2E31 (EE20+WF10) measuring 500 mm wide x 1500 mm long x 30 mm thick were installed on top of OSB subfloor. The rabbeted edges of the Fermacell panels were glued using the Fermacell floor glue and screwed together using Fermacell floor screws 3.9 mm x 19 mm spaced at a minimum of 200 mm on centre along the joints. Each row of Fermacell panels was offset from the adjoining rows. Perimeter strips were installed all around the floor to decouple the Fermacell panels from the test frame. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the batten leaving a 12 mm (1/2”) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-28F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
30 mm Fermacell 2E31 (EE20+WF10) 30 514 26.6 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 253 3 514 181.9 kg/m2
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 65 of 101
* The thickness of the sand is not included in the total specimen thickness. Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 66 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-020
Specimen ID: A1-008253-28F Date of Test: March 30, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.7 21.1 to 21.1 33.3 to 33.4 Area S of test specimen: 17.85 m2
Lower 176.9 17.9 to 18.0 37.6 to 37.7 Mass per unit area: 181.9 kg/m2
f (Hz)
Airborne TL (dB)
50 33
63 34
80 31
100 31
125 37
160 42
200 44
250 49
315 49
400 55
500 65
630 66
800 68
1000 71
1250 78
1600 83
2000 88 c
2500 91 c
3150 93 *
4000 93 *
5000 93 *
Sound Transmission
Class (STC) 59
Sum of Deficiencies (dB)
27 Max. Deficiency (dB)
6 dB at 125 and 315 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
6 4
5 3
6
3
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 59
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 67 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-021
Specimen ID: A1-008253-28F Date of Test: March 30, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.7 21.4 to 21.5 33.5 to 34.2 Area S of test specimen: 17.85 m2
Lower 176.9 18.1 to 18.2 37.4 to 37.6 Mass per unit area: 181.9 kg/m2
f (Hz)
NISPL (dB)
50 57
63 56
80 62
100 63
125 67
160 67
200 63
250 60
315 60
400 56
500 52
630 55
800 51
1000 47
1250 39
1600 35
2000 30
2500 24 *
3150 19 *
4000 17 *
5000 18 *
Impact Insulation
Class (IIC)
53
Sum of Positive Differences (dB)
26 Max. Positive Difference (dB)
8 dB at 125 and 160 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
4
8 8
4
1 1
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 53
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 68 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen SonoDeck placed on OSB wood raft with sand on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-29F
Construction Date March 31, 2016
Specimen Description Topping: SonoDeck engineered acoustic panels from InsulFloor measuring 800 mm x 1220 mm x 25 mm (31.5” x 48” x 1”) are composed of two layers of 9.5 mm (3/8”) OSB glued together with 6 mm (1/4”) fiberglass mat on the bottom. The SonoDeck was placed on top of the OSB subfloor. The 25 mm (1”) overlapping joints of the panels were glued and stapled using 18 Ga. ¼” x ¾” narrow crown staples along the joints every 305 mm (12”). Each row of SonoDeck panels was offset by half a panel length (400 mm). The gap between the SonoDeck and the test frame was filled with closed cell polyethylene foam. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2”) air gap between the sand and the OSB. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-29F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
25 mm SonoDeck engineered acoustic panels 25 261 13.5 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 248 3 261 168.8 kg/m2
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 69 of 101
* The thickness of the sand is not included in the total specimen thickness. Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 70 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-021
Specimen ID: A1-008253-29F Date of Test: March 31, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.8 21.4 to 21.5 35.8 to 35.9 Area S of test specimen: 17.85 m2
Lower 176.9 17.8 to 17.8 40.1 to 40.2 Mass per unit area: 168.8 kg/m2
f (Hz)
Airborne TL (dB)
50 34
63 34
80 32
100 31
125 34
160 39
200 41
250 45
315 46
400 52
500 64
630 67
800 70
1000 73
1250 79
1600 84
2000 89 c
2500 92 *
3150 93 *
4000 93 *
5000 94 *
Sound Transmission
Class (STC) 56
Sum of Deficiencies (dB)
28 Max. Deficiency (dB)
6 dB at 125 and 315 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
6 4
5 4
6
3
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 56
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 71 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-022
Specimen ID: A1-008253-29F Date of Test: March 31, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.7 21.9 to 21.9 35.6 to 35.7 Area S of test specimen: 17.85 m2
Lower 176.9 17.9 to 17.9 39.8 to 40.3 Mass per unit area: 168.8 kg/m2
f (Hz)
NISPL (dB)
50 59
63 57
80 62
100 67
125 70
160 69
200 65
250 63
315 62
400 56
500 51
630 52
800 45
1000 38
1250 30
1600 24 c
2000 18 *
2500 14 *
3150 14 *
4000 15 *
5000 17 *
Impact Insulation
Class (IIC)
50
Sum of Positive Differences (dB)
24 Max. Positive Difference (dB)
8 dB at 125 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
5
8 7
3 1
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 50
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 72 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-30F
Construction Date April 5, 2016
Specimen Description Topping: 38 mm (1-1/2”) precast concrete slab was placed on 17 mm Regupol® SonusWave™ on top of OSB sheeting. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-30F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 17 mm Regupol® SonusWave™ 17 157 8.1 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 278 3 675 190.2 kg/m2
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 73 of 101
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 74 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-022
Specimen ID: A1-008253-30F Date of Test: April 5, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.4 22.6 to 22.8 33.6 to 33.3 Area S of test specimen: 17.85 m2
Lower 176.9 18.1 to 18.1 38.2 to 38.3 Mass per unit area: 190.2 kg/m2
f (Hz)
Airborne TL (dB)
50 32
63 29
80 33
100 34
125 40
160 41
200 43
250 46
315 50
400 54
500 59
630 63
800 68
1000 73
1250 78
1600 82
2000 91 c
2500 92 c
3150 93 *
4000 93 *
5000 95 *
Sound Transmission
Class (STC) 59
Sum of Deficiencies (dB)
29 Max. Deficiency (dB)
6 dB at 200 and 250 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
3 5
6 6 5
4
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 59
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 75 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-023
Specimen ID: A1-008253-30F Date of Test: March 31, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.4 23.3 to 23.9 32.1 to 36.7 Area S of test specimen: 17.85 m2
Lower 176.9 18.1 to 18.1 38.2 to 38.2 Mass per unit area: 190.2 kg/m2
f (Hz)
NISPL (dB)
50 59
63 57
80 62
100 67
125 70
160 69
200 65
250 63
315 62
400 56
500 51
630 52
800 45
1000 38
1250 30
1600 24
2000 18
2500 14 c
3150 14 *
4000 15 *
5000 17 *
Impact Insulation
Class (IIC)
54
Sum of Positive Differences (dB)
31 Max. Positive Difference (dB)
7 dB at 400 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
1 1
4 5
4 5
7
4
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 54
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 76 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) with glass fiber batts on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-31F
Construction Date April 7, 2016
Specimen Description Topping: A 38 mm (1-1/2”) precast concrete slab was placed on 17 mm Regupol® SonusWave™ on top of OSB sheeting. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. 65 mm (2-1/2”) glass fibre insulation batts were placed in the cavity. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-31F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 17 mm Regupol® SonusWave™ 17 157 8.1 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 65 mm Glass Fibre Insulation Batts *65 13 0.7 kg/m2 10 mm Rubber Membrane 10 21 7.7 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 278 3 688 190.9 kg/m2 * The thickness of the glass fibre insulation batts is not included in the total specimen thickness.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 77 of 101
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 78 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-024
Specimen ID: A1-008253-31F Date of Test: April 7, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.4 21.4 to 21.8 33.2 to 34.0 Area S of test specimen: 17.85 m2
Lower 176.9 17.9 to 18.2 40.5 to 43.8 Mass per unit area: 190.9 kg/m2
f (Hz)
Airborne TL (dB)
50 32
63 30
80 34
100 35
125 40
160 42
200 44
250 47
315 52
400 55
500 59
630 63
800 68
1000 73
1250 78
1600 83
2000 91 c
2500 93 *
3150 94 *
4000 93 *
5000 94 *
Sound Transmission
Class (STC) 60
Sum of Deficiencies (dB)
30 Max. Deficiency (dB)
6 dB at 200 and 250 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements” with the exception that the humidity variation in the lower room was greater than 3%. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
4 5
6 6 4 4
1
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 60
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 79 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-024
Specimen ID: A1-008253-31F Date of Test: April 8, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.4 21.2 to 21.3 30.1 to 30.3 Area S of test specimen: 17.85 m2
Lower 176.9 17.8 to 17.9 36.7 to 36.7 Mass per unit area: 190.9 kg/m2
f (Hz)
NISPL (dB)
50 63
63 62
80 57
100 59
125 59
160 60
200 62
250 62
315 62
400 63
500 60
630 55
800 50
1000 46
1250 41
1600 34
2000 26
2500 17 *
3150 15 *
4000 16 *
5000 17 *
Impact Insulation
Class (IIC)
54
Sum of Positive Differences (dB)
26 Max. Positive Difference (dB)
6 dB at 400 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
1 1 2
4 4 4 6
4
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 54
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 80 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen OSB wood raft with sand on top of glulam decking (89 mm)
Specimen ID A1-008253-33F
Construction Date April 11, 2016 to April 12, 2016
Specimen Description Topping: The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2”) air gap between the sand and the OSB. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15” x 3-1/2” x 153”). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2”) long common nails spaced 300 mm (12”) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam.
Cross-section of A1-008253-33F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 89 mm Glulam Decking 89 971 50.2 kg/m2 Total 181 2 628 136.0 kg/m2 * The thickness of the sand is not included in the total specimen thickness.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 81 of 101
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 82 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-025
Specimen ID: A1-008253-33F Date of Test: April 12, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.0 21.9 to 22.0 31.2 to 31.6 Area S of test specimen: 17.85 m2
Lower 177.1 17.7 to 17.7 34.4 to 34.6 Mass per unit area: 136.0 kg/m2
f (Hz)
Airborne TL (dB)
50 33
63 34
80 34
100 33
125 33
160 33
200 34
250 39
315 42
400 45
500 51
630 53
800 55
1000 57
1250 61
1600 63
2000 66
2500 72
3150 76
4000 80
5000 82
Sound Transmission
Class (STC) 51
Sum of Deficiencies (dB)
29 Max. Deficiency (dB)
7 dB at 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
2
5 7
5 5 5
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 51
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 83 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-026
Specimen ID: A1-008253-33F Date of Test: April 12, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 176.0 22.4 to 22.9 32.0 to 32.5 Area S of test specimen: 17.85 m2
Lower 177.1 17.8 to 17.8 33.8 to 34.1 Mass per unit area: 136.0 kg/m2
f (Hz)
NISPL (dB)
50 60
63 59
80 62
100 64
125 69
160 71
200 71
250 69
315 67
400 64
500 66
630 65
800 63
1000 59
1250 54
1600 48
2000 42
2500 36
3150 31
4000 26 *
5000 22 *
Impact Insulation
Class (IIC)
47
Sum of Positive Differences (dB)
30 Max. Positive Difference (dB)
6 dB at 160 and 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
4 6 6
4 2
3 3 2
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 47
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 84 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft on top of glulam decking (89 mm)
Specimen ID A1-008253-34F
Construction Date April 13, 2016
Specimen Description Topping: A 38 mm (1-1/2”) precast concrete slab was placed on 17 mm Regupol® SonusWave™ on top of OSB sheeting. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. Fill: A 6 mil polyethylene sheet was placed on the CLT and the wood battens with rubber membrane were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the battens leaving a 12 mm (1/2”) air gap between the sand and the OSB. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15” x 3-1/2” x 153”). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2”) long common nails spaced 300 mm (12”) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam.
Cross-section of A1-008253-34F
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 17 mm Regupol® SonusWave™ 17 157 8.1 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 89 mm Glulam Decking 89 971 50.2 kg/m2 Total 236 4 690 242.8 kg/m2 * The thickness of the sand is not included in the total specimen thickness.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 85 of 101
Test Specimen Installation
• The exposed area of the floor specimen used for the calculations of the airborne sound transmission loss was 17.85 m2 (4.71 m x 3.79 m).
• The total area of the floor assembly resting on top of the lip was 19.32 m2 (4.88 m x 3.96 m). • The mass per area of the elements above the lip was calculated using the total area (19.32 m2).
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 86 of 101
ASTM E90 Test Results – Airborne Sound Transmission Loss
Client: Nordic Engineered Wood Test ID: TLF-16-026
Specimen ID: A1-008253-34F Date of Test: April 13, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.9 23.1 to 23.2 32.3 to 32.5 Area S of test specimen: 17.85 m2
Lower 177.1 17.8 to 17.8 37.0 to 37.3 Mass per unit area: 242.8 kg/m2
f (Hz)
Airborne TL (dB)
50 32
63 32
80 38
100 39
125 44
160 48
200 48
250 53
315 57
400 60
500 65
630 67
800 69
1000 71
1250 78
1600 84
2000 91 c
2500 93 *
3150 94 *
4000 95 *
5000 96 *
Sound Transmission
Class (STC) 65
Sum of Deficiencies (dB)
29 Max. Deficiency (dB)
7 dB at 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Airborne sound transmission loss measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements”. In the graph: The solid line is the measured sound transmission loss for this specimen. The dashed line is the STC contour fitted to the measured values according to ASTM E413-10. The dotted line (may be above the displayed range) is 10 dB below the flanking limit established for this facility. For any frequency band where the measured transmission loss is above the dotted line, the reported value is potentially limited by flanking transmission via laboratory surfaces, and the true value may be higher than that measured. Bars at the bottom of the graph show deficiencies where the measured data are less than the reference contour as described in the fitting procedure for the STC, defined in ASTM E413-10. The shaded cells in the table and areas in the graph are outside the STC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. The reported values have been corrected according to the procedure outlined in ASTM E90-09. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level, in which case, the corrected values provide an estimate of the lower limit of airborne sound transmission loss.
5 4
7 5
4 4
20
30
40
50
60
70
80
90
100
63 125 250 500 1000 2000 4000
Airb
orne
Sou
nd T
rans
mis
sion
Los
s, T
L, in
dB
Frequency, f, in Hz
STC 65
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 87 of 101
ASTM E492 Test Results – Normalized Impact Sound Pressure Levels
Client: Nordic Engineered Wood Test ID: IIF-16-027
Specimen ID: A1-008253-34F Date of Test: April 13, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.9 23.0 to 23.1 33.0 to 33.4 Area S of test specimen: 17.85 m2
Lower 177.1 17.8 to 17.8 37.5 to 37.8 Mass per unit area: 242.8 kg/m2
f (Hz)
NISPL (dB)
50 61
63 60
80 59
100 56
125 57
160 56
200 57
250 55
315 57
400 56
500 52
630 52
800 51
1000 48
1250 41
1600 31
2000 26
2500 16 *
3150 15 *
4000 16 *
5000 17 *
Impact Insulation
Class (IIC)
59
Sum of Positive Differences (dB)
29 Max. Positive Difference (dB)
4 dB at 125, 200, 315 and 400 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted in accordance with the requirements of ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
3 4
3 4
2 4 4
1 2 2
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 59
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 88 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Small patch of Fermacell 2E31 on 70 mm precast concrete slab on 25 mm SonusWave placed on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-21SF
Construction Date April 13, 2016
Specimen Description Covering (small patch): Fermacell panels type 2E31 (EE20+WF10) measuring 500 mm wide x 1500 mm long x 30 mm thick were installed on top of OSB subfloor. The rabbeted edges of the Fermacell panels were not glued or screwed. The patch covered an approximate area of 4 m2 in the middle of the floor. Topping: A 70 mm (2-3/4”) precast concrete slab was placed on 25 mm Regupol® SonusWave™ which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-21SF
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
30 mm Fermacell 2E31 (EE20+WF10) 30 * 26.6 kg/m2 70 mm Precast Concrete Slab 70 3 202 165.8 kg/m2 25 mm Regupol® SonusWave™ 25 261 13.5 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 256 * 272.0 kg/m2 * Mass of small patch not added to total floor mass.
Test Results – Normalized Impact Sound Pressure Levels (Non-Standard)
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 89 of 101
Client Nordic Engineered Wood
Client: Nordic Engineered Wood Test ID: IIF-16-016
Specimen ID: A1-008253-21SF Date of Test: March 10, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.3 21.9 to 22.1 33.3 to 33.8 Area S of test specimen: 17.85 m2
Lower 176.9 21.0 to 21.1 36.9 to 37.7 Mass per unit area: 272.0 kg/m2
f (Hz)
NISPL (dB)
50 54
63 55
80 61
100 63
125 66
160 67
200 68
250 65
315 60
400 60
500 54
630 49
800 45
1000 37
1250 28 c
1600 20 c
2000 14 *
2500 15 *
3150 16 *
4000 18 *
5000 18 *
Impact Insulation
Class (IIC)
52
Sum of Positive Differences (dB)
30 Max. Positive Difference (dB)
8 dB at 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
3
6 7
8
5
1
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 52
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 90 of 101
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Small patch of laminate floor on AcoustiTech Premium on 70 mm precast concrete slab on 32 mm ROXUL ComfortBoard IS placed on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-22SF
Construction Date March 4, 2016
Specimen Description Covering (small patch): 8 mm click laminate flooring installed on AcousticTech Premium felt membrane. The patch covered an approximate area of 4 m2 in the middle of the floor. Topping: A 70 mm (2-3/4”) precast concrete slab was placed on Roxul® ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-22SF
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
8 mm Click Laminate Flooring 8 * 8.6 kg/m2 3 mm AcoustiTech Premium 3 * 0.5 kg/m2 70 mm Precast Concrete Slab 70 3 202 165.8 kg/m2 32 mm ROXUL ComfortBoard IS 32 78 4.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 244 * 248.5 kg/m2 * Mass of small patch not added to total floor mass.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 91 of 101
Test Results – Normalized Impact Sound Pressure Levels (Non-Standard)
Client: Nordic Engineered Wood Test ID: IIF-16-013
Specimen ID: A1-008253-22SF Date of Test: March 4, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.1 21.5 to 21.6 29.8 to 30.3 Area S of test specimen: 17.85 m2
Lower 176.9 19.6 to 19.8 34.4 to 34.6 Mass per unit area: 248.5 kg/m2
f (Hz)
NISPL (dB)
50 65
63 65
80 64
100 69
125 66
160 68
200 66
250 64
315 61
400 56
500 49
630 46
800 40
1000 34
1250 27 c
1600 17 *
2000 12 *
2500 13 *
3150 15 *
4000 16 *
5000 18 *
Impact Insulation
Class (IIC)
51
Sum of Positive Differences (dB)
28 Max. Positive Difference (dB)
8 dB at 100 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
8
5 7
5 3
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 51
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 92 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Small patch of laminate floor on Roberts Soft Stride on 70 mm precast concrete slab on 32 mm ROXUL ComfortBoard IS placed on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-23SF
Construction Date March 4, 2016
Specimen Description Covering (small patch): 8 mm click laminate flooring was installed on Roberts® Soft Stride closed cell foam. The patch covered an approximate area of 4 m2 in the middle of the floor. Topping: A 70 mm (2-3/4”) precast concrete slab was placed on Roxul® ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-23SF
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
8 mm Click Laminate Flooring 8 * 8.6 kg/m2 2 mm Roberts® Soft Stride Closed Cell Foam 2 * 0.1 kg/m2 70 mm Precast Concrete Slab 70 3 202 165.8 kg/m2 32 mm ROXUL ComfortBoard IS 32 78 4.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 243 * 248.1 kg/m2 * Mass of small patch not added to total floor mass.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 93 of 101
Test Results – Normalized Impact Sound Pressure Levels (Non-Standard)
Client: Nordic Engineered Wood Test ID: IIF-16-014
Specimen ID: A1-008253-23SF Date of Test: March 4, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.1 21.8 to 22.0 28.5 to 28.9 Area S of test specimen: 17.85 m2
Lower 176.9 19.6 to 19.9 34.3 to 34.8 Mass per unit area: 248.1 kg/m2
f (Hz)
NISPL (dB)
50 64
63 63
80 63
100 69
125 65
160 67
200 65
250 63
315 59
400 56
500 49
630 46
800 44
1000 39
1250 33
1600 23 c
2000 14 *
2500 14 *
3150 15 *
4000 17 *
5000 18 *
Impact Insulation
Class (IIC)
51
Sum of Positive Differences (dB)
24 Max. Positive Difference (dB)
8 dB at 100 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
8
4 6
4 2
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 51
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 94 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Small patch of laminate floor on Roberts Soft Stride on 70 mm precast concrete slab on 32 mm ROXUL ComfortBoard IS placed on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-24SF
Construction Date March 4, 2016
Specimen Description Covering (small patch): 10 mm Torlys Everest Premier Hardwood with attached cork underlay was installed on top of a 2 mm Roberts® Soft Stride closed cell foam. The patch covered an approximate area of 4 m2 in the middle of the floor. Topping: A 70 mm (2-3/4”) precast concrete slab was placed on Roxul® ComfortBoard IS which was placed on the CLT floor. The edge of the precast concrete slab was filled with insulation and taped. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-24SF
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
10 mm Torlys Everest Premier Hardwood 10 * 7.3 kg/m2 2 mm Roberts® Soft Stride Closed Cell Foam 2 * 0.1 kg/m2 70 mm Precast Concrete Slab 70 3 202 165.8 kg/m2 32 mm ROXUL ComfortBoard IS 32 78 4.1 kg/m2 131 mm CLT 5 ply 131 1 343 69.5 kg/m2 Total 245 * 246.8 kg/m2 * Mass of small patch not added to total floor mass.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 95 of 101
Test Results – Normalized Impact Sound Pressure Levels (Non-Standard)
Client: Nordic Engineered Wood Test ID: IIF-16-015
Specimen ID: A1-008253-24SF Date of Test: March 7, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 175.1 21.7 to 21.9 29.0 to 29.2 Area S of test specimen: 17.85 m2
Lower 176.9 20.7 to 20.7 35.5 to 35.7 Mass per unit area: 246.8 kg/m2
f (Hz)
NISPL (dB)
50 64
63 65
80 64
100 69
125 66
160 67
200 66
250 64
315 61
400 59
500 52
630 47
800 46
1000 39
1250 32
1600 24 c
2000 15 *
2500 14 *
3150 15 *
4000 17 *
5000 19 *
Impact Insulation
Class (IIC)
51
Sum of Positive Differences (dB)
27 Max. Positive Difference (dB)
8 dB at 100 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
8
5 6
5 3
10
20
30
40
50
60
70
80
90
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 51
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 96 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft (no sand) with glass fiber batts on top of a CLT 5 ply (131 mm)
Specimen ID A1-008253-32SF
Construction Date April 8, 2016
Specimen Description Covering (small patch): 8 mm click laminate flooring was installed on Roberts® Soft Stride closed cell foam. The patch covered an approximate area of 4 m2 in the middle of the floor. Topping: A 38 mm (1-1/2”) precast concrete slab was placed on 17 mm Regupol® SonusWave™ on top of OSB sheeting. The 18 mm (23/32”) OSB sheeting was screwed down with the long side perpendicular to 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens running along the short direction (3978 mm) and spaced at 610 mm (24”) o.c. and glued to strips of 10 mm thick rubber membranes at the bottom. 65 mm (2-1/2”) glass fibre insulation batts were placed in the cavity. CLT Floor: The specimen was composed of two cross-laminated timber (CLT) 5 ply panels (131 mm thick x 1989 mm wide x 4872 mm long) with a butt joint in the middle of the floor. The combined panels filled the entire floor opening of the test frame. The two CLT panels were joined using a 120 mm wide x 12 mm thick plywood strip spanning the full joint (4.9 m). The plywood strip was nailed with common nails 75 mm (3”) long spaced 305 mm (12”) on centre along the joint with beads of PL premium adhesive between the plywood strip and the CLT panels. The CLT floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the CLT floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the CLT.
Cross-section of A1-008253-32SF
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
8 mm Click Laminate Flooring 8 * 8.6 kg/m2 2 mm Roberts® Soft Stride Closed Cell Foam 2 * 0.1 kg/m2 38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 17 mm Regupol® SonusWave™ 17 157 8.1 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 65 mm Glass Fibre Insulation Batts *65 13 0.7 kg/m2 10 mm Rubber Membrane 10 21 7.7 kg/m2 131 mm CLT 5 ply 131 1 343 69.3 kg/m2 Total 288 * 271.3 kg/m2 * Mass of small patch not added to total floor mass.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 97 of 101
Test Results – Normalized Impact Sound Pressure Levels (Non-Standard)
Client: Nordic Engineered Wood Test ID: IIF-16-025
Specimen ID: A1-008253-32SF Date of Test: April 8, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.4 21.6 to 21.7 27.9 to 29.2 Area S of test specimen: 17.85 m2
Lower 176.9 17.9 to 18.0 36.7 to 36.9 Mass per unit area: 271.3 kg/m2
f (Hz)
NISPL (dB)
50 64
63 62
80 58
100 59
125 59
160 59
200 59
250 58
315 57
400 55
500 49
630 38
800 30
1000 23
1250 13 *
1600 10 *
2000 11 *
2500 12 *
3150 13 *
4000 15 *
5000 17 *
Impact Insulation
Class (IIC)
58
Sum of Positive Differences (dB)
29 Max. Positive Difference (dB)
5 dB at 100, 125, 160 and 200 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
5 5 5 5 4
3 2
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 58
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 98 of 101
Client Nordic Engineered Wood
1100 Ave des Canadiens-de-Montreal Montreal QC H3B 2S2
Specimen Small patch of laminate floor on Roberts Soft Stride on 38 mm precast concrete slab on 17 mm SonusWave placed on a OSB wood raft on top of glulam decking (89 mm)
Specimen ID A1-008253-35SF
Construction Date April 14, 2016
Specimen Description Covering (small patch): 8 mm click laminate flooring was installed on Roberts® Soft Stride closed cell foam. The patch covered an approximate area of 4 m2 in the middle of the floor. Topping: A 38 mm (1-1/2”) precast concrete slab was placed on 17 mm Regupol® SonusWave™ on top of 18 mm (23/32”) OSB sheeting. The OSB sheets screwed down with the long side perpendicular to the 38 mm x 64 mm (2x3) wood battens, with the narrow side down, using 50 mm (2”) long #10 wood screws spaced 150 mm (6”) o.c. along the edges and 200 mm (8”) o.c in the field. Wood battens spaced at 610 mm (24”) o.c. and glued to 10 mm rubber membrane were installed at the bottom. Fill: A 6 mil polyethylene sheet was put down on the CLT and the wood batten and resilient layer were installed directly on top (floating). 50 mm (2”) of dry silica sand (#71) filled the cavity of the batten leaving a 12 mm (1/2”) air gap between the OSB and the sand. Glulam Decking: The specimen was composed of 13 glued-laminated timber (glulam) decking panels nominally 384 mm wide x 89 mm thick x 3890 mm long (15” x 3-1/2” x 153”). The combined panels filled the entire floor opening of the test frame. The glulam decking panels were joined using 90 mm (3-1/2”) long common nails spaced 300 mm (12”) on centre along the joints. The glulam decking floor was resting on the lip of the test frame and was not fastened to the test frame. The air gaps between the edges of the glulam decking floor and the test frame were filled with glass fiber insulation and covered with cloth tape. Duct putty was installed around the lower perimeter of the test frame and the glulam.
Cross-section of A1-008253-35SF
Specimen Properties
Element Actual
thickness (mm)
Mass (kg) Mass/length, area or volume
8 mm Click Laminate Flooring 8 * 8.6 kg/m2 2 mm Roberts® Soft Stride Closed Cell Foam 2 * 0.1 kg/m2 38 mm Precast Concrete Slab 38 1 905 98.6 kg/m2 17 mm Regupol® SonusWave™ 17 157 8.1 kg/m2 18 mm OSB Tongue and Groove Sheeting 18 202 10.5 kg/m2 38 mm x 64 mm Wood Battens 64 47 0.3 kg/m 10 mm Rubber Membrane 10 21 7.7 kg/m2 50 mm Silica Sand (#71) *50 1 385 77.2 kg/m2 6 mil Polyethylene Sheeting 0 2 0.1 kg/m2 89 mm Glulam Decking 89 971 50.2 kg/m2 Total 246 * 251.5 kg/m2 * Mass of small patch not added to total floor mass.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 99 of 101
Test Results – Normalized Impact Sound Pressure Levels (Non-Standard)
Client: Nordic Engineered Wood Test ID: IIF-16-028
Specimen ID: A1-008253-35SF Date of Test: April 14, 2016
Room Volume (m³) Air Temperature (°C) Humidity (%)
Upper 174.9 23.5 to 23.7 22.6 to 28.3 Area S of test specimen: 17.85 m2
Lower 177.1 17.8 to 17.8 36.8 to 36.9 Mass per unit area: 251.5 kg/m2
f (Hz)
NISPL (dB)
50 61
63 59
80 59
100 55
125 57
160 55
200 56
250 53
315 53
400 49
500 41
630 35
800 30
1000 24
1250 13 *
1600 10 *
2000 11 *
2500 12 *
3150 14 *
4000 15 *
5000 17 *
Impact Insulation
Class (IIC)
62
Sum of Positive Differences (dB)
29 Max. Positive Difference (dB)
7 dB at 125 Hz
For a description of the test specimen and mounting conditions see text pages before. The results in this report apply only to the specific sample submitted for measurement. No responsibility is assumed for performance of any other specimen. Measurements of normalized impact sound pressure level (NISPL) were conducted following ASTM E492-09, “Standard Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine” but had a small patch of covering material instead of full surface coverage. In the graph: The solid line is the measured normalized impact sound pressure level (NISPL) for this specimen. The dashed line is the IIC contour fitted to the measured values according to ASTM E989-06. The dotted line is the background sound level measured in the receiving room during this test (may be below the displayed range). For any frequency where the measured NISPL is less than 10 dB above the dotted line, the reported values were adjusted as noted below. Bars at the bottom of the graph show positive differences; where the measured data are greater than the reference contour as defined in ASTM E989-06. Shaded cells in the table and areas in the graph are outside the IIC contour range. In the table: Values marked “c” indicate that the measured background level was between 5 dB and 10 dB below the combined receiving room level and background level. Values marked “*” indicate that the measured background level was less than 5 dB below the combined receiving room level and background level and the reported values of NISPL provide an estimate of the upper limit of normalized impact sound pressure level, according to the procedure outlined in ASTM E492-09. The reported values of NISPL have been corrected according to the procedure outlined in ASTM E492-09.
5 7
5 6
3 3
0
10
20
30
40
50
60
70
80
63 125 250 500 1000 2000 4000
Nor
mal
ized
Impa
ct S
ound
Pre
ssur
e Le
vel,
NIS
PL,
in d
B
Frequency, f, in Hz
IIC 62
| Construction | Acoustics Laboratory Client Report A1-008253.1
Page 100 of 101
APPENDIX: ASTM E90-09 – Airborne Sound Transmission – Floor Facility
Facility and Equipment: The NRC Construction Floor Sound Transmission Facility comprises two reverberation rooms (referred to in this report as the upper and lower rooms) with a moveable test frame between the rooms. Both rooms have an approximate volume of 175 m3. In each room, a calibrated Bruel & Kjaer condenser microphone (type 4166 or 4165) with preamp is moved under computer control to nine positions, and measurements are made in both rooms using an 8-channel National Instrument NI-4472 system installed in a computer. Each room has four bi-amped loudspeakers driven by separate amplifiers and noise sources. To increase randomness of the sound field, there are fixed diffusing panels in each room.
Test Procedure: Airborne sound transmission measurements were conducted in accordance with the requirements of ASTM E90-09, “Standard Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions”. Airborne sound transmission loss tests were performed in the forward (receiving room is the lower room) and reverse (receiving room is the upper room) directions. Results presented in this report are the average of the tests in these two directions. In each case, sound transmission loss values were calculated from the average sound pressure levels of both the source and receiving rooms and the average reverberation times of the receiving room. One-third octave band sound pressure levels were measured for 32 seconds at nine microphone positions in each room and then averaged to get the average sound pressure level in each room. Five sound decays were averaged to get the reverberation time at each microphone position in the receiving room; these reverberation times were averaged to get the average reverberation times for each room. Information on the flanking limit of the facility and reference specimen test results are available on request.
Significance of Test Results: ASTM E90-09 requires measurements in 1/3-octave bands in the frequency range 100 Hz to 5000 Hz. The standards recommend making measurements and reporting results over a larger frequency range, and this report presents such results, which may be useful for expert evaluation of the specimen performance. The precision of results outside the 100 to 5000 Hz range has not been established, but is expected to depend on laboratory-specific factors.
Sound Transmission Class (STC): The Sound Transmission Class (STC) was determined in accordance with ASTM E413-10, “Classification for Rating Sound Insulation”. It is a single number rating scheme intended to rate the acoustical performance of a partition element separating offices or dwellings. The higher the value of the rating, the better the performance. The rating is intended to correlate with subjective impressions of the sound insulation provided against the sounds of speech, radio, television, music, and similar sources of noise characteristic of offices and dwellings. The STC is of limited use in applications involving noise spectra that differ markedly from those referred to above (for example, heavy machinery, power transformers, aircraft noise, motor vehicle noise). Generally, in such applications it is preferable to consider the source levels and insulation requirements for each frequency band.
In Situ Performance: Ratings obtained by this standard method tend to represent an upper limit to what might be measured in a field test, due to structure-borne transmission (“flanking”) and construction deficiencies in actual buildings.
Client Report A1-008253.1 | Construction | Acoustics Laboratory
Page 101 of 101
APPENDIX: ASTM E492-09 – Light Impact Sound Transmission – Floor Facility
Facility and Equipment: The NRC Construction Floor Sound Transmission Facility comprises two reverberation rooms (referred to in this report as the upper and lower rooms) with a moveable test frame between the two rooms. Both rooms have an approximate volume of 175 m3. For impact sound transmission, only the lower room is used. A calibrated Bruel & Kjaer condenser microphone (type 4166 or 4165) with preamp is moved under computer control to nine positions, and measurements are made using an 8-channel National Instrument NI 4472 system installed in a computer. The room has 4 bi-amped loudspeakers driven by separate amplifiers and incoherent noise sources. To increase randomness of the sound field, there are fixed diffusing panels in the room.
Test Procedure: Impact sound transmission measurements were conducted in accordance with ASTM E492-09, “Standard Test Method for Laboratory Measurement of Impact Sound Transmission through Floor-Ceiling Assemblies Using the Tapping Machine”. This method uses a standard tapping machine placed at four prescribed positions on the floor. One-third octave band sound pressure levels were measured for 32 seconds at each microphone position in the receiving room and then averaged to get the average sound pressure level in the room. Five sound decays were averaged to get the reverberation time at each of the nine microphone positions in the receiving room; these nine reverberation times were averaged to get the spatial average reverberation times for the room. The spatial average sound pressure levels and reverberation times of the receiving room were used to calculate the Normalized Impact Sound Pressure Levels.
Significance of Test Results: ASTM E492-09 requires measurements in 1/3-octave bands in the frequency range 100 Hz to 3150 Hz. The standard recommends making measurements and reporting results over a larger frequency range, and this report presents such results, which may be useful for expert evaluation of the specimen performance. The precision of results outside the standard ranges has not been established, and is expected to depend on laboratory-specific factors such as room size and specimen dimensions.
Impact Insulation Class (IIC): The Impact Insulation Class (IIC) was determined in accordance with ASTM E989-06, “Standard Classification for Determination of Impact Insulation Class (IIC)”. It is a single number rating scheme intended to rate the effectiveness of floor-ceiling assemblies at preventing the transmission of impact sound from the standard tapping machine. A higher IIC value indicates a better floor performance.
In Situ Performance: Ratings obtained by this standard method tend to represent an upper limit to what might be measured in a field test, due to structure-borne transmission (“flanking”) and construction deficiencies in actual buildings.