2
Chloride CP-70Z 31 AC UPS System 5 to 250kVA - 1ph output Industrial Power for Business-Critical Continuity™ The Chloride CP-70Z industrial Uninterruptible Power Supply system (UPS) is the flagship product of Chloride Industrial Power. It combines conservative design topology with proven digital control technology to offer the best performances in any electrical and environmental condition. The Chloride CP range is designed to meet the stringent electrical and mechanical requi- rements in industrial environments. Each Chloride CP product is based on interchangeable sub-assemblies to allow full customization, in compliance with client’s technical specification and with project docu- mentation requirements. The Chloride CP range is designed to meet the harshest electrical and mechanical requirements in industrial environments. Each Chloride CP product is based on interchangeable sub-assemblies to allow full customization, in compliance with client’s technical specification and with project documentation requirements. Associated with an industrial stand-by battery, the Chloride CP-70Z 31 range is dedicated to protect critical industrial single phase AC equipments and processes from the damaging effects of power interruption and losses. Benefits n Tailor made systems to comply with all customer’s specifications. n Ruggedized solutions for demanding environments: extended temperatures, vibrations, dust, elevation, dripping water and moisture. n Efficient maintenance thanks to easy front- access to all vital modules of the system. Key Features n Reliability - Unique design which allows the UPS to continuously operate for at least 20 years at full load at a permanent 40°C ambient temperature. n On-line double conversion - UPS classified VFI SS 111 as per IEC62040-3 n Robust mechanical design - the system withstands vertical and horizontal acceleration stress tests up to 0.5g as standard n Galvanic isolation –input and output transformers as standard n Multilingual digital graphic display with embedded event log n Remote monitoring capabilities: Modbus, Profibus, DF1, ethernet, volt-free contact, monitoring software n Fully customized electrical and mechanical solutions – On demand design to comply with every standards (e.g. UL, ANSI, NEMA, IEC, CSA, ABS, DNV) n Full compatibility with lead-acid and nickel- cadmium batteries sealed or vented Applications The Chloride CP-70Z AC UPS System range suits all applications such as: n Oil and Gas offshore and onshore n Refining and petrochemical plants n Power generation plants n Transportation (rail, metro, tramway)

AC UPS System - usermanual.wiki · Charging characteristic UI according to DIN 41773 Ouput Available ratings see table above (at PF 0.8 lagging) AC Voltage 1 x 230V (220, 240) ; 1

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AC UPS System - usermanual.wiki · Charging characteristic UI according to DIN 41773 Ouput Available ratings see table above (at PF 0.8 lagging) AC Voltage 1 x 230V (220, 240) ; 1

Chloride CP-70Z 31 AC UPS System5 to 250kVA - 1ph output

Industrial Power forBusiness-Critical Continuity™

The Chloride CP-70Z industrial Uninterruptible Power Supply system (UPS) is the flagship product of Chloride Industrial Power. It combines conservative design topology with proven digital control technology to offer the best performances in any electrical and environmental condition.

The Chloride CP range is designed to meet the stringent electrical and mechanical requi-rements in industrial environments.Each Chloride CP product is based on interchangeable sub-assemblies to allow full customization, in compliance with client’s technical specification and with project docu-mentation requirements.

The Chloride CP range is designed to meet the harshest electrical and mechanical requirements in industrial environments.Each Chloride CP product is based on interchangeable sub-assemblies to allow full customization, in compliance with client’s technical specification and with project documentation requirements.

Associated with an industrial stand-by battery, the Chloride CP-70Z 31 range is dedicated to protect critical industrial single phase AC equipments and processes from the damaging effects of power interruption and losses.

Benefitsn Tailor made systems to comply with all

customer’s specifications.n Ruggedized solutions for demanding

environments: extended temperatures, vibrations, dust, elevation, dripping water and moisture.

n Efficient maintenance thanks to easy front-access to all vital modules of the system.

Key Featuresn Reliability - Unique design which allows

the UPS to continuously operate for at least 20 years at full load at a permanent 40°C ambient temperature.

n On-line double conversion - UPS classified VFI SS 111 as per IEC62040-3

n Robust mechanical design - the system withstands vertical and horizontal acceleration stress tests up to 0.5g as standard

n Galvanic isolation –input and output transformers as standard

n Multilingual digital graphic display with embedded event log

n Remote monitoring capabilities: Modbus, Profibus, DF1, ethernet, volt-free contact, monitoring software

n Fully customized electrical and mechanical solutions – On demand design to comply with every standards (e.g. UL, ANSI, NEMA, IEC, CSA, ABS, DNV)

n Full compatibility with lead-acid and nickel-cadmium batteries sealed or vented

ApplicationsThe Chloride CP-70Z AC UPS System range suits all applications such as:n Oil and Gas offshore and onshoren Refining and petrochemical plantsn Power generation plantsn Transportation (rail, metro, tramway)

Page 2: AC UPS System - usermanual.wiki · Charging characteristic UI according to DIN 41773 Ouput Available ratings see table above (at PF 0.8 lagging) AC Voltage 1 x 230V (220, 240) ; 1

Chloride CP-70Z 31 UPS System5 to 250 kVA - 1ph output

Industrial Power forBusiness-Critical Continuity™

Emerson, Business-Critical Continuity and Emerson Network Power are trademarks of

Emerson Electric Co. or one of its affiliated companies. ©2013 Emerson Electric Co.

CP70Z 31 AC UPS System-DSUK-Rev2-02/2013

Whi

le e

very

pre

caut

ion

has

been

take

n to

ens

ure

the

accu

racy

and

com

plet

enes

s of

this

lite

ratu

re, E

mer

son

Net

wor

k po

wer

ass

umes

no

resp

onsa

bilit

y an

d di

scla

ims

all l

iabi

lity

for d

amag

es re

sult

ing

from

use

of t

his

info

rmat

ion

or fo

r any

err

ors

or

omis

sion

s.

Emerson Network Power.The global leader in enablingBusiness-Critical Continuity™.

n AC Power

n Connectivity

n DC Power

n Embedded Computing

n Embedded Power

n Industrial Power

n Infrastructure Management & Monitoring

n Outside Plant

n Power Switching & Controls

n Precision Cooling

n Racks & Integrated Cabinets

n Services

Emerson Network Power IS S.A.S30 Avenue Montgolfier - BP90 - 69684 Chassieu Cedex FranceT: +33 (0)4 78 40 13 56 F: +33 (0)4 78 90 58 [email protected]

Technical DataInput

AC voltage 3 x 400V (380, 415)*

Voltage tolerance +/- 10%

Frequency 50Hz (60Hz)

Frequency tolerance +/- 5%

Intermediate DC Circuit

Nominal DC voltage 110 / 120 / 220 / 240 / 400 V

Voltage stability +/- 1% in float mode, input within tolerance+/-1.5% for parallel rectifiers

Voltage ripple 1% RMS, in float, battery connected

Current limitation I nominal

Charging characteristic UI according to DIN 41773

Ouput

Available ratings see table above (at PF 0.8 lagging)

AC Voltage 1 x 230V (220, 240) ; 1 x 110V (115, 120)*

Frequency 50Hz (60Hz)

Frequency stability

• with internal oscillator +/- 0.5%

• with reserve synchronism +/-3% (from 0.2 to 6% adjustable)

Frequency response <1Hz/s (0.1Hz/s for parallel systems)

Voltage stability (for 0-100% load variation)

• static +/-1% (+/-2% for parallel systems)

• dynamic +/-2% (+/-3% for parallel systems)

Overload inverter

• 1 minute 150% of nominal power

• 10 minutes 125% of nominal power

Short circuit clearance

• 100 ms 250% of nominal current

• 5 s 175% of nominal current

Distortion

• With 100% linear load 3%

• With 100% non-linear load Complies with IEC 62040-1-2

Allowable power factor 0.5 lagging to 0.5 leading

Allowable crest factor 3

Battery

Type Lead Acid or Nickel Cadmium vented or recombination

Autonomy From few minutes to several hours, as per customer’s requirement

Battery current limitation (typical, float & charge modes)

0.1C (Lead Acid battery)0.2C (Nickel Cadmium battery)

Battery current limitation (typical, boost mode)

0.05C (Lead acid battery)0.1C (Nickel Cadmium battery)

General Data

Operating temperature 0 to 40°C*

Storage temperature (°C) -20 to +70°C

Relative humidity (%) <90% non condensing

Operating altitude (m) 1000 m max without derating

Cooling Forced ventilation

Efficiency Up to 90% according to rating

External protection IP 20* according to IEC 60529

Noise (dB) 60 – 75 dB according to rating

Frame colour Grey RAL 7032

Dimensions Varying according to ratings & options

* other available on request

OptionsRectifier 12-pulse rectifier

Harmonic filterRipple filtersBlocking diodeOther input voltage (3x190 to 3x690VAC)Inrush current limitation to 8InSurge and Lightning protections

Battery Battery circuit protection boxBattery cabinetLow-voltage disconnect contactorBattery Management SystemBattery room temperature sensor

System Dual configurationsHot stand-by configurationInput / intermediate /output isolatorsDC/DC serial regulatorisolated DC/DC converterAC distributionEarth fault monitoringBackfeed protectionInternal lightingAnti-condensation heaterTemperature monitorSpecial cabinet identificationReserve transformerReserve stabilizer

Mechanical Up to IP42 externalTop cable entryOther frame colourAnti-seismic design

Communication Front-panel analog meters (72x72 class 1.5)TransducersAdditional Volt-free contactsRemote monitoring via ModbusRemote monitoring via other busPPVis monitoring softwarePassive or active mimic panel

Non-exhaustive list of options. Consult us for any other requirements.

Ratings - Output power (kVA) vs DC intermediate voltage (Vdc)110–120Vdc 220-240Vdc 400Vdc

2.5

5

7.5

10 10

15 15

20 20

25 25

30 30

40 40 40

50 50 50

60 60 60

80 80

100 100

120 120

Up to 250 kVA on request

Standards

Compliance IEC 62040 (-1, -2, -3) / 60146 (-1-1, -1-3, -2) / IEC 60950IEC 61000-6-2 - IEC 61000-6-4IEC 60529 / IEC 60439 / IEC 60076

Conformity Low voltage directive: 2006/95/ECEMC directive: 2004/108/ECCE Mark