72
TCF Series Installation and Operation Manual Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

AC Tech TCF Series Drives Installation & Operation Manual...AC Tech makes no warranty that its products are compatible with any other equipment, or to any specific application, to

  • Upload
    others

  • View
    9

  • Download
    0

Embed Size (px)

Citation preview

  • TCF SeriesInstallation and Operation Manual

    Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

    https://www.valinonline.com/catalog/manufacturers/lenze-americas/drives

  • Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • Table of Contents1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    1 .1 PRODUCTSCOVEREDINTHISMANUAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 .2 PRODUCTCHANGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 .3 WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 .4 RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 .5 SAFETYINFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 .6 CUSTOMERMODIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2 TCFDIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 TCFMODELDESIGNATIONCODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 TCFSPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 TCFRATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    6 .1 INSTALLATIONAFTERALONGPERIODOFSTORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 .2 EXPLOSIONPROOFAPPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    7 INPUTACPOWERREQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 .1 INPUTVOLTAGERATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117 .2 INPUTFUSING&DISCONNECTREQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 .3 INPUTWIRESIZEREQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 .4 INSTALLATIONACCORDINGTOEMCREQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    8 POWERWIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 .1 WIRINGFORSINGLEPHASEORTHREEPHASEINPUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    9 TCFPOWERWIRINGDIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1510 CONTROLWIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    10 .1 CONTROLWIRINGVS .POWERWIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1610 .2 TB-2ANDTB-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1610 .3 SURGESUPPRESSIONONRELAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1610 .4 START/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1610 .5 SPEED/TORQUEREFERENCESIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1710 .6 SPEEDREFERENCESELECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1710 .7 ANALOGOUTPUTSIGNALS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1910 .8 DRIVESTATUSDIGITALOUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    11 TCFCONTROLWIRINGDIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011 .1 TCFTERMINALSTRIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2011 .2 TWO-WIRESTART/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2111 .3 ALTERNATETWO-WIRESTART/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2211 .4 THREE-WIRESTART/STOPCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2311 .5 SPEEDPOTANDPRESETSPEEDCONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2411 .6 BIPOLARSPEEDCONTROL(-10to+10VDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    12 INITIALPOWERUPANDMOTORROTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2613 PROGRAMMINGTHETCFDRIVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    13 .1 ELECTRONICPROGRAMMINGMODULE(EPM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2913 .2 TCFDRIVEPERSONALITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    14 PARAMETERMENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3215 DESCRIPTIONOFPARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3616 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5717 TCFDISPLAYMESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    17 .1 SPEED/TORQUEDISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5917 .2 CHANGINGTHESPEEDREFERENCESOURCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6017 .3 STATUSANDWARNINGMESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    A APPENDIX-VECTORMODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62B APPENDIX-INPUTASSERTIONLEVEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

    Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • TCF Sub-Micro Drive

    INPUTPOWERTERMINALS

    OUTPUT(MOTOR)

    TERMINALS

    CONTROLTERMINAL

    STRIP

    3-DIGITLEDDISPLAY

    ELECTRONICPROGRAMMINGMODULE(EPM)

    PROGRAMMINGBUTTONS

    DCBUSTERMINALS

    Safety InformationAllsafetyinformationgivenintheseOperatingInstructionhavethesamelayout:

    Signal Word!(Characterizestheseverityofthedanger)

    Note(describesthedangerandinformsonhowtoproceed)

    Icon Signal Words

    Warningofhazardouselectricalvoltage

    DANGER! Warnsofimpending danger .Consequencesifdisregarded:Deathorsevereinjuries .

    Warningofageneraldanger

    WARNING! Warnsofpotential, very hazardous situations .Consequencesifdisregarded:Deathorsevereinjuries .

    Warningofdamagetoequipment

    STOP! Warnsofpotential damage to material and equipment .Consequencesifdisregarded:Damagetothecontroller/driveoritsenvironment .

    Information Note Designatesageneral,usefulnote .Ifyouobserveit,handlingthecontroller/drivesystemismadeeasier .

    Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 1 GENERAL

    1 .1 PRODUCTSCOVEREDINTHISMANUAL

    ThismanualcoverstheLenzeACTechTCFSeriesVariableFrequencyDrive .

    1 .2 PRODUCTCHANGES

    LenzeACTechCorporationreservestherighttodiscontinueormakemodificationstothedesignofitsproductswithoutpriornotice,andholdsnoobligationtomakemodificationstoproductssoldpreviously .LenzeACTechalsoholdsnoliabilityforlossesofanykindwhichmayresult from this action . Instruction manuals with the most up-to-date information areavailablefordownloadfromtheLenzeACTechwebsite .

    1 .3 WARRANTY

    LenzeACTechCorporationwarrantstheTCFSeriesACmotorcontroltobefreeofdefectsinmaterialandworkmanshipforaperiodof24monthsfromthedateofshipmentfromLenzeACTech'sfactory .IfaTCFmotorcontrol,undernormaluse,becomesdefectivewithinthestatedwarrantytimeperiod,contactLenzeACTech'sServiceDepartmentforinstructionsonobtainingawarranty replacementunit .LenzeACTechreserves theright tomake thefinal determination as to the validity of a warranty claim, and sole obligation is to repairorreplaceonlycomponentswhichhavebeenrendereddefectiveduetofaultymaterialorworkmanship .Nowarrantyclaimwillbeacceptedforcomponentswhichhavebeendamagedduetomishandling,improperinstallation,unauthorizedrepairand/oralterationoftheproduct,operationinexcessofdesignspecificationsorothermisuse,orimpropermaintenance .LenzeACTechmakesnowarrantythatitsproductsarecompatiblewithanyotherequipment,ortoanyspecificapplication,towhichtheymaybeappliedandshallnotbeheldliableforanyotherconsequentialdamageorinjuryarisingfromtheuseofitsproducts .Thiswarrantyisinlieuofallotherwarranties,expressedorimplied .Nootherperson,firmorcorporationisauthorizedtoassume,forLenzeACTech,anyotherliabilityinconnectionwiththedemonstrationorsaleofitsproducts .

    1 .4 RECEIVING

    Inspectallcartonsfordamagewhichmayhaveoccurredduringshipping .Carefullyunpackequipmentandinspectthoroughlyfordamageorshortage .Reportanydamagetocarrierand/orshortagestosupplier .Allmajorcomponentsandconnectionsshouldbeexaminedfordamageandtightness,withspecialattentiongiventoPCboards,plugs,knobsandswitches .

    1 .5 SAFETYINFORMATION

    GENERALSomepartsofLenzeACTechcontrollerscanbeelectricallyliveandsomesurfacescanbehot .Non-authorizedremovaloftherequiredcover,inappropriateuse,andincorrectinstallationoroperationcreatestheriskofsevereinjurytopersonnelordamagetoequipment .Alloperationsconcerningtransport,installation,andcommissioningaswellasmaintenancemust be carried out by qualified, skilled personnel who are familiar with the installation,assembly,commissioning,andoperationofvariablefrequencydrivesandtheapplicationforwhichitisbeingused .

    1Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • INSTALLATIONEnsureproperhandlingandavoidexcessivemechanicalstress .Donotbendanycomponentsand do not change any insulation distances during transport, handling, installation ormaintenance . Do not touch any electronic components or contacts . This drive containselectrostatically sensitive components, which can easily be damaged by inappropriatehandling .Staticcontrolprecautionsmustbeadheredtoduringinstallation,testing,servicingandrepairingofthisdriveandassociatedoptions .Componentdamagemayresultifproperproceduresarenotfollowed .ThisdrivehasbeentestedbyUnderwritersLaboratory(UL)andisanapprovedcomponentincompliancewithUL508SafetyStandard .

    Warnings!

    •SuitableforuseonacircuitasdescribedinSection7 .0ofthismanual .•Useminimum75°Ccopperwireonly .•Shallbeinstalledinapollutiondegree2macro-environment .

    Thisdrivemustbeinstalledandconfiguredinaccordancewithbothnationalandinternationalstandards .LocalcodesandregulationstakeprecedenceoverrecommendationsprovidedinthisandotherLenzeACTechdocumentation .TheTCFdriveisconsideredacomponentforintegrationintoamachineorprocess .Itisneitheramachinenoradevice ready foruse inaccordancewithEuropeandirectives (referencemachinerydirectiveandelectromagneticcompatibilitydirective) .Itistheresponsibilityoftheendusertoensurethatthemachinemeetstheapplicablestandards .

    ELECTRICALCONNECTIONWhenworkingonlivedrivecontrollers,applicablenationalsafetyregulationsmustbeobserved .Theelectricalinstallationmustbecarriedoutaccordingtotheappropriateregulations(e .g .cablecross-sections,fuses,protectiveearth[PE]connection) .Whilethisdocumentdoesmakerecommendationsinregardstotheseitems,nationalandlocalcodesmustbeadheredto .ThedocumentationcontainsinformationaboutinstallationincompliancewithEMC(shielding,grounding,filtersandcables) .ThesenotesmustalsobeobservedforCE-markedcontrollers .ThemanufacturerofthesystemormachineisresponsibleforcompliancewiththerequiredlimitvaluesdemandedbyEMClegislation .

    APPLICATIONThedrivemustnotbeusedasasafetydeviceformachineswherethereisariskofpersonalinjuryormaterialdamage .EmergencyStops,over-speedprotection,accelerationanddecelerationlimits,etcmustbemadebyotherdevicestoensureoperationunderallconditions .The drive does feature many protection devices which are aimed at protecting the driveandthedrivenequipmentbygeneratingafaultandshuttingthedriveandmotordownbyremovingpower .Mainspowervariancescanalsoresultinshutdownofthedrive .Whenthefaultconditiondisappearsoriscleared,thedrivecanbeconfiguredtoautomaticallyrestart,it is theresponsibilityof theuserand/orOEMand/or integrator toensurethat thedrive isconfiguredforsafeoperation .

    1 .6 CUSTOMERMODIFICATION

    LenzeACTech,itssalesrepresentativesanddistributors,welcometheopportunitytoassistourcustomersinapplyingourproducts .Manycustomizingoptionsareavailabletoaidinthisfunction .LenzeACTechcannotassumeresponsibilityforanymodificationsnotauthorizedbyitsengineeringdepartment .

    2Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 2 TCF DIMENSIONS

    MountingTabDetail

    IfR<6 .30"(160)S=0 .19"(5)T=0 .38"(10)U=0 .18"(5)V=0 .66"(17)

    IfR=6 .30"(160)S=0 .28"(7)T=0 .50"(13)U=0 .24"(6)V=0 .90"(23)

    D

    H

    W

    R

    P

    T

    U

    V

    SDia. Slot

    3Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • HP kWINPUT

    VOLTAGEMODEL H W D P R

    0 .5 0 .37208/240 TF205Y 5 .75(146) 2 .88(73) 3 .94(100) 0 .80(20) 4 .37(111)

    400/480 TF405 5 .75(146) 3 .76(96) 5 .24(133) 1 .90(48) 4 .37(111)

    1 0 .75

    208/240 TF210Y 5 .75(146) 2 .88(73) 4 .74(120) 1 .60(41) 4 .37(111)

    208/240 TF210 5 .75(146) 2 .88(73) 4 .74(120) 1 .60(41) 4 .37(111)

    400/480 TF410 5 .75(146) 3 .76(96) 5 .24(133) 1 .90(48) 4 .37(111)

    480/590 TF510 5 .75(146) 3 .76(96) 5 .24(133) 1 .90(48) 4 .37(111)

    1 .5 1 .1

    208/240 TF215Y 5 .75(146) 3 .76(96) 5 .24(133) 1 .90(48) 4 .37(111)

    208/240 TF215 5 .75(146) 2 .88(73) 5 .74(146) 2 .60(66) 4 .37(111)

    400/480 TF415 5 .75(146) 3 .76(96) 5 .24(133) 1 .90(48) 4 .37(111)

    2 1 .5

    208/240 TF220Y 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 4 .37(111)

    208/240 TF220 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 4 .37(111)

    400/480 TF420 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 4 .37(111)

    480/590 TF520 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 4 .37(111)

    3 2 .2

    208/240 TF230Y 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 3 .25(83)

    208/240 TF230 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 3 .25(83)

    400/480 TF430 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 3 .25(83)

    480/590 TF530 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 3 .25(83)

    5 4 .0

    208/240 TF250 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 3 .25(83)

    400/480 TF450 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 3 .25(83)

    480/590 TF550 5 .75(146) 3 .76(96) 6 .74(171) 3 .40(86) 3 .25(83)

    7 .5 5 .5

    208/240 TF275 7 .75(197) 5 .02(128) 7 .18(182) 3 .40(86) 4 .81(122)

    400/480 TF475 7 .75(197) 5 .02(128) 7 .18(182) 3 .40(86) 4 .81(122)

    480/590 TF575 7 .75(197) 5 .02(128) 7 .18(182) 3 .40(86) 4 .81(122)

    10 7 .5

    208/240 TF2100 7 .75(197) 5 .02(128) 7 .18(182) 3 .40(86) 4 .81(122)

    400/480 TF4100 7 .75(197) 5 .02(128) 7 .18(182) 3 .40(86) 4 .81(122)

    480/590 TF5100 7 .75(197) 5 .02(128) 7 .18(182) 3 .40(86) 4 .81(122)

    4Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 3 TCF MODEL DESIGNATION CODETheTCFmodelnumbergivesafulldescriptionofthebasicdriveunit .

    EXAMPLE:TF210Y=TCFSeries,208/240Vac,1HP,singleorthreephaseinput

    TF 2 10 Y

    Series:

    TF=TCFSeriesSensorlessVectorVariableSpeedACMotorDrive

    Input Voltage:

    2=208/240Vac(For208,230,and240Vac;50or60Hz)

    4=400/480Vac(For380,415,440,460and480Vac;50or60Hz)

    5=480/590Vac(For440,460,480,575and600Vac;50or60Hz)

    Rating:

    05=½HP(0 .37kW) 30 = 3HP(2 .2kW)

    10=1HP(0 .75kW) 50 = 5HP(4 .0kW)

    15=1½HP(1 .1kW) 75 = 7½HP(5 .5kW)

    20=2HP(1 .5kW) 100 = 10HP(7 .5kW)

    Input Phase:

    Y=Singleorthreephaseinput . No character indicates three phase input only

    5Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 4 TCF SPECIFICATIONS

    Specification Range

    StorageTemperature -20°to70°C

    AmbientOperatingTemperature 0°to50°C(derate2 .5%per°Cabove50°)

    AmbientHumidity <95%(non-condensing)

    MaximumAltitude 3300ft .(1000m)abovesealevel(derate5%peradditional3300ft .)

    InputLineVoltages 208/240Vac,400/480Vac,480/590Vac

    InputVoltageTolerance +10%,-15%

    InputFrequencyTolerance 48to62Hz

    OutputWaveForm SineCodedPWM

    OutputFrequency 0-240Hz(consultfactoryforhigheroutputfrequencies)

    CarrierFrequency 2kHz,4kHz,8kHz(8kHzrequiresderating;seeparameterP02)

    ServiceFactor 1 .00(upto4kHzcarrier;deratefor8kHz;seeparameterP02)

    Efficiency Upto98%

    PowerFactor(displacement) 0 .96orbetter

    OverloadCurrentCapacity 150%for60seconds,200%for25seconds

    SpeedReferenceFollower 0-10VDC,4-20mA

    ControlVoltage 15VDC

    PowerSupplyforAuxiliaryRelays 50mAat12VDC

    AnalogOutput 0-10VDCor2-10VDC:Proportionaltospeed,load,ortorque

    DigitalOutputs Open-collectoroutputs:50mAat30VDC

    EarthLeakageCurrent <3 .5mAtoearthground

    6Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 5 TCF RATINGS

    MODELNUMBER(NOTE1)

    FORMOTORSRATED

    INPUT(50-60Hz) OUTPUTHEATLOSS

    (WATTS)(NOTE5)

    INPUTPHASE

    CURRENT(AMPS)

    POWER(kVA)

    CURRENT(AMPS)HP kW

    TF200YSERIES(NOTE2) 208/240Vac 0-200/230Vac

    TF205Y 0 .5 0 .37 1 5 .4/4 .7 1 .2 2 .5/2 .2 26

    TF205Y 0 .5 0 .37 3 3 .1/2 .7 1 .1 2 .5/2 .2 26

    TF210Y 1 0 .75 1 10 .6/9 .2 2 .2 4 .8/4 .2 49

    TF210Y 1 0 .75 3 5 .8/5 .1 2 .1 4 .8/4 .2 49

    TF215Y 1 .5 1 .1 1 13 .9/12 .0 2 .9 6 .9/6 .0 82

    TF215Y 1 .5 1 .1 3 8 .0/6 .9 2 .9 6 .9/6 .0 82

    TF220Y 2 1 .5 1 14 .8/12 .9 3 .1 7 .8/6 .8 86

    TF220Y 2 1 .5 3 9 .1/7 .9 3 .2 7 .8/6 .8 86

    TF230Y 3 2 .2 1 19 .7/17 .1 4 .1 11 .0/9 .6 130

    TF230Y 3 2 .2 3 12 .4/10 .8 4 .4 11 .0/9 .6 130

    TF200SERIES(NOTE2) 208/240Vac 0-200/230Vac

    TF210 1 0 .75 3 5 .8/5 .1 2 .1 4 .8/4 .2 41

    TF215 1 .5 1 .1 3 8 .0/6 .9 2 .9 6 .9/6 .0 69

    TF220 2 1 .5 3 9 .1/7 .9 3 .3 7 .8/6 .8 78

    TF230 3 2 .2 3 12 .4/10 .8 4 .5 11 .0/9 .6 117

    TF250 5 4 .0 3 19 .6/17 .1 7 .1 17 .5/15 .2 187

    TF275 7 .5 5 .5 3 28/25 10 .3 25/22 286

    TF2100 10 7 .5 3 34/32 13 .1 30/28 379

    NOTE1:RefertoSection3formodelnumberbreakdown .NOTE2:Thehighercurrentratingsarefor208Vacinputandthelowercurrentratingsarefor240Vacinput .NOTE5:Valuesareworst-case(nottypical)for4kHzcarrierfrequencyatfullspeedandfullload .

    7Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • MODELNUMBER(NOTE1)

    FORMOTORSRATED

    INPUT(50-60Hz) OUTPUT HEATLOSS(WATTS)(NOTE5)

    INPUTPHASE

    CURRENT(AMPS)

    POWER(kVA)

    CURRENT(AMPS)HP kW

    TF400SERIES(NOTE3) 400/480Vac 0-400/460Vac

    TF405 0 .5 0 .37 3 1 .6/1 .4 1 .1 1 .3/1 .1 26

    TF410 1 0 .75 3 2 .9/2 .5 2 .1 2 .4/2 .1 40

    TF415 1 .5 1 .1 3 4 .0/3 .6 3 .0 3 .4/3 .0 56

    TF420 2 1 .5 3 4 .6/4 .0 3 .3 3 .9/3 .4 67

    TF430 3 2 .2 3 6 .2/5 .4 4 .5 5 .5/4 .8 100

    TF450 5 4 .0 3 10 .6/8 .8 7 .1 9 .4/7 .8 168

    TF475 7 .5 5 .5 3 14 .2/12 .4 10 .3 12 .6/11 .0 254

    TF4100 10 7 .5 3 18 .1/15 .8 13 .1 16 .1/14 .0 310

    TF500SERIES(NOTE4) 480/590Vac 0-460/575Vac

    TF510 1 0 .75 3 2 .2/2 .0 1 .9/2 .0 1 .9/1 .7 40

    TF520 2 1 .5 3 4 .0/3 .5 3 .3/3 .6 3 .4/3 .0 67

    TF530 3 2 .2 3 4 .7/4 .7 3 .9/4 .8 4 .2/4 .2 100

    TF550 5 3 .7 3 7 .4/7 .4 6 .1/7 .5 6 .6/6 .6 168

    TF575 7 .5 5 .5 3 11 .2/11 .2 9 .3/11 .4 9 .9/9 .9 254

    TF5100 10 7 .5 3 13 .7/13 .7 11 .4/14 .0 12 .2/12 .2 310

    NOTE1:RefertoSection3formodelnumberbreakdown .NOTE3:Thehighercurrentratingsarefor400Vacinputandthelowercurrentratingsarefor480Vacinput .NOTE4:Thehighercurrentratingsarefor480Vacinputandthelowercurrentratingsarefor590Vacinput .NOTE5:Valuesareworst-case(nottypical)for4kHzcarrierfrequencyatfullspeedandfullload

    8Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 6 INSTALLATION

    NOTE

    TCF Series drives are intended for inclusion within other equipment, byprofessionalelectricalinstallersaccordingtoEN61000-3-2 .TheTCFdriveisnotintendedforstand-aloneoperation

    WARNING!

    Drives must NOT be installed where subjected to adverse environmentalconditionssuchas:combustible,oily,orhazardousvaporsordust;excessivemoistureordirt;vibration;excessiveambienttemperatures .ConsultLenze-AC Tech for more information on the suitability of a drive to a particularenvironment .

    TCFmodelsaresuitableforULpollutiondegree2environmentonly,andMUSTbeinstalledinanelectricalenclosurewhichwillprovidecompletemechanicalprotectionandwillmaintainthe internal temperaturewithin thedrive’sambientoperating temperature rating .AlldrivemodelsMUSTbemountedinaverticalpositionforproperheatsinkcooling .

    Maintainaminimumspacingaroundthedriveofatleast1inch(25mm)oneachsideand2inches(50mm)onthetopandbottomforunitsratedupto5HP(3 .7kW) .Forunitsrated7 .5-10HP(5 .5-7 .5kW),maintainatleast2inches(50mm)oneachsideand4inches(100mm)onthetopandbottom .Allowmorespacingifthedriveismountednexttootherheat-producingequipment .Donotmountdrivesaboveotherdrivesorheatproducingequipment .Fansorblowersshouldbeusedtoinsurepropercoolingintightquarters .

    Inordertoproperlysizeanenclosure,theheatgeneratedbythedrive(s)mustbeknown .RefertotheHEATLOSScolumninSection5-TCFRATINGS .Anenclosuremanufacturercanthendeterminetherequiredenclosuresizebasedonthetotalheatgeneratedinsidetheenclosure(fromthedrive(s)andotherheatsources),themaximumallowabletemperatureinside the enclosure, the maximum ambient temperature outside the enclosure, and theenclosureproperties .

    The TCF Series is UL approved for solid state motor overload protection . Therefore, aseparatethermaloverloadrelayisnotrequiredforsinglemotorapplications .

    9Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 6 .1 INSTALLATIONAFTERALONGPERIODOFSTORAGE

    STOP!

    SeveredamagetothedrivecanresultifitisoperatedafteralongperiodofstorageorinactivitywithoutreformingtheDCbuscapacitors!

    Ifinputpowerhasnotbeenappliedtothedriveforaperiodoftimeexceedingthreeyears(duetostorage,etc),theelectrolyticDCbuscapacitorswithinthedrivecanchangeinternally,resultinginexcessiveleakagecurrent .Thiscanresultinprematurefailureofthecapacitorsifthedriveisoperatedaftersuchalongperiodofinactivityorstorage .

    Inordertoreformthecapacitorsandpreparethedriveforoperationafteralongperiodofinactivity,applyinputpowertothedrivefor8hourspriortoactuallyoperatingthemotor .

    6 .2 EXPLOSIONPROOFAPPLICATIONS

    Explosionproofmotorsthatarenotratedforinverteruselosetheircertificationwhenusedforvariablespeed .Duetothemanyareasofliabilitythatmaybeencounteredwhendealingwiththeseapplications,thefollowingstatementofpolicyapplies:

    “Lenze AC Tech inverter products are sold with no warranty of fitness for a particular purpose or warranty of suitability for use with explosion proof motors. Lenze AC Tech accepts no responsibility for any direct, incidental or consequential loss, cost, or damage that may arise through the use of its AC inverter products in these applications. The purchaser expressly agrees to assume all risk of any loss, cost, or damage that may arise from such application."

    10Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 7 INPUT AC POWER REQUIREMENTS

    DANGER!

    Hazard of electrical shock! Capacitors retain charge after they've beenremoved . Disconnect incoming power and wait until the voltage betweenterminalsB+andB-is0VDCbeforeservicingthedrive .

    Theinputvoltagemustmatchthenameplatevoltageratingofthedrive .Voltagefluctuationmustnotvarybygreaterthan10%overvoltageor15%undervoltage .

    NOTE

    Driveswithdual inputvoltageratingsmustbeprogrammedforthepropersupply voltage (refer to Parameter 01 - LINE VOLTAGE SELECTION inSection15-DESCRIPTIONOFPARAMETERS) .

    Thedrive issuitable foruseonacircuit capableofdeliveringnotmore than5,000RMSsymmetricalamperesat5HP(4 .0kW)andbelow,and18,000RMSsymmetricalamperesat7 .5-10HP(5 .5-7 .5kW),atthedrive’sratedvoltage .

    IfthekVAratingoftheACsupplytransformerisgreaterthan10timestheinputkVAratingofthedrive(s),anisolationtransformeror2-3%inputlinereactormustbeaddedtothelinesideofthedrive(s) .

    Threephasevoltageimbalancemustbelessthan2 .0%phasetophase .Excessivephasetophaseimbalancecancauseseveredamagetothedrive’spowercomponents .

    Motorvoltageshouldmatchlinevoltageinnormalapplications .Thedrive’smaximumoutputvoltagewillequaltheinputvoltage .Useextremecautionwhenusingamotorwithavoltageratingwhichisdifferentfromtheinputlinevoltage .

    7 .1 INPUTVOLTAGERATINGS

    TF200 Seriesdrivesareratedfor208/240Vac,threephase,50-60Hzinput .Thedrivewillfunctionwithinputvoltagesof208to240Vac(+10%,-15%)at48to62Hz .

    TF200Y Seriesdrivesareratedfor208/240Vac,singleorthreephase,50-60Hzinput .Thedrivewillfunctionwithinputvoltageof208to240Vac(+10%,-15%)at48to62Hz .

    TF400 Seriesdrivesareratedfor400/480Vacthreephase,50-60Hzinput .Thedrivewillfunctionwithinputvoltagesof400to480Vac(+10%,-15%)at48to62Hz .

    TF500 Seriesdrivesareratedfor480/590Vac,threephase,50-60Hzinput,andwillfunctionwithinputvoltagesof480to590Vac(+10%,-15%)at48to62Hz .

    NOTE

    Parameter 01 - LINE VOLTAGE SELECTION must be programmedaccordingtotheappliedinputvoltage .RefertoSection15-DESCRIPTIONOFPARAMETERS .

    11Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 7 .2 INPUTFUSING&DISCONNECTREQUIREMENTS

    AcircuitbreakeroradisconnectswitchwithfusesmustbeprovidedinaccordancewiththeNationalElectricCode(NEC)andall localcodes .Refer to the following tables forproperfuse/circuitbreakerratingsandwiresizes .

    INPUT FUSE & CIRCUIT BREAKER RATINGS

    208/240Vac,1phase 208/240Vac,3phase 400/480Vac,3phase 480/590Vac,3phase

    MODEL RATING MODEL RATING MODEL RATING MODEL RATING

    TF205Y 10A TF205Y 10A TF405 10A

    TF210Y 15A TF210(Y) 10A TF410 10A TF510 10A

    TF215Y 20A TF215(Y) 12/10A TF415 10A

    TF220Y 25/20A TF220(Y) 15/12A TF420 10A TF520 10A

    TF230Y 30/25A TF230(Y) 20/15A TF430 10A TF530 10A

    TF250 30/25A TF450 15A TF550 12A

    TF275 45/40A TF475 20A TF575 20A

    TF2100 50/50A TF4100 30/25A TF5100 20A

    NOTE

    • Applicable national and local electrical codes take precedence overrecommendationsinthesetables .

    • UseULClassCCfast-acting,current limiting type fuses .Select fuseswith low I2T values, rated at 200,000 AIC . Recommended fuses areBussmanKTK-R,JJN,andJJS .Similarfuseswithequivalentratingsbyothermanufacturersmayalsobeacceptable .

    WARNING!

    This product can cause a DC current in the protective conductor . Wherearesidualcurrentdevice(RCD) isused forprotection incaseofdirectorindirectcontact,onlyanRCDofTypeB isallowedon thesupplysideofthisproduct .Otherwise,anotherprotectivemeasureshallbeapplied,suchasseparation from theenvironmentbydoubleor reinforced insulation,orisolationfromthesupplysystembyatransformer .

    ObservethefollowingwhenusingRCDs:

    1 . OnlyinstalltheRCDbetweenthesupplymainsanddrivecontroller .2 . TheRCDcanbeactivatedby:

    • capacitiveleakagecurrentsbetweenthecablescreensduringoperation(especiallywithlong,screenedmotorcables)

    • connectingseveraldrivestothemainsatthesametime• additionalRFIfilters

    12Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 7 .3 INPUTWIRESIZEREQUIREMENTS

    INPUT WIRE SIZE REQUIREMENTS

    208/240Vac,1phase 208/240Vac,3phase 400/480Vac,3phase 480/590Vac,3phase

    MODEL AWG mm2 MODEL AWG mm2 MODEL AWG mm2 MODEL AWG mm2

    TF205Y 14 1 .5 TF205Y 14 1 .5 TF405 14 1 .5

    TF210Y 14 1 .5 TF210(Y) 14 1 .5 TF410 14 1 .5 TF510 14 1 .5

    TF215Y 12 2 .5 TF215(Y) 14 1 .5 TF415 14 1 .5

    TF220Y 12 2 .5 TF220(Y) 14 1 .5 TF420 14 1 .5 TF520 14 1 .5

    TF230Y 10 4 .0 TF230(Y) 12 2 .5 TF430 14 1 .5 TF530 14 1 .5

    TF250 10 4 .0 TF450 14 1 .5 TF550 14 1 .5

    TF275 8 6 .0 TF475 12 2 .5 TF575 14 1 .5

    TF2100 8 10 TF4100 10 4 .0 TF5100 12 2 .5

    7 .4 INSTALLATIONACCORDINGTOEMCREQUIREMENTS

    ThisdrivecanbeinstalledtomeettheEuropeanstandardsforElectromagneticCompatibility(EMC)requirements .Theserequirementsgovernthepermissibleelectromagneticemissionsandimmunity,bothradiatedandconducted,ofadrivesystem .

    The EMC requirements apply to the final installation in its entirety, not to the individualcomponents used . Because every installation is different, the recommended installationshould follow these guidelines as a minimum . Additional equipment (such as ferrite coreabsorbers on power conductors) or alternative wiring practices may be required to meetconformanceinsomeinstallations .

    Filter:Theinputtothedrive(orgroupofdrives)mustincludeafiltertoreducetheelectricalnoisereflectedbacktotheACLine .TomeettheindustrialstandardssetbytheEU,EN61800-3forconductedemissionsandEN55011forradiatedemissionstoclassAcompliance,thedrivemustbeinstalledwithanappropriatefilterandamaximummotorcablelengthof10m .

    EMCCompliancewithEN61800-3/A11

    SM01 1

    B

    C

    DA

    E

    Installation:Shieldedcablemustbeusedforallcontrolandpowercablesandexposedwiringmustbekeptasshortaspossible .

    AScreenclamps

    BControlcable

    CLow-capacitancemotorcable

    (core/core<75pF/m,core/screen<150pF/m)

    DElectricallyconductivemountingplate

    EFilter

    13Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 8 POWER WIRING

    DANGER!

    Hazardofelectricalshock!Capacitors retain charge after power is removed . Disconnect incomingpowerandwaituntil thevoltagebetween terminalsB+andB- is0VDCbeforeservicingthedrive .

    Notedriveinputandoutputcurrentratingsandcheckapplicableelectricalcodesforrequiredwire typeandsize,grounding requirements,over-currentprotection,and incomingpowerdisconnect,beforewiringthedrive .Sizeconservativelytominimizevoltagedrop .

    Refer toSection9-TCFPOWERWIRINGDIAGRAMfor informationon torqueandwirestrippingrequirementsforpowerwiring .

    Input fusing and a power disconnect switch or contactor MUST be wired in series withterminalsL1,L2,andL3forthreephaseinputmodels .For208/240Vacsinglephaseinputmodels,useterminalsL1andL3 .Thisdisconnectmustbeusedtopowerdownthedrivewhenservicing,orwhenthedriveisnottobeoperatedforalongperiodoftime,butshouldnotbeusedtostartandstopthemotor .

    Repetitive cycling of a disconnect or input contactor (more than once every two minutes) may cause damage to the drive.

    8 .1 WIRINGFORSINGLEPHASEORTHREEPHASEINPUT

    Ifthedriveisratedforsingleandthreephaseinput(TF200Ymodels),wiretoterminalsL1andL3forsinglephaseinput,orwiretoterminalsL1,L2,andL3forthreephaseinput .

    Ifthedriveisratedforthreephaseinput,wiretheinputtoterminalsL1,L2,andL3 .

    Allthreepoweroutputwires,fromterminalsT1,T2,andT3tothemotor,mustbekepttightlybundledandruninaseparateconduitawayfromallotherpowerandcontrolwiring .Itisnotrecommended to install contactors or disconnect switches between the drive and motor .Operatingsuchdeviceswhilethedriveisrunningcanpotentiallycausedamagetothedrive'spowercomponents .Ifsuchadeviceisrequired,itshouldonlybeoperatedwhenthedriveisinaSTOPstate .Ifthereispotentialforthedevicetobeopenedwhilethedriveisrunning,thedrivemustbeprogrammedforCOASTtostop(refertoParameter04-STOPMETHOD),andanauxiliarycontactonthedevicemustbeinterlockedwiththedrive'sruncircuit .Thiswillgivethedriveastopcommandatthesametimethedeviceopens,andwillnotallowthedrivetostartagainuntilthedeviceisclosed .

    14Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 9 TCF POWER WIRING DIAGRAMTHREEPHASEINPUT

    (ALLSERIES)

    L1 L2 L3

    OUTPUT(ALLSERIES)

    3PHASEACMOTOR

    DCBUSVOLTAGE

    T1 T2 T3 B- B+

    +

    SINGLEPHASEINPUT(TF200YSERIES)

    L1 L2 L3Forallothermodels,

    useoutputtorquevalues .

    TF230Y&TF250only

    7 .0lb-in/0 .8Nm0 .24in/6mm

    0 .5-5HP

    (0 .37-3 .7kW)

    4 .5lb-in/0 .5Nm

    0 .24in/6mm

    7 .5-10HP

    (5 .5-7 .5kW)

    10lb-in/1 .2Nm

    0 .35in/9mm

    STOP!

    • DoNOTconnectAClinepowertooutputterminalsT1,T2,orT3 .Severedamagetothedrivewillresult .

    • Leakagecurrentmayexceed3 .5mAAC .Minimumsizeoftheprotectiveearthconductorshallcomplywithlocalsafetyregulationsforhighleakagecurrentequipment .

    • WireandGroundinaccordancewithNECorCEC,andallapplicablelocalcodes .

    • MotorwiresMUSTberuninaseparatesteelconduitawayfromcontrolwiringandincomingACpowerwiring .

    • Do not install contactors between the drive and the motor withoutconsultingLenze-ACTechformoreinformation .Failuretodosomayresultindrivedamage .

    • UseonlyULandCSAlistedandapprovedwire .• Minimumwirevoltageratingis300Vfor120,208,and240Vacsystems,

    and600Vfor400and480Vacsystems .• Wiregaugemustbebasedonaminimumof125%oftheratedinput/

    outputcurrentofthedrive,andaminimum75°Cinsulationrating .Usecopperwireonly .

    15Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 10 CONTROL WIRING

    10 .1 CONTROLWIRINGVS .POWERWIRING

    ExternalcontrolwiringMUSTbe run inaseparateconduitaway fromallother inputandoutputpowerwiring .Ifcontrolwiringisnotkeptseparatefrompowerwiring,electricalnoisemaybegeneratedonthecontrolwiringthatwillcauseerraticdrivebehavior .UsetwistedwiresorshieldedcablegroundedatthedrivechassisONLY .RecommendedcontrolwireisBelden8760or8770,orequivalent .

    NOTE

    Control terminals provide basic isolation (insulation per EN 61800-5-1) .Protectionagainstcontactcanonlybeassuredbyadditionalmeasurese .g .supplementalinsulation .

    Strip off 0 .20 to 0 .25 inches (5 to 6 mm) of insulation for control wiring, and torque theterminalsto2lb-in(0 .2Nm) .Becarefulnottoovertorquetheterminals,asthiswillcausedamagetotheterminalstrip .Thisisnotcoveredunderwarrantyandcanonlyberepairedbyreplacingthecontrolboard .

    10 .2 TB-2ANDTB-4

    TheTB-2terminalsarethecircuitcommonfortheanaloginputandanalogoutputfunctions .TheTB-4terminalsarethereferenceforallofthedigitalinputs(TB-1,13A,13B,13C,and13D) .Thedigital inputsareactive-highasstandard,butcanbeconfigured foractive-lowduring initial set-up . Refer to APPENDIX B - INPUT ASSERTION LEVEL . When set foractive-high,TB-4isat+12VDC .

    NOTETB-2maybeconnectedtochassisgroundifnoiseisaconcern .TB-2mustbeconnectedtochassisgroundwhenusingserialcommunications .

    10 .3 SURGESUPPRESSIONONRELAYS

    Currentandvoltagesurgesandspikesinthecoilsofcontactors,relays,solenoids,etc,nearor connected to thedrive, cancauseerraticdriveoperation .Therefore,asnubbercircuitshouldbeusedoncoilsassociatedwith thedrive .ForACcoils,snubbersshouldconsistof a resistor and a capacitor in series across the coil . For DC coils, a free-wheeling orflybackdiodeshouldbeplacedacross thecoil .Snubbersare typicallyavailable from themanufacturerofthedevice .

    10 .4 START/STOPCONTROL

    Therearevariouscontrolschemesthatallowfor2-wireand3-wireStart/Stopcircuits .RefertothewiringdiagramsinSection11-TCFCONTROLWIRINGDIAGRAMS

    16Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 10 .5 SPEED/TORQUEREFERENCESIGNALS

    SPEEDPOT ConnectthewiperofthespeedpottoterminalTB-5,andthehighandlowleadstoterminalsTB-6andTB-2,respectively .Thespeedpotcanbe2 .5kΩupto10kΩ .

    0-10VDC WirethepositivetoterminalTB-5andthenegativetoterminalTB-2 .TB-5inputimpedanceis120kΩ .

    -10to+10VDC ConnectthesignalwiretoTB-5andthecommontoTB-2 .TB-5inputimpedanceis120kΩ .Thissignalcanbeusedforspeedreferenceonly .

    4-20mA WirethepositivetoterminalTB-25andthenegativetoterminalTB-2 .TB-25inputimpedanceis100Ω .

    10 .6 SPEEDREFERENCESELECTION

    Ifananalogspeed/torquereferenceinputisusedtocontrolthedrive,terminalTB-13A,13B,13C,or13D(Parameter10,11,12,or49)maybeprogrammedastheinputselectforthedesiredanaloginputsignal .WhenthatTB-13terminalisthenclosedtoTB-4,thedrivewillrespondtotheselectedanalogreferenceinput .

    Ifananalogspeed/torquereferenceinputisnotselectedontheterminalstripusingTB-13A,13B,13C,or13D,controlwilldefaulttoSTANDARDmode,whichisgovernedbythesettingof Parameter 05 - STANDARD REFERENCE SOURCE . The STANDARD REFERENCESOURCEcanbethesandtbuttonsonthefrontofthedrive,PRESETSPEED#1(speedmodeonly;nottorquemode),a0-10VDCsignal,ora4-20mAsignal .

    0-10VDC,-10to+10VDC,and4-20mAINPUTSIGNALS

    TB-13A,TB-13B,TB-13C,andTB-13Dcanallbeprogrammedtoselecta0-10VDCor4-20mAanalogspeed/torquereferenceinput .Toselecta-10to+10VDCbipolarspeedinput,Parameter07-BIPOLARREFERENCESELECTIONmustbesettoENABLE(02),whichdisablesallotherspeedreferencesexceptforJOGFORWARDandJOGREVERSE(refertoParameter07) .

    PRESETSPEEDS

    TB-13A(or13D)canbeprogrammedtoselectPRESETSPEED#1,TB-13BtoselectPRESETSPEED#2,andTB-13CtoselectPRESETSPEED#3 .Thereareatotalofsevenpresetspeeds,whichareactivatedbydifferentcombinationsofcontactclosuresbetweenTB-13A(or13D),13B,13CandTB-4 .RefertoParameters31-37inSection15-DESCRIPTIONOFPARAMETERS .

    JOG(notavailableinVectorTorquemode)

    TB-13BcanbeprogrammedforJOGFORWARD,andTB-13CcanbeprogrammedforJOGREVERSE .TheJOGFORWARDspeedissetbyPRESETSPEED#2,andtheJOGREVERSEspeedissetbyPRESETSPEED#4 .CloseTB-13BorTB-13CtoTB-4toJOGinthedesireddirection,andopenthecontacttoSTOP .

    17Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • WARNING!

    WhenoperatinginJOGmode,theSTOPsignalandtheAUXILIARYSTOPfunction (Parameters10-12)WILLNOTstop thedrive .Tostop thedrive,removetheJOGcommand .

    JOGREVERSEwilloperatethedriveinreverserotationevenifROTATIONDIRECTION(Parameter17)issettoFORWARDONLY

    NOTE

    If thedrive iscommandedtoJOGwhilerunning, thedrivewillenterJOGmode,butwhentheJOGcommandisremoved,thedrivewillSTOP .

    MOTOROPERATEDPOT(MOP)/FLOATINGPOINTCONTROL

    TB-13BandTB-13Careusedforthisfunction,whichcontrolsthedrivespeedusingcontactswiredtotheterminalstrip .ProgramTB-13BforDECREASEFREQ(05),andprogramTB-13CforINCREASEFREQ(05) .

    ClosingTB-13BtoTB-4willcausethespeedsetpointtodecreaseuntilthecontactisopened .ClosingTB-13CtoTB-4willcausethespeedsetpointtoincreaseuntilthecontactisopened .TheINCREASEFREQfunctionwillonlyoperatewhilethedriveisrunning .

    NOTE

    IfTB-13A,TB-13B,TB-13C,andTB-13Dareallprogrammedtoselectspeedreferences,andtwoormoreoftheterminalsareclosedtoTB-4,thehigherterminalhaspriorityandwilloverride theothers .Forexample, ifTB-13A isprogrammed to select 0-10 VDC, and TB-13C is programmed to selectPRESETSPEED#3,closingboth terminals toTB-4willcause thedrive torespondtoPRESETSPEED#3becauseTB-13CoverridesTB-13A .

    TheexceptiontothisistheMOPfunction,whichrequirestheuseofTB-13BandTB-13C .This leaves TB-13A and TB-13D to be used for other functions . If TB-13A or TB-13D isprogrammedforaspeedreferenceandthatterminal isclosedtoTB-4, itwilloverridetheMOPfunction .

    NOTE

    Thisanalogoutputsignalcannotbeusedwith"loop-powered"devicesthatderivepowerfroma4-20mAsignal .

    18Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 10 .7 ANALOGOUTPUTSIGNALS

    Terminal TB-30 can provide a 0-10 VDC or a 2-10 VDC signal proportional to outputfrequency,load,ortorque .The2-10VDCsignalcanbeconvertedtoa4-20mAsignalusingaresistorinserieswiththesignalsuchthatthetotalloadresistanceis500Ohms .RefertoTB-30OUTPUT(Parameter08)inSection15-DESCRIPTIONOFPARAMETERS .

    10 .8 DRIVESTATUSDIGITALOUTPUTS

    There are two open-collector outputs at terminals TB-14 and TB-15 . The open-collectorcircuitsarecurrent-sinkingtypesratedat30VDCand50mAmaximum .

    The open-collector outputs can be programmed to indicate any of the following: RUN,FAULT, INVERSEFAULT,FAULTLOCKOUT,ATSPEED,ABOVEPRESETSPEED#3,CURRENTLIMIT,AUTOSPEEDMODE,andREVERSE .RefertoParameters06and13inSection15-DESCRIPTIONOFPARAMETERS .

    Thefollowingdiagramillustrateshowthe12VDCpowersupplyatTB-11canbeusedwiththeopen-collectoroutputtodriveanexternalrelay .

    TB-11

    TB-14

    TC

    FT

    ER

    MIN

    AL

    ST

    RIP

    RELAYCOIL

    DIODESNUBBER(1N4148orEquivalent)

    19Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 11 TCF CONTROL WIRING DIAGRAMS

    11 .1 TCFTERMINALSTRIP

    Thefollowingdiagramrepresentstheterminalstriponthemaincontrolboardandprovidesabriefdescriptionofthefunctionofeachterminal .

    AN

    ALO

    GS

    IGN

    AL

    CO

    MM

    ON

    0-10

    VD

    CS

    PE

    ED

    RE

    FE

    RE

    NC

    EIN

    PU

    T

    10V

    DC

    SU

    PP

    LYF

    OR

    SP

    EE

    DP

    OT

    0-10

    OR

    2-1

    0V

    DC

    OU

    TP

    UT

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    RU

    N

    TB

    -13A

    FU

    NC

    TIO

    NS

    ELE

    CT

    TB

    -13B

    FU

    NC

    TIO

    NS

    ELE

    CT

    TB

    -13C

    FU

    NC

    TIO

    NS

    ELE

    CT

    OP

    EN

    -CO

    LLE

    CT

    OR

    OU

    TP

    UT

    OP

    EN

    -CO

    LLE

    CT

    OR

    OU

    TP

    UT

    RS

    -485

    SE

    RIA

    LC

    OM

    MU

    NIC

    AT

    ION

    S

    4-20

    mA

    SP

    EE

    DR

    EF

    ER

    EN

    CE

    INP

    UT

    12V

    DC

    SU

    PP

    LY(

    50m

    AM

    AX

    )

    1 2 5 6 14 TXA TXB4 13A 13B 13C4 13D 2511 15 302

    TB

    -13D

    FU

    NC

    TIO

    NS

    ELE

    CT

    AN

    ALO

    GS

    IGN

    AL

    CO

    MM

    ON

    DIG

    ITA

    L IN

    PU

    TR

    EF

    ER

    EN

    CE

    NOTE

    • ThefunctionofterminalsTB-13A,TB-13B,TB-13C,TB-13D,TB-14,TB-15,andTB-30aredependentontheprogrammingofcertainparameters .RefertoSection15-DESCRIPTIONOFPARAMETERS .

    • Thefollowingdiagramsandtheircorrespondingnotesassumethatalloftheparameters,otherthanthoserequiredfortheparticularconfiguration,remainatfactorydefaultsettings .

    AdditionalinformationonoperatingthedrivefromtheterminalstripcanbefoundinSection10 .Thediagramsinsections11 .2-11 .6provideaquickreferenceonwiringthedriveforthemostcommonconfigurationsusingdrycontactstoactivatethedigital inputs . Ifsolid-statecircuitsaretobeused,refertoAPPENDIXB-INPUTASSERTIONLEVEL,astheassertionlevelofthedigitalinputsmayhavetobechangedtoactive-low .

    20Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 11 .2 TWO-WIRESTART/STOPCONTROL

    Thiswiringdiagramshowsatypicaltwo-wirestart/stopcontrolscheme,usingonemaintainedcontact(suchasthatfromaPLC)forRUNandSTOPcommands,andaselectorswitchtoselectrotationdirection .

    MAINTAINEDRUN/STOPCONTACT

    SIG

    NA

    LC

    OM

    MO

    N

    0-10

    VD

    CIN

    PU

    T

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    ST

    AR

    T

    ST

    AR

    TR

    EV

    ER

    SE

    4-20

    mA

    INP

    UT

    1 2 5 6 14 TXA TXB4 13A 13B 13C4 13D 2511 15 302

    SIG

    NA

    LC

    OM

    MO

    N

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    (SeeNote3)

    ST

    AR

    TF

    OR

    WA

    RD

    FWDREV(SeeNote3)

    NOTES

    • CloseTB-1toTB-4toRUN,andopenTB-1toTB-4toSTOP .• Forthisconfiguration,ROTATIONDIRECTION(Parameter17)mustbe

    settoFORWARDANDREVERSE(02),TB-13A(Parameter10)mustbesettoSTARTREVERSE(07),andTB-13D(Parameter49)mustbesettoSTARTFORWARD(05) .If reverse rotation is not required, simply close TB-1 to TB-4 to RUN, and open to STOP (no other wiring or programming is required).

    • For0-10VDCor4-20mAspeedcontrol,useoneofthefollowingmethods:

    - ProgramParameter05-STANDARDREFERENCESOURCEfor0-10VDC(03)or4-20mA(04) .Thismethodispreferableifonlyonespeedsourceisrequired,asthismethodleavestheTB-13terminalsfreetobeusedforotherfunctions .

    - ProgramoneoftheTB-13terminals(13B,13Careavailableinthisexample)for0-10VDC(02)or4-20mA(03) .WhenthatTB-13terminalisclosedtoTB-4,thedrivewillrespondtotheselectedspeedreferencesignal .IfthatTB-13terminalisnotclosedtoTB-4,thedrivewillrespondtothespeedcontrolsourceselectedinParameter05-STANDARDREFERENCESOURCE .Thismethodmustbeusedifitisnecessarytotogglebetweentwospeedsources .

    21Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 11 .3 ALTERNATETWO-WIRESTART/STOPCONTROL

    Thiswiringdiagramshowsanalternatetwo-wirestart/stopcontrolscheme,usingonemaintainedcontactforRUNFORWARDandanothermaintainedcontactforRUNREVERSE .

    MAINTAINEDRUNFORWARD

    CONTACT

    SIG

    NA

    LC

    OM

    MO

    N

    0-10

    VD

    CIN

    PU

    T

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    RU

    NF

    OR

    WA

    RD

    RU

    NR

    EV

    ER

    SE

    0-10

    VD

    Co

    r4-

    20m

    AS

    ELE

    CT

    4-20

    mA

    INP

    UT

    1 2 5 6 14 TXA TXB4 13A 13B 13C4 13D 2511 15 302

    SIG

    NA

    LC

    OM

    MO

    N

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    MAINTAINEDRUNREVERSE

    CONTACT

    (SeeNote3)

    (SeeNote3) (SeeNote3)

    NOTES

    • CloseTB-1toTB-4toRUNFORWARDandopenTB-1toTB-4toSTOP .CloseTB-13AtoTB-4toRUNREVERSEandopentoSTOP .

    • Forthisconfiguration,ROTATIONDIRECTION(Parameter17)mustbesettoFORWARDANDREVERSE(02),andTB-13A(Parameter10)mustbesettoRUNREVERSE(06) .If reverse rotation is not required, simply close TB-1 to TB-4 to RUN, and open to STOP (no other wiring or programming is required).

    • For0-10VDCor4-20mAspeedcontrol,useoneofthefollowingmethods:

    - ProgramParameter05-STANDARDREFERENCESOURCEfor0-10VDC(03)or4-20mA(04) .Thismethodispreferableifonlyonespeedsourceisrequired,asthismethodleavestheTB-13terminalsfreetobeusedforotherfunctions .

    - ProgramoneoftheTB-13terminals(13B,13Cor13Dareavailableinthisexample)for0-10VDC(02)or4-20mA(03) .WhenthatTB-13terminalisclosedtoTB-4,thedrivewillrespondtotheselectedspeedreferencesignal .IfthatTB-13terminalisnotclosedtoTB-4,thedrivewillrespondtothespeedcontrolsourceselectedinParameter05-STANDARDREFERENCESOURCE .Thismethodmustbeusedifitisnecessarytotogglebetweentwospeedsources .

    22Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 11 .4 THREE-WIRESTART/STOPCONTROL

    Thiswiringdiagramshowsatypicalthree-wirestart/stopcontrolscheme,usingmomentarycontacts(suchaspush-buttons)forSTARTandSTOPcommands,andaselectorswitchtoselectrotationdirection .

    MOMENTARYSTOPCONTACT

    SIG

    NA

    LC

    OM

    MO

    N

    0-10

    VD

    CIN

    PU

    T

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    ST

    AR

    T

    4-20

    mA

    INP

    UT

    1 2 5 6 14 TXA TXB4 13A 13B 13C4 13D 2511 15 302

    SIG

    NA

    LC

    OM

    MO

    N

    (SeeNote3)

    ST

    AR

    TF

    OR

    WA

    RD

    MOMENTARYSTARTCONTACT

    (SeeNote3)

    FWDREV

    ST

    AR

    TR

    EV

    ER

    SE

    NOTES

    • MomentarilycloseTB-13AorTB-13DtoTB-4toSTARTthedriveinthedesireddirectionandmomentarilyopenTB-1toTB-4toSTOPthedrive .

    • Forthisconfiguration,ROTATIONDIRECTION(Parameter17)mustbesettoFORWARDANDREVERSE(02),TB-13A(Parameter10)mustbesettoSTARTREVERSE(07),andTB-13D(Parameter49)mustbesettoSTARTFORWARD(05) .If reverse direction is not required, wire the START push-button directly between TB-4 and TB-13D, and do not program TB-13A for START REVERSE.

    • For0-10VDCor4-20mAspeedcontrol,useoneofthefollowingmethods:

    - ProgramParameter05-STANDARDREFERENCESOURCEfor0-10VDC(03)or4-20mA(04) .Thismethodispreferableifonlyonespeedsourceisrequired,asthismethodleavestheTB-13terminalsfreetobeusedforotherfunctions .

    - ProgramoneoftheTB-13terminals(13Bor13Careavailableinthisexample)for0-10VDC(02)or4-20mA(03) .WhenthatTB-13terminalisclosedtoTB-4,thedrivewillrespondtotheselectedspeedreferencesignal .IfthatTB-13terminalisnotclosedtoTB-4,thedrivewillrespondtothespeedcontrolsourceselectedinParameter05-STANDARDREFERENCESOURCE .

    23Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 11 .5 SPEEDPOTANDPRESETSPEEDCONTROL

    ThiswiringdiagramillustratesSPEEDPOTand/orPRESETSPEEDcontrolwithatwo-wirestart/stopcircuit .

    MAINTAINEDRUNFORWARD

    CONTACT

    SIG

    NA

    LC

    OM

    MO

    N

    0-10

    VD

    CIN

    PU

    T

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    RU

    NF

    OR

    WA

    RD

    PR

    ES

    ET

    SP

    EE

    DS

    ELE

    CT

    1 2 5 6 14 TXA TXB4 13A 13B 13C4 13D 2511 15 302

    DIG

    ITA

    LIN

    PU

    TR

    EF

    ER

    EN

    CE

    PR

    ES

    ET

    SP

    EE

    DS

    ELE

    CT

    PR

    ES

    ET

    SP

    EE

    DS

    ELE

    CT

    10V

    DC

    SU

    PP

    LY

    SPEEDPOT(2 .5k-10kΩ)

    NOTES

    • Program the PRESET SPEEDS (Parameters 31-37) to the desiredvalues .

    • ProgramTB-13A(Parameter10)toPRESETSPEED#1(04),TB-13B(Parameter11) toPRESETSPEED#2 (04), andTB-13C (Parameter12) toPRESETSPEED#3 (04) .To select a preset speed, close theappropriateTB-13terminal(s)toTB-4(refertoParameters31-37forthePresetSpeedActivationtable) .

    • Forspeedpotcontrol,programParameter05-STANDARDREFERENCESOURCEfor0-10VDC(03) .Ifnoneofthepresetspeedsareselected(alloftheTB-13terminalsareopen),thedrivewillrespondtothespeedpot .

    24Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 11 .6 BIPOLARSPEEDCONTROL(-10to+10VDC)

    Thethreewiringdiagramshereinprovideexamplesofusinga-10to+10VDCbipolarspeedreference .

    SIG

    NA

    LC

    OM

    MO

    N

    0-10

    VD

    CIN

    PU

    T

    1 2 5 6 11

    -10to+10VDCSOURCE

    (suchasPLC)

    SIG

    NA

    LC

    OM

    MO

    N

    0-10

    VD

    CIN

    PU

    T1 2 5 6 11

    10V10V

    SPEEDPOT(2 .5k-10kΩ)

    - + - +

    SIG

    NA

    LC

    OM

    MO

    N

    0-10

    VD

    CIN

    PU

    T

    1 2 5 6 11

    +10

    VD

    CS

    UP

    PLY

    10V

    SPEEDPOT(2 .5k-10kΩ)

    - + (COM)(SIGNAL)

    NOTES:

    • Tousea-10to+10VDCspeedreferencesignal,thefollowingparametersmustbeset:

    P07 BIPOLARREFERENCESELECTIONmustbesettoENABLE(02) .

    P17 ROTATIONmustbesettoFORWARDANDREVERSE(02) .

    P45 SPEED AT MIN SIGNAL must be set to the maximum desiredspeedinthereversedirection .

    P46 SPEEDATMAXSIGNALmustbeset to themaximumdesiredspeedintheforwarddirection .

    • Inthisconfiguration,allotherspeedreferencesaredisabledexceptJOGFORWARDandJOGREVERSE .

    • In this configuration, the RUN and START functions on TB-13A andTB-13Dwillonlystartthedrive,theywillnotselectdirection .Directionisdeterminedbythepolarityofthe-10to+10VDCsignal .

    25Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 12 INITIAL POWER UP AND MOTOR ROTATION

    DANGER!

    Hazardofelectricalshock!Capacitors retain charge after power is removed . Disconnect incomingpowerandwaituntil thevoltagebetween terminalsB+andB- is0VDCbeforeservicingthedrive .

    STOP!

    • DoNOTconnectincomingACpowertooutputterminalsT1,T2,andT3!Severedamagetothedrivewillresult .

    • DoNOTcontinuouslycycle inputpower to thedrivemore thanonceeverytwominutes .Damagetothedrivewillresult .

    • SeveredamagetothedrivecanresultifitisoperatedafteralongperiodofstorageorinactivitywithoutreformingtheDCbuscapacitors!

    Ifinputpowerhasnotbeenappliedtothedriveforaperiodoftimeexceedingthreeyears(duetostorage,etc),theelectrolyticDCbuscapacitorswithinthedrivecanchangeinternally,resultinginexcessiveleakagecurrent .Thiscanresultinprematurefailureofthecapacitorsifthedriveisoperatedaftersuchalongperiodofinactivityorstorage .

    Inordertoreformthecapacitorsandpreparethedriveforoperationafteralongperiodofinactivity,applyinputpowertothedrivefor8hourspriortoactuallyoperatingthemotor .

    Beforeattemptingtooperatethedrive,motor,anddrivenequipment,besureallprocedurespertainingtoinstallationandwiringhavebeenproperlyfollowed .

    Disconnectthedrivenloadfromthemotor .Verifythatthedriveinputterminals(L1,L2,andL3)arewiredtotheproperinputvoltageperthenameplateratingofthedrive .

    Energizetheincomingpowerline .TheLEDdisplaywillsequencethroughdisplaysthatshowthedrive'sparameterversion(500intheexamplebelow),HPrating,andvoltagerating .Itshouldthenread“---”,whichindicatesthatthedriveisinaSTOPcondition .ThefollowingdiagramillustratestheinitialLEDdisplaysequence .

    Display flashes HP rating

    Apply input power

    Display flashes parameter version (500-599)

    Display shows "- - -" to indicate STOP

    Display flashes voltage rating

    26Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • Followtheprocedurebelowtocheckthemotorrotation .Thisprocedureassumesthatthedrivehasbeenpoweredupfor thefirst time,andthatnoneof theparametershavebeenchanged .

    1 . Usethetbuttontodecreasethespeedsetpointto00 .0Hz .Ifthetbuttonishelddown,thespeedsetpointwilldecreasebytenthsofHzuntilthenextwholeHzisreached,andthenitwilldecreasebyoneHzincrements .Otherwise,eachpushofthetbuttonwilldecreasethespeedsetpointbyatenthofaHz .

    Once00 .0Hzisreached,thedisplaywilltogglebetween“00 .0”and“---”,whichindicatesthatthedriveisinaSTOPconditionwithaspeedsetpointof00 .0Hz .

    2 . GivethedriveaSTARTcommand .ThiscanbedoneusingoneofseveralwiringmethodsdescribedinSection11-TCFCONTROLWIRINGDIAGRAMS .OncetheSTARTcommandisissued,thedisplaywillread“00 .0”,indicatingthatthedriveisinaRUNconditionwithaspeedsetpointof00 .0Hz .

    3 . Usethesbuttontoincreasethespeedsetpointuntilthemotorstartstorotate .Ifthesbuttonishelddown,thespeedsetpointwillincreasebytenthsofHzuntilthenextwholeHzisreached,andthenitwillincreasebyoneHzincrements .Otherwise,eachpushofthebuttonwillincreasethespeedsetpointbyatenthofaHz .

    4 . Ifthemotorisrotatinginthewrongdirection,givethedriveaSTOPcommandandremovepowerfromthedrive .Waitthreeminutesforthebuscapacitorstodischarge,andswapanytwoofthemotorwiresconnectedtoT1,T2,andT3 .

    NOTE

    Thedrive isphase insensitivewith respect to incoming linevoltage .Thismeansthatthedrivewilloperatewithanyphasesequenceoftheincomingthreephasevoltage .Therefore, tochange themotor rotation, thephasesmustbeswappedatthedriveoutputterminalsoratthemotor .

    27Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 13 PROGRAMMING THE TCF DRIVEThedrivemaybeprogrammedbyoneofthreemethods:usingthethreebuttonsand3-digitLEDdisplayonthefrontofthedrive,programmingtheElectronicProgrammingModule(EPM)usingtheoptionalEPMProgrammer,andthroughaseriallinkusingserialcommunications .Thissectiondescribesprogrammingthedriveusingthebuttonsanddisplay .

    NOTE

    Refer toAppendixA for informationonoperating theTCFSeriesdrive invectormode .

    BUTTONS

    Mode

    Display

    ToenterthePROGRAMmodetoaccesstheparameters,presstheModebutton .ThiswillactivatethePASSWORDprompt(ifthepasswordhasnotbeendisabled) .Thedisplaywillread“00”andtheupperdecimalpointwillbeblinkingasshownbelow .

    PressMode Displayreads"00"

    Upperdecimalpointblinks

    Use thesandtbuttons toscroll to thepasswordvalue (the factorydefaultpasswordis “225”) and press the Mode button . Once the correct password value is entered, thedisplaywillread"P01",whichindicatesthatthePROGRAMmodehasbeenaccessedatthebeginningoftheparametermenu(P01isthefirstparameter) .

    Usesandttoscrolltothe passwordvalue Pressmodetoenterpassword

    Parametermenuisaccessedat

    thefirstparameter

    NOTE

    Ifthedisplayflashes“Er”,thepasswordwasincorrect,andtheprocesstoenterthepasswordmustberepeated .

    28Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • Usethesandtbuttonstoscrolltothedesiredparameternumber .Intheexamplebelow,Parameter19isdisplayed .Parameter19istheACCELERATIONTIMEofthedrive .

    Use s and t to scroll to the desiredparameter number (the example isParameter19-ACCELERATIONTIME)

    Once thedesiredparameternumber is found,press theModebutton todisplay thepresentparameter setting . The upper decimal point will begin blinking, indicating that the presentparametersettingisbeingdisplayed,andthatitcanbechangedbyusingthesandtbuttons .

    PressModetodisplaypresentparametersetting(examplesettingis20 .0)

    Upperdecimalpointblinks

    Usesandttochangesetting(examplesettingchangedto30 .0)

    PressModetostorenewsetting

    PressingtheModewillstorethenewsettingandalsoexitthePROGRAMmode .Tochangeanother parameter, press the Mode key again to re-enter the PROGRAM mode (theparametermenuwillbeaccessedattheparameterthatwaslastviewedorchangedbeforeexiting) .IftheModekeyispressedwithintwominutesofexitingthePROGRAMmode,thepasswordisnotrequiredtoaccesstheparameters .Aftertwominutes,thepasswordmustbeenteredinordertoaccesstheparametersagain .

    13 .1 ELECTRONICPROGRAMMINGMODULE(EPM)

    Every TCF Series drive has an Electronic Programming Module (EPM) installed on themaincontrolboard .TheEPMstorestheuser’sparametersettingsandspecialOEMdefaultsettings(ifprogrammed) .TheEPMisremovable,allowingittobeinstalledinanotherdriveforquickset-up .Forexample,ifadriveisbeingreplacedwithanewone,theEPMcanbetakenoutofthefirstdriveandinstalledinthenewdrive .Downtimeisminimizedbecausethenewdrivedoesnotrequireprogramming-itisreadytorunwhentheEPMisinstalled .

    29Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • TheTCFSeriesdrivecontainstwoorthreesetsofparametervalues,dependingonwhetherthedrivehasbeenprogrammedwithoptionalOEMdefaultsettings .Thefirstsetofvaluesis the factory default settings, which are permanently stored on the main control boardandcannotbechanged .Thesecondsetofvaluesistheusersettings,whicharestoredintheEPM .Whenthedriveleavesthefactory,theusersettingsarethesameasthefactorydefaultsettings,buttheusersettingscanbechangedtoconfigurethedriveforaparticularapplication .

    TheoptionalthirdsetofvaluesistheOEMdefaultsettings,whicharealsostoredintheEPM .OEMdefaultsettingsaretypicallyusedincaseswheremanydrivesareusedforthesameapplication,whichrequiresthatallofthedriveshavethesameparametersettings .TheOEMdefaultsettingscannotbechangedwithouttheoptionalEPMProgrammer .ThedrivecanbeprogrammedtooperateaccordingtotheusersettingsortheOEMdefaultsettings(refertoParameter48inSection15) .

    NOTEThedrivewillnotoperatewithouttheEPMinstalled .Thedrivewilldisplay“F1”if theEPMismissingordamaged .TheTCFdrivewillonlyworkwithblueEPMs;theblackEPMswillnotwork .

    STOP!

    DoNOTremovetheEPMwhilepowerisappliedtothedrive .DamagetotheEPMand/ordrivemayresult .

    TheEPMProgrammer,availableasanoptionfromLenze-ACTech,hastheabilitytoquicklyandeasilyprogrammanyTCFSeriesdrivesforthesameconfiguration .Oncea“master”EPMisprogrammedwith thedesiredparametersettings, theEPMProgrammercancopy thosesettingstootherEPMs,allowingmanydrivestobeconfiguredveryquickly .ConsulttheEPMProgrammerInstructionManualorcontactLenze-ACTechformoreinformation .

    IftheOEMsettingsintheEPMbecomecorrupted,thedrivewilloperatenormally,untilanattemptismadetoperformaRESETOEMusingParameter48-PROGRAMSELECTION .Thedrivewillthenflash“GF”toindicatethattheOEMsettingsarenolongervalid .ThiswillrequirethattheEPMbere-programmedusingtheoptionalEPMProgrammer .

    If the OEM settings and the user settings are both corrupted, the drive will display “GF”immediately and the drive will require a RESET 60 or RESET 50 using Parameter 48 -PROGRAM SELECTION . Once the RESET is performed, the parameters can then beprogrammed individually to match the OEM default settings . This will allow the drive tooperateasifitwereinOEMmode,eventhoughitisactuallyoperatinginUSERmode .RefertoParameter48inSection15-DESCRIPTIONOFPARAMETERS .

    NOTE

    Thedrivewillalsodisplay“GF”ifaRESETOEMorOPERATEWITHOEMSETTINGSisattemptedwhentheEPMdoesnotcontainOEMdefaults .

    30Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 13 .2 TCFDRIVEPERSONALITY

    EachTCFmodelhasaunique"personality"(voltageandHP) .ThisinformationisstoredintheEPM,andisalsopermanentlystoredwithinthedrive .If theEPMisreplaced,andthepersonalitystoredintheEPMdoesnotmatchthepersonalitystoredinthedrive,itmaytripintoa"bF"fault,dependingontheinformationstoredonthenewEPM .

    1 . IfthenewEPMwasfromaTCFdrivethatwasconfiguredforV/Hzmode(refertoParameter80-DRIVEMODE),thedrivewilloperatenormallyandwillnottripintoa"bF"fault .TosetupthedriveforVectormode,followtheinstructionsinAppendixA .

    2 . IfthenewEPMwasfromaTCFdrivethatwasconfiguredforVectormodeorEnhancedV/Hzmode(refertoParameter80-DRIVEMODE),thedrivewilltripintoa"bF"fault .Thisfaultcanberesetbyoneoftwomethods:a . PerformaRESET60orRESET50usingParameter48-PROGRAM

    SELECTION .Thiswillresetalloftheparametersbacktofactorydefaults .TosetupthedriveforVectororEnhancedV/Hzmode,followtheinstructionsinAppendixA .

    b . Setparameters85-91properlyfortheconnectedmotorandthensetParameter94-DRIVEPERSONALITYtothecorrectvaluebasedontheHPandvoltageratingofthedrive .ThenperformtheAutoCalibrationfunctionaccordingtotheinstructionsinAppendixA .

    NOTE

    If an attempt is made to change Parameter 94 - DRIVE PERSONALITYbeforeparameters85-91arechanged,thedrivewilldisplaya"GH"fault .

    31Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 14 PARAMETER MENU

    NO. PARAMETER NAME RANGE OF ADJUSTMENTFACTORYDEFAULT

    (NOTE1)

    01 LINEVOLTAGE HIGH(01),LOW(02) HIGH(01)

    02 CARRIERFREQUENCY 2kHz(01),4kHz(02),8kHz(03) 4kHz(02)

    03 STARTMETHOD

    NORMAL(01),STARTONPOWERUP(02),

    NORMAL(01)

    STARTWITHDCBRAKE(03),

    AUTORESTARTWITHDCBRAKE(04),

    FLYINGRESTART1(05),

    FLYINGRESTART2(06)

    04 STOPMETHODCOAST(01),COASTWITHDCBRAKE(02),

    COAST(01)RAMP(03),RAMPWITHDCBRAKE(04)

    05STANDARD

    REFERENCESOURCE

    speed mode:KEYPAD(01),PRESET#1(02),

    KEYPAD(01)0-10VDC(03),4-20mA(04)

    torque mode:KEYPAD(01),KEYPAD(02),

    0-10VDC(03),4-20mA(04)

    0613

    TB-14OUTPUTTB-15OUTPUT

    NONE(01),RUN(02),FAULT(03),

    NONE(01)NONE(01)

    INVERSEFAULT(04),FAULTLOCKOUT(05),

    ATSETSPEED(06),ABOVEPRESET#3(07),

    CURRENTLIMIT(08),AUTOSPEED(09),

    REVERSE(10),DYNAMICBRAKING(11)

    07 BIPOLARREFERENCESELECTION

    DISABLE(01),ENABLE(02) DISABLE(01)

    08 TB-30OUTPUT

    NONE(01),0-10VDCFREQ(02),

    NONE(01)2-10VDCFREQ(03),0-10VDCLOAD(04),

    2-10VDCLOAD(05),0-10VDCTORQUE(06),

    2-10VDCTORQUE(07)

    10TB-13A

    FUNCTIONSELECT

    NONE(01),0-10VDC(02),4-20mA(03),

    NONE(01)

    PRESETSPEED#1(04),

    STARTFORWARD(05),RUNREVERSE(06),

    STARTREVERSE(07),EXTERNALFAULT(08),

    REMOTEKEYPAD(09),DBFAULT(10),

    AUXILIARYSTOP(11),ACCEL/DECEL#2(12)

    NOTE1:Factorydefaultsareshownfora60Hzbasefrequency .RefertoParameter48for50Hzbasefrequency .

    32Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • NO. PARAMETER NAME RANGE OF ADUSTMENTFACTORYDEFAULT

    (NOTE1)

    11TB-13BFUNCTION

    SELECT

    NONE(01),0-10VDC(02),4-20mA(03),

    NONE(01)PRESETSPEED#2(04),DECREASEFREQ(05),

    JOGFORWARD(06),AUXILIARYSTOP(07)

    12TB-13CFUNCTION

    SELECT

    NONE(01),0-10VDC(02),4-20mA(03),

    NONE(01)

    PRESETSPEED#3(04),INCREASEFREQ(05),

    EXTERNALFAULT(06),REMOTEKEYPAD(07),

    DBFAULT(08),JOGREVERSE(09),

    ACCEL/DECEL#2(10)

    13 TB-15OUTPUT (SEEPARAMETER6-TB-14OUTPUT) NONE(01)

    14 CONTROL

    TERMINALSTRIPONLY(01),TERMINALSTRIP

    ONLY(01)REMOTEKEYPADONLY(02),

    TERMINALSTRIPORREMOTEKEYPAD(03)

    15 SERIALLINK

    DISABLE(01),9600,8,N,2WITHTIMER(02),

    9600,8,N,2WITHOUTTIMER(03),

    9600,8,E,1WITHTIMER(04), 9600,8,N,2

    9600,8,E,1WITHOUTTIMER(05), WITHTIMER(02)

    9600,8,O,1WITHTIMER(06),

    9600,8,O,1WITHOUTTIMER(07)

    17 ROTATIONFORWARDONLY(01), FORWARD

    FORWARDANDREVERSE(02) ONLY(01)

    18 MTROVERLOADTYPE SPEEDCOMP(01),NOCOMP(02) SPEEDCOMP(01)

    19 ACCELERATIONTIME 0 .1-1300 .0SEC 20 .0SEC

    20 DECELERATIONTIME 0 .1-1300 .0SEC 20 .0SEC

    21 DCBRAKETIME 0 .0-999 .0SEC 0 .0SEC

    22 DCBRAKEVOLTAGE 0 .0-30 .0% 0 .00%

    23 MINIMUMFREQUENCY 0 .0-MAXIMUMFREQUENCY 0 .0Hz

    24 MAXIMUMFREQUENCY MINIMUMFREQ-240 .0Hz 60 .0Hz

    25 CURRENTLIMIT 50-200%(NOTE2) 200%

    26 MOTOROVERLOAD 30-100% 100%

    27 BASEFREQUENCY 25 .0-500 .0Hz 60 .0Hz

    NOTE1:Factorydefaultsareshownfora60Hzbasefrequency .RefertoParameter48for50Hzbasefrequency .NOTE2:IfLINEVOLTAGEissettoLOW,maximumsettingis167% .

    33Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • NO. PARAMETER NAME RANGE OF ADJUSTMENTFACTORYDEFAULT

    (NOTE1)

    28 FIXEDBOOST 0 .0-30 .0% 1 .0%

    29 ACCELBOOST 0 .0-20 .0% 0 .0%

    30 SLIPCOMPENSATION 0 .0-5 .0% 0 .0%

    31-37 PRESETSPEEDS 0 .0-MAXIMUMFREQUENCY 0 .0Hz

    38 SKIPBANDWIDTH 0 .0-10 .0Hz 0 .0Hz

    39 SPEEDSCALING 0 .0-6500 .0 0 .0

    40 FREQUENCYSCALING 3 .0-1200 .0Hz 60 .0Hz

    41 LOADSCALING 10-200% 200%

    42 ACCEL/DECEL#2 0 .1-1300 .0SEC 20 .0SEC

    43 SERIALADDRESS 1-247 1

    44 PASSWORD 000-999 225

    45 SPEEDATMINSIGNAL 0 .0-999Hz 0 .0Hz

    46 SPEEDATMAXSIGNAL 0 .0-999Hz 60 .0Hz

    47 CLEARHISTORY MAINTAIN(01),CLEAR(02) MAINTAIN(01)

    48 PROGRAMSELECTION

    USERSETTINGS(01),OEMSETTINGS(02),USERSETTINGS

    (01)RESETOEM(03),RESET60(04),

    RESET50(05),TRANSLATE(06)

    49TB-13D

    FUNCTIONSELECT

    NONE(01),0-10VDC(02),4-20mA(03),

    NONE(01)

    PRESETSPEED#1(04),

    STARTFORWARD(05),

    EXTERNALFAULT(06),

    REMOTEKEYPAD(07),DBFAULT(08),

    AUXILIARYSTOP(09),ACCEL/DECEL#2(10)

    50 SOFTWARECODE (VIEW-ONLY) (N/A)

    51 SOFTWARECODE (VIEW-ONLY) (N/A)

    52 DCBUSVOLTAGE (VIEW-ONLY) (N/A)

    53 MOTORVOLTAGE (VIEW-ONLY) (N/A)

    54 LOAD (VIEW-ONLY) (N/A)

    55 0-10VDCINPUT (VIEW-ONLY) (N/A)

    56 4-20mAINPUT (VIEW-ONLY) (N/A)

    NOTE1:Factorydefaultsareshownfora60Hzbasefrequency .RefertoParameter48for50Hzbasefrequency .

    34Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • NO. PARAMETER NAME RANGE OF ADJUSTMENTFACTORYDEFAULT

    (NOTE1)

    57 TBSTRIPSTATUS (VIEW-ONLY) (N/A)

    58 KEYPADSTATUS (VIEW-ONLY) (N/A)

    59 TB-30OUTPUT (VIEW-ONLY) (N/A)

    73 HEATSINKTEMP (VIEW-ONLY) (N/A)

    79INPUTASSERTION

    LEVELHIGH(01),LOW(02) HIGH(01)

    80 DRIVEMODE

    CONSTANTV/Hz(01),VARIABLEV/Hz(02),

    CONSTANTV/Hz(01)

    ENHANCEDCONSTANTV/Hz(03),

    ENHANCEDVARIABLEV/Hz(04),

    VECTORSPEED(05),VECTORTORQUE(06)

    81 AUTOCALIBRATION

    CALIBRATIONNOTDONE(00),CALIBRATION

    NOTDONE(00)CALIBRATIONCYCLEENABLED(01),

    CALIBRATIONCOMPLETE(02)

    82 CURRENTLOOPPGAIN 0 .00-16 .0 0 .25

    83 CURRENTLOOPIGAIN 12-9990mSEC 65mSEC

    84 STATORRESISTANCE 0 .00-64 .0OHMS(NOTE3) 0 .00OHMS

    85 MOTORRATEDSPEED 300-65000RPM 1750RPM

    86 MOTORRATEDAMPS 0 .0-480AMPS 0 .0AMPS

    87 MOTORRATEDVOLTS 0-600Vac 0Vac

    88 MOTORBASEFREQ 25-500Hz 60Hz

    91 MOTORCOSINEPHI 0 .40-0 .99 0 .80

    92 MOTORINDUCTANCE 0 .0-2000mH(NOTE3) 0 .0mH

    93 TORQUELIMIT 0-400% 100%

    94 DRIVEPERSONALITY (NOTE4) (NOTE4)

    95 MOTORCURRENT (VIEW-ONLY) (N/A)

    96 TORQUEPERCENT (VIEW-ONLY) (N/A)

    NOTE1:Factorydefaultsareshownfora60Hzbasefrequency .RefertoParameter48for50Hzbasefrequency .NOTE3:ThisparameterisautomaticallysetduringtheAUTOCALIBRATIONfunction .NOTE4:RefertoSection15-DESCRIPTIONOFPARAMETERS .

    35Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 15 DESCRIPTION OF PARAMETERSP01 LINE VOLTAGE SELECTIONThiscalibratesthedrivefortheactualappliedinputvoltage,andcanbesettoHIGH(01)orLOW(02) .Refertothetablebelowforthepropersettingdependingontheinputvoltage .

    MODELRATED INPUT

    VOLTAGEINPUTPHASE

    APPLIED INPUTVOLTAGE

    PARAMETERSETTING

    TF200Y 208/240Vac1or3 220-240Vac HIGH(01)

    1or3 200-208Vac LOW(02)

    TF200 208/240Vac3 220-240Vac HIGH(01)

    3 200-208Vac LOW(02)

    TF400 400/480Vac3 440-480Vac HIGH(01)

    3 380-415Vac LOW(02)

    TF500 480/590Vac3 575-600Vac HIGH(01)

    3 460-480Vac LOW(02)

    NOTE

    Ifthisparameterischangedwhilethedriveisrunning,thenewvaluewillnottakeeffectuntilthedriveisstopped .

    P02 CARRIER FREQUENCYThissetstheswitchingrateoftheoutputIGBT’s .Increasingthecarrierfrequencywillresultinlessaudiblemotornoise .Availablesettingsare:2kHz,4kHz,and8kHz .

    TheTCFdriveisfullyratedupto4kHzcarrierfrequency .Ifthe8kHzcarrierfrequencyisselected,thedrive’sambienttemperatureratingmustbede-ratedto43°C,ORtheoutputcurrentratingmustbede-ratedto92% .

    NOTE

    • Ifthedrive'sheatsinktemperaturegetstoohotwhilerunning,thecarrierfrequencywillautomaticallyshift toalowervalueto increaseefficiencyandlowerheatgeneration .

    • Ifthisparameterischangedwhilethedriveisrunning,thechangewillnottakeeffectuntilthedriveisstopped .

    36Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • P03 START METHOD

    WARNING!

    Automatic starting of equipment may cause damage to equipment and/orinjurytopersonnel!Automaticstartshouldonlybeusedonequipmentthatisinaccessibletopersonnel .

    01 NORMAL:Thedrivewillstartwhentheappropriatecontactisclosedontheterminalstrip,orbypressingtheSTARTkeyontheoptionalremotekeypad .RefertoParameter14 .

    02 STARTONPOWERUP:Thedrivewillautomaticallystartuponapplicationofinputpower .

    03 STARTWITHDCBRAKE:WhenaSTARTcommandisgiven,thedrivewillapplyDCBRAKEVOLTAGE(Parameter22)forthedurationofDCBRAKETIME(Parameter21)priortostartingthemotortoensurethatthemotorisnotturning .

    04 AUTORESTARTWITHDCBRAKING:UponaSTARTcommand,afterafault,oruponapplicationofpower,thedrivewillapplyDCBRAKEVOLTAGE(Parameter22)forthedurationofDCBRAKETIME(Parameter21)priortostarting(orrestarting)themotor .

    05 FLYINGRESTART1:StartsthespeedsearchforthemotoratMAXIMUMFREQUENCY(Parameter24) .Thissettingshouldbeusedifitispossiblefortheloadtoincreasespeedafterthedrivetripsorlosespower .

    06 FLYINGRESTART2:Startsthespeedsearchforthemotoratthelastfrequencyitwasrunningatbeforethedrivetrippedonafaultorlostpower .

    TheFLYINGRESTART1and2settingsallowthedrivetostart intoaspinningloadafterafaultoruponapplicationofinputpower .Also,ifSTOPMETHOD(Parameter04)issettoCOAST(01),thedrivewillperformaflyingstartwheneveritisstarted(exceptonapplicationofpower) .

    Whenprogrammed forauto-restart, thedrivewill attempt three restartsaftera fault .Theintervalbetweenrestartattemptsis15secondsforsetting04,and3secondsforsettings05and06 .Duringtheintervalbetweenrestartattempts,thedisplaywillread“SP”toindicateStart Pending . If all three restart attempts fail, the drive will trip into FAULT LOCKOUT(displayed“LC”)andrequireamanualreset .RefertoSection16-TROUBLESHOOTING .

    NOTE

    Settings02and04-06requireatwo-wirestart/stopcircuittooperate .TheRUNcontactmustremainclosedforthepower-upstartandauto-restartfunctionstooperate .

    37Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • P04 STOP METHOD01 COASTTOSTOP:WhenaSTOPcommandisgiven,thedriveshutsoffthe

    outputtothemotor,allowingittocoastfreelytoastop .

    02 COASTWITHDCBRAKE:Whenastopcommandisgiven,thedrivewillactivateDCbraking(afteradelayofupto2seconds,dependingonfrequency)tohelpdeceleratetheload .RefertoParameters:21-DCBRAKETIME,and22-DCBRAKEVOLTAGE .

    03 RAMPTOSTOP:Whenastopcommandisgiven,thedrivewilldeceleratethemotortoastopattheratedeterminedbyParameter20-DECELERATIONTIME .

    04 RAMPWITHDCBRAKE:Whenastopcommandisgiven,thedrivewilldeceleratethemotordownto0 .2Hz(attheratesetbyParameter20-DECELERATIONTIME)andthenactivateDCbrakingaccordingtothesettingsofParameters21-DCBRAKETIMEand22-DCBRAKEVOLTAGE .Thisisusedtobringtheloadtoafinalstop,asthemotormaystillbeturningslightlyafterthedrivestops .

    P05 STANDARD REFERENCE SOURCEThisselectsthedefaultspeedortorquereferencesourceforthedriveifanotherreferenceisnotselectedusingTB-13A,13B,13C,or13D,orParameter07-BIPOLARREFERENCESELECTION .Thefollowingreferencesourcescanbeselected:

    01 KEYPAD:Usethesandtbuttonstoscrolltothedesiredspeed/torque .

    02 PRESETSPEED#1:ThedrivewilloperateatfrequencysetinParameter31 .

    03 0-10VDC:Thedrivewillrespondtoa0-10VDCsignalwiredtoTB-2andTB-5 .

    04 4-20mA:Thedrivewillrespondtoa4-20mAsignalwiredtoTB-2andTB-25 .

    NOTEWhenthedriveisinVECTORTORQUEmode(seeParameter80),setting02(PRESET#1)willbecomethesameassetting01(KEYPAD) .Intorquemode,presetspeedscannotbeusedastorquereferences .

    P06 TB-14 OPEN COLLECTOR OUTPUTThisselectsthestatusindicationfortheopen-collectoroutputatTB-14 .Theterms“open”and “close” refer to thestateof the internal transistor thatactivates thecircuit .When thetransistoris“closed”,TB-14isatthesamepotentialasTB-2,allowingcurrenttoflow .

    01 NONE:Disablestheopen-collectoroutput .

    02 RUN:ClosesuponaSTARTcommand .OpensifthedriveisinaSTOPstate,thedrivefaults,orinputpowerisremoved .DCbrakingisconsideredaSTOPstate .

    03 FAULT:Closesifthereisnofaultcondition .Opensifthedrivefaults,orinputpowerisremoved .

    04 INVERSEFAULT:Closesifthedrivefaults .Opensifthereisnofaultcondition .

    38Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 05 FAULTLOCKOUT:Closeswheninputpowerisapplied .Opensifthreerestartattemptsareunsuccessful,orifinputpowerisremoved .

    06 ATSETSPEED:Closesifthedriveiswithin+0 .5Hzofthespeedsetpoint .

    07 ABOVEPRESETSPEED#3:ClosesiftheoutputfrequencyexceedsthevalueinPRESETSPEED#3 .OpensiftheoutputfrequencyisequaltoorlessthanthevalueinPRESETSPEED#3(Parameter33) .

    08 CURRENTLIMIT:ClosesiftheoutputcurrentexceedstheCURRENTLIMITsetting .OpensiftheoutputcurrentisequaltoorlessthanCURRENTLIMIT(refertoParameter25) .

    09 AUTOMATICSPEEDMODE:ClosesifanAUTOMATIC(terminalstrip)speedreferenceisselectedusingTB-13A,13B,13C,or13D .OpensifaSTANDARD(Parameter5)speedreferenceisactive .

    10 REVERSE:Closeswhenreverserotationisactive .Openswhenforwardrotationisactive .(RefertoParameter17-ROTATIONDIRECTION) .

    11 DYNAMICBRAKING:Usedto"trigger"theoptionalexternalDynamicBrakingmodule .RefertotheinstructionsincludedwiththeDynamicBrakingoption .

    P07 BIPOLAR REFERENCE SELECTIONThisparameterisusedtoenablethe-10to+10VDCbipolarspeedreferenceinput(cannotbeusedasatorquereference) .RefertoSection11 .6for-10to+10VDCwiringexamples .

    01 DISABLE:ThedrivewilloperatenormallyandrespondtothespeedreferenceselectedinParameter5-STANDARDREFERENCESOURCE,orselectedusingterminals13A,13B,13C,and13D .RefertoSection10 .6formoreinformationonspeedreferenceselection .

    02 ENABLE:Thedrivewillonlyrespondtoa-10to+10VDCbipolarsignal(allotherspeedreferencesaredisabled) .

    From+0 .1to+10VDCthedrivewilloperateintheForwarddirection,withthemaximumspeeddeterminedbySPEEDATMAXSIGNAL(Parameter46)orMAXIMUMFREQUENCY(Parameter24),whicheverislower .

    From-0 .1to-10VDC,thedrivewilloperateintheReversedirection,withthemaximumspeeddeterminedbySPEEDATMINSIGNAL(Parameter45)orMAXIMUMFREQUENCY(Parameter24),whicheverislower .

    NOTE

    • Whensetting02isselected,Parameter17-ROTATIONmustbesettoFORWARDANDREVERSE(02)forthebipolarspeedreferencetoworkproperly .

    • Whensetting02isselected,theRUNandSTARTfunctionsonterminalsTB-13AandTB-13Dcanonlybeusedtostartthedrive;theywillnolongerselectdirection(directionisonlydeterminedbythepolarityofthe-10to+10VDCsignal) .However,TB-13BandTB-13CcanstillbeusedforJOGFORWARDandJOGREVERSEfunctions .

    RefertoParameters10,11,12,and49

    39Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • P08 TB-30 ANALOG OUTPUTTerminalTB-30canbeusedasananalogoutputproportionaltooutputfrequency,loadormotortorque .

    01 NONE DisablesTB-30Output

    02 0-10VDCFREQUENCY10VDC=SettingofP40-FrequencyScaling

    03 2-10VDCFREQUENCY

    04 0-10VDCLOAD10VDC=SettingofP41-LoadScaling

    05 2-10VDCLOAD

    06 0-10VDCTORQUE10VDC=SettingofP93-TorqueLimit

    07 2-10VDCTORQUE

    NOTEThe2-10VDCsignalcanbeconvertedtoa4-20mAsignalbyconnectingaresistorinserieswiththesignalsuchthatthetotalloadresistanceis500Ohms .However,thisoutputcannotbeusedwithdevicesthatderivepowerfroma4-20mAsignal .

    P10 TB-13A FUNCTION SELECTThis selects the function of terminal TB-13A . Closing TB-13A to TB-4 (or opening in thecaseofsettings08and11)activatestheselectedfunction .Thefollowingfunctionscanbeselected:

    01 NONE:DisablestheTB-13Afunction .02 0-10VDC:Setsa0-10VDCsignal(atTB-5)astheAUTOspeedreferenceinput .03 4-20mA:Setsa4-20mAsignal(atTB-25)astheAUTOspeedreferenceinput .

    04 PRESETSPEED#1:SelectsPRESETSPEED#1astheAUTOspeedreference .ThedrivewilloperateatfrequencyprogrammedinParameter31 .

    05 STARTFORWARD:MomentarilycloseTB-13AtoTB-4toSTARTthedriveintheforwarddirection .MomentarilyopenTB-1toTB-4toSTOP .

    06 RUNREVERSE:CloseTB-13AtoTB-4toRUNinthereversedirection,andopentoSTOP .CloseTB-1toTB-4toRUNintheforwarddirection,andopentoSTOP .

    07 STARTREVERSE:MomentarilycloseTB-13AtoTB-4toSTARTthedriveinthereversedirection .MomentarilyopenTB-1toTB-4toSTOP .Forforwardoperation,programTB-13D(Parameter49)toSTARTFORWARD .MomentarilycloseTB-13DtoTB-4toSTARTintheforwarddirection,andmomentarilyopenTB-1toTB-4toSTOP .

    08 EXTERNALFAULT:SetsTB-13Aasanormallyclosedexternalfaultinput .IfTB-13AisopenwithrespecttoTB-4,thedrivewillfault .

    09 REMOTEKEYPAD:Selectstheoptionalremotekeypadasthecontrolsource .RefertoParameter14-CONTROL .

    10 DBFAULT:SetsTB-13Aasadynamicbrakingfaultinputwhenusingtheoptionaldynamicbrakingmodule .Whenthisinputisactivatedbythedynamicbrakingmodule,thedrivewilltripintoa"dF"faultandthemotorwillcoasttoastop .RefertothemanualincludedwiththeDynamicBrakingoption .

    40Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • 11 AUXILIARYSTOP:WhenTB-13AisopenedwithrespecttoTB-4,thedrivewilldeceleratetoaSTOP(evenifSTOPMETHODissettoCOAST)attherateprogrammedintoParameter42-ACCEL/DECEL#2 .

    12 ACCEL/DECEL#2:SelectstheaccelerationanddecelerationtimeprogrammedintoParameter42-ACCEL/DECEL#2 .

    NOTE

    • InorderfortheRUNREVERSEandSTARTREVERSEfunctionstooperate,Parameter17-ROTATIONDIRECTIONmustbesettoFORWARDANDREVERSE(02) .

    • Ifa-10to+10VDCbipolarspeedreferenceisbeingused(Parameter07-BIPOLARREFERENCESELECTIONisENABLED),theRUNandSTARTfunctionsonTB-13Awillonlystartthedrive,theywillnotselectdirection .Directionisdeterminedbythepolarityofthe-10to+10VDCsignal .

    P11 TB-13B FUNCTION SELECTThisselectsthefunctionofterminalTB-13B .ClosingTB-13BtoTB-4(oropeninginthecaseofsetting07)activatestheselectedfunction .Thefollowingfunctionscanbeselected:

    01 NONE:DisablestheTB-13Bfunction .

    02 0-10VDC:Selectsa0-10VDCsignal(atTB-5)astheAUTOspeedreferenceinput .

    03 4-20mA:Selectsa4-20mAsignal(atTB-25)astheAUTOspeedreferenceinput .

    04 PRESETSPEED#2:SelectsPRESETSPEED#2astheAUTOspeedreference .ThedrivewilloperateatthefrequencyprogrammedinParameter32 .

    05 DECREASEFREQUENCY:DecreasesthespeedsetpointwhenusingtheMOPfunction .RefertoSection10 .6 .

    06 JOGFORWARD:Jogintheforwarddirection .Inthismode,thedrivewillJOGatthespeedprogrammedintoParameter32-PRESETSPEED#2 .JOGisnotavailableinVectorTorquemode .

    WARNING!

    Whenoperating inJOGmode, theSTOP terminal (TB-1), theAUXILIARYSTOPfunction(setting07),andtheSTOPkeyontheoptionalremotekeypadWILL NOTstopthedrive .Tostopthedrive,removetheJOGcommand

    NOTE

    If thedrive iscommandedtoJOGFORWARDwhilerunning, thedrivewillenterJOGmodeandrunatPRESETSPEED#2 .WhentheJOGcommandisremoved,thedrivewillSTOP .

    07 AUXILIARYSTOP:WhenTB-13BisopenedwithrespecttoTB-4,thedrivewilldeceleratetoaSTOP(evenifSTOPMETHODissettoCOAST)attherateprogrammedintoParameter42-ACCEL/DECEL#2 .

    41Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • P12 TB-13C FUNCTION SELECTThisselectsthefunctionofterminalTB-13C .ClosingTB-13CtoTB-4(oropeninginthecaseofsetting06)activatestheselectedfunction .Thefollowingfunctionscanbeselected:

    01 NONE:DisablestheTB-13Cfunction .

    02 0-10VDC:Selectsa0-10VDCsignal(atTB-5)astheAUTOspeedreferenceinput .

    03 4-20mA:Selectsa4-20mAsignal(atTB-25)astheAUTOspeedreferenceinput .

    04 PRESETSPEED#3:SelectsPRESETSPEED#3astheAUTOspeedreference .ThedrivewilloperateatfrequencyprogrammedinParameter33 .

    05 INCREASEFREQUENCY:IncreasesthespeedsetpointwhenusingtheMOPfunction .RefertoSection10 .6 .

    06 EXTERNALFAULT:SetsTB-13Casanormallyclosedexternalfaultinput .IfTB-13CisopenwithrespecttoTB-4,thedrivewillfault .

    07 REMOTEKEYPAD:Selectstheoptionalremotekeypadasthecontrolsource .RefertoParameter14-CONTROL .

    08 DBFAULT:SetsTB-13Casadynamicbrakingfaultinputwhenusingtheoptionaldynamicbrakingmodule .Whenthisinputisactivatedbythedynamicbrakingmodule,thedrivewilltripintoa"dF"faultandthemotorwillcoasttoastop .RefertothemanualincludedwiththeDynamicBrakingoption .

    09 JOGREVERSE:Joginthereversedirection .Inthismode,thedrivewillJOGatthespeedprogrammedintoParameter34-PRESETSPEED#4 .JOGisnotavailableinVectorTorquemode .

    10 ACCEL/DECEL#2:SelectstheaccelerationanddecelerationtimeprogrammedintoParameter42-ACCEL/DECEL#2 .

    WARNING!

    Whenoperating inJOGmode, theSTOP terminal (TB-1), theAUXILIARYSTOPfunction(setting07),andtheSTOPkeyontheoptionalremotekeypadWILL NOTstopthedrive .Tostopthedrive,removetheJOGcommand .

    JOGREVERSEwilloperatethedriveinreverserotationevenifROTATIONDIRECTION(Parameter17)issettoFORWARDONLY .

    NOTE

    If thedrive is commanded to JOGREVERSEwhile running, thedrivewillenterJOGmodeandrunatPRESETSPEED#4 .WhentheJOGcommandisremoved,thedrivewillSTOP .

    42Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • P13 TB-15 OPEN COLLECTOR OUTPUT

    Thisselectsthestatusindicationfortheopen-collectoroutputatTB-15,andhasthesameselectionsasParameter6-TB-14OPENCOLLECTOROUTPUT .

    P14 CONTROLThisselectsthesourceofSTART/STOPanddirectioncommands .

    01 TERMINALSTRIPONLY:ThedrivewillonlyrespondtoSTART/STOPanddirectioncommandsfromtheterminalstrip .

    02 REMOTEKEYPADONLY:ThedrivewillonlyrespondtoSTART/STOPanddirectioncommandsfromtheoptionalremotekeypad .

    03 TERMINALSTRIPORREMOTEKEYPAD:TerminalTB-13A,TB-13C,orTB-13Dcanbeusedtoselectterminalstripcontrolorremotekeypadcontrol .RefertoParameters10,12,and49 .

    NOTE

    TheSTOPbuttonontheoptionalremotekeypadisalwaysactiveaslongastheseriallinkremainsintact .

    P15 SERIAL LINKThisparameterconfiguresthedriveforModbusRTUserialcommunications .Theoptionsarelistedbybaudrate,numberofdatabits,parity,numberofstopbitsandwhetherthewatchdogtimerisenabledordisabled .

    WARNING!

    Controlling the drive from the serial link without the watchdog timer couldcausedamagetoequipmentand/orinjurytopersonnel!

    Thewatchdog timerwill stop thedriveafter10secondsofnoserialactivity tosafeguardagainstafailedseriallink .Duringset-uportroubleshootingitmaybeusefultodisablethewatchdogtimerbutisitnotrecommendedtorunnormallywithoutthewatchdogtimer .

    01 DISABLED:Disablestheseriallink

    02 9600,8,N,2-ENABLEDWITHTIMER

    03 9600,8,N,2-ENABLEDWITHOUTTIMER

    04 9600,8,E,1-ENABLEDWITHTIMER

    05 9600,8,E,1-ENABLEDWITHOUTTIMER

    06 9600,8,O,1-ENABLEDWITHTIMER

    07 9600,8,O,1-ENABLEDWITHOUTTIMER

    43Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

  • P17 ROTATION DIRECTION01 FORWARDONLY:Thedrivewillonlyallowrotationintheforwarddirection .

    However,JOGREVERSE(Parameter12)willstillope