AC Input Output Bypass switches are confusing to many experienced installers. Outback Power Systems continues to expand flexibility and capability thus making this subject even more confusing. This document will attempt to shed some light on the possible configurations available with the OutBack products. Let’s start simple. What is an AC-Input/Output Bypass switch? Why do I need one? The Bypass switch allows an inverter system to be “bypassed”, usually when there is a problem with the inverter. Review the following over-simplified pictures. The first one shown in the normal position depicts an inverter powering a house. The second one shows the switch in the bypass position. The house is now being powered by a generator. The generator could just as easily have been grid too. Notice that when bypassed, there is no electrical connection between the AC wiring and the inverter. This allows the inverter to be safely worked on or removed. Disconnection of the DC cabling is also required to de-energize the system. Why do you need a Bypass switch? You don’t want to be without one when your customer calls you at work and says “The lights are out, what do I do now ?” Your answer would be to throw the Bypass switch to the bypass position and start the generator. Anytime you want to work on your alternative energy system, it may be necessary to bypass the inverter to accomplish the task at hand.

AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

AC Input Output Bypass switches are confusing to many experienced installers. Outback Power Systems continues to expand flexibility and capability thus making this subject even more confusing. This document will attempt to shed some light on the possible configurations available with the OutBack products. Let’s start simple. What is an AC-Input/Output Bypass switch? Why do I need one? The Bypass switch allows an inverter system to be “bypassed”, usually when there is a problem with the inverter. Review the following over-simplified pictures. The first one shown in the normal position depicts an inverter powering a house. The second one shows the switch in the bypass position. The house is now being powered by a generator. The generator could just as easily have been grid too.

Notice that when bypassed, there is no electrical connection between the AC wiring and the inverter. This allows the inverter to be safely worked on or removed. Disconnection of the DC cabling is also required to de-energize the system. Why do you need a Bypass switch? You don’t want to be without one when your customer calls you at work and says “The lights are out, what do I do now ?” Your answer would be to throw the Bypass switch to the bypass position and start the generator. Anytime you want to work on your alternative energy system, it may be necessary to bypass the inverter to accomplish the task at hand.

Page 2: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

The Bypass switch is a quick and foolproof way to keep the house powered up from your other AC source. The following is a list of the Bypass switch part numbers offered for use in the PSAC and some typical applications. The OutBack PS2AC comes standard with a dual 50 amp Bypass switch and cannot be modified. The AC inputs are not mechanically tied to the bypass assembly on the PS2 system and must be turned off in addition to throwing the bypass switch. AC-IOB-30 Used when the inverter has only a 30 amp transfer relay such as a Stat Power ProSine or Trace DR series AC-IOB30D Used with the Vanner 120/240 VAC RE-4500 inverter AC-IOB-60 Use with an inverter that has a 60 amp transfer relay such as the Trace SW or OutBack FX series. Two of these can be installed in a PSAC enclosure for use with two inverters. The inverters will be controlled independently. This has advantages and disadvantages. The advantage is that if one inverter is to be worked on, only one inverter needs to be bypassed. The house will still receive power from the other inverter. The disadvantage is that under this situation, the house may be receiving power on both leg1 and leg2 that is not out of phase. In other words, if the bypassed circuit has an AC input from either a generator or the grid, it will not necessarily be out of phase with the non-bypassed circuit. This is only a problem for a 240 volt load or for house wiring that utilizes a common neutral. Many homes are wired with common neutrals to save on wire. This out of phase condition can overload the neutral conductor. AC-IOB-60D Use for two SW or FX inverters. Both AC legs are bypassed together so that the previous condition cannot happen. AC-IOB-100Q This bypass switch comes with a dual 100 amp breaker and 4 50 amp inverter output breakers. Most off-grid homes can get along with only a 60 amp Bypass, but if your generator is over that rating, this is the choice. Four OutBack inverters will put you over the 60 amp limit so for quad stacked FX’s use this part. Another feature of this arrangement is the 4 inverter output breakers. Another way to use these bypass switches is with two inverters. You get four 50 amp breakers, so using two for AC input and two for AC output works fine. When installing 4 inverters you will need to add four breakers for the AC input in addition to the breakers that come with the kit. AC-IOB-60Q Same as 100Q, but with a dual 60 amp bypass. Use with 12,000 watt generators max. The following diagrams will help to show different installations. These diagrams are a reference only and are not necessarily complete. These diagrams are available on the OutBack website in AutoCAD format. You may want to download some and customize one to fit your particular system. DXF versions can be made available for those of you that have other Cad systems.

Page 3: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

SH

OW

N A

RE

: FA

CTO

RY

INST

ALLE

D P

AR

TS, O

PTIO

NS

AN

D U

SER

INST

ALLE

D P

ARTS

.

OB

DC

-GFP

/2

PV+

INP

UT

120/

240V

AC

OR

GR

IDG

ENER

ATO

RA

C S

OU

RC

E

AC IN LEG 1

AC IN LEG 2

120V

AC

X-F

AN

BYPASS

BY

PA

SSO

UT

PUT

50A

50A

50A

50A

50A

PS2

SYST

EM

AC

OUT

AC

IN

AC

OUT

AC OUT LEG 1

AC OUT LEG 2

GROUND

BUS

CO

PPE

R

60A

60A

60A

175A

175A

RO

DG

ND

PV+

HU

B 4 FX

202

4

FX 2

024

.5A

60A

60A

60A

PS2

AC

X-2

40

L1#4N

#2&3

ING

SCR

EWS

THE

MO

UNT-

PLA

TE T

HRU

TO T

HE B

ACK

ARE

BO

NDE

DA

LL G

NDS

CEN

TER

PS2

AC A

S LO

ADW

IRE

WH

EN U

SING

AD

D N

EU

/GND

BO

ND

L2#1

NEUTRAL

120/

240V

ACLO

AD

S

MX6

0

B+

INTE

RNA

LLY

CO

NNE

CTE

D TO

GET

HER

SHO

WN

WIT

H P

V &

BAT

NE

GAT

IVES

PV-

B-

B+P

V+P

V-B

-P

V+

HO

USE

LOAD

SO

UT LET

X-2

40

50A

25A

25A

15A

20A

15A

15A

15A

AC

IN

15A

15A

15A

RTS

BAT

TERI

ES

PS2

DC

12V

FAN

DC POSITIVE

MAT

E

Page 4: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

AC LOADS

50A 50A 50A 50A 25A 25A

X-240BYPASS OUTPUT INPUT

50A 50A

L1

L2

BREAKERS50A OUTPUT2 POLE

BREAKERS

(2) 50A

50A BYPASS

X-240PS2AC

AC LOADS

MAX50A INPUT

MAX50A2 POLE

TWO PAIR 2/0 CABLES48V: TWO 100A BRKRSTWO PAIR 2/0 CABLES24V: TWO 175A BRKRS

4-5KW @ 120/240VAC

FX2000L2

FX2000L1

PS2DC

BATTERY

(SERIES)

X-240

75 AMPSMAX#4AWG

50 AMPS

#6AWGMAX

L2 N L1

ALL OTHER WIRE#6AWG

4-7.2KW @ 120/240VAC(SERIES)#1 #2&3 #4

19009 62nd AVE NEARLINGTON, WA. 98223360-435-6030

NEUTRAL

AC IN

NEUTRAL

AC OUT

AC OUT

NEUTRAL

AC IN

ALL BREAKERS SHOWN,BYPASS MECHANISM,X-240 AND TERMINALBLOCKS ARE HOUSEDIN THE OUTBACK PS2AC50D

NORMAL

BYPA

SS

BREAKERS

50A BYPASS

50A BYPASS

50A DUAL BYPASSSTANDARD ON PS2AC

MASTER

SLAVE

4-7.2KW-50A-BYPASS-SER

TWO PAIR 2/0 CABLES48V: TWO 175A BRKRSTWO PAIR 4/0 CABLES24V: TWO 250A BRKRS

7-7.2KW @ 120/240VAC(SERIES) 50A BYPASS

4KW = 2 FX20245KW = 2 FX254814KW = 4 VFX352414.4 = 4 VFX3638

MATE

HUB OR STACK 4

MATE

HUB OR STACK 4

MATE

This arrangement is shown using the bypass switch that comes with the PS2AC50D

100 AMPS

#2AWGMAX

ARLINGTON, WA. 9822319009 62nd AVE NE

360-435-6030

AC LOADS

ALL OTHER WIRE

100 AMPS

#6AWG

#2AWGMAX

50A50A

BYPASS

50A50A

OUTPUT

50A

INPUT

50A

L1

(2) 50A

BREAKERS

50A BYPASS

PS2AC

BREAKERS50A OUTPUT2 POLE

AC LOADS120VAC

120VACMAX

MAX

50A

50A

INPUT

2 POLE

TWO PAIR 2/0 CABLES48V: TWO 100A BRKRSTWO PAIR 2/0 CABLES24V: TWO 175A BRKRS

4-5KW @ 120VAC

FX2000

FX2000L1

L1

PS2DC(PARALLEL)

BATTERY

4-7.2KW @ 120VAC(PARALLEL)

L1

NEUTRAL

120VAC

120VACNEUTRAL

AC OUT

AC IN

AC IN

NEUTRAL

AC OUT

AND TERMINAL BLOCKSARE STANDARD IN THEOUTBACK PS2AC50D

BYPASS MECHANISM,ALL BREAKERS SHOWN,

NORMAL

BYPA

SS

50A DUAL BYPASSSTANDARD ON PS2AC

50A BYPASSMATE

HUB OR STACK 4

MASTER

SLAVE

4-7.2KW-50A-BYPASS-PAR

TWO PAIR 2/0 CABLES48V: TWO 175A BRKRSTWO PAIR 4/0 CABLES24V: TWO 250A BRKRS

7-7.2KW @ 120VAC(PARALLEL)

4KW = 2 FX20245KW = 2 FX254814KW = 4 VFX352414.4 = 4 VFX3638

MATE

HUB OR STACK 4

MATE

This arrangement is shown using the bypass switch that comes with the PS2AC50D

Page 5: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

NEUTRALAC OUT

NEUTRAL

NEUTRAL

NEUTRAL

AC OUT

AC IN

L2AC OUT

AC IN

AC OUT

AC IN

AC IN

L1

NEUTRAL

L2

50A50A

INPUT INPUT

50A 50A

L1

125 AMPS

125 AMPS

BYPASS

100A 100A

OUTPUT

50A50A

8-14.4KW @ 120/240VAC(SERIES)

50A 50A

#6AWGALL OTHER WIRE

360-435-6030ARLINGTON, WA. 9822319009 62nd AVE NE

MAX

MAX

8-10KW @ 120/240VAC

2 POLE100A BYPASS

BREAKERS

(4) 50AINPUT

(4) 50A

BREAKERSOUTPUT

L2

L2FX2000

BATTERY

FX2000

FX2000L1

AC LOADS X-240

AC BOXDC BOXFX2000

L1(SERIES)

#2AWG

#2AWG

X-240

25A 25A

X-240L1NL2

#2&3#1 #4

ALL BREAKERS SHOWN,BYPASS MECHANISM,X-240 AND TERMINALBLOCKS ARE HOUSEDIN THE OUTBACK PSAC

NORMAL

BYPASS

100 AMP DUAL BYPASS WITH FOUR50 AMP OUTPUT

ON MODEL PSAC-100Q

BYPASS KIT AC-IOB-100QKIT INCLUDES 100A DUALQOU, FOUR 50A CBI BRKRS,METAL PANELS, LABEL

100A BYPASS

HUB OR STACK 4

MASTER

SLAVE

SLAVE

SLAVE

8-14.4KW-100A-BYPASS-SER

MATE

FULL SET OF BUSBARS TOO

24V: FOUR 175A BRKRS

48V: FOUR 100A BRKRSFOUR PAIR 2/0 CABLES

FOUR PAIR 2/0 CABLES24V: FOUR 250A BRKRS

48V: FOUR 175A BRKRSFOUR PAIR 2/0 CABLES

FOUR PAIR 4/0 CABLES

8KW = 4 FX202410KW = 4 FX254814KW = 4 VFX352414.4 = 4 VFX3638

14-14.4KW @ 120/240VAC(SERIES)

This arrangement shows the PSAC-100Q or (PSAC + AC-IOB-100Q same thing, different names)

100 AMPS

120VAC

MAX

NEUTRAL

19009 62nd AVE NEARLINGTON, WA. 98223360-435-6030

120VAC

100 AMPS

ALL OTHER WIRE

AC LOADS

#6AWG

MAX

BYPASS

OUTPUT

50A50A

8-14.4KW @ 120VAC

50A50A

INPUT

(PARALLEL)

L1

(4) 50A

BREAKERS

BREAKERSOUTPUT(4) 50A

100A BYPASS

AC BOX

AC LOADS120VAC

120VAC INPUT

2 POLE24V: FOUR 175A BRKRS

48V: FOUR 100A BRKRSFOUR PAIR 2/0 CABLES

FOUR PAIR 2/0 CABLESFX2000

FX2000

FX2000

L1

L1

L1

BATTERY

8-10KW @ 120VACFX2000L1

DC BOX(PARALLEL)

50A 50A

INPUT

50A 50A

L1

L1

L1

AC OUT

AC IN

AC IN

AC OUT

AC IN

AC OUT

AC IN

AC OUT

NEUTRAL

NEUTRAL

NEUTRAL

NEUTRAL

ALL BREAKERS SHOWN,BYPASS MECHANISM,X-240 AND TERMINALBLOCKS ARE HOUSEDIN THE OUTBACK PS4AC

NORMAL

BYPASS

100A 100A100 AMP DUAL BYPASS WITH FOUR50 AMP OUTPUT

ON MODEL PS4AC-100BYPASS KIT AC-IOB-100D

KIT INCLUDES 100A DUALQOU, FOUR 50A CBI BRKRS,METAL PANELS, LABEL

100A BYPASSMATE

HUB OR STACK 4

MASTER

SLAVE

SLAVE

SLAVE

8-14.4KW-100A-BYPASS-PAR

24V: FOUR 250A BRKRS

48V: FOUR 175A BRKRSFOUR PAIR 2/0 CABLES

FOUR PAIR 4/0 CABLES

14-14.4KW @ 120VAC(PARALLEL)

8KW = 4 FX202410KW = 4 FX254814KW = 4 VFX352414.4 = 4 VFX3638

MATE

This arrangement shows the PSAC-100Q or (PSAC + AC-IOB-100Q same thing, different names)

Page 6: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

PSAC-30D or (PSAC + AC-IOB-30D same thing, different names)

PSACSCHEMATIC

LEFT BREAKER ON=BY-PASSING INVERTER. ALL POWERWILL BE SUPPLIED BY THEUTILITY OR GENERATOR

RIGHT BREAKER ON=INVERTERSYSTEM IS ON

240VACLOAD

AC LOAD120VAC

X-240AUTO TRANSFORMER

SERVICE CRIMP TERMINALS

GROUND RODOR SYSTEM

INV HOT IN 1INV HOT IN 2INV HOT OUT

INV NEU IN 1

INV NEU IN 2INV NEU OUT

INV CHASSIS GND

NC

INVERTER/CHARGER

NEUTRALHOT

GROUND

NEUTRALHOT

GROUND

GENERATOR

UTILITYGRID

AC HOTLEG 2

AC HOTLEG 1 NEUAC HOT LEG 2

AC HOT LEG 1

AC NEUTRALBUS

GROUNDBUS

THIS SCHEMATIC IS FOR REFERENCE ONLY !

SHOWN ARE: FACTORY INSTALLED PARTS,OPTIONS AND USER INSTALLED PARTS.

ACTUAL INSTALLATIONS WILL DIFFER FROM THIS.

AC-IOB-60

PN 375-0004-01

11

1

2

2

PSAC-60 or (PSAC + AC-IOB-60 )

Page 7: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

L2

L1

8-10 KW @ 120/240VAC

L2

L1

AC-IOB-60

2

1 1

AC IN HOT LEG 2

AC IN HOT LEG 1

AC OUT HOT LEG 1

AC OUT HOT LEG 2

STACKED FX INVERTERS WITH TWOAC-IOB-60 BYPASSES IN A PSAC BOXOUTBACK STACKED FOR 120/240VAC

MATEHUB

MATEHUB

NEUTRAL

AC IN

NEUTRAL

AC OUT

AC OUT

NEUTRAL

AC IN

MATE

HUB-4 OR HUB-10

MASTER

STACK2, STACK4,

SLAVE

240 VAC

25A 25A

X-240

X-240XFMR

120/240V#4 #2&3 #1

AC-IOB-60

11

2

AC LOADS

L1

L2

This arrangement is shown in the PSAC cabinet. (PSAC-60 + additional AC-IOB-60)

Page 8: AC Input Output Bypass switches are confusing to many … · 2003. 8. 30. · 100 amp dual bypass with four 50 amp output on model psac-100q bypass kit ac-iob-100q kit includes 100a

Below are examples of current flow of a quad bypass assembly. One example is shown in the normal position and the other is shown bypassed. The AC input breakers to the inverters are not mechanically tied to the bypass assembly. These inputs must be turned off separately to de-energize AC from the inverter.

NORMAL POSITION

L2

L1

L2

L1

BYPASS POSITION

L1

L1

L2

L2

Rev B 8-30-03