98
Relion ® 650 series Transformer protection RET650 Product Guide

Abb Ret650

Embed Size (px)

Citation preview

Page 1: Abb Ret650

Relion® 650 series

Transformer protection RET650Product Guide

Page 2: Abb Ret650

Contents

1. 650 series overview........................................................3

2. Application.....................................................................3

3. Available functions..........................................................8

4. Differential protection....................................................17

5. Current protection........................................................17

6. Voltage protection........................................................19

7. Frequency protection....................................................20

8. Secondary system supervision.....................................20

9. Control.........................................................................20

10. Logic...........................................................................22

11. Monitoring...................................................................23

12. Metering......................................................................25

13. Human Machine interface............................................26

14. Basic IED functions.....................................................26

15. Station communication................................................27

16. Hardware description..................................................28

17. Connection diagrams Customized...............................30

18. Connection diagrams Configured................................35

19. Technical data.............................................................55

20. Ordering for Customized IED.......................................86

21. Ordering for Configured IED........................................91

22. Ordering for Accessories.............................................94

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any

errors that may appear in this document.

© Copyright 2012 ABB.

All rights reserved.

Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered

trademarks of their respective holders.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

2 ABB

Page 3: Abb Ret650

1. 650 series overviewThe 650 series IEDs provide both customized andconfigured solutions. With the customized IEDsyou have the freedom to completely adapt thefunctionality according to your needs.

The 650 series IEDs provide optimum 'off-the-shelf', ready-to-use solutions. It is configured withcomplete protection functionality and defaultparameters to meet the needs of a wide range ofapplications for generation, transmission and sub-transmission grids.

The 650 series IEDs include:• Customized versions providing the possibility to

adapt the functionality to the application needs.• Configured solutions are completely ready to

use solutions optimized for a wide range ofapplications for generation, transmission andsub-transmission grids.

• Support for user-defined names in the locallanguage for signal and function engineering.

• Minimized parameter settings based on defaultvalues and ABB's new global base valueconcept. You only need to set thoseparameters specific to your own application,such as the line data.

• GOOSE messaging for horizontalcommunication.

• Extended HMI functionality with 15 dynamicthree-color-indication LEDs per page, on up tothree pages, and configurable push-buttonshortcuts for different actions.

• Programmable LED text-based labels.• Settable 1A/5A -rated current inputs.

2. ApplicationRET650 provides fast and selective protection,monitoring and control for two- and three-windingtransformers, autotransformers, generator-transformer units and shunt reactors. Thetransformer IED is designed to operate correctlyover a wide frequency range in order toaccommodate power system frequency variationsduring disturbances and generator start-up andshut-down.

A very fast differential protection function withautomatic CT ratio matching and vector groupcompensation makes this IED the ideal solutioneven for the most demanding applications. SinceRET650 has very low requirements on the main

CTs, no interposing CTs are required.Thedifferential protection function is provided with2nd harmonic and wave-block restraint featuresto avoid tripping for magnetizing inrush current,and 5th harmonic restraint to avoid tripping foroverexcitation.

The differential function offers a high sensitivity forlow-level internal faults. The unique and innovativesensitive differential protection feature of theRET650 provides the best possible coverage forwinding internal turn-to-turn faults, based on thetheory of symmetrical components .

A low impedance restricted earth-fault protectionfunction is available as a complimentary sensitiveand fast main protection against winding earthfaults. This function includes a directional zero-sequence current criterion for additional security.

The binary inputs are heavily stabilized againstdisturbance to prevent incorrect operations at forexample, dc system capacitive discharges or DCearth faults.

Tripping from pressure relief/buchholz andtemperature devices can be done through thetransformer IED where trip signal conditioning canbe performed (pulsing, lockout, additional logics,etc). The binary inputs are heavily stabilizedagainst disturbances to prevent incorrectoperations for example, during DC systemcapacitive discharges or DC earth faults.

Versatile phase, earth, negative and zerosequence overcurrent functions which can bemade directional provide further alternativebackup protection. Thermal overload with twotime-constants, volts per hertz and over/undervoltage protection functions are also available.

A built-in disturbance and event recorder providesvaluable data to the user about status andoperation for post-fault disturbance analysis.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2 Issued: June 2012Revision: -

ABB 3

Page 4: Abb Ret650

Breaker failure protection allows high speed back-up tripping of surrounding breakers.

Three packages have been defined for thefollowing applications:

• Two-winding transformer in single breakerarrangements (A01)

• Three-winding transformer in single breakerarrangements (A05)

• Tap changer control (A07)

The packages are configured and ready for directuse. Analog and tripping IO has been pre-definedfor basic use. Other signals need to be applied asrequired for each application.

The graphical configuration tool ensures simpleand fast testing and commissioning.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

4 ABB

Page 5: Abb Ret650

T2W PDIF

87T 3Id/I

CC RBRF

50BF 3I> BF

CC RBRF

50BF 3I> BF

OC4 PTOC

50/51 3I>

OC4 PTOC

50/51 3I>

CC RPLD

52PD PD

EF4 PTOC

51N IN>

CC RPLD

52PD PD

TR PTTR

49 Ith

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

TR8 ATCC

90 U

TCM YLTC

84

UV2 PTUV

27 U<

OV2 PTOV

59 U>

PH PIOC

50 3I>>

TR PTTR

49 Ith

REF PDIF

87N IdN/I

Other configured functions

REF PDIF

87N IdN/I

EF4 PTOC

51N/67N IN>

DRP RDRE

Mont.

YY

P

ROV2 PTOV

59N 3U0>

RET650 A01 - 2 Winding Transformer protection 10AI (8I+2U)

20 MVA110±11*1.5% / 21 kV

105 / 550 AYNd5

20 kV Bus

110 kV Bus

200/1

600/120kV/100V

200/1

600/1

IEC61850

ANSI IEC

Function Enabled in Settings

IEC61850

ANSI IEC

Function Disabled in Settings

W1

W2

IEC09000645-4-en.vsd

IEC09000645 V4 EN

Figure 1. A typical protection application for a two-winding transformer in single breaker arrangement

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 5

Page 6: Abb Ret650

RET650 A05 - 3 Winding Transformer protection 20AI 2*(6I+4U)

W1

T3W PDIF

87T 3Id/I

CC RBRF

50BF 3I> BF

CC RBRF

50BF 3I> BF

OC4 PTOC

50/51 3I>

OC4 PTOC

51/67 3I>

CC RPLD

52PD PD

CC RBRF

50BF 3I> BF

CC RPLD

52PD PD

EF4 PTOC

51N IN>

CC RPLD

52PD PD

TR PTTR

49 Ith

TR PTTR

49 Ith

V MSQI

Meter.

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

V MSQI

Meter.

C MSQI

Meter.

V MMXU

Meter.

C MMXU

Meter.

CV MMXN

Meter.

TCS SCBR

Cond

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

TR8 ATCC

90 U

TCM YLTC

84

UV2 PTUV

27 U<

OV2 PTOV

59 U>

PH PIOC

50 3I>>

TR PTTR

49 Ith

REF PDIF

87N IdN/I

Other configured functions

REF PDIF

87N IdN/I

REF PDIF

87N IdN/I

OEX PVPH

24 U/f>

OC4 PTOC

51/67 3I>

EF4 PTOC

51N/67N IN>

EF4 PTOC

51N/67N IN>

DRP RDRE

Mont.

CV MMXN

Meter.

YY

@

ROV2 PTOV

59N 3UO>

35 kV Bus

110 kV Bus

10 kV Bus

IEC61850

ANSI IEC

Function Onin Settings

IEC61850

ANSI IEC

Function Off in Settings

Transformer Data:40/40/15 MVA

110±11*1.5% / 36.75 / 10.5 kV210/628/825 A

YNyn0d5

110kV/100V

300/1

1000/1

800/1

800/1

300/1

10kV/100V

35kV/100V

1000/1W3 W2

IEC09000646-3-en.vsd

IEC09000646 V3 EN

Figure 2. A typical protection application for a three-winding transformer in single breaker arrangement

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

6 ABB

Page 7: Abb Ret650

RET650 A07 – OLTC Control for 1 or 2 Transformers 10AI (6I+4U)

TR PTTR

49 Ith

EF4 PTOC

51N/67N IN>

CV MMXN

Meter.

T1

OC4 PTOC

50/51 3I>

ETP MMTR

Meter.

ROV PTOV

59N 3U0>

T2TRx ATCC

90 UUV2 PTOV

27 U<

OV2 PTOV

59 U>

TR PTTR

49 Ith

EF4 PTOC

51N/67N IN>

CV MMXN

Meter.OC4 PTOC

50/51 3I>

ETP MMTR

Meter.

ROV2 PTOV

59N 3Uo>TR8 ATCC

90 U

UV2 PTUV

27 U<

OV2 PTOV

59 U>

T1

T2

YY

Ø

YY

Ø

TCM YLTC

84

TCM YLTC

84

TCS SCBR

Cond

TCS SCBR

Cond

SPVN ZBAT

Cond

Other configured functions

DRP RDRE

Mont.

T1 Data:20 MVA

110±11*1.5% / 21 kV105 / 550 A

YNd5XT=11 %

T2 Data:20 MVA

110±11*1.5% / 21 kV105 / 550 A

YNd5XT=11 %

20 kV Bus #1 20 kV Bus #2

IEC61850

ANSI IEC

Function Enabled in Settings

IEC61850

ANSI IEC

Function Disabled in Settings

600/1

20kV/100V

600/1

20kV/100V

W2

W2

IEC09000647-4-en.vsd

IEC09000647 V4 EN

Figure 3. A typical tap changer control application for one or two transformers

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 7

Page 8: Abb Ret650

3. Available functions

Main protection functions

IEC 61850/Function blockname

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

Differential protection

T2WPDIF 87T Transformer differential protection, twowinding

0–1 1

T3WPDIF 87T Transformer differential protection, threewinding

0–1 1

REFPDIF 87N Restricted earth fault protection, lowimpedance

0–3 2 3

HZPDIF 87 1Ph High impedance differentialprotection

0–2 2 2

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

8 ABB

Page 9: Abb Ret650

Back-up protection functions

IEC 61850/Functionblock name

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

Current protection

PHPIOC 50 Instantaneous phase overcurrentprotection, 3–phase output

0–3 2 3

OC4PTOC 51 Four step phase overcurrentprotection, 3–phase output

2 2

OC4PTOC 51/67 Four step directional phase protection,3–phase output

0–3 3

EFPIOC 50N Instantaneous residual overcurrentprotection

0–3 2 3

EF4PTOC 51N/67N Four step residual overcurrentprotection, zero/negative sequencedirection

0–3 2 3 2

TRPTTR 49 Thermal overload protection, two timeconstants

0–3 2 3 2

CCRBRF 50BF Breaker failure protection, 3–phaseactivation and output

0–3 2 3

CCRPLD 52PD Pole discordance protection 0–3 2 3

GUPPDUP 37 Directional underpower protection 0–2 1 1 2

GOPPDOP 32 Directional overpower protection 0–2 1 1 2

DNSPTOC 46 Negative sequence based overcurrentfunction

0–2 1 2

Voltage protection

UV2PTUV 27 Two step undervoltage protection 0–2 1 1 2

OV2PTOV 59 Two step overvoltage protection 0–2 1 1 2

ROV2PTOV 59N Two step residual overvoltageprotection

0–2 1 1 2

OEXPVPH 24 Overexcitation protection 0–1 1 1

Frequency protection

SAPTUF 81 Underfrequency function 0–4 4 4 4

SAPTOF 81 Overfrequency function 0–4 4 4 4

SAPFRC 81 Rate-of-change frequency protection 0–4 2 2 4

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 9

Page 10: Abb Ret650

Control and monitoring functions

IEC 61850/Functionblock name

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

Control

QCBAY Bay control 1 1 1 1

LOCREM Handling of LR-switch positions 1 1 1 1

LOCREMCTRL LHMI control of Permitted SourceTo Operate (PSTO)

1 1 1 1

CBC2 Circuit breaker for 2CB 0–1 1

CBC3 Circuit breaker for 3CB 0–1 1

CBC4 Circuit breaker for 4CB 0–1 1

TR8ATCC 90 Automatic voltage control for tapchanger, parallel control

0–2 1 1 2

TCMYLTC 84 Tap changer control andsupervision, 6 binary inputs

0–2 1 1 2

SLGGIO Logic Rotating Switch for functionselection and LHMI presentation

15 15 15 15

VSGGIO Selector mini switch extension 20 20 20 20

DPGGIO IEC 61850 genericcommunication I/O functionsdouble point

16 16 16 16

SPC8GGIO Single point generic control 8signals

5 5 5 5

AUTOBITS AutomationBits, commandfunction for DNP3.0

3 3 3 3

I103CMD Function commands forIEC60870-5-103

1 1 1 1

I103IEDCMD IED commands forIEC60870-5-103

1 1 1 1

I103USRCMD Function commands user definedfor IEC60870-5-103

4 4 4 4

I103GENCMD Function commands generic forIEC60870-5-103

50 50 50 50

I103POSCMD IED commands with position andselect for IEC60870-5-103

50 50 50 50

Secondary system supervision

TCSSCBR Breaker close/trip circuitmonitoring

3 3 3 3

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

10 ABB

Page 11: Abb Ret650

IEC 61850/Functionblock name

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

Logic

SMPPTRC 94 Tripping logic, common 3–phaseoutput

1–3 2 3 2

TMAGGIO Trip matrix logic 12 12 12 12

OR Configurable logic blocks, OR gate 283 283 283 283

INVERTER Configurable logic blocks,Inverter gate

140 140 140 140

PULSETIMER Configurable logic blocks, Pulsetimer

40 40 40 40

GATE Configurable logic blocks,Controllable gate

40 40 40 40

XOR Configurable logic blocks,exclusive OR gate

40 40 40 40

LOOPDELAY Configurable logic blocks, loopdelay

40 40 40 40

TIMERSET Configurable logic blocks, timerfunction block

40 40 40 40

AND Configurable logic blocks, ANDgate

280 280 280 280

SRMEMORY Configurable logic blocks, set-reset memory flip-flop gate

40 40 40 40

RSMEMORY Configurable logic blocks, reset-set memory flip-flop gate

40 40 40 40

FXDSIGN Fixed signal function block 1 1 1 1

B16I Boolean 16 to Integer conversion 16 16 16 16

B16IFCVI Boolean 16 to Integer conversionwith logic node representation

16 16 16 16

IB16A Integer to Boolean 16 conversion 16 16 16 16

IB16FCVB Integer to Boolean 16 conversionwith logic node representation

16 16 16 16

Monitoring

CVMMXN Measurements 6 6 6 6

CMMXU Phase current measurement 10 10 10 10

VMMXU Phase-phase voltagemeasurement

6 6 6 6

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 11

Page 12: Abb Ret650

IEC 61850/Functionblock name

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

CMSQI Current sequence componentmeasurement

6 6 6 6

VMSQI Voltage sequence measurement 6 6 6 6

VNMMXU Phase-neutral voltagemeasurement

6 6 6 6

AISVBAS Function block for service valuespresentation of the analog inputs

1 1 1 1

TM_P_P2 Function block for service valuespresentation of primary analoginputs 600TRM

1 1 1 1

AM_P_P4 Function block for service valuespresentation of primary analoginputs 600AIM

1 1 1 1

TM_S_P2 Function block for service valuespresentation of secondary analoginputs 600TRM

1 1 1 1

AM_S_P4 Function block for service valuespresentation of secondary analoginputs 600AIM

1 1 1 1

CNTGGIO Event counter 5 5 5 5

DRPRDRE Disturbance report 1 1 1 1

AxRADR Analog input signals 4 4 4 4

BxRBDR Binary input signals 6 6 6 6

SPGGIO IEC 61850 genericcommunication I/O functions

64 64 64 64

SP16GGIO IEC 61850 genericcommunication I/O functions 16inputs

16 16 16 16

MVGGIO IEC 61850 genericcommunication I/O functions

16 16 16 16

MVEXP Measured value expander block 66 66 66 66

SPVNZBAT Station battery supervision 0–1 1 1 1

SSIMG 63 Insulation gas monitoring function 0–2 2 2 2

SSIML 71 Insulation liquid monitoringfunction

0–2 2 2 2

SSCBR Circuit breaker conditionmonitoring

0–3 2 3 2

I103MEAS Measurands for IEC60870-5-103 1 1 1 1

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

12 ABB

Page 13: Abb Ret650

IEC 61850/Functionblock name

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

I103MEASUSR Measurands user defined signalsfor IEC60870-5-103

3 3 3 3

I103AR Function status auto-recloser forIEC60870-5-103

1 1 1 1

I103EF Function status earth-fault forIEC60870-5-103

1 1 1 1

I103FLTPROT Function status fault protectionfor IEC60870-5-103

1 1 1 1

I103IED IED status for IEC60870-5-103 1 1 1 1

I103SUPERV Supervison status forIEC60870-5-103

1 1 1 1

I103USRDEF Status for user defined signals forIEC60870-5-103

20 20 20 20

Metering

PCGGIO Pulse counter logic 16 16 16 16

ETPMMTR Function for energy calculationand demand handling

3 3 3 3

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 13

Page 14: Abb Ret650

Communication

IEC 61850/Functionblock name

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

Station communication

IEC61850-8-1 IEC 61850 communicationprotocol

1 1 1 1

DNPGEN DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

RS485DNP DNP3.0 for EIA-485communication protocol

1 1 1 1

CH1TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

CH2TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

CH3TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

CH4TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

OPTICALDNP DNP3.0 for optical serialcommunication

1 1 1 1

MSTSERIAL DNP3.0 for serialcommunication protocol

1 1 1 1

MST1TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

MST2TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

MST3TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

MST4TCP DNP3.0 for TCP/IPcommunication protocol

1 1 1 1

RS485GEN RS485 1 1 1 1

OPTICALPROT Operation selection for opticalserial

1 1 1 1

RS485PROT Operation selection for RS485 1 1 1 1

DNPFREC DNP3.0 fault records for TCP/IP communication protocol

1 1 1 1

OPTICAL103 IEC60870-5-103 Optical serialcommunication

1 1 1 1

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

14 ABB

Page 15: Abb Ret650

IEC 61850/Functionblock name

ANSI Function description Transformer

RE

T65

0

RE

T65

0 (A

01)

2W/1

CB

RE

T65

0 (A

05)

3W/1

CB

RE

T65

0 (A

07)

OLT

C

RS485103 IEC60870-5-103 serialcommunication for RS485

1 1 1 1

GOOSEINTLKRCV Horizontal communication viaGOOSE for interlocking

59 59 59 59

GOOSEBINRCV GOOSE binary receive 4 4 4 4

GOOSEVCTRCONF GOOSE VCTR configurationfor send and receive

1 1 1 1

VCTRSEND Voltage control sending blockfor GOOSE

1 1 1 1

GOOSEVCTRRCV Voltage control receiving blockfor GOOSE

3 3 3 3

ETHFRNTETHLAN1GATEWAY

Ethernet configuration of frontport, LAN1 port and gateway

1 1 1 1

GOOSEDPRCV GOOSE function block toreceive a double point value

32 32 32 32

GOOSEINTRCV GOOSE function block toreceive an integer value

32 32 32 32

GOOSEMVRCV GOOSE function block toreceive a measurand value

16 16 16 16

GOOSESPRCV GOOSE function block toreceive a single point value

64 64 64 64

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 15

Page 16: Abb Ret650

Basic IED functions

IEC 61850/Functionblock name

Function description

Basic functions included in all products

INTERRSIG Self supervision with internal event list 1

SELFSUPEVLST Self supervision with internal event list 1

TIMESYNCHGEN Time synchronization 1

SNTP Time synchronization 1

DTSBEGIN, DTSEND,TIMEZONE

Time synchronization, daylight saving 1

IRIG-B Time synchronization 1

SETGRPS Setting group handling 1

ACTVGRP Parameter setting groups 1

TESTMODE Test mode functionality 1

CHNGLCK Change lock function 1

TERMINALID IED identifiers 1

PRODINF Product information 1

SYSTEMTIME System time 1

RUNTIME IED Runtime comp 1

PRIMVAL Primary system values 1

SMAI_20_1 -SMAI_20_12

Signal matrix for analog inputs 2

3PHSUM Summation block 3 phase 12

GBASVAL Global base values for settings 6

ATHSTAT Authority status 1

ATHCHCK Authority check 1

SPACOMMMAP SPA communication mapping 1

FTPACCS FTP access with password 1

DOSFRNT Denial of service, frame rate control for front port 1

DOSLAN1 Denial of service, frame rate control for LAN1 1

DOSSCKT Denial of service, socket flow control 1

SAFEFILECOPY Safe file copy function 1

SPATD Date and time via SPA protocol 1

BCSCONF Basic communication system 1

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

16 ABB

Page 17: Abb Ret650

4. Differential protection

Transformer differential protection T2WPDIF/T3WPDIFThe Transformer differential protection, two-winding (T2WPDIF) and Transformer differentialprotection, three-winding (T3WPDIF) are providedwith internal CT ratio matching and vector groupcompensation and settable zero sequencecurrent elimination.

The function can be provided with two or threethree-phase sets of current inputs. All currentinputs are provided with percentage bias restraintfeatures, making the IED suitable for two- or three-winding transformer arrangements.

Two-winding applications

xx05000048.vsd

IEC05000048 V1 EN

two-winding powertransformer

Three-winding applications

xx05000052.vsd

IEC05000052 V1 EN

three-winding powertransformer with allthree windingsconnected

xx05000049.vsd

IEC05000049 V1 EN

three-winding powertransformer withunconnected deltatertiary winding

Figure 4. CT group arrangement fordifferential protection and otherprotections

The setting facilities cover the applications of thedifferential protection to all types of powertransformers and auto-transformers with orwithout load tap changer as well as for shuntreactors and local feeders within the station. Anadaptive stabilizing feature is included for heavythrough-faults.

Stabilization is included for inrush currents as wellas for overexcitation conditions. Adaptivestabilization is also included for system recoveryinrush and CT saturation for external faults. A highset unrestrained differential current protection is

included for a very high speed tripping at a highinternal fault currents.

An innovative sensitive differential protectionfeature, based on the theory of symmetricalcomponents, offers the best possible coveragefor power transformer winding turn-to-turn faults.

Restricted earth fault protection REFPDIFRestricted earth fault protection, low impedanceREFPDIFRestricted earth-fault protection, low-impedancefunction (REFPDIF) can be used on all directly orlow-impedance earthed windings. The REFPDIFfunction provides high sensitivity and high speedtripping as it protects each winding separatelyand thus does not need inrush stabilization.

The low-impedance function is a percentagebiased function with an additional zero sequencecurrent directional comparison criterion. Thisgives excellent sensitivity and stability duringthrough faults. The function allows the use ofdifferent CT ratios and magnetizing characteristicson the phase and neutral CT cores. Unlike highimpedance restricted earth fault it allows formixing with other functions and protection IEDson the same CT cores.

1Ph High impedance differential protectionHZPDIFThe 1Ph High impedance differential protection(HZPDIF) function can be used when the involvedCT cores have the same turns ratio and similarmagnetizing characteristics. It utilizes an externalsummation of the currents in the interconnectedCTs, a series resistor, and a voltage dependentresistor which are mounted externally connectedto the IED.

HZPDIF can be used as high impedance REFprotection.

5. Current protection

Instantaneous phase overcurrent protection, 3-phase output PHPIOCThe instantaneous three phase overcurrentfunction has a low transient overreach and shorttripping time to allow use as a high set short-circuit protection function.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 17

Page 18: Abb Ret650

Four step phase overcurrent protection, 3-phaseoutput OC4PTOCThe four step phase overcurrent protectionfunction OC4PTOC has an inverse or definite timedelay independent for step 1 and 4 separately.Step 2 and 3 are always definite time delayed.

All IEC and ANSI inverse time characteristics areavailable.

The directional function is voltage polarized withmemory. The function can be set to be directionalor non-directional independently for each of thesteps.

A 2nd harmonic blocking can be set individuallyfor each step.

Instantaneous residual overcurrent protectionEFPIOCThe Instantaneous residual overcurrent protectionEFPIOC has a low transient overreach and shorttripping times to allow use for instantaneous earth-fault protection, with the reach limited to less thantypical eighty percent of the transformerimpedance at minimum source impedance.EFPIOC can be configured to measure theresidual current from the three-phase currentinputs or the current from a separate currentinput. EFPIOC can be blocked by activating theinput BLOCK.

Four step residual overcurrent protection, zerosequence and negative sequence directionEF4PTOCThe four step residual overcurrent protection,zero or negative sequence direction (EF4PTOC)has a settable inverse or definite time delayindependent for step 1 and 4 separately. Step 2and 3 are always definite time delayed.

All IEC and ANSI inverse time characteristics areavailable.

EF4PTOC can be set directional or non-directional independently for each of the steps.

The directional part of the function can be set tooperate on following combinations:

• Directional current (I3PDir) versus Polarizingvoltage (U3PPol)

• Directional current (I3PDir) versus Polarizingcurrent (I3PPol)

• Directional current (I3PDir) versus Dualpolarizing (UPol+ZPol x IPol) where ZPol = RPol+ jXPol

IDir, UPol and IPol can be independently selectedto be either zero sequence or negative sequence.

Second harmonic blocking restraint level can beset for the function and can be used to blockeach step individually.

Thermal overload protection, two time constantTRPTTRIf a power transformer or generator reaches veryhigh temperatures the equipment might bedamaged. The insulation within the transformer/generator will have forced ageing. As aconsequence of this the risk of internal phase-to-phase or phase-to-earth faults will increase. Hightemperature will degrade the quality of thetransformer/generator insulation.

The thermal overload protection estimates theinternal heat content of the transformer/generator(temperature) continuously. This estimation ismade by using a thermal model of the transformer/generator with two time constants, which isbased on current measurement.

Two warning levels are available. This enablesactions in the power system to be done beforedangerous temperatures are reached. If thetemperature continues to increase to the tripvalue, the protection initiates a trip of theprotected transformer/generator.

Breaker failure protection, 3-phase activation andoutputCCRBRF can be current based, contact based, oran adaptive combination of these two conditions.

Breaker failure protection, 3-phase activation andoutput (CCRBRF) ensures fast back-up tripping ofsurrounding breakers in case the own breakerfails to open. CCRBRF can be current based,contact based, or an adaptive combination ofthese two conditions.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

18 ABB

Page 19: Abb Ret650

Current check with extremely short reset time isused as check criterion to achieve high securityagainst unnecessary operation.

Contact check criteria can be used where thefault current through the breaker is small.

Breaker failure protection, 3-phase activation andoutput (CCRBRF) current criteria can be fulfilledby one or two phase currents the residual current,or one phase current plus residual current. Whenthose currents exceed the user defined settings,the function is triggered. These conditionsincrease the security of the back-up tripcommand.

CCRBRF function can be programmed to give athree-phase re-trip of the own breaker to avoidunnecessary tripping of surrounding breakers.

Pole discordance protection CCRPLDCircuit breakers and disconnectors can end upwith thes in different positions (close-open), dueto electrical or mechanical failures. An openphase can cause negative and zero sequencecurrents which cause thermal stress on rotatingmachines and can cause unwanted operation ofzero sequence or negative sequence currentfunctions.

Normally the own breaker is tripped to correctsuch a situation. If the situation persists thesurrounding breakers should be tripped to clearthe unsymmetrical load situation.

The pole discordance function operates based oninformation from the circuit breaker logic withadditional criteria from unsymmetrical phasecurrents when required.

Directional over/underpower protectionGOPPDOP/GUPPDUPThe directional over-/under-power protectionGOPPDOP/GUPPDUP can be used wherever ahigh/low active, reactive or apparent powerprotection or alarming is required. The functionscan alternatively be used to check the direction ofactive or reactive power flow in the power system.There are a number of applications where suchfunctionality is needed. Some of them are:

• detection of reversed active power flow• detection of high reactive power flow

Each function has two steps with definite timedelay. Reset times for both steps can be set aswell.

Negative sequence based overcurrent functionDNSPTOCNegative sequence based overcurrent function(DNSPTOC) is typically used as sensitive earth-fault protection of power lines, where incorrectzero sequence polarization may result frommutual induction between two or more parallellines.

Additionally, it is applied in applications oncables, where zero sequence impedancedepends on the fault current return paths, but thecable negative sequence impedance is practicallyconstant.

The directional function is current and voltagepolarized. The function can be set to forward,reverse or non-directional independently for eachstep.

DNSPTOC protects against all unbalanced faultsincluding phase-to-phase faults. The minimumstart current of the function must be set to abovethe normal system unbalance level in order toavoid unwanted operation.

6. Voltage protection

Two step undervoltage protection UV2PTUVUndervoltages can occur in the power systemduring faults or abnormal conditions. Two stepundervoltage protection (UV2PTUV) function canbe used to open circuit breakers to prepare forsystem restoration at power outages or as long-time delayed back-up to primary protection.

UV2PTUV has two voltage steps, where step 1 issettable as inverse or definite time delayed. Step2 is always definite time delayed.

Two step overvoltage protection OV2PTOVOvervoltages may occur in the power systemduring abnormal conditions such as suddenpower loss, tap changer regulating failures, openline ends on long lines etc.

Two step overvoltage protection (OV2PTOV)function can be used to detect open line ends,normally then combined with a directional reactiveover-power function to supervise the system

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 19

Page 20: Abb Ret650

voltage. When triggered, the function will causean alarm, switch in reactors, or switch outcapacitor banks.

OV2PTOV has two voltage steps, where step 1can be set as inverse or definite time delayed.Step 2 is always definite time delayed.

OV2PTOV has an extremely high reset ratio toallow settings close to system service voltage.

Two step residual overvoltage protectionROV2PTOVResidual voltages may occur in the power systemduring earth faults.

Two step residual overvoltage protectionROV2PTOV function calculates the residualvoltage from the three-phase voltage inputtransformers or measures it from a single voltageinput transformer fed from an open delta orneutral point voltage transformer.

ROV2PTOV has two voltage steps, where step 1can be set as inverse or definite time delayed.Step 2 is always definite time delayed.

Overexcitation protection OEXPVPHWhen the laminated core of a power transformeror generator is subjected to a magnetic fluxdensity beyond its design limits, stray flux will flowinto non-laminated components not designed tocarry flux and cause eddy currents to flow. Theeddy currents can cause excessive heating andsevere damage to insulation and adjacent parts ina relatively short time. The function has settableinverse operating curves and independent alarmstages.

7. Frequency protection

Underfrequency protection SAPTUFUnderfrequency occurs as a result of a lack ofsufficient generation in the network.

Underfrequency protection SAPTUF is used forload shedding systems, remedial action schemes,gas turbine startup and so on.

SAPTUF is also provided with undervoltageblocking.

Overfrequency protection SAPTOFOverfrequency protection function SAPTOF isapplicable in all situations, where reliabledetection of high fundamental power systemfrequency is needed.

Overfrequency occurs because of sudden loaddrops or shunt faults in the power network. Closeto the generating plant, generator governorproblems can also cause over frequency.

SAPTOF is used mainly for generation sheddingand remedial action schemes. It is also used as afrequency stage initiating load restoring.

SAPTOF is provided with an undervoltageblocking.

Rate-of-change frequency protection SAPFRCRate-of-change frequency protection function(SAPFRC) gives an early indication of a maindisturbance in the system. SAPFRC can be usedfor generation shedding, load shedding andremedial action schemes. SAPFRC candiscriminate between positive or negative changeof frequency.

SAPFRC is provided with an undervoltageblocking.

8. Secondary system supervision

Breaker close/trip circuit monitoring TCSSCBRThe trip circuit supervision function TCSSCBR isdesigned to supervise the control circuit of thecircuit breaker. The invalidity of a control circuit isdetected by using a dedicated output contactthat contains the supervision functionality.

The function operates after a predefinedoperating time and resets when the faultdisappears.

9. Control

Bay control QCBAYThe Bay control QCBAY function is used togetherwith Local remote and local remote controlfunctions to handle the selection of the operatorplace per bay. QCBAY also provides blockingfunctions that can be distributed to differentapparatuses within the bay.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

20 ABB

Page 21: Abb Ret650

Local remote LOCREM /Local remote controlLOCREMCTRLThe signals from the local HMI or from an externallocal/remote switch are applied via the functionblocks LOCREM and LOCREMCTRL to the Baycontrol (QCBAY) function block. A parameter infunction block LOCREM is set to choose if theswitch signals are coming from the local HMI orfrom an external hardware switch connected viabinary inputs.

Voltage control TR8ATCC and TCMYLTCAutomatic voltage control for tap changerTR8ATCC and Tap changer control andsupervision, 6 binary inputs TCMYLTC are usedfor control of power transformers with a on-loadtap changer. The functions provide automaticregulation of the voltage on the secondary side oftransformers or alternatively on a load pointfurther out in the network.

Control of a single transformer, as well as controlof up to two transformers within a single RET650,or parallel control of up to four transformers intwo or even four separate RET650 is possible.Note that the last alternative is achieved by usingthe GOOSE interbay communication on the IEC61850-8-1 protocol. For parallel control of powertransformers, three alternative methods areavailable, the master-follower method, thecirculating current method and the reversereactance method.

In RET650 a local HMI page with voltage controlstatus and manual control possibilities isavailable. Manual control is under authoritycontrol if so defined.

IEC09000670-1-en.vsd

IEC09000670 V1 EN

Figure 5. Manual control via local HMI

Voltage control includes many extra features suchas possibility of to avoid simultaneous tapping ofparallel transformers, extensive tap changermonitoring including contact wear and huntingdetection, monitoring of the power flow in thetransformer so that for example, the voltagecontrol can be blocked if the power reverses etc.

In manual operating mode it is possible to giveraise- or lower-commands to the load tapchanger from the local HMI. Such facilities are pre-made in the factory.

Circuit breaker control for circuit breakers, CBC2,CBC3 and CBC4The CBC2, CBC 3 and CBC4 consists of 3functions each:

• SCILO - The Logical node for interlocking.SCILO function is used to enable a switchingoperation if the interlocking conditionspermit. SCILO function itself does notprovide any interlocking functionality. Theinterlocking conditions are generated inseparate function blocks containing theinterlocking logic.

• SCSWI - The Switch controller initializes andsupervises all functions to properly selectand operate switching primary apparatuses.The Switch controller may handle andoperate on one three-phase device.

• SXCBR - The purpose of SXCBR is toprovide the actual status of positions and toperform the control operations, that is, passall the commands to primary apparatuses inthe form of circuit breakers via output boards

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 21

Page 22: Abb Ret650

and to supervise the switching operation andposition.

Logic rotating switch for function selection andLHMI presentation SLGGIOThe logic rotating switch for function selectionand LHMI presentation (SLGGIO) (or the selectorswitch function block) is used to get a selectorswitch functionality similar to the one provided bya hardware selector switch. Hardware selectorswitches are used extensively by utilities, in orderto have different functions operating on pre-setvalues. Hardware switches are however sourcesfor maintenance issues, lower system reliabilityand an extended purchase portfolio. The logicselector switches eliminate all these problems.

Selector mini switch VSGGIOThe Selector mini switch VSGGIO function blockis a multipurpose function used for a variety ofapplications, as a general purpose switch.

VSGGIO can be controlled from the menu or froma symbol on the single line diagram (SLD) on thelocal HMI.

IEC 61850 generic communication I/O functionsDPGGIOThe IEC 61850 generic communication I/Ofunctions (DPGGIO) function block is used tosend double indications to other systems orequipment in the substation. It is especially usedin the interlocking and reservation station-widelogics.

Single point generic control 8 signals SPC8GGIOThe Single point generic control 8 signals(SPC8GGIO) function block is a collection of 8single point commands, designed to bring incommands from REMOTE (SCADA) to those partsof the logic configuration that do not needextensive command receiving functionality (forexample, SCSWI). In this way, simple commandscan be sent directly to the IED outputs, withoutconfirmation. Confirmation (status) of the result ofthe commands is supposed to be achieved byother means, such as binary inputs and SPGGIOfunction blocks. The commands can be pulsed orsteady.

AutomationBits AUTOBITSThe Automation bits function (AUTOBITS) is usedto configure the DNP3 protocol commandhandling.

10. Logic

Tripping logic common 3-phase output SMPPTRCA function block for protection tripping isprovided for each circuit breaker involved in thetripping of the fault. It provides pulse prolongationto ensure a three-phase trip pulse of sufficientlength, as well as all functionality necessary forcorrect co-operation with autoreclosing functions.

The trip function block also includes functionalityfor breaker lock-out.

Trip matrix logic TMAGGIOThe Trip matrix logic TMAGGIO function is usedto route trip signals and other logical outputsignals to the tripping logics SMPPTRC andSPTPTRC or to different output contacts on theIED.

TMAGGIO output signals and the physical outputsallows the user to adapt the signals to thephysical tripping outputs according to the specificapplication needs.

Configurable logic blocksA number of logic blocks and timers are availablefor the user to adapt the configuration to thespecific application needs.

• OR function block.

• INVERTER function blocks that inverts the inputsignal.

• PULSETIMER function block can be used, forexample, for pulse extensions or limiting ofoperation of outputs, settable pulse time.

• GATE function block is used for whether or nota signal should be able to pass from the inputto the output.

• XOR function block.

• LOOPDELAY function block used to delay theoutput signal one execution cycle.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

22 ABB

Page 23: Abb Ret650

• TIMERSET function has pick-up and drop-outdelayed outputs related to the input signal. Thetimer has a settable time delay and must be Onfor the input signal to activate the output withthe appropriate time delay.

• AND function block.

• SRMEMORY function block is a flip-flop thatcan set or reset an output from two inputsrespectively. Each block has two outputs whereone is inverted. The memory setting controls ifthe block's output should reset or return to thestate it was, after a power interruption. The SETinput has priority if both SET and RESET inputsare operated simultaneously.

• RSMEMORY function block is a flip-flop thatcan reset or set an output from two inputsrespectively. Each block has two outputs whereone is inverted. The memory setting controls ifthe block's output should reset or return to thestate it was, after a power interruption. TheRESET input has priority if both SET andRESET are operated simultaneously.

Boolean 16 to Integer conversion B16IBoolean 16 to integer conversion function (B16I)is used to transform a set of 16 binary (logical)signals into an integer.

Boolean 16 to Integer conversion with logic noderepresentation B16IFCVIBoolean 16 to integer conversion with logic noderepresentation function (B16IFCVI) is used totransform a set of 16 binary (logical) signals intoan integer.

Integer to Boolean 16 conversion IB16AInteger to boolean 16 conversion function (IB16A)is used to transform an integer into a set of 16binary (logical) signals.

Integer to Boolean 16 conversion with logic noderepresentation IB16FCVBInteger to boolean conversion with logic noderepresentation function (IB16FCVB) is used totransform an integer to 16 binary (logic) signals.

IB16FCVB function can receive remote valuesover IEC61850 depending on the operatorposition input (PSTO).

11. Monitoring

IEC61850 generic communication I/O functionSPGGIOIEC61850 generic communication I/O functions(SPGGIO) is used to send one single logical signalto other systems or equipment in the substation.

IEC61850 generic communication 1/O function 16inputsIEC 61850 generic communication I/O functions16 inputs (SP16GGIO) function is used to send upto 16 logical signals to other systems orequipment in the substation.

Measurements CVMMXN, CMMXU, VNMMXU,VMMXU, CMSQI, VMSQIThe measurement functions are used to get on-line information from the IED. These servicevalues make it possible to display on-lineinformation on the local HMI and on theSubstation automation system about:

• measured voltages, currents, frequency,active, reactive and apparent power andpower factor

• primary and secondary phasors• current sequence components• voltage sequence components

Event counter CNTGGIOEvent counter (CNTGGIO) has six counters whichare used for storing the number of times eachcounter input has been activated.

Disturbance report DRPRDREComplete and reliable information aboutdisturbances in the primary and/or in thesecondary system together with continuous event-logging is accomplished by the disturbance reportfunctionality.

Disturbance report DRPRDRE, always included inthe IED, acquires sampled data of all selectedanalog input and binary signals connected to thefunction block with a, maximum of 40 analog and96 binary signals.

The Disturbance report functionality is a commonname for several functions:

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 23

Page 24: Abb Ret650

• Event list• Indications• Event recorder• Trip value recorder• Disturbance recorder

The Disturbance report function is characterizedby great flexibility regarding configuration, startingconditions, recording times, and large storagecapacity.

A disturbance is defined as an activation of aninput to the AxRADR or BxRBDR function blocks,which are set to trigger the disturbance recorder.All signals from start of pre-fault time to the endof post-fault time will be included in the recording.

Every disturbance report recording is saved in theIED in the standard Comtrade format. The sameapplies to all events, which are continuouslysaved in a ring-buffer. The local HMI is used toget information about the recordings. Thedisturbance report files may be uploaded toPCM600 for further analysis using the disturbancehandling tool.

Event list DRPRDREContinuous event-logging is useful for monitoringthe system from an overview perspective and is acomplement to specific disturbance recorderfunctions.

The event list logs all binary input signalsconnected to the Disturbance report function. Thelist may contain up to 1000 time-tagged eventsstored in a ring-buffer.

Indications DRPRDRETo get fast, condensed and reliable informationabout disturbances in the primary and/or in thesecondary system it is important to know, forexample binary signals that have changed statusduring a disturbance. This information is used inthe short perspective to get information via thelocal HMI in a straightforward way.

There are three LEDs on the local HMI (green,yellow and red), which will display statusinformation about the IED and the Disturbancereport function (triggered).

The Indication list function shows all selectedbinary input signals connected to the Disturbance

report function that have changed status during adisturbance.

Event recorder DRPRDREQuick, complete and reliable information aboutdisturbances in the primary and/or in thesecondary system is vital, for example, time-tagged events logged during disturbances. Thisinformation is used for different purposes in theshort term (for example corrective actions) and inthe long term (for example functional analysis).

The event recorder logs all selected binary inputsignals connected to the Disturbance reportfunction. Each recording can contain up to 150time-tagged events.

The event recorder information is available for thedisturbances locally in the IED.

The event recording information is an integratedpart of the disturbance record (Comtrade file).

Trip value recorder DRPRDREInformation about the pre-fault and fault values forcurrents and voltages are vital for the disturbanceevaluation.

The Trip value recorder calculates the values of allselected analog input signals connected to theDisturbance report function. The result ismagnitude and phase angle before and during thefault for each analog input signal.

The trip value recorder information is available forthe disturbances locally in the IED.

The trip value recorder information is anintegrated part of the disturbance record(Comtrade file).

Disturbance recorder DRPRDREThe Disturbance recorder function supplies fast,complete and reliable information aboutdisturbances in the power system. It facilitatesunderstanding system behavior and relatedprimary and secondary equipment during andafter a disturbance. Recorded information is usedfor different purposes in the short perspective (forexample corrective actions) and long perspective(for example functional analysis).

The Disturbance recorder acquires sampled datafrom selected analog- and binary signalsconnected to the Disturbance report function

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

24 ABB

Page 25: Abb Ret650

(maximum 40 analog and 96 binary signals). Thebinary signals available are the same as for theevent recorder function.

The function is characterized by great flexibilityand is not dependent on the operation ofprotection functions. It can record disturbancesnot detected by protection functions. Up to threeseconds of data before the trigger instant can besaved in the disturbance file.

The disturbance recorder information for up to100 disturbances are saved in the IED and thelocal HMI is used to view the list of recordings.

Measured value expander block MVEXPThe current and voltage measurements functions(CVMMXN, CMMXU, VMMXU and VNMMXU),current and voltage sequence measurementfunctions (CMSQI and VMSQI) and IEC 61850generic communication I/O functions (MVGGIO)are provided with measurement supervisionfunctionality. All measured values can besupervised with four settable limits: low-low limit,low limit, high limit and high-high limit. Themeasure value expander block has beenintroduced to enable translating the integer outputsignal from the measuring functions to 5 binarysignals: below low-low limit, below low limit,normal, above high-high limit or above high limit.The output signals can be used as conditions inthe configurable logic or for alarming purpose.

Station battery supervision SPVNZBATThe station battery supervision functionSPVNZBAT is used for monitoring battery terminalvoltage.

SPVNZBAT activates the start and alarm outputswhen the battery terminal voltage exceeds the setupper limit or drops below the set lower limit. Atime delay for the overvoltage and undervoltagealarms can be set according to definite timecharacteristics.

In the definite time (DT) mode, SPVNZBAToperates after a predefined operate time andresets when the battery undervoltage orovervoltage condition disappears after reset time.

Insulation gas monitoring function SSIMGInsulation gas monitoring function SSIMG is usedfor monitoring the circuit breaker condition. Binary

information based on the gas pressure in thecircuit breaker is used as input signals to thefunction. In addition, the function generatesalarms based on received information.

Insulation liquid monitoring function SSIMLInsulation liquid monitoring function SSIML isused for monitoring the circuit breaker condition.Binary information based on the oil level in thecircuit breaker is used as input signals to thefunction. In addition, the function generatesalarms based on received information.

Circuit breaker monitoring SSCBRThe circuit breaker condition monitoring functionSSCBR is used to monitor different parameters ofthe circuit breaker. The breaker requiresmaintenance when the number of operations hasreached a predefined value. The energy iscalculated from the measured input currents as a

sum of Iyt values. Alarms are generated when thecalculated values exceed the threshold settings.

The function contains a blocking functionality. It ispossible to block the function outputs, if desired.

12. Metering

Pulse counter logic PCGGIOPulse counter (PCGGIO) function countsexternally generated binary pulses, for instancepulses coming from an external energy meter, forcalculation of energy consumption values. Thepulses are captured by the BIO (binary input/output) module and then read by the PCGGIOfunction. A scaled service value is available overthe station bus.

Function for energy calculation and demandhandling ETPMMTROutputs from the Measurements (CVMMXN)function can be used to calculate energyconsumption. Active as well as reactive values arecalculated in import and export direction. Valuescan be read or generated as pulses. Maximumdemand power values are also calculated by thefunction.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 25

Page 26: Abb Ret650

13. Human Machine interface

Local HMI

IEC12000175 V1 EN

Figure 6. Local human-machine interface

The LHMI of the IED contains the followingelements:• Display (LCD)• Buttons• LED indicators• Communication port

The LHMI is used for setting, monitoring andcontrolling.

The Local human machine interface, LHMIincludes a graphical monochrome LCD with aresolution of 320x240 pixels. The character sizemay vary depending on selected language. Theamount of characters and rows fitting the viewdepends on the character size and the view thatis shown.

The LHMI is simple and easy to understand. Thewhole front plate is divided into zones, each witha well-defined functionality:

• Status indication LEDs• Alarm indication LEDs which can indicate

three states with the colors green, yellowand red, with user printable label. All LEDsare configurable from the PCM600 tool

• Liquid crystal display (LCD)• Keypad with push buttons for control and

navigation purposes, switch for selectionbetween local and remote control and reset

• Five user programmable function buttons• An isolated RJ45 communication port for

PCM600

14. Basic IED functions

Self supervision with internal event listThe Self supervision with internal event list(INTERRSIG and SELFSUPEVLST) function reacts

to internal system events generated by thedifferent built-in self-supervision elements. Theinternal events are saved in an internal event list.

Time synchronizationUse a common global source for example GPStime synchronization inside each substation aswell as inside the area of the utility responsibilityto achieve a common time base for the IEDs in aprotection and control system. This makescomparison and analysis of events anddisturbance data between all IEDs in the powersystem possible.

Time-tagging of internal events and disturbancesare an excellent help when evaluating faults.Without time synchronization, only the eventswithin the IED can be compared to one another.With time synchronization, events anddisturbances within the entire station, and evenbetween line ends, can be compared duringevaluation.

In the IED, the internal time can be synchronizedfrom a number of sources:

• SNTP• IRIG-B• DNP• IEC60870-5-103

Parameter setting groups ACTVGRPUse the four different groups of settings tooptimize the IED operation for different powersystem conditions. Creating and switchingbetween fine-tuned setting sets, either from thelocal HMI or configurable binary inputs, results ina highly adaptable IED that can cope with avariety of power system scenarios.

Test mode functionality TESTMODEThe protection and control IEDs may have manyincluded functions. To make the testingprocedure easier, the IEDs include the featurethat allows individual blocking of all functionsexcept the function(s) the shall be tested.

There are two ways of entering the test mode:

• By configuration, activating an input signal ofthe function block TESTMODE

• By setting the IED in test mode in the localHMI

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

26 ABB

Page 27: Abb Ret650

While the IED is in test mode, all protectionfunctions are blocked.

Any function can be unblocked individuallyregarding functionality and event signaling. Thisenables the user to follow the operation of one orseveral related functions to check functionalityand to check parts of the configuration, and soon.

Change lock function CHNGLCKChange lock function (CHNGLCK) is used toblock further changes to the IED configurationand settings once the commissioning is complete.The purpose is to block inadvertent IEDconfiguration changes beyond a certain point intime.

Authority status ATHSTATAuthority status (ATHSTAT) function is anindication function block for user log-on activity.

Authority check ATHCHCKTo safeguard the interests of our customers, boththe IED and the tools that are accessing the IEDare protected, by means of authorizationhandling. The authorization handling of the IEDand the PCM600 is implemented at both accesspoints to the IED:

• local, through the local HMI• remote, through the communication ports

15. Station communication

IEC 61850-8-1 communication protocolThe IED supports the communication protocolsIEC 61850-8-1 and DNP3 over TCP/IP. Alloperational information and controls are availablethrough these protocols. However, somecommunication functions, for example, horizontalcommunication (GOOSE) between the IEDs, isonly enabled by the IEC 61850-8-1communication protocol.

The IED is equipped with an optical Ethernet rearport for the substation communication standard

IEC 61850-8-1. IEC 61850-8-1 protocol allowsintelligent electrical devices (IEDs) from differentvendors to exchange information and simplifiessystem engineering. Peer-to-peer communicationaccording to GOOSE is part of the standard.Disturbance files uploading is provided.

Disturbance files are accessed using the IEC61850-8-1 protocol. Disturbance files areavailable to any Ethernet based application viaFTP in the standard Comtrade format. Further,the IED can send and receive binary values,double point values and measured values (forexample from MMXU functions), together withtheir quality bit, using the IEC 61850-8-1 GOOSEprofile. The IED meets the GOOSE performancerequirements for tripping applications insubstations, as defined by the IEC 61850standard. The IED interoperates with other IEC61850-compliant IEDs, tools, and systems andsimultaneously reports events to five differentclients on the IEC 61850 station bus.

The event system has a rate limiter to reduceCPU load. The event channel has a quota of 10events/second. If the quota is exceeded the eventchannel transmission is blocked until the eventchanges is below the quota, no event is lost.

All communication connectors, except for thefront port connector, are placed on integratedcommunication modules. The IED is connected toEthernet-based communication systems via thefibre-optic multimode LC connector (100BASE-FX).

The IED supports SNTP and IRIG-B timesynchronization methods with a time-stampingresolution of 1 ms.

• Ethernet based: SNTP and DNP3• With time synchronization wiring: IRIG-B

The IED supports IEC 60870-5-103 timesynchronization methods with a time stampingresolution of 5 ms.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 27

Page 28: Abb Ret650

Table 1. Supported station communication interfaces and protocols

Protocol Ethernet Serial

100BASE-FX LC Glass fibre (ST connector) EIA-485

IEC 61850–8–1 ● - -

DNP3 ● ● ●

IEC 60870-5-103 - ● ●● = Supported

Horizontal communication via GOOSE forinterlockingGOOSE communication can be used forexchanging information between IEDs via the IEC61850-8-1 station communication bus. This istypically used for sending apparatus positionindications for interlocking or reservation signalsfor 1-of-n control. GOOSE can also be used toexchange any boolean, integer, double point andanalog measured values between IEDs.

DNP3 protocolDNP3 (Distributed Network Protocol) is a set ofcommunications protocols used to communicatedata between components in process automationsystems. For a detailed description of the DNP3protocol, see the DNP3 Communication protocolmanual.

IEC 60870-5-103 communication protocolIEC 60870-5-103 is an unbalanced (master-slave)protocol for coded-bit serial communicationexchanging information with a control system,

and with a data transfer rate up to 19200 bit/s. InIEC terminology, a primary station is a master anda secondary station is a slave. Thecommunication is based on a point-to-pointprinciple. The master must have software that caninterpret IEC 60870-5-103 communicationmessages.

IEC 60870-5-103 protocol can be configured touse either the optical serial or RS485 serialcommunication interface on the COM05communication module. The functions Operationselection for optical serial (OPTICALPROT) andOperation selection for RS485 (RS485PROT) areused to select the communication interface.

The functions IEC60870-5-103 Optical serialcommunication (OPTICAL103) andIEC60870-5-103 serial communication for RS485(RS485103) are used to configure thecommunication parameters for either the opticalserial or RS485 serial communication interfaces.

16. Hardware description

Layout and dimensionsMounting alternativesThe following mounting alternatives are available(IP40 protection from the front):

• 19” rack mounting kit

See ordering for details about available mountingalternatives.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

28 ABB

Page 29: Abb Ret650

Rack mounting a single 3U IED

B

A C

D

IEC11000248 V1 EN

Figure 7. Rack mounted 3U IED

A 224 mm + 12 mm with ring-lug connectors

B 22.5 mm

C 482 mm

D 132 mm, 3U

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 29

Page 30: Abb Ret650

17. Connection diagrams Customized

Connection diagrams for 650 series

IEC12000593 V1 EN

Figure 8. Designation for 3U, 1/1x19" casing with 1 TRM

IEC12000594 V1 EN

Figure 9. Designation for 3U, 1/1x19" casing with 1 TRM and 1 AIM

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

30 ABB

Page 31: Abb Ret650

IEC12000595 V1 EN

Figure 10. Communication module (COM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 31

Page 32: Abb Ret650

IEC12000596 V1 EN

Figure 11. Power supply module (PSM) 48-125V DC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

32 ABB

Page 33: Abb Ret650

IEC12000597 V1 EN

Figure 12. Power supply module (PSM) 110-250V DC, 100–240V AC

IEC12000598 V1 EN

Figure 13. Transformer module (TRM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 33

Page 34: Abb Ret650

IEC12000599 V1 EN

Figure 14. Analog input (AIM)

IEC12000600 V1 EN

Figure 15. Binary input/output (BIO) option

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

34 ABB

Page 35: Abb Ret650

18. Connection diagrams Configured

IEC12000560 V1 EN

Figure 16. Designation for 3U, 1/1x19" casing with 1 TRM and 1 AIM (A05)

IEC12000568 V1 EN

Figure 17. Designation for3U, 1/1x19" casing with 1 TRM (A01/A07)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 35

Page 36: Abb Ret650

Connection diagrams for RET650 A01

IEC12000569 V1 EN

Figure 18. Communication module (COM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

36 ABB

Page 37: Abb Ret650

IEC12000570 V1 EN

Figure 19. Power supply module (PSM) 48-125V DC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 37

Page 38: Abb Ret650

IEC12000571 V1 EN

Figure 20. Power supply module (PSM), 110-250V DC, 100–240V AC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

38 ABB

Page 39: Abb Ret650

IEC12000572 V1 EN

Figure 21. Transformer module (TRM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 39

Page 40: Abb Ret650

IEC12000573 V1 EN

Figure 22. Binary input/output (BIO) option

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

40 ABB

Page 41: Abb Ret650

IEC12000574 V1 EN

Figure 23. Binary input/output (BIO) option

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 41

Page 42: Abb Ret650

Connection diagrams for RET650 A05

IEC12000561 V1 EN

Figure 24. Communication module (COM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

42 ABB

Page 43: Abb Ret650

IEC12000562 V1 EN

Figure 25. Power supply module (PSM) 48-125V DC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 43

Page 44: Abb Ret650

IEC12000563 V1 EN

Figure 26. Power supply module (PSM), 110-250V DC, 100–240V AC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

44 ABB

Page 45: Abb Ret650

IEC12000564 V1 EN

Figure 27. Transformer module (TRM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 45

Page 46: Abb Ret650

IEC12000565 V1 EN

Figure 28. Analog input module (AIM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

46 ABB

Page 47: Abb Ret650

IEC12000566 V1 EN

Figure 29. Binary input/output (BIO) option

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 47

Page 48: Abb Ret650

IEC12000567 V1 EN

Figure 30. Binary input/output (BIO) option

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

48 ABB

Page 49: Abb Ret650

Connection diagrams for RET650 A07

IEC12000554 V1 EN

Figure 31. Communication module (COM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 49

Page 50: Abb Ret650

IEC12000555 V1 EN

Figure 32. Power supply module (PSM) 48-125V DC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

50 ABB

Page 51: Abb Ret650

IEC12000556 V1 EN

Figure 33. Power supply module (PSM), 110-250V DC, 100–240V AC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 51

Page 52: Abb Ret650

IEC12000557 V1 EN

Figure 34. Transformer module (TRM)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

52 ABB

Page 53: Abb Ret650

IEC12000558 V1 EN

Figure 35. Binary input/output (BIO) option

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 53

Page 54: Abb Ret650

IEC12000559 V1 EN

Figure 36. Binary input/output (BIO) option

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

54 ABB

Page 55: Abb Ret650

19. Technical data

General

Definitions

Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment

Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions,the equipment meets the specified requirements

Operative range The range of values of a given energizing quantity for which the equipment, under specifiedconditions, is able to perform its intended functions according to the specified requirements

Energizing quantities, rated values and limitsAnalog inputs

Table 2. Energizing inputs

Description Value

Rated frequency 50/60 Hz

Operating range Rated frequency ± 5 Hz

Current inputs Rated current, In 0.1/0.5 A1) 1/5 A2)

Thermal withstand capability:

• Continuously 4 A 20 A

• For 1 s 100 A 500 A *)

• For 10 s 20 A 100 A

Dynamic current withstand:

• Half-wave value 250 A 1250 A

Input impedance <100 mΩ <20 mΩ

Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC

Voltage withstand:

• Continuous 420 V rms

• For 10 s 450 V rms

Burden at rated voltage <0.05 VA

*) max. 350 A for 1 s when COMBITEST test switch is included.

1) Residual current2) Phase currents or residual current

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 55

Page 56: Abb Ret650

Auxiliary AC and DC voltage

Table 3. Power supply

Description 600PSM02 600PSM03

Uauxnominal 48, 60, 110, 125 V DC 100, 110, 120, 220, 240 V AC, 50and 60 Hz

110, 125, 220, 250 V DC

Uauxvariation 80...120% of Un (38.4...150 V DC) 85...110% of Un (85...264 V AC)

80...120% of Un (88...300 V DC)

Maximum load of auxiliary voltagesupply

35 W for DC40 W for AC

Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 and 120 Hz)

Maximum interruption time in theauxiliary DC voltage without resettingthe IED

50 ms at Uaux

Binary inputs and outputs

Table 4. Binary inputs

Description Value

Operating range Maximum input voltage 300 V DC

Rated voltage 24...250 V DC

Current drain 1.6...1.8 mA

Power consumption/input <0.38 W

Threshold voltage 15...221 V DC (parametrizable in the range in steps of 1% ofthe rated voltage)

Table 5. Signal output and IRF output

IRF relay change over - type signal output relay

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5 A

Make and carry for 3.0 s 10 A

Make and carry 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at U< 48/110/220 V DC

≤0.5 A/≤0.1 A/≤0.04 A

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

56 ABB

Page 57: Abb Ret650

Table 6. Power output relays without TCS function

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8 A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at U< 48/110/220 V DC

≤1 A/≤0.3 A/≤0.1 A

Table 7. Power output relays with TCS function

Description Value

Rated voltage 250 V DC

Continuous contact carry 8 A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at U< 48/110/220 V DC

≤1 A/≤0.3 A/≤0.1 A

Control voltage range 20...250 V DC

Current drain through the supervision circuit ~1.0 mA

Minimum voltage over the TCS contact 20 V DC

Table 8. Ethernet interfaces

Ethernet interface Protocol Cable Data transfer rate

100BASE-TX - CAT 6 S/FTP or better 100 MBits/s

100BASE-FX TCP/IP protocol Fibre-optic cable with LCconnector

100 MBits/s

Table 9. Fibre-optic communication link

Wave length Fibre type Connector Permitted path

attenuation1)

Distance

1300 nm MM 62.5/125 μmglass fibre core

LC <8 dB 2 km

1) Maximum allowed attenuation caused by connectors and cable together

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 57

Page 58: Abb Ret650

Table 10. X8/IRIG-B and EIA-485 interface

Type Protocol Cable

Screw terminal, pin rowheader

IRIG-B Shielded twisted pair cableRecommended: CAT 5, Belden RS-485 (9841- 9844) orAlpha Wire (Alpha 6222-6230)

Screw terminal, pin rowheader

Shielded twisted pair cableRecommended: DESCAFLEX RD-H(ST)H-2x2x0.22mm2,Belden 9729, Belden 9829

Table 11. IRIG-B

Type Value Accuracy

Input impedance 430 Ohm —

Minimum input voltageHIGH

4.3 V —

Maximum input voltageLOW

0.8 V —

Table 12. EIA-485 interface

Type Value Conditions

Minimum differential driveroutput voltage

1.5 V —

Maximum output current 60 mA —

Minimum differentialreceiver input voltage

0.2 V —

Supported bit rates 300, 600, 1200, 2400,4800, 9600, 19200, 38400,57600, 115200

Maximum number of 650IEDs supported on thesame bus

32 —

Max. cable length 925 m (3000 ft) Cable: AWG24 or better, stub lines shall be avoided

Table 13. Serial rear interface

Type Counter connector

Serial port (X9) Optical serial port, type ST for IEC 60870-5-103 and DNPserial

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

58 ABB

Page 59: Abb Ret650

Table 14. Optical serial port (X9)

Wave length Fibre type Connector Permitted path attenuation1)

820 nm MM 62,5/125 µmglass fibre core

ST 6.8 dB (approx. 1700m length with 4 db / kmfibre attenuation)

820 nm MM 50/125 µm glassfibre core

ST 2.4 dB (approx. 600m length with 4 db / kmfibre attenuation)

1) Maximum allowed attenuation caused by fibre

Influencing factors

Table 15. Degree of protection of rack-mounted IED

Description Value

Front side IP 40

Rear side, connection terminals IP 20

Table 16. Degree of protection of the LHMI

Description Value

Front and side IP40

Table 17. Environmental conditions

Description Value

Operating temperature range -25...+55ºC (continuous)

Short-time service temperature range -40...+70ºC (<16h)Note: Degradation in MTBF and HMI performanceoutside the temperature range of -25...+55ºC

Relative humidity <93%, non-condensing

Atmospheric pressure 86...106 kPa

Altitude up to 2000 m

Transport and storage temperature range -40...+85ºC

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 59

Page 60: Abb Ret650

Table 18. Environmental tests

Description Type test value Reference

Cold tests operation storage

96 h at -25ºC16 h at -40ºC 96 h at -40ºC

IEC 60068-2-1/ANSI C37.90-2005(chapter 4)

Dry heat tests operation storage

16 h at +70ºC 96 h at +85ºC

IEC 60068-2-2/ANSI C37.90-2005(chapter 4)

Damp heat tests steady state cyclic

240 h at +40ºChumidity 93% 6 cycles at +25 to +55ºChumidity 93...95%

IEC 60068-2-78 IEC 60068-2-30

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

60 ABB

Page 61: Abb Ret650

Type tests according to standards

Table 19. Electromagnetic compatibility tests

Description Type test value Reference

100 kHz and 1 MHz burstdisturbance test

IEC 61000-4-18, level 3IEC 60255-22-1ANSI C37.90.1-2002

• Common mode 2.5 kV

• Differential mode 2.5 kV

Electrostatic discharge test IEC 61000-4-2, level 4IEC 60255-22-2ANSI C37.90.3-2001

• Contact discharge 8 kV

• Air discharge 15 kV

Radio frequency interference tests

• Conducted, common mode 10 V (emf), f=150 kHz...80 MHz IEC 61000-4-6 , level 3IEC 60255-22-6

• Radiated, amplitude-modulated 20 V/m (rms), f=80...1000 MHz andf=1.4...2.7 GHz

IEC 61000-4-3, level 3IEC 60255-22-3ANSI C37.90.2-2004

Fast transient disturbance tests IEC 61000-4-4IEC 60255-22-4, class AANSI C37.90.1-2002

• Communication ports 4 kV

• Other ports 4 kV

Surge immunity test IEC 61000-4-5, level 3/2IEC 60255-22-5

• Communication 1 kV line-to-earth

• Other ports 2 kV line-to-earth, 1 kV line-to-line

Power frequency (50 Hz) magneticfield

IEC 61000-4-8, level 5

• 3 s 1000 A/m

• Continuous 100 A/m

Pulse magnetic field immunity test 1000A/m IEC 61000–4–9, level 5

Power frequency immunity test IEC 60255-22-7, class AIEC 61000-4-16

• Common mode 300 V rms

• Differential mode 150 V rms

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 61

Page 62: Abb Ret650

Table 19. Electromagnetic compatibility tests, continued

Description Type test value Reference

Voltage dips and short interruptionscon DC power supply

Dips:40%/200 ms70%/500 msInterruptions:0-50 ms: No restart0...∞ s : Correct behaviour at powerdown

IEC 60255-11IEC 61000-4-11

Voltage dips and interruptions on ACpower supply

Dips:40% 10/12 cycles at 50/60 Hz70% 25/30 cycles at 50/60 HzInterruptions:0–50 ms: No restart0...∞ s: Correct behaviour at powerdown

IEC 60255–11IEC 61000–4–11

Electromagnetic emission tests EN 55011, class AIEC 60255-25

• Conducted, RF-emission (mainsterminal)

0.15...0.50 MHz < 79 dB(µV) quasi peak< 66 dB(µV) average

0.5...30 MHz < 73 dB(µV) quasi peak< 60 dB(µV) average

• Radiated RF-emission

30...230 MHz < 40 dB(µV/m) quasi peak, measuredat 10 m distance

230...1000 MHz < 47 dB(µV/m) quasi peak, measuredat 10 m distance

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

62 ABB

Page 63: Abb Ret650

Table 20. Insulation tests

Description Type test value Reference

Dielectric tests: IEC 60255-5ANSI C37.90-2005

• Test voltage 2 kV, 50 Hz, 1 min1 kV, 50 Hz, 1 min, communication

Impulse voltage test: IEC 60255-5ANSI C37.90-2005

• Test voltage 5 kV, unipolar impulses, waveform1.2/50 μs, source energy 0.5 J1 kV, unipolar impulses, waveform1.2/50 μs, source energy 0.5 J,communication

Insulation resistance measurements IEC 60255-5ANSI C37.90-2005

• Isolation resistance >100 MΏ, 500 V DC

Protective bonding resistance IEC 60255-27

• Resistance <0.1 Ώ (60 s)

Table 21. Mechanical tests

Description Reference Requirement

Vibration response tests (sinusoidal) IEC 60255-21-1 Class 2

Vibration endurance test IEC60255-21-1 Class 1

Shock response test IEC 60255-21-2 Class 1

Shock withstand test IEC 60255-21-2 Class 1

Bump test IEC 60255-21-2 Class 1

Seismic test IEC 60255-21-3 Class 2

Product safety

Table 22. Product safety

Description Reference

LV directive 2006/95/EC

Standard EN 60255-27 (2005)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 63

Page 64: Abb Ret650

EMC compliance

Table 23. EMC compliance

Description Reference

EMC directive 2004/108/EC

Standard EN 50263 (2000)EN 60255-26 (2007)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

64 ABB

Page 65: Abb Ret650

Differential protection

Table 24. Transformer differential protection T2WPDIF, T3WPDIF

Function Range or value Accuracy

Operating characteristic Adaptable ± 1.0% of Ir for I < Ir± 1.0% of I for I > Ir

Reset ratio >94% -

Unrestrained differential current limit (1.00-50.00)xIBase onhigh voltage winding

± 1.0% of set value

Base sensitivity function (0.05 - 0.60) x IBase ± 1.0% of Ir

Minimum negative sequence current (0.02 - 0.20) x IBase ± 1.0% of Ir

Operate angle, negative sequence (30.0 - 90.0) degrees ± 1.0 degrees

Second harmonic blocking (5.0-100.0)% offundamental differentialcurrent

± 2.0% of applied harmonic magnitude

Fifth harmonic blocking (5.0-100.0)% offundamental differentialcurrent

± 12.0% of applied harmonic magnitude

Connection type for each of the windings Y or D -

Phase displacement between high voltagewinding, W1 and each of the windings, W2and W3. Hour notation

0–11 -

Operate time, restrained function 25 ms typically at 0 to 5x set level

-

Reset time, restrained function 25 ms typically at 5 to 0x set level

-

Operate time, unrestrained function 20 ms typically at 0 to 5x set level

-

Reset time, unrestrained function 25 ms typically at 5 to 0x set level

-

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 65

Page 66: Abb Ret650

Table 25. Restricted earth-fault protection, low impedance REFPDIF

Function Range or value Accuracy

Operate characteristic Adaptable ± 1% of IBase if Ibias < 1.25 IBase (i.e. basesensitivity in section 1 of the operate - restraincharacteristic)± 2% of theoretical operate value (Idiff) if Ibias>= 1.25 IBase (i.e. sections 2 and 3)(The above is valid if IBase is equal to theprotected winding rated current.)

Reset ratio 0.95 -

Directional characteristic, forzero sequence directionalfunction

ROA ± 60 to ± 90 degrees ± 1 degrees at Ibias = IBase± 2 degrees at Ibias = 2 * IBase± 3 degrees at Ibias = 4 * IBase(The above is valid if IBase is equal to theprotected winding rated current.)

Operate time, trip function 25 ms typically at 0 to 10 x IdMin -

Reset time, trip function 30 ms typically at 10 to 0 x IdMin -

Table 26. 1Ph High impedance differential protection HZPDIF

Function Range or value Accuracy

Operate voltage (20-400) VI=U/R

± 1.0% of Ir

Reset ratio >95% -

Maximum continuous power U>Trip2/SeriesResistor ≤200 W -

Operate time 10 ms typically at 0 to 10 x Ud -

Reset time 105 ms typically at 10 to 0 x Ud -

Critical impulse time 2 ms typically at 0 to 10 x Ud -

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

66 ABB

Page 67: Abb Ret650

Current protection

Table 27. Instantaneous phase overcurrent protection, 3-phase output PHPIOC

Function Range or value Accuracy

Operate current (5-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate time 20 ms typically at 0 to 2 x Iset -

Reset time 30 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 5 x Iset -

Reset time 40 ms typically at 5 to 0 x Iset -

Critical impulse time 2 ms typically at 0 to 5 x Iset -

Dynamic overreach < 5% at t = 100 ms -

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 67

Page 68: Abb Ret650

Table 28. Four step phase overcurrent protection, 3-phase output OC4PTOC

Function Setting range Accuracy

Operate current (5-2500)% of lBase ± 1.0% of Ir at I ≤ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I ≤ Ir±1.0% of I at I > Ir

2nd harmonic blocking (5–100)% of fundamental ± 2.0% of Ir

Independent time delay (0.000-60.000) s ± 0.5% ±25 ms

Minimum operate time forinverse characteristics

(0.000-60.000) s ± 0.5% ±25 ms

Inverse characteristics, seetable 65, table 66 and table 67

17 curve types 1) ANSI/IEEE C37.112IEC 60255–151±3% or ±40 ms0.10 ≤ k ≤ 3.001.5 x Iset ≤ I ≤ 20 x Iset

Operate time, nondirectionalstart function

25 ms typically at 0 to 2 x Iset -

Reset time, nondirectional startfunction

30 ms typically at 2 to 0 x Iset -

Operate time, directional startfunction

50 ms typically at 0 to 2 x Iset -

Reset time, directional startfunction

35 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Impulse margin time 15 ms typically -

1) Note: Timing accuracy only valid when 2nd harmonic blocking is turned off

Table 29. Instantaneous residual overcurrent protection EFPIOC

Function Range or value Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate time 20 ms typically at 0 to 2 x Iset -

Reset time 30 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset -

Operate time 10 ms typically at 0 to 5x Iset -

Reset time 40 ms typically at 5 to 0x Iset -

Critical impulse time 2 ms typically at 0 to 5 x Iset -

Dynamic overreach < 5% at t = 100 ms -

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

68 ABB

Page 69: Abb Ret650

Table 30. Four step residual overcurrent protection EF4PTOC

Function Range or value Accuracy

Operate current (1-2500)% of lBase ± 1.0% of Ir at I < Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Operate current for directionalcomparison, Zero sequence

(1–100)% of lBase ± 2.0% of Ir

Operate current for directionalcomparison, Negative sequence

(1–100)% of lBase ± 2.0% of Ir

Min. operating current (1-10000)% of lBase ± 1.0% of Ir at I < Ir± 1.0% of I at I >Ir

Minimum operate time forinverse characteristics

(0.000-60.000) s ± 0.5% ± 25 ms

Timers (0.000-60.000) s ± 0.5% ±25 ms

Inverse characteristics, see table65, table 66 and table 67

17 curve types 1) ANSI/IEEE C37.112IEC 60255–151±3% or ±40 ms0.10 ≤ k ≤ 3.001.5 x Iset ≤ I ≤ 20 x Iset

Minimum polarizing voltage, Zerosequence

(1–100)% of UBase ± 0.5% of Ur

Minimum polarizing voltage,Negative sequence

(1–100)% of UBase ± 0.5% of Ur

Minimum polarizing current, Zerosequence

(2–100)% of IBase ±1.0% of Ir

Minimum polarizing current,Negative sequence

(2–100)% of IBase ±1.0% of Ir

Real part of source Z used forcurrent polarization

(0.50-1000.00) W/phase -

Imaginary part of source Z usedfor current polarization

(0.50–3000.00) W/phase -

Operate time, non-directionalstart function

30 ms typically at 0.5 to 2 x Iset -

Reset time, non-directional startfunction

30 ms typically at 2 to 0.5 x Iset -

Operate time, directional startfunction

30 ms typically at 0,5 to 2 x IN -

Reset time, directional startfunction

30 ms typically at 2 to 0,5 x IN -

1) Note: Timing accuracy only valid when 2nd harmonic blocking is turned off.

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 69

Page 70: Abb Ret650

Table 31. Thermal overload protection, two time constants TRPTTR

Function Range or value Accuracy

Base current 1 and 2 (30–250)% of IBase ± 1.0% of Ir

Operate time:

2 2

2 2ln p

b

I It

I It

æ ö-ç ÷= ×ç ÷-è ø

EQUATION1356 V1 EN (Equation 1)

I = Imeasured

Ip = load current before overloadoccursTime constant τ = (1–500)minutes

IEC 60255–8, ±5% + 200 ms

Alarm level 1 and 2 (50–99)% of heat content tripvalue

± 2.0% of heat content trip

Operate current (50–250)% of IBase ± 1.0% of Ir

Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip

Table 32. Breaker failure protection, 3-phase activation and output CCRBRF

Function Range or value Accuracy

Operate phase current (5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio, phase current > 95% -

Operate residual current (2-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio, residual current > 95% -

Phase current level for blocking ofcontact function

(5-200)% of lBase ± 1.0% of Ir at I £ Ir± 1.0% of I at I > Ir

Reset ratio > 95% -

Timers (0.000-60.000) s ± 0.5% ±10 ms

Operate time for current detection 35 ms typically -

Reset time for current detection 10 ms maximum -

Table 33. Pole discordance protection CCRPLD

Function Range or value Accuracy

Operate value, currentasymmetry level

(0-100) % ± 1.0% of Ir

Reset ratio >95% -

Time delay (0.000-60.000) s ± 0.5% ± 25 ms

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

70 ABB

Page 71: Abb Ret650

Table 34. Directional over/underpower protection GOPPDOP, GUPPDUP

Function Range or value Accuracy

Power level (0.0–500.0)% of SBase ± 1.0% of Sr at S < Sr

± 1.0% of S at S > Sr

(1.0-2.0)% of SBase < ± 50% of set value

(2.0-10)% of SBase < ± 20% of set value

Characteristic angle (-180.0–180.0) degrees 2 degrees

Timers (0.010 - 6000.000) s ± 0.5% ± 25 ms

Table 35. Negative sequence based overcurrent function DNSPTOC

Function Range or value Accuracy

Operate current (2.0 - 5000.0) % of IBase ± 1.0% of Ir at I <Ir± 1.0% of I at I > Ir

Reset ratio > 95 % -

Low voltage level for memory (0.0 - 5.0) % of UBase < ± 0.5% of Ur

Relay characteristic angle (-180 - 180) degrees ± 2.0 degrees

Relay operate angle (1 - 90) degrees ± 2.0 degrees

Timers (0.00 - 6000.00) s ± 0.5% ± 25 ms

Operate time, non-directional 30 ms typically at 0 to 2 x Iset

20 ms typically at 0 to 10 x Iset

-

Reset time, non-directional 40 ms typically at 2 to 0 x Iset -

Operate time, directional 30 ms typically at 0 to 2 x Iset

20 ms typically at 0 to 10 x Iset

-

Reset time, directional 40 ms typically at 2 to 0 x Iset -

Critical impulse time 10 ms typically at 0 to 2 x Iset

2 ms typically at 0 to 10 x Iset

-

Impulse margin time 15 ms typically -

Dynamic overreach < 10% at t = 300 ms -

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 71

Page 72: Abb Ret650

Voltage protection

Table 36. Two step undervoltage protection UV2PTUV

Function Range or value Accuracy

Operate voltage, low and high step (1–100)% of UBase ± 0.5% of Ur

Reset ratio <105% -

Inverse time characteristics for lowand high step, see table 69

- See table 69

Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms

Definite time delays, step 2 (0.000-60.000) s ± 0.5% ±25 ms

Minimum operate time, inversecharacteristics

(0.000–60.000) s ± 0.5% ± 25 ms

Operate time, start function 30 ms typically at 1.2 to 0.5 x Uset -

Reset time, start function 40 ms typically at 0.5 to 1.2 xUset -

Critical impulse time 10 ms typically at 1.2 to 0.8 x Uset -

Impulse margin time 15 ms typically -

Table 37. Two step overvoltage protection OV2PTOV

Function Range or value Accuracy

Operate voltage, low and high step (1-200)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Reset ratio >95% -

Inverse time characteristics for lowand high step, see table 68

- See table 68

Definite time delay, step 1 (0.00 - 6000.00) s ± 0.5% ± 25 ms

Definite time delays, step 2 (0.000-60.000) s ± 0.5% ± 25 ms

Minimum operate time, Inversecharacteristics

(0.000-60.000) s ± 0.5% ± 25 ms

Operate time, start function 30 ms typically at 0 to 2 x Uset -

Reset time, start function 40 ms typically at 2 to 0 x Uset -

Critical impulse time 10 ms typically at 0 to 2 x Uset -

Impulse margin time 15 ms typically -

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

72 ABB

Page 73: Abb Ret650

Table 38. Two step residual overvoltage protection ROV2PTOV

Function Range or value Accuracy

Operate voltage, step 1 (1-200)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Operate voltage, step 2 (1–100)% of UBase ± 0.5% of Ur at U < Ur

± 0.5% of U at U > Ur

Reset ratio >95% -

Inverse time characteristics for lowand high step, see table 70

- See table 70

Definite time setting, step 1 (0.00–6000.00) s ± 0.5% ± 25 ms

Definite time setting, step 2 (0.000–60.000) s ± 0.5% ± 25 ms

Minimum operate time for step 1inverse characteristic

(0.000-60.000) s ± 0.5% ± 25 ms

Operate time, start function 30 ms typically at 0 to 2 x Uset -

Reset time, start function 40 ms typically at 2 to 0 x Uset -

Critical impulse time 10 ms typically at 0 to 1.2 xUset -

Impulse margin time 15 ms typically -

Table 39. Overexcitation protection OEXPVPH

Function Range or value Accuracy

Operate value, start (100–180)% of (UBase/frated) ± 0.5% of U

Operate value, alarm (50–120)% of start level ± 0.5% of Ur at U ≤ Ur

± 0.5% of U at U > Ur

Operate value, high level (100–200)% of (UBase/frated) ± 0.5% of U

Curve type IEEE

2

(0.18 ):

( 1)k

IEEE tM

×=

-

EQUATION1319 V1 EN (Equation 2)

where M = (E/f)/(Ur/fr)

± 5% + 40 ms

Minimum time delay for inversefunction

(0.000–60.000) s ± 0.5% ± 25 ms

Alarm time delay (0.000–60.000) s ± 0.5% ± 25 ms

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 73

Page 74: Abb Ret650

Frequency protection

Table 40. Under frequency protection SAPTUF

Function Range or value Accuracy

Operate value, start function (35.00-75.00) Hz ± 2.0 mHz

Operate value, restore frequency (45 - 65) Hz ± 2.0 mHz

Reset ratio <1.001 -

Operate time, start function At 50 Hz: 200 ms typically at fset +0.5 Hz tofset -0.5 HzAt 60 Hz: 170 ms typically at fset +0.5 Hz tofset -0.5 Hz

-

Reset time, start function At 50 Hz: 60 ms typically at fset -0.5 Hz to fset

+0.5 HzAt 60 Hz: 50 ms typically at fset -0.5 Hz to fset

+0.5 Hz

-

Operate time delay (0.000-60.000)s <250 ms

Restore time delay (0.000-60.000)s <150 ms

Table 41. Overfrequency protection SAPTOF

Function Range or value Accuracy

Operate value, start function (35.00-75.00) Hz ± 2.0 mHz atsymmetrical three-phase voltage

Reset ratio >0.999 -

Operate time, start function At 50 Hz: 200 ms typically at fset -0.5 Hz tofset +0.5 HzAt 60 Hz: 170 ms typically at fset -0.5 Hz tofset +0.5 Hz

-

Reset time, start function At 50 and 60 Hz: 55 ms typically at fset +0.5Hz to fset-0.5 Hz

-

Timer (0.000-60.000)s <250 ms

Table 42. Rate-of-change frequency protection SAPFRC

Function Range or value Accuracy

Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s

Operate value, restore enable frequency (45.00 - 65.00) Hz ± 2.0 mHz

Timers (0.000 - 60.000) s <130 ms

Operate time, start function At 50 Hz: 100 ms typicallyAt 60 Hz: 80 ms typically

-

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

74 ABB

Page 75: Abb Ret650

Secondary system supervision

Table 43. Breaker close/trip circuit monitoring TCSSCBR

Function Range or value Accuracy

Operate time delay (0.020 - 300.000) s ± 0,5% ± 110 ms

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 75

Page 76: Abb Ret650

Control

Table 44. Voltage control TR8ATCC, TCMYLTC

Function Range or value Accuracy

Transformer reactance on ATCC side (0.1–200.0)Ω, primary -

Time delay for lower command when faststep down mode is activated

(1.0–100.0) s -

Voltage control set voltage (85.0–120.0)% of UB2 ±0.5% of Ur

Outer voltage deadband (0.2–9.0)% of UB2 ± 5,0% of set value

Inner voltage deadband (0.1–9.0)% of UB2 ± 5,0% of set value

Upper limit of busbar voltage (80–180)% of UB2 ± 0.5% of Ur

Lower limit of busbar voltage (70–120)% of UB2 ± 0.5% of Ur

Undervoltage block level (0–120)% of UB2 ± 0.5% of Ur

Time delay (long) for automatic controlcommands

(3–1000) s ± 0.5% ± 110 ms

Time delay (short) for automatic controlcommands

(1–1000) s ± 0.5% ± 110 ms

Minimum operating time in inverse mode (3–120) s ± 0.5% ± 110 ms

Line resistance (0.00–150.00)Ω, primary -

Line reactance (-150.00–150.00)Ω, primary -

Load voltage adjustment constants (-20.0–20.0)% of UB2 ± 5,0% of set value

Load voltage auto correction (-20.0–20.0)% of UB2 ± 5,0% of set value

Overcurrent block level (0–250)% of IBase ± 1.0% of Ir at I≤Ir± 1.0% of I at I>Ir

Level for number of counted raise/lowerwithin one hour

(0–30) operations/hour -

Level for number of counted raise/lowerwithin 24 hours

(0–100) operations/day -

Time window for hunting alarm (1–120) minutes -

Hunting detection alarm, max operations/window

(3–30) operations/window -

Alarm level of active power in forward andreverse direction

(-9999.99–9999.99) MW ± 1.0% of Sr

Alarm level of reactive power in forward andreverse direction

(-9999.99–9999.99) MVAr ± 1.0% of Sr

Time delay for alarms from power supervision (1–6000) s ± 0.5% ± 110 ms

Tap position for lowest and highest voltage (1–63) -

Type of code conversion Binary, BCD, Gray, ContactPerTap -

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

76 ABB

Page 77: Abb Ret650

Table 44. Voltage control TR8ATCC, TCMYLTC, continued

Function Range or value Accuracy

Time after position change before the valueis accepted

(1–60) s ± 0.5% ± 110 ms

Tap changer constant time-out (1–120) s ± 0.5% ± 110 ms

Raise/lower command output pulse duration (0.5–10.0) s ± 0.5% ± 110 ms

Logic

Table 45. Tripping logic common 3-phase output SMPPTRC

Function Range or value Accuracy

Trip action 3-ph -

Timers (0.000-60.000) s ± 0.5% ± 10 ms

Table 46. Configurable logic blocks

Logic block Quantity with cycle time Range or value Accuracy

5 ms 20 ms 100 ms

AND 60 60 160 - -

OR 60 60 160 - -

XOR 10 10 20 - -

INVERTER 30 30 80 - -

SRMEMORY 10 10 20 - -

RSMEMORY 10 10 20 - -

GATE 10 10 20 - -

PULSETIMER 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms for20 ms cycle time

TIMERSET 10 10 20 (0.000–90000.000) s ± 0.5% ± 25 ms for20 ms cycle time

LOOPDELAY 10 10 20

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 77

Page 78: Abb Ret650

Monitoring

Table 47. Technical datacovering measurement functions:CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU

Function Range or value Accuracy

Voltage (0.1-1.5) ×Ur ± 0.5% of Ur at U£Ur

± 0.5% of U at U > Ur

Connected current (0.2-4.0) × Ir ± 0.5% of Ir at I £ Ir± 0.5% of I at I > Ir

Active power, P 0.1 x Ur< U < 1.5 x Ur

0.2 x Ir < I < 4.0 x Ir± 1.0% of Sr at S ≤ Sr

± 1.0% of S at S > Sr

Reactive power, Q 0.1 x Ur< U < 1.5 x Ur

0.2 x Ir < I < 4.0 x Ir± 1.0% of Sr at S ≤ Sr

± 1.0% of S at S > Sr

Apparent power, S 0.1 x Ur < U < 1.5 x Ur

0.2 x Ir< I < 4.0 x Ir± 1.0% of Sr at S ≤ Sr

± 1.0% of S at S > Sr

Apparent power, S Three phasesettings

cos phi = 1 ± 0.5% of S at S > Sr

± 0.5% of Sr at S ≤ Sr

Power factor, cos (φ) 0.1 x Ur < U < 1.5 x Ur

0.2 x Ir< I < 4.0 x Ir< 0.02

Table 48. Event counter CNTGGIO

Function Range or value Accuracy

Counter value 0-10000 -

Max. count up speed 10 pulses/s -

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

78 ABB

Page 79: Abb Ret650

Table 49. Disturbance report DRPRDRE

Function Range or value Accuracy

Current recording - ± 1,0% of Ir at I ≤ Ir± 1,0% of I at I > Ir

Voltage recording - ± 1,0% of Ur at U ≤ Ur

± 1,0% of U at U > Ur

Pre-fault time (0.05–3.00) s -

Post-fault time (0.1–10.0) s -

Limit time (0.5–8.0) s -

Maximum number of recordings 100, first in - first out -

Time tagging resolution 1 ms See time synchronizationtechnical data

Maximum number of analog inputs 30 + 10 (external + internallyderived)

-

Maximum number of binary inputs 96 -

Maximum number of phasors in the Trip Valuerecorder per recording

30 -

Maximum number of indications in a disturbance report 96 -

Maximum number of events in the Event recording perrecording

150 -

Maximum number of events in the Event list 1000, first in - first out -

Maximum total recording time (3.4 s recording timeand maximum number of channels, typical value)

340 seconds (100 recordings) at50 Hz, 280 seconds (80recordings) at 60 Hz

-

Sampling rate 1 kHz at 50 Hz1.2 kHz at 60 Hz

-

Recording bandwidth (5-300) Hz -

Table 50. Event list DRPRDRE

Function Value

Buffer capacity Maximum number of events in the list 1000

Resolution 1 ms

Accuracy Depending on time synchronizing

Table 51. Indications DRPRDRE

Function Value

Buffer capacity Maximum number of indications presented for singledisturbance

96

Maximum number of recorded disturbances 100

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 79

Page 80: Abb Ret650

Table 52. Event recorder DRPRDRE

Function Value

Buffer capacity Maximum number of events in disturbance report 150

Maximum number of disturbance reports 100

Resolution 1 ms

Accuracy Depending on timesynchronizing

Table 53. Trip value recorder DRPRDRE

Function Value

Buffer capacity

Maximum number of analog inputs 30

Maximum number of disturbance reports 100

Table 54. Disturbance recorder DRPRDRE

Function Value

Buffer capacity Maximum number of analog inputs 40

Maximum number of binary inputs 96

Maximum number of disturbance reports 100

Maximum total recording time (3.4 s recording time and maximum numberof channels, typical value)

340 seconds (100 recordings) at 50 Hz280 seconds (80 recordings) at 60 Hz

Table 55. Station battery supervision SPVNZBAT

Function Range or value Accuracy

Lower limit for the battery terminalvoltage

(60-140) % of Ubat ± 1.0% of set battery voltage

Reset ratio, lower limit <105 % -

Upper limit for the battery terminalvoltage

(60-140) % of Ubat ± 1.0% of set battery voltage

Reset ratio, upper limit >95 % -

Timers (0.000-60.000) s ± 0.5% ± 110 ms

Table 56. Insulation gas monitoring function SSIMG

Function Range or value Accuracy

Pressure alarm 0.00-25.00 -

Pressure lockout 0.00-25.00 -

Temperature alarm -40.00-200.00 -

Temperature lockout -40.00-200.00 -

Timers (0.000-60.000) s ± 0.5% ± 110 ms

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

80 ABB

Page 81: Abb Ret650

Table 57. Insulation liquid monitoring function SSIML

Function Range or value Accuracy

Alarm, oil level 0.00-25.00 -

Oil level lockout 0.00-25.00 -

Temperature alarm -40.00-200.00 -

Temperature lockout -40.00-200.00 -

Timers (0.000-60.000) s ± 0.5% ± 110 ms

Table 58. Circuit breaker condition monitoring SSCBR

Function Range or value Accuracy

Alarm levels for open and close traveltime

(0-200) ms ± 0.5% ± 25 ms

Alarm levels for number of operations (0 - 9999) -

Setting of alarm for spring chargingtime

(0.00-60.00) s ± 0.5% ± 25 ms

Time delay for gas pressure alarm (0.00-60.00) s ± 0.5% ± 25 ms

Time delay for gas pressure lockout (0.00-60.00) s ± 0.5% ± 25 ms

Metering

Table 59. Pulse counter PCGGIO

Function Setting range Accuracy

Cycle time for report of countervalue

(1–3600) s -

Table 60. Function for energy calculation and demand handling ETPMMTR

Function Range or value Accuracy

Energy metering MWh Export/Import, MVArhExport/Import

Input from MMXU. No extra error at steady load

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 81

Page 82: Abb Ret650

Station communication

Table 61. Communication protocol

Function Value

Protocol TCP/IP Ethernet

Communication speed for the IEDs 100 Mbit/s

Protocol IEC 61850–8–1

Communication speed for the IEDs 100BASE-FX

Protocol DNP3.0/TCP

Communication speed for the IEDs 100BASE-FX

Protocol, serial IEC 60870–5–103

Communication speed for the IEDs 9600 or 19200 Bd

Protocol, serial DNP3.0

Communication speed for the IEDs 300–19200 Bd

HardwareIED

Table 62. Degree of protection of rack-mounted IED

Description Value

Front side IP 40

Rear side, connection terminals IP 20

Table 63. Degree of protection of the LHMI

Description Value

Front and side IP40

Dimensions

Table 64. Dimensions of the IED - 3U full 19" rack

Description Value

Width 442 mm (17.40 inches)

Height 132 mm (5.20 inches), 3U

Depth 249.5 mm (9.82 inches)

Weight box 10 kg (<22.04 lbs)

Weight LHMI 1.3 kg (2.87 lbs)

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

82 ABB

Page 83: Abb Ret650

Inverse time characteristics

Table 65. ANSI Inverse time characteristics

Function Range or value Accuracy

Operating characteristic:

( )1= + ×

-

æ öç ÷ç ÷è ø

P

At B k

I

EQUATION1249-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 -

ANSI Extremely Inverse A=28.2, B=0.1217, P=2.0

ANSI Very inverse A=19.61, B=0.491, P=2.0

ANSI Normal Inverse A=0.0086, B=0.0185, P=0.02, tr=0.46

ANSI Moderately Inverse A=0.0515, B=0.1140, P=0.02

ANSI Long Time Extremely Inverse A=64.07, B=0.250, P=2.0

ANSI Long Time Very Inverse A=28.55, B=0.712, P=2.0

ANSI Long Time Inverse A=0.086, B=0.185, P=0.02

Table 66. IEC Inverse time characteristics

Function Range or value Accuracy

Operating characteristic:

( )1= ×

-

æ öç ÷ç ÷è ø

P

At k

I

EQUATION1251-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01 -

IEC Normal Inverse A=0.14, P=0.02

IEC Very inverse A=13.5, P=1.0

IEC Inverse A=0.14, P=0.02

IEC Extremely inverse A=80.0, P=2.0

IEC Short time inverse A=0.05, P=0.04

IEC Long time inverse A=120, P=1.0

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 83

Page 84: Abb Ret650

Table 67. RI and RD type inverse time characteristics

Function Range or value Accuracy

RI type inverse characteristic

1

0.2360.339

= ×

-

t k

IEQUATION1137-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01

RD type logarithmic inverse characteristic

5.8 1.35= - ×æ öç ÷è ø

tI

Ink

EQUATION1138-SMALL V1 EN

I = Imeasured/Iset

k = (0.05-999) in steps of 0.01

Table 68. Inverse time characteristics for overvoltage protection

Function Range or value Accuracy

Type A curve:

=- >

>

æ öç ÷è ø

tk

U U

U

EQUATION1436-SMALL V1 EN

U> = Uset

U = Umeasured

k = (0.05-1.10) in steps of 0.01 ±5% +60 ms

Type B curve:

2.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1437-SMALL V1 EN

k = (0.05-1.10) in steps of 0.01

Type C curve:

3.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1438-SMALL V1 EN

k = (0.05-1.10) in steps of 0.01

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

84 ABB

Page 85: Abb Ret650

Table 69. Inverse time characteristics for undervoltage protection

Function Range or value Accuracy

Type A curve:

=< -

<

æ öç ÷è ø

kt

U U

UEQUATION1431-SMALL V1 EN

U< = Uset

U = UVmeasured

k = (0.05-1.10) in steps of 0.01 ±5% +60 ms

Type B curve:

2.0

4800.055

32 0.5

×= +

< -× -

<

æ öç ÷è ø

kt

U U

U

EQUATION1432-SMALL V1 EN

U< = Uset

U = Umeasured

k = (0.05-1.10) in steps of 0.01

Table 70. Inverse time characteristics for residual overvoltage protection

Function Range or value Accuracy

Type A curve:

=- >

>

æ öç ÷è ø

tk

U U

U

EQUATION1436-SMALL V1 EN

U> = Uset

U = Umeasured

k = (0.05-1.10) in steps of0.01

±5% +70 ms

Type B curve:

2.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1437-SMALL V1 EN

k = (0.05-1.10) in steps of0.01

Type C curve:

3.0

480

32 0.5 0.035

- >× - -

>

æ öç ÷è ø

tk

U U

U

EQUATION1438-SMALL V1 EN

k = (0.05-1.10) in steps of0.01

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 85

Page 86: Abb Ret650

20. Ordering for Customized IED

Guidelines

Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functionscan only be ordered in combination with other functions and that some functions require specific hardware selections.

Product specification

Basic IED 650 platform and common functions housed in 3U 1/1 sized 19” casing

RET650 Quantity: 1MRK 006 516-AC

Option:

Customer specific configuration On request

Connection type for Analog modules

Rule: One connection type must be selected

Compression terminals 1MRK 002 960-CA

Ring lug terminals 1MRK 002 960-DA

Connection type for Power supply, Input/Output and communication modules

Rule: One connection type must be selected

Compression terminals 1MRK 002 960-EA

Ring lug terminals 1MRK 002 960-FA

Power supply module

Rule: One Power supply module must be specified

Power supply module(PSM) 48-125 VDC 1KHL178073R0001

110-250 VDC, 100–240V AC 1KHL178082R0001

Differential protection

Rule: One and only one of Transformer differential protection can be ordered

Transformer differential protection, two winding (T2WPDIF)

Qty:

1MRK 004 904-AB

Transformer differential protection, three winding (T3WPDIF) Qty: 1MRK 004 904-BB

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

86 ABB

Page 87: Abb Ret650

Control

Rule: One and only one of Circuit breaker must be ordered

Circuit breaker for 2 CB (CBC2) Qty: 1MRK 004 918-BA

Circuit breaker for 3 CB (CBC3) Qty: 1MRK 004 918-CA

Circuit breaker for 4 CB (CBC4) Qty: 1MRK 004 918-DA

Logic

Rule: One Tripping logic must be ordered

Tripping logic, common 3–phase output (SMPPTRC) Qty:

1 2 3 1MRK 004 922-AA

Optional functionsDifferential protection

Restricted earth fault protection, low impedance (REFPDIF)

Qty:

1 2 3 1MRK 004 904-CA

1Ph High impedance differential protection (HZPDIF)

Qty:

1 2 1MRK 004 904-DA

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 87

Page 88: Abb Ret650

Current protection

Instantaneous phase overcurrent protection, 3–phaseoutput (PHPIOC)

Qty:

1 2 3 1MRK 004 908-AA

Four step phase overcurrent protection, 3–phase output(OC4PTOC)

Qty:

1 2 3 1MRK 004 908-BB

Instantaneous residual overcurrent protection (EFPIOC)

Qty:

1 2 3 1MRK 004 908-CA

Four step residual overcurrent protection, zero/negativesequence direction (EF4PTOC)

Qty:

1 2 3 1MRK 004 908-FA

Thermal overload protection, two time constants(TRPTTR)

Qty:

1 2 3 1MRK 004 908-KA

Breaker failure protection, 3–phase activation and output(CCRBRF)

Qty:

1 2 3 1MRK 004 908-LA

Pole discordance protection (CCRPLD)

Qty:

1 2 3 1MRK 004 908-NA

Directional underpower protection (GUPPDUP)

Qty:

1 2 1MRK 004 908-RB

Directional overpower protection (GOPPDUP)

Qty:

1 2 1MRK 004 908-SB

Negative sequence based overcurrent function(DNSPTOC)

Qty:

1 2 1MRK 004 908-TA

Voltage protection

Two step undervoltage protection (UV2PTUV)

Qty:

1 2 1MRK 004 910-AB

Two step overvoltage protection (OV2PTOV)

Qty:

1 2 1MRK 004 910-BB

Two step residual overvoltage protection (ROV2PTOV)

Qty:

1 2 1MRK 004 910-CB

Overexcitation protection (OEXPVPH) Qty: 1MRK 004 910-DC

Frequency protection

Underfrequency protection (SAPTUF)

Qty:

1 2 3 4 1MRK 004 912-AA

Overfrequency protection (SAPTOF)

Qty:

1 2 3 4 1MRK 004 912-BA

Rate-of-change frequency protection (SAPFRC)

Qty:

1 2 3 4 1MRK 004 912-CA

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

88 ABB

Page 89: Abb Ret650

Control

Automatic voltage control for tapchanger, parallel control(TR8ATCC)

Qty:

1 2 1MRK 004 917-EB

Tap changer control and supervision, 6 binary inputs,(TCMYLTC)

Qty:

1 2 1MRK 004 917-FA

Monitoring

Station battery supervision (SPVNZBAT) Qty: 1MRK 004 925-HB

Insulation gas monitoring function (SSIMG)

Qty:

1 2 1MRK 004 925-KA

Insulation liquid monitoring function (SSIML)

Qty:

1 2 1MRK 004 925-LA

Circuit breaker condition monitoring (SSCBR)

Qty:

1 2 3 1MRK 004 925-MA

First local HMI user dialogue language

HMI language, English IEC Always included

Additional local HMI user dialogue language

HMI language, English US 1MRK 002 940-MA

Optional hardwareHuman machine interface

Rule: One must be ordered.

Display type Keypad symbol Case size

Local human machine interface (LHMI) IEC 3U 1/1 19" 1KHL160055R0001

Local human machine interface (LHMI) ANSI 3U 1/1 19" 1KHL160042R0001

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 89

Page 90: Abb Ret650

Analog system

Rule: One Transformer input module must be ordered

Transformer module (TRM) 6I+4U, 1/5A,100/220V Qty: 1KHL178083R0001

Transformer module (TRM) 8I+2U, 1/5A, 100/220V Qty: 1KHL178083R0013

Transformer module (TRM) 4I, 1/5A+1I, 0.1/0.5A+5U, 100/220V Qty: 1KHL178083R0016

Transformer module (TRM) 4I+6U, 1/5A, 100/220V Qty: 1KHL178083R0003

Rule: Only one Analog input module can be ordered

Analog input module (AIM) 6I+4U, 1/5A, 100/220V Qty: 1KHL178083R5001

Analog input module (AIM) 4I, 1/5A+1I, 0.1/0.5A+5U, 100/220V Qty: 1KHL178083R5016

Binary input/output modules

Note: If analog input module (AIM) is ordered only 2 BIO modulescan be ordered

Binary input/output module (BIO) Qty: 1 2 3 4 1KHL178074R0001

Rack mounting kit

Rack mounting kit for 3U 1/1 x 19” case Quantity: 1KHL400352R0001

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

90 ABB

Page 91: Abb Ret650

21. Ordering for Configured IED

GuidelinesCarefully read and follow the set of rules to ensure problem-free order management.Please refer to the available functions table for included application functions.

To obtain the complete ordering code, please combine code from the tables, as given in the example below.

Exemple code: RET650*1.2-A01X00-X00-B1A5-B-A-SA-AB1-RA2B1-AAXX-E. Using the code of each position #1-11specified as RET650*1-2 2-3-4 4-5-6-7 7-8 8-9 9 9-10 10 10 10-11

# 1 - 2 - 3 - 4 - 5 6 - 7 - 8 - 9 - 10 - 11

RET650* - - - - - - - - -

Po

sitio

n

SOFTWARE #1 Notes and Rules

Version number

Version no 1.2

Selection for position #1. 1.2

Configuration alternatives #2 Notes and Rules

Single breaker, 2 winding A01

Single breaker, 3 winding A05

Tap changer control A07

ACT configuration

ABB standard configuration X00

Selection for position #2. X00

Software options #3 Notes and Rules

No option X00

Selection for postition #3 X00

First HMI language #4 Notes and Rules

English IEC B1

Selection for position #4.

Additional HMI language #4

No second HMI language X0

Selection for position #4. B1 X0

Casing #5 Notes and Rules

Rack casing, 3U 1/1 x 19" D

Selection for position #5. D

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 91

Page 92: Abb Ret650

Mounting details with IP40 of protection from the front #6 Notes and Rules

No mounting kit included X

Rack mounting kit for 3U 1/1 x 19" H

Selection for position #6.

Connection type for Power supply, Input/output andCommunication modules

#7 Notes and Rules

Compression terminals S

Ringlug terminals R

Power supply

Slot position:pP

SM

100-240V AC, 110-250V DC, 9BO A

48-125V DC, 9BO B

Selection for position #7.

Human machine interface #8 Notes and Rules

Local human machine interface, OL8000, IEC3U 1/1 x 19", Basic

E

Detached LHMI

No detached mounting of LHMI X0

Selection for position #8. E X0

Connection type for Analog modules #9 Notes and Rules

Compression terminals S

Ringlug terminals R

Analog system

Slot position: p2

Transformer module, 6I + 4U, 1/5A, 100/220V A1 Only in A05 and A07

Transformer module, 8I + 2U, 1/5A, 100/220V A2 Only in A01

Slot position: p4

Analog input module, 6I + 4U, 1/5A, 100/220V B1 Only in A05

Selection for position #9.

Binary input/output module #10 Notes and Rules

Slot position (rear view) p3 p4 p5 p6

Available slots in 1/1 case

No board in slot X X AIM in P4 for A05

Binary input/output module 9 BI, 3 NOTrip, 5 NO Signal, 1 CO Signal

A A A A P5 and P6 option only valid for A01 and A07

Selection for position #10. A A

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

92 ABB

Page 93: Abb Ret650

Communication and processing module #11 Notes and Rules

Slot position (rear view)

pCO

M

12BI, IRIG-B, RS485, Ethernet, LC optical, ST serial F

Selection for position #11. F

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 93

Page 94: Abb Ret650

22. Ordering for Accessories

External resistor unit

High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 20-100V operating voltage

Quantity:

1 2 RK795101-MA

High impedance resistor unit 1-ph with resistor and voltagedependent resistor for 100-400V operating voltage

Quantity:

1 2 RK795101-CB

Configuration and monitoring tools

Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA

LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA

LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA

Manuals

Note: One (1) IED Connect DVD containing user documentationOperation manualTechnical manualInstallation manualCommissioning manualApplication manualCommunication protocol manual, DNP3Communication protocol manual, IEC61850-8-1Communication protocol manual, IEC60870-5-103Cyber security deployment guidelinesType test certificateEngineering manualPoint list manual, DNP3Connectivity packages and LED label template is always included for each IED

Rule: Specify additional quantity of IED Connect DVD requested

User documentation Quantity: 1MRK 003 500-AA

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

94 ABB

Page 95: Abb Ret650

Rule: Specify the number of printed manuals requested

Operation manual IEC Quantity: 1MRK 500 095-UEN

Technical manual IEC Quantity: 1MRK 504 129-UEN

Commissioning manual IEC Quantity: 1MRK 504 130-UEN

Application manual IEC Quantity: 1MRK 504 128-UEN

Communication protocol manual, DNP3 IEC Quantity: 1MRK 511 257-UEN

Communication protocol manual, IEC 61850-8-1 IEC Quantity: 1MRK 511 258-UEN

Communication protocol manual, IEC 60870-5-103 IEC Quantity: 1MRK 511 259-UEN

Engineering manual IEC Quantity: 1MRK 511 261-UEN

Installation manual IEC Quantity: 1MRK 514 015-UEN

Point list manual, DNP3 IEC Quantity: 1MRK 511 260-UEN

Cyber Security deployment guidelines IEC Quantity: 1MRK 511 268-UEN

Reference information

For our reference and statistics we would be pleased to be provided with the following application data:

Country: End user:

Station name: Voltage level: kV

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

ABB 95

Page 96: Abb Ret650

Related documents

Documents related to RET650 Identity number

Application manual 1MRK 504 128-UEN

Technical manual 1MRK 504 129-UEN

Commissioning manual 1MRK 504 130-UEN

Product Guide, configured 1MRK 504 131-BEN

Type test certificate 1MRK 504 131-TEN

Application notes for Circuit Breaker Control 1MRG006806

650 series manuals Identity number

Communication protocol manual, DNP3 1MRK 511 257-UEN

Communication protocol manual, IEC 61850–8–1 1MRK 511 258-UEN

Communication protocol manual, IEC 60870-5-103 1MRK 511 259-UEN

Cyber Security deployment guidelines 1MRK 511 268-UEN

Point list manual, DNP3 1MRK 511 260-UEN

Engineering manual 1MRK 511 261-UEN

Operation manual 1MRK 500 095-UEN

Installation manual 1MRK 514 015-UEN

Transformer protection RET650 1MRK 504 131-BEN -

Product version: 1.2

96 ABB

Page 97: Abb Ret650

97

Page 98: Abb Ret650

Contact us

ABB ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone +46 (0) 21 32 50 00Fax +46 (0) 21 14 69 18

www.abb.com/substationautomation

1MR

K 5

04 1

31-B

EN

Cop

yrig

ht 2

012

AB

B. A

ll rig

hts

rese

rved

.