ABB Reles de Frecuencia

Embed Size (px)

Citation preview

  • 7/27/2019 ABB Reles de Frecuencia

    1/80

    Relion 615 series

    Voltage Protection and ControlREU615

    Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    2/80

  • 7/27/2019 ABB Reles de Frecuencia

    3/80

    Document ID: 1MRS757054

    Issued: 2010-09-24

    Revision: C

    Product version: 3.0

    Copyright 2010 ABB. All rights reserved

  • 7/27/2019 ABB Reles de Frecuencia

    4/80

    CopyrightThis document and parts thereof must not be reproduced or copied without written

    permission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.

    The software or hardware described in this document is furnished under a license

    and may be used, copied, or disclosed only in accordance with the terms of such

    license.

    TrademarksABB and Relion are registered trademarks of ABB Group. All other brand or

    product names mentioned in this document may be trademarks or registered

    trademarks of their respective holders.

    WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    ABB Oy

    Distribution Automation

    P.O. Box 699

    FI-65101 Vaasa, Finland

    Telephone: +358 10 2211

    Facsimile: +358 10 22 41094

    http://www.abb.com/substationautomation

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 7/27/2019 ABB Reles de Frecuencia

    5/80

    DisclaimerThe data, examples and diagrams in this manual are included solely for the concept

    or product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in this

    manual must satisfy themselves that each intended application is suitable and

    acceptable, including that any applicable safety or other operational requirements

    are complied with. In particular, any risks in applications where a system failure and/

    or product failure would create a risk for harm to property or persons (including but

    not limited to personal injuries or death) shall be the sole responsibility of the

    person or entity applying the equipment, and those so responsible are hereby

    requested to ensure that all measures are taken to exclude or mitigate such risks.

    This document has been carefully checked by ABB but deviations cannot be

    completely ruled out. In case any errors are detected, the reader is kindly requested

    to notify the manufacturer. Other than under explicit contractual commitments, in

    no event shall ABB be responsible or liable for any loss or damage resulting from

    the use of this manual or the application of the equipment.

  • 7/27/2019 ABB Reles de Frecuencia

    6/80

    ConformityThis product complies with the directive of the Council of the European

    Communities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerning

    electrical equipment for use within specified voltage limits (Low-voltage directive

    2006/95/EC). This conformity is the result of tests conducted by ABB in

    accordance with the product standards EN 50263 and EN 60255-26 for the EMC

    directive, and with the product standards EN 60255-1 and EN 60255-27 for the low

    voltage directive. The IED is designed in accordance with the international

    standards of the IEC 60255 series.

  • 7/27/2019 ABB Reles de Frecuencia

    7/80

    Table of contentsSection 1 Introduction.......................................................................3

    This manual........................................................................................3

    Intended audience..............................................................................3

    Product documentation.......................................................................4

    Product documentation set............................................................4

    Document revision history.............................................................5

    Related documentation..................................................................6

    Symbols and conventions...................................................................6

    Safety indication symbols..............................................................6

    Manual conventions.......................................................................7

    Functions, codes and symbols......................................................7

    Section 2 REU615 overview...........................................................11Overview...........................................................................................11

    Product version history................................................................11

    PCM600 and IED connectivity package version..........................11

    Operation functionality......................................................................12

    Optional functions........................................................................12

    Physical hardware............................................................................12

    Local HMI.........................................................................................14Display.........................................................................................14

    LEDs............................................................................................15

    Keypad........................................................................................15

    Web HMI...........................................................................................16

    Authorization.....................................................................................17

    Communication.................................................................................18

    Section 3 REU615 standard configurations...................................21Standard configurations....................................................................21

    Connection diagrams........................................................................24Presentation of standard configurations...........................................27

    Standard configuration A..................................................................28

    Applications.................................................................................28

    Functions.....................................................................................29

    Default I/O connections..........................................................30

    Default disturbance recorder settings.....................................31

    Functional diagrams....................................................................32

    Functional diagrams for protection.........................................32

    Functional diagram for disturbance recorder..........................38

    Functional diagrams for control and interlocking....................40

    Table of contents

    REU615 1Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    8/80

    Standard configuration B..................................................................43

    Applications.................................................................................43

    Functions.....................................................................................44

    Default I/O connections..........................................................45Default disturbance recorder settings.....................................47

    Functional diagrams....................................................................47

    Functional diagrams for protection.........................................48

    Functional diagrams for disturbance recorder and

    supervision functions..............................................................51

    Functional diagrams for control and interlocking ...................53

    Section 4 Requirements for measurement transformers................59Current transformers........................................................................59

    Current transformer requirements for non-directional

    overcurrent protection..................................................................59

    Current transformer accuracy class and accuracy limit

    factor......................................................................................59

    Non-directional overcurrent protection...................................60

    Example for non-directional overcurrent protection................61

    Section 5 IED physical connections...............................................63Inputs................................................................................................63

    Energizing inputs.........................................................................63

    Phase currents.......................................................................63

    Residual current.....................................................................63Phase voltages.......................................................................63

    Residual voltage.....................................................................64

    RTD/mA inputs............................................................................64

    Auxiliary supply voltage input......................................................65

    Binary inputs................................................................................65

    Outputs.............................................................................................67

    Outputs for tripping and controlling..............................................67

    Outputs for signalling...................................................................67

    IRF...............................................................................................68

    Section 6 Glossary.........................................................................69

    Table of contents

    2 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    9/80

    Section 1 Introduction

    1.1 This manualThe application manual contains application descriptions and setting guidelines

    sorted per function. The manual can be used to find out when and for what purpose

    a typical protection function can be used. The manual can also be used when

    calculating settings.

    1.2 Intended audienceThis manual addresses the protection and control engineer responsible for

    planning, pre-engineering and engineering.

    The protection and control engineer must be experienced in electrical power

    engineering and have knowledge of related technology, such as communication

    and protocols.

    1MRS757054 C Section 1Introduction

    REU615 3Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    10/80

    1.3 Product documentation1.3.1 Product documentation set

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manual

    Operation manual

    Installation manual

    Service manual

    Engineering manual

    Commissioning manual

    Communication protocolmanual

    Technical manual

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Planning&purchase

    Engineering

    Installing

    Commissioning

    Operation

    Maintenance

    Decommissioning

    deinstalling&disposal

    Application manualApplication manual

    Operation manualOperation manual

    Installation manualInstallation manual

    Service manualService manual

    Engineering manualEngineering manual

    Commissioning manualCommissioning manual

    Communication protocolmanualCommunication protocolmanual

    Technical manualTechnical manual

    en07000220.vsd

    IEC07000220 V1 EN

    Figure 1: The intended use of manuals in different lifecycles

    The engineering manual contains instructions on how to engineer the IEDs using

    the different tools in PCM600. The manual provides instructions on how to set up a

    PCM600 project and insert IEDs to the project structure. The manual also

    recommends a sequence for engineering of protection and control functions, LHMI

    functions as well as communication engineering for IEC 61850 and othersupported protocols.

    The installation manual contains instructions on how to install the IED. The

    manual provides procedures for mechanical and electrical installation. The chapters

    are organized in chronological order in which the IED should be installed.

    The commissioning manual contains instructions on how to commission the IED.

    The manual can also be used by system engineers and maintenance personnel for

    assistance during the testing phase. The manual provides procedures for checking

    of external circuitry and energizing the IED, parameter setting and configuration as

    Section 1 1MRS757054 CIntroduction

    4 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    11/80

    well as verifying settings by secondary injection. The manual describes the process

    of testing an IED in a substation which is not in service. The chapters are organized

    in chronological order in which the IED should be commissioned.

    The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controlling

    and setting the IED. The manual also describes how to identify disturbances and

    how to view calculated and measured power grid data to determine the cause of a

    fault.

    The service manual contains instructions on how to service and maintain the IED.

    The manual also provides procedures for de-energizing, de-commissioning and

    disposal of the IED.

    The application manual contains application descriptions and setting guidelines

    sorted per function. The manual can be used to find out when and for what purpose

    a typical protection function can be used. The manual can also be used when

    calculating settings.

    The technical manual contains application and functionality descriptions and lists

    function blocks, logic diagrams, input and output signals, setting parameters and

    technical data sorted per function. The manual can be used as a technical reference

    during the engineering phase, installation and commissioning phase, and during

    normal service.

    The communication protocol manual describes a communication protocol

    supported by the IED. The manual concentrates on vendor-specific implementations.

    The point list manual describes the outlook and properties of the data points

    specific to the IED. The manual should be used in conjunction with the

    corresponding communication protocol manual.

    Some of the manuals are not available yet.

    1.3.2 Document revision historyDocument revision/date Product version HistoryA/2010-06-11 3.0 First release

    B/2010-06-29 3.0 Terminology corrected

    C/2010-09-24 3.0 Content corrected

    Download the latest documents from the ABB web site http://

    www.abb.com/substationautomation.

    1MRS757054 C Section 1Introduction

    REU615 5Application Manual

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATIONhttp://http//WWW.ABB.COM/SUBSTATIONAUTOMATIONhttp://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 7/27/2019 ABB Reles de Frecuencia

    12/80

    1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MRS756468

    DNP3 Communication Protocol Manual 1MRS756709

    IEC 60870-5-103 Communication Protocol Manual 1MRS756710

    IEC 61850 Engineering Guide 1MRS756475

    Engineering Manual 1MRS757121

    Installation Manual 1MRS756375

    Operation Manual 1MRS756708

    Technical Manual 1MRS756887

    1.4 Symbols and conventions1.4.1 Safety indication symbols

    The electrical warning icon indicates the presence of a hazard

    which could result in electrical shock.

    The warning icon indicates the presence of a hazard which could

    result in personal injury.

    The caution icon indicates important information or warning related

    to the concept discussed in the text. It might indicate the presence

    of a hazard which could result in corruption of software or damage

    to equipment or property.

    The information icon alerts the reader to important facts and

    conditions.

    The tip icon indicates advice on, for example, how to design your

    project or how to use a certain function.

    Although warning hazards are related to personal injury, it should be understood

    that operation of damaged equipment could, under certain operational conditions,

    result in degraded process performance leading to personal injury or death.

    Therefore, comply fully with all warning and caution notices.

    Section 1 1MRS757054 CIntroduction

    6 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    13/80

    1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in this

    manual.

    Abbreviations and acronyms in this manual are spelled out in the glossary. The

    glossary also contains definitions of important terms.

    Push button navigation in the LHMI menu structure is presented by using the

    push button icons, for example:

    To navigate between the options, use and .

    HMI menu paths are presented in bold, for example:

    Select Main menu/Settings.

    LHMI messages are shown in Courier font, for example:

    To save the changes in non-volatile memory, select Yes and press .

    Parameter names are shown in italics, for example:

    The function can be enabled and disabled with the Operation setting.

    Parameter values are indicated with quotation marks, for example:

    The corresponding parameter values are "On" and "Off".

    IED input/output messages and monitored data names are shown in Courier

    font, for example:

    When the function starts, the START output is set to TRUE.

    1.4.3 Functions, codes and symbolsTable 1: REU615 Functions, codes and symbolsFunction IEC 61850 IEC 60617 IEC-ANSIProtectionThree-phase non-directional

    overcurrent protection, low stage,

    instance 1

    PHLPTOC1 3I> (1) 51P-1 (1)

    Three-phase non-directional

    overcurrent protection, high stage,

    instance 1

    PHHPTOC1 3I>> (1) 51P-2 (1)

    Three-phase non-directional

    overcurrent protection,

    instantaneous stage, instance 1

    PHIPTOC1 3I>>> (1) 50P/51P (1)

    Residual overvoltage protection,

    instance 1ROVPTOV1 Uo> (1) 59G (1)

    Residual overvoltage protection,

    instance 2ROVPTOV2 Uo> (2) 59G (2)

    Residual overvoltage protection,

    instance 3ROVPTOV3 Uo> (3) 59G (3)

    Three-phase undervoltage

    protection, instance 1PHPTUV1 3U< (1) 27 (1)

    Three-phase undervoltage

    protection, instance 2PHPTUV2 3U< (2) 27 (2)

    Three-phase undervoltage

    protection, instance 3PHPTUV3 3U< (3) 27 (3)

    Table continues on next page

    1MRS757054 C Section 1Introduction

    REU615 7Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    14/80

    Function IEC 61850 IEC 60617 IEC-ANSIThree-phase overvoltage

    protection, instance 1PHPTOV1 3U> (1) 59 (1)

    Three-phase overvoltage

    protection, instance 2

    PHPTOV2 3U> (2) 59 (2)

    Three-phase overvoltage

    protection, instance 3PHPTOV3 3U> (3) 59 (3)

    Positive-sequence undervoltage

    protection, instance 1PSPTUV1 U1< (1) 47U+ (1)

    Positive-sequence undervoltage

    protection, instance 2PSPTUV2 U1< (2) 47U+ (2)

    Negative-sequence overvoltage

    protection, instance 1NSPTOV1 U2> (1) 47O- (1)

    Negative-sequence overvoltage

    protection, instance 2NSPTOV2 U2> (2) 47O- (2)

    Frequency protection, instance 1 FRPFRQ1 f>/f/f/f/f/f/fT 49T

    Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)

    Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)

    Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)

    Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)

    Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)

    Multi-purpose protection, instance

    11)MAPGAPC1 MAP (1) MAP (1)

    Multi-purpose protection, instance

    21)MAPGAPC2 MAP (2) MAP (2)

    Multi-purpose protection, instance

    31)MAPGAPC3 MAP (3) MAP (3)

    Load shedding and restoration,

    instance 1LSHDPFRQ1 UFLS/R (1) 81LSH (1)

    Load shedding and restoration,

    instance 2LSHDPFRQ2 UFLS/R (2) 81LSH (2)

    Load shedding and restoration,

    instance 3LSHDPFRQ3 UFLS/R (3) 81LSH (3)

    Load shedding and restoration,

    instance 4LSHDPFRQ4 UFLS/R (4) 81LSH (4)

    Load shedding and restoration,

    instance 5LSHDPFRQ5 UFLS/R (5) 81LSH (5)

    ControlCircuit-breaker control CBXCBR1 I O CB I O CB

    Table continues on next page

    Section 1 1MRS757054 CIntroduction

    8 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    15/80

    Function IEC 61850 IEC 60617 IEC-ANSIDisconnector position indication,

    instance 1DCSXSWI1 I O DC (1) I O DC (1)

    Disconnector position indication,

    instance 2

    DCSXSWI2 I O DC (2) I O DC (2)

    Disconnector position indication,

    instance 3DCSXSWI3 I O DC (3) I O DC (3)

    Earthing switch indication ESSXSWI1 I O ES I O ES

    Tap changer position indication TPOSSLTC1 TPOSM 84M

    Tap changer control with voltage

    regulatorOLATCC1 COLTC 90V

    Synchronism and energizing check SECRSYN1 SYNC 25

    Condition monitoringTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

    Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

    Current circuit supervision CCRDIF1 MCS 3I MCS 3I

    Fuse failure supervision SEQRFUF1 FUSEF 60

    MeasurementDisturbance recorder RDRE1 - -

    Three-phase current

    measurement, instance 1CMMXU1 3I 3I

    Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0

    Three-phase voltage measurement VMMXU1 3U 3U

    Residual voltage measurement RESVMMXU1 Uo Vn

    Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0

    Three-phase power and energy

    measurement, including power

    factor

    PEMMXU1 P, E P, E

    RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

    Frequency measurement FMMXU1 f f

    1) Multi-purpose protection is used for, for example, RTD/mA based protection.

    1MRS757054 C Section 1Introduction

    REU615 9Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    16/80

    10

  • 7/27/2019 ABB Reles de Frecuencia

    17/80

    Section 2 REU615 overview

    2.1 OverviewThe voltage protection and control IED, REU615 is available in two standard

    configurations, denoted A and B. Configuration A is preadapted for voltage and

    frequency-based protection schemes in utility and industrial power systems and

    distribution systems including networks with distributed power generation. The B

    configuration is designed for automatic voltage regulation of power transformers

    equipped with an on-load tap-changer. Both configurations also feature additional

    CB control, measuring and supervising functions. REU615 is a member of ABBs

    Relion product family and part of its 615 protection and control product series.

    The 615 series IEDs are characterized by their compactness and withdrawableunit

    design.

    Re-engineered from the ground up, the 615 series has been designed to unleash the

    full potential of the IEC 61850 standard for communication and interoperability

    between substation automation devices. Once the standard configuration IED has

    been given the application-specific settings, it can directly be put into service.

    The 615 series IEDs support a range of communication protocols including IEC

    61850 with GOOSE messaging, IEC 60870-5-103, Modbus

    and DNP3.

    2.1.1 Product version historyProduct version Product history3.0 Product released

    2.1.2 PCM600 and IED connectivity package version Protection and Control IED Manager PCM600 Ver. 2.3 or later

    REU615 Connectivity Package Ver. 3.0 or later

    Parameter Setting

    Firmware Update

    Disturbance Handling

    Signal Monitoring

    Lifecycle Traceability

    Signal Matrix

    Communication Management

    IED Configuration Migration

    Configuration Wizard

    Label Printing

    1MRS757054 C Section 2REU615 overview

    REU615 11Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    18/80

    IED User Management

    Application Configuration

    Graphical Display Editor

    Download connectivity packages from the ABB web site http://

    www.abb.com/substationautomation

    2.2 Operation functionality2.2.1 Optional functions

    Arc protection (configuration A only)

    Modbus TCP/IP or RTU/ASCII

    IEC 60870-5-103

    DNP3 TCP/IP or serial

    RTD/mA measurements and multi-purpose protection (configuration B only)

    2.3 Physical hardwareThe IED consists of two main parts: plug-in unit and case. The content depends onthe ordered functionality.

    Table 2: Plug-in unit and caseMain Slot ID Content optionsPlug-in

    unit

    - HMI Small (4 lines, 16 characters)

    Large (8 lines, 16 characters)

    X100 Auxiliary power/BO

    module

    48-250V DC/100-240 V AC; or 24-60 V DC

    2 normally-open PO contacts

    1 change-over SO contacts

    1 normally open SO contact

    2 double-pole PO contacts with TCS

    1 dedicated internal fault output contact

    X110 BIO module 8 binary inputs

    4 signal output contacts

    X120 AI/BI module Only with configuration B:

    3 phase current inputs (1/5 A)

    1 residual current input (1/5 A)

    3 phase voltage inputs (60-210 V)

    Table continues on next page

    Section 2 1MRS757054 CREU615 overview

    12 REU615Application Manual

    http://http//WWW.ABB.COM/SUBSTATIONAUTOMATIONhttp://http//WWW.ABB.COM/SUBSTATIONAUTOMATION
  • 7/27/2019 ABB Reles de Frecuencia

    19/80

    Main Slot ID Content optionsCase X130 AI/BI module Only with configuration A:

    3 phase voltage inputs (60-210 V)

    1 residual voltage input (60-210 V)

    1 reference voltage input for SECRSYN1 (60-210 V)

    4 binary inputs

    Optional RTD/mA module Optional for configuration B:

    2 generic mA inputs

    6 RTD sensor inputs

    Optional BIO module Optional for configuration B:

    6 binary inputs

    3 signal output contacts

    X000 Optional communication

    module

    See technical manual for details about different

    type of communication modules.

    Rated values of the current and voltage inputs are basic setting parameters of the

    IED. The binary input thresholds are selectable within the range 18176 V DC by

    adjusting the binary input setting parameters.

    The rated input levels are selected in the IED software for phase current and

    ground current. The binary input thresholds 18...176 V DC are selected by

    adjusting the IED's parameter settings.

    The optional BIO module can be added in the IED to all standard

    configurations.

    The connection diagrams of different hardware modules are presented in this manual.

    See the installation manual for more information about the case and

    the plug-in unit.

    T ab le 3: N um be r of p hysica l co nne ction s in sta nda rd co nfig ura tio nsConf. Analog channels Binary channels CT VT RTD/mA BI BO

    A - 5 - 12 10

    B 4 3- 8 (14)1) 10 (13)1)

    6/22) 8 10

    1) With optional BIO module

    2) With optional RTD/mA module

    1MRS757054 C Section 2REU615 overview

    REU615 13Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    20/80

    2.4 Local HMI

    REF615

    Overcurrent

    Dir. earth-fault

    Voltage protection

    Phase unbalance

    Thermal overload

    Breaker failure

    Disturb. rec. Triggered

    CB condition monitoring

    Supervision

    Arc detected

    Autoreclose shot in progr.

    A070704 V3 EN

    Figure 2: Example of 615 series LHMI

    The LHMI of the IED contains the following elements:

    Display

    Buttons

    LED indicators

    Communication port

    The LHMI is used for setting, monitoring and controlling.

    2.4.1 DisplayThe LHMI includes a graphical display that supports two character sizes. The

    character size depends on the selected language. The amount of characters and

    rows fitting the view depends on the character size.

    Section 2 1MRS757054 CREU615 overview

    14 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    21/80

    Table 4: Characters and rows on the viewCharacter size Rows in view Characters on rowSmall, mono-spaced (6x12

    pixels)

    5 rows

    10 rows with large screen

    20

    Large, variable width (13x14

    pixels)

    4 rows

    8 rows with large screen

    min 8

    The display view is divided into four basic areas.

    1 2

    3 4

    A070705 V2 EN

    Figure 3: Display layout

    1 Header

    2 Icon

    3 Content

    4 Scroll bar (displayed when needed)

    2.4.2 LEDsThe LHMI includes three protection indicators above the display: Ready, Start and

    Trip.

    There are also 11 matrix programmable LEDs on front of the LHMI. The LEDs

    can be configured with PCM600 and the operation mode can be selected with the

    LHMI, WHMI or PCM600.

    2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in different

    views or menus. With the push-buttons you can give open or close commands to

    one object in the primary circuit, for example, a circuit breaker, a contactor or a

    disconnector. The push-buttons are also used to acknowledge alarms, reset

    indications, provide help and switch between local and remote control mode.

    1MRS757054 C Section 2REU615 overview

    REU615 15Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    22/80

    A071176 V1 EN

    Figure 4: LHMI keypad with object control, navigation and command push-

    buttons and RJ-45 communication port

    2.5 Web HMIThe WHMI enables the user to access the IED via a web browser. The supported

    web browser version is Internet Explorer 7.0 or later.

    WHMI is disabled by default.

    WHMI offers several functions.

    Programmable LEDs and event lists

    System supervision

    Parameter settings

    Measurement display

    Disturbance records

    Phasor diagram

    Single-line diagram

    The menu tree structure on the WHMI is almost identical to the one on the LHMI.

    Section 2 1MRS757054 CREU615 overview

    16 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    23/80

    A070754 V3 EN

    Figure 5: Example view of the WHMI

    The WHMI can be accessed locally and remotely.

    Locally by connecting your laptop to the IED via the front communication port.

    Remotely over LAN/WAN.

    2.6 AuthorizationThe user categories have been predefined for the LHMI and the WHMI, each with

    different rights and default passwords.

    The default passwords can be changed with Administrator user rights.

    User authorization is disabled by default but WHMI always uses

    authorization.

    1MRS757054 C Section 2REU615 overview

    REU615 17Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    24/80

    Table 5: Predefined user categoriesUsername User rightsVIEWER Read only access

    OPERATOR Selecting remote or local state with (only locally) Changing setting groups

    Controlling

    Clearing indications

    ENGINEER Changing settings

    Clearing event list

    Clearing disturbance records

    Changing system settings such as IP address, serial baud rate

    or disturbance recorder settings

    Setting the IED to test mode

    Selecting language

    ADMINISTRATOR All listed above

    Changing password Factory default activation

    For user authorization for PCM600, see PCM600 documentation.

    2.7 CommunicationThe IED supports a range of communication protocols including IEC 61850, IEC

    60870-5-103, Modbus and DNP3. Operational information and controls are

    available through these protocols. However, some communication functionality,

    for example, horizontal communication between the IEDs, is only enabled by the

    IEC 61850 communication protocol.

    The IEC 61850 communication implementation supports all monitoring and

    control functions. Additionally, parameter settings, disturbance recordings and

    fault records can be accessed using the IEC 61850 protocol. Disturbance recordings

    are available to any Ethernet-based application in the standard COMTRADE file

    format. The IED can send and receive binary signals from other IEDs (so calledhorizontal communication) using the IEC61850-8-1 GOOSE profile, where the

    highest performance class with a total transmission time of 3 ms is supported.

    Further, the IED supports sending and receiving of analog values using GOOSE

    messaging. The IED meets the GOOSE performance requirements for tripping

    applications in distribution substations, as defined by the IEC 61850 standard. The

    IED can simultaneously report events to five different clients on the station bus.

    The IED can support five simultaneous clients. If PCM600 reserves one client

    connection, only four client connections are left, for example, for IEC 61850 and

    Modbus.

    Section 2 1MRS757054 CREU615 overview

    18 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    25/80

    All communication connectors, except for the front port connector, are placed on

    integrated optional communication modules. The IED can be connected to Ethernet-

    based communication systems via the RJ-45 connector (100Base-TX) or the fibre-

    optic LC connector (100Base-FX).

    Managed Ethernet switch

    with RSTP support

    Managed Ethernet switch

    with RSTP support

    RED615 REF615 RET615 REU615 REM615

    Client BClient A

    Network

    Network

    GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V1 EN

    Figure 6: Self-healing Ethernet ring solution

    The Ethernet ring solution supports the connection of up to thirty

    615 series IEDs. If more than 30 IEDs are to be connected, it is

    recommended that the network is split into several rings with no

    more than 30 IEDs per ring.

    1MRS757054 C Section 2REU615 overview

    REU615 19Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    26/80

    20

  • 7/27/2019 ABB Reles de Frecuencia

    27/80

    Section 3 REU615 standard configurations

    3.1 Standard configurationsREU615 is available in two standard configurations. The standard signal

    configuration can be altered by means of the graphical signal matrix or the optional

    graphical application functionality of the Protection and Control IED Manager

    PCM600. Further, the application configuration functionality of PCM600 supports

    the creation of multi-layer logic functions using various logical elements, including

    timers and flip-flops. By combining protection functions with logic function

    blocks, the IED configuration can be adapted to user-specific application

    requirements.

    Table 6: Standard configurationsDescription Std.conf.Voltage and frequency based protection and measurement functions, synchrocheck

    and load sheddingA

    Automatic voltage regulator B

    Table 7: Supported functionsFunctionality A BProtection1)Three-phase non-directional overcurrent protection, low stage, instance 1 -

    Three-phase non-directional overcurrent protection, high stage, instance 1 -

    Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 -

    Residual overvoltage protection, instance 1 2) -

    Residual overvoltage protection, instance 2 2) -

    Residual overvoltage protection, instance 3 2) -

    Three-phase undervoltage protection, instance 1

    Three-phase undervoltage protection, instance 2

    Three-phase undervoltage protection, instance 3

    Three-phase overvoltage protection, instance 1

    Three-phase overvoltage protection, instance 2

    Three-phase overvoltage protection, instance 3

    Positive-sequence undervoltage protection, instance 1 -

    Positive-sequence undervoltage protection, instance 2 -

    Negative-sequence overvoltage protection, instance 1 -

    Negative-sequence overvoltage protection, instance 2 -

    Table continues on next page

    1MRS757054 C Section 3REU615 standard configurations

    REU615 21Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    28/80

    Functionality A BFrequency protection, instance 1 -

    Frequency protection, instance 2 -

    Frequency protection, instance 3 -

    Frequency protection, instance 4 -

    Frequency protection, instance 5 -

    Frequency protection, instance 6 -

    Three-phase thermal overload protection for power transformers, two time constants -

    Master trip, instance 1

    Master trip, instance 2

    Arc protection, instance 1 o3) -

    Arc protection, instance 2 o3) -

    Arc protection, instance 3 o3) -

    Multi-purpose protection, instance 14) - o

    Multi-purpose protection, instance 24) - o

    Multi-purpose protection, instance 34) - o

    Load shedding and restoration, instance 1 -

    Load shedding and restoration, instance 2 -

    Load shedding and restoration, instance 3 -

    Load shedding and restoration, instance 4 -

    Load shedding and restoration, instance 5 -

    ControlCircuit-breaker control

    Disconnector position indication, instance 1

    Disconnector position indication, instance 2

    Disconnector position indication, instance 3

    Earthing switch indication

    Tap changer position indication -

    Tap changer control with voltage regulator -

    Synchronism and energizing check -

    Condition MonitoringTrip circuit supervision, instance 1 Trip circuit supervision, instance 2

    Current circuit supervision -

    Fuse failure supervision -

    MeasurementDisturbance recorder

    Three-phase current measurement, instance 1 -

    Sequence current measurement -

    Three-phase voltage measurement

    Table continues on next page

    Section 3 1MRS757054 CREU615 standard configurations

    22 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    29/80

    Functionality A BResidual voltage measurement -

    Sequence voltage measurement

    Three-phase power and energy measurement, including power factor -

    RTD/mA measurement - o

    Frequency measurement -

    = included, o = optional at the time of order

    1) Note that all directional protection functions can also be used in non-directional mode.

    2) Uo selectable by parameter, Uo measured as default.

    3) Light only.

    4) Multi-purpose protection is used for, for example, RTD/mA based protection.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 23Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    30/80

    3.2 Connection diagrams

    GUID-E8E4A6F1-57F5-4E53-AACF-FA95E7D92D83 V1 EN

    Figure 7: Connection diagram for the A configuration

    Section 3 1MRS757054 CREU615 standard configurations

    24 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    31/80

    GUID-46B7ECD1-0F3F-4DCA-8144-8A485D02061A V1 EN

    Figure 8: Connection diagram for the A configuration (voltage protection with

    phase-to-earth voltage measurement)

    1MRS757054 C Section 3REU615 standard configurations

    REU615 25Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    32/80

    GUID-64ADD3D1-99D0-458B-8E28-5023277CFD6C V1 EN

    Figure 9: Connection diagram for the B configuration

    Section 3 1MRS757054 CREU615 standard configurations

    26 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    33/80

    GUID-AE8916E5-D21C-4C90-B38A-C93EDE80FF2E V1 EN

    Figure 10: Connection diagram for the B configuration (on load tap changer

    control with phase-to-earth voltage measurement)

    3.3 Presentation of standard configurationsFunctional diagramsThe functional diagrams describe the IED's functionality from the protection,

    measuring, condition monitoring, disturbance recording, control and interlocking

    perspective. Diagrams show the default functionality with simple symbol logics

    1MRS757054 C Section 3REU615 standard configurations

    REU615 27Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    34/80

    forming principle diagrams. The external connections to primary devices are also

    shown, stating the default connections to measuring transformers. The positive

    measuring direction of directional protection functions is towards the outgoing feeder.

    The functional diagrams are divided into sections with each section constitutingone functional entity. The external connections are also divided into sections. Only

    the relevant connections for a particular functional entity are presented in each

    section.

    Protection function blocks are part of the functional diagram. They are identified

    based on their IEC 61850 name but the IEC based symbol and the ANSI function

    number are also included. Some function blocks, such as PHHPTOC, are used

    several times in the configuration. To separate the blocks from each other, the IEC

    61850 name, IEC symbol and ANSI function number are appended with a running

    number, that is an instance number, from one upwards. If the block has no suffix

    after the IEC or ANSI symbol, the function block has been used, that is,instantiated, only once. The IEDs internal functionality and the external

    connections are separated with a dashed line presenting the IEDs physical casing.

    Signal Matrix and Application ConfigurationWith Signal Matrix and Application Configuration in PCM600, it is possible to

    modify the standard configuration according to the actual needs. The IED is

    delivered from the factory with default connections described in the functional

    diagrams for binary inputs, binary outputs, function-to-function connections and

    alarm LEDs. The Signal Matrix is used for GOOSE signal input engineering and

    for making cross-references between the physical I/O signals and the function

    blocks. The Signal Matrix tool cannot be used for adding or removing functionblocks, for example, GOOSE receive function blocks. The Application

    Configuration tool is used for these kind of operations. If a function block is

    removed with Application Configuration, the function related data disappears from

    the menus as well as from the 61850 data model, with the exception of some basic

    function blocks, which are mandatory and thus cannot be removed from the IED

    configuration by removing them from the Application Configuration.

    3.4 Standard configuration A3.4.1 Applications

    The standard configuration is intended for voltage protection and synchronism

    check in medium voltage networks. The standard configuration handles fault

    conditions originating from abnormal voltages in the power system. Also the

    synchronism and energizing check can be handled for two galvanically

    interconnected networks.

    The IED with a standard configuration is delivered from the factory with default

    settings and parameters. The end-user flexibility for incoming, outgoing and

    Section 3 1MRS757054 CREU615 standard configurations

    28 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    35/80

    internal signal designation within the IED enables this configuration to be further

    adapted to different primary circuit layouts and the related functionality needs by

    modifying the internal functionality using PCM600.

    3.4.2 FunctionsTable 8: Functions included in the standard configuration AFunctionality IEC 61850 IEC 60617 IEC-ANSIProtectionResidual overvoltage protection,

    instance 1

    ROVPTOV1 Uo> (1) 59G (1)

    Residual overvoltage protection,

    instance 2

    ROVPTOV2 Uo> (2) 59G (2)

    Residual overvoltage protection,

    instance 3

    ROVPTOV3 Uo> (3) 59G (3)

    Three-phase undervoltage

    protection, instance 1

    PHPTUV1 3U< (1) 27 (1)

    Three-phase undervoltage

    protection, instance 2

    PHPTUV2 3U< (2) 27 (2)

    Three-phase undervoltage

    protection, instance 3

    PHPTUV3 3U< (3) 27 (3)

    Three-phase overvoltage

    protection, instance 1

    PHPTOV1 3U> (1) 59 (1)

    Three-phase overvoltage

    protection, instance 2

    PHPTOV2 3U> (2) 59 (2)

    Three-phase overvoltage

    protection, instance 3

    PHPTOV3 3U> (3) 59 (3)

    Positive-sequence undervoltage

    protection, instance 1

    PSPTUV1 U1< (1) 47U+ (1)

    Positive-sequence undervoltage

    protection, instance 2

    PSPTUV2 U1< (2) 47U+ (2)

    Negative-sequence overvoltage

    protection, instance 1

    NSPTOV1 U2> (1) 47O- (1)

    Negative-sequence overvoltage

    protection, instance 2

    NSPTOV2 U2> (2) 47O- (2)

    Frequency protection, instance 1 FRPFRQ1 f>/f/f/f/f/f/f

  • 7/27/2019 ABB Reles de Frecuencia

    36/80

    Functionality IEC 61850 IEC 60617 IEC-ANSILoad shedding and restoration,

    instance 1

    LSHDPFRQ1 UFLS/R (1) 81LSH (1)

    Load shedding and restoration,

    instance 2

    LSHDPFRQ2 UFLS/R (2) 81LSH (2)

    Load shedding and restoration,

    instance 3

    LSHDPFRQ3 UFLS/R (3) 81LSH (3)

    Load shedding and restoration,

    instance 4

    LSHDPFRQ4 UFLS/R (4) 81LSH (4)

    Load shedding and restoration,

    instance 5

    LSHDPFRQ5 UFLS/R (5) 81LSH (5)

    ControlCircuit-breaker control CBXCBR1 I O CB I O CB

    Disconnector position indication,

    instance 1

    DCSXSWI1 I O DC (1) I O DC (1)

    Disconnector position indication,instance 2

    DCSXSWI2 I O DC (2) I O DC (2)

    Disconnector position indication,

    instance 3

    DCSXSWI3 I O DC (3) I O DC (3)

    Earthing switch indication ESSXSWI1 I O ES I O ES

    Synchronism and energizing check SECRSYN1 SYNC 25

    Condition monitoringTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

    Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

    MeasurementDisturbance recorder RDRE1 - -

    Three-phase voltage measurement VMMXU1 3U 3U

    Residual voltage measurement RESVMMXU1 Uo Vn

    Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0

    Frequency measurement FMMXU1 f f

    3.4.2.1 Default I/O connectionsTable 9: Default connections for binary inputsBinary input Default usage Connector pinsX110-BI1 Setting group change X110-1,2

    X110-BI2 Manual restore group 1 X110-3,4

    X110-BI3 Manual restore group 2 X110-5,6

    X110-BI4 X110-7,6

    X110-BI5 Voltage transformer truck in indication X110-8,9

    X110-BI6 Voltage transformer truck out indication X110-10,9

    X110-BI7 Earth switch closed indication X110-11,12

    X110-BI8 Earth switch open indication X110-13,12

    Table continues on next page

    Section 3 1MRS757054 CREU615 standard configurations

    30 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    37/80

    Binary input Default usage Connector pinsX130-BI1 Blown primary fuse indication X130-1,2

    X130-BI2 Line voltage transformer MCB open X130-2,3

    X130-BI3 Bus voltage transformer MCB open X130-4,5

    X130-BI4 Lockout reset X130-5,6

    Table 10: D efault connections for binary outputsBinary output Default usage Connector pinsX100-PO1 X100-6,7

    X100-PO2 In synchronism for close X100-8,9

    X100-SO1 General start indication X100-10,11,(12)

    X100-SO2 General operate indication X100-13,14

    X100-PO3 Open circuit breaker/trip coil 1 X100-15-19

    X100-PO4 Open circuit breaker/trip coil 2 X100-20-24

    X110-SO1 Load shedding group 1 X110-14,15,16

    X110-SO2 Load shedding group 2 X110-17,18,19

    X110-SO3 Load restore group 1 X110-20,21,22

    X110-SO4 Load restore group 2 X110-23,24

    Table 11: Default connections for LEDsLED Default usage1 Overvoltage protection operated

    2 Undervoltage protection operated

    3 Residual voltage protection operated

    4 Sequence voltage protection operated

    5 Frequency protection operated

    6 Load shedding operated

    7 Disturbance recorder triggered

    8 Systems synchronized

    9 Voltage transformer secondary MCB open

    10 Arc fault detected

    11 Primary voltage transformer fuse blown

    3.4.2.2 Default disturbance recorder settings

    1MRS757054 C Section 3REU615 standard configurations

    REU615 31Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    38/80

    T ab le 12 : D efa ult ana lo g ch an nel se le ction an d tex t s ettin gsChannel Selection and text1 Uo

    2 U13 U2

    4 U3

    5 U1B

    6 -

    7 -

    8 -

    9 -

    10 -

    11 -

    12 -

    Additionally, all the digital inputs that are connected by default are also enabled

    with the setting. Default triggering settings are selected depending on the

    connected input signal type. Typically all protection START signals are selected to

    trigger the disturbance recorded by default.

    3.4.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function-

    to-function connections. The default connections can be viewed and changed with

    PCM600 according to the application requirements, if necessary.

    The analog channels, measurements from voltage transformers, have fixed

    connections towards the different function blocks inside the IEDs standard

    configuration. Exceptions from this rule are the eight analog channels available for

    the disturbance recorder function. These channels are freely selectable and a part of

    the disturbance recorders parameter settings.

    The analog channels are assigned to different functions. The common signal

    marked with 3U represents the three phase voltages. The signal marked with Uorepresents the measured residual voltage via open-delta connected voltage

    transformers.

    3.4.3.1 Functional diagrams for protectionThe functional diagrams describe the IEDs protection functionality in detail and

    picture the factory set default connections.

    Section 3 1MRS757054 CREU615 standard configurations

    32 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    39/80

    GUID-4071AE4F-377A-4D4A-A506-B5A55C840C74 V1 EN

    Figure 11: Overvoltage protection

    Three overvoltage protection stages (PHxPTOV) protect against abnormal phase

    voltage conditions in the power system. The operation of voltage functions is

    connected to alarm LED 1.

    Depending on the selected operation mode, the active setting group can be changed

    either with a parameter or via binary input.

    All operate signals are connected to the Master Trip and also to the alarm LEDs.

    LED 1 indicates operation of overvoltage and LED 2 operation of undervoltage

    protection functions. LED 3 indicates operation of residual overvoltage and LED 4

    voltage unbalance protection. LED 5 indicates operation of frequency protection.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 33Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    40/80

    GUID-BBD0D81F-5F94-4E97-8CF5-560F9EA9562F V1 EN

    Figure 12: Undervoltage protection

    Three undervoltage protection stages (PHxPTUV) protect against abnormal phase

    voltage conditions in the power system. The operation of voltage functions is

    connected to alarm LED 2. An external supervision device detects failures in

    primary high voltage fuses and the activation is connected to binary input

    X130:BI1. Activating the binary input to avoid faulty undervoltage tripping blocks

    the undervoltage protection functions.

    GUID-6A4FADFD-F55D-433D-894F-370CF538F902 V1 EN

    Figure 13: Residual overvoltage protection

    Section 3 1MRS757054 CREU615 standard configurations

    34 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    41/80

    The residual overvoltage protection (ROVPTOV) provides earth-fault protection

    by detecting abnormal level of residual voltage. It can be used, for example, as a

    nonselective backup protection for the selective directional earth-fault

    functionality. The operation signal is connected to alarm LED 3.

    GUID-98C7A5F0-B1A7-4008-92D2-FBACE327C843 V1 EN

    Figure 14: Positive and negative sequence voltage protection

    Four unbalance voltage protection functions are offered: two stages of negative-

    sequence overvoltage protection (NSPTOV1) and two stages positive-sequence

    undervoltage protection (PSPTUV1) functions. NSPTOV1 and PSPTUV1 are

    blocked in case a blown primary fuse is detected.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 35Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    42/80

    GUID-0F39CC9C-7388-47F5-89F3-666E4D0D42CB V1 EN

    Figure 15: Frequency protection

    The selectable underfrequency or overfrequency protection (FRPFRQ) prevents

    damage to network components under unwanted frequency conditions.

    Section 3 1MRS757054 CREU615 standard configurations

    36 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    43/80

    The function contains a selectable rate of change of the frequency (gradient)

    protection to detect an increase or decrease in the fast power system frequency at

    an early stage. This can be used as an early indication of a disturbance in the

    system. The operation signal is connected to alarm LED 5.

    GUID-3B69C572-5221-4320-850C-DD1DB0933037 V2 EN

    Figure 16: Load shedding and restoration

    Five load shedding and restoration stages are offered in the standard configuration.

    The load shedding and restoration function (LSHDPFRQ) is capable of shedding

    load based on underfrequency and the rate of change of the frequency. The load

    that is shed during the frequency disturbance can be restored once the frequency is

    stabilized to the normal level. Also manual restore commands can be given via

    binary inputs.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 37Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    44/80

    In this standard configuration two restore stages are implemented. Depending on

    input and output usage, it is possible to take other stages into use as well. The

    operation signal is connected to the alarm LED 6.

    GUID-ACA8588C-03FB-4389-B559-92CB612C6F8A V1 EN

    Figure 17: Arc protection

    Arc protection (ARCSARC1...3) is included as an optional function.

    The arc protection offers individual function blocks for three arc sensors that can

    be connected to the IED. The arc protection in this standard configuration detects

    an arc flash and supplies the information for the operating arc protection unit,

    which de-energizes the faulty area by opening the circuit breaker. It is possible to

    use, for example, fast GOOSE communication to route the detected information to

    the circuit breaker.

    The alarm LED 10 is used as a common arc detected indication.

    3.4.3.2 Functional diagram for disturbance recorder

    Section 3 1MRS757054 CREU615 standard configurations

    38 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    45/80

    GUID-95F1202A-A4AD-46C5-B059-B36F02FB2951 V1 EN

    Figure 18: Disturbance recorder

    All start and operate signals from the protection stages are routed to trigger the

    disturbance recorder or alternatively only to be recorded by the disturbance

    recorder depending on the parameter settings. Additionally, the ARC protection,

    synchrocheck and voltage measuring circuit related signals are also connected.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 39Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    46/80

    3.4.3.3 Functional diagrams for control and interlocking

    GUID-4F3709BF-87AC-4EB7-86AE-0FD490AA925A V1 EN

    Figure 19: Synchronism and energizing check

    The synchronism and energizing check (SECRSYN) function is offered in the

    standard configuration. It is used for interconnecting two separate power system

    network parts. The standard configuration is implemented to be used as continuous

    mode by default. The permission signal for circuit breaker closing is connected to

    X100:PO2 and it can be used in series in circuit breaker closing circuit. Theinformation that systems are synchronous to be interconnected is connected to LED

    8.

    SECRSYN is blocked if primary voltage transformer fuse is blown (X130:BI1) or

    if the miniature circuit breaker failure is detected from the line or bus-side

    secondary voltage measuring circuit (X130:BI2 or X130:BI3).

    Section 3 1MRS757054 CREU615 standard configurations

    40 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    47/80

    GUID-134FABAF-FD7D-4CDF-A47A-B6E9D988065E V1 EN

    Figure 20: Master Trip

    The operate signals from the protections are connected to the two trip output

    contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master

    Trips TRPPTRC1 and TRPPTRC2.

    TRPPTRC1 and 2 provide the lockout/latching function, event generation and the

    trip signal duration setting. If the lockout operation mode is selected, one binary

    input can be reassigned to the RST_LKOUT input of the Master Trip to enable

    external reset with a push button.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 41Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    48/80

    GUID-1CF419D7-518A-431F-BCAB-02413BE39E22 V1 EN

    Figure 21: Disconnector position indication

    The voltage transformer truck position indication is done with DCSXSWI1

    function block. There are three disconnector status blocks (DCSXSWI13)

    available in the IED. The remaining two not described in the functional diagram

    are available in PCM600 for connection where applicable.

    The binary inputs X110:5 and X110:6 are used for connection of voltage

    transformer truck position. The inputs are connected to DCSXSWI1.

    T ab le 13 : D ev ice pos itio ns ind ic ate d b y b in ary inp uts 5 a nd 6Primary device position Input to be energized

    Input 5 (X110:8-9) Input 6 (X110:10-9)

    Busbar disconnector closed x

    Busbar disconnector open x

    Voltage transformer truck in service

    position

    x

    Voltage transformer truck in test position x

    The binary inputs X110:7 and X110:8 are used for the position indication of thebusbar-side earth switch.

    Section 3 1MRS757054 CREU615 standard configurations

    42 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    49/80

    GUID-02E97DB4-8623-4B39-A38A-589778A9186A V1 EN

    Figure 22: Common alarm/indication 1 and 2

    The signal outputs from the IED are connected to give dedicated information on:

    Start of any protection function SO1 (X100:10-12)

    Operation (trip) of any protection function SO2 (X100: 13-15)

    TPGAPC are timers and used for setting the minimum pulse length for the outputs.

    There are four generic timers (TPGAPC1..4) available in the IED. The remaining

    ones not described in the functional diagram are available in PCM600 for

    connection where applicable.

    3.5 Standard configuration B3.5.1 Applications

    The standard configuration is intended for automatic voltage regulation of power

    transformers equipped with an on-load tap changer. It also features three-stage three-

    1MRS757054 C Section 3REU615 standard configurations

    REU615 43Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    50/80

    phase non-directional overcurrent protection, three-phase under and overvoltage

    protection. The IED also incorporates a thermal overload protection function,

    which supervises the thermal stress of the transformer windings to prevent

    premature aging of the winding's insulation.

    The RTD/mA input module is optional in the standard configuration. When using

    the RTD/mA input module it is possible to have the tap changer position indication

    as an mA signal, ambient temperature of the power transformer can be used in

    thermal protection and the multi-purpose protection functions are available. The

    multi-purpose protection function enables protection based on analog values from

    the IEDs RTD/mA input module, or from other IEDs using analog horizontal

    GOOSE messaging.

    The IED with a standard configuration is delivered from the factory with default

    settings and parameters. The end-user flexibility for incoming, outgoing and

    internal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs by

    modifying the internal functionality using PCM600.

    3.5.2 FunctionsT ab le 14 : F unc tio ns in clu de d in th e s ta nda rd co nfig ura tion BFunctionality IEC 61850 IEC 60617 IEC-ANSIProtectionThree-phase non-directional

    overcurrent protection, low stage,

    instance 1

    PHLPTOC1 3I> (1) 51P-1 (1)

    Three-phase non-directional

    overcurrent protection, high stage,

    instance 1

    PHHPTOC1 3I>> (1) 51P-2 (1)

    Three-phase non-directional

    overcurrent protection,

    instantaneous stage, instance 1

    PHIPTOC1 3I>>> (1) 50P/51P (1)

    Three-phase undervoltage

    protection, instance 1

    PHPTUV1 3U< (1) 27 (1)

    Three-phase undervoltage

    protection, instance 2

    PHPTUV2 3U< (2) 27 (2)

    Three-phase undervoltage

    protection, instance 3

    PHPTUV3 3U< (3) 27 (3)

    Three-phase overvoltage

    protection, instance 1

    PHPTOV1 3U> (1) 59 (1)

    Three-phase overvoltage

    protection, instance 2

    PHPTOV2 3U> (2) 59 (2)

    Three-phase overvoltage

    protection, instance 3

    PHPTOV3 3U> (3) 59 (3)

    Three-phase thermal overload

    protection for power transformers,

    two time constants

    T2PTTR1 3Ith>T 49T

    Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)

    Table continues on next page

    Section 3 1MRS757054 CREU615 standard configurations

    44 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    51/80

    Functionality IEC 61850 IEC 60617 IEC-ANSIMaster trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)

    Multi-purpose protection, instance 1 MAPGAPC1 MAP (1) MAP (1)

    Multi-purpose protection, instance 2 MAPGAPC2 MAP (2) MAP (2)

    Multi-purpose protection, instance 3 MAPGAPC3 MAP (3) MAP (3)

    ControlCircuit-breaker control CBXCBR1 I O CB I O CB

    Disconnector position indication,

    instance 1

    DCSXSWI1 I O DC (1) I O DC (1)

    Disconnector position indication,

    instance 2

    DCSXSWI2 I O DC (2) I O DC (2)

    Disconnector position indication,

    instance 3

    DCSXSWI3 I O DC (3) I O DC (3)

    Earthing switch indication ESSXSWI1 I O ES I O ES

    Tap changer position indication TPOSSLTC1 TPOSM 84M

    Tap changer control with voltage

    regulator

    OLATCC1 COLTC 90V

    Condition monitoringTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)

    Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)

    Current circuit supervision CCRDIF1 MCS 3I MCS 3I

    Fuse failure supervision SEQRFUF1 FUSEF 60

    MeasurementDisturbance recorder RDRE1 - -

    Three-phase current measurement,

    instance 1

    CMMXU1 3I 3I

    Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0

    Three-phase voltage measurement VMMXU1 3U 3U

    Sequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0

    Three-phase power and energy

    measurement, including power

    factor

    PEMMXU1 P, E P, E

    RTD/mA measurement XRGGIO130 X130 (RTD) X130 (RTD)

    3.5.2.1 Default I/O connectionsTable 15: Default connections for binary inputsBinary input Default usage Connector pinsX110-BI1 Tap changer operates X110-1,2

    X110-BI2 Voltage transformer secondary MCB open X110-3,4

    X110-BI3 Lower local request X110-5,6

    X110-BI4 Raise local request X110-7,6

    Table continues on next page

    1MRS757054 C Section 3REU615 standard configurations

    REU615 45Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    52/80

    Binary input Default usage Connector pinsX110-BI5 Activate parallel operation X110-8,9

    X110-BI6 Activate automatic mode X110-10,9

    X110-BI7 Circuit breaker closed indication X110-11,12

    X110-BI8 Circuit breaker open indication X110-13,12

    Tab le 16 : Defau lt connec tions for bina ry inpu ts (a lterna tive to the RTD ca rd )Binary input Default usage Connector pinsX130-BI1 BCD sign bit (tap changer position) X130-1,2

    X130-BI2 BCD bit 1 MSB X130-2,3

    X130-BI3 BCD bit 2 X130-4,5

    X130-BI4 BCD bit 3 X130-5,6

    X130-BI5 BCD bit 4 X130-7,8

    X130-BI6 BCD bit 5 LSB X130-8,9

    Table 17: Default connections for RDT/m A inputsRTD/mA input Default usage Connector pinsX130-AI1 Tap changer position X130-1,2

    X130-AI2 X130-3,4

    X130-AI3 Transformer ambient temperature X130-5,6,11c

    X130-AI4 X130-7,8,11c

    X130-AI5 X130-9,10,11c

    X130-AI6 X130-13,14,12c

    X130-AI7 X130-15,16,12c

    X130-AI8 X130-17,18,12c

    Table 18: D efault connections for binary outputsBinary output Default usage Connector pinsX100-PO1 Lower own command X100-6,7

    X100-PO2 Raise own command X100-8,9

    X100-SO1 General start indication X100-10,11,(12)

    X100-SO2 General operate indication X100-13,14

    X100-PO3 Master trip X100-15-19

    X100-PO4 Close circuit breaker X100-20-24

    X110-SO1 Tap changer control alarm X110-14,15,16

    X110-SO2 Overcurrent operate alarm X110-17,18,19

    X110-SO3 Voltage protection operate alarm X110-20,21,22

    X110-SO4 Overload protection operate alarm X110-23,24

    Section 3 1MRS757054 CREU615 standard configurations

    46 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    53/80

    Table 19: Default connections for LEDsLED Default usage1 Overcurrent protection operated

    2 Overvoltage protection operated3 Undervoltage protection operated

    4 Thermal overload protection operated

    5 Raise own

    6 Lower own

    7 Disturbance recorder triggered

    8 Tap changer control alarm

    9 Supervision

    10 Tap changer operates

    11

    3.5.2.2 Default disturbance recorder settingsT ab le 20: D efau lt a nalog ch ann el se lec tio n a nd te xt se tting sChannel Selection and text1 IL1

    2 IL2

    3 IL3

    4 Io5 U1

    6 U2

    7 U3

    8 -

    9 -

    10 -

    11 -

    12 -

    Additionally, all the digital inputs that are connected by default are also enabled

    with the setting. Default triggering settings are selected depending on the

    connected input signal type. Typically all protection START signals are selected to

    trigger the disturbance recorded by default.

    3.5.3 Functional diagrams

    1MRS757054 C Section 3REU615 standard configurations

    REU615 47Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    54/80

    The functional diagrams describe the default input, output, alarm LED and function-

    to-function connections. The default connections can be viewed and changed with

    PCM600 according to the application requirements, if necessary.

    The analog channels, measurements from current transformers and voltagetransformers, have fixed connections towards the different function blocks inside

    the IEDs standard configuration. Exceptions from this rule are the eight analog

    channels available for the disturbance recorder function. These channels are freely

    selectable and a part of the disturbance recorders parameter settings.

    The analog channels are assigned to different functions. The common signal

    marked with 3I represents the three phase currents and 3U represents the three

    phase voltages. The signal marked with Uo represents the measured residual

    voltage via open-delta connected voltage transformers. The signal marked with Io

    represents the measured residual current, via a sum connection of second current

    transformer cores of the phase current transformers.

    3.5.3.1 Functional diagrams for protectionThe functional diagrams describe the IEDs protection functionality in detail and

    picture the factory set default connections.

    GUID-2125AE49-AD79-460A-AF83-3965D2F06F2F V1 EN

    Figure 23: Overcurrent protection

    Section 3 1MRS757054 CREU615 standard configurations

    48 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    55/80

    Three overcurrent stages (PHLPTOC1, PHHPTOC1 and PHIPTOC1) are offered

    for overcurrent and short-circuit protection. LED 1 is used for indicating the

    operation of overcurrent and short circuit functions. Also the same alarm

    information is connected to the binary output SO2 (X110:17-19).

    All operate signals are connected to the Master Trip and also to the alarm LEDs.

    LED 1 indicates operation of overcurrent and LED 2 operation of overvoltage

    protection functions. LED 3 indicates operation of undervoltage and LED 4

    thermal overload protection.

    GUID-C07A4101-8768-4365-BB4F-17CF3CF3D075 V1 EN

    Figure 24: Thermal overload protection

    Three-phase thermal overload protection (T2PTTR1) provides indication onoverload situations. The operate signal of the thermal overload protection is

    connected to the Master Trip and also to an alarm LED 4.

    If the RTD/mA input module is included in the IED, the ambient temperature of

    the power transformer is connected from the RTD channel to the thermal overload

    function.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 49Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    56/80

    GUID-3EC07F90-DCAB-436A-B36F-965BD8AAB645 V1 EN

    Figure 25: Overvoltage protection

    Three overvoltage protection stages (PHPTOV1, PHPTOV2 and PHPTOV3) offer

    protection against abnormal overvoltage conditions in the power system. LED 2

    indicates the operation of PHPTOV. The same alarm information is connected to

    the binary output SO3 (X110:20-22).

    Section 3 1MRS757054 CREU615 standard configurations

    50 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    57/80

    GUID-CA6719A8-E586-4B52-80F2-9504EA0CCA26 V1 EN

    Figure 26: Undervoltage protection

    Three undervoltage protection stages (PHPTUV1, PHPTUV2 and PHPTUV3)

    offer protection against abnormal undervoltage conditions in the power system.

    LED 3 indicates the operation of PHPTUV. The same alarm information is

    connected to the binary output SO3 (X110:20-22).

    3.5.3.2 Functional diagrams for disturbance recorder and supervisionfunctions

    1MRS757054 C Section 3REU615 standard configurations

    REU615 51Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    58/80

    GUID-F538B88A-B5BB-4DB8-8364-06E7CF14239C V1 EN

    Figure 27: Disturbance recorder

    All start and operate signals from the protection stages are routed to trigger the

    disturbance recorder or alternatively only to be recorded by the disturbance

    recorder depending on the parameter settings. Additionally, the supervision related

    signals, tap changer control signals and circuit breaker position indications are also

    connected.

    Section 3 1MRS757054 CREU615 standard configurations

    52 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    59/80

    GUID-E7EAE99F-92BC-4192-B485-EB1677BA407D V1 EN

    Figure 28: Trip circuit supervision

    Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3

    (X100:15-19) for Master trip and TCSSCBR2 for PO4 (X100:20-24) for circuit

    breaker closing. The trip circuit supervision 1 is blocked by the Master Trip

    (TRPPTRC1) and the circuit-breaker open position signal. The trip circuit

    supervision 2 is blocked by the circuit breaker closed position signal. The trip

    circuit supervision alarm indication is connected to LED 9.

    The fuse failure supervision SEQRFUF1 detects failures in voltage measurement

    circuits. Failures, such as open miniature circuit breaker, are detected and the alarm

    is connected to supervision alarm LED 9.

    Failures in current measuring circuits are detected by CCRDIF. The alarm signal isconnected to the supervision alarm LED 9.

    3.5.3.3 Functional diagrams for control and interlocking

    1MRS757054 C Section 3REU615 standard configurations

    REU615 53Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    60/80

    GUID-73D10A91-CE58-4368-9C88-39D2268580E6 V1 EN

    Figure 29: Master Trip

    The operate signals from the protections are connected to the trip output contact

    PO3 (X100:15-19) via the corresponding Master Trip TRPPTRC1.

    TRPPTRC provides the lockout/latching function, event generation and the trip

    signal duration setting. If the lockout operation mode is selected, one binary input

    can be reassigned to the RST_LKOUT input of the Master Trip to enable external

    reset with a push button.

    GUID-E4270342-93C0-4C06-B8F2-297E24A434FE V1 EN

    Figure 30: On load tap changer control

    The on load tap changer control functionality is provided with the OLATCC1

    function. Both manual and automatic controlling of the on load tap changer is done

    via OLATCC. The external push button controlling of the local tap changer can be

    wired to binary inputs, BI3 (X110:5-6) for lower request and BI4 (X110:7-6) for

    raise request. Also it is possible to set the function into parallel mode with

    activating the BI5 (X110:8-9) input and to the automatic mode with BI6 (X110:10-9).

    Section 3 1MRS757054 CREU615 standard configurations

    54 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    61/80

    The tap changer operating information can be connected to the binary input BI1

    (X110:1-2).

    OLATCC is blocked in automatic mode as a default setting if the LTC_BLOCK

    input is active. The activation of the input fuse failure or current circuit failure isdetected.

    The output commands are routed to the binary outputs and programmable LEDs.

    The raise command is connected to PO2 (X100:8-9) and to the alarm LED 5. The

    lower command is connected to PO1 (X100:6-7) and to the alarm LED 6.

    The common alarm signal of OLATCC1 is connected to SO1 (X110:14-16) and to

    the alarm LED 8.

    GUID-61FA8F81-6848-4DBE-83B8-0750C33AA255 V1 EN

    Figure 31: Circuit breaker control and interlocking

    The ENA_CLOSE input, which enables the closing of the circuit breaker, is a

    status of the Master Trip in the breaker control function block CBXCBR. The open

    operation is always enabled.

    If the ENA_CLOSE signal is completely removed from the breaker

    control function block CBXCBR with PCM600, the function

    assumes that the breaker close commands are allowed continuously.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 55Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    62/80

    GUID-A6A3A186-BAC4-4609-B163-E13A00C528D6 V1 EN

    Figure 32: Tap changer position indication

    The tap changer position indication (TPOSSLTC1) can be made by using binary

    coded information or an mA signal. It depends on the selected IED hardware. By

    using the mA/RTD input module in the X130 slot, the tap changer position can be

    connected as an mA signal. If the binary input output card is selected in the X130

    slot, the position indication can be made with binary coded information.

    When the mA/RTD card is used, the ambient temperature of the power transformer

    is connected from first RTD channel to the thermal overload protection function.

    Section 3 1MRS757054 CREU615 standard configurations

    56 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    63/80

    GUID-160A639B-35DA-446D-B176-D606EBE3FDB9 V1 EN

    Figure 33: Common alarm/indication 1-5

    The signal outputs from the IED are connected to give dedicated information on:

    Start of any protection function SO1 (X100:10-12)

    Operation (trip) of any protection function SO2 (X100:13-14)

    Operation of overcurrent protection function SO2 (X110:17-19)

    Operation of voltage protection function SO3 (X110:20-22)

    Operation of thermal overload protection SO4 (X110:23-24)

    TPGAPC are timers and used for setting the minimum pulse length for the outputs.

    There are four generic timers (TPGAPC1..4) available in the IED. The remaining

    ones not described in the functional diagram are available in PCM600 for

    connection where applicable.

    1MRS757054 C Section 3REU615 standard configurations

    REU615 57Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    64/80

    58

  • 7/27/2019 ABB Reles de Frecuencia

    65/80

    Section 4 Requirements for measurementtransformers

    4.1 Current transformers4.1.1 Current transformer requirements for non-directionalovercurrent protection

    For reliable and correct operation of the overcurrent protection, the CT has to bechosen carefully. The distortion of the secondary current of a saturated CT may

    endanger the operation, selectivity, and co-ordination of protection. However,

    when the CT is correctly selected, a fast and reliable short circuit protection can be

    enabled.

    The selection of a CT depends not only on the CT specifications but also on the

    network fault current magnitude, desired protection objectives, and the actual CT

    burden. The protection settings of the IED should be defined in accordance with

    the CT performance as well as other factors.

    4.1.1.1 Current transformer accuracy class and accuracy limit factorThe rated accuracy limit factor (Fn) is the ratio of the rated accuracy limit primary

    current to the rated primary current. For example, a protective current transformer

    of type 5P10 has the accuracy class 5P and the accuracy limit factor 10. For

    protective current transformers, the accuracy class is designed by the highest

    permissible percentage composite error at the rated accuracy limit primary current

    prescribed for the accuracy class concerned, followed by the letter "P" (meaning

    protection).

    Table 21: L imits o f errors according to IEC 60044-1 for protect ive current transformersAccuracy class Current error at

    rated primarycurrent (%)Phase displacement at rated primarycurrent

    Composite error atrated accuracy limitprimary current (%)inutes centiradians

    5P 1 60 1.8 5

    10P 3 - - 10

    The accuracy classes 5P and 10P are both suitable for non-directional overcurrent

    protection. The 5P class provides a better accuracy. This should be noted also if

    there are accuracy requirements for the metering functions (current metering,

    power metering, and so on) of the IED.

    1MRS757054 C Section 4Requirements for measurement transformers

    REU615 59Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    66/80

    The CT accuracy primary limit current describes the highest fault current

    magnitude at which the CT fulfils the specified accuracy. Beyond this level, the

    secondary current of the CT is distorted and it might have severe effects on the

    performance of the protection IED.

    In practise, the actual accuracy limit factor (Fa) differs from the rated accuracy

    limit factor (Fn) and is proportional to the ratio of the rated CT burden and the

    actual CT burden.

    The actual accuracy limit factor is calculated using the formula:

    F FS S

    S Sa n

    in n

    in

    +

    +

    A071141 V1 EN

    Fn the accuracy limit factor with the nominal external burden Sn

    Sin the internal secondary burden of the CT

    S the actual external burden

    4.1.1.2 Non-directional overcurrent protectionThe current transformer selection

    Non-directional overcurrent protection does not set high requirements on the

    accuracy class or on the actual accuracy limit factor (Fa) of the CTs. It is, however,recommended to select a CT with Fa of at least 20.

    The nominal primary current I1n should be chosen in such a way that the thermal

    and dynamic strength of the current measuring input of the IED is not exceeded.

    This is always fulfilled when

    I1n > Ikmax / 100,

    Ikmax is the highest fault current.

    The saturation of the CT protects the measuring circuit and the current input of the

    IED. For that reason, in practice, even a few times smaller nominal primary current

    can be used than given by the formula.

    Recommended start current settingsIf Ikmin is the lowest primary current at which the highest set overcurrent stage is to

    operate, the start current should be set using the formula:

    Current start value < 0.7 x (Ikmin / I1n)

    I1n is the nominal primary current of the CT.

    Section 4 1MRS757054 CRequirements for measurement transformers

    60 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    67/80

    The factor 0.7 takes into account the protection IED inaccuracy, current

    transformer errors, and imperfections of the short circuit calculations.

    The adequate performance of the CT should be checked when the setting of the

    high set stage overcurrent protection is defined. The operate time delay caused bythe CT saturation is typically small enough when the overcurrent setting is

    noticeably lower than Fa.

    When defining the setting values for the low set stages, the saturation of the CT

    does not need to be taken into account and the start current setting is simply

    according to the formula.

    Delay in operation caused by saturation of current transformersThe saturation of CT may cause a delayed IED operation. To ensure the time

    selectivity, the delay must be taken into account when setting the operate times of

    successive IEDs.

    With definite time mode of operation, the saturation of CT may cause a delay that

    is as long as the time the constant of the DC component of the fault current, when

    the current is only slightly higher than the starting current. This depends on the

    accuracy limit factor of the CT, on the remanence flux of the core of the CT, and

    on the operate time setting.

    With inverse time mode of operation, the delay should always be considered as

    being as long as the time constant of the DC component.

    With inverse time mode of operation and when the high-set stages are not used, the

    AC component of the fault current should not saturate the CT less than 20 times thestarting current. Otherwise, the inverse operation time can be further prolonged.

    Therefore, the accuracy limit factor Fa should be chosen using the formula:

    Fa > 20*Current start value / I1n

    The Current start value is the primary pickup current setting of the IED.

    4.1.1.3 Example for non-directional overcurrent protectionThe following figure describes a typical medium voltage feeder. The protection isimplemented as three-stage definite time non-directional overcurrent protection.

    1MRS757054 C Section 4Requirements for measurement transformers

    REU615 61Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    68/80

    A071142 V1 EN

    Figure 34: Example of three-stage overcurrent protection

    The maximum three-phase fault current is 41.7 kA and the minimum three-phase

    short circuit current is 22.8 kA. The actual accuracy limit factor of the CT is

    calculated to be 59.

    The start current setting for low-set stage (3I>) is selected to be about twice the

    nominal current of the cable. The operate time is selected so that it is selective with

    the next IED (not visible in the figure above). The settings for the high-set stage

    and instantaneous stage are defined also so that grading is ensured with the

    downstream protection. In addition, the start current settings have to be defined sothat the IED operates with the minimum fault current and it does not operate with

    the maximum load current. The settings for all three stages are as in the figure above.

    For the application point of view, the suitable setting for instantaneous stage (I>>>)

    in this example is 3 500 A (5.83 x I2n). For the CT characteristics point of view, the

    criteria given by the current transformer selection formula is fulfilled and also the

    IED setting is considerably below the Fa. In this application, the CT rated burden

    could have been selected much lower than 10 VA for economical reasons.

    Section 4 1MRS757054 CRequirements for measurement transformers

    62 REU615Application Manual

  • 7/27/2019 ABB Reles de Frecuencia

    69/80

    Section 5 IED physical connections

    5.1 Inputs5.1.1 Energizing inputs5.1.1.1 Phase currents

    The IED can also be used in single or two-phase applications by

    leaving one or two energizing inputs unoccupied. However, at leastterminals X120/7-8 must be connected.

    T ab le 2 2: P ha se cu rre nt in pu ts inc lu de d in co nfigu ra tio n BTerminal DescriptionX120-7, 8 IL1

    X120-9, 10 IL2

    X120-11, 12 IL3

    5.1.1.2 Residual currentT ab le 23: R esidu al cu rr