AAC_SPEC_412010

Embed Size (px)

Citation preview

  • 8/2/2019 AAC_SPEC_412010

    1/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 1 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    CONTENTS PAGE

    1 SCOPE 22 TECHNICAL REQUIREMENTS TO BE SPECIFIED BY THE ENGINEER 22.1 PIPE OUTSIDE DIAMETER 22.2 INSULATION SECTION LENGTHS 22.3 TOTAL LENGTH OF PIPING 22.4 BEND OR PIPE FITTING DETAILS 22.5 PIPE MATERIAL 22.6

    PIPE JOINT DETAILS (FLANGED OR SHOULDERED) 2

    2.7 REQUIRED LIFE OF CORROSION PROTECTION 22.8 THE PREVAILING AMBIENT CONDITIONS AFFECTING CORROSION 22.9 PACKAGING REQUIREMENTS. 22.10 PIPES TO BE PRE-INSULATED ON SURFACE OR INSULATION TO BE INSTALLED IN-SITU

    UNDERGROUND. 23 DEFINITIONS 24 REQUIREMENTS 34.1 GENERAL 34.2

    MATERIALS 3

    4.3 INSULATION SYSTEM 44.4 CONSTRUCTION 54.5 DESIGN 55 QUALITY ASSURANCE REQUIREMENTS 75.1 QUALITY MANAGEMENT SYSTEM 75.2 QUALITY PLAN 75.3 INSPECTION 75.4 SAMPLING 76 INSPECTION AND TEST 86.1 TYPE TESTS 86.2 PRODUCTION TESTS 87 MARKING AND PACKING 97.1 MARKING 97.2 PACKING 10APPENDIX A : RELATED DOCUMENTS 11APPENDIX B : RECORD OF AMENDMENTS 11

  • 8/2/2019 AAC_SPEC_412010

    2/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 2 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    1 SCOPE

    This specification details the requirements for the thermal insulation of chilled water pipesinstalled underground and covers pre-insulation of pipes on surface and in-situapplications underground.

    2 TECHNICAL REQUIREMENTS TO BE SPECIFIED BY THE ENGINEER

    2.1 PIPE OUTSIDE DIAMETER

    2.2 INSULATION SECTION LENGTHS

    2.3 TOTAL LENGTH OF PIPING

    2.4 BEND OR PIPE FITTING DETAILS

    2.5 PIPE MATERIAL

    2.6 PIPE JOINT DETAILS (FLANGED OR SHOULDERED)

    2.7 REQUIRED LIFE OF CORROSION PROTECTION

    2.8 THE PREVAILING AMBIENT CONDITIONS AFFECTING CORROSION

    2.9 PACKAGING REQUIREMENTS.

    2.10 PIPES TO BE PRE-INSULATED ON SURFACE OR INSULATION TO BE INSTALLED IN-SITUUNDERGROUND.

    3 DEFINITIONS

    ACCEPTABLE/APPROVED : Acceptable to and approved by the Engineer

    CSIR MINING TEK : Council fir Scientific and Industrial Research MiningTek

    ENGINEER : The Consulting Engineer, Consulting Mechanical andElectrical Engineer of AAC or their appointedrepresentative

    INSULATION SYSTEM : Combination of one or more of sleeve, vapour barrierand insulant so providing required properties

    INSULANT : Material providing thermal insulation through low heattransfer

    NBS : National Building Standards

    NES : Naval Engineering Standard (Royal Navy)

  • 8/2/2019 AAC_SPEC_412010

    3/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 3 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    PIPE : Water reticulation pipe

    SLEEVE : Outer covering which provides protection to the insulant

    UPVC : Unplasticised poly-vinyl chloride

    VAPOUR BARRIER : Layer of continuous impermeable material sealing theinsulant

    The following terms are defined in the General Conditions of Contract:

    AAC, Company, Contractor.

    4 REQUIREMENTS

    4.1 GENERAL

    4.1.1 Insulants produced by the chemical reaction of two or more constituents, whichduring the chemical action produce a water vapour: shall not be injected or cast into aclosed void unless:

    4.1.1.1 Provision is made: to vent this moisture from the insulant to ensure that the coefficient ofconductivity specified by the manufacturer is obtained.

    This conductivity must be stabilised after the insulation has been used in the conditionsshown in table 5 for a period of 200 hours.

    4.1.2 Insulants produced by the chemical reaction of two or more constituents, one ofwhich is an acid, shall not be used as slab stock in voids, or be injected into voids whichhave metallic walls unless the walls are suitably protected against corrosion.

    4.2 MATERIALS

    4.2.1 Sleeve: the sleeve shall comply with the requirements specified in Table 1.

    TABLE 1: SLEEVE REQUIREMENTS

    1 2 3

    MATERIAL REQUIREMENTS TEST METHOD

    UPVC

    (See note below)

    1. Maximum thickness 3,2mm

    2. Impact resistanceminimum value 50 kJ/m

    3. Comply with AECISpecification No. 130/S/03or approved equivalent

    4. UPVC sleeves must becolour coded blue

    DIN 53448

  • 8/2/2019 AAC_SPEC_412010

    4/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 4 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    Steel Minimum thickness 0,3mm

    Phoenolic Resin Glassreinforced

    See AAC Specification 173/1

    Note: Where UPVC sleeved piping is routed closer than 2,0m from fuelling bays, oilstores, conveyor belts, oil filled transformers and switchgear, timber supports, etc,external steel cladding shall be applied. See AAC Drawing No Y1903.

    4.2.2 Vapour barrier: the vapour barrier shall comply with the requirements specified inTable 2.

    Where pipe insulation is purchased without a mechanical protective sleeve, the vapourbarrier material shall comply with the AAC Specification No 412/9.

    TABLE 2: VAPOUR BARRIER REQUIREMENTS

    1 2 3

    PROPERTY REQUIREMENTS TEST METHOD

    Water Vapour 0,2g maximum per m/24h at38C 2% and 90% R.H. 5% R.H.

    ASTM E96

    4.2.3 Insulant: the insulant shall comply with the requirements specified in Table 3.

    TABLE 3: INSULANT REQUIREMENTS

    1 2 3

    PROPERTY REQUIREMENTS TEST METHOD

    Combustibility Pass SABS 0177 Part V

    (Modified) CSIR

    Test Method

    Toxicity Maximum Index of 2 SABS Test Method TI (NES)

    Thermal Conductivity 0,05 W/mC Max ASTM C177

    Smoke Production SpecificOptical Density Value

    Maximum index of 10,0 NBS Smoke Density TestMethod

    Min Compressive Strength(Parallel to Rise)

    175 kPa

    Density Max 200kg/m

    4.3 INSULATION SYSTEM

    The insulation system shall comply with the requirements specified in Table 4.

  • 8/2/2019 AAC_SPEC_412010

    5/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 5 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    TABLE 4: SYSTEM REQUIREMENTS

    1 2 3

    PROPERTY REQUIREMENT TEST METHOD CLAUSE

    Fire Resistance Pass CSIR Mining Tek/CSIR Fire Lab.Tunnel tests

    Thickness of insulant Clause 4.4.2 To be specified byContractor

    CSIR Mining Tek Dynamic Test(see Clauses 6.2.8 and 4.4.2)

    Thermal Conductivity 0.05 W/m C max ASTM C177

    Heat gain Table 6 CSIR Mining Tek Dynamic Test

    Distortion (Pre-insulated pipes) 10mm Clauses 6.2.5

    Note: The overall length of insulation system on pre-insulated pipes shall allow adequateaccess to flange bolt holes etc.

    4.4 CONSTRUCTION

    4.4.1 Insulant: shall be homogenous, free of voids and shall occupy all cavities within theprotective sleeve.

    4.4.2 Thickness of insulant: shall be such that the heat gain values detailed in Table 6 shallnot be exceeded after ageing and after use for 200 hours in conditions as set out inTable 5.

    4.4.3 Water vapour protection: of the insulant shall be such that it is encapsulated in amaterial which complies with the requirements for a water vapour barrier as detailed inTable 2. Where this material is joined, the joint shall exhibit the same characteristics asthe parent material.

    4.4.4 Products of organic nature: polyurethane or polystyrene based materials shall not beused.

    The density of the insulant: shall not be greater than 200 kg/m3.

    4.4.5 The complete product: comprising insulant, water vapour barrier and sleeve shall not

    show any deformation greater than 5 mm nor any permanent visible deterioration whentested in accordance with the requirements of Clause 6.2.7.

    4.4.6 Glass reinforced organic material: if used as a protective sleeve shall comply with therequirements of AAC Specification 173/1.

    4.5 DESIGN

    The Contractor shall provide for approval, dimensioned drawings and design calculationsat time of tender response accompanied by an SABS certificate stating that an insulationsystem complying with the design has been tested by SABS and complies with therequirements of Clause 4.2 and 4.3. The results of the heat gain tests and fire

    performance tests conducted by CSIR Mining Tek and CSIR Fire Lab. shall be included.

  • 8/2/2019 AAC_SPEC_412010

    6/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 6 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    The Contractor shall also provide for approval the methods and materials used for fixing in-

    situ type insulation to the pipes.

    4.5.1 Calculations: the parameters detailed in Table 5 shall be used for design purposes.

    TABLE 5: CALCULATIONS PARAMETERS

    1 2

    PARAMETER VALUES

    Water velocity

    Water Temperature

    Pipe diameter range

    Pipe wall thickness

    Pipe thermal conductivity

    Air temperature

    Air velocity

    1m/s

    5C

    100 - 300mm

    6mm

    45W/m C

    (Mild steel)

    32C

    5m/s

    Note: If pipes of different thermal conductivity are used this shall be specified by theCompany.

    4.5.2 Design performance requirements: maximum heat gain per linear metre of insulatedpipe shall not exceed the value given in Table 6.

    Note: Value given is for the combined insulating value of pipe wall, vapour barrier andsleeve and is based on a dry clean sleeve outer surface.

    TABLE: 6 HEAT GAIN

    1 2 3

    PIPE: NOMINAL SIZE(mm)

    HEAT GAIN(W/LINEAR m)

    TEST METHOD

    100

    150

    200

    250

    300

    14

    19

    24

    29

    34

    See Clause

    6.1.2

    4.5.3 Designed maximum outside diameter: of insulation shall comply with the requirementsof Table 7.

  • 8/2/2019 AAC_SPEC_412010

    7/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 7 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    TABLE 7

    MAXIMUM INSULATION SYSTEM OUTSIDE DIAMETERS

    1 2

    NOMINAL PIPE SIZE (mm) INSULATIONS, SYSTEMOUTSIDE DIAMETER (mm)

    100

    150

    200

    250300

    225

    290

    350

    420470

    5 QUALITY ASSURANCE REQUIREMENTS

    5.1 QUALITY MANAGEMENT SYSTEM

    The requirements of SABS ISO 9001 shall apply. All volitional requirements in SABSISO 9001 shall be mandatory for material supplied against this specification.

    5.2 QUALITY PLAN

    The Contractor shall compile and submit a quality plan which shall be approved prior tocommencement of manufacture. The quality plan shall list all major works, specifications,tests, methods of test and equipment to be used and acceptance/rejection criteria.

    5.3 INSPECTION

    The Contractor shall provide SABS certification to the effect that items supplied to theCompany comply with the requirements of this specification.

    The Company's representative shall have access at all reasonable times to those parts ofthe manufacturing facilities engaged in the manufacture of items to this specification. He isauthorised to witness any stage of manufacture, tests and inspection documentation.

    The representative is authorised to reject any items not manufactured to the requirements ofthis specification.

    All quality costs including SABS certification shall be for the account of the Contractor.

    5.4 SAMPLING

    5.4.1 Sampling for type testing: shall be as determined by the AAC Consulting EnvironmentalEngineer.

    5.4.2 Sampling for production testing: shall be in accordance with the requirements detailedin the approved Quality Plan.

  • 8/2/2019 AAC_SPEC_412010

    8/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 8 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    6 INSPECTION AND TEST

    6.1 TYPE TESTS

    6.1.1 CSIR Mining Tek tunnel testing

    Full scale pipe insulation tests shall be performed on two 200 mm diameter insulatedpipes complete with vapour barriers and external protective sheaths. The pipes shall beinstalled in parallel.

    6.1.2 CSIR Mining Tek heat gain test

    An insulated 6m length of 150 mm nominal bore pipe shall be submitted to CSIR Mining Tekfor the determination of the thermal conductivity of the insulation system at conditions as set

    out in Table 5.

    6.2 PRODUCTION TESTS

    Production tests shall be performed on samples as detailed in the Quality Plan and at thefrequency specified in Table 8.

    TABLE 8

    SAMPLING PLANS FOR TEST CLAUSE, 6.2

    1 2 3

    LOT SIZE SAMPLE SIZE DEFECTIVE ACCEPTABLE

    3 - 25 3 0

    26 - 50 13 0

    51 - 150 20 0

    6.2.1 Combustibility

    Combustibility shall be tested in accordance with the requirements of SABS 0177 Part V.(Modified) CSIR method.

    6.2.2 Toxicity

    Toxicity shall be tested in accordance with the requirements of SABS Method T1 (NES 713).

    6.2.3 Smoke density

    Smoke density production shall be tested according to the NBS Smoke Density Testmethod.

    6.2.4 Conductivity

    The conductivity of a sample of the insulant shall be tested according to ASTM C177.

    6.2.5 Water vapour transmission

  • 8/2/2019 AAC_SPEC_412010

    9/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 9 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    The water vapour transmission values of the water vapour barrier or outside sleeve shall be

    tested according to ASTM E96.

    6.2.6 Density of insulant

    Remove a cube from an insulated pipe and determine its mass. Calculate the volume of thecube and determine the density of the insulant by dividing the mass by the volume. Express

    the result in kg/m3. The result shall comply with the requirements of Table 3.

    6.2.7 Distortion

    Apply a force of 5kN, via a 50 x 50 steel angle positioned at 90o

    to the pipe axis, onto theouter surface of the insulated pipe (with the point of the 'V' of the angle contacting with the

    insulation). Remove the force and measure the depth of indentation. The results shallcomply with the requirements of Clause 4.4.5

    6.2.8 Thickness of insulant

    Measure thickness of insulant prior to encapsulation in the vapour barrier and outsideprotective sleeve, for in-situ type insulation.

    For pre-insulated pipes, measure the circumference of the pipe and the outsidecircumference of the protective sleeve of the insulated pipe. Calculate the thickness ofinsulation and protective sleeve and then deduct thickness of protective sleeve.

    The result shall comply with requirements to satisfy the heat gain specifications as set out inTable 6.

    6.2.9 SABS 0177 Part V (Modified) CSIR combustibility

    The empty sample cradle shall be introduced into the furnace and the temperaturesrecorded for 5 minutes.

    When the furnace has reached equilibrium temperature a 40mm x 40mm x 40mm sampleof the test material shall be introduced into the furnace and the temperatures shall berecorded for 5 minutes.

    Any material, of which the flame temperature rise exceeds that of the empty cradle for the

    initial 2 minutes of the test or which exhibits a quenching effect of less than that of the emptycradle for the initial 2 minute period of the test shall be deemed to have failed.

    The results shall comply with the requirements detailed in Table 6.

    7 MARKING AND PACKING

    7.1 MARKING

    The outer surface of the insulation system shall be marked as follows.

    7.1.1 Logo or name of Contractor

    7.1.2 Date of manufacture

  • 8/2/2019 AAC_SPEC_412010

    10/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 10 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    7.2 PACKING

    Packing shall provide protection during transit and handling of insulation systemcomponents.

  • 8/2/2019 AAC_SPEC_412010

    11/11

    AAC_SPEC_41201002.DOC APPROVED 11 July 1994 Page 11 of 11

    Anglo Technical Division accepts no liability for any damage whatsoever that may result from the use of this material orthe information contained therein, irrespective of the cause and quantum thereof.

    AAC SPECIFICATION 412010

    ISSUE 2THERMAL INSULATION FOR CHILLED WATERPIPING COPYRIGHT

    APPENDIX A : RELATED DOCUMENTS

    The latest issues of the following documents shall be deemed to form part of this specification.

    ASTM C177 : Test method for steady-state heat flux measurements and thermaltransmission properties by means of the guarded-hot-plate apparatus

    ASTM D304 : Recommended practice for heat ageing of plastics without load

    ASTM E96 : Test for water vapour transmission of materials

    SABS ISO 9001 : Quality management systems

    SABS 0177 : Fire testing of materials, components and elements used in buildings

    SABS 0177 Part V : Fire testing of materials, components and elements (Modified) CSIRused in buildings

    SABS Method T1 : Determination of the toxicity index of the products of combustion fromsmall specimens of materials

    AECI 130/5/03 : Specification for PVC formulation

    DIN 53448 : Testing of plastics; tensile impact test

    AAC Drawing Y1903 : Cladding

    AAC 412/9 : Vapour barrier for use with blanket type insulation for chilled waterreticulation piping

    APPENDIX B : RECORD OF AMENDMENTS

    Issue 2 : Table 8 added to Clause 6.2

    Refs to COMRO changed to C.S.I.R. Mining Tek.

    (P.N. Eksteen 1994-04-11)