A Review on Load Flow Studies Final

Embed Size (px)

Citation preview

  • 7/22/2019 A Review on Load Flow Studies Final

    1/46

    A review on Load flowstudies

  • 7/22/2019 A Review on Load Flow Studies Final

    2/46

    Outline

    Introduction Methodology Classical methodsGauss-Seidal methodNewton Raphson methodFast Decoupled method Other methods

    Fuzzy Logic application Genetic Algorithm application Particle swarm method (PS0)

  • 7/22/2019 A Review on Load Flow Studies Final

    3/46

    Load/Power Flow studies Load-flow studies are performed to determine the steady-state

    operation of an electric power system. It calculates the voltagedrop on each feeder, the voltage at each bus, and the powerflow in all branch and feeder circuits.

    Determine if system voltages remain within specified limitsunder various contingency conditions, and whether equipment

    such as transformers and conductors are overloaded. Load-flow studies are often used to identify the need for

    additional generation, capacitive, or inductive VAR support, orthe placement of capacitors and/or reactors to maintain systemvoltages within specified limits.

    Losses in each branch and total system power losses are also

    calculated. Necessary for planning, economic scheduling, and control of an

    existing system as well as planning its future expansion

    Pulse of the system

  • 7/22/2019 A Review on Load Flow Studies Final

    4/46

    Power Flow Equation

    Note: Transmission lines arerepresented by their equivalent pi

    models (impedance in p.u.)

    Applying KCL to this bus results

    in

    (1)

    Fig. 1. A typical bus of the power system.

  • 7/22/2019 A Review on Load Flow Studies Final

    5/46

    (2)

    The real and reactive power at bus

    iis

    Substituting for Ii in (2) yields

    Equation (5) is an algebraic non linear equation which must be solved by

    iterative techniques

  • 7/22/2019 A Review on Load Flow Studies Final

    6/46

    Gauss-Seidel method

    Equation (5) is solved for Visolved iteratively

    Where yi jis the actual admittance in p.u.

    Pischand Qi

    schare the net real and reactive powers in p.u.

    In writing the KCL, current entering bus Iwas assumed positive. Thus

    for:Generator buses (where real and reactive powers are injected), Pi

    schand

    Qisch have positive values.

    Load buses (real and reactive powers flow away from the bus), Pischand

    Qisch have negative values.

  • 7/22/2019 A Review on Load Flow Studies Final

    7/46

    Eqn.5 can be solved forPiand Qi

    The power flow equation is usually expressed in terms of the

    elements of the bus admittance matrix, Ybus ,shown by upper case

    letters, are Yij = -yij, and the diagonal elements are Yii = yij.

    Hence eqn. 6 can be written as

  • 7/22/2019 A Review on Load Flow Studies Final

    8/46

    Iterative steps:

    Slack bus: both components of the voltage are specified. 2(n-1)

    equations to be solved iteratively.

    Flat voltage start: initial voltage of 1.0+j0 for unknown voltages.

    PQ buses: Pisch and Qisch are known. with flat voltage start, Eqn. 9 issolved for real and imaginary components of Voltage.

    PV buses: Pisch and [Vi] are known. Eqn. 11 is solved for Qi

    k+1which is

    then substituted in Eqn. 9 to solve for Vik+1

  • 7/22/2019 A Review on Load Flow Studies Final

    9/46

    However, since [Vi] is specified, only the imaginary part of Vik+1 is

    retained, and its real part is selected in order to satisfy

    acceleration factor:the rate of convergence is increased by applying anacceleration factor to the approx. solution obtained from each iteration.

    Iteration is continued until

    Once a solution is converged, the net real and reactive powers at the slack

    bus are computed from Eqns.10 & 11.

  • 7/22/2019 A Review on Load Flow Studies Final

    10/46

    Line flows and Line losses

    Considering Ii jpositive in the given direction,

    Similarly, considering the line current Ijiin the given direction,

    The complex power Si jfrom bus i to j and Sji from bus j to i are

  • 7/22/2019 A Review on Load Flow Studies Final

    11/46

    Newton Raphson Method

    Power flow equations formulated in polar form. For the

    system in Fig.1, Eqn.2 can be written in terms of busadmittance matrix as

    Expressing in polar form;

    Note:jalso includes i

    Substituting for Iifrom Eqn.21 in Eqn. 4

  • 7/22/2019 A Review on Load Flow Studies Final

    12/46

    Separating the real and imaginary parts,

    Expanding Eqns. 23 & 24 in Taylor's series about the initial estimateneglecting h.o.t. we get

  • 7/22/2019 A Review on Load Flow Studies Final

    13/46

    The Jacobian matrix gives the linearized relationship between small changes ini

    (k ) and voltage magnitude [Vik] with the small changes in real and reactive

    power Pi(k) and Qi

    (k)

    The diagonal and the off-diagonal elements of J1are:

    Similarly we can find the diagonal and off-diagonal elements of J2,J3and J4

    The terms Pi(k) and Qi

    (k )are the difference between the scheduled

    and calculated values, known as the power residuals.

  • 7/22/2019 A Review on Load Flow Studies Final

    14/46

    Procedures:

    1. For Load buses (P,Q specified), flat voltage start. For voltage controlledbuses (P,V specified),set equal to 0.

    2. For Load buses,Pi(k) and Qi(k )are calculated from Eqns.23 & 24 andPi

    (k) and Qi(k )are calculated from Eqns. 29 & 30.

    3. For voltage controlled buses, and Pi(k) and Pi

    (k )are calculated from

    Eqns. 23 & 29 respectively.

    4. The elements of the Jacobian matrix are calculated.

    5. The linear simultaneous equation 26 is solved directly by optimally

    ordered triangle factorization and Gaussian elimination.

  • 7/22/2019 A Review on Load Flow Studies Final

    15/46

    6. The new voltage magnitudes and phase angles are computed from (31)

    and (32).7. The process is continued until the residuals Pi

    (k) and Qi(k ) are less

    than the specified accuracy i.e.

    3. Fast Decoupled Method

    practical power transmission lines have high X/R ratio.Real power changes are less sensitive to voltage magnitude changes andare most sensitive to changes in phase angle .

    Similarly, reactive power changes are less sensitive to changes in angle

    and are mainly dependent on changes in voltage magnitude.

    Therefore the Jacobian matrix in Eqn.26 can be written as

  • 7/22/2019 A Review on Load Flow Studies Final

    16/46

    The diagonal elements of J1 given by Eqn.27 is written as

    Replacing the first term of the (37) withQi from (28)

    Bi i = sum of susceptances of all the elements incident to bus i.

    In a typical power system, Bi i Qi therefore we may neglect Qi

  • 7/22/2019 A Review on Load Flow Studies Final

    17/46

    Furthermore, [Vi]2 [Vi] . Ultimately

    In equation (28) assuming ii-i+j ii, the off diagonal elements of J1

    becomes

    Assuming [Vj] 1 we get

    Similarly we can simplify the diagonal and off-diagonal elements of J4 as

    With these assumptions, equations (35) & (36) can be written in

    the following form

  • 7/22/2019 A Review on Load Flow Studies Final

    18/46

    B and B are the imaginary part of the bus admittance

    matrix Ybus. Since the elements of the matrix are constant,need to be triangularized and inverted only once at the

    beginning of the iteration.

  • 7/22/2019 A Review on Load Flow Studies Final

    19/46

    Other Methods

    Repetitive solution of a large set of linear equations

    in LF- time consuming in simulations

    Large number of calculations on the Jacobian

    matrix.

    Jacobian of load flow equation tends to be singular

    under heavy loading.

    Ill conditioned Jacobian matrix

    Doesnt require the formation of the Jacobian matrix

    Insensitive to the initial settings of the solutionvariables

    Ability to find multiple load-flow solutions.

  • 7/22/2019 A Review on Load Flow Studies Final

    20/46

    Fuzzy Logic application Repetitive solution of a large set of linear equations in the load flow

    problem is one of the most time consuming parts of power system

    simulations.

    Large number of calculations need on account of factorisation,

    refactorization and computations of Jacobian matrix.

    Fundamentally FL is implemented in a fast decoupled load flow(FDLF) problem.

    Mathematical analysis of FDLF

    In eqn. 1, the state vector is updated

    but state vector V is fixed. Eqn. 2 isused to update the state vector Vwhile state vector is fixed. The

    whole calculation will terminate only if

    the errors of both these equations are

    within acceptable tolerances

  • 7/22/2019 A Review on Load Flow Studies Final

    21/46

    Main idea of FLF Algorithm

    FLF algorithm is based on FDLF equation but the repeated update of the state

    vector performed via Fuzzy Logic Control instead of using the classical load flow

    approach.

    The FLF algorithm is illustrated

    schematically in Fig. 1.In this Figure

    the power parameters FPand FQ

    are calculatedand introduced to the

    P- FLCP- and Q-V FLCQ-V,

    respectively.

    The FLCs generate the correction of

    the state vector DX namely, the

    correction of voltage angle for the

    P- cycle and the correction ofvoltage magnitude V for the Q- V

    cycle.

  • 7/22/2019 A Review on Load Flow Studies Final

    22/46

    Structure of the fuzzy load flow controller (FLFC)

    Calculate and per-unite the power parameters FPand FQat each node

    of the system.

    The above parameters are elected as crisp input signals. The maximum (orworst) power parameter (FPmax or FQmax) determines the range of scale

    mapping that transfers the input signals into corresponding universe ofdiscourse, at every iteration.The input signals are fuzzified into corresponding fuzzy signals (FPfuzor

    FQfuzwith seven linguistic variables; largenegative (LN), medium negative

    (MN), small negative(SN), zero (ZR), small positive (SP), medium positive

    (MP), large positive (LP). They are represented in triangular function.

  • 7/22/2019 A Review on Load Flow Studies Final

    23/46

    The rule base involves seven rules tallying with seven linguistic

    variables:Rule 1: if Ffuzis LN then Xfuzis LN

    Rule 2: if Ffuzis MN then Xfuzis MN

    Rule 3: if

    Ffuzis SN thenXfuzis SNRule 4: if Ffuzis ZR then Xfuzis ZR

    Rule 5: if Ffuzis SP then Xfuzis SP

    Rule 6: if Ffuzis MP then Xfuzis MP

    Rule 7: if Ffuzis LP then Xfuzis LP

    These fuzzy rules are consistent to that of Eqn.3.

  • 7/22/2019 A Review on Load Flow Studies Final

    24/46

    The maximum corrective action xmaxof state variables determines

    the range of scale mapping that transfers the output signals into the

    corresponding universe of discourse at every iteration.

    where FI expresses the real or reactive power balance

    equation at node-I with maximum real or reactive power

    mismatch of the system, XI represents the voltage angle or

    magnitude at node-I.

    The fuzzy signalsffuzare sent to process logic, which generatesthe fuzzy output signals xfuzbased on the previous rule base and

    are represented by seven linguistic variables similar to input fuzzy

    signals.

  • 7/22/2019 A Review on Load Flow Studies Final

    25/46

    finally the defuzzifier will transform fuzzy output signals into crisp

    values for every node of the network. The state vector is updated

    as

    Index idepicts the number of iterations.

  • 7/22/2019 A Review on Load Flow Studies Final

    26/46

    Case studies

  • 7/22/2019 A Review on Load Flow Studies Final

    27/46

  • 7/22/2019 A Review on Load Flow Studies Final

    28/46

    GA applicationsLoad flow problem

    where Gij and Bijare the (I,j)th

    element of the admittance

    matrix. Ei, and Fi are real and

    imaginary parts of the voltage at

    node i.

    If node i is a PQ node where the load demand is specified, then themismatches in active and reactive powers, Pi and Qi , respectively,

    are given by

    Pisp

    and Qisp

    are the specifiedactive and reactive powers at

    node i.

  • 7/22/2019 A Review on Load Flow Studies Final

    29/46

    When node i is a PV node, the magnitude of the voltage, Vispand

    the active power,Q;P, at i are specified. The mismatch in voltage

    magnitude at node i can be defined as

    The active power mismatch is as given

    in Eqn.3

    Objective function H is to be minimized.

    Where Npq, Npvare the total numbers of PQ and PV

    nodes.

  • 7/22/2019 A Review on Load Flow Studies Final

    30/46

    Components in genetic approach

    1. Chromosomes: The real and imaginary parts of the

    voltages of the nodes in the power system are

    encoded using floating-point numbers and are set aselements in the chromosomes.

    2. Fitness function:

    3. Crossover operation: 2 point crossover method to

    bring more diversity in the population of

    chromosomes.4. Mutation operation: An element of a chromosome is

    selected randomly. The voltage value of the element

    is replaced by a value arbitrarily chosen within a

    range of voltage values.

    M is a constant for amplifying the fitness value.

  • 7/22/2019 A Review on Load Flow Studies Final

    31/46

    Initialize schromosomes in the population

    Fitness f(x) of each chromosome (fittest

    chromosomes always retained)

    Replace the current population with new population

    Mutation

    Crossover (Pc= crossover

    rate/probability)

    Selection of chromosomes (roulette

    wheel method)

    No of

    Offspring

    =s? Maxnumber of

    generation

    reached?

    End

    Fig.1 GA Load flow

    Algorithm flowchart

    No

    Yes

    Yes No

  • 7/22/2019 A Review on Load Flow Studies Final

    32/46

    Constraint satisfaction technique for updating candidate nodal

    voltages

    (a) Satisfying the powers at a PQ node i by updating a PQ node d.

    (b) updating the voltage at a PV node to satisfy its voltage and activepower requirements

    Constraint satisfaction for PQ nodes

    Let the real and imaginary voltages of node d be Eidand Fid. The power

    mismatches Pi in eqn. 3 and Q

    i in eqn. 4 for node i are now set to zero.

    From eqns. 1-4, when d i, Eidand Fid can be calculated according to

  • 7/22/2019 A Review on Load Flow Studies Final

    33/46

    When d = i , the power constraints at PQ node d itself are required to be met.

    The constraint equations for calculating Eidand Fid of node d can be derived

    from eqns. 1- 4 by the same procedure above and by setting the subscript i

    in eqns. 1-4 to d.

    Constraint satisfaction for PV nodes

    Let the real and imaginary voltages of the PV node d in the chromosome be

    Eddand Fdd. The mismatches Pdin eqn. 3 and Vdin eqn. 5 for node d can

    now be set to zero. From eqns. 1, 3, 5 and 6, the expressions for Eddand Fddare:

  • 7/22/2019 A Review on Load Flow Studies Final

    34/46

    Methods for enhancing the CGALF Algorithm

    a) Dynamic population technique

    Diversity of the chromosomes increased by introducing new

    chromosomes in the population to escape from local minimum points.

    % of existing weaker chromosomes replaced by randomly generatedchromosomes when the values of objective function H are identical for a

    specified number of generations or iterations- subject to constraint

    satisfaction.

    b) Solution acceleration technique

    Faster convergence. Modify the constrained candidate solution process such that the revised

    solutions in the chromosomes are closer to the candidate solution in the

    best or fittest chromosome found so far.

    Vk=2Vk,bestVk

    c) Nodal voltage updating sequencei. Update the voltages of the PV nodes in the sequence of the node

    number using eqns. 12-14.

    ii. Then, the PQ node, which has the largest total mismatch, is updated

    first using the constraint satisfaction methods.

  • 7/22/2019 A Review on Load Flow Studies Final

    35/46

    (iii) Repeat step (ii) until all the PQ nodes are processed.

    In step (i) above, the update operation attempts to meet the

    voltage magnitude constraints and active power requirements of

    the PV nodes.The strategy employed in step (ii) guarantees a reduction of the

    mismatch at the node with the largest total mismatch. The strategy

    is applied dynamically during the processing of the nodes as

    indicated in step (iii).

    Application examples

    Klos-kerner 11 node test system.

    Two loading condition considered.

  • 7/22/2019 A Review on Load Flow Studies Final

    36/46

    Node 1: Slack node,voltage level=1.05pu. Nodes 5 and 9 are PV nodes

    with target voltages of 1.05pu and 1.0375pu.

  • 7/22/2019 A Review on Load Flow Studies Final

    37/46

  • 7/22/2019 A Review on Load Flow Studies Final

    38/46

  • 7/22/2019 A Review on Load Flow Studies Final

    39/46

  • 7/22/2019 A Review on Load Flow Studies Final

    40/46

  • 7/22/2019 A Review on Load Flow Studies Final

    41/46

    Hybrid Particle swarm optimization

    application

    1. Problem Formulation: The load flow equations, at any given bus(i) inthe system, are as follows:

  • 7/22/2019 A Review on Load Flow Studies Final

    42/46

    The optimization problem is formulated as follows:

    2. Hybrid Particle Swarm Optimization.

    The PSO model consists of a number of particles moving around

    in the search space, each representing a possible solution to a

    numerical problem. Each particle has a position vector (xi)and avelocity vector (vi)), the position (pbesti) is the best position

    encountered by the particle (i) during its search and the position

    (gbest) is that of the best particle in the swarm group.

  • 7/22/2019 A Review on Load Flow Studies Final

    43/46

    In each iteration the velocity of each particle is updated according to its

    best-encountered position and the best position encountered among

    the group, using the following equation:

    The position of each particle is then updated in each iteration by

    adding the velocity vector to the position vector.

    Inertia weight wcontrol the impact of the previous history of velocities

    on the current velocity-it regulates the trade-off between the global and

    local exploration abilities of the swarm.

    Suitable value for w usually provide balance between global and local

    exploration abilities and consequently a reduction on the number of

    iterations for optimal solution.

  • 7/22/2019 A Review on Load Flow Studies Final

    44/46

    Ability of breeding, a powerful property of GA is used.

  • 7/22/2019 A Review on Load Flow Studies Final

    45/46

    Numerical Examples

    IEEE 14 bus system:

  • 7/22/2019 A Review on Load Flow Studies Final

    46/46

    Thank youReferences:

    1. Power System Analysis, Hadi saadat, McGraw Hill International editions.

    2. Fuzzy Logic application in load flow studies,J.G.Vlachogiannis,IEE,2001.

    3. Development of constrained-Genetic Algorithm load flow method,

    K.P.Wong,A.Li,M.Y.Law,IEE,1997.4. Load flow solution using Hybrid Particle Swarm Optimization, Amgad

    A.El-Dib et.al, IEEE,2004.