A Next Generation OCS
OCS connectivity to
(aka the Evil Empire)
RockwellAutomation
A Next Generation OCS
What if I want more than an Ethernet/IP I/O Connection and its 256 Byte limit?• There are several options for communicating
with A-B products• DF1 full duplex serial is available as a
downloadable serial protocol• With an affordable external device, Allen-Bradley
Ethernet and Ethernet/IP are also an option
A-B Connectivity
A Next Generation OCS
PCCC & CIP are the two Protocol families supported by Rockwell
• What is PCCC?• It is the application layer message packet of
DF1• It allows you to issue poll/response messages
to arrays of A-B data (register/table/file)• It is the core message that moves easily
between DF1, DH485, DH+, AB/Ethernet & Ethernet/IP with PCCC encapsulation
• What is CIP?• As discussed - Common Industrial Protocol• Used in ControlLogix & CompactLogix CPUs• It is Object Oriented - services are sent to
specific instances of objects. It is not based on accessing arrays of file data.
A-B Protocol Families
A Next Generation OCS
A summary of A-B protocols existing over a variety of media
• RS-232• DF1 Full Duplex. The core protocol spoken by
most A-B PLCs. Is proprietary but published.• DF1 Half Duplex. Very slow and rarely used.• DF1 Radio. Recently added in approx. 2003.• DF1 to Logix CPU. Encapsulates fragmented
CIP messages within DF1. Not documented.• RS-485
• DH485. A proprietary (closed), token passing network allowing slaves to talk directly to one another. Does not work over Ethernet or radio due to token speed. Some 3rd parties attempt to support it in a “single master” mode - which often doesn’t work.
A-B Protocols
A Next Generation OCS
A summary of A-B protocols existing over a variety of media
• Ethernet• AB/Ethernet. Sometimes called CSP. An older
TCP port 2222 protocol from the PLC5E. Very closely related to DF1 & DH+. Only works on non-CIP messaging. A-B would like to obsolete it.
• Ethernet/IP. Can move CIP or even DF1 encapsulated messages. In its non-encapsulated form is object based and not register/table/file based like DF1.
• Others• DH, DH+. Older, proprietary token bus
systems. NOT RS-485 based, but requires custom hardware. A-B wants to move these users over to ControlNet.
A-B Protocols
A Next Generation OCS
• Directly supported through OCS Downloadable Protocol• Lowest Cost• Works with virtually all A-B PLCs• Good solution for MicroLogix, SLC
OCS Connectivity to A-B
MicroLogix
XLe OCS
SLC 5
NX OCS
DF1 Protocol Dialog
DF1 Serial
A Next Generation OCS
ControlLogixCompactLogix
• Indirectly supported - requires an economical gateway solution (IAP Gateway)• Connection at OCS end can be either
serial OR Ethernet
OCS Connectivity to A-BA-B/Ethernet
LX OCS
QuickTime™ and aTIFF (LZW) decompressor
are needed to see this picture.
IAP Gateway
SLC 5/05 PLC-5E
AB/EthernetDF1 RS-232
A Next Generation OCS
ControlLogix
CompactLogix
• IAP Gateway re-configures and re-routes Modbus/TCP messages to/from A-B PLC via Ethernet/IP
• A-B PLC responds to traffic as if it were coming from another A-B product
OCS Connectivity to A-BEthernet/IP (non CIP based)
QX OCS
QuickTime™ and aTIFF (LZW) decompressor
are needed to see this picture.
IAP Gateway
Modbus/TCP Ethernet/IP