A Fault Line Selection Algorithm Using Neural Network Based on S-Transform Energy

Embed Size (px)

Citation preview

  • 8/10/2019 A Fault Line Selection Algorithm Using Neural Network Based on S-Transform Energy

    1/5978-1-4244-5961-2/10/$26.00 2010 IEEE 1478

    2010 Sixth International Conference on Natural Computation (ICNC 2010)

    A Fault Line Selection Algorithm Using Neural

    Network Based on S-Transform Energy

    Shu Hongchun, Qiu GefeiLi Chaofan

    School of Electrical Engineering

    Kunming University of Science and Technology

    Kunming, Yunnan Province, China

    Peng Shixin

    Kunming Power Supply Bureau

    Kunming 650011, Yunnan Province, China

    AbstractAn approach to detect fault line in distribution network

    using neural network based on S-transform energy is proposed undafter analyzing the variance of fault characteristic frequency of zerosequence current in each feeder line of overhead line and

    underground cable mixed lines. In order to avoid the effect of TAsdisconnection angle, the short window data of first 1/4 cycle areselected. The S-transform is carried out to determine the maincharacteristic frequency of fault zero sequence current, and taking the

    Short Window energy of the main characteristic frequency as thetarget input to form BP neural network model, thus the fault line can

    be detected adaptively. State component and various noises can befiltered out utilizing S-transform to determine the main characteristic

    frequency. Fault detecting margin can be enhanced by adjusting theweight of criterion through neural network training accurately. Thetheoretic analysis and simulations demonstrate the feasibility andvalidity of this approach, also the problem that training time is too

    long and network result is too complex is well solved when usingtraditional neural network to detect fault line.

    Keywords- S-transform energy; main characteristic frequency;

    neural network; overhead line and underground cable

    I.

    INTRODUCTION

    Fault in distribution network mostly is single phase fault.

    In recent years, the massive researches on fault line selection

    technology have been done by scholars. And lots of fault line

    selection methods based on stable component[1,2], transient

    component[3-10]and the selection of wave head of traveling

    wave[11-18] were proposed. There are richness transient

    component of single phase fault in distribution network, and

    the acquisition of transient component does not need too high

    sampling frequency, so the fault line selection method based

    on transient component attracts scholars attention. By now,

    the veracity and reliability of fault line selection can not

    satisfy the project actual request by far, so it is necessary to

    process fundamental research and project practice.

    S-transformed is a kind of time-frequency analysis method

    which based on continual wavelet transformation and short-

    time Fourier transformation. The direct result of extracted

    signal been S-transformed is a duplicate time-frequency

    matrix, which include the information distributed by time and

    frequency such as signal peak-to-peak value and phase etc. It

    supplies the foundation information to extract each kind of

    character of the signal.

    BP network is a sort of multi-layered, forward feed neural

    network. Its neuron's transfer function is the S form function,

    and the output is a continual quantity between 0 and 1, which

    realizes the random nonlinearity mapping from the input to the

    output.By analyzing the variance of fault characteristic frequency of

    zero sequence current in each feeder line of overhead line andunderground cable mixed lines, the short window data of first 1/4

    cycle are selected to detect fault line in distribution network usingneural network based on S-transform energy. The S-transform iscarried out to determine the main characteristic frequency of faultzero sequence current, and taking the Short Window energy of themain characteristic frequency as the target input to form BP neural

    network model, thus the fault line can be detected adaptively.

    II. ELECTROMAGNETISM TRANSIENT CHARACTERISTIC

    ANALYSIS OF MIXED CABLE-LINE GRID

    Without lose of generality, take a mixed cable-line

    resonance grounding system as example. The model of

    110kV/35kV distribution grid with single phase grounding

    fault is constructed as Fig. 1, it has 6 lines, and the neutral

    point of Z transformer has been grounded via arc

    suppression coil, the current transformer is LSJC-35 type. The

    overhead lines L1=15kmL3=18kmL5=30kmcable-line

    mixed line L4=17kmin which the length of overhead line is

    12km and the length of cable is 5km, the cable L2=6km

    L6=8km. In which the overhead line use JS1 pole and LGJ

    70 line conductor, the line span is 80m, the type of cable is

    YJV23-35/95.

    L1

    35kV110kV

    TZ

    L

    R

    T

    K

    CBA ..

    .C BA

    .. .

    . ..

    ... . ..

    . ..Rf

    .

    ... . ..

    L2 L3 omission

    L4

    L6

    L5 omission

    i01

    i04

    i06

    load

    load

    load

    Fig.1 Radial resonant earthed system

    When single phase fault occurs in resonance grounding

    system with 10% over compensation, the transition resistance

    is 20and the closing angle of fault is 90, the zero-sequence

    current of fault line L1 and sound line L2, L3 is shown in

  • 8/10/2019 A Fault Line Selection Algorithm Using Neural Network Based on S-Transform Energy

    2/5

    1479

    Figure 2. The process of the electric charge and discharge in

    the capacity between sound lines and earth are similar. Due to

    action of the additional zero-sequence current source, the

    transient component waveforms of zero-sequence current of

    fault lines are the most distinct from the other lines.

    0 0 .01 0.02 0 .03 0 .04-200

    0

    200

    400

    600

    t/s

    i/A

    0 0.01 0.02 0.03 0.04-150

    -100

    -50

    0

    50

    100

    t/s

    L2

    L3

    i/A

    (a) fault line (b) sound line

    Fig.2 Fault zero-sequence current of 90o

    III.

    CALCULATION OF SHORT WINDOW ENERGY USING S-

    TRANSFORM

    A. Theory of S-Transform

    S-transformed is a kind of time-frequency analysis method

    which based on continual wavelet transformation and short-

    time Fourier transformation.

    The discrete form of S-transform can be expressed as:

    [ ] [ ]2 2 2

    12 / j2 /

    0

    , 0N

    k n km N

    k

    S m n X n k e e n

    =

    = + 1

    [ ] [ ]1

    0

    1, 0

    N

    k

    S m n x k nN

    =

    = = 2

    in which

    [ ] [ ]1

    j2 /

    0

    1 Nkn N

    k

    X n x k eN

    =

    = 3

    B.

    Transient Energy

    Zero sequence energy function of each feeder is defined

    as:

    0 00

    ( ) ( ) ( ) =1,2, ,6t

    i iW t u i d i = 4

    In which, Wi(t)-zero sequence energy function of Li after

    fault, u0(t)-zero sequence voltage of bus i0i(t)0-zero

    sequence current of Li.

    Transient energy function of the first 1/4 cycle after fault is

    defined as:T

    40 0

    0

    T( ) ( ) ( ) =1,2, ,6

    4i i

    W u i d i = 5

    Utilizing S-transform to extract the characteristic of each

    frequency of each signal and according to formula (1),(2) and(5) simultaneously transient energy of each line on fn by S-

    transform is defined as:

    [ ]2

    ( , ) =1,2, ,6i nm

    W S m n i

    = 6

    C. Determination of Characteristic Frequency

    Sample data zero current in the first 1/4 cycle after fault

    was analyzed utilizing S-transform and frequency spacing oftwo adjacent frequencies is obtained according to thedefinition of frequency S-transform resolution.

    200Hzsf

    fN

    = = 7

    The energy distribution of fault line L1and sound lines on

    frequency fn are shown in Fig.3.

    5 10 15 20 250

    1

    2

    3

    4x10

    m

    W5

    5 10 15 20 250

    1

    2

    3

    4x10

    m

    W

    4

    (a) fault line L1 (b) sound line L2

    5 10 15 20 250

    100

    200

    300

    400

    500

    m

    W

    5 10 15 20 250

    1

    2

    3

    m

    Wx10

    4

    (c) sound line L3 (d) sound line L4

    5 10 15 20 250

    500

    1000

    1500

    m

    W

    5 10 15 20 250

    2

    4

    6

    8

    m

    Wx104

    (e) sound line L5 (f) sound line L6

    Fig.3 Energy distribution at each frequencyL1 fault

    As shown in Fig.3, short window energy of all lines is

    largest on frequency 400Hz and the energy on this frequencycan reflect the characteristics of fault short window energy.

    5 10 15 20 250

    20

    40

    60

    80W

    m 5 10 15 20 250

    1000

    2000

    3000

    m (a) sound line L1 (b) sound line L2

    5 10 15 20 250

    10

    20

    30

    40

    50

    m

    W

    5 10 15 20 250

    5

    10

    15x10

    m

    W4

    (c) sound line L3 (d) fault line L4

    5 10 15 20 250

    20

    40

    60

    80

    100

    m

    W

    5 10 15 20 250

    2000

    4000

    6000

    m

    W

    (e) sound line L5 (f) sound line L6

    Fig.4 Energy distribution at each frequencyL4 fault

    When fault occurred on L4 with 20o closing angle through

    200 transition resistance, transient energy of each line on

    each frequency point fn were obtained by performing S-

  • 8/10/2019 A Fault Line Selection Algorithm Using Neural Network Based on S-Transform Energy

    3/5

    1480

    transform on zero sequence current of each line in 1/4 cycleafter fault, which is shown in Fig.4.

    As shown in Fig.4, energy of L2, L4, L5, L6 concentrateon f0=0Hz mostly, i.e. direct current component, and energy

    of L1 and L3 concentrate on the frequency 3600Hz and

    3000Hz respectively. While transient energy of fault line L4 is

    100 times larger than other ones. Transient energy sum on

    each frequency point fn were obtained according to formula

    (6) by adding the energy on each frequency point of all lines.

    [ ]2

    ( , ) =1,2, ,6ni m

    W S m n i= 8

    In term of formula (8), sum up the energy on each

    frequency point fn of each line in Fig.4 and the result is shown

    in Fig.5.

    5 10 15 20 250

    5

    10

    15x10

    m

    W

    4

    Fig.5 Total energy distribution at each frequency

    From Fig.5 and Fig.6, it can be concluded that the

    frequency with largest energy sum on each frequency point of

    each line is consistent with the one on which fault linesenergy is mostly concentrated, therefore the frequency with

    largest short window energy of zero sequence current in all

    lines is defined as main characteristic frequency ftz of fault.

    D.

    Transient Energy of Characteristic Frequency

    Short window energy on main characteristic frequency ofeach line can be calculated according to formula (6) after main

    characteristic frequency is determined:

    [ ]2

    _ ( , ) =1,2, ,6i tem

    W S m k i= 9

    In the cases that shown in Fig.3 and Fig.4, the

    distribution of short window energy on main characteristic

    frequency of each line is shown in Fig.6.

    1 2 3 4 5 60

    1

    2

    3

    4

    5

    i

    Wx10

    1 2 3 4 5 60

    5

    10

    15x10

    i

    W

    4

    (a) line L1fault (b) line L4fault

    Fig.6 Energy distribution at characteristic frequency of each line

    IV. DESIGN OF BPNETWORK

    A. Structure Design Based on BP Network

    (1) Input layer and output layer design

    Fault line's short window energy is the largest, so fault lineselection can be realized by comparing the short windowenergy of all the lines. When fault occurs, taking short window

    energy of 6 lines of the system in Fig.1 as input layer

    information, thus the dimension of input layer, whichrepresent short window energy of the 6 lines, is 6.

    (2) The selection of hidden layer numberThe performance of the network depends on the number of

    hidden layer directly. A single hidden layer BP network may

    approach any complicated function. With the single hidden

    layer, the triplex layer neural network can carry out any

    complicated function mapping. The triplex layer network is

    chosen in this article chooses with single hidden layer to makethe network in simplification.

    (3) The neuron number of hidden layer

    By the methods of the hidden layer neuron number

    determination such as trim method, growth method, self-adapting method etc, the range of the hidden layer neuron

    number is determined in [5,14]. According to the sample dataand the designed network structure, the neuron number of the

    concealment layer is finally fixed on 8 through simulation

    testing utilizing the data mining tools like WEKA and the

    neural network toolbox.

    The structure of BP network is shown in Fig.7.

    Fault

    Fault

    Input

    Layer

    Output

    Layer

    Hidden Layer

    Fault

    Fault

    Fig.7 Structure of BP network

    B.

    The Parameter Design of BP Network

    (1) The selection of network initial value

    The range of initial value from the input layer to the

    hidden layer is (0, 1/ 6 ), and the range of initial value from

    the hidden layer to output layer is setting as (02/ 3 ).

    (2) The setting of network study parameter

    The experiment is processed with the goal of definite

    performance as 0.1. Train the network unceasingly by

    selecting different study rate and momentum constant, afterthe weight values reach the steady state, it is found that the

    effect of network study is most ideal when setting studyparameter as 0.3 and momentum constant as 0.2.

    V. THE TRAINING OF BPNETWORK

    A.

    The Selection of Training Samples

    Simulation was performed when single phase grounding

    fault occur in the distribution grid shown in Fig.1, while faultposition was separately set at 20%, 40%, 60%, 80% of the

    total length in each line, the transition resistance is separately20, 60, 80, 100, 120, 150, 200, 250 and the

    closing angle is separately 0, 30, 45, 60, 90. 20 different

    types of bus faults were designed and thus 860 groups of

    waiting training samples were obtained.

  • 8/10/2019 A Fault Line Selection Algorithm Using Neural Network Based on S-Transform Energy

    4/5

    1481

    Initial training samples were pretreated, i.e. short windowenergy data from zero sequence current of the 6 lines were

    extracted and finally 860 groups of training samples wereobtained.B.

    The Pretreatment of Sample Data

    To eliminate the effect of energy absolute value of

    networks study ability, normalized pretreatment is performed

    on study sample data according to formula (9). Thus the

    sample date ranges in the zone [0,1] after normalizedpretreatment.

    * min

    max min

    W WW

    W W

    =

    9

    In which, W*-short window energy of line after

    normalized pretreatment, W-absolute value, WmaxWmin

    maximum and minimum short window energyin 6 lines

    C.

    Error Criterion Function

    Order N as the sum of the modes including training set

    and the average value of error energy is:

    1

    1( )

    N

    av

    n

    E E nN =

    = (10)

    In which,E(n)-instantaneous value of error energy.D.

    Stop Condition of Training

    Two conditions that the value of minimum error criterion

    function and the maximum iteration times are chosen as the

    condition to stop training and judge convergent of network.

    VI. IDENTIFICATION OF BPNETWORK

    As for a trained network, the process of identification is

    just a recall process of network. Prescribe that the output valueof component reaching 0 when it is less than or equal to 0.2

    and reaching 1 when it is more than or equal to 0.8. The output

    value of component reaches 1 means the lines correspondingly

    is fault, while all output values of component reach 0 resultingin the bus fault.

    VII. METHOD OF FAULT LINE SELECTION

    The schematic diagram of fault line selection is shown in

    Fig.8. Firstly, characteristic frequency of transient zero

    sequence current is determined according to the maximumenergy sum criterion, then the transient energy on each

    frequency point of each line is extracted as the characteristicvalue to perform of training neural network and thus fault lineis obtained through adjusting the weighting value and outing

    the value.

    Fig.8 Schematic diagram of fault line selection

    VIII. SIMULATION

    Samples with different closing angle and transition

    resistance of various fault types were selected as testing onesto verify the stability and validity of the system throughnetwork recall. Limited by the pages, only part simulation

    results are shown in Table 1.compared with the actual

    situation, precision of fault line selection reaches 99.31%.

    TABLE I. RESULT OF FAULT LINE SELECTION

    Fault type LiXf

    (km)

    Rf()

    (deg)Output of network recall Fault line

    Line fault

    1 2

    40 0 [10.00010000.0002] L1

    300 30 [0.92240.00010.00240.010.00020.248] L1

    40 60 [0.98250.00040.1470.2480.00660.0541] L1

    300 90 [0.968500.01120.0040.00030.1786] L1

    5

    15300 0 [0.00180.0020.02650.0020.9980] L5

    40 30 [0.00050.00110.0250.000510.046] L5

    28300 60 [00.16740.01530.00010.8760.004] L5

    400 90 [0.00260.00350.02680.00210.91340.001] L5

    Bus fault bus 0

    300 0 [0.05750.00010.19680.00330.09890.0054] bus

    40 30 [0.00170.02970.00540.00130.00190.057] bus

    20 60 [0.09640.00010.00080.006400.0029] bus

    200 90 [0.2250.00540.0160.18510.380.021] bus

    Arc fault 3 10 40

    0 [0.14370.12620.998700.11710.0296] L3

    30 [0.0010.00010.79250.03660.17630.0361] L3

    60 [0.13890.07120.99990.34250.00010] L3

    90 [0.05940.06370.86270.04140.01060.016] L3

    Note: Li-fault line; Xf-distance from fault point to bus; Rf-transition resistance-fault closing angle.

    IX. CONCLUSION

    The fault line selection algorithm proposed in this paperusing neural network based on S-transform adopts T/4 short

    window data, thus CTs saturation disconnection angle is

    avoided; utilizes S-transform to extract fault transientinformation, the effect of fundamental frequency component

    and other non characteristic frequency band component are

    eliminated, so the reliability and sensitivity are both improved;

    ANN1

    ANN2

    ANN6

    .

    .

    .

    FAULT

    FAULT

    FAULT

    FAULT

    FAULT

    FAULT

    1_

    2_

    6_

    W

    W

    W

    te

    te

    te

  • 8/10/2019 A Fault Line Selection Algorithm Using Neural Network Based on S-Transform Energy

    5/5