Two-channel safety barriersSeries 9002
ww
w.s
tah
l.d
e
Series 9002 A2
2013-05-24·AK00·III·en
04101E00
A2
A2
A2
A2
A2
A2
A2
A2
NEC 500
Class I Class II Class III
ivision 1 2 1 2 1 2
x i interface x x x x x x
stallation in x x*) x*)
WebCode 9002A
Sa
fety ba> Wide product range for all standard applications of theautomation
> Flexible and space-saving – available in single and double channel versions
> Time-saving installation thanks to simultaneous– snap-on mounting on rails
and – connection to PE and earth
> Reduced stock-keeping thanks to a uniform back-up fuse
The R. STAHL INTRINSPAK safety barriers of Series 9002 can be used for various tasks in the field of automation. The wide product range and scope of different combinations offer you a large field of applications.The safety barriers allow the intrinsically safe operation of HART transmitters, proximity sensors, potential-free contacts, temperature sensors, DMS, solenoid valves, indicators and others.Due to the compact width, space-saving and flexible installation in the switch cabinet is possible. Thanks to DIN-rail mounting and simultaneous connection of the equipotential bonding, theinstallation can be performed very easily.
*) For restrictions, see Explosion protection table
ATEX / IECEX NEC 505 NEC 506
Class I
Zone 0 1 2 20 21 22 Zone 0 1 2 20 21 22 D
Ex i interface x x x x x x Ex i interface E
Installation in x x Installation in x x In
rriers A2/1
Two-channel safety barriersSeries 9002
A2/2
Explosion Protection
Global (IECEx)Gas and dust IECEx PTB 08.0057X
Ex nA [ia Ga] IIC T4 Gc[Ex ia Da] IIIC
Europe (ATEX)Gas and dust PTB 01 ATEX 2053 X
E II 3 (1) G Ex nA [ia Ga] IIC/IIB T4 GcE II (1) D [Ex ia Da] IIIC
CertificatesCertificates IECEx, ATEX, Canada (CSA), Kazakhstan (operating licence), Russia (GOST R), Serbia (SRPS),
Ukraine (TR), USA (FM, UL), Belarus (operating licence)Further parameters
Installation in Zone 2, Division 2 and in safe areaFurther information see respective certificate and operating instructions
Technical Data
Electrical dataTransmission characteristic
Leakage current at UN ( 2 mA (unless specified otherwise)Temperature influence ( 0.25 % / 10 KTransmission frequency
In case of resistive current limiting
Im ( 50 mA ( 50 kHzIm ) 50 mA ( 100 kHz
In case of electronic current limiting
( 10 kHz
Ambient conditionsAmbient temperature -20 ... +60 °CStorage temperature -20 ... +75 °C Maximum relative humidity
95 % on average, no condensation
Mechanical dataDegree of protection
according to IEC 60529Terminal support IP20Enclosure IP40
Enclosure material polyamide 6GFConnection type 4 connection terminals (cage terminals), each maximum 1.5 mm2 finely stranded / solid wire
2 PA-terminals, each maximum 4 mm2 finely stranded / solidWeight approx 0.115 kg
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriersSeries 9002
Selection table
Version Description Type series Page
Dual-channel barriers • Connection to regulated power supply UN 9002/11 A2/4• Application for 3-wire NPN, sensors with voltage output• Low nominal current
9002/11 A2/6
• Application for 4/20 mA transmitters with 1-5 V input in the wiper• Incl. precision resistance of 250 Ω
9002/11 A2/7
• Connection to regulated power supply UN 9002/00 A2/8• Application for load cells• Channel for positive and negative potential in one module
9002/10 A2/9
• Connection of a resistance teletransmitter is possible• High precision resistance of each channel, 20 Ω ±0.1• Low temperature influence of < 50 ppm/K• Connection to regulated power supply UN
9002/22 A2/11
• Connection to regulated power supply UN 9002/22 A2/13• Function:
Channel 1 current supplyChannel 2 evaluation barrierNo safety-relevant output current Io for channel 2
• Connection to unregulated power supply on UN to channel 1• Nominal current limited to 35 mA
9002/13 A2/14
• Function:Channel 1 current supplyChannel 2 evaluation barrierNo safety-relevant output current Io for channel 2
• Connection to regulated power supply UN
9002/13 A2/16
• Function:Channel 1 current supplyChannel 2 evaluation barrierNo safety-relevant output current Io for channel 2
• Nominal current limited to 40 mA at 250 Ω load• Connection to unregulated power supply on UN to channel 1
9002/13 A2/18
• Evaluation barrier for direct current signals with max. output current Io• Suitable for potential-free contacts and floating 4/20 mA signals• Positive potential of both channels
9002/33 A2/19
• Evaluation barrier for direct current signals with max. output current Io• Application for passive signals of 4/20 mA (transmitter with 4 conductors
or more) with insulated analog input on the control system• Channel for positive and negative potential in one module
9002/34 A2/20
• Connection to regulated power supply UN• Suitable for voltage signals
9002/77 A2/21
A2
A2
A2
A2
A2
Safety barriers A2/32013-05-24·AK00·III·en
Two-channel safety barriers, potential: + / +Series 9002/11
A2/4
Series 9002/11
Two-channel safety barriers, potential: + / +
05820E01
• Connection to regulated power supply UN
• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax Safety data Order number
Uo Io Po IIC IIB
V Ω Ω mA V mA mW mH mF mH mF
121+2
99- -
10431043- -
11561156- -
7.77.7- -
121212
121224
404070
24024063
1.411.411.1
850850230
997.1
9002/11-120-024-001
121+2
101- -
4545- -
5252- -
10019- -
131.613
32139360
1040161170
0.19240.17
11000.79
1.6911.3
61005
9002/11-130-360-001 *)
121+2
1010- -
953953- -
978978- -
1010- -
13.713.713.7
14.514.529
5050100
16016043
0.790.790.67
560560160
554.18
9002/11-137-029-001
121+2
1616- -
14231423- -
15761576- -
1010- -
19.919.919.9
151530
7575150
16016040
0.2230.2230.223
560560150
1.421.421.42
9002/11-199-030-001
121+2
22.517.5- -
321416- -
358463- -
6237- -
262026
8751138
570260850
2.7140.81
0.0990.220.087
15.4545.1
0.771.410.67
9002/11-260-138-001
121+2
2525- -
321321- -
358358- -
6969- -
282828
9393186
6506501300
22- -
0.0830.083- -
13132.8
0.650.650.551
9002/11-280-186-001
121+2
256- -
32159- -
35868- -
6988- -
289.628
89180269
6304301050
2.20.6- -
0.0833.6- -
1450.56
0.65260.62
9002/11-280-293-001
*) max. leakage current Ileak ( 10 mA
Functional data and safety-relevant maximum valuesUN Nominal voltage Imax Maximum output current Po Maximum powerRmin Minimum resistance of the safety
barrierUo Maximum voltage Lo max. permissible external
inductanceRmax Maximum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
+ve +ve
+ve
0V
+ve
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, potential: + / +Series 9002/11
Application caseLoad cell (DMS) 350 Ω or 700 Ω6 conductors + 16 V, field circuit unearthedSchematic
09963E01
Operating dataOperating voltage UN ( + 16 VVoltage for load cell and electric line
UL (at UN = + 16 V)
Current for load cell IL (at UN = + 16 V)
Safety dataMaximum voltage Uo = 19.9 VMaximum current Io = 285 mAMaximum permissibleexternal inductance Lo
IIC0.2 mH
IIB1.8 mH
Maximum permissibleexternal capacity Co
IIC0.223 μF
IIB1.42 μF
Maximum power Po = 1.42 WApplication note For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 255 mA, themaximum power to Po = 1.3 W.
3-wire NPN inputs (negative switching) of proximity switches, photocells and encodersSchematic
06601E01
Discrete 2-wire output for solenoid valves, LEDs and signalling devicesSchematic
06606E01
Hazardous area Safe area
9002/13-199-225-001
9002/11-199-030-001
9002/11-199-030-001
+16 V
0 V
Number of the load cells connected in parallel
350 Ω 700 ΩUL (V) ImA (V) UL (V) ImA (V)
1 10.4 30 12.1 172 8.3 47 10.4 303 6.9 60 9.5 414 5.9 67 8.3 47
Hazardous area Safe area
+24 V DC
NPN
VSupply
9002/11-280-186-001
+0 V
Hazardous area Safe area
9002/11-280-186-001 +24 V DC
+24 V DC
Safety barriers A2/52013-05-24·AK00·III·en
Two-channel safety barriers, potential: + / +Series 9002/11
A2/6
Two-channel safety barriers, potential: + / +
05823E01
• Application for 3-wire NPN, sensors with vol-tage output
• Low nominal current• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V mA mW mH mF mH mF
121+2
2424- -
26411979- -
29612221- -
912- -
282828
1093112
76020780
1.3500.76
0.0830.0830.065
915084
0.650.650.551
9002/11-280-112-001
Functional data and safety-relevant maximum valuesUN Nominal voltage Imax Maximum output current Po Maximum powerRmin Minimum resistance of the safety
barrierUo Maximum voltage Lo max. permissible external
inductanceRmax Maximum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
Application case3-wire NPN inputs (negative switching) of proximity switches, photocells and encodersSchematic
06597E01
Application note With this barrier all loop voltages must be checked to ensure correct function.
+ve +ve
+ve+ve
0V
RL
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
UN
/ PA
Hazardous area Safe area
+24 V DC
NPN
VSupply
9002/11-280-112-001
0 V
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, potential: + / +Series 9002/11
Two-channel safety barriers, potential: + / +
05824E01
• Application for 4/20 mA transmitter with 1-5 V input in the wiper
• Incl. precision resistance of 250 Ω• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V mA mW mH mF mH mF
121+2
256- -
32159- -
35868- -
6988- -
289.628
89180269
6304301050
2.20.6- -
0.0833.6- -
1450.56
0.65260.62
9002/11-280-293-021
Functional data and safety-relevant maximum valuesUN Nominal voltage Imax Maximum output current Po Maximum powerRmin Minimum resistance of the safety
barrierUo Maximum voltage Lo max. permissible external
inductanceRmax Maximum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
Application case2-wire, 4/20 mA transmitters - standard and HARTSchematic
11332E01
Application note This safety barrier is used if the automation system only accepts signals from 1 to 5 V.This barrier contains a 250 Ω resistor to convert the signal 1 ... 5 V.
+ve +ve
+ve+ve
0V
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
+24 V DC4 ... 20 mA
9002/11-280-293-021 +1 ... 5 VInput
V
Hazardous area Safe area
A2
A2
A2
A2
Safety barriers A2/72013-05-24·AK00·III·en
Two-channel safety barriers, potential: - / -Series 9002/00
A2/8
Series 9002/00
Two-channel safety barriers, potential: - / -
05822E01
• Connection to regulated power supply UN
• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V mA mW mH mF mH mF
121+2
99- -
10431043- -
11561156- -
7.77.7- -
121212
121224
404070
24024063
1.411.411.1
850850230
997.1
9002/00-120-024-001
121+2
22.517.5- -
321416- -
358463- -
6237- -
262026
8751138
540245785
2.7140.81
0.0990.220.087
15.4545.1
0.771.410.67
9002/00-260-138-001
121+2
2525- -
321321- -
358358- -
6969- -
282828
9393186
6506501300
22- -
0.0830.083- -
13132.8
0.650.650.551
9002/00-280-186-001
Functional data and safety-relevant maximum valuesUN Nominal voltage Imax Maximum output current Po Maximum powerRmin Minimum resistance of the safety
barrierUo Maximum voltage Lo max. permissible external
inductanceRmax Maximum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
Application caseVibration sensorSchematic
06615E01
Operating dataOperating voltage UN = - 24VSeries resistance of the safety barrier
R = 358 Ω
Safety dataMaximum voltage Uo = 26 VMaximum current Io = 138 mAMaximum permissibleexternal inductance Lo
IIC0.81 mH
IIB5.1 mH
Maximum permissibleexternal capacity Co
IIC0.087 μF
IIB0.67 μF
Maximum power Po = 850 mWApplication note Application of the barrier for Bentley Nevada and Metrix position transducer. This barrier has negative
potential; for a positive potential, use the barrier 9002/11-260-138-001.
-ve -ve
-ve-ve
0V
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
UN
/ PA
Hazardous area
9002/00-260-138-001
Safe area
-24 V DC max.Sensor
Transducer Input
0 V
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, potential: + / -Series 9002/10
Series 9002/10
Two-channel safety barriers, potential: + / -
05821E01
• Application for load cells• Channel for positive and negative potential in
one module• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V mA mW mH mF mH mF
121+2
66- -
490490- -
543543- -
1111- -
9.339.3318.7
202020
505090
909090
3.93.90.27
330330330
29291.64
9002/10-187-020-001
121+2
66- -
4242- -
4949- -
122122- -
9.339.3318.7
270270270
6306301260
0.230.230.23
3.93.90.27
2.22.22.2
29291.64
9002/10-187-270-001
Functional data and safety-relevant maximum valuesUN Nominal voltage Imax Maximum output current Po Maximum powerRmin Minimum resistance of the safety
barrierUo Maximum voltage Lo max. permissible external
inductanceRmax Maximum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
Intrinsically safefield device(s)
Control roomequipment
+ve +ve
-ve-ve
0V
Safe areaHazardous area
UN
/ PA
Safety barriers A2/92013-05-24·AK00·III·en
Two-channel safety barriers, potential: + / -Series 9002/10
A2/10
Application caseLoad cell (DMS) 350 Ω or 700 Ω6 conductors +/- 7.5 V (15 V), field circuit unearthedSchematic
09962E01
Operating dataOperating voltage UN ( +/- 7.5 V (15 V)Voltage for load cell and electric line
UL (at UN ( +/- 7.5 V)
Current for load cell IL (at UN ( +/- 7.5 V)
Safety dataMaximum voltage Uo = 18.7 VMaximum current Io = 330 mAMaximum permissibleexternal inductance Lo
IIC0.18 mH
IIB1.45 mH
Maximum permissible external capacity Co
IIC0.27 μF
IIB1.64 μF
Maximum power Po = 1.45 WApplication note For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 310 mA, the maximum power to Po = 1.36 W.
Hazardous area Safe area
9002/10-187-270-001
9002/10-187-020-001
9002/77-093-040-001
+7,5 V
-7,5 V
Number of the load cells connected in parallel
350 Ω 700 Ω
UL (V) ImA (V) UL (V) ImA (V)
1 11.6 35 13.2 19
2 9.6 55 11.6 35
3 8 70 10.6 45
4 7 80 9.6 55
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, potential: ~ / ~Series 9002/22
Series 9002/22
Two-channel safety barriers, potential: ~ / ~
05835E01
• Connection of a resistance teletransmitter is possible
• High precision resistance of each channel, 20 Ω ±0.1
• Low temperature influence of < 50 ppm/K• Connection to regulated power supply UN
• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V mA mW mH mF mH mF
121+2
0.70.71.4
19.919.9- -
20.120.1- -
3333- -
1.61.63.2
150150300
6060120
1.31.30.2
100100100
771.8
100010001000
9002/22-032-300-111 *)
*) max. leakage current Ileak ( 10 mA
Functional data and safety-relevant maximum valuesUN Nominal voltage Imax Maximum output current Po Maximum powerRmin Minimum resistance of the safety
barrierUo Maximum voltage Lo max. permissible external
inductanceRmax Maximum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
+/-ve
+/-ve
0V
+/-ve
+/-ve
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
Safety barriers A2/112013-05-24·AK00·III·en
Two-channel safety barriers, potential: ~ / ~Series 9002/22
A2/12
Application casePt100, 2-wire circuit, field circuit unearthedSchematic
09959E01
Operating dataOperating voltage UN ( 1.4 VSeries resistance of thesafety barrier
R = 2 x (20 Ω +/- 0.1 Ω)
Measuring range ( 400 °C (IN ( 5 mA) ( 850 °C (IN ( 3 mA)
Safety dataMaximum voltage Uo = 3.2 VMaximum current Io = 300 mAMaximum permissible external inductance Lo
IIC0.2 mH
IIB1.8 mH
Maximum permissibleexternal capacity Co
IIC100 μF
IIB1000 μF
Pt100, 3-wire circuit, field circuit unearthedSchematic
09960E01
Operating dataOperating voltage UN ( 1.4 VSeries resistance of the safety barrier
R = 2 x (20 Ω +/- 0.1 Ω)
Measuring range ( 400 °C (IN ( 5 mA) ( 850 °C (IN ( 3 mA)
Safety dataMaximum voltage Uo = 3.2 VMaximum current Io = 450 mAMaximum permissibleexternal inductance Lo
IIC0.12 mH
IIB0.5 mH
Maximum permissible external capacity Co
IIC100 μF
IIB1000 μF
Hazardous area
9002/22-032-300-111
Safe area
RTDInput
T
Hazardous area
9002/22-032-300-111
Safe area
9001/02-016-150-111
T
RTDInput
SupplyVoltage
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, potential: ~ / ~Series 9002/22
Two-channel safety barriers, potential: ~ / ~
05845E01
• Connection to regulated power supply UN
• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V mA mW mH mF mH mF
121+2
5.55.511
8484- -
9595- -
5757- -
7.97.915.8
100100200
198198395
440.5
8.88.80.478
15154
1151152.88
9002/22-158-200-001
121+2
9918
10431043- -
11561156- -
7.77.7- -
121224
121224
404080
24024041
1.411.410.125
850850145
990.93
9002/22-240-024-001
121+2
9918
158158- -
177177- -
5050- -
121224
8080160
240240480
660.7
1.411.410.125
22224
990.93
9002/22-240-160-001
Functional data and safety-relevant maximum valuesUN Nominal voltage Imax Maximum output current Po Maximum powerRmin Minimum resistance of the safety
barrierUo Maximum voltage Lo max. permissible external
inductanceRmax Maximum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
Application casewith RS 232Schematic
06624E01
+/-ve
+/-ve
0V
+/-ve
+/-ve
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
9002/22-240-160-001
Tx / Rx
GND
Tx / Rx
GND
RS-232
Hazardous area Safe area
InterfaceModule
Intrinsically SafeField Device
A2
A2
A2
Safety barriers A2/132013-05-24·AK00·III·en
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +Series 9002/13
A2/14
Series 9002/13
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +
05439E01
• Function:Channel 1 current supplyChannel 2 evaluation barrierNo safety-relevant output current Io for channel 2
• Nominal current limited to 40 mA at 250 Ω load
• Connection to unregulated power supply on UN to channel 1
• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax ãU Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V V mA mW mH mF mH mF
121+2
20 - 3522- -
216- -- -
243- -- -
86- -- -
- -3.5- -
25.225.225.2
1180121
74020760
1.3501.25
0.1070.1070.104
7.41507.35
0.820.820.8
9002/13-252-121-041 *)
*) only for channel 1: leakage current at 24 V / 35 V Ileak ( 1 mA / 10 mA
Functional data and safety-relevant maximum valuesUN Nominal voltage ãU Additional voltage drop across the
safety barrierLo max. permissible external
inductanceRmin Minimum resistance of the safety
barrierUo Maximum voltage Co max. permissible external capacity
Rmax Maximum resistance of the safety barrier
Io Maximum current
Imax Maximum output current Po Maximum power
+ve +ve
0V
+ve +ve
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +Series 9002/13
Application caseAnalog output (current source) for I/P converter etc., field circuit unearthedSchematic
09953E01
Operating dataOperating voltage UN = + 20 ... 35 VOperating current IN = 0 ... 22 mAMaximum voltage drop at the safety barrier
ΔUmax ( 8.9 V
Safety dataMaximum voltage Uo = 25.2 VMaximum current Io = 121 mAMaximum permissibleexternal inductance Lo
IIC1.25 mH
IIB7.35 mH
Maximum permissible external capacity Co
IIC0.104 μF
IIB0.8 μF
Maximum power Po = 763 mWAnalog output (current source) for I/P converter etc., field circuit unearthedSchematic
06604E01
Operating dataOperating voltage UN = + 20 ... 35 VOpen-circuit output voltage (terminal 3 4, In = 0) UL)
UN ( 24 VUN - 3.5 V
UN > 24 V21 V
Operating current IN = UL / 243 Ω + RL
Safety dataMaximum voltage Uo = 25.2 VMaximum current Io = 121 mAMaximum permissibleexternal inductance Lo
IIC1.25 mH
IIB7.35 mH
Maximum permissibleexternal capacity Co
IIC0.104 μF
IIB0.8 μF
Maximum power Po = 760 mWApplication note This safety barrier is used if the automation system activates the analog output signal in the return
(negative) line. The field device and automation system are not earthed and unregulated power supply can be used.
4 ... 20 mA9002/13-252-121-041
+20 ... 35 V DC
Hazardous area Safe area
Hazardous area Safe area
9002/13-252-121-041
+20 ... 35 V DC
A2Safety barriers A2/152013-05-24·AK00·III·en
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +Series 9002/13
A2/16
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +
05826E01
• Function:Channel 1 current supplyChannel 2 evaluation barrierNo safety-relevant output current Io for chan-nel 2
• Connection to regulated power supply UN
• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax ãU Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V V mA mW mH mF mH mF
121+2
1616- -
95- -- -
108- -- -
148- -- -
- -2- -
19.919.919.9
2223225
1100151120
0.3910000.37
0.2230.2230.213
3.1810003.15
1.421.421.38
9002/13-199-225-001 *)
121+2
2424- -
321- -- -
358- -- -
67- -- -
- -2- -
282828
90393
63021651
2.2502
0.0830.0830.08
1415013
0.650.650.636
9002/13-280-093-001
121+2
2424- -
269- -- -
290- -- -
82- -- -
- -2- -
282828
1073110
74921770
1.35501.25
0.0830.0830.08
9.61509
0.650.650.635
9002/13-280-110-001
*) only for channel 2: max. leakage current Ileak ( 10 mA
Functional data and safety-relevant maximum valuesUN Nominal voltage ãU Additional voltage drop across the
safety barrierLo max. permissible external
inductanceRmin Minimum resistance of the safety
barrierUo Maximum voltage Co max. permissible external capacity
Rmax Maximum resistance of the safety barrier
Io Maximum current
Imax Maximum output current Po Maximum power
+ve +ve
0V
+ve+ve
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +Series 9002/13
Application caseLoad cell (DMS) 350 Ω or 700 Ω6 conductors + 16 V, field circuit unearthedSchematic
09963E01
Operating dataOperating voltage UN ( + 16 VVoltage for load cell and electric line
UL (at UN = + 16 V)
Current for load cell IL (at UN = + 16 V)
Safety dataMaximum voltage Uo = 19.9 VMaximum current Io = 285 mAMaximum permissibleexternal inductance Lo
IIC0.2 mH
IIB1.8 mH
Maximum permissibleexternal capacity Co
IIC0.223 μF
IIB1.42 μF
Maximum power Po = 1.42 WApplication note For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating data remains
unchanged. The safety-relevant maximum current is reduced to Io = 255 mA, the maximum power to Po = 1.3 W.
Discrete 2-wire output for solenoid valves, LEDs and signalling devicesSchematic
06605E01
Application note This barrier is suitable for use with regulated power supplies and earthed return circuits. The nominal voltage is 24 V.2-wire 4/20 mA I/P converters and control valves - standard and HART, 4/20 mA indicatorsSchematic
11334E01
Application note This safety barrier is used if the automation system activates the analog output signal in the return (negative) line. The field device and automation system are not earthed and a regulated power supply must be used. At an operating current of 0 ... 22 mA, the maximum voltage drop across the barrier will be 8.4 V.
Hazardous area Safe area
9002/13-199-225-001
9002/11-199-030-001
9002/11-199-030-001
+16 V
0 V
Number of the load cellsconnected in parallel
350 Ω 700 ΩUL (V) ImA (V) UL (V) ImA (V)
1 10.4 30 12.1 172 8.3 47 10.4 303 6.9 60 9.5 414 5.9 67 8.3 47
Hazardous area Safe area
9002/13-280-110-001
+24 V DC
4 ... 20 mA9002/13-280-110-001
+24 V DC
Hazardous area Safe area
Safety barriers A2/172013-05-24·AK00·III·en
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +Series 9002/13
A2/18
Two-channel safety barriers, safety barrier potential: + / evaluation barrier potential: +
05827E01
• Function:Channel 1 current supplyChannel 2 evaluation barrierNo safety-relevant output current Io for chan-nel 2
• Connection to unregulated power supply on UN to channel 1
• Nominal current limited to 35 mA• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Rmin Rmax Imax ãU Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω mA V V mA mW mH mF mH mF
121+2
20 - 3526- -
292- -- -
327- -- -
52- -- -
- -3.5- -
282828
970100
67921700
1.8501.55
0.0830.0830.08
1215011
0.650.650.635
9002/13-280-100-041 *)
*) only for channel 1: leakage current < 26 V / > 26 V Ileak ( 1 mA / 35 mA
Functional data and safety-relevant maximum valuesUN Nominal voltage ãU Additional voltage drop across the
safety barrierLo max. permissible externa
l inductanceRmin Minimum resistance of the safety
barrierUo Maximum voltage Co max. permissible external capacity
Rmax Maximum resistance of the safety barrier
Io Maximum current
Imax Maximum output current Po Maximum power
Application case3-wire PNP inputs (positive switching) of proximity switches, photocells and encodersSchematic
06595E01
+ve +ve
0V
+ve +ve
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
Hazardous area Safe area
9002/13-280-100-041
+20 ... 35 V DC
PNP
V
+0 V
Supply
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: +Series 9002/33
Series 9002/33
Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: +
05829E01
• Evaluation barrier for direct current signals with max. output current Io
• Suitable for potential-free contacts andfloating 4/20 mA signals
• Positive potential of both channels• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Imax ãU Safety data Order number
Uo Io IIC IIB
Lo Co Lo Co
V mA V V mA mH mF mH mF
121+2
25.525.5- -
6060- -
3.5 *)3.5 *)- -
282828
000
100010001000
0.0830.0830.083
100010001000
0.650.650.65
9002/33-280-000-001
*) 2.5 V to 20 mA
Functional data and safety-relevant maximum valuesUN Nominal voltage Uo Maximum voltage Co max. permissible external capacityImax Maximum output current Io Maximum currentãU Additional voltage drop across the
safety barrierLo max. permissible external
inductance
+ve +ve
+ve
0V
+ve
UN
/ PA
Hazardous area
Intrinsically safefield device(s)
Safe area
Control roomequipment
A2
A2
A2
A2
A2
A2
A2
Safety barriers A2/192013-05-24·AK00·III·en
Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: -Series 9002/34
A2/20
Series 9002/34
Two-channel safety barriers, evaluation barrier potential: + / evaluation barrier potential: -
05828E01
• Evaluation barrier for direct current signals with max. output current Io
• Application for passive signals of 4/20 mA (transmitter with 4 conductors or more) with insulated analog input on the control system
• Channel for positive and negative potential in one module
• Installation permitted in Division 2 and Zone 2
Selection table
Channel UN Imax ãU Safety data Order number
Uo Io IIC IIB
Lo Co Lo Co
V mA V V mA mH mF mH mF
121+2
+ 16- 521
100100- -
3.5 *)3.5 *)- -
28828
000
100010001000
0.228.40.083
100010001000
1.141000.65
9002/34-280-000-001
*) 2.5 V to 20 mA
Functional data and safety-relevant maximum valuesUN Nominal voltage Uo Maximum voltage Co max. permissible external capacityImax Maximum output current Io Maximum currentãU Additional voltage drop across the
safety barrierLo max. permissible external
inductance
Application caseVibration sensorSchematic
09951E011
Operating dataOperating current IN = 0 ... 22 mALoad RL (750 ΩMaximum voltage drop at the safety barrier
Δ Umax ( 3.5 V
Safety dataMaximum voltage Uo = 28 VMaximum current Io = 0 mAMaximum permissibleexternal inductance
The inductance is determined depending on the maximum current of the transmitter
Maximum permissibleexternal capacity Co
IIC0.083 μF
IIB0.65 μF
Maximum power Po = 0 mWApplication note A potential-free input is required for the circuit.
If the input is earthed, (RL to /PA), the safety barrier 9001/03-280-000-001 can be used.
+ve
-ve
+ve
-ve
0V
RLUN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
4 ... 20 mA9002/34-280-000-001
Hazardous area Safe area
Safety barriers 2013-05-24·AK00·III·en
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriers, star barrier / star barrierSeries 9002/77
Series 9002/77
Two-channel safety barriers, star barrier / star barrier
05836E01
• Connection to regulated power supply UN
• Suitable for voltage signals• Installation permitted in Division 2 and Zone 2• AC version
Selection table
Channel UN Rmin Rmax Safety data Order number
Uo Io Po IIC IIB
Lo Co Lo Co
V Ω Ω V mA mW mH mF mH mF
121+2 6
492492- -
545545- -
9.39.39.3
202040
505090
909023
4.14.14.1
33033087
313131
9002/77-093-040-001
121+2 6
7171- -
82.182.1- -
9.39.39.3
150150300
350350700
1.31.30.2
4.14.14.1
771.8
313131
9002/77-093-300-001
121+2 6
6060- -
69.269.2- -
101010
200200400
5005001000
0.50.50.15
333
440.8
20.220.220.2
9002/77-100-400-001
121+2 12
111111- -
126126- -
151515
150150300
5605601130
1.31.30.2
0.580.580.58
771.8
3.553.553.55
9002/77-150-300-001
121+2 18
321321- -
358358- -
222222
7373146
400400800
771.4
0.1650.1650.165
26267.4
1.141.141.14
9002/77-220-146-001 *)
121+2 18
159159- -
180180- -
222222
148148296
8108101630
1.351.350.24
0.1650.1650.165
7.27.21.84
1.141.141.14
9002/77-220-296-001 *)
121+2 24
657657- -
730730- -
282828
474794
330330660
10.110.11.96
0.0830.0830.083
303012.5
0.650.650.65
9002/77-280-094-001
*) Ambient temperature - 20 ... + 50 °C
Functional data and safety-relevant maximum valuesUN Nominal voltage Uo Maximum voltage Lo max. permissible external
inductanceRmin Minimum resistance of the safety
barrierIo Maximum current Co max. permissible external capacity
Rmax Maximum resistance of the safety barrier
Po Maximum power
+ve/-ve
0V
+ve/-ve
+ve/-ve
+ve/-ve
UN
/ PA
Intrinsically safefield device(s)
Control roomequipment
Safe areaHazardous area
Safety barriers A2/212013-05-24·AK00·III·en
Two-channel safety barriers, star barrier / star barrierSeries 9002/77
A2/22
2013-05-24·AK00·III·enApplication caseLoad cell (DMS) 350 Ω or 700 Ω6 conductors +/- 7.5 V (15 V), field circuit unearthedSchematic
09962E01
Operating dataOperating voltage UN ( +/- 7.5 V (15 V)Voltage for load cell and electric line
UL (at UN ( +/- 7.5 V)
Current for load cell IL (at UN ( +/- 7.5 V)
Safety dataMaximum voltage Uo = 18.7 VMaximum current Io = 330 mAMaximum permissible external inductance Lo
IIC0.18 mH
IIB1.45 mH
Maximum permissible external capacity Co
IIC0.27 μF
IIB1.64 μF
Maximum power Po = 1.42 WApplication note For 4-wire circuits (without sense) the respective safety barrier might be unnecessary. The operating
data remains unchanged. The safety-relevant maximum current is reduced to Io = 310 mA, themaximum power to Po = 1.36 W.
Vibration sensorSchematic
09958E01
Operating dataMaximum series resistance of the safety barrier
Rmax = 2 x 82.1 Ω
Sensor voltage U ( +/- 4 Veff / 6 VppSafety dataMaximum voltage Uo = 9.3 VMaximum current Io = 300 mAMaximum permissibleexternal inductance Lo
IIC0.2 mH
IIB1.8 mH
Maximum permissibleexternal capacity Co
IIC4.1 μF
IIB31 μF
Hazardous area Safe area
9002/10-187-270-001
9002/10-187-020-001
9002/77-093-040-001
+7,5 V
-7,5 V
Number of the load cells connected in parallel
350 Ω 700 Ω
UL (V) ImA (V) UL (V) ImA (V)
1 11.6 35 13.2 19
2 9.6 55 11.6 35
3 8 70 10.6 45
4 7 80 9.6 55
Hazardous area
9002/77-093-300-001
Safe area
VoltageInput
Safety barriers
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
A2
Two-channel safety barriersSeries 9002
Series 9002
Accessories and Spare Parts
Designation Figure Description Art. no. Weight
kg
Back-up fuse09919E00
for all safety barriers of Series 9001, 9002 and 9004Packaging unit: 5 pieces
158964 0.008
Label carrier
09920E00
158977 0.002
Labelling sheet
09921E00
perforated, for automatic inscriptionFormat: DIN A4
158973 0.005
Adapter
09922E00
158826 0.006
Clamping base, moulded material
09924E00
165283 0.004
DIN rail
03856E00
NS 35 / 15 (available by the metre) 103714 1.410
Protective conductor terminal
09926E00
USLKG 5 (clamping range ( 4 mm2) 112760 0.012
Earthing terminal
09926E00
USLKG 6 N (clamping range ( 6 mm2) 112599 0.030
Fuse holder
09927E00
158834 0.020
Insulation andfastening material
09928E00
for mounting rail NS 35/15 158828 0.023
Safety barriers A2/232013-05-24·AK00·III·en
Two-channel safety barriersSeries 9002
A2/24
Dimensional drawings (all dimensions in mm / inches) - subject to modifications
09929E00
Safety barrier 9001, 9002, 9004
09930E00
09932E00
09933E00
Safety barrier 9001, 9002, 9004mounted on the mounting rail LV 35/15EN 50 022
Safety barrier 9001, 9002, 9004mounted on the mounting rail LV 32 EN 50 035 with adaptor and clamping base made of moulded material
Safety barrier 9001, 9002, 9004mounted onmounting plate with adaptor
We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.
7m
m / 2
."
283
10 mm / 4.0 "3 6
12 m
m / 0
.4"
78
0 m
m /
3.1
5 "
95 m
m / 3
.74 "
66 mm2.60 "
38 mm1.50 "
76
mm
/ 3
.00
"
66 mm2.60 "
38 mm1.50 "
Safety barriers 2013-05-24·AK00·III·en