Upload
others
View
8
Download
1
Embed Size (px)
Citation preview
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
71
SIMULATION OF THERMODYNAMIC ANALYSIS OF
CASCADE REFRIGERATION SYSTEM WITH
ALTERNATIVE REFRIGERANTS
Mr. PARTHIBAN KASI
Assistant Professor, Department of Mechanical Engineering,
Velammal Institute of Technology, Chennai, India
ABSTRACT
The main aim of this project is to analyses the cascade refrigeration system by employing
various alternative refrigerant pairs and choosing the best pair for higher temperature circuit (HTC)
and lower temperature circuit (LTC). The analysis was done in various refrigerants pairs which are
R134a/R23, R290/R23, R404A/R23, R407C/R23, R410A/R23, R134a/R508B, R290/R508B,
R404A/R508B, R407C/R508B, R410A/R508B, R134a/R170, R290/R170, R404A/R170,
R407C/R170 and R410A/R170. Assuming the degrees of sub cooling and superheating as 5°C and
10°C, respectively. The condenser temperature in higher temperature circuit (HTC) was varied from
30°C to 50°C and evaporator temperature in lower temperature circuit (LTC) was varied from -70 to
-50°C. The intermediate heat exchanger temperature is about -20°C. Furthermore, the efficiencies of
the compressors are assumed to be equal as 0.7. It has been found that the coefficient of performance
(COP) of the cascade refrigeration system increases and the mass flow rate of higher temperature
circuit increases, along with the work of compressor with rise in evaporator temperature for all
refrigerant pairs. On the other hand, the COP of the cascade refrigeration system decreases and the
mass flow rate of higher temperature circuit increases, also there is increase in work of compressor
with increase in condenser temperature. Finally, the refrigerant pair R134a–R170 has the highest
COP and lowest mass flow rate, while R404A–R508B has the lowest COP and highest mass flow
rate.
Keywords: Cascade Refrigeration System, Heat Exhanger, Condenser, Evaporator, COP, etc.
1. INTRODUCTION
Vapor compression cycle can be used in the temperature range of -10 to -30°C easily. And
low-temperature refrigeration systems are typically required in the temperature range from –30°C to –
100°C for applications in food, pharmaceutical, chemical, and other industries, e.g., blast freezing,
INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND
TECHNOLOGY (IJMET)
ISSN 0976 – 6340 (Print)
ISSN 0976 – 6359 (Online)
Volume 6, Issue 1, January (2015), pp. 71-91
© IAEME: www.iaeme.com/IJMET.asp
Journal Impact Factor (2014): 7.5377 (Calculated by GISI)
www.jifactor.com
IJMET
© I A E M E
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp.
cold storages, liquefaction of gases such as natural gas, etc. At such low temper
compression systems with reciprocating compressors are generally not feasible due to high pressure
ratios. A high pressure ratio implies high discharge and oil temperatures and low volumetric
efficiencies and, hence it has low COP valu
volumetric efficiency curves and have been reported to achieve temperatures as low as
50°C in single-stage systems.
Fig.1
Cascade refrigeration cycle can be u
stage units are used that are thermally coupled through evaporator/conden
Fig. 1 for a two-circuit cascade unit. Each circuit has a different refrigerant suitable for that
temperature, the lower temperature units
Generally, two-circuit and rarely three
temperature it can be easily achieved in a single
cascade system due to irreversibility and losses associated with a large number of components.
2. THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM
Fig. 2 shows vapor compression cascade refrigeration system un
consists of low and high side refrigeration systems indicated as A and B. Refrigeration systems A
and B are coupled to each other by means of a heat exchanger in which the total heat from
refrigeration system A is rejected to refri
are usually different from each other although there are some cases where the same refrigerant can be
used in both systems.
Fig. 2: P-H diagram of cascade refrigeration system
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976
), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
72
cold storages, liquefaction of gases such as natural gas, etc. At such low temperatures, single
compression systems with reciprocating compressors are generally not feasible due to high pressure
ratios. A high pressure ratio implies high discharge and oil temperatures and low volumetric
low COP values. Screw and scroll compressors have relatively flat
volumetric efficiency curves and have been reported to achieve temperatures as low as
Fig.1: Cascade refrigeration system
ascade refrigeration cycle can be used to achieve low temperatures, where series of single
stage units are used that are thermally coupled through evaporator/condenser cascades, as shown in
circuit cascade unit. Each circuit has a different refrigerant suitable for that
perature, the lower temperature units are progressively using lower boiling point refrigerants.
circuit and rarely three-circuit cascade systems are used. In general, if the desired
easily achieved in a single-stage machine, it will be more efficient than a
cascade system due to irreversibility and losses associated with a large number of components.
THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM
compression cascade refrigeration system under consideration, which
consists of low and high side refrigeration systems indicated as A and B. Refrigeration systems A
and B are coupled to each other by means of a heat exchanger in which the total heat from
refrigeration system A is rejected to refrigeration system B. The refrigerants flowing in both systems
are usually different from each other although there are some cases where the same refrigerant can be
H diagram of cascade refrigeration system
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
atures, single-stage
compression systems with reciprocating compressors are generally not feasible due to high pressure
ratios. A high pressure ratio implies high discharge and oil temperatures and low volumetric
es. Screw and scroll compressors have relatively flat
volumetric efficiency curves and have been reported to achieve temperatures as low as –40°C to –
sed to achieve low temperatures, where series of single-
ser cascades, as shown in
circuit cascade unit. Each circuit has a different refrigerant suitable for that
progressively using lower boiling point refrigerants.
circuit cascade systems are used. In general, if the desired
hine, it will be more efficient than a
cascade system due to irreversibility and losses associated with a large number of components.
THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM
der consideration, which
consists of low and high side refrigeration systems indicated as A and B. Refrigeration systems A
and B are coupled to each other by means of a heat exchanger in which the total heat from
geration system B. The refrigerants flowing in both systems
are usually different from each other although there are some cases where the same refrigerant can be
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
73
Thermodynamic analysis is based on the energy and irreversibility analyses of the elements
of the two stage vapor compression cascade refrigeration system. Each element in the system is
treated as a control volume. The equations energy and continuity for a control volume can be written
as
2 2
.. .
2 2
i c v oc v i i i o o o c v
V dE VQ m h gZ m h gZ W
dt
+∑ + + = +∑ + + +
.0
c vo i
d mm m
d t+ ∑ − ∑ =
where Qc.v, Wc.v and Ec.v are the heat transfer rate to the control volume, the actual power done
by the control volume and the energy within the boundary of the control volume respectively, while
m, h, V2/2, gZ are the mass flow rate specific enthalpy, specific kinetic energy and potential energy
of the fluid at the inlet or outlet conditions.
It is assumed that sub cooling occurs in the liquid line while superheating occurs in the suction
line inside the refrigerated space, changes in kinetic and potential energies and pressure drop through
the cycle are negligible. It is assumed that steady-state and uniform flow conditions exist through the
components of the cascade refrigeration system, in other words, the condition of the mass at each
point of the components doesn’t change with time. It is also assumed that isentropic efficiencies of the
compressors which are equal, and the heat loss from the compressors, heat exchanger and expansion
valves are negligible.
.0
c v
o i A
d E
d t
m m m
=
∑ = ∑ =
The heat transfer rate of the evaporator (refrigeration capacity) Qe is
e A eQ m q=
where qe and mA are the specific refrigeration capacity of system A and the refrigerant mass flow rate
flowing through system A, respectively.
The total work input to the compressors in both systems can be calculated from
where mB is the refrigerant mass flow rate flowing through system B, while wcompA and wcompB are the
specific work of compressions in system A and system B, respectively.
The coefficient performance of the cascade system COPcas is
ec a s
t o t
QC O P
W=
tot A compA B compBW m w m w= +
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
74
2.1 Low Temperature Side of the Cascade
Refrigeration System As mentioned earlier, the low temperature side of the cascade refrigeration system consists of
compressor A, one side of the heat exchanger, thermostatic expansion valve A, and the evaporator.
In the refrigeration cycle A, the refrigerant enters compressor A at state 1 as superheated
vapour at low pressure and low temperature. From state 1 to 2, the refrigerant is compressed and
discharged as superheated vapour at high pressure and high temperature. Then, it enters the heat
exchanger where it condenses and rejects heat to the evaporator of system B. It leaves the heat
exchanger at state 3 as high pressure saturated liquid. From state 3 to 4, the refrigerant is sub cooled
as a result of heat transfer to the condensing medium. At state 4, the refrigerant enters expansion valve
A, where its pressure is reduced in a throttling process to the evaporator pressure. After leaving the
valve at state 5, it enters the evaporator, where it absorbs heat from the refrigerated space. At state 6, it
leaves the evaporator as saturated vapour at low pressure and low temperature.
When the assumptions mentioned previously are taken into consideration, specific work of
compression for the compressor can be written as
2 1c o m p Aw h h= −
where h1 and h2 are the specific enthalpies across compressor A.
The refrigerants are simulated as ideal gases during compression process. Hence the specific
work of compression can also be expressed by
2 1( )r
c o m p
c o m p
mw h h
η= −
where Pc, Pe, and Tcomp,i are the condenser pressure, evaporator pressure, and the temperature
at compressor inlet, respectively, while ηisen is the isentropic efficiency of the compressor; cp and K
are constant pressure specific heat and specific heat ratio of the refrigerant, respectively. Isentropic
efficiency of the compressor can be expressed in terms of polytrophic efficiency ηp; pressure ratio
and specific heat ratio.
The specific heat rejected in the heat exchanger can be written as
( )2 4H E Aq h h
−= −
where h4 is the enthalpy of the refrigerant at the expansion valve inlet. The enthalpy of the sub
cooled liquid at state 4 can be calculated by assuming that saturated liquid at point 3 is cooled to
state 4 at a constant pressure. Therefore, specific enthalpy at state 4 can be expressed as
( )3 43 ,4 p lh h c T T= − −
where cp,l is the specific heat at constant pressure of refrigerant in liquid state between states 3 and 4,
h3 the enthalpy of saturated liquid at the heat exchanger exit, T3 the saturation temperature in the heat
exchanger and T4 is the temperature at the expansion valve inlet.
During the throttling process in the expansion valve, it is assumed that there is no heat
transfer to the environment, which results in
54h h=
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
75
The specific refrigeration capacity of refrigeration cycle A can be written as
1 5( )req m h h= −
where h5 is the enthalpy of refrigerant at evaporator inlet. The enthalpy of superheated vapour at
state 1 can be calculated by assuming that saturated vapour at state 6 which is heated to state 1 at a
constant pressure. Therefore, specific enthalpy at state 1 can be expressed as
( )1 6 , 1 6p vh h c T T= + −
Where cp,v is the constant pressure specific heat of refrigerant in vapor state between states 6 and 1,
T6 is the evaporator temperature, and T1 is the temperature at the compressor inlet.
2.2 High Temperature Side of the Cascade
Refrigeration System In refrigeration system B, the same processes exist and same assumptions are valid as in
system A. The specific work of compression for the adiabatic compression process in system B can
be written as
8 7com pBw h h= −
where h7 and h8 are the specific enthalpies across compressor B.
8 7( )r
co m p
co m p
mw h h
η= −
The rate of enthalpy change of the condenser can be determined from
10 8( )rcq m h h= −
where h10 is the enthalpy of the refrigerant at the expansion valve inlet. The enthalpy of sub cooled
liquid can be calculated using the same approach. Therefore, specific enthalpy at state 10 can be
expressed as
( )10 9 , 10 9p lh h c T T= − −
where cp,l is the constant pressure specific heat of the refrigerant in liquid state between states 9 and
10, T9 is the condenser temperature and T10 is the temperature at the expansion valve inlet.
The assumption in refrigeration system A can also be used for the throttling process in
expansion valve B,
10 8h h=
where h10 and h11 are the enthalpies of refrigerant at the expansion valve inlet and exit, respectively.
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
76
The specific heat absorbed in the heat exchanger can be written as
( )7 1 1H E Bq h h− = −
The specific enthalpy of superheated vapor at state 7 can be expressed by
( )7 1 2 , 7 1 2p vh h c T T= + −
where cp,v is the constant pressure specific heat of the superheated refrigerant vapor between states 12
and 7, h12 is the enthalpy of saturated vapor at the heat exchanger exit, T12 is the saturation
temperature in the heat exchanger, and T7 is the temperature at the compressor inlet.
2.3 Heat Exchanger
Combining refrigeration systems A and B, the heat exchanger is the key component of the
cascade system. The heat rejected from the refrigeration system A is transferred to the refrigeration
system B in the heat exchanger. It is also well insulated to provide that the total heat rejected from
refrigeration cycle A be equal to the total heat absorbed by the refrigeration system B. As a result,
the first law of thermodynamics for the heat exchanger can be written as
( ) ( )7 11 2 4B Am h h m h h− = −
A computer code based on the thermodynamic models presented above has been developed
to calculate the COPs and mass ratio of various refrigerant pairs.
3. SIMULATION METHODOLOGY
The engineering calculation and simulation of the cascade refrigeration cycle system requires
the availability of simple and efficient mathematical methods for the determination of
thermodynamic property values of the operating fluid. Values of the thermodynamic property are
necessary both at the key points in the cycle and along the process taking in the various components.
3.1 Input Data for Simulation
Condenser Temperature Tc = 30 to 50°C
Evaporator Temperature TE = -70 to -50°C
Intermediate temperature TINT = -20°C
Compressor efficiency of the system ηcomp= 0.7
Refrigerant in high temperature circuit R-134a, R-290,
R-407C, R-404A, R410A
Refrigerant in low temperature circuit R-23, R508B,
R170
Sub cooling (in HTC and LTC) 5°C
Superheating (in HTC and LTC) 10°C
By carrying out the thermodynamic analysis of the system for the conditions stated above the
values at various state points of the cascade refrigeration cycle have been obtained.
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
77
In the present work, following parameters have been computed.
• Coefficient of performance of a cascade refrigeration cycle.
• Mass Flow rate of HTC.
• Work of compression.
3.2 Selection of Working Fluid Many factors need to be considered
• Ozone depletion potential
• Global warming potential
• Combustibility
• Thermal factors
• Toxicity
• Cost
• Environmental friendliness, etc.
3.2.1 Low Temperature Circuit
Table.1: Properties of LTC refrigerants
REFRIGERANTS PROPERTIES
R-23 (Trifluormethane) BP: -82.1°C
Tcrit:25.9°C
ODP:0, GWP:12000
R-170 (Ethane) BP: -88.6°C
Tcrit:32.2°C
ODP: 0, GWP:20
R-508B BP: -87.6°C
Tcrit:11.2°C
ODP:0,GWP:13000
3.2.2 Higher Temperature Circuit
Table.2: Properties of HTC refrigerants
REFRIGERANT PROPERTIES
R-134a (Tetrafluoroethane) Boiling point: -26.1°C
Critical temperature:101.1°C
ODP: 0, GWP:1300
R-290 (Propane) Boiling point: -42.2°C
Critical temperature:96.6°C
ODP: 0, GWP:-20
R-407C Boiling point: -43.6°C
Critical temperature:85.8°C
ODP: 0, GWP:1800
R-404A Boiling point: -46.2°C
Critical temperature:72°C
ODP: 0, GWP:3900
R-410A Boiling point: -51.3°C
Critical temperature:70.5°C
ODP: 0, GWP:2100
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
78
4. RESULTS & DISCUSSIONS
Using the developed computer code, the COPs and mass flow rates of the HTC refrigerant in
the cascade refrigeration system and work of compression are determined as functions of the
evaporator temperature, condenser temperature, the intermediate temperatures of the lower and
higher temperature systems in the heat exchanger and the compressor efficiency. Then, COPs and
mass flow rates and work of compression of the considered pairs are compared and the best
refrigerant pair among them is selected.
4.1 Variation of COP with the Condenser Temperature
The changes in the COP of the cascade system will vary in the condenser temperature for an
evaporator temperature of -70°C intermediate temperature as -20°C and compressor efficiency of 0.7
respectively. As the condenser temperature of the cascade system increases, the condenser pressure
increases, while the evaporator temperature, intermediate temperature and compressor efficiency are
kept in constant. On increasing the condenser pressure, more compressor power is obtained, which
makes the COP of the cascade system for all considered refrigerant pairs to decrease.
Fig.3: COP as a function of condenser temperature
4.2 Variation of mass flow rate with the Condenser Temperature
Fig.4: Mass Flow Rate as a Function of Condenser Temperature
0.6
0.7
0.8
0.9
1
1.1
30 35 40 45 50
CO
P
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R23
R290-R23
R404A-R23
R407C-R23
R410A-R23
0.3
0.4
0.5
0.6
0.7
0.8
30 35 40 45 50
mr2
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R23
R290-R23
R404A-R23
R407C-R23
R410A-R23
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
79
The changes in the mass flow rate of the HTC refrigerant will change in the cascade
refrigeration system with respect to the condenser temperature for an evaporator temperature of -
70°C, intermediate temperature as -20°C and compressor efficiency of 0.7 respectively. As the
condenser temperature of the cascade system increases, the condenser pressure increases, while the
evaporator temperature, intermediate temperature and compressor efficiency are kept in constant. On
increasing the condenser pressure, more compressor power is obtained, which causes the mass flow
rate of the HTC refrigerant in the cascade refrigeration system for all considered refrigerant pairs to
increase. As the condenser temperature of the cascade system increases, the mass flow rate of the
HTC refrigerant in the cascade refrigeration system increases. It is seen that R290–R23 has the lowest
mass flow rate, while R134a–R23 has the highest one. The mass flow rate of R404A–R23, R407C–
R23 and R410A–R23 place in the middle range and increases and they are parallel to each other.
4.3 Variation of work of compression with the Condenser Temperature
Fig.5: Changes in Compressor Work with Condenser temperature
The change in compressor work of the refrigerant pairs increase with respect to the condenser
temperature. The figure shows, the evaporator temperature is -70°C, intermediate temperature is -
20°C and compressor efficiency is 0.7 which are kept constant. As the condenser temperature
increases, the low temperature circuit compressor’s work done (WCOMP1) decreases, but the high
temperature circuit compressor’s work done (WCOMP2) increases, and the combined effect of these
are to increase the work done. In the considered condenser temperature range, R404A–R23 has the
highest work done values, while R134a–R23 has the lowest ones. The work done of refrigerant pairs
placed in the middle range, namely R290–R23, R407C–R23 and R410A–R23, increases and they are
parallel to each other.
4.4 Variation of COP with the Evaporator Temperature
The changes in the COP of the cascade system with respect to the evaporator temperature for
an condenser temperature of 40°C, intermediate temperature as -20°C and compressor efficiency of
0.7, respectively. When condenser temperature, intermediate temperature and compressor efficiency
which are kept constant. The refrigeration effect of the cascade system increases and the specific
work of compression decreases on increasing the evaporator temperature. Consequently, the COP of
the cascade refrigeration system increases. It is seen that R134a–R23 has the highest COP, while
R404A–R23 has the lowest one. The COPs of R290–R23, R407C–R23, and R410A–R23 place in the
middle range and increase parallel to each other.
1.5
1.7
1.9
2.1
2.3
2.5
30 35 40 45 50
Wc
kW
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R23
R290-R23
R404A-R23
R407C-R23
R410A-R23
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
80
Fig.6: Changes in COP with Evaporator Temperature
4.5 Variation of mass flow rate with the Evaporator Temperature The variation in mass flow rate with the evaporator temperature for a constant condenser
temperature is 40°C, intermediate temperature is -20°C and compressor efficiency is 0.7. When the
condenser temperature, intermediate temperature and compressor efficiency which are kept constant.
The refrigeration effect of the cascade system increases and the specific work of compression
decreases on increasing the evaporator temperature. Consequently, the mass floe rate of the HTC
cascade refrigeration system increases. In the considered evaporator temperature range, R410A–R23
has the lowest mass flow rate values, while R404A–R23 has the highest ones. The mass flow rate of
refrigerant pairs placing in the middle range, namely R134a–R23, R407C–R23 and R290–R23,
increases parallel to each other.
Fig.7: Variation of mass flow rate as a function of evaporator temperature
0.8
0.9
1
1.1
1.2
1.3
-50 -55 -60 -65 -70
CO
P
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R23
R290-R23
R404A-R23
R407C-R23
R410A-R23
0.2
0.3
0.4
0.5
0.6
0.7
-50 -55 -60 -65 -70
mr2
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R23
R290-R23
R404A-R23
R407C-R23
R410A-R23
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
81
4.6 Variation of work of compression with the Evaporator Temperature
Fig.8: Variation in compressor work as a function of Evaporator temperature
The changes in compressor work of the refrigerant pairs with respect to the evaporator
temperature. The figure shows, the condenser temperature of 40°C, intermediate temperature as -
20°C and compressor efficiency of 0.7 which are kept constant. As the evaporator temperature
increases, the low temperature circuit compressor’s work done (WCOMP1) decreases but the high
temperature circuit compressor’s work done (WCOMP2) increases, and the combined effect of these
are to increase the work done. In the considered evaporator temperature range, R404A–R23 has the
highest work done values, while R134a–R23 has the lowest ones. The work done of refrigerant pairs
placing in the middle range, namely R290–R23, R407C–R23 and R410A–R23, increase parallel to
each other.
4.7 Variation of COP with the Condenser Temperature
The changes in the COP of the cascade system will vary in the condenser temperature for an
evaporator temperature of -70°C intermediate temperature as -20°C and compressor efficiency of 0.7
respectively. As the condenser temperature of the cascade system increases, the condenser pressure
increases, while the evaporator temperature, intermediate temperature and compressor efficiency are
kept in constant. On increasing the condenser pressure, more compressor power is obtained, which
makes the COP of the cascade system for all considered refrigerant pairs to decrease. In the
considered condenser temperature range, R134a–R170 has the highest COP values, while R404A–
R170 has the lowest ones. The COPs of refrigerant pairs placing in the middle range, namely
R410A–R170, R407C–R170 and R290–R170, decrease parallel to each other.
1.3
1.5
1.7
1.9
2.1
-50 -55 -60 -65 -70
Wc
kW
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R23
R290-R23
R404A-R23
R407C-R23
R410A-R23
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
82
Fig.9: Changes in COP with Condenser Temperature
4.8 Variation of mass flow rate with the Condenser Temperature
The changes in the mass flow rate of the HTC refrigerant in the cascade refrigeration system
with respect to the condenser temperature for an evaporator temperature of -70°C, intermediate
temperature as -20°C and compressor efficiency of 0.7, respectively. As the condenser temperature
of the cascade system increases, the condenser pressure also increases, while the evaporator
temperature, intermediate temperature and compressor efficiency are kept constant. On increasing
the condenser pressure, more compressor power is required, which causes the mass flow rate of the
HTC refrigerant in the cascade refrigeration system for all considered refrigerant pairs to increases.
As the condenser temperature of the cascade system increases, the mass flow rate of the HTC
refrigerant in the cascade refrigeration system increases. It is seen that R404A–R170 has the lowest
mass flow rate, while R407C–R170 has the highest one. The mass flow rate of R134a–R170, R290–
R170, and R410A–R170 place in the middle range and increases any they are parallel to each other.
Fig.10: Changes in Mass Flow Rate with Condenser Temperature
0.6
0.7
0.8
0.9
1
1.1
30 35 40 45 50
CO
P
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R170
R290-R170
R404A-R170
R407C-R170
R410A-R170
0.3
0.4
0.5
0.6
0.7
0.8
30 35 40 45 50
mr2
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R170
R290-R170
R404A-R170
R407C-R170
R410A-R170
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
83
4.9 Variation of work of compression with the Condenser Temperature
Fig.11: Variation in Compressor Work as a Function of Condenser Temperature
The changes in compressor work of the refrigerant pairs with respect to the condenser
temperature. The figure shows, the evaporator temperature of -70°C, intermediate temperature as -
20°C and compressor efficiency of 0.7 are kept constant. As the condenser temperature increases, the
low temperature circuit compressor’s work done (WCOMP1) decreases but the high temperature circuit
compressor’s work done (WCOMP2) increases, and the combined effect of these are to increase the
work done. In the considered condenser temperature range, R404A–R170 has the highest work done
values, while R134a–R170 has the lowest ones. The work done of refrigerant pairs placing in the
middle range, namely R290–R170, R407C–R170 and R410A–R170, increase parallel to each other.
4.10 Variation of COP with the Evaporator Temperature
Fig.12 Variation in COP as a Function of Evaporator Temperature
The changes in the COP of the cascade system with respect to the evaporator temperature for
an condenser temperature of 40°C, intermediate temperature as -20°C and compressor efficiency of
0.7 respectively. When condenser temperature, intermediate temperature and compressor efficiency
3
3.5
4
4.5
5
30 35 40 45 50
Wc
kW
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R170
R290-R170
R404A-R170
R407C-R170
R410A-R170
0.8
0.9
1
1.1
1.2
1.3
-50 -55 -60 -65 -70
CO
P
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R170
R290-R170
R404A-R170
R407C-R170
R410A-R170
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
84
which are kept constant. The refrigeration effect of the cascade system increases and the specific
work of compression decreases on increasing the evaporator temperature. Consequently, the COP of
the cascade refrigeration system increases. It is seen that R134a–R170 has the highest COP, while
R404A–R170 has the lowest one. The COPs of R290–R170, R407C–R170, and R410A–R170 place
in the middle range and increase parallel to each other.
4.11 Variation of mass flow rate with the Evaporator Temperature
The variation in mass flow rate with the evaporator temperature for a constant condenser
temperature of 40°C, intermediate temperature of -20°C and compressor efficiency is 0.7. When the
condenser temperature, intermediate temperature and compressor efficiency which are kept constant.
The refrigeration effect of the cascade system increases and the specific work of compression
decreases on increasing the evaporator temperature. Consequently, the mass flow rate of the HTC
cascade refrigeration system increases. In the considered evaporator temperature range, R404A–
R170 has the lowest mass flow rate values, while R134a–R170 has the highest ones. The mass flow
rate of refrigerant pairs placing in the middle range, namely R410A–R170, R407C–R170 and R290–
R170, increases parallel to each other.
Fig.13: Mass Flow Rate as a Function of Evaporator Temperature
The variation in mass flow rate with the evaporator temperature for a constant condenser
temperature of 40°C, intermediate temperature of -20°C and compressor efficiency is 0.7. When the
condenser temperature, intermediate temperature and compressor efficiency which are kept constant.
The refrigeration effect of the cascade system increases and the specific work of compression
decreases on increasing the evaporator temperature. Consequently, the mass flow rate of the HTC
cascade refrigeration system increases. In the considered evaporator temperature range, R404A–
R170 has the lowest mass flow rate values, while R134a–R170 has the highest ones. The mass flow
rate of refrigerant pairs placing in the middle range, namely R410A–R170, R407C–R170 and R290–
R170, increases parallel to each other.
4.12 Variation of work of compression with the Evaporator Temperature
The changes in compressor work of the refrigerant pairs with respect to the evaporator
temperature. In this figure, the condenser temperature of 40°C, intermediate temperature as -20°C
and compressor efficiency of 0.7 are kept constant. As the evaporator temperature increases, the low
temperature circuit compressor’s work done (WCOMP1) decreases but the high temperature circuit
compressor’s work done (WCOMP2) increases, and the combined effect of these are to increase the
work done. In the considered evaporator temperature range, R404A–R170 has the highest work done
0.3
0.4
0.5
0.6
0.7
-50 -55 -60 -65 -70
mr2
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R170
R290-R170
R404A-R170
R407C-R170
R410A-R170
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
85
values, while R134a–R170 has the lowest ones. The work done of refrigerant pairs placing in the
middle range, namely R290–R170, R407C–R170 and R410A–R170, increase parallel to each other.
Fig.14: Compressor Work as a Function of Evaporator Temperature
4.13 Variation of COP with the Condenser Temperature
The changes in the COP of the cascade system will vary in the condenser temperature for an
evaporator temperature of -70°C intermediate temperature as -20°C and compressor efficiency of 0.7
respectively. As the condenser temperature of the cascade system increases, the condenser pressure
increases, while the evaporator temperature, intermediate temperature and compressor efficiency are
kept in constant. On increasing the condenser pressure, more compressor power is obtained, which
makes the COP of the cascade system for all considered refrigerant pairs to decrease. In the
considered condenser temperature range, R290–R508B has the highest COP values, while R404A–
R508B has the lowest ones. The COPs of refrigerant pairs placing in the middle range, namely
R410A–R508B, R407C–R508B and R134a–R508B, decrease parallel to each other.
Fig.15: Variation in COP as a function of condenser temperature
2.5
3
3.5
4
4.5
-50 -55 -60 -65 -70
Wc k
W
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R170
R290-R170
R404A-R170
R407C-R170
R410A-R170
0.6
0.7
0.8
0.9
1
1.1
30 35 40 45 50
CO
P
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R508B
R290-R508B
R404A-R508B
R407C-R508B
R410A-R508B
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
86
4.14 Variation of mass flow rate with the Condenser Temperature
Fig.16: Variation in Mass Flow Rate as a Function of Condenser Temperature
The changes in the mass flow rate of the HTC refrigerant in the cascade refrigeration system
with respect to the condenser temperature for an evaporator temperature of -70°C, intermediate
temperature as -20°C and compressor efficiency of 0.7, respectively. As the condenser temperature
of the cascade system increases, the condenser pressure also increases, when evaporator temperature,
intermediate temperature and compressor efficiency which are kept constant. On increasing the
condenser pressure, more compressor power is required, which causes the mass flow rate of the HTC
refrigerant in the cascade refrigeration system for all considered refrigerant pairs to increases. As the
condenser temperature of the cascade system increases, the mass flow rate of the HTC refrigerant in
the cascade refrigeration system increases. It is seen that R404A–R508B has the lowest mass flow
rate, while R407C–R508B has the highest one. The mass flow rate of R134a–R508B, R290–R508B,
and R410A–R508B place in the middle range and increases parallel to each other.
4.15 Variation of work of compression with the Condenser Temperature The changes in compressor work of the refrigerant pairs with respect to the condenser
temperature. In this figure, the evaporator temperature of -70°C, intermediate temperature as -20°C
and compressor efficiency of 0.7 which are kept constant. As the condenser temperature increases,
the low temperature circuit compressor’s work done (WCOMP1) decreases but the high temperature
circuit compressor’s work done (WCOMP2) increases, and the combined effect of these are to increase
the work done. In the considered condenser temperature range, R404A–R508B has the highest work
done values, while R290–R508B has the lowest ones. The work done of refrigerant pairs placing in
the middle range, namely R134a–R508B, R407C–R508B and R410A–R508B, increase parallel to
each other.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
30 35 40 45 50
mr2
Tc °C
Te=-70°, Tint=-20°C, ηc=0.7
R134a-R508B
R290-R508B
R404A-R508B
R407C-R508B
R410A-R508B
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
87
Fig.17: Compressor Work as a Function of Condenser Temperature
4.16 Variation of COP with the Evaporator Temperature
The changes in the COP of the cascade system with respect to the evaporator temperature for
an condenser temperature of 40°C, intermediate temperature as -20°C and compressor efficiency of
0.7, respectively. When condenser temperature, intermediate temperature and compressor efficiency
which are kept constant. The refrigeration effect of the cascade system increases and the specific
work of compression decreases on increasing the evaporator temperature. Consequently, the COP of
the cascade refrigeration system increases. It is seen that R290–R508B has the highest COP, while
R404A–R508B has the lowest one. The COPs of R134a–R508B, R407C–R508B, and R410A–
R508B place in the middle range and increase parallel to each other.
Fig.18: COP as a Function of Evaporator Temperature
1
1.1
1.2
1.3
1.4
1.5
1.6
30 35 40 45 50
Wc
kW
Tc °C
Te=-70°C, Tint=-20°C, ηc=0.7
R134a-R508B
R290-R508B
R404A-R508B
R407C-R508B
R410A-R508B
0.8
0.9
1
1.1
1.2
1.3
-50 -55 -60 -65 -70
CO
P
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R508B
R290-R508B
R404A-R508B
R407C-R508B
R410A-R508B
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
88
4.17 Variation of mass flow rate with the Evaporator Temperature
Fig.19: Changes in Mass Flow Rate with Evaporator Temperature
The variation in mass flow rate with the evaporator temperature for a constant condenser
temperature of 40°C, intermediate temperature of -20°C and compressor efficiency is 0.7. When the
condenser temperature, intermediate temperature and compressor efficiency which are kept constant.
The refrigeration effect of the cascade system increases and the specific work of compression
decreases on increasing the evaporator temperature. Consequently, the mass flow rate of the HTC
cascade refrigeration system increases. In the considered evaporator temperature range, R404A–
R508B has the lowest mass flow rate values, while R407C–R508B has the highest ones. The mass
flow rate of refrigerant pairs placing in the middle range, namely R410A–R508B, R134a–R508B and
R290–R508B, increases parallel to each other.
4.18 Variation of work of compression with the Evaporator Temperature
The changes in compressor work of the refrigerant pairs with respect to the evaporator
temperature. In this figure, the condenser temperature of 40°C, intermediate temperature as -20°C
and compressor efficiency of 0.7 are kept constant. As the evaporator temperature increases, the low
temperature circuit compressor’s work done (WCOMP1) decreases but the high temperature circuit
compressor’s work done (WCOMP2) increases, and the combined effect of these is to increases work
done. In the considered evaporator temperature range, R404A–R508B has the highest work done
values, while R290–R508B has the lowest ones. The work done of refrigerant pairs placing in the
middle range, namely R134a–R508B, R407C–R508B and R410A–R508B, increase parallel to each
other.
Fig.20: Changes in Compressor Work with Evaporator Temperature
0.2
0.3
0.4
0.5
0.6
-50 -55 -60 -65 -70
mr2
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R508B
R290-R508B
R404A-R508B
R407C-R508B
R410A-R508B
0.80.9
11.11.21.31.4
-50 -55 -60 -65 -70
Wc
kW
Te °C
Tc=40°C, Tint=-20°C, ηc=0.7
R134a-R508B
R290-R508B
R404A-R508B
R407C-R508B
R410A-R508B
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
89
The changes in compressor work of the refrigerant pairs with respect to the evaporator
temperature. The figure shows, the condenser temperature of 40°C, intermediate temperature as -
20°C and compressor efficiency of 0.7 are kept constant. As the evaporator temperature increases,
the low temperature circuit compressor’s work done (WCOMP1) decreases but the high temperature
circuit compressor’s work done (WCOMP2) increases, and the combined effect of these is to increases
work done. In the considered evaporator temperature range, R404A–R508B has the highest work
done values, while R290–R508B has the lowest ones. The work done of refrigerant pairs placing in
the middle range, namely R134a–R508B, R407C–R508B and R410A–R508B, increase parallel to
each other.
CONCLUSION
Coefficient of performance, mass flow rate and compressor work of the cascade refrigeration
system for the various refrigerant pairs have been analyzed and compared with the evaporator
temperature, condenser temperature, the temperature difference between the saturation temperatures
of the lower and higher temperature systems in the heat exchanger (∆T), intermediate temperature
and the compressor efficiency of the cascade refrigeration system.
Refrigerant pair R134a–R170 is found to be best pair for the vapour compression cascade
refrigeration systems among all considered pairs.
NOMENCLATURE
Cp - constant pressure specific heat of (kJ kg-1 K-1
)
E - Energy (kJ)
h - Specific enthalpy of refrigerant (kJ kg-1
)
K - Ratio of constant specific heats
m - Mass flow rate (kg s-1
)
q - Specific capacity (kJ kg-1
)
Q - Heat transfer rate (kW)
P - Pressure (kPa)
T - Temperature (K)
∆T - temperature difference between the saturation temperatures of the lower and higher temperature
systems in the heat exchanger (K)
w - Specific compressor capacity (kJ kg-1
)
Greek words
ηc - efficiency of the compressor
Subscripts
A refrigeration system A
B refrigeration system B
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
90
c condenser
cas cascade
comp compressor
crit critical
e evaporator
HE heat exchanger
i inlet
l liquid
o outlet
v vapour
Abbreviations
BP Boiling Point
HTC Higher Temperature circuit
LTC Lower Temperature circuit
COP Coefficient of Performance
ODP Ozone Depletion Potential
GWP Global Warming Potential
REFERENCES
1. Alberto Dopazo.J, Jose Fernandez-Seara,” Experimental evaluation of a cascade refrigeration
system prototype with CO2 and NH3 for freezing process applications”, International journal
of refrigeration 34 (2011) 257-267.
2. Alberto Dopazo.J, Jose Fernandez-Seara, Jaime Sieres, Francisco J. Uhia, “Theoretical
analysis of a CO2–NH3 cascade refrigeration system for cooling applications at low
temperatures”, Applied Thermal Engineering 29 (2009) 1577–1583.
3. Agnew.B, Ameli.S.M, “A finite time analysis of a cascade refrigeration system using
alternative refrigerants”, Applied Thermal Engineering 24 (2004) 2557–2565.
4. Calm. J. M. and Hourahan. G. C, “Refrigerant Data Summary,” Engineered Systems, 18(11)
74- 88, November 2001.
5. Eric B. Rattsa, Steven Brown.J,” A generalized analysis for cascading single fluid vapor
compression refrigeration cycles using an entropy generation minimization method”,
International Journal of Refrigeration 23 (2000) 353-365.
6. Getu.H.M, Bansal.P.K, “Thermodynamic analysis of an R744–R717 cascade refrigeration
system”, International journal of refrigeration 31 (2008) 45-54.
7. Jianlin Yu, Hua Zhao, Yanzhong Li, “Application of an ejector in auto cascade refrigeration
cycle for the performance improvement”, International journal of refrigeration 31 (2008) 279-
286.
8. JIN Hongguang, LI Bingyu, FENG Zhibing, GAO Lin, HAN Wei, “Integrated energy systems
based on cascade utilization of energy”, Energy Power Eng. China 2007, 1(1) 16–31.
9. Jose Fernandez-Seara, Jaime Sieres, Manuel Vazquez, “Compression–absorption cascade
refrigeration system”, Applied Thermal Engineering 26 (2006) 502–512.
International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 – 6340(Print),
ISSN 0976 – 6359(Online), Volume 6, Issue 1, January (2015), pp. 71-91 © IAEME
91
10. Kim.S.G, Kim.M.S, “Experiment and simulation on the performance of an auto cascade
refrigeration system using carbon dioxide as a refrigerant”, International Journal of
Refrigeration 25 (2002) 1093–1101.
11. Marimon.M.A, Arias.J, Lundqvist.P, Bruno.J.C, Coronas.A, “Integration of trigeneration in
an indirect cascade refrigeration system in Supermarkets”, Energy and Buildings 43 (2011)
1427–1434.
12. Mafi.M, Mousavi Naeynian.S.M, Amidpour.M, “Exergy analysis of multistage cascade low
temperature refrigeration systems used in olefin plants”, International journal of refrigeration
32 (2009) 279-294.
13. Murat HOSOZ, “Performance Comparison of Single-Stage and Cascade Refrigeration
Systems Using R134a as the Working Fluid”, Turkish J. Eng. Env. Sci. 29 (2005), 285 - 296.
14. Omid Rezayan, Ali Behbahaninia, “Thermo economic optimization and exergy analysis of
CO2/NH3 cascade refrigeration systems”, Energy 36 (2011) 888-895.
15. Anirban Sur and Dr.Randip.K.Das, “Review on Solar Adsorption Refrigeration Cycle”,
International Journal of Mechanical Engineering & Technology (IJMET), Volume 1, Issue 1,
2010, pp. 190 - 226, ISSN Print: 0976 – 6340, ISSN Online: 0976 – 6359.
16. Peethambaran K M, Asok Kumar N and John T D, “Adsorption Refrigeration System for
Automobiles an Experimental Approach”, International Journal of Mechanical Engineering &
Technology (IJMET), Volume 5, Issue 2, 2014, pp. 122 - 132, ISSN Print: 0976 – 6340,
ISSN Online: 0976 – 6359.