7SJ600 Catalogue

Embed Size (px)

DESCRIPTION

book

Citation preview

  • SIPROTEC 7SJ600Numerical Overcurrent, Motorand Overload Relay

    Protection Systems

    CatalogLSA 2.1.15 1997

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    Fig. 1SIPROTEC 7SJ600numerical overcurrent,motor and overload relay

    Protection systemsPage

    Description 2 and 3

    Tripping characteristics 4 to 6

    Functions 7 to 11

    Typical application 11Typical elementarydiagrams 12 to 13

    Scope of functions 14

    Technical data 15 to 19

    Selection andordering data 20

    LSA

    2-00

    1f.ti

    f

    Circuit diagram 21 to 23Dimension drawings

    n

    Feeder protection

    n

    Optional auto-reclosing

    n

    Transformer protection

    n

    Motor protection

    n

    Busbar protection

    n

    Trip coil monitor

    n

    Metering

    n

    Event log

    n

    Fault recorder

    n

    Self diagnostics

    n

    Remote communication

    Trip

    Busbar

    Trip Trip

    Pickup

    Pic

    kup

    Blo

    ckin

    gI>

    >

    Fig. 2Typical applications

    Recloser

    RecloserTrip

    Not containedin 7SJ600

    Siemens LSA 2.1.15 1997 1

    Siemens AG 1997

    Protection functions

    50 I>>, I>>> Instantaneousovercurrent

    50N IE>> Instantaneousground overcurrent

    51 I>t, Ip Time overcurrent

    51N IE>t, IEp Time groundovercurrent

    46 I2>>t, I2>t Negative sequence

    49 >t Overload protection

    79M Multishot reclosing

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    Wide range of applicationsThe SIPROTEC 7SJ600 is a nu-merical overcurrent relaywhich, in addition to its prima-ry use in radial distribution pow-er systems and motor protec-tion, can also be employed asbackup for feeder, transformerand generator differential pro-tection.The SIPROTEC 7SJ600 provi-des definite-time and inverse-time overcurrent protectionalong with overload and unba-lanced load protection for avery comprehensive relaypackage. In this way, equip-ment such as motors can beprotected against asymmetricand excessive loading. Asym-metric short-circuits whose cur-rents can be smaller than thelargest possible load currentsor phase interruptions are relia-bly detected.

    ConstructionThe relay contains all thecomponents needed for acquisition and evaluation of

    measured values operation and display (local

    HMI) output of signals and trip

    commands input and evaluation of bina-

    ry signals data transmission (RS485) auxiliary voltage supplyThe nominal CT currents app-lied to the SIPROTEC 7SJ600can be 1 A or 5 A.This is selectable via a jumperinside the relay.Two different cases areavailable. The flush-mountingversion has terminals accessi-ble from the rear. The surface-mounting version has termi-nals accessible from the front.

    Improved measurementtechniqueThe SIPROTEC 7SJ600 relayoperates fully numerical withenhanced algorithms. Due tothe numerical processing ofmeasured values, the influ-ence of higher-frequency tran-sient phenomena and tran-sient DC components islargely suppressed.

    Continuous self-monitoringThe hardware and software inthe SIPROTEC 7SJ600 relayare continuously self-monito-red. This ensures a very highlevel of availability and redu-ces the need for routine test-ing.

    Circuit-breaker /Trip contact testingThe trip and reclose commandcontacts can be activated viathe keyboard or through theRS485 interface. This facili-tates testing of the trip andclose circuits during commis-sioning without the need foradditional test equipment.

    Programmable inputs andoutputsUp to 10 different functionscan be activated by each bina-ry input via a form a(NO) orb(NC) contactUp to 20 internal events canactivate each signal or trip re-lay.

    For easy commissioning thestatus of each binary input, re-lay or LED can be displayedvia HMI or DIGSI program.

    2 Siemens LSA 2.1.15 1997

    Description

    Fig. 3Front view of the7SJ600 flushmounting case

    Fig. 4Rear view of the7SJ600 surfacemounting case

    LSA

    2006

    f.eps

    LSA

    2002

    f.eps

  • Siemens LSA 2.1.15 1997 3

    Serial data transmissionThe SIPROTEC 7SJ600 is fit-ted with an RS485 port. A PCcan be connected via this portto ease setup of the relay usingDIGSI. This program, which runsunder MSWINDOWS, can alsobe used to evaluate up to 8oscillographic fault records, 8fault logs and 1 event log con-taining up to 30 events. TheSIPROTEC 7SJ600 can be hook-ed up to a PC or substationautomation system. (IEC 870-5)

    Convenient settingThe menu driven HMI or con-nected PC is used for settingparameters. These parametersare stored in a non-volatile me-mory so that the settings areretained even if the supply volt-age is cut off.

    Oscillographic fault record-ing of up to 8 records(5 seconds maximum)The Fault recording functionis used to record the phase cur-rents in the event of a powersystem fault. Either pickup,tripping or binary input can beselected to trigger waveformcapture. The maximum lengthof a record can be program-med. The recorded traces ofthe phase and ground currentsand pickup and drop-off of in-ternal events can be transmit-ted to a PC for convenient ana-lysis using DIGRA.

    Event logging with timestampThe SIPROTEC 7SJ600 relaysupplies detailed data for theanalysis of faults and for check-ing on operating conditions Fault Logs

    The last 8 fault record logscan always be displayed. If anew fault occurs, the oldestwill be overwritten. Theselogs give a detailed descrip-tion of the fault in the powersystem and the reaction ofthe SIPROTEC 7SJ600, with1ms resolution. Each recordis time stamped and assigneda sequential number to easilyassociate it with the corre-sponding waveform capture.

    Event Log (operational an-nunciation) This log recordsup to 30 internal events inthe relay with 1ms resoluti-on. These events include set-ting changes and resets tothe relay, binary input activityand other relay internal activi-ties.

    or

    OptRS485RS232RS485Converter

    Protectionrelay 17SJ600

    Protectionrelay 27SJ600

    Protectionrelay 327SJ600

    Terminatingresistor120 (cable-dependent)

    Fig. 5Wiring,communi-cation

    Fig. 6Settingswindows

    Fig. 7Analog andbinary traces

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    4 Siemens LSA 2.1.15 1997

    Tripping characteristics

    t =

    +

    F

    HGGG

    I

    KJJJ

    8 9341

    10179662 0938

    .

    I I.

    .

    p

    De j

    t =

    +

    F

    HGGG

    I

    KJJJ

    0 2663

    10 0339312969

    .

    I I.

    .

    p

    De j

    Fig. 8Inverse

    Fig. 9Short inverse

    t =

    +F

    HGG

    I

    KJJ

    5 6143

    1218592

    .

    I I.

    pD

    e jt =

    +

    F

    HGGG

    I

    KJJJ

    0 0103

    10 02280 02

    .

    I I.

    .

    p

    De j

    Fig. 10Long inverse

    Fig. 11Moderately inverse

    Inverse-time characteristicsWith regard to the inverse-time overcurrent protectionfunction, the tripping time de-pends on the magnitude ofthe current (see Figs. 8 to 19).The following tripping charac-teristics are available:Inverse-time characteristics inaccordance with ANSI/IEEE: inverse short inverse long inverse moderately inverse very inverse extremely inverse definite inverse I squared T

    t = tripping time in s I = measured current Ip = parameterizable

    threshold value0.1 to 4 I/IN

    D = time multiplier

    Note for Figs. 8, 10, 13 to 15:Equations valid from1.1 to 20 for I/Ip

  • Siemens LSA 2.1.15 1997 5

    t =

    +

    F

    HGGG

    I

    KJJJ

    3922

    10 09822

    .

    I I.

    p

    De j

    t =

    +

    F

    HGGG

    I

    KJJJ

    5 64

    10 024342

    .

    I I.

    p

    De j

    t =

    +

    F

    HGGG

    I

    KJJJ

    0 4797

    10 2135915625

    .

    I I.

    .

    p

    De j

    Fig. 12Very inverse

    Fig. 13Extremely inverse

    Fig. 14Definite inverse

    Fig. 15I squared T

    t = +50 7 1014

    2. .

    I I

    D

    pe j

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    6 Siemens LSA 2.1.15 1997

    Tripping characteristics

    t T= 014

    0 02.

    I I.

    pp

    e jt T=

    135

    1

    .

    I Ipp

    e j

    tI I

    =

    80

    12

    pp

    e jT t T=

    120

    1I Ipp

    e j

    Fig. 16Inverse

    Fig. 17Very inverse

    Fig. 18Extremelyinverse

    Fig. 19Long inverse

    Inverse-time characteristics(51, 51N)Characteristics of the inverse-time overcurrent curves in ac-cordance with IEC 255-3:

    inverse very inverse extremely inverse long inverse

    t = tripping time in s I = measured current Ip = pickup value 0.1 to 4 I/IN Tp = time multiplier

    Note for Figs. 16 to 19:Equations valid from 1.1 to 20for I/Ip

  • Definite-time characteristicsThe definite-time overcurrentfunction is based on phase-se-lective measurement of thethree phase currents.The earth (ground) current IE(Gnd) is calculated from thethree line currents IL1 (A),IL2(B), and IL3(C). Alternatively,IE (Gnd) can be connected tothe relay in place of IL2(B) andthe relay will then calculateIL2(B).The definite-time overcurrentprotection for the 3 phase cur-rents has a low-set overcur-rent element (I>), a high-setovercurrent element (I>>) andan instantaneous-tripping ele-ment (I>>>). Intentional tripdelays can be parameterizedfrom 0.00 to 60.00 seconds forthe low-set and high-set over-current elements. The instanta-neous zone I>>> trips withoutany intentional delay.The definite-time overcurrentprotection for the earth(ground) current has a low-setovercurrent element (I>), anda high-set overcurrent element(I>>). Intentional trip delayscan be parameterized from0.00 to 60.00 seconds.

    Negative sequence overcur-rent protection (I2>>, I2>/ 46Unbalanced-loadprotection)The negative sequence over-current protection has the taskof detecting a phase interrup-tion or unbalanced load.This function is especially use-ful for motors since negativesequence currents cause im-permissible overheating of therotor.Furthermore, low level single-phase and two-phase short-cir-cuits (such as faults beyond atransformer) as well as phaseinterruptions can be detected. I2 = negative phase-

    sequence current TI2 = tripping time

    Siemens LSA 2.1.15 1997 7

    Locked-rotor protectionThe start-up monitor protectsthe motor against excessivelylong start-ing. This can occur,for example, if the rotor is blok-ked, if excessive voltage dipsoccur when the motor is swit-ched on or if excessive load tor-ques occur.

    The tripping time depends onthe current. It is determined inaccordance with the followingequation:

    where tTRIP = tripping time IStart = start-up current

    of the motor TStartmax = maximum

    permissiblestarting time

    Irms = actual currentflowing

    tII

    tTRIPStart

    rmsStartmax=

    FHG

    IKJ

    Fig. 20Definite-timeovercurrent characteristic

    Delay

    Fig. 21Characteristic of thenegative sequenceprotection function

    Tripping characteristic

    Fig. 22Characteristic ofstart-up monitor

    tStart max

    Ipick-up IStart

    IStart = start-up currentof the motor

    IStart max = maximum per-missible startingtime

    Ipick-up = pick-up setting offunction

    t

    I

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    8 Siemens LSA 2.1.15 1997

    Tripping characteristics

    Fig. 23Tripping characteristicsof thermal overloadfor complete memorywithout previous load andat 90 % of previous load

    Thermal overload protection(49)The thermal overload protec-tion func-tion provides trippingor alarm-ing based on a ther-mal model calculated fromphase currents.Thermal overload protectionwithout preloadFor thermal overload protec-tion without consideration ofthe preload current, the follow-ing tripping characteristic app-lies only whenI 1.1 ILFor different thermal time con-stants TL, the tripping time t iscalculated in accordance withthe following equation:

    The reset threshold is above1.03125 I/INThermal overload protectionwith preloadThe thermal overload protec-tion with consideration of pre-load current constantly upda-tes the thermal model calcula-tion regardless of themagnitude of the phase cur-rents. The tripping time t iscalculated in accordance withthe following tripping charac-teristic (complete memory inaccordance with IEC 255-8).

    t = tripping time afterbeginning of the thermaloverload

    = 35.5 x TL Ipre = pre-load current TL = time multiplier I = overload current k = k factor (in accordance

    with IEC 255-8) ln = natural logarithm(See Fig. 23)

    t T=FHG

    IKJ

    35

    12

    IIL

    L

    tk k

    k

    =

    FHG

    IKJ

    FHG

    IKJ

    FHG

    IKJ

    t ln N

    pre

    N

    N

    II

    II

    II

    2 2

    2

    1

  • Siemens LSA 2.1.15 1997 9

    3-pole multishot automaticreclosing (AR, 79)(see Fig. 25) (optional)Automatic reclosing (AR) en-ables 3-phase auto-reclosing ofa feeder which has previouslybeen disconnected by time-overcurrent protection(I>, I>>, I>>>, Ip, IE>, IE>>,IEp/50, 51, 50N, 51N).The SIPROTEC 7SJ600 allowsup to 9 reclosing shots. Thefirst four dead times can beset individually. Reclosing canbe blocked or initiated by a bi-nary input or internally. Afterthe first trip in a reclosing se-quence, the high-set instanta-neous elements (I>>>, I>>,IE>>) are blocked. This is usedfor fuse saving applicationsand other similar transientschemes using simple overcur-rent relays instead of fuses.The low-set definite-time(I>, IE>) and the inverse-time(Ip, IEp) overcurrent elementsremain operative during the en-tire sequence.

    Fig. 24Feeder protection

    Busbar

    Typical feeder

    Trip

    Recloser

    Recloser

    Busbar

    Typical feeder

    Fuse is saved during arcing faults, butblows after the first unsuccesful reclosingcycle to clear permanent faults

    These elements tripfaster than the fuses.They are blocked afterthe first reclosing cycle

    These elements tripslower than the fuses.They allow the fuse to blowafter the first reclosing cycle

    Fig. 25Automatic reclosingwith fuse saving scheme

    Trip

    Recloser

    Busbar

    Trip Transformer stand-by protection

    Unbalancedfaults

    Typical feederFig. 26Transformerbackup protection

    Applications

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    10 Siemens LSA 2.1.15 1997

    Applications

    Cold load pickup (see Fig. 28)By means of a binary inputwhich can be wired from a ma-nual close contact, it is possi-ble to switch the overcurrentpickup settings to less sensi-tive settings for a program-mable amount of time. Afterthe set time has expired, thepickup settings automaticallyreturn to their original setting.This can compensate for initialinrush when energizing a cir-cuit without compromising thesensitivity of the overcurrentelements during steady stateconditions.

    Fig. 27Motor protection

    Busbar

    Typical feeder

    Trip

    Left/Right rotation (5144 > rev PhR)

    Busbar

    Typical feeder

    Fig. 28Cold load pickup(Timer controlledsetting group)

    Trip

    Trip

    Binary input(1727 > c/o)

    Desensetize during inrush

    Binaryinput(1727 > c/o)

    Trip

    Fig. 29Switch-onto-faultprotection

    Busbar

    Trip (high speed dead fault clearance)

    Manual close(356 > m close)

    Typical feeder

    Feeder grounded

    200 ms

  • Applications

    Busbar protection(Reverse interlocking)Reverse interlock principle in-volves the blocking of the high-speed overcurrent protectionon the supply feeder, to theauxiliary bus, if any of the loadfeeder overcurrent relays arein pickup. If a fault is not pre-sent on any of the associatedload feeders, the supplys high-speed overcurrent protectionwill not be blocked, providingreliable protection for busfaults.In this manner, selective high-speed overcurrent relaying canbe applied to the supply andload feeders to provide coordi-nated bus protection. The re-lays, through contact input andoutput interconnection, can dis-criminate and operate selec-tively for various types offaults and locations, trippingonly the affected parts of thesystem.

    Trip circuit monitor(see Fig. 31)One or two binary inputs canbe used for the trip circuit mon-itoring.

    Siemens LSA 2.1.15 1997 11

    Clears faultsat the busbarTI>> = 50 msec

    Backup forfeeder relaysTI> = 300 msec

    Power flow

    Typical feeder

    Busbar

    Block 50, I>>, I>>> elements

    Bus relay 1 trips forfaults on location A

    Feeder relayst1 = 0 msec

    Pickup

    Feeder relay 2 will not tripfor faults on location B

    Feeder relayst1 = 0 msec

    Pickup

    Feeder relay 3 trips forfaults on location B whileblocking bus relay 1

    Relay 3

    Relay 2

    Relay 1

    Fig. 30Busbar protection(Reserve interlocking)

    7SJ600

    7SJ600

    7SJ600

    7SJ600or anyprotectiverelay

    Tripcircuitfaulty

    CLOSE TRIP

    TCo Trip contact of the 7SJ600sBI Binary input of the 7SJ600TC Trip coilAux Circuit-breaker auxiliary

    contactR Equivalent resistorVcv Control voltageCB Circuit-breaker

    Fig. 31Trip-circuit monitorwith one binary input1)

    VCV

    TCo

    Bl 1

    Aux 152a

    Aux 252b

    TC

    52CB

    R

    1) Example with 2 binary inputs,see manual for the 7SJ600.

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    12 Siemens LSA 2.1.15 1997

    Typical schematic diagrams

    AC schematics(optional connections) measured

    IL1 (A), IL3 (C), IE (Gnd) calculated

    IL2 (B)

    measuredIL1 (A), IL2 (B), IL3 (C)

    Fig. 32Three CT circuit withmeasurement of the earth(ground) current

    Fig. 33Two CT circuit only forisolated orresonant-earthed(grounded) power systems

    Fig. 34Sensitive earth-faultprotection(three times increasedsensitivity)

  • * Factory settings

    Fig. 35Three CT circuit withmeasurement of thephase currents

    Fig. 36Serial port

    AC schematics(standard connection) measured

    IL1 (A), IL2 (B), IL3 (C) calculated

    IE (Gnd)

    DC schematics

    Siemens LSA 2.1.15 1997 13

    Power-supply

    BI1 BI2 BI3

    I>>Otherprotecti-on

    Manual*Close

    Alarm*

    Fig. 37DC schematics

    LED*Reset

    Trip

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload RelayScope of functions

    14 Siemens LSA 2.1.15 1997

    Fig. 38Scope of functions *Automatic reclosing (AR, 79) (optional)

    Multiple applications Feeder protection, overhead

    line cable protection Motor protection (overload

    and short-circuit protection) Transformer protection (main

    or backup protection, over-load protection)

    Generator protection (backupprotection)

    Busbar protection (reverseinterlocking)

    Cost effective Less wiring: one relay - many

    functions Reliable and available, inter-

    nal hardware and softwaremonitoring, current transfor-mer monitoring, trip-circuitmonitoring

    Reduced testing due to selfdiagnostics and numericaltechnology

    Easy commissioning Simplified parameterization

    and fault analysis using Win-dows-based DIGSI program

    Remote communication (viamodem)

    Additional functions Protection

    automatic reclosing(AR, 79)

    cold load pickup trip circuit monitoring

    Metering functions currents thermal model (49)

    Fault recording status indications event log fault log records waveform capture/fault ana-

    lysisParallel running functionsOvercurrent protection Definite-time overcurrent pro-

    tection (up to three zones) phase currents IL1 (A), IL2

    (B), IL3 (C)I>>>, I>>, I> (50)

    earth (ground) current IE(Gnd) (50N) IE>>, IE>

    Inverse-time overcurrent pro-tection (51, 51N) IEC

    inversevery inverseextremely inverselong inverse

    ANSI/IEEEinverselong inversemoderately inversevery inverseextremely inverse

    I squared T phase currents IL1 (A), IL2 (B), IL3 (C) Ip earth (ground) current IE, IEp

    Negative sequence overcurrent pro-tection (46, unbalanced load) (2 zones)

    Thermal overload protection (49) Locked-rotor protection

    CLOSE

    TRIP

    Earth (ground)Phase

    Serial RS485 port

    Furt

    her7

    SJ60

    0un

    its

    orPC

    AR50HS

    50(51)

    51(50)

    50N(51N)

    51N(50N)

    51N51

    Over-load 49

    or PC

  • Siemens LSA 2.1.15 1997 15

    Technical Data

    CT circuits Rated current IN 1 A or 5 ARated frequency fN 50 Hz/60 Hz (selectable)

    Overload capability current pathThermal (rms)

    Dynamic (pulse current)

    100 x IN for 1s30 x IN for 10s4 x IN continuous250 x IN one half cycle

    Power consumptionCurrent input at IN = 1 A

    at IN = 5 A< 0.1 VA< 0.2 VA

    Power supply via integratedDC/DC converter

    Rated auxiliary voltage Vaux /permissible variations 24/48 V DC/19 to 58 V DC60/110/125 V DC/48 to 150 V DC220/250 V DC/176 to 300 V DC115 V AC/88 to 133 V AC230 V AC/176 to 265 V AC

    Superimposed AC voltage,peak to peak

    at rated voltageat limits of admissible voltage

    12% 6%

    Power consumptionQuiescentEnergized

    Approx. 2 WApprox. 4 W

    Bridging time during failure/short-circuit of auxiliary voltage 50 ms at Vaux 110 V DC

    20 ms at Vaux 24 V DC

    Binary inputs Number 3 (marshallable)Operating voltage 24 to 250 V DC

    Current consumption, independent ofoperating voltage

    Approx. 2.5 mA

    Pick-up threshold, reconnectable bysolder bridges

    Rated aux. voltage24/48/60 V DC Vpick-up

    Vdrop-off110/125/220/250 V DC Vpick-up

    Vdrop-off

    17 V DC< 8 V DC 74 V DC< 45 V DC

    Signal contacts Signal/alarm relays 2 (marshallable)Contacts per relay 1 CO

    Switching capacityMakeBreak

    1000 W / VA30 W / VA

    Switching voltage 250 V

    Permissible current 5 A

    Heavy-duty (command) contacts Trip relays, number 2Contacts per relay 2 NO

    Switching capacityMakeBreak

    1000 W / VA30 W / VA

    Switching voltage 250 V

    Permissible currentContinuousFor 0.5s

    5 A30 A

    Serial interface, isolated Standard RS485Test voltage 2.8 kV DC for 1 min

    Connection Data cable at housing terminals, two datawires, one frame reference, for connection ofa personal computer or similar; core pairs withindividual and common screening, screenmust be earthed (grounded), communicationpossible via modem

    Transmission speed As delivered 9600 Baudmin. 1200 Baud,max. 19200 Baud

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    16 Siemens LSA 2.1.15 1997

    Technical Data

    Design Housing 7XP20 For dimensions refer to dimension drawingsWeight

    Flush mounting /cubicle mountingSurface mounting

    Approx. 4 kgApprox. 4.5 kg

    Degree of protection acc. to EN 60529HousingTerminals

    IP51IP21

    Insulation tests Standards IEC 255-5, ANSI/IEEE C37.90.0High-voltage test (routine test)

    Except DC voltage supply input and RS485Only DC voltage supply input and RS485

    2 kV (rms), 50 Hz2.8 kV DC

    Impulse voltage test (type test)all circuits, class III

    5 kV ( peak), 1.2/50 s,0.5 J, 3 positive and 3 negative shots atintervals of 5 s

    EMC tests, immunity(type tests)

    Standards IEC 255-6; IEC 255-22 (product standard)EN 50082-2 (generic standard),DIN VDE 0435 Part 303

    High-frequency testIEC 255-22-1 class III

    2.5 kV (peak), 1 MHz, =15 s,400 shots/s, duration 2 s

    Electrostatic discharge IEC 255-22-2 class IIIand EN 61000-4-2 class III

    4 kV/6 kV contact discharge,8 kV air discharge, both polarities,150 pF, Ri=330

    Radio-frequency electromagnetic fieldNon-modulated, IEC 255-22-3 (report) class IIIAmplitude modulated, IEC 1000-4-3, class III

    Pulse modulated, IEC1000-4-3class III

    10 V/m, 27 to 500 MHz10 V/m, 80 to 1000 MHz,80% AM, 1 kHz10 V/m, 900 MHz, repetition frequency200 Hz, duty cycle 50%

    Fast transientsIEC 255-22-4 and IEC 1000-4-4, class III

    2 kV, 5/50 ns, 5 kHz, burst length 15 ms,repetition rate 300 ms, both polarities,Ri = 50, duration 1 min

    Conducted disturbances induced by radio-frequency fields,amplitude modulated IEC 1000-4-6, class III

    10 V, 150 kHz to 80 MHz,80% AM, 1 kHz

    Power frequency magnetic fieldIEC 1000-4-8, class IVIEC 255-6

    30 A/m continuous, 50 Hz300 A/m for 3 s, 50 Hz0.5 mT; 50 Hz

    Oscillatory surge withstand capability ANSI/IEEE C37.90.1(common mode)

    2.5 kV to 3 kV (peak), 1 MHz to 1.5 MHz,decaying oscillation,50 shots per s,duration 2 s, Ri = 150 to 200

    Fast transient surge withstand capabilityANSI/IEEE C37.90.1 (commom mode)

    4 kV to 5 kV, 10/150 ns, 50 shots per s, bothpolarities, duration 2 s, Ri = 80

    Radiated electromagnetic interferenceANSI/IEEE C37.90.2

    10 to 20 V/m, 25 to 1000 MHz,amplitude and pulse modulated

    High-frequency testDocument 17C (SEC) 102

    2.5 kV (peak, alternating polarity), 100 kHz,1 MHz, 10 MHz and 50 MHz,decaying oscillation,Ri = 50

    EMC tests, emission(type tests)

    Standard EN 50081-* (generic standard)Conducted interference voltage, aux. voltageCISPR 22, EN 55022, DIN VDE 0878 Part 22,limit value class B

    150 kHz to 30 MHz

    Interference field strength CISPR 11,EN 55011, DIN VDE 0875 Part 11, limit value class A

    30 to 1000 MHz

    Climatic stress tests Recommended temperatureduring service - 5 C to + 55 C (25 F to 131 F),

    > 55 C decreased display contrastPermissible temperature

    during serviceduring storageduring transport(Storage and transport with standard works packaging)

    - 20 C to + 70 C (- 4 F to 158 F)- 25 C to + 55 C (-13 F to 131 F)- 25 C to + 70 C (- 13 F to 158 F)

    Permissible humidity Mean value per year 75% relative humidity,on 30 days per year 95%relative humidity,condensation not permissible

  • Siemens LSA 2.1.15 1997 17

    Mechanical stress testsVibration and shock duringoperation

    Standards Acc. to IEC 255-21and IEC 68-2Vibration

    IEC 255-21-1, class1IEC 68-2-6

    Sinusoidal 10 to 60 Hz: 0.035 mm amplitude,60 to 150 Hz: 0.5 g accelerationSweep rate 1 octave/min20 cycles in 3 orthogonal axes

    ShockIEC 255-21-2, class 1

    Half sine, acceleration 5 g , duration 11 ms,3 shocks in each direction of 3 orthogonal axes

    Seismic vibrationIEC 255-21-3, class 1,IEC 68-3-3

    Sinusoidal1 to 8Hz: 3.5 mm amplitude (horizontal axis)1 to 8 Hz: 1.5 mm amplitude (vertical axis)8 to 35 Hz: 1 g acceleration (horizontal axis)8 to 35 Hz: 0.5 g acceleration (vertical axis)Sweep rate 1 octave/min1 cycle in 3 orthogonal axes

    Vibration and shock during trans-port

    VibrationIEC 255-21-1, class 2IEC 68-2-6

    Sinusoidal5 Hz to 8 Hz: 7.5 mm amplitude;8Hz to 150 Hz: 2 g accelerationSweep rate 1 octave/min20 cycles in 3 orthogonal axes

    ShockIEC 255-21-2, class 1IEC 68-2-27

    Half sine, acceleration 15 g ,duration 11 ms,3 shocks in each direction of 3 orthogonal axes

    Continuous shockIEC 255-21-2, class 1IEC 68-2-27

    Half sine, acceleration 10 gduration 16 ms, 1000 shocks in each directionof 3 orthogonal axes

    Definite-time overcurrent protec-tion (50, 50N)

    Setting range/stepsOvercurrent pick-up phase I>

    earth IE>phase I>>earth IE>>phase I>>>

    I/IN = 0.1 to 25.0 (steps 0.1), or = 0.1 to 25.0 (steps 0.1), or

    I/IN = 0.1 to 25.0 (steps 0.1, or = 0.1 to 25.0 (steps 0.1), or

    I/IN = 0.3 to 12.5 (steps 0.1, or Delay times T for I>, IE>, I>> and IE>>The set times are pure delay times

    0.00 s to 60.00 s (steps 0.01 s)

    Pick-up timesI>, I>>, IE>, IE>>at 2 x setting value, without meas. repetitionat 2 x setting value, with meas. repetitionpick-up times for I>>> at 2 x setting value

    Approx. 35 msApprox. 55 msApprox. 20 ms

    Reset timesI>, I>>, I>>>, IE>, IE>> Approx. 65 ms at 50 Hz

    Approx. 95 ms at 60 Hz

    Reset ratios Approx. 0.95

    Overshot time Approx. 55 ms

    TolerancesPick-up values I>, I>>, I>>>, IE>, IE>>Delay times T

    5% of setting value1% of setting value or 10 ms

    Influence variablesAuxiliary voltage in range 0.8 Vaux/VauxN 1.2Temperature in range 0 C amb 40 C(32 F amb 104 F)Frequency in range 0.98 f/fN 1.02Frequency in range 0.95 f/fN 1.05Harmonicsup to 10% of 3rd harmonicup to 10% of 5th harmonic

    1 % 0.5 %/10 K

    1.5 % 2.5 %

    1 % 1 %

    Inverse-time overcurrent protec-tion (51/51N)

    Setting range/stepsOvercurrent pick-up phase Ip

    earth IEpI/IN = 0.1 to 4.0 (steps 0.1)

    = 0.1 to 4.0 (steps 0.1)Time multiplier for Ip, IEp Tp

    D(IEC charac.) 0.05 to 3.20 s(ANSI charac.) 0.5 to 15.0 s

    Overcurrent pick-up phase I>>phase I>>>

    I/IN = 0.1 to 25.0 (steps 0.1), or =0.3 to 12.5 (steps 0.1), or

    Delay time T for I>>, IE>>Pick-up thresholdDrop-off thresholdDrop-off time

    0.00 s to 60.00 sApprox. 1.1 x IpApprox. 1.03 x IpApprox. 50 ms at 50 HzApprox. 60 ms at 60 Hz

    TolerancesPick-up valuesDelay time for 1 I/Ip 20 and0.5 I/IN 24

    5 %5 % of theoretical value 2 % current tolerance;at least 30 ms

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    18 Siemens LSA 2.1.15 1997

    Technical Data

    Inverse-time overcurrent protec-tion (51/51N) (cont d)

    Influence variablesAuxiliary voltage in range0.8 Vaux/VauxN 1.2Temperature in range-5 C amb 40 C-32 F amb 104 FFrequency in range0.95 f/fN 1.05

    1 %

    0.5 %/10 K

    8 % referred to theoretical time value

    Negative sequence overcurrentprotection (46)

    Setting range/stepsTripping stage I2> in steps of 1%

    I2>> in steps of 1%8 % to 80 % of IN8 % to 80 % of IN

    Time delays T(I2>), T(I2>>) in steps of 0.01s) 0.00 s to 60.00 s

    Lower function limit at least one phase current 0.1 x INPick-up times

    Tripping stage I2>, tripping stage I2>>but with currents I/IN>1.5 (overcurrent case)or negative-sequence current < (set value +0.1 x IN)

    at fN = 50 Hz 60 Hzapprox. 60 ms 75 msapprox. 200 ms 310 ms

    Reset timesTripping stage I2>, tripping stage I2>>

    at fN = 50 Hz 60 Hzapprox. 35 ms 42 ms

    Reset ratiosTripping stage I2>, tripping stage I2>> Approx. 0.95 to 0.01 x IN

    TolerancesPick-up values I2>, I2>> current I/IN 1.5

    current I/IN > 1.5Stage delay times

    1 % of IN 5 % of set value 5 % of IN 5 % of set value 1 % but min. 10 ms

    Influence variablesAuxiliary DC voltage in range0.8 Vaux /VauxN 1.2Temperature in range --5 C amb +40 C-32 F amb +104 FFrequencyin range 0.98 f/fN 1.02in range 0.95 f/fN 1.05

    1%

    0.5%/10K

    1% of IN 5% of IN

    Auto-reclosing (option)(79)

    Number of possible shotsAuto-reclose modes

    1 up to 93-pole

    Dead times for 1st to 3rd shotfor 4th and any further shot

    0.05 s to 1800.00 s (steps 0.01 s)0.05 s to 1800.00 s (steps 0.01 s)

    Reclaim time after successful AR 0.05 s to 320.00 s (steps 0.01 s)

    Lock-out time after unsuccessful AR 0.05 s to 320.00 s (steps 0.01 s)

    Reclaim time after manual close 0.50 s to 320.00 s (steps 0.01 s)

    Duration of RECLOSE command 0.01s to 60.00 s (steps 0.01 s)

    Thermal overload protection withmemory (49)(total memory according to IEC 255-8)

    Setting rangesFactor k according to IEC 255-8 0.40 to 2.00 (steps 0.01)Thermal time constant th 1.0 to 999.9 min (steps 0.1 min)

    Thermal warning stage alarm/trip 50 to 99% referred to trip temperature rise(steps 1%)

    Prolongation factor at motor stand-still k 1.00 to 10.00 (steps 0.01)

    Trip time characteristic see page 8

    Reset ratios/trip/alarm

    Reset below 0.99 alarmApprox. 0.99

    Tolerancesreferring to k INreferring to trip time

    5 % (class 5 % acc. to IEC 255-8) 5 % 2 s (class 5 % acc. to IEC 255-8)

    Influence variables referred to k INAuxiliary DC voltage in the range of0.8 < Vaux / VauxN < 1.2

    Temperature in the range of-5 C < amb< +40 C-32F amb +104 FFrequency in the range of 0.95 < f / fN < 1.05

    1 %

    0.5 % / 10 K

    1 %

  • Siemens LSA 2.1.15 1997 19

    Thermal overload protection(contd) without memory

    Pick-up value IL / IN 0.4 to 4.0 (steps 0.1)Time multiplier tL (= t6 -time) 1.0 to 120.0 s (steps 0,1 s)

    Tripping characteristic see page 8

    Reset ratio I/IL Approx. 0.94Tolerances

    referring to pick-up threshold 1.1 ILreferring to trip time

    5% 5% 2 s

    Influence variablesAuxiliary DC voltage in the range of 0.8 < Vaux / VauxN < 1.2

    Temperature in the range of -5 C < amb< +40 CFrequency in the range of 0.95 < f/fN < 1.05

    < 1 %< 0.5 %/10 K< 1 %

    Start-up monitorMotor protection

    Setting rangesPermissible start-up current IStart / IN 0.4 to 20.0 (steps 0.1)Permissible start-up time tStart 1.0 to 360.0 s (steps 0.1 s)

    Tripping characteristic

    Reset ratio Irms / IStart Approx. 0.94Tolerances

    Pick-up valueDelay time

    5%5% of setting value or 330 ms

    Fault recording Measured values IL1, IL2, IL3Start signal Trip, start release, binary input

    Recording duration 5000 ms

    Additional functions Operational value measurementsOperational current valuesMeasurement rangeTolerance

    IL1, IL2, IL30% to 240% IN3% of rated value

    Thermal overload valuesCalculated temperature riseMeasurement rangeTolerance

    /trip0% to 300%5% referred to trip

    Fault event data storage Storage of annunciations of the last 3 faults

    Time assignmentResolution for operational annunciationsResolution for fault event annunciationsMax. time deviation

    1 s1 ms0.01 %

    Data storage for fault recordingTotal storage time (fault detection or trip command = 0 ms)

    Max. storage period per fault event TmaxPre-trigger time TprePost-fault time TpostSampling rate

    max. 8 fault eventsmax. 5 s, selectable pre-trigger andpost-fault time0.30 to 5.00 s (steps 0.01 s)0.05 to 0.50 s (steps 0.01s)0.05 to 0.50 s (steps 0.01 s)1 instantaneous value per ms at 50 Hz1 instantaneous value per 0.83 ms at 60 Hz

    Trip circuit monitor with one or two binary inputs

    Circuit-breaker trip test with live trip or trip/reclose cycle(models with auto-reclose)

    CE conformity, regulations The product meets the stipulations of the guideline of the councilof the European Communities for harmonization of the legalrequirements of the member states on electro-magneticcompatibility (EMC guideline 89/336/EEC).The product conforms with the international standard of theIEC 255 series and the German national standardDIN VDE 57 435,Part 303.The unit has been developed andmanufactured for use in industrial areas in accordance with theEMC standard. The unit has not been designed for use in livingquarters as defined in standard EN 50081.This conformity is the result of a test that was performed bySiemens AG in accordance with article 10 of the guideline andthe EN 50081-2 and EN 50082-2 basic specifications.

    t t=FHG

    IKJ

    >II

    I IStartrms

    2

    rms Startfor

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    20 Siemens LSA 2.1.15 1997

    Selection and ordering data

    In addition we offer:SIPROTEC 7SJ601(Reduced version of the SIPROTEC7SJ600 protection device)See Catalog LSA 2.1.16Order No.:E50001-K5712-A261-A1-7600

    1) Contained in the full version ofDIGSIGerman 7XS5020-0AA00English 7XS5020-1AA00French 7XS5020-2AA00Italian 7XS5020-3AA00Spanish 7XS5020-4AA00

    Designation Order No.

    7SJ600 numerical overcurrent, motor and overload relay 7SJ600 A0 DA0Binary input voltage 24 to 250 V DCwith isolated RS485 portRated current at 50/60 Hz1 A5 A

    Rated power supply voltage24, 48 V DC60, 110, 125 V DC220, 250 V DC, 115 V AC230 V AC

    HousingSurface mountingFlush mounting/cubicle mounting

    LanguagesEnglish, German, Spanish, French

    Auto-reclosing (option)withoutwith

    AccessoriesCommunication cable (copper)between PC (9-pole socket) and converter/protection device 7XV5100- 2

    Converter V.24 - RS485with communication cable for the 7SJ600numerical overcurrent, Motor and overload relayLength 1 m (3 ft)PC adapterwith power supply unit 230 V ACwith power supply unit 110 V AC

    Converter full-duplexFibre-optic cable - RS485with built-in power supply unitAuxiliary voltage 24 to 250 V DC and 110/230 V AC

    Manual 7SJ600GermanEnglishFrenchSpanish

    DIGSI-LIGHT1) protection softwareParameterizing and operating software for the 7SJ600protection unit without graphical evaluation programRequirements: MS WINDOWS 3.1 or higherGermanEnglishFrenchSpanish

    DIGRA graphical evaluation program for DIGSI-LIGHT1)

    For visualization of fault recording, in conjunctionwith DIGSI-LIGHT protection software for 7SJ600Requirements:MS WINDOWS 3.1 or higherGermanEnglishFrenchSpanish

    Sample order7SJ6001-4EA00-1DA0 7SJ600 1A, 60-125V,

    flush mounting, ARC7XV5700-0AA00 Converter RS485-RS232C53000-G1176-C106 Manual, English7XS5120-1AA0 DIGSI Light English

    7XS5130- 0AA0- 1AA0- 2AA0- 4AA0

    7XS5120- 0AA0- 1AA0- 2AA0- 4AA0

    C53000 - G1100 - C106-3- G1176 - C106-2- G1177 - C106-1- G1178 - C106-1

    7XV5600 - 0AA00

    7XV5700 - 0AA007XV5700 - 1AA00

    s

    15

    s

    2456

    s

    BE

    s

    0

    s

    01

  • Siemens LSA 2.1.15 1997 21

    Circuit diagram

    Vers

    ion

    fors

    urfa

    ce-m

    ount

    ing

    Vers

    ion

    forf

    lush

    /cub

    icle

    mou

    ntin

    g

    Trip

    rela

    y

    Trip

    ping

    ofde

    f.-tim

    eov

    ercu

    r.pr

    ot.I

    >>

    (pha

    ses)

    Trip

    ping

    ofde

    f.-tim

    eov

    ercu

    r.pr

    ot.I

    >(p

    hase

    s)

    Trip

    ping

    ofde

    f.-tim

    eov

    ercu

    r.pr

    ot.I

    >(g

    roun

    d)

    ALA

    RM

    cont

    acts

    Rea

    dy(

    Life

    -con

    tact

    )

    Pic

    kup

    (gro

    unde

    d)(g

    roun

    ded)

    INPU

    T

    Res

    etLE

    Ddi

    spla

    ys

    Blo

    cktim

    eov

    ercu

    rren

    tpro

    tect

    ion

    Man

    ualC

    lose

    Pow

    ersu

    pply

    Fig. 39 connection circuit diagram for the 7SJ600numerical overcurrent, motor and overload relay

    K1:

    -BI1

    -BI3

    K2:

    M1:

    M2:

    -BI2

  • SIPROTEC 7SJ600 (Version V2.1)Numerical Overcurrent, Motor and Overload Relay

    22 Siemens LSA 2.1.15 1997

    Terminals

    Wire size Fittings Order No.(manufacturer)

    Order No.(Siemens)

    Contacts 1 to 6

    Ring-cable lugs Crimp spring contacts1)from Grote & Hartmann (type DFK 2)

    d1 = 6 mm (0.24 in)

    Wmax.= 13 mm (0.51 in)

    Wire size2,7 to 6,6 mm2(AWG 12 to 10)

    0,5 to 1 mm2one-sided locating spring

    3000 units 26456.331.042 W53073-A2508-C1

    1,5 to 2,5 mm2one-sided locating spring

    2500 units 26457.331.042 W53073-A2509-C1

    2,5 to 4 mm2double-sided locating spring

    2000 units 26473.331.042 W53073-A2510-C1

    Contacts 7 to 31

    Ring-cable lugs Crimp spring contacts1) from Weidmller

    d1 = 4 mm (0.2 in)

    Wmax.= 9 mm (0.36 in)

    Wire size1 to 2,6 mm2(AWG 16 to 14)

    0,5 to 1mm 2 3000 units 162 552 W73073-A2502-C1

    1,5 to 2,5 mm2 2500 units 162 550 W73073-A2503-C1

    1) Only for panel mounting

  • Siemens LSA 2.1.15 1997 23

    Dimension drawings in mm (inch)

    Frontview

    Sideview

    Terminal forearth (ground)

    A View

    Sideview

    Terminal

    View fromthe rear

    Panel cutout

    5 (0.2)

    Assembly plate

    For panel surface mounting, terminals on the side (7XP20 housing)

    For flush mounting, terminals on the rear (7XP20 housing)

  • Catalog Index

    Title Designation Order No.

    Measurement and Recording Systems

    Fault Recorder OSCILLOSTORE SR 10.1 E50001-K4010-A101-A1-7600

    Numerical Protective Relaying

    7SJ41 Definite-Time Overcurrent Protection Relay LSA 2.1.10 E50001-K5712-A201-A2-76007SJ511 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.3 E50001-K5712-A131-A3-76007SJ512 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.4 E50001-K5712-A141-A3-76007SJ531 Numerical Overcurrent Protection Relay LSA 2.1.9 E50001-K5712-A191-A3-76007SJ551 Multi-Function Protection Relay LSA 2.4.2 E50001-K5742-A121-A2-76007SJ600 SIPROTEC Overcurrent, Motor and Overload Protection LSA 2.1.15 E50001-K5712-A251-A2-76007SJ601 SIPROTEC Overcurrent Protection LSA 2.1.16 E50001-K5712-A261-A1-7600

    7SA511 Line Protection Relay (Version V3) LSA 2.1.11 E50001-K5712-A211-A2-76007SA513 Line Protection Relay (Version V3) LSA 2.1.12 E50001-K5712-A221-A1-76003VU13 Miniature Circuit-Breaker LSA 2.1.8 E50001-K5712-A181-A1-7600

    7SD502 Line Differential Protection with Two Pilot Wires LSA 2.2.1 E50001-K5722-A111-A2-76007SD503 Line Differential Protection with Three Pilot Wires LSA 2.2.2 E50001-K5722-A121-A2-76007SD511/512 Current Comparison Protection Relay (Version V3)for Overhead Lines and Cables LSA 2.2.3 E50001-K5722-A131-A2-76007UT512/513 Differential Protection Relay (Version V3)for Transformers, Generators and Motors LSA 2.2.4 E50001-K5722-A141-A2-7600

    7SS5 Station Protection LSA 2.2.5 E50001-K5722-A151-A2-7600Auxiliary Current Transformers 4AM50, 4AM51, 4AM52and Isolating Transformers 7XR95 LSA 2.2.6 E50001-K5722-A161-A1-7600

    7SN71 Transient Earth-Fault Relay LSA 2.3.2 E50001-K5732-A121-A1-76007VC1637 Earth-Leakage Monitor LSA 2.3.4 E50001-K5732-A141-A1-7600

    7UM511 Generator Protection Relay (Version V3) LSA 2.5.2 E50001-K5752-A121-A2-76007UM512 Generator Protection Relay (Version V3) LSA 2.5.3 E50001-K5752-A131-A2-76007UM515 Generator Protection Relay (Version V3) LSA 2.5.4 E50001-K5752-A141-A2-76007VE51 Synchronizing Unit LSA 2.5.7 E50001-K5752-A171-A1-7600

    7VK512 Numerical Auto-Reclose/Check-Synchronism Relay LSA 2.7.3 E50001-K5772-A131-A1-7600Test Switch 7XV72 R 2.20 E50001-K4502-A301-A1-76007VP151 Three-Phase Portable Test Set (Omicron CMC56) LSA 2.6.1 E50001-K5762-A111-A2-7600

    Centralized and Remote Control of Siemens Protection Relays (Overview)* LSA 2.8.1 E50001-K5782-A111-A1-7600Operating and Analysis Software DIGSI V3* LSA 2.8.2 E50001-K5782-A121-A1-7600

    Substation Control and Protection

    Input/Output Unit 6MB522 LSA 1.1.1 E50001-K5701-A111-A4-7600Input/Output Unit 6MB523 LSA 1.1.2 E50001-K5701-A121-A2-76006MB511/6MB512 Substation Master Unit 7SW511/7SW512 Relay Data Concentrator LSA 1.1.3 E50001-K5701-A131-A2-76006MB520/6MB521 Input/Output Units LSA 1.1.4 E50001-K5701-A141-A1-76006MB513/514 Compact Control Master Unit and Relay Data Concentrator LSA 1.1.6 E50001-K5701-A161-A1-7600

    6MB5510 Station Control Unit LSA 1.2.1 E50001-K5701-A211-A2-76006MB552 Compact Remote Terminal Unit LSA 1.2.2 E50001-K5701-A221-A1-76006MB5530-0 Minicompact Remote Terminal Unit LSA 1.2.3 E50001-K5701-A231-A1-7600

    6MB5530-1 Minicompact Remote Terminal Unit for Cable Shield Communication LSA 1.2.4 E50001-K5701-A241-A1-76006MB5540 SINAUT LSA COMPACT Remote Terminal Unit LSA 1.2.5 E50001-K5701-A251-A1-76006MB5515 Station Control Unit LSA 1.2.6 E50001-K5701-A261-A1-7600

    Control in SINAUT LSA Substation Control and Protection LSA 1.4.1 E50001-K5701-A411-A1-7600Status Indications in SINAUT LSA Substation Control and Protection LSA 1.4.2 E50001-K5701-A421-A1-7600Analog Values in SINAUT LSA Substation Control and Protection LSA 1.4.3 E50001-K5701-A431-A1-7600Metering in SINAUT LSA Substation Control and Protection LSA 1.4.4 E50001-K5701-A441-A1-7600

    Voltage Control with Input/Output Units 6MB520/6MB521 LSA 1.4.5 E50001-K5701-A451-A1-7600Network Synchronization with Input/Output Units 6MB520/521 LSA 1.4.6 E50001-K5701-A461-A1-7600Operation with Two Control Master Units LSA 1.4.7 E50001-K5701-A471-A1-7600Node Functions in SINAUT LSA Substation Control and Protection LSA 1.4.8 E50001-K5701-A481-A1-7600System Management with the SINAUT LSA Substation Control and Protection System LSA 1.4.9 E50001-K5701-A491-A1-7600

    LSADIAG - Testing and Diagnostics System for SINAUT LSA LSA 1.5.2 E50001-K5701-A521-A1-7600Substation Control and ProtectionLSACONTROL - Control and Monitoring LSA 1.5.3 E50001-K5701-A531-A1-7600LSAPROCESS - Process Information Analysis LSA 1.5.5 E50001-K5701-A551-A1-7600

    LSA 678 Standard Cubicle LSA 1.6.1 E50001-K5701-A611-A1-7600

    * Information on additional equipment for 7SJ600/601

    Catalog Index of the Power Transmission Distribution Group

    Responsible forTechnical contents: Hans Heining-TriebsSiemens AG, EV S V13, NrnbergGeneral editing: Claudia Khn-SutionoSiemens AG EV BK T, Erlangen

    24 Siemens LSA 2.1.15 1997

  • Conditions of Sale and Delivery Export RegulationsTrademarks DimensionsConditions of Sale and Delivery

    Export Regulations Dimensions

    Subject to theGeneral Conditions of Supplyand Deliveryfor Products and Services ofthe Electrical and ElectronicIndustry and to any otherconditions agreed upon withthe recipients of catalogs.

    The technical data, dimensionsand weights are subject tochange unless otherwise statedon the individual pages of thiscatalog.The illustrations are forreference only.We reserve the right to adjustthe prices and shall charge theprice applying on the date ofdelivery. En 1.91a

    In accordance with the presentprovisions of the German Ex-port List and the US CommercialControl List, export licences arenot required for the productslisted in this catalog.

    An export licence may how-ever be required due to country-specific application and finaldestination of the products.Relevant are the export crite-ria stated in the delivery noteand in the invoice subject to apossible export and reexport li-cence.Subject to change without no-tice.

    All dimensions in this catalogare given in mm (inch).

    Trademarks

    All product designations usedare trademarks or productnames of Siemens AG or ofothersuppliers.

    Siemens online!

    The Power Transmission and Distri-bution Group can also be found inthe Internet:http://www.ev.siemens.de

    Order No.: E50001-K5712-A251-A2-7600

    Printed in GermanyKG K 0697 6.0 24 EN321542 U0564

  • BereichEnergiebertragung und -verteilungGeschftsgebiet SekundrsystemePostfach 4806D-90026 Nrnberg

    Siemens Aktiengesellschaft Order No.: E50001-K5712-A251-A2-7600

    Your Siemens representative