7 Heat pumps sizing

heat pump characteristics

testing & operation conditions

balance point

storage size

hydraulics

Page 2: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

2/51

Heat pump

velk QPQ

el

k

P

QCOP

elkv PQQ

COPQQ kv

11

Qv

Qk

Pel

source side

sink side

extracted heat

rejected heat

Page 3: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

3/51

Heat pumps: ground source (borehole)

Page 4: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

4/51

Heat pumps: ground source (ground HX)

Page 5: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

5/51

Heat pumps: water source (water well)

Page 6: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

6/51

Heat pumps: air source (ambient)

Page 7: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

7/51

Types of heat pumps on the market

Page 8: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

8/51

The trend is air source

Page 9: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

9/51

... also sanitary hot water HP increase

Page 10: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

10/51

Heat pumps market in Europe

Page 11: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

11/51

Top ten countries is the market

Page 12: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

12/51

Heat pump parameters

heat output, heat capacity Qk [kW] – heat output from condenser

coefficient of performance COP [-]

- electric power Pel [kW]

- evaporator input = source output Qv [kW]

at given boundary conditions

-

and

-

tv1

tv1

tk2

tk2

Page 13: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

13/51

0

2

4

6

8

-10 -5 0 5 10

t v1 [°C]

Qk,

Pel

[kW

]

50 °C

35 °C

50 °C

35 °C

1

2

3

4

5

-10 -5 0 5 10

t v1 [°C]

et [

-]

50 °C

35 °C

Air-water heat pump characteristics

tk2

tk2

air-water air-water

CO

P [

-]

Page 14: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

14/51

Air-water heat pump characteristics

elec

tric

po

wer

, hea

tin

g c

apac

ity

[kW

] conden.output

temperature

ambient air temperature

Page 15: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

15/51

Air-water heat pump characteristics

CO

P [

-]

ambient air temperature

Page 16: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

16/51

2

3

4

5

6

-5 0 5 10 15

t v1 [°C]

et [

-]

50 °C

35 °C

0

2

4

6

8

10

12

-5 0 5 10 15

t v1 [°C]

Qk,

Pel

[kW

]

50 °C

35 °C

50 °C

35 °C

Brine-water heat pump (ground source)

tk2

tk2

brine-water brine-water

CO

P [

-]

Page 17: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

17/51

Brine-water heat pump (ground source)

source temperature

hea

tin

g c

apac

ity

[kW

]

conden.output

temperature

Page 18: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

18/51

Water-water heat pumph

eati

ng

cap

acit

y [k

W]

source temperature

conden.output

temperature

Page 19: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

19/51

Testing of heat pumps

EN 14511 - Air conditioners, liquid chilling packages and heat pumps

with electrically driven compressors for space heating and cooling.

EN 14511-1: dtto - Terms and definitions

EN 14511-2: dtto - Test conditions

EN 14511-3: dtto – Test methods

EN 14511-4: dtto - Requirements

EN 16147 – Heat pumps with electrically driven compressors.

Testing and requirements for marking of domestic hot water units

Page 20: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

20/51

Testing conditions

EN 14511: water-water W/W (W10 / W35)

nominal: 10/35 °C 10/45 °C

operation: 15/45 °C 10/55 °C

EN 14511: brine-water (ground-water) B/W (B0 / W35)

nominal: 0/35 °C 0/45 °C

operation: 5/35 °C 5/45 °C 0/55 °C

-5/45 °C

EN 14511: air-water (ambient air) A/W (A2 / W35)

nominal: 7/35 °C 7/45 °C

operation: 2/35 °C 2/45 °C 7/55 °C

-7/35 °C -7/45 °C -7/55 °C

-15/35 °C -15/45 °C

Page 21: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

21/51

21/26

Requirements on heat pump

Quality label EHPA (European Heat Pump Association)

minimum COP from testing according to EN 14511 in respected lab

brine-water B0/W35 COP > 4.3

water-water W10/W35 COP > 5.1

air-water A2/W35 COP > 3.1

declaration of sound power level

documentation: planning, service and operation guides in local language

customer service network, 24 h reaction time on customer complaints

2 years full warranty, spare parts inventory available for 10 years in stock

Page 22: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

22/51

Seasonal performance factor

totel,

hwsh,

Q

QSPF

hot water

space heating

COP

SPF

HPel,

HP

Q

QCOP

Qel,tot

Qsh,hw

heat pump

back-up

Qel,HP Qel,aux Qel,bu

QHP

Page 23: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

23/51

RES directive, minimum SPF

heat pumps consume electric energy

produced mainly from fossil fuels (primary non-renewable energysource)

he electricity production efficiency

european average 45.5 % SPF > 2.5

if SPF < 2.5 ... better to use fossil fuels directly by combustion

e

SPFh

115,1

Page 24: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

24/51

EN 15450 – Annex C (informative)

Page 25: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

25/51

Operation modes

monovalent operation

only heating device

parallel bivalent operation

under bivalent temperature

(balance point) back-up heater is

switched-on

low temperature systems

monovalent

bivalent parallel

HP

HP

BU

Page 26: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

26/51

Operation modes

alternatively bivalent operation

under bivalent temperature back-up

replaced heat pump. for high

temperature heating systems

bivalent alternative

the balance point = temperature

under which the back-up heater is required

HP

BU

Page 27: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

27/51

Operation modes

monoenergetic operation

e.g. bivalent operation of electric heat pump with electroboiler

(integrated in one device)

balance point

according to heat output (dimensioning)

acc. heating water temperature

sufficient heat output from heat pump

high temperatures of heating water needed, which couldnt be

supplied by heat pump, esp. in extreme winter

Page 28: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

28/51

Heat pump sizing

determination of heat pump type

available heat source

determination of (condenser) heat output Qk (for space heating)

building heat loss

heat output for hot water

design flow temperature

design source temperature

Page 29: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

29/51

Balance point according to temperature

0

10

20

30

40

50

60

70

80

90

100

-15 -10 -5 0 5 10 15 20

Tep

lota

pří

vod

vod

y [°

C]

Venkovní teplota [°C]

90/70 °C

75/55 °C

60/45 °C

55/40 °C

45/35 °C

35/30 °C

max output temperature

outdoor temperature [°C]

flow

tem

pera

ture

[°C

]

example of air source HP

radiators

underfloor heating

Page 30: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

30/51

0

5

10

15

20

25

30

-12 -8 -4 0 4 8 12 16 20

ambient temperature t e [°C]

hea

t o

utp

ut Q

k [k

W],

hea

t lo

ad Q

l [kW

]

output temperature 35 °C

output temperature 50 °C

heat load

Balance point according to heat output

balance point

ground source HP

Qk

QL

QL, des

Page 31: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

31/51

0

5

10

15

20

25

30

-12 -8 -4 0 4 8 12 16 20

ambient temperature t e [°C]

hea

t o

utp

ut Q

k [k

W],

hea

t lo

ad Q

l [kW

]

output temperature 35 °C

output temperature 50 °C

heat load

Balance point according to heat output

balance point

air source HP

Qk

QL

QL, des

Qk,bal

Page 32: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

32/51

Balance point determination

design heat load QL,des

calculation according to EN 12 831 for design external

temperature (e.g. -12 °C, -15 °C, -18 °C in CZ )

heat output at balance point Qk = QL

e.g. from desired fraction 60 to 100 % Qk,bal / QL,des

ei

L

desei

desL

tt

Q

tt

Q

,

,

balei

balk

tt

Q

,

,

desei

desL

balkibale tt

Q

Qtt ,

,

,, if Qk = konst

if Qk = konst - graph/

0

5

10

15

20

25

30

-12 -8 -4 0 4 8 12 16 20

ambient temperature t e [°C]

hea

t o

utp

ut Q

k [k

W],

hea

t lo

ad Q

l [kW

]

output temperature 35 °C

output temperature 50 °C

heat load

Page 33: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

33/51

Example

family house

design load 15 kW for

design temperature -15 °C

heat pump (SE WPL18)

heating system 50/40 °C

determine the balance point

balance point heat output

balance point power input

balance point COP

Qk =10.5 kW

Page 34: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

34/51

20

25

30

35

40

45

50

55

-15 -10 -5 0 5 10 15 20

ambient temperature t e [°C]

flo

w t

emp

erat

ure

[°C

]Flow temperature

desei

deseewdeswdesww

tt

tttttt

,

,min,1,1,11

flow tw1

return tw2

42 °C

Page 35: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

35/51

Power input at balance point

for balance power point

tv1 = -5 °C, tk2 = 42 °C

P35 = 3.3 kW

P50 = 4.5 kW

355035

3550

1

351

PP

t

PP

w

tw

3550

3513550351

w

tw

tPPPP

balance power point

P42 = 3.9 kW

interpolation

Page 36: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

36/51

Example

COP35

COP50

3550

50 15035501

w

tw

tCOPCOPCOPCOP

Page 37: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

37/51

Example

family house

design load 15 kW for

design temperature -15 °C

heat pump (SE WPL18)

heating system 50/40 °C

determine the balance point

balance point heat output

balance point power input

balance point COP

Qk =10.5 kW

balance power point

P42 = 3.9 kW

balance point COP =

Page 38: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

38/51

Heat pump sizing – coverage of demand

-12

-10

-8

-6

-4

-2

0

2

4

6

8

10

12

0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220

days

ou

tdo

or

tem

per

atu

re te

[°C

]

100%

25%

50%

75%

60%

0%

Page 39: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

39/51

Heat pump sizing – coverage of demand

0,0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

1,0

0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0

a

ar

residential sector

based on heating

demand

HP heating output / design heating load

supp

lied

ener

gy b

y H

P /

heat

ing

dem

and

Page 40: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

40/51

Heat pump sizing (ground source)

dimensioning heat output (independent on ambient conditions)

50 % heat loss - coverage 85 % heat demand

60 % heat loss – coverage 93 % heat demand

70 % heat loss - coverage 97 % heat demand

water-water

Page 41: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

41/51

Heat pump sizing (air source)

dimensioning heat output (dependent on ambient conditions)

50 % heat loss - coverage 75 % heat demand

60 % heat loss – coverage 85 % heat demand

70 % heat loss - coverage 92 % heat demand

air-water

Page 42: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

42/51

Heating capacity control

usual heat pumps

start-stop regime

cycling = reduction of durability compressor

elimination cycling

undersizing

heat storage – sizing of store for minimum operation time of heat

pump

heat pump with heating capacity control

compressor speed control

possibility for monovalent operation

Page 43: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

43/51

Heating capacity control

0

5

10

15

20

25

30

-12 -8 -4 0 4 8 12 16 20

ambient temperature t e [°C]

hea

t o

utp

ut Q

k [k

W],

hea

t lo

ad Q

l [kW

]

output temperature 35 °C

output temperature 50 °C

heat load

Without capacity control

With capacity control

100%

30%

backup

backup

part load – cycling

part load – cycling

Page 44: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

44/51

Heat storage for heat pump

oversized storage for most of operation time

balancing heat output and heat load

reduction of frequency compressor on/off (1 x 10 min)

longer durability of compressor

heat source for outdoor units (air-water)

antifreeze protection

Page 45: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

45/51

Heat storage for heat pump

hydraulic decoupling of heat pump from load circuit

hydraulic shunt

heating systems can’t influence HP circuit

providing required (higher) flowrates at condenser

heat pump storage tank

heating

system

Page 46: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

46/51

Sizing of storage tank

balance to reduce on/off frequency

minimum operation time period Dt

increase of temperature Dt in store during operation of heat pump

heat stored during operation of heat pump

tcVQQ HPstored DD t

Page 47: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

47/51

Sizing of storage tank

specific volume

Dt [s] minimum operation time: 15 min

Dt [K] increase of store temperature: 3 - 5 K

usually 15 to 30 l/kW

thermal capacity (momentum) of heating system results in lower

volume requirement

tcQ

V

HP D

D

t1000

Page 48: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

48/51

Example

calculate heat storage volume for balance point heat output 10.5 kW

minimum operation time period Dt = 15 min

increase of temperature Dt in store 3 K

tcQV HP

D

D

t1000

34187998

60151000]kW[]m[ 3

HPQV

V = 754 l

Page 49: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

49/51

Integration of store

electronically

controlled pump

heat pump

control

temperature sensor

pump

bypass valve

heating system

storage tank

Page 50: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

50/51

Hydraulics

with two stores

heating water store, hot water store

bivalent (back-up) heater inside heat pump

SH HWEL.HEATER

heating

system

HW

CW

Page 51: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

51/51

Hydraulics

with central store

hot water heated in heat exchanger immersed in heating water store

volume

bivalent (back-up) heater: immersed in store

EL.HEATER

HEAT PUMP

heating

system

HW

CW

Page 52: 7 Heat pumps sizing - cvut.czusers.fs.cvut.cz/tomas.matuska/wordpress/wp... · 7 Heat pumps sizing heat pump characteristics testing & operation conditions ... calculation according

52/51

Guides for design

low temperature heating < 45 °C

floor heating, wall heating

radiators with larger surface

pool water heating

hot water

low temperature 45 °C

air-water: advantage in summer, high ambient temperatures

brine-water: reduction of borehole regeneration (!)