Water Molecules
Remarkable Properties ofWater1.Water vapor steam has a high energy content and is an effective
medium for transferring energy in industrial plant operations,
buildings, and homes
2. Great heat capacity than many substances, so it is an effective heat
transfer medium. For each incremental change in temperature, waterabsorbs or release more heat.
3. Water also releases more heat upon freezing than do other
compounds. It is the only chemical compound that is present in the
natural environment in all 3 states of matter.
4. High surface tension this causes water to rise in a capillary tube.This physical property (capillarity) is partly responsible for the system
of circulationdeveloped by living plants through their roots and tissue
system.
8/9/2019 7. Boiler Feed Water Conditioning
3/55
Water Molecules
Remarkable Properties ofWater
5. High dielectric constant water molecules in contact with a crystal
orient themselves to neutralize the attractive forces between the ions
in the crystal structure. The liberated ions are then hydrated by these
water molecules. This keep ions from recombining and thus
precipitating from solution.6. Osmotic pressure This important phenomenon occurring in water
solutions related to dissolved matter (solutes), rather than to water
(solvent) is osmotic pressure.
If 2 aqueous solutions are separated by a membrane, water will pass
from the more dilute into the more concentrated one. This important
process controls the performance of all living cells.
8/9/2019 7. Boiler Feed Water Conditioning
4/55
Water Molecules
Remarkable Properties ofWater
The formula for water H2O- by its self tells us only its composition and
molecular weight. It does nothing to explain the remarkable properties.
The remarkable properties of water are the result of its unique molecular
arrangement.
105o
8/9/2019 7. Boiler Feed Water Conditioning
5/55
Water Molecules
Two hydrogen atoms are located 105O apart, adjacent to the oxygen
atom, so that the molecule is asymmetrical, positively charged onthe hydrogen side and negatively charged on the oxygen side. For
this reason water is said to be dipolar.
This causes the molecules to agglomerate, the hydrogen of one
molecule attracting the oxygen of a neighboring molecule. The
linking of molecules resulting from this attraction force is calledhydrogen bonding.
One of the consequence of hydrogen bonding is that molecules
cannot leave surface readily
Hydrogen bonding produces crystal arrangement that causes ice to
expand beyond its original liquid volume.
8/9/2019 7. Boiler Feed Water Conditioning
6/55
Water
Water - The universal solvent
Water is a poor conductor of electricity
As more ions dissolve, water becomes a better conductor
As the conductivity of water increases, the potential for corrosion andscale formation increases
The polar charges on the water molecule make it an exceptional
solvent
8/9/2019 7. Boiler Feed Water Conditioning
7/55
Water
Water - The universal solvent
Water contains various types of impurities
1. Dissolved solids magnesium, calcium, iron, silica
2. Dissolved gases oxygen, carbon dioxide/monoxide, ammonia3. Suspended solids silts, clay, sand
8/9/2019 7. Boiler Feed Water Conditioning
8/55
Effect ofWater Impurities on Boiler Operation
Certain impurities have harmful effects on effective and economical boileroperation when they are present in feedwater.
Scale forming impurities
1. Dissolved calcium carbonates, calcium sulphate, magnesium
carbonate, magnesium chloride, magnesium sulfate and silica.
2. Some suspended solids particularly salts of a wide variety ofchemical make up coming from industrial wastes which abound in
the waters from rivers.
Corrosion
1. Corrosion results from dissolved carbon dioxide and oxygen.
2. Grease and oil from animal or vegetable sources in feedwater has a
specific ultimate corrosive effect.
3. Much of the organic and sewage content of impure water also tends
to increase corrosion.
8/9/2019 7. Boiler Feed Water Conditioning
9/55
How Scale is Formed
The basic types of scales encountered in the steam boiler
are salts of calcium and magnesium. The troublesome
scales are usually carbonate and sulfates.
Silicate scale will develop in high pressure operations where
there is appreciable clay or source of alumina.
Scale can be form either by physical attachment to the
metal of precipitated calcium or magnesium salts or by
crystallization on the metal direct from the boiler water.
8/9/2019 7. Boiler Feed Water Conditioning
10/55
Scale Control
Scale control are generally concerned with the control of carbonate or
salts of calcium and magnesium.
External treatment of the feedwater can reduce sources of scales to
such low level that subsequent treatment is reduced to minimum.
8/9/2019 7. Boiler Feed Water Conditioning
11/55
Water Treatment
The objective of water treatment is to eliminate internal waterconditions that lead to scale formation, corrosion, embrittlement andcarryover.
The prevention of scale formation becomes a problem of puttingthese salts into such a condition that they cannot or will not deposit
in either way. The best answer therefore, lies in treatment of the boiler water in
accordance with its content of scale forming salts or solids.
One treatment is based on the fact that it is possible to precipitatecalcium and magnesium salts in a form that will no longer crystallizeon the boiler metal to form scale.
8/9/2019 7. Boiler Feed Water Conditioning
12/55
Water Treatment
Generally water treatment is approached two ways:
1. External water treatment
2. Internal treatment
8/9/2019 7. Boiler Feed Water Conditioning
13/55
Water Treatment
External water treatment process
1. Clarification suspended solid removal
- Coagulation
- Flocculation
- Sedimentation
- Filtration
2. Softening hardness removal
- Precipitation
- Ion exchange- Demineralizer
8/9/2019 7. Boiler Feed Water Conditioning
14/55
Water Treatment
External Water Treatment
Clarification
Turbid raw water contains suspended matter - both settleable solids
(particles large enough to settle quiescently) and dispersed solids
(particles which will nor readily settle).
A significant portion of these nonsettleable solids may be colloidal.Each particle is stabilized by negative electric charges on its surface,
causing it to repel neighboring particles just as magnetic poles repel
each other.
Above prevents these charged particles from colliding to form larger
masses, they do not settle.
8/9/2019 7. Boiler Feed Water Conditioning
15/55
Water Treatment
ExternalWater TreatmentClarification - removal of suspended solids
1. Coagulation
Colloidal species encountered in raw water include clay,silica, ironand other heavy metals, color and organic solids.
The destabilization (charge neutralization) of the colloidal
particles in the water caused by the addition of the coagulantwhich neutralizes the electrical charges of the particles.
Colloids are categorized as hydrophobic (water hating) orhydrophilic (water loving).
Hydrophobic colloids do not react with water. Most naturalclay are hydrophobic.
Hydrophilic colloids react with water. The organics causingcolor are hydrophilic.
Aluminum salts, iron salts, or polyelectrolytes are thechemical coagulants usually used.
Coagulant used here ferric chloride
8/9/2019 7. Boiler Feed Water Conditioning
16/55
Water Treatment
Coagulation cont
Colloids always require coagulation to achieve aneffective size and settling rate
Mixing is required to supplement coagulant addition todestroy stability in the colloidal system.
Zeta potential is the measurement of colloidal particlecharge strength. For natural water in a ph range of 5 to 8,the zeta potential is generally -14 to -30 mv. The morenegative the number, the stronger the particle charge.
8/9/2019 7. Boiler Feed Water Conditioning
17/55
Water Treatment
2. Flocculation The coagulated particles formed by the agglomeration of
several colloids may not be large enough to settle ordewater at the desired rate.
A flocculant gathers together these particles in a net,bridging from one surface to another and binding the
individual particles into large agglomerates (grouping andcompacting of coagulated particles into largerassemblages called floc)
Alum, iron salts, and high molecular weight polymers arecommon flocculants
Flocculant used here sodium aluminate
8/9/2019 7. Boiler Feed Water Conditioning
18/55
Water Treatment
3. Sedimentation Removal of suspended solids from water by gravitational
settling.
The velocity of the water must be reduced to a point where
solids will settle by gravity if the detention time in the
sedimentation vessel is great enough. Settling rate of particles is affected by their size, shape, and
density as well by the liquid they are settling through
As a particle settles, it accelerates until the frictional drag of its
surface against the liquid equals the weight of the paticle in the
suspending liquid.
8/9/2019 7. Boiler Feed Water Conditioning
19/55
Water Treatment
Sedimentation contSteps in settling of particulates in water
1. Particles at first fall freely through the water.
2. As they come closer together, their rate of sedimentation is
restricted, and settled sludge volume increases. In the final
stages, compaction or compression becomes very slow- Hindered settling is reached as particulates become so
close to each other that the passages between them restrict
the ability of water to escape from the sludge
- Compaction occurs naturally, but slowly, by gravity and by
dehydration of the particulates
8/9/2019 7. Boiler Feed Water Conditioning
20/55
Water treatment
Polyelectrolytes Polyelectrolytes are large water soluble organic molecules made up of
small building blocks called monomers, repeated in a long chain.
Structure contain an ion exchange sites which give the molecule an
ionic charge.
Cationic positive charge, Anionic negative charge They react with colloidal material in the water by neutralizing charge or
by bridging (tying together) individual particles to form a visible,
insoluble precipitate or floc
Polyelectrolytes used here -
8/9/2019 7. Boiler Feed Water Conditioning
21/55
Water Treatment
Test Used to Select Best Chemical and Dosage Level for Clarification
1. Jar test (Used for stream with 5000 mg/l suspended solids)
Jar Test
1. Measured coagulant is measured into a sample of turbid waterwith a high degree of mixing [to disperse it in the water and
promote increased frequency of collisions. The duration may be
short, less than 1 min. The actual mixing time is refined as the test
regimen proceed (in essence, defining the optimum G factor.
2. Particle growth starts to occur because of charge neutralization.3. Additional coagulant or flocculant is added during the last few
seconds of rapid mix if required
8/9/2019 7. Boiler Feed Water Conditioning
22/55
Water Treatment
Test Used to Select Best Chemical and Dosage Level for Clarification
1. Jar test (Used for stream with 5000 mg/l suspended solids)
Jar Test
4. In the slow mix period which follows, floc building proceeds untilthe floc becomes so big that shear forces finally overcome the
bridging forces, breaking the floc apart, limiting floc size
5. After slow mixing for optimum period of time, found only by
repeated test (usually 5 to 20 mins), the jars are allowed to settle
for 5 to 10 mins.
8/9/2019 7. Boiler Feed Water Conditioning
23/55
Water Treatment
Cylinder Test
Designed to indicate how fast the suspended solids will settle
1. The slurry sample is placed in a cylinder, chemical is added and
cylinder is stoppered
2. Cylinder is gently inverted several times to mix3. After mixing cylinder is set upright and the interface between the
water and the settling solids observed.
4. Time and solids level are recorded
5. Data are plotted on a graph.
Note: On both tests different chemicals [and at different dosages] are
run side by side to determine most effective products.
8/9/2019 7. Boiler Feed Water Conditioning
24/55
Water Treatment
ExternalWater Treatment
Filtration -Water is filtered by passing it through fine strainers or other
porous media to remove suspended solids mechanically
1. Granular Media Filtration
Generally applicable for removal of suspended solids in the
5 to 50 mg/l range where an effluent of less than 1 JTU
Medium normally silica sand or crushed anthracite
Backwashing water or water & air
Bed coarse to fine grain medium
2. Multimedia Filter Beds
Two layers (Dual media) Provide coarse to fine filtration in a down flow pattern
Medium Anthracite grains and silica sand
Different grain size and specific gravity
8/9/2019 7. Boiler Feed Water Conditioning
25/55
Water Treatment
ExternalWater Treatment
Filtration
3. Septum Filters
Often referred to as DE (diatomaceous earth) filter
Above is used as a filter precoat
Applied as slurry to a porous septum to produce a filteringsurface
8/9/2019 7. Boiler Feed Water Conditioning
26/55
8/9/2019 7. Boiler Feed Water Conditioning
27/55
Water Softening
Hardness Removal by Precipitation
Stability Index roughly predict whether a particular water will tend to
corrode metal or form a CaCO3 scale
Precipitation process makes use of the solubility product of a compoundcontaining an ion or radical that is considered detrimental, and that
should be removed before water is put to use
Key variable in precipitation
1. solubility
2. particle size3. temperature
4. time
8/9/2019 7. Boiler Feed Water Conditioning
28/55
Water Softening Process
Hardness Removal by Precipitation
Treatment chemicals are generally used to lower solubility of scale
forming impurities and to precipitate them as sludge.
Either lime or caustic soda gives hydroxide for precipitation of
magnesium hydroxide.
Carbonate to precipitate calcium is usually added as soda ash.
Some carbonate is available when natural bicarbonate is converted to
carbonate form by use of lime or caustic soda.
When raw water does not contain enough magnesium to reduce silica
content, it is added as magnesium oxide or a component of dolomitic
lime.
8/9/2019 7. Boiler Feed Water Conditioning
29/55
Hardness Removal by Precipitation
Lime and Soda Ash Reaction
1. Lime removes carbonate hardness as insoluble calcium carbonate
Ca (HCO3)2 + Ca (OH)2 2CaCO3 + 2H2O
calcium bicarbonate calcium hydroxide calcium carbonate water
2. Soda-ash is the second step in removing noncarbonated hardness
CaSO4 + Na2CO3 CaCO3 + Na2SO4
calcium sulfate sodium carbonate calcium carbonate sodium sulfate
3. Soda ash (sodium carbonate) also reacts with calcium chloride to form
calcium carbonateCaCl2 + Na2CO3 CaCO3 + 2NaCl
calcium chloride sodium carbonate calcium carbonate sodium chloride
Cold process softening is the term used when these reactions are carried
out at room temperature.When water is heated above room temperature,
it is called hot process softening. Usually, above 212oF
8/9/2019 7. Boiler Feed Water Conditioning
30/55
Water Softening Ion Exchange
Ion exchange
Removes unwanted ions from a raw water by transferring them to
a solid material, called an ion exchanger, which accepts them
while giving back an equivalent number of a desirable species
stored on the ion exchanger skeleton.
Ion exchangers sodium aluminosilicates, zeolite (greensand),
synthetic organic ion exchangers.
Ion exchangers used in water conditioning are skeleton like structure
having many ion exchange sites.
This insoluble plastic skeleton is an enormously large ion that is
electrically charged to hold ions of opposite charge
Types of ion exchangers cation and anion exchangers
8/9/2019 7. Boiler Feed Water Conditioning
31/55
Water Softening Ion Exchange
Ion exchange
Exchangers with negatively charged sites are cation exchangers
because they take up positively charged ions
2 types of operations sodium cycle and hydrogen cycle
Sodium cycle regenerated by sodium salt (ie NaCl)
Hydrogen cycle regenerated by Acid (ie H2SO4)
Anion exchangers have positively charged sites and take up negativeions. 2 general varieties weak base and strong base exchangers
Anion exchangers are regenerated using alkali (i.e. NaOH, NaCl)
Plastic structure is porous and permeable, so entire ion exchange
particle participates in the process.
8/9/2019 7. Boiler Feed Water Conditioning
32/55
Ion Exchange Operation
Cation Exchangers
Softening
Assume a unit, filled with styrene base resins, and start running
water through it. Calcium and magnesium ions in the water are
replaced with sodium ions from the resin. This is called sodium cycle
operation.
If hydrogen cycle is used, the calcium, magnesium, and sodium
ions in the water would be traded for hydrogen ions.
On both cases, the trading or exchange of ions continues until the
resin run out of ions to exchange. This is called breakthrough point
and when it occurs the exchanger is taken out of service.
8/9/2019 7. Boiler Feed Water Conditioning
33/55
Ion Exchange Operation
Regeneration
The first step in regeneration of the resins is backwashing.Whereas the normal flow is downward, this initial backwash of the
resin is upward. This upflow lifts the resin and scrubs off dirt and
debris.When the upflow is stopped the resin settles into a uniform
bed, decreasing the posibility of direct water flow through the bed
(channeling).
Next the regenerant chemical is added to the resin bed. Sodium
cycle units use salt at a concentration of 10 to 12 as regenerant.
Various acids are used for hydrogen cycle regeneration with sulfuric
and hydrochloric acid being the most common. Acid concentration islow at first with 2 % being maximum. Further into the process it may
reach 6 %.
8/9/2019 7. Boiler Feed Water Conditioning
34/55
Ion Exchange Operation
The amount of regenerant is calculated to provide the greatest
exchange capacity for the amount of chemical added
Once the regenerant has been added, the resin is rinsed, usually intwo stages to wash away excess regenerant. Now the resin is
ready for service and the cycle begins again.
A common method used in treatment today is stream softening
where the outlets of hydrogen and sodium cycle are combined.
Reason is to use the alkalinity in sodium cycle water to neutralize
the slight acidity in the hydogen cycle effluent.
8/9/2019 7. Boiler Feed Water Conditioning
35/55
Hardness Removal - Ion Exchange
Zeolite Softening Systems (sodium cycle operation)
Impurities that dissolve in water dissociate to form positively and negatively
charged particles known as ions. These impurities or compounds are
called electrolytes.
1. The positive ions are called cations because they migrate to thenegative electrode (cathode) in an electrolytic cell.
2. Negative particles are then anions since they are attracted to the anode.
3. These ions exist throughout the solution and act almost independently.
For example, magnesium sulfate (MgSO4) dissociates in solution toform positive magnesium ions and negative sulfate ions.
4. Generally, all natural waters contain electrolytes in varying
concentration.
8/9/2019 7. Boiler Feed Water Conditioning
36/55
Hardness Removal Ion Exchange
Zeolite Softening Systems (sodium cycle exchanger)
5. Ion exchange material has the ability to exchange one ion for another,
hold it temporary in chemical combination, and give it up to a strong
regenerating solution.
6. Since sodium zeolite method works by replacing calcium and magnesium
In the raw water with sodium, there is no precipitation of solids from the
water. The actual content of dissolved solids in the water is increased.
7. The treated water will contain sodium carbonate and bicarbonate from the
carbonate hardness And sodium sulfate, sodium chloride and sodium
nitrate from non-carbonate hardness.
8/9/2019 7. Boiler Feed Water Conditioning
37/55
Hardness Removal Ion Exchange
Zeolite Softening Systems (sodium cycle exchanger)
Chemical Reactions
1. Softening (exhaustion)
Sodium cation exchangers swap sodium ions for other metal ions
Ca2+ + Na2X CaX + 2Na+
Mg2+ + Na2X MgX + 2Na+
2. Regeneration (brining)
Regeneration restores exchanger capacity by replacing calcium
ions with sodium
2NaCl + CaX Na2X + CaCl22NaCl + MgX Na2X + MgCl2
8/9/2019 7. Boiler Feed Water Conditioning
38/55
Hardness Removal Ion ExchangeHydrogen Cycle Exchanger
The development of ion exchange that could be regenerated with acid
to exchange hydrogen ions for cations in water provided the first practicalChemical process for removal of sodium, potassium, and ammonia, all of
whose
salts are extremely soluble
Chemical Reactions
1. Softening (exhaustion)
Hydro cation exchangers swap hydrogen ions for metal cationsCa2+ + H2X CaX + 2H
+
Mg2+ MgX
Fe2+ FeX
2Na+ Na2X
2NH4+ (NH4)2X
Ca(HCO3)2 + H2X CaX + 2H2O + 2CO2CaSO4 + H2X CaX + H2SO4
8/9/2019 7. Boiler Feed Water Conditioning
39/55
8/9/2019 7. Boiler Feed Water Conditioning
40/55
Ion Exchange
Anion Exchanger
Anion exchange fall into 2 general categories weak base andstrong base. Strongly basic exchange material picks up acid radicals
and silica from a hydrogen unit, leaving essentially pure water
Weak Base Resins
Weak base exchangers dont take out carbon dioxide and silica.Theyremove strong acids by a process thats more like absorption than itis ion exchange. However the end result is the same, and efficiencyof strong acid removal is far superior to that of a strong base materialdoing the same job.
So weak base units are very useful when water is high in sulfatesand chlorides. In these cases they precede a strong base unit. Ifsilica isnt an objection, they handle the complete job ofdemeneralizing alone.
8/9/2019 7. Boiler Feed Water Conditioning
41/55
Anion Exchanger (cont)
Strong Base Resins
Strong base resins are available as either type I or type II.
Type II resins capacity and efficiency is somewhat higher
than type I.
But type I is commonly used because of 2 main reasons:
1. Type I exchangers are usually more stable
2. They reduce silica to lower residual in range of 0.02 ppm.
8/9/2019 7. Boiler Feed Water Conditioning
42/55
Ion Exchanger
Anion Exchanger
Chemical Reaction
1 Softening (exhaustion)
Anion exchanger takes on sulfate anion, gives up hydroxide to
form water
H2SO4 + X(OH)2
XSO4 + 2H2OStrong base anion exchanger takes on silica ion, gives up
hydroxide to form water
2H2SiO3 + X(OH)2 X(HSiO3)2 + 2H2O
2. RegenerationRegeneration with caustic restores capacity for hydroxide
exchange
XSO4 + 2NaOH X(OH)2 + Na2SO4
8/9/2019 7. Boiler Feed Water Conditioning
43/55
Demineralization
Demineralization
Generally refer to external treatment scheme where relatively pure
water is desired
Conventional demineralization unit cation (hydrogen form)
exchanger follows by anion (strong base) exchanger
In this process, the anions in the cation effluent are exchanged for
hydroxide.
If there are cations present, such as sodium, the effluent will contain
sodium hydroxide and this is the most prominent factor affecting the
quality of finished demineralized water.
8/9/2019 7. Boiler Feed Water Conditioning
44/55
Basic Types of Demins & Resin Used
8/9/2019 7. Boiler Feed Water Conditioning
45/55
Deaeration
Dissolved oxygen in the feedwater is one major source of corrosion
in a steam boiler.
Oxygen is a dissolved gas that does not react chemically with water
and become less and less soluble as water temperature increases.
Oxygen can be removed by bringing water to the boiling point
corresponding to its operating pressure.
8/9/2019 7. Boiler Feed Water Conditioning
46/55
Deaeration
Deaerator
Steam deaerator break up water into a spray or film and then sweepthe steam across and through it to force out dissolved gases likeoxygen or carbon dioxide.
A typical deaerator has a heating and deaerating section plus storage
for hot deaerated water. Sometimes a separate tank is providedalongside or underneath unit to hold 10 minutes storage at ratedcapacity.
Steam deaerators fall into 2 broad types.
1. Spray
2. tray
3. combination of both.
8/9/2019 7. Boiler Feed Water Conditioning
47/55
Internal Water Treatment
Scale prevention
Phosphates
Phosphates are known to be effective precipitating agents.When used,
the calcium and magnesium salts causing scale formation are
precipitated in such form that there is negligible tendency to formadherent deposits.
Advantages:
Precipitate calcium and magnesium as insoluble phosphate salts which
has no marked scale forming tendencies. When used in conjunction with suitable dispersants, the precipitated
phosphates become integrated parts of the sludge formed.
Requires relatively lower concentration.
8/9/2019 7. Boiler Feed Water Conditioning
48/55
Internal Water Treatment
Chelants
Chelants are also used to minimize scale formation in boilers. They are
the prime additives in solubilizing boiler water treatment program.
Advantages:
Ability to complex with, and prevent the deposition of many cations(hardness and heavy metals) under boiler water conditions by locking the
metal into a soluble organic ring structure.
Boilers with higher evaporation rates create conditions suitable for iron
oxide deposition. Chelants have the ability to complex iron deposits.
Forgiving type ability to remove deposits that may form when feedwaterquality or treatment control deviates
8/9/2019 7. Boiler Feed Water Conditioning
49/55
Internal water Treatment
Dispersant
Boiler water dispersants are used in conjunction with precipitating(phosphate) or solubilizing (chelant) internal treatment programs.
Dispersants prevent deposition of solid particles and precipitates onheat transfer surfaces. Rather, a fluid sludge forms which collects inthe boiler mud drum and exits via blowdown.
Solid particles in boiler water can be carryover from raw water filters,clarifiers, or lime softeners, corrosion products from condensate
returns, or calcium and magnesium precipitates resulting fromhardness in feedwater.
8/9/2019 7. Boiler Feed Water Conditioning
50/55
8/9/2019 7. Boiler Feed Water Conditioning
51/55
Condensate Treatment
Corrosion in condensate return lines presents 2 problems:
1. Equipment damage and frequent replacement of steam traps andcondensate lines
2. Corrosion products are frequently carried back into steam generating
equipment and can result in increased internal deposition and tubefailure within the boiler.
8/9/2019 7. Boiler Feed Water Conditioning
52/55
Condensate Treatment
The major causes of condensate corrosion are dissolved oxygen andcarbon dioxide
Dissolved oxygen attack is characterized by tuberculation, pitting, and
iron oxide buildup
Dissolved oxygen can enter the condensate system with boiler feedwater
or by direct infiltration
Carbon dioxide corrosion is characterized by a general thinning or
grooving attack, normally resulting from carbonate and bicarbonate
alkalinity decomposition in the boiler which liberates CO2
Carbon dioxide in the presence of water, forms carbonic acid
which can cause acidic attack
8/9/2019 7. Boiler Feed Water Conditioning
53/55
Condensate Treatment
Condensate corrosion can be controlled by:
neutralizing amines
filming amines
combination of both
8/9/2019 7. Boiler Feed Water Conditioning
54/55
Condensate Treatment
1. Neutralizing amines directly react with dissolved carbon dioxide,thereby raising ph and eliminating acidic attack. It will not preventattack by dissolved oxygen
2. Filming amines function by placing a protective
barrier film between the metal and corrosive environment
3. Combination treatment jointly employ neutralizing and
filming amines. The neutralizer functions to distribute the filmer toinsure against an over buildup and to promote the detergency of thefilming amine.
8/9/2019 7. Boiler Feed Water Conditioning
55/55
Condensate Treatment
Control1. Ph effect of neutralization can be seen directly
2. Iron/copper values indicate any increase or decrease in
corrosion
3. Corrosion coupon this are preweighed test specimens which are
inserted into condensate bypass piping. Periodically removed andreweighed.