6.2. F-MPC60B_manual_English (1).pdf

Embed Size (px)

Citation preview

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    1/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    2/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    3/68

    The accessories indicated below are appended to this product. Please confirm this.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    4/68

    Contents

    1. Handling precautions 1

    2. Mounting and wiring2.1 Panel cutting and mounting 3

    2.2 Wiring 32.3 Grounding 4

    2.4 Wiring of communication line 5

    2.5 Terminal assignments 6

    2.6 External connection of each model 10

    3. Specification3.1 Model list 11

    3.2 Type 11

    3.3 Specification 12

    3.4 External appearance drawing 16

    4. Operation and handling

    4.1 Names of controls on front panel and their functions 194.2 Operation and selection of the key switch 20

    4.3 Operation when setting 21

    4.4 Operation in normal state 22

    4.5 Reset method of the measurement hysteresis maximum value, the measurement hysteresis minimum value

    and the integrated value 22

    4.6 Operation at testing time 23

    5. Type and functions of external input/output5.1 Type and functions of external input 24

    5.2 Setting method of external input 25

    5.3 Types and function of External output 26

    5.4Setting method of external output 27

    5.5Description of ON/OFF/trip output motions 28 6. Measures to be taken when relay motion or equipment failure occurs, and

    Reading of code display6.1 Outline of code display 29

    6.2 Reading of code display and measures to be taken 29

    6.3 The method of relay test 31

    7. Maintenance and inspection7.1 Inspection item 32

    7.2 Design life 32

    Appendix Table 1 List of setting and history items 33

    Appendix Table 2 List of operation in normal state 41Appendix Table 3 List of setting items for setting value entry 45

    Appendix Table 4 The relay test 49

    Appendix Figure 1 Characteristic of an OC-relay 53

    Appendix Figure 2 Outside connection diagram collection 59

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    5/68

    Chapter 1 handling precautions

    1.1 Outline and characteristic of "UM43FG-E5AK type"

    The F-MPC60B is a digital multi-functional digital relay for high-voltage distribution facilities. It is a compact unit produced by combining

    the function of protection, measurement, control, kWh pulse output and transmission with a transducer (provided only when the relay

    incorporates transducer output).

    High reliabilityBy the combination of conventional individual devices, this device realized the following function with difficult realization. The F-

    MPC60B improved the function that records the history and fault data.

    Improved maintainabilityThe F-MPC60B reduced the time of the relay test by using the trial output for the test. To prevent operation errors such as a mistaken

    disconnect of a circuit the F-MPC60B adopted the fail-safe function and the auto monitoring function.

    Flexibility

    The F-MPC60B is able to change the circuit conditions, such as VT and CT ratio, by changing the setting value.

    The F-MPC60B realizes the standardization of wiring in the distribution facilities, reduces the cost of the wiring and the maintenance.

    So, the high economic efficiency is demonstrated in the engineering, production and maintenance division by using F-MPC60B.

    The features: the F-MPC60B is able to apply to "the 3-pahse 4-wire system for the high or low voltage facilities" and " the 3-pahse 3-wire

    system for the high or low voltage facilities ".

    Please carefully read this manual before you use the product in order to use it safely and correctly.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    6/68

    1.2 Handling precautions

    The F-MPC60B is used in both 100V AC and 100V DC. Provided when the F-MPC60B is used by AC power, use in combinationwith UPS (Power Supply: option) or the F-MPC60 100V AC power supply unit for the F-MPC60B.

    The rated CT secondary current is AC 5A. The F-MPC60B detects the current of main circuit: I A, IB, IC and the earth leakage

    current: I0. By considering the application circuit and the number of CT, use the F-MPC60B correctly.

    (1) Precautions for creating a connection diagram, mounting and wiring Equipment error output is a normally closed contact output (excited in steady state, and if an error occurs, excitation terminates

    and contact is closed). Therefore, a lag of around 100ms occurs before the contact opens, since the power was ON (in operation).Consider the use of a timer, if necessary, when creating the external sequence. (See section 2.6.)

    If the trip coil open circuit monitor function will not be used set Trip-coil open circuit monitor function at No in the setting.

    Refer the code No 63 in the appendix table 3.

    The external connector of the product(which incorporates transducer output)consists of a housing(Type:178289-

    7,Manufacturer:AMP)and contacts(Type:175218-2,Manufacturer:AMP). Carry out connection treatment using a dedicated manual

    tool(Type:919602-1(standard type),914596-3(economy type ))or 90648-1(economy type , Manufacturer: AMP).

    Selective input/output (Eight points each) permits selection of function type by setup. See chapter 5 for types of selectable

    functions and see chapter 5 for the setup method.Each terminal block is the connector type, and it can be mounted and dismounted by lock screws on both sides of the terminal

    block, with wires remaining intact. At the time of mounting/dismounting the terminal block, alternately drive/loosen lock screws

    on both sides sequentially. If lock screws on one side only are forcibly tightened (or loosened) the terminal block may be broken.

    Certainly tear off the upper and dust-proof seal after the wiring. There is the fear in which that the temperature of the inside rises,

    when it is used without tearing off, and that it causes the abnormality and product are shorten.

    (2) Precautions of settingThe frequency of this unit is the form of selecting 50Hz or 60Hz.

    Set correctly at 50Hz or 60Hz to suit the rated-frequency of application.

    In respect to setting items, frequency will not become valid unless the power is ON/OFF after setting. When the frequency

    setting is changed, turn ON/OFF the control power once.

    As the setting value of the code No 73 and No 74 in the setting table, set the sum of the 100ms and the operating time of external

    device. The F-MPC60B spends the time for filtering the input signal, so it is necessary to add the time.

    (3) Precautions for shipping the panelFix the front panel door using adhesive tape so that it will not open up due to excessive vibration or the like during loading or

    shipping. (It has been assured that the JEC 2500 has been cleared in regard to vibration resistance.)

    (4) Precautions for using the external output relayRefer to the Table 3.4 "specification for external input/output". The specification of output current of the relay for ON/OFF/trip

    is valid for only the closing current. So, do not use the relay of this devise for tripping the CB current. Use the external relay totrip the CB current.

    As the relay except the ON/OFF/trip relay, observe the specification of the section 3.3 (2).

    (5) Others Function of OC relay

    In case the external CT used as 2CT,use A-phase and C-phase for the CT, and connect the CT secondary synthesized line

    (common line) to the B-phase. 2CT provides the overload protect function for the B-phase even against an unbalanced load to the

    3-phase circuit as a result. However, it is possible that the B-phase will also operate when single-phase relay testing of A-phase or

    C-phase is conducted in a relay test because of this function. (It depends on the positions of test terminal.)

    Active electric energy integrated value

    The integrated value is also kept when a power failure occurs. If the setting of the VT ratio and CT ratio was changed, however,

    the integrated value is reset to the initial value (0).

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    7/68

    2. Mounting and wiring2.1 Panel cutting and mountingCut the relay mounting panel as shown in the panel cut drawing in section 3.4 External appearance drawings. Then mount the unit so that

    the top face of the unit become level.

    Ventilation holes are provided at the top and bottom of the cases main unit. If these holes are plugged, the internal temperature rises and

    errors may occur, or it is possible that the products service life will be shortened. When any equipment is mounted above or below the

    cases main unit, provide a space of 100 mm or more from the cases main unit.

    2.2 WiringWiring to the F-MPC60B is roughly classified as indicated table 2.1. Be careful that these wires do not come in contact with each other.

    Table 2.1 the wiring of F-MPC60B

    Classification Name

    Communication line,signal line

    Communication (RS-485)cable,Transducer(4-20mA,kW pulses) output lines

    Control line

    (classification 1)

    Control power lines, VT secondary lines, CT secondary lines, input/output lines(excluding those of

    classification 2)

    Control line

    (classification 2)

    CB ON lines, CB OFF lines, CB trip lines

    Grounding line Grounding line

    1) Communication line, signal line

    Use KPEV-SB (0.5sq),CPEV-SB ( 0.9mm) or equivalent for communication cables(RS-485). Lay shielded wire for SD or SG

    terminal (No.2 of terminal block A).

    Separate route of communication line and signal line from high voltage apparatus or power line.

    Separate them from CB control line or high voltage line.

    Connect terminal resistor on both ends of communication cables without branching.

    If this unit is provided with a communication function (RS-485) and this unit is located at the end (terminal) of a communication line, use

    short terminals No.3-5. Terminal resistance of 100 is built-in.

    Transmission distance of communication cable is 1,000m or less at RS-485.

    Use twisted wires (cables) for transducer output lines.

    2) Control line (classification 1)

    Wiring of control power line doesnt connect in parallel with such as load that will be source of generating noise.

    When the control power lines, input/output and VT/CT secondary lines are located in the same duct, separate VT/CT secondary lines, as

    bound together using a tube or the like, from other.

    3) Control line (classification 2)

    Separate CB ON/OFF/trip lines from other lines.

    4) Grounding line

    Be sure to ground the earth terminal (FG).

    Lay the grounding line (FG terminal) for each unit independently, and separate it from other line.

    (See section 2.3)

    Figure 2.1 Typical separation of the wiring

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    8/68

    5) Terminal block (the interface terminal block)

    Disposition of terminal block is indicated figure 2.2.

    Figure 2.2 the interface terminal block

    6) Other

    Arrange the wires as connected on the panel side in such a manner that no stress is applied to the terminal unit before connecting the

    wires.

    The terminal screw is M3.5. Tighten them to the proper tightening torque. (Recommended value:0.8N m)

    Use a tightening torque of 0.8N m or more for fitting the main unit with fixtures.

    Use pressure terminal matched size of cable, and check to see if mounting screws are correctly tightened.

    In case driving load above contact rating of relay, be sure to use in combination with power relay.

    2.3 GroundingThe typical grounding of the panel is indicated below.Figure 2.3 the typical grounding of panel

    Note: Separate grounding should be made if there is any equipment such as an inverter that will be source of generating high-frequency

    noise.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    9/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    10/68

    2.5 Terminal assignmentsEach terminal block is the connector type, and it can be mounted and dismounted by lock screws on both sides of the terminalblock, with wires remaining intact. At the time of mounting/dismounting the terminal block, alternately drive/loosen lockscrews on both sides sequentially. If lock screws on one side only are forcibly tightened (or loosened) the terminal block may

    be broken. Each terminal block units is composed of two terminal blocks, i.e. a 30-pole block (row A) and 30-pole block (row

    B).Pay attention because it becomes the cause that this device is damaged, when mistake the terminal unit of the "block: A" and the "block: B"and wire. As for the details of wiring, refer to section 2.6.

    2.5.1 UM43FG-E5AK type

    Figure 2.5 the 30-pole block (A) Figure 2.6 the 30-pole block (B)

    Figure 2.7 the connector of transducer output

    N.C N.C Output 6- Output 5- Output 4- Output3- Output 2- Output 1-

    N.C N.C Output 6+ Output 5+ Output 4+ Output 3+ Output 2+ Output 1+

    Pin No.

    The minus side of output signal: 4-20mA is common.

    Precautions for connection to the row "A": 30-poles terminal block.

    (1) The connection position of "Va, Vb, Vc and Vn " differs with "3-phase 3-wire system" and "3-phase 4-wire system".(2) If this unit is provided with a communication function (RS-485) and this unit is located at the end (terminal) of a communication line,

    use short terminals No.3-5. Terminal resistance of 100 is built-in.

    (3) Terminal with marks are NC (no connection) terminals. Do not connect wires to these terminals.

    7: kWh pulse output (+)

    8: kWh pulse output (-)

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    11/68

    2.5.2 the wiring of CT and VT the fuse, the test terminal and the ground line are omitted.

    The under voltage relay: 27 monitors the line voltage: Vab or Vbc

    The over voltage relay: 59 monitors the line voltage: Vab

    The under voltage relay: 27 monitors the phase voltage: Van, Vbn, Vcn

    The over voltage relay: 59 monitors the phase voltage: Van

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    12/68

    Figure 2.10 the wiring of 3-phase 4-wire system with external 3CT

    The connection method of CT: Input the inverse synthesis current of Ia, Ib and Ic to the N-phase input.

    Note 1: tighten the short circuit bar of No 13-24 with the terminal screw certainly.

    The under voltage relay: 27 monitors the phase voltage: Van, Vbn, Vcn

    The over voltage relay: 59 monitors the phase voltage: Van

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    13/68

    2.5.3 In the case that VT is composed with 3-phase: Va, Vb and Vc

    The wiring of the single-phase system shows in Figure 2.11.1, Figure 2.11.2 and Figure 2.11.3.

    Figure 2.11.1 the wiring of single-phase system: the load between A and B

    Figure 2.11.2 the wiring of single-phase system: the load between B and C

    Figure 2.11.3 the wiring of single-phase system: the load between A and C

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    14/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    15/68

    Chapter 3 Specification3.1 Model list

    Table 3.1 shows the functions of this devise. The functions are generally classified by the combination of protecting elements and

    measuring elements. Unnecessary protecting elements may be locked.

    Table 3.1 the functions of this device

    Protection Measurement Transducer; (4 to 20mA)

    Model/basictype

    50

    51

    51DT1Dt2

    50G50N

    51G51N

    27

    59

    OCA,O

    CGA

    A

    W

    var

    PF

    Wh

    DA

    DW

    HI,

    A0

    A0max,

    DAmax,

    DWmax,

    V.Hz,Varh,Vmin

    The kind of the signal is 14.

    Line voltage (Vab, Vbc, Vca)

    Phase voltage (Van, Vbn, Vcn)

    Current (Ia, Ib, Ic)W, var, power factor, Hz

    UM43FG Number of output: 6 quantity

    Note 1: See section 3.3(6) for a complete breakdown of transducers output.

    Note 2: OCA: Over-current alarm (may be used as a pre-alarm by setting an alarm value.)

    Note 4: OCGA: Earth leakage pre-alarm (may be used as the preventive maintenance for the cable deterioration.)

    Standing standard

    JEC-2500 Protective relays for electric power systems

    JEC-2510 (Over-current relays)

    JEC-2511 (Voltage relays)

    JIS C4602 (Over-current relays for 6.6Kv receiving)

    JIS C4609 (Directional ground relay set for 6.6kV consume)

    JIS C1102-1 -9(Direct acting analogue electrical instrument and their accessories)

    IEC255-3 (1989)

    3.2 Type

    Represents the series(Model for 3-phase 4-wire system)

    Classification of ground fault protection

    50G 51G

    Control power supply

    100V DC AC common use

    CT secondary current

    5A

    External interface

    "4-20mA output" & "RS-485 interface": note 1

    Classification of characters on the panel

    Except for Japanese

    Note 1: Refer to the next manual."F-MPC60B (UM4 type) Application manual for RS-485 communication": FH866 that is the same contents as "FIN 75 96 25".

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    16/68

    3.3 Specification(1) General specification

    Table 3.2 general specification

    Note 1 Operation guaranteed temperature means that operation is guaranteed within two times of the accuracy guaranteed value at JEC

    characteristics guaranteed temperature or within the accuracy of influence of JIS temperature.

    (2) Specification for external input/output

    Table 3.4 specification for external input/output

    item Specification

    Input circuitCommon to 100V DC(143V DC or less) and 100V AC(132V DC or less)

    ON voltage 40V DC to 70V DC ON voltage 40V AC to 70V AC

    CB ON/OFF/trip Closing current:15A(110V DC)

    allowable continuous conduction current:4A

    Output circuit

    Other than above Closing current 0.2A (110V DC, inductive load L/R=15ms or less) allowable

    continuous conduction current:1A

    Item Specification

    Control power supplyCommon to 100V DC(80-143V

    DC) and 100V AC(85-132V AC)

    Power consumption Max. 15W

    Power consumption of

    CT,VT

    Max. 1.0VA

    Rated current

    (CT secondary current)

    5A AC

    ("1A AC" type is the non-standard

    correspondence.)

    Line

    voltage

    Select "110V AC" or " 110 3

    AC" (VT secondary voltage)

    Rated

    voltage

    Phase

    voltage

    Select "110V / 3 AC" or "110V

    AC" (VT secondary voltage)

    Zero-Phase current 5A AC

    Insulation resistance 10M or morebetween external terminals and

    ground

    Vibration16.7Hz, double amplitude 0.4mm

    acceleration:1.96m/s2

    10 minutes in each of 3 directions.

    Shock 300m/s2 3 time in each of 3

    direction

    Withstand voltage

    2kV AC 1 minute note 4 (between

    external terminal and ground)

    However, RS-485 signal line and

    transducer output line is excluded.

    Item Specification

    Noise resistanceJEC2500(conforms to ANSI),

    Square wave 1.5kV (1ns/1 s 10

    minutes)

    Overload

    resistance

    CT circuit: at ratting 40times,a second, 2

    times

    VT circuit: at ratting 1.25 times, 10

    seconds

    Ambient

    temperature

    -10 60 operation is guaranteed.

    Note 1

    (0 40 characteristics are

    guaranteed.)

    Storage

    temperature

    -20 70

    Relative humidity 20% 90% RH(no condensation)Working

    atmosphere

    No corrosive gas and no heavy dirt and

    dust.

    Grounding class Class D grounding

    (100-ohm or less)

    Mass 1.4kg

    Dropout tolerance 20ms

    Continues operation, however, display go

    out.

    Electrostatic

    discharge

    Contact discharge 8kV

    Aerial discharge 15kV

    Lightning impulse 5.0kV , between external terminal and

    ground

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    17/68

    (3) Specification for measurement and display

    Table 3.4 specification for measurement and display

    Item Effective display range Display range and accuracy Note 2

    Current

    /Demand current

    /Demand maximum current

    0, "0.8%" "CT rating" "CT rating 8

    times" note 1

    1.5% 0 0.8% 100%

    5% 100 800%

    Zero-phase current/Zero-phase maximumcurrent

    CT: 0, "2%" "CT rating" "CT rating 8times"

    1.5% 0 "2%" "CT rating"

    5% more than CT rating

    Effective power/demand effective power/reactive power

    0.015 1kW at VT secondary circuit

    (The value is converted into the VT rated

    voltage: 110V AC)

    1.5% 0 " 0.015" " 1kW"

    (Refer to figure 3.1)

    Power factor Lead 0%-100%-Lag 0 5% (Refer to figure 3.1)

    Effective electric energy

    Reactive electric energyNote 3

    0 99999

    multiplying factor 1 10 100 1000

    Equivalent to ordinary instrument shown in table 4 of

    JIS C 1216(instruments with transformers)

    Line voltage 9.5V-260V on VT secondary side

    Phase voltage 5.5V-150V on VT secondary side1.5%

    Note: The rating voltage of phase voltage is

    equivalent to "the line voltage/ 3".Frequency 45-55Hz(50Hz) 55-65Hz(60Hz) 0.5%

    Demand max. value Same as the above measuring range. Same as the above indication range and the precision.

    Harmonics current 3rd,5th,7th,total

    Note 1 the accident electric current can be indicated by the electric current value indication to max.2000%

    ( 5% of the precision)

    Note 2 Meaning of 0, A% is 0 is indicated if a range under 0 to A%.

    Note 3 There are two indications in the electric power indication that total electric power value (zero clear disable) and period electric

    power quantity (zero clear is possible).

    Note 4 Here, the mark: "" displays "LEAD/LAG" of the electric power selling, the power purchase or power factor.

    The mark: "+" is a blank. The meaning of "mark: " for each item of measuring shows Figure 3.1.

    Figure 3.1

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    18/68

    (4) Specification for history data

    Table 3.5 specification for history data

    Item Display range Display

    code

    Item Display range Display

    code

    Number of times of the

    tripping: 50(INST)0-9,999 times Number of times of the

    motion: OCA0-9,999 times

    Number of times of thetripping: 51DT1

    0-9,999 times Running times 0-9,999 100(hr)

    Number of times of the

    tripping: 51(OC)0-9,999 times Number of times of switching 0-9,999 10

    times

    Number of times of the

    tripping: 51G0-9,999 times Number of times of the

    motion: OCGA0-9,999 times

    Number of times of thetripping: 50G

    0-9,999 times Number of times of themotion: 51DT2

    0-9,999 times

    Number of times of the

    tripping: 59(OV)0-9,999 times --- --- ---

    Number of times of the

    tripping: 27(UV)0-9,999 times --- --- ---

    Other displayFault value display: Display of fault value on occurrence of a fault, maximum values in the history of zero-phase current/voltage,

    and maximum demand value (A, W), minimum values of instantaneous voltage.

    Note 1 Display code in the above table is the code used when displayed on this unit.

    Note 2 As for Changing of setting value of history data, see section 4.3.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    19/68

    (5) Specification for protective relays

    Table specification for protective relays

    Characteristics

    Item

    Current/voltage operation

    value setting range Operation time(timer) setting range Operation

    value

    Tripping time

    Instant 1-16 times of CT rated

    current(0.2 times step) Lock

    Fixed 5% 40ms or less

    definite time

    1-16 times of CT rated

    current(0.2 times step) Lock0-5s

    0.05s step

    5% Less than 1s 50ms

    More than 1s 5%

    definite time

    20-240% of CT rating current

    (2% step) Lock0-10s

    0.1s step

    5% Less than 1s 50ms

    More than 1s 5%

    Inverse time

    SI,EI,VI,LT,I t

    20 240% of CT rating

    current(2% step

    Lock

    Time multiplication:0.5-20 times

    0.1 times step

    operation time:150m min.

    5% Setting value 300% 12%

    500,1000% 7%

    (lower limit 100ms)

    (instant, definite time)

    0.2-8times of CT rating(0.1

    times step) Lock0.0 10s 180s note 1

    (0.1s step)

    5% 5%(lower limit 50ms)

    SI,EI,VI,LT

    2-100% of CT rating(1%

    step) Lock

    Time multiplication:0.5-20 times 0.1

    times step

    operation time:150m min. note 1

    5%(min

    100mA)

    Equivalent to that of 51

    above.

    VT secondary:60-150V(1V step),Lock

    0.0 5.0 60s

    (0.5s step) (1s step)

    5% 5%(min 50ms)

    VT secondary:10-100V(1V step),Lock

    0.0 5.0 60s

    (0.5s step) (1s step)

    5% 5%(min 35ms)

    (Over current pre-

    alarm)

    10-100% of CT rating

    (5% step) Lock10 200s

    (10s step)

    10% 5%

    (Leakage current pre-alarm)

    50,60,70,80% of the settingvalue of "51G operating

    current" Lock

    10 200s

    (10s step)

    10%

    (min

    100mA)

    5%

    Note 1 With measures for preventing malfunction by exciting rush current (locked when secondary higher harmonics content is about

    15% or higher)(this function operates at 15% or higher of basic wave current rating.)However, Without measures for preventing malfunction by exciting rush current in the case of setting motion time 0s of

    "protections 50G".

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    20/68

    (6) Specification for transducer output (for product with transducer output)

    Table 3.7 specification for transducer output

    Item Specification

    Transducer output signal 4 to 20mA DC (external load resistance:270 or less Tolerance

    Current (Ia, Ib, Ic For rated 0 to CT,4 to 20mA

    Line voltage (Vab,Vbc,Vca

    Note 1

    For VT secondary

    For 0 to 150V, 4 to 20mA.

    For 0 to 150V 3, 4 to 20mA.

    Phase voltage (Van,Vbn,Vcn

    Note 1

    For VT secondary

    For 0 to 150V/ 3, 4 to 20mA.

    For 0 to 150V, 4 to 20mA.

    Effective power (W) For 0 to 1kw (CT5A, VT 110V AC conversion), 4 to 20mA.Reactive power (var) For -1 to 0 to 1kvar (CT5A, VT 110V AC conversion), 4 to 12 to 20mA.

    Frequency (Hz) For 45 to 55Hz or 55 to 65Hz, 4 to 20mA.

    1.5%

    Signaltype

    Power factor LEAD 0.5 to 1 to 0.5LAG/4 to 12 to 20mA. 5%

    * The minus side: "-" of the output signal at the transducer circuit is common.

    * For the output signal exceeding upper or lower value, the output signals cause 4mA at lower limit and 20mA at upper limit. Theoutput signal is limited 4mA at lower value and 20mA at upper value.

    Note 1: " " is applied for the line voltage: 100V/110V/120V AC. " " is applied for the linevoltage: 100V/110V/120V 3 AC.

    Refer to the code No 04 of appendix table 1.

    (7) Specification for the "kWh" pulse output

    Table 3.8 specification for the "kWh" pulse output

    Item Specification

    Output Open collector output

    Output capacity Maximum 150V DC 100mA.

    Pulse width 200 20ms

    Output pulse unit10 kWh per pulse(n -2 4 setting) or 2,000 pulse/k h

    (8) Specification for communication

    Table 2.9 specification for communication

    Item Specification

    Standard EIA RS-485

    Data exchange method 1:N (polling/selecting system)

    Transmission distance Maximum 1000 m

    Number of connectable modules Maximum 32 modules (included in master module)

    Setting address 00-99

    Transmission speed 4800/9600/19200 bps

    Start bit 1 bit (fixed)

    Data bits 7/8bits (selectable)

    Parity bit None/odd/even (selectable)

    Data type

    Stop bit 1 bit (fixed)As for communication cable, use "KPEV-SB (0.5mm2)", "CPEV-SB ( 0.9mm)"or the equivalent cable.

    Connect the shield line to terminal: "SG".

    The RS-485 bus must form a single continuous path, and requires termination because of fast transition, high data rates, or long cables. Both

    end of the main cable require termination. When this devise is on the end of RS-485 bus, connect the terminal: No 3 and the terminal: No 5

    on the terminal: "A" with short circuit bar. This device is including a 100 termination resistor.

    The RS-485 cable must separate from the power line, motors, or high-voltage apparatus.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    21/68

    3.4 External appearance drawingFigure 3.1 external appearance drawing

    Angle

    180

    42.5

    B

    151

    Connector for

    transducer output

    A

    Figure 3.2 Rear view

    F-MPC

    165

    192

    179

    18 85.3 27

    min.

    100

    min.

    100

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    22/68

    180

    152 +0.5-0

    +0.5

    -0

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    23/68

    4. Operation and handlingThe circuit breaker ON/OFF switch, REMOTE-LOCAL select switch, etc. are protected in dual structure front panel door and switch

    protection covers. If the door is open, damage to the door will occur if a worker hits it. The door should be kept closed expect during switch

    operation.

    4.1 Names of controls on front panel and their functions.

    The state in which the front panel door is opened is indicated in Figure 1.

    Figure 4.1 front panel

    The code table of setting value, history and test is described in the rear of the front panel door.

    UM4F(K)

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    24/68

    Table 4.1 the name of control of the front panel and their function

    Item

    POWER At lighting of this LED, it indicates that the control power is ON.

    RUN At lighting of this LED, it indicates that running is normal.

    ALARM At lighting of this LED, it indicates that the equipment has failed. The details of a failure are

    indicated by Code of Chapter 6.

    RELAY

    RELEASE

    This relay flickers when the relay is detected, and it lights up when the relay is actuated.

    1)Running status

    indicator LEDs

    PLURAL

    FAULTS

    This relay is lit while there are multiple factors for relay motion and for equipment failure.

    Explains the contents of the display code of item 6 when relay motion occurs.2) Relay release failure code chart

    Example: When E2 is indicated by E2 OC(A) code, it means that the OC relay was actuated in

    the A-phase.

    CodeIndicates contents of relay failure, equipment failure and setting item at time of setting. See

    section 6 and separate table 1 for details.

    3) Indication of

    measured value,

    setting value or

    failure value.Data Data is displayed.(in 5 digits by 7-segment LEDs)

    4)Display item and unit indicator

    LEDs

    Indicates item and unit of data of item 3. 10 and 100LED indicate display magnification.

    (when both 10 100 are lit, this indicates that the display magnification is 1,000 times.)Example: when R and A are lit, this indicates that the data display is of R-phase current value and

    the unit is A(ampere).

    5) Sheet switches Used for switching of display item, setting operation, etc.

    6) Key switch NORMAL/SET/TEST mode select switch

    (insertion/extraction of the key is permitted only in the NORMAL position)

    7) Operation indication LEDREMOTE/LOCAL: indicates whether remote running or local running has been selected.

    CLOSE/OPEN: indicates whether the CB or the like is ON or OFF.

    8)REMOTE/LOCAL,CLOSE,OPE

    N operation switch

    REMOTE/LOCAL select switch and CLOSE/OPEN operation switch.

    (switch with protective cover)

    4.2 Operation and selection of the key switch

    The key switch has three positions, i.e. setting, normal and test. The motion when each one of three positions is selected is indicated below.

    Table 4.2 the operation and selection of the key switch

    Item Position of key

    switch

    Outline of the motion

    Setting Select this position any setting value, for checking any setting value or for checking or re-setting

    any history data. Even when the key switch selects the SET position, the protective relay function

    is continued for conventional setting values.

    Normal Select this position for normal running. Insertion and extraction of the key switch can be

    performed in this position only. (This front panel door will not be closed unless the key is

    extracted.)

    Test

    Select this position for conducting manual testing such as a system check. This normal running

    function of protective relays, etc. is suspended when the TEST position is selected.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    25/68

    4.3 Operation when setting

    The key switch selects the SET position.

    Key switch

    Figure 4.2

    Step 1 Step 2 Step 4 Step 3

    Operation procedure

    Step 1

    Confirmation of setting value.

    The setting value item number and historical value code is updated each time the sheet switch or is pressed, and the

    current setting value is indicated by the 7-segment LED.

    (Operation for confirmation is step.1 only.)

    Step 2

    Change to setting value and historical value.

    Press sheet switch SET in the state where a setting change item and historical value is selectively indicated in step 1 above. (The

    setting value begins to flicker.) to step 3

    Step3

    The setting value changes each time the sheet switch or is pressed. Select the data to be set.

    (The setting value is flickering, and has not yet been finalized.) to step 4

    Step 4

    When sheet switch ENT is pressed, the setting value is lit continuously; indicating that setting has terminated.

    Repeat step 1 to 4 above to continuously change the setting of multiple items. The selecting lock can delete an unnecessary

    relay function item. Confirmation of history data and change to the current value can also be performed in the same manner.A list of setting items and history data of the feeder unit, the receiving unit and the bus unit are shown in appendix table 1.

    NoteIn the setup for time of monitoring contact open/close jamming, the set time should not be less than external equipment (sequence) motion

    (Ans. signal) time plus 100ms. (This is because the F-MPC60B internal measurement time is from CPU output to finalization after the input

    filter time.)

    (Locking the setting value)

    Change to the setting cannot be performed unless the key switch is located in the SET position.

    Therefore, mischievous changes to setting cannot be performed by an unspecified person who does not have the key. In addition, a setting

    lock function is provided, and a value which was once set cannot be changed even if the key switch is located in the SET position.

    (Method for setup of "setting lock".)

    Step 1: Setup of setting lock/cancel can be performed only in any of the display statuses indicated below in the normal mode.

    Table 4.3 setting lock

    Selection of

    display item

    Operation

    IA current display

    status Press sheet switches SET and ENT simultaneously. The lock status has been selected if the display is Lon. Or, the

    lock has been canceled if the display is LOFF. The Lon/LOFF display is switched each time the sheet switches

    indicated above are pressed simultaneously. Terminate the operation, after confirming the Lon is displayed, to the

    setting.

    Step 2: Assure that the setting value does not flicker even during work step 2 (change to setting value) of the operating procedure indicated

    above is performed.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    26/68

    4.4 Operation in normal stateThe key switch selects NORMAL position.

    (Operation of keys is unnecessary during normal running.)As for the display item and display method, see appendix table 2.

    Note: " 10" and " 100LED" indicate display magnification in unit indicator LEDs .

    when both " 10" " 100" are lit, this indicates that the display magnification is 1,000 times.

    Figure 4.3 the operation of normal

    Key switch

    Normal

    The display of measured value can be switched by operating of this switch.

    The display of measured value (meter) can be switched during normal running.

    The display item is switched sequentially each time the sheet switch or is pressed. Check the display item and unit by reading the

    LEDs. The 7-segment LEDs of this unit go out automatically if no switch operation is performed for a continuous 10 minutes, as an

    energy conserving measure. However, they light up when any switch operation is performed, any relay is detected or when any equipment

    error is detected. (Press one sheet switch to have LEDs to light up again. No change will occur in the running status regardless of whichsheet switch is operated.)

    4.5 Rest method of "the measurement hysteresis maximum value", "the measurement hysteresis minimum value" and "theintegrated value".

    This appliance has the display function of the hysteresis maximum value, the hysteresis minimum value and integrated value shown at the

    bottom table. Please do it by the following in confirmation and the case in which it is reset of period data, etc. And, please similarly reset

    field startup test and relay test in the periodic check after the execution on zero-phase current maximum value.

    Table 4.4 the list of the measurement hysteresis maximum value and the measurement hysteresis minimum value.

    The measurement display item display method in 5 digits by 7-

    segment LEDs

    Period effective power( ) kWh

    Period reactive power( ) kvar

    Demand A,B,C-phasecurrent maximum value

    Demand effective power maximum value kW

    Minimum value of instantaneous AB,BC,CA-phasevoltage

    Zero-phase current maximum value

    Reset method.1) By the measured value confirmation operation in the usual time described at 4.4 terms, the correspondence data is displayed. (example:

    I0 LED is the condition that H A was displayed in the lighting in the 7-segment display part in zero-phase current maximum

    value.)

    2) In the condition that the correspondence data was display, the SET switch is pushed.

    the hysteresis maximum value is reset. (It is cleared in the zero.)

    Note:

    Though period electric power quantity is reset in the superscription operation, the active power quantity is not reset, even if thesuperscription operation is carried out.

    It is reset only in the case of setting change of the CT, VT ratio the total effective power quantity.

    (It is cleared in the zero.)

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    27/68

    4.6 Operation at testing timeThe key switch selects TEST position. (the function of protection, measurement is all ignored.

    The [lamp test (all lamps are lit) status] is produced when the TEST position is selected by the key switch, and switching to [all lamps are

    out (code L2 is displayed)] - [input/output testing] - [relay forced motion testing] - [transducer output testing (only with a product with

    transducer output)] - [return to lamp test status] each time the sheet switch is pressed thereafter. (Reverse turn occurs when sheet switch

    is pressed.)

    The contents of input/output testing relay forced motion testing and of transducer output testing are indicated in the Figure 4.5. The test

    output is not output even in the test mode, unless the external TEST position input is ON (the CB, etc. have not been pulled out to the TESTpositions). (When the external TEST position is not used, the test output is output in the test mode. Refer to the test position of table 5.2 and

    note 3.)

    Table 4.5 the operation of the test position

    Test item Code display Operation for testing

    The state when TEST position input is OFF and actual output is not made is indicated.

    The state when test position input is ON and actual output is not made is indicated. CLOSED/OPEN output and

    status indication is made by the CLOSE/OPEN operation that corresponds to the REMOTE/LOCAL setup.

    Input/output testing

    If any equipment error is detected in the input/output testing, the following display is made in the data area.

    F4568 A failure detection No. only is displayed. Check the applicable item.

    F: Equipment failure

    4/5: CB contact open/close is jammed 6: CB trip coil open circuit

    8: F-MPC60B internal circuit error See Chapter 6 for processing when a failure is indicated.

    The applicable output is made when sheet switch: SET and ENT are pressed simultaneously in the state when any of the

    code displays indicated below are selected. If the product is provided with a communication function, the applicable bit data is also

    transmitted.

    Code display Testing item andoutput

    Code display Testing item andoutput

    Code display Testing item and output

    C0 Equipment failure

    output

    CP E0 50INST CP EF OCGA

    C1 Selective output 1 CP E1 50DT1

    C2 Selective output 2 CP E2 51(OC)

    C3 Selective output 3 CP E3 27(UV)C4 Selective output 4 CP E4 59(OV)

    C5 Selective output 5 CP E8 51G

    C6 Selective output 6 CP E9 50G

    C7 Selective output 7 CP EC OCA

    Relay forced motion

    testing transduceroutput testing

    Note 1

    C8 Selective output 8 CP EE 51DT2

    Transducer output(DC 4-20mA)

    Code display Motion when testing Code display Motion when testing Code display Motion when testing

    Ao 4 4mA DC output Ao CH1 V only, 12mA output Ao CH6 CH6 only, 12mA output

    Ao 8 8mA DC output Ao CH2 Hz only, 12mA output

    Ao 12 12mA DC output Ao CH3 I only, 12mA output

    Ao 16 16mA DC output Ao CH4 W only, 12mA output

    Transducer outputtesting

    Note 2

    Ao 20 20mA DC output Ao CH5 Var only, 12mAoutput

    Electric energy pulse output

    Code display Motion when testing

    P0

    Output of one pulse (each time the sheet switch ENT is pressed)

    Pulse output testing

    P1 Repeated pulse output of one pulse per second when switch ENT is pressed.

    The output stops when sheet switch RST is pressed.

    * The stopped status is produced if P1 is initially selected.

    * Description of C code display is printed on the panel sheet.

    Note 1 The protecting elements, which are locked by setting, will not be output.

    Testing of CP E* is made to output contact that is set according to section 5.4.

    Note 2 the transducer output testing is a test item applicable only to a product with transducer output.

    At testing of Ao 4,8,12,16 and 20, outputs of all channels are made simultaneously.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    28/68

    Chapter 5 Type and functions of external input/output

    5.1 Type and functions of external input/outputThe names and functions of external input/output are indicated in the Table 5.1.

    Table 5.1 Types and functions of external input

    Name Setting code RemarksCB52a Circuit breaker (CB) ON answer back signal. (the fixed Input )

    Trip coil circuit monitoring The monitoring signal of trip coil (the fixed Input )

    Selective input 1 70 Duplexes internal hardware note 1

    Selective input 2 71 Duplexes internal hardware note 1

    Selective input 3 72 Duplexes internal hardware note 1

    Selective input 4 73

    Selective input 5 74

    Selective input 6 75

    Selective input 7 76

    Selective input 8 77

    Note 1: The circuits of "the selective input 1", "the selective input 2" and "the selective input 3"are duplicated.

    In the case that "external OFF", "external trip 1" and "external trip 2" is allocated to "selective input 1, 2 and 3", it is valid forpreventing the miss-trip when the part of this device is failure.

    Selective input means input that permits selection of input function (meaning) by setting. Its description is indicated in the Table 5.2. Using

    this selection, the application to the various kind circuits becomes easy.

    Table 5.2 selective input

    Set number Item Function and application Remark

    No function

    External display select

    switch The function is the same as that of sheet switch on the panel face

    (when the key switch is in the NORMAL position).

    * Valid at the time of switching of display by external operation such as

    operation on the panel face.

    External rest switch

    The function is the same as that of the sheet switch RST on the panel

    face (when the key switch is in the NORMAL position.

    * Valid while switching of display by external operation on the panel

    face.Transmission element 1

    Transmission element 2

    Transmission element 3

    Transmission element 4

    Transmission element 5

    Transmission element 6

    General-purpose communication input

    * Valid as local remote DI input of the more significant controller

    (through communication).

    CB52b CB OFF input

    * When CB52b is selected, display of CB OFF is made by this input.

    Note 2

    External OFF External CB OFF signal when remote is selected.

    External ON External CB ON signal when remote is selected.

    External 43

    (selection of external

    remote-local)

    Remote is selected when ON, and direct is selected when OFF.

    * The remote-local select switch on the panel face is invalid when this

    function is selected.

    Selective of local-central Selection of CB ON/OFF valid signal when remote is selected by

    remote-direct selection.

    ON: Local (external) operation is valid.OFF: Central (communication) operation is valid.

    * When this function is not selected, ON/OFF operation is valid at both

    local and central. (OFF takes precedence if a duplicate operation is

    performed.)

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    29/68

    Set number Item Function and application Remark

    CB ON interlock Circuit breaker ON is interlocked when input is ON (close lock).

    CB OFF interlock Circuit breaker OFF is interlocked when input is ON (open lock).

    CB ON/OFF interlock Circuit breaker ON/OFF is interlocked when input is ON (open/close

    lock).

    External trip 1 External trip input(with lockout signal is OFF by pressing RST on the

    panel face.

    External trip 2 External trip input(without lockout)

    External alarm 1

    External alarm 2

    The input does in on, code display Ed, when the external alarm was

    set, while the input signal condition is done in the communication data.

    Test position The output test while the key switch is located in the TEST position is

    valid when the input is ON.

    * Signal for interlocking with circuit breaker draw-out position.

    Note 3

    Note 1 The internal circuit of each of selective input 1, 2, 3 is duplexes. When External OFF, External trip 1 or External trip 2 is

    selectively used, it is effective as a measure for preventing erroneous breaking when a part failure occurs if allocation is made to

    selective input 1-3.

    Note 2 when this selection is not made, the judgment of the ON/OFF status of the CB is made by CB52a input. ON is displayedwhen "52a" is ON, and OFF is displayed when 52a is OFF.

    Note 3 When this selection is not made, output testing also becomes valid unconditionally when the key switch selects the TEST

    position.In the case that "test position" is valid at the setting code: No 21, the output of "ON/OFF/trip" relay does not output when the

    position of key switch is "normal" or "setting" and when the input signal of "test position" is ON.

    Note 4 For selection setup, select setting code of input 1-8 and set a Set number in the state where the key switch is located in the

    SET position. See section 4.3 for the operating procedure. (Do not set the same function in duplication for other than Lock. It is

    possible that motion will become unstable.)

    5.2 Setting method of external inputFor selection setup of selective input 1-8, set a Set number by using setting code 70-77. By using appendix table 3 of list of setting items,

    decide set number (function) in advance. Setting for example is the following.

    Step 1: Selective input 1-8 is set for set number (function) of the diagram below.

    Step 2: See section 4.3 for the operating procedure.

    For setting selective input 1,select 70 of setting code and set 17 of set Number.

    Likewise, select 71-77 of setting code and set an appropriate Set number.

    Table 5.3 example of the setting of external input

    Setting

    Code

    Name of Setting function Setting value Remarks

    Setting Selective input 1 17 External trip 1 Selective input 1 is set for external trip 1.

    Setting Selective input 2 10 External OFF Selective input 2 is set for external OFF.Setting Selective input 3 11 External ON Selective input 3 is set for external ON.

    Setting Selective input 4 09 CB52b Selective input 4 is set for the answer-back signal input of CBs OFF.

    Setting Selective input 5 21 Test position Selective input 5 is set for signal of CB draw-out position when testposition is selected.

    Setting Selective input 6 03 Transmission element 1 Selective input 6 is set for transmission element 1. Use as local remoteDI input of the more significant controller.

    Setting Selective input 7 04 Transmission element 2 Selective input 7 is set for transmission element 2. Use as local remoteDI input of the more significant controller.

    Setting Selective input 8 Lock Selective input 8 is set for the unused.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    30/68

    5.3 Types and function of External output Table 5.4 the types and function of external output

    Name Remarks

    Equipment failure Equipment failure signal

    CB ON CB ON operation output

    CB OFF CB OFF operation output

    CB trip CB trip outputSelective output 1 Selective output

    Selective output 2 Selective output

    Selective output 3 Selective output

    Selective output 4 Selective output

    Selective output 5 Selective output

    Selective output 6 Selective output

    Selective output 7 Selective output

    Selective output 8 Selective output

    functions and motions1) With or without CB trip output may be set for each protective relay element. If multiple protecting elements are set for with trip

    output, the trip output become or output motion.

    2) Selective output may be set as an alarm output of each protective relay. If multiple protecting elements are set for the same selective

    output, the output becomes or output motion.

    3) Setup of selective output permits the following besides item 2) above.

    Table 5.5

    Name Function Setting code

    Failure pickup (batch) Output of ON with pickup of motion value of any protective relay (automaticrest)

    81

    Transmission element 1 82

    Transmission element 2

    General-purpose output

    * Valid as local remote DO of more significant controller (through

    communication).

    83

    Output of remote-localselection status

    Refer to "Note 15 " that is described in the page after Appendix table 1. 84

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    31/68

    5.4 Setting method of external output For selection setup of selective output 1-8, use setting codes 11, 14, 18, 1b, 23, 26, 32, 42, 45, 52 and 81-84. Setting for example is the

    following.

    5.4.1 example setting of external input

    1) By using appendix table 3 of list of setting items, decide the output in advance when actuating each protective relay. *CBs trip output

    become or output of INST, DT, OG and DG in the diagram below.

    Table 5.6 example setting of external With Without

    Type of protective

    relay element

    Setting

    code

    The presence or

    absence of CB's tripoutput

    The presence or

    absence of alarmoutput

    Number of selective

    output for alarm's output

    Remarks

    Protective INST

    (50)

    11

    Protective DT 14

    Protective OC 18

    Selective output 1 The alarm output of "50" and

    "51" is made for selective output1 on the block.

    Protective DG 32 Selective output 2

    Protective OV 42 Selective output 3

    Protective UV 45 Selective output 4

    Protective OVG 52 Selective output 5

    The alarm output of "DG", "OV"and "OVG" is made for selective

    output 2-5 individually.

    5.4.2 Setting the output of each Protective relay is indicated below.

    Lockout: With: 1 Without: 0

    Output contact selection 1-8: contact 1-8: 1-8 No output: 0

    CBs trip output: With: 1 Without: 0

    Setup for shipping: 000 CBs trip output: without

    Output contact selection: No contact output

    Lockout: without

    If the setting is with lockout, both display and output are continued and the CLOSE signal is invalidated until the sheet switch

    RST is pressed, even after the cause of the error was eliminated.

    If the setting is without lockout, the output resets automatically (after continuation for at least 1 second) when the cause of the

    error was eliminated. But the display is continued until the sheet switch RST is pressed.

    When the setting is with lockout in the case of 1) item, setting for example is shown below.Table 5.7 setting for exampleType of protective relay element Setting code Setting value

    Protective INST(50)

    Protective

    Protective

    Protective

    Protective

    Protective

    Protective

    5.4.3 See section 4.3 for the operating procedure.For setting protective INST (50), select 11 of setting code and set 111 of set Number.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    32/68

    5.5 Description of ON/OFF/trip output motions1) Once the subject input signal is finalized (soft filter about 20ms), the ON/OFF/trip output is continued for one second at minimum even if

    the input is gone thereafter. Also CBs trip output permits selection of manual-rest or automatically-reset by setting of the presence or

    absence of lockout.

    2) When ON/OFF operations are performed simultaneously, the OFF motion takes precedence. Detection of ON signal is made at the

    activation (ON) edge. If OFF operation is performed in the state when the ON signal is continuously ON, therefore, OFF output is

    made, and the ON output thereafter will not be made until the ON signal is once OFF and is than On again.

    Figure 5.1 example of ON/OFF/trip output motions

    ON operation signal ON

    OFF operation signal

    ON output

    OFF output

    3) The ON signal is not accepted during trip output.

    4) At setting code No.65, OFF operation of any becomes also effective regardless of the selection of REMOTE-LOCAL of the

    operation place, when the OFF precedence was set at with.

    (Supplement)

    There is the test position input signal as a signal input that is related to the ON/OFF/trip output action.

    The test position input signal determines that the CB (switch) is on "the normal operation position or the extraction position.

    In the normal operation, the output action is made to be the case in which the external input setting has made to be test position: 21 in

    test position input: OFF. And, the output action is done in the test, if it is made to be test position input: ON.

    The output action is done with the setting of the key-switch, if the external input is not set at test position: 21.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    33/68

    Chapter 6 Measures to be taken when relay motion or equipment failure occurs, and reading of code display

    The code display (7-segment LED of 2 digits) is out during normal running. If it lights up, take the measures indicate below.

    6.1 Outline of code displayIf the code display lights up during normal running, it means that a failure occurred in the F-MPC60B main unit or any peripheral

    equipment or any relay motion occurred. F represents equipment failure and E represents a relay motion.

    6.2 Reading of code display and measures to be taken1) Equipment failure

    When an equipment failure is detected, the ALARM LED is lighted, the output of the equipment failure relay is output, and the code is

    displayed. If the code display is other than FE, the running is continued and an equipment failure code and normal operation display

    (measured data) are displayed as switched about once every second.

    Table 6.1 the code display of the alarm

    Code display Description Running of F-MPC60B

    Measure to be taken

    Serious failure in F-MPC60B interior(error of

    CPU,ROM,RAM or the like)

    Stopped Replace the F-MPC60B

    Unbalance in 3 phases of PT,CT signal(whether the functionis valid or invalid may be selected)

    Continued Check the external wiring.

    Jammed CB contact opening Continued

    Jammed CB contact closing Continued

    Check the CB ON/OFFwiring and "answer-back"

    signal wiring.

    Open circuit in CB trip coil Continued Check the trip coil system.

    History data error(mismatch of memory check data) Continued Set the history data again.

    Error in F-MPC60B constant monitoring internal circuit Continued This device is normal, in the

    case that "F8" turned off it by

    pushing "the sheet switch;

    RST".

    Note 1

    F

    Light-up of

    ALARM

    LED

    Error in setting frequency 50/60Hz Continued ON/OFF the control power after setting the frequency to

    the normal level.

    F3 is reset automatically when the cause of failure is eliminated.

    F6 is reset automatically when the cause of failure is eliminated. It also goes out when the sheet switch RST is pressed in the state

    when the CB is OFF. (If the trip coil open circuit monitor function is not used, set Trip coil open circuit monitoring: None in the

    setting.)

    F4 and F5 go out when the sheet switch RST is pressed.

    Other than the above, execute self-hold when a failure is detected and then goes out when the sheet switch RST is pressed.

    Note 1; In the case that the abnormality of the signal is detected in the analogue input circuit, digital input circuit and output relay drive

    circuit of this device, the Code display; " F8" is displayed in the 7-segment LED.

    There is not abnormality in this device that depends on a temporary factor, in the case that F8 turns off it by pushing the return switch RST.

    Therefore, there is not a problem by using this device.

    Malfunction has occurred inside this device, in the case that "F8" is displayed even if pushing the switch RST.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    34/68

    2) Relay motion

    When any relay motion occurs, lighting of the relay motion LED and output of an alarm (trip) are performed besides the code display.

    Check the cause for relay motion. Description of E codes is printed on the front panel sheet.

    Table 6.2 the display of the relay motion

    Code display Description of relay motion

    E0 50(INST)

    E1 50DT1

    E2 note 1 51(OC)

    E3 27(UV)

    E4 59(OV)

    E5 External trip

    E8 51G(OCG)

    E9 50G

    Ec OCA

    Ed External alarm

    EE 51DT2

    EF OCG pre-alarm

    When PLURAL FAULTS LEDs are lit, have a code displayed as switched by pressing sheet switch or .

    The relay motion display and T-link data are kept after the cause of the failure was eliminated, and they go out when the sheet switch

    RST is pressed. If the control power was gone in the state when the sheet switch RST has not been pressed yet, storage is done

    automatically, and the status before the power failure occurred is output and displayed when the control power is recovered.

    When the E code display is flickering, it means relay detection in motion. (Operates after elapse of timer time.)

    Note 1: When the OC relay is actuated, the fault current value (unit A) and the motion time (unit s) are displayed as switched

    approximately once every second.

    The tripping time display of 51(OC) relay and 51G(OCG) relay is reference value.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    35/68

    6.3 The method of relay test

    Refer to the appendix table 4: "The relay test".

    As the relay test is tested at the condition of normal state, the position of the key switch must be the normal.

    (When the position of the key switch is the test, the protection function of F-MPC60B does not act at all.)

    The note at the test

    (1) The Table 6.3 shows the allowable continuous current at input circuit of the phase current. Refer to the Table 6.3 when the operation

    time is tested.

    Table 6.3 the allowable continuous current (for the F-MPC60B that the secondary rating current is 5A.)

    The input current The time of the allowable continuous

    current

    The input current The time of the allowable continuous

    current

    0-15A For more than 100 s 40-80A 6.3 s

    15-20A 100 s 80-100A 4.0 s

    20-40A 25 s --- ---

    The overload capacity of the current input circuit is 200A, 1s and 2 times: 60 s as an interval. Refer to Figure 6.1 when the operation time is

    tested.

    Figure 6.1 the overload capacity of the current input circuit

    (2) The F-MPC60B has the band-pass-filter to prevent the wrong action by the harmonic current, and changes the circuit constant of the

    band-pass-filter using the setting value of the frequency: 50Hz or 60Hz. So, at the relay test, set up the setting value, and input the signal that

    has the same frequency with the setting value.If the generator is used at the test, keep the accuracy oh frequency: 2.5% or more less.

    The current

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    36/68

    Chapter 7 Maintenance and inspection

    7.1 Inspection itemPerform maintenance and inspection as indicated in the Table 7.1 to use the product in the stable state.

    Table 7.1 maintenance and inspection

    Inspection periodNo Inspection item Description of inspectionDaily periodic

    ally

    Criteria for judgment

    Ambient temperature 50 or less(annual average 40 or less

    Ambient humidity 90% or less(no condensation on the surface)

    Vibration No vibration

    1 Ambient

    environment

    Dust, etc. Excessive contamination or accumulation of dust

    should not be observed.

    2 Display of errorcode

    Check visually.Note 1

    F should not be displayed.

    Check for looseness and play of

    the unit.

    Check for abnormal noise, odorand discoloration.

    Check for looseness of screws

    of External wiring.

    3 Mounting

    conditions

    Check for damage and

    deterioration to external.

    Looseness and other abnormality in the external

    appearance should not be observed.

    4 Indicator LEDs Assure that POWER and RUN

    LEDs are lit.

    5 Setting values Assure that setting values are

    normally displayed. Note 2

    6 Relay test

    7 Elimination of

    foreign matter

    Remove dust, etc.

    Note 1: the alarm output, the communication and the display on the panel of F-MPC60B output the errors detected by self-diagnosis.

    Note 2: the controller is able to check the setting value by using the communication.

    The main purpose of the daily check is the check such as the appearance and structure of a relay and also switchboard. As for the dailycheck, carry out several months to the rough standard. Also, carry out the inspection promptly, in the case that it corresponds to the next

    item.

    (1) It is in the case that abnormality admitted the fear that occurs with the daily check and the periodic check.

    (2) It is in the case that the abnormality occurred with automatic monitoring (continuous monitoring /automatic inspection) the function.

    (3) In the case that the setting value and the sequence circuit of the relay are changed.

    As for the periodic check, carry out 1 time to the rough standard in 4 years from 2.

    As for the method of the relay test, refer to Section 6.3 ant appendix 4: "The relay test".

    7.2 Design lifeThe exchange part in a periodic check does not exist. The design life value type of F-MPC60B is 15 years at ambient temperature 40 per

    a year. If temperature goes up 10 life becomes to about half. The vent (the slit) is opening to the upper part and lower part of the case

    main body. There is the fear that the product life becomes short, because the inside temperature goes up when the vent of this device is

    closed. Therefore, avoid it to close the vent.

    Please understand, because also, the design life is not the guarantee-life. Exchange this device when this device reached life.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    37/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    38/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    39/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    40/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    41/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    42/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    43/68

    2 1 0 2 2 0 3 8 0 4 4 0 4 6 0 3 3 0 0 4 1 6 0 6 6 0 0 1 1 0 0 0 1 3 2 0 0 1 3 8 0 0 1 5 0 0 0 2 2 0 0 0 2 2 9 0 0 3 3 0 0 0 3 5 0 0 0 6 6 0 0 0 7 7 0 0 0

    5 n = - 2 41 0 n = - 1 ( 1 0 A ) ( 1 0 A )

    1 5 ( 1 5 A ) ( 1 5 A ) ( 1 5 A )

    2 0

    2 5 ( 2 5 A ) ( 2 5 A )

    3 0 n = - 2 4 n = - 1 4 (3 0 A )4 0 n = 0 n = 1 (4 0 A )5 0 ( 5 0 A )

    6 0 ( 6 0 A )

    7 5

    8 0 ( 8 0 A ) ( 8 0 A )

    1 0 0 n = 0 41 2 0 ( 1 2 0 A ) n = 21 5 0 ( 1 5 0 A ) ( 1 5 0 A ) ( 1 5 0 A )

    2 0 0

    2 5 0 ( 2 5 0 A )

    3 0 0 ( 3 0 0 A )

    4 0 0 ( 4 0 0 A )

    5 0 0 ( 5 0 0 A )

    6 0 0

    6 3 0 ( 6 3 0 A )

    7 5 0

    8 0 0 ( 8 0 0 A ) n = 1 4 (8 0 0 A )1 0 0 0 n = 31 2 0 0

    1 2 5 0 ( 1 2 5 0 A )

    1 5 0 0 (1 5 0 0 A )

    1 6 0 0 ( 1 6 0 0 A ) ( 1 6 0 0 A )

    2 0 0 0

    2 5 0 0 ( 2 5 0 0 A )

    3 0 0 0

    3 1 5 0 ( 3 1 5 0 A )

    4 0 0 0 ( 4 0 0 0 A )

    5 0 0 0 ( 5 0 0 0 A ) T h e o u t s id e o f s e t t in g6 0 0 0

    7 5 0 0

    ( 5 A ) ( 5 A )

    T h e p r im a r y r a t e d v o lt a g e o f V T (V )

    (2 5 0 A )

    ( 1 2 0 A )

    ( 2 5 0 0 A )

    (1 2 5 0 A )

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    44/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    45/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    46/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    47/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    48/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    49/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    50/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    51/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    52/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    53/68

    The relay test is a test in relay operation value and operation time in the normal operation condition. Therefore, key SW

    is an operating state of "NORMAL" position and the relay test is done.

    (In "TEST" position, the protective function does not work in key SW.)

    The attention of the test

    This appliance contains the band-pass filter in order to prevent the unnecessary operation according to the harmonic.

    And, the circuit constant of the band-pass filter is being switched by the 50/60Hz selection setting in the main body

    inside.Still, please make the output frequency of the generator to be within 2.5% of set rated frequency in the case

    of the relay test by the generator.

    The method of the test

    In proportion to the unit type, characteristic test content and decision value refer to the after next page.

    The following are shown in the following: Identification method of the operation value and identification method in

    operation time.

    Test item The method of test

    Operation

    value

    (note)

    The signal is applied to the input terminal, and it gradually changes, and the value in which 7segLED

    started the "E" flashing display is the operation value.

    However, operation value in case of the short time operation type is any of value that "E"

    continued and that it lit, and that it displayed it or the value which output the trip ( alarm ).

    Operation

    time

    The adjustment-finished signal is applied to the input terminal, and the time until a trip (alarm) output

    operates is measured.

    Note:

    The signal value in the pickup relay output action becomes the operation value in trouble pickup output setting (code

    of 81) in any of the selective output 1-8.

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    54/68

    UM43FG-E5AK 13

    Test purpose: It is confirmed that it goes in the characteristic of the relay simple substance abnormal.

    Test content Quality criterion

    1.Appearance structural examination: It is confirmed that it goes in the

    appearance abnormal.

    1. There are no fracture, damage,

    stain and corrosion.

    2. Withstand voltage test: Between charge division consolidation and ground.

    However, transmission lines and transducer output line is excluded.

    2. 2kV AC 1minute

    3. Characteristic test: UM43FG type 3. Within the accuracy of thefollowing

    The protection

    element name

    Test item Testing condition Test input Accuracy

    (1)Operation

    value

    Working current setting

    value

    AB and C-phasenote 2

    ZeroOperation value Setting value5Instant over-currentrelay.

    50INST

    (2)Operation

    time

    Working current setting

    value

    ZeroBy changing to

    200% of the setting value

    suddenly, it is applied.

    Within 40ms

    (1)Operationvalue

    note1

    Working current settingvalue

    Time settingMinimum

    or use setting values

    AB and C-phase

    note 2

    Zerooperation value Setting value5Over-current relay.51

    inverse characteristic

    (SI) or

    or applying inverse

    characteristic(EI or VI

    or LT or I2t).

    Definite time

    DT1,DT2

    (2)Operation

    time

    Working current setting

    value

    Time settingUse

    setting values

    AB and C-phase

    Zero% Input of the

    current setting value

    300

    500

    1,000

    note 3

    Operation timenote 4

    300TTheory value12

    5001,0007

    The lower limit in operation

    time 150ms

    (1)Operation

    value

    Working current setting

    valueTime settingMinimum

    or use setting values.

    ZeroOperation value Setting value5

    min100mA

    Ground fault over-

    current relay51G (51N)

    inverse

    characteristic(SI) or

    applying inverse

    characteristic(EI or VI

    or LT).

    (2)Operation

    time

    Working current setting

    value

    Time settingUse

    setting values

    Zero% Input of the

    current setting value

    300500

    1,000note 3

    Operation timenote 4

    300TTheory value12

    5001,0007

    The lower limit in operation

    time 150ms

    (1)Operation

    value

    Working current setting

    value

    ZeroOperation value Setting value5

    min100mA

    Instant ground fault

    over-current relay

    50G (50N) (2)Operation

    time

    Working current setting

    value

    ZeroBy changing to

    200% of the setting value

    suddenly, it is applied.

    Within 50ms

    Over-voltage relay

    (OV)

    (1)Operation

    value

    note 1

    Working voltage setting

    value

    Time setting0s

    Voltage Vab

    100VThe operation

    value as the

    voltage gradually

    rises. note 5

    Setting value5

    Under-voltage

    relay (UV)

    (2)Operation

    time

    Working voltage setting

    value

    Time setting0s

    Vab,Vbc (note 6)

    Voltage Vab

    100V The operation

    value as the voltage

    gradually down.

    Setting value5

    min50ms

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    55/68

    UM43FG-E5AK type 23

    Note 4: TTheory operation time

    Theory operation time at Time magnification10%INPUTSI EI I2t VI LT

    300 6.30s 10.00s 80.00s 6.75s 60.0s

    500 4.28s 3.30s 28.80s 3.38s 30.0s

    700 3.53s 1.67s 14.69s 2.27s 20.0s

    1,000 2.97s 0.81s 7.20s 1.50s 13.3s

    Theory operation time formula for computation of the each over-current element

    SI1.0I

    0.140.02

    10

    LEI

    1.0I

    802

    10

    LI2t

    2I

    72010

    L It constant

    VII1

    13.510

    LLT

    I1

    12010

    L

    Precaution in the test

    (1)

    Allowable conduction time of phase current input circuit. CT secondary current: 5A/1A typeInput current Allowable energization time Input current Allowable energization time

    015A It can be energized continuously. 2040A 25s

    1520A 100s 4080A 6.3s

    80100A 4s

    Take the non-energization period over 1minute, after the current over rated 5A is applied, when the test is resumed.

    (I2t=(200A)21=40,000) between 40 times 1second conformed for JEC-2500 is a standard on the overload capacity.

    (2) Electric circuit largest applied voltage in the test. (The applied voltage of F-MPC60Bbody to input circuit.)

    Line voltageVab, Vbc, Vca 150V

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    56/68

    UM43FG-E5AK 33

    Basic test circuit

    (1) Instant, definite time and over-current relay test/ Over-voltage relay test/ Under-voltage test

    (50INST, 51DT1, 51DT2, 51, OV, UV)

    (2)Ground fault over-current relay test

    (51G, 51N)

    T.Tm F-MPC60B UM43FG-E5AK

    Current and voltage

    amplifier

    Oscillator

    A

    V

    I

    V

    AC100V

    AC100V

    Tester or buzzer(The case in which a selective output was set.)

    B1

    B2

    B29

    B30 tr ip

    Selective output

    Selective outputSelective output

    P

    N

    A13A15A14A16A21A23A22A24

    A9

    A10

    A11

    Ia

    Ic

    IbA17A19A18A20

    a

    b

    c

    Hour meter

    Tester or buzzer

    Current and voltage

    amplifier

    T.Tm

    Oscillator

    F-MPC60BUM43FG type

    I

    V

    AC100V

    AC100V

    A25

    A26

    B1

    B2

    B29

    B30 tr ip

    Selective output

    P

    N

    Io

    Hour meter

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    57/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    58/68

    100

    10

    1

    0.15

    0.1

    0.01

    100 200 500 1000 2000( )

    L=20.0

    15.0

    9 .0

    7 .0

    5 .0

    10.0

    8.0

    6.0

    4 .0

    3 .0

    2 .0

    1 .0

    0 .5

    ionmagnificattime10

    1I

    0.14t

    0.02 =

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    59/68

    100

    10

    1

    0.15

    0.1

    0.01

    100200 500 1000 2000( )

    L=20.0

    15.0

    9.0

    7.0

    5.0

    10.0

    8.0

    6.0

    4.0

    3.0

    2.01 .00 .5

    ionmagnificattime10

    I1

    13.5t =

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    60/68

    5.0

    L=20.0

    15.0

    9 .0

    7 .0

    10.0

    8.0

    6.0

    4 .0

    3 .0

    0 .5

    1 .0

    2 .0

    1000

    100

    10

    0.1

    100 200 500 1000 2000( )

    1

    ionmagnificattime10

    I1

    120t =

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    61/68

    100

    0.1

    100 200 500 1000 2000( )

    1

    10

    0.15

    L=20.0

    15.0

    10.0 9.0 8.0

    0.5 1 .0 2 .0 3.0 5 .0 7.06.04.0

    ionmagnifucattime10

    1I

    80t

    2 =

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    62/68

    1000

    0.1

    100 200 500 1000 2000( )

    1

    100

    0.15

    L=20.0

    15.010.0

    9 .07 .0

    10

    8.0

    5 .06.0

    4 .0

    3 .0

    2 .0

    1 .0

    0 .5

    ionmagnificattime10

    I

    720t

    2 =

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    63/68

    Appendix Figure 2 the outside connection diagram collection

    Application example 01the circuit diagram is a reference.

    By switching "REMOTE/LOCAL" switch in the panel plane of F-MPC60B (UM43FG-E5AK) to "REMOTE",

    CLOSE-OPENcontrol of the circuit breaker is changed from the outside.

    24

    CCInside of CB

    TRIP

    F-MPC60 UM43FG-E5AK

    Trip lock

    1 2 3 4

    26

    1

    2

    27

    TC

    5 6 7 8 13

    16

    30 25

    17 18 19 20 21 22 234

    N

    "Off (open)" is set at selective input of 1, and then, the case in, which on (close)is set, is shown in

    selection input of 2 in the following.

    Selective input of 1 (terminals number 5) is function setting code "70", and "off (open)" function is

    "10". Setting code No.70 is set at "10".

    Similarly, selective input of 2 (terminals number 6) is function setting code 71, and on (close)

    function is 11. Setting code No.71 is set at 11.

    Refer to section 5.1 and 5.2.

    28 29

    Developments

    LOCAL

    Note 1

    In case of the T link communication, it is operable

    at 2 places of "the outside" and "communication"

    in respect of the "REMOTE/LOCAL" switch, when

    "REMOTE" was chosen.

    Note 2

    It is possible by connecting field-center and

    selection switch with selective input circuit of the

    F-MPC60B main body, when it is surely made to be

    the one place operation.

    Application example 03

    REMOTE

    28 27

    Outside

    F-MPC60 UM43FG-E5AK

    Emergency

    stopPower lock

    CloseOpen

    CloseOpen

    Close

    Open

    Close

    Open Communication

    Selective input

    Selective outputAlarm

    Circuit breaker (CB) ON

    answer back signal

    Close Open

    9 10 11 12

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    64/68

    Application example 02the circuit diagram is a reference.

    It makes "REMOTE/LOCAL" switch of the F-MPC60B (UM43FG-E5AK)panel plane the invalidity, operation place

    (43D"REMOTE-LOCAL") is chosen in long way (external input by using selective input), and "CLOSE/OPEN" control

    of the circuit breaker is changed.

    Off (open)" is set at selective input of 1, and "on" is set at selection input of 2, and then, the case in which

    external 43D (the operation site selection) are set is shown in selective input of 3 in the following.

    Selective input of 1 (terminals number 5) is function setting code "70", and "off(open)" function is "10".

    Setting code No.70 is set at "10".

    Similarly, selective input of 2 (terminals number 6) is function setting code 71, and on(close)function is

    11. Setting code No.71 is set at 11.

    Similarly, selective input of 3(terminal number 7) is function setting code 72, and 43function is 12.

    Setting code No.72 is set at 12. Refer to section 5.1 and 5.2.

    "ON" in long way (43D).

    (It is judged after the setting with "LOCAL",

    when "OFF" is done.)

    24

    CC

    TRIP

    Power lock

    F-MPC60UM43FG-E5AK

    Alarm

    Selective outputTrip lock

    1 2 3 4

    261

    2

    27

    TC

    5 6 7 8 13

    16

    30 25

    17 18 19 20 21 22 234

    N

    28 29

    LOCAL

    Note 1

    It is possible by connecting field-center and

    selection switch with selective input circuit of

    the F-MPC60B main body, when it is surely

    made to be the one place operation.(Application example 03)

    REMOTE

    28 27

    Outside

    43D

    F-MPC60

    UM43FG-E5AK

    Emergency

    stop

    Inside of CB

    Developments

    Open Close

    Open Close

    Open Close

    CloseOpen

    Communication

    Selective inputClose Open

    Circuit breaker (CB) ON

    answer back signal

    9 10 11 12

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    65/68

    Application example 03The circuit diagram is a reference.

    It makes "REMOTE/LOCAL" switch of the F-MPC60B (UM43FG-E5AK)panel plane the invalidity, operation place

    (43D"REMOTE-LOCAL") is chosen in long way (external input), and "CLOSE/OPEN" control of the circuit breaker

    is changed. Moreover, equipping operation place priority diverted switch (43C "the field-center) is made to be a

    system of operation by "field: External input" or operation by "communication".Off(open)is set at selective input of 1,and on(close)is set at selective input of 2,and external 43D(Operation site

    selection) is set at selective input of 3,and then, the case in which operation place priority diverted switch (43C "the

    field-center) are set is shown in selective input of 4 in the following.

    Selective input of 1 (terminals number 5) is function setting code "70", and "off(open)" function is "10". Setting

    code No.70 is set at "10".

    Similarly, selective input of 2 (terminals number 6) is function setting code 71, and on(close)function is 11. Setting code

    No.71 is set at 11.

    Similarly, selective input of 3(terminal number 7) is function setting code 72, and 43D REMOTE-LOCALfunction is 12.

    Setting code No.72 is set at 12.

    Similarly, selective input of 4(terminal number 8) is function setting code 73, and 43C the field-center function is 13.

    Setting code No.73 is set at 13. Refer to section 5.1 and 5.2.

    24

    CC

    Inside of CB

    Close Open Trip

    Power lockEmergency

    Stop

    Selective outputTrip lock

    1 2 3 4

    26

    1

    2

    27

    TC

    5 6 7 8 13

    16

    30 25

    17 18 19 20 21 22 234

    N

    28 29

    ONin the field (43C)

    "ON" in long way (43D).

    Developments

    LOCAL

    Note:

    After setting each diverted switch, the signal is

    switched to other side, when "OFF" is done.

    Remote LocalThe fieldThe center

    (ON) (OFF) (ON) (OFF)

    REMOTE

    Communication

    28 27

    Outside

    43D

    F-MPC60

    UM3FG-E5AK

    The fieldThe center

    43C

    Open Close

    Selective input

    CloseOpen Close Open

    Open Close

    Alarm

    9 10 11 12

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    66/68

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    67/68

    Application example 05 the circuit breaker is put on by the trip in the external signal

    Example: the case in which it was applied to the large-capacity transformer.

    Figure 5.1 the configuration

    Figure 5.2 the conection

    CT

    PRT

    87T

    F-MPC60B ( UM43FG-E5AK

    Ratio differential protection

    TR

    266369

    Selective input

    5

    87T

    6 7 8 4Terminal number

    1 2 3 4

    F-MPC60B UM43FG-E5AK

    26 63 69 (No voltage contact)

    9 10 11 12

    5 6 7 8

  • 8/11/2019 6.2. F-MPC60B_manual_English (1).pdf

    68/68