Upload
anonymous-n5psqp
View
215
Download
0
Embed Size (px)
Citation preview
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
1/161
Floatless Level Switch (Compact, Plug-in Type)
61F-GP-N@
Space-saving Design Ideal for Control PanelDownsizing. Easy Maintenance.
• Compact: 49.4×
38×
84 mm (H×
W×
D).• Easy identification of operating status with LED operation
indicator.
• Independent DPDT contacts on 11-Pin Models.
• CE marking and UL/CSA compliance.
Refer to Safety Precautions for Floatless LevelControllers .
■Model Number Legend
■Ordering Information
Note: When ordering, specify the desired operating voltage at the end of the model number.
1. No. of Pins 2. Type
N: 11 pinsN8: 8 pins
Blank: General-purposeL 2KM: Long-distance (for 2 km)
L 4KM: Long-distance (for 4 km)
H: High-sensitivity
D: Low-sensitivity
R: Two-wire
T: High-temperature
Position of LED indicator
21
61F-GP-@@
Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)
Model Model Model
11-pin 61F-GP-N 61F-GP-NL 2KM 61F-GP-NL 4KM
Type High-sensitivity Low-sensitivity Two-wire
Model Model Model
11-pin 61F-GP-NH 61F-GP-ND 61F-GP-NR
Type Tropical environments High-temperature
Model Model
8-pin 61F-GP-N-TDL 61F-GP-NT
Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km)
Model Model Model
8-pin 61F-GP-N8 61F-GP-N8L 2KM 61F-GP-N8L 4KM
Type High-sensitivity Low-sensitivity Two-wire
Model Model Model
8-pin 61F-GP-N8H 61F-GP-N8D 61F-GP-N8R
61F-GP-N8HY
Example: 61F-GP-N [220 VAC]
Desired supply voltage
Cat. No. N42I-E-01
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
2/16
61F-GP-N@
2
■Compact Plug-in Models (11-pin Type)
Specifications
Note: 1. The length when using completely insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter asthe cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers .
2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between powerterminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions forFloatless Level Controllers .
3. Possible to use with 15 kΩ or less, however, this may cause reset failure.
4. 61F-GP-NH High-sensitivity Controller uses advanced operation.When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-nal relay will not operate.When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internalrelay will operate.If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation.
Item General-purposeController
61F-GP-N
High-temperatureController
61F-GP-NT
Long-distanceControllers
61F-GP-NL 2KM(for 2 km)
61F-GP-NL 4KM(for 4 km)
High-sensitivityController
61F-GP-NH(see note 4)
Low-sensitivityController
61F-GP-ND
Two-wireController
61F-GP-NR
Controlling materialsand operating condi-tions
For control of ordi-nary purified wateror sewage water
For control of ordi-nary purified wateror sewage whereoperating ambienttemperature ishigh.
For control of ordi-nary purified waterin cases where thedistance betweensewage pumpsand water tanks orbetween receivertanks and supplytanks is long orwhere remote con-trol is required.
For control of liq-uids with high spe-cific resistancesuch as distilledwater
For control of liq-uids with low spe-cific resistancesuch as salt water,sewage water,acid chemicals, al-kali chemicals
For control of ordi-nary purified wateror sewage waterused in combina-tion with Two-wireElectrode Holder(incorporating aresistor of 6.8 kΩ)
Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
Operating voltagerange
85% to 110% of rated voltage
Interelectrode voltage 8 VACInterelectrode current Approx. 1 mA AC max. Approx. 0.12 mA
AC max.Approx. 1 mA AC max.
Power consumption Approx. 3.5 VA max.
Interelectrode operateresistance
0 to approx. 4 kΩ 0 to approx. 4 kΩ 0 to approx. 1.3 kΩ(for 2 km)0 to approx. 0.5 kΩ(for 4 km)
Approx. 10 kΩ toapprox. 40 kΩ(see note 3)
0 to approx.1.3 kΩ
0 toapprox. 2 kΩ
Interelectrode releaseresistance
Approx. 15 k to∞ Ω
Approx. 15 k to∞ Ω
4 k to ∞ Ω (for 2km)2.5 k to ∞ Ω (for 4km)
Approx. 100 k to∞ Ω
Approx. 4 k to ∞ Ω Approx. 15 k to∞ Ω
Response time Operate:80 ms max.Release:160 ms max.
Cable length(see note 1) 1 km max. 600 m max. 2 km max.4 km max. 50 m max. 1 km max. 800 m max.
Control output 1 A, 250 VAC (Inductive load: cosφ = 0.4)3 A, 250 VAC (Resistive load)
Ambient temperature Operating:–10 to 55°C (–10 to 70°C for high-temperature controller)
Ambient humidity Operating:45% to 85% RH
Insulation resistance(see note 2)
100 MΩ min. (at 500 VDC)
Dielectric strength(see note 2)
2000 VAC, 50/60 Hz for 1 min.
Life expectancy Electrical: 100,000 operations min.Mechanical:5,000,000 operations min.
Weight Approx. 155 g
Accessories Hold-down clip PFC-N8
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
3/16
61F-GP-N@
3
Internal Circuit Diagrams
Note: When applying a self-holding circuit, short between terminals 5 and 6 and use terminal 7 as E2.
61F-GP-N/-NT/-NL/-ND 61F-GP-NR61F-GP-NH
3 9 14 1011
U
24 V
8 V
Control circuit
S0 S1 E3
5
E1 Ta1 Tc1 Tb1
867
U
Ta2 Tc2 Tb2
3 9 14 1011
U
24 V
8 V
Control circuit
S0 S1 E3
5
E1 Ta1 Tc1 Tb1
867
U
Ta2 Tc2 Tb2
3 9 14 1011
U
24 V
8 V
Control circuit
S0 S1 E3
5
E1 Ta1 Tc1 Tb1
U
Power supply Power supply Power supply
(See note.) (See note.)
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
4/16
61F-GP-N@
4
■Connections
Automatic Water Supply Control Automatic Drainage Control
Compact, Plug-in Type61F-GP-N
Dimensions:
page 14
Automatic Water Supply andDrainage Control
Water supplysource
MCCB
R S
M
TCommercial Voltage 61F-GP-N
PS-3S
Stop
3 9
E2E3
E1
P
Start
8 VPowersupply
0 V U
U
U
24 VControlcircuit
(See note.)
4
8 7 6 5
10 11 1 2
Contac-tor
Watertank
Motorprotectionrelay
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
Connection SocketsPF113A (Front-connecting)PL11 (Rear-connecting)
Connect terminal 1 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
Connections
Reservoir
MCCB
R S
M
TCommercial Voltage 61F-GP-N
PS-3S
3 9
E2E3
E1
P
8 V
0 V U
U
U
24 VControlcircuit
(See note.)
4
8 7 6 5
10 11 1 2
Start
Stop
Contac-tor
Powersupply
Motorprotectionrelay Waste-
watertank
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
Connection SocketsPF113A (Front-connecting)PL11 (Rear-connecting)
Connect terminal 1 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
Connections
E1
E2
E3
P
Water
supply
(Indicator ON)Pump OFF
Pump ON (Indicator OFF)
The pump stops when the water level reaches E1 (indicator ON)and starts when the water level drops below E2 (indicator OFF).
Principles of Operation
E1
E2
E3
Water drainage
(Indicator ON)
Pump OFF
Pump ON
(Indicator OFF)
P
The pump starts when the water level reaches E1 (indicator ON)and stops when the water level drops below E2 (indicator OFF).
Principles of Operation
http://-/?-http://-/?-
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
5/16
61F-GP-N@
5
Liquid Level Indication
Liquid Level Indication(Connection Example)
Compact, Plug-in Type61F-GP-N
Dimensions:
page 14
E1
E2
E3E4
Water supplysource
Intermediate
Upper limit
Lower limit
MCCB
R S
M
T
Commercial Voltage
P
PS-4S
U
U
61F-GP-N
Lower limit Intermediate Upper limit
5678
4
8 VPowersupply
Powersupply
Powersupply
0 V 24 V
10
3 9
1 211
Controlcircuit
U
U
U
61F-GP-N
5678
4
8 V
0 V 24 V
10
3 9
1 211
Controlcircuit
U
U
U
61F-GP-N
5678
4
8 V
0 V 24 V
10
3 9
1 211
Controlcircuit
U
(See note.)
Watertank
Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for thecommon Electrode (the longest Electrode, terminal 4).
Connections
Terminals 6 and 7, and terminals 10 and 11 on the lower -limit 61F-GP-N are shorted when the water level reaches E3 (indicator ON).
• Terminals 6 and 7, and terminals 10 and 11 on the intermediate 61F-GP-N are shorted when the water level reaches E2 (indicator ON).
• Terminals 6 and 7, and terminals 10 and 11 on the upper-limit 61F-GP-N are shorted when the water level reaches E1 (indicator ON).
Principles of Operation
http://-/?-http://-/?-
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
6/16
61F-GP-N@
6
Replacing 61F-G3N Functions
Replacing 61F-G3N Functions (Automatic WaterSupply Control with Abnormal Water Increase andWater Shortage Alarms)
Compact, Plug-in Type61F-GP-N
Dimensions:
page 14
E1
E2
E4E5
Contactor
Water supplysource
Stop
Full tank
Start
Water shortage
MCCB
R S
M
T
Commercial Voltage
Water shortage Pump control Full tank
P
PS-5S
E3
U3
U3
61F-GP-N
5678
4
8 VPowersupply
Powersupply
Powersupply
0 V 24 V
10
3 9
1 211
Control
circuit
U3
U1
U1
61F-GP-N
5678
4
8 V
0 V 24 V
10
3 9
1 211
Control
circuit
U1
U2
U2
61F-GP-N
5678
4
8 V
0 V 24 V
10
3 9
1 211
Control
circuit
U2
BPL PL
(See note.)
Upper limitLower limit Alarm
Watertank
Motor protection
relay
Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for the common Electrode(the longest Electrode, terminal 4).
Connections
E1
E3
E4E5
Upper
limit
Lower
limit
Pump OFF
Pump ON
(U1 indicator ON)
(U2 indicator ON)
(U2 indicator OFF)
(U3 indicator OFF)
BLH
BLL
P
Water supply
E2
• The pump stops when the water levelreaches E2 (U2 indicator ON) and startswhen the water level drops below E3 (U2 indicator OFF).
• If the water level rises to E1 for any reason,the upper-limit indicator turns ON and thealarm sounds (U1 indicator ON).If the water level drops below E4 for anyreason, the lower-limit indicator turns ONand the alarm sounds (U3 indicator OFF).
Principles of Operation
http://-/?-http://-/?-
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
7/16
61F-GP-N@
7
Automatic Water Supply Control Automatic Drainage Control
Two-Wire ConnectionsAutomatic Water Supply and Drainage Control
Compact, Plug-in Type61F-GP-NR
Dimensions:
page 14
E1E2
E3
U
U
Water supplysource
Stop
Start
MCCB
R S
M
TCommercial Voltage
61F-GP-NR
(See note.)
5
4
P
8 VPowersupply
0 V 24 V
PS-3SR
10
3 9
1 211
Controlcircuit
R
Contac-tor
Watertank
Motorprotectionrelay
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
Connection SocketsPF113 (Front-connecting)PL11 (Rear-connecting)
• Connect terminal 1 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
• With 2-wire connections, only two wires are required betweenthe 61F-GP-NR and Electrode Holder, but three wires arerequired for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.(Resistance R is built into Electrode Holders for 2-WireConnections.)
Connections
E1E2
U
U
Reservoir
MCCB
R S
M
T61F-GP-NR
(See note.)
5
4
P
R
8 V
0 V 24 V
PS-3SR
10
3 9
1 211
Controlcircuit
E3
Contac-tor
TCommercial Voltage
Powersupply
Motorprotectionrelay
Waste-watertank
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
Connection SocketsPF113 (Front-connecting)PL11 (Rear-connecting)
• Connect terminal 11 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
• With 2-wire connections, only two wires are required betweenthe 61F-GP-NR and Electrode Holder, but three wires arerequired for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.(Resistance R is built into Electrode Holders for 2-WireConnections.)
Connections
E1
E2
E3
P
Watersupply
(Indicator ON)Pump OFF
Pump ON (Indicator OFF)
The pump stops when the water level reaches E1 (indicator ON)and starts when the water level drops below E2 (indicator OFF).
Principles of Operation
E1
E2
E3
Water drainage
(Indicator ON)
Pump OFF
Pump ON
(Indicator OFF)
P
The pump starts when the water level reaches E1 (indicator ON)and stops when the water level drops below E2 (indicator OFF).
Principles of Operation
http://-/?-http://-/?-
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
8/16
61F-GP-N@
8
■Connection with Three-phase Four-line CircuitWhen supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.Line voltage (R-S, S-T, or R-T): 380 or 415 VACPhase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-GP-N@ 220 or 240 VAC
Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 1 to terminal 11.
2. Be sure to ground terminal 4.
Power source380 or 415 VACR S T N *
M
Watertank
Stop
StartE2
E3
E1
P
Electromagnetic switch
A
*
Water supply source
Source voltage:between 3 and 9
61F-GP-N
0 V
220 or240 V
8 V
24 V Control circuit
U
U
78 6 5
211110
U
4
3 9
(See note 1)
(See note 2.)
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
9/16
61F-GP-N@
9
■Compact Plug-in Models (8-pin Type)
Specifications
Note: 1. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter asthe cable diameter or number of conductors becomes larger.
2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power ter-minals and contact terminals, and between Electrode terminals and contact terminals.
3. Possible to use with 15 kΩ or less, however, this may cause reset failure.
4. 61F-GP-N8H/-N8Y High-sensitivity Controllers use advanced operation.When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter-nal relay will not operate.When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal
relay will operate.If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation.
Item General-purposeController
61F-GP-N861F-GP-N8Y (see note 4)
Long-distanceControllers
61F-GP-N8L 2KM(for 2 km)
61F-GP-N8L 4KM(for 4 km)
High-sensitivityControllers
61F-GP-N8H61F-GP-N8HY(see note 4)
Low-sensitivityController
61F-GP-N8D
Two-wireController
61F-GP-N8R
VariableSensitivityController
61F-GP-N8-V50
Controlling mate-rials and operat-ing conditions
For control of ordi-nary purified wateror sewage water
For control of ordi-nary purified waterin cases where thedistance betweensewage pumps andwater tanks or be-tween receivertanks and supplytanks is long orwhere remote con-trol is required.
For control of liq-uids with high spe-cific resistancesuch as distilledwater
For control of liq-uids with low spe-cific resistancesuch as salt water,sewage water, acidchemicals, alkalichemicals
For control of ordi-nary purified wateror sewage waterused in combina-tion with Two-wireElectrode Holder(incorporating a re-sistor of 6.8 kΩ)
For control of caseswhere variable sen-sitivity control is re-quired such asdetection of froth onthe surface of a liq-uid, control of soilmoisture content,or detection of de-gree of water pollu-tion
Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz 24, 110, 220 or240 VAC; 50/60 Hz
Operating voltage
range
85% to 110% of rated voltage
Interelectrodevoltage
8 VAC 24 VAC 8 VAC 24 VAC
Interelectrodecurrent
Approx. 1 mA AC max. Approx.0.4 mA AC max.
Approx. 1 mA AC max. Approx. 3 mA ACmax.
Power consump-tion
Approx. 3.5 VA max.
Interelectrode op-erate resistance
0 to approx. 4 kΩ 0 to 1.3 kΩ (for2 km)0 to 0.5 kΩ (for4 km)
Approx. 15 kΩ toapprox. 70 kΩ(see note 3)
0 to approx. 1.3 kΩ 0 to approx. 2 kΩ 0 to 50 kΩ (Vari-able)
Interelectrode re-lease resistance
Approx. 15 k to ∞ Ω 4 k to ∞ Ω(for 2 km)2.5 k to ∞ Ω(for 4 km)
Approx. 300 k to∞ Ω
Approx. 4 k to ∞ Ω Approx. 15 k to∞ Ω Operating resis-tance +50 kΩ max.
Response time Operate: 80 ms max.Release: 160 ms max.
Cable length(see note 1)
1 km max. 2 km max.4 km max.
50 m max. 1 km max. 800 m max. 50 m max.
Control output 1 A, 250 VAC (Inductive load: cosφ = 0.4)3 A, 250 VAC (Resistive load)
Ambient tempera-ture
Operating: –10 to 55°C
Ambient humidity Operating: 45% to 85% RH
Insulation resis-tance(see note 2)
100 MΩ min. (at 500 VDC)
Dielectricstrength
(see note 2)
2000 VAC, 50/60 Hz for 1 min.
Life expectancy Electrical: 100,000 operations min.Mechanical: 5,000,000 operations min.
Weight Approx. 155 g
Accessories Hold-down clip PFC-N8
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
10/16
61F-GP-N@
10
Internal Circuit Diagrams
24 V
24 V
Control circuit
Power supply
Control circuit24 V
Power supply
8 V (see note)
61F-GP-N8/-N8L/-N8D/-N8HY 61F-GP-N8H 61F-GP-N8R
24 V
8 V
Power supply
Control circuit
2
243
61F-GP-N8Y
24 V
8 V
Control circuit
Power supply
Note: 24 V for the 61F-GP-N8HY.
Control circuit24 V
Power supply
24 V
61F-GP-N8-V50
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
11/16
61F-GP-N@
11
Automatic Water Supply Control Automatic Drainage Control
Automatic Water Supply and Drainage Control Compact, Plug-in Type61F-GP-N8
Dimensions:
page 14
Water supplysource
MCCB
R S
M
TCommercial Voltage
61F-GP-N8
PS-3S
Stop
E2E3
E1
P
Start
8 V0 V
U
U
U
24 VControlcircuit
(See note.)
2 1 8 7
3 4 5 6
Watertank
Contac-
tor
Powersupply
Motorprotectionrelay
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
Connection SocketsPF083A (Front-connecting)PL08 (Rear-connecting)
• Connect terminal 2 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
Connections
Reservoir
MCCB
R S
M
T
61F-GP-N8
P
8 V0 V
U
U
U
24 V
(Seenote.)
3 4 5 6
PS-3S
E2E3
E1
Start
Stop
2 1 8 7
Control circuit
Contac-tor
Powersupply
Motorprotectionrelay Waste-
watertank
Commercial Voltage
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
Connection SocketsPF083A (Front-connecting)PL08 (Rear-connecting)
• Connect terminal 3 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
Connections
E1
E2
E3
P
Watersupply
(Indicator ON)Pump OFF
Pump ON (Indicator OFF)
The pump stops when the water level reaches E1 (indicator ON)and starts when the water level drops below E2 (indicator OFF).
Principles of Operation
E1
E2
E3
Water drainage
(Indicator ON)
Pump OFF
Pump ON
(Indicator OFF)
P
Principles of Operation
The pump starts when the water level reaches E1 (indicator ON)and stops when the water level drops below E2 (indicator OFF).
http://-/?-http://-/?-
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
12/16
61F-GP-N@
12
Water Supply Automatic Drainage
Two-Wire ConnectionsAutomatic Water Supply and Drainage Control
Compact, Plug-in Type61F-GP-N8R
Dimensions:
page 14
E1E2
E3
U
U
A
Water supplysource
Stop
Start
MCCB
R S
M
T 61F-GP-N8R
7812
P
8 V0 V
24 V
PS-3SR
3 5 64
Controlcircuit
R
(See note.)
Watertank
Contac-
tor
Commercial Voltage
Powersupply
Motorprotectionrelay
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
• Connect terminal 2 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
• With 2-wire connections, only two wires are required betweenthe 61F-GP-N8R and Electrode Holder, but three wires arerequired for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.(Resistance R is built into Electrode Holders for 2-WireConnections.)
Connections
E2E3
U
U
A
Reservoir
MCCB
R S
M
T61F-GP-N8R
(Seenote.)
7812
P
R
8 V0 V
24 V
PS-3SR
3 5 64
Controlcircuit
Stop
StartE1
Contac-tor
Commercial Voltage
Powersupply
Motorprotectionrelay
Waste-watertank
Note: Be sure to ground the common Electrode E3 (thelongest Electrode).
• Connect terminal 3 to the contactor’s coil terminal.
Note: The power supply depends on the specifications of themodel.
• With 2-wire connections, only two wires are required betweenthe 61F-GP-N8R and Electrode Holder, but three wires arerequired for the Electrodes.
• The Electrode Holder must be specified for 2-wire connections.(Resistance R is built into Electrode Holders for 2-WireConnections.)
Connections
E1
E2
E3
P
Watersupply
(Indicator ON)Pump OFF
Pump ON (Indicator OFF)
The pump stops when the water level reaches E1
(indicator ON)and starts when the water level drops below E2 (indicator OFF).
Principles of Operation
E1
E2
E3
Water drainage
(Indicator ON)
Pump OFF
Pump ON
(Indicator OFF)
P
The pump starts when the water level reaches E1
(indicator ON)and stops when the water level drops below E2 (indicator OFF).
Principles of Operation
http://-/?-http://-/?-
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
13/16
61F-GP-N@
13
■Connection with Three-phase Four-line CircuitWhen supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.Line voltage (R-S, S-T, or R-T): 380 or 415 VACPhase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-GP-N8@, 220 or 240 VAC
Note: Be sure to ground terminal 1.
Power source380 to 415 VAC
R S T N *
M
Water tankStop
StartE2E3
E1
P
6
Electromagnetic switch
Transformer
4 3
7
5
1 2
U
24 V
8 V
A
*
U Controlcircuit
8
Water supply source
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
14/16
61F-GP-N@
14
Dimensions
Note: All units are in millimeters unless otherwise indicated.
■Safety PrecautionsRefer to Safety Precautions for All Level Controllers .
49.4
38 70
84
61F-GP-N
PF113A
101
61F- P-N, -NT, -NL, -NH, -ND, -NR, -N -TDL, -N14, -N15, -NH3 When mounting a Display Unit to a PF113ASurface-mounting Socket, secure the PF113A withthe groove facing toward the bottom and thenconnect the 61F-GP-N the PFC-N8 accessory.
PFC-N8
Note: PFC-N8 Mounting Bracket (provided withthe Level Controller)
t = 0.3
4.5
83
4
6
Approx.80
38 70
84
49.4
61F-GP-N8
PF083A
91
61F-GP-N8, -N8L, -N8H, -N8HY, -N8D, -N8R Use a PFC-N8 Mounting Bracket to mount theLevel Controller to a PF083A Rail-mountedSocket.
PFC-N8
Note: PFC-N8 Mounting Bracket (provided withthe Level Controller)
83
4
4.5
t=0.36
Approx.
80
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
15/16
Terms and Conditions of Sale1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed
part of al l quotes, agreements, purchase orders, acknowledgments, price lists,catalogs, manuals, brochures and other documents, whether electronic or inwriting, relating to the sale of products or services (collectively, the "Products")by Omron Electronics LLC and its subsidiary companies (“Omron”). Omronobjects to any terms or conditions proposed in Buyer’s purchase order or otherdocuments which are inconsistent with, or in addition to, these Terms.
2. Prices; Payment Terms. All prices stated are current, subject to change with-
out notice by Omron. Omron reserves the right to increase or decrease priceson any unshipped portions of outstanding orders. Payments for Products aredue net 30 days unless otherwise stated in the invoice.
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoicessent to Buyer after deducting transportation charges, taxes and duties, and willbe allowed only if (i) the invoice is paid according to Omron’s payment termsand (ii) Buyer has no past due amounts.
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month orthe maximum legal rate, whichever is less, on any balance not paid within thestated terms.
5. Orders. Omron will accept no order less than $200 net billing.6. Governmental Approvals. Buyer shall be responsible for, and shall bear all
costs involved in, obtaining any government approvals required for the impor-tation or sale of the Products.
7. Taxes. All taxes, duties and other governmental charges (other than generalreal property and income taxes), including any interest or penalties thereon,imposed directly or indirectly on Omron or required to be collected directly orindirectly by Omron for the manufacture, production, sale, delivery, importa-tion, consumption or use of the Products sold hereunder (including customsduties and sales, excise, use, turnover and license taxes) shall be charged toand remitted by Buyer to Omron.
8. Financial. If the financial position of Buyer at any time becomes unsatisfactoryto Omron, Omron reserves the right to stop shipments or require satisfactorysecurity or payment in advance. If Buyer fails to make payment or otherwisecomply with these Terms or any related agreement, Omron may (without liabil-ity and in addition to other remedies) cancel any unshipped portion of Prod-ucts sold hereunder and stop any Products in transit until Buyer pays allamounts, including amounts payable hereunder, whether or not then due,which are owing to it by Buyer. Buyer shall in any event remain liable for allunpaid accounts.
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellationunless Buyer indemnifies Omron against all r elated costs or expenses.
10. Force Majeure. Omron shall not be liable for any delay or failure in deliveryresulting from causes beyond its control, including earthquakes, fires, floods,strikes or other labor disputes, shortage of labor or materials, accidents tomachinery, acts of sabotage, riots, delay in or lack of transportation or therequirements of any government authority.
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship
except in “break down” situations.b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall
constitute delivery to Buyer;c. All sales and shipments of Products shall be FOB shipping point (unless oth-
erwise stated in writing by Omron), at which point title and risk of loss shallpass from Omron to Buyer; provided that Omron shall retain a security inter-est in the Products until the full purchase price is paid;
d. Delivery and shipping dates are estimates only; ande. Omron will package Products as it deems proper for protection against nor-
mal handling and extra charges apply to special conditions.12. Claims. Any claim by Buyer against Omron for shortage or damage to the
Products occurring before delivery to the carrier must be presented in writingto Omron within 30 days of receipt of shipment and include the original trans-portation bill signed by the carrier noting that the carrier received the Productsfrom Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that theProducts will be free from defects in materials and workmanship for a period oftwelve months from the date of sale by Omron (or such other period expressedin writing by Omron). Omron disclaims all other warranties, express or implied.(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THEPRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIRINTENDED USE. Omron further disclaims all warranties and responsibility ofany type for claims or expenses based on infringement by the Products or oth-erwise of any in tellectual property right. (c) Buyer Remedy. Omron’s sole obli-gation hereunder shall be, at Omron’s election, to (i) replace (in the formoriginally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complyingProduct, or (iii) repay or credit Buyer an amount equal to the purchase price ofthe non-complying Product; provided that in no event shall Omron be responsi-ble for warranty, repair, indemnity or any other claims or expenses regardingthe Products unless Omron’s analysis confirms that the Products were prop-erly handled, stored, installed and maintained and not subject to contamina-tion, abuse, misuse or inappropriate modification. Return of any Products byBuyer must be approved in writing by Omron before shipment. Omron Compa-nies shall not be liable for the suitability or unsuitability or the results from theuse of Products in combination with any electrical or electronic components,circuits, system assemblies or any other materials or substances or environ-ments. Any advice, recommendations or information given orally or in writing,are not to be construed as an amendment or addition to the above warranty.See http:// www.omron247.com or contact your Omron representative for pub-lished information.
14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLEFOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANYWAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM ISBASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.Further, in no event shall liability of Omron Companies exceed the individualprice of the Product on which liability is asserted.
15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies andtheir employees from and against all liabilities, losses, claims, costs andexpenses (including attorney's fees and expenses) related to any claim, inves-tigation, litigation or proceeding (whether or not Omron is a party) which arisesor is alleged to arise from Buyer's acts or omissions under these Terms or inany way with respect to the Products. Without limiting the foregoing, Buyer (atits own expense) shall indemnify and hold harmless Omron and defend or set-tle any action brought against such Companies to the extent based on a claimthat any Product made to Buyer specifications infringed intellectual propertyrights of another party.
16. Property; Confidentiality. Any intellectual property in the Products is the exclu-sive property of Omron Companies and Buyer shall not attempt to duplicate itin any way without the written permission of Omron. Notwithstanding anycharges to Buyer for engineering or tooling, all engineering and tooling shallremain the exclusive property of Omron. All information and materials suppliedby Omron to Buyer relating to the Products are confidential and proprietary,and Buyer shall limit distribution thereof to its trusted employees and strictlyprevent disclosure to any third party.
17. Export Controls. Buyer shall comply with all applicable laws, regulations andlicenses regarding (i) export of products or information; (iii) sale of products to“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of
regulated technology or information.18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any rightand no course of dealing between Buyer and Omron shall operate as a waiverof rights by Omron. (b) Assignment. Buyer may not assign its rights hereunderwithout Omron's written consent. (c) Law. These Terms are governed by thelaw of the jurisdiction of the home office of the Omron company from whichBuyer is purchasing the Products (without regard to conflict of law princi-ples). (d) Amendment. These Terms constitute the entire agreement betweenBuyer and Omron relating to the Products, and no provision may be changedor waived unless in writing s igned by the par ties. (e) Severability. If any provi-sion hereof is rendered ineffective or invalid, such provision shall not invalidateany other provision. (f) Setoff. Buyer shall have no right to set off any amountsagainst the amount owing in respect of this invoice. (g) Definitions. As usedherein, “including” means “including without limitation”; and “Omron Compa-nies” (or similar words) mean Omron Corporation and any direct or indirectsubsidiary or affiliate thereof.
Certain Precautions on Specifications and Use1. Suitability of Use. Omron Companies shall not be responsible for conformity
with any standards, codes or regulations which apply to the combination of theProduct in the Buyer’s application or use of the Product. At Buyer’s request,Omron will provide applicable third party certification documents identifyingratings and limitations of use which apply to the Product. This information byitself is not sufficient for a complete determination of the suitability of the Prod-uct in combination with the end product, machine, system, or other applicationor use. Buyer shall be solely responsible for determining appropriateness ofthe particular Product with respect to Buyer’s application, product or system.Buyer shall take application responsibility in all cases but the following is anon-exhaustive list of applications for which particular attention must be given:(i) Outdoor use, uses involving potential chemical contamination or electricalinterference, or conditions or uses not described in this document.(ii) Use in consumer products or any use in significant quantities.(iii) Energy control systems, combustion systems, railroad systems, aviationsystems, medical equipment, amusement machines, vehicles, safety equip-ment, and installations subject to separate industry or government regulations.(iv) Systems, machines and equipment that could present a risk to life or prop-erty. Please know and observe all prohibitions of use applicable to this Prod-uct.NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUTENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THEOVERALL EQUIPMENT OR SYSTEM.
2. Programmable Products. Omron Companies shall not be responsible for theuser’s programming of a programmable Product, or any consequence thereof.
3. Performance Data. Data presented in Omron Company websites, catalogsand other materials is provided as a guide for the user in determining suitabil-ity and does not constitute a warranty. It may represent the result of Omron’stest conditions, and the user must correlate it to actual application require-ments. Actual performance is subject to the Omron’s Warranty and Limitationsof Liability.
4. Change in Specifications. Product specifications and accessories may bechanged at any time based on improvements and other reasons. It is our prac-tice to change part numbers when published ratings or features are changed,or when significant construction changes are made. However, some specifica-tions of the Product may be changed without any notice. When in doubt, spe-cial part numbers may be assigned to fix or establish key specifications foryour application. Please consult with your Omron’s representative at any timeto confirm actual specifications of purchased Product.
5. Errors and Omissions. Information presented by Omron Companies has beenchecked and is believed to be accurate; however, no responsibility is assumed
for clerical, typographical or proofreading erro rs or omissions.
8/19/2019 61F-GP-N Level Switch Datasheet en N42I-E-01
16/16
OMRON CANADA, INC. • HEAD OFFICE Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com
OMRON ELECTRONICS DE MEXICO • HEAD OFFICEMéxico DF • 52.55.59.01.43.00 • 01-800-226-6766 • [email protected]
OMRON ELECTRONICS DE MEXICO • SALES OFFICEApodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • [email protected]
OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICESão Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br
OMRON ARGENTINA • SALES OFFICECono Sur • 54.11.4783.5300
OMRON CHILE • SALES OFFICESantiago • 56.9.9917.3920
OTHER OMRON LATIN AMERICA SALES54.11.4783.5300
Au tho ri zed Dist ri bu tor : Automation Control Systems• Machine Automation Controllers (MAC) • Programmable Controllers (PLC)
• Operator interfaces (HMI) • Distributed I/O • Software
Drives & Motion Controls• Servo & AC Drives • Motion Controllers & Encoders
Temperature & Process Controllers • Single and Multi-loop Controllers
Sensors & Vision• Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors
• Amplified Photomicrosensors • Measurement Sensors
• Ultrasonic Sensors • Vision Sensors
Industrial Components • RFID/Code Readers • Relays • Pushbuttons & Indicators
• Limit and Basic Switches • Timers • Counters • Metering Devices
• Power Supplies
Safety• Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety
Controllers • Light Curtains • Safety Relays • Safety Interlock Switches
OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Hoffman Estates, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com
OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu