    Field Panel GOUser's Manual545-001 Revision January 27, 2006

  • 7/29/2019 545001 Field Go Manual

    2/98

    Notice

    Document information is subject to change without notice and should not be construed as a commitment by SiemensBuilding Technologies, Inc. Companies, names, and various data used in examples are fictitious unless otherwisenoted. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in thisdocument. No part of this document may be reproduced or transmitted in any form or by any means, electronic ormechanical, for any purpose, without the express written permission of Siemens Building Technologies, Inc.

    All software described in this document is furnished under a license agreement and may be used or copied only inaccordance with license terms.

    For further information, contact your nearest Siemens Building Technologies, Inc. representative.

    Copyright 2006 by Siemens Building Technologies, Inc.

    Credits

    APOGEE and Insight are registered trademarks of Siemens Building Technologies, Inc.

    LonWorks is a registered trademark of Echelon Corporation.Internet Explorer is a trademark of Microsoft Corporation.

    JVM is a trademark of Sun Microsystems, Inc.

    Ethernet is a registered trademark of Xerox Corporation.

    Other product or company names mentioned herein may be the trademarks of their respective owners.

    Contact Us

    Your feedback is important to us. If you have comments about this manual, please submit them [email protected].

    Country of Origin: US

  • 7/29/2019 545001 Field Go Manual

    3/98

    END USER LICENSE AGREEMENT

    IMPORTANTREAD CAREFULLY: This End-User License Agreement ("EULA") is a legal

    agreement between you and Siemens Building Technologies, Inc. from which you obtainedlimited nonexclusive rights to use the FIELD PANEL GO Firmware Product. By installing,receiving, implementing or otherwise using the Siemens Building Technologies, Inc. FIELDPANEL GO Firmware Product, you agree to be bound by the terms of this EULA. If you donot agree with the terms, Siemens Building Technologies, Inc. is unwilling to license theFIELD PANEL GO Firmware Product to you. In such event, you should promptly contactSiemens Building Technologies, Inc. for instructions on return of the FIELD PANEL GOFirmware Product.

    Siemens Building Technologies, Inc. provides this FIELD PANEL GO Firmware Product andlicenses its use by the terms herein. You assume responsibility for the selection of the FIELDPANEL GO Firmware Product to achieve your intended results.

    GRANT OF LICENSE.

    If the FIELD PANEL GO Firmware Product was obtained by you for use on a singlemachine, then you may only install the FIELD PANEL GO Firmware Product on asingle machine at any one time.

    If you obtained functionalities from Siemens Building Technologies, Inc. that permitnetworked use of the FIELD PANEL GO Firmware Product, you may only install theFIELD PANEL GO Firmware Product over an internal network for use, at any onetime, by the number of active concurrent users for which you obtained an EULA.

    You may not sublicense, assign or transfer the EULA or the FIELD PANEL GOFirmware Product. Any attempt to sublicense, assign or transfer any of the rights,duties or obligations hereunder is void.

    YOU MAY NOT OTHERWISE COPY, DISTRIBUTE OR TRANSFER THE FIELD

    PANEL GO FIRMWARE PRODUCT. IF YOU TRANSFER POSSESSION OF ANY COMPLETE COPY OR PORTION OF

    THE FIELD PANEL GO FIRMWARE PRODUCT TO ANOTHER PARTY, WITHOUTTHE EXPRESS WRITTEN CONSENT OF SIEMENS BUILDING TECHNOLOGIES,INC, YOUR LICENSE IS AUTOMATICALLY TERMINATED. YOU RECOGNIZE

    THAT SUCH TERMINATION IS NOT A COMPLETE REMEDY AND SIEMENSBUILDING TECHNOLOGIES, INC. IS ENTITLED TO SEEK FURTHER RELIEFSHOULD YOU VIOLATE THIS EULA.

    REVERSE ENGINEERING, DISASSEMBLY.

    You are prohibited from reverse engineering, disassembling, decompiling, or decoding theobject code provided to you, or otherwise translating the object code for the FIELD PANELGO Firmware Product, or permitting any third party to do the same. You recognize that your

    rights to use the FIELD PANEL GO Firmware are strictly limited to use of the code in theobject form as provided to you by Siemens Building Technologies, Inc. pursuant to thisEULA.

  • 7/29/2019 545001 Field Go Manual

    4/98

    TERM.

    The EULA is effective until terminated. You may terminate it at any time by destroying theFIELD PANEL GO Firmware Product together with all copies in any form. It will also

    terminate upon conditions set forth elsewhere in the EULA or if you fail to comply with anyterm or condition of this EULA. You agree upon such termination to destroy the FIELDPANEL GO Firmware Product together with all copies.

    LIMITED WARRANTY.

    THE FIELD PANEL GO FIRMWARE PRODUCT IS PROVIDED "AS IS" WITHOUTWARRANTY OF ANY KIND, EITHER EXPRESSED OR IMPLIED, INCLUDING, BUT NOTLIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR APARTICULAR PURPOSE. THE ENTIRE RISK AS TO THE QUALITY ANDPERFORMANCE OF THE FIELD PANEL GO FIRMWARE PRODUCT IS WITH YOU.SHOULD THE FIELD PANEL GO FIRMWARE PRODUCT PROVE DEFECTIVE, YOUASSUME THE ENTIRE COST OF ALL NECESSARY SERVICING, REPAIR ORCORRECTION.

    Siemens Building Technologies, Inc. does not warrant the functions contained in the FIELDPANEL GO Firmware Product will meet your requirements or that the operation of the FIELDPANEL GO Firmware Product will be uninterrupted or error free.

    However, Siemens Building Technologies, Inc. warrants the media on which the FIELDPANEL GO Firmware Product is furnished to be free from defects in materials andworkmanship under normal use for a period of ninety days from the date of shipment.

    LIMITATIONS ON REMEDIES.

    Siemens Building Technologies, Inc.s entire liability and your exclusive remedy shall be:

    the replacement of any media not meeting Siemens Building Technologies, Inc."Limited Warranty" and which is returned to Siemens Building Technologies, Inc. oran authorized Siemens Building Technologies, Inc. distributor, or

    if Siemens Building Technologies, Inc. or an authorized Siemens BuildingTechnologies, Inc. distributor is unable to deliver a replacement media which is freeof defects in materials or workmanship, you may terminate the EULA by returning theFIELD PANEL GO Firmware Product and your money will be refunded.

    IN NO EVENT WILL SIEMENS BUILDING TECHNOLOGIES, INC. BE LIABLE TO YOU FORANY DAMAGES INCLUDING ANY LOST PROFITS, LOST SAVINGS OR OTHERINCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE ORINABILITY TO USE SUCH PRODUCT EVEN IF SIEMENS BUILDING TECHNOLOGIES,INC. OR ANY AUTHORIZED SIEMENS BUILDING TECHNOLOGIES, INC. DISTRIBUTORHAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES OR FOR ANY CLAIMBY ANY OTHER PARTY.

    TERMINATION.Upon termination of this EULA, all rights granted to you will terminate and revert to Licensor.Promptly upon termination of this EULA for any reason or upon discontinuance orabandonment of your possession or use of the FIELD PANEL GO Firmware Product, youmust return or destroy all copies of the FIELD PANEL GO Firmware Product in yourpossession, and all other materials pertaining to the FIELD PANEL GO Firmware Product(including all copies thereof). You agree to certify your compliance with such restriction uponLicensor's request.

  • 7/29/2019 545001 Field Go Manual

    5/98

    GENERAL.

    This EULA will be governed by the laws of the State of Illinois, USA. Because somestates/jurisdictions do not allow the exclusion or limitation of liability for consequential or

    incidental damages, and/or a limitation of implied warranty, such limitations may not apply toyou.

    In the event that any term of this EULA is or becomes or is declared to be invalid or void byany court or tribunal of competent jurisdiction, such term or terms shall be null and void andshall be deemed severed from this EULA and all the remaining terms of this EULA shallremain in full force and effect.

  • 7/29/2019 545001 Field Go Manual

    6/98

  • 7/29/2019 545001 Field Go Manual

    7/98

    Siemens Building Technologies, Inc. I

    Table Of Contents

    How to Use This Manual...............................................................................................IRelated Documents ...................................................................................................ISymbols Used in this Manual ....................................................................................IManual Conventions..................................................................................................IIContact Us .................................................................................................................II

    Chapter 1Introduction to Field Panel GO .................................................................1-1Chapter Overview......................................................................................................1-1Applications................................................................................................................1-2

    Alarms .....................................................................................................................1-2Graphics..................................................................................................................1-2Point Commander ...................................................................................................1-2

    Trend Data Report...................................................................................................1-2Scheduler................................................................................................................1-2Point Log Report.....................................................................................................1-3Setup.......................................................................................................................1-3

    Field Panel GO Basic Setup, Navigation, and System Concepts .............................1-3Browser Requirements............................................................................................1-3Configuring the Mircosoft J ava Virtual Machine......................................................1-3Connecting to Field Panel GO and Logging On......................................................1-4Logging Off..............................................................................................................1-5User Interface Description.......................................................................................1-6Using the Object Selector .......................................................................................1-8

    Basic Concepts for Points .......................................................................................1-10

    Chapter 2Field Panel GO System Admin ist ration ...................................................2-1Chapter Overview......................................................................................................2-1Compatibility ..............................................................................................................2-2Field Panel GO System Performance........................................................................2-2System Security.........................................................................................................2-4Field Panel GO User Access.....................................................................................2-5

    Tips for Field Panel GO Startup.................................................................................2-6Tips for Managing Field Panel GO Users..................................................................2-6Configuring Field Panel GO.......................................................................................2-8

    User Interface Description for Setup.......................................................................2-8Setting up Alarm Notification...................................................................................2-10Adding Language Translation Files and Setting Language....................................2-11Setting up Graphics Display Options ......................................................................2-14Configuring the Default Graphic..............................................................................2-15Adding Custom Graphics and TEC Template Graphics .........................................2-17Backing up and Restoring Files ..............................................................................2-19

  • 7/29/2019 545001 Field Go Manual

    8/98

    Field Panel GO Users Manual

    II Siemens Building Technologies, Inc.

    Chapter 3Alarms Application.....................................................................................3-1Chapter Overview......................................................................................................3-1Alarms Application Overview.....................................................................................3-1

    User Interface Descriptions for Alarms ...................................................................3-2Alarms Step-by-Step Instructions ..............................................................................3-5

    Displaying Point Alarms ..........................................................................................3-5Acknowledging Alarm States ..................................................................................3-6

    Chapter 4Graphics Application .................................................................................4-1Chapter Overview......................................................................................................4-1Graphics Application Overview..................................................................................4-2

    User Interface Descriptions for Graphics ................................................................4-3Graphics Step-by-Step Instructions...........................................................................4-4

    Commanding Points in Graphics.............................................................................4-4Chapter 5Point Commander Application..................................................................5-1

    Chapter Overview......................................................................................................5-1Point Commander Application Overview...................................................................5-2Tips for Using the Point Commander......................................................................5-2User Interface Description for Point Commander...................................................5-3

    Point Commander Step-by-Step Instructions............................................................5-7Commanding Point Values......................................................................................5-7Commanding a Point to Alarm................................................................................5-8Disabling and Re-enabling a Point (Out of Service) ...............................................5-9Disabling and Re-enabling Alarm Printing..............................................................5-10Resetting Totalization..............................................................................................5-11

    Chapter 6Trend Applicat ion .......................................................................................6-1Chapter Overview......................................................................................................6-1

    Trend Application Overview.......................................................................................6-1User Interface Description for Trend.......................................................................6-1

    Trend Step-by-Step Instructions................................................................................6-3Generating a Trend Data Report for a Single Trend Point......................................6-3Generating a Trend Data Report for Multiple Trend Points ....................................6-3Printing a Trend Data Report..................................................................................6-4

    Chapter 7Scheduler Application ...............................................................................7-1Chapter Overview......................................................................................................7-1Scheduler Application Overview................................................................................7-2

    User Interface Description for Scheduler................................................................7-2The Schedule Properties Window...........................................................................7-4The Schedule Override Window.............................................................................7-6

    Scheduler Step-by-Step Instructions .........................................................................7-7Viewing a Mode Schedule Entry.............................................................................7-7

  • 7/29/2019 545001 Field Go Manual

    9/98

    Table of Contents

    III Siemens Building Technologies, Inc.

    Modifying Properties of a Mode Schedule Entry.....................................................7-8Enabling or Disabling a Mode Schedule Entry........................................................7-9Adding or Modifying a Mode Schedule Override ....................................................7-10Deleting a Mode Schedule Override.......................................................................7-11

    Chapter 8Reports Application ...................................................................................8-1Chapter Overview......................................................................................................8-1Reports Application Overview....................................................................................8-2

    User Interface Description for Reports....................................................................8-2Reports Step-by-Step Instructions.............................................................................8-3

    Generating a Point Log Report for a Single Point...................................................8-3Generating a Point Log Report for Multiple Points..................................................8-4Printing a Point Log Report.....................................................................................8-4

    Chapter 9Troubleshoot ing .........................................................................................9-1Log On Error Messages.............................................................................................9-2Connection Errors......................................................................................................9-3Field Panel GO Display and Settings ........................................................................9-4

    Default Graphic.......................................................................................................9-5Custom Graphics.....................................................................................................9-5

    TEC Templates .......................................................................................................9-6Reports and Trend..................................................................................................9-6

    Index ...............................................................................................................................Index-1

  • 7/29/2019 545001 Field Go Manual

    10/98

    Field Panel GO Users Manual

    IV Siemens Building Technologies, Inc.

  • 7/29/2019 545001 Field Go Manual

    11/98

    Siemens Building Technologies, Inc. I

    How to Use This Manual

    This manual is for users of APOGEEBuilding Automation Systems whouse Field Panel GO to command and monitor their APOGEE field panels. Itis designed to help you use the functions and applications of Field Panel GO.

    To effectively use this manual you should be familiar with basic operation ofthe APOGEE Building Automation Systems and a Web browser.

    Related Documents

    In addition to this user's manual, you may also wish to review the followingSiemens Building Technologies documentation:

    APOGEE Field Panel User's Manual (125-3000). This manualdescribes the operator interface program used to communicate withAPOGEE field panels.

    If your site uses Modular Building Controllers or Remote Building Controllers:

    Modular Building Controller/Remote Building Controller Owner'sManual (125-1992), which describes the operation of ModularBuilding Controllers (MBCs) and Remote Building Controllers(RBCs).

    If your site uses Modular Equipment Controllers:

    Modular Equipment Controller Owner's Manual (125-2183), whichdescribes the operation of Modular Equipment Controllers (MECs).

    These manuals, along with information about other Siemens BuildingTechnologies products, technical training classes, and services can beobtained from your local Siemens Building Technologies representative.

    Symbols Used in this Manual

    CAUTION: Equipment damage or loss of data may occur if you donot follow a procedure as specified.

    NOTE: Provides additional information related to a particulartopic.

    TIP: Suggests alternative methods or shortcuts that mayhelp you better understand the capabilities of theproduct.

  • 7/29/2019 545001 Field Go Manual

    12/98

    How to Use This Manual

    II Siemens Building Technologies, Inc.

    Manual Conventions

    The following style conventions are used throughout this manual:

    Convention Example

    Numbered Lists (1,2,3)indicate a procedure withsequential steps.

    1. From theTrend menu, click CopyDefinition.

    2. Select the Trend Definition window whereyou want to place the copied information.

    Actions that you should performare specified in boldface font.

    Type F for field panels.

    Click OK to save changes and close the dialogbox.

    Sample screens and reportsare displayed in Cour i er Newf ont .

    Report names and any information presented inscreen shots.

    New terms appearing for thefirst time in the manual areitalicized.

    A background graphic is the basic drawing of thebuilding control system.

    Short cut keys are specified asAl t+D.

    Move to previous prompt by pressingCTRL+L.

    Brackets [placeholder] indicatetext that can vary based onyour selection.

    If you select Hours, Days, Weeks or Months fromthe Time Period list, specify a parameter in the #of [units] box.

    Contact Us

    Your feedback is important to us. If you have comments about this manual,please submit them to [email protected].

  • 7/29/2019 545001 Field Go Manual

    13/98

    Siemens Building Technologies, Inc. 1-1

    Chapter 1Introduction to FieldPanel GO

    Welcome to Field Panel GO, a field panel product that provides a Web-baseduser interface to your APOGEEBuilding Automation System. Field PanelGO is an option available for the Power Open Processor with EthernetAutomation Level Network (ALN) and the Power Modular EquipmentController (MEC) with Ethernet ALN.

    The Building Automation Level Network (BLN) is now calledthe Automation Level Network (ALN). However, all firmwareprompt strings continue to use the BLN abbreviation.

    Chapter Overview

    Chapter 1 discusses the following topics:

    Applications

    Alarms

    Graphics

    Point Commander

    Trend Data Report

    Scheduler Point Log Report

    Setup

    Field Panel GO Basic Setup, Navigation, and System Concepts

    Browser Requirements

    Configuring the Microsoft J ava Virtual Machine

    Connecting to Field Panel GO and Logging On

    Logging Off

    User Interface Description

    Using the Object Selector

    Basic Concepts for Points

  • 7/29/2019 545001 Field Go Manual

    14/98

    Chapter 1Field Panel GO Users Manual

    1-2 Siemens Building Technologies, Inc.

    Applications

    Field Panel GO includes all the applications a facility operator needs to easilymonitor and control the APOGEEBuilding Automation System through asimple Web-based user interface.

    Alarms Displays alarm conditions for the points you have permission to

    view.

    Provides the ability to acknowledge alarm states.

    Provides navigation to the Point Commander application.

    Graphics

    Displays a list of available graphics, and supports the followinggraphics:

    One default field panel graphic

    Up to ten custom graphics

    TEC template graphics

    Supports graphic backgrounds, point information blocks, arrows,and analog bars.

    Provides navigation to the Point Commander application.

    Point Commander Displays the points you have permission to view.

    Shows details for a selected point.

    Allows commanding of point values and priorities, commanding apoint to alarm, disabling points or alarm printing, and resettingtotalization.

    Trend Data Report Displays a Trend Data report for the trend points you have

    permission to view.

    Provides navigation to the Point Commander application.

    Generates a printer-ready format of the Trend Data report.

    Scheduler Displays mode schedules for a selected date.

    Allows you to view and modify properties of a mode schedule.

    Allows you to override a mode schedule on a selected date.

  • 7/29/2019 545001 Field Go Manual

    15/98

    Field Panel GO Basic Setup, Navigation, and System Concepts

    Siemens Building Technologies, Inc. 1-3

    Point Log Report Displays a Point Log report for the points you have permission to

    view.

    Provides navigation to the Point Commander application.

    Generates a printer-ready format of the Point Log report.

    Setup Allows you to configure Field Panel GO settings for Alarm

    Notification and Graphics and to select a language option.

    Field Panel GO Basic Setup, Navigation, andSystem Concepts

    This section describes browser requirements, setting up your browser,logging on and logging off, navigating the Field Panel GO user interface, andunderstanding point priority and point status.

    Browser Requirements Internet Explorer (IE) version 6.0 is required for Field Panel GO.

    Cookies must be enabled.

    The MicrosoftJ ava Virtual Machine (MSJ VM) is required forviewing graphics in Field Panel GO.

    You must use the MicrosoftJ ava Virtual Machine (MSJ VM)

    with Field Panel GO. Using the Sun Microsystems J ava VirtualMachine may lead to unexpected results.

    Configuring the Mircosoft Java Virtual Machine

    The MicrosoftJ ava Virtual Machine (MSJ VM) is required for viewinggraphics in Field Panel GO. In Internet Explorer (IE), complete the followingsteps to determine whether or not the MicrosoftJ ava Virtual Machine(MSJ VM) is installed on your computer:

    1. Launch IE.

    2. From theTools menu, click Internet Options.

    3. In the Internet Options dialog box, click theAdvanced tab.4. Scroll down through the Settings section and look for the Microsoft VM

    group.

    If the Microsoft VM group exists, your computer has the J avaVirtual Machine it needs. Select the check boxes as shown in thefollowing figure.

  • 7/29/2019 545001 Field Go Manual

    16/98

    Chapter 1Field Panel GO Users Manual

    1-4 Siemens Building Technologies, Inc.

    If the Microsoft VM group doesnt exist, the MSJ VM is notinstalled on your computer. Request themsjavx86.exe file fromyour local Siemens representative and follow the online

    instructions to complete the installation.

    Connecting to Field Panel GO and Logging OnBegin a Field Panel GO session by opening the Field Panel GO Welcome page throughInternet Explorer and then logging on to the APOGEEBuilding Automation System.Whenever a Field Panel GO session begins, the system sends a log on message to allconfigured alarm printers.

    Steps for Logging On

    1. Launch Internet Explorer on your computer.

    2. Type one of the following in the Internet Explorer address field:

    IP address of the field panel

    Field panel node name

    The Field Panel GO Welcome page displays.

    If you cannot connect to the Field Panel GO Welcome page,seeTroubleshooting.

    3. To go to the log on window, click either the Welcome page image or thearrow following the message Click Here to Enter.

    4. Type your user name and password in the appropriate fields of the logon window and click Logon.

    If you receive an error message in the log on window and areunable to log on, seeTroubleshooting.

  • 7/29/2019 545001 Field Go Manual

    17/98

    Field Panel GO Basic Setup, Navigation, and System Concepts

    Siemens Building Technologies, Inc. 1-5

    A log on message is sent to all configured alarm printers, and the firstapplication you are allowed to access is displayed. For example, if you haveaccess to Alarms, the Alarms application page is the first page displayed.

    Logging Off

    End a Field Panel GO session by either manually logging off or allowing thesystem to automatically log off. Manually logging off immediately preventsunauthorized users from having access to the system and reduces networktraffic. Whenever a Field Panel GO session ends, the system sends a logoffmessage to all configured alarm printers and returns you to the Field PanelGO Welcome page.

    Manual logoff ends a Field Panel GO session when the Log officon is clicked.

    Automatic logoff ends a Field Panel GO session after a period ofinactivity at the browser.

    Field Panel GO performs an automatic logoff after theautologoff delay time that is defined in the ALN/BLN useraccount expires.

    After the system performs a logoff, the message You havebeen automatically logged offdisplays on the Welcomepage.

    CAUTION:

    Do not close the browser without logging off! If the browser is closedbefore a manual or automatic logoff is performed, the Field Panel GOsession is still active in the system, and the following problems occur:

    Other users are prevented from logging on to one of the two availablesessions.

    A logoff message is not sent to all configured alarm printers until anew Field Panel GO session is begun.

    The system continues to send COVs to the Field Panel GO Graphicsapplication even though the browser is closed.

    For information on resolving these problems, see the sectionTips forManaging Field Panel GO Users.

    Step for Manually Logging Off

    From the right side of the Application toolbar, click (the Log officon).

    The Field Panel GO session ends, a logoff message is sent to allconfigured alarm printers, and the Welcome page displays.

  • 7/29/2019 545001 Field Go Manual

    18/98

    Chapter 1Field Panel GO Users Manual

    1-6 Siemens Building Technologies, Inc.

    User Interface Descript ion

    Once a user is logged on, the Field Panel GO user interface is divided into a

    page header and an application page. The application page may be dividedinto left and right panes. The following elements are used in the Field PanelGO user interface:

    1. Page Header

    The page header contains the Application toolbar and the Alarm Notificationmessage.

    2. Object Selector

    The Object Selector allows you to enter search criteria to filter the objectsdisplayed in the Objects Retrieved list. For more information, see the sectionUsing the Object Selector.

    3. Objects Retrieved List

    The Objects Retrieved List displays information based on the search criteriaset in the Object Selector. A maximum of 100 objects is displayed. If FieldPanel GO retrieves more than 100 objects, additional objects can be viewed

    by clicking More.

    4. Left Pane

    For most applications, the left pane contains the Object Selector and theObjects Retrieved list.

  • 7/29/2019 545001 Field Go Manual

    19/98

    Field Panel GO Basic Setup, Navigation, and System Concepts

    Siemens Building Technologies, Inc. 1-7

    5. Alarm Notification

    When Alarm Notification is set to ON in the Setup application, a blinking redicon displays on the right side of the page header next to the messageUnacknowledged Alarms if at least one point is in the unacknowledgedstate.

    6. Application Toolbar

    The application toolbar provides navigation to each Field Panel GOapplication. Icons only display if access to the application has been grantedin the ALN/BLN user account.

    7. Right Pane

    The information displayed in the right pane depends on the application.

    8. Application PageThe information displayed in the application page depends on theapplication. The following table outlines all the options.

    ToolbarIcon

    IconDescription

    Appl ication Page Descript ion

    Alarmsapplication

    The left pane does not display. The Alarm List and Unack Listdisplay in the right pane.

    Graphicsapplication

    The Object Selector and Objects Retrieved List display in the leftpane. The selected graphic displays in the right pane.

    PointCommanderapplication

    The Object Selector and Objects Retrieved List display in the leftpane. The Commander window displays point detail information inthe right pane.

    Trendapplication

    The Object Selector and Objects Retrieved List display in the leftpane. A generated Trend Data report displays in the right pane.

    Schedulerapplication

    The daily equipment schedule displays in the left pane. A monthlycalendar and the View Schedules by Filters menu display in theright pane.

    Reportsapplication

    The Object Selector and Objects Retrieved List display in the leftpane. A generated Panel Point Log report displays in the rightpane.

    Setupapplication The left pane does not display. The Setup window displays in theright pane.

    Log off When this icon is selected, the user returns to the Welcome page.

  • 7/29/2019 545001 Field Go Manual

    20/98

    Chapter 1Field Panel GO Users Manual

    1-8 Siemens Building Technologies, Inc.

    Using the Object Selector

    The Object Selector is used to enter search criteria. Wildcards can be used

    to filter the objects displayed in the Graphics, Point Commander, Trend, andReports applications.

    The first time you open an application, the Object Selectorcontains the default search criteria for the application. Once youmodify the search criteria in an application and click Find now,the updated search criteria is maintained throughout the FieldPanel GO session.

    To close the Object Selector and minimize the left pane, clickin the upper right corner. To reopen the Object Selector, click

    .

    The following fields, buttons, and check box are used in the Object Selector:

    1. Name

    The Name text field allows you to enter a point name as part of the searchcriteria. Wildcards can be used in this field to represent one or more

    characters in the point name. The default entry for this field is an asterisk (*), which selects all

    objects.

    This field is not case sensitive.

    The two wildcard characters available are:

    The asterisk (*), which can represent multiple characters inthe point name.

    The question mark (?), which replaces only one character inthe point name.

    In order for wildcarding to be effective, it is important for a

    point naming convention to be used consistentlythroughout the system. Point naming conventions aredescribed in the Point Database chapter of the Field PanelUser's Manual (125-3000).

  • 7/29/2019 545001 Field Go Manual

    21/98

    Field Panel GO Basic Setup, Navigation, and System Concepts

    Siemens Building Technologies, Inc. 1-9

    2. Type

    The Type drop-down list allows you to select one object type as part of thesearch criteria.

    For Point Commander and Reports, the drop-down list optionsare and the twelve point types.

    For the Graphics application, the drop-down list options areGraphic and the appropriate FLN type.

    TEC is the option if the field panel containing Field Panel GOFirmware supports P1 FLN devices.

    LTEC is the option if the field panel containing Field PanelGO Firmware supports LONWORKSFLN devices.

    NOTE: The Type field is disabled in the Trend application.

    3. Panel

    The Panel drop-down list displays all available field panels on the ALN/BLN.You can select an individual field panel as part of the search criteria.

    4. Show Subpoints Check Box

    Selecting the Show Subpoints check box expands the searchcriteria to include subpoints.

    The search criteria entered for the Name field (Item 1) is used incombination with the Show Subpoints selection. For example, ifabc* is entered for the Name and Show Subpoints is selected,the Objects Retrieved list will include all points named abc, as

    well as subpoints with an abc prefix.

    5. Run Report Button

    The Run Report button only displays in the Trend and Reportsapplications.

    Generates a report using the search criteria set in the Namefield.

    When you click Run Report, the Type, Panel, and ShowSubpoints inputs are ignored.

    Clicking the Run Report button with an asterisk (*) in theName field generates a report for all field panels on the

    ALN/BLN. The system may take a few minutes to generatethis report. You can navigate to other applications whilethe report is being generated.

    6. Find Now Button

    Executes a search for objects matching the search criteria.

  • 7/29/2019 545001 Field Go Manual

    22/98

    Chapter 1Field Panel GO Users Manual

    1-10 Siemens Building Technologies, Inc.

    Basic Concepts for Points

    The point database contains all information defined for every point in the

    APOGEE system. The system controls points according to their definitionsand the purposes they represent.

    Point Priority

    The five point priorities, from highest to lowest priority, are: OPER, SMOKE,EMER, PDL, and NONE.

    Manually changing the value of a point is known as commandingthe point. When a point is commanded, its priority changes toOPER.

    To allow the system to regain control, points in OPER prioritymust be reset to NONE. This manual change in priority is knownas releasing the point. If the system is running a control

    sequence that uses one of the other priorities (PDL, EMER orSMOKE), then the system changes the priority to reflect thatcontrol upon a point release.

    CAUTION:

    Remember to eventually release all commanded points to NONEpriority so that the system is automatically controlled. Failure torelease commanded points may lead to unexpected results.

    In most cases, under normal operating conditions, the priority of a pointshould be NONE. Depending on the type of application, the system maychange point priority to prevent interaction with PPCL or other applications.

    The following table describes each command priority:

    CommandPriority

    Description

    OPER

    (Operator)

    Highest command priority.

    An operator has control for commanding the point to a new value. Thesequence of operation set up in the control program has been overriddenand the control program cannot command the point until it is released to alower priority. PPCL statements do not affect this point until it is releasedfrom OPER.

    SMOKE Second highest command priority.

    SMOKE control is a safety program sequence that controls the system whenthe Life Safety smoke detector is tripped. A point may be commanded to

    SMOKE for smoke alarm testing. The SMOKE command priority may requireuser intervention.

    EMER

    (Emergency)

    Third highest command priority.

    The point is controlled by a special program sequence that commands thepoint during emergency situations. EMER command priority is used duringemergency conditions; for example, a low temperature detector shuts down asupply fan because the duct is too cold.

    Continued on the next page

  • 7/29/2019 545001 Field Go Manual

    23/98

    Field Panel GO Basic Setup, Navigation, and System Concepts

    Siemens Building Technologies, Inc. 1-11

    CommandPriority

    Description

    PDL(PeakDemandLimiting)

    Fourth highest command priority.The point is commanded by Peak Demand Limiting (PDL). PDL control is aspecial energy management program routine that limits electrical demand byturning off electrical loads when demand approaches a set point; forexample, shutting down a fan if demand approaches setpoint. There is noneed for intervention when PDL has control of a point.

    NONE Lowest command priority.

    The point is commanded by the standard PPCL control program. The point isnot controlled by the operator or special control programs. Most pointcommanding in a building control system is done automatically by PPCLprograms commanding points with the NONE priority.

    Point Status

    The point status indicates the current condition of a logical point. It can alsoreflect two or more statuses. For example, the point may be commanded intoalarm by an operator (*AC*) and set to trouble by the PPCL program (*T*).

    The status for the point would then be displayed as *ACT*. The followingtable describes each point status:

    Status Meaning Explanation

    -N- NORMAL The point is in regular operation. The value and alarmconditions of the point can be updated by control programsor operator commands.

    *A* ALARM The condition of the point is outside its defined limits and analarm priority has been assigned to the point. An alarm

    occurs when:

    The value of an analog point is outside a defined high or lowlimit.

    The value of a proof point does not correspond to thecommanded value of the associated output point within theproof delay time.

    An LDI or LDO point is ON and the point was defined to gointo alarm when it turns ON. For example, a smoke detectorpoint.

    *An* ALARM The condition of the point is outside its defined limits and anenhanced alarm priority has been assigned to the point. Then represents the number of the alarm level.

    *AC* ALARM-BY-COMMAND The value of a point is within its normal operating range.However, the point has been commanded into alarm by anoperator or by the control program. The point remains in thisstate until it is commanded back to the Normal state by anoperator or control program.

    *ACK* ACKNOWLEDGE The point is in alarm and has been acknowledged by a user.

    Continued on t he next page

  • 7/29/2019 545001 Field Go Manual

    24/98

    Chapter 1Field Panel GO Users Manual

    1-12 Siemens Building Technologies, Inc.

    Status Meaning Explanation

    *F* FAILED The field panel is unable to command or read any of the

    physical points associated with the logical point. This maybe the result of hardware failure or a sensor reading outsideof its defined limits.

    *Value* HAND When the value of the point is surrounded by * in theAlarms, Graphics, and Point Log Report application, amanual override switch has been used, and the system nolonger has control of the point. The system will not be ableto control that point until the manual override switch isreturned to AUTOMATIC mode.

    *O* OPERATORDISABLED

    The point has been disabled by an operator. The point valueand alarm conditions are not reported to the ALN/BLN andcannot be updated by operator commands or controlprograms until the point is commanded back to Enabled.

    *ODSB* OPERATORDISABLEDALARM

    An operator has manually disabled a point from alarmreporting.

    *P* PROOFING The field panel is waiting to verify that the value of a proofpoint corresponds to the commanded value of an associatedoutput point. The point is in this state for the duration of theproof delay time that is defined for the point.

    *PDSB* PROGRAMDISABLEDALARM

    An alarm has been disabled from reporting by PPCL.

    *T* TROUBLE The TROUBLE status appears when a PPCL program or anoperator commands the point to this state.

  • 7/29/2019 545001 Field Go Manual

    25/98

    Siemens Building Technologies, Inc. 2-1

    Chapter 2Field Panel GO SystemAdministration

    Chapter Overview

    Chapter 2 discusses the following topics:

    Compatibility

    Field Panel GO System Performance

    System Security

    Field Panel GO User Access Tips for Field Panel GO Startup

    Tips for Managing Field Panel GO Users

    Configuring Field Panel GO

    User Interface Description for Setup

    Setting up Alarm Notification

    Adding Language Translation Files and Setting Language

    Setting up Graphics Display Options

    Configuring the Default Graphic

    Adding Custom Graphics and TEC Template Graphics

    Backing up and Restoring Files

  • 7/29/2019 545001 Field Go Manual

    26/98

    Chapter 2Field Panel GO Users Manual

    2-2 Siemens Building Technologies, Inc.

    Compatibility

    Field Panel GO resides on an Ethernet ALN. A minimum of one Ethernet fieldpanel containing Field Panel GO is required per ALN.

    The Building Automation Level Network (BLN) is now calledthe Automation Level Network (ALN). However, all firmwareprompt strings continue to use the BLN abbreviation.

    Field Panel GO may coexist on the same ALN/BLN with Ethernetfield panels that contain Firmware Revision 2.6 Build 9.45 orlater. It may coexist with earlier builds of Firmware Revision 2.6;however, system performance may be affected.

    Insight 3.7 and Datamate Advanced 3.7 software provide thefollowing supporting features for Field Panel GO:

    Backup and restoration of Field Panel GO graphic files, TECtemplate files, language translation files, and the setup file.

    Optional add-on component for creating and converting FieldPanel GO graphic files and TEC template files.

    This optional add-on component requires an additionallicense code for the Insight server Sentinel.

    To create graphic files, Micrografx must be installed on theInsightRevision 3.7 server.

    These features are also available as services from your localSiemens office.

    Field Panel GO System Performance

    Field Panel GO is a memory- and processor-intensive application. As thenumber of field panels, TECs, and points on the network increases, theamount of time required to load Field Panel GO Web pages increases.

    Field Panel GO is designed for optimal performance on smallAPOGEEBuilding Automation Systems. A small systemcontains a maximum of six field panels per Ethernet ALN/BLN.

    An Insightworkstation, rather than Field Panel GO, is a moreappropriate user interface for larger Building Automation

    Systems. For optimal performance, install Field Panel GO on an Ethernet

    ALN/BLN only with field panels that contain Firmware Revision2.6 Build 9.45 or later.

    For networks with field panels containing firmware earlier thanRevision 2.6 Build 9.45, more time is required to execute FieldPanel GO functions.

  • 7/29/2019 545001 Field Go Manual

    27/98

    Field Panel GO System Performance

    Siemens Building Technologies, Inc. 2-3

    Performance testing indicates that load times for user log on, theAlarms application, and the Unacknowledged Alarm Notificationfeature increases by a factor of three for each field panel on the

    network containing firmware earlier than Revision 2.6 Build 9.45.

    The following table compares the time it takes to load a Field Panel GO Webpage on different-sized systems:

    System Size

    Action6 Field Panels,

    33 TECs10 Field Panels,

    45 TECs

    Logon 6-7 seconds 9-12 seconds

    Open Alarms Application 6-7 seconds 10 seconds

    Open Commander Application 9 seconds 10-12 seconds

    Open Scheduler Application 10 seconds 16 seconds

    NOTE: The results in this table were obtained in a controlled performance test environment. Testswere conducted on a network only containing field panels with Firmware Revision 2.6Build 9.45.

  • 7/29/2019 545001 Field Go Manual

    28/98

    Chapter 2Field Panel GO Users Manual

    2-4 Siemens Building Technologies, Inc.

    System Security

    Field Panel GO offers the same security measures and access to yourAutomation Level Network (ALN) as any Ethernet field panel on yournetwork. The following illustration shows an example network layout withField Panel GO.

    The Building Automation Level Network (BLN) is now calledthe Automation Level Network (ALN).

    INTERNET

    Modem

    NT0304R1

    Web

    Browser

    Clients

    Web Browser Clients

    ETHERNET (INTRANET)

    RAS Server

    Modem/Firewall

    Firewall

    Virtual Private

    Network (VPN)

    Remote Access

    Service (RAS)

    Internet

    ServiceProvider

    (ISP)MBC on Ethernet

    with Field Panel GO

    MEC on Ethernet

    Example Network Layout with Field Panel GO.

    Observe the following practices to help control unauthorized access to theALN/BLN:

    Assign privileges in each ALN/BLN user account based on theuser's responsibilities and the need to use an application orfunction. For example:

    If the ALN/BLN user account is set toNo Access to Alarms,then the Field Panel GO Alarms application is not available

    when that user logs on to Field Panel GO. If the ALN/BLN user account is set for access groups 1..5,

    then points assigned to access groups 6..30 are notavailable in the Field Panel GO Point Commanderapplication when that user logs on to Field Panel GO.

    Change the passwords for the HIGH, MED, and LOW defaultuser accounts.

    Only enable Telnet on the field panel when it is needed.

  • 7/29/2019 545001 Field Go Manual

    29/98

    Field Panel GO User Access

    Siemens Building Technologies, Inc. 2-5

    If your site requires detailed tracking of system modifications, you should usethe Compliance Support Option available through the Insightsoftware tomanage your ALN/BLN. The Compliance Support Option for Insight provides

    an additional level of system security that protects critical system objectsfrom damage by inadvertent operator changes, and provides enhanced audittrails, which are most often used to support compliance with federalregulations; for example, FDA 21 CFR Part 11.

    Field Panel GO User Access

    Access to Field Panel GO applications is controlled through privileges, whichare granted in the ALN/BLN user account. The following table outlines theALN/BLN user account privilege that grants access to each Field Panel GOapplication:

    ALN/BLN User

    Account Privilege

    Provides Access to This

    Field Panel GO Application

    User Privilege

    Required

    Alarm Alarms and Alarm Notification Read Only or higher

    Point Graphics, Point Commander,and Point Log Report

    Read Only or higher

    Trend Trend Data Report Read Only or higher

    Equipment Scheduler Scheduler Read Only or higher

    System Field Panel GO Setup Edit

    Users with Read Only or higher access to a Field Panel GOapplication can view application information by clicking theappropriate icon.

    Users with Command or higher access to a Field Panel GOapplication can also execute the procedures discussed in theStep-by-Step sections of this manual.

    Users with Edit access to the Field Panel GO Setup applicationcan also configure settings for Alarm Notification and Graphicsand select a language option.

    ALN/BLN user accounts are configured through the MMIterminal or Insightworkstation, not Field Panel GO. Forinformation on setting up ALN/BLN user account privileges, seethe Field Panel User's Manual (125-3000).

  • 7/29/2019 545001 Field Go Manual

    30/98

    Chapter 2Field Panel GO Users Manual

    2-6 Siemens Building Technologies, Inc.

    Tips for Field Panel GO Startup

    Field Panel GO is an option available for the Power Open Processor withEthernet ALN/BLN and the Power Modular Equipment Controller (MEC) withEthernet ALN/BLN.

    Use the appropriate IP address and subnet mask for the fieldpanel and your computer's network connections.

    For more information on setting the field panel networkconnections, see the start-up procedures for the Ethernetfield panel you are installing or contact your local Siemensrepresentative.

    For more information on setting your computer's networkconnections, see the Help for your computer's operatingsystem.

    Set the field panel IP settings according to your infrastructure.

    If your infrastructure uses a fixed IP address, then you mustselect IP addresses and subnet masks that permit TCP/IPcommunication and do not conflict.

    If your infrastructure is based on DHCP, then the systemautomatically obtains IP addresses.

    If your computer and the field panel are not on the sameEthernet network, you can directly connect them using either acrossover cable or a hub and cables.

    If you are using a crossover cable, connect the cable to theEthernet connections on the field panel and on yourcomputer.

    If you are using a hub, connect one cable to the hub and tothe Ethernet connection on the field panel. Connect asecond cable to the hub and to the Ethernet connection onyour computer.

    Tips for Managing Field Panel GO Users

    Only two Field Panel GO sessions can be active at the sametime. Once two users are logged on to a field panel containingField Panel GO Firmware, all other users are prevented from

    logging on. The Field Panel GO automatic logoff feature is enabled through

    the ALN/BLN user account.

    IfAutologoff enabled is set to Y (Yes) in the ALN/BLN useraccount, you must also enter anAutologoff delay value(from1 to 1440 minutes). The autologgoff delay defines theamount of time the browser must be inactive before FieldPanel GO triggers an automatic logoff.

  • 7/29/2019 545001 Field Go Manual

    31/98

    Tips for Managing Field Panel GO Users

    Siemens Building Technologies, Inc. 2-7

    IfAutologoff enabled is set to N (No) in the ALN/BLN useraccount, Field Panel GO does not trigger an automatic logoffregardless of the level of activity at the browser.

    BLN user accounts withAutologoff enabled set to N (No)(autologoff disabled) cannot log on to multiple Field Panel GOsessions at the same time. If you attempt to start a simultaneousField Panel GO session with an autologoff disabled useraccount, the system automatically closes the first session.

    CAUTION:

    Do not close the browser without logging off! If the browser isclosed before a manual or automatic logoff is performed, the FieldPanel GO session is still active in the system, and the followingproblems occur:

    Other users are prevented from logging on to one of the two

    available sessions. A logoff message is not sent to all configured alarm printers.

    The system continues to send COVs to the Field Panel GOGraphics application even though the browser is closed.

    Do one of the following to resolve the problems that occur whena user closes the browser before logging off from Field PanelGO:

    If the session was ended by an ALN/BLN user account withAutologoff enabled set to Y (Yes), the autologoff delay timemust expire and another user must log on to end theincomplete session. Once the autologoff delay time expires

    and a new user logs on, the incomplete Field Panel GOsession ends and a logoff message is sent to all configuredalarm printers.

    If the session was ended by an ALN/BLN user account withAutologoff enabled set to N (No), the same user accountmust be used to end the incomplete session. Since there isnot a logoff delay time for this ALN/BLN user account, thesame user may immediately log on again. When this occurs,the incomplete Field Panel GO session ends and a logoffmessage is sent to all configured alarm printers.

    If the session was ended by an ALN/BLN user account thathas since been deleted, any valid Field Panel GO user can

    immediately log on to end the incomplete session. When avalid Field Panel GO user logs on, the incomplete FieldPanel GO session ends and a logoff message is sent to allconfigured alarm printers.

  • 7/29/2019 545001 Field Go Manual

    32/98

    Chapter 2Field Panel GO Users Manual

    2-8 Siemens Building Technologies, Inc.

    Configuring Field Panel GO

    This section describes the procedures for configuring your system andsetting up user accounts.

    User Interface Descript ion for SetupThe features in this section are only available to ALN/BLNuser accounts with Edit System privileges.

    The Setup application is used to configure Alarm Notification and Graphicsoptions and to select the language. The following fields and buttons are usedin the Setup window:

    1. General Section

    Alarm Notif ication and Alarm Notif ication Interval

    The Alarm Notification feature is activated or deactivated usingthe drop-down list. The default setting is ON.

    When Alarm Notification is set to ON, the Alarm NotificationInterval field defines the number of seconds Field Panel GOwaits between each scan of the ALN/BLN to identify points in theunacknowledged state.

    The default Alarm Notification Interval is 30 seconds.

    The valid range for this field is 30 through 300 seconds.

    If you are looking for ways to reduce network traffic, increase theAlarm Notification Interval or set Alarm Notification toOFF.

  • 7/29/2019 545001 Field Go Manual

    33/98

    Configuring Field Panel GO

    Siemens Building Technologies, Inc. 2-9

    Header Image Transition

    This option activates or deactivates the photo slideshow that displays on theleft side of the page header. The default setting is ON.

    Language

    Selects the language displayed in Field Panel GO.

    If a translated headings.xml file was downloaded to the FieldPanel GO file system, the name of the subdirectory that containsthe translated headings.xml file displays in the drop-down list asanother language option.

    The default setting is EN-US, which indicates English (UnitedStates).

    For more information on setting up language options, see the sectionAddingLanguage Translation Files and Setting Language.

    2. Graphics Section

    Refresh Mode and Graphics Update Interval

    The Refresh Mode is set using the drop-down list. The defaultsetting isAutomatic .

    When Refresh Mode is set toAutomatic, the Graphics UpdateInterval field defines the number of seconds the Graphicsapplication waits between each automatic scan of the ALN/BLNto retrieve updated point information.

    The default Graphics Update Interval is 15 seconds.

    The valid range for this field is 5 through 60 seconds.

    When Refresh Mode is set to Manual, you must manuallyrefresh the Graphics application to retrieve updated pointinformation from the ALN/BLN.

    If you are looking for ways to reduce network traffic, increase theGraphics Update Interval or set the Refresh Mode to Manual.

    Blink Options

    Determines the blink options for the controls in the Graphicsapplication. The default setting is OFF (disabled).

    There are two blink options:

    Off (disabled). Select this option if you don't want graphiccontrols to blink.

    On when Off-Normal. Select this option if you want agraphic control to blink when a point is in alarm.

  • 7/29/2019 545001 Field Go Manual

    34/98

    Chapter 2Field Panel GO Users Manual

    2-10 Siemens Building Technologies, Inc.

    Default Graphic Size

    Sets the display size for the default graphic. The default settingis 800 600.

    There are three options:

    800 600, which displays a maximum of 15 pointinformation blocks.

    1024 768, which displays a maximum of 30 pointinformation blocks.

    1280 1024, which displays a maximum of 72 pointinformation blocks.

    Default Graphic Points L ist

    This option is used for setting up the Field Panel GO Default Graphic. A point

    information block is created in the Default Graphic for each point nameentered in the list.

    3. Point State to Color Map Section

    Controls the color options that indicate point status in the Graphicsapplication.

    4. Restore Defaults But ton

    Restores all Setup options to the default settings.

    5. Save Button

    Saves the selected Setup options.

    Setting up Alarm NotificationCAUTION:

    If Alarm Notification is not used, you should regularly check for newalarms by either going to the Alarms application or clicking theRefresh button while viewing the Alarms application.

    When Alarm Notification is set to ON in the Setup application, the systemautomatically checks for ALN/BLN points in the unacknowledged state. If atleast one point is in the unacknowledged state, a blinking red icon displayson the right side of the page header next to the message Unacknowledged

    Alarms.

  • 7/29/2019 545001 Field Go Manual

    35/98

    Configuring Field Panel GO

    Siemens Building Technologies, Inc. 2-11

    Steps

    This procedure is only available to users with Edit System privileges.

    1. From the right side of the Application toolbar, click (theSetupicon).

    The Setup window displays.

    2. Select an option in the Alarm Notification drop-down list.

    ON activates Alarm Notification

    OFF deactivates Alarm Notification

    3. Do one of the following:

    If Alarm Notification is set to ON, go to the Alarm Notification

    Interval field and enter the number of seconds between eachautomatic scan of the ALN/BLN for points in theunacknowledged state. The valid range is 30 through 300seconds.

    If Alarm Notification is set to OFF, continue with Step 4.

    4. Click Save to apply your settings for Alarm Notification

    The information in the Alarm Notification fields reflects the changes.

    Alarm Notification setup is now complete.

    Adding Language Translation Files and Sett ing Language

    The Field Panel GO user interface can be translated to meet your locallanguage needs. The language option selected in the Field Panel GO Setupapplication is activated for all users; language options cannot be set forindividual user accounts.

    This topic provides an overview of the process for creating the translation fileand saving it to the file system. If you need step-by-step instructions for thesetasks, contact your local Siemens representative.

    Creating the Language Translation Files

    1. Use an FTP client to copy the translations\en-us\headings.xml filefrom the field panel to a directory on your local hard drive.

    2. Translate all of the words or phrases between the start and end tags in

    the xml file.

    You must save the translation file using UTF-8 encoding.

    The Notepad editor included with Windows 2000 or latersupports UTF-8 encoding.

  • 7/29/2019 545001 Field Go Manual

    36/98

    Chapter 2Field Panel GO Users Manual

    2-12 Siemens Building Technologies, Inc.

    The following example compares an excerpt from the English headings.xmlfile with the same excerpt translated to French. (Bold is added for emphasis):

    English headings.xml File French headings.xml File

    Name

    Val ue

    Status

    Pri or i t y

    Nom

    Val eur

    t at

    Pri or i t

    3. In the translations directory of the field panel file system, create asubdirectory for the translated headings.xml file.

    Use the standard values for the xml:lang attribute as the namefor the subdirectory.

    For additional information, see the sectionStandard Values forthe xml:lang Attribute.

    4. Use an FTP client to download the translated headings.xml file to thetranslations\xx directory in the field panel file system, where xx is thesubdirectory for the user-defined language.

    You are now ready to set the language option for your work site. Continuewith the procedureSetting the Language.

    Standard Values for the xml:lang Attr ibute

    Standards for using language identification tags are defined in the InternetEngineering Taskforce (IETF) documentRequest for Comments (RFC) 3066,which can be found at http://www.ietf.org/rfc/rfc3066.txt.

    The most commonly used value is the following:

    [ - ]

    Where:

    is an ISO language two-letter code (ISO 639-1)or three-letter code (ISO 639-2T).

    is an ISO country code (ISO 3166).

    A dash (-) (U+002D) is the separator (not an underscore (_)).

  • 7/29/2019 545001 Field Go Manual

    37/98

    Configuring Field Panel GO

    Siemens Building Technologies, Inc. 2-13

    Using the ISO Language Codes

    Use the two-letter language codes. Seehttp://www.loc.gov/standards/iso639-2/langcodes.html for theofficial list of the ISO language codes.

    If a two-letter code does not exist for a given language, use theTerminology form of the three-letter code (ISO 639-2t), not theBibliography form (ISO 639-2b).

    See http://www.iso.org/iso/en/prods-services/iso3166ma/index.htmlfor the official list of the ISOcountry codes.

    Common xml:lang Standard Values

    Language ISO 639-1 ISO 639-2T

    Chinese zh zhoFrench fr fra

    German de deu

    J apanese ja jpn

    Korean ko kor

    Latin la lat

    Spanish es spa

    Setting the Language

    This procedure is only available to users with Edit Systemprivileges.

    Once the headings.xml file is translated and downloaded to theappropriate subdirectory in the field panel file system, otherlanguage options are available in the Language drop-down list inthe Setup application.

    The name of the subdirectory that contains the translatedheadings.xml file displays in the Language drop-down list asanother language option.

    1. Log on to Field Panel GO.

    2. From the right side of the Application toolbar, click (theSetupicon).

    The Setup window displays.

    3. From the Language drop-down list, select the appropriate option for yourwork site.

  • 7/29/2019 545001 Field Go Manual

    38/98

    Chapter 2Field Panel GO Users Manual

    2-14 Siemens Building Technologies, Inc.

    If other language options do not display in the drop-down list,click Save and then select the appropriate option for yourwork site.

    4. Click Save to apply your settings for Language.

    The information in the Language field reflects the changes.

    Language setup is now complete.

    Setting up Graphics Display Options

    This section outlines the procedure for setting the following display options inthe Graphics application:

    Refresh Mode

    Graphics Update Interval

    Blink Options

    Default Graphic Size

    Point State to Color Map

    See the sectionConfiguring the Default Graphicfor the procedure to addpoints to the Default Graphic Points List.

    Steps

    This procedure is only available to users with Edit System privileges.

    1. From the right side of the Application toolbar, click (theSetupicon).

    The Setup window displays.

    2. Under the Graphics section of the Setup window, select a Refresh Modeoption from the drop-down list. The following options are available:

    Automatic (This is the default setting.)

    Manual

    3. If you selected Automatic Refresh Mode in Step 2, you may wish tochange the Graphics Update Interval.

    The default update interval is 15 seconds. The valid range for this field is 5 through 60 seconds.

    4. From the Blink Options drop-down list, select one of the following optionsfor graphics representing points in alarm:

    Off (disabled) (This is the default setting.) Select this option ifyou don't want graphic controls to blink.

    On when Off-Normal Select this option if you want a graphiccontrol to blink when a point is in alarm.

  • 7/29/2019 545001 Field Go Manual

    39/98

    Configuring Field Panel GO

    Siemens Building Technologies, Inc. 2-15

    5. From the Default Graphic Size drop-down list, select one of the followingoptions for the Default Graphic:

    800 600 (maximum of 15 point information blocks) (This is the

    default setting.)

    1024 768 (maximum of 30 point information blocks)

    1280 1024 (maximum of 72 point information blocks)

    6. Under the Point State to Color Map section of the window, do thefollowing to modify the color options representing each point state:

    a. Click (the Palette icon) for the point state you want tomodify.

    b. Color Palette is the default setting for the palette. If youwant to use a gray scale, select Grayscale Palette from thedrop-down list at the top of the window.

    c. Click one of the colors in the palette to select it as the colorfor the point state.

    7. Click Save at the bottom of the Setup window to save your changes.

    The graphics display options are now set up.

    Configuring the Default Graphic

    Point Names or Point System Names are used to create the Field Panel GODefault Graphic, which displays your building operations with pointinformation blocks.

    The Field Panel GO Graphics application does not displaypoint names based on the Syst em, User namespace

    setting in the ALN/BLN user account. The point name styleused to define the graphic is the point name style that alwaysdisplays.

    The following example illustrates a Point Name and a Point System Name:

    Point Name: BUILDING1.AHU1.SPACETEMP

    Point System Name: B1A1ST

    Each name entered in the Default Graphic Points List creates apoint information block in the Default Graphic.

    You can enter the Point Name, the Point System Name, orboth point name styles in the Default Graphic Points List.

    The Default Graphic always displays all the point informationblocks for any Field Panel GO user with access to theGraphics application.

  • 7/29/2019 545001 Field Go Manual

    40/98

    Chapter 2Field Panel GO Users Manual

    2-16 Siemens Building Technologies, Inc.

    The Field Panel GO Graphics application limits access tocommanding a point on a graphic as follows:

    The Field Panel GO user must be granted Command or

    higher access to the point in the ALN/BLN user account.

    Field Panel GO users whose account setting forSyst em,

    User namespace is set to System, can only commandpoints that are defined in the Field Panel GO Graphicsapplication as Point System Names.

    Field Panel GO users whose account setting for Syst em,

    User namespace is set to User, can only command pointsthat are defined in the Field Panel GO Graphics applicationas Point Names.

    Steps

    This procedure is only available to users with Edit System privileges.

    During this procedure, you need to type the names of points youwish to add to the Default Graphic. Before you begin, print a PanelPoint Log report.

    1. From the right side of the Application toolbar, click (theSetupicon).

    The Setup window displays.

    2. Under the Graphics section of the window, clickAdd Points.

    The Default Graphic Points List is maximized.

    3. Do one of the following:

    To add points, type point names in the Default Graphic PointsList. Press ENTER after each point name so that there's onlyone point name per line.

    To remove points, delete the point name from the DefaultGraphic Points List.

    4. ClickApply to update the Default Graphic Points List.

    5. Click Close to minimize the Default Graphic Points List.

    6. Click Save at the bottom of the Setup window to save your changes.

    The Default Graphic is now configured.

  • 7/29/2019 545001 Field Go Manual

    41/98

    Configuring Field Panel GO

    Siemens Building Technologies, Inc. 2-17

    Verifying the Default Graphic Configuration

    1. From the Application toolbar, click (theGraphics icon).

    2. Select Graphic from the Object Selector Type drop-down list and clickFind now.

    3. In the Objects Retrieved list, click Default Graphic.

    Field Panel GO displays the Default Graphic in the Application frame.

    Adding Custom Graphics and TEC Template Graphics

    Custom field panel graphics and TEC template graphics must bedownloaded to the field panel before they can be viewed in the Field PanelGO Graphics application.

    The Field Panel GO Graphics application does not display

    point names based on the Syst em, User namespacesetting in the ALN/BLN user account. The point name styleused to define the graphic is the point name style that alwaysdisplays.

    The following example illustrates a Point Name and a Point System Name:

    Point Name: BUILDING1.AHU1.SPACETEMP

    Point System Name: B1A1ST

    The Field Panel GO Graphics application limits access tocommanding a point on a graphic as follows:

    The Field Panel GO user must be granted Command orhigher access to the point in the ALN/BLN user account.

    Field Panel GO users whose account setting forSyst em,

    User namespace is set to System, can only commandpoints that are defined in the Field Panel GO Graphicsapplication as Point System Names.

    Field Panel GO users whose account setting for Syst em,

    User namespace is set to User, can only command pointsthat are defined in the Field Panel GO Graphics applicationas Point Names.

    Either the Point Name or the Point System Name is displayed incustom graphics and TEC template graphics.

    When exporting custom graphics and TEC templategraphics, be aware that your ALN/BLN account setting forSyst em, User namespace determines which point namestyle displays in the Field Panel GO Graphics application.

    The point name style is fixed once the custom graphics andTEC template graphics are exported for Field Panel GO.

  • 7/29/2019 545001 Field Go Manual

    42/98

    Chapter 2Field Panel GO Users Manual

    2-18 Siemens Building Technologies, Inc.

    When graphics are exported for Field Panel GO, the point namesin the graphic are compared to the point names in the database.If a point name is not in the database, it is removed from the

    graphic.

    Steps

    This procedure provides an overview of the process for adding customgraphics and TEC template graphics to the Field Panel GO file system. If youneed more detailed instructions for these tasks, contact your local Siemensrepresentative.

    This procedure is only available to users with Edit System privileges.

    1. Create custom graphics and TEC template graphics in the Graphicsapplication of InsightRevision 3.7 or Datamate Advanced Revision 3.7

    software.

    As an alternative, the local Siemens office can provide theservice of creating the custom and TEC template graphics.

    Custom graphic file names and graphic background file namesare limited to 255 characters; acceptable characters include:Athrough Z, a through z, 0 through 9, and underscores (_).

    Do not use the following in file names: spaces ( ), periods (.),commas (,), dashes (-), apostrophes ('), and the characters & ? *[ ] { } %.

    Use the application ID number as the file name for TEC template

    graphics.2. Use Insight Revision 3.7 or Datamate Advanced Revision 3.7 to export

    the custom graphics and TEC template graphics to the Field Panel GOfile format. These tools store the Field Panel GO graphic files on yourlocal hard disk. Otherwise, the local Siemens office can provide thisservice.

    3. Use one of the following tools to download custom graphics and TECtemplate graphics to the Field Panel GO file system:

    Insight Revision 3.7 or Datamate Advanced Revision 3.7. Formore information, see the user documentation for these tools.

    Any available FTP client tool.

    When logging on to the Field Panel GO FTP server, use aALN/BLN user account name and password.

    Custom graphic definition xml files must be downloaded tothe \graphics directory.

    TEC template definition xml files must be downloaded to the\tectemplates directory.

  • 7/29/2019 545001 Field Go Manual

    43/98

    Configuring Field Panel GO

    Siemens Building Technologies, Inc. 2-19

    Background jpg files must be downloaded to the\backgrounds directory.

    For more information on using FTP clients to connect to the

    field panel, see the sectionSteps for Using Windows FTP Client.

    Backing up and Restoring Files

    All Field Panel GO graphic files, language translation files, and setup filesshould be backed up on your local hard drive so that they can be restored ifthe field panel coldstarts.

    This feature is only available to users with Edit System privileges.

    Use InsightRevision 3.7, Datamate Advanced Revision 3.7, or anyavailable FTP client tool to back up and restore the following Field Panel GO

    files:

    Graphic definition files created with Insight software or DatamateAdvanced software (*.xml files in the \graphics directory).

    TEC template definition files created with Insight software orDatamate Advanced software (*.xml files in the \tectemplatesdirectory).

    Background files created with Insight software or DatamateAdvanced software (*.jpg files in the \backgrounds directory).

    Language translation files created by an editor (headings.xmlfile, which is in one or more \translations\xx directories, wherexx is the defined language directory).

    Configuration file named \wssetup\wssetup.xml.

    For more information on using Insight or Datamate software to back up andrestore files, see the user documentation for these tools.

    Steps for Using Windows FTP Client

    If Insight Revision 3.7 or Datamate Advanced Revision 3.7 is not available,there are many user-friendly FTP tools publicly available that can be used fortransferring files between your computer and the field panel. If you'recomfortable using the WindowsFTP client, it also works fine for backing up,restoring, and downloading Field Panel GO files.

    Telnet must be enabled in order to use FTP. Remember todisable Telnet on the field panel when you are done using the

    Telnet and FTP services. For information on enabling Telnet,seeTroubleshooting.

  • 7/29/2019 545001 Field Go Manual

    44/98

    Chapter 2Field Panel GO Users Manual

    2-20 Siemens Building Technologies, Inc.

    Logging On

    1. At your computer's command prompt (C:>prompt), type f t p I PAddr ess or f t p Host Name of the Ethernet field panel.

    2. Type your ALN/BLN user account name and password to log on andconnect to the field panel FTP server.

    Copying Files from Your Computer to the Field Panel

    This step assumes you have translated the headings.xml file toFrench, and you now want to transfer the filec:\FPGOFiles\translations\fr\headings.xml from your computerto the \translations\frdirectory in the field panel. If necessary,adjust the commands to match your file structure.

    1. Type mkdi r \ t r ansl at i ons\ f r

    The mkdircommand lets you create a new directory on the field panel.2. Type cd \ t r ansl at i ons\ f r and press ENTER.

    This command takes you to the frdirectory

    3. Type l cd \ FPGOFi l es\ t r ansl at i ons\ f r and press ENTER.

    The lcd command lets you change the FTP clients working directory.

    4. Type put headi ngs. xml and press ENTER.

    The put command copies the file from your local computer to the fieldpanel.

    Transferring Files from the Field Panel to Your ComputerThis step assumes you want to transfer the file\translations\en-us\headings.xml from the field panel to thec:\FPGOFiles\translations\en-us directory on your local computer.If necessary, adjust the commands to match your file structure.

    1. Type l cd \ FPGOFi l es\ t r ansl at i ons\ en- us and press ENTER.

    The lcd command lets you change the FTP clients working directory.

    2. Type cd \ t r ansl at i ons\ en- us and press ENTER.

    The cd command lets you change the working directory on the fieldpanel.

    3. Type get headi ngs. xml and press ENTER.

    The get command copies the file from the field panel to the localcomputer.

    Logging Off and Exiting the Windows FTP Client

    When youre finished transferring files, type qui t and press ENTER.

    The quit command closes the FTP session and exits the FTP console.

  • 7/29/2019 545001 Field Go Manual

    45/98

    Configuring Field Panel GO

    Siemens Building Technologies, Inc. 2-21

    Example

    The following example shows the process of copying a translatedheadings.xml file to a French language directory (\translations\frdirectory)on the field panel. (Bold is added for emphasis.)

    Mi cr osof t Wi ndows 2000 [ Versi on 5. 00. 2195]

    ( C) Copyri ght 1985- 2000 Mi cr osof t Corp.

    C: \ Document s and Set t i ngs\ Poi r otH>f t p 136. 157. 37. 243

    Connect ed t o 136. 157. 37. 243.

    220 Nucl eus FTP Server ( Versi on 1. 5) r eady.

    User ( 136. 157. 37. 243: ( none)) : xxxx

    331 User name okay, need passwor d.

    Passwor d:

    230 User l ogged i n, proceed.f tp> mkdi r \ t r ansl at i ons\ f r

    257 " \ TRANSLATI ONS\ FR" di r ect ory has been cr eated.

    f tp> cd \ t r ansl at i ons\ f r

    250 Request ed f i l e acti on okay, compl eted.

    f tp> l cd \ FPGOFi l es\ t r ansl at i ons\ f r

    f tp> put headi ngs. xml

    f tp> qui t

    221 Servi ce cl osi ng cont r ol connect i on. Logged out i fappr opr i ate.

    C: \ Document s and Set t i ngs\ Poi r otH>

  • 7/29/2019 545001 Field Go Manual

    46/98

    Chapter 2Field Panel GO Users Manual

    2-22 Siemens Building Technologies, Inc.

  • 7/29/2019 545001 Field Go Manual

    47/98

    Siemens Building Technologies, Inc. 3-1

    Chapter 3Alarms Application

    Chapter Overview

    Chapter 3 discusses the following topics:

    Alarms Application Overview

    User Interface Description for Alarms

    Alarms Step-by-Step Instructions

    Displaying Point Alarms

    Acknowledging Alarm States

    Alarms Application Overview

    The Field Panel GO Alarms application displays point alarms detected inyour APOGEE Building Automation System. From the Alarms application,you can view and acknowledge alarms or select a point name to navigate tothe Point Commander application.

    Alarm acknowledgement is commonly used with critical points that requireimmediate response once they enter ALARM. Acknowledging a point alarmindicates to other users on the network that a particular alarm has been seenand is being managed.

    Points are defined as alarmable for the following reasons:

    To prevent critical problems. Points that affect human safety orcan cause a severe problem in building operation should bedefined as alarmable. For example, an alarm that notifies youthat the temperature of a heating coil is too low and action mustbe taken before it freezes.

    To notify you when equipment is not functioning properly.Sometimes problems may occur and go unnoticed. Alarming is auseful tool to identify equipment that is not working properly andto prevent other devices from becoming damaged.

    To indicate a runtime threshold has been reached. For example,an alarm can indicate when a fan has run for a certain number ofhours, which may prompt for maintenance.

    The following are some examples of equipment that is monitored withalarmable points:

    Temperature sensors

    Heating and cooling coils

    CO2 detectors

    Door sensors

    Proof switches

  • 7/29/2019 545001 Field Go Manual

    48/98

    Chapter 3Field Panel GO Users Manual

    3-2 Siemens Building Technologies, Inc.

    User Interface Descriptions for Alarms

    When you select the Alarms icon from the application toolbar, the application

    page consists of two tabs: the Alarm List and the Unack (unacknowledged)List.

    If a user has access to Alarms, the Alarms application is the firstpage to display when a Field Panel GO session begins.

    Points in the Alarm List and Unack List are grouped by fieldpanel and displayed in alphabetical order.

    The Alarms application displays 20 points per page. If Field PanelGO retrieves more than 20 points, additional pages can be viewedby clicking More.

    Once a point is acknowledged, Field Panel GO updates the Alarmsapplication page as follows:

    The point alarm is removed from the Unack List.

    The time and date of the alarm acknowledgement are added tothe Ack Time field in the Alarm List.

    *ACK* is added to the point status in the Alarm List.

    Once a point returns to NORMAL, that point no longer displays in the AlarmList. Point alarms that were not acknowledged before the point returned toNORMAL will remain in the Unack List.

    The following fields, buttons, and check boxes are used in the Alarmsapplication page:

  • 7/29/2019 545001 Field Go Manual

    49/98

    Alarms Application Overview

    Siemens Building Technologies, Inc. 3-3

    1. Alarms Buttons

    The Ack, Select All, and Clear All buttons are only available to users withCommand or higher access to the Alarms application.

    Ack is used in conjunction with the Select check box toacknowledge a point.

    Select All checks the Select check box for all points in the listthat are unacknowledged.

    Clear All clears the Select check box for all points you haveselected for acknowledgment.

    Refresh updates the alarm data with information from theAutomation Level Network (ALN) and regenerates the list.

    The Building Automation Level Network (BLN) is now calledthe Automation Level Network (ALN). However, all firmware

    prompt strings continue to use the BLN abbreviation.

    2. Alarms Detail Information

    The Select check box is used in conjunction with the Ack buttonto acknowledge an alarm state.

    This check box is grayed out once the alarm state isacknowledged.

    The Select check box is only available to users withCommand or higher access to the Alarms application.

    Name displays either the point name or the point system name,

    which is the label that identifies a particular point in thedatabase.

    You may navigate to the Point Commander application byclicking the point name.

    Each user account defines the type of name that is displayedin the interface. Those with User access see the point name.

    Those with System access see the point system name.

    When multiple rows are displayed, the point descriptor isincluded below the point name.

    Value displays the current value of the point. For example, 62.84DEG F, 8.66 Volts, or OFF.

    Status displays the status of the point.

    The following point statuses may be displayed in this field: -N-, *A*, *An*, *AC*, *F*, *O*, *ODSB*, *P*, *PDSB*, or *T*.

    See the sectionPoint Statusfor a description of eachcondition.

  • 7/29/2019 545001 Field Go Manual

    50/98

    Chapter 3Field Panel GO Users Manual

    3-4 Siemens Building Technologies, Inc.

    Priority displays the command priority of the point at the time ofalarm.

    The following command priorities may be displayed in this

    field: OPER (Operator), SMOKE, EMER (Emergency), PDL(Peak Demand Limiting), or NONE.

    See the sectionPoint Priorityfor a description of eachcondition.

    Initial Time displays the time of the first instance for the alarm.

    If the alarm state changes more than once, the Initial fielddisplays the time of the first alarm state.

    When multiple rows are displayed, the date of the first alarmstate is included below the Initial Time.

    Current Time displays the most recent time of an alarm state

    change.

    If the alarm state changes more than once, the Current Timefield displays the time of the most recent state change for thepoint.

    When multiple rows are displayed, the date of the mostrecent state change is included below the Current Time.

    Ack Time displays the time an alarm was acknowledged.

    When multiple rows are displayed, the date of