QUALITROL ® 505 ITM Intelligent transormer monitor  Advanced, accurate and intelligent monitoring or your transormer   The power to know your transormer health immediately with TransLie™    Advanced thermal modeling o winding temperatures   Superior temperature control or increased transormer loading  Product Summary  Description  Advanced transormer monitor, easy to confgure, control and track accurately all aspects o your power transormer. Dynamic loading analysis to optimize loading and maximize asset lie.   Application Industry leader in remote and local monitoring o oil-flled transormer and load tap changer parameters. Advanced control o cooling systems and alarms through intuitive ITM manager interace.

505_ITM_AP-M09-08A-01EN

Embed Size (px)

Citation preview

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 1/8

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 2/8

QUALITROL® 505 ITM intelligent transormer monitor

 Improve asset protection  •  In addition to traditional mechanical monitoring and protection,

  and utilization electronic transormer monitoring improves reliability, saety,and the availability o key decision making inormation.  

•  Expanded capabilities and features are now available in one single device.

  •  Avoid installation, maintenance and capital cost on additional devices.

` Immediately know your transormer  •  TransLie™ eature provides a dashboard o required critical inormation.  health with TransLie™  •  Computes loss of asset life rate, life consumption and remaining asset life  •  Critical Forecast eature determines the time remaining until a critical

temperature is reached based on current conditions  •  Monitor your windings with TransLie™  •  Temperature Proler eature provides the history o the

transormer’s temperature

  Optimize loading and equipment lie  •  Improved accuracy gained by use o advanced calculated windingtemperature measurement permit sae operation at higher loads

  •  Automatic cooling bank switching normalizes an and pump usageor maximum lie

  •  Pre-cooling unctionality reduces damaging high temperatures producedby overloads.

  •  Adaptive setback improves cooling system eciency by measuringambient temperature and then adapting cooling and alarm set pointsbased on temperature trends

  •  Low temperature lock-out insures oil pumps remain o at coldtemperatures, this prevents static electrication and arcing

  •  Seasonal setback allows or customized cooling schemes depending onthe time o the year

 Simpliy root cause analysis •  Continuous information of all important transformer operating parameters or condition-based maintenance aids in “drilling down” to the root, undamental cause o the problem

  •  Relay control contacts and “go/no-go” alarms serve as economicalmethod or remotely determining status o a transormer

  Flexibility  •  Flexible modular inputs (compatible with RTDs, CTs, voltages, currentloops & switch contacts) enable all parameters o transormers to bemonitored in one integrated device. 

•  New matrix relays can be set to alarm based on set points, a matrix oset points and dierence calculations. Improves identication otransormer issues and reduces alse trips

  •  0-1mA or 4-20mA outputs provide inormation toSCADA systems

  •  Multiple mounting options: control panel congurations; sel-containedcorrosion/weatherproo enclosure congurations; 19 inch mountrack congurations

  •  Utilizes digital protocols over RS-232 or RS-485  •  Field upgradeable or uture monitoring inputs

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 3/8

505 ITM intelligent transormer monitor capabilities

Email [email protected]

www.qualitrolcorp.com

Temperature

Third party devices

Oil levelLoad current

Pressure

Load tap changer

Cooling system

Control Inormation

• TransLie™

• Predictive loading

• SCADA outputs (0-1mA or 4-20mA)

Digital communication (RS 485, RS 232)• Protocols (DNP 3.0, MODBUS)

• Cooling system optimization

• Local and remote alarms

• Programmable relays

Cooling system exerciser• Seasonal set points

•  Ambient orecast

i

Monitor and measure

LTC

 Analyze and communicate

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 4/8

  QUALITROL® 505 ITM intelligent transormer monitor

 

TransLie™, the report card or transormers 

General Description

  •  TransLie™ eature provides a dashboard o

critical inormation needed to eectively managetransormer operation

  •  ITM manager is an intuitive helpul tool

to manage transormers, to provide data or

condition-based maintenance and to plan

capital expenditures eectively

  •  Critical orecast eature estimates the time to

reach critical temperature based on the present

transormer load

•  Temperature proler records the time at various

temperatures that relate to asset lie, this inormationis displayed graphically or quick identication o time

spent at peak temperatures

•  Monitoring a winding, the QUALITROL 505 ITM

receives inputs rom oil, winding and ambient

temperature to report loss o lie rates, lie

consumption (daily and hourly), total loss o lie and

remaining asset lie

TransLie™

Monitoring awinding

Temperature

Proiler

Logs the duration

that the transormer

is at each

temperature range

TransLie™ Control

Contains all the

selections o input

measurements or

TransLie™

Consumed Lie

Computes loss o

asset lie rate, lie

consumed, remainingasset lie and hours

in operation

Temperature

Proiler Graph

Graphical representation

o the transormer’shistorical temperature

Red bars provide quick

indication o time spent

at accelerated lie

consumption

Critical Forecast

Determines the time

remaining until acritical temperature

is reached based on

current conditions

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 5/8

 

QUALITROL® 505 ITM intelligent transormer monitor series

 505intelligent transormer monitor For general transormer control

 

•  Monitors and reports on important parameters such as liquid

temperature, winding temperature, load current, oil level,

and mechanical alarms.

  •  The 505 ITM uses the same accessories and sotware as the bigger

and very successul brother, the 509 ITM. This minimizes any retrainingto operate the 505 ITM.

Email [email protected]

www.qualitrolcorp.com

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 6/8

QUALITROL® 505 ITM intelligent transormer monitor

 

Components and accessories

Pt and Cu resistant  •  Provides transormer temperature measurements

  temperature devices (RTDs)  •  Many varieties available to custom t hundreds

o transormer applications with easy upgrade

to dierent types o equipment

  • Magnetic RTDs available or easy retrot when

wells are not available

   Ambient RTD (103-047)  •  For ambient temperature measurement within substation (close to transormer)

  •  Includes sun shield to prevent alse readings

 

Current transormers (CTs)  •  Measures current f ow needed to calculate

winding temperature, monitor cooling systems

and suppport advanced unctions

  •  Clip-on design simplies installation

  Pressure transducers (TRN-603-1)  •  Monitors static tank pressure and can provide

sudden pressure protection

  (requires QUALITROL 930)

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 7/8

  TECHNICAL SPECIFICATIONS

Power supply Type Universal ; 90 to 264 watts VAC; 47-63 Hz, 40-290 VDC

  Consumption < 30 watts AC IN; <15 watts DC IN 

Input module Number o inputs Accepts up to 4 input modules, 2 ixed, 2 conigurable  parameters   Accuracy ± 0.5% ull-scale input range

  RTD 10 ohm copper & 100 ohm platinum-40°F to 248°F range (-40°C to 120°C)

  CT, winding temperature Uses clamp-on sensor; range 0 to 5, 10, 20 amps

  AC voltage 0 to 140 and 0 to 360 VAC ranges

  Potentiometer Accepts potentiometers rom 5K to 15K

Dry switch contact Measures a dry switch contact as either open or closed

Powered switch contact Optically isolated; detects AC or DC rom 120 to 250 volts

Output relays  Number o relays 4 programmable, 1 system status, 1 relay or heater control

  Type Form C, 10 amps @ 120/240 VAC, 10 amps @ 30 VDC

  Output current  Number o loops 2 magnetically-isolated current loops  loop

  Type Customer congurable in sotware to choose between 0-1 mA(max load 10,000Ω ) and 4-20 mA (max load 450Ω )

  Communications  RS232 port 1 port or set-up communications located on the ront panel;varying baud rates

  RS485 port 1 port, 4-wire optically isolated or digital protocols

  USB port 1 type B (slave) or local setup

Protocols DNP 3.0 level 3 slave, Modbus RTU, ASCII

User interace  Control 8 pushdown buttons located on ront panel

Local display 2 x 16 character backlit LCD

  Environmental  Operating temperature -40°F to 161.6°F (-40°C to + 72°C)(-60°C when a heater is used)

Storage temperature -58°F to 185°F (-50°C to + 85°C)

Humidity 5% to 90% non-condensing

  Shock 10 G’s hal-sine, in three orthogonal planes

    Vibration 60/120 Hz @ .004 inch displacement; 10/150 Hz at 1G

  Immunity  Dielectric strength 2500 VAC, 60 seconds to ground

Surge withstand capability IEEE C37.90.1

  Cond./radiated emissions IEC 61000-6-1

  Cond./radiated RFI IEC 61000-6-2

  Saety IEC 61010-1 

CE approved Yes

Email [email protected]

www.qualitrolcorp.com

8/3/2019 505_ITM_AP-M09-08A-01EN

http://slidepdf.com/reader/full/505itmap-m09-08a-01en 8/8

  QUALITROL® 505 ITM intelligent transormer monitor

Weatherproo enclosure

Panel mount

19” rack mount