5-35 kv cables

Embed Size (px)

Citation preview

  • 5/28/2018 5-35 kv cables

    1/16

    Alcatel Canada Wire

    1

    ENERGEX-SPPOWER CABLES

    5 kV to 35 kVStandardsThe cables covered in this catalogueare designed, manufactured andtested in accordance with thefollowing standards and specifications:

    CSA C68.3-M97Shielded and Concentric N eutralPower Cables Rated 546 kV.

    ICEA S-66-524Crosslinked Thermosetting PolyethyleneInsulated Wire and Cable for the

    Transmission and Distribution ofElectrical Energy.

    CEA Purchasing SpecificationWCWG-02 (95) XLPE Primary FeederCable.

    AEIC CS5-94Specification for CrosslinkedPolyethylene Insulated Shielded PowerCables Rated Through 46 kV.

    The AEIC specification is applied inparticular to the conductor shield,insulation and insulation shield system

    so as to obtain the highest qualityafforded by any standard in thesecritical cable components. Therequirements of the other standardswill, of course, be met or exceeded.

    The conductor, metallic shielding andthe outer jacket meet the requirementsof CSA and ICEA standard.

    The cables in this catalogue meet CSAcold bend and impact tests at 40C.

    Information on shielded power cables

    rated above 35 kV is available bycontacting Alcatel Canada Wire SalesOffices.

    Quality SystemsTo ensure that our customers areprovided with products and servicesthat fully meet their requirements andexpectations, the Markhamheadquarters of Alcatel Canada Wireis certified to the ISO Standard

    9001-94 for the design anddevelopment of ENERGEX-SP PowerCables. Similarly, Alcatel CanadaWires sites for the manufacture andtesting of ENERGEX-SP Power Cablesare certified to the ISO Standard9002-94.

  • 5/28/2018 5-35 kv cables

    2/16

    Alcatel Canada Wire

    2

    Cable DesignConductors

    The conductor materials used in AlcatelCanada Wire ENERGEX-SP cables arein accordance with the latest editionsof the relevant ASTM standards. At thetime of publication, the standards ineffect are as follows:

    ASTM B 3 Annealed Copper Wire.

    ASTM B 8 Concentric-Lay-Stranded

    Copper Conductors.ASTM B 230 Aluminum 1350-H19Wire.

    ASTM B 231 Concentric-Lay-Stranded Aluminum Conductors.

    ASTM B 609 Aluminum 1350 Wire,Annealed and Intermediate Tempers.

    Compact Class B stranded conductorsare also available upon request.

    Note: Conductors to these standardsmeet or exceed CSA and othernational and international standardsfor a given size and stranding.

    Conductor Material Properties

    Property Annealed Copper Aluminum

    Atomic weight 63.57 26.97Specific gravity 8.89 2.705Melting point (C) 1083 660Resistivity (ohm-sq.mm/ km) 17.241 28.235

    (ohm-cmil/ ft) 10.371 17.002Conductivity (%IACS) 100.0 61.0Coefficient of resistance (/ C) 0.00393 0.00403Coefficient of expansion (/ C) 17 x 10-6 23 x 10-6

    Caution NoticeIn case of fire, well-maintained early-warningsmoke detectors will give an alarm longbefore non-metallic coverings becomecombustible.

    However, Alcatel Canada Wire advises that: Non-metallic coverings of electrical cables

    can burn and may transmit fire whenignited.

    Burning non-metallic coverings may emit

    STRANDBLOCKAlcatel Canada Wire offers, as anoption, stranded conductors withSTRANDBLOCK , which effectively

    prevents moisture migration throughthe conductor. STRANDBLOCKcables are fully qualified to allapplicable standards.

    acid gases which are toxic and maygenerate dense smoke.

    Emission of acid gases may corrode metalin the vicinity; e.g. sensitive instrumentsand reinforcing rods in concrete.

    Compressed Conductor DataWeight DC Resistance

    Size (stranding) Area Diameter kg/ km ohm/ km at 20C

    AWG/ kcmil sq.mm mm Cu Al Cu Al 8 (7) 8.37 3.61 76 23 2.10 3.44

    6 (7) 13.3 4.52 121 37 1.32 2.17

    4 (7) 21.2 5.72 192 58 0.830 1.36

    3 (7) 26.7 6.40 242 74 0.670 1.07

    2 (7) 33.6 7.19 305 93 0.522 0.856

    1 (19) 42.4 8.18 385 117 0.413 0.679

    1/ 0 (19) 53.5 9.19 485 147 0.328 0.538

    2/ 0 (19) 67.4 10.29 611 186 0.261 0.427

    3/ 0 (19) 85.0 11.58 771 234 0.207 0.338

    4/ 0 (19) 107 13.00 972 296 0.164 0.269

    250 (37) 127 14.17 1150 349 0.139 0.228

    300 (37) 152 15.52 1380 419 0.116 0.190

    350 (37) 177 16.79 1610 489 0.0991 0.163

    400 (37) 203 17.94 1840 559 0.0868 0.142

    500 (37) 253 20.04 2300 699 0.0700 0.114

    600 (61) 304 22.00 2760 838 0.0578 0.0948

    750 (61) 380 24.59 3450 1050 0.0463 0.0758

    1000 (61) 507 28.37 4590 1400 0.0348 0.0568

  • 5/28/2018 5-35 kv cables

    3/16

    Alcatel Canada Wire

    3

    Insulation Thickness and Minimum Conductor Size

    Thickness, mmRated Minimum 100% 133%

    voltage size, AWG insulation level insulation level

    5 8 2.29 2.928 6 2.92 3.56

    15 2 4.45 5.5925 1 6.60 8.1328 1 7.11 8.7635 1/ 0 8.76 10.67

    Conductor Shield Thickness

    Conductor Size Thickness, mm(AWG/ kcmil) Minimum average Minimum at 1 Pt

    84/ 0 0.38 0.31250500 0.51 0.416001000 0.64 0.51

    The 133% insulation level is frequentlyspecified for systems without agrounded neutral, or where faultdurations may exceed 1 minute, butnot 1 hour. In the case where the faultduration exceeds 1 hour, we recom-mend a voltage rating of at least 1.73times the system voltage.

    Requirements for Extruded Semiconducting XLPO Conductor Shield

    Unaged tensile strength 7.0 MPa min.Volume resistivity at room temperature 1000 ohmm max.

    at 90C 1000 ohmm max. at 130C 1000 ohmm max.

    Elongation, aged 168 h at 121C 100% min.Brittleness temperature 25C max.Voids >0.076 mm noneProtrusions into insulation 0.076 mm max.Protrusions into conductor shield 0.18 mm max.

    Conductor ShieldingA conductor shield is provided on allcables in this catalogue. The standardconductor shield on Alcatel CanadaWire ENERGEX-SP cables is extrudedsemiconducting crosslinked polyolefin(XLPO), which meets or exceeds theAEIC, ICEA and CSA requirementsshown at right. In addition, AlcatelCanada Wire offers cable withsupersmooth conductor shielding,which enhances the life expectancy ofthe cable.

    Insulation

    The standard insulation on AlcatelCanada Wire ENERGEX-SP Cables isunfilled crosslinked polyethylene(XLPE), meeting or exceeding therequirements of AEIC CS5, ICEA S-66-524 and CSA C68.3 as shown at

    right.Using Alcatel Canada WiresEXELCURE process, the conductorshield, insulation and insulation shieldare true-triple extruded and curedtogether in a sealed, dry curingsystem.

    All insulating compounds are dis-pensed through an Extra CleanCompound Handling System tominimize contamination and increasecable life expectancy.

    Requirements for XLPE Insulation

    Unaged tensile strength 12.4 MPa min.Elongation at rupture 250% min.Aged 168 h at 121C:

    Tensile strength 75% of unaged value, min.Elongation 75% of unaged value, min.

    Heat distortion at 121C:4/ 0 AWG and smaller 25% max.Larger than 4/ 0 AWG 15% max.

    Moisture absorption at 75C:Dielectric constant after 24 h 3.5 max.Increase in capacitance 114 days 3.0% max.

    714 days 1.5% max.Stability factor after 14 days 1.0 max.Solvent extraction after 20 h 30% max.

    Power factor at room temperature 2.0% max.Insulation resistance: K at 15C 6100 megohm-km min.

    Alcatel Canada Wire also offers tree-retardant crosslinked polyethylene (TR-

    XLPE) insulation, which meets orexceeds the same standards andspecifications.

  • 5/28/2018 5-35 kv cables

    4/16

    Alcatel Canada Wire

    4

    Requirements for 75C PVC Jacket

    Unaged tensile strength 10.3 MPa min.Elongation 100% min.Aged 168 h at 121C:

    Tensile strength 85% of unaged value, min.Elongation 60% of unaged value, min.

    Immersed in oil for 4 h at 70C:Tensile strength 75% of unaged value, min.

    Heat distortion at 121C: 50% max.

    Heat shock at 121C no cracksCold bend at 40C no cracksCold impact at 40C no cracks

    Insulation ShieldingThe standard insulation shield onAlcatel Canada Wire ENERGEX-SPCables is semiconducting crosslinkedpolyolefin (XLPO), meeting or exceed-ing the requirements of AEIC, ICEAand CSA as shown at right.

    In addition, Alcatel Canada Wire cansupply, on request, bonded insulationshielding.

    Requirements for Extruded Semiconducting XLPO Insulation Shield

    Unaged tensile strength 7.0 MPa min.Volume resistivity at room temperature 500 ohmm max.

    at 90C 500 ohmm max. at 110C 500 ohmm max.

    Elongation, aged 168 h at 121C 100% min.Brittleness temperature 25C max.Voids >0.13 mm noneProtrusions into insulation 0.13 mm max.Protrusions into insulation shield 0.13 mm max.

    Jacket

    The standard jacket on AlcatelCanada Wire ENERGEX-SP Cables islow-temperature, low-gas-emission,limited-flame-spread polyvinyl chloride(PVC).

    The standard PVC jacket meets or

    exceeds the requirements of ICEA andCSA as shown at right.

    Low density polyethylene(LDPE), linearlow density polyethylene (LLDPE) andmedium density polyethylene (MDPE)jackets are available upon request. Inaddition, special jacket marking (e.g.,lightning bolt symbol, sequential lengthmarking, etc.) is available uponrequest.

    Insulation Shield Thickness, mm

    Insulation Thickness, mmdiameter

    mm Min avg Min 1 Pt Max 1 Pt*

    =

  • 5/28/2018 5-35 kv cables

    5/16

    Alcatel Canada Wire

    5

    Ampacity, amperes

    Cable rated < = 5 kV Cable rated > 5 kV

    Size Direct Triplexed in Triplexed in Direct Triplexed in Triplexed in(AW G/ kcmil) buried buried duct isolated conduit buried buried duct isolated conduit

    4 Cu 180 110 97 170 115 1104 Al 140 86 76 130 91 842 Cu 230 145 130 210 155 1502 Al 180 115 100 165 120 1151 Cu 260 170 155 240 175 1701 Al 205 130 120 185 135 1301/ 0 Cu 295 195 180 275 200 1951/ 0 Al 230 150 140 215 155 1502/ 0 Cu 335 220 205 310 230 2252/ 0 Al 265 170 160 245 175 175

    3/ 0 Cu 385 250 240 355 260 2603/ 0 Al 300 195 190 275 200 2004/ 0 Cu 435 290 280 405 295 2954/ 0 Al 340 225 215 315 230 230250 Cu 470 320 315 440 325 330250 Al 370 250 250 345 250 255350 Cu 570 385 385 535 390 395350 Al 445 305 305 415 305 310500 Cu 690 470 475 650 465 480500 Al 540 370 380 510 370 385750 Cu 845 585 600 805 565 585750 Al 665 470 490 635 455 4851000 Cu 980 670 690 930 640 6751000 Al 780 545 580 740 525 565

    Technical DataAmpacity

    The ampacities given in the tablesbelow are based on the followingconditions:

    Conductor temperature 90C Ambient earth temperature 20C Earth interface temperature not limited Ambient air temperature 40C Direct burial depth 0.9 m (3 ft.) with

    cables spaced 19 cm centre-to-centrein one horizontal layer of 3 cables

    Depth to top of duct bank 0.8 m(2.5 ft.)

    Earth thermal resistivity 90C cm/ W Load factor 100% One circuit operating No shield circulating current

    Where shields are grounded at morethan one point, the ampacities shownabove should be adjusted to take intoconsideration the heating due to shieldcurrents.

    For buried installations, the valuesshown may be limited by the maximumearth interface temperature due to soil

    moisture migration. Knowledge oflocal soil conditions is necessary forthe determination of the proper earthinterface temperature to be used.Typical values are between 50C and60C, which experience has indicatedshould be satisfactory for most types ofsoils.

  • 5/28/2018 5-35 kv cables

    6/16

    Alcatel Canada Wire

    6

    Ampacity Correction Factors

    For different conductor temperatures:

    wherel =current at conductor temperature

    Tc

    l =current at conductor temperature90C

    Ta

    =ambient temperatureT

    o=inferred temperature of zero

    resistance (= 234.5 for Cu,228.1 for Al)

    Tc

    =desired conductor temperature

    For certain temperatures, this factor is:

    Conductor Ambient Ambienttemp, C 20C 40C

    90 1.00 1.0080 0.93 0.8970 0.85 0.7760 0.76 0.63

    For different ambient temperatures:

    wherel = current at ambient Ta

    '

    l = current at ambient Ta

    Tc

    = conductor temperatureTa

    ' = desired conductor temperature

    l = lTc Ta

    '

    Tc Ta

    l = l x

    Load Factor

    All tabulated ampacities of cablesburied in soil or in ducts are based on100% load factor (continuousoperation at the stated load). Where adaily load cycle is involved, the currentrating may be increased according tothe load factor as follows:

    Load Directly Buried factor buried ducts

    100% 1.00 1.0075% 1.08 1.04

    50% 1.16 1.07

    Tc Ta90 Ta

    To+ 90

    To+ Tc

    Inductive Reactance

    The inductive reactance of cables in amulticable circuit is:XL = 0.0754 ln(GMD/ GMR) ohm/ km

    to neutral at 60 Hz(= 0.023 ln(GMD/ GMR) ohm/1000 ft)

    whereGMD=equivalent axial spacing

    between the phase conductors

    For trefoil GMD = axialspacingFor flat GMD = 1.26 axialspacing

    GMR =geometric mean radius of theconductor(Note: GMD and GMR mustbe in same units)

    Conductor Resistance

    Conductor resistance may becorrected to temperatures other than20C by the following formula:

    R = R (1 + a (Tc 20))

    whereR = resistance at temperature TcR = resistance at 20Ca = 0.00393 for Cu, 0.00403 for Al

    Ampacity In Free Air

    Rated Rated Rated Size < = 5 kV < = 15 kV < = 35 kV

    4 Cu 145 150 4 Al 115 115 2 Cu 190 195 2 Al 150 150 1 Cu 225 225 2251 Al 175 175 1751/ 0 Cu 260 260 2601/ 0 Al 200 200 2002/ 0 Cu 300 300 3002/ 0 Al 230 235 230

    3/ 0 Cu 345 345 3453/ 0 Al 270 270 2704/ 0 Cu 400 400 3954/ 0 Al 310 310 310250 Cu 445 445 440250 Al 345 345 345350 Cu 550 550 545350 Al 430 430 430500 Cu 695 685 680500 Al 545 535 530750 Cu 900 885 870750 Al 710 700 6851000 Cu 1075 1060 10401000 Al 855 840 825

  • 5/28/2018 5-35 kv cables

    7/16

    Alcatel Canada Wire

    7

    Short Circuit Capacity

    The short circuit capacity of phaseconductors and shields is limited bytheir heat capacity and by themaximum temperature permitted in theadjacent cable materials. Thetemperature limits established byAlcatel Canada Wire are:Phase conductors 250CShield 200C

    The following equation is used tocalculate short circuit capacity:

    wherelsc = short circuit current, amperesk = constant

    (= 0.0297 for copper, 0.0125for aluminum)

    A = conductor or metallic shield*area, cmil

    T0

    = inferred temperature of zeroresistance(= 234.5 for copper, 228.1 foraluminum)

    T1 = temperature of conductor orshield at start of short circuit

    T2

    = limiting temperature for shortcircuit

    t = short circuit duration, seconds

    *Shield area = 4 dsm bdsm = mean shield diameter, milsb = shield tape thickness, mils

    In using the above formula, the shortcircuit duration should not exceed 3seconds, after which time heat will

    begin to flow and a differentcalculation procedure is required.

    The self reactance of a single cable is:XL =0.0754 ln(rn/ GMR) ohm/ km at

    60 Hz(= 0.023 ln(rn/ GMR) ohm/ 1000ft)

    wherern =mean radius of the shield

    The reactance of the shield is:XL =0.0754 ln(GMD/ rn) ohm/ km at

    60 Hz(= 0.023 ln(GMD/ rn) ohm/ 1000ft)

    Capacitance

    The capacitance of single conductor,insulated and shielded cables is:C =0.0556 e/ ln(D/ d) F/ km

    (= 0.0169 e/ ln(D/ d) F/1000 ft)wheree =dielectric constant of the

    insulation(= 2.3 for XLPE)

    D =diameter over the insulationd =diameter under the insulation

    Capacitive reactance, Xc = 1.0 x 10+6

    2 fC

    ohm/ km (or ohm/ 1000 ft), is usuallyignored in cables up to about 20 km(12 miles) in length. Note thatcapacitive reactance is inverselyproportional to the cable length.

    Charging current, lch = 2 fC Eo(mA/ km or mA/ 1000 ft), where Eo isthe line-to-neutral voltage, or appliedtest voltage in kV.

    lsc = A k log10

    t

    ( )T2+ T0T1+ T0

  • 5/28/2018 5-35 kv cables

    8/16

    Alcatel Canada Wire

    8

    InstallationPulling Tension

    The maximum tension applied to acable during installation is limited inorder to prevent damage or distortionof cable components which couldreduce the life or reliability of thecable.

    The method of pulling is significant inthat different methods will result indifferent stresses on critical cable

    components for the same overalltension

    Alcatel Canada Wire recommendsthat, wherever possible, the cable bepulled by means of the conductor,aided where feasible by a grip overthe outer jacket.

    Maximum Pulling Tension* for ENERGEX-SP Power Cables

    Single-conductor Three-conductor

    Size Copper Aluminum Copper Aluminum(Newtons) (Newtons) (Newtons) (Newtons)

    8 805 460 1610 9206 1285 735 2570 14704 2040 1165 4080 23303 2575 1470 5150 29402 3245 1855 6490 37101 4095 2340 8190 4680

    1/ 0 5160 2950 10320 59002/ 0 6510 3720 13020 74403/ 0 8210 4690 16420 93804/ 0 10350 5915 20700 11830250 12230 6985 24460 13970350 17120 9780 34240 19560500 24460 13975 48920 27950

    750 36690 20960 73380 419201000 48920 27950 97840 55900

    *Note: Maximum allowable tension when pulling directly on the conductor(s).

    The tension developed in any straightsection of a duct is calculated asfollows:T = 9.81 LWFwhereT = pulling force, NewtonsL = section length, metresW = cable weight, kg/ metref = coefficient of dynamic friction

    The tension developed in a bend iscalculated as follows:T = T1 e(fa)

    whereT = tension leaving bend

    T1 = tension at bend entrancee = base of natural logarithms

    (2.71828)f = coefficient of dynamic frictiona = angle of bend, radians

    The parameter e(fa)is evaluated forsome common conditions.

    Bend e(fa)

    angle(degrees) f = 0.25 f = 0.30 f = 0.4

    30 1.14 1.17 1.2345 1.22 1.27 1.3760 1.30 1.37 1.5290 1.48 1.60 1.88

    At any bend the tension should notexceed 22.5 kN per metre of radius ofthe bend.

    When designing the duct layout, it isrecommended that the bends beconcentrated near the end from whichthe cable is to be pulled. This practicewill result in lower tensions. In somecases, the tensions resulting fromalternative directions should becalculated.

    Both the cable and pulling rope shouldbe well lubricated with a goodcommercial cable lubricant followingthe lubricant suppliers instructions.

    The recommendations given above areintended to cover a wide range ofpulling conditions. It is possible, underideal conditions, and with experiencedsupervision, to exceed these limits. Forfurther guidance, see IEEE Paper 84T&D 365-3, or contact Alcatel CanadaWire.

    Coefficients of Dynamic Frictionwith Lubricant

    (low Sidewall Pressure)

    One Three Duct Cable cable cables type covering per duct per duct

    PVC PVC 0.50 0.60PE 0.40 0.45

    PE PVC 0.30 0.45PE 0.25 0.85

    Fibre PVC 0.25 0.60PE 0.40 0.45

    Asbestos PVC 0.70 0.70cement PE 0.70

  • 5/28/2018 5-35 kv cables

    9/16

    Alcatel Canada Wire

    9

    DC Test Voltage, kV

    Voltage Proof Acceptance Maintenance rating, kV Test Test Test

    5100% 25 28 95133% 34 36 118100% 34 36 118133% 41 44 14

    15100% 53 56 1815133% 60 64 2025100% 75 80 25

    25133% 90 96 3028100% 79 84 2628133% 94 100 3135100% 94 100 3135133% 116 124 39

    DC Test Voltage (kV)Leakage current = x 10-3A

    Insulation Resistance (M )

    Insulation Resistance = k/ L x log10

    (D/ d) x 103M

    where D = Diameter over insulationd = Diameter over conductorL = Length of conductor under test, m or ftk = 6100 where L is in metres

    = 20000 where L is in feet

    Field TestingA high-voltage DC test made beforeplacing a new cable system in servicewill normally reveal grossimperfections such as mechanicaldamage during installation orimproperly made accessories. It is notexpected to reveal deterioration due toageing in service.

    At any time during installation, a ProofTest may be made at a voltage notexceeding that shown in the tableapplied for five consecutive minutes.

    After installation and before the cableis placed in regular service, anAcceptance Test may be made at avoltage not exceeding that shown inthe table applied for 15 consecutiveminutes.

    After the cable has been completelyinstalled and placed in regular service,a Maintenance Test may be made atany time within the first five years at avoltage not exceeding that shown in

    the table applied for five consecutiveminutes. Recent research has shownthat the loss of dielectric strengthcaused by normal wet ageing willshorten cable life when subjected toDC testing. After that time, such testingis not recommended.

    These tests should only be undertakenby persons familiar with the use of theequipment and appropriate safetyprecautions. If any equipment isincluded beyond the cableterminations, the dielectric strength of

    such equipment must be taken intoconsideration when establishing thetest voltage.

    The maximum permissible leakagecurrent can be calculated with theformula below. Note that this does notinclude terminal leakage.

    For further information, see AlcatelCanada Wire Product InformationLetter number PIL 14-12.

  • 5/28/2018 5-35 kv cables

    10/16

    Alcatel Canada Wire

    10

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    8 3.61 9.70 11.22 13.7 255 205 2.679 4.416 0.175

    6 4.52 10.60 12.12 15.4 345 260 1.686 2.779 0.166

    4 5.72 11.80 13.32 16.6 445 310 1.060 1.748 0.155

    3 6.40 12.50 14.02 17.3 510 340 0.841 1.386 0.149

    2 7.19 13.30 14.82 18.1 590 380 0.667 1.100 0.1441 8.18 14.25 15.77 19.1 690 420 0.529 0.872 0.137

    1/ 0 9.19 15.30 16.82 20.1 810 470 0.420 0.691 0.132

    2/ 0 10.29 16.40 17.92 21.2 960 535 0.333 0.548 0.128

    3/ 0 11.58 17.65 19.17 23.5 1200 665 0.265 0.435 0.127

    4/ 0 13.00 19.10 20.62 24.9 1435 760 0.210 0.345 0.122

    250 14.17 20.50 22.02 26.3 1650 850 0.178 0.293 0.119

    300 15.52 21.85 23.37 27.7 1910 950 0.149 0.244 0.116

    350 16.79 23.15 24.67 29.0 2175 1055 0.129 0.210 0.113

    400 17.93 24.30 25.82 30.1 2435 1150 0.113 0.184 0.111

    500 20.04 26.40 28.40 32.7 2970 1375 0.0919 0.148 0.109

    600 22.00 28.60 30.60 34.9 3490 1575 0.0779 0.124 0.107

    750 24.59 31.20 33.20 37.5 4250 1850 0.0643 0.101 0.104

    1000 28.37 35.00 37.00 41.3 5490 2295 0.0513 0.0777 0.100

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    *CSA, ICEA and UL recognize the use of 2.29 mm (90 mils) insulation thickness for 133% insulation level, while AEIC requires 2.92 mm (115 mils).

    ENERGEX-SP5 kV 100 and 133% Insulation Level* XLPE Insulation 2.29 mm (90 mils)

  • 5/28/2018 5-35 kv cables

    11/16

    Alcatel Canada Wire

    11

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    8 3.61 10.95 12.47 15.8 315 265 2.679 4.416 0.186

    6 4.52 11.85 13.37 16.7 380 295 1.686 2.779 0.172

    4 5.72 13.05 14.57 17.9 480 350 1.060 1.748 0.161

    3 6.40 13.75 15.27 18.6 545 380 0.841 1.386 0.155

    2 7.19 14.55 16.07 19.4 630 420 0.667 1.099 0.1491 8.18 15.55 17.07 20.4 730 460 0.529 0.872 0.142

    1/ 0 9.19 16.55 18.07 21.4 855 515 0.420 0.691 0.137

    2/ 0 10.29 17.65 19.17 23.5 1060 635 0.333 0.548 0.135

    3/ 0 11.58 18.95 20.47 24.8 1255 715 0.265 0.435 0.131

    4/ 0 13.00 20.35 21.87 26.2 1490 815 0.210 0.345 0.126

    250 14.17 21.80 23.32 27.6 1705 905 0.178 0.293 0.123

    300 15.52 23.15 24.67 29.0 1970 1010 0.149 0.244 0.119

    350 16.79 24.40 25.92 30.2 2235 1115 0.129 0.210 0.117

    400 17.93 25.55 27.07 31.4 2495 1215 0.113 0.184 0.114

    500 20.04 27.65 29.65 34.0 3040 1445 0.0918 0.148 0.112

    600 22.00 29.85 31.85 36.2 3565 1645 0.0777 0.124 0.109

    750 24.59 32.45 34.45 38.8 4330 1925 0.0641 0.101 0.106

    1000 28.37 36.25 38.25 42.6 5580 2380 0.0510 0.0775 0.102

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    Cables 6 AWG and larger may be dual rated 5 kV 133% / 8 kV 100% Insulation Level.

    *CSA, ICEA and UL recognize the use of 2.29 mm (90 mils) insulation thickness for 133% insulation level, while AEIC requires 2.92 mm (115 mils).

    ENERGEX-SP5 kV 133% Insulation Level* XLPE Insulation 2.92 mm (115 mils)

  • 5/28/2018 5-35 kv cables

    12/16

    Alcatel Canada Wire

    12

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    2 7.19 17.60 19.12 23.4 790 580 0.667 1.099 0.163

    1 8.18 18.60 20.12 24.4 900 630 0.529 0.872 0.156

    1/ 0 9.19 19.60 21.12 25.4 1030 690 0.419 0.691 0.150

    2/ 0 10.29 20.70 22.22 26.5 1190 765 0.333 0.548 0.144

    3/ 0 11.58 22.00 23.52 27.8 1390 850 0.265 0.435 0.1394/ 0 13.00 23.40 24.92 29.2 1635 955 0.210 0.345 0.134

    250 14.17 24.85 26.37 30.7 1855 1055 0.178 0.292 0.130

    300 15.52 26.20 28.20 32.5 2155 1200 0.149 0.244 0.128

    350 16.79 27.45 29.45 33.8 2430 1310 0.128 0.210 0.125

    400 17.93 29.60 30.60 34.9 2695 1415 0.113 0.184 0.122

    500 20.04 30.70 32.70 37.0 3220 1620 0.0914 0.148 0.118

    600 22.00 32.95 34.95 39.3 3750 1835 0.0773 0.124 0.116

    750 24.59 35.50 37.50 41.8 4525 2125 0.0637 0.100 0.112

    1000 28.37 39.30 41.80 47.7 6010 2815 0.0502 0.0769 0.111

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    ENERGEX-SP15 kV 100% Insulation Level XLPE Insulation 4.45 mm (175 mils)

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    1 8.18 20.85 22.37 26.7 995 730 0.529 0.872 0.162

    1/ 0 9.19 21.90 23.42 27.7 1130 795 0.419 0.691 0.156

    2/ 0 10.29 23.00 24.52 28.8 1295 870 0.333 0.548 0.151

    3/ 0 11.58 24.25 25.77 30.1 1500 960 0.264 0.435 0.145

    4/ 0 13.00 25.70 27.22 31.5 1750 1070 0.210 0.345 0.140250 14.17 27.10 29.10 33.4 2005 1205 0.178 0.292 0.137

    300 15.52 28.45 30.45 34.8 2280 1325 0.149 0.244 0.133

    350 16.79 29.75 31.75 36.1 2560 1440 0.128 0.210 0.130

    400 17.93 30.90 32.90 37.2 2830 1550 0.113 0.184 0.127

    500 20.04 33.00 35.00 39.3 3360 1765 0.0913 0.148 0.123

    600 22.00 35.20 37.20 41.5 3900 1985 0.0771 0.124 0.120

    750 24.59 37.80 39.80 45.7 4850 2450 0.0632 0.100 0.119

    1000 28.37 41.60 44.10 50.0 6195 2995 0.0498 0.0767 0.115

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    AEIC CS5-94 recognizes No 2 AW G with 5.59 mm (220 mils) insulation.

    ENERGEX-SP15 kV 133% Insulation Level XLPE Insulation 5.59 mm (220 mils)

  • 5/28/2018 5-35 kv cables

    13/16

    Alcatel Canada Wire

    13

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    1 8.18 22.90 24.42 28.7 1090 825 0.529 0.872 0.168

    1/ 0 9.19 23.90 25.42 29.7 1230 890 0.419 0.691 0.162

    2/ 0 10.29 25.00 26.52 30.8 1395 970 0.333 0.548 0.156

    3/ 0 11.58 26.30 28.30 32.6 1635 1100 0.264 0.435 0.151

    4/ 0 13.00 27.70 29.70 34.0 1890 1215 0.210 0.345 0.146250 14.17 29.40 31.40 35.7 2125 1325 0.176 0.292 0.142

    300 15.52 30.75 32.75 37.1 2405 1445 0.149 0.244 0.138

    350 16.79 32.00 34.00 38.3 2685 1565 0.128 0.209 0.134

    400 17.93 33.15 35.15 39.5 2960 1680 0.113 0.184 0.132

    500 20.04 35.25 37.25 41.6 3500 1900 0.0911 0.147 0.127

    600 22.00 37.50 39.50 45.4 4205 2290 0.0768 0.123 0.127

    750 24.59 40.05 42.55 48.5 5055 2655 0.0630 0.100 0.123

    1000 28.37 43.85 46.35 52.3 6365 3170 0.0496 0.0765 0.118

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    ENERGEX-SP25 kV 100% Insulation Level XLPE Insulation 6.60 mm (260 mils)

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    1 8.18 25.95 27.47 31.8 1245 980 0.529 0.872 0.176

    1/ 0 9.19 26.95 28.95 33.3 1420 1080 0.419 0.691 0.170

    2/ 0 10.29 28.05 30.05 34.4 1595 1165 0.333 0.548 0.164

    3/ 0 11.58 29.35 31.35 35.7 1810 1270 0.264 0.435 0.1584/ 0 13.00 30.75 32.75 37.1 2070 1390 0.210 0.345 0.152

    250 14.17 32.45 34.45 38.8 2310 1510 0.178 0.292 0.148

    300 15.52 33.80 35.80 40.1 2600 1640 0.149 0.244 0.144

    350 16.79 35.05 37.05 41.4 2885 1765 0.128 0.209 0.140

    400 17.93 36.20 38.20 42.5 3165 1885 0.112 0.183 0.137

    500 20.04 38.30 40.30 46.2 3875 2280 0.0909 0.147 0.135

    600 22.00 40.55 43.05 49.0 4490 2575 0.0766 0.123 0.132

    750 24.59 43.15 45.65 51.6 5305 2905 0.0627 0.100 0.128

    1000 28.37 46.90 49.40 55.3 6630 3435 0.0493 0.0763 0.122

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    ENERGEX-SP25 kV 133% Insulation Level XLPE Insulation 8.13 mm (320 mils)

  • 5/28/2018 5-35 kv cables

    14/16

    Alcatel Canada Wire

    14

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    1 8.18 23.90 25.42 29.7 1140 875 0.529 0.872 0.171

    1/ 0 9.19 24.90 26.42 30.7 1280 940 0.419 0.691 0.164

    2/ 0 10.29 26.00 27.52 31.8 1450 1025 0.333 0.548 0.158

    3/ 0 11.58 27.30 29.30 33.6 1690 1155 0.264 0.435 0.154

    4/ 0 13.00 28.75 30.75 35.1 1950 1270 0.210 0.345 0.148250 14.17 30.40 32.40 36.7 2185 1385 0.178 0.292 0.144

    300 15.52 31.75 33.75 38.1 2470 1510 0.149 0.244 0.140

    350 16.79 33.05 35.05 39.4 2750 1630 0.128 0.209 0.136

    400 17.93 34.15 36.15 40.5 3025 1745 0.113 0.184 0.134

    500 20.04 36.30 38.30 42.6 3570 1970 0.0910 0.147 0.129

    600 22.00 38.50 40.50 46.4 4285 2370 0.0767 0.123 0.128

    750 24.59 41.10 43.60 49.5 5140 2740 0.0629 0.100 0.125

    1000 28.37 44.85 47.35 53.3 6455 3255 0.0495 0.0764 0.119

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    ENERGEX-SP28 kV 100% Insulation Level XLPE Insulation 7.11 mm (280 mils)

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    1 8.18 27.20 29.20 33.5 1345 1080 0.529 0.872 0.180

    1/ 0 9.19 28.20 30.20 34.5 1490 1155 0.419 0.691 0.173

    2/ 0 10.29 29.30 31.30 35.6 1665 1240 0.333 0.548 0.167

    3/ 0 11.58 30.60 32.60 36.9 1885 1345 0.264 0.435 0.1614/ 0 13.00 32.05 34.05 38.4 2150 1470 0.210 0.345 0.155

    250 14.17 33.70 35.70 40.0 2395 1590 0.178 0.292 0.150

    300 15.52 35.05 37.05 41.4 2680 1720 0.149 0.244 0.146

    350 16.79 36.35 38.35 42.7 2970 1850 0.128 0.209 0.143

    400 17.93 37.45 39.45 45.4 3415 2135 0.112 0.183 0.142

    500 20.04 39.60 42.10 48.0 4020 2425 0.0908 0.147 0.138

    600 22.00 41.80 44.30 50.2 4590 2675 0.0765 0.123 0.134

    750 24.59 44.40 46.90 52.8 5415 3015 0.0626 0.100 0.129

    1000 28.37 48.15 50.65 56.6 6745 3550 0.0492 0.0762 0.124

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    ENERGEX-SP28 kV 133% Insulation Level XLPE Insulation 8.76 mm (345 mils)

  • 5/28/2018 5-35 kv cables

    15/16

    Alcatel Canada Wire

    15

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    1/ 0 9.19 28.20 30.20 34.5 1490 1155 0.419 0.691 0.173

    2/ 0 10.29 29.30 31.30 35.6 1665 1240 0.333 0.548 0.167

    3/ 0 11.58 30.60 32.60 36.9 1885 1345 0.264 0.435 0.161

    4/ 0 13.00 32.05 34.05 38.4 2150 1470 0.210 0.345 0.155

    250 14.17 33.85 35.85 40.2 2395 1595 0.178 0.292 0.151

    300 15.52 35.20 37.20 41.5 2685 1725 0.149 0.244 0.146

    350 16.79 36.45 38.45 42.8 2970 1850 0.128 0.209 0.143

    400 17.93 37.60 39.60 45.5 3420 2135 0.112 0.183 0.142

    500 20.04 39.70 42.20 48.1 4025 2425 0.0908 0.147 0.138

    600 22.00 41.95 44.45 50.4 4595 2680 0.0765 0.123 0.134

    750 24.59 44.50 47.00 52.9 5415 3015 0.0626 0.100 0.130

    1000 28.37 48.30 50.80 56.7 6750 3550 0.0492 0.0762 0.124

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    ENERGEX-SP35 kV 100% Insulation Level XLPE Insulation 8.76 mm (345 mils)

    Three Cables in Trefoil

    Size Nominal Diameter Weight AC Resistance 90C Inductive

    AWG/ Conductor Insulation InsulShld Jacket Cu Al Cu Al Reactance

    kcmil (mm) (mm) (mm) (mm) (kg/ km) (kg/ km) (ohm/ km) (ohm/ km) (ohm/ km)

    (0.75) (1.25)

    4/ 0 13.00 35.85 37.85 42.2 2400 1720 0.210 0.345 0.162

    250 14.17 37.65 39.65 45.6 2820 2020 0.178 0.292 0.160

    300 15.52 39.00 41.50 47.4 3165 2210 0.149 0.244 0.156

    350 16.79 40.30 42.80 48.7 3470 2350 0.128 0.209 0.153400 17.93 41.40 43.90 49.8 3760 2480 0.112 0.183 0.149

    500 20.04 43.55 46.05 52.0 4335 2735 0.0906 0.147 0.144

    600 22.00 45.75 48.25 54.2 4915 3000 0.0764 0.123 0.140

    750 24.59 48.35 50.85 56.8 5755 3355 0.0624 0.0994 0.135

    1000 28.37 52.10 54.60 60.5 7110 3910 0.0489 0.0760 0.129

    AC resistance, including both skin and proximity effects, and inductive reactance are calculated at 60 Hz for cables in trefoil.

    AEIC CS5-94 recognizes sizes No. 1/ 0 AWG and larger with 10.67 mm (420 mils) insulation.

    ENERGEX-SP35 kV 133% Insulation Level XLPE Insulation 10.67 mm (420 mils)

  • 5/28/2018 5-35 kv cables

    16/16

    Alcatel Canada Wire

    16

    Dimensions

    Lengthmils x 0.0254 = mm (millimetres)inches x 25.4 = mmfeet x 0.3048 = m (metres)miles x 1.609344 = km (kilometres)

    Areacircular mils x 0.0005067 = mm2

    (square millimetres)

    sq. in x 645.16 = mm2

    sq. ft. x 0.092903 = m2

    (square metres)sq. yd. x 0.836127 = m2

    sp. mi. x 2.58999 = km2

    (square kilometres)

    Volumecu. in. x 16.387 = cm3

    (cubic centimetres)cu. ft. x 0.028317 = m3

    (cubic metres)gallons x 4.54609 = L (litres)U.S. gal. x 3.7854 = L (litres)

    SI Prefixes

    Multiplying factor Prefix Symbol

    1 000 000 000 000 =1012 tera T1 000 000 000 =109 giga G

    1 000 000 =106 mega M1 000 =103 kilo k

    100 =102 hecto h

    10 = 101 deca da0.1 =10-1 deci d

    0.01 =10-2 centi c0.001 =10-3 milli m

    0.000 001 =10-6 micro 0.000 000 001 =10-9 nano n

    0.000 000 000 001 =10-12 pico p0.000 000 000 000 001 =10-15 femto f

    0.000 000 000 000 000 001 =10-18 atto a

    Mass

    pounds x 0.45359 = kg (kilograms)tons (2000 lb) x 0.907185 = t

    (metric tonnes)

    Mass per unit lengthlb/ 1000 ft. x 1.48816 = kg/ km

    (kilograms per kilometre)lb/ mi x 0.28185 = kg/ kmmm2x 8.89 = kg/ km (for copper)

    mm2

    x 2.70 = kg/ km (for aluminum)mm2x 7.83 = kg/ km (for steel)

    Force or Tension

    pounds (force) x 4.448 = N(newtons)

    mass (in kg) x 9.8066 = N(weight at or near sea level)

    Force per unit area(stress, pressure, tensile strength, etc.)lbf/ in2= (psi) x 6.895 = kPa

    (kilopascals)

    lbf/ in2

    x 0.006895 = MPa(megapascals)

    N/ mm2= MPa

    NoteKilopascals are used generally for fluidpressures. Megapascals are usedgenerally for stresses in materials, i.e.for tensile stress, modulus of elasticity,etc.

    Temperature Conversion

    F to C: C = (F minus 32) x 5/ 9C to F: F = (C x 9/5) plus 32

    NOTICE

    Alcatel Canada Wire Inc. hasendeavored to ensure theaccuracy of the data in thispublication, however we cannotbe liable for the consequences oferrors or omissions. All data issubject to change without notice.The installer and/or user assumesall liability for the consequences ofthe installation and/ or use of anyof our products in contravention ofany applicable law, regulation orcode.

    Wire and Cable Metric Calculations