Upload
a-sharma
View
5
Download
0
Embed Size (px)
Citation preview
3. 132/11 kv Power Transformer Protection
3.1 Differntial Protection relay P642
3.1.1 Data
a Transformer Data
Rated Voltage 132 11
Rated Power @ 132 KV 20 MVA
Rated Power @ 11KV 20 MVA
Vector Group YNd11
Short Circuit Impedance
Normal Tapping 9.48 ℅
Min Tapping
Max. Tapping
b Relay Data
Relay type P642
Rated Current 1/5A
c CT data Primary in A Secondary in A
At 132 KV side 100 1
At 11 KV side 1200 1
3.1.2 Relay Configuration
a Configuration Parameters
b Configuration function parameters
Eneblinmg the protection relay
Phase Sequence
Nominal Current CT primary
132 kv, end A 100
11kv, end B 1200
Nominal Current CT primary
132 kv, end a 100
11 kv, end b 1200
c Referance Current
At 132 KV side I Ref A 87 A
At 11 KV side I Ref B 1050 A
d Referance Power
At 132 KV side S Ref A 20MVA
At 11 KV side S Ref B 20MVA
e Maching Factor
Maching Factor 132 Kv Side 1.14
Maching Factor 11Kv Side 1.14
3.1.3 Differntial Protection Setting Calculation
a The differntial starting thershold (Idiff>)
The transformer has voltage range of voltage regulation per tap as 1%
(Idiff>) 0.2xIref
b The differntial thershold (Idiff>>)
(Idiff>>) 7xIref
The differntial starting thershold (Idiff>) is set between 0.2xIntrafo and 0.4x intrafo taking in to account the CT accuracy and
the voltage difference due to the voltage regulation.
The threshold (Idiff>>) is used to disable the inrush and overflux restraint functions. It must be set above the magnetizing
current of the transformer.Assuming the inrush current is less than 6 times the rated current in peak value:-
3.2 Back up Overcurrent Protection relay P14DB
3.2.1 132 KV side Back up Overcurrent Protection relay P14DB
3.2.1.1 Data
a Relay data
Relay type P14DB
Rated current 1/5A
Rated Voltage 110-250 V DC
b Configuration Set up
Overcurrent Enabled
Earth Fault 1 Enabled
CB fail Enabled
c CT raito
CT Primary 100
CT secondary 1
E/F CT Primary 100
E/F CT secondary 1
4.1.1.2 Back Up Over current Protection Setting Calculation 132KV Side
a The low thershold (I>)
The low thrershold (I>) is set to protect the Autotransformer against overloading.
The thersholod is set to 120 % of the rated primary current.
Rated primary current of transformer 87 A
Overloading factor 1.2
CT raito 100
The low thrershold (I>) is
(I>) 1.05
Selection of time characterstic IEC E Inverse (IEC Extremely Inverse)
The TMS is set to ensure a tripping time of 40 sec for 2xIref
For IEC E inverse k=80 , L=0 , α=2
TMS 0.56282
For a better safety the TMS shall be 0.33 thus the tripping time will be 35.8 sec
b The High thershold (I>>)
Selection of time characterstic DT
The Maximum three phase fault current at Kanoria seen by 132 kv side is :-
I 3ph 2353 A
The High thershold (I>>) is set 1.2 times If 2823.14
(I>>) 28.2
(t>>) 600 msec
4.1.1.3 Back Up Over current Protection Setting Calculation 11KV Side
a The low thershold (I>)
The low thrershold (I>) is set to protect the transformer against overloading.
The thersholod is set to 120 % of the rated primary current.
Rated primary current of transformer 1050 A
Overloading factor 1.2
CT raito 1200
The low thrershold (I>) is
(I>) 1.05
Selection of time characterstic IEC E Inverse (IEC Extremely Inverse)
The TMS is set to ensure a tripping time of 35 sec for 2xIref
For IEC E inverse k=80 , L=0 , α=2
TMS 0.49246
For a better safety the TMS shall be 0.5 thus the tripping time will be 30 sec
b The High thershold (I>>)
Selection of time characterstic DT
The Maximum three phase fault current at Kanoria seen by 11 kv side is :-
I 3ph 28231 A
The High thershold (I>>) 28231.43
(I>>) 23.5
(t>>) 400 msec