Upload
others
View
9
Download
0
Embed Size (px)
Citation preview
Subcategory :
Phase :
Frequency:
kVA:
K rating:
Pri. configuration:
Sec. configuration:
Reverse connectable:
Winding material:
Electrostatic shielded:
Temperature rise:
Insulation system:
Enclosure rating:
Enclosure material:
Construction style:
Mounting type:
Connection type:
Cooling:
Agency approvals:
Sound level:
Warranty:
Corporate Headquarters: TEMCo – Tower Electric Motor Company 41474 Christy Street Fremont, CA 94538 Inside USA (877) 474-8209 International (510) 490-2187 Fax (510) 490-1507
T4T15E to T4J1000E
Isolation
Three
60 Hz
15 to 1000 kVA
1
Delta
Wye
Aluminum
No
150 Deg C
220 Deg C
NEMA 1
Steel
Enclosed - Ventilated Core & Coil
Floor
Lugs/bolt down terminals
Air/dry
UL and cUL Listed, CSA Approved.
Less than 45 dB(10 to 50 kva)Less than 50 dB (51 to 150 kva)Less than 55 dB (151 to 300 kva)Less than 60 dB (301 to 500 kva)Less than 62 dB (501 to 700 kva)Less than 64 dB (701 to 1000 kVA)
12 years
Federal Pacific General Purpose Transformer
www.temcoindustrialpower.com
Yes
480 Primary - 208Y/120 Secondary
TM
Corporate Headquarters: TEMCo – Tower Electric Motor Company 41474 Christy Street Fremont, CA 94538 International (510) 490-2187 Fax (510) 490-1507
www.temcoindustrialpower.comInside USA (877) 474-8209
Dimensions (in inches)
Federal Pacific General Purpose Transformer
TM
T4T15E to T4J1000E
480 Primary - 208Y/120 Secondary
Part # kVA Height Width Depth Weight (lbs) Wiring DiagramT4T15E 15 29 17.125 19.375 210 22T4T30E 30 34 22.375 19.875 370 22T4T45E 45 34 22.375 19.875 400 22T4T75E 75 37 26 19.875 575 22T4T112E 112.5 43 28.5 23.5 760 22T4T150E 150 44.5 39 23 960 22AT4T225E 225 51 42.125 26 1320 22AT4T300E 300 63 46.5 30.875 1630 22AT4T500E 500 72.75 53.375 36.875 2335 22AT4T750E 750 76.75 53.375 44.375 3280 22AT4J1000E 1000 80 61 44.375 4450 22B
Corporate Headquarters: TEMCo – Tower Electric Motor Company 41474 Christy Street Fremont, CA 94538 International (510) 490-2187 Fax (510) 490-1507
www.temcoindustrialpower.comInside USA (877) 474-8209
Federal Pacific General Purpose Transformer
TM
T4T15E to T4J1000E
480 Primary - 208Y/120 Secondary
Diagram #22
VOLTS CONNECTIONS LINE LEADS504 1 TO 2 H1, H2, H3492 1TO 3 H1, H2, H3480 1 TO 4 H1, H2, H3468 1 TO 5 H1, H2, H3456 1 TO 6 H1, H2, H3444 1 TO 7 H1, H2, H3432 1 TO 8 H1, H2, H3
208Y/120 X0, X1, X2, X3
PRIMARYVOLTAGE
SECONDARYVOLTAGE TAPS
480 ∆ 208Y/120 2-2 1/2% FCAN &4-2 1/2% FCBN
Diagram #22A - 22B
(A)VOLTS CONNECTIONS LINE LEADS
504 2 TO 3 H1, H2, H3492 2 TO 5 H1, H2, H3480 3 TO 4 H1, H2, H3468 4 TO 5 H1, H2, H3456 5 TO 6 H1, H2, H3444 4 TO 7 H1, H2, H3432 6 TO 7 H1, H2, H3
208Y/120 X0, X1, X2, X3(B)
VOLTS CONNECTIONS LINE LEADS509 2 TO 3 H1, H2, H3494 2 TO 5 H1, H2, H3480 3 TO 4 H1, H2, H3466 4 TO 5 H1, H2, H3451 5 TO 6 H1, H2, H3
208Y/120 X0, X1, X2, X3
PRIMARYVOLTAGE
SECONDARYVOLTAGE TAPS
480 ∆ 208Y/120 (A) 2-2 1/2 % FCAN &4-2 1/2% FCBN
(B) 2-3% FCAN &2-3% FCBN