Upload
hanga
View
217
Download
0
Embed Size (px)
Citation preview
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 1 of 77Part 4 – Schedules of Technical Information
4. SCHEDULES OF TECHNICAL INFORMATION
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 2 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
1. GENERAL
1.1. Standards IEC IEC 62271-100, 62271-102, 62271-1,
62155, 60044-1, 60044-5, 60383,
60815
1.2. Rated voltage kV 245
1.3. System Voltage kV 220
1.4. Rated frequency Hz 50
1.5. Rated lightning impulse withstand voltage (at altitude <1000m)
- Phase to earth KVp 1050- Across the isolating distance kVp 1200
1.6. Rated power frequency withstand voltage (at altitude <1000m)- Phase to earth kV 460- Across the isolating distance kV 530
1.7. Rated short-time withstand current (1 s) kA 31.5
1.8. Rated peak withstand current kA 80
1.9. Rated Current - at 40 oC A 2000- at 50 oC (Contractor to confirm by calculation) A
1.10. Material of HV conductor
1.11. Material of contacts
1.12. Minimum factors of safety for switchgear- Busbars or other connections based on elastic
limit2.5
- Complete insulators based on electro-mechanical test
2.5
- Insulator metal fittings based on elastic limit 2.5- Steel structures based on elastic limit of
tension members and on cripping loads of compression members
2.5
- Foundations for structures against overturning or uprooting under maximum simultaneous working loadings
2.5
1.13. Creepage distance (based on Um) mm/kV 311.14. Seismic factor
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 3 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2. CIRCUIT BREAKER
2.1. Manufacturer & Place of manufacturing
2.2. Type designation
2.3. Type SF6
2.4. Standards 62271-1, IEC 62271-100, 62271-101,
62271-110, 60376, 60480
2.5. Rated operating sequence O -0.3 sec- CO -3 min - CO
2.6. Auto reclosing O -0.3 sec- CO -3 min - CO
2.7. Rated making current KAp 80
2.8 Rated breaking current kA 31.5Rated breaking current (asymmetrical) KA To IEC 62271-100
- %dc %dc2.9. Rated breaking current under out-of-phase
conditionskA 10
2.10. First phase to clear factor 1.5
2.11 Transient Recovery Voltages TRVs To IEC 62271-100
2.12. Rated capacitive breaking current To IEC 62271-100Rated line charging breaking current A 125Rated cable charging breaking current A 250Rated Single/Back to Back Capacitor bank breaking current
A 400
2.13. Rated small inductive/reactor breaking currents of: To IEC 62271-110- small inductive A 10, 20, 50 and 100- reactor A 306
2.14. Maximum overvoltage factor on any switching duty pu 2.3
2.15. Maximum overvoltage factor when interrupting rated line/cable/capacitor bank charging currents
pu 2.3
2.16. Maximum overvoltage factor when switching small inductive/reactor currents
pu 2.3
2.17. Maximum total break time (trip initiation to final arc extinction)
ms 60
2.18. Opening time (trip initiation to contact separation)- Without current ms- With 100% rated breaking current ms
2.19. Maximum time interval between opening of first ms 3
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 4 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
and last phase of three phase circuit breakers
2.20. Maximum time interval between opening of interrupters of one phase
- - -
2.21. Closing time from energisation of close coil to latching of circuit breaker in fully closed position
ms
2.22. Making time (energisation of close coil to contact touch)- Without current ms- 100% making current ms
2.23. Maximum time interval between closure of first and last phase of three phase circuit breaker
ms 3
2.24. Maximum time interval between closure of interrupters of one phase
- - -
2.25. Minimum time from extinction of main arc to contact make during auto-reclosing duty
ms
2.26. Mechanical life of circuit breaker and mechanism in No. of operations
10,000
2.27. Electrical contact life in number of operations at:- Rated current -2000 A- Fault current - 31.5 kA 15 to 20- Cumulative ampere rating
2.28. Number of current interrupting break units in series per phase
One
2.29. Type of operating mechanism Motor charged spring operated
2.30. Type of power device (motor charged)- For closing Spring or hydraulic- For opening Spring or hydraulic
2.31. Hand operating facility Yes
2.32. Manual spring release Yes
2.33. Mechanical on/off indicator Yes
2.34. Mechanical spring charge / discharge indication Yes
2.35. Charging time s
2.36. Number of trip coils 2
2.37. Number of close coils 1
2.38. Nominal control and operating voltage V 110 DC
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 5 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.39. Nominal heater voltage V 240 AC
2.40. Rated power of trip coil W
2.41. Rated power of close coil W
2.42. Rated motor power W
2.43. Total load of heaters for circuit breaker W
2.44. Mass of circuit breaker complete (three pole) kg
2.45. Mass of single phase circuit breaker - - -
2.46 Emergency Trip Facility Yes
3. ISOLATORS
3.1. Manufacturer & Place of Manufacturing
3.2. Type designation
3.3. Type of operating mechanism Motor
3.4. Standards IEC 62271-102,IEC 62271-1
3.5. Maximum capacitive current that can be interrupted by the isolator
A
3.6. Total time from initiation of opening operation to isolator in fully open position
s
3.7 Time from contact separation to extinct of capacitive arc
s
3.8 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage
s
3.9 Hand operating facility Yes
3.10 Locking arrangement in on/off position Yes
3.11 Nominal control and operating voltage V 110 DC
3.12 Automatic isolation of control supplies when lock off
Yes
3.13. Accessibility to operating mechanism from ground level
Yes
3.14. Nominal heater voltage V 240 AC
3.15. Rated power of operation coil W
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 6 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
3.16. Rated motor power W
3.17. Total load of heaters for isolator W
3.18. Total mass of three phase isolator complete kg
3.19 Mass of single phase isolator kg
3.20. Contact type
3.21. Type of interlocking
4. EARTHING SWITCH
4.1. Manufacturer & place of manufacturing
4.2. Type designation
4.3. Type of operating mechanism Motor
4.4. Standards IEC 62271-102, 62271-1
4.5. Hand operating facility Yes
4.6. Locking arrangement in on/off position Yes
4.7. Nominal control and operating voltage V 110 DC
4.8. Automatic isolation of control supplies when lock off
Yes
4.9. Accessibility to operating mechanism from ground level
Yes
4.10. Nominal heater voltage V 240 AC
4.11. Total load of heaters for earthing switch W
4.22. Total mass of earthing switch complete kg
5. CURRENT TRANSFORMER
5.1. Manufacturer & Place of manufacturing
5.2. Type Post
5.3. Standards IEC 62271-1, 60044-1
5.4. Rated continuous thermal current at 40oC Rated extended primary current
Note: All Cl PX CTs shall be ISN 1.2 A
5.5. Current transformers Refer to Tender Drawings
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 7 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Number of cores- Rated extended primary current 120%- Ratio (TR – turns ratio)
I core A II core A III core A IV core A
- Class I core II core III core IV core
- Knee point voltage (Ek) I core V II core V III core V IV core V
- Exciting current (IE) at Ek
I core mA II core mA III core mA IV core mA
- Rated output (burden to be 25-100% rated burden) I core VA II core VA III core VA IV core VA
Total mass of single phase current transformer complete
kg
6. CAPACITIVE VOLTAGE TRANSFORMERS
6.1. Manufacturer & Place of manufacturing
6.2. Type Capacitive6.3. Standards IEC 60044-5
6.4. Maximum permissible partial discharge levelUm
pC 10
6.5. Maximum permissible partial discharge level1.2Um /3
pC 5
6.6. Method of suppressing ferroresonance phenomena
6.7. Voltage transformer Refer to Tender Drawings
- Number of secondaries- Rated transformation ratio kV- Rated accuracy class
I secondary II secondary
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 8 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Rated output (burden to be 25-100% rated burden) I secondary VA II secondary VA
- Mass of single phase voltage transformer kg
7. BUSBARS AND CONNECTIONS
7.1 Manufacturer
7.2 Type (flexible or tubular)
7.3 Material
7.4 Short-circuit current rating / duration KA/s
7.5 Normal current rating- at 40oC- at 50oC
AA
7.6 Maximum continuous current rating A
7.7 Flexible conductors- stranding- nominal cross-sectional area- outer diameter- no. of conductors per bundle- spacing between conductors
mm2
mm
mm
7.8 Tubular conductors- nominal cross-sectional area- outer diameter- inner diameter
mm2
mmmm
7.9 Maximum stress at surface of flexible conductor kV/mm
7.10 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz
µV
8 POST TYPE INSULATORS
8.1 Manufacturer
8.2 Type designation
8.3 Insulator material
8.4 Number of units in complete post insulator
8.5 Length of each unit mm
8.6 Mass of complete post insulator kg
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 9 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
8.7 Maximum cantilever working load (complete post insulator)
N
8.8 Minimum cantilever breaking load, upright (complete post insulator)
N
8.9 Power frequency withstand voltage dry: wet kV
8.10 Basic insulation level kVp
8.11 Minimum dry/wet switching surge withstand level kVp
8.12 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz
µv
9 TENSION AND SUSPENSION INSULATORS
9.1 Manufacturer
9.2 Type designation
9.3 Insulator material
9.4 Number of units in string mm
9.5 Greatest diameter of units mm
9.6 Distance between centres of units mm
9.7 Length of string, overall mm
9.8 Mass of string complete with all fittings kg
9.9 Maximum working load N
9.10 Power frequency withstand voltage of complete string
kV
9.11 Basic insulation level of complete string kVp
9.12 Minimum wet switching surge withstand level of complete string
kVp
9.13 Radio influence voltage measured at 1.1 times Us/3 at 1 MHz
µv
10. Manufacturer quality system in accordance to ISO 9000, 9001 and 9004
Yes
10.1 Date of issue Latest
10.2 Validity Valid Certificates -Yes
11. Type test certificate to be issued by Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 10 of 77Part 4 – Schedules of Technical Information
220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
independent laboratory or independently witnessed type test certificate to be submitted
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
LONGITUDINAL DIFFERENTIAL PROTECTION AND BACK-UP DISTANCE (87L/21)
Manufacturer
Type reference
Relay design (microprocessor based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 77150
Input frequency range (50Hz nominal) Hz 47.552.5
Differential protection requirements
Phase segregated protection Yes
Ratio and Vector correction for CTs Yes
Adjustable biased differential protection characteristic Yes
Sensitivity:
- For phase faults
- For earth faults
Operating time ms <30
Distance protection requirements
3 zone ph-ph & ph-E Yes
Phase fault & Earth fault characteristic shapes (Mho, Quad)
Operating time <30ms
SOTF Yes
Power swing blocking (depending on relaying point in the power system)
Yes
Voltage transformer supervision Yes
Time delays for all zones Yes
Zone enable/disable for all zones Yes
Other requirements
Thermal overload, 49 – (requirement if cable over-temperature unsuitable for tripping)
No
Circuit breaker failure. 50BF- (dependent on application) Yes
Event recording function Yes
Disturbance recording function Yes
Fault locator function Yes
Integral operator interface for local interrogation Yes
Programmable scheme logic Yes
User-friendly HMI, Windows based software for relay setting, relay configuration and event, disturbance and fault record management.
Yes
Tripping contacts ratingCarry continuous 5A
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 11 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedMake 30A maximum for 0.2sBreak dc 50W resistive
25W inductive(L/R40ms)
Yes
Self checking facility Yes
Integral intertrip send and receive, with external input interface Yes
Communications
Protection
Direct optical fibre 1300nm single mode Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
others
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 12 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedTest method A, 27MHz through 500MHz
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient Disturbance
IEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
DISTANCE PROTECTION (21)
Manufacturer
Type reference
Relay design (microprocessor based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 77150
Input frequency range (50Hz nominal) Hz 47.552.5
Distance protection requirements
3 zone ph-ph & ph-E Yes
Phase fault & Earth fault characteristic shapes (Mho, Quad)
Operating time <30ms
SOTF Yes
Power swing blocking (depending on relaying point in the power system)
Yes
Voltage transformer supervision Yes
Time delays for all zones Yes
Zone enable/disable for all zone Yes
Teleprotection modes PUR/POR/Block Yes
DEF plain & Blocking modes Blk
Z1 min and max operating time (mid zone) ms <30
Other requirements
Thermal overload, (49) No
Circuit breaker failure. 50BF- (dependent on application) Yes
Event recording function Yes
Disturbance recording function Yes
Fault locator function Yes
Integral operator interface for local interrogation Yes
Programmable scheme logic Yes
User-friendly HMI, Windows based software for relay setting, relay configuration and event, disturbance and fault record management.
Yes
Tripping contacts ratingCarry continuous 5AMake 30A maximum for 0.2sBreak dc 50W resistive
25W inductive(L/R40ms)
Yes
Self checking facility Yes
Integral intertrip send and receive, with external input interface Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 13 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedIntertrip send and receive operate time
Communications
Protection
Direct optical fibre 1300nm single mode
Others (please list)
Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
others
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 14 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedElectromagnetic Emissions
IEC 60255-25 Yes
Type test certificate provided Yes
LOW IMPEDANCE BUSBAR PROTECTION INCLUDING BREAKER FAILURE PROTECTION
Manufacturer
Type reference
Relay design (static, microprocessor-based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 77150
Input frequency range (50Hz nominal) Hz 47.552.5
State principle of operation, i.e.,low impedance Low Z
Integral check zone feature (state principle of operation) Yes
Distributed Bay Modules and Central Unit (Y/N) Yes
Maximum number of Bays
Isolator replica
CT saturation detector and stabilisation
Integral CT supervision
CT matching functions
Phase segregated protection
Sensitivity
1. Phase faults A sec’y
2. Earth faults A sec’y
Operating time at 5 x fault setting ms 30
Two stage Circuit Breaker Failure Adjustable current setting Adjustable time delays per stage
Yes
Other requirements
User-friendly HMI, Windows based software for relay setting, relay configuration and event, disturbance and fault record management.
Yes
Tripping contacts ratingCarry continuous 5AMake 30A maximum for 0.2sBreak dc 50W resistive
25W inductive (L/R40ms)
Event recording function Yes
Disturbance recording function Yes
Self monitoring and alarm facility
Communications
Bay to central Module communication f.o.
Integral operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 15 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered others
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient Disturbance
IEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
MULTI-FUNCTIONAL OVERCURRENT & EARTH FAULT PROTECTION {50/51/50N/51N)
Manufacturer
Type reference
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 16 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedRelay design (static, microprocessor-based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 77150
Input frequency range (50Hz nominal) Hz 47.552.5
Number of phase CT inputs
Number of earth fault CT inputs
Standard, Very and Extreme Inverse and definite time characteristics curves conforming to IEC 60255
Yes
Number of inverse overcurrent functions (per phase)
Number of high set overcurrent functions (per phase)
Number of low set overcurrent functions (per phase)
Number of inverse earth fault functions
Number of high set earth fault functions
Number of low set earth fault functions
Number of group settings
Earth fault element suitable of high impedance REF (with external resistor)
Yes
Operating time at 5 x setting when configured for REF ms 30
Suitable for Blocked Overcurrent busbar protection scheme Yes
Other functions provided
Thermal overload 49 Y/N
Directional OC&EF Y/N
Number of output relays
Rated for tripping
Rated for control and alarm
Integral metering functions Yes
Opto-isolator inputs Yes
Programmable scheme logic Yes
Event and Fault recording functions
Self-monitoring facility
User-friendly HMI, Windows based software for relay setting, relay configuration and event, disturbance and fault record management.
Yes
Tripping contacts rating
Carry continuous 5A
Make 30A maximum for 0.2s
Break dc 50W resistive
25W inductive (L/R40ms)
Communications
Integral operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 17 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offeredothers
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient Disturbance
IEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
MULTI-FUNCTIONAL DIRECTIONAL OVERCURRENT & EARTH FAULT PROTECTION {67/67N)
Manufacturer
Type reference
Relay design (static, microprocessor-based, numerical) Numerical
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 18 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedAuxiliary voltage range (Vn = 110Vdc) Vdc 77150
Input frequency range (50Hz nominal) Hz 47.552.5
Number of phase CT inputs
Number of earth fault CT inputs
Three phase VT input Yes
Method of determining zero sequence voltage
Broken delta VT input (Y/N)
Derived mathematically (Y/N)
Standard, Very and Extreme Inverse and definite time characteristics curves conforming to IEC 60255
Yes
Number of inverse DOC overcurrent functions (per phase)
Number of high set DOC functions (per phase)
Number of low set DOC functions (per phase)
Number of inverse DEF functions
Number of high set DEF functions
Number of low set DEF functions
Number of group settings
Other functions provided
Non-directional overcurrrent50/51 (Y/N)
Non-directional earth fault 50N/51N (Y/N)
Thermal overload 49 (Y/N)
Suitable for Blocked Overcurrent busbar protection scheme
Earth fault element suitable of high impedance REF (with external resistor)
Number of output relays
Rated for tripping
Rated for control and alarm
Integral metering functions Yes
Opto-isolator inputs Yes
Programmable scheme logic Yes
Event and Fault recording functions
Self-monitoring facility
User-friendly HMI, Windows based software for relay setting, relay configuration and event, disturbance and fault record management.
Yes
Tripping contacts rating
Carry continuous 5A
Make 30A maximum for 0.2s
Break dc 50W resistive
25W inductive (L/R40ms)
Communications
Integral operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 19 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedPhysical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
others
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient Disturbance
IEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
CONNECTIONS DIFFERENTIAL PROTECTION (87C)
Manufacturer
Type reference
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 20 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Relay design (static, microprocessor-based, numerical, E-M) Numerical
Estimated minimum fault setting (% of CT rating) %
Operating time at 5 x setting ms
State principle of operation,
H = high impedance
L = low impedance
Metrosils provided
Self monitoring (excluding EM) Yes
User-friendly HMI, Windows based software for relay setting, relay configuration and event, disturbance and fault record management.
Tripping contacts rating
Carry continuous 5A
Make 30A maximum for 0.2s
Break dc 50W resistive
25W inductive (L/R40ms)
Communications (numerical relays)
Integral operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
others
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 21 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient Disturbance
IEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
SHUNT REACTOR DIFFERENTIAL PROTECTION 87R
Manufacturer
Type reference
Relay design (microprocessor based, numerical) numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 77150
Input frequency range (50Hz nominal) Hz 47.552.5
Biased Differential function
Operation time at 5 times setting ms <25
Adjustable bias characteristics Yes
Differential current stage Id >> Yes
Magnetisation inrush restraint Yes
“5th” Harmonic inrush restraint Yes
Maximum through fault current for which relay remains stable (multiple of rating)CT ratio and vector group compensation
Other requirements
Integral operator interface for local interrogation Yes
Programmable scheme logic Yes
User-friendly HMI, Windows based software for relay setting, relay configuration and event, disturbance and fault record management.
Yes
Tripping contacts ratingCarry continuous 5AMake 30A maximum for 0.2sBreak dc 50W resistive
25W inductive (L/R40ms)
Event recording function Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 22 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedDisturbance recording function Yes
Fault recording function Yes
Self monitoring and alarm facility
Integral intertrip send and receive
Communications
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
others
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient Disturbance
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 23 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedIEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
TRIP CIRCUIT SUPERVISION
Manufacturer
Type reference
Relay design (Electro-Mech, static, numerical)
Auxiliary voltage range (Vn = 110Vdc) Vdc 77150
Operating time ms
Supervision of the whole trip circuit with CB open and closed. Yes
Relay operated indicator Yes
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Electromagnetic Emissions
IEC 60255-25 Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 24 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required OfferedFast Transient Disturbance
IEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
MULTI-CONTACT TRIPPING RELAYS
Manufacturer
Type reference
Operating time ms <12
Auxiliary voltage range (Vn = 110Vdc) Vdc 77150
Is relay mechanically latched or self resetting
Method used to reset latched relay (hand or electrical)
Burden at rated voltage
Minimum voltage at which reliable operation occurs
Tripping contacts rating
Carry continuous 5A
Make 30A maximum for 0.2s
Break dc 50W resistive
25W inductive (L/R40ms)
Relay operated indicator type
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 25 of 77Part 4 – Schedules of Technical Information
PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered1MHz Burst disturbance test,
IEC 60255-22-1 severity class III Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field Disturbance
IEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHz
Yes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient Disturbance
IEC 60255-22-4 severity level IV Yes
Type test certificate provided Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 26 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
1.0.0 Substation Control System Yes
2.1.0 Substation Computer
2.1.1 Manufacturer
2.1.2 Model
2.1.3 Processor
2.1.4 Type
2.1.5 Word length Bits
2.1.6 Clock speed (minimum) MHz
2.1.7 Memory size
2.1.8 Supplied (minimum) Mb
2.1.9 Supportable/expandable Gb
2.1.10 Hard disk size
2.1.11 Supplied (minimum) Gb
2.1.12 Supportable/expandable Gb
2.1.13 Optical Storage
2.1.14 Operating system
2.1.15 Software supplied
2.1.16 Operating temperature range °C
2.1.17 Maximum relative humidity %
2.1.18 Nominal voltage V ac
2.1.19 Operating frequency Hz
2.1.20 Starting current A
2.1.21 Power requirement W
2.1.22 Mean time between failure h
2.1.23 Mean time to repair h
2.2.0 Gateway
2.2.1 Manufacturer
2.2.2 Model
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 27 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.2.3 Processor
2.2.4 Type
2.2.5 Word length Bits
2.2.6 Clock speed (minimum) MHz
2.2.7 Memory size
2.2.8 Supplied (minimum) Mb
2.2.9 Supportable/expandable Gb
2.2.10 Hard disk size
2.2.11 Supplied (minimum) Gb
2.2.12 Supportable/expandable Gb
2.2.13 Communication Protocols To Control Centre(s)
2.2.14 RCC Main IEC 60870-5-101
2.2.15 RCC Alt IEC 60870-5-101
2.2.16 RCC TCP/IP Intranet
2.2.17 RCC IEC 60870-5-104
2.2.18 Communication Protocols in Substation
2.2.19 RCC IEC 61850
2.2.20 List other operating Protocols
2.2.21 Data Communications Interface
2.2.22 V.35 interface at 64Kb/s
2.2.23 X.21 / V.11 interface at 64Kb/s
2.2.24 Operating system
2.2.25 Operating temperature range °C
2.2.26 Maximum relative humidity %
2.2.27 Nominal voltage V dc
2.2.28 Operating frequency Hz
2.2.29 Starting current A
2.2.30 Power requirement W
2.2.31 Mean time between failure h
2.2.32 Mean time to repair h
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 28 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.3.0 Operator Workstations / HMI
2.3.1 Manufacturer
2.3.2 Model
2.3.3 Literature reference for principle of operation
2.3.4 Processor
2.3.5 Type
2.3.6 Word length Bits
2.3.7 Clock speed (minimun) MHz
2.3.8 Memory size
2.3.9 Supplied (minimum) Mb
2.3.10 Supportable/expandable Gb
2.3.11 Hard disk size
2.3.12 Supplied (minimum) Gb
2.3.13 Supportable/expandable Gb
2.3.14 Optical Storage
2.3.15 Pointer Device
2.3.16 Operating system
2.3.17 Operator interface screens
2.3.18 Operating temperature range °C
2.3.19 Maximum relative humidity %
2.3.20 Nominal voltage V ac
2.3.21 Operating frequency Hz
2.3.22 Starting current A
2.3.23 Power requirement W
2.3.24 Mean time between failure h
2.3.25 Mean time to repair h
2.3.26 Operator Desk Yes
2.3.27 Manufacturer Yes
2.3.28 Type of construction
2.3.29 Finish and material of working surfaces
2.3.30 Method of mounting VDUs
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 29 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.3.31 Number
2.3.32 Operator Chairs
2.3.33 Manufacturer
2.3.34 Type of construction
2.3.35 Type of upholstery
2.3.36 Number
2.4.0 Colour Visual Display Units (VDUs) Yes
2.4.1 Manufacturer Yes
2.4.2 Model Yes
2.4.3 Literature reference for principle of operation
2.4.4 Screen size across diagonal mm
2.4.5 Usable display area mm
2.4.6 Resolution (minimum) pixels
2.4.7 Dot pitch mm
2.4.8 Operating temperature range °C
2.4.9 Operating relative humidity range %
2.4.10 Nominal voltage V ac
2.4.11 Operating frequency Hz
2.4.12 Starting current A
2.4.13 Power requirement W
2.4.14 Approximate lifetime of monitor under continuous use h
2.4.15 Mean time between failure h
2.4.16 Mean time to repair h
2.5.0 Substation Local Area Network (LAN)
2.5.1 Architecture and Technology
2.5.2 Literature reference for principle of operation
2.5.3 Transmission medium (e.g. optical fibre) and physical specification
2.5.4 Protocols
2.5.5 IEC 60870-5-101
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 30 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.5.6 IEC 60870-5-104
2.5.7 IEC 61850
2.5.8 List all other protocols
2.5.9 Data transmission rate(s) Mbps
2.5.10Physical arrangement - Identify all main elements in the supply including hubs, concentrators, bridges, routers, gateways switches etc. and the number of each
2.5.11 For each element of the LAN indicate the
2.5.12 No and type of ports
2.5.13 % of spare for each type of port
2.5.14 Management software package, functions and facilities, and hardware platform
2.5.15 % Loading under various system activity scenarios including
2.5.16 normal loading for performance testing %
2.5.17 high loading for performance testing %
2.5.18 system power up %
2.5.19 main server fail-over and database resynchronisation
2.5.20 Overall availability %
2.6.0 Individual Elements
2.6.1 For each element of the LAN equipment provide the following information
2.6.2 Manufacturer
2.6.3 Type
2.6.4 Nominal voltage
2.6.5 Power requirements V ac
2.6.6 Range of ambient temp. and max relative humidity for continuous reliable operation
W
2.6.7 Mean time between failures oC
2.6.8 Mean time to repair %RH
2.7.0 Printers
2.7.1 Logging Printer
2.7.2 Manufacturer
2.7.3 Model
2.7.4 Literature reference for principle of operation
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 31 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.7.5 Number
2.7.6 Mounting arrangement
2.7.7 Method of printing (e.g. ink jet)
2.7.8 Print speed ppm
2.7.9 Paper feed mechanism
2.7.10 Number of columns (minimum)
2.7.11 Operating temperature range °C
2.7.12 Maximum relative humidity %
2.7.13 Nominal voltage V ac
2.7.14 Operating frequency Hz
2.7.15 Power requirement W
2.7.16 Max noise level at 1 m dB(A)
2.7.17 Mean time between failure h
2.7.18 Mean time to repair h
2.7.19 Colour Printers
2.7.20 Manufacturer
2.7.21 Model
2.7.22 Literature reference for principle of operation
2.7.23 Number
2.7.24 Mounting arrangement
2.7.25 Print speed (minimum) ppm
2.7.26 Technology
2.7.27 Resolution dpi
2.7.28 Paper size
2.7.29 Sheet feed paper tray capacity Sheets
2.7.30 Internal memory (minimum) Mb
2.7.31 Operating temperature range °C
2.7.32 Maximum relative humidity %
2.7.33 Nominal voltage V ac
2.7.34 Operating frequency Hz
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 32 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.7.35 Power requirement W
2.7.36 Max noise level at 1 m dB(A)
2.7.37 Mean time between failure h
2.7.38 Mean time to repair h
3.0.0 Bay Control unit Hardware
3.1.0 General Yes
3.1.1 Manufacturer Yes
3.1.2 Module designation Yes
3.1.3 Literature reference for principle of operation Yes
3.1.4 Power supply V dc 110
3.1.5Power requirements
W
3.1.6 Maximum Number of expansion modules
3.1.7 Mean-time to repair for each type of RTU H
3.1.8 Mean-time between failure for each type of RTU H
3.1.9 Local LCD Display
3.1.10 Operating temperature range °C 0 – 50
3.1.11 Operating relative humidity range % 100
3.2.0 BCU Enclosure
3.2.1 Manufacturer
3.2.2 Module designation
3.2.3 Literature reference for enclosure
3.2.4 Weight
3.2.5 Dimensions
3.2.6.0 Degree of protection
3.2.6.1 Flush Mounted housing
3.2.6.2 Surface mounted housing
3.3.0 IEC Standards ( Or Equivalent )
3.3.1 EMC Type tests (Provide Class/Level or Severity rating)
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 33 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.3.2 EMC Compliance IEC 60255-22-3
3.3.3 Dielectric withstand test IEC 60255-4/-5
3.3.4 High Voltage impulse test IEC 60255-4/-5
3.3.5 Fast transient disturbance test IEC 61000-4-4
3.3.6 Oscillatory transient IEC 61000-4-12
3.3.7 Radiated immunity test IEC 61000-4-6
3.3.8 Electrostatic discharge test IEC 61000-4-2
3.3.9 Emitted interference test IEC 61000-4-3
3.3.10 Mechanical test Compliance
3.3.11 Vibration test IEC 60255-21-1
3.3.12 Shock test IEC 60255-21-2
3.3.13 Seismic test IEC 60255-21-3
3.3.14 Temperature rise test IEC 60068-2-2
3.4.0 BCU Functions
3.4.1 The monitoring functions include:
3.4.2 Switching status monitoring (breakers)
3.4.3 Indication & alarm status monitoring
3.4.4 Analogue measurements (currents, voltages, etc.)
3.4.5 Resolution of time tagging ms 1
3.4.6.0 The control functions include:
3.4.6.1 Close / open of circuit breakers
3.4.6.2 Close / Open of isolators / disconnectors
3.4.6.3 Transformer Automatic tap change control
3.4.6.4 Breaker Voltage Synchronisation Check Control
3.4.6.5 Bay interlocking facilities
3.4.7.0 The reporting functions include:
3.4.7.1 Sequence of Events recording
3.4.7.2 Post – Mortem Review / Fault waveform capture
3.4.7.3 Tenderers to state memory capacity and functionality of Sequence of events and fault waveform capture
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 34 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.5.0 BCU Configuration
3.5.1 Number of processors
3.5.2 Main processor
3.5.3 Secondary processors
3.5.4 Communication processor (module)
3.5.5 Type of communication between processors
3.5.6.0 LCD Display and selector Buttons on front of BCU Yes
3.5.6.1 Functionality to include
3.5.6.2 Full control of circuit bay
3.5.6.3 Status of bay plant
3.5.6.4 Circuit active line diagram
3.5.6.5 Power system Measurements
3.5.6.6 Display alarms and events
3.6.0 Processing Units
3.6.1 Main CPU
3.6.2 Manufacturer
3.6.3 Module designation
3.6.4 Literature reference for principle of operation
3.6.5 Mean - time between failure h
3.6.6 Power requirements W
3.6.7 Type of processor
3.6.8 Word length bit
3.6.9 Clock speed MHz
3.6.10.0 Kinds of memory used:
3.6.10.1 Type, size and extension capabilities KByte
3.6.10.2 Type, size and extension capabilities Kbytes
3.6.10.3 Type, size and extension capabilities Kbytes
3.7.0 Secondary CPU
3.7.1 Manufacturer
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 35 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.7.2 Module designation
3.7.3 Literature reference for principle of operation
3.7.4 Mean - time between failure h
3.7.5 Power requirements W
3.7.6 Type of processor
3.7.7 Word length bit
3.7.8 Clock speed MHz
3.7.9.0 Kinds of memory used:
3.7.9.1 Type, size and extension capabilities Kbytes
3.7.9.2 Type, size and extension capabilities Kbytes
3.7.9.3 Type, size and extension capabilities Kbytes
3.8.0 Communications
3.8.1 Manufacturer Yes
3.8.2 Module designation
3.8.3 Literature reference for principle of operation
3.8.4 Number of communications channels
3.8.5 Type of processor
3.8.6 Word length
3.8.7 Clock speed bit
3.8.8 Type and size of memory MHz
3.8.9 Line interface to communication channel
3.8.10 Speed of transmission B/s
3.8.11 Number and type of communication ports
3.8.12 Meantime between failure h
3.8.13 Power requirement W
3.8.14.0 Communication Interfaces
3.8.14.1IEC60870-5-101 direct to Control Centre(s)
3.8.14.2 IEC60870-5-103 interface to protection IED
3.8.14.3 IEC61850 interface to substation LAN
3.8.14.4 IEC60870-5-101 for remote downloading of BCU data
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 36 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.8.14.5 List all Protocols available at BCU
3.8.15 Local interface for Laptop Computer
3.8.16.0IED Interface
3.8.16.1 List of manufactures the BCU has interfaced Yes
3.8.16.2 Standard communication protocols available Yes
3.8.16.3 Optional communication protocols available Yes
3.9.0 Power Supply Module
3.9.1 Module designation
3.9.2 Literature reference for principle of operation
3.9.3 Maximum number of modules per processor
3.9.4 Nominal Input voltage VDC
3.9.5 Operating voltage range
3.9.6 Power requirement W
3.9.7 Isolation
3.9.8 Meantime between failure h
3.9.9 Power requirement W
3.10.0 Digital Input Module
3.10.1 Module designation
3.10.2 Literature reference for principle of operation
3.10.3 Maximum number of modules per processor
3.10.4 Input voltage V dc
3.10.5.0 Is contact input type configurable as
3.10.5.1 Status and alarms
3.10.5.2 Sequence of events
3.10.5.3 BCD or parallel inputs
3.10.5.4 Pulse accumulator
3.10.5.5 Or any combination of these
3.10.6.0 Standard number of inputs per module:
3.10.6.1 double position
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 37 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.10.6.2 single position
3.10.7 Type of input circuit isolation
3.10.8 Input galvanic separation
3.10.9 Impulse voltage withstand kV
3.10.10 Scan time ms
3.10.11 Minimal pulse duration ms
3.10.12 Input impedance ohm
3.10.13 Filter time constant ms
3.10.14 Meantime between failure h
3.10.15 Power requirement W
3.11.0 Pulse Counting Module
3.11.1 Is this facility incorporated into the digital input module?
3.11.2 Module designation
3.11.3 Literature reference for principle of operation
3.11.4 Maximum number of modules per processor
3.11.5 Type of counter
3.11.6 Maximum count
3.11.7 Storage and resetting under control of external clock?
3.11.8 Number of inputs per module
3.11.9 Input current mA
3.11.10 Impulse voltage withstand kV
3.11.11 Signal range : pulse widths ms
3.11.12 Meantime between failure h
3.11.13 Power requirement W
3.12.0 Command Output Module
3.12.1 Module designation
3.12.2 Literature reference for principle of operation
3.12.3 Maximum number of modules per processor
3.12.4.0 Contact ratings
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 38 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.12.4.1 Switched voltage V
3.12.4.2 Switched power VA max
3.12.4.3 Switched current A
3.12.4.4 Range of duration of command output S
3.12.5 Number of two position output channels per module
3.12.6 Are outputs activated by select-check-actuate procedure?
3.12.7 Are welded contacts checked prior to command output?
3.12.8 Are the outputs fused and fuse status monitored?
3.12.9 Impulse voltage withstand kV
3.12.10 Meantime between failure h
3.12.11 Power requirement W
3.13.0 Digital Output Module
3.13.1 Module designation
3.13.2 Literature reference for principle of operation
3.13.3 Number of outputs per module
3.13.4 Maximum number of modules per processor
3.13.5 Maximum output current mA
3.13.6 Maximum switched output voltage V
3.13.7 Impulse voltage withstand kV
3.13.8 Type of protection against back EMF kV
3.13.9 Command duration adjustable in the range s
3.13.10 Meantime between failure h
3.13.11 Power requirement W
3.14.0 Analogue to digital conversion module
3.14.1 Module designation
3.14.2 Literature reference for principle of operation
3.14.3 Number of inputs per module
3.14.4 Maximum number of modules per processor
3.14.5 Resolution bits
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 39 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.14.6 Accuracy %
3.14.7 Common mode noise rejection dB
3.14.8 Normal mode noise rejection dB
3.14.9 Conversion time ms
3.14.10 Scanning time (per channel) ms
3.14.11 Meantime between failures h
3.14.12 Power requirement W
3.15.0 Analogue Input Module
3.15.1 Module designation
3.15.2 Literature reference for principle of operation
3.15.3 Maximum number of modules per processor
3.15.4 Scanning resolution bits
3.15.5 Accuracy %
3.15.6 How are overflow and conversion failures dealt with?
3.15.7 Conversion time
3.15.8 Input filter attenuation at 50 Hz dB
3.15.9 Input signal types (e.g. 4-20 mA)
3.15.10 Method of isolation
3.15.11 Impulse voltage withstand kV
3.15.12 Input impedance ohm
3.15.13 Type of ADC switching
3.15.14 Standard number of inputs per module
3.15.15 Mean time between failure h
3.15.16 Power requirement W
3.16.0 Analogue Output Module
3.16.1 Module designation
3.16.2 Literature reference for principle of operation
3.16.3 Number of outputs per module
3.16.4 Maximum number of modules per processor
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 40 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.16.5 Output voltage range V
3.16.6 Output current range mA
3.16.7 Type of isolation
3.16.8 Load resistance range ohms
3.16.9 Maximum error over-current ranges %
3.16.10 Impulse voltage withstand kV
3.17.0 Direct AC Connection Voltage
3.17.1 Module designation
3.17.2 Literature reference for principle of operation
3.17.3 Maximum number of modules processor
3.17.4 Number of inputs per module
3.17.5 Input voltage ranges V ac
3.17.6 Input filter attenuation at 50 Hz dB
3.17.7 Burden on instrument transformer circuit VA
3.17.8 Conversion time ms
3.17.9 Scanning resolution bits
3.17.10 Accuracy %
3.17.11 What calculations are supported
3.17.12 How are overflow and conversion failures dealt with?
3.17.13 Method of isolation
3.17.14 Impulse voltage withstand kV kV
3.18.0 Direct AC Connection Current
3.18.1 Module designation
3.18.2 Literature reference for principle of operation
3.18.3 Maximum number of modules processor
3.18.4 Number of inputs per module
3.18.5 Input current ranges A
3.18.6 Input filter attenuation at 50 Hz dB
3.18.7 Burden on instrument transformer circuit VA
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 41 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.18.8 Conversion time ms
3.18.9 Scanning resolution bits
3.18.10 Accuracy %
3.18.11 What calculations are supported
3.18.12 How are overflow and conversion failures dealt with?
3.18.13 Method of isolation
3.18.14 Impulse voltage withstand kV kV
4.0.0 BCU Software
4.1.0 GENERAL REQUIREMENTS
4.1.1 Program structure
4.1.2 System software
4.1.3 Standard functions programs
4.1.4 User functions programs
4.2.0 Capability of:
4.2.1 BCU program downloading from Control Centre
4.2.2 Application configuration from Control Centre
4.2.3 Remote selection of processing parameters
4.2.4 Selection of communication protocols
4.2.5 Selection of operation modes (cyclic, polled, etc.)
4.2.6Appropriate protection of software against power failure
4.2.7 Automatic BCU re-start without software down-loading
4.3.0 SYSTEM SOFTWARE
4.3.1 Operating System (Monitor) Functions and capabilities
4.3.2 Calendar program Type, functions and capabilities
4.3.3 Time Synchronization Program Functions and capabilities
4.3.4 Data Base Updating program Functions and capabilities
4.3.5 Testing and Diagnostics Programs Functions and capabilities Yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 42 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
4.4.0 STANDARD FUNCTIONS PROGRAMS
4.4.1 Data Communication Programs: Functions and capabilities
4.4.2 Capability of communication protocol selection
4.4.3 Capability of operating modes selection
4.5.0Analogue Measurements, Scanning and Transmission Programs
4.5.1 Capabilities of adjustments
4.5.2 Transducers constants
4.5.3 Periodic transmission/transmission by exception
4.5.4 Automatic checking of A/D-conversion accuracy
4.5.5 Smoothing
4.5.6 Threshold values
4.5.7 Limits
4.5.8 Scan duration (range)
4.5.9 Cycle duration (range) s
4.5.10 Priority of transmission s
4.5.11 Digital Input Data Scanning and transmission Program
4.6.0 Functions and capabilities
4.6.1 Capability of adjustments;
4.6.2 Scan duration (range) ms
4.6.3 Transient time of status information (range)
4.6.4 Cycle duration (range) ms
4.6.5 Debouncing filter s
4.6.6 Suppression of intermediate status information
4.6.7 Time tagging
4.6.8 Transmission mode
4.6.9 Priority of transmission
4.7.0 Alarm and Event handling
4.7.1 Grouping of alarms and events
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 43 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
4.7.2 Maximum number of groups
4.8.0Supervisory Control Programs: Functions and capabilities
4.8.1 Select before execute
4.8.2 Target check
4.8.3 Cancelling control after adjustable time delay
4.8.4 Capability of adjustments:
4.8.5 Duration of output (range) s
4.8.6 Allowed duration of execution (range) s
4.8.7 Sequence of Events programs
4.8.8 Minimal sequence of events time resolution ms
4.8.9 Sequence of events memory capacity
4.8.10 Events time resolution (adjustable range)
4.8.11 Priority of transmission
4.8.12 Post - Mortem Review / Program
4.8.13 Selection of analogues for post-mortem review
4.8.14 Short interval time resolution (adjustable range) s
4.8.15 Long interval time resolution (adjustable range) s
4.9.0 Data processing programs: Functions and capabilities
4.9.1 Required minimum data processing:
4.9.2 Logic functions
4.9.3 Arithmetical functions (MW , Mvar etc )
4.9.4 Limiting functions s
4.9.5 Comparative functions
4.9.6 Time functions
5.0.0 GATEWAY SOFTWARE
5.1.0 GENERAL REQUIREMENTS
5.1.1 Database management application
5.1.2 Alarm and Event Grouping
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 44 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
5.1.3 Alarm and Event Separation for NCC and DCC
5.1.4Alarm and Event storage and remote / local access
5.2.0 Capability of:
5.2.1 Gateway program downloading from Control Centre
5.2.2 Application configuration from Control Centre
5.2.3 Remote selection of processing parameters
5.2.4 Selection of communication protocols
5.2.5 Selection of operation modes (cyclic, polled, etc.)
5.2.6 Appropriate protection of software against power failure
5.2.7 Automatic re-start without software down-loading
5.3.0 SYSTEM SOFTWARE
5.3.1 Operating System (Monitor) Functions and capabilities
5.3.2 Calendar program Type, functions and capabilities
5.3.3 Time Synchronization Program Functions and capabilities
5.3.4 Data Base Updating program Functions and capabilities
5.3.5 Testing and Diagnostics Programs Functions and capabilities
6.0.0 Transducers
6.1.0 Current transducer.
6.1.1 Manufacturer
6.1.2 Type reference
6.1.3 Number
6.1.4 Principle (e.g. 3 phase, 3 wire, unbalanced)
6.1.5 Output range mA
6.1.6 Input ranges available A
6.1.7 Burden on instrument transformer circuit VA
6.1.8 Insulation level kV
6.1.9 Impulse withstand level kV peak
6.1.10 Minimum accuracy over working range %
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 45 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.1.11 Response time (0 to 90%) ms
6.1.12 Mounting details
6.1.13 Operating temperature range °C
6.1.14 Operating humidity range %
6.1.15 Auxiliary supply if required
6.1.16 Voltage range V
6.1.17 Power requirements VA
6.1.18 Frequency Hz
6.1.19 Type of overload protection
6.1.20 Permissible continuous input overload %A
6.2.0 Voltage transducer
6.2.1 Manufacturer
6.2.2 Type
6.2.3 Number
6.2.4 Output range mA
6.2.5 Input ranges available V
6.2.6 Burden on instrument transformer circuit VA
6.2.7 Insulation level kV
6.2.8 Impulse withstand level kV peak
6.2.9 Minimum accuracy over working range %
6.2.10 Response time (0 to 90%) ms
6.2.11 Mounting details
6.2.12 Operating temperature range °C
6.2.13 Operating humidity range %
6.2.14 Auxiliary supply
6.2.15 V range V
6.2.16 Power requirements VA
6.2.17 Frequency Hz
6.2.18 Type of overload protection
6.2.19 Permissible continuous input overload %A
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 46 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.3.0 Active Power MW
6.3.1 Manufacturer
6.3.2 Type reference
6.3.3 Number
6.3.4 Principle (e.g. 3 phase, 3 wire, unbalanced)
6.3.5 Output range mA
6.3.6 Input ranges available
6.3.7 Voltage V
6.3.8 Current A
6.3.9 Burden on instrument transformer circuit
6.3.10 Current Transformer (CT) VA
6.3.11 Voltage Transformer (VT) VA
6.3.12 Insulation level kV
6.3.13 Impulse withstand level kV peak
6.3.14 Minimum accuracy over working range %
6.3.15 Response time (0 to 90%) ms
6.3.16 Mounting details
6.3.17 Operating temperature range °C
6.3.18 Operating humidity range %
6.3.19 Auxiliary supply if required
6.3.20 Voltage range V
6.3.21 Power requirements VA
6.3.22 Frequency Hz
6.3.23 Type of overload protection
6.3.24 Permissible continuous input overload
6.3.25 Voltage %V
6.3.26 Current %A
6.4.0 Reactive Power Mvars
6.4.1 Manufacturer
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 47 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.4.2 Type reference
6.4.3 Number
6.4.4 Principle (e.g. 3 phase, 3 wire, unbalanced)
6.4.5 Output range mA
6.4.6 Input ranges available
6.4.7 Voltage V
6.4.8 Current A
6.4.9 Burden on instrument transformer circuit
6.4.10 Current Transformer (CT) VA
6.4.11 Voltage Transformer (VT) VA
6.4.12 Insulation level kV
6.4.13 Impulse withstand level kV peak
6.4.14 Minimum accuracy over working range %
6.4.15 Response time (0 to 90%) ms
6.4.16 Mounting details
6.4.17 Operating temperature range °C
6.4.18 Operating humidity range %
6.4.19 Auxiliary supply
6.4.20 Voltage range V
6.4.21 Power requirements VA
6.4.22 Frequency Hz
6.4.23 Type of overload protection
6.4.24 Permissible continuous input overload
6.4.25 Voltage %V
6.4.26 Current %A
6.5.0 Frequency
6.5.1 Manufacturer
6.5.2 Type
6.5.3 Number
6.5.4 Measurement range Hz
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 48 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.5.5 Output range mA
6.5.6 Input ranges available V ac
6.5.7 Burden on instrument VT circuit VA
6.5.8 Insulation level kV
6.5.9 Impulse withstand level kV peak
6.5.10 Minimum accuracy over working range %
6.5.11 Response time (0 to 90%) ms
6.5.12 Mounting details
6.5.13 Operating temperature range °C
6.5.14 Auxiliary supply
6.5.15 Voltage range V
6.5.16 Power requirements VA
6.5.17 Frequency Hz
6.5.18 Type of overload protection
6.5.19 Permissible continuous input overload %V %
6.6.0 Power Factor
6.6.1 Manufacturer
6.6.2 Type
6.6.3 Number
6.6.4 Measurement range
6.6.5 Output range mA
6.6.6 Input ranges available V ac
6.6.7 Burden on instrument VT circuit VA
6.6.8 Insulation level kV
6.6.9 Impulse withstand level kV peak
6.6.10 Minimum accuracy over working range %
6.6.11 Response time (0 to 90%) ms
6.6.12 Mounting details
6.6.13 Operating temperature range °C
6.6.14 Auxiliary supply
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 49 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.6.15 Voltage range V
6.6.16 Power requirements VA
6.6.17 Frequency Hz
6.6.18 Type of overload protection
6.6.19 Permissible continuous input overload %
6.7.0 Combined active and reactive power
6.7.1 Manufacturer
6.7.2 Type
6.7.3 Number
6.7.4 Measurement range
6.7.5 Input ranges available
6.7.6 Voltage V ac
6.7.7 Current A
6.7.8 Burden on instrument transformer circuit
6.7.9 Current Transformer (CT) VA
6.7.10 Voltage Transformer (VT) VA
6.7.11 Insulation level kV
6.7.12 Impulse withstand level kV peak
6.7.13 Minimum accuracy over working range %
6.7.14 Response time (0 to 90%) ms
6.7.15 Number of analogue outputs
6.7.16 Analogue output range mA
6.7.17 Calculations available
6.7.18 Serial output protocol
6.7.19 Mounting details
6.7.20 Operating temperature range °C
6.7.21 Auxiliary supply
6.7.22 Voltage range V
6.7.23 Power requirements VA
6.7.24 Frequency Hz
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 50 of 77Part 4 – Schedules of Technical Information
SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.7.25 Type of overload protection
6.7.26 Permissible continuous input overload
6.7.27 Voltage %V
6.7.28 Current %A
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 51 of 77Part 4 – Schedules of Technical Information
LV CABLES UNIT DATA
Required Offered
1. L.V. POWER CABLES
1.1. Manufacturer
1.2. Cable type Cu/XLPE/SWA/LSOH
1.3. Standards IEC 60189, 60227, 60228, 60287, 60724, 60811, 60885, 60332.
BS 67241.4. Rated voltage V 600/1000
1.5. Test voltage (1 min) VAC/min 4000
1.6. Conductor Cross sectional area Material: copper Design (stranded, sectoral, etc.) Overall dimensions No. of Cores
mm2
mm
min 2.5Cu
Stranded
1.7. Insulation XLPE
1.8. Fillers Material: polypropylene
1.9. Armour bedding Type Nominal thickness mm
1.10. Armour Type of wire Number of wire Diameter of wire
No.mm
1.11. Outer covering Material Minimum average thickness mm
LSOH
1.12. Completed cable Overall diameter Weight per metre Maximum drum length
mmkgm
*
1.13. Cable drums Overall diameter Width Weight loaded
mmkg
*
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 52 of 77Part 4 – Schedules of Technical Information
LV CABLES UNIT DATA
Required Offered
1.14. Continuous current carrying capacity based on the conditions specified:Laid in the ground One Circuit Two Circuits Three CircuitsDrawn into ducts One Circuit Two Circuits Three CircuitsIn air One Circuit at 50C
AAA
AAA
A
*
1.15. Maximum conductor temperature oC 90
1.16. Conductor short circuit current Carrying capacity for one second, cable
loaded as above prior to short circuit and final conductor
Temperature of
KA
oC
1.17. Minimum radius of bend around which cable can be laid Laid direct In ducts In air
mmm
1.18. Ducts Nominal internal diameter of pipes or ducts
through which cable may be pulled mm
1.19. Maximum DC resistance Per km of cable at 20oC of conductor ohm
*
1.20. Maximum AC resistance Of conductor per km of cable at maximum
conductor temperature ohm
*
1.21. Insulation resistance per km of cable per core Megaohm
1.22. Manufacturer quality assurance according to ISO 9000, 9001 and 9004
1.23. Type test certificate to be issued by independent laboratory or independently witnessed type test certificate available
* The tenderer may provide a table of data for each of the cables offered.
2. MULTICORE CONTROL CABLES
2.1. Manufacturer
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 53 of 77Part 4 – Schedules of Technical Information
LV CABLES UNIT DATA
Required Offered
2.2. Cable type
2.3. Standards IEC 60189, 60227, 60228, 60287, 60332, 60724, 60811, 60885.
BS 67242.4. Rated Voltage V 600/1000
2.5. Test voltage (1 min) V AC/min 4000
2.6. Cores Number of cores No 2, 3, 4,7, 12, 19, 27,
372.7. Conductor
Cross sectional area: annealed copper Material
mm2
2.8. Insulation Thickness nominal minimum
mmmm
XLPE
2.9. Armour bedding Type: Nominal thickness mm
LSOH
2.10. Armour Number of wire: Diameter of wire
No.mm
2.11. Outer covering Material: Minimum average thickness mm
LSOH
2.12. Completed cable Overall diameter Weight per metre Maximum drum length
mmkgm
***
2.13. Mean electrostatic capacity of each conductor to earth per km of each core at 20C
pF*
2.14. Maximum DC resistance per km of each core at 20C max.
1.5mm2
2.5mm2ohm
2.15. Minimum radius of bend round which cable can be laid
mm
2.16. Manufacturer quality assurance according to ISO 9000, 9001, 9002, 9003 and 9004
2.17. Type test certificate to be issued by independent laboratory or independently witnessed type test certificate available
* The tenderer may provide a table of data for each of the cables offered.
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 54 of 77Part 4 – Schedules of Technical Information
EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
1. EARTHING SYSTEM
1.1. Manufacturers
1.2. Standard Applied
The following standards shall apply to the earthing installations and to the accessories: Guide for safety in A.C. substation grounding Earthing system in A.C. installation for rated voltages
above 1000 V
IEEE80 & 81VDE 0141
1.3. Physical Properties of Copper
The most important physical properties of copper used for the earthing conductors: Density kg/dm3 8.89 Electrical resistivity at 20C mm2/m 0.0176 Melting point C 1083 Current density at which the conductor temperature rises
from 50C to 300C in a time of 1 s if all heat is retained in conductor A/mm2 190
1.4. Physical Properties of Lead-Sheathed Copper
The most important physical properties of lead-sheathed copper used for the earth electrodes: Thickness of lead sheath mm 2.0 Electrical resistivity of copper at 20C mm2/m 0.0176 Copper melting point C 1083 Lead melting point C 327 Current density at which the conductor temperature rises
from 40C to 150C in a time of 1 s if all heat is retained in conductor A/mm2 140
1.5. Earthing Conductors
1.5.1. Stranded copper conductors
The following stranded copper conductor will be used as earthing conductors: Cross-section area mm2
Number of wires No. Diameter of each wire mm Conductor diameter mm Density kg/m
Cross-section area mm2
Number of wires No. Diameter of each wire mm Conductor diameter mm
Density kg/m
Cross-section area mm
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 55 of 77Part 4 – Schedules of Technical Information
EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
Number of wires pcs Diameter of each wire mm Conductor diameter mm Density kg/m
1.5.2. Copper Flat Bars
The following copper flat bars will be used as earthing conductors: Cross section area mm2
Dimensions mm x mm Density kg/m
Cross section area mm2
Dimensions mm x mm Density kg/m
Cross section area mm2
Dimensions mm x mm Density kg/m
1.5.3. Copper Cables
The following PVC single-core copper cables will be used as earthing conductors: Cross-section area mm2
Cross-section area mm2
Cross-section area mm2
1.6. Earth Electrodes
1.6.1. Lead-sheathed stranded copper conductors
The following lead-sheathed stranded copper conductor will be used as earth electrodes: Thickness of lead sheath mm Copper cross-section area mm2
Number of wires pcs Diameter of each wire mm Conductor diameter mm Density kg/m
Thickness of lead sheath mm Copper cross-section area mm2
Number of wires pcs Diameter of each wire mm Conductor diameter mm Density kg/m
Thickness of lead sheath mm Copper cross-section area mm2
Diameter of each wire mm Conductor diameter mm Density kg/m
1.6.2. Earth rod
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 56 of 77Part 4 – Schedules of Technical Information
EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
Manufacturer Length m Diameter mm Material (copper, stainless steel)
1.6.3. Stainless steel electrodes
The following steel flat bars will be used as earth electrodes: Cross-section area dimensions Density
mm2
mm x mmkg/m
1.7. Connections
Mode of Connection in the Earthing Systems: Between earthing conductors and earth electrodes Crossing of earth electrodes
BrazedCompressio
n2. LIGHTNING PROTECTION
2.1. Manufacturers
2.2. Standard Applied: Protection of structures against lightning IEC 62305
Manufacturer Cross-section area mm2
Thickness of lead-sheath mm2.3. Supports
Conductor supports of the lightning protection system Type
2.4. Earth rod
Manufacturer Length m Diameter mm Material (copper, stainless steel)
3. Type test certificate (to be issued by independent laboratory or independently witnessed type test certificate available) yes
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 57 of 77Part 4 – Schedules of Technical Information
400 kV SHUNT REACTOR UNIT DATA
Required Offered
1. Shunt Reactor
1.1 Manufacturer & Place of manufacturing
1.2 Type designation
1.3 Type Outdoor, Oil Immersed
1.4 Construction (Gapped core/Air-cored shielded)
1.5 Principal standards IEC 60076-1,-2,-3, -6
1.6 Max ambient (Design) temperature oC 40
1.7 Altitude m 1645
1.8 Rated voltage(Initial operation will be at reduced voltage)
kV(kV)
400(220)
1.9 Highest voltage for equipment, Um; Reactor must be able to operate continuously at this voltage.(Initial operational highest voltage for equipment)
kV
(kV)
420
(245)
1.10 Rated frequency Hz 50
1.11 Vector group YN
1.12 Cooling ONAN
1.13 Method of earthing Solid
1.14 Type (graded/non-graded) of windings Graded
1.15 Rated lightning impulse withstand voltage at:- HV terminals kV 1425- HV neutral-end terminals kV 125
1.16 Rated switching impulse voltage kV 1050
1.17 Rated power frequency withstand voltage at- HV terminals kV 436 (U1)- HV neutral-end terminals kV 50
1.18 Rated power:- Rated current IN- Max continuous current at Um
AA
144152
- Rated (reactive) power at Ur
- Rated power at 220 kV (initial energisation)MVArMVAr
10030 approx
- Rated reactance XN /phase 1600- Zero sequence reactance X0 - Mutual reactance XM /phase
1.19 Magnetic characteristic: Linear to percent of rated voltage
% 105
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 58 of 77Part 4 – Schedules of Technical Information
400 kV SHUNT REACTOR UNIT DATA
Required Offered
1.20 Maximum temperature rise at rated power at:- Windings K 65- Hot spot of windings K 78- Top oil K 60- Oil at inlet of cooler K
- Oil at outlet of cooler K
- Core- Tank Wall
KK
1.21 Losses at rated voltage and rated frequency kW
1.22 Maximum current density at rated power:- HV winding A/mm2
1.23 Maximum flux density at rated voltage, power frequency:- Wound limbs/core packets T- Yokes- Shield
TT
1.24 Resistance of winding at 75C and principal tapping: /phase
1.25 Terminal connection- Bushing standards- Pollution Class - Is KD Correction factor required?
(mm/kV)IEC 60137
IV (31)Yes
- HV terminals- Minimum Voltage Class- Minimum Current rating - Manufacturer- Manufacturers designation- Type (OIP/RIP)
kVA
Bushing 420400
- HV neutral-end terminals- Minimum Voltage Class- Minimum Current rating - Manufacturer- Manufacturers designation- Type (OIP/RIP/Porcelain)
kVA
Bushing24
400
Porcelain
1.26 Current transformers
1.26a HV-Bushing turrets
- Number of cores 2- Rated extended primary current - Ratio (TR = turns ratio)
I core A 800/400/1 II core A 800/400/1
- Class I core 5P20 II core 5P20
- Knee point voltage (Ek) I core V II core V
- Exciting current (IE ) at Ek
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 59 of 77Part 4 – Schedules of Technical Information
400 kV SHUNT REACTOR UNIT DATA
Required Offered
I core mA II core mA
- Rated output (Burden to be 25-100% rated burden) I core VA II core VA
1.26b HV Neutral-End
- Number of cores/phase 1- Rated extended primary current - Ratio (TR = turns ratio)
I core 800/400/1- Class
I core 5P20- Knee point voltage (Ek)
I core V- Exciting current (IE ) at Ek
I core mA- Rated output (Burden to be 25-100% rated
burden) I core VA
1.26b HV Neutral
- Number of cores 1- Rated extended primary current - Ratio (TR = turns ratio)
I core 800/400/1- Class
I core 5P20- Knee point voltage (Ek)
I core V- Exciting current (IE ) at Ek
I core mA- Rated output (Burden to be 25-100% rated
burden) I core VA
All class PX CTs shall have a rated secondary current, ISN
A
1.27 Radiators- Tank or Separate Mounting- Number banks- Number of radiators elements per bank
1.28 Oil- Manufacturer- Type designation- Standards IEC 60296- Minimum flash point C- Viscosity
at 20C mm2/s at 50C mm2/s at 80C mm2/s
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 60 of 77Part 4 – Schedules of Technical Information
400 kV SHUNT REACTOR UNIT DATA
Required Offered
- Maximum dielectric strength for 1 min. kV- Dielectric factor- Acidity (neutralization value) mgKOH/
g
1.29 Oil preservation system- Type (Refrigerant/Bag/Membrane)- Breather- Oil Level Gauge
Maintenance-freeMagnetic
1.30 Types and arrangement of winding:
1.31 Conductor Material (e.g., copper, work hardened copper, etc.)
1.32 Conductor type (CTC, other)
1.33 Conductor insulation:
1.34 Calculated thermal time constant Hours
1.35 Oil circulation (i.e., natural/partially directed/directed)
To the windings:
Through the windings:
1.36 Core construction:- Core segment- Core gaps- Taped/banded/bolted limbs - Taped/banded/bolted yokes- Taped/banded/bolted shield- Taping/banding material- Number of limbs- Type of joint in core (90% butt, overlap, mitre, etc.)- Core steel- Specific loss of core steel at 1.5 Tesla W/kg
1.37 Thickness of reactor tank- Sides mm- Bottom mm- Top mm
1.38 Material of reactor tank
1.39 Thickness of radiator plates mm
1.40 Total volume of conservator litres
1.41 Minimum volume of conservator between highest and lowest levels as percentage of total cold oil at 15C volume of transformer
7.5%
1.42 Volumetric expansion of oil from 0 to 90C m3
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 61 of 77Part 4 – Schedules of Technical Information
400 kV SHUNT REACTOR UNIT DATA
Required Offered
1.43 Pressure increase inside tank due to expansion of oil
1.44 Masses of reactor- Core and coils kg- Total mass excluded oil kg- Oil mass in tank kg
in radiators kg total kg
- Total mass kg
1.45 Mass of reactor as arranged for transport (heaviest part) kg
1.46 Dimensions of reactor arranged for transport- Height m- Width m- Length m
1.47 Filling medium of reactor tank for shipment
1.48 Maximum noise level dB(A) 86
1.49 Conservator vessel, radiators, control boxes or cubicles and pipework anticorrosion protection
Hot dip galvanized and painted
1.50 Tank anticorrosion protection
1.51 Supply voltage for reactor auxiliaries V 415/240 AC
1.52 Control/Protection voltage V 110 DC
1.53 Manufacturer quality assurance- According to ISO 9000, 9001, 9002, 9003 and
9004; List current accreditationYes
1.54 Type test certificate to be issued by:- Independent laboratory or independently witnessed
type test certificateYes
1.55 Routine tests
The ACLD test is to be carried out at the enhanced values given in IEC 60076-3; U1 @ 180%, U2 at 160% of Um. - 1 x 3-phase test or 3 x 1-phase test- U1, enhanced level- U2, 1 hour duration- Max PD level during 1 hour stage
kVkVpC
To IEC 60076-6
436388 500
Note 2: The method of carrying out loss measurements and any limitations of manufacturer’s test field which restricts the test programme are to be advised with bid documents.
1.56 Special Tests to be performed: (R=Routine/All units: T=Type/1 unit))
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 62 of 77Part 4 – Schedules of Technical Information
400 kV SHUNT REACTOR UNIT DATA
Required Offered
- Dielectric test – Chopped wave lightning impulse- Measurement of zero-sequence impedance- Measurement of mutual reactance- Determination of sound levels- Measurement of vibration- Measurement of harmonics- Determination of capacitance, windings to earth
and between windings- Measurement of insulation resistance to earth and
loss angle of insulation system capacitances- Verification of magnetic characteristic
Yes(R)Yes(R)Yes (R)Yes (R)Yes (R)Yes (R)Yes (R)
Yes (R)
Yes (T)
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 63 of 77Part 4 – Schedules of Technical Information
220kV XLPE INSULATED CABLE SYSTEM (334MVA) UNIT DATA
(with special bonding) Required Offered
1.0 General1.1 Name of manufacturer
1.2 Location of manufacturing site
1.3 Manufacturers Quality Certification ISO 9001
- Certified by (Company Name)- Certification valid till (year)
1.4 Circuit rating required MVA 334
1.5 General description of cable- number of cores 1
- system voltage kV 220
- conductor size mm2
- Insulation Type XLPE
- metal sheath type Lead
- oversheath type HDPE
1.6 Year of first commercial operation of cable type
2.0 Insulation Coordination2.1 Highest system voltage (Um) (insulation class) kV 245
2.2 Nominal voltage between conductors (U) kV 220
2.3 Rated frequency Hz 50
2.4 Nominal voltage between conductor and sheath (Uo) kV 130
2.5 Rated impulse withstand voltage (Up) (at altitude <1000m) kV 1050
2.6 Rated short duration power frequency withstand voltage (at altitude <1000m)
kV 460
3.0 Ratings3.1 Maximum continuous direct-buried current rating, assuming,
- Ground temperature at burial depth of 40oC- Maximum Soil thermal resistivity of 2.7K.m/W- Touching trefoil configuration- Special bonding of metal sheathsFor,Guaranteed Current Rating (Single Circuit in Trench) AGuaranteed Current Rating (Double Circuit in one Trench, distance between middle phases, s = 1500 mm)
A
Calculation Method IEC 60287
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 64 of 77Part 4 – Schedules of Technical Information
220kV XLPE INSULATED CABLE SYSTEM (334MVA) UNIT DATA
(with special bonding) Required Offered 3.2
3.3
Maximum continuous direct-buried current rating, assuming,- Ground temperature at burial depth of 40oC- Maximum Soil thermal resistivity of 2.7K.m/W- Flat formation configuration- Special bonding of metal sheathsFor,Guaranteed Current Rating (Single Circuit in Trench)Guaranteed Current Rating (Double Circuit in one Trench,distance between middle phases, s = 1500 mm)Calculation Method
Maximum continuous in-air current rating, assuming,
AA
IEC 60287
- Air temperature (in shade) of 50 oC- Special bonding of metal sheaths- Flat spaced configuration, phase spacing of 250mm- Thermally independent of other cable circuitsFor,Guaranteed Current Rating (single circuit) ACalculation Method
3.4 Maximum permissible core temperature for continuous operation
oC 90
3.5 Short circuit capacity for 1 sec- Short circuit current kA- Permissible maximum sheath temperature oC 200- Permissible maximum conductor temperature
oC 250
3.6 Permissible emergency overload3.6.1 Applied on 100% continuous load
- Emergency current rating A- Maximum emergency temperature oC- Allowable duration/operation hours- Allowable total duration/annum hours- Maximum average duration/annum on total life of cable hours
3.6.2 Applied on 50% continuous load- Emergency current rating A- Maximum emergency temperature °C- Allowable duration/operation hours- Allowable total duration/annum hours- Maximum average duration/annum on total life of cable hours
3.6.3 Applied on 20% continuous load- Emergence current rating A- Maximum emergency temperature °C- Allowable duration/operation hours- Allowable total duration/annum hours- Maximum average duration/annum on total life of cable hours
4.0 Construction Features4.1 Conductor
- Material Cu, - Nominal cross-section mm2
- Shape and type of conductor- Overall diameter mm
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 65 of 77Part 4 – Schedules of Technical Information
220kV XLPE INSULATED CABLE SYSTEM (334MVA) UNIT DATA
(with special bonding) Required Offered
- Waterblocking method Tape/yarn- Semiconducting binder tape yes
4.2 Conductor screen- Type of material Fully bonded
semicon. XLPE- Nominal thickness mm- Minimum thickness mm- Nominal overall diameter mm
- Compound Identification Reference yes
4.3 Insulation- Material XLPE- Nominal thickness mm- Minimum thickness mm- Nominal overall diameter mm- Maximum continuous operating temperature
oC 90- Compound Identification Reference yesMaximum stress at nominal voltage- At conductor screen kV/mm- At insulation screen kV/mmMaximum stress at impulse voltage- At conductor screen kV/mm- At insulation screen kV/mm
4.4 Insulation screen- Type of material Fully bonded
semicon. XLPE- Nominal thickness mm- Nominal overall diameter mm
- Compound Identification Reference- Indelible ink marking on screen yes
4.5 XLPE Manufacturing Methods- Extrusion line type e.g. CCV, MDCV, VCV- Single pass, triple extrusion yes- Curing method Dry- Cooling method Dry- Degassing Period days
4.6 Bedding for moisture absorption- Type and material- Nominal thickness mm- Minimum thickness mm- Nominal overall diameter over bedding mm
4.7 Metallic screen- Type and material Copper wire- Nominal thickness mm- Minimum thickness mm- Wire diameter No.- Nominal diameter over the screen mm- Cross sectional area of screen mm2
- Short time current density (1 sec) kA/mm2
4.8 Bedding/Binder tape- Type and material
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 66 of 77Part 4 – Schedules of Technical Information
220kV XLPE INSULATED CABLE SYSTEM (334MVA) UNIT DATA
(with special bonding) Required Offered
- Nominal thickness mm- Minimum thickness mm- Nominal overall diameter over bedding mm
4.9 Metallic sheath- Type and material Lead-alloy 1/2C- Nominal thickness mm- Minimum thickness mm- Nominal diameter over the sheath mm- Cross sectional area of sheath mm2
- Short time current density (1 sec.) kA/mm2
4.10 Protective anti-corrosion external sheath covering- Bitumen undercoat layer- Type and material HDPE- Colour Black- Nominal thickness mm- Minimum thickness mm- Termite resistant yes/no Yes- Type of anti-termite protection specify- Thermal resistivity K.m/W Max 6.0
- Type of fire protection for closing section
4.11 Type of conductive outer layer Graphite/or semicon. polymer
4.12 Nominal overall cable diameter mm
4.13 Weight of completed cable- Copper kg/m- Insulation kg/m- Lead-Alloy kg/m- Gross Weight kg/m
5.0 Losses5.1 Maximum dielectric loss per metre / phase when operating at
nominal voltage and frequency and at maximum conductor temperature
W/m
5.2 Maximum sheath loss per metre / phase when operating at nominal voltage and frequency and at current rating stipulated in Item 3 with sheath bonded and earthed as recommended (sectionalizing cross bonding)
W/m
5.3 Maximum conductor loss per metre / phase when operating at nominal voltage and frequency and at current rating stipulated in Item 3.
W/m
5.4 Total loss of cable per metre / phase of three phase circuit W/m
6.0 Electrical Values6.1 Maximum d.c. resistance of conductor at 20oC /m
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 67 of 77Part 4 – Schedules of Technical Information
220kV XLPE INSULATED CABLE SYSTEM (334MVA) UNIT DATA
(with special bonding) Required Offered6.2 Maximum a.c. resistance of conductor at operating
temperature/m
6.3 Equivalent reactance of three phase circuit at 50 Hz /m
6.4 Electrostatic capacitance per conductor of cable at nominal voltage and operating temperature
pF/m
6.5 Maximum charging current per conductor at nominal voltage mA/m
6.6 Charging capacity of three phase system (at Uo) VAr/m
6.7 Maximum dielectric loss factor of cable at normal voltage and frequency at a conductor temperature of:- 20oC- 90oC
6.8 Positive & Negative sequence impedance /m
6.9 Zero sequence impedance (as installed conditions)- Resistance /m- Reactance /m- Capacitance pF/m
6.10 Surge impedance
7.0 Bonding & Earthing7.1 Type of special bonding7.2 Maximum sheath potential of completed cable with conductor
at rated current with sheath bonded and earthed as recommended
V/m
7.3 Maximum sheath potential of completed cable with conductor at maximum earth fault current of 40 kA with sheath bonded and earthed as recommended
V/m
7.4 SVL Rating Min. 6kV
8.0 Testing8.1 Routine Tests
- As per IEC 62067 Yes- Additional tests specified in KETRACO spec. yes
8.2 Sample Tests - 5Uo for 1 hour (as per KETRACO spec.) yes
8.3 Type Tests- Test Regime IEC 62067- Location of Test- Date of Test- Name of independent witness
8.4 Prequalification Test- Test Regime- Date completed- Location of Test- Name of independent witness
8.5 Commissioning Tests- AC voltage withstand test 1.7Uo for 1 hour
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 68 of 77Part 4 – Schedules of Technical Information
220kV XLPE INSULATED CABLE SYSTEM (334MVA) UNIT DATA
(with special bonding) Required Offered
- Partial discharge monitoring <10pC- Oversheath DC voltage test kV 12kV for 15
minutes
9.0 Other Installation Data9.1 Minimum cable bending radius when laid:
- Direct burial mm- In air mm- In ducts mm- At terminations (with former) mm
9.2 Maximal permissible pulling force of total cable kN
9.3 Maximal side wall bearing pressure to the cable at bending points
kN/m
9.4 Delivery length per drum Normal m Maximum m
9.5 Maximal weight of full drum with maximum delivery length of cable
kg
9.6 Drum dimensions: Flange diameter m Core diameter m Width m
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 69 of 77Part 4 – Schedules of Technical Information
220kV CABLE SHEATH BONDING AND EARTHING EQUIPMENT UNIT DATA
Required Offered
1. SHEATH VOLTAGE LIMITERS
1.1. Manufacturer
1.2. Type designation
1.3. Type ZnO, non linear
1.4. Type test carried out Yes/no
1.5.. Rated frequency Hz 50
1.6. System voltage kV 220
1.7. Protective level kV
1.8. Peak values of residual voltage on 8/20 microsecond current impulse current of:
- 2000A kV
- 5000A kV
- 10000A kV
- 15000A kV
- 20000A kV
1.9. Withstand energy Joule
1.10. Maximum specified a.c. voltage which can be withstood for 2 sec. kV
1.11. Conductivity characteristics of SVL at 200V- d.c. test current MA- voltage limit minimal V- voltage limit maximal V 0 – 10 mA
1.12. Insulation resistance at 1000V d.c. voltage M 10
1.13 Permissible ambient temperature 0C 0 – 900C
1.14 Nominal physical dimensions- diameter mm
- height mm
2. LINK BOXES
2.1. Manufacturer
2.2. Type designation- with SVL- for solid bonding
2.3. Type- along the route- at the terminal location Lockable/
Buried
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 70 of 77Part 4 – Schedules of Technical Information
220kV CABLE SHEATH BONDING AND EARTHING EQUIPMENT UNIT DATA
Required Offered2.4. Type test carried out Yes/no
2.5. Rated frequency Hz 50
2.6. System voltage kV 220
2.7. Material- thickness of sheet- material of gaskets Compound/
dry- way of gasket fitting
2.8. Impulse voltage test- between cable sheaths kV 40- between sheaths and water kV 20
2.9. D. C. Voltage test kV/min 20kV/1min.
2.10. Box dimensions- width mm- length mm- height mm- weight kg
2.11 Protection class IP65
3. SINGLE CORE BONDING CABLE
3.1. Manufacturer
3.2. Type designation
3.3. Standards BS 6346C.55/4
3.4. Conductor Nominal Cross Section mm² No. of wires/Diameter 1/mm Diameter Min/max
3.5. PVC Insulation Material PVC Thickness mm Diameter Min/max. Graphite coating Yes/no Yes
3.6. Nominal overall diameter mm
3.7. Weight of cable kg/m
3.8. Maximum d.c. resistance at 20°C Inner conductor 10-6 Ohm/m Outer conductor 10-6 Ohm/m
3.9. DC Voltage test Between conductor and screen kV/min 20kV/ 1min
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 71 of 77Part 4 – Schedules of Technical Information
220kV CABLE SHEATH BONDING AND EARTHING EQUIPMENT UNIT DATA
Required Offered3.10. Impulse voltage test (1.2/50)
Between conductor and screen kV 45
3.11. Maximum short circuit current, 1 second kA 31.5
3.12. Type test carried out Yes/no- Independent Laboratory Name- Year of the type test performance
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 72 of 77Part 4 – Schedules of Technical Information
220kV CABLE ACCESSORIES UNIT DATA
Required Offered
1. TERMINATIONS
1.1. Manufacturer
1.2. Location of manufacturing site
1.3. Year of first commercial operation
1.3a Operational experience in the region Yes/no
1.4. Type tests- Test Regime IEC 62067- Location of Test- Date of Test- Name of independent witness
1.5.. Identifying reference number (for cross reference with type test)
1.6. Termination type (ODSE, OISE, GISE, wet type, dry type) ODSE
1.7. Partial Discharge Sensor Internal
1.8. Conductor connection method
1.9. Method of stress control
1.10. Compliant with IEC 60859 (GISE only)
1.11. Overall weight kg
1.12. Overall diameter mm
1.13 Overall length mm
2. JOINTS
2.1. Manufacturer
2.2. Location of manufacturing site
2.3. Year of first commercial operation
2.4. Operational experience in the region Yes/no
2.5. Type tests- Test Regime IEC 62067- Location of Test- Date of Test- Name of independent witness
2.6. Identifying reference number (for cross reference with type test)
2.7. Joint type Premoulded
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 73 of 77Part 4 – Schedules of Technical Information
220kV CABLE ACCESSORIES UNIT DATA
Required Offered
1-piece2.8. Partial discharge sensor Internal
2.9. Conductor connection method
2.10. Copper joint shell with lead plumb seals yes
2.11 Sheath insulation (taped, heat shrink sleeve, GF box plus bitumen)
2.12 Overall diameter mm
2.13 Overall length mm
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 74 of 77Part 4 – Schedules of Technical Information
FIBRE OPTIC PILOT CABLE SYSTEM UNIT DATA
Required Offered1. FIBRE OPTIC PILOT CABLE
1.1. Name of manufacturer
1.2. Type designation
1.3. Cable type Non-zero dispersion shifted single mode
1.4. Standards:
- for single mode fibres ITU-T G.655
- for optical fibre cables
1.5. Number of optical fibres Nos. 48
1.6. Optical wavelength nm 1550 or 1625(optimized for 1550)
1.7. Attenuation coefficient dB/km- at 1550 nm- at 1625 nm
1.8. Dispersion coefficient ps/nm.km- at 1550 nm- at 1625 nm
1.9. Cut off wavelength nm- at 1550 nm- at 1625 nm
1.10. Maximum optical loss variation at temperature range of 0 oC to +40 oC
dB/km
1.11. Transmission speed Mbit/s
1.12. Tensile strength (without temporary or permanent optical degradation and mechanical cable damage)
N
1.13. Permissible bending radius mm
1.14. Mode field diameter and tolerance m
1.15 Mode field non-circularity %
1.16. Mode field concentricity error m
1.17. Cladding diameter and tolerance m
1.18. Cladding non-circularity %
1.19. Primary coating material
1.20. Diameter over primary coating and tolerance m
1.21. Type of secondary coating
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 75 of 77Part 4 – Schedules of Technical Information
FIBRE OPTIC PILOT CABLE SYSTEM UNIT DATA
Required Offered1.22. Secondary coating material
1.23. Type of central strength element Fibre-reinforced plastic material
1.24. Filler Non-hygroscopic
1.25. Type of belt insulation- Material PVC tapes- Radial thickness mm
1.26. Inner jacket (peripheral tensile strength member)- Material- Radial thickness mm
1.27. Outer jacket- Material PVC- Radial thickness mm
1.28. Anti-termite protection “Rigid” plastic over the outer
cable jacket
1.29. Overall diameter of completed cable mm
1.30. Drum length km
1.31. Mass of cable (per km) kg
1.32. Manufacturer quality system in accordance with ISO 9000, 9001 and 9004
Yes/No Yes
- Applicable Standard- Certified by (Company Name)- Certification valid till (year)
1.33. Type test carried out Yes/No Yes- Independent Laboratory Name- Year of the type test performance
2. FIBRE OPTIC JOINT CLOSURE
2.1. Name of manufacturer
2.2. Type designation Splice
2.3. Splice capacity Nos. Min. 2 fibre optic cables, each with
min. 48 single modefibres with loose
tube
2.4. Fibre Optical Cable Gland To accept metal-free optical cable, min 48single mode fibres,
with loose tube
2.5. Maximum optical attenuation per splice dB 0.1
Mombasa – Nairobi 400kV Transmission Line Contract KETRACO/1/6/09 Lot 3
Section VII – Forms and Procedures Page 76 of 77Part 4 – Schedules of Technical Information
FIBRE OPTIC PILOT CABLE SYSTEM UNIT DATA
Required Offered
2.6. Housing Waterproof, and corrosion resistant
2.7. Installation Direct burial into ground
2.8. Dimensions mm
2.9. Mass kg
2.10. Manufacturer quality system in accordance with ISO 9000, 9001 and 9004
Yes/No Yes
- Applicable Standard- Certified by (Company Name)- Certification valid till (year)
2.11. Type test carried out Yes/No Yes- Independent Laboratory Name- Year of the type test performance
3. OPTICAL TERMINAL BOX3.1. Name of manufacturer
3.2. Type designation
3.3. Number of optical fibres Nos. min. 48
3.4. Fibre Optical Cable Gland To accept metal-free optical cable, min 48single mode fibres,
with loose tube
3.5. Maximum optical attenuation per splice dB 0.1
3.6. Type of optical connectors F.C. – P.C.
3.7. Housing Tamper-proof, sealed, rugged
construction3.8. Installation
- at substation end
- at OHL tower end
Wall/structuremounted
Supplied by others
3.9. Dimensions mm
3.10. Mass kg
3.11. Manufacturer quality system in accordance with ISO 9000, 9001 and 9004
Yes/No Yes
- Applicable Standard- Certified by (Company Name)- Certification valid till (year)
3.12. Type test carried out Yes/No Yes- Independent Laboratory Name