3C1 Russell ChilledWaterLoadShedding

Embed Size (px)

Citation preview

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    1/23

    Chilled Water Load

    Shedding: Planning and

    Procedures

    IDEA ConferenceFeb. 2008Jay Russell, PE

    University of Michigan

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    2/23

    Overview Definitions

    Background - Palmer Chiller Plant Communicate with the Stakeholders

    Minimize the Likelihood and Severity ofExcursions

    Regain Control of the Plant During

    Excursions Conclusions

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    3/23

    Definitions Load Shedding (CHW System): Restricting

    or turning off the flow of chilled water forselected users in a controlled, repeatablemanner.

    Excursion (CHW system): Period ofelevated supply temperatures due tocapacity shortfall, equipment or control

    problems

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    4/23

    Background -

    Palmer Drive Chiller Plant

    3,000-ton electric centrifugal chiller plant

    (2) x 1,250-ton plus (1) x 500-ton w/generator backup

    Primary-Secondary-Tertiary system w/

    14-degree design Delta T

    Serves about 600,000 GSF of laboratory,

    vivarium, office, conference, classroom,and admin space.

    Plant does not have full N-1 reliability

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    5/23

    Life Sciences Institute (LSI) ~350K GSF

    Background - Palmer Drive Chiller Plant

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    6/23

    Background - Palmer Drive Chiller Plant LSI Cooling Coil Design Conditions: 92 Fdb, 72

    Fwb (40% RH)

    Actual daytime conditions, July 31 August 2,2006: 95 Fdb, 84 Fwb (65% RH)

    Worst conditions Ive seen in 19 years trackingHVAC systems BAS staffer

    Result: most air handlers could not meetsetpoint, CHW valves opened wide, causingmassive negative flow through decoupler

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    7/23

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    8/23

    Chilled Water System Reliability PlanThree major goals for reliability plan:

    1. Maintain communication betweenstakeholders at all times, but especially duringunforeseen outages or excursions.

    2. Minimize the likelihood and severity of chilledwater outages and excursions

    3. Establish a repeatable plan for bringing the

    plant back into normal control ranges duringexcursions

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    9/23

    Goal 1: Maintain Communication

    Between Stakeholders Communication must be timely and must

    be maintained at all times Use existing shutdown notification system

    and building contact database

    Use Building Automation System to trendand analyze plant performance

    Establish load database for planning andfor emergency response

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    10/23

    Goal 2: Minimize the likelihood and

    severity of excursions Limit flows for tertiary systems

    Establish alarms for critical flows andtemperatures

    Add flexiblility to temperature setpoints

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    11/23

    Goal 2: Minimize the likelihood and

    severity of excursionsFlow limitations for tertiary systems

    Tertiary Max. Flow (gal/min)

    LSI-AHU 2,500

    LSI-Vivarium 700

    LSI-Process 250LSI-Server 95

    Palmer Commons 450

    Undergraduate Science Bldg 1,050TOTAL 5,045

    Max. primary CHW flowrate: 4,800

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    12/23

    Goal 2: Minimize the likelihood and

    severity of excursionsFlow limitations for tertiary systems

    Progam maximum tertiary flow limits intotertiary valve control code. These limitvariables can then be altered automatically byload shedding algorithm.

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    13/23

    Goal 2: Minimize the likelihood and

    severity of excursionsAlarms for critical flows and temperatures

    Program alarms into Building AutomationSystem to alert operators of excursionsbefore they get out of hand.

    Cut through the chaff of routine alarmsby using email, phone, or pagernotification for critical stakeholders.

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    14/23

    Goal 2: Minimize the likelihood and

    severity of excursionsAdding flexibility to temperature setpoints

    Load Type Critical CHWS Temp? Critical DAT Temp?

    AHU-Offices NO NO

    AHU-Labs YES, BUT CAN RANGE YES, BUT CAN RANGE

    AHU-Vivarium YES, BUT CAN RANGE YES, BUT CAN RANGE

    AHU/Fan Coils-Server Rms YES, BUT CAN RANGE YES, BUT CAN RANGE

    AHU-Stairwells NO NO

    Fan Coils-Elec. Rooms NO NO

    Fan Coils-Telecom Rooms NO NO

    Fan Coil-BDF NO NO

    Fan Coils-Elevator Rooms NO NO

    Cold Rooms NO-condenser water DOES NOT APPLY

    Environmental Rooms NO-condenser water DOES NOT APPLY

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    15/23

    Goal 2: Minimize the likelihood and

    severity of excursionsAdding flexibility to temperature setpoints

    Most air handling systems, even critical vivariumfans, can accommodate a few degrees of chilledwater supply temp variation, since in manycases reheat coils can compensate.

    Emphasize stable versus unstable

    During excursions, allow tertiary supplysetpoints to rise, especially in non-critical areas.

    Consider floating DAT setpoints

    DAT SP = (CHWS Temp) + (Design coil approach)

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    16/23

    Goal 3: Establish a repeatable plan for bringing the plant

    into control during excursions

    Bodys response to shock

    Establish multi-level load shedding modes Establish stakeholder responsibilities in

    advance

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    17/23

    Goal 3: Establish a repeatable plan for bringing the plant

    into control during excursions

    Establish multi-level load shedding modesLevel 1: ~ 430 tons shed total

    Tertiary Normal Max.Flow

    (gal/min)

    Level 1 Max.Flow

    (gal/min)

    Expected dischargeair temp

    increase (deg F)

    LSI-AHU 2,500 2,150 2

    LSI-Vivarium 700 600 2

    LSI-Process 250 205 2

    LSI-Server 95 80 2Commons 450 385 2

    USB 1,050 900 2

    Total 5,045 4,320

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    18/23

    Goal 3: Establish a repeatable plan for bringing the plant

    into control during excursions

    Establish multi-level load shedding modesLevel 2: ~ 1,200 tons shed total

    Tertiary Normal Max.Flow (gal/min)

    Level 2 Max.Flow (gal/min)

    Expected dischargeair temp increase

    (deg F)

    LSI-AHU 2,500 1,400 6

    LSI-Vivarium 700 550 3

    LSI-Process 250 110 6

    LSI-Server 95 55 6Commons 450 250 6

    USB 1,050 600 6

    Total 5,045 2,965

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    19/23

    Goal 3: Establish a repeatable plan for bringing the plant

    into control during excursions

    Establish multi-level load shedding modesLevel 3-Start to shut off non-critical systems:~1,850 tons shed totalShut-offSequence

    Load Name Service Area Design Demand(Tons)

    1 LSI Systems AHU-7, -8 Offices 160 total

    2 USB Systems AHU-2, -3 Offices, Classrooms 200 total

    3 Commons Systems AHU-1, -2 Offices, Meeting Rooms 240 total

    4 Commons Systems AHU-3 Kitchen/Food Service 50 total

    Total 650 tons

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    20/23

    Goal 3: Establish a repeatable plan for bringing the plant

    into control during excursions

    Establish multi-level load shedding modesLevel 4 All loads shut off except Vivarium, to

    match capacity of 500-ton chiller withemergency power

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    21/23

    Load Shedding in Action: August 8, 2007

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    22/23

    Load Shedding in Action: August 8, 2007

  • 8/13/2019 3C1 Russell ChilledWaterLoadShedding

    23/23

    Conclusions Know your customers and communicate

    with them regularly Know your loads

    Think of bending but not breaking: let

    temperature/flow setpoints flex ratherthan outright shutoff if possible

    Establish a consensus on load sheddingplans in advance of emergency outage orexcursion