36109419 Summer Training Report on Unnao Sub Station

Embed Size (px)

Citation preview

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    1/59

    VOCATIONAL TRAINING

    ON

    UTTAR PRADESH POWER

    TRANSMISSION CORPORATIONLIMETED

    For

    The partial fulfillment of award

    Of

    B.TECH. Degree

    By

    SHAILENDRA YADAV

    (0705420096)

    Electrical Engineering(Final Year)

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    2/59

    ACKNOWLEDGEMENT

    I am extremely thankful & indebted to the numerous UPPTCL Engineers, who providedvital information about the functioning of their respective departments thus helping me to

    gain an overall idea about the working of organization. I am highly thankful for the support

    & guidance of each of them.

    I am highly indebted to my project guide, Mr. Ramlal(A.E.), Mr. Mevalal(J.E.), Mr.

    P.K. Mishra (A.E.-T&C) for giving me his valuable time and helping me to grasp the various

    concepts of switchyard equipments and their control instruments and their testing.

    Last but not the least, I would like to thank my parents & all my fellow trainees who

    have been a constant source of encouragement & inspiration during my studies & have

    always provided me support in every walk of life.

    SHAILENDRA YADAV

    B.TECH. FINAL YEAR

    ELECTRICAL ENGINEERING

    B.B.D.N.I.T.M. (LUCKNOW)

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    3/59

    Contents

    What is an Electrical Substation?

    Energy growth in UP

    Grid map of UP

    Introduction: about substation

    Overview of substation

    Single line digram of substation

    Brief description : Power transformer

    Isolators

    Circuit breaker

    Lightning arrestor

    Current transformer

    Capacitor voltage transformer

    Wave trap Protective relays

    Shunt reactor for bus voltage

    Capacitor bank

    Clearance at glance Power line communication & SCADA system

    Other definitions

    Appendix

    References

    http://answers.yahoo.com/question/index?qid=20080507043529AAzol6lhttp://answers.yahoo.com/question/index?qid=20080507043529AAzol6l
  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    4/59

    What is a n Electrical Substation

    Electric Power is generated in Power Stations and transmitted to various cities and towns. During

    transmissions, there are power (energy) loss and the whole subject of Transmission and

    Distribution...

    An electrical substation is a subsidiary station of an electricity generation, transmission and

    distribution system where voltage is transformed from high to low or the reverse using

    transformers. Electric power may flow through several substations between generating plant and

    consumer, and may be changed in voltage in several steps.

    The word substation comes from the days before the distribution system became a grid. The first

    substations were connected to only one power station where the generator was housed, and were

    subsidiaries of that power station.

    Elements of a substation

    Substations generally have switching, protection and control equipment and one or more

    transformers. In a large substation, circuit breakers are used to interrupt any short-circuits or

    overload currents that may occur on the network. Smaller distribution stations may use reclose

    circuit breakers or fuses for protection of distribution circuits. Substations do not usually have

    generators, although apower plant may have a substation nearby. Other devices such as power

    factor correctioncapacitors andvoltage regulatorsmay also be located at a substation.

    Substations may be on the surface in fenced enclosures, underground, or located in special-

    purpose buildings. High-rise buildings may have several indoor substations. Indoor substations are

    usually found in urban areas to reduce the noise from the transformers, for reasons of

    appearance, or to protect switchgear from extreme climate or pollution conditions.

    Where a substation has a metallic fence, it must be properly grounded (UK: earthed) to protect

    people from high voltages that may occur during a fault in the network. Earth faults at a substation

    can cause a ground potential rise. Currents flowing in the Earth's surface during a fault can cause

    metal objects to have a significantly different voltage than the ground under a person's feet; this

    touch potentialpresents a hazard of electrocution.

    http://answers.yahoo.com/question/index?qid=20080507043529AAzol6lhttp://www.ask.com/wiki/Electricity?qsrc=3044http://www.ask.com/wiki/Electricity?qsrc=3044http://www.ask.com/wiki/Electrical_generation?qsrc=3044http://www.ask.com/wiki/Electric_power_transmission?qsrc=3044http://www.ask.com/wiki/Electricity_distribution?qsrc=3044http://www.ask.com/wiki/Voltage?qsrc=3044http://www.ask.com/wiki/Transformer?qsrc=3044http://www.ask.com/wiki/Electrical_power_transmission?qsrc=3044http://www.ask.com/wiki/Power_station?qsrc=3044http://www.ask.com/wiki/Circuit_breakers?qsrc=3044http://www.ask.com/wiki/Short-circuit?qsrc=3044http://www.ask.com/wiki/Autorecloser?qsrc=3044http://www.ask.com/wiki/Autorecloser?qsrc=3044http://www.ask.com/wiki/Fuse_(electrical)?qsrc=3044http://www.ask.com/wiki/Power_plant?qsrc=3044http://www.ask.com/wiki/Power_factor_correction?qsrc=3044http://www.ask.com/wiki/Power_factor_correction?qsrc=3044http://www.ask.com/wiki/Capacitor?qsrc=3044http://www.ask.com/wiki/Voltage_regulator?qsrc=3044http://www.ask.com/wiki/Voltage_regulator?qsrc=3044http://www.ask.com/wiki/Ground_(electricity)?qsrc=3044http://www.ask.com/wiki/Earth_potential_rise?qsrc=3044http://answers.yahoo.com/question/index?qid=20080507043529AAzol6lhttp://www.ask.com/wiki/Electricity?qsrc=3044http://www.ask.com/wiki/Electrical_generation?qsrc=3044http://www.ask.com/wiki/Electric_power_transmission?qsrc=3044http://www.ask.com/wiki/Electricity_distribution?qsrc=3044http://www.ask.com/wiki/Voltage?qsrc=3044http://www.ask.com/wiki/Transformer?qsrc=3044http://www.ask.com/wiki/Electrical_power_transmission?qsrc=3044http://www.ask.com/wiki/Power_station?qsrc=3044http://www.ask.com/wiki/Circuit_breakers?qsrc=3044http://www.ask.com/wiki/Short-circuit?qsrc=3044http://www.ask.com/wiki/Autorecloser?qsrc=3044http://www.ask.com/wiki/Autorecloser?qsrc=3044http://www.ask.com/wiki/Fuse_(electrical)?qsrc=3044http://www.ask.com/wiki/Power_plant?qsrc=3044http://www.ask.com/wiki/Power_factor_correction?qsrc=3044http://www.ask.com/wiki/Power_factor_correction?qsrc=3044http://www.ask.com/wiki/Capacitor?qsrc=3044http://www.ask.com/wiki/Voltage_regulator?qsrc=3044http://www.ask.com/wiki/Ground_(electricity)?qsrc=3044http://www.ask.com/wiki/Earth_potential_rise?qsrc=3044
  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    5/59

    Transmission substation:

    A transmission substation connects two or more transmission lines. The simplest case is where

    all transmission lines have the same voltage. In such cases, the substation contains high-voltageswitches that allow lines to be connected or isolated for fault clearance or maintenance. A

    transmission station may have transformersto convert between two transmission voltages, voltage

    control devices such as capacitors, reactors or static VAr compensator and equipment such as

    phase shifting transformers to control power flow between two adjacent power systems.

    Transmission substations can range from simple to complex. A small "switching station" may be

    little more than a busplus some circuit breakers. The largest transmission substations can

    cover a large area (several acres/hectares) with multiple voltage levels, many circuit

    breakers and a large amount of protection and control equipment (voltage and current

    transformers, relays and SCADAsystems).

    Distribution substation:

    A distribution substation in Scarborough, Ontario, Canada disguised as a house, complete with a

    driveway, front walk and a mown lawn and shrubs in the front yard. A warning notice can be

    clearly seen on the "front door".

    A distribution substation transfers power from the transmission system to the distribution system

    of an area. It is uneconomical to directly connect electricity consumers to the high-voltage main

    transmission network, unless they use large amounts of power, so the distribution station reduces

    voltage to a value suitable for local distribution.

    The input for a distribution substation is typically at least two transmission or sub transmissionlines. Input voltage may be, for example, 115 kV, or whatever is common in the area. The output is

    a number of feeders. Distribution voltages are typically medium voltage, between 2.4 and 33 kV

    depending on the size of the area served and the practices of the local utility.

    Energy growth in UP:

    http://www.ask.com/wiki/Transformers?qsrc=3044http://www.ask.com/wiki/Transformers?qsrc=3044http://www.ask.com/wiki/Voltage_compensation?qsrc=3044http://www.ask.com/wiki/Voltage_compensation?qsrc=3044http://www.ask.com/wiki/Static_VAr_compensator?qsrc=3044http://www.ask.com/wiki/Quadrature_booster?qsrc=3044http://www.ask.com/wiki/Electrical_bus?qsrc=3044http://www.ask.com/wiki/Circuit_breakers?qsrc=3044#High-voltage_circuit_breakershttp://www.ask.com/wiki/Transformer?qsrc=3044#Instrument_transformershttp://www.ask.com/wiki/Digital_protective_relay?qsrc=3044http://www.ask.com/wiki/SCADA?qsrc=3044http://www.ask.com/wiki/Transformers?qsrc=3044http://www.ask.com/wiki/Voltage_compensation?qsrc=3044http://www.ask.com/wiki/Voltage_compensation?qsrc=3044http://www.ask.com/wiki/Static_VAr_compensator?qsrc=3044http://www.ask.com/wiki/Quadrature_booster?qsrc=3044http://www.ask.com/wiki/Electrical_bus?qsrc=3044http://www.ask.com/wiki/Circuit_breakers?qsrc=3044#High-voltage_circuit_breakershttp://www.ask.com/wiki/Transformer?qsrc=3044#Instrument_transformershttp://www.ask.com/wiki/Digital_protective_relay?qsrc=3044http://www.ask.com/wiki/SCADA?qsrc=3044
  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    6/59

    Grid map of UP:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    7/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    8/59

    Introduction: about substation

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    9/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    10/59

    As we said earlier the whole substation is divided in three parts:132kv site ,400/220kv site and 765

    kv site 765 kv sit is on under construction. The civil work is completing by L&T Company. Other

    part of project Design, Engineering, Manufacture, Supply, Erection, Testing and Commissioning of

    Bays will complete by CGL.

    In 400/220kv switchyard following outdoor instrument used:

    1. One 400kv transfer bus control bus coupler

    2. Two 100MVA 220/132kv autotransformer

    3. Two 315MVA 400/220kv autotransformer

    4. Five 50MVAR shunt reactor

    5. Two 63MVAR bus reactor

    6. 15 lighting tower

    7. SF6 circuit breaker

    8. Capacitor voltage transformer(CVT)

    9. Current transformer(CT)

    In switchyard one room for mulsi fire system and one for generator system is also present.

    In 400kv switchyard following lines are present for incoming and outgoing power:

    i) Unnao to Lucknow

    ii) Unnao to Bareily-1

    iii) Unnao to Bareily-2

    iv) Unnao to Agara

    v) Unnao to Panki kanpur

    vi) Unnao to Anpara

    vii) Unnao to PGCIL-1

    viii) Unnao to PGCIL-2

    ix) One bus bar for 400/220kv 315MVA ICT-1 & ICT-2 line.

    The buses of 400kv switchyard charged by Unnao - Anpara line. This line is the Indias first line

    which is made for 765KV transmission. But till today it is charged by 400kv. In futureit work on 765

    kv .

    From 220kv switchyard two lines for Lucknow and two lines for Panki Kanpur comes out.

    In whole switchyard following main equipment are used:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    11/59

    i) One 400kv transfer bus control bus coupler.

    ii) Two 100MVA 220/132 KV auto transformer manufactured from BHEL.

    iii) Two 315 MVA 400/220 KV auto transformer manufactured from BHEL.

    iv) Five 50 MVAR shunt reactor manufactured from BHEL.

    v) Two 63 MVAR bus reactor manufactured from HITACTI.

    vi) Circuit breaker from CGL.

    vii) Isolators from S&S.

    viii) Current transformer from WS and CGL.

    ix) CVT

    x) Wave trap

    xi) Lighting arrester

    xii)Surge capacitor

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    12/59

    Single line diagram of unnao substation

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    13/59

    Brief Description

    Of all

    Outdoor Equipment

    Power transformer:

    Various types of transformers have been provided at 220& 400 KV Substation from UPPTCL.

    Capacity and voltage ratio wise 100 MVA , 315MVA & 160 MVA and 220/132/11 kV. 400/220 kV,

    These transformers are of TELK, BHEL, GEC, NGEF, C & G, Hitachi and Bharat Bijlee make and

    have most of the features common except few accessories which may be different. In this

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    14/59

    substation all transformers made by BHEL. These

    transformers have following main components:

    1. MAIN CORE & WINDING.

    2. BUSHING :-

    (a) 220 kV High voltage bushings:

    Condenser type bushings with insulating body and central conducting tube-

    backelised with paper wound capacitor have been provided. Innermost of the

    capacitor layer is electrically connected to the tube and outermost to the mounting

    flange on insulating body. The central tube insulating body and mounting flange are

    oil filled assembled. High dielectric Strength oil is filled between central tube and

    insulating body. Oil level indicators are provided on the bushing.

    (b) 132 kV Medium voltage bushing:

    These bushing are also of condenser type and are of similar construction as in the

    case of 220 kV bushing in 200 MVA transformers.

    In 40 & 20 MVA transformers 132 kV bushings are also of oil filled type in which oil is

    filled up when the transformer tank is topped up. Necessary air vent screws are

    provided on top of the bushings for release of trapped air at the top of oil fitting.

    (c) 66 kV. 33 kV. & 11 kV. Bushings:

    These are oil filled bushing and simpler in construction.

    3. TAP CHANGER:

    The transformers have been provided with on load tap changer, which consists of diverterswitch installed in an oil compartment separated from transformer oil and the tap selector

    mounted below it. The tap changer is attached to the transformer cover by means of tap

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    15/59

    changer head, which also serves for connecting the driving shaft and the oil conservator.

    4. PROTECTIVE RELAYS:

    Generally there are two protective buchholz relays, one for main transformer tank and other

    for tap changer.

    In 40MVA GEC transformers oil surge relay has also been provided in tap changer.

    5. PRESSURE RELIEF VALVE:

    40 MVA GEC make transformers have been provided with pressure relief valve which

    operates in case of sudden pressure formation in side the transformer.

    6. COOLING SYSTEM :

    100 MVA transformers have been provided with cooling bank installed on separate

    structures. These cooling banks have provided with to groups of fans and 2 nos. pumps.

    These fans and pumps automatically operate, depending upon the settings of winding

    temperature Indicator.

    7. TERTIARY BUSING:

    100 MVA transformers have been provided with tertiary bushing connected with 11 kv

    capacitor and lighting arrestor t absorb switching surges.

    ELECTRICAL PROTECTION :

    The following electrical protection have been provided on the transformers :-

    (i) Differential Protection(ii) Restricted Earth Fault

    (iii) Winding temp high

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    16/59

    (iv) Oil temp high

    (v) Pressure relief valve

    (vi) Oil surge relay

    (vii) Over current relay

    (viii) Local Breaker Back up protection

    (ix) Surge arrestors on HV, MV & LV sides.

    The main Tank - The transformer is transported on trailor to substation site and as far as

    possible directly unloaded on the plinth. Transformer tanks up to 25 MVA capacity are

    generally oil filled, and those of higher capacity are transported with N2 gas filled in them

    +ve pressure of N2 is maintained in transformer tank to avoid the ingress of moisture. This

    pressure should be maintained during storage; if necessary by filling N2 Bushings -

    generally transported in wooden cases in horizontal position and should be stored in that

    position. There being more of Fragile material, care should be taken while handling them.

    Rediators These should be stored with ends duly blanked with gaskets and end plates to

    avoid in gross of moisture, dust, and any foreign materials inside. The care should be taken

    to protect the fins of radiators while unloading and storage to avoid further oil leakages.

    The radiators should be stored on raised ground keeping the fins intact. Oil Piping. The Oil

    piping should also be blanked at the ends with gasket and blanking plates to avoid in gross

    of moisture, dust, and foreign

    All other accessories like temperature meters, oil flow indicators, PRVs, buchholtz relay;

    oil surge relays; gasket O rings etc. should be properly packed and stored indoor in store

    shed. Oil is received in sealed oil barrels . The oil barrels should be stored in horizontal

    position with the lids on either side in horizontal position to maintain oil pressure on them

    from inside and subsequently avoiding moisture and water ingress into oil. The

    transformers are received on site with loose accessories hence the materials should be

    checked as per bills of materials.

    The transformers that are used in Unnao substation have following specification:

    Specification of 100 MVA 220/132/11 KV 3- auto transformer:

    Types of cooling ONAN ONAF OFAF

    Rating of H.V. & I.V.(MVA) 60 80 100

    Rating of L.V. (MVA) 18 24 30

    Line current H.V.(Amps) 157.4 209.9 262.4

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    17/59

    Line current I.V. (Amps) 262.4 349.9 437.4

    Line current L.V. (Amps) 944.8 1259.7 1574.6

    No load voltage H.V. 220KV

    No load voltage I.V. 132KV

    No load voltage L.V. 11KV

    Temp. Rise winding C 55 55 60

    [ Above ambient of 50 C ]

    Temp. rise oil C 50 [ Above ambient of 50 C ]

    Phase 3

    Frequency 50Hz

    Connection symbol YNa0d11

    Insulation level:

    H. V. - LI950 AC395-AC38

    L. V. - LI170 AC70

    I. V. - LI550-AC230-AC38

    Core & winding (Kg.) 54000

    Weight of oil (Kg.) 39410

    Total weight (Kg.) 127995

    Oil quantity (liters) 45300

    Transport weight (Kg. ) 69000

    Untanking weight (Kg.) 54000

    Specification of 315 MVA 400/220 KV 3- auto transformer:

    Types of cooling ONAN ONAF OFAF

    Rating of H.V. & I.V.(MVA) 189 252 315

    Rating of L.V. (MVA) 105 105 105

    Line current H.V.(Amps) 272.76 363.68 454.6

    Line current I.V. (Amps) 495.96 661.28 826.6

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    18/59

    Line current L.V. (Amps) 837.0 1857.0 1837.0

    No load voltage H.V. 400KV

    No load voltage I.V. 220KV

    No load voltage L.V. 33KV

    Temp. Rise winding C 55 55 60

    [ Above ambient of 50 C ]

    Temp. rise oil C 50 [ Above ambient of 50 C ]

    Phase 3

    Frequency 50Hz

    Connection symbol YNa0d11

    Insulation level:

    H. V. - LI950 AC395-AC38

    L. V. - LI170 AC70

    I. V. - LI550-AC230-AC38

    Oil quantity (liters) : 84550 liter

    Impedance volt

    315 MVA Base

    H.V. position 9/L.V. 71.81%

    H.V. position 9/I.V. 11.47%I.V./L.V. 67.92%

    Vector group:

    1U

    N 2U

    3U

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    19/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    20/59

    In the substation following type isolators are used for the protection:

    Horizontal break center rotating double break isolator:

    This type of construction has three insulator stacks per pole. The two one each side is fixed and

    one at the center is rotating type. The central insulator stack can swing about its vertical axis

    through about 900C. The fixed contacts are provided on the top of each of the insulator stacks on

    the side. The contact bar is fixed horizontally on the central insulator stack. In closed position, the

    contact shaft connects the two fixed contacts. While opening, the central stack rotates through

    900C, and the contact shaft swings horizontally giving a double break.

    The isolators are mounted on a galvanized rolled steel frame. The three poles are interlocked by

    means of steel shaft. A common operating mechanism is provided for all the three poles. One pole

    of a triple pole isolator is closed position.

    Pantograph isolator:

    illustrates the construction of a typical pantograph isolator. While closing, the linkages of

    pantograph are brought nearer by rotating the insulator column. In closed position the upper two

    arms of the pantograph close on the overhead station bus bar giving a grip. The current is carriedby the upper bus bar to the lower bus bar through the conducting arms of the pantograph. While

    opening, the rotating insulator column is rotated about its axis. Thereby the pantograph blades

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    21/59

    collapse in vertical plane and vertical isolation is obtained between the line terminal and

    pantograph upper terminal.

    Pantograph isolators cover less floor area. Each pole can be located at a suitable point and the

    three poles need not be in one line, can be located in a line at desired angle with the bus axis.

    Isolator with earth switches (ES):

    The instrument current transformer (CT) steps down the current of a circuit to a lower value and is

    used in the same types of equipment as a potential transformer. This is done by constructing the

    secondary coil consisting of many turns of wire, around the primary coil, which contains only a few

    turns of wire. In this manner, measurements of high values of current can be obtained. A current

    transformer should always be short-circuited when not connected to an external load. Because the

    magnetic circuit of a current transformer is designed for low magnetizing current when under

    load, this large increase in magnetizing current will build up a large flux in the magnetic

    Panto ra h isolator

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    22/59

    circuit and cause the transformer to act as a step-up transformer, inducing an excessively

    high voltage in the secondary when under no load.

    The main use of using the earth switch (E/S) is to ground the extra voltage which may b

    dangerous for any of the instrument in the substation.

    Circuit breaker:

    A circuit breaker is an automatically-operated electricalswitch designed to protect an electrical

    circuit from damage caused by overload or short circuit. Its basic function is to detect a fault

    condition and, by interrupting continuity, to immediately discontinue electrical flow. Unlike a fuse,

    which operates once and then has to be replaced, a circuit breaker can be reset (either manually

    or automatically) to resume normal operation. Circuit breakers are made in varying sizes, from

    small devices that protect an individual household appliance up to large switchgeardesigned to

    http://en.wikipedia.org/wiki/Electricityhttp://en.wikipedia.org/wiki/Switchhttp://en.wikipedia.org/wiki/Electrical_networkhttp://en.wikipedia.org/wiki/Electrical_networkhttp://en.wikipedia.org/wiki/Electrical_networkhttp://en.wikipedia.org/wiki/Overcurrenthttp://en.wikipedia.org/wiki/Short_circuithttp://en.wikipedia.org/wiki/Fuse_(electrical)http://en.wikipedia.org/wiki/Switchgearhttp://en.wikipedia.org/wiki/Electricityhttp://en.wikipedia.org/wiki/Switchhttp://en.wikipedia.org/wiki/Electrical_networkhttp://en.wikipedia.org/wiki/Electrical_networkhttp://en.wikipedia.org/wiki/Overcurrenthttp://en.wikipedia.org/wiki/Short_circuithttp://en.wikipedia.org/wiki/Fuse_(electrical)http://en.wikipedia.org/wiki/Switchgear
  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    23/59

    protect high voltage circuits feeding an entire city. Once a fault is detected, contacts within the

    circuit breaker must open to interrupt the circuit; some mechanically-stored energy (using

    something such as springs or compressed air) contained within the breaker is used to separate

    the contacts, although some of the energy required may be obtained from the fault current itself.

    Small circuit breakers may be manually operated; larger units have solenoids to trip the

    mechanism, and electric motors to restore energy to the springs.

    The circuit breaker contacts must carry the load current without excessive heating, and must also

    withstand the heat of the arc produced when interrupting the circuit. Contacts are made of copper

    or copper alloys, silver alloys, and other materials. When a current is interrupted, an arc is

    generated. This arc must be contained, cooled, and extinguished in a controlled way, so that the

    gap between the contacts can again withstand the voltage in the circuit. Different circuit breakers

    use vacuum, air, insulating gas or oil as the medium in which the arc forms. Different techniques

    are used to extinguish the arc including:

    Lengthening of the arc

    Intensive cooling (in jet chambers)

    Division into partial arcs

    Zero point quenching (Contacts open at the zero current time crossing of the AC waveform,

    effectively breaking no load current at the time of opening. The zero crossing occures at

    twice the line frequency i.e. 100 times per second for 50Hz ac and 120 times per second for

    60Hz ac )

    Connecting capacitors in parallel with contacts in DC circuits

    Finally, once the fault condition has been cleared, the contacts must again be closed to restore

    power to the interrupted circuit.

    Types of circuit breaker:

    Many different classifications of circuit breakers can be made, based on their features such as

    voltage class, construction type, interrupting type, and structural features.

    Electrical power transmission networks are protected and controlled by high-voltage breakers. The

    definition ofhigh voltage varies but in power transmission work is usually thought to be 72.5 kV or

    higher, according to a recent definition by the International Electrotechnical Commission(IEC).

    http://en.wikipedia.org/wiki/Solenoidhttp://en.wikipedia.org/wiki/Solenoid
  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    24/59

    High-voltage breakers are nearly always solenoid-operated, with current sensing protective relays

    operated through current transformers. In substations the protection relay scheme can be

    complex, protecting equipment and busses from various types of overload or ground/earth fault.

    High-voltage breakers are broadly classified by the medium used to extinguish the arc.

    Bulk oil

    Minimum oil

    Air blast

    Vacuum

    SF6

    In unnao substation only SF6 circuit breaker is used. The breaker uses SF6 (Sulpher Hexa

    fluoride) gas for arc extinction purpose. This gas has excellent current interrupting and insulating

    properties, chemically, it is one of the most stable compound in the pure state and under normal

    condition it is physically inert, non-flammable, non toxic and odorless and there is no danger te

    personnel and fire hazard. It's density is about. 5 times that of air insulating strength is about 2-3

    times that of air and exceeds that of oil at 3 Kg/Cm pressure.

    SF6 breaker called as maintenance free breaker, has simple construction with few moving parts:

    The fission products created during breaking and not fully recombined are, either precipitated as

    metallic fluoride or absorbed by a static filter which also absorbs the residual moisture.

    Since no gas is exhausted from the breaker and very little compressed air is required for

    operation, noise during the operation is also very Jess.

    Since SF6 gas is inert and stable at normal temperature, contacts do not settler from oxidization or

    other chemical reactions, whereas in air or oil type breakers oxidation of contacts would cause

    high temperature rise. SF6 gas circuit breakers, designed to conform to the same standards as air

    or oil breakers, but in operation it is possible to get better service even at higher fault levels.

    Sulphur hexafluoride gas is prepared by burning coarsely crushed roll sulphur in the fluorine gas,

    in a steel box, provided with staggered horizontal shelves, each bearing about 4 kg of sulphur. The

    steel box is made gas tight. The gas thus obtained contains other fluorides such as S2F10, SF4

    and must be purified further SF6 gas generally supplier by chemical firms. The cost of gas is low if

    http://en.wikipedia.org/wiki/Sulfur_hexafluoridehttp://en.wikipedia.org/wiki/Sulfur_hexafluoridehttp://en.wikipedia.org/wiki/Sulfur_hexafluoridehttp://en.wikipedia.org/wiki/Sulfur_hexafluoride
  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    25/59

    manufactured in large scale.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    26/59

    During the arcing period SF6 gas is blown axially along the arc. The gas removes the heat fromthe arc by axial convection and radial dissipation. As a result, the arc diameter reduces during thedecreasing mode of the current wave. The diameter becomes small during the current zero andthe arc is extinguished. Due to its electro negativity, and low arc time constant, the SF6 gasregains its dielectric strength rapidly after the current zero, the rate of rise of dielectric strength isvery high and the time constant is very small.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    27/59

    Fig: SF6 circuit breaker.

    Gas circuit breaker: high voltage side

    Type 220-SFM-20B

    Voltage rating: 220kv

    Rated lightening impulse withstand voltage: 1050 kVp

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    28/59

    Rated short circuit breaker current: 40 kV

    Rated operating pressure: 16.5 kg/ cm2g

    First pole to clear factor 1.3

    Rated duration of short circuit current is 40 kA for 30 sec.

    Rated ling charging breaker breaking current 125 Amp

    Rated voltage 245 kV

    Rated frequency 50 Hz

    Rated normal current 1600 Amp

    Rated closing voltage: 220 V dc

    Rated opening voltage 220 V dc

    Main parts:

    (a) Power circuit(b) Control circuit

    Gas circuit breaker: low voltage side

    Type 120-SFM-32A

    Voltage rating: 220kv

    Rated lightening impulse withstand voltage: 650 kVp

    Rated short circuit breaker current: 31.5 kV

    Rated operating pressure: 15.5 kg/ cm2g

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    29/59

    Lightning arrester:

    High Voltage Power System experiences overvoltages that arise due to natural lightning or the

    inevitable switching operations. Under these overvoltage conditions, the insulation of the power

    system equipment are subjected to electrical stress which may lead to catastrophic failure.

    Broadly, three types of overvoltages occur in power systems: (i) temporary over-voltages,(ii)

    switching overvoltages and(iii) lightning overvoltages.

    The duration of these overvoltages vary in the ranges of microseconds to sec depending upon the

    type and nature of overvoltages. Hence, the power system calls for overvoltage protective devices

    to ensure the reliability.

    Conventionally, the overvoltage protection is

    obtained by the use of lightning / surge arresters .

    Under normal operating voltages, the impedance

    of lightning arrester, placed in parallel to the

    equipment to be protected, is very high and allow

    the equipment to perform its respective function.

    Whenever the overvoltage appears across the

    terminals, the impedance of the arrester

    collapses in such a way that the power system

    equipment would not experience the overvoltage.

    As soon as the overvoltage disappears, the arrester recovers its impedance back. Thus the

    arrester protects the equipment from overvoltages.

    The technology of lightning arresters has undergone major transitions during this century. In the

    early part of the century, spark gaps were used to suppress these overvoltages. The siliconcarbide gapped arresters replaced the spark gaps in 1930 and reigned supreme till 1970. During

    the mid 1970s, zinc oxide (ZnO) gapless arresters, possessing superior protection characteristics,

    replaced the silicon carbide gapped arresters. Usage of ZnO arresters have increased the

    reliability of power systems many fold.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    30/59

    Current transformer:

    Current Transformers (CTs) are instrument transformers that are used to supply a reduced valueof current to meters,protective relays, and other instruments. CTs provide isolation from the high voltage primary,permitgrounding of the secondary for safety, and step-down the magnitude of the measured current to avalue that can besafely handled by the instruments.

    TECHNICAL SPECIFICATION FOR CURRENT TRANSFORMERS

    1.0 GENERAL

    1.1 This specification covers manufacture, test, & supply of LT Current transformers ofclass 0.5 accuracy.

    1.2 The CTs shall be suitable for metering purpose.

    2.0 TYPE:

    2.1 The CTs shall be of ring type or window type (bar type or bus-bar type CTs shall not beaccepted).

    2.2 The secondary leads shall be terminated with Tinned Cooper rose contact terminals witharrangements for sealing purposes.

    2.3 Polarity (both for primary and second leads) shall be marked.

    2.4 The CTs shall be varnished, fiberglass tape insulated or cast resin, air-cooled type. Only superenameled electrolytic grade copper wires shall be used.

    2.5 The CTs shall conform to IS 2705:Part-I & II/IEC:185 with latest amendments.

    3.0 TECHNICAL DETAILS:

    3.1 Technical details shall be as given below:

    1. Class of Accuracy 0.52. Rated Burden 5.00 VA3. Power Frequency Withstand

    Voltage3KV

    4. Highest System Voltage 433 V

    5. Nominal System Voltage 400 V6. Frequency 50 Hz7. Supply System 3 Ph. Solidly grounded Neutral

    System

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    31/59

    3.2 Transformation ratio shall be specified from the following standard ratings as per requirement :

    Ratio 50/5 150/5 300/5 400/5 1000/5

    (Secondary with 1 A may be specified by the utility incase the same is desired.)

    3.3 Bore diameter of the CT shall not be less than 40 mm. Ring type CTs shall have suitable

    clamp to fix the CT to panel Board, wherever required.

    3.4 The limits of current error and phase angle displacement as per IS:2705 at several defined

    percentage of rated current are:

    Accuracy

    Class

    % Ratio error at % of

    rated current

    Phase displacement in minutes

    at % of rated current

    5 20 100 120 5 20 100 1200.5 1.5 0.75 0.5 0.5 90 45 30 30

    Note : Current error and phase displacement at rated frequency is required to be as above when

    the secondary burden from 25% to 100% of the rated burden i.e. 50 V A.

    3.5 Rated extended primary current shall be 120% of rated primary Current in accordance with

    IS:2705 Pt-II.

    3.6 Rated ISF (Instrument Security Factor) shall be declared by the manufacturer & marked on the

    CT.

    3.7CTs shall be made with good engineering practices. Core winding shall evenly spread stress &

    avoid stress concentration at any one point. Cast resin CTs sha;; be processed by hot curing

    method under controlled vacuum conditions.

    3.8 The base shall be of hot dip galvanized steel.

    4.0 TESTS:

    4.1. TYPE TESTS:

    4.1.1 Copies of all type tests as per IS.2705 Part-I and II including short time current &

    temperature rise tests in NABL accredited laboratory shall be submitted and got approved before

    commencement of supply.

    4.2 ROUTINE TESTS:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    32/59

    4.2.1 The supplier shall conduct all the routine tests such as Ratio test, phase angle error test for

    0.5 accuracy class as per IS 2705 Part I & II.

    4.3 Commissioning test :

    4.3.1 In accordance with IS:2705, Power frequency test on primary winding shall be carried out

    after erection on site on sample basis.

    5.0 Marking :

    5.1 The CTs shall have marking and nameplate as per IS 2705 in addition to class of insulation &

    ISF. The markings shall be indellible. The nameplate shall be securely fixed to the body of the CT.

    6.0 PACKING:

    6.1 Each CT shall be securely packed so as to withstand rough handling during transit and

    storage.

    7.0 QUALITY ASSURANCE PLAN:

    7.1 The requirements of clause 29.0 of Section I of

    main specification for Energy Meters shall apply.

    Wave trap

    Current transformer

    Current transformer rating table for all cores:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    33/59

    CTNaming

    Ratio BurdenVA

    KneepointVoltage

    V(min.)

    Mag.Current

    at

    KpvmA(max)

    Class Sec.resistance

    Purpose

    1CT 1N 500/1 - 300 40AT Vk/2 PS 5 REF

    1CT 1U11CT 1V11CT

    1W1

    500/1 - 300 40AT Vk/2 PS 5 REF

    1CT 2U11CT 2V11CT2W1

    500/1 - 300 40AT Vk/2 PS 5 REF

    1CT 3U11CT 3V11CT3W1

    2000/1 - 600 30AT Vk/2 PS 5 Differenti

    al

    2CT 3U12CT 3V12CT3W1

    2000/1 - 300 40AT Vk/2 PS 5 Spare

    3CT 3U13CT 3V13CT3W1

    2000/1 30VA - - 1.0 5 Metering

    WCT

    1U2

    198/3.0

    -2.5

    1.7VA - - 5 - WTT+RT

    D

    Capacitor voltage transformer:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    34/59

    In high and extra high voltage transmission systems, capacitor voltage transformers (CVTs) are

    used to provide potential outputs to metering instruments and protective relays. In addition, when

    equipped with carrier accessories, CVTs can be used for power line carrier (PLC) coupling.

    A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra

    high voltage signals and provide low voltage signals either for measurement or to operate a

    protective relay. In its most basic form the device consists of three parts: two capacitors across

    which the voltage signal is split, an inductive element used to tune the device to the supply

    frequency and a transformer used to isolate and further step-down the voltage for the

    instrumentation or protective relay. The device has at least four terminals, a high-voltage terminal

    for connection to the high voltage signal, a ground terminal and at least one set of secondary

    terminals for connection to the instrumentation or protective relay. CVTs are typically single-phase

    devices used for measuring voltages in excess of one hundred kilovolts where the use of voltage

    transformers would be uneconomical. In practice the first capacitor, C 1, is often replaced by a

    stack of capacitors connected in series. This results in a large voltage drop across the stack of

    capacitors that replaced the first capacitor and a comparatively small voltage drop across the

    second capacitor, C2, and hence the secondary terminals.

    INSULATING SYSTEMS:

    The external insulation is provided by the porcelain housing and coordinated with the capacitor

    stack, consisting of virtually identical elements so that the axial voltage distribution from the line

    terminal to ground is essentially uniform. The capacitor elements have a mixed dielectric material

    consisting of alternating layers of polypropylene film and Kraft paper. The Kraft paper layers serve

    as a wicking agent to ensure homogenous synthetic oil impregnation. The electromagnetic unit

    (EMU) is housed in an oil-filled tank at the base of the capacitor stack. Mineral oil is employed as

    the insulating medium instead of air because of its superior insulating and heat transfer properties.

    The use of an oil-filled base tank removes the need for space heaters in the secondary terminal

    box as this area is warmed by heat transfer from the insulating oil. This results in a more reliable

    and cost effective design.

    INSULATING OIL:

    We use insulating oils with excellent dielectric strength, aging, and gas absorbing properties. The

    synthetic oil used for the capacitor units possesses superior gas absorption properties resulting inexceptionally low partial discharge with high inception/extinction voltage ratings. The oil used for

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    35/59

    the EMU is premium naphthenic mineral oil. The oil is filtered, vacuum dried and degassed within

    house processing. It contains no PCB.

    CAPACITOR STACK:

    The capacitor stack is a voltage divider which provides a reduced voltage at the intermediate

    voltage bushing for a given voltage applied at the primary terminal. The capacitor stack is a multi-

    capacitor-unit assembly. Each unit is housed in an individual insulator. A cast aluminum

    cover is on top of the upper capacitor assembly and is fitted with an aluminum terminal. An

    adapter for mounting a line trap on top of the CVT can be

    provided with an optional (and removable) HV terminal.

    The capacitor units are mechanically coupled together by

    means of stainless steel hardware passing through the

    corrosion resistant cast aluminum housing. The mechanical

    connection also establishes the electrical connection between

    capacitor units. This facilitates field assembly of the CVT

    .

    1 - Primary terminal

    2 - Cast aluminum bellow housing

    3 - Stainless steel expansionbellow

    4 - Compression spring

    5 - Insulated voltage connection

    6 - Capacitor elements

    7 - Insulator (porcelain orcomposite)

    8 - Voltage divider tap connection

    9 - Cast-epoxy bushing

    10 - HF terminal connection

    11 - Ferro-resonance suppressiondevice

    12 - Secondary terminals

    13 - Oil level sight-glass

    14 - Aluminum terminal box

    15 - Intermediate transformer

    16 - Oil/air block

    17 - Oil sampling device

    18 - Compensating reactor

    19 - Aluminum cover plate

    1 - Primary terminal

    2 - Cast aluminum bellow housing

    3 - Stainless steel expansionbellow

    4 - Compression spring

    5 - Insulated voltage connection

    6 - Capacitor elements

    7 - Insulator (porcelain orcomposite)

    8 - Voltage divider tap connection

    9 - Cast-epoxy bushing

    10 - HF terminal connection

    11 - Ferro-resonance suppressiondevice

    12 - Secondary terminals

    13 - Oil level sight-glass

    14 - Aluminum terminal box

    15 - Intermediate transformer

    16 - Oil/air block

    17 - Oil sampling device

    18 - Compensating reactor

    19 - Aluminum cover plate

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    36/59

    PRINCIPLE CIRCUIT DIAGRAM

    Wave trap:

    1. High Voltage terminal2. Compensation reactor

    3. Intermediate voltage transformer

    4. Ground terminal

    5. Ferro-resonance suppression

    device

    6. Damping resistor

    7. Carrier (HF) terminal (optional)

    8. Overvoltage protective device

    9. Secondary terminals

    10. Link, to be opened for test

    purposes

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    37/59

    Line trap also is known as Wave trap. What it does is trapping the high frequency communication

    signals sent on the line from the remote substation and diverting them to the telecom/teleportation

    panel in the substation control room (through coupling capacitor and LMU).

    This is relevant in Power Line Carrier Communication (PLCC) systems for communication among

    various substations without dependence on the telecom company network. The signals are

    primarily teleportation signals and in addition, voice and data communication signals.

    The Line trap offers high impedance to the high frequency communication signals thus obstructs

    the flow of these signals in to the substation busbars. If there were not to be there, then signal loss

    is more and communication will be ineffective/probably impossible.

    Construction:

    1. Main coil:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    38/59

    The main coil winding are encapsulated by winding continuous filament fiberglass

    That has been impregnated with a specially selected epoxy resin harden system. The epoxy resin

    fiberglass composite is then curved according to a programmed temperature Schedule.

    2. Tuning pack:

    Tuning pack is connected in parallel with the main coil to provide a high

    impedance to the desired carrier frequency.

    3. Lighting arresters:

    The line traps are protected by a lighting arrestors against high voltage surges

    caused by atmospheric effects or switching operations.

    Protective relays:

    Protective relaying is one of the several features of power system design.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    39/59

    Every part of the power system is protected. The protective relaying is used to give an alarm or to

    cause prompt removal of any element of power system from service when hat element behave

    abnormally.

    The relays are compact and self contained devices which can sense abnormal conditions.

    Whenever abnormal condition occur , the relays contacts get closed. This in turn closes the trip

    circuit of a circuit breaker.

    For switchyard protections following type relays are used:

    1. Overcurrent relay

    2. Earth fault relay

    3. REF relay

    4. Differential relay

    5. Directional relay

    6. Over flux relay

    7. Buchoolz relay

    8. IDMT relay

    Restricted earth fault protection relay:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    40/59

    The REF protection method is a type of "unit protection" applied to transformers or generators and

    is more sensitive than the method known as differential protection.

    An REF relay works by measuring the actual current flowing to earth from the frame of the unit. If

    that current exceeds a certain preset maximum value of milliamps (mA) then the relay will trip to

    cut off the power supply to the unit.

    Differential protection can also be used to protect the windings of a transformer by comparing the

    current in the power supply's neutral wire with the current in the phase wire. If the currents are

    equal then the differential protection relay will not operate. If there is a current imbalance then the

    differential protection relay operates.

    REF protection is applied on transformers in order to detect ground faults on a given winding more

    sensitively than differential protection.

    Directional relay:

    Directional relays have protection zones that include all of the power system situated in only one

    direction from the relay location. (This is in contrast to magnitude relays which are not directional,

    i.e., they trip based simply on the magnitude of the relay.

    Consider the one-line diagram in Fig. 1.

    Bus 1

    y

    Fig. 1If the relays R1 and R2 in Fig. 1 are directional relays, then

    - R1 looks to the left but not to the right, and

    - R2 looks to the right but not to the left.

    In order to understand how the directional relay works, first, consider that R2 measures the

    phasors V2 and I23. Now define the following parameters associated with Fig. 1:

    L23: length of circuit 2-3.

    x: distance from R2 to a fault on circuit 2-3.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    41/59

    x=x/L23: the fraction of the circuit length between the relay R2 and the fault at point x.

    I23: the current in circuit 2-3 resulting from the fault x on circuit 2-3 (a phasor).

    V2: the bus 2 voltage (a phasor).

    Z23: total series impedance of circuit 2-3.

    If a fault occurs on circuit 2-3, at point x, then the fraction of total circuit length is x. If the circuithas uniform impedance per unit length, then the impedance between the relay R2 and the fault

    point is xZ23, and with the bus 2 voltage being V2, the current flowing into circuit 2-3 from bus 2 is:

    23

    223

    Z

    VI

    x=

    (1)

    But recall that for transmission lines, it is generally the case that R

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    42/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    43/59

    If an arc forms, gas accumulation is rapid, and oil flows rapidly into the conservator. This flow of oiloperates a switch attached to a vane located in the path of the moving oil. This switch normally willoperate a circuit breaker to isolate the apparatus before the fault causes additional damage.Buchholz relays have a test port to allow the accumulated gas to be withdrawn for testing.

    IDMT relay:

    The IDMT relay work on the induction principle, where an aluminum or copper disc rotates

    between the poles of electromagnet and damping magnet. The fluxes induce eddy current in the

    disc which interact and produce rotational torque. The disc rotates to a point where it operates a

    pair of contact that breaks the circuit and removes the fault condition.

    Shunt reactor for bus voltage:

    In EHV substations, it is a common practice to use breaker switched bus reactors to maintain the

    bus voltage within permissible limits under varying load conditions. With the development of

    Controlled Shunt Reactor (CSR) which is a thyristor controlled high impedance transformer, a

    stable bus voltage can be maintained by providing variable reactive power based on the bus

    voltage deviations due to the load variations. The high impedance transformer which is also known

    as reactor transformer (RT) can be made to any size without any limitation unlike gapped core

    http://en.wikipedia.org/wiki/Electric_archttp://en.wikipedia.org/wiki/Circuit_breakerhttp://en.wikipedia.org/wiki/Electric_archttp://en.wikipedia.org/wiki/Circuit_breaker
  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    44/59

    shunt reactors. As a single CSR of large capacity can be realized with suitable control mechanism,

    this approach proves to be technically superior and economical compared to the existing practice

    of breaker switched bus reactors.

    A CSR with a detailed control system is modeled along with a typical EHV system in

    PSCAD/EMTDC environment. The study includes the effectiveness of filters introduced in the

    tertiary of the reactor transformer in controlling the harmonics generated during partial conduction

    of thyristors. The transient and steady state performance of the CSR system for varying system

    conditions is studied and the same is compared with the conventional practice. The paper

    presents and discusses the results of the study.

    Keywords: High impedance transformer, shunt reactor, reactive power, compensation, EHV

    systems, voltage control, thyristors. Shunt reactors which are meant to be used for controlling the

    bus voltage of sub station are known as bus reactors. These are always connected through a

    circuit breaker and switched on or off, based on the voltage variations. In large switching

    substations, it is not uncommon to find multiple bus reactors when the total reactor capacity

    required is large. Due to limited standard ratings of gapped core shunt reactors, it is necessary to

    provide in multiples of standard ratings along with associated bay equipment and space for

    accommodating the same. The CSR mentioned above is based on a high impedance transformer

    known as Reactor Transformer (RT) with a provision to control from the secondary side through

    thyristor valves. As RT of any large capacity can be realized as a single three phase unit or three

    single phase units, it is possible to provide variable reactive power support by controlling the firing

    angle of the thyristor valves. This continuously variable CSR as bus reactor offers following

    advantages.

    1. Continuously variable reactive power based on the voltage variation.

    2. Fast Response to dynamic conditions like load throw off

    3. Reduced losses with optimized reactive power support.

    4. Better economy in terms of substation space and auxiliary equipment.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    45/59

    Figure: shunt reactor

    Shunt capacitor bank:

    Shunt capacitor banks are used to improve the quality of the electrical supply and the efficient

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    46/59

    operation of the power system. Studies show that a flat voltage profile on the system can

    significantly reduce line losses. Shunt capacitor banks are relatively inexpensive and can be

    easily installed anywhere on the network. Shunt capacitor banks (SCB) are mainly installed to

    provide capacitive reactive compensation/

    Power factor correction. The use of SCBs has increased because they are relatively inexpensive,

    easy and quick to install and can be deployed virtually anywhere in the network. Its installation

    has other beneficial effects on the system such as: improvement of the voltage at the load, better

    voltage regulation (if they were adequately designed), reduction of losses and reduction or

    postponement of investments in transmission.

    The main disadvantage of SCB is that its reactive power output is proportional to the square of

    the voltage and consequently when the voltage is low and the system need them most, they are

    the least efficient.

    Figure

    Clearances At A Glance:

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    47/59

    Various clearances required to be maintained as per Indian Electricity Rules and Code ofpractice etc. during construction of a transmission line are given at appropriate places in variouschapters. However, for convenience, the various clearances required to be maintained in theconstruction of a transmission line at a glance are given in the following table:

    TABLE

    SI.

    No.

    Particulars Units

    Clearance required to be maintained for

    132 KV 220 KV 400 KV

    1. Live Metal Clearance

    (a) Suspension Towers mm 1525(0- 25 swing)1075(25 - 45 swing)

    2130 (0 - 20)1675 (20 -50")

    2600 (V - string)

    (b) Tension towers mm 1525 2130 2600

    2. Ground Clearance m 6.1 7.0 8.84

    3. Mid Span Clearance in 6.1 8.5 9.0

    4. Phase to PhaseClearance

    mm 3900 5130 7000

    5. Maximum ShieldingAngle

    30 30 30 20

    6. Power LineCrossing Clearancebetween Lines

    m 3.05 (from other linesof 11 KV to 132KV)

    4.58 (from otherlines of 11 KV to220 KV)

    6.10 (front other linesof 11-KV to 400KV)

    7. Clearance Between lines

    and Tramway Crossing

    m 3.05 3.05 3.05

    8. Clearance from Railway^

    Track

    m 14.60 15.40 17.90

    9. Prescribed Corridor forForest clearance etc.

    m 27.60 35.00 52.00

    10. Minimum Clearancesfrom Trees

    m 4.0 4.6 5.5

    11. Clearance over Rivers from HFL

    (i) Non Navigable River m 6.1 7.00 8.84

    (ii) Navigable River m To be maintained in relation to tallest mast in consolation withnavigation authorities

    12. Clearances from Buildings

    (a) Horizontal m 2.744 3.659 5.489

    (b) Vertical m 4.573 5.488 7.318

    13. Clearance overTelecommunication lines

    m 2.745 3.050 4.880

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    48/59

    Power line communication & SCADA system of UPPTCL:

    Uttar Pradesh Power Transmission Corporation Ltd. (UPPTCL) has a very large network of high

    voltage transmission lines in whole UP (about 24,000Km). Transmission lines transfer power from

    power houses to substations and from one substation to many other substations or vice versa.

    Power is generated at low Voltage (of the order of 3.3KV to 25KV) and is stepped-up to high

    voltage (765KV, 400KV, 220KV & 132KV) for evacuating power into the grid network through

    transmission lines.

    Transmission of Data

    Below in Figure 1, main equipment from substation/power house to its subLDC has been shownin a very simple form.

    Figure 1:Transmission of Data from substation/Power house to subLDC

    Current Transformers (CTs) and Potential Transformers (PTs), installed on transmission lines,provide inputs to transducers of SIC (Supervisory Interface & Control) & RTU (Remote TerminalUnit) panel. Circuit breakers & isolators' status are extended up to SIC panel. If for such extensionextra potential free contacts are not available in the Control Panels, Contact Multiplying Relays(CMRs) are used to provide potential free contacts. The output of RTU is connected to thecommunication equipment, through Modem. In between substation & subLDC, a communicationlink has been shown. Telephone exchanges are connected with the communication equipment.Such communication links can be of any type. UPPTCL has got its own three different type ofcommunication systems, i.e. PLCC (Power Line Carrier Communication), microwave and fibre-optic. PLCC system is more prevalent in UPPTCL. Modem output at receive side is connected

    with the CFE (Communication End Frame). Its output is connected with data takes over. EachRTU is automatically polled by Server of subLDC to obtain each data of repeats at least once in 10sec and is stored in the database of subLDC. This data is processed in database formats and isretrieved for different applications. These formats or graphics are displayed or printed as perrequirement. At subLDC, System Control Officers use this data to monitor and analyze position ofthe grid.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    49/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    50/59

    Voice Frequency (VF) channels of all these systems have been integrated/interconnected to make

    a hybrid communication system. Microwave & Fibre Optic are multi-channels communication

    systems and are also called 'Wideband communication system'. PLCC is single channel

    communication system.

    SCADA SYSTEM

    In SCADA system measured values, i.e. analogue (measured value) data (MW, MVAR, V, Hz

    Transformer tap position), and Open/Closed status information, i.e. digital data (Circuit

    Breakers/Isolators position i.e. on/off status), are transmitted through telecommunication channels

    to respective sub-LDCs. For this purpose Remote Terminal Units (RTUs) at 400KV, 220KV and

    few important 132KV sub-stations have been installed. System values & status information below

    132 KV have not been picked up for data transmission, except for 33KV Bus isolator position andLV side of generators. Secondary side of Current Transformers (CT) and Potential Transformer

    (PT) are connected with 'Transducers'. The output of transducers is available in dc current form (in

    the range of 4mA to 20mA). Analogue to digital converter converts this current into binary pulses.

    Different inputs are interleaved in a sequential form and are fed into the CPU of the RTU. The

    output of RTU, containing information in the form of digital pulses, is sent to subLDC through

    communication links. Depending upon the type of communication link, the output of RTU is

    connected, directly or through Modem, with the communication equipment. At subLDC end, data

    received from RTU is fed into the data servers. In general, a SCADA system consists of a

    database, displays and supporting programmes. In UPPTCL, subLDCs use all major functional

    areas of SCADA except the 'Supervisory Control/Command' function. The brief overview of major

    'functional areas' of SCADA system is as below:

    1. Communications - Sub-LDC's computer communicates with all RTU stations under its

    control, through a communication system. RTU polling, message formatting, polynomial

    checking and message retransmission on failure are the activities of 'Communications'

    functional area.

    2. Data Processing - After receipt of data through communication system it is processed.

    Data process function has three sub-functions i.e. (i) Measurements, (ii) Counters and (iii)

    Indications.

    'Measurements' retrieved from a RTU are converted to engineering units and linearised, if

    necessary. The measurement are then placed in database and are checked against various

    limits which if exceeded generate high or low limit alarms.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    51/59

    The system has been set-up to collect 'Counters' at regular intervals: typically 5 or 10

    minutes. At the end of the hour the units is transferred into appropriate hour slot in a 24-

    hour archive/history.

    'Indications' are associated with status changes and protection. For those statuses that are

    not classified as 'alarms', logs the change on the appropriate printer and also enter it into a

    cyclic event list. For those statuses, which are defined as an 'alarms' and the indication

    goes into alarm, an entry is made into the appropriate alarm list, as well as in the event list

    and an audible alarm is generated in the sub-LDC.

    3. Alarm/Event Logging - The alarm and event logging facilities are used by SCADA data

    processing system. Alarms are grouped into different categories and are given different

    priorities. Quality codes are assigned to the recently received data for any 'limit violation'

    and 'status changes'. Alarms are acknowledged from single line diagram (or alarm lists) on

    display terminal in LDCs.

    4. Manual Entry - There is a provision of manual entry of measured values, counters and

    indications for the important sub-station/powerhouse, which are uncovered by an RTU or

    some problem is going on in its RTU, equipment, communication path, etc.

    5. Averaging of Measured Values-As an option, the SCADA system supports averaging of

    all analogue measurements. Typically, the averaging of measured values over a period of

    15 minutes is stored to provide 24 hours trend.6. Historical Data Recording (HDR)- The HDR, i.e. 'archive', subsystem maintains a history

    of selected system parameters over a period of time. These are sampled at a pre-selected

    interval and are placed in historical database. At the end of the day, the data is saved for

    later analysis and for report generation.

    7. Interactive Database Generation- Facilities have been provided in such a way that an off-

    line copy of the SCADA database can be modified allowing the addition of new RTUs,

    pickup points and communication channels.8. Supervisory Control/Remote Command - This function enables the issue of 'remote

    control' commands to the sub-station/powerhouse equipment e.g. circuit breaker trip

    command. Though, there is provision of this function in this system, yet it is not used in U.P.

    As such, related/associated equipment have not been ordered.

    9. Fail-over - A 'Fail-over' subsystem is also provided to secure and maintain a database of

    devices and their backups. The state of the device is maintained indicating whether it is 'on-

    line' or 'failed'. There is a 'backup' system, which maintains database on a backup computer

    and the system is duplicated.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    52/59

    SLDC Lucknow has a large and active 'Mimic Board' in its Control room. This mimic board

    displays single line diagram of intra State transmission system i.e. grid network of 400KV, 220KV

    and important 132KV sub-stations, transmission lines, thermal & hydro powerhouses. Outgoing

    feeders, shown in the mimic board, have 'achieve' (LED display) colored indications, of three

    different colors, to show the range of power flow at any moment i.e. 'Normal', 'Nominal' or

    'Maximum' of its line capacity. UPPTCL's transmission network is expanding rapidly and thereby

    number of RTUs is also increasing. For new substations and lines, displays in active and passive

    forms are required to be made in the Mimic diagram. But, Mimic Board has a limitation that it

    cannot incorporate/add large volume of displays for substations/power houses/transmission lines

    in 'active' form due to space constraint and congestion. Due to this Mimic Board is going to be

    supplemented with a Video Projection System (VPS) at SLDC, Lucknow in near future. Also in

    SLDC & subLDCs, displays of single line diagrams of RTU sub-stations/power house are viewed

    on VDUs of large size (21").

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    53/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    54/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    55/59

    The primary objective of back-up protection is to open all sources of generation to anunclearedfault on the system. To accomplish this objective, an adequate back-up protectivesystem must meet the following functional requirements:1. It must recognize the existence of all faults which occur within its prescribed zoneof protection.2. It must detect the failure of the primary protection to clear any fault as planned.3. In clearing the fault from the system, it must

    a. Initiate the tripping of the minimum number of circuit breakers.b. Operate fast enough (consistent with coordination requirements) to maintain system stability,prevent excessive equipment damage, and maintain a prescribed degree of service continuity.

    Insulators:

    Table for insulators string:

    Line voltage Singlesuspension Single tension Doublesuspension

    Double tension

    132 KV 9 10 2*9 2*10

    220KV 14 16 2*14 2*16400KV 2*21 2*21

    Corona ring:

    A corona ring, also called anti-corona ring, is a toroid of (typically) conductive material located in

    the vicinity of a terminal of a high voltage device. It is electrically insulated. Stacks of more spaced

    rings are often used. The role of the corona ring is to distribute the electric field gradient and lower

    its maximum values below the corona threshold, preventing the corona discharge.

    Corona rings are typically installed on very high voltage power line insulators. Manufacturers

    suggest a corona ring on the line end of the insulator for above 230 kV and on both ends for above

    500 kV. Corona rings prolong lifetime of insulator surfaces by suppressing the effects of corona

    discharge.

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    56/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    57/59

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    58/59

    C.Terminal on tank cover of transformer

  • 7/31/2019 36109419 Summer Training Report on Unnao Sub Station

    59/59

    References

    1 .www.upptcl.com

    2 .www.cgl.com

    3 . Electrical power system by Ashfaq Hussain

    4 .Switchgear & protection by U.V.Bakashi