September 05, 2019
THE REGIONAL MUNICIPALITY OF YORK ADDENDA # 3
T-19-16 FOR: Construction of Paramedic Response Station No. 29 at 107 Glen Cameron Road in the
City of Markham CLOSING: September 13, 2019 at 1:00:00 P.M. (Eastern Time) Bidders are requested to incorporate the changes/clarifications noted below to the above noted bid documents in your possession and be governed accordingly.
1. Please refer to the following attached documents for responses to bidder’s questions and further changes to the Contract Documents:
Architectural Addendum, attaching: o Architectural Drawings o Door Hardware Schedule
M/E Addendum, attaching o M/E Drawings o Replacement Specification Section 26 30 00 o Replacement Specification Section 26 30 10
Each Bidder shall acknowledge receipt of all addenda to this RFT prior to submitting their Bid. Bids that do not contain evidence of receipt of all addenda will be deemed to be “incomplete” and will not be accepted in the Bidding Website. This addendum shall remain attached to and form part of the Contract Documents. Yours truly,
Sabrina D’Angelo Senior Purchasing Analyst Procurement Office
THOMASBROWNARCHITECTS 197 SPADINA AVENUE I TORONTO ONTARIO I M5T 2C8
ARCHITECTURAL ADDENDUM 01 Contract No. T-1916
York Region Paramedic Response Station #29 107 Glen Cameron Road, Markham
The following are responses to questions submitted by bidders:
Q1 When is the projected date of award? A It is anticipated that the contract will be awarded in late September – beginning of
October 2019.
Q2 Section 07 81 00 – Sprayed Fire-Resistive Material is included in the specification, please provide location of application on drawings.
A Refer to A0.1 OBC Chart and A0.3 Fire, Exit and AODA Plan for scope of work.
Q3 Section 07 13 26 – Sheet Waterproofing is included in the specification, please provide location of application on drawings
A Refer to Section 07 13 26 for applicable locations.
Q4 Cash Allowance CA-2 – Supply & install of exterior digital signage: Is there a scope of work for GC in this item?
A Refer to Section 01 21 00 Allowances for scope of work by the Contractor. Review detail 3/A1.4 for scope of work completed by Digital Sign Provider. The Contractor shall provide all power / data requirements as outlined in Architectural and Electrical Drawings.
Q5 Cash Allowance CA-3 – Supply & install of interior building signage: Is there a scope of work for
GC in this item? A Refer to Section 01 21 00 Allowances for scope of work by the Contractor.
Q6 Dwg CV2 – We see site services work extending beyond the property line and onto Glen Cameron Road. We suggest the owner create a cash allowance to cover off the street connection and road restoration. Normally general contractors work within the confines of the property line. If we are asked to work beyond the property line than it must be reconfirmed. We ask clarification be offer on responsibility of site services extending beyond the property line.
A All workout noted beyond the property line is included in the scope of Work under the Contract. Refer to General Notes – Site Plan detail 2/A1.3.
Q7 Dwg CV2 – There is a note calling for “coordinate” the relocation of an existing sign and
light. There are no further details. This seems to be work that would fall under traffic management systems to which there is no specification for on this project and requires specialty trades dealing with traffic lights. We assume the Region is taking care of this task with their regular vendor that performs traffic light work. Please issue clarification or establish a cash allowance for general contractors to carry and retain the vendor that normally does this work for York Region.
THOMASBROWNARCHITECTS 197 SPADINA AVENUE I TORONTO ONTARIO I M5T 2C8
ARCHITECTURAL ADDENDUM 01 Contract No. T-1916
York Region Paramedic Response Station #29 107 Glen Cameron Road, Markham
A Refer to A1.2 Demo Site Plan and A1.3 Site Plan. The Contractor shall coordinate
relocation with Authorities having Jurisdiction. This is a Municipal Road not Regional Road. Bidders are responsible to contact authorities having jurisdiction in order to determine the costs associated with relocation.
Q8 Dwg CV2 – We see a detail right side of the drawing providing a “sub drain detail” and we ask
that clear direction be given on the desired locations. Does the civil engineer want it along curbing? Along both sides of curbing? Around catch basins? Behind the retaining wall? Foundation walls? Please disclose to bidder’s information so that we may quantify how many lineal meters is desired.
A Refer to note on detail: All CBMH and CB Structures to have subdrain connections installed as shown on subdrain detail.
Q9 Dwg A1.3 – A generator is shown to sit atop a concrete pad. Details should be given to identify
slab thickness, extent of reinforcing, granular assembly. A Concrete slab shall be 200mm in thickness, reinforced w/15@ 300 T&BEW. Provide
compacted 250mm of 19mm clear stone compacted to min. 98% standard proctor max. Dry density.
Q10 Dwg E2.0 – The electrical drawing shows the secondary ductbank going across the street on
Glen Cameron Road. The cross section on the electrical drawing should be updated to reflect the actual assembly including restoration when it passes through the road. In addition (and similar to the question above) please reconfirm if this tender is to include work beyond the property line and if this tender is to include road restoration. It is proper for electrical drawings to show ductbank assemblies as electrical contractors normally provide the civil work for ductbank construction however electrical bidders may exclude the restoration and suggest it is not in the tender because it is not indicated on their drawing. Electrical bidders will need a scope of work directive, otherwise the roadway will be closed during the stages of ductbank assembly (having inspections before backfilling, etc) and it should be established now if the road can be closed, and what costs are involved (ie road occupancy permits, special insurance, traffic management or any detour planning not likely determined in the tender period, etc). Kindly update electrical drawing details showing roadwork assembly on the cross section of the ductbank. In the alternative, a cash allowance could be established to satisfy the electrical ductbank street connection and restoration.
A All work outside of property line is included in the scope of Work under the Contract. All restorations required for the existing road shall be restored to Municipal Standards. Refer to road restoration requirements OPSD 509.010. The Contractor is responsible to obtain all road permits as noted in Specification Section 01 31 13 Coordination and Responsibility 1.4 Permits, Deposits and Responsibilities.
Q11 Owner should clarify if electrical contractor is provide Audio-Visual & pull string (roughin only)
for owner Data/IT/Communication system, any security system, any CCTV system, any Audio Visual system, etc. Please clarify what is provided by electrical contractor and what is provided by owner (or provided by owner prequalified trades by cash allowance).
THOMASBROWNARCHITECTS 197 SPADINA AVENUE I TORONTO ONTARIO I M5T 2C8
ARCHITECTURAL ADDENDUM 01 Contract No. T-1916
York Region Paramedic Response Station #29 107 Glen Cameron Road, Markham
A The supply and installation of Structured I.T Cabling is carried under the Cash Allowance
Item No. CA5. This includes the cabling and server hardware. All related work is included in the scope of Work under the Contract and all costs associated with this work shall be included in the Contract Price. Refer to all requirements on Drawing E1.0 General Notes, Legend and specifications for scope of work for electrical Subcontractor.
Q12 Drawing E4.0 Note 1 Which card access doors have door operators?
A Refer to 3.0, A8.1 and door hardware schedule for locations of door operators. All electrical work is included in the scope of Work under the Contract.
Q13 Drawing E4.0 Note 2 Why is Honeywell supplying the cameras?
A Cameras shall be supplied as outlined in Specification Section 28 00 00 Security System.
Q14 Drawing E4.0 Note 3 Is the Fire Panel in the security scope of work?
A Refer to Section 26 70 00 Fire Alarm System for scope of work. Refer to Section 28 00 00 Security System for scope of work.
Q15 Who is providing the CAT 6 cabling and POE network for the cameras?
A Refer to Section 28 00 00 Security System for scope of work.
Q16 Where are the cameras being recorded? A The cameras are being monitored by our security department.
Q17 Is the Bosch alarm system need if the station is in operations 24/7? A Yes, as the station is not occupied 24/7
Q18 Corner Guards 10 26 13 Please provide location of corner guards. Part 2.1.2 shows full height and 3.1.5.4 show 1500 high, please advise the correct height.
A Review A2.3 Floor Finish & Furniture Plan for locations of Corner Guards (CG). All corner guards shall be full height.
Q19 Request for product approval for Aluminum & Glazing
Aluminum Screen - Kawneer 601UT Same as 655 thermal storefront system but Windspec does not have 6” back section only 4 ½” Aluminum Screen - Kawneer 1620 SSG - 5500 series SSG or 5500 htp ssg Aluminum Screen - Kawneer 451 – 655 thermal storefront system Aluminum Screen - Kawneer Tri Fab 450 – Interior 630 framing Aluminum Doors - Kawneer '350 Medium Stile' – 350 Medium stile door or 375 htp medium stile
THOMASBROWNARCHITECTS 197 SPADINA AVENUE I TORONTO ONTARIO I M5T 2C8
ARCHITECTURAL ADDENDUM 01 Contract No. T-1916
York Region Paramedic Response Station #29 107 Glen Cameron Road, Markham
Aluminum Screen - Kawneer 518 Isoport – 855 /875 window framing
A Requests for product substitutions will be considered only after the Contract award. Please refer to Section 01 25 00 - Product Substitution Procedures for the process of approval of proposed alternative products.
THOMASBROWNARCHITECTS 197 SPADINA AVENUE I TORONTO ONTARIO I M5T 2C8
ARCHITECTURAL ADDENDUM 01 Contract No. T-1916
York Region Paramedic Response Station #29 107 Glen Cameron Road, Markham
Owner/Architect Changes
1. General Instructions
.1 All Bidders are hereby advised that the information contained in the issued Bid Documents for the above captioned project, has been amended to include the information contained within this Addendum, and such information is to be covered in the tender submission and shall form part of the Contract Documents.
2. Affected Sections of the Project Manual Architectural
1. Refer to Section 08 71 00 Door Hardware .1 Insert Door Hardware Schedule dated April 10, 2019, attached to this Addendum.
Structural – none included as part of this addendum
Mechanical – Refer to enclosed Electrical Addendum 1
Electrical - Refer to enclosed Electrical Addendum 1
Civil – none included as part of this addendum
Landscape – none included as part of this addendum
THOMASBROWNARCHITECTS 197 SPADINA AVENUE I TORONTO ONTARIO I M5T 2C8
ARCHITECTURAL ADDENDUM 01 Contract No. T-1916
York Region Paramedic Response Station #29 107 Glen Cameron Road, Markham
3. Affected Drawings
Architectural
1. Refer to Drawing A1.4 Site and General Details
.1 Replace detail 3 with the revised version, which is attached to this Addendum.
.2 Insert note – the General Contractor shall remove and dispose of all lose debris (bricks, garbage etc) from the site boundary, including within the ditch/swale.
2. Refer to Drawing A1.5 Site and General Details
.1 Replace detail 2 with the revised version, which is attached to this Addendum.
3. Refer to Drawing A3.1 Roof Plan
.1 Replace detail 10 with the revised version, which is attached to this Addendum.
4. Refer to Drawing A4.3 Cladding, Glazing, & Louver Elevations, I.T Room Plan And Elevations
.1 Details 17, 18,19 and 20 have been updated to indicate electrical outlet locations for I.T room. The General Contractor shall coordinate on site with electrical Drawings and review with project team prior to rough-in. Provide fire rated plywood as indicated. Replace Details 17, 18 and 19 with the revised versions attached to this Addendum.
5. Refer to Drawing A5.1 – Building Sections and Details
.1 Replace detail 7 and 8 with revised the revised versions, which are attached to this Addendum.
6. Refer to Drawing A7.1 – Washroom Details & Fixture Mounting Heights
.1 Replace detail 2 and 3 with the revised versions, which are attached to this Addendum.
7. Refer to Drawing A7.2 – Millwork Plan, Elevations and Details
.1 Replace detail 13 and 18 with the revised versions, which are attached to this Addendum.
8. Refer to Drawing A8.1 – Door Finish Schedules & Universal Washroom Operation
.1 Replace detail 2 with the revised version which is attached to this Addendum.
9. Refer to Drawing A8.2 – Room Finish Schedule
.1 Refer to the attached updated Interior Finishes Schedule for revised description of PT-3 and PT-4.
.2 Refer to the attached updated detail 1 for revised PT-4 locations at Four-Fold and Sectional Door jambs, exposed steel, etc.
Structural – none included as part of this addendum
THOMASBROWNARCHITECTS 197 SPADINA AVENUE I TORONTO ONTARIO I M5T 2C8
ARCHITECTURAL ADDENDUM 01 Contract No. T-1916
York Region Paramedic Response Station #29 107 Glen Cameron Road, Markham
Mechanical – Refer to enclosed Mechanical Addendum 1. Electrical - Refer to enclosed Electrical Addendum 1 Civil – none included as part of this addendum Landscape -– none included as part of this addendum Attachments: Replacement Architectural Drawings Door Hardware Schedule
END OF DOCUMENT
3500 - TYPE 'A'
2400 - TYPE 'B' 1500
PAINTED LINES
5600
190
5000 - TYPE 'A'
3900 - TYPE 'B'
2-0008 - AODA PARK-1 - AODA PARKING SPACE DETAILS
EQ EQ
AODA MANDATORY REQUIREMENT
400
BARRIER FREE
PARKING SIGN 1500
FLAREMAX. SLOPE 1:10
(TYP.) AT FLARED SIDE RAMP RETURN CURB RAMP
FLARED SIDE RAMP
TO S
IDEW
ALK
ED
GE
920
MIN
.
825 MAX.
DETECTABLE HAZARD INDICATOR
610
190
PAINTED LINES
CURB
DEPRESS CURB AT FLARE (TYP)
RETURN CURB AT RETURN CURB RAMP
TRANSITION
1350 1500
TRANSITION
1350
OC
T-152-0008 - AODA RAMP-1 AODA PARKING SPACE DETAILS
AODA MANDATORY REQUIREMENT
SLOPE
SLO
PE
1350 1500 1350
1500
920
MIN
.
610
190
RAMP SLOPE (MAX. 1:10)
FLARED SIDE (MAX. 1:10)
FAR EDGE OF SIDEWALK(MIN. 920MM)
FACE OF CURB
DEPRESS CURB (MAX. SLOPE 1:20)
SJ1SJ1
CJ1CJ1
CJ1
DETECTABLE HAZARD STRIP
CJ1 CJ1
SJ1SJ1
FLARED CURB RAMP DETAILS (WHERE INDICATED)
SLO
PE
1500
1500
920
MIN
.
610
190
RAMP SLOPE (MAX. 1:10)
RETURN CURBTOP TO MATCH ADJACENT SIDEWALK
FAR EDGE OF SIDEWALK(MIN. 920MM)
FACE OF CURB
SJ1SJ1
CJ1CJ1
CJ1
DETECTABLE HAZARD STRIP
CJ1 CJ1
SJ1SJ1
RETURN CURB RAMP DETAILS (WHERE INDICATED)
SLOPE
MAY
-16
R 250R 250
2-0011 - CD-1 - CURB DETAILS
MAY
-16
50 250 50
150
270
50
32MPa CONCRETE 5-8% AIR ENTRAINED CLASS -C2 EXPOSUREC/W 2 x 15M BARS
GRAVEL BED
FLUSH TYPE CURB (FTC)
GRASS
ASPHALT ROLLED TYPE CURB (ARTC)
390
135.00°
225
12045 deg.
120
45.0
0°45
.00°
PAVED SURFACE
13mm EXPANSION JOINT
250 50
400
150
SIDEWALK / PAVER THICKNESS
30
50MM SUPPORT LEDGE WHEN SIDEWALK IS ADJACENT TO CURB
BARRIER TYPE CURB (BTC) - ADJACENT TO SIDEWALK / HARD SURFACE
107
5025
LINE OF DEPRESSED CURB(WHERE INDICATED OR REQUIRED)
190
PAVED SURFACE
250
400
150
BLEND SIDEWALK GRANULAR BASE DOWN TO ASPHALT/CURB GRANULAR BASE (TYP.)BARRIER TYPE CURB (BTC) - ADJACENT TO LANDSCAPED AREAS
50
190
135.00°
GR
ANU
LAR
BASE
45.0
0°
GR
ANU
LAR
BAS
E TH
ICKN
ESSLINE OF RAMP
(AT DEPRESSED CURB)
45.0
0°
GR
ANU
LAR
BASE
PAVED SURFACE
PAVED SURFACE
GR
ANU
LAR
BASE
GR
ANU
LAR
BASE
NOTE: NOT ALL CURB TYPES MAY BE REQUIRED. ALL CURBS SHALL BE BARRIER TYPE UNLESS SPECIFICALLY NOTED OTHERWISE
FACE OF FOUNDATION WALL
EXTERIOR INTERIOR
REINFORCED CONCRETE TRANSITION APRON REFER TO
STRUCTURAL FOR REINFORCING REQUIREMENTS
VAR
IES
ASPHALT PAVING
NOTCH APRON EDGE AT ADJACENT ASPHALT
200
1500MM FROM FOUNDATION WALL CENTRELINE
LINE OF BUILDING FACE/OVERHEAD DOOR JAMB BEYOND
FINISH APRON TO FACE OF FOUNDATION WALL BETWEEN DOORS
+/- 1
50
DEPRESS FOUNDATION TO ACCOMODATE SLAB
AND APRON THICKNESS AT DOOR OPENINGS
400LINE OF BOLLARD C/W BOLLARD COVER BEYOND
LINE OF BOLLARD FOOTING BEYOND
3-0001 - CAA-1 - CONCRETE TRANSISTION APRON TYPICAL (ASPHALT)
ALL REINFORCING STEEL EPOXY COATED
OC
T-15
SLAB MUST BE CROWNED BENEATH DOOR TO ENSURE FLOW OF WATER FROM EXTERIOR FACE
OF DOOR TO EXTERIOR
SLOPE
CJ3
CL CL
SLOPE
CROWN
LINE OF OVERHEAD DOOR
THE INTENT OF THE TRANSITION APRON SLAB IS TO ENSURE A SMOOTH TRANSITION AS VEHICLES ENTER OR EXIT THE BUILDING BY PREVENTING THE APRON SLAB FROM HEAVING DUE TO FROST OR SETTLEMENT.PRIOR TO PLACEMENT DO THE FOLLOWING:1. DETERMINE THE LOCATION OF DOOR EXTERIOR FACE AND ENSURE THAT THE INTERIOR
SLAB SLOPES DOWN FROM THIS POINT TO THE EXTERIOR2. ENSURE THAT APRON WILL CONTINUE THIS SLOPE CONSISTENTLY TO DIRECT WATER AWAY
FROM THE FACE OF THE DOORUNDER NO CIRCUMSTANCES SHALL WATER BE DIRECTED TOWARD BUILDING
3-0001.1 - CAT-1
TRANSITION APRON SLABSEE ALSO
TYPICAL APRON TRANSITION FROM APPARATUS/VEHICLE BAY TO DRIVEWAY
CURB TO BUILDING FACE
SLOPE TRANSITION APRON DOWN FROM APPARATUS / VEHICLE BAY SLAB
ELEVATION TO ADJACENT ASPHALT/CONCRETE APRON SURFACE
MAX SLOPE - 1:10
APRON
DRIVE AISLE
BUILDING FACE
TOP OF CURB ELEVATION TO MATCH APPARATUS / VEHICLE BAY SLAB ELEVATION (SITE CONFIRM)
AT ADJACENT ASPHALT SURFACES:NOTCH APRON TO THICKNES OF ASPHALT
AT ADJACENT CONCRETE SURFACES:PROVIDE CONSTRUCTION JOINT (CJ4)
3-0001.1 - CAT-1 - CONCRETE TRANSITION APRON TYPICAL (AXO)
ENSURE THAT TRANSITION APRON WILL SLOPE CONSISTENTLY TO DIRECT WATER
AWAY FROM THE FACE OF DOORUNDER NO CIRCUMSTANCES SHALL
WATER BE DIRECTED TOWARD BUILDING
SLOPE
CROWN
A700-150000-IWS-1
SE
PT-1
8
GCCOORD
SUBTRADES* MULTIPLE SUBTRADE COORDINATION REQ'D
OUTLET TEE
FLOOR
FLOOR DRAIN(100MM DIA. MIN.)
OUTLET VALVE
GATE VALVE
DRAINAGE VALVE
19MM DRAIN PORT TEE WITH THREADED REMOVABLE
BRASS PLUG
WATER METER
600M
M M
AX.
POINT OF
ENTRY
INLET TEE
BY-PASS VALVE
GATE VALVE
THE INTENT OF THE DETAIL IS TO ENSURE A COMPLETE AND COMPLIANT INSTALLATION.WITHOUT EXCEPTION CONTRACTOR SHALL ENSURE THAT INSTALLATION CONFORMS TO MUNICIPAL STANDARD DETAILS AND AUTHORITIES HAVING JURISDICTION.INSTALLATION AS SHOWN IS SCHEMATIC. COMPONENTS SHOWN (OR NOT SHOWN) IS SUBJECT TO MUNICIPAL REQUIREMENTS. THIS DRAWING IS SUPPLEMENTAL TO MECHANICAL AND CIVIL DRAWINGS
25MM BRANCH OFF TEEFLUSHING VALVE
NOTES:
1. CLEARANCES TO WALL(S) IN ACCORDANCE WITH MUNICIPAL STANDARDS2. UNLESS OTHERWISE NOTED, INSTALLATION OF WATER METER(S) IS PART OF CONTRACT.3. BACKFLOW PREVENTER(S) TO BE INSTALLED IN ACCORDANCE WITH MUNICIPAL STANDARDS.
BACKFLOW PREVENTER
MAIN BUILDING CONTROL VALVE(G.C TO CONFIRM WITH AHJ)
2-0012 - CD-2 - CURB AND RAMP DETAILS - SIDEWALKS AND DRIVEWAY ENTRANCES
APR
-19
R 1
25
150
TRANSITION
400
WIDTH
SIDEWALK / RAMP/ DRIVEWAY
TRANSITION
400 150
CURB FACE
30
TOP OF ASPHALT
R 125
R 125
150
400
BOTTOM OF CURB
R 1
25
TYPICAL TRANSITION TO DEPRESSED CURB (NON-AODA)
CURB SAWCUT
TRANSITION
400
TYPICAL TRANSITION TO DEPRESSED CURB AT SIDEWALKS / RAMPS (NON-AODA)
TRANSITION DOWNMINIMUM TRANSITION
LENGTH SHOWN
CURB DEPRESSION
RAMP FLARE FROM SIDEWALK EDGE TO TRANSITION EDGE(SAME MATERIAL AS SIDEWALK)
TRANSITION
400
300
TYPICAL TRANSITION TO DEPRESSED CURB AT DRIVEWAY ENTRANCES (NON-AODA)
TRANISITION DOWNMINIMUM TRANSITION LENGTH SHOWN
CONFIRM WITH MUNICIPALITY PRIOR TO PROCEEDING
CURB DEPRESSION
BLEND DRIVEWAY FLARE TO FROM DRIVEWAY EDGE TO TRANSITION EDGE(SAME MATERIAL AS DRIVEWAY) DRIVEWAY RADIUS(REFER TO SITE PLAN)
EXISTING CURB
BLEND NEW CURB TO EXISTING(WHERE APPLICABLE)
300 MM MIN. DISTANCE FROM EXISTING CURB TO START OF TRANSITION
(WHERE APPLICABLE)
DRIVEWAY
STREET
RAMP/SIDEWALK
ASPHALT OR LOWER SURFACE
65 MAX. SPACING25 MAX. DIA.
3 M
AX.
610 MIN.
DETECTABLE HAZARD INDICATOR REQUIREMENTS
5 M
AX.
TRUNCATED DOMES IN GRID PATTERN
300
600
300
300
SLOPESLOPE
SLOPE
SLOPE
CONCRETE RAMP (1:10 SLOPE MAX.)
6-13
mm
DETECTABLE HAZARD INDICATOR
2000 - (MAX LENGTH)
AT FLARED CURB RAMPS:LINE OF TRANSITION BEYONDAT RETURN CURB RAMPS:FACE OF CURB BEYOND
CURB RAMP AT AODA PARKING SPACES
PAVED SURFACE
2-0013 - CD-3 - AODA RAMP DETAILS
AODA MANDATORY REQUIREMENT
LINE OF CURB BEYOND
65 MAX. SPACING25 MAX. DIA.
3 M
AX.
610 MIN.
DETECTABLE HAZARD INDICATOR REQUIREMENTS
5 M
AX.
TRUNCATED DOMES IN GRID PATTERN
SIDEWALK THICKNESS
APR
-19
300
600
300
300
TRANSITION
1350 (SITE CONFIRM)
TYPICAL TRANSITION TO DEPRESSED CURB - AODA FLARED CURB RAMPS
TRANSITION DOWN
CURB DEPRESSION
RAMP FLARE FROM SIDEWALK EDGE TO TRANSITION EDGE
(SAME MATERIAL AS SIDEWALK)
AODA RAMP/SIDEWALK
ASPHALT OR LOWER SURFACEDETECTABLE HAZARD INDICATOR
150
TRANSITION
1350
WIDTH
SIDEWALK / RAMP/ DRIVEWAY
TRANSITION
1350 150
CURB FACE
30
TOP OF ASPHALT
BOTTOM OF CURB
R 1
25
TYPICAL TRANSITION TO DEPRESSED CURB - AODA FLARED CURB RAMPS
CURB SAWCUT
R 1
25
R 1 25
R 125
13mm EXPANSION JOINT
13mm EXPANSION JOINTCURB DEPRESSION
RAMP THICKNESS- TO MATCH SIDEWALK THICKNESS
SLOPE - 1:10 MAX.
SLOPE - 1:10 MAX.
2-0016 - SUR-1 - ASPHALT AND CONCRETE SURFACES
FEB
-19
OPSS HL3 ASPHALT OPSS HL8 ASPHALT
OPSS GRANULAR 'A'
OPSS GRANULAR B - TYPE 2SUB-BASE
BASE
HDA - HEAVY DUTY ASPHALT
300
200
9040
ASPHALT PAVING
630
- TO
TAL
THIC
KNES
S
BASE
SW-1 - SIDEWALK SECTIONCONCRETE SLAB c/w 5-8% AIR, C2 EXPOSURE, 32Mpa.
OPSS GRANULAR B - TYPE 1
135
012
5
SIDEWALK
476
- TO
TAL
THIC
KNES
S
NOTES:1. REFER ALSO TO GEOTECHNICAL REPORT(S) TO CONFIRM LAYER THICKNESSES. REPORT ANY
DISCREPANCIES TO THE CONSULTANT PRIOR TO PROCEEDING.
SUB-BASE
BASE
RCA - REINFORCED CONCRETE APRONCONCRETE SLAB c/w 5-8% AIR, C2 EXPOSURE, 32Mpa. 15M EPOXY COATED REINFORCING B.E.W @ 400mm o/c
OPSS GRANULAR 'A'
OPSS GRANULAR B - TYPE 2
300
200
200 APRON
700
- TO
TAL
THIC
KNES
S
BASE
GVL - GRAVEL BED50MM CLEAR STONE
OPSS GRANULAR B - TYPE 1
350
300
GRAVEL BED
650
- TO
TAL
THIC
KNES
S
GEOTEXTILE
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
34:0
6 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A1.4
2019/07/09
TENDER
SITE AND GENERALDETAILS
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
A1.46 /A1.48 /
A1.45 /
A1.44 /
A1.43 /
NO. ISSUED FOR DATE1 SPA SUBMISSION 01 2018.01.293 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
A1.42 /
A1.41 /
A1.47 /
11
500
+ D
EPTH
OFA
DJA
CEN
T SL
AB O
R S
LOPE
D A
PRO
N
650
400
BOLLARD COVER AT BOLLARD LOCATIONS UNLESS NOTED OTHERWISE
200 DIAMETER STEEL TUBE x 6mm THICK FILLED WITH CONCRETE
SLOPE ADJACENT SLAB OR APRON AWAY FROM BASE OF BOLLARDCJ1
ADJACENT SLAB OR SLOPED APRON
CONCRETE FOOTING
1. ALL STEEL GALVANIZED2. CONCRETE SHALL BE CLASS C2, 32 MPa CONCRETE COMPLETE WITH 5-8% AIR ENTRAINMENT
200 dia.
BOLL
ARD
SH
IELD
TO
SU
IT
1300
5-0006 - BO-1 - TYPICAL BOLLARD DETAILS
SE
PT-1
8
BOLLARD COVER C/W TWO REFLECTIVE STRIPES OVER STEEL BOLLARDINSTALL IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS.COLOUR TO BE SELECTED FROM MANUFACTURERS FULL RANGE
300
200
150 200 150
BOLLARDFACE OF WALL
EDGE OF DOOR
PLAN VIEW
BOLLARD COVERS AS MANUFACTURED BY ONTARIO BOLLARD,
SUREGUARD OR EQUIVALENT
ALIGN EDGE OF DOOR TO EDGE OF BOLLARD
EDGE OF BOLLARD
SECTION VIEW
BOLLARD COVER
2-0017 - TF-1 - TYPICAL FENCE DETAILS
AUG
-19
TYPICAL FENCE PANEL1. 38x140mm HORIZONTAL COMPOSITE FENCE BOARDS BOLTED TO FENCE POSTS @ 150MM o/c 2. BOLTS SHALL BE 9.5mm DIA. 3. CARRIAGE BOLTS C/W NYLON INSERT LOCK NUTS 4 BOLTS PER BOARD.4. PRE-DRILL FENCE POSTS PRIOR TO BOARD INSTALLATION
1. ALL STEEL GALVANIZED (INCLUDING HINGES)2. ENGINEERING STAMPED DRAWING REQUIRED PRIOR TO FABRICATION3. CONCRETE SHALL BE CLASS C2, 32 MPa CONCRETE COMPLETE WITH 5-8% AIR ENTRAINMENT
102x76x6.4 TOP ANGLE
38x140 COMPOSITE FENCE BOARD (HORIZONTAL)
SLOPE TOP OF FOOTING
300
CONCRETE FOOTING
990
2058
3048
- M
IN. P
OST
HEI
GH
T
FINISHED GRADE
L76x76x4.8 BOTTOM ANGLE
LINE OF VERTICAL FENCE POST BEYOND
FENCE SECTION
25
300
TOP FENCE CONDITION
BASE FENCE CONDITION
PLAN FENCE DETAIL
102x76x6.4 ANGLE
BACK-TO-BACK L89x76x9.5 ANGLES (FENCEPOSTS)
38x89 COMPOSITE BOARDBOLTED TO ANGLE38x140 COMPOSITE BOARD
76x76x4.8 ANGLE
BACK-TO-BACK L89x76x9.5 ANGLES (FENCEPOSTS)
38x89 COMPOSITE BOARDBOLTED TO ANGLE
38x140 COMPOSITE BOARD
TOP OF FOOTING
25
76x76x4.8 ANGLE BELOW (102x76x6.4 ANGLE ABOVE)
BACK-TO-BACK L89x76x9.5 ANGLES (FENCEPOSTS)38x89 COMPOSITE BOARDBOLTED TO ANGLE
38x140 COMPOSITE BOARDTOP OF FOOTINGPLAN HINGE DETAIL
(WHERE GATE IS INDICATED)
25
76x76x4.8 ANGLE BELOW(102x76x6.4 ANGLE ABOVE)
L89x76x9.5 ANGLE ANCHORED TO FOOTING 38x89 COMPOSITE BOARD
BOLTED TO ANGLE
38x140 COMPOSITE BOARDTOP OF FOOTING
EXTRA HEAVY DUTY GATE HINGE (3 TOTAL) WELDED TO ANGLE AND GATE FRAME
HINGE LEAVES TO FIT WITHIN DEPTH OF ANGLES
L89x76x9.5 ANGLE GATE FRAME
- MIN
. FO
OTI
NG
DEP
TH
1200
2-0014 - CLF-1 - CHAIN LINK FENCE DETAILS
1200
UN
LESS
OTH
ERW
ISE
NO
TED
1800
300
900
30-5
0MM
300
EXTEND CONCRETE 25MM ABOVE FINISHED
GRADE AND SLOPE AWAY FROM POSTS
POURED IN PLACE CONCRETE FOOTINGS
INSTALL TUBE FORM TO FOOTING DEPTH
89MM O.D. TERMINAL POSTS INSTALLED AT ALL ENDS CORNERS AND GATES
42.9MM O.D. TOP RAIL WITH TOP EDGE FASTENERS AT 450MM o/c.FASTENERS SHALL BE 3.6MM (9 GAUGE) STEEL OR ALUMINUM (TYP.)180MM COUPLERS
VINYL COATED CHAIN LINK FABRIC
3.2MM X 19MM STEEL OR 4.8MM X 19MM ALUMINUM STRETCHER BAR BANDS AT 300MM o/c MAX.42.9MM O.D. BRACE RAILS TO BE INSTALLED AT ALL ENDS, STRAINING AREAS AND STEEP TOPOGRAPHY.LOCATE EQUIDISTANT BETWEEN TOP RAIL AND BOTTOM OF FENCE
60MM O.D LINE POSTS89MM O.D TERMINAL POST
5MM X 19MM STEEL STRETCHER BAR
SINGLE STRAND 4MM (9 GAUGE) GALVANIZED STEEL TENSION WIRE FASTENED AT 450MM o/c WITH DROP FORGED TURN BUCKLE
NOTES:1. ENGINEERING STAMPED DRAWING REQUIRED PRIOR TO FABRICATION2. ALL FABRIC SHALL BE 3.6MM (9 GAUGE WITH 11 GAUGE STEEL CORE) KNUCKLED AT TOP AND
BOTTOM.3. FABRIC SHALL BE VINYL COATED. COLOUR: BLACK4. FABRIC SHALL BE INSTALLED ON EXTERNAL SIDE OF FENCE POSTS AND SECURED TO TOP RAIL, LINE
RAIL AND BOTTOM TENSION WIRE WITH WIRE TIES AT 450MM o/c.5. ALL POSTS AND RAILS SHALL BE GALVANIZED STEEL PIPE, STANDARD WEIGHT CONFORMING TO
ASTM A120.6. ALL POSTS AND RAILS SHALL BE POLYESTER POWDER COATED TO MATCH FENCE FABRIC 7. ALL REQUIRED FITTINGS AND HARDWARE SHALL CONFORM TO ASTM A152.8. ALL REQUIRED FITTINGS AND HARDWARE SHALL BE COLOURED TO MATCH FENCE FABRIC9. CONCRETE SHALL BE CLASS C2, 32 MPa CONCRETE COMPLETE WITH 5-8% AIR ENTRAINMENT
FINISHED GRADE
3000MM o/c MAX.
250
TERMINAL POST FOOTING LINE POST FOOTING
OC
T-15
TOP OF CONVENTIONAL FIBER FORM AT 50 BELOW FINISHED GRADE50mm RIGID PVC CONDUIT SLEEVE - 915 RADIUS(REFER TO ELECTRICAL)19mm RIGID CONDUIT SLEEVE FOR GROUND CONNECTION AS REQUIRED & SPECIFIED-SEE DWGS. (REFER TO NOTE 4)8-20M REINFORCED RODS & 10M TIES PER ONTARIO PROVINCIAL STANDARD DRAWING OPSD-2200.01
FIBE
R F
OR
M
(SEE
ALS
O N
OTE
5)
DEP
TH IN
AC
CO
RD
ANC
E W
ITH
MAN
UFA
CTU
RER
S R
ECO
MM
END
ATIO
N
LOW BASE
ALUMINUM COLOR ACCENT BAND
50
460 dia.
730
2-0019 - LS-2 - LIGHT STANDARD LOW BASE DETAIL
CAST IN-PLACE ARCHITECTURAL CONCRETE BASE
PREFABRICATED CONCRETE FORM
GALVANIZED STEEL 'J' BOLTS AS SUPPLIED BY POLE MANUFACTURER
GRADE
GR
ADE
550
ABO
VE
50
MAY
-16
460 DIA.
510 DIA.
LIGHTING POLE POLE BASE COVERLOCK NUTSLEVELING NUTS
POLE CENTERLINE 900mm FROM BACK FACE OF CURB. CL
900
BACK FACE OF CURB
IF THERE RISK OF DAMAGE DURING SUBSEQUENT WORK, FORM HALVES
CAN BE WIRE TIED AROUND FINISHED WORK TO PROTECT FROM DAMAGE UNTIL WORK IS COMPLETE
REMOVE PREFABRICATED FORM WITHIN 24 HOURS OF POUR. WIRE
BRUSH TO REMOVE REMAINING FORM MATERIAL. USE RUBBING
STONE TO REMOVE ROUGH EDGES AND VERTICAL SEAMS.
GCCOORD
SUBTRADES
NOTES:1. CAST-IN-PLACE CONCRETE MECHANICALLY VIBRATED AND HAND TAPPED TO ENSURE BEST
FINISHED RESULT. TOP OF BASE SHALL BE TROWELLED SMOOTH AND LEVEL. • NOTE: POOR FINISHED RESULTS WILL BE REJECTED AND REPLACED AT NO ADDITIONAL COST
TO THE CONTRACT.2. CONCRETE SHALL BE 25mPa., 5-8% AIR ENTRAINED, CLASS-C2 EXPOSURE.3. MINIMUM OF TWO SLEEVES REQUIRED FOR EACH CONCRETE FOUNDATION. CONTRACTOR TO
VERIFY OPENING SIZE IN POLE BASE PLATE PRIOR TO SETTING CONDUIT SLEEVES.4. PROVIDE A 19mm DIAMETER 3000mm STEEL COPPER COATED GROUND ROD ADJACENT TO POLES
IN ACCORDANCE WITH ESA AND ANY OTHER AUTHORITIES HAVING JURISDICTION. CONNECT TO METAL POLE WITH BARE COPPER CONDUCTOR.
5. SUBJECT TO SOIL CONDITIONS, REFER TO SOIL REPORT.
760
610
195
(SEE
ALS
O N
OTE
4)
ACTU
AL D
EPTH
IN A
CC
OR
DAN
CE
WIT
HM
ANU
FAC
TUR
ERS
REC
OM
END
ATIO
NS
FLAG POLEPOLE BASE COVERLOCK NUTSLEVELING NUTS
PREFABRICATED CONCRETE FORM
TOP OF CONVENTIONAL FIBRE FORM CUT 50MM BELOW FINISHED GRADEGALVANIZED STEEL 'J' BOLTS AS SUPPLIED BY FLAGPOLE MANUFACTURER
75mm MINIMUM COVER
8-20M REINFORCED RODS & 10M TIES INACCORDANCE WITH OPSD-2200.01
2-0015 - FP-1 - FLAG POLE BASE
NOTES:1. TOP OF FOUNDATION SHALL BE TROWELLED SMOOTH AND LEVEL.2. CONCRETE SHALL BE 32 MPa CONCRETE 5-8% AIR ENTRAINED CLASS-C2 EXPOSURE.3. CAST-IN-PLACE CONCRETE MECHANICALLY VIBRATED AND HAND TAPPED TO ENSURE BEST
FINISHED RESULT.• NOTE: POOR FINISHED RESULTS WILL BE REJECTED AND REPLACED AT NO ADDITIONAL
COST TO THE CONTRACT4. SUBJECT TO SOIL CONDITIONS, REFER TO SOIL REPORT.
OC
T-15
610
WHERE TWO OR MORE FLAGPOLES ARE SHOWN IN A LINE
UNDER NO CIRCUMSTANCESSHALL THE CENTER TO CENTER
SPACING OF FLAGPOLES BE LESS THAN 2400mm
REMOVE PREFABRICATED FORM WITHIN 24 HOURS OF POUR. WIRE BRUSH TO REMOVE REMAINING FORM MATERIAL. USE RUBBING STONE TO REMOVE ROUGH EDGES AND VERTICAL SEAMS.IF THERE IS RISK OF DAMAGE DURING SUBSEQUENT WORK, FORM HALVES CAN BE WIRE TIED AROUND FINISHED WORK TO PROTECT FROM DAMAGE UNTIL WORK IS COMPLETE
GCCOORD
SUBTRADES
VisitorParking
TYPICAL
305
TYPI
CAL
457
Idle FreeZone
TurnEngine Off
TYPICAL
305
TYPI
CAL
457
VEHICLES WILL BE TAGGED AND/OR
TOWED AWAY
TYPICAL
305
TYPI
CAL
457
NO ENTRY
TYPICAL
305
TYPI
CAL
457
SIGN TYPE'VPS'
SIGN TYPE'IFS'
7040
50
1. STANDARD FONT TYPE IS FUTURA MDBT IN PANTONE 287 C
2. WHITE BACKGROUND
SIGN TYPE'NES'
1. STANDARD FONT TYPE IS ARIAL BOLD IN RED
2. WHITE BACKGROUND
SIGN TYPE'FRS'
1. STANDARD FONT TYPE IS ARIAL BOLD IN BLACK
2. WHITE BACKGROUND
PANTONE 287 C
10 6 273 6 10
1. STANDARD FONT TYPE IS FUTURA MDBT IN PANTONE 287 C
2. WHITE BACKGROUND
FIRE ROUTERED
SYMBOL
RED LETTERS
SE
PT-1
6
A700-101410-ES-1
* ALL SIGNS SHALL BE IN ACCORDANCE WITH MUNICIPAL STANDARDS. CONFIRM PRIOR TO INSTALLATION
POST MOUNTED SIGN - FIXED POST
SIGN FACE- 1.6mm THICK ALUMINUM SIGN BLANK- HOLES - METRO PUNCH
MOUNTINGMOUNT SIGN FACE TO POST WITH TWO GALVANIZED 12mm HEX HEAD BOLTS AND NUTS WITH FLAT WASHERS ON BOTH SIDES
POST75mm dia. GALVANIZED STEEL POST c/w POST CAP IN 300mm dia.CONCRETE FOOTING
FINISHED GRADE
700
1980
300
400
900m
m M
INIM
UM
PAVING SIGNLOCATE ONE POST MOUNTED SIGN AT EACH PARKING SPACE PROVIDED SIGNAGE TO CONFORM TO LOCAL AUTHORITES HAVING JURISDICTION
POST MOUNTED SIGN - FIXED POST
SIGN FACE- 1.6mm THICK ALUMINUM SIGN BLANK- HOLES - METRO PUNCH
MOUNTINGMOUNT SIGN FACE TO POST WITH TWO GALVANIZED 12mm HEX HEAD BOLTS AND NUTS WITH FLAT WASHERS ON BOTH SIDES
POST75mm dia. GALVANIZED STEEL POST c/w POST CAP IN 300mm dia.CONCRETE FOOTINGPAVING SIGN
GRAPHICPAINTED INTERNATIONAL SYMBOL OF ACCESSIBILITY. COLOUR TO MATCH ADJACENT PAINTED PARKING LINES.
2-0010 - BF-2 - HCP SIGN FIXED POST
BY PERMITONLY
1755
BY PERMIT
BLACK LETTER 'P' LEGEND AND BORDER20MM RED REFLECTIVE ANNULAR BAND
WHITE REFLECTIVE SYMBOL AND BORDER
450 BLUE REFLECTIVE BACKGROUND
AND OUTLINE
300
301030 3212
515 15
035
75
ONLYBLACK LETTER 'P', LEGEND AND BORDERWHITE REFLECTIVE BACKGROUND
AODA MANDATORY REQUIREMENTN
OV-
15
2-0060 - DPS - DIGITAL PYLON SIGNNO
V-18
ParamedicResponseStation #29
107 GLEN CAMERON ROAD
PARAMEDICSERVICES
2440 DIGITAL TEXT
1016
510
915
1982
76 25 1780 25 76
BY P
YLO
N S
IGN
SU
PPLI
ER/IN
STAL
LER
FOU
ND
ATIO
N S
IZE,
DEP
TH A
ND
DES
IGN
GRADE
LED MESSAGE BOARD
CAITEM
2546
025
2596
5
25
ALUMINUM BASE PLATE BY SIGN SUPPLIER
TUBULAR ALUMINUM POSTS
PROVIDE POWER AND DATA CONDUIT & WIRING THOUGH CONC. BASE AND INTO SIGN INTERIOR. REFER TO ELECTRICAL DRAWINGS.
532
VERTICAL REBAR AND TIES BY SIGN SUPPLIER
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
N N
TRUE NORTH CONSTRUCTION NORTH
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
47:5
8 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
Author
A1.5
2019/07/09
TENDER
SITE AND GENERALDETAILS
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
NO. ISSUED FOR DATE6 SPA SUBMISSION 05 2018.11.0711 ADDENDUM 1 2019.08.22
A1.55 /
A1.52 /
A1.53 /
A1.54 /
A1.51 /
A1.56 /
A1.57 /
A1.58 /
11
3
A5.1
2
A5.1
1
A5.1
1
A5.1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
AA
10
10
D
E
G
13
11 12
14
15
15
C
F
1
A6.2
2
A6.2
1
A6.1
5
A6.2
4
A6.1
3
A6.2
2
A6.1
3
A6.1
FAC
E O
F W
ALL
BE
LLO
W
RD
RD RD
RD
RD
RD
RD
9
A3.1
7
A3.1
4
A6.2
3
A3.1
3
A3.1
Sim
5
A3.1
RD
..
.
SLOPED INSULATION TYP.SLOPED INSULATION TYP.
SLOPED INSULATION AT PERIMETER OF ROOF TYP.
AREA FOR FUTURE SOLAR PANEL LOCATION
ROOF HATCHREFER TO DETAIL /7 A5.1
SLOPED INSULATION AT PERIMETER OF ROOF (TYP)
SLOPED INSULATION TO CONTINUE ALONG PERIMETER
4%
4% [No Slope][No Slope]
LOCATION OF ANTENNA
ROOF PENETRATION LOCATION C/W GOOSENECK CABLE FLASHING
AREA FOR A/C UNITS AND CONDENSING UNITS. REFER TO 8/A3.1 FOR CURB DETAILS.
ROOF PENETRATION LOCATION C/W GOOSENECK CABLE FLASHING FOR FUTURE SOLAR PANELS.
ROOF DRAIN AND SUMP. REFER TO DETAIL 6/A3.1 (TYPICAL)
ROOF PAVERS AS PER DETAIL 11/A3.1
DOTTED LINE OF I.T ROOM BELOW
2%
1% 2%
2% 2%
LOW PARAPET WALL C/W METAL FLASHING.REFER TO DETAIL 12/A3.1 FOR ROOF EXPANSION JOINT.
300
CL
AP-2
AP-2
AP-2
AP-2
AP-3
AP-3
AP-3
AP-2
AP-2F-1
F-1
F-1
F-1
F-1
AP-3
AP-2
F-1
D
RT7PA-1
RETURN ROOF MEMBRANE COUNTER FLASHING OVER 13mm PLYWOOD
MOP ROOFING FELTS ON FACE OF 13mm PLYWOOD
MIN
200
STEEL STUD RUNNER TRACK (TYP)
CANT STRIP
FULLY ADHERED AIR/VAPOUR BARRIER
FURRING CHANNELS
Z-GIRTS
17820337
INTEGRAL PREFINISHED ALUMINUM COPING BY CLADDING MANUFACTURER. COLOR TO MATCH PORCELAIN CERAMIC PANEL SYSTEM
360
380
PT WOOD BLOCKING AS REQUIRED AT PARAPETS
13
RT7
PREFINISHED ALUMINUM FLASHING TIES INTO BUILDING
RETURN ROOF MEMBRANE COUNTER FLASHING OVER BRICK
MOP ROOFING FELTS ON FACE OF BRICK
RT-9
275
806
LSH
240
345
R20 MINERAL WOOL INSULATIONAIR BARRIER15.9 EXTERIOR SHEATHING150 STEEL STUDS @ 400MM o/c38 RIGID INSULATION15.9 EXTERIOR SHEATHINGROOF MEMBRANE
PREFINISHED ALUMINUM COPING
EOD
224 PARAPET FRAMING (TYP)19mm EXTERIOR SHEATHING38x89 PT WOOD CLEAT (CONT.)19mm EXTERIOR SHEATHINGSCREW TO PARAPET FRAMING
LOUVER SHALL BE ANCHORED BACK TO BUILDING STRUCTURE AS PER SPECIFICATIONS (TYP)
STEEL STUD RUNNER TRACK. (TYP)
14
RT-9
INTEGRAL PREFINISHED ALUMINUM COPING BY CLADDING MANUFACTURER. COLOR TO MATCH PANEL SYSTEM
PT WOOD BLOCKING AS REQUIRED.
EOD
278
FASCIA SUPPORT16 GAUGE FURRING CHANNELS15mm EXTERIOR SHEATHINGFASTENED TO PARAPET AND STRUCTURAL STEEL
EXTERIOR SHEATING, 150mm STEEL STUD @ 400 o/cEXTERIOR SHEATING
LAP ROOF VAPOUR BARRIER AND AIR BARRIER OVER PARAPET (TYP.)
CPREFINISHED ALUMINUM COPING
SEAL AIR/VAPOUR BARRIER TO WINDOW FRAME
REFER TO STRUCTURAL FOR LINTEL
STEEL BEAM. REFER TO
STRUCTURAL DRAWINGS
ALUMINUM FLASHING (TYPICAL AT ALL WINDOWS & DOORS)
166
METAL DECK
METAL DECK
320
ROOFING MEMBRANE TO WRAP OVER PARAPET
EOD
120
RAINWATER LEADERDOWNSPOUT WIDTH 100MM UNLESS OTHERWISE NOTED
A700-7462-RWL(CH)-1
100
CONDUCTOR HEADCONDUCTOR HEAD TAPER
THROUGHWALL SCUPPER
25
20
DOWNSPOUT WIDTH
CONDUCTORWIDTH 3X 20
RAINWATER LEADERDOWNSPOUT WIDTH 100MM UNLESS OTHERWISE NOTED
SCUPPER THROUGH PARAPET WALL
SCUPPER THROUGH FASCIA
DO
WN
SPO
UT
WID
TH
CO
ND
UC
TOR
HEI
GH
T 2X
GRAVEL STOP10
0MM
U/N
200MM U/N
FLASHING MIN. 100MM AROUND SCUPPER OPENING (ROOF SIDE)
CONDUCTOR HEAD
CONDUCTOR HEAD TAPER
20
SCUPPER OPENING 200MM W x 100MM H U/N
TOP OF CONDUCTOR HEAD 25MM BELOW SCUPPER OPENING (TYP.)
45.0
0°
20MM PERIMETER LIP
12
SCUPPER FLASHING MIN 12MM PAST CONDUCTOR HEAD (TYP)
FLASHING MIN. 65MM AROUND SCUPPER OPENING (WALL FACE)
SCUPPER OPENING 200MM W U/N
20MM PERIMETER LIPCUT DRIP EDGE OF FLASHING FOR CONDUCTOR HEAD AS REQUIRED
200MM U/N
GRAVEL STOP
MAY
-19
a. FABRICATE AND INSTALL IN ACCORDANCE WITH SMACNA ARCHITECTURAL SHEET METAL MANUAL - CURRENT EDITION
b. ALL JOINTS - METAL SHALL BE SOLDERED - ALUMINUM SHALL BE WELDED
50 50
5050
600
600
PAVER
RIGID INSULATION50
50
PAVERRIGID
INSULATION(BELOW)
NOTES:1. PROVIDE ROOF PAVERS AROUND PERIMETER OF VEGETATED ROOF ASSEMBLIES AND IN
OTHER LOCATIONS AS INDICATED.2. CUT RIGID INSULATION 50MM BACK FROM EDGE OF PAVER (TYPICAL).3. ON MEMBRANE ROOF SURFACES, INSULATION SHALL BE RAIN CHANNELED ON BOTTOM
EDGES.
ROOF SURFACE
7-0002 - VRA-2 - ROOF PAVER DETAIL
OC
T-15
A700-7462-SCPR-1
THROUGHWALL SCUPPER - OVERFLOW TYPE
GRAVEL STOP
100M
M H
U/N
FLASHING MIN. 100MM AROUND SCUPPER OPENING (ROOF SIDE)
SCUPPER OPENING 200MM W x 100MM H U/N
PREFINISHED METAL FLASHING 65MM (MAX.) AROUND SCUPPER OPENING (WALL FACE)
a. FABRICATE AND INSTALL IN ACCORDANCE WITH SMACNA ARCHITECTURAL SHEET METAL MANUAL - CURRENT EDITION
b. ALL JOINTS - METAL SHALL BE SOLDERED - ALUMINUM SHALL BE WELDED
THICKNESSPARAPET
OC
T-15
EXTERIOR PARAPET WALL FACE
INTERIOR (ROOF SIDE) PARAPET FACE
TOP OF ROOF
200MM W
75
BOTTOM OF SCUPPER 75MM FROM TOP OF ROOF
TOP JOINTDETAIL A
DETAIL A
BOTTOM JOINTDETAIL B
DETAIL B
ROOF DRAIN (RD)
LINE OF SUMP EDGE
1200
MIN
.
1200 MIN.
7-0014-ROOF DRAIN SUMP
OC
T-15
CLAMPING RINGSTRAINER
DECK CLAMP
TAPERED ROOF DRAIN SUMP ROOF DECK
LINE OF SUMP EDGE
SLOPE TO DRAIN
SLOPE TO DRAIN
SLOPE TO DRAIN
WITHOUT EXCEPTION1. UNLESS NOTED OTHERWISE,
ALL ROOF DRAINS SHALL BE SUMPED IN ACCORDANCE WITH APPLICABLE CRCA DETAIL
2. MIN SLOPE OF SUMP FROM SUMP EDGE TO DRAIN - 8%
NOTE:1. NOT INTENDED TO DESCRIBE ACTUAL ROOF DRAIN
INSTALLATION. ROOF DRAIN TO BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATION
THIC
KNES
S
RO
OF
ASSE
MBL
Y
WOOD BLOCKING
GCCOORD
SUBTRADES
THIC
KNES
S
RO
OF
ASSE
MBL
Y
MIN
IMU
M
250
7-0013-ROOF CURB
NO
V-18
RTU (OR SIMILAR EQUIPMENT)
ROOF CURB
RO
OF
CU
RB
HEI
GH
T
WITHOUT EXCEPTION1. ROOF MOUNTED EQUIPMENT AND FITTINGS THAT REQUIRE A ROOF CURB SHALL BE
SUPPORTED BY A CURB OF SUFFICIENT HEIGHT SO THAT THE TOP OF CURB IS AT LEAST 250mm ABOVE THE ADJACENT ROOF SURFACE.
2. ROOF CURB HEIGHT AS INDICATED BELOW MUST BE NOTED ON SUBMITTALS. 3. CONTRACTOR TO COORDINATE WITH SUPPLIERS/MANUFACTURERS ACCORDINGLY.
ROOF SURFACE
NOT INTENDED TO DESCRIBE ACTUAL ROOF CURB INSTALLATION. ROOF CURB INSTALLED IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATION
1. ROOF PLAN DOES NOT SHOW ALL PENETRATIONS THROUGH ROOF. CONTRACTOR TO REVIEW ALL CONTRACT DRAWINGS AND SPECIFICATIONS TO DETERMINE FULL SCOPE OF WORK. MAKE PROVISIONS FOR ROOF PENETRATIONS WHERE INDICATED AND REQUIRED UNDER THE SCOPE OF THIS CONTRACT.
2. PROVIDE TAPERED INSULATION AT PERIMETER OF ALL ROOFS, SKYLIGHTS AND AS INDICATED. SLOPE SHALL BE 2%.
3. UNLESS NOTED OTHERWISE, SUMP ALL ROOF DRAINS IN ACCORDANCE WITH APPLICABLE CRCA DETAIL. AS INDICATED OR AS REQUIRED, PROVIDE TAPERED CRICKETS OR SIMILAR TYPE MEASURES TO ENSURE THAT ROOF WATER FLOWS TO DRAINS.
4. SLOPE OF ROOF STRUCTURE TO BE SUPPLEMENTED BY TAPERED INSULATION. SLOPE ROOF INSULATION MIN. 1.5% TO DRAINS, TYPICAL. CRICKETS, CONSTRUCTED OUT OF TAPERED INSULATION, ARE TO PROVIDE TWO TIMES THE SLOPE OF THE ROOF STRUCTURE.
5. UPSTANDS ON ROOF FOR MECHANICAL UNITS, PARAPETS, SKYLIGHTS TO COME COMPLETE WITH CANT STRIPS.
6. WITHOUT EXCEPTION, ROOF MOUNTED EQUIPMENT AND FITTINGS THAT REQUIRE A ROOF CURB SHALL BE SUPPORTED BY A CURB OF SUFFICIENT HEIGHT SO THAT THE TOP OF CURB IS AT LEAST 250mm ABOVE THE ADJACENT ROOF SURFACE. CONTRACTORTO COORDINATE WITH SUPPLIERS/MANUFACTURERS ACCORDINGLY.
7. CONTINUOUS VAPOUR RETARDER MEMBRANE COMPONENT OF ROOF ASSEMBLIES TO BE WRAPPED UP AT ALL PARAPETS, CURBS, EXTERIOR WALL ASSEMBLIES BY A MIN. 200mm OR AS DETAILED ON DRAWINGS. TIE INTO VAPOUR BARRIER & AVB MEMBRANES ON ALL VERTICAL SURFACES. PROVIDE 'PEEL & STICK' TYPE TRANSITION MEMBRANES IN ORDER TO ENSURE CONTINUITY OF AIR BARRIERS/BUILDING ENVELOPE
A700 GENERAL NOTES - ROOF PLAN
FEB
-16
GCCOORD
SUBTRADES
WATERPROOF EXPANSION JOINT
ASPHALT ENCAPSULATING
LAYER
CAP SHEETBASE SHEET
SLIT BASE SHEET OVER JOINT
JOINT PACKED WITH COMPRESSIBLE BATT
INSULATION
2 PLY FLASHING OR TORCHED MODIFIED BITUMEN MEMBRANE
FLASHING PROVIDE TERMINATION BAR FASTENED AT 200MM O.C.
MEMBRANE CAN BE CONTINUOUS WITH EXCESS MATERIAL OR ADD
PROTECTION LAYER OVER GLAND
TORCHED APPLICATION
CL
A700 7000-REJ-TD-1
OC
T-15
GCCOORD
SUBTRADES
A700-7270-AB-2
MAY
-16
FULLY ADHERED AIR/VAPOUR BARRIER
WOOD CANT STRIP
THROUGH WALL MEMBRANE FLASHING TO FACE OF ARCHITECTURAL BLOCKRETURN ROOF MEMBRANE COUNTER FLASHING OVER BLOCKMOP ROOFING FELTS ON FACE OF BLOCK
STEEL STUD RUNNER TRACK
12.7mm PT PLYWOOD
ROOF ASSEMBLY90x200x400 CMU BLOCK
2 BL
OC
K C
OU
RSE
S
40
0
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
N N
TRUE NORTH CONSTRUCTION NORTH
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
49:4
1 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A3.1
2019/07/09
TENDER
ROOF PLAN
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
1 : 751 ROOF PLAN
1 : 109 PARAPET DETAIL
1 : 107 PARAPET DETAIL
1 : 103 CANOPY FASCIA DETAIL
1 : 105 PARAPET DETAIL
A3.110 /
A3.111 /
A3.14 /A3.16 /A3.18 / A3.12 /
A3.112 /
A3.113 /
NOTEMAINTAIN CONTINUITY OF AIR/VAPOUR BARRIERS (TYP) REFER TO DETAIL 6/A6.2
NOTEMAINTAIN CONTINUITY OF AIR/VAPOUR BARRIERS (TYP) REFER TO DETAIL 6/A6.2 NOTE
MAINTAIN CONTINUITY OF AIR/VAPOUR BARRIERS (TYP) REFER TO DETAIL 6/A6.2
NO. ISSUED FOR DATE1 SPA SUBMISSION 01 2018.01.293 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
11
TS
332
600
600
606
5684
1443 1400 1400 1442
GLGLGL
W4
GL
GLGLGLGL
GL GL GL GL
GLGLGLGL 2138
GL
GL
1206
600
332
GL
2138
18353601115360
SP SPSP
GL GL GL
GLGL FG100A
W2
2166
559
274
GLGLGLGLGL
GLGLGLGLGLGLGLGLGL GLGLGLGL
GLGLGLGLGLGLGLGLGLGLGLGLGL
GLGLGLGLGL
GLGLGLGLGL
GLGLGLGLGL
GLGLGLGLGL
GLGLGLGLGL
GLGLGLGLGLGLGLGLGLGLGLGLGL
905184018401170184018401170184018401170184018402030
21175
470
605
590
615
600
600
600
600
W1
45641220363212203632122036322054
625
5301
W7
GL
GL
332
600
1206
2138
GL
GL
GL GL
1798019051157
W6
2138
568
1546
612
3042
3751800180018001800930
PROVIDE BLANK OUT PANEL AT BACK OF LOUVER (TYP)
785
150015001500150015001365
PROVIDE BLANK OUT PANEL AT BACK OF LOUVER (TYP)
785
111018001800180018001800131511425
PROVIDE BLANK OUT PANEL AT BACK OF LOUVER (TYP)
664
1828 1704 1475
5006
PROVIDE BLANK OUT PANEL AT BACK OF LOUVER (TYP)
1083
620
785
PROVIDE BLANK OUT PANEL AT BACK OF LOUVER (TYP)
613
GROUND FLOOR 0
139721291397
W9 W8
GLGL
EQEQEQEQ
GLGL 500
2100
1833
3541125353
FG100B
GL GLGL
GL GL
W3
2166
534
2400
FG101
W10
1650475 1175
225
2175
GL-FR GL-FR
GL-FR GL-FR
720
600
A4.3M17
M19
M20 M 18
MINISTRY OF HEALTH BOX FOR PA SYSTEM
SEC
UR
ITY
PAN
EL
M109
CR
FIRE MONITORING CONTROL PANEL
BAS SYSTEM
I.T SYSTEM RACK
886 610 867
1054
600
550
FE & CA
1987
2931
A-39
FIRE MONITORING PANEL
FIRE RATED PLAYWOODPLYWOOD SHALL NOT BE PAINTED.
AREA DESIGNATED FOR BAS
2200
1584
REFER TO ELEC DWG. FOR BREAKER INFO. (TYP)
B-19
A-41
11
M.O.HBOX
FIRE RATED PLAYWOODPLYWOOD SHALL NOT BE PAINTED.
2200
1987
B-45
A-16
11
FIRE RATED PLAYWOODPLYWOOD SHALL NOT BE PAINTED.
NEMA PLUG FOR SERVER
B-43
MO
H B
OX
B-18
B-20
B-21
11
FIR
E R
ATED
PLA
YWO
OD
PLYW
OO
D S
HAL
L N
OT
BE P
AIN
TED
.
B-28
BELL DEMARC
DESIGNATED AREA FOR BELL EQUIPMENT
2200
B-24
B-26
11
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 1:
21:2
7 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A4.3
2019/07/09
TENDER
CLADDNG, GLAZING,& LOUVERELEVATIONS, I.TROOM PLAN ANDELEVATIONS
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
1 : 503 GLAZING - CREW AREA
1 : 504 GLAZING - CREW AREA
1 : 505 GLAZING - ENTRANCE VESTIBULE
1 : 501 GLAZING - VEHICLE BAY
1 : 507 GLAZING - WRITE UP ROOM
1 : 508 GLAZING - WRITE UP ROOM
WINDOW SCHEDULE
TYPE SPECIFIED BASIS OF DESIGNW1 BASIS OF DESIGN KAWNEER 1620 SSG OR EQUIVALENTW2 BASIS OF DESIGN KAWNEER 601UT OR EQUIVALENTW3 BASIS OF DESIGN KAWNEER 451 OR EQUIVALENTW4 BASIS OF DESIGN KAWNEER 1620 SSG OR EQUIVALENTW6 BASIS OF DESIGN KAWNEER 1620 SSG OR EQUIVALENTW7 BASIS OF DESIGN KAWNEER 1620 SSG OR EQUIVALENTW8 BASIS OF DESIGN KAWNEER 518 ISOPORT OR EQUIVALENTW9 BASIS OF DESIGN KAWNEER 518 ISOPORT OR EQUIVALENT
W10 BASIS OF DESIGN FLEMING TYPE 'D' FRAME OR EQUIVALENT
1 : 5010 CLADDING - LOUVERS
1 : 5011 CLADDING - LOUVERS
1 : 509 CLADDING - LOUVERS
1 : 5012 CLADDING - LOUVERS
1 : 5013 CLADDING - LOUVERS
1 : 752 GLAZING - CLERSTORY WINDOW IN WASHROOM
1 : 506 GLAZING - ENTRANCE INTERIOR
2. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS FOR INTAKE AND EXHAUST ACTIVE LOUVER LOCATIONS.
1 : 5014 GLAZING - VEHICAL BAY TO CORRIDOR
NOTEHOLLOW METAL FRAME AND GLASS SHALL BE FIRE RATED. REFER TO SPECIFICATIONS
1 : 5015 CLADDING - LOUVER AT BAY
CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS FOR INTAKE AND EXHAUST ACTIVE LOUVER LOCATIONS.
L2 - LOUVER FINISH L1 - LOUVER FINISH L1 - LOUVER FINISH
L1 - LOUVER FINISHL1 - LOUVER FINISHL1 - LOUVER FINISH
1. LOUVER SHALL BE ANCHORED BACK TO BUILDING STRUCTURE AS PER SPECIFICATIONS (TYP)
2. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS FOR INTAKE AND EXHAUST ACTIVE LOUVER LOCATIONS.
1. LOUVER SHALL BE ANCHORED BACK TO BUILDING STRUCTURE AS PER SPECIFICATIONS (TYP)
2. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS FOR INTAKE AND EXHAUST ACTIVE LOUVER LOCATIONS.
1. LOUVER SHALL BE ANCHORED BACK TO BUILDING STRUCTURE AS PER SPECIFICATIONS (TYP)
2. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS FOR INTAKE AND EXHAUST ACTIVE LOUVER LOCATIONS.
1. LOUVER SHALL BE ANCHORED BACK TO BUILDING STRUCTURE AS PER SPECIFICATIONS (TYP)
2. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS FOR INTAKE AND EXHAUST ACTIVE LOUVER LOCATIONS.
1. LOUVER SHALL BE ANCHORED BACK TO BUILDING STRUCTURE AS PER SPECIFICATIONS (TYP)
NO. ISSUED FOR DATE3 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
1 : 3016 I.T ROOM FLOOR PLAN
1 : 3017 I.T ROOM - NORTH ELEVATION1 : 30
18 I.T ROOM - EAST ELEVATION
1 : 3019 I.T ROOM - SOUTH ELEVATION
1 : 3020 I.T ROOM - WEST ELEVATION
T ectonic Cop yright 2007T ectonic Cop yright 2007T ectonic Cop yright 2007T ectonic Cop yright 2007T ectonic Cop yright 2007
SPDT
GROUND FLOOR 0
U/S OF ROOF DECK 4200
U/S OF LOW ROOF DECK 3500
ADG F
RT7
X21A P22
A.F.F.
GB2750 mm
A.F.F.
GB2700 mm
P5 P8 X21
W9
RT-9
P21 P1
IS1
A.F.F.
ATC-12750 mm
A.F.F.
GB WRGBB2600 mm
LSH
P1
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
PS-2
AP-1
GROUND FLOOR 0
U/S FINISHED CEILING 2750
U/S OF ROOF DECK 4200
U/S OF VEHICLE BAY DECK 5500
U/S OF LOW ROOF DECK 3500
2 3 4 5 6 7 8 91 10 11 12 15
M108
FG100B
P24 P21X21A P21
RT7
RT7a
X22A
GL
GLGL
GL GL
GL
WB-1 TB-1
GROUND FLOOR 0
U/S OF VEHICLE BAY DECK 5500
B ADEG CF
M112A
G112
RT7a
X22
X21
P22P22
P22
P24
X22ACW1
PS-2
PS-2
PS-2
LSH
X21
BOL
/5 A1.5REF. TO DETAIL
AP-1
WAL
L H
EIG
HT
2800
CR
OPEN
CLOSE
STOP
AUTO/HAND
WIRELESS SAFETY EDGEBY DOOR MANUFACTURER
PRESENCE SENSORBY DOOR MANUFACTURER
SENSORBY DOOR MANUFACTURER
DOOR MOTORBY DOOR MANUFACTURER
PHOTOSENSOR RECEIVER
BY DOOR MANUFACTURE
R
PHOTOSENSOR TRANSMITTERBY DOOR MANUFACTURER
RADIO REMOTE RECEIVER
BY OTHERS
MAIN PANEL BY DOOR
MANUFACTURER OPEN
CLOSE
STOP
DOOR CONTROLS
BY DOOR MANUFACTURER
LINE POWER (IN CONTRACT)
ANTENNA
WIRELESS SAFETY EDGE RECEIVERS BY DOOR MANUFACTURER
JUNCTION BOX
JUNCTION BOX
JUNCTION BOX
JUNCTION BOX
JUNCTION BOX
PREFABRICATED STEEL TABS ON PREMANUFACTURED STEEL FRAME
(BY DOOR MANUFACTURER)-18 TABS PER DOOR
ANCHOR FRAME TO EXISTING OPENING USING HILTI HY-HIT EPOXY ANCHORS
PREFABRICATED STEEL TABS ON PREMANUFACTURED STEEL FRAME (BY
DOOR MANUFACTURER)-18 TABS PER DOOR
ANCHOR FRAME TO EXISTING OPENING USING HILTI HY-HIT EXPOXY ANCHORS
*PROVIDE ALL STICKERS AND LABELS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS*
9
A2.2
Sim9
A2.2
Sim
A700-8351-FFD-1
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
SENSOR CONFIGURATION• CONFIGURE SENSOR SO THAT DOORS CLOSE 12
SECONDS AFTER PHOTOSENSOR (BEAM TO BEAM) IS BROKEN
OC
T-15
PHOTOSENSOR RECEIVERBY DOOR MANUFACTURER
MOUNTING HEIGHT DETERMINED BY DOOR MANUFACTURER
PHOTOSENSOR TRANSMITTERBY DOOR MANUFACTURERMOUNTING HEIGHT DETERMINED BY DOOR MANUFACTURER
RADIO REMOTE RECEIVER
OPEN
CLOSE
STOP
DOOR CONTROLS
BY DOOR MANUFACTURER
LINE POWER (IN CONTRACT)
JUNCTION BOX
JUNCTION BOX
JUNCTION BOX
STEEL DOOR TRACK PROTECTORS(BY DOOR MANUFACTURER)
*PROVIDE ALL STICKERS AND LABELS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS*
9
A2.2
Sim9
A2.2
Sim
A700-8363-OHD-1
LINE OF DOOR IN OPEN POSITION
610
JAMB EXTENSIONWELDED TO HEAD
JAMB EXTENSIONWELDED TO JAMB
BENT STEEL PLATE JAMB
JAMB EXTENSIONWELDED TO JAMB
DOOR OPERATORCOORDINATE SIZE, LOCATION AND MOUNTING REQUIREMENTS WITH MANUFACTURER
BENT STEEL PLATE JAMB
BENT STEEL PLATE HEAD OR STRUCTURAL STEEL
LINTEL
OPE
NIN
G T
O S
UIT
DO
OR
HEI
GH
T60
0
OPENING TO SUIT DOOR WIDTH
FULL GLAZED SECTIONAL OVERHEAD DOOR
MANUAL CHAIN OPERATOR BY DOOR MANUFACTURER
NO
CO
NTR
OLS
GR
EATE
R T
HAN
110
0 M
M A
FF
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
NOTE: JAMB EXTENSIONS ARE FOR MOUNTING OVERHEAD DOOR SPRING BRACKETS
75 75 75 75CL
NOTES:• ALL WIRING FOR DOORS (INCLUDING
LOW VOLTAGE WIRING) TO BE INSTALLED IN SURFACE MOUNTED EMT (CONDUIT)
• WIRING SHOWN IS SCHEMATIC ACTUAL INSTALLATION TO SUIT SITE CONDITIONS
ALUMINUM PANEL
ALUMINUM PANEL
ALUMINUM PANEL
ALUMINUM PANEL
SENSOR CONFIGURATION• CONFIGURE SENSOR SO THAT DOORS CLOSE AT A RATE OF
300MM PER SECOND AFTER PHOTOSENSOR (BEAM TO BEAM) IS BROKEN
OC
T-15
300
TYP.
ANCHOR TO CONCRETE SLAB AT BASE OF LADDERUSING 4mm BENT STEEL PLATE 40 x 50 x 50BOLTED TO LADDER CHANNELS AND FLOOR
C100x8 LADDER CHANNELS (OR ENGINEERED EQUIVALENT) COMPLETE WITH WELDED 32 DIA. STEEL RUNGS ALL TO BE SHOP ASSEMBLED
100 x 10mm BENT STEEL BRACKETPLATE BOLTED TO LADDER CHANNELS AND THROUGH WALL- AT MASONRY WALLS, DRILL THROUGH WALL- AT FRAMED WALLS, PROVIDE SOLID WOOD BLOCKING IN CAVITY AND DRILL THROUGH WALL
300
TYP.
ROOF ACCESS HATCH900 x 800 FINISHED OPENING
5-0003 - AL-3 - INTERIOR ROOF ACCESS LADDER DETAIL
OC
T-15
305
MIN
.
LINE OF SOLID WOOD BLOCKING IN FRAMED WALLS MIN DEPTH AS INDICATED
NOTES:ALL STEEL GALVANIZED. ENGINEERED STAMPED DRAWING REQUIRED PRIOR TO FABRICATIONALL LADDERS TO BE DESIGNED IN ACCORDANCE WITH OBC AND OHSA REQUIREMENTS AND REGULATIONS. REF. OHSA ENG DATA SHEET 2-04 (CURRENT REVISION).
150
SITE
VER
IFY
HEI
GH
TTOP OF LADDER 150 BELOW U/S OF ACCESS HATCH
150
CL
C100 STEEL CHANNEL
25mm DIAMETER STEEL RUNG AT 300o/c VERTICALLY AND WELDED BETWEEN C100 STEEL CHANNELS
400 x 175 x 100 x 10mmU-BENT STEEL PLATE BRACKET
300
o/c
5-0004 - AL-4 - INTERIOR ROOF ACCESS LADDER DETAIL
• GRIND SMOOTH ALL WELDS• PRIME AND PAINT ALL
STEEL
OC
T-15
NOTES:1. ALL STEEL GALVANIZED. 2. ENGINEERED STAMPED DRAWING REQUIRED PRIOR TO FABRICATION3. ALL LADDERS TO BE DESIGNED IN ACCORDANCE WITH OBC AND OHSA REQUIREMENTS
AND REGULATIONS. REF. OHSA ENG DATA SHEET 2-04 (CURRENT REVISION).
AT FRAMED WALLS - LINE OF SOLID WOOD BLOCKING IN WALLS MIN DEPTH AS INDICATED
CL150
480
C100 STEEL CHANNEL
AT MASONRY WALLS - FILL BLOCKS SOLID AT THROUGH BOLT LOCATIONS
1 : 752 BUILDING SECTION - CREW AREA
1 : 751 BUILDING SECTION - VEHICLE AND CREW AREA
1 : 753 BUILDING SECTION - VEHICLE BAYS
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
50:3
6 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A5.1
2019/07/09
TENDER
BUILDING SECTIONS& DETAILS
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
A5.14 / A5.15 /
A5.17 /
A5.18 /
NO. ISSUED FOR DATE1 SPA SUBMISSION 01 2018.01.293 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
11
11
T ecton ic Cop yright 2007
T ecton ic Cop yright 2007
A7.1
6
4
10
8A7.1
7
5
11
9
140 714 1397 1000 129 1000 1397 709
1200
129
2075
123
480
1185
144
2075
123
2247
FEMALEWASHROOM/ SHOWER
107
MI-T
TOWM
VANITY REFER TO DETAIL 1/A7.3
SPACE FOR ADULT CHANGE TABLE
(N.I.C.)
M106
WOOD BENCH REFER TO 2/A7.3
VANITY REFER TO DETAIL 1/A7.3
WOOD BENCHREFER TO 2/A7.3
M107
TOWM
FSFS
MALEWASHROOM/ SHOWER
106
1920
129
1355
P8 P8P8
P5P5P21
X21
P8
P8
DODO
DO
RSPH RSPH
PROVIDE WOOD BLOCKING AS REQUIRED FOR FOLDING SEAT PRIOR TO BOARDING OF WALLS
500
DO
P1aSD SD
2600
BFSH-GBR
SHOWER CURTAIN REFER TO DETAIL
1000
RSHDO
/3 A7.3REFER TO DETAIL
2600
1951
1000
BFSH-GBR
TOWM
SHOWER CURTAINREFER TO DETAIL
RSH
MARBLE TRIM
2600
WT - 1
WT - 2
FS
1291355
SHOWER CURTAINREFER TO DETAIL
REFER TO DETAIL
/3 A7.3
500
2100
2397
W9
WOOD BENCH REFER TO DETAIL
FS
WT - 1
WT- 2
2600
SHOWER CURTAIN - REFER TO DETAIL
MARBLE TRIM
RSPH10
00
EQ EQCH
CH CH
REFER TO DETAIL
/5 A7.3
/2 A7.3
1100
1550
PTD
1100
/3 A7.3
2600
MI-T
WOOD BENCH REFER TO DETAIL
820
185
1095
TOWM
2100
500
CH
WT -3
SD
TP
/2 A7.3
1
A7.3
TOWM
MI-T
TP
SD
CH
1
A7.3
2600
500
1280
820
W8
SHOWER CURTAINREFER TO DETAIL
FS
MARBLE TRIM
EQ EQ
RSPH
CH
CH CH
WOOD BENCH REFER TO DETAIL /2 A7.3
1100
PTD
1100
2600
BFSH
-GBR
?
SHOWER CURTAIN REFER TO DETAIL
1951
649
1355129
A700-1000-FMH -2
AUG
-18
BIOHAZARD WASTE DISPOSAL
(BWD)
**NOTE: BIOHAZARD BIN MUST BE MOUNTED AT A VISIBLE LOCATION WITH THE UNIVERSAL BIOHAZARD
DANGER SYMBOL.
LIGHT SWITCH (LS)
900
MIN
. - 1
100
MAX
.
OUTLET(O)
400
MIN
. 900
MIN
. - 1
100
MAX
.
THERMOSTAT(T)
FIRE EXTINGUISHER
(FE)90
0 M
IN. -
110
0 M
AX.
LINE OF CABINET INSTALLATION TO MAINTAIN REQUIRED HEIGHT OF EXISTINGUISHER (TYP.)
CARD READER(CR)
FIRE ALARM PULL STATION
(FP)
900
MIN
. - 1
100
MAX
.
DOORBELL(DB)
900
MIN
. - 1
100
MAX
.
DOOR OPERATOR BUTTON
(DO)
900
MIN
. - 1
100
MAX
.
900
MIN
. - 1
100
MAX
.
FOUR FOLD DOOR CONTROLS
(FFDC)
900
MIN
. - 1
100
MAX
.
OVERHEAD DOOR CONTROLS
(OHDC)
900
MIN
. - 1
100
MAX
.
300 MIN.
MINIMUM CLEARANCE TO
DOOR EDGE
WHERE DO, DB, CR MOUNTED SIDE BY SIDE,
MOUNT ALL AT SAME HEIGHT
DO
OR
ED
GE
900
MIN
. - 1
100
MAX
.
CO
NTR
OLS
OTH
ER
GCCOORD
SUBTRADES
NOTE: ALL DIMENSIONS SUBJECT TO SPECIFIC MUNICIPAL REQUIREMENTS. CONFIRM WITH CONSULTANT PRIOR TO INSTALLATION.
NOTE: FOR MOUNTING HEIGHTS NOT SHOWN. CONFIRM HEIGHT WITH CONSULTANT PRIOR TO INSTALLATIONNO CONTROLS, OPERATING OR DISPENSING COMPONENTS HIGHER THAN 1100mm AFF.
AODA MANDATORY REQUIREMENTENSURE CLEAR FLOOR SPACE OF 860MMx1480MM MIN CLEAR OF DOOR SWINGS.REVIEW WITH CONSULTANT PRIOR TO ROUGH-IN
NOTE: FOR MOUNTING HEIGHTS SHOWN AS A RANGE. SELECT HEIGHT AND INSTALL ALL FIXTURES AT THAT HEIGHT (TYP.). FIXTURES THAT ARE WITHIN VISUAL SIGHTLINE OF EACH OTHER MUST BE AT SAME HEIGHT.
900
MIN
. - 1
100
MAX
.
CO/NOx SYSTEMS
CONTROL PANEL
NOx SENSOR(MOUNTED HIGH)LOCATION ??
CO SENSOR(MOUNTED LOW)LOCATION ??
LINE OF CEILING ABOVE
LINE OF FLOOR
RETRACTABLE SHOWER SEAT
(RSS)
FACE OF WALL
SHOWER HEAD(SH)
RECESSED SOAP HOLDER
(RSH)
SHOWER CURTAIN + ROD
(SC+R)
1905
NOTE: HAND-HELD SHOWER HEAD TO BE LOCATED SO THAT IT CAN BE REACHED AND OPERATED FROM SHOWER SEAT POSITION.
FIXED SHOWER HEAD
MINIMUM 1800mm OF FLEXIBLE HOSE
SHOWER VALVE INSTALLED ABOVE GRAB BAR (DO NOT OBSTRUCT THE USE OF THE SHOWER CONTROLS)
CURTAIN
ROD
MO
UN
T
460
MIN
.
400
MAX.
500
MIN.
450
FACE OF WALL WITH SHOWER HEAD (SH)
900
MIN
. - 1
200
MAX
.
BA
RR
IER
FR
EE S
HO
WER
DET
AIL
S
CLEQ EQ
GBR
LINE OF RETRACTABLE SHOWER SEAT (RSS) - SEE DETAIL
MIN
1004
- TO
SH
OW
ER V
ALVE
2100
- T
O F
IXED
SH
OW
ER H
EAD
LINE OF CORNER AT OPEN SIDE OF SHOWER
PROVIDE WOOD BLOCKING AS
REQUIRED
RSH - SEE DETAIL
SC+R - SEE DETAIL
GCCOORD
SUBTRADES
1200
800
AFF
750
- GR
AB B
AR H
EIG
HT
1000 - GRAB BAR LENGTH
HAND DRYERS
(HD)
GRAB BARS (GBR - LGBR)SANITARY NAPKIN DISPOSAL (SN)TISSUE DISPENSERS (TTD)
840
600 - GRAB BAR
GBR
FRONT
NOTE: ALL DIMENSIONS SUBJECT TO SPECIFIC MUNICIPAL REQUIREMENTS. CONFIRM WITH CONSULTANT PRIOR TO INSTALLATION.
NOTE: FOR MOUNTING HEIGHTS NOT SHOWN. CONFIRM HEIGHT WITH CONSULTANT PRIOR TO INSTALLATIONNO CONTROLS, OPERATING OR DISPENSING COMPONENTS HIGHER THAN 1100mm AFF.
WR
WASTE RECEPTACLES
(WR)
PTWR
COMBINED PAPER TOWEL DISPENSER/WASTE
RECEPTACLES (PTWR)
GBR
SIDE
MI(T)
MI(T)
BF LAV
840
MAX
.
BF LAV
840
MAX
.
1000
T.O
. SH
ELF
EQ EQ
1000
T.O
. SH
ELF
SLFSLF
TILT MIRROR (MI(T))STAINLESS STEEL SHELF (SSS)
SN
600
300
STD
STD
900
MIN
. - 1
200
MAX
.
COAT HOOK (CH)
A700-1000-FMH -1
CL
CL
CL
AODA MANDATORY REQUIREMENTENSURE CLEAR FLOOR SPACE OF 860MMx1480MM MIN CLEAR OF DOOR SWINGS.REVIEW WITH CONSULTANT PRIOR TO ROUGH-IN
900
MIN
. - 1
000
MAX
.
900
MIN
. - 1
100
MAX
.
900
MIN
. - 1
100
MAX
.
NO
V-15
BARRIER-FREE SINK
NOTE: FOR MOUNTING HEIGHTS SHOWN AS A RANGE. SELECT HEIGHT AND INSTALL ALL FIXTURES AT THAT HEIGHT (TYP.). FIXTURES THAT ARE WITHIN VISUAL SIGHTLINE OF EACH OTHER MUST BE AT SAME HEIGHT.GC
COORD
SUBTRADES
MAX
.
1000
TOP VIEW
MIN.
400
MIN
.
200
SHELF / COUNTER(SLF)
TWIN TISSUE DISPENSER
(TTD)
SINGLE TISSUE DISPENSER
(STD)
900
MAX
.
450
MIN
.
**NOTE: TISSUE DISPENSER ELEVATION MAY VARY. REPORT ANY
DISCREPANCIES TO CONSULTANT PRIOR TO
INSTALLATION.
BA
RR
IER
FR
EE S
INK
DET
AIL
S
WA
SHR
OO
M A
CC
ESO
RIE
S
PAPER TOWEL DISPENSER
(PTD)
SOAP DISPENSER
(SD)
1100
MAX
.
900
MIN
.
900
MIN
. - 1
100
MAX
.
E
IN UNIVERSAL WASHROOMS EQUIPPED WITH AN EMERGENCY CALL SYSTEM- REFER TO DETAIL ECS-1
IN THE EVENT OF AN EMERGENCY PUSH
EMERGENCY BUTTONAND AUDIBLE AND
VISUAL SIGNALWILL ACTIVATE
430
MAX
.
URINAL(UR)
750
VER
TIC
AL C
OM
PON
ENT
750
- GR
AB B
AR
BAR TO FACE OF FIXTURE150 - FACE OF GRAB
HORIZONTAL COMPONENT
750 - GRAB BAR
EQ EQ
SN
<50mm>38mm
30
300 460
CL
<50mm>38mm
30
LGBR LGBR
TO SIDE WALL
460 - DISTANCE 460 460
URINAL (SEE PLAN)
920 - DISTANCE TO NEXT
VER
T G
RAB
BAR
600
1000
MAX.
380
MAX.
38050MM MIN.
CLCL
CL
CL URINAL SCREEN(WHERE INDICATED)
CL CL
CL GRAB BARS(WHERE INDICATED)
EQ EQ
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
N N
TRUE NORTH CONSTRUCTION NORTH
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
41:4
5 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A7.1
2019/07/09
TENDER
WASHROOMDETAILS & FIXTUREMOUNTING HEIGHTS
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
1 : 351 EMS - WASHROOMS
1 : 356 RM 107 - SOUTH ELEVATION
1 : 357 RM 106 - SOUTH ELEVATION
1 : 358 RM 107 - EAST ELEVATION
1 : 3510 RM 107 - NORTH ELEVATION
1 : 354 RM 107 - WEST ELEVATION
1 : 359 RM 106 - EAST ELEVATION
1 : 3511 RM 106 - NORTH ELEVATION
1 : 355 RM 106 - WEST ELEVATION
WASHROOM ACCESSORIESTAG DESCRIPTION QUANITY
PTD PAPER TOWEL DISPENSER 2RSPH RECESSED SHAMPOO HOLDER 2RSH RECESSED SOAP HOLDER 2FS RETRACTABLE SHOWER SEAT 2
SC+R SHOWER CURTAIN 2SD SOAP DISPENSER 3TP SURFACE MOUNTED TOILET TISSUE DISPENSER 2
WASHROOM ACCESSORIESTAG DESCRIPTION QUANITY
BFSH-GBR BARRIER FREE SHOWER GRAB BAR (750mmVERTICAL AND HORIZONTAL)
2
MI-T BARRIER FREE TILTED MIRROR 2CH COAT HOOK 16
GBR LS-H L-SHAPED 31mm BAR TO BE 750mm LONG AND750mm VERTICAL (LS), GRAB BAR TO HAVE 600mmLONG HORIZONTAL (H)
2
L LOCKERS AS SPECIFIED (REFER TO DRAWINGSFOR LAYOUT)
34
A7.13 /
A7.12 /
NOTEREFER TO DETAIL 4/A8.1 FOR UNIVERSAL WASHROOM DETAILS.
NO. ISSUED FOR DATE3 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
11
A7.2M5
A7.2
A7.2M11
M 2
A7.2M10
A7.2M6
1100 350 610 350
CHARGING STATION REFER TO 4/A7.2
MILLWORK NICHE -REFER TO DETAIL
13/A7.2
SOLID SURFACE COUNTER
2700
1050
100
MILLWORK NICHE - REFER TO DETAIL 19/A7.2
FR
1450
1150
G.C TO COORDINATE POWER WITH ELECTRICAL DRAWINGS PRIOR TO POURING OF SLAB
FE & CA640 1100 1100
CL
3190
350 350610(U)2DRMRW
(U)2DR1SHLF (U)2DR1SHLF
2DRSNK 1DR1DWR3
DWR
2DRFR
2DR2DWR
3771
EQEQEQ
EQEQ 1/2 EQ1/2 EQ
990
16
A7.2
17
A7.2
12
A7.2
914
525
900
14
A7.2
1560
BULKHEAD
SD
470
1870
410
470
350610350
1310
DSPNCH 874
40
CHARGING STATION REFER TO 18/A7.2
350 610 350
DSPNCH
1310
4087
4
10025001002700
WDPNL874x2500 87
440
914
10025001002700
874
40
WDPNL874x2500 91
4
GABLE
LIGHT VALANCE
DRAWER UNITBACKSPLASH
35011301130350
90
TB-1REFER TO ELECTRICAL DRAWINGS
FOR POWER AND VOICE/DATA
EQ EQ EQ
GYPSUM BULKHEAD
(U)2DR1SHLF (U)2DR1SHLF (U)2DR1SHLF (U)2DR1SHLF
3DWR
3DWR
SSCTRTP
520
565 565 565 565
780
810
100
750
WDPNL
SIM
15
A7.2
TACKBOARD SHALL BE FLUSH MOUNTED TO BLOCKWALL
50mm GROMMET
G.C TO COORDINATE CUTOUTS FOR POWER AND DATA IN WOOD PANELS AND TACKBOARD
2460
A700-16000-CHST-1
4X USB CHARGERS WITH TAMPER RESISTANT 20A DUPLEX RECEPTACLESCL
150
LINE OF ADJACENT COUNTER OR OTHER SURFACE
FOUR-GANG COVER PLATEUSB CHARGING STATION PROVIDE LABEL ON PLATE
SINGLE TWO GANG
FOUR GANG
PROVIDE LABEL ON PLATE
TWO-GANG COVER PLATE
USB CHARGERUSB CHARGER PROVIDE LABEL ON PLATE
TWO-GANG COVER PLATE
4X USB CHARGERS WITH TAMPER RESISTANT 20A DUPLEX RECEPTACLES
4X USB CHARGERS WITH TAMPER RESISTANT 20A DUPLEX RECEPTACLES
MAY
-16
** ALL WORK TO BE COMPLETED IN ACCORDANCE WITH AWMAC ARCHITECTURAL WOODWORK STANDARDS AS SPECIFIED
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
OC
T-15
METAL PILASTER STRIPS
GYPSUM BOARD BULKHEADALIGN WITH FACE OF UPPER CABINET BODY (TYP.)
6mm PANEL ON 19mm WOOD RAILS
CABINET PULL
UNDER CABINET LIGHT FIXTURE
20mm PANEL LIGHT VALANCE c/w SOLID EDGING
20mm PANEL SHELF c/w SOLID EDGING ALL SIDES
20 305 20
10
AS N
OTE
D52
5
(U)2
DR
1SH
LF
105
20
7579
5
325
20mm PANEL c/w SOLID EDGING
20mm PANEL DRAWER FACE c/w SOLID EDGING ALL SIDES
6mm PANEL ON 19mm WOOD RAILS
BASE
CABINET PULL
SOLID SURFACE COUNTERTOP
20mm PANEL DOOR CLEAT
20mm PANEL DOOR FACE c/w SOLID EDGING ALL SIDES
CUT PANEL NEATLY FOR PLUMBING ROUGH-INS (TYP.)
SINK
PROVIDE WOOD SUPPORT AROUND CUT OPENINGS (TYP.) 91
5
75
655
100
795
20 100
2DR
SNK
409
140
5
625
40
610
** ALL WORK TO BE COMPLETED IN ACCORDANCE WITH AWMAC ARCHITECTURAL WOODWORK STANDARDS AS SPECIFIED
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
OC
T-15
GYPSUM BOARD BULKHEADALIGN WITH FACE OF UPPER CABINET BODY (TYP.)
6mm PANEL ON 19mm WOOD RAILSCONNECT WOOD RAILS TO GABLES (TYP.)
SS 'D' PULL
305 20
10
LINE OF 20mm PANEL GABLE c/w SOLID WOOD EDGING ON ALL EXPOSED EDGES
20mm PANEL DOOR FACE c/w SOLID EDGING ALL SIDES
20mm PANEL VALENCE c/w SOLID WOOD EDGING ON ALL EXPOSED EDGES GABLE DEPTH TO SUIT FRIDGE
FRID
GE
TO S
UIT
(U)2
DR
FR
** ALL WORK TO BE COMPLETED IN ACCORDANCE WITH AWMAC ARCHITECTURAL WOODWORK STANDARDS AS SPECIFIED
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
OC
T-15
METAL PILASTER STRIPS
GYPSUM BOARD BULKHEADALIGN WITH FACE OF UPPER CABINET BODY (TYP.)
6mm PANEL ON 19mm WOOD RAILS
CABINET PULL
UNDER CABINET LIGHT FIXTURE
20mm PANEL LIGHT VALANCE c/w SOLID EDGING
20mm PANEL SHELF c/w SOLID EDGING ALL SIDES
20 305 20
10
AS N
OTE
D52
5
(U)2
DR
1SH
LF
105
20
7579
5
325
20mm PANEL COMPLETE WITH MATCHED EDGE BANDING
20mm PANEL DRAWER FACE COMPLETE WITH MATCHED EDGE BANDING ALL SIDES
BASE TILE
SOLID SURFACE COUNTERTOP
CABINET PULL20mm PANEL DRAWER FACE COMPLETE WITH MATCHED EDGE BANDING ALL SIDES
20mm PANEL DRAWER FACE COMPLETE WITH MATCHED EDGE BANDING ALL SIDES
655
CABINET PULL
CABINET PULL
610
40
480
5140
5140
94010
020
795
100
3DW
R
6mm PANEL ON 19mm WOOD RAILS
** ALL WORK TO BE COMPLETED IN ACCORDANCE WITH AWMAC ARCHITECTURAL WOODWORK STANDARDS AS SPECIFIED
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
OC
T-15
20mm PANEL COMPLETE WITH SOLID EDGING
BASE TILE
SOLID SURFACE COUNTERTOP20mm PANEL DOOR CLEAT
20mm PANEL DRAWER FACE COMPLETE WITH SOLID EDGING ALL SIDES
20mm PANEL DRAWER FACE COMPLETE WITH SOLID EDGING ALL SIDESCABINET PULL
ALIGN FACE OF BOTTOM DRAWER TO ALIGN WITH BOTTOM OF CABINET BODY
40
762
750
20mm PANEL DRAWER FACE COMPLETE WITH SOLID EDGING ALL SIDESCABINET PULL
CABINET PULL
300
0514
55
145
SOLID SURFACE BACKSPLASH (IF INDICATED ON ELEVATION)
64
METAL PILASTER STRIPS
GYPSUM BOARD BULKHEADALIGN WITH FACE OF UPPER CABINET BODY (TYP.)
6mm PANEL ON 19mm WOOD RAILS
SS 'D' PULL
FLOURESCENT LIGHT FIXTURE
20mm PANEL LIGHT VALANCE COMPLETE WITH SOLID EDGING
725
110
20mm PANEL SHELF c/w SOLID EDGING ALL SIDES
26 300 20
10
300
AS N
OTE
D
(U)1
DR
1SH
LF
200
WB-1 TB-1
778
322
116
1184
/*REF. - 7 A7.3/*REF. - 7 A7.3
1600
EQ EQ EQ EQ
BULKHEAD
13
A7.2
WHITEBOARD AND TACKBOARD SHALL BE FLUSH MOUNTED TO BLOCKWALL
PROVIDE 2 - DUPLEX POWER OUTLETS ON EACH SIDE SIDE
WALL AT COUTER HEIGHT REFER TO ELEC. DRAWINGS
1100
950
** ALL WORK TO BE COMPLETED IN ACCORDANCE WITH AWMAC ARCHITECTURAL WOODWORK STANDARDS AS SPECIFIED
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
OC
T-15
GYPSUM BOARD BULKHEADALIGN WITH FACE OF UPPER CABINET BODY (TYP.)
6mm PANEL ON 19mm WOOD RAILS
CABINET PULL
UNDER CABINET LIGHT FIXTURE
20 305 20
10
AS N
OTE
D52
5
(U)2
DR
MR
W
OPE
NIN
G
410
MIC
RO
WAV
E
500
105
20
325
795
75
AS N
OTE
D
LINE OF SIDE GABLE BEYOND
20mm PANEL LIGHT VALANCE c/w SOLID EDGING
SOLID SURFACE COUNTERTOP
75
20mm PANEL c/w MATCHING EDGE BANDING
20mm PANEL DRAWER FACE c/w MATCHING EDGE BANDING ALL SIDES
METAL PILASTER STRIPS
6mm PANEL ON 19mm WOOD RAILS
BASE
CABINET PULL7520mm PANEL DOOR CLEAT
2DR
2DW
R
610
400 180
100
2079
510
0
625
5
140
940
655
40
CABINET PULL
** ALL WORK TO BE COMPLETED IN ACCORDANCE WITH AWMAC ARCHITECTURAL WOODWORK STANDARDS AS SPECIFIED
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
OC
T-15
SOLID SURFACE COUNTERTOP
20mm PANEL BACK PANEL
20mm PANEL SIDE / MID GABLE COMPLETE WITH SOLID WOOD EDGING
40
300
2026
379
520 20mm TOP PANEL COMPLETE WITH
SOLID WOOD EDGINGRN
WY
1200
311
611
00
WHITEBOARD / TACKBOARDREFER TO ELEVATION
20mm BOTTOM PANEL COMPLETE WITH SOLID WOOD EDGING
POWER OUTLETS AS INDICATED
A7.2M
8
WB TBRNWY
1600
350
140
DO
A700 6400-MW-DETAIL
** ALL WORK TO BE COMPLETED IN ACCORDANCE WITH AWMAC ARCHITECTURAL WOODWORK STANDARDS AS SPECIFIED
* SHOP DRAWING REQUIRED PRIOR TO FABRICATION
BASE TILE
SOLID SURFACE COUNTERTOP
20mm PANEL BACK PANEL
20mm PANEL SIDE GABLE COMPLETE WITH SOLID WOOD EDGING
20mm PANEL SHELF COMPLETE WITH SOLID WOOD EDGING
40
300
2026
325
025
010
9
20
20mm PANEL SHELF COMPLETE WITH SOLID WOOD EDGING
20mm TOP PANEL COMPLETE WITH SOLID WOOD EDGING
20mm BOTTOM PANEL COMPLETE WITH SOLID WOOD EDGING
LINE OF GABLE BEYONDDSP
NC
H
914
1. ALL CUPBOARDS, GABLES, SHELVES, DOORS & DRAWER FRONTS TO BE:A. 20mm HD52 - RIVA - PB-M2 CORE c/w MATCH EDGEBANDING.
2. ALL CUPBOARD BACKINGS TO BE:A. 6mm HD52 - RIVA - MDF CORE c/w MATCH ING EDGEBANDING.
3. DRAWER SIDES @ BOTTOMS TO BE:A. 12.7mm WHITE MELAMINE.
4. ALL EXPOSED PANEL EDGES TO BE EDGED IN MATCHING EDGEBANDING , INCLUDING ALL 4 EDGES OF DOORS, DRAWER FACES, AND ADJUSTABLE SHELVES.
SUPPLY AND INSTALL HARDWARE AS FOLLOWS:1. CONCEALED SELF-CLOSING HINGES.2. 185mm STAINLESS STEEL ROD TYPE DOOR & DRAWER HANDLES.3. ALL DRAWERS ON HEAVY DUTY TELESCOPING CUSHIONED ROLLING METAL SLIDES.4. RECESSED METAL ADJUSTABLE PILASTER STRIPS.5. PROVIDE KEY LOCKS WHERE INDICATED, EACH LOCK SHALL BE UNIQUE.6. BOBRICK B-6827 S.S. HAT & COAT HOOKS FOR ALL CLOTHES HOOKS IN SHOWERS.
**NOTE: ALL MILLWORK HARDWARE SUPPLIED & INSTALLED UNDER MILLWORK CONTRACT.
A700 GENERAL NOTES - MILLWORK
AUG
-18
11
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
N N
TRUE NORTH CONSTRUCTION NORTH
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
15:2
0 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A7.2
2019/07/09
TENDER
MILLWORK PLAN,ELEVATIONS &DETAILS
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
1 : 301 KITCHEN FLOOR PLAN
1 : 305 KITCHENETTE ELEVATION
1 : 3011 NORTH EMS-KTCHN ISLAND ELEV.
1 : 3010 SOUTH EMS-KTCHN ISLAND ELEV.
1 : 302 WEST EMS-KTCHN ISLAND ELEV.
1 : 306 EAST EMS-KTCHN ISLAND ELEV.
1 : 303 WRITE-UP DESK ELEVATION
A7.24 /
A7.212 /
A7.217 /
A7.216 /
A7.215 /
1 : 308 MILLWORK - RUNWAY
A7.214 /
A7.213 /
1 : 257 RUNWAY - MILLWORK
PROVIDE 2 - DUPLEXPOWER OUTLETS ONEACH SIDE OF WALLAT COUTER HEIGHTREFER TO ELEC DRAWINGS
A7.29 /
A7.218 /
NO. ISSUED FOR DATE3 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
11
TS
HM - TYPE 'M' HM - TYPE 'L'HM - TYPE 'NL2' HM - TYPE 'G' HM - TYPE '2G' HM - TYPE 'FG' HM - TYPE 'M2'
EQ EQ
HIN
GE
SID
E
MIN. 300 (PUSH SIDE)MIN. 600 (PULL SIDE)
LIN
E O
F FR
AM
E (R
EFE
R T
O F
RA
ME
TYP
ES
)
ED
GE
OF
AD
JAC
EN
T W
ALL
150
00-0001 - DR-1 - DOOR LEGEND AND FRAME TYPES
VARIES
HM FRAME TYPE - WRAP (FRAMED WALL)
DOUBLE STUD AT FRAME (METAL STUD SHOWN)COMBINATION STUD ANCHOR(UNLESS OTHERWISE NOTED)
FRAMED WALL ASSEMBLY
VARIES
HM FRAME TYPE - WRAP (MASONRY WALL)
WIRE ANCHOR(UNLESS OTHERWISE NOTED)
FRAME THROAT TO SUIT WALL THICKNESS
FILL FRAME SOLID
MASONRY WALL
*FOR WALLS < 200MM REFER TO WALL THICKNESS ON DOOR SCHEDULE
*FOR WALLS < 200MM REFER TO WALL THICKNESS ON DOOR SCHEDULE
VARIES (>200MM)
HM FRAME TYPE - BUTT (MASONRY WALL)
WIRE ANCHOR(UNLESS OTHERWISE NOTED)
FRAME 146 THROAT
FILL FRAME SOLID
MASONRY WALL
*FOR WALLS > 200MM REFER TO WALL THICKNESS ON DOOR SCHEDULE
BULLNOSE EXPOSED CORNER
FRAME TYPES
DOOR TYPES
VARIES
HM FRAME TYPE - BUTT (EXTERIOR WALL)
2-PLY 38x89 WOOD BLOCKING AT JAMB (TYP.) ANCHORED TO WALL ASSEMBLY
FRAME -146 THROAT
INSULATED FRAME
WALL
WALL CAVITY
BUTTERFLY WALL ANCHOR AND ANCHOR BOLT
VARIES
ALUM FRAME TYPE - BUTT (INTERIOR WALL)
WIRE ANCHOR(UNLESS OTHERWISE NOTED)
MASONRY WALL
FRAME THROAT TO SUIT WALL THICKNESS LINE OF FINISHED WALL
CAULK
VARIES
ALUM FRAME TYPE - BUTT (EXTERIOR WALL)
2-PLY 38x89 WOOD BLOCKING AT JAMB (TYP.) ANCHORED TO WALL ASSEMBLY
THERMALLY BROKEN ALUMINUM FRAME
WALL
WALL CAVITY
BUTTERFLY WALL ANCHOR AND ANCHOR BOLT
LINE OF FINISHED WALL CAULK
EQ EQ
EQ EQINTEXT
INTEXT
EQ.EQ.
EQ EQ
THERMALLY BROKEN ALUMINUM FRAME
1922
565
020
0
1075
150 150
180
1910
75
150 150150 150
1940
014
00
150 150
180
225
19
WIDTH
DOOR TYPE
MIN
. DIS
TAN
CE
FR
OM
FR
AM
E T
O C
OR
NE
R
19
150 150
MIN. CLEARANCE FROM FRAME TO SWITCHES OR CONTROLS (TYP.)
WIDTH
HEI
GH
T
WIDTH
19H
EIG
HT
HEI
GH
T
CL
CL
CL
EQ EQ
CAULK
1350
CL
DECAL STRIP
FIRE PROTECTION RATED GLASS IN RATED DOORS (TYP.)WIRE GLASS IN EXTERIOR DOORS (TYP.)
180
HM - TYPE 'NL1'
150 150
1912
0160
0
FIRE PROTECTION RATED GLASS IN RATED DOORS (TYP.)
FIRE PROTECTION RATED GLASS IN RATED DOORS (TYP.)
FIRE PROTECTION RATED GLASS IN RATED DOORS (TYP.)
ASTRAGAL
ED
GE
OF
AD
JAC
EN
T W
ALL
LATC
H S
IDE
NOTES:1. SHOP DRAWING REQUIRED PRIOR TO FABRICATION. SHOP DRAWINGS SHALL REFERENCE DOOR TYPE ELEVATIONS AS SHOWN2. DOOR AND FRAME MATERIAL - REFER TO SCHEDULE.3. ALL DOORS AND FRAMES IN RATED ASSEMBLIES SHALL BE APPROPRIATELY LABELLED4. CAULK AND PAINT ALL EXPOSED EDGES OF DOORS AND FRAMES5. UNDERCUT DOORS WHERE INDICATED ON DRAWINGS6. REFER TO MECHANCIAL DRAWINGS FOR LOUVER SIZES IN TYPE 'L' DOORS7. ALL LITES IN EXTERIOR DOORS SHALL BE SEALED AND THERMALLY BROKEN8. ALL EXTERIOR DOOR FRAMES SHALL BE FILLED WITH CLOSED CELL FOAM INSULATION (JAMBS AND HEAD)9. ALL EXTERIOR DOORS SHALL BE COMPLETELY WEATHERSTRIPPED AND GASKETED10. ALL EXTERIOR DOORS SHALL HAVE A PREFABRICATED ALUMINUM THRESHOLD11. CAULK FRAME TO FLOOR AT EXPOSED CONCRETE FLOOR FINISHES12. PROVIDE DOOR BUMPERS ON ALL STEEL FRAMES
TYPICAL DOOR INSTALLATION DETAILS
UN
DE
RC
UT
DO
OR
WH
ER
E N
OTE
D- S
EE
AR
CH
ITE
CTU
RA
L A
ND
ME
CH
AN
ICA
L
DOOR OPERATOR (WHERE NOTED)
LOU
VER
(H)
225
EQ. 481 EQ.
LOUVER(W)
HIN
GE
SID
E
DOOR TYPE
LATC
H S
IDE
FIRE DOOR INSTALLATION DETAILS
19MM MAX. CLEARANCE BETWEEN DOOR EDGE AND FINISHED FLOOR/THRESHOLD
3.18MM CLEARANCE BETWEEN DOOR EDGE AND FRAME(1.59 MIN./ 4.77 MAX)
3.18MM CLEARANCE BETWEEN DOOR EDGE AND FRAME(1.59 MIN./ 4.77 MAX)
* ALL FIRE DOOR INSTALLATIONS
SHALL CONFORM TO NFPA 80
JUN
E-17
60
SPACED
EQUALLY60
75 (typ.)
R 25
DECAL STRIP IN ACCORDANCE WITH OBC 3.8.3.3
ACTIVE LEAF - LEFT DOOR UNLESS OTHERWISE NOTED
REF
. TYP
. FM
H D
ETAI
LS
(DOOR IN OPEN POSITION)
MIN. 865 CLEAR
LINE OF DOOR IN OPEN POSITION
MIN
. DIS
TAN
CE
FR
OM
FR
AM
E T
O C
OR
NE
R
ALUM - TYPE 'FG'
89 89
8617
219
1350
CL
DECAL STRIP
46
SPACED
EQUALLY 46
75 (typ.)
R 25
DECAL STRIP IN ACCORDANCE WITH OBC 3.8.3.3
FIRE PROTECTION RATED GLASS IN RATED DOORS (TYP.)
THROAT BACKBENDBACKBEND
FACE OF DOOR FRAME
JAMB DEPTH
FACE OF DOOR FRAME
HM FRAME DEFINITIONS
OHD110J
NL1110A
G112
M112B
M107
M106
M112A
M109
M108
FG100B
FG100AFFD
110FFFD110E
FFD110D
FFD110C
OHD110I
OHD110H
OHD110G
NL1110B
VESTIBULE
100
ACCESSCORRIDOR
101
KITCHEN /DINING
102LOUNGE
ROOM
103
WRITE-UPROOM
104
LOCKERROOM
105
FEMALEWASHROOM/ SHOWER
107
MALEWASHROOM/ SHOWER
106
OXYGENSTORAGE
112
MEDICALSTORAGE
111
I.T ROOM
109
UTILITYROOM
108
VEHICLEBAYS
110
FG101
FG104
CR CR CR CR CR
CR
CR CR CR CR
CRDO
CR
CRDO
DO
DO
CR
CR
DO
DO
WD103
DO
DO
TRACK LENGTH
2400
150
1900
250250
50
100
DOOR OPENING
1100
RO
UG
H O
PEN
ING
2200
SOLID WOOD CORE DOOR. PAINTED WHITE.
DOOR PULL - BOTH SIDES
200
GLASS
SIDEWALL MOUNTED TRACK TO BLOCK WALL. BOTTOM OF TRACK SHALL BE PAINTED BLACK.
SOLID FILL CONCRETE BLOCK AT SLIDING DOOR TRACK
A700-101410-ECS-1
JAN
-19
EMERGENCY CALL SYSTEM OPERATION
1. DOOR IS NORMALLY CLOSED AND UNLOCKED.
2. THE DOOR CAN BE MANUALLY OPENED OR AUTOMATICALLY OPENED VIA THE EXTERIOR HANDICAP ACTUATOR (A).
3. ONCE A USER HAS ENTERED THE WASHROOM, DOOR CAN BE LOCKED VIA THE "PUSH TO LOCK" BUTTON (B) WHICH WILL: A. LOCK THE ELECTRIC STRIKEB. DISABLE OUTSIDE HANDICAP ACTUATORC. PREVENT AUTOMATIC DOOR OPERATOR
FROM OPENING DOOR. D. THE "LOCKED" INDICATOR (C) NEXT TO
"PUSH TO LOCK" BUTTON AND EXTERIOR "OCCUPIED" INDICATOR (D) WILL BE ON.
4. EXIT SHALL BE ALWAYS FREE BY INSIDE HANDICAP ACTUATOR (E) OR BY OPENING DOOR MANUALLY, "LOCKED" AND "OCCUPIED" INDICATORS SHALL TURN OFF.
5. IN CASE OF EMERGENCY, THE USER CAN PUSH THE EMERGENCY CALL BUTTON (F)WHICH WILL:A. ACTIVATE VISUAL AND AUDIBLE SIGNALS
(G) INSIDE AND OUTSIDE OF THE WASHROOM.
B. ALARM IS RESET AT THE EMERGENCY PUSH BUTTON SWITCH.
6. EMERGENCY ACCESS INTO WASHROOM SHALL BE BY USE OF A KEY IN OUTSIDE LEVER HANDLE (H).
OUTSIDE WASHROOM - AT DOOR
INSIDE WASHROOM - AT DOOR
IF NOTED CLEARANCES ARE NOT ACHIEVABLE NOTIFY CONSULTANT FOR
ALTERNATE LOCATION PRIOR TO ROUGH-IN
LOCKED INDICATOR (C)PUSH TO LOCK BUTTON (B)ACTUATOR SWITCH (E)
LATCH SIDE(INSIDE WASHROOM)
LATCH SIDE(OUTSIDE WASHROOM)
IPSUM LOREM
ACTUATOR SWITCH (A)
OCCUPIED INDICATOR (D)
CL
WASHROOM SIGN
WASHROOM KEY BOX (H)
CL
EMERGENCY CALL HORN/STROBE (G)
IN THE EVENT OF AN EMERGENCY PUSH
EMERGENCY BUTTONAND AUDIBLE AND
VISUAL SIGNALWILL ACTIVATE
CL
EMERGENCY CALL BUTTON (F)
1000
mm
A.F
.F.
EMERGENCY CALL BUTTON SIGN
EMERGENCY CALL HORN/STROBE (G)
FIN. WALL
500 FROM
INSIDE WASHROOM - AT TOILET
CL
900
MIN
. - 1
100
MAX
.
A B B
A B B
2130
A.F
.F.
2130
A.F
.F.
900
MIN
. - 1
100
MAX
.
A = 350B = 150
CL
A = 350B = 150
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
N N
TRUE NORTH CONSTRUCTION NORTH
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
37:3
6 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A8.1
2019/07/09
TENDER
DOOR FINISHSCHEDULES &UNIVERSALWASHROOMOPERATION
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
A8.12 /
1 : 1001 DOOR SCHEDULE KEY PLAN
DOOR SCHEDULE
No. FROM TO
DOORS FRAMES
FRR
-D
HARDWARE
COMMENTSWID
TH
HEI
GH
T
THIC
KN
ESS
TYPE
DOO
R M
ATL
INSU
LATE
D
FRA
ME
TYPE
FRAM
E M
ATL
THR
ESHO
LD
KIC
K P
LATE
DO
OR
SW
EEP
DO
OR
BEL
L
KEY
PAD
CAR
D RE
ADER
DO
OR
CO
NTAC
T
ELEC
TRIC
STR
IKE
REX
EXIT
DEV
ICE
DO
OR
OPE
RATO
R
DO
OR
CLO
SER
PUSH
TO
LO
CK
LOC
KSET
100A VESTIBULE EXTERIOR 1100 2150 51 FG AL Yes AL AL Yes No Yes No No Yes Yes Yes Yes Yes Yes Yes No STOREROOMDOOR OPERATOR MUST BE INTEGRATED WITH ACCESSCONTROL BY USE OF CX 12 PROVIDED BY OPERATORSUPPPLIER
100B ACCESS CORRIDOR VESTIBULE 1100 2150 51 FG AL No AL AL No No No No No No No No No Yes Yes Yes No PASSAGE101 ACCESS CORRIDOR VEHICLE BAYS 1100 2150 51 FG HM No BUTT HM 1.5HR Yes No No No No No No No No Yes No No No PASSAGE FIRE RATED GLASS AS PER SPECIFICATIONS103 LOUNGE ROOM WRITE-UP ROOM 1300 2760 45 WD WD No N/A N/A No No No No No No No No No No No No No N/A SOLID WOOD CORE SLIDING DOOR c/w WINDOW104 WRITE-UP ROOM EXTERIOR 1100 2150 51 FG AL Yes AL AL Yes No Yes No No Yes Yes Yes Yes Yes No Yes No STOREROOM
106 LOCKER ROOM MALE WASHROOM /SHOWER 965 2150 45 M HM No WRAP HM No Yes No No No No No Yes No No Yes Yes Yes STOREROOM TO COMPLY WITH AODA REGULATION UNIVERSAL
WASHROOM
107 LOCKER ROOM FEMALE WASHROOM /SHOWER 965 2150 45 M HM No WRAP HM No Yes No No No No No Yes No No Yes Yes Yes STOREROOM TO COMPLY WITH AODA REGULATION UNIVERSAL
WASHROOM108 VEHICLE BAYS UTILITY ROOM 965 2150 45 M HM No WRAP HM 1.5HR No Yes No No No No No No No Yes No Yes No PASSAGE DOOR SHALL BE UNDERCUT 25mm109 ACCESS CORRIDOR I.T ROOM 965 2150 45 M HM No WRAP HM Yes Yes No No No Yes Yes Yes Yes No No No No STOREROOM
110A EXTERIOR VEHICLE BAYS 965 2150 45 NL1 HM Yes BUTT HM Yes Yes Yes No No Yes Yes Yes Yes No No No No STOREROOM110B EXTERIOR VEHICLE BAYS 965 2150 45 NL1 HM Yes BUTT HM Yes Yes Yes No No Yes Yes Yes Yes No No No No STOREROOM
110C EXTERIOR VEHICLE BAYS 3600 3600 54 FFD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AFOUR-FOLD DOOR, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
110D EXTERIOR VEHICLE BAYS 3600 3600 54 FFD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AFOUR-FOLD DOOR, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
110E EXTERIOR VEHICLE BAYS 3600 3600 54 FFD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AFOUR-FOLD DOOR, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
110F EXTERIOR VEHICLE BAYS 3600 3600 54 FFD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AFOUR-FOLD DOOR, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
110G EXTERIOR VEHICLE BAYS 3600 3600 50 OHD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AOVERHEAD SECTIONAL, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
110H EXTERIOR VEHICLE BAYS 3600 3600 50 OHD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AOVERHEAD SECTIONAL, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
110I EXTERIOR VEHICLE BAYS 3600 3600 50 OHD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AOVERHEAD SECTIONAL, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
110J EXTERIOR VEHICLE BAYS 3600 3600 50 OHD AL Yes N/A N/A No No Yes No No Yes No No No No No No No N/AOVERHEAD SECTIONAL, GC TO PROVIDE RELAY FOR CARDACCESS INTEGRATION TO BE WIRED AND TESTED BYSECUIRTY CONTRACTOR.
112 MEDICAL STORAGE VEHICLE BAYS 965 2150 44 G HM No BUTT HM 1.5HR No Yes No No No Yes Yes Yes Yes No No No No STOREROOM112A VEHICLE BAYS OXYGEN STORAGE 965 2150 45 M HM No BUTT HM 1.5HR No Yes No No No No No No No No No No No PASSAGE112B EXTERIOR OXYGEN STORAGE 965 2150 45 M HM Yes BUTT HM Yes Yes Yes No No Yes Yes Yes Yes Yes No Yes No STOREROOM
114 EXTERIOR EXTERIOR GARBAGE ROOM 1800 2150 45 M2 HM Yes BUTT HM No Yes Yes No No No No No No No No Yes No UNICAN LOCK UNICAN LOCK ON EXTERIOR PROGRAMMED TO CODEPROVIDED BY EMS. EACH DOOR SHALL HAVE A LOUVER.
1 : 303 INTERIOR - SLIDING DOOR
A8.14 /
NO. ISSUED FOR DATE1 SPA SUBMISSION 01 2018.01.293 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
11
TS
PT-1
W
T- 4
PT-1
PT
-2
PT-1
PT
-1
PT-1
PT
-2
PT-1
PT
-1
PT-1
PT
-1
PT-1 PT
-1 PT-1
PT
-1
PT-1
PT
-1
PT
-2
PT-2 PT
-2
PT-2
PT-2
PT
-2 PT
-2
PT-2
PT-2
PT-2
PT
-2
PT
-2
PT-1
PT
-1
PT-1
PT
-1
PT
-1 PT-1
PT
-1
PT-1 PT
-2
PT-1
PT
-1
PT-1
PT
-1
PT
-1
PT-1
PT-1
PT-1
PT
-1
PT-1 PT
-1 PT-1
PT
-1
PT-1
PT
-1
PT-1
PT
-1
PT-1
PT
-1
PT-1
PT
-1
PT-1
PT
-1
PT
-1
W
T- 3 WT-1
W
T-1
WT-1
W
T-1
W
T-1
WT-1
WT-1
WT-1 WT-2
W
T-2 WT-2
W
T-2
WT-2 WT-1
W
T-1 WT-1 W
T-1 WT-1
W
T- 3
W
T-1 WT-1
WT-
1 WT-1
WT-2
W
T-1
ALL EXPOSED VERTICAL STEEL FRAME - PT 4 FINISHALL EXTERIOR STEEL JAMBS SHALL BE PAINTED. (TYP)
PT- 4 FINISH TO ALL CEILING JOIST AND DECK
EPOXY PAINTED DANGER AREA
ZONES ON CONCRETE SLAB
(YELLOW)
IS-3
IS-2
560
230
140
ALL EXTERIOR STEEL JAMBS SHALL BE PAINTED PT 4 FINISH (TYP)
ALL EXPOSED EXTERIOR STEEL SHALL BE PAINTED PT 3 FINISH (TYP)
ALL EXPOSED INTERIOR STEEL SHALL BE PAINTED PT 1 FINISH WITHIN CREW AREAS (TYP)
IS-4
IS-2 IS-1IS-2
IS-2
FL-10
CT-1
IS-2
UTILITYROOM
108
LOUNGEROOM
103
KITCHEN /DINING
102
WRITE-UPROOM
104
LOCKERROOM
105
I.T ROOM109
MEDICALSTORAGE
111
OXYGENSTORAGE
112FEMALE
WASHROOM/ SHOWER
107
MALEWASHROOM/ SHOWER
106
ACCESSCORRIDOR
101
VESTIBULE100
VEHICLEBAYS
110
IS-2
IS-2
11
11
A700-10000-IS-1SE
P-
16
WAYFINDING INTERIOR SINAGETYPE DANSIGN CURVE
FONT FUTURA MEDIUM & FUTURA HEAVY
COLOR 1. INTERIOR SIGNS SHALL BE PANTONE 287C BLUE BACKGROUND WITH WHITE TEXT AND GRAPHICS.2. SURFACE TO HAVE MATTE NON-GLARE FINISH
BRAILLE AND TACTILE LETTERS1. BRAILLE SHALL BE OF "RASTER" METHOD E.G. HOLES DRILLED AND BALL BEARINGS INSERTED
SUITABLY ROUNDED FOR EASY READING
2. BRAILLE DOTS MUST HAVE A DOMED OR ROUNDED SHAPE
3. BRAILING PROCESS USED AND APPLIED ON SIGNAGE SHALL NOT BE SUSCEPTIBLE TO VANDALISM
4. BRAILLE SHALL BE INTEGRAL TO SIGN SURFACE/DESIGN
5. TACTILE SIGNS SHALL HAVE LETTERING AND GRAPHICS THAT ARE RAISED 0.8MM TO 1.5MM ABOVE THE SURFACE OF THE SIGN
6. BRAILLE IS REQUIRED TO BE LOWERCASE, EXCEPT FOR PROPER NOUNS, NAMES AND THE FIRST WORD OF SENTENCES OR INDIVIDUAL LETTERS OF THE ALPHABET
7. THE BRAILLE TEXT/CHARACTERS SHALL ALWAYS BE PLACED IN THE SAME RELATIVE POSITION, MOUNTED NEAR THE BOTTOM EDGE OF SIGNAGE, BELOW OTHER TEXT, SYMBOLS OR TACTILE CHARACTERS. IF TEXT IS MULTI-LINED, BRAILLE SHALL BE PLACED BELOW ENTIRE TEXT
8. ENSURE BRAILLE TEXT IS SEPARATED A MINIMUM OF 9.5MM FROM ANY OTHER TACTILE CHARACTERS
9. WHERE TACTILE CHARACTERS ARE USED, ENSURE EDGES ARE BEVELED AND SMOOTH
NOTE: IT IS THE RESPONSIBILITY OF THE SIGN SUPPLIER TO VERIFY THAT A BRAILLE PROOFREADER HAS APPROVED FINAL ARTWORK. BRAILLE DOTS SHOWN IN THIS GUIDELINE ARE TO SHOW PLACEMENT ONLY
OFFICE/ROOM SIGNS (CHANGEABLE MESSAGE)
TYPE
DANSIGN PAPERFLEX CURVE SIGN WITH A MAGNETIC LOCKING SYSTEM AND TAMPER PROOF PAPER INSERT SYSTEM
MATERIALLACQUERED ABS WITH EXTRUDED ALUMINUM BRACKETS
MESSAGEVINYL ROOM NUMBER ON HEADER PANEL AND PAPER INSERT WITH ROOM NAME OR OCCUPANT'S NAME
INSTALLATIONMOUNTED AT 1500MM TO CENTRELINE ABOVE THE FINISHED FLOOR AND 150MM AWAY FROM THE DOOR FRAME
ROOM SIGNS (PERMANENT MESSAGE)
MATERIAL
LACQUERED ABS WITH EXTRUDED ALUMINUM BRACKETS
MESSAGE
VINYL ROOM NUMBER ON HEADER PANEL AND VINYL ROOM NAME ON BODY PANEL
INSTALLATION
MOUNTED AT 1500MM TO CENTRELINE ABOVE THE FINISHED FLOOR AND 150MM AWAY FROM THE DOOR FRAME
WASHROOM SIGNS
MATERIAL
LACQUERED ABS WITH EXTRUDED ALUMINUM BRACKETS.
MESSAGE
TACTILE TEXT AND PICTOGRAM AND BRAILLE
INSTALLATION
MOUNTED AT 1500MM TO CENTRELINE ABOVE THEFINISHED FLOOR AND 150MM AWAY FROM THE DOOR FRAME, ADJACENT TO THE DOOR HANDLE
###
150
150
NAME
###
150
150
NAME
HEADER PANEL 25mm FONT (FUTURA HV BT)PAPER INSERT 15mm FONT (FUTURA MD BT)
HEADER PANEL 25mm FONT (FUTURA HV BT)
BODY PANEL WITH 15mm FONT (FUTURA MD BT)
BLUE BACKGROUND WITH WHITE TEXT
BLUE BACKGROUND WITH WHITE TEXT
WOMEN
1500
mm
FR
OM
F.F
.
150mm FROM DOOR FRAME
IS-1
IS-2
WOMEN MEN
200
200
IS-3 IS-4
WOMEN MEN
IS-5 IS-6
A700 6400-DSFFD-1
1093
75 3450 75
7594
575
EQEQ
TEXT 200mm HIGH EPOXY PAINT
(ARIAL FONT, YELLOW COLOUR)
200
DOOR OPENING
3600
OC
T-15
BORDER75mm EPOXY PAINT (YELLOW COLOUR)
1545
EQ EQ
CL
CL
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
N N
TRUE NORTH CONSTRUCTION NORTH
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ONT: 416-364-5710 EXT 101W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC. AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No. REVISION
DRAWN BYSCALE
DATE
ORIENTATION
8/21
/201
9 4:
55:2
5 PM
As indicated
11
1509
YOR
K R
EGI O
N P
RS
STAT
ION
#2 9
T-1
9 -1 6
SRL
A8.2
2019/07/09
TENDER
ROOM FINISHSCHEDULE
107
GLE
N C
AMER
ON
RO
AD, M
ARKH
AM
ROOM FINISH SCHEDULE
NUMBER ROOM NAME
FLOOR WALLS CEILING
COMMENTS
FIN
ISH
BA
SE F
INIS
H
NO
RTH
EAST
SOU
TH
WES
T
FIN
ISH
HEIGHT100 VESTIBULE CT-1 CT-1 PT-1 PT-1 PT-1 PT-1 PT-1 2750101 ACCESS CORRIDOR CT-1 CT-1 PT-1 N/A PT-1 PT-1 PT-1 2750102 KITCHEN / DINING CT-1 CT-1 PT-1 PT-1 PT-1 WT-4 PT-1 2750103 LOUNGE ROOM CT-1 CT-1 PT-1 PT-2 PT-1 N/A PT-1 2750104 WRITE-UP ROOM CT-1 CT-1 PT-1 PT-2 PT-1 PT-1 PT-1 2750105 LOCKER ROOM CT-1 CT-1 PT-1/PT-2 PT-1/PT-2 PT-1/PT-2 PT-1/PT-2 PT-1 2750106 MALE WASHROOM / SHOWER CT-1 / CT-2 WT-1 / WT-2 WT-1 / WT-2 WT-1 / WT3 WT-1 / WT2 WT-1 / WT2 PT-1 2750107 FEMALE WASHROOM / SHOWER CT-1 / CT-2 WT-1 / WT-2 WT-1 / WT2 WT-1 / WT2 WT-1 / WT2 WT-1 / WT3 PT-1 2750108 UTILITY ROOM SC N/A N/A N/A N/A N/A N/A 2750109 I.T ROOM PT-5 N/A N/A N/A N/A N/A PT-4 2750110 VEHICLE BAYS CHC N/A PT-1 PT-1 PT-1 PT-1 PT-4 5500111 MEDICAL STORAGE PT-5 N/A PT-1 PT-1 PT-1 PT-1 PT-1 2750112 OXYGEN STORAGE PT-5 N/A PT-1 PT-1 PT-1 PT-1 PT-4 2750114 EXTERIOR GARBAGE ROOM PT-5 N/A PT-1 PT-1 PT-1 PT-1 PT-4 2438
INTERIOR FINISHES SCHEDULEFLOOR TILE FINSHES
CT-1 STONE TILE - ASH NATURAL 300 x 600 - 1/4 RUNNING BOND - 25% OVERLAPGROUT SHALL BE: MAPEI #107 IRON
CT-2 OLYMPIA TILE - QUEBEC - DARK GREY UNGLAZED MOSAIC 50 x 50 (SHOWERS)GROUT SHALL BE: MAPEI #107 IRON
SC SEALED CONCRETE
CHC COLOR HARDNED CONCRETE
WALL TILE
WT-1 OLYMPIA TILE - WARM WHITE MATTE 100 x 400 - STACK BONDGROUT SHALL BE: MAPEI #38 AVALANCHE
WT-2 OLYMPIA TILE - QUEBEC - DARK GREY UNGLAZED MOSAIC 50 x 50 (SHOWERS)GROUT SHALL BE: MAPEI #107 IRON
WT-3 OLYMPIA TILE - DARK GREY MATTE - 100 x 400 - REGULAR HERRINGBONEGROUT SHALL BE: MAPEI #38 AVALANCHE
WT-4 OLYMPIA TILE - BLACK MATTE - 100 x 400 - STACK BOND (KITCHEN BACKSPLASH)GROUT SHALL BE: MAPEI #38 AVALANCHE
PAINT FINISHES
PT-1 SIMPLY WHITE OC - 117 (ALL WALLS, EXPOSED STEEL WINDOW HEADERS AND COLUMNS IN CREW AREA, AND EXPOSED CIELINGS UNLESS OTHERWISE NOTED)
PT-2 7604 SMOKY BLUE - BENJAMIN MOORE (ACCENT WALLS)
PT-3 FOREST BLACK 30YY 10/038 (HOLLOW METAL DOORS AND FRAMES)
PT-4 DEEP SPACE 2125-20 (SECTIONAL AND FOUR FOLD DOOR JAMB FRAMES, AND ALL EXPOSED VERTICAL STEEL IN BAY AND OUTSIDE, ALL EXPOSED STEEL IN VEHICLE BAY CEILING I.E JOISTS AND DECK, CONDUITS, PIPES, ETC. REFER TO SPECIFICATIONS FOR COLOR FOR GAS AND SPRINKLER PIPES)
PT-5 COROTECH EPOXY - V400-75 BATTLESHIP GREY
1 : 1001 ROOM FINISH SCHEDULE KEY PLAN
A8.22 /
A8.23 /
NO. ISSUED FOR DATE3 80% CLIENT REVIEW 2018.05.297 90% CLIENT REVIEW 2018.12.058 100% CLIENT REVIEW 2019.02.129 BUILDING PERMIT 2019.04.1111 ADDENDUM 1 2019.08.22
11
Page 1 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
HARDWARE SCHEDULE FOR
YORK REGION PRS STATION #29107 GLEN CAMERON ROAD
ArchitectTHOMAS BROWN ARCHITECTS INC.
197 SPADINA AVESUITE 200
TORONTO, ONTARIOM5T 2C8
Tel: 416-364-5710
Consultant: SHAUN CRAIG, DHC
Plan Revision: 7, Dated: DEC 5 2018 Submittal Date: APRIL 10 2019
Page 2 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Manufacturers & Finishes
Manufacturers
Cal-Royal ProductsCAMDEN 'CAMDEN
Corbin-Russwin 'Corbin-Russwin
HES 'HES
Ilco-Unican 'Ilco-Unican
K.N. Crowder 'K.N. Crowder
McKinneyNorton 'Norton
Pemko 'Pemko
Rixson 'Rixson
Rockwood ManufacturingSargent 'Sargent
Securitron 'Securitron
Von Duprin 'Von Duprin
Finishes
26D - Satin chromium platedover nickel
630 - Satin stainless steel689 - Aluminum painted
US26D - Satin chromium platedover nickel
US32D - Satin stainless steel
Page 3 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Index of Abbreviations
Door Mat'l
PGS - Paintable Galvanneal Steel
Door Type
FG - Full LiteG - Half LiteM - Flush
NL1 - Narrow Lite
Frame Mat'l
PGS - Paintable Galvanneal Steel
Page 4 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
OPENINGS
OpeningNumber(s)
HeadingNum. Qty Location 1
To/From Location 2
NominalWidth
NominalHeight
DoorThicknessHand Label
FrameMat'l
FrameType
DoorMat'l
DoorType Remarks
100A 1 1 EXTERIOR From VESTIBULE 100 1100 2150 51 RHR ALUM AL ALUM FG BY OTHERS100B 2 1 ACCESS
CORRIDOR 101From VESTIBULE 100 1100 2150 51 RHR ALUM AL ALUM FG BY OTHERS
101 3 1 VEHICLE BAYS 110 From ACCESSCORRIDOR 101
1100 2150 44 RHR WH-B PGS BUTT PGS FG
103 4 1 LOUNGE ROOM 103 To/From WRITE-UP ROOM104
1300 2760 44 SLIDING NONEN/A WOOD M
104 5 1 EXTERIOR From WRITE-UP ROOM104
1100 2150 51 LHR ALUM AL ALUM FG
106 6 1 LOCKER ROOM 105 To MALE WASHROOM106
965 2150 44 RH PGS WRAP PGS M
107 6 1 LOCKER ROOM 105 To FEMALEWASHROOM 107
965 2150 44 LH PGS WRAP PGS M
108 7 1 VEHICLE BAYS 110 From UTILITY ROOM 108 965 2150 44 LHR WH-B PGS WRAP PGS M109 8 1 ACCESS
CORRIDOR 101To IT ROOM 109 965 2150 44 LH PGS WRAP PGS M
110A 9 1 EXTERIOR From VEHICLE BAYS 110 965 2150 44 RHR PGS BUTT PGS NL1110B 9 1 EXTERIOR From VEHICLE BAYS 110 965 2150 44 RHR PGS BUTT PGS NL1 FOUR-FOLD
DOOR BY OTHERS110C 10 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 54 FFD N/A N/A ALUM FFD FOUR-FOLD
DOOR BY OTHERS110D 10 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 54 FFD N/A N/A ALUM FFD FOUR-FOLD
DOOR BY OTHERS110E 10 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 54 FFD N/A N/A ALUM FFD110F 10 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 54 FFD N/A N/A ALUM FFD OVERHEAD DOOR
BY OTHERS110G 11 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 50 OHD N/A N/A ALUM OHD OVERHEAD DOOR
BY OTHERS110H 11 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 50 OHD N/A N/A ALUM OHD OVERHEAD DOOR
BY OTHERS110I 11 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 50 OHD N/A N/A ALUM OHD OVERHEAD DOOR
BY OTHERS110J 11 1 EXTERIOR From VEHICLE BAYS 110 3600 3600 50 OHD N/A N/A ALUM OHD OVERHEAD DOOR
BY OTHERS112 12 1 VEHICLE BAYS 110 To MEDICAL STORAGE
111965 2150 44 RH WH-B PGS BUTT PGS G BY OTHERS
112A 7 1 VEHICLE BAYS 110 To OXYGEN STORAGE112
965 2150 44 LH WH-B PGS BUTT PGS M
112B 13 1 EXTERIOR To OXYGEN STORAGE112
965 2150 44 LHR PGS BUTT PGS M
114 14 1 EXTERIOR From EXT. GARBAGEROOM
900, 900 2150 44 RHRA PGS BUTT PGS M2
Page 5 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Hardware Schedule
Heading #1
Item #1 1 Single door 100A, EXTERIOR From VESTIBULE 100 RHR
1100 x 2150 x 51 - ALUM DR x ALUM FR
1 Continuous Hinge MCK-12HD 2150 mm Clear CLEAR1 Exit Device 33A-NL US26D 388 US26D RHR 1100 x 2150 Door US26D/US26D1 Cylinder 8000ICRIM US26D US26D1 Cylinder 2000ICC1 Cylinder 1000ICC US26D GMK US26D1 Electric Strike 9400-630 - By LENEL 6301 Door Pull BF158 US32D Type 12 HD Mounting US32D1 Auto Door Operator Besam SW200i x FWH2 Push Button CM60/2 6302 Surface Mounted Box CM-69S BLK1 Miscellaneous Item CX 121 Overhead Door Stop 6-536 689 6891 Threshold 252X2AFGx1100 AFG1 Sweep 29326CNBx1100mm C1 Door Contact 3287 - OR SIMILAR BY LENEL1 Card Reader Card Reader By LENEL1 REX Switch REX By LENEL
-Balance of gasketing by Door Supplier. - Pressing actuators button cycles the operator.Manual operation with exit device from inside. REX inside , shuntsthe door contact When door is locked, valid card read Releases the Electric strike and makes push button active,inside push button to unlock strike and open the door. - keyed exterior of exit device is STOREROOM Function . -All wiring high and low voltage, conduit and back boxes by Electrical.
Page 6 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Heading #2
Item #2 1 Single door 100B, ACCESS CORRIDOR 101 From VESTIBULE 100 RHR
1100 x 2150 x 51 - ALUM DR x ALUM FR
1 Continuous Hinge MCK-12HD 2150 mm Clear CLEAR1 Exit Device 33A-NL US26D 388 US26D RHR 1100 x 2150 Door US26D/US26D1 Cylinder 8000ICRIM US26D US26D1 Cylinder 2000ICC1 Cylinder 1000ICC US26D GMK US26D1 Door Pull BF158 US32D Type 12 HD Mounting US32D1 Auto Door Operator Besam SW100 x FWH x EXU-SI2 Push Button CM60/2 6301 Miscellaneous Item CX 121 Overhead Door Stop 6-536 689 689
-Balance of gasketing by Door Supplier.- Exit device to be doged down during normal use to make it unlocked / PASSAGE function/ Push Pull . - Pushing inside or out side buttons will open door. When door is locked / Undogged opperator must be shut off. -All wiring high and low voltage, conduit and back boxes by Electrical.
Heading #3
Item #3 1 Single door 101, VEHICLE BAYS 110 From ACCESS CORRIDOR 101 RHR
1100 x 2150 x 44 - HM DR x HM FR - WH-B
3 Standard Hinge T4A3786 127mm x 114mm US26D NRP US26D1 Exit Device 99-L-BE-F US26D 996L-BE-R US26D RHR 1100 x 2150 Door US26D/US26D1 Surface Closer CPS7500 689 6891 Kick Plate K1050 200mm X 875mm US26D 4BE SA US26D1 Sweep 29326CNBx1100mm C1 Gasketing S88 BL 5215mm BL1 Threshold 252X3AFGx1100mm AFG
Exit Device is Passage Function
Heading #4
Item #4 1 Single door 103, LOUNGE ROOM 103 To/From WRITE-UP ROOM 104 SLIDING
1300 x 2760 x 44 - WOOD DR x NONE FR
1 Track / Hanger C-818HD x 96" 1DR KIT1 Track / Hanger C-110-BLA x 96" BLA1 Miscellaneous Item C-90DP x 626 x 626
KIT INCLUDES STOP AND FLOOR GUIDE.
Page 7 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Heading #5
Item #5 1 Single door 104, EXTERIOR From WRITE-UP ROOM 104 LHR
1100 x 2150 x 51 - ALUM DR x ALUM FR
1 Continuous Hinge MCK-12HD 2150 mm Clear CLEAR1 Exit Device 33A-NL US26D 388 US26D LHR 1100 x 2150 Door US26D/US26D1 Cylinder 8000ICRIM US26D US26D1 Cylinder 2000ICC1 Cylinder 1000ICC US26D GMK US26D1 Electric Strike 9400-630 - By LENEL 6301 Door Pull BF158 US32D Type 12 HD Mounting US32D1 Surface Closer CPS7500 689 7788 6891 Miscellaneous Item 68911 Threshold 252X2AFGx1100 AFG1 Sweep 29326CNBx1100mm C1 Door Contact 3287 - OR SIMILAR BY LENEL1 Card Reader Card Reader By LENEL1 REX Switch REX By LENEL
-Balance of gasketing by Door Supplier. -Manual operation with exit device from inside. REX inside , shunts the door contact When door is locked, validcard read Releases the Electric strike, - keyed exterior of exit device is STOREROOM Function . -All wiring high and low voltage, conduit and back boxes by Electrical.
Page 8 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Heading #6
Item #6 1 Single door 106, LOCKER ROOM 105 To MALE WASHROOM 106 RH
Item #7 1 Single door 107, LOCKER ROOM 105 To FEMALE WASHROOM 107 LH
965 x 2150 x 44 - HM DR x HM FR
6 Standard Hinge T4A3386 127mmx 114mm US26D US26D1 Lockset ML2057 LWA/LWA 626/626 LH LC 626/6261 Lockset ML2057 LWA/LWA 626/626 RH LC 626/6262 Cylinder 7000ICMC US26D US26D2 Cylinder 1000ICC US26D GMK US26D2 Electric Strike 1006F-630-LBM HM-630 2005M3 630-LBM2 Auto Door Operator Besam SW100 x FWH x EXU-SI2 Electronic Closer CM45/42 Electronic Closer CM-43-CBL2 Electronic Closer CX-WC13XSM2 Electronic Closer CX-WEC10 6302 Kick Plate K1050 200MM x 914MM" US26D SA US26D2 Wall Stop 406 US32D US32D2 Power Supply BPS-12/24-12 Electrolynx Harness QC-C1500P2 Key Switch MKA2 Coat Hook RM821 US32D US32D2 Key Box Smash Box - mounted between 2 washrooms - HPC511
-Operator mounted inside washroom. Entry by pushing door or by pressing corridor wall mounted operator button.Upon entry and door closing, pressing of interior "push to lock" switch. Egress by using lever trim or by pressingwall mounted operator button. System automatically resets when door opens. Pressing emergancy switchunlocks electric strike and illuminates interior and exterior assistance required indicators and sound local alerts,until help arrives and opens door. System can be configured to open door upon alarm. For maintenancepurposes, corridor side keyswitch secures washroom door and turns corridor side operator actuator off. Relay tobe used to latch wall mount momentary tape switches to maintain assistance required status. Free egress at alltimes. Door is unlocked in a power fail condition.-All wiring high and low voltage, conduit and back boxes by Electrical.
- RELAY INCLUDED IN RESTROOM KIT
Page 9 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Heading #7
Item #8 1 Single door 108, VEHICLE BAYS 110 From UTILITY ROOM 108 LHR
Item #9 1 Single door 112A, VEHICLE BAYS 110 To OXYGEN STORAGE 112 LH
965 x 2150 x 44 - HM DR x HM FR - WH-B
6 Standard Hinge T4A3786 114mm x 102mm US26D NRP US26D1 Latchset ML2010 LWA/LWA 626/626 LH LC 626/6261 Latchset ML2010 LWA/LWA 626/626 LHR LC 626/6262 Surface Closer CPS7500 689 6892 Kick Plate K1050 200MM x 914MM" US26D SA US26D2 Astragal 29326CNB 38" C2 Weatherstripping S88 BL18 BL
Passage Function
Heading #8
Item #10 1 Single door 109, ACCESS CORRIDOR 101 To IT ROOM 109 LH
965 x 2150 x 44 - HM DR x HM FR
3 Standard Hinge T4A3786 114mm x 102mm US26D NRP US26D1 Lockset ML2057 LWA/LWA 626/626 LH LC 626/6261 Electric Strike 1006CLB-630 By LENEL 6301 Cylinder 7000ICMC US26D US26D1 Cylinder 2000ICC1 Cylinder 1000ICC US26D GMK US26D1 Surface Closer CPS7500 689 6891 Kick Plate K1050 200MM x 914MM" US26D SA US26D1 Card Reader Card Reader By LENEL1 Door Contact 3287 - OR SIMILAR BY LENEL1 REX Switch REX By LENEL
-Valid card read releases the electric strike and door can be pulled open.Door closes and locks. REX inside thelockset shunts the door contact.Storeroom lockset -All wiring high and low voltage, conduit and back boxes by Electrical.
Page 10 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Heading #9
Item #11 1 Single door 110A, EXTERIOR From VEHICLE BAYS 110 RHR
Item #12 1 Single door 110B, EXTERIOR From VEHICLE BAYS 110 RHR
965 x 2150 x 44 - HM DR x HM FR
2 Continuous Hinge MCK-12HD 2150 mm Clear CLEAR2 Exit Device 99-L-NL US26D 996L-NL-R US26D RHR 965 x 2150 Door US26D/US26D2 Electric Strike 9400-630 - By LENEL 6302 Cylinder 8000ICRIM US26D US26D2 Cylinder 2000ICC2 Cylinder 1000ICC US26D GMK US26D2 Surface Closer UNI7500 689 (965 Door) x 6191B-25 6892 Kick Plate K1050 200MM x 914MM" US26D SA US26D2 Weatherstripping 2891AS-38" x 85" A2 Threshold 252X3AFG38" AFG2 Astragal 29326CNB 38" C2 Door Contact 3287 - OR SIMILAR BY LENEL2 Card Reader Card Reader By LENEL2 REX Switch REX By LENEL
. Manual operation with exit device from inside. REX inside shunts the door contact.When door is locked, validcard read releases the electric strike and door can be pulled open.- Extreior keyed side is Storeroom function.
-All wiring high and low voltage, conduit and back boxes by Electrical.
Heading #10
Item #13 1 Single door 110C, EXTERIOR From VEHICLE BAYS 110 FFD
Item #14 1 Single door 110D, EXTERIOR From VEHICLE BAYS 110 FFD
Item #15 1 Single door 110E, EXTERIOR From VEHICLE BAYS 110 FFD
Item #16 1 Single door 110F, EXTERIOR From VEHICLE BAYS 110 FFD
3600 x 3600 x 54 - ALUM DR x N/A FR
4 Card Reader Card Reader By LENEL4 REX Switch REX By LENEL4 OH Door Contact OH DOOR CONTACT BY LENEL
FOUR FOLD DOORS COMPLEATE BY DOOR MANUFACTURE.
Page 11 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Heading #11
Item #17 1 Single door 110G, EXTERIOR From VEHICLE BAYS 110 OHD
Item #18 1 Single door 110H, EXTERIOR From VEHICLE BAYS 110 OHD
Item #19 1 Single door 110I, EXTERIOR From VEHICLE BAYS 110 OHD
Item #20 1 Single door 110J, EXTERIOR From VEHICLE BAYS 110 OHD
3600 x 3600 x 50 - ALUM DR x N/A FR
4 REX Switch REX By LENEL4 Card Reader Card Reader By LENEL4 OH Door Contact OH DOOR CONTACT BY LENEL
OVER HEAD DOOR COMPLEAT BY MANUFACTURE
Heading #12
Item #21 1 Single door 112, VEHICLE BAYS 110 To MEDICAL STORAGE 111 RH
965 x 2150 x 44 - HM DR x HM FR - WH-B
3 Standard Hinge T4A3786 114mm x 102mm US26D NRP US26D1 Lockset ML2057 LWA/LWA 626/626 RH LC 626/6261 Electric Strike 1006CLB-630 By LENEL 6301 Cylinder 7000ICMC US26D US26D1 Cylinder 2000ICC1 Cylinder 1000ICC US26D GMK US26D1 Surface Closer CPS7500 689 6891 Kick Plate K1050 200MM x 914MM" US26D SA US26D1 Card Reader Card Reader By LENEL1 Door Contact 3287 - OR SIMILAR BY LENEL1 REX Switch REX By LENEL
-Valid card read releases the electric strike and door can be pulled open.Door closes and locks. REX inside thelockset shunts the door contact.Storeroom lockset -All wiring high and low voltage, conduit and back boxes by Electrical.
Page 12 of 12
595-16 Cityview Blvd Vaughan , Ontario, L4H 3M7
YORK REGION PRS STATION #29 107 GLEN CAMERON ROAD
Submittal Date: APRIL 10 2019
Heading #13
Item #22 1 Single door 112B, EXTERIOR To OXYGEN STORAGE 112 LHR
965 x 2150 x 44 - HM DR x HM FR
1 Continuous Hinge MCK-12HD 2150 mm Clear CLEAR1 Lockset ML2057 LWA/LWA 626/626 LHR LC 626/6261 Cylinder 7000ICMC US26D US26D1 Cylinder 2000ICC1 Cylinder 1000ICC US26D GMK US26D1 Surface Closer CPS7500 689 6891 Armor Plate K1050 900mm x 875mm US32D 4BE US32D1 Threshold 252X3AFG38" AFG1 Astragal 29326CNB 38" C1 Weatherstripping 2891AS-38" x 85" A1 Door Contact 3287 - OR SIMILAR BY LENEL1 Card Reader Card Reader By LENEL1 Electric Strike 1006CLB-630 By LENEL 6301 REX Switch REX By LENEL
LOCK IS STOREROOM FUNCTION.
Heading #14
Item #23 1 Pair of doors 114, EXTERIOR From EXT. GARBAGE ROOM RHRA
900, 900 x 2150 x 44 - PGS DR x HM FR
2 Continuous Hinge MCK-12HD 2134 mm Clear CLEAR1 Surface Bolt 585-12" US26D US26D1 Surface Bolt 585-24" US26D US26D1 Lockset LL1021S-26D-41 - RHR 26D1 Cylinder 2000ICC1 Cylinder 1000ICC US26D GMK US26D2 Surface Closer UNI7500H 689 (900 Door) x 6191B-25 6891 Threshold 252X3AFGx1800mm AFG2 Sweep 29326CNB 900mm C1 Gasketing 2891AS-2@2134,1@1800 A1 Astragal 357C x S88 x 2134mm C
Unican lockset to be programed to code Provided by owner
MECHANICAL-ELECTRICAL ADDENDUM ME-1 Page 1
August 23, 2019
Contract No. T-19-16 YORK EMS STATION #29 107 Glen Cameron Road, Markham, ON Regal Project No 2016-147
REGAL CONSULTING ENGINEERS INC. 201-2359 Royal Windsor Drive,
Mississauga, ON L5J 4S9
This addendum forms part of the Contract Documents and amends the original bidding requirements, Drawings and Specifications, as noted below.
MECHANICAL DRAWINGS
1. Mechanical Drawings have been revised and re-issued with this Addendum. Please delete the
mechanical Drawings in your possession and replace them with the revised version included with this Addendum.
ELECTRICAL DRAWINGS
1. Electrical Drawings have been revised and re-issued with this Addendum. Please delete the electrical Drawings in your possession and replace them with the revised version included with this Addendum.
MECHANICAL SPECIFICATIONS The following revisions have been made in the mechanical Specification Sections:
1. Refer to Section 22 42 01
Replace subsection 2.6.2 Interior Wall Hydrants with “.2 Interior Wall Hydrant, (H-2):
.1 Watts Drainage model HY-300-2 (Duo-Temp Mild climate Wall Hydrant Encased Type)
.2 Concealed key operated dual-temp mild climate wall hydrant with nickel bronze box and door, polished bronze hydrant face, 3/4" (19 mm) hose connection, all bronze head, seat casing and internal working parts, galvanized wall casing and hydrant key. “
2. Refer to section 25 90 00
Revise the heading subsection 1. General, Item 2. to read as follows
1. Acceptable BAS Contractors are: Automated Logic Delta Controls
Reliable Controls (Set Point). Or equivalent
3. Refer to section 23 09 13
Add the following requirements to this Section:
Gas Sub Meter:
1. Meter to be supplied and installed by the mechanical Subcontractor as shown on the Drawings.
2. Meter to be supplied with complete pulse output. 3. Sub Meter by American Meter, Itron or Norgas or equivalent are acceptable. 4. Pulse output should be complete with wiring harness.
MECHANICAL-ELECTRICAL ADDENDUM ME-1 Page 2
August 23, 2019
Contract No. T-19-16 YORK EMS STATION #29 107 Glen Cameron Road, Markham, ON Regal Project No 2016-147
REGAL CONSULTING ENGINEERS INC. 201-2359 Royal Windsor Drive,
Mississauga, ON L5J 4S9
5. BAS Subcontractor to supply intrinsically safe barrier as required. 6. Manufacturer’s technician shall be on Site for the startup, to be included with the
meter supply.
Water Sub Meter:- 7. Meter shall be supplied and installed by the mechanical Subcontractor as shown
on the Drawings. 8. Meter must have Dual pulse contacts (1 for utility and 1 for BAS) or separate meter for
BAS with pulse contacts.
ELECTRICAL SPECIFICATIONS
The following revisions have been made to the electrical Specification Sections:
1. Refer to Section 26 09 13 under Part 2 Products 2.0 and revise as follows
Energy Meter and Sub Meter 1. Meter shall be supplied and installed by electrical Subcontractor as shown on the Drawings. 2. Meter to be supplied complete with pulse output. 3. Meters must be BACnet listed. 4. Manufacturer’s technician shall be on site for the startup, to be included with meter
supply.
2. Refer to Section 26 30 00
Revised specification section 26 30 00 is attached.
3. Refer to Section 26 30 10
Revised Power Generator Specification Section is attached.
4. Refer to section 26 50 00
Lighting Fixtures – Lithonia lighting fixtures are treated as equivalent.
5. Refer to section 26 60 00
Lighting Control Systems – Acuity Lighting Controls should be treated as equivalent.
Attachments: Replacement Mechanical and Electrical Drawings Replacement Specification Section 26 30 00 Replacement Specification Section 26 30 10
END OF MECHANICAL-ELECTRICAL ADDENDUM ME-1
T
T
T
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M1.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
N.T.S.DH
LEAD SHEET
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
NFWH
NFWH
FL-1
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M2.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #
29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
DRAINAGE FLOOR
PLAN
1:75
DH
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
NFWH
NFWH
FL-1
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M3.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #
29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
PLUMBING FLOOR
PLAN
1:75DH
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
NFWH
NFWH
FL-1
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M4.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #
29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
SPRINKLER FLOOR
PLAN
1:75 DH
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
NFWH
NFWH
FL-1
CO
/N
Ox
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
CO
/N
Ox
EF-2
EF-3
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M5.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #
29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
HVAC FLOOR PLAN
1:75 DH
TAG FIXTURN NAME
SANITARY VENT DCWS DHWS TEMPERED REMARKS
MM INS MM INS MM INS MM INS MM INS
W1
BARRIER FREE FLUSH VALVE
WATER CLOSET
75 3.00 38 1.50 32 1.25 - - - -
L1
BARRIER FREE COUNTERTOP
LAVATORY
32 1.25 32 1.25 13 0.50 13 0.50 13 0.5
SH1 BARRIER FREE SHOWER - - - - 13 0.50 13 0.50 19 0.75
SH1 SHOWER HEAD SET - - - - 13 0.50 13 0.50 19 0.75
S1
SINGLE COMPARTMENT
STAINLESS STEEL SINK
38 1.50 32 1.25 13 0.50 13 0.50 - -
S2
SINK PROVIDED BY GENERAL
CONTRACTOR, REFER TO
ARCHITECTURAL
SPECIFICATIONS, FAUCET
PROVIDE BY MECHANICAL
CONTRACTOR
38 1.50 32 1.25 13 0.50 13 0.50 - -
MS1 MOP SINK 75 3.00 38 1.50 19 0.75 19 0.75 - -
EW EMERGENCY EYE WASH 32 1.25 32 1.25 19 0.75 19 0.75 19 0.75
HB HOSE BIB - - - - 13 0.50 13 0.50 13 0.50
HR HOSE REEL - - - - 13 0.50 13 1.50 13 1.50
NFWH NON-FROZEN WALL HYDRANT - - - - 13 0.50 - - - -
FD FLOOR DRAIN 75 3.00 38 1.50 10 0.38 - - - -
FFD FUNNEL FLOOR DRAIN 75 3.00 38 1.50 10 0.38 - - - -
TSP TRAP SEAL PRIMER - - - - 10/13 0.38/0.50 - - - -ONE - 10MM/0.38" PER FD, FFD, HD, PD
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M6.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
1:75 DH
MECHANICAL
SCHEDULES
FULL HEIGHT LOCKABLE SPLITTER DAMPER
`L'=1-1/2 D FOR 8" (200mm) TO 24" (600mm)
`L'=1-1/4 D FOR OVER 24" (600mm)
INLINE EXHAUST FAN/ HRV UNIT
CEILING
TRANSFORMATION AS REQUIRED
FLEXIBLE DUCT CONNECTION
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M7.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
N.T.S DH
MECHANICAL
DETAILS - 1
S
T
T
FOR DETAILS OF CABLE,
HARDWARE AND INSERTS.
STANDARD EQUIPMENT HANGER
ROD AND ISOLATOR
SLACK CABLE RESTRAINT.
TYPICAL OF 4.
REFER TO DWG. 2 OF 2
CABLES TO BE TAUT, NOT
INTERFERE WITH SPRING
ISOLATORS FOR EQUIPMENT.
STRUCTURE - CONFORM TYPE OF
ANCHOR WITH STRUCTURAL ENGINEER
- SUBMIT SAMPLES AS REQ'D.
SUSPENDED
MECHANICAL
EQUIPMENT
SUSPENDED
MECHANICAL
EQUIPMENT
45° NOMINAL
ATTACH ONLY TO MEMBERS
WITH THE APPROVAL OF THE
STRUCTURAL ENGINEER.
REFER TO DRAWING 2 OF 21.
NOTES:
PROVIDE CABLE RESTRAINT AT EACH OF
4 CORNERS OF THE UNIT.
3/8"(9mm) MACHINE
BOLT, NUT AND
LOCK WASHER.
SECURE TO UNIT FRAME.
CORNER OF
SUSPENDED
MECHANICAL
EQUIPMENT.
HILTI HSL HEAVY DUTY
1/2"(12mm)~ STEEL INSERT BOLT AND
EXPANSION ANCHOR INTO CONCRETE.
PROVIDE LOCK WASHER BETWEEN
BRACKET AND NUT.
2"x2"x 1/4"(50mm x 50mm x 6mm) x 1"(25mm) WIDE
STEEL ANGLE BRACKET WITH NEOPRENE
GROMMET @ THIMBLE END.
TYPICAL AT EACH END OF CABLE.
DO NOT OVER DRILL BRACKET AT
STRUCTURE AND EQUIPMENT
CONNECTIONS.
HEAVY WIRE ROPE
THIMBLES.
U-BOLT CLIPS
2 PER END, ORIENTED
AS SHOWN.
1/4"(6mm) DIAMETER
AIRCRAFT CABLE.
TENSION CABLE ONLY
ENOUGH TO REMOVE
SAG.
1
2
MAX.
THIS DETAIL APPLIES FOR UNIT WEIGHTS UP
TO 500 LBS. MAX. FOR OTHER WEIGHTS
CONSULT THE ENGINEER.
PROVIDE SLACK CABLE RESTRAINT.
NOTES:
1.
2.
3.
CO/NOx
CO/NOx
C
DX
HSP
1
T
T
T
T
T
T
CO2
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
M7.1
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
N.T.S. DH
MECHANICAL
DETAILS - 2
H
EX
EX
2
VOLT
LAMP
MOUNT REMARKS
WATT TYPE COL.
”
”
ECUH-1
EBH-1
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E1.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
$
NOTES:
ALECTRA WILL SUPPLY AND INSTALL THE FOLLOWING:
1. 120/208V PHASE 4 WIRE POLE MOUNTED TRANSFORMER WITH
KVA RATING TO SUIT LOAD REQUIREMENTS.
2. PRIMARY HIGH VOLTAGE CABLES.
3. POWER CONNECTION AT HYDRO POLE, PRIMARY AND
SECONDARY SIDE OF TRANSFORMER.
4. HYDRO METER
5. CONTRACTOR TO CARRY A CASH ALLOWANCE AS PER
SPECIFICATIONS FOR ITEM 1,2,3&4 TO BE DONE BY ALECTRA.
6. CONTACT ALECTRA UTILITY TEL: 905-273-9050.
ELECTRICAL CONTRACTOR SHALL SUPPLY & INSTALL THE
FOLLOWING:
1. 2-103MM SECONDARY DUCTS ENCASED IN CONCRETE FROM
HYDRO POLE TO THE LOCATION AS SHOWN ON DRAWING.
2. GROUNDING AT POLE MOUNTED TRANSFORMER AS PER
ALECTRA REQUIREMENTS.
3. RUN 4#250MCM RWU 90 XLPE+GROUND FROM HYDRO POLE
TO MAIN SWITCH IN THE BASEMENT. LEAVE 12 METERS SLACK
WITH LUGS AT THE POLE MOUNTED TRANSFORMERS.
4. SECONDARY CABLES CONNECTION AT MAIN DISCONNECT
SWITCH.
5. INSTALL METER AS PER REQUIREMENTS OF ALECTRA.
6. CO-ORDINATE ALL WORK WITH LOCAL UTILITIES.
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E2.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
10
7 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:150
ELECTRICAL
SITE PLAN
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
NFWH
NFWH
FL-1
$
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E3.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
POWER
FLOOR PLAN
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
NFWH
BOL
BOL BOLBOL
BOLBOL BOL
BOL
BOLBOL
BOL
BOL
BOL
BOLBOL
BOL
NFWH
FC
FC
FC
FC
REX
CR
DC
ES
CR
CR
OHD
CR
OHD
CR
OHD
CR
OHD
CR
OHD
CR
OHD
CR
OHD
CR
OHD
RE
X
DC
ES
CR
REX
CR
DC
ES
RE
X
CR
DC
ES
RE
X
CR
DC
ES
DC
ES
REX
CR
REX
DC
ES
CR
AB
KP
2G
101
M
110A
M
112
M
112B
M
107
M
106
M
112A
M
109
M
108
FG
100B
FG
100A
FG
104
M
110B
FFD
110C
FFD
110D
FFD
110E
FFD
110F
OHD
110G
OHD
110H
OHD
110I
OHD
110J
FCFC
FC
FC
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E4.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
SECURITY
SYSTEM
FLOOR PLAN
APAP
AP AP
APAP
AP AP
LOCKER
ROOM
105
I.T ROOM
109
MEDICAL
STORAGE
111
OXYGEN
STORAGE
112
UTILITY
ROOM
108
VESTIBULE
100
KITCHEN /
DINING
102
ACCESS
CORRIDOR
101
WRITE-UP
ROOM
104
MALE
WASHROOM
/ SHOWER
106
FEMALE
WASHROOM
/ SHOWER
107
VEHICLE
BAYS
110
AP AP AP AP
APAPAPAP
AP AP AP AP
APAPAPAP
AP AP AP AP
APAPAPAP
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
FL-1
BATTERY UNIT SCHEDULE
LOCATION UNIT UNMBER
EXIT
SIGNS
DOUBLE
HEADS
SINGLE
HEADS
CONNECTED
LOAD (WATT)
CAPACITY
(WATT)
UTILITY ROOM # 126 BU-1 10 7 8 490 720
REFER TO SPECIFICATION SECTION 26 50 00
MA MA MA
MA
MA
E
X
BU-1
EX
EX
E
X
EX
MA
$
$
$
E
X
$
EX
EX
$
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
$
$
$
$
$
$
$
MA
$
$
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E5.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
LIGHTING
FLOOR PLAN
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
1
1
B
A
10
10
D
E
GG
13
11 12
14
15
15
C
F
NFWH
BOL
BOL BOLBOL
BOLBOL BOL
BOL
BOLBOL
BOL
BOL
BOL
BOLBOL
BOL
NFWH
FL-1
NOTES:
FIRE ALARM SYSTEM SCHEMATICS
FIRE ALARM ZONE SCHEDULE
ABBREVIATIONS
HD - HEAT DETECTOR FS - FLOW SWITCH
FZ - ALARM ZONE SD - SMOKE DETECTOR PS - PRESSURE SWITCH
SZ - ALERT ZONE DSD - DUCT SMOKE DETECTOR SV - SUPERVISED VALVE
CZ - CONTROL ZONE MP - MANUAL PULL STATION MS - MONITOR SWITCH
SC - SUPERVISED CONTACT
ZONE NO. ZONE IDENTIFICATIONS DEVICES FUNCTIONS REMARKS ZONE NO. ZONE IDENTIFICATIONS DEVICES FUNCTIONS REMARKS
FZ-01 EMS CREW AREA SD/HD/PS ALARM SZ-01 SPRINKLER VALVE MS-01 ALERT
FZ-02 EMS VEHICLE BAY HD/PS ALARM SZ-02 SPRINKLER VALVE MS-02 ALERT
NOTES:
1. PROVIDE FIRE ALARM GRAPHICS TO BE INSTALLED ADJACENT TO THE LED ANNUNCIATOR IN THE MAIN ENTRANCE.
2. FOR NUMBER AND LOCATION OF DEVICES REFER TO FLOOR PLANS.
3. PROVIDE WRING IN CONDUIT FOR COMPLETE OPERATIONAL SYSTEM.
4. ALL PULL STATIONS SHALL BE C/W PLASTIC COVERS WITH LOCAL HORN.
5. PROVIDE ISOLATORS FOR EVERY ONE TO TWO HOUR RATED FIRE COMPARTMENT.
6. ALL LOOP WIRING FOR INITIATING CIRCUITS SHOULD RUN ON SEPARATE ROUTE INCLUDING RISER.
7. SOUND ALL AUDIBLE SIGNALS AND SHUT DOWN AIR SYSTEM IN CASE OF GENERAL ALARM.
8. PROVIDE CONNECTIONS C/W EMT CONDUIT AND WIRING TO ALL FIRE PROTECTION EQUIPMENT AND DEVICES (SPRINKLER SYSTEM) SHOWN ON THE FIRE ALARM ZONE SCHEDULE AS
ALARM OR SUPERVISORY ZONE. REFER TO MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT LOCATIONS OF DEVICE PRIOR TO ROUGH IN.
VESTIBULE
100
ACCESS
CORRIDOR
101
KITCHEN /
DINING
102
LOUNGE
ROOM
103
WRITE-UP
ROOM
104
LOCKER
ROOM
105
FEMALE
WASHROOM
/ SHOWER
107
MALE
WASHROOM
/ SHOWER
106
OXYGEN
STORAGE
112
MEDICAL
STORAGE
111
I.T ROOM
109
UTILITY
ROOM
108
VEHICLE
BAYS
110
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E6.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
FIRE ALARM
SYSTEM
FLOOR PLAN
#### CONNECTED LOAD
## TOTAL AMPS
#### CONNECTED LOAD
## TOTAL AMPS
CC
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E7.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
SINGLE LINE
DIAGRAM &
SCHEDULES
S
P
D
T
OPEN
CLOSE
STOP
AUTO/HAND
WIRED SAFETY EDGE
BY DOOR MANUFACTURER
PRESENCE SENSOR
BY DOOR
MANUFACTURER
SENSOR
BY DOOR
MANUFACTURER
DOOR MOTOR
BY DOOR MANUFACTURER
PHOTOSENSOR
RECEIVER
BY DOOR
MANUFACTURER
PHOTOSENSOR
TRANSMITTER
BY DOOR
MANUFACTURER
RADIO REMOTE
RECEIVER
BY OTHERS
MAIN PANEL BY
DOOR
MANUFACTURER
OPEN
CLOSE
STOP
DOOR CONTROLS
BY DOOR
MANUFACTURER
LINE POWER
(IN CONTRACT)
WIRED SAFETY
EDGE RECEIVERS
BY DOOR
MANUFACTURER
JUNCTION
BOX
JUNCTION
BOX
JUNCTION BOX
JUNCTION
BOX
JUNCTION
BOX
PREFABRICATED STEEL TABS ON
PREMANUFACTURED STEEL FRAME
(BY DOOR MANUFACTURER)
-18 TABS PER DOOR
ANCHOR FRAME TO EXISTING OPENING
USING HILTI HY-HIT EPOXY ANCHORS
PREFABRICATED STEEL TABS ON
PREMANUFACTURED STEEL FRAME (BY
DOOR MANUFACTURER)
-18 TABS PER DOOR
ANCHOR FRAME TO EXISTING OPENING
USING HILTI HY-HIT EXPOXY ANCHORS
*PROVIDE ALL STICKERS AND LABELS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS*
Ceiling
NOTES:
1. ALL CONDUITS ARE 16MM UNLESS OTHERWISE
NOTED.
2. LOCAL DOOR CONTACT FOR DOOR OPERATOR
INTERLOCK OPERATION. (THIS DOOR CONTACT IS
NOT REQUIRED TO BE CONNECTED TO THE
SECURITY SYSTEM.)
3. ALL LOW VOLTAGE WIRING FOR DOOR HARDWARE
COMPONENTS TO BE 4#18 AWG, SUPPLIED AND
INSTALLED BY ELECTRICAL CONTRACTOR.
CO-ORDINATE ALL WORK ON SITE.
4. MOUNTING HEIGHT OF ACTUATION, LOCKING,
ASSISTANCE REQUIRED/EMERGENCY DEVICES TO BE
990MM TO 1066MM ABOVE FINISHED FLOOR.
5. EMERGENCY RESPONSE SYSTEM FOR B/F
WASHROOM TO BE BY MIRCOM OR APPROVED
EQUIVALENTS.
UNIVERSAL WASHROOM DOOR OPERATOR SCHEMATICS
(TYPICAL)
INSIDE OUTSIDE
PUSH TO OPEN BUTTON WITH "OCCUPIED" LIGHT
ASSISTANCE REQUIRED AUDIBLE & VISUAL SIGNAL
21 M
MC
21 M
MC
21 M
MC
PUSH TO LOCK BUTTON WITH "LOCKED LIGHT"
EMERGENCY ASSISTANCE BUTTON
PUSH TO OPEN BUTTONI
I
ELECTRIC STRIKE
SUBSTRATE
COVERBOARD (AS REQUIRED)
SUBSTRATE
COVERBOARD (AS REQUIRED)
8" (2
03 m
m) M
IN.
3" (76 mm) MIN.3" (76 mm) MIN.
SHEET METAL ENCLOSURE
INTERPLY REQUIRED FOR 15 & 20 YEAR SYSTEMS
SLOPE PIPE DOWN AWAY FROM HOOD
FOUR PLYBUILT UP ROOF
FASTEN APPROX. 8" (203 mm) O.C.
MODIFIED BITUMEN GRANULESURFACED CAP SHEET
HIGH-DOMED, CAPPED, GASKETEDFASTENERS AS REQUIRED
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E8.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
ELECTRICAL
DETAILS
(LOUNGE/KITCHEN)
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E9.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
LIGHTING
CONTROL
DETAILS
EMS MARKHAM #29 SECURITY DEVICE SUMMARY
SECURITY / ACCESS SYSTEM COMPONENTS INTRUSION DETECTION EQUIPMENT LOCKSMITHING & KEYS
SE
CU
RIT
Y A
CC
ES
S C
ON
TR
OL S
YS
TE
M D
EV
IC
ES
DOOR #
ON
DRAWING
SUPPLIED
DOOR DESCRIPTION
SECURITY
OPERATION
TYPE
EXTERIOR
CARD
READER
INTERIOR
CARD
READER
ARMING
BUTTON
ELECTRIC
STRIKE
MECHANISM
ELECTROMAETIC
LOCK
MAGNETIC
DOOR
CONTACT
OVERHEAD
DOOR
CONTACT
REQUEST
TO EXIT
MOTION
PEIZZO
BUZZER
DOOR /
GATE
RELEASE
INTERCOM OR
COMMUNICATOR
NEEDED KEYPAD
CONTROL
PANEL
DIRECTIONAL
MOTION
DETECTOR
360
DEGREE
MOTION
VICINITY
GLASS
BREAKER
DETECTOR
IN VICINITYREQUIRED LOCKSMITHING
DETAILSCOMMENTS OR QUESTIONS
FG 100A
SINGLE EXTERIOR
DOOR LEADING IN TO
VESTIBULE 100 T1 1 1 1 1 0 1 0 1 0 0 0 1 0 0 0 0
GGMK ONLY
(Lockbox to be
installed on
exterior)
EXTERIOR CARD READER TO
BE INSTALLED NEXT TO THE
DOOR OPERATOR BUTTON.
FG 100B
SINGLE INTERIOR
DOOR LEADING INTO
ACCESS CORRIDOR
101 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
PASSAGE FUNCTION
N/A
FG 101
SINGLE EXTERIOR
DOOR FROM GARAGE
BAY INTO CORRIDOR
101 N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PASSAGE FUNCTION N/A
FG 104
SINGLE EXTERIOR
DOOR LEADING INTO
THE WRITE UP ROOM T2 1 0 0 1 0 1 0 1 0 0 0 0 0 0 STOREROOM FUNCTION LOCKSET GGMK ONLY
M 106
Single door leading into
Male Washroom N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 STOREROOM FUNCTION
Change key 1
GC to install all required
equipment to comply with AODA
regulation. Red emergency box
to be installed between the two
washrooms which house key to
override the lock.
M 107
Single door leading into
Women's Washroom N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 STOREROOM FUNCTION
Change key 1
GC to install all required
equipment to comply with AODA
regulation. Red emergency box
to be installed between the two
washrooms which house key to
override the lock.
M 108
Single Door leading into
Utility room
N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 PASSAGE FUNCTION N/A
M 109
Single Door leading into
the IT room T2 0 1 0 1 0 1 0 1 0 0 0 0 0 0 0 0 STOREROOM FUNCTION LOCKSET GGMK ONLY
NL1 110A
Single Exterior door
leading into the Bay Area
T2 1 0 0 1 0 1 0 1 0 0 0 0 0 0 0 0 STOREROOM FUNCTION LOCKSET GGMK ONLY .
M 110B
Single Exterior door
leading into the Bay Area
T2 1 0 0 1 0 1 0 1 0 0 0 0 0 0 0 0 STOREROOM FUNCTION LOCKSET GGMK ONLY
2G 112
SINGLE INTERIOR
DOOR LEADING INTO
MEDICAL STORAGE T2 0 1 0 1 0 1 0 1 0 0 0 0 0 0 0 0 STOREROOM FUNCTION LOCKSET GGMK ONLY
M 112B
Single Interior door
leading into the Bays
Area T2 0 1 0 1 0 1 0 1 0 0 0 0 0 0 0 0 PASSAGE FUNCTION GGMK ONLY
M 112A
Single Exterior door
leading into the oxygen
room N/A 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 STOREROOM FUNCTION UNICAN LOCK GGMK ONLY
Code to be programed by GC as
per EMS instruction.
OHD
110H
Overhead door leading
into Bay 1
T5 2 0 0 0 0 0 2 2 0 0 0 0 0 0 0 0 N/A N/A
GC to provide relay for card
access integration to be wired
and tested by sec. contractor
OHD
110I
Overhead door leading
into Bay 2
T5 2 0 0 0 0 0 2 2 0 0 0 0 0 0 0 0 N/A N/A
GC to provide relay for card
access integration to be wired
and tested by sec. contractor
OHD
110J
Overhead door leading
into Bay 3
T5 2 0 0 0 0 0 2 2 0 0 0 0 0 0 0 0 N/A N/A
GC to provide relay for card
access integration to be wired
and tested by sec. contractor
OHD
110G
Overhead door leading
into Bay 4
T5 2 0 0 0 0 0 2 2 0 0 0 0 0 0 0 0 N/A N/A
GC to provide relay for card
access integration to be wired
and tested by sec. contractor
TOTALS 12 4 1 7 0 7 8 15 0 0 0 1 0 0 0 0
N/A N/A
GC to provide relay for card
access integration to be wired
and tested by sec. contractor
2016-147
ISSUE OR REVISION
PR
OJE
CT
:
DWG TITLE
PROFESSIONAL SEAL
E10.0
Jan. 03, 2019
PERMIT
--
N N
TRUE NORTH CONSTRUCTION NORTH
Approval to Proceed
Project Phase
Authorization (signature)
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
TO COMMENCEMENT OF THE WORK. ANY DISCREPANCIES
ARE TO BE REPORTED TO THE CONSULTANT.
A 197 SPADINA AVE, SUITE 500, TORONTO, ON
T: 416-364-5710 EXT 101
W: WWW.TBROWNARCH.COM
THE CONTENTS OF THIS DRAWING AND SPECIFICATIONS
REMAIN THE COPYRIGHT PROPERTY OF
THOMAS BROWN ARCHITECT INC.
AND MUST BE RETURNED UPON COMPLETION OF THE WORK.
ARCHITECT
CLIENT
PROJECT No.
DWG STATUS :
DRAWING No.
REVISION
DRAWN BYSCALE
DATE
ORIENTATION
NO. ISSUED FOR DATE
1ISSUED FOR REVIEW 2018-05-14
2ISSUED FOR 80% REVIEW 2018-10-02
3ISSUED FOR 90% DESIGN DEVELOPMENT 2018-11-21
YO
RK
R
EG
IO
N P
RS
ST
AT
IO
N #29
107 G
LE
N C
AM
ER
ON
R
OA
D, M
AR
KH
AM
2359 Royal Windsor Drive, Suite 201, Misissauga, Ontario L5J 4S9
PHONE: (905)855-3010
www.regal-eng.com
RCEI
REGAL CONSULTING ENGINEERS INC.
CONSULTING MECHANICAL & ELECTRICAL ENGINEER S
4ISSUED FOR REVIEW 2019-01-03
5ISSUED FOR BUILDING PERMIT 2019-03-14
6ISSUED FOR ADDENDUM ME-1 2019-08-20
MJ
1:75
TYPICAL
SECURITY
DOOR
DETAILS
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Electrical Service & Distribution Section 26 30 00 Page 1 of 5
1. GENERAL 1.1 RELATED INSTRUCTIONS
.1 Refer to Section 26 00 00, Electrical General Requirements. 1.2 SCOPE
.1 Work includes, but is not limited to: 1. Secondary ductbank and secondary cables including termination from pole
mounted transformer to service entrance switchboard. Terminal connectors shall be provided as per the Local Hydro Authority’s requirements/standards.
2. Grounding System. 3. Supply and install a 1.25” rigid PVC conduit complete with fish wire from Service
Entrance Board metering compartment to outdoor P-base Hydro meter cabinet (supplied by the Local Hydro Authority and installed by the electrical Subcontractor. Provide phone line to meter and coordinate on site with the Local Hydro Authority for the location of the meter enclosure prior to rough in.
4. Obtaining approvals from, co-operation and scheduling the work with Supply and Inspection Authorities, before commencing work.
5. Preparation of all necessary working drawings for submission to Inspection Authorities.
1.3 SYSTEM CO-ORDINATION & SHORT CIRCUIT STUDY
.1 Characteristics of protective devices (relays, circuit breakers, fuses and the like) shall be selected to provide a coordinated fully-rated protective system; affording minimum fault-clearing times, and fault values.
.2 Retain services of approved testing company to perform protective co-ordination study to
establish optimum settings and selections for all protective devices.
.3 Study shall be plotted on reproducible logarithmic paper (K&E #48-5257) illustrating: 1. Study single line diagram, showing steady-state and transient values. 2. Three phase bolted fault current, symmetrical and asymmetrical, and minimal arcing
ground fault values. 3. Time-current characteristics curves of all pertinent relays, breakers, fuses, etc.
including Supply Authority's primary protective devices, for the complete project. 4. Thermal damage curves for cable, transformers, motors and the like. 5. Summation chart showing all ratings and settings referenced to the appropriate time-
current characteristic curve.
.4 Provide full scale transparencies for time-current characteristic curves of proposed devices.
.5 Submit study for approval by the Consultant. Make all necessary subsequent changes to form "as-built" document.
.6 Provide system coordination and short circuit study for complete high voltage and 120/208V power
system
1.4 ARC FLASH PROTECTION
.1 Retain the services of an industry-approved testing company to perform arc flash hazard study and calculation for all switchboards, panel boards, transformer, panels, control panels, MCC, meters, disconnect switches, breakers, etc, that require examination, adjustment, servicing, or maintenance while energized.
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Electrical Service & Distribution Section 26 30 00 Page 2 of 5
.2 The study and calculation shall meet IEEE 1584-2002, Guide for Performing Arc-Flash Hazard
Calculations.
.3 Provide arc flash report to include the following, but not limited to: 1. Results of the study and calculation. 2. Detailed hazard/risk category (0 to 5). 3. Voltage shock hazard, incident current and energy. 4. Flash protection boundary and shock approach boundaries. 5. The protection plan including safe work procedures, preventive maintenance programs,
personal protective equipment, etc. The protection plan shall meet CSA Z462-08, workplace electrical safety.
.4 Based on the arc flash report, provide required labels state the existence of arc flash hazard
and the corrective action to take. The labels must meet ANSI Z535.4-2002, product Safety signs and Labels.
1.5 INSPECTION & TESTING
.1 Systems, equipment and all major items of material shall be tested to the satisfaction of the Consultant, and as required to establish compliance with plans and specifications, and with the requirements for the Supply and Inspection Authorities.
.2 Faulty and defective equipment shall be replaced with new materials Conductors which are found
to be shorted or grounded, or to have less than proper insulation resistance, shall be replaced with new conductors.
.3 Tests shall include but are not limited to the following:
1. Test of power cables shall include megger tests to establish proper insulation resistance, and phase-to-ground resistance of cables.
2. of all adjustable electrical protective devices of switchgear to establish calibration and operation in accordance with specifications and approved co-ordination curves.
3. Visual examination of switchgear to determine adherence to allowable manufacturing tolerance and compliance with manufacturer's recommended installation requirements.
4. Proper functioning of all systems. 5. Polarity tests - to establish proper polarity connections to all sockets and receptacles. 6. Calibration setting, and test-tripping, of all protective relays and devices, using
"Primary-injection" equipment, in accordance with approved co-ordination schedule. 7. Test of all alarm devices and contacts. 8. Test of system neutral to establish proper insulations resistance and isolation of
neutral from ground except for required ground connection at service 9. Inspection after system is energized shall include infrared thermographic examination of
current carrying parts in switchgear, transformers, and at ducts. The Contractor shall cooperate with inspection personnel, open all equipment enclosures to permit inspection, and make good defective conditions.
.4 Testing Company
1. Retain the services of an independent testing company, to the Consultant’s approval
to perform the above tests. 2. The testing company shall submit test results directly to the Consultant. 3. Include copy of tests in Maintenance and Operating Manual.
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Electrical Service & Distribution Section 26 30 00 Page 3 of 5
.5 Certification of Tests
1. When work is complete, submit three copies of test results and a signed statement listing all tests that have been performed as required by specifications and manufacturer's instructions.
2. PRODUCTS 2.1 SERVICE ENTRANCE SWITCHBOARD
.1 Provide metal enclosed 120/208 volt switchboard as arranged on the Drawings and further described herein, and detailed on the Drawings.
.2 The switchboard shall comprise an indoor, metal enclosed free standing assembly employing
breakers manufactured by Federal Pioneer or equal.
.3 Assembly shall be factory assembled CEMA Type 2 "Sprinkler Proof" construction, and constructed in accordance with applicable CEMA and AIEE Standards. The equipment design shall be CSA approved. Note that all other panels and equipment in Electrical Rooms shall be "Sprinkler Proof" as noted in the Contract Documents.
.4 Bus and connections shall be copper, supported and braced to withstand short-circuit stresses
in excess of main breaker rating (50 KA SYM minimum).
.5 Structures shall consist of metal enclosed steel frame and front enclosures, which shall include separate compartments for each breaker and metering section. All joints of buses shall have tin-plated high pressure contacts and flame retardant bus supports.
.6 A ground bus shall be provided bolted to each unit.
.7 Provide bus extensions for connection to outgoing feeders and provide adequate space to suit
connections to outgoing cables. Compression indent type terminals shall be used for all cable connections.
.8 Provide suitable worded engraved plastic laminate nameplates for each device and compartment.
.9 Provide all necessary fuses, fuse mounts, disconnect switches, small wiring, terminal blocks, and
the like, as required for metering and relaying accessories as detailed.
.10 The switchgear shall be completely assembled, wired and tested at the factory. After assembly, the complete switchgear shall be tested for operation under simulated service conditions to assure the accuracy of the wiring and functioning of the equipment.
.11 The manufacturer shall provide necessary drawings prior to assembly of the equipment
for approvals and provide final drawings upon completion of fabrication.
.12 The entire structure shall be thoroughly cleaned and phosphated prior to application of the primary and finishing coats of paint.
.13 Main 120/208 volt switchboard / Splitter - to contain generally as detailed on the Drawings and as
follows: 1. 200 ampere, 3 pole, 208 volt Main Bus - full capacity neutral with provisions for
incoming bus and cables. 2. Main breaker to comprise 200A/200AT amp fixed moulded case circuit breaker,100%
rated, solid state trip unit, for metered distribution. Interrupting rating shall be 50 KA-Symmetrical minimum.
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Electrical Service & Distribution Section 26 30 00 Page 4 of 5
3. Metering compartment for Supply Authority's transformers with hinged door complete with sealing and padlock provisions. Provide removable mounting pan within compartment for mounting of transformers. These provisions shall be submitted to and approved by the Supply Authority before manufacture.
4. Distribution Sections - Distribution Sections have 4 00 ampere main bus and full capacity neutral and circuit breakers with coordinated fault and trip ratings to suit main and distribution switches.
5. Auxiliary Customer Metering Compartments which shall include: .1 Power Logic Digital Metering system capable of displaying voltage, current, KVA,
KVAR, KW, PF, HZ, and the accumulated MWHR, and KW demand. It shall be capable of continuously monitoring and storing minimum values of volts and PF and maximum values of amps., - KW-KVA-KVAR-KWS. All minimum/maximum values can be displayed. KYZ Pulse output to BMS. 1pulse=1kwh. Ethernet communications interface and all hardware/software. Field server RS232 to Ethernet Gateway and BACnet drivers for Ethernet and IP interface to BMS.
.2 All necessary instrument current and potential transformers and control protection devices.
6. The neutral conductor of the wiring system together with the conduit and service
grounding system shall be bonded to the water service as detailed and in accordance with the Local Hydro Authority requirements.
7. All access to unmetered bus to be provided with bolted panels and provisions for sealing and padlocking.
8. Switchboard / Main Splitter shall be provided c/w 200 kA TVSS surge protection system. 3. EXECUTION 3.1 SECONDARY DUCT BANKS
.1 Provide underground secondary duct bank as detailed to provide for installation of secondary cables. Construction details and exact location of terminations shall be verified on the site prior to installation commencing. Entire installation shall meet OESC requirements and local ESA Inspector’s approval.
.2 Provide warning tapes for secondary duct banks as per latest OESC code & bulletins.
.3 Provide a secondary duct bank constructed to OESC approval comprising PVC Class 1 CSA
approved ducts with minimum internal diameter of 104 mm (4 inches), buried to a depth as indicated on the Drawings to provide cover over the duct run. Ducts shall be laid parallel, spaced 152 mm (6") on centre horizontally and vertically, encased throughout their length in concrete, with a minimum cover of 76 mm (3") on all sides. The duct shall be on even grade, sloped not less than 76 mm (3") in 30 mm (100 feet). The duct bank enclosure shall be steel reinforced as detailed. Provide Bell ends for all ducts.
.4 Provide in each duct a 5/16" (8 mm) polypropylene Draw Rope, to facilitate the cable installation.
.5 The ducts shall be encased in a concrete envelope which shall be worked below and between ducts
to provide a homogenous mass. Duct spacers shall be plastic to provide required spacing both horizontally and vertically. Minimum of two spacers per 3050 mm (10 ft.) length of duct shall be used.
3.2 GROUNDING
.1 Provide a grounding system at the transformer and switchgear in accordance with OESC. Provide #2/0 AWG copper conductor connected to building ground system.
.2 All work in connection with the pole mounted transformer shall be performed in strict accordance
with regulations and the OESC. Obtain approval of all details before commencing work.
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Electrical Service & Distribution Section 26 30 00 Page 5 of 5
3.3 ELECTRICAL SERVICE
.1 Provide complete electrical service as shown on the Drawings and as further described here.
.2 The Local Hydro Authority will supply electrical service at 208 volt, 3 phase, 4 wire, 60 cycles.
.3 Grounding service, equipment, feeders, and the like shall be performed in accordance with the Local Hydro Authority requirements.
The neutral conductor of the wiring system together with the conduit system and service equipment shall be bonded to the water service as near as practical to the service entrance. Confirm type of water service pipe system with Mechanical Division and provide grounding system in accordance with O.H.E.P.C. regulations. Provide an "Artificial Grounding" system in accordance with Canadian Electric Code, Section 10-702 and Ontario Hydro Supplement. Location shall be to approval of the Supply & Inspection Authority requirements.
.4 Install an outdoor P-base metering cabinet as per requirements and connected to switchboard with
an empty1-1/4" rigid conduit and telephone line all to approval of the Local Hydro Authority. 3.4 SECONDARY CABLES
.1 Secondary cables c/w termination lugs (coordinate with the Local Hydro Authority for more information regarding termination lugs requirement at transformer secondary side and comply accordingly) shall be supplied and installed by the electrical Subcontractor.
3.5 HYDRO STANDARDS / REQUIREMENTS
.1 Coordinate on site with t h e L o c a l Hydro Authority representative for more information and details regarding hydro standards and requirement and exact scope of work prior to commencing the work and comply accordingly.
END OF SECTION
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Power Generator Section 26 30 10 Page 1 of 11
SECTION SPECIFICATIONS: GENERATOR SET
1. Scope of Work id101_Scope_of_Work 1.1. It is the intent of this specification to secure an engine-driven generator set that has been
prototype tested, factory built, production-tested, and site-tested together with all accessories necessary for a complete installation as shown on the plans and the Drawings and specified herein.
1.2. Any and all exceptions to the published specifications shall be subject to the approval of the Consultant.
1.3. The power system shall be furnished by a single manufacturer who shall be responsible for the design, coordination, and testing of the complete system. The entire system shall be installed as shown on the plans, the Drawings, and specifications herein.
1.4. The equipment shall be produced by a manufacturer who has produced this type of equipment for a period of at least 10 years and who maintains a service organization available twenty-four hours a day throughout the year.
1.5. The equipment shall be produced by a manufacturer who is ISO 9001 certified for the design, development, production and service of its complete product line.
2. General Requirements id102_General_Requirements 2.1. It is the intent of this specification to secure a generator set system that has been tested
during design verification, in production, and at the final job site. The generator set will be a commercial design and will be complete with all of the necessary accessories for complete installation as shown on the plans, drawings, and specifications herein. The equipment supplied shall meet the requirements of the Ontario Electrical Code and applicable local codes and regulations.
2.2. All equipment shall be new and of current production by a firm that manufactures the generator sets and controls, transfer switches, and switchgear, and assembles the generator sets as a complete and coordinated system. There will be one-source responsibility for warranty, parts, and service through a local representative with factory-trained servicemen.
3. Submittal id103_Submittal 3.1. The submittal shall include prototype test certification and specification sheets showing all
standard and optional accessories to be supplied; schematic wiring diagrams, dimension drawings, and interconnection diagrams identifying by terminal number each required interconnection between the generator set, the transfer switch, and the remote annunciator panel if it is included elsewhere in these specifications.
4. Codes and Standards id104_Codes_and_Standards 4.1. The generator set shall be listed to UL 2200 or submitted to an independent third party
certification process to verify compliance as installed. 4.2. The generator set shall conform to the requirements of the following codes and standards:
4.2.1. CSA C22.2, No. 14-M91 Industrial Control Equipment. 4.2.2. EN50082-2, Electromagnetic Compatibility-Generic Immunity Requirements,
Part 2: Industrial. 4.2.3. EN55011, Limits and Methods of Measurement of Radio Interference
Characteristics of Industrial, Scientific and Medical Equipment. 4.2.4. IEC8528 part 4, Control Systems for Generator Sets.
York Region Contract NO. T-15-40 York Region Paramedic Response Station #25 Markham 5590 14th Avenue, Markham, Ontario
Power Generator Section 26 30 10 Page 2 of 11
4.2.5. IEC Std 61000-2 and 61000-3 for susceptibility, 61000-6 radiated and conducted electromagnetic emissions.
4.2.6. IEEE446 Recommended Practice for Emergency and Standby Power Systems for Commercial and Industrial Applications.
4.2.7. CSA-C282-09 Emergency Electrical Power Supply for Buildings. The generator set shall meet all requirements of the specification including all alarms, shutdowns, and indications shown on Table-2 of the specification. The generator enclosure shall include dampers, heaters, emergency lighting, and a distribution panel in accordance with this specification.
4.2.8. CSA-149.1-10 Natural Gas and Propane Installation Code. 5. Testing id105_Testing
5.1. To ensure that the equipment has been designed and built to the highest reliability and quality standards, the manufacturer and/or local representative shall be responsible for three separate tests: design prototype tests, final production tests, and site tests.
5.2. Design Prototype Tests. Components of the emergency system, such as the engine/generator set, transfer switch, and accessories, shall not be subjected to prototype tests because the tests are potentially damaging. Rather, similar design prototypes and preproduction models shall be subject to the following tests:
5.2.1. Maximum power (kW). 5.2.2. Maximum motor starting (kVA) at 35% instantaneous voltage dip. 5.2.3. Alternator temperature rise by embedded thermocouple and/or by resistance
method per NEMA MG1-32.6. 5.2.4. Governor speed regulation under steady-state and transient conditions. 5.2.5. Voltage regulation and generator transient response. 5.2.6. Harmonic analysis, voltage waveform deviation, and telephone influence factor. 5.2.7. Three-phase short circuit tests. 5.2.8. Alternator cooling air flow. 5.2.9. Torsional analysis to verify that the generator set is free of harmful torsional
stresses. 5.2.10. Endurance testing.
5.3. Final Production Tests. Each generator set shall be tested under varying loads with guards and exhaust system in place. Tests shall include:
5.3.1. Single-step load pickup 5.3.2. Safety shutdown device testing 5.3.3. Rated Power @ 0.8 PF 5.3.4. Maximum power 5.3.5. Upon request, a witness test, or a certified test record sent prior to shipment.
5.4. Site Tests. The manufacturer's distribution representative shall perform an installation check, start-up, and building load test. The Consultant, regular operators, and the maintenance staff shall be notified of the time and date of the site test. The tests shall include:
5.4.1. Fuel, lubricating oil, and antifreeze shall be checked for conformity to the manufacturer's recommendations, under the environmental conditions present
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Power Generator Section 26 30 10 Page 3 of 11
and expected. 5.4.2. Accessories that normally function while the set is standing by shall be checked
prior to cranking the engine. These shall include: block heaters, battery chargers, alternator strip heaters, remote annunciators, etc.
5.4.3. Generator set start-up under test mode to check for exhaust leaks, path of exhaust gases outside the building, cooling air flow, movement during starting and stopping, vibration during operation, normal and emergency line-to-line voltage and frequency, and phase rotation.
5.4.4. Automatic start by means of a simulated power outage to test remote-automatic starting, transfer of the load, and automatic shutdown. Prior to this test, all transfer switch timers shall be adjusted for proper system coordination. Engine coolant temperature, oil pressure, and battery charge level along with generator set voltage, amperes, and frequency shall be monitored throughout the test.
6. Warranty and Maintenance id106_Warranty_and_Maintenance 6.1. The generator set shall include a standard one year warranty to guarantee against
defective material and workmanship in accordance with the manufacturer's published warranty from date of start-up. Optional warranties shall be available upon request.
6.2. The generator set manufacturer and its distributor shall maintain a 24-hour parts and service organization. This organization shall regularly engage in maintenance contract programs to perform preventive maintenance and service on equipment similar to that specified. A service agreement shall be available and shall include system operation under simulated operating conditions; adjustment to the generator set, transfer switch, and switchgear controls as required, and certification in the owner's maintenance log of repairs made and function tests performed on all systems.
7. Equipment id107_Equipment 7.1. The generator set shall be a Kohler model 60REZGB with a 4P7BX alternator or
equivalent. It shall provide 60kW/75 kVA when operating at 120/208 volts, 60 Hz, .8 power factor. The generator set shall be capable of a Standby 130°C rating while operating in an ambient condition of less than or equal to 77° F and a maximum elevation of 656 feet above sea level.
7.2. Motor starting performance and voltage dip determinations shall be based on the complete generator set. The generator set shall be capable of supplying 135 LRKVA for starting motor loads with a maximum instantaneous voltage dip of 35%, as measured by a digital RMS transient recorder in accordance with IEEE standard 115. Motor starting performance and voltage dip determination that does not account for all components affecting total voltage dip i.e. engine, alternator, voltage regulator and governor will not be acceptable. As such, the generator set shall be prototype tested to optimize and determine performance as a generator set system.
7.3. Vibration isolators shall be provided between the engine-alternator and heavy-duty steel base.
8. Engine id108_Engine 8.1. The minimum 305-cubic-inch displacement engine shall deliver a minimum of 89 HP at a
governed engine speed of 1800 rpm, and shall be equipped with the following: 8.1.1. Electronic isochronous governor capable of 0.5% steady-state frequency
regulation. Engine speed shall be nominally 1800 rpm. Engines running at higher rpm’s and featuring speed reduction gear drives are not acceptable.
8.1.2. 12-volt positive-engagement solenoid shift-starting motor. 8.1.3. 70-ampere automatic battery charging alternator with a solid-state voltage
York Region Contract NO. T-15-40 York Region Paramedic Response Station #25 Markham 5590 14th Avenue, Markham, Ontario
Power Generator Section 26 30 10 Page 4 of 11
regulation. 8.1.4. Positive displacement, full-pressure lubrication oil pump, cartridge oil filters,
dipstick, and oil drain. 8.1.5. Dry-type replaceable air cleaner elements for normal applications. 8.1.6. Engine-driven or electric fuel-transfer pump including fuel filter and electric
solenoid fuel shutoff valve capable of lifting fuel. 8.2. The turbocharged engine shall be fueled by natural gas. 8.3. The engine shall have a minimum of 8 cylinders and be liquid-cooled by Unit Mounted
Radiator 122°F/50°C. 8.4. The engine shall be EPA certified from the factory, and shall not require a site performance
test. 8.5. Natural Gas fuel supply pressure, measured at the generator set fuel inlet downstream of
any fuel system equipment accessories shall be within the operating range of 1.74-2.74 kPa (7.0-11.0 in. H²O). Engines requiring higher gas pressures are not acceptable.
9. Alternator id109_Alternator 9.1. The alternator shall be salient-pole, brushless, 2/3-pitch, 12 lead, self-ventilated with drip-
proof construction and amortisseur rotor windings and skewed for smooth voltage waveform. The ratings shall meet the NEMA standard (MG1-32.40) temperature rise limits. The insulation shall be class H per UL1446 and the varnish shall be a fungus resistant epoxy. Temperature rise of the rotor and stator shall be limited to Standby 130°C. The excitation system shall be of brushless construction controlled by a solid- state voltage regulator capable of maintaining voltage within ±2.0% at any constant load from 0% to 100% of rating. The AVR shall be capable of proper operation under severe nonlinear loads and provide individual adjustments for voltage range, stability and volts-per-hertz operations. The AVR shall be protected from the environment by conformal coating. The waveform harmonic distortion shall not exceed 5% total RMS measured line-to-line at full rated load. The TIF factor shall not exceed 50.
9.2. The alternator shall have a single maintenance-free bearing, designed for 40000 hour B10 life. The alternator shall be directly connected to the flywheel housing with a semi-flexible coupling between the rotor and the flywheel.
9.3. The generator shall be inherently capable of sustaining at least 250% of rated current for at least 10 seconds under a 3-phase symmetrical short circuit without the addition of separate current-support devices.
10. Controller id110_Controller 10.1. Decision-Maker® 550 Controller
10.1.1. The generator set controller shall meet CSA-C282-09 requirements and shall include an integral alarm horn as required by NFPA.
10.1.2. The controller shall meet all alarms, shutdowns, and indication stipulated in Table 2 of the CSA-C282-09 specification.
10.1.3. The controller shall be UL 508 listed. 10.1.4. Controller shall have a key switch to meet local code requirements and shall be
removable only in the AUTO position. 10.2. Applicability
10.2.1. The controller shall be standard on a 60REZGB. 10.2.2. The controller shall support 12-volt starting systems. 10.2.3. The controller's environmental specification shall be: -40°C to 70°C operating
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Power Generator Section 26 30 10 Page 5 of 11
temperature range and 5-95% humidity, non-condensing. 10.2.4. The controller shall mount on the generator or remotely within 40 feet with
viewable access. 10.3. Hardware Requirements
10.3.1. Control Panel shall include: 1. The control shall have a run-off/reset-auto three-position selector switch. 2. A controller-mounted, latch-type emergency stop pushbutton. 3. Five indicating lights: System Ready - green Not in Auto - yellow
Programming Mode - yellow System Warning - yellow System Shutdown - red
4. Display with two lines of 20-alphanumeric characters, viewable in all light conditions.
5. Sixteen position snap action sealed keypad for menu selection and data entry.
6. For ease of use, an operating guide shall be printed on the controller faceplate.
7. An audible alarm with alarm silence capability. 8. Panel lights shall be supplied as standard.
10.4. Control Functional Requirements 10.4.1. Field-programmable time delay for engine start. Adjustment range 0-5 minutes
in 1 second increments. 10.4.2. Field-programmable time delay engine cooldown. Adjustment range 0-10
minutes in 1 second increments. 10.4.3. Capability to start and run at user-adjustable idle speed during warmup for a
selectable time period (0-10 minutes), until engine reaches preprogrammed temperature, or as supported by ECM-equipped engine.
10.4.4. The idle function including engine cooldown at idle speed. 10.4.5. Real-time clock and calendar for time stamping of events. 10.4.6. Output with adjustable timer for an ether injection starting system. Adjustment
range, 0-10 seconds. 10.4.7. Output for shedding of loads if the generator set reaches a user programmable
percentage of its kW rating. Load shed shall also be enabled if the generator set output frequency falls below 59 Hz.
10.4.8. Programmable cyclic cranking that allows up to six crank cycles and up to 35 seconds of crank time per crank cycle.
10.4.9. The capability to reduce controller current battery draw, for applications where no continuous battery charging is available. The controller vacuum fluorescent display should turn off automatically after the controller is inactive for 5 minutes.
10.4.10. Control logic with alternator protection for overload and short circuit matched to each individual alternator and duty cycle.
10.4.11. Control logic with RMS digital voltage regulation. A separate voltage regulator is not acceptable. The digital voltage regulator shall be applicable to single- or three-phase systems.
10.4.12. The capability to exercise the generator set by programming a running time into
York Region Contract NO. T-15-40 York Region Paramedic Response Station #25 Markham 5590 14th Avenue, Markham, Ontario
Power Generator Section 26 30 10 Page 6 of 11
the controller. This feature shall also be programmable through the PC software. 10.4.13. Control function shall include output voltage adjustment. 10.4.14. Battle switch function selection to override normal fault shutdowns, except
emergency stop and overspeed shutdown. 10.4.15. The control shall detect the following conditions and display on control panel:
1. Customer programmed digital auxiliary input ON (any of the 21 inputs available)
2. Customer programmed analog auxiliary input out of bounds (any of 7 inputs for ECM equipped engines and 5 inputs for non ECM engines)
3. Emergency stop 4. High & low coolant temperature 5. High oil temperature 6. Controller internal fault 7. Locked rotor - fail to rotate 8. Low coolant level 9. Low oil pressure 10. Master switch error 11. CSA-C282-09 common alarm 12. Overcrank 13. Overspeed with user-adjustable level, range 60-70 Hz. 14. Overvoltage with user adjustable level, range 105% to 135% 15. Overfrequency with user adjustable level, range 102% to 140% 16. Underfrequency with user adjustable level, range 80% to 90% 17. Undervoltage with user adjustable level, range 70% to 95% 18. Coolant temperature signal loss 19. Oil pressure gauge signal loss Conditions resulting in generator warning (generator will continue to operate): 1. Battery charger failure 2. Customer programmed digital auxiliary input on (any of the 21 inputs
available) 3. Customer programmed analog auxiliary input on (any of the 7 inputs
available on ECM engines and 5 inputs for non ECM engines) 4. Power system supplying load 5. Ground fault detected - detection by others 6. High battery voltage - Level shall be user adjustable. 7. Range 29-33 volts for 24-volt systems. 8. High coolant temperature 9. Load shed
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Power Generator Section 26 30 10 Page 7 of 11
10. Loss of AC sensing 11. Underfrequency 12. Low battery voltage - level shall be user adjustable, range 20-25 volts for
24-volt systems. 13. Low coolant temperature 14. Low fuel level or pressure 15. Low oil pressure 16. CSA-C282-09 common alarms 17. Overcurrent 18. Speed sensor fault 19. Weak battery 20. Alternator protection activated
10.5. Control Monitoring Requirements 10.5.1. All monitored functions must be viewable on the control panel display. 10.5.2. The following generator set functions shall be monitored:
1. All output voltages - single phase, three phase, line to line, and line to neutral, 0.25% accuracy
2. All single phase and three phase currents, 0.25% accuracy 3. Output frequency, 0.25% accuracy 4. Power factor by phase with leading/lagging indication 5. Total instantaneous kilowatt loading and kilowatts per phase, 0.5%
accuracy 6. kVARS total and per phase, 0.5% accuracy 7. kVA total and per phase, 0.5% accuracy 8. kW hours 9. A display of percent generator set duty level (actual kW loading divided by
the kW rating) 10.5.3. Engine parameters listed below shall be monitored: (*available with ECM
equipped engines) 1. Coolant temperature both in English and metric units 2. Oil pressure in English and metric units 3. Battery voltage 4. RPM 5. Lube oil temperature* 6. Lube oil level* 7. Crankcase pressure* 8. Coolant level* 9. Coolant pressure* 10. Fuel pressure* 11. Fuel temperature*
York Region Contract NO. T-15-40 York Region Paramedic Response Station #25 Markham 5590 14th Avenue, Markham, Ontario
Power Generator Section 26 30 10 Page 8 of 11
12. Fuel rate* 13. Fuel used during the last run* 14. Ambient temperature*
10.5.4. Operational records shall be stored in the control beginning at system start-up. 1. Run time hours 2. Run time loaded hours 3. Run time unloaded hours 4. Number of starts 5. Factory test date 6. Last run data including date, duration, and whether loaded or unloaded 7. Run time kilowatt hours
10.5.5. The following operational records shall be a resettable for maintenance purposes: 1. Run time hours 2. Run time loaded hours 3. Run time unloaded hours 4. Run time kilowatt hours 5. Days of operation 6. Number of starts 7. Start date after reset
10.5.6. The controller shall store the last one hundred generator set system events with date and time of the event.
10.5.7. For maintenance and service purposes, the controller shall store and display on demand the following information: 1. Manufacturer's model and serial number 2. Battery voltage 3. Generator set kilowatt rating 4. Rated current 5. System voltage 6. System frequency 7. Number of phases
10.6. Inputs and Outputs 10.6.1. Inputs
1. There shall be 21 dry contact inputs that can be user-configured to shut down the generator set or provide a warning.
2. There shall be 7 user-programmable analog inputs for ECM-equipped engines (5 for non-ECM engines) for monitoring and control.
3. Each analog input can accept 0-5 volt analog signals 4. Resolution shall be 1:10,000
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Power Generator Section 26 30 10 Page 9 of 11
5. Each input shall include range settings for 2 warnings and 2 shutdowns. 6. All values shall be on the control panel display. 7. Shall be user-assigned. 8. Additional standard inputs required: • Input for an external ground fault detector. Digital display shall show
"ground fault" upon detection of a ground fault. • Reset of system faults. • Remote two-wire start. • Remote emergency stop. 9. Idle mode enable.
10.6.2. Outputs 1. All CSA-C282-09 outputs shall be available. 2. Thirty outputs shall be available for interfacing to other equipment:
• All outputs shall be user-configurable from a list of 25 functions and faults. • These outputs shall drive optional dry contacts.
3. A programmable user-defined common fault output with over 40 selections shall be available.
10.7. Communications 10.7.1. If the generator set engine is equipped with an ECM (engine control module),
the controller shall communicate with the ECM for control, monitoring, diagnosis, and meet SAE J1939 standards.
10.7.2. Industry standard Modbus communication shall be available. 10.7.3. A Modbus master shall able to monitor and alter parameters, and start or stop a
generator. 10.7.4. The controller shall have the capability to communicate to a personal computer
(IBM or compatible) running Windows ’9X or Windows NT. 10.7.5. Communications shall be available for serial, CAN, and Ethernet bus networks. 10.7.6. A variety of connections shall be available based on requirements:
1. A single control connection to a PC. 2. Multiple controls on an intranet network connected to a PC. 3. A single control connection to a PC via phone line. 4. Multiple controls to a PC via phone line.
10.7.7. Generator and transfer switch controls shall be equipped with communications modules capable of connecting to the same communication network.
10.7.8. The capability to connect up to 128 controls (any combination of generator sets and transfer switches) on a single network shall be supported.
10.7.9. Cabling shall not be limited to the controller location. 10.7.10. Network shall be self-powered.
York Region Contract NO. T-15-40 York Region Paramedic Response Station #25 Markham 5590 14th Avenue, Markham, Ontario
Power Generator Section 26 30 10 Page 10 of 11
11. Accessories id111_Accessories 11.1. Air Restriction Indicator. The air cleaner restriction indicator shall indicate the need for
maintenance of the air cleaners. 11.2. Battery Charger. A 6-ampere automatic float to equalize battery charger with the following
features: 1. 12 VDC output 2. 1% steady-state voltage regulation from no load to full load over 10% AC input line
voltage variation 3. LED lamps for charge state indication 4. Temperature compensated for ambient temperatures for -40°C to 70°C 5. Potting for durability 6. Short-circuit and reverse polarity protection 7. UL 1236 listed
11.3. Battery Rack and Cables. Battery rack and battery cables capable of holding the manufacturer's recommended batteries shall be supplied.
11.4. Circuit Breaker. The generator shall come with a primary, factory installed, 100% rated line circuit breaker of 200 amperes that is UL2200 listed. Line circuit breakers shall be sized for the rated ampacity of the genset. Load side lugs shall be provided from the factory. The line circuit breaker shall include auxiliary contacts, shunt trip, undervoltage trip, alarm switch, and overcurrent switch functionality. Load side breaker connections made at the factory shall be separated from field connections. When GFI breakers are required, additional neutrals shall be factory installed.
11.5. Dry Contact Kits. The 10 Dry Contact Kit shall provide normally open and normally closed, gold-plated contacts in a form C configuration to activate warning devices and other customer-provided accessories allowing remote monitoring of the generator set. Typically, lamps, audible alarms, or other devices signal faults or status conditions.
11.7. Failure Relay. 11.7.1. The common failure relay shall remotely signal auxiliary faults, emergency stop,
high engine temperature, low oil pressure, overcrank, and overspeed via one single-pole, double-throw relay with 10 amps at 120 VAC contacts.
11.7.2. The relay contacts shall be gold flashed to allow use of low current draw devices (100ma @ 28VDC min.).
11.7.3. Once energized the relay shall remain latched until the system is reset by the main controller switch.
11.8. Remote Annunciator Panel. The remote annunciator shall meet CSA-C282-09 Table 2 requirements and enable remote viewing of the generator status. The panel shall be connected to the generator controller via either network communication wires or via hard wired connections. Options shall be available to provide ATS source availability, contactor position, and loaded or unloaded test for up to four transfer switches. The panel shall have the capability to be either flush- mounted or surface-mounted. The annunciator shall meet UL508 requirements.
11.9. Rodent Guards. Generator rodent guards shall prevent intrusion and protect internal components.
11.10. Run Relay. The run relay shall provide a three-pole, double-throw relay with 10-amp/ 250 VAC contacts to indicate that the generator is running. The relay provides three sets of dry contacts for energizing or de-energizing customer devices while the generator is running
York Region Contract No #T-19-16 York Region Paramedic Response Station #29 107 Glen Cameron Road, City of Markham
Power Generator Section 26 30 10 Page 11 of 11
(e.g. louvers, indicator lamps, etc.) 11.11. Skid End Caps. The generator shall include skid end caps. 11.12. Standard Air Cleaner. The air cleaner shall provide engine air filtration which meets the
engine manufacturer's specifications under typical operating conditions. 11.13. Block Heater. The block heater shall be thermostatically controlled and sized to maintain
manufacturers recommended engine coolant temperature to meet the start-up requirements of CSA-C282-09.
12. Sound Enclosure id117_Sound_Enclosure 12.1. The enclosure shall be constructed from high strength, low alloy steel, aluminum or
galvanized steel. 12.2. The enclosure shall be finish coated with powder baked paint for superior finish, durability
and appearance. Enclosures will be finished in the manufacturer's standard color. 12.3. The enclosure shall allow the generator set to operate at full load in an ambient of 40°C -
45°C with no additional de-rating of the electrical output. 12.4. The enclosure shall be equipped with sufficient side and end doors to allow access for
operation, inspection, and service of the unit and all options. Minimum requirements are two doors per side. When the generator set controller faces the rear of the generator set, an additional rear facing door is required. Access to the controller and main line circuit breaker must meet the requirements of the Ontario Electric Code.
12.5. Doors shall be equipped with lockable latches. Locks must be keyed alike. 12.6. A duct between the radiator and air outlet shall be provided to prevent re-circulation of hot
air. 12.7. The complete exhaust system shall be internal to the enclosure. 12.8. All acoustical insulation shall be fixed to the mounting surface with pressure sensitive
adhesive or mechanically fastened. In addition, all acoustical insulation mounted on a horizontal plane shall be mechanically fastened. The acoustical insulation shall be flame retardant.
12.9. The enclosure shall include an exhaust scoop to direct the cooling air in a vertical direction. 12.10. The enclosure shall include a mounted load centre to be fed from the buildings normal
electrical supply. The load centre shall include individual feeder breakers pre-wired to all engine and enclosure electrical devices requiring normal supply power including, but not limited to: block heater, battery heater, battery charger, enclosure space heater, enclosure dampers, and 2-hour battery back-up emergency light pack (as specified in CSA-C282-09).
12.11. The enclosure dampers and space heater shall be configured so as to keep the interior space of the enclosure at 10°C at all times when the engine is not running. Dampers shall be installed in a fail-safe to open configuration. The dampers shall be configured to open upon failure of normal power. Dampers shall also be configured to open upon engine running, regardless of the condition of normal supply power.
12.12. If the plans show the generator is not being installed on a solid concrete pad and will be elevated in any way such the bottom of the generator set enclosure will be open to the elements, provide a solid sheet metal bottom to the enclosure. The solid bottom shall be installed in such a way that it does not compromise the enclosure heating, engine cooling, or sound emissions of the unit, while also preventing rodent intrusions.
END OF SECTION