AMORPHOUS CAST RESIN DRY TYPE TRANSFORMERCapacity: Up to 5000kVAVoltage: Up to 36kV
PowerBusiness Group
Industrial ApplianceBusiness Unit
Industrial Appliance Business Unit Export Division102 Minsheng Rd., Neihai Village, Tayuan, Taoyuan County, Taiwan, 33759, R.O.C.TEL : +886-3-3863123 #1304 FAX : +886-3-3863123 #1380E-mail Address : [email protected]
Head officeNo. 22, Sec. 3, ChungShan N. Rd., Taipei City, Taiwan, 10435, R.O.C.TEL: +886-2-25925252#3633FAX: +886-2-25984425 Web site: www.tatung.com
2012.10
AccessoriesItem Standard parts Option parts
Capacity(kVA)
Rated current (A)Name plate – Primary
(20000V)Secondary
(400V)Earthing terminal –Base – 315 9.1 455Lifting lug – 400 11.5 577Warning label – 500 14.4 722HV coil terminal – 630 18.2 909LV coil terminal – 800 23.1 1155No voltage tap changer – 1000 28.9 1443Bi-direction wheel – 1250 36.1 1804Digital temp. monitor – 1600 46.2 2310Dial type thermometer – 2000 57.7 2887Anti-vibration pad – 2500 72.2 3609Static shield –Cooling fan –Enclosure –LV copper busway –Flexible copper strip –
Ordering or inquiring information requiredPhase □ Three □ Single Frequency □ 50Hz □ 60Hz □ Other: Hz
Capacity kVA Condition Altitude m, ambient temp. ℃
HV sideRated voltage V Connection □ △ connection □ Y connection
Tap □ No □ Yes( □ ± 2 × 2.5% □ Other: )
LV side Rated voltage V Connection □ △ connection □ Y connection
Standard □ IEC 60076-11 □ Other:
Impedance □ 4% □ 6% □ % Vector group □ Dyn11 □ Dd0 □Other:
Cooling type □ Natural air (AN) □ Forced air (AF) ( AF capacity: kVA )
Enclosure□ Yes ( Protection level: □ IP20 □ IP23 □ IP ) Cable entrance
(with enclosure)HV side □ Top □ Bottom □ Side
□ No (IP00) LV side □ Top □ Bottom □ Side
Specialaccessories
□ Yes □ Bi-direction wheel □ Anti-vibration pad □ Temperature( □ digital type □ dial type )□ Static shield between HV & LV □ Other:
□ No ( Standard accessories )
Quantities
(A)Rated current =(KVA)x1000
x Rated voltage (V)3√
Rated current quick index table
AMT-MT SERIES
Partial discharge
free
70% ~ 80%No load loss
reduced
Transformer comply with E2/C2/F1 class
No pollution,all materials can be recycled
SpecificationType Cast-resin dry type, self cooled Dielectric Strength Primary voltage Secondary voltageService condition Indoor 24kV ≦ 1.1kVInsulation Class F Applied voltage 50kV 3kVTemperature rise 100K BIL 125kV ---
Rating
Phase Primary voltage (V)
Secondary voltage (V)
Rated capacity
(kVA)Frequency
(Hz) Connection Standard
ThreeF21000 F20500 R20000 F19500
F19000400/231
315、400、500、630、
800、1000、1250、1600、2000、2500
50 △ /Y IEC 60076-11
Characteristics (at 75℃ )
Capacity(kVA)
Prim.voltage(V)
Sec. voltage(V)
Vector group
No load loss(W)
Load loss(W)
Efficiency(%)No load
current(%)Impedance(reference)
(%)30% load
50% load
100% load
315
20000 400 Dyn11
365 3300 99.30 99.25 98.85 0.6 4.0400 450 3680 99.35 99.32 98.97 0.6 4.0500 480 4500 99.41 99.36 99.01 0.5 4.0630 530 5550 99.45 99.39 99.04 0.5 6.0800 580 6520 99.51 99.45 99.12 0.5 6.0
1000 710 7650 99.53 99.47 99.17 0.4 6.01250 800 9150 99.56 99.50 99.21 0.4 6.01600 910 11290 99.60 99.53 99.24 0.3 6.02000 1070 13800 99.61 99.55 99.26 0.3 6.02500 1380 16200 99.62 99.56 99.30 0.3 6.0
※ Tolerance is comply with IEC 60076-11.
DimensionCapacity
(kVA)Outline dimension (mm) IP00 Approx.
weight(kg)Outline dimension (mm) IP20 Approx.
weight(kg)X Y Z X Y Z315 1400 800 1500 2200 1900 1300 2000 2700400 1500 800 1550 2700 2000 1300 2100 3200500 1500 800 1650 2900 2000 1300 2200 3500630 1650 1000 1700 3400 2100 1500 2200 4000800 1650 1000 1750 3900 2100 1500 2250 4500
1000 1700 1100 1800 4500 2200 1600 2300 51001250 1700 1200 2000 5200 2200 1600 2500 58001600 1900 1200 2100 6200 2400 1700 2600 69002000 1900 1200 2200 7100 2400 1700 2700 79002500 2100 1200 2300 8900 2500 1700 2800 9700
※ The dimensions and weights are reference only, final drawing will be issued after receipt of order.
Outline of transformer
Introduction of amorphous alloyRaw materials are melted down in induction furnace, melt jet is quenched at 106℃ per second to form an amorphous strip. Atoms are solidified before crystallization to have non-crystalline structures like glass resulting in excellent properties as a soft magnetic metal.
Comparison of amorphous alloy and silicon SteelAtom model of material & core structure
Hysteresis curve comparison
Benefits of using amorphous core transformer
AMT-MT SERIES
AMT-MT SERIES
Non-crystal amorphous model Amorphous alloy ribbon Amorphous core
Crystal metal model Silicon steel Silicon steel core
Features of amorphous alloy compare to silicon steel
Tesla
Oersteds
2
1
0
2
1
1.56T2.03T
Silicon steel (CRGO)Amorphous alloy
IP00 IP20
Patented amorphous core manufacturing process is adopted resulting in superior low core loss and with low load loss design of coil increasing the transformer efficiency greatly, no-load loss of the transformer is about 70~80% lower than the traditional silicon ones.
Non-polluted insulating materials and low energy consumption amorphous alloy are adopted as well as the energy saving characteristics of the transformer, achieve the goal of less CO2 emission and environment friendly.
The non-inflammable epoxy resin is adopted for casting coils of the transformers to have excellent dust-proof, anti-moisture and high insulating abilities, the coil has passed the C2/E2/F1 test of IEC 60076-11 ensuring the operation safety.
Patented three-phase three-leg amorphous core structure owned by Tatung is adopted for the transformer resulting in very low noise level (lower than the NEMA standard about 3~5dB). The low operating temperature due to low losses help longer life span of the transformer.
Low lossHigh efficiency
Energy saving
No pollutionLess co2 emission
Environmental friendly
Fire preventionExcellent insulation
Safety
Low noiseLong operation life
Quality
H2 H3H1
Z
X Y
X Y
Z
Lower retentivity Lower hysteresis losses(1/3)
Less thickness Less eddy current(1/10)
Higher resistance Less eddy current(3 times)