7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 1/18 Pjt Name : Facility Upgrade Relocation of U/G Process Piping 2nd TECHNIC SMALL POWER & LIG GENERAL 1 GENERAL 1) Proposal No. Bidder to Specify V AS/SM/LTR/7312/2005 Confirmed 2) Country of Origin Bidder to Specify V KUWAIT Confirmed 3) Manufacturer Bidder to Specify V  AL-AHLEIA SWITCHGEAR CO., K.S.C.C., KUWAIT Confirmed 4) Delivery Date Bidder to Specify ? To show 5) Manufacturer  As per attached KOC Approved Vendor List ? To show 6) Delivery Date after PO Bidder to Specify ? To show 7) Delivery Condition Bidder to Specify ? To show 8) Warranty period Bidder to Specify ? To show 2 ITEM & QUANTITY 1) MOV POWER DISTRIBUTION BOARD 1) 01-PDB-001 FOR GC-01, DESALTER S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed - DIMENSION Bidder to Specify  V 2560W x 1250D x 2400D Confirmed 2) 02-PDB-001 FOR GC-02, DESALTER S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed - DIMENSION Bidder to Specify  V 2560W x 1250D x 2400D Confirmed 3) 09-PDB-001 FOR GC-09, CENTRALIZED S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed - DIMENSION Bidder to Specify  V 2560W x 1250D x 2400D Confirmed 4) 10-PDB-001 FOR GC-10, CENTRALIZED S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed - DIMENSION Bidder to Specify  V 2560W x 1250D x 2400D Confirmed 5) 11-PDB-001 FOR GC-11, DESALTER S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed - DIMENSION Bidder to Specify  V 2560W x 1250D x 2400D Confirmed 6) 19-PDB-001 FOR GC-19, DESALTER S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed - DIMENSION Bidder to Specify  V 2560W x 1250D x 2400D Confirmed 7) 20-PDB-001 FOR GC-20, DESALTER S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed - DIMENSION Bidder to Specify  V 2560W x 1250D x 2400D Confirmed 8) 22-PDB-001 FOR GC-22, DESALTER S/S 1 SET V YES Confirmed - 100A BUS 25KA sym. rms. V YES Confirmed 4POLE 100A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES Confirmed 4POLE 32A FEEDER MCCB w/ Earth Fault Protection Device 50 CKTS V YES Confirmed 1st Technical Clarification by Purchaser(2006_01_13) NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

Embed Size (px)

Citation preview

Page 1: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 1/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNIC

SMALL POWER & LIG

GENERAL

1 GENERAL

1) Proposal No. Bidder to Specify V AS/SM/LTR/7312/2005 Confirmed

2) Country of Origin Bidder to Specify V KUWAIT Confirmed

3) Manufacturer Bidder to Specify V AL-AHLEIA SWITCHGEAR CO.,

K.S.C.C., KUWAITConfirmed

4) Delivery Date Bidder to Specify ? To show

5) Manufacturer  As per attached KOC Approved

Vendor List? To show

6) Delivery Date after PO Bidder to Specify ? To show

7) Delivery Condition Bidder to Specify ? To show

8) Warranty period Bidder to Specify ? To show

2 ITEM & QUANTITY

1) MOV POWER DISTRIBUTION BOARD

1) 01-PDB-001 FOR GC-01, DESALTER S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES Confirmed

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

- DIMENSION Bidder to Spec ify   V 2560W x 1250D x 2400D Confirmed

2) 02-PDB-001 FOR GC-02, DESALTER S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES Confirmed4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

- DIMENSION Bidder to Spec ify   V 2560W x 1250D x 2400D Confirmed

3) 09-PDB-001 FOR GC-09, CENTRALIZED S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES Confirmed

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

- DIMENSION Bidder to Spec ify   V 2560W x 1250D x 2400D Confirmed

4) 10-PDB-001 FOR GC-10, CENTRALIZED S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES Confirmed

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

- DIMENSION Bidder to Spec ify   V 2560W x 1250D x 2400D Confirmed

5) 11-PDB-001 FOR GC-11, DESALTER S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES Confirmed

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

- DIMENSION Bidder to Spec ify   V 2560W x 1250D x 2400D Confirmed

6) 19-PDB-001 FOR GC-19, DESALTER S/S 1 SET V YES Confirmed- 100A BUS 25KA sym. rms. V YES Confirmed

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

- DIMENSION Bidder to Spec ify   V 2560W x 1250D x 2400D Confirmed

7) 20-PDB-001 FOR GC-20, DESALTER S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES Confirmed

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

- DIMENSION Bidder to Spec ify   V 2560W x 1250D x 2400D Confirmed

8) 22-PDB-001 FOR GC-22, DESALTER S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES Confirmed

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES Confirmed

4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device50 CKTS V YES Confirmed

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

Page 2: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 2/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHN

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

- DIMENSION B idder to Specify   V 2560W x 1250D x 2400D Confirmed

2) MAIN LIGNTING DISTRIBUTION BOARD

1) 01-MDB-100 FOR GC-01, DESALTER S/S 1 SET V YES Confirmed

- 200A BUS 25KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device8 CKTS ? 8 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

2) 01-MDB-200 FOR GC-01, CRU S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

3) 02-MDB-100 FOR GC-02, DESALTER S/S 1 SET V YES Confirmed- 200A BUS 25KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device8 CKTS ? 8 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

4) 02-MDB-200 FOR GC-02, CRU S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

5) 09-MDB-100 FOR GC-09, CENTRALIZED S/S 1 SET V YES Confirmed

- 200A BUS 25KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 63A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 63A

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device6 CKTS ? 6 x 3POLE 50A

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

6) 09-MDB-200 FOR GC-10, CRU S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

7) 10-MDB-100 FOR GC-10, CENTRALIZED S/S 1 SET V YES Confirmed

- 200A BUS 25KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 63A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 63A

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device6 CKTS ? 6 x 3POLE 50A

  4POLE 32A FEEDER MCCB w/ Earth Fault ProtectionDevice

2 CKTS ? 2 x 3POLE 32A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

8) 10-MDB-200 FOR GC-10, CRU S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

9) 11-MDB-100 FOR GC-11, DESALTER S/S 1 SET V YES Confirmed

- 250A BUS 25KA sym. rms. V YES

4POLE 250A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 63A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 63A

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device9 CKTS ? 9 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

10) 11-MDB-200 FOR GC-11, CRU S/S 1 SET V YES Confirmed

Page 3: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 3/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHN

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device 5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

11) 19-MDB-100 FOR GC-19, DESALTER S/S 1 SET V YES Confirmed

- 200A BUS 25KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 63A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS  ? 1 x 3POLE 63A

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

12) 19-MDB-200 FOR GC-19, CRU S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & ControlCircuits

1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

13) 19-MDB-300 FOR GC-19, CONTROL BUILDING 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

14) 20-MDB-100 FOR GC-20, DESALTER S/S 1 SET V YES Confirmed

- 200A BUS 25KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device7 CKTS ? 7 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

15) 20-MDB-200 FOR GC-20, CRU S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

16) 22-MDB-100 FOR GC-22, DESALTER S/S 1 SET V YES Confirmed

- 200A BUS 25KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device9 CKTS ? 9 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

17) 22-MDB-200 FOR GC-22, CRU S/S 1 SET V YES Confirmed

- 100A BUS 25KA sym. rms. V YES

4POLE 100A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 50A FEEDER MCCB w/ Earth Fault Protection

Device5 CKTS ? 5 x 3POLE 50A

- DIMENSION B idder to Specify   V 1000W x 300D x 1700H

3) SMALL POWER DISTRIBUTION BOARD Confirmed1) 01-SDB-101 FOR GC-01, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 36 CKTS V YES

- DIMENSION B idder to Specify   ? 900W x 300D x 2150H

2) 01-SDB-102 FOR GC-01, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 48 CKTS V YES

- DIMENSION B idder to Specify   ? 1800W x 300D x 2150H

3) 01-SDB-201 FOR GC-01, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION B idder to Specify   ? 900W x 300D x 2150H

Page 4: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 4/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

5) 01-SDB-301 FOR GC-01, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 30mA RCD 6 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1000W x 300D x 1700H

6) 01-SDB-302 FOR GC-01, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

7) 02-SDB-101 FOR GC-02, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 36 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

8) 02-SDB-102 FOR GC-02, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 48 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1800W x 300D x 2150H

9) 02-SDB-201 FOR GC-02, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

10) 02-SDB-202 FOR GC-02, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

11) 02-SDB-301 FOR GC-02, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 30mA RCD 6 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1000W x 300D x 1700H

12) 02-SDB-302 FOR GC-02, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1200H

13) 09-SDB-101 FOR GC-09, CENTRALIZED S/S 1 SET V YES Confirmed

- 100A BUS 10KA sym. rms. V YES

4POLE 63A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

14) 09-SDB-102 FOR GC-09, CENTRALIZED S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 54 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1800W x 300D x 2150H

15) 09-SDB-201 FOR GC-09, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

Page 5: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 5/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

16) 09-SDB-202 FOR GC-09, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

17) 09-SDB-301 FOR GC-09, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device

2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 30mA RCD 6 CKTS  ? 5 x 2POLE 16A

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

18) 09-SDB-302 FOR GC-09, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1700H

19) 10-SDB-101 FOR GC-10, CENTRALIZED S/S 1 SET V YES Confirmed

- 100A BUS 10KA sym. rms. V YES

4POLE 63A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 38 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1800W x 300D x 2150H

20) 10-SDB-102 FOR GC-10, CENTRALIZED S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 54 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1800W x 300D x 2150H

21) 10-SDB-201 FOR GC-10, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

22) 10-SDB-202 FOR GC-10, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

23) 10-SDB-301 FOR GC-10, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 30mA RCD 6 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1000W x 300D x 1700H

24) 10-SDB-302 FOR GC-10, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

25) 11-SDB-101 FOR GC-11, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 40 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1800W x 300D x 2150H

26) 11-SDB-102 FOR GC-11, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

Page 6: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 6/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 48 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 1800W x 300D x 2150H

27) 11-SDB-201 FOR GC-11, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 900W x 300D x 2150H

28) 11-SDB-202 FOR GC-11, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 900W x 300D x 2150H

29) 11-SDB-301 FOR GC-11, EXTENDED CONTROL ROOM 1 SET V YES Confirmed- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 30mA RCD 6 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 1000W x 300D x 1700H

30) 11-SDB-302 FOR GC-11, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 12 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 900W x 300D x 1200H

31) 19-SDB-101 FOR GC-19, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 36 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 900W x 300D x 2150H

32) 19-SDB-102 FOR GC-19, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 48 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 1800W x 300D x 2150H

33) 19-SDB-201 FOR GC-19, CRU S/S 1 SET V YES Confirmed- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 900W x 300D x 2150H

34) 19-SDB-202 FOR GC-19, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 900W x 300D x 2150H

35) 19-SDB-301 FOR GC-19, CONTROL BUILDING 1 SET V YES Confirmed

- 200A BUS 10KA sym. rms. V YES

4POLE 200A INCOMER MCCB w/ Metering & Control

Circuits1 CKT V YES

  4POLE 63A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS  ? 1 x 3POLE 63A

2POLE 20A FEEDER MCB w/ 30mA RCD 8 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 40 CKTS V 41 x 2POLE 16A

- DIMENSION Bidder to Spec ify   ? 1800W x 300D x 2150H

36) 19-SDB-302 FOR GC-19, CONTROL BUILDING 1 SET V YES Confirmed

- 100A BUS 10KA sym. rms. V YES

4POLE 63A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 8 CKTS V YES2POLE 16A FEEDER MCB w/ 30mA RCD 28 CKTS V YES

- DIMENSION Bidder to Spec ify   ? 900W x 300D x 2150H

37) 20-SDB-101 FOR GC-20, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

Page 7: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 7/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

2POLE 16A FEEDER MCB w/ 30mA RCD 30 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 900W x 300D x 2150H

38) 20-SDB-102 FOR GC-20, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 48 CKTS V YES

- DIMENSION B idder to Spec i fy   V 1800W x 300D x 2150H

39) 20-SDB-201 FOR GC-20, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 900W x 300D x 2150H

40) 20-SDB-202 FOR GC-20, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 900W x 300D x 2150H

41) 20-SDB-301 FOR GC-20, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 900W x 300D x 2150H

42) 22-SDB-101 FOR GC-22, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 40 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 1800W x 300D x 2150H

43) 22-SDB-102 FOR GC-22, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 48 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 1800W x 300D x 2150H

44) 22-SDB-201 FOR GC-22, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 20 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 900W x 300D x 2150H

45) 22-SDB-202 FOR GC-22, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 30mA RCD 2 CKTS V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 34 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 900W x 300D x 2150H

46) 22-SDB-301 FOR GC-22, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 30mA RCD 6 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 1000W x 300D x 1700H

47) 22-SDB-302 FOR GC-22, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec i fy   ? 900W x 300D x 1500H

48) 01-SDB-103 FOR GC-01, DESALTER S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

- 50A BUS 10KA sym. rms.

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT

2POLE 16A FEEDER MCB w/ 30mA RCD 36 CKTS

- DIMENSION B idder to Spec i fy  

49) 02-SDB-103 FOR GC-02, DESALTER S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

Page 8: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 8/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

- 50A BUS 10KA sym. rms.

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT

2POLE 16A FEEDER MCB w/ 30mA RCD 36 CKTS

- DIMENSION B idder to Spec ify  

50) 09-SDB-103 FOR GC-09, CENTRALIZED S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

- 50A BUS 10KA sym. rms.

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT

2POLE 16A FEEDER MCB w/ 30mA RCD 36 CKTS

- DIMENSION B idder to Spec ify  

51) 10-SDB-103 FOR GC-10, CENTRALIZED S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 30mA RCD 36 CKTS V YES

- DIMENSION B idder to Spec ify  

53) 11-SDB-103 FOR GC-11, DESAL TER S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

- 50A BUS 10KA sym. rms.

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT

2POLE 16A FEEDER MCB w/ 30mA RCD 50 CKTS

- DIMENSION B idder to Spec ify  

54) 19-SDB-103 FOR GC-11, DESAL TER S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

- 50A BUS 10KA sym. rms.

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT

2POLE 16A FEEDER MCB w/ 30mA RCD 40 CKTS

- DIMENSION B idder to Spec ify  

55) 20-SDB-103 FOR GC-20, DESAL TER S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

- 50A BUS 10KA sym. rms.

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT

2POLE 16A FEEDER MCB w/ 30mA RCD 24 CKTS

- DIMENSION B idder to Spec ify  

56) 22-SDB-103 FOR GC-22, DESAL TER S/S  1 SET AS ADDITIONAL ? NOT QUOTED To submit relevant quotation

- 50A BUS 10KA sym. rms.

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT

2POLE 16A FEEDER MCB w/ 30mA RCD 50 CKTS

- DIMENSION B idder to Spec ify  

4) LIGHTING DISTRIBUTION BOARD

1) 01-LDB-101 FOR GC-01, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 15 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

2) 01-LDB-102 FOR GC-01, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w / Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 12 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 5 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1700H

3) 01-LDB-201 FOR GC-01, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

4) 01-LDB-202 FOR GC-01, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w / Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

Page 9: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 9/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 3 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

5) 01-LDB-301 FOR GC-01, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1000W x 300D x 1700H

6) 01-LDB-302 FOR GC-01, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

7) 02-LDB-101 FOR GC-02, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 15 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1700H

8) 02-LDB-102 FOR GC-02, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w / Internal ci rcui ts for 2P 16A MCB 

feeders  1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 14 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 5 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

9) 02-LDB-201 FOR GC-02, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

10) 02-LDB-202 FOR GC-02, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 3 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

11) 02-LDB-301 FOR GC-02, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 300mA RCD 8 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1000W x 300D x 1700H

12) 02-LDB-302 FOR GC-02, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

13) 09-LDB-101 FOR GC-09, CENTRALIZED S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 32 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

14) 09-LDB-102 FOR GC-09, CENTRALIZED S/S 1 SET V YES Confirmed

- 100A BUS 10KA sym. rms. V YES

4POLE 63A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w / Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 63A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

Page 10: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 10/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

2POLE 20A FEEDER MCB w/ 300mA RCD 12 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

15) 09-LDB-201 FOR GC-09, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

16) 09-LDB-202 FOR GC-09, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w / Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 3 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

17) 09-LDB-401FOR GC-09, GENERATOR HOUSE  1 SET V YES Confirmed, but to change tag no.

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

18) 09-LDB-301 FOR GC-09, EXTENDED CONTROL ROOM  1 SET V YES Confirmed, but to change tag no.

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 300mA RCD 8 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1000W x 300D x 1700H

19) 09-LDB-302 FOR GC-09, EXTENDED CONTROL ROOM  1 SET V YES Confirmed, but to change tag no.

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

20) 10-LDB-101 FOR GC-10, CENTRALIZED S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 32 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

21) 10-LDB-102 FOR GC-10, CENTRALIZED S/S 1 SET V YES Confirmed

- 100A BUS 10KA sym. rms. V YES

4POLE 63A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w / Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 63A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 12 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 12 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

22) 10-LDB-201 FOR GC-10, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

23) 10-LDB-202 FOR GC-10, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w / Internal ci rcui ts for 2P 16A MCB 

feeders 

1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 3 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

24) 10-LDB-401 FOR GC-10, GENERATOR HOUSE 1 SET V YES Confirmed, but to change tag no.

Page 11: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 11/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

25) 10-LDB-301 FOR GC-10, EXTENDED CONTROL ROOM  1 SET V YES Confirmed, but to change tag no.

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 300mA RCD 8 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1700H

26) 10-LDB-302 FOR GC-10, EXTENDED CONTROL ROOM  1 SET V YES Confirmed, but to change tag no.

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

27) 11-LDB-101 FOR GC-11, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 15 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

28) 11-LDB-102 FOR GC-11, DESALTER S/S 1 SET V YES Confirmed

- 100A BUS 10KA sym. rms. V YES

4POLE 63A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 63A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

29) 11-LDB-201 FOR GC-11, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H30) 11-LDB-202 FOR GC-11, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 3 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

31) 11-LDB-301 FOR GC-11, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 300mA RCD 8 CKTS V YES

- DIMENSION B idder to Spec ify   ? 1000W x 300D x 1700H

32) 11-LDB-302 FOR GC-11, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

33) 19-LDB-101 FOR GC-19, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 15 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

34) 19-LDB-102 FOR GC-19, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

Page 12: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 12/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNI

SMALL POWER & LIG

GENERA

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

4POLE 63A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders  1 SET  ? NOT SHOWN 

3POLE 63A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 17 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 5 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

35) 19-LDB-201 FOR GC-19, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

36) 19-LDB-202 FOR GC-19, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 3 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

37) 19-LDB-301 FOR GC-19, CONTROL BUILDING 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 30 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

38) 19-LDB-302 FOR GC-19, CONTROL BUILDING 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 26 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 2150H

39) 19-LDB-303 FOR GC-19, CONTROL BUILDING 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 6 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H

40) 20-LDB-101 FOR GC-20, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 15 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1700H

41) 20-LDB-102 FOR GC-20, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 5 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1700H

42) 20-LDB-201 FOR GC-20, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Spec ify   ? 900W x 300D x 1500H43) 20-LDB-202 FOR GC-20, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders1 SET  ? NOT SHOWN 

Page 13: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 13/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNIC

SMALL POWER & LIG

GENERAL

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 3 CKTS V YES

- DIMENSION B idder to Speci fy   ? 900W x 300D x 1500H

44) 20-LDB-301 FOR GC-20, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 15 CKTS V YES

- DIMENSION B idder to Speci fy   ? 900W x 300D x 1700H

45) 22-LDB-101 FOR GC-22, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 15 CKTS V YES

- DIMENSION B idder to Speci fy   ? 900W x 300D x 1700H46) 22-LDB-102 FOR GC-22, DESALTER S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

3POLE 16A MCB w/ Internal ci rcui ts for 2P 16A MCB 

feeders 1 SET  ? NOT SHOWN 

3POLE 50A Contactor Switch w/ Photo-cell Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 5 CKTS V YES

- DIMENSION B idder to Speci fy   ? 900W x 300D x 1700H

47) 22-LDB-201 FOR GC-22, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 11 CKTS V YES

- DIMENSION B idder to Speci fy   ? 900W x 300D x 1500H

48) 22-LDB-202 FOR GC-22, CRU S/S 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 20A FEEDER MCB w/ 300mA RCD & Contactor 

Switch7 CKTS V YES

2POLE 16A FEEDER MCB w/ 300mA RCD & Contactor 

Switch3 CKTS V YES

- DIMENSION B idder to Speci fy   ? 900W x 300D x 1500H

49) 22-LDB-301 FOR GC-22, EXTENDED CONTROL ROOM 1 SET V YES Confirmed- 50A BUS 10KA sym. rms. V YES

4POLE 50A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

  4POLE 32A FEEDER MCCB w/ Earth Fault Protection

Device2 CKTS ? 2 x 3POLE 32A

2POLE 16A FEEDER MCB w/ 300mA RCD 8 CKTS V YES

- DIMENSION B idder to Speci fy   ? 1000W x 300D x 1700H

50) 22-LDB-302 FOR GC-22, EXTENDED CONTROL ROOM 1 SET V YES Confirmed

- 50A BUS 10KA sym. rms. V YES

4POLE 32A INCOMER MCCB w/ Metering & Control Circuits 1 CKT V YES

2POLE 16A FEEDER MCB w/ 300mA RCD 9 CKTS V YES

- DIMENSION B idder to Speci fy   ? 900W x 300D x 1500H

5 Spare Parts

1) For Construction 1 Lot V YES Confirmed

2) For Commissioning & Start-up 1 Lot ? Not shown To confirm

3) For One(1) year Operation 1 Lot(Priced list only) V YES Confirmed

6 Factory Test 1 Lot V YES Confirmed

3 SCOPE OF WORK

1) Design including Calculation Required ? To confirm

2) Manufacturing Required ? To confirm

3) Painting (including Finish) Required ? To confirm

Page 14: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 14/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNICA

SMALL POWER & LIGH

GENERAL

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

4) Protection & Packing as per KOC-G-004 Required ? To confirm

5) Transportation (Inland to the designated location) Required ? To confirm

6) Shop Test & Inspection (FAT) Required ? To confirm

7) Supervision for Construction Required(Optional Bid) ? To confirm

8) Site Test(SAT), Commissioning, Start-up Required(Optional Bid) ? To confirm

9) Training for KOC personnel in Kuwait Required(Optional Bid) ? To confirm

10) Application of Local Regulation in design Required ? To confirm

11) Performance Guarantee Required ? To confirm

12) Documentation as per 'Vendor Data Requirements' Required ? To confirm

4 ENGINEERING NOTES

1.0 GENERAL

Clause 1.1 Bidder to comply ? To confirm

Clause 1.2 Bidder to comply ?To submit deviation list with reasons if there are

any deviated items.

Clause 1.3 Bidder to comply ? To confirm

Clause 1.4 Bidder to comply ? To confirm

Clause 1.5 Bidder to comply ? To confirm

Clause 1.6 Bidder to comply ? To confirm

Clause 1.7 Bidder to comply ? To confirm

Clause 1.8 Bidder to comply ? To confirm

Clause 1.9 Bidder to comply ? To confirm

Clause 1.10 Bidder to comply ? To submit the statement

2.0 APPLICABLE CODES, STANDARDS &

SPECIFICATION

Clause 2.1 Bidder to comply ? To confirm

Clause 2.2 Bidder to comply ? To confirm

Clause 2.3 Bidder to comply ? To confirm

Clause 2.4 Bidder to comply ? To confirm

Clause 2.5 Bidder to comply ? To confirm

Clause 2.6 Bidder to comply ?To submit deviation list with reasons if there are

any deviated items.

3.0 SCOPE OF SUPPLY/WORKS ?

Clause 3.1 Bidder to comply ? To confirm

Clause 3.2 Bidder to comply ? To confirm

Clause 3.3 Bidder to comply ? To confirm

Clause 3.4 Bidder to comply ? To confirm

Clause 3.5 Bidder to comply ? To confirm

Clause 3.6 Bidder to comply ? To confirm

Clause 3.7 Bidder to comply V YES confirmed

Clause 3.8 Bidder to comply ? To confirm

Clause 3.9 Bidder to comply V YES confirmed

Clause 3.10 Bidder to comply V YES confirmed

Clause 3.11 Bidder to comply ? To confirm

Clause 3.12 Bidder to comply ? To confirm

Clause 3.13 Bidder to comply ? To confirm

4.0 DESIGN CONSIDERATION

Clause 4.1 Bidder to comply ? To confirm

Clause 4.2 Bidder to comply ? To confirm

Clause 4.3 Bidder to comply ? To confirm

LEGEND

Page 15: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 15/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNICA

SMALL POWER & LIGH

GENERAL

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

Clause 4.4 Bidder to comply ? To confirm

Clause 4.5 Bidder to comply ? To confirm

5.0 QA/QC REQUIREMENT ?

Clause 5.1 Bidder to comply ? To confirm

Clause 5.2 Bidder to comply ? To confirm

Clause 5.3 Bidder to comply ? To confirm

Clause 5.4 Bidder to comply ? To confirm

Clause 5.5 Bidder to comply ? To confirm

Clause 5.6 Bidder to comply ? To confirm

Clause 5.7 Bidder to comply ? To confirm

Clause 5.8 Bidder to comply ? To confirm

Clause 5.9 Bidder to comply ? To confirm

Clause 5.10 Bidder to comply ? To confirm

6.0 TECHNICAL DOCUMENTS TO BE SUBMITTED

WITH BID

Clause 6.1Bidder to submit with this

ClarificationV YES confirmed

Clause 6.2Bidder to submit with this

ClarificationV YES confirmed

Clause 6.3Bidder to submit with this

Clarification? To submit

Clause 6.4Bidder to submit with this

ClarificationV YES confirmed

Clause 6.5 Bidder to submit with thisClarification

? YES, but partially submitted To submit all relevant purchaser DATA sheets withcomplete data

Clause 6.6Bidder to submit with this

Clarification? To submit all SLDs for relevant boards

Clause 6.7Bidder to submit with this

Clarification? To submit all DWGs for relevant boards

Clause 6.8Bidder to submit with this

Clarification? To submit all DWGs for relevant boards

Clause 6.9Bidder to submit with this

ClarificationV YES confirmed

Clause 6.10Bidder to submit with this

Clarification? To submit

Clause 6.11 Bidder to submit with thisClarification ? To submit deviation list with reasons if there areany deviated items.

Clause 6.12Bidder to submit with this

Clarification? To submit

Clause 6.13Bidder to submit with this

Clarification? To submit

7.0 MANUFACTURING RECORD BOOKS(MRB)

Clause 7.1 Bidder to comply ? To confirm

Clause 7.2 Bidder to comply ? To confirm

Clause 7.3 Bidder to comply ? To confirm

Clause 7.4 Bidder to comply ? To confirm

5 VENDOR DATA REQUIREMENTS

 A1) Vendor Document Index Bidder to comply ? To confirm

 A2) Vendor Document Submittal Schedule Bidder to comply ? To confirm

 A3) Manufacturing Schedule Bidder to comply ? To confirm

 A4) Progress Report Bidder to comply ? To confirm

 A5) Organization Chart Bidder to comply ? To confirm

 A6) Sub-Vendor ListBidder to submit with this

ClarificationV confirmed

 A7) Deviation List, If anyBidder to submit with this

Clarification?

To submit deviation list with reasons if there are

any deviated items.

LEGEND

Page 16: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 16/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNIC

SMALL POWER & LIGH

GENERAL

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

B1) Packing, Knockdown & Transportation Procedure Bidder to comply ? To confirm

B2) Shipping Schedule and Packing List Bidder to comply ? To confirm

B3) Weight List / Unit Shipping WeightBidder to submit with this

Clarification? To submit

C1) Recommended Spare Parts List for ConstructionBidder to submit with this

ClarificationV confirmed

C2) Recommended Spare Parts List for Commissioning & Start-

up

Bidder to submit with this

Clarification? To confirm

C3) Recommended Spare Parts List for One(1) year Operation

With Price

Bidder to submit with this

Clarification (Priced List only)V confirmed

C4) Special Tool List Bidder to submit with thisClarification

V confirmed

D1) Equipment SpecificationsBidder to submit with this

ClarificationV confirmed

D2) Complete Equipment Data SheetsBidder to submit with this

Clarification? YES, but partially submitted

To submit all relevant purchaser DATA sheets with

complete data

D3) Single Line DiagramBidder to submit with this

Clarification? To submit

D4) Schematic Wiring Diagram Bidder to comply ? To confirm

D5) Terminal Arrangements and Numbering Bidder to comply ? To confirm

D6) Vendor Calculation SheetBidder to submit with this

Clarification? To submit, if necessary

D7) General Arrangement DrawingsBidder to submit with this

Clarification? To submit

D8) Dimensional Outline DrawingsBidder to submit with this

Clarification? To submit

D9) Foundation plan including anchor bolt locationBidder to submit with this

Clarification? To submit

D10) Detailed Parts List Bidder to comply ? To confirm

D11) Component Detail Drawings Bidder to comply ? To confirm

D12) Fuse and Circuit Breaker Discrimination CurvesBidder to submit with this

Clarification? To submit

D13) Name Plate Details Bidder to comply ? To confirm

D14) Certificate of guarantee Bidder to comply ? To confirm

D15) Catalogue, Information, etc.Bidder to submit with this

Clarification? To submit

D16) Utility Consumption List (If Required)Bidder to submit with this

Clarification? To submit

D17) Paint Specification Bidder to comply ? To confirm

E1) Installation and Commissioning Instructions Bidder to comply ? To confirm

E2) Operation and Maintenance Manual Bidder to comply ? To confirm

E3) Maintenance Schedule for Two(3) year Operation Bidder to comply ? To confirm

E4) Certificate of Type Tests Bidder to comply ? To confirm

E5) Inspection & Test Procedure Bidder to comply ? To confirm

E6) Quality Plan Bidder to comply ? To confirm

E7) Inspection & Test Plan Bidder to comply ? To confirm

E8) Inspection & Test Report Bidder to comply ? To confirm

E9) Details of previous order executed Bidder to comply ? To confirm

E10) Compliance StatementBidder to submit with this

Clarification? To submit

E11) Manufacturing Record Book(AS-BUILT) Bidder to comply ? To confirm

6 DATA SHEETS FOR ALL DISTRIBUTION BOARDS

1)26422-01U-EA-E-0601 ~ 26422-22U-EA-E-0601

MOV POWER DIST. BOARDS FOR GC-01 ~ GC-22

Bidder to comply according to

DATA sheets? To confirm

2)26422-01U-EA-E-0611 ~ 26422-22U-EA-E-0612

MAIN LIGHTING DIST. BOARDS FOR GC-01 ~ GC-22

Bidder to comply according to

DATA sheets? To confirm

3)26422-01U-EA-E-0621 ~ 26422-22U-EA-E-0627

SMALL POWER DIST. BOARDS FOR GC-01 ~ GC-22

Bidder to comply according to

DATA sheets? To confirm

Page 17: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 17/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNICA

SMALL POWER & LIGHT

GENERAL P

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION

4)26422-01U-EA-E-0631 ~ 26422-22U-EA-E-0636

LIGHTING DIST. BOARDS FOR GC-01 ~ GC-22

Bidder to comply according to

DATA sheets? To confirm V

7 TECHNICAL SPECIFICATIONS

1)SPC-1501-EE-03

Distribution Board

1.0 SCOPE Bidder to comply ? To confirm V

2.0 APPLICATION AND STANDARDS

Clause 2.1 Bidder to comply ? To confirm V

3.0 SERVICE CONDITION

Clause 3.1 Bidder to comply ?To confirm to consider 50 oC ambient temperature

conditionV

Clause 3.2 Bidder to comply ? To confirm V

Clause 3.3 Bidder to comply ? To confirm V

Clause 3.4 Bidder to comply ?To confirm to consider derating factor for 50o C

ambient temperature conditionV

Clause 3.5 Bidder to comply ? To confirm V

Clause 3.6 Bidder to comply ?To submit deviation list with reasons if there are

any deviated items.V

Clause 3.7 Bidder to comply ? To confirm V

4.0 ENCLOSURE

Clause 4.1 Bidder to comply ? To confirm V

Clause 4.2 Bidder to comply ? To confirm V

Clause 4.3 Bidder to comply ? To confirm V

Clause 4.4 Bidder to comply ? To confirm V

Clause 4.5 Bidder to comply ? To confirm V

Clause 4.6 Bidder to comply ? To confirm V

Clause 4.7 Bidder to comply ? To confirm V

Clause 4.8 Bidder to comply ? To confirm V

5.0 TECHNICAL REQUIREMENTS

Clause 5.1 Incomer 

Clause 5.1.1 Bidder to comply ? To confirm V

Clause 5.1.2 Bidder to comply ? To confirm V

Clause 5.2 Busbars

Clause 5.2.1 Bidder to comply ? To confirm V

Clause 5.2.2 Bidder to comply ? To confirm V

Clause 5.3 Distribution Circuits

Clause 5.3.1 Bidder to comply ? To confirm V

Clause 5.3.2 Bidder to comply ?

To confirm and submit technical Data including

catalogue for earth fault protection device of 

MCCB circuit

V

Clause 5.3.3 Bidder to comply ?

To confirm and submit technical Data including

catalogue for 30mA and 300mA earth leakage

protection device of MCB circuit

V

Clause 5.3.4 Bidder to comply ? To confirm V

Clause 5.4 Contactor

Clause 5.4.1 Bidder to comply ? To confirm V

Clause 5.4.2 Bidder to comply ? To confirm V

Clause 5.4.3 Bidder to comply ? To confirm V

Clause 5.4.4 Bidder to comply ? To confirm V

Clause 5.4.6 Bidder to comply ? To confirm V

Clause 5.6 Wiring/Terminals

Clause 5.6.1 Bidder to comply ? To confirm V

Clause 5.6.2 Bidder to comply ? To confirm V

6.0 PAINTING

Clause 6.1 Bidder to comply ? To confirm V

LEGEND

Page 18: 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

7/29/2019 2nd Technical Clarifications_AL_AHLEIA_2006_01_25 ASC REPLY.xls

http://slidepdf.com/reader/full/2nd-technical-clarificationsalahleia20060125-asc-replyxls 18/18

Pjt Name : Facility Upgrade Relocation of U/G Process Piping2nd TECHNICAL CL

SMALL POWER & LIGHTING D

GENERAL PURP

1st Technical Clarification

by Purchaser(2006_01_13)NO. DESCRIPTION REQUIREMENTS Bidder's QUOTATION B

Clause 6.2 Bidder to comply ? To confirm V

7.0 LABELS

Clause 7.1 Bidder to comply ? To confirm V

Clause 7.2 Bidder to comply ? To confirm V

Clause 7.3 Bidder to comply ? To confirm V

Clause 7.4 Bidder to comply ? To confirm V

Clause 7.5 Bidder to comply ? To confirm V

8.0 INSPECTION AND TESTING

Clause 8.1 Bidder to comply ? To confirm V

Clause 8.2 Bidder to comply ? To confirm V

Clause 8.3 Bidder to comply ? To confirm V

Clause 8.4 Bidder to comply ? To confirm V

9.0 DOCUMENTATION

Clause 9.1 Bidder to comply ? To confirm and submit relevant documents V

Clause 9.2 Bidder to comply ? To confirm V

Clause 9.3 Bidder to comply ? To confirm V

10.0 ATTACHEMENTS

Clause 10.1 Bidder to comply ? YES, but partially submittedTo submit all relevant purchaser DATA sheets with

complete dataV

2)KOC-G-004

Packing, Marking and DocumentationBidder to comply ? To confirm V

3)KOC-G-007

Basic Design DataBidder to comply ? To confirm V

5) KOC-P-001Paining and Coating

Bidder to comply ? To confirm V

8 QA/QC SPECIFICATIONS

1)26422-SIP-EL-6004

Source Inspection PlanBidder to comply ? To confirm V

2)

26422-PR-0002

QA/QC, Shop Inspection & Test Requirements for 

Procured Equipment & Materials

Bidder to comply ? To confirm V

3)

26422-EN-0001

Instruction for Vendor Document Preparation, Submittal,

Review and Approval

Bidder to comply ? To confirm V