SIZE: DRAWN BY: TITLE: MC-25 WITH RECEIVER, ELECTRIC STRIKE, PUSHPLATE, LOW ENERGY AUTOMATIC DOOR APPLICATION A 100 ENTERPRISE DRIVE PITTSBURGH, PA 15275 PHONE: (412) 249-4100 FAX: (412) 249-4101 EMAIL: www.beasensors.com REV BY: KJG JEG 80.0011.02 SCALE: DATE: NONE 24 APR 2005 PART NO: SHEET 1 OF 1 NOTE: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #1. 2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT. 3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMINED BY CURRENT DRAW OF ELECTRIC STRIKE. GRAY 6 5 4 3 2 1 MC-25 RELAY 1 RELAY 2 RED COMMON COM N/O BLACK RED GREEN WHITE POWER 24 VAC POWER 24 VAC N / O COMMON AUTOMATIC DOOR CONTROL ACT - + DC-ELECTRIC STRIKE BRIDGE RECTIFIER ~ ~ + - IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC. FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS, CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOT LEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM 24 V TRANSFORMER

24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

Embed Size (px)

Citation preview

Page 1: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH RECEIVER, ELECTRICSTRIKE, PUSHPLATE, LOW ENERGYAUTOMATIC DOOR APPLICATION

A

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG JEG 80.0011.02SCALE: DATE:NONE 24 APR 2005

PART NO:

SHEET1 OF 1

NOTE: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #1.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMINED BY CURRENT DRAW OF

ELECTRIC STRIKE.

GRAY654

321

MC-25RELAY 1

RELAY 2

RED COMMON

COMN/O

BLACK

RED

GREEN

WHITE

POWER 24 VACPOWER 24 VAC

N / OCOMMON

AUTOMATICDOOR CONTROL

ACT

- +

DC-ELECTRICSTRIKE

BRIDGERECTIFIER

~~

+-

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

24 V TRANSFORMER

Page 2: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

DWG NO SIZE

SHEET SCALE

CAGE CODE

PH: (412) 249-4100 FAX: (412) 249-4101

B.E.A., Inc.100 Enterprise Drive, Pittsburgh, PA 15275

DATE:

ENG'GFILE OF: DRAWN BY: REV

01

24 VAC

MC-25 #1

PUSHPLATE

DOOR CONTROLWITH ELECTRIC STRIKE

ELECTRICSTRIKE

RECTIFIER

ISO24RELAY

DOOR CONROL WITH AUTOMATIC FLUSH BOLTS

110 VAC

brown

orange

jumpers on 1&2/ 4&5 dry

input from N.O.ISO Relay

MC-25 #2

RELAY #1 RELAY #2NO Com NCNO Com NC

RELAY #2NO Com NC

RELAY #1NO Com NC

jumpers on 2&3/ 5&6 dry

input frompushplate

black

red

blue

yellow

greygrey

brown

orange

blue

yellow

~ ~

+ -

ACT COM SAf.

24Vcoil

ACT COM SAf.

TITLE: DUAL MC-25's. Pair of doors w/Electric Strike in the active leaf and automatic flush bolts in the active leaf.

We open up New Horizons

JED80.0012A

02 JAN 04 1 OF 1NONE

Page 3: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

DWG NO SIZE

SHEET SCALE

CAGE CODE

A

PH: (412) 249-4100 FAX: (412) 249-4101

B.E.A., Inc.100 Enterprise Drive, Pittsburgh, PA 15275

DATE:

FILE OF: DRAWN BY: REV

TITLE: PAIR OF DOORS WITH MC25, ELECTRIC STRIKE AND MANUAL FLUSH BOLTS

PUSHPLATE

MC25 #2DRY CONTACT

LO-21SLOCK OUTRELAY

DOOR CONTROL

#1

ISO24RELAY

MC25#1WET

CONTACTS ELECTRIC

STRIKE

MOTOR

DOORCONTROL

#2

DOORCONTROL

#1

24VACTRANSFORMER

110 VAC

yell

ow

graygray

orangebrown

DK-12/ BODYGUARD

COMSAFETY

24VAC

data + 7data - 6

NC 5NO 4

COM 3PWR 2PWR 1

ACTIVE

ACTIVE

COMMON

red

black

COMMON

red/ whitewhite

blue

gray

gray

green

brownorange

green

gray

yell

owbl

ue

orange

brown black

red

5 6

7

ACTIVE

MOTOR {

8 3 4

NONE 1 OF 1

We open up New Horizons

red +

blac

k -

-+

02 JAN 04

80.0014 ENG'G JED 01

Page 4: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

PH: (412) 249-4100 FAX: (412) 249-4101100 Enterprise Drive, Pittsburgh, PA 15275

DATE: SHEET:SCALE:A

REV:DRAWN BY:SIZE: CAGE CODE: DWG NO: FILE OF:

B.E.A., Inc.

ENG'G JED80.0015 01

1 OF 1NONE 02 JAN 04

purple (N/C)

red (COM)

RELAY 2

RELAY 1

Activation

blue

yellow

DOORCONTROL

MAGLOCK

+ -

DOOR POSITION SWITCH

BRIDGERECTIFIER

24 V TRANSFORMER115 VAC

orange

brown

PUSHPLATE

COMMON gray

CARDREADER

COMMON

N/O

OPTIONAL

N/O gray

Common

TITLE: MC-25 WITH SAME POWER SUPPLY FOR MAGLOCK

NOTES: 1) JUMPERS JP1 & JP2 ARE PLACED ON PINS 2,3 AND 5,6 FOR WET CONTACTS. 2) DOOR POSITION SWITCH CONTACTS CLOSED WHEN DOOR IS CLOSED. 3) TRANSFORMER AND BRIDGE RECTIFIER CURRENT RATING MUST BE SUFFICIENT TO SUPPORT MC-25 AND MAGLOCK. 4) BRIDGE RECTIFIER SUPPLIED BY OTHERS.

MC-25

JP1

JP2

321

654

We open up New Horizons

Page 5: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

A FILE OF: DRAWN BY:

1 OF 1NTS

CAGE CODE: DWG NO: REV:SIZE:

SHEET:SCALE: DATE:

NOTES: 1) JUMPERS JP1 & JP2 ARE PLACED ON PINS 1,2 AND 4,5 FOR DRY CONTACTS. 2) BRIDGE RECTIFIER SUPPLIED BY OTHERS.

80.0017 JED 01

02 JAN 04

TITLE: MC-25 WITH SEPERATE POWER SUPPLY FOR MAGLOCK

ENG'G

purple (N/C)

red (COM)

RELAY 2

RELAY 1

Activation

blue

yellow

DOORCONTROL

MAGLOCK

+ -

BRIDGERECTIFIER

24 V TRANSFORMER115 VAC

orange

brown

PUSHPLATE

COMMON gray

CARDREADER

COMMON

N/O

OPTIONAL

N/O gray

Common

MC-25

JP1

JP2

321

654

EXTERNAL POWERSUPPLY

We open up New Horizons

PH: (412) 249-4100 FAX: (412) 249-4101

B.E.A., Inc.100 Enterprise Drive Pittsburgh, PA 15275

Page 6: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 w/ SARGENT EL PANICDEVICE & AUTOMATIC DOOR OPERATOR

A

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG KJG 80.0018.02SCALE: DATE:NONE 17 MAY 2005

PART NO:

SHEET1 OF 1

COMDOOR

CONTROLACT

RED COMMONBLACK N/O

COMN/O

24 V TRANSFORMER

SARGENTPOWER SUPPLY

120VAC GND

* N.C. = CONTACT CLOSEDWHEN RELAY NOT POWERED

SARGENTPANIC

DEVICE

+24VDC

-24VDC

RELAY24VAC

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 7: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH ELECTRIC STRIKE,APT. BUZZER RELAY/ FIRE ALARM

A

NOTES: 1) JUMPERS JP1,JP2 ARE PLACED ON PINS 1,2 AND 4,5 FOR DRY CONTACTS ON RELAY OUTPUT #2.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMINED BY CURRENT

DRAW OF ELECTRIC STRIKE.4) BRIDGE RECTIFIER SUPPLIED BY OTHERS.

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG KJG 80.0019.02SCALE: DATE:NONE 18 MAY 2005

PART NO:

SHEET1 OF 1

COMDOOR

CONTROLACT

RED COMMONBLACK N/O

24 V TRANSFORMER

COMN/O

COMN/O

OPTIONAL

BRIDGERECTIFIER

~~

+ -

-+

D/C ELECTRICSTRIKE

VOLTAGE FORRELAY FROM

EXISTING APT.BUZZER OR FIREALARM SYSTEM

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 8: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH RECEIVERS, SEPARATEPOWER SUPPLY FOR MAGLOCK,NIGHT MODE RELAY

A

NOTES: 1) JUMPERS JP1 & JP2 ARE PLACED ON PINS 1,2 AND 4,5 FOR DRY CONTACTS.2) TYPE OF RELAY WILL BE DETERMINED BY MAGLOCK VOLTAGE (12 OR 24 VOLTS).

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG KJG 80.0020.02SCALE: DATE:NONE 18 MAY 2005

PART NO:

SHEET1 OF 1

COMDOOR

CONTROLACT

RED COMMONBLACK N/O

24 V TRANSFORMER

COMPUTER SYSTEMPOWER SUPPLY

MAGLOCK

WHITEGREENBLACKREDPOWER 24 VAC

POWER 24 VACN / O

COMMON

WHITEGREENBLACKREDPOWER 24 VAC

POWER 24 VACN / O

COMMON

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 9: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH ELECTRIC STRIKE,AUTOMATIC DOOR APPLICATION

A

NOTES: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #2.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER VOLT/ AMPERE RATING IS DETERMINED BY CURRENT DRAW OF ELECTRIC STRIKE.

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG KJG 80.0022.02SCALE: DATE:NONE 19 MAY 2005

PART NO:

SHEET1 OF 1

COMDOOR

CONTROLACT

RED COMMONBLACK N/O

24 V TRANSFORMER

COMN/O

COMN/O

OPTIONAL

BRIDGERECTIFIER

~~

- +

- +

D/C ELECTRICSTRIKE

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 10: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

DWG NO SIZE

SHEET SCALE

CAGE CODE

PH: (412)782-4100 FAX: (412) 249-4101

B.E.A., Inc.100 Enterprise Drive, Pittsburgh, PA 15275

DATE:NONE

FILE OF: DRAWN BY: REV

MC25 #2

TRANSFORMER

KM 2000DOOR

CONTROL

ACTIVATION

com n/o

red

black

gray

gray

orange

brown

red

blue

yellow

black

120 VACDOOR #2MOTOR

blue

yell

ow

oran

ge

whit

e

RECTIFIER

ISO24VACCOIL

DRYCONTACT

MOTOR #2

DOOR #1

1.5sec DELAY

0.5sec DELAY

~

~ -

+ ELECTRICSTRIKE

gray

gray

MC25 #1 WETCONTACT

TITLE: DOOR PROS WITH 2 MC-25's

oran

ge

brow

n

24VAC

ENG'G

1 OF 102 JAN 04

80.0023

We open up New Horizons

A JED 01

Page 11: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH 3 WIRE RECEIVER,ELECTRIC STRIKE, PUSHPLATEAUTOMATIC DOOR APPLICATION

A

NOTES: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #2.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMIND BY CURRENT DRAW OF

ELECTRIC STRIKE.

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG TUC 80.0135.02SCALE: DATE:NONE 23 NOV 2005

PART NO:

SHEET1 OF 1

BLACK

PURPLE

RED

24 V TRANSFORMER

RELAY

GRAY

GRAYCOMN/O

PUSH TOOPEN

* N.C. = CONTACT CLOSEDWHEN RELAY NOT POWERED

N / O 2

COMMON 3

POWER 1

ACTIVATE

COMMON BRIDGERECTIFIER

~~

+ -

D/C ELECTRICSTRIKE

+ -

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 12: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH RECEIVER, ELECTRICSTRIKE, PUSHPLATE AUTOMATICDOOR APPLICATION

A

NOTES: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #2.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMIND BY CURRENT DRAW

OF ELECTRIC STRIKE.

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG TUC 80.0138.02SCALE: DATE:NONE 23 NOV 2005

PART NO:

SHEET1 OF 1

BLACK

PURPLE

RED

24 V TRANSFORMER

GRAY

GRAYCOMN/O

PUSH TOOPEN

ACTIVATE

COMMON BRIDGERECTIFIER

~~

+-

D/C ELECTRICSTRIKE

+-

BLACKRED

GREENWHITE

POWER 24 VACPOWER 24 VAC

N / OCOMMON

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 13: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH RECEIVER, MAGNETICLOCK, PUSHPLATE AUTOMATICDOOR APPLICATION

A

NOTES: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #1.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMIND BY CURRENT DRAW OF

MAGNETIC LOCK.

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG KJG 80.0140.02SCALE: DATE:NONE 15 NOV 2005

PART NO:

SHEET1 OF 1

BLACK

PURPLE

RED

24 V TRANSFORMER

GRAY

GRAYCOMN/O

PUSH TOOPEN

ACTIVATE

COMMON BRIDGERECTIFIER

~~

+-

BLACKRED

GREENWHITE

POWER 24 VACPOWER 24 VAC

N / OCOMMON

MAGLOCK

COMMON

N/O

OPTIONAL

NIGHT MODEKEY SWITCH

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 14: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: MC-25 WITH ELECTRIC PANIC,PUSHPLATE AUTOMATIC DOORAPPLICATION

A

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG JDC 80.0142.02SCALE: DATE:NONE 20 MARCH 2006

PART NO:

SHEET1 OF 1

NOTES: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #1.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER AND BRIDGE RECTIFIER VOLT/ AMPERE RATING IS DETERMIND BY CURRENT DRAW OF

ELECTRIC PANIC.4) MAGNETIC REED SWITCH MUST BE CLOSED WHILE DOOR IS OPEN.5) SET MC-10 TIME DELAY FOR THE LENGTH OF TIME TO KEEP PANIC UNLOCKED ONCE CLOSED. IF PANIC CURRENT

LOAD IS GREATER THAN 500 mA, AN AUXILLARY RELAY MUST BE USED. PLEASE CONTACT BEA TECHNICALSERVICES FOR MORE INFORMATION.

24 V TRANSFORMER

COMN/O

PUSH TOOPEN

BLACK

PURPLE

RED

GRAY

GRAY

ACTIVATE

COMMON BRIDGERECTIFIER

~~

+-

+-

BLACK

PURPLE

RED

PANICHARDWARE

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

Page 15: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

TITLE: 2 MC-25s WITH ELECTRIC STRIKE,SEQUENCING 2 DOOR PANELS

A

NOTES: 1) JUMPERS ARE PLACED ON J1 PINS 1&2, J2 PINS 4&5 FOR DRY CONTACTS ON RELAY OUTPUT #1.2) PUSH PLATE, MOTION SENSOR, CARD READER MUST BE DRY CONTACT.3) TRANSFORMER VOLT/ AMPERE RATING IS DETERMIND BY CURRENT DRAW OF ELECTRIC STRIKE.

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG KJG 80.0147.02SCALE: DATE:NONE 16 NOV 2005

PART NO:

SHEET1 OF 1

24 V TRANSFORMER

ACTIVATE

COMMON

ACTIVATE

COMMONBLACK

PURPLE

RED

GRAY

GRAY

BLACK

PURPLE

RED

GRAY

GRAYCOMN/O

PUSH TOOPEN

COMMON

N/O

OPTIONAL

A/C ELECTRICSTRIKE

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC.FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIME AT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS,CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOTLEAVE ANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THEDOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVER SACRIFICE THE SAFE OPERATION OF THEAUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM

BRIDGERECTIFIER

~~

-+

Page 16: 24 V TRANSFORMER - · PDF fileautomatic door application a 100 enterprise drive pittsburgh, pa 15275 ... transformer and bridge rectifier volt/ ampere rating is determind by current

SIZE: DRAWN BY:

B

100 ENTERPRISE DRIVEPITTSBURGH, PA 15275PHONE: (412) 249-4100FAX: (412) 249-4101EMAIL: www.beasensors.com

REV BY:KJG JDCSCALE: DATE:NONE 20 MARCH 2006

PART NO:

SHEET1 OF 1

80.0164.02

TITLE: MC-25, LE-21 WITH LO-21,BODYGUARD, APPROACHSIDE SUPERSCANS

NOTE: 1) ENSURE THAT A MINIMUM OF 3 SECONDS OF HOLD OPEN TIME IS LEFT ON THE LE-21.

DATA + 7blueDATA - 6brownN.C. 5

N.O. 4greenCOM 3whitePOWER 2blackPOWER 1red

RED/WHITE

WHITE

BODYGUARD

OFF

ON

LO-21 DEFAULT DIP SWITCHESRED

GREEN

BLACK

RED

OFF

ON

RED

GREEN

LE21 DEFAULT DIP SWITCHES

DOOR POSITION SWITCHCLOSED CONTACTS WHEN

DOOR IS CLOSED

BLUE

BLUE

YELLOW

GREEN

RED

YELLOW

24 V TRANSFORMER

PURPLE

RED

BLACK

GRAY

GRAY

PUSH TOOPEN

PUSH TOOPEN

GREEN

OPERATOR+

-MOTOR VOLTAGE

ACTIVATIONCOMMONSAFETY DOOR CONTROL

LEFT APPRCH SIDE SSCAN RIGHT APPRCH SIDE SSCAN

IF AFTER TROUBLESHOOTING A PROBLEM, A SATISFACTORY SOLUTION CANNOT BE ACHIEVED, PLEASE CALL B.E.A., INC. FOR FURTHER ASSISTANCE DURING EASTERN STANDARD TIMEAT 1-800-523-2462 FROM 8AM - 5PM. FOR AFTER-HOURS, CALL EAST COAST: 1-866-836-1863 OR 1-800-407-4545 / MID-WEST: 1-888-308-8843 / WEST COAST: 1-888-419-2564. DO NOT LEAVEANY PROBLEM UNRESOLVED. IF YOU MUST WAIT FOR THE FOLLOWING WORKDAY TO CALL B.E.A., LEAVE THE DOOR INOPERABLE UNTIL SATISFACTORY REPAIRS CAN BE MADE. NEVERSACRIFICE THE SAFE OPERATION OF THE AUTOMATIC DOOR OR GATE FOR AN INCOMPLETE SOLUTION.WEB: WWW.BEASENSORS.COM