21206 (C33561.20 B0) User Manual

Embed Size (px)

Citation preview

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    1/130

    C33561001PE_A0 E Copyright Nokia Networks Oy

    TU 21206

    Channel Unit SUB / SUB2 400 Ohm, 6 channels

    User Manual

    C33561.20 B0

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    2/130

    TU 21206 User Manual

    C33561001PE_A0ECopyright Nokia Networks Oyii

    The following products comply with the protection requirements of the European Union Council Directive89/336/EEC relating to electromagnetic compatibility (EMC), provided that installed using EMC-compatibleinstallation practices (installation in mechanical housings stated to be EMC-compatible and using cabling material[at least as well shielded] and practices as stated in relevant Nokia Telecommunications user manuals):

    Product code Product name Release

    TU 21206 Channel unit SUB / SUB, 2 400 Ohm, 6 channels 03A

    E COPYRIGHT Nokia Networks Oy 2001All rights reserved.

    No part of this publication may be copied, distributed, transmitted, transcribed, stored in a retrieval system, or translated into

    any human or computer language without the prior written permission of Nokia NetworksOy.

    The manufacturer has made every effort to ensure that the instructions contained in the documents are adequate and freeof errors and omissions. The manufacturer will, if necessary, explain issues which may not be covered by the documents.The manufacturers liability for any errors in the documents is limited to the correction of errors and the aforementionedadvisory services.

    The documents have been prepared to be used by professional and properly trained personnel, and the customer assumesfull responsibility when using them.The manufacturer welcomes customer comments as part of the process of continualdevelopment and improvement of the documentation in the best way possible from the users viewpoint. Please submit yourcomments to the nearest Nokia sales representative.

    NOKIA is a registered trademark of Nokia Corporation.

    DYNANET is a trademark of Nokia Networks Oy. Any other trademarks mentioned in the documents are the property of theirrespective owners.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    3/130

    C33561001PE_A0 ECopyright Nokia Networks Oy iii

    Document History

    Document Date Comment

    C33561001PE_00 24 Jan 2000

    C33561001PE_A0 30 Apr 2001 New hardware adapted.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    4/130

    TU 21206 User Manual

    C33561001PE_A0ECopyright Nokia Networks Oyiv

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    5/130

    C33561001PE_A0 ECopyright Nokia Networks Oy v

    Contents

    1 Product Description C33561002SE_A0

    2 Installation C33561003SE_A0

    3 Commissioning and Maintenance C33561004SE_A0

    4 Service Menu ReferenceSoftware version 01B C33561005SE_A0

    5 Criterion Table S10002883RE_00Software version 01B

    6 Glossary C33561006SE_A0

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    6/130

    TU 21206 User Manual

    C33561001PE_A0ECopyright Nokia Networks Oyvi

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    7/130

    C33561002SE_A0 E Copyright Nokia Networks Oy

    TU 21206

    Channel Unit SUB / SUB2 400 Ohm, 6 channels

    Product Description

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    8/130

    TU 21206 Product Description

    C33561002SE_A0ECopyright Nokia Networks Oyii

    E COPYRIGHT Nokia Networks Oy 2001All rights reserved.

    No part of this publication may be copied, distributed, transmitted, transcribed, stored in a retrieval system, or translated into

    any human or computer language without the prior written permission of Nokia NetworksOy.

    The manufacturer has made every effort to ensure that the instructions contained in the documents are adequate and freeof errors and omissions. The manufacturer will, if necessary, explain issues which may not be covered by the documents.The manufacturers liability for any errors in the documents is limited to the correction of errors and the aforementionedadvisory services.

    The documents have been prepared to be used by professional and properly trained personnel, and the customer assumesfull responsibility when using them.The manufacturer welcomes customer comments as part of the process of continualdevelopment and improvement of the documentation in the best way possible from the users viewpoint. Please submit yourcomments to the nearest Nokia sales representative.

    NOKIA is a registered trademark of Nokia Corporation.

    DYNANET is a trademark of Nokia Networks Oy. Any other trademarks mentioned in the documents are the property of theirrespective owners.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    9/130

    C33561002SE_A0 ECopyright Nokia Networks Oy iii

    Document History

    Document Date Comment

    C33561002SE_00 24 Jan 2000

    C33561002SE_A0 30 Apr 2001

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    10/130

    TU 21206 Product Description

    C33561002SE_A0ECopyright Nokia Networks Oyiv

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    11/130

    C33561002SE_A0 ECopyright Nokia Networks Oy v

    Contents

    Chapter 1

    About this document 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Related documents 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 2Introduction to SUB / SUB unit 3. . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 3Features 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 4

    Technical specifications 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    12/130

    TU 21206 Product Description

    C33561002SE_A0ECopyright Nokia Networks Oyvi

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    13/130

    About this document

    C33561002SE_A0 ECopyright Nokia Networks Oy 1

    Chapter 1

    About this document

    This document gives a detailed description of Channel Unit SUB / SUB (Sub-scriber unit / Subscriber end). In this document, the unit will be referred to as theSUB / SUB. The following topics are covered:

    D overview of the SUB / SUB unitD key featuresD technical specifications.

    SUB / SUB units cannot function on their own and, therefore, they are always apart of a larger system. SUB / SUB units are always operated and controlled bythe main unit of DM 2 or DM 2+. In this document, both equipment are referred toas DM 2.

    Related documents

    DM 2 is described in detail in theDM 2-MUXOperating Handbookand DM 2+ isdescribed in detail in theDM 2+ Operating Manual.

    For information on mechanical structures and power supplies, please refer to theirown manuals.

    The Glossary of this manual lists the abbreviations and some terms used in thisdocument.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    14/130

    TU 21206 Product Description

    C33561002SE_A0ECopyright Nokia Networks Oy2

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    15/130

    Introduction to SUB / SUB unit

    C33561002SE_A0 ECopyright Nokia Networks Oy 3

    Chapter 2

    Introduction to SUB / SUB unit

    Channel Unit SUB / SUB belongs to the DYNANET family of equipment.SUB / SUB refers to the subscriber interface end of the transmission path (asopposed to the exchange end). The unit simulates the functions of an exchange tothe subscriber and controls the functions for the exchange signalling.

    SUB / SUB units can be used in the following applications:

    D in ordinary telephone networks

    S to connect subscribers to a digital exchange directly at the 2048 kbit/sinterface (see Figure 1)

    S to connect subscribers to an analogue exchange via a SUB / EXCH unit

    (see Figure 2)

    D in hot line applications (see Figure 3).

    2048 kbit/s

    SUB

    SUB

    MUX

    SUB / SUB interface

    Digitalexchange

    Figure 1 SUB / SUB connecting subscribers to a digital exchange

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    16/130

    TU 21206 Product Description

    C33561002SE_A0ECopyright Nokia Networks Oy4

    If subscribers are connected to an analogue exchange, the unit is always used witha SUB / EXCH unit, which is installed at the exchange end of the transmissionpath.

    SUB / EXCH interface

    SUB

    SUB

    MUX

    MUX

    EXCH

    EXCH2048 kbit/s

    SUB / SUB interface

    Analogueexchange

    Figure 2 SUB / SUB connecting subscribers to an analogue exchange

    In a hot line application, a SUB / SUB unit is needed at both ends of theconnection. The hot line is activated with a menu command.

    SUB / SUB interface

    SUB

    SUB

    MUX

    MUX

    2048 kbit/s

    SUB / SUB interface

    SUB

    SUB

    Figure 3 Use of SUB / SUB unit in a hot line application

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    17/130

    Features

    C33561002SE_A0 ECopyright Nokia Networks Oy 5

    Chapter 3

    Features

    General features

    D constant resistance type 2400 ohmD six two-wire speech channelsD impulse / DTMF diallingD ground key detectionD loop detectionD polarity reversalD forwarding of the ringing to the subscriberD metering signal (12 kHz)D protection against hazardous voltages (mains voltages and residual voltages

    due to lightning) by a protection circuitryD Loop Start signalling protocolD installation into:

    S CEPT A type mechanical structuresS 19 mechanical structures, for example DYNANET subrack

    D compliance with ITU-T Recommendations G.712, G.713 and Q.552.

    The unit has the ability to key the ringing signal. As this is the most efficient modeof operation for minimal power dissipation, it is recommended to configure thering generator for keyed operation if the following conditions are met:

    D the ring generator used and the other channel units configured in the same

    subrack support keyed operationD each subrack has its own ring generator.

    If several subracks or cartridges share a ring generator, using the same rack bus, setthe ring generator for continuous operation. This is necessary because the controlsignal to key the generator is local to the subrack backplane and it is not passed onto the rack bus.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    18/130

    TU 21206 Product Description

    C33561002SE_A0ECopyright Nokia Networks Oy6

    Voltages

    D The unit generates the +5 V and 5 V supplies required for internal functionsfrom the central battery voltage (20 to 72 V). The unit receives the centralbattery voltage through its back connector and the subrack backplane.

    D DC-loop current supply is connected to the speech lines.D The subscriber line circuitry runs from a separate signalling voltage supply

    (nominal 48 V"15%). If the line is short, the unit automatically chooses alower signalling voltage (36 V) if such a voltage is available in the subrack.

    D The ringing voltage is brought to the unit from the ring generator or from thesubrack pins.

    D The ringing voltage is switched to the speech lines through 2 400W.Usinga jumper connection, the ringing voltage can be configured for:S ringing about groundS ringing about the signalling voltage

    (see Installation section for full details).

    Interfaces

    D The connectors for the subscriber interfaces are on the front panel of the unit.The pinout for the front connector is given in theInstallation document ofthis manual.

    D The unit receives the power supply and communicates with the equipmentthrough the back connector and subrack backplane.

    D The unit is automatically grounded to the subrack body and connected to therack alarms through the back connector and subrack backplane.

    Settings for the unit

    D Management of the unit, including settings, is done through the serviceinterface of the DM 2-MUX. For more information on managementprinciples, please refer to DM 2-MUX Operating Handbook or DM 2+Operating Manual.

    D All channel settings are retained when the channels are out of use.D The following settings can be set separately for each channel:

    S channel usageS channel time slots 1 to 15 and 17 to 31S level setting range (can be set in 0.5 dB steps):

    Tx direction 6 to +6 dBr; default level 0 dBrRx direction 12 to +0 dBr; default level 7 dBr

    S balance impedanceS channel blockingS signalling mode (normal or hot line).

    The line impedance is chosen by a jumper setting. For details, see theInstallationdocument.

    Troubleshooting features

    D indication of alarms through the front panel LEDsD voltage supervision and further information on some alarm conditions

    through the service interface on the main unit.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    19/130

    Technical specifications

    C33561002SE_A0 ECopyright Nokia Networks Oy 7

    Chapter 4

    Technical specifications

    Voice frequency

    Voice frequency

    Interface ITU-T G.712, G.713 and Q.552

    Connector Euro, 16 + 32 pin

    Number of channels 6

    Nominal levels Rx:7 dBrTx: 0 dBr

    Current feed 40 mA (44 mA max)

    DC feed 2 x 400 ohm

    Longitudinal balance loss 46 dB

    Return loss > 18 dB at 200 Hz to 4 kHz

    Balance impedance when nominal impedance is:

    D 600 ohm 600 ohm390 ohm + (620 ohm // 100 nF)270 ohm + (1200 ohm // 120 nF)

    D 270 ohm +750 ohm //150 nF (ETSI) 270 + (750 ohm //150 nF)390 ohm + (620 ohm // 100 nF)270 ohm + (1200 ohm // 120 nF)

    Metering

    Nominal amplitude, terminated at 200 ohms >1.5 VRMS

    Frequency 12 kHz "60 Hz

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    20/130

    TU 21206 Product Description

    C33561002SE_A0ECopyright Nokia Networks Oy8

    Voltages

    Voltages

    Battery 72 to20 V

    Signalling (B1) 48 V nom. reference to GND (58 to43 V)

    Signalling (B2; optional) 36 V nom. reference to GND (43 to30 V)

    Auxiliary 5 V 5 V 5%

    Ringing 75 VRMS nom. at 25 Hz (60 to 90 VRMS)

    Power consumption

    Power consumption

    Battery supply (at48 V) 2.4 W

    Signalling supply (at48 V) 1.1 W All channels on-hook10 W All channels off-hook, 330Wloop4.4 W All channels off-hook, 2200 W loop1.7 W All channels in ringing state *

    * this figure does not include the ringing signal power, which is provided by thering generator unit

    Dimensions and weight

    Dimensions and weight

    Height 233 mm (6 U)

    Width 25 mm (5 T)

    Depth 160 mm

    Weight 290 g

    Environmental specifications

    The environmental specifications of DM 2-MUX or DM 2+ apply also for theSUB / SUB unit. Please refer to theDM 2-MUX Operating HandbookorDM 2+Operating Manual.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    21/130

    C33561003SE_A0 E Copyright Nokia Networks Oy

    TU 21206

    Channel Unit SUB / SUB2 400 Ohm, 6 channels

    Installation

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    22/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oyii

    E COPYRIGHT Nokia Networks Oy 2001All rights reserved.

    No part of this publication may be copied, distributed, transmitted, transcribed, stored in a retrieval system, or translated into

    any human or computer language without the prior written permission of Nokia NetworksOy.

    The manufacturer has made every effort to ensure that the instructions contained in the documents are adequate and freeof errors and omissions. The manufacturer will, if necessary, explain issues which may not be covered by the documents.The manufacturers liability for any errors in the documents is limited to the correction of errors and the aforementionedadvisory services.

    The documents have been prepared to be used by professional and properly trained personnel, and the customer assumesfull responsibility when using them.The manufacturer welcomes customer comments as part of the process of continualdevelopment and improvement of the documentation in the best way possible from the users viewpoint. Please submit yourcomments to the nearest Nokia sales representative.

    NOKIA is a registered trademark of Nokia Corporation.

    DYNANET is a trademark of Nokia Networks Oy. Any other trademarks mentioned in the documents are the property of theirrespective owners.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    23/130

    C33561003SE_A0 ECopyright Nokia Networks Oy iii

    Document History

    Document Date Comment

    C33561003SE_00 24 Jan 2000

    C33561003SE_A0 30 Apr 2001

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    24/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oyiv

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    25/130

    C33561003SE_A0 ECopyright Nokia Networks Oy v

    Contents

    Chapter 1

    About this document 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Related documents 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 2Precautions 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 3Work order 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 4

    Checking mechanical installation and power supply 7. . . . . . . . . .

    4.1 Mechanical installation 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.2 Power supply 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Signalling voltages 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Using central battery voltage as signalling voltage 8. . . . . . . . . . . .Ring trip 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 5Connecting jumpers 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5.1 Ringing voltage reference configuration 12. . . . . . . . . . . . . . . . . . . . .5.2 Line impedance configuration 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 6Connecting cables 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.1 Cabling example 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6.2 Specifying cable connections 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    26/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oyvi

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    27/130

    About this document

    C33561003SE_A0 ECopyright Nokia Networks Oy 1

    Chapter 1

    About this document

    This document gives the instructions on installation and cabling of Channel UnitSUB / SUB (Subscriber unit / Subscriber end). In this document, the unit will bereferred to as the SUB / SUB. The following topics are covered:

    D Precautions (Chapter 2)D Work order (Chapter 3)D Checking power supply and mechanical installation (Chapter 4)D Connecting jumpers (Chapter 5)D Connecting cables (Chapter 6).

    SUB / SUB units cannot function on their own and, therefore, they are alwaysinstalled as a part of a larger system. SUB / SUB units are always operated and

    controlled by the main unit of DM 2 or DM 2+. In this document, both equipmentare referred to as DM 2.

    If the SUB / SUB unit is to be installed in a subrack that has already been set upcorrectly (for instance, as a replacement to a faulty SUB / SUB unit), it is onlynecessary to ensure that the configuration jumpers for the ringing voltage and lineimpedance settings are correctly positioned (see Chapter 5). No other hardwareconfiguration will be necessary.

    Related documents

    In addition to this document, you may find the following documentation useful:

    Document Information

    Product Descriptionof thismanual

    Technical specifications of SUB / SUB unit forinstallation planning

    DM 2-MUX Operating Handbookor DM 2+ Operating Manual

    Technical specifications of DM 2 equipment forinstallation planning; installation requirements

    Installation manual of thesubrack

    General cabling instructions

    Manual of the power supply unit Power supply configuration for the subrack

    Ring Generator OperatingInstructions

    Ring generator configuration

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    28/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy2

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    29/130

    Precautions

    C33561003SE_A0 ECopyright Nokia Networks Oy 3

    Chapter 2

    Precautions

    Caution

    Take standard anti-static precautions (such as a wrist strap earthed to the subrack)when handling the SUB / SUB unit, as it contains components which may bedamaged by static discharge.

    Caution

    Set the jumpers on the SUB / SUB unit before installing the unit into a subrack. It ispossible to cause damage to the SUB / SUB unit if the jumper settings are notcorrect.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    30/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy4

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    31/130

    Work order

    C33561003SE_A0 ECopyright Nokia Networks Oy 5

    Chapter 3

    Work order

    Before starting the installation, read also the Installation document in theDM 2-MUXOperating Handbookor DM 2+ Operating Manual to find out thegeneral installation requirements.

    Install the SUB / SUB unit in the following order:

    1. Make sure that the subrack or cartridge has been correctly installed and thatthe appropriate voltages have been connected to the subrack (see Chapter 4).

    2. Connect the jumper settings on the SUB / SUB unit (see Chapter 5).3. Plug the SUB / SUB unit into the subrack or cartridge.4. Connect and identify the signal cables (see Chapter 6).5. Specify the cable connections and jumper settings on the marking card (see

    Chapter 6).

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    32/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy6

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    33/130

    Checking mechanical installation and power supply

    C33561003SE_A0 ECopyright Nokia Networks Oy 7

    Chapter 4

    Checking mechanical installation and power supply

    This chapter lists the preliminary inspections you should make on mechanicalinstallation and power supply before starting to set up a new DM 2 system thatincludes SUB / SUB units. If you are installing the unit as a replacement to a faultySUB / SUB unit, you can skip this chapter and continue from Chapter 5.

    4.1 Mechanical installation

    The SUB / SUB unit can be installed into CEPT A type or 19 mechanicalstructures, in any unit location. The dimensions of the SUB / SUB unit are 6Uhigh by 5T wide.

    If you are setting up a completely new DM 2 system that contains SUB / SUBunits, check the following:

    D Make sure that the subrack into which you are installing the units isundamaged.

    D Make sure that the subrack or cartridge has been correctly installed (forsubrack installation, please refer to the subracks own installation manual).

    D Make sure that the main unit has been installed correctly (for instructions,please refer to DM 2-MUX Operating Handbook or DM 2+ Operating

    Manual).

    4.2 Power supply

    If you are setting up a completely new DM 2 system that contains SUB / SUBunits, check the following:

    D Make sure that the rack has been properly earthed.

    D If you want to use other kinds of channel units in the same setup as theSUB / SUB unit, make sure that the units are compatible with each other inthe area of voltage requirements.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    34/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy8

    D Make sure that the following supplies are available in the subrack:

    S battery voltage: 20 to 72 VS signalling voltage

    B1: 43 to 58 V (nominally 48 V) with reference to ground

    B2: 30 to 43 V with reference to groundS ringing voltage: approximately 75 V, 25 Hz.

    The ringing voltage can be generated in a ring generator within the subrack or itcan be brought to the subrack from a central ringing source that is shared betweenseveral DM 2 setups.

    The voltages are delivered to the SUB / SUB unit via the units back connector,PB1. The unit connects automatically to the voltages and to the subrack groundwhen it is plugged in the subrack.

    Signalling voltages

    B1 is the signalling voltage which generates the current for subscriber loop. In theunit TU 21206 the signalling voltage is 48 V (58 to 43 V).

    The B2 signalling voltage 36 V (43 to 30 V) is optional and it is not necessaryfor operation of the unit. If the B2 signalling voltage is connected, the unitautomatically selects the lower signalling voltage for short subscriber lines. In thiscase the power dissipation in the unit is lower.

    No separate signalling voltage is needed if the central battery voltage is in therange of43 to 58 V.

    The positive pole of the battery voltage and the positive pole of the signalling

    voltage must be connected to the subrack body even if the signalling voltage isbrought from outside of the system.

    Using central battery voltage as signalling voltage

    Normally the central battery voltage is 48 V whereupon it can be used assignalling voltage. In this case VNB (negative pole of the central battery voltage)and signalling voltage B1 are connected together.

    Because the ground of the signalling voltage is connected in the unit to unitsground and further to the subracks body, the positive pole of the signallingvoltage source must be connected to the earthing of the rack/subrack. You should

    also take this into account when you use the central battery voltage as signallingvoltage.

    Ring trip

    Ring trip detection is provided by connecting the signalling voltage in series withthe ringing voltage. Detection takes place as DC current detection.

    The ringing voltage can be connected in two different ways:

    D Ringing with reference to negative (-) voltage (default)S Jumper settings: TU 21206 NR4=RG_ref=GNDS

    Ringing voltage RG1 of ring generator is connected to signalling voltageB1 (48 V).

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    35/130

    Checking mechanical installation and power supply

    C33561003SE_A0 ECopyright Nokia Networks Oy 9

    D Ringing with reference to positive (+) voltageS Jumper settings: TU 21206 NR4=RG_ref=B1S Ringing voltage RG1 of ring generator is connected to ground (GND).

    (This jumper setting is possible to do in the ring generator of version08A or newer.)

    NoteAll TU 21206 units fed by the same ring generator must have the jumper settingNR4 connected.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    36/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy10

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    37/130

    Connecting jumpers

    C33561003SE_A0 ECopyright Nokia Networks Oy 11

    Chapter 5

    Connecting jumpers

    Caution

    Take standard anti-static precautions (such as a wrist strap earthed to the subrack)when handling the SUB / SUB unit, as it contains components which may bedamaged by static discharge.

    Caution

    Set the jumpers on the SUB / SUB unit before installing the unit into a subrack. It ispossible to cause damage to the SUB / SUB unit if the jumper settings are notcorrect.

    The following jumpers have to be connected on the SUB / SUB unit:

    D NR4 for ringing voltage reference (affects all channels)S ringing about groundS ringing about signalling voltage

    D NR1, NR2, NR3 for line impedance (separately for each channel)

    S 600 WS 270 W + (750 W // 150 nF).

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    38/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy12

    5.1 Ringing voltage reference configuration

    You may configure SUB / SUB units to use a ringing voltage about rack ground orabout the signalling voltage (48 V nominal). To configure the ringing voltage

    reference, do the following:D On the SUB / SUB unit, configure jumper NR4. The setting affects all

    channels.

    D On the power supply unit, configure the ringing voltage reference line (RG1).

    NoteThe RG1 connection at the power supply configures RG1 for all subracks orcartridges supplied by that power supply.

    Figure 1 shows a summary of the hardware configurations for the ringing voltagereference setup.

    NR4

    NR4 position

    on SUB / SUB

    Ringing about

    Ground

    Signalling voltage 2-3 (RG_ref = GND)

    1-2 (RG_ref B1)

    SUB / SUB

    ALARM LEDS

    ABD

    RG1 connection

    at power supply

    Ground

    B1

    1 2 3

    BackconnectorPB1

    Subscriber lineconnector P1

    Figure 1 Ringing voltage reference hardware configurations

    If NR4 is set up incorrectly for the ringing signal connected to the SUB / SUB unit,then premature ring trip may occur. For this reason you should take care whenusing a mix of compatible channel units in a DM 2 setup. All the units should be

    capable of working with a ringing signal referenced about the same voltage andthe ringing signal should be configured accordingly.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    39/130

    Connecting jumpers

    C33561003SE_A0 ECopyright Nokia Networks Oy 13

    5.2 Line impedance configuration

    Connect all line impedance jumpers for one channel in the same way. The defaultsetting for the jumpers is 600 W.

    NoteRemember to configure the line impedance setting also in the settings menu.

    Figure 2 shows the principle of configuring the line impedance jumpers.

    connector

    PB1

    Back

    SUB / SUB

    ALARM LEDS

    ABD

    D

    E

    F

    G

    H

    J

    NR1 NR2 NR3

    Channels:

    D = Channel 1

    E = Channel 2

    F = Channel 3

    G = Channel 4

    H = Channel 5

    J = Channel 6

    1 2 3 1 2 3

    270 ohm + (750 ohm // 150 nF): 600 ohm(default):

    Subscriber lineconnector P1

    Figure 2 Jumpers for line impedances

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    40/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy14

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    41/130

    Connecting cables

    C33561003SE_A0 ECopyright Nokia Networks Oy 15

    Chapter 6

    Connecting cables

    This chapter specifies the cables and connectors for the SUB / SUB unit and givesan example on how to connect the cables.

    All operational connections are wired at the units front connectors. The backconnector is used for equipment power supply and internal bus interfaces, and itrequires no cabling at the installation stage.Figure 3 shows the pinout of the frontconnector.

    30c

    32c31c

    Ch ChP1UseSignal Use Direction SignalDirection

    27a

    29c

    speech Pb2

    speech Pb1

    23c22c

    28c

    24c25c26c

    20c

    27c

    21c

    1

    220a

    Pa1 speech

    32a31a

    28a

    30a29a

    Pa2 speech

    26a

    23a

    25a24a

    22a21a

    Pa3 speech

    18c17c16c

    19c

    15c15a

    19a18a17a16a

    speech Pb33

    10a 10c

    14c

    13a12a11a 11c

    13c12c

    9c8c

    14a

    Pb4speech4

    Pa6 speech2a1a6

    2c1c Pb66

    5c

    7c6c

    Pa5 speech4a5a

    7a6a

    Pb5speech4c3c 53a

    Pa4 speech 9a8a

    speech

    1

    2

    3

    4

    5

    A-wire signals B-wire signals

    Figure 3 SUB / SUB unit TU 21206, front connector (P1)

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    42/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy16

    6.1 Cabling example

    Cable and connector

    Cable MMHS 8 x 2 x 0.4 + 0.4 mm,product code TI 22701.42

    Connector 16 + 32-pin Euroconnector, product code TX 21474

    A cabling example is given in Table 1. For EMC cabling practices, refer to themanual of the subrack or cartridge used.

    LINE INTERFACES CHANNEL CABLE

    PINS SYMBOL NUMBER USE PAIR COLOUR

    a27c27

    Pa1Pb1

    1 Speech 1blue

    white/blue

    a21c21

    Pa2Pb2

    2 Speech 2orange

    white/orange

    a15c15

    Pa3Pb3

    3 Speech 3green

    white/green

    a09c09

    Pa4Pb4

    4 Speech 4brown

    white/brown

    a03c03

    Pa5Pb5

    5 Speech 5grey

    white/grey

    a01c01

    Pa6Pb6

    6 Speech 6 blueblack/blue

    7orange

    black/orange

    8green

    black/green

    Table 1 Cabling example for connector P1

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    43/130

    Connecting cables

    C33561003SE_A0 ECopyright Nokia Networks Oy 17

    6.2 Specifying cable connections

    Mark the cables so that it is possible to see to which unit and connector they lead.Record the information about the cable connections and jumper settings on the

    marking card delivered with the unit. Figure 4 shows the main principles of the useof marking cards.

    Instructions concerning the markings can be found in the subracks installationdocument.

    When properly filled in, the card also facilitates later servicing, testing andinstallation.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    44/130

    TU 21206 Installation

    C33561003SE_A0ECopyright Nokia Networks Oy18

    1 B 2 S 3 P1

    Write this down on thewire label.

    Identify here how thecable is connected atthe SUB end.

    Key to marking:

    1 Rack row

    B Rack location in the row

    2 Subrack location (bottom

    edge of the subrack)

    S Subrack shelf

    (R = cables from above,

    S = cables from below

    into subrack)

    3 Unit location

    P1 Connectors identification

    Identifyherewhere theother endof thecable is

    connected.

    TU21206SUB/SUB

    TU21206

    SUB/SUB

    a c

    Unit location:

    Equipment ID:

    Address:

    Cable identification:

    This end Other end

    3

    1 B 2 S 3 P1

    Ch1

    Ch2

    Ch3

    Ch4

    Ch5

    Ch6

    27

    21

    15

    9

    3

    1

    a

    a

    a

    a

    a

    a

    b

    b

    b

    b

    b

    b

    Figure 4 Marking card for the SUB / SUB unit, TU 21206

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    45/130

    C33561004SE_A0 E Copyright Nokia Networks Oy

    TU 21206

    Channel Unit SUB / SUB2 400 Ohm, 6 channels

    Commissioning and Maintenance

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    46/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oyii

    E COPYRIGHT Nokia Networks Oy 2001All rights reserved.

    No part of this publication may be copied, distributed, transmitted, transcribed, stored in a retrieval system, or translated into

    any human or computer language without the prior written permission of Nokia NetworksOy.

    The manufacturer has made every effort to ensure that the instructions contained in the documents are adequate and freeof errors and omissions. The manufacturer will, if necessary, explain issues which may not be covered by the documents.The manufacturers liability for any errors in the documents is limited to the correction of errors and the aforementionedadvisory services.

    The documents have been prepared to be used by professional and properly trained personnel, and the customer assumesfull responsibility when using them.The manufacturer welcomes customer comments as part of the process of continualdevelopment and improvement of the documentation in the best way possible from the users viewpoint. Please submit yourcomments to the nearest Nokia sales representative.

    NOKIA is a registered trademark of Nokia Corporation.

    DYNANET is a trademark of Nokia Networks Oy. Any other trademarks mentioned in the documents are the property of theirrespective owners.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    47/130

    C33561004SE_A0 ECopyright Nokia Networks Oy iii

    Document History

    Document Date Comment

    C33561004SE_00 24 Jan 2000

    C33651004SE_A0 30 Apr 2001

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    48/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oyiv

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    49/130

    C33561004SE_A0 ECopyright Nokia Networks Oy v

    Contents

    Chapter 1

    About this document 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Related documents 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 2Accessing and controlling SUB / SUB 3. . . . . . . . . . . . . . . . . . . . . .

    Chapter 3Commissioning SUB / SUB 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.1 Replacing a damaged unit 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1.1 Restoration of settings 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.1.2 No restoration of settings 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3.2 Commissioning units in a new DM 2 system 6. . . . . . . . . . . . . . . . . .3.2.1 Configuring units in a DM 2 setup 6. . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.2 Setting default settings 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.3 Setting identifications 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.4 Setting unit settings 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.5 Configuring interfaces 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3.2.6 Checking the operational condition 10. . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 4

    Locating faults 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4.1 Rack alarms 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.2 LEDs 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.3 State and fault messages 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.4 Loopbacks 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.5 Performance measurements 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.6 Tests 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4.7 Frequently asked questions 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    50/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oyvi

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    51/130

    About this document

    C33561004SE_A0 ECopyright Nokia Networks Oy 1

    Chapter 1

    About this document

    This document describes the procedures for commissioning and maintenance ofChannel Unit SUB / SUB (Subscriber unit / Subscriber end). The following topicsare covered:

    D Accessing and controlling the unit (Chapter 2)D Commissioning of the unit (Chapter 3)D Locating faults (Chapter 4).

    Related documents

    In addition to this document, you may find the following documentation useful:

    Document Information

    Product Descriptionof this manual Overall functioning and features of theunit.

    Service Menu Referenceof this manual Service menus used for configuring thesoftware and for managing the unit.

    Glossaryof this manual Explanation of abbreviations and someterms used in this manual.

    DM 2-MUX Operating HandbookorDM 2+ Operating Manual

    Configuring and commissioning of a DM 2system.

    Service Terminal TC 21700Operating Manual

    Information on how to use the ServiceTerminal.

    Macro STE Users Manual Information on how to use the Macro STE.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    52/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy2

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    53/130

    Accessing and controlling SUB / SUB

    C33561004SE_A0 ECopyright Nokia Networks Oy 3

    Chapter 2

    Accessing and controlling SUB / SUB

    All software-configurable parameters for the unit are accessed via the serviceinterface of the main unit of DM 2-MUX or DM 2+. The main unit provides themenus related to the common parts of the equipment, and the SUB / SUB unitprovides menus relating to its own operation.

    The SUB / SUB units are accessed and controlled using a Service Terminal orMacro STE (Service Terminal Emulator).

    To access the SUB / SUB unit

    D Connect, with an interface cable, the Service Terminal to the main unitsservice interface connector. If you are using the Macro STE, connect your PC

    to the PC interface connector.

    D Switch on the Service Terminal or start the Macro STE. After a few seconds,the top level menu that is common to all equipment is displayed.

    D Establish a direct connection to DM 2: OBJ 7 RET. After a while, the main menuof DM 2 appears on the screen.

    D Choose the type of function you want to access (for example, Settings) in themain menu.

    D Choose number 9 in the subsequent menu.

    D Choose the unit by typing in the number of unit slot in the subrack. Thesubrack slot numbering starts from the left of the subrack.

    If the selected unit slot is empty or houses a MUX unit instead of a SUB unit, youwill get the following response:

    No tributary unit

    in this location

    If a unit has been taken out from the subrack and the equipment configuration hasnot yet been modified with a software command, the response below will be given.You will get the same response also if the selected unit location contains aninoperative unit.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    54/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy4

    Missing unit in

    this unit location

    After you have selected the unit, the SUB / SUB menu for the type of function

    selected (for example, Settings) appears on the screen.

    Configuration dependent entities in the command strings are represented byabbreviations (listed in Service Menu Reference of this manual). You will have toreplace the abbreviation by a proper value when keying in the command.

    NoteIf the Service Terminal is left unused, it will disconnect and switch offautomatically after a specified time-out has elapsed (the default time-out is 10minutes).

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    55/130

    Commissioning SUB / SUB

    C33561004SE_A0 ECopyright Nokia Networks Oy 5

    Chapter 3

    Commissioning SUB / SUB

    The following describes the steps necessary for commissioning a SUB / SUB unit

    for normal operation in a DM 2 system. This chapter deals only with the softwareconfigurable parameters and is divided into the following sections:

    D commissioning procedure for replacing a damaged unitS with the settings of the old unit restored to the new unitS without restoring the settings of the old unit to the new unit

    D commissioning procedure for configuring a unit in a new DM 2 system.

    Before configuring the software, make sure that the jumper settings for ringingvoltage reference and line impedances have been set correctly (seeInstallation inthis manual).

    If you request the commissioning of a unit that is already in the commissionedstate, then its current configuration is copied to the next unit in the cartridge. Thisallows the configuration back-up of the unit to be kept up-to-date if changes aremade to its settings.

    NoteCommission a configured unit only when all of its channels are idle. Thecommissioning process will terminate any calls that are currently in progress.

    3.1 Replacing a damaged unit

    There are two alternative ways to do the replacement depending on whether youwant to restore the settings of the old unit to the new unit or not.

    NoteRemove only one unit at a time. When a new unit is inserted in the subrack,back-up copies are exchanged between the units next to each other. To make surethat this is done successfully, let the equipment stabilise for about 2 minutes beforechanging the next unit.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    56/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy6

    3.1.1 Restoration of settings

    When this procedure is used, the new unit will have the same settings as the oldone. This procedure can be used only if the Hardware ID of the new unit is thesame as the one of the old unit.

    1. Disconnect the signal cables and pull out the damaged unit from the subrack.2. Insert the new unit in the same unit slot and connect the signal cables.

    3.1.2 No restoration of settings

    When this procedure is used, the new unit will have all settings at their defaultvalues.

    1. Remove the old unit from the configuration using the Remove unit command(6,2,2,u; u = number of unit slot in subrack).

    2. Disconnect the signal cables from the damaged unit and pull out the unit fromthe subrack.3. Insert the new unit in the subrack.4. Issue the Add unit command (6,2,1,u; u = number of unit slot in subrack).5. Connect the signal cables.6. Make sure that the new unit works as intended.

    3.2 Commissioning units in a new DM 2 system

    The commissioning procedure consists of the following steps:

    1. Configure the units in the DM 2 setup by the Install all units command.2. Set default settings.3. Set identifications.4. Set unit settings.5. Configure interfaces.6. Make sure that the new unit works as intended.

    NoteIf you add a new channel unit to a partially complete DM 2 system which iscurrently in use, configure the unit using the Add unitcommand (6,2,1,u) ratherthan the Install all units command (6,2,3). Install all units command will terminateall calls currently present on the existing units.

    3.2.1 Configuring units in a DM 2 setup

    To configure all units in a DM 2 setup, enter:

    TOP6,2,3RET Install all units

    To verify that the SUB units are configured, enter:

    TOP6,2,0RET Display

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    57/130

    Commissioning SUB / SUB

    C33561004SE_A0 ECopyright Nokia Networks Oy 7

    To check that no errors were encountered while installing the new units, enter:

    TOP1RET Fault display

    If the fault display indicates a SUB / SUB power supply fault, check the following

    points:

    D Is the SUB / SUB unit correctly installed into the cartridge or subrack?D Are the connections for the voltages and grounding correct?

    3.2.2 Setting default settings

    If you have installed the unit with the 6,2,3 Install all units or 6,2,1 Add unitcommand, default settings for that type of unit should already be in use. If,however, you make a mistake during reconfiguration of the unit and start theconfiguration process again, you can restore the default settings for the unit using

    the Set default settings command, 6,9,u,1,1.You can display all current parameters using the Display settings option, 6,9,u,0.

    Commissioning the unit requires setting of some parameters. Many of theparameters are channel-specific, and many have default values (factory set),which may already be acceptable to you. The default settings are listed in Table 1.

    Parameter Default setting

    Voltage supervision Enabled for all three supervised voltages (signalling,5 V and ringing)

    Channel use All channels out of use

    Time slots Time slots set to 1 to 6 (for channels 1 to 6)

    Wire levels for all channels 7.0 dBr in the receive and +0.0 dBr in transmitdirection

    2-wire balance impedancegroup for all channels

    Set to group 1: 600, 600

    Channel blocking Disabled for all channels

    Signalling mode Set to Normal for all channels

    Metering use Disabled for all channels

    Fault consequences:Channel-associated AIS insignalling

    Causes a B-alarm

    Blocking Causes a B-alarm

    Analog line state when block/fault

    Open

    Time-out period for controls Set to No time-out

    User-defined balance impe-dance coefficients

    Set to impedance group number 1

    Table 1Default settings

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    58/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy8

    3.2.3 Setting identifications

    To help you in managing the unit, you can set an identifier for the unit. The otheridentifications are fixed and can only be displayed.

    The identifier can be up to 15 characters long. Usually, it describes either thelocation or function of the unit.

    To display the identifier, enter:

    TOP4,9,u,2RET

    To modify the identifier, enter:

    TOP4,9,u,7,2,1RET

    Note

    When entering IDs using the Service Terminal, the alphabetic characters have tobe entered as hexadecimal integers, terminated by the ASCII key (characters from Ato F may, however, be entered as INV1...6). Spaces are not accepted but may besubstituted by underline characters. For further details and hexadecimal codes,refer to TC 21700 Service Terminal, Operating Handbook.

    3.2.4 Setting unit settings

    Voltage supervision

    The unit supervises three voltages on the board:

    D signalling voltage (48 V)D 5 VD ringing voltage (75 VAC).

    Each of these individual voltages can be set supervised.

    To set voltage supervision ON or OFF for the channels, enter:

    TOP6,9,u,2RET

    If supervision is enabled, a Power supply fault alarm will be generated if asupervised voltage exceeds its specified range. We recommend that supervision isenabled for all three voltages, as this will allow rapid detection of faults such as afailure in the ring generator.

    The measurement circuitry for these voltages is calibrated at the factory, but ifnecessary, this calibration can be redone using the Voltages option (7,9,u,1). It isnot likely that the unit will require re-calibration, unless you have accidentallyaltered the calibration values.

    Fault consequences

    To specify the consequences of some fault conditions, enter:

    TOP6,9,u,4RET

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    59/130

    Commissioning SUB / SUB

    C33561004SE_A0 ECopyright Nokia Networks Oy 9

    This option sets the consequences of AIS or blocking. You can set the events tocause a B-alarm, or no alarm. Additionally, you can set blocking to leave thesubscriber line in either the Open state, or with reversed polarity feed applied.

    3.2.5 Configuring interfaces

    Each SUB / SUB unit can be configured either separately or by copying thesettings from another SUB / SUB unit. The settings can be entered separately foreach channel.

    Wire levels

    To set the wire levels, enter:

    TOP6,9,u,3,3RET

    This option sets the relative voice level on the subscriber interface lines.

    2-wire balance impedance

    To select a balance impedance most suitable for the speech wire interface, enter:

    TOP6,9,u,3,5RET

    This option sets the 2-wire balance impedance group for individual channels.

    The 2-wire balance impedance should be selected for the closest match with theimpedance of the line plus terminating equipment connected to a channel.

    Signalling modeTo set the subscriber line signalling to use either normal (back-to-back) or hot lineprotocol, enter:

    TOP6,9,u,3,7,ch,RET

    Metering use

    To set metering ON on a subscriber line, enter:

    TOP6,9,u,3,8,ch,RET

    Time slots for channels

    To allocate time slots to channels, enter:

    TOP6,9,u,3,1, ch,3RET

    You can allocate any time slot 1 15 or 17 31 to any channel. However, you mayfind it convenient to allocate channels to units in consecutive groups of six.Allocate consecutive time slots using the All channels option (6,9,u,3,3,11) in theSelect channel menu. Time slot 16 is used for signalling, and it will be skippedautomatically if you use the All channels option.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    60/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy10

    Channel use

    Each channel of the unit can be set into use or out of use. The channel settings areretained also when the channels are out of use.

    To set channels in use or out of use, enter:

    TOP6,9,u,3,1,chRET

    Channel blocking

    Blocking can be used to take a line out of use temporarily, without affecting theother parameters of the channel.

    To block a channel, enter:

    TOP6,9,u,3,6,chRET

    3.2.6 Checking the operational condition

    Check operation

    By connecting the 2-wire interfaces, make sure that the SUB / SUB unit is workingas intended.

    Check fault indications

    Check that the red and yellow LED both on the DM 2 main unit and on the SUBunit are OFF. The service LEDs indicate the following conditions:

    Fault indications

    RED Serious fault impairing the function of the equipment

    YELLOW Exceptional condition in the equipment or unit, forexample, a loopback or other service function

    GREEN Equipment or unit is accessed via a Service Terminal

    Check the fault display for possible fault conditions. The fault display showsfaults in all units controlled by the DM 2 main unit. In the case of a fault, it shows

    the faulty units ID, fault status and fault data.

    To display faults, enter

    TOP1RET

    If no faults have occurred, the response is:

    *DM2 (OK) (where DM2 is the identifier of the main unit)

    If a fault has been detected by the main unit:

    S check the equipment configurationS look for possible causes, for example, loopbacks set on.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    61/130

    Locating faults

    C33561004SE_A0 ECopyright Nokia Networks Oy 11

    Chapter 4

    Locating faults

    The SUB / SUB units do not require scheduled maintenance. Maintenance actionsare necessary only when a fault is indicated by means of an alarm.

    This chapter lists some features that may be useful in finding out a cause of a faultin the operation of the SUB / SUB unit.

    4.1 Rack alarms

    The different alarm classes are:

    A Prompt alarm

    Generated by a fault which inhibits the normal operation of the equipment. AnA-alarm is always generated only by the equipment that has actually detected thefault (AIS or far-end alarm is sent to the other parts of the system as an indicationof an already detected fault). Immediate actions are usually required to return theequipment back to normal operational state.

    B Deferred alarm

    The equipment is still operational but the quality of the services provided hasdegenerated.

    D Reminder of an alarm

    In a fault situation, rack alarms A and B can be removed by giving the Local alarmcancel command. As a result, rack alarm D is given to remind of the cancelledalarm(s). When the fault has been repaired, the alarm indication functions arerestored to normal state by selecting Reset local cancel command.

    S Service alarm

    An S-alarm is generated when the equipment in the far end sends a far-end alarmor an alarm indication signal (AIS) is received. An S-alarm is also given when themain transmission channel is not available. Thus, the S-alarm providesinformation on the state of both transmission directions.

    The difference between S- and A-alarms is that the S-alarm indicates a seriousfault in the operation of the main transmission path, whereas the A-alarm indicates

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    62/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy12

    faults on a certain channel (or channels), while other channels (services) may stillbe operating normally.

    4.2 LEDsThe LEDs on the front of the unit provide some indication as to current activity ofthe unit, or the type of fault, if one is present.

    The red LED indicates either that the unit has not yet been configured into theDM 2 system or that a serious fault has occurred in the unit. If the LED isindicating that the unit is not configured, the fault display does not indicate anyfault.

    The yellow service LED indicates faults in the signal received by the unit, powersupply faults, or service conditions, such as loopback or blocking. The unit itself isnot usually at fault if the yellow LED is lit, as this alarm generally indicates either a

    user-initiated service condition, or a fault in far-end equipment or cabling.

    The green service LED is lit when the unit is accessed by the Service Terminal.

    4.3 State and fault messages

    The state and fault messages of the equipment obtained through the service menuoption 1 Fault display are described below. The rack alarm/service LED indicationin each situation is also given.

    Fault code Defect or fault condition Rack Service

    HEX DECalarm LED

    00 000 Power supply fault A yellow

    14 020 Channel blocked B* yellow*

    16 022 Loop to equipment A yellow

    17 023 Test mode B yellow

    4A 074 AIS TS16/ Exch. blocking B* yellow*

    80 128 Equipment fault A red

    8E 142 Installation error A red

    95 149 Forced indication B red *yellow*green*

    Unit not installed red

    Unit accessed via serviceinterface

    green

    *= indication optional

    Table 2 Indication of fault conditions

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    63/130

    Locating faults

    C33561004SE_A0 ECopyright Nokia Networks Oy 13

    Power supply fault

    One or more of the supervised voltages (signalling, 5 V or ringing) has exceededits specified range. Possible causes of this alarm are:

    D failure of external signalling voltage supplyD partial failure of unit power supplyD failure of ring generatorD measuring circuitry out of calibration.

    Channel blocked

    One or more channels in the unit has been blocked from use via the serviceinterface or the unit is trying to use a time slot that is currently in use in anotherunit.

    Loop to equipment

    A loopback has been set up on one or more channels in the unit.

    NoteA loopback will disconnect the traffic for a channel on which it is active.

    Test mode

    The unit has been put into one of the production test states, and thus cannotfunction normally.

    AIS in TS 16

    There is a fault external to the unit on the digital signal path or blocking has beenapplied from the exchange on a time slot allocated to the unit.

    Equipment fault

    A major failure of the unit. Faults such as EEPROM memory failure and unitpower supply failure are indicated by this alarm. If an equipment fault isregistered, it is probable that the unit will need to be replaced with a new one.

    Installation error

    The software version is incompatible with the hardware. The alarm is issued:

    D when two units have accidentally been inserted in each others slots in thesubrack

    D in the unusual circumstance when a new version of software is installed on anold version of hardware which it cannot control correctly.

    Forced indication

    One or more of the LEDs of the equipment have been set in a forced state (Forced

    ON or OFF), and they are therefore unable to provide normal indication of alarmsor conditions until the forced state is removed.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    64/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy14

    Unit not installed

    The unit has not been configured into the DM 2 setup. This condition does notgenerate any alarm, but does cause the red LED to be lit.

    Unit accessed via service interface

    The unit is currently being accessed through the service interface.

    4.4 Loopbacks

    To help with fault location on the digital signal paths, a digital loopback can beconnected on the digital side of the CODEC (D-D loop). The loopback can be seton with command 5,9,u,2,ch,2.

    Loopbacks and other controls operate on a timed basis. Set a time-out period using

    command 6,9,u,6,1. After this selection, controls will continue to operate untilcancelled or until the time-out period expires. If you set the time-out period to65535, time-out will never occur.

    4.5 Performance measurements

    The unit can provide some (limited) performance or usage information using theTraffic andAlarms logs (7,9,u,5 and 7,9,u,6). These provide information on thenumber of calls processed, and the number of 2048 kbit line failure alarm eventsreceived by the unit. Both logs display a count of their respective events since theywere last reset.

    The operating voltages can be checked by command 7,9,u,1. If the operatingvoltages deviate from the recommended values, it is advisable to check the batteryand the signalling voltage, and the connection between the positive pole of thesignalling voltage and the subrack ground.

    4.6 Tests

    For production purposes the unit has a set of test options, given in menu 9,9,u.Normally, you should not need to use this test facility.

    NoteIf you enter a production test state accidentally (a rack alarm B, test mode, isgenerated), cancel the state with command 9,9,u,1,1.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    65/130

    Locating faults

    C33561004SE_A0 ECopyright Nokia Networks Oy 15

    4.7 Frequently asked questions

    Problem

    A telephone call generates a very short ringing tone.

    Action

    Check the connection of ringing voltage. If the ringing voltage is connected withreference to minus in the ring generator (TU 21261), the jumper setting RG_ref(NR4) of SUB units must be connected to ground (GND).

    or

    If the ringing voltage is connected with reference to ground (GND) in the ringgenerator (TU 21261 version 08A or newer), the SUB units jumper settingRG_ref (NR4) must be connected to B1.

    Problem

    A telephone gives a high-frequency tone.

    Action

    The metering signal 12 kHz (charge indication) is active. If in the exchange endthe unit TU 21215 is used which does not support the metering function, thismetering function must be set out of use also in the SUB unit TU 21206 bycommand 6,9,u,3,8,ch,2.

    NoteThis action concerns the SUB unit version 01A; in the unit version 03A thefunction is disabled by default.

    Problem

    In the hot line connection, a telephone gives a re-ring signal if both subscribershave not laid down the receiver exactly the same time.

    ActionYou must set the hot line function into use by the Service Terminal command6,9,u,3,7,ch,2.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    66/130

    TU 21206 Commissioning and Maintenance

    C33561004SE_A0ECopyright Nokia Networks Oy16

    Problem

    A new SUB unit in connection with an old EXC unit.

    Action

    When you use a new SUB unit (TU 21206 version 01A) together with an old EXCunit (TU 21215), the metering function must be set out of use.

    In the new SUB unit version 03A this metering function is disabled by default.

    In addition to this, in the old EXC unit the Ringing timing control setting (6,9,u,7)must be set to Direct timing (6,9,u,7,1).

    NoteThe following question concerns the unit TU 21216.

    Problem

    The signalling is functioning normally but the voice is hardly to be heard.

    Action

    Unlike old units, the unit TU 21216 requires for its operation signalling voltage48 V. For this reason you have to connect the signalling voltage 48 V tosubracks B1. The positive pole of the voltage is to be connected to thesubracks/racks earth screw.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    67/130

    C33561005SE_A0 E Copyright Nokia Networks Oy

    TU 21206 / TS 25060.00

    Channel Unit SUB / SUB2 400 Ohm, 6 channels

    Service Menu Reference

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    68/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oyii

    E COPYRIGHT Nokia Networks Oy 2001All rights reserved.

    No part of this publication may be copied, distributed, transmitted, transcribed, stored in a retrieval system, or translated into

    any human or computer language without the prior written permission of Nokia NetworksOy.

    The manufacturer has made every effort to ensure that the instructions contained in the documents are adequate and freeof errors and omissions. The manufacturer will, if necessary, explain issues which may not be covered by the documents.The manufacturers liability for any errors in the documents is limited to the correction of errors and the aforementionedadvisory services.

    The documents have been prepared to be used by professional and properly trained personnel, and the customer assumesfull responsibility when using them.The manufacturer welcomes customer comments as part of the process of continualdevelopment and improvement of the documentation in the best way possible from the users viewpoint. Please submit yourcomments to the nearest Nokia sales representative.

    NOKIA is a registered trademark of Nokia Corporation.

    DYNANET is a trademark of Nokia Networks Oy. Any other trademarks mentioned in the documents are the property of theirrespective owners.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    69/130

    C33561005SE_A0 ECopyright Nokia Networks Oy iii

    Document History

    Document Date Comment

    C33561005SE_00 24 Jan 2000 This document is valid for program

    TS 25060.00 version 01A.C33561005SE_A0 30 Apr 2001 This document is valid for program

    TS 25060.00 version 01B.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    70/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oyiv

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    71/130

    C33561005SE_A0 ECopyright Nokia Networks Oy v

    Contents

    Chapter 1

    About this document 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Related documents 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 2Service menus 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 3Identifications 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4,9,u Unit IDs 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,9,u,1 Name 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    4,9,u,2 Identifier 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,9,u,3 User manual 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,9,u,5 Hardware ID 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,9,u,6 Program version 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4,9,u,7 Modify IDs 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 4Controls 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5,9,u Unit controls 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,0 Display active controls 17. . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,1 Controls to normal 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5,9,u,2 Loop to equipment (channel-associated) 18. . . . . . . . . . . . . .5,9,u,2,ch Loop 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,2,ch,2 D>D> loop 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,2,ch,3 Loop off 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,3 Forced indication (LED-associated) 18. . . . . . . . . . . . . . . . .5,9,u,3,led Forced indication 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,3,led,0 Display state 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,3,led,1 Forced state 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,3,led,1,1 Forced ON 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,3,led,1,2 Forced OFF 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5,9,u,3,led,2 Free state 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    72/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oyvi

    Chapter 5Settings 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u Unit settings 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,0 Display settings 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u,1 Default settings 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,1,1,2 Cancel 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,1,1,9 Set def. settings 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,2 Voltage supervision (voltage-associated) 24. . . . . . . . . . . . . .6,9,u,3 Channel settings 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,1 Channel use (channel-associated) 25. . . . . . . . . . . . . . . . . .6,9,u,3,1,ch Channel use (single channel) 25. . . . . . . . . . . . . . . . . . .6,9,u,3,1,ch,1 ON 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,1,ch,2 OFF 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,1,ch,3 Modify timeslot 26. . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,1,ch,3,t Timeslot 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u,3,1,11 Channel use (all channels) 27. . . . . . . . . . . . . . . . . . . . .6,9,u,3,1,11,1 ON 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,1,11,2 OFF 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,1,11,3 Modify timeslot 27. . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,1,11,3,t Timeslot 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,3 Wire levels (channel-associated) 28. . . . . . . . . . . . . . . . . .6,9,u,3,3,ch Modify levels (single channel) 28. . . . . . . . . . . . . . . . . .6,9,u,3,3,ch,1 Receive 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,3,ch,2 Transmit 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,3,11 Modify Levels (all channels) 29. . . . . . . . . . . . . . . . . . .6,9,u,3,3,11,1 Receive 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,3,11,2 Transmit 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u,3,5 2-w balance impedance 30. . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,5,0 Display used impedance (channel-associated) 31. . . . . .6,9,u,3,5,1 Display impedance parameters (group-associated) 32. . .6,9,u,3,5,1,g Display group g 32. . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,5,2 Select new impedance (channel-associated) 32. . . . . . . .6,9,u,3,5,2,ch Select impedance (group-associated) 32. . . . . . . . . . .6,9,u,3,5,2,ch,g Assign group g 33. . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,5,3 Modify coefficient parameters (byte-associated) 33. . . .6,9,u,3,6 Channel blocking (channel-associated) 33. . . . . . . . . . . . .6,9,u,3,6,ch Channel blocking (single channel) 34. . . . . . . . . . . . . . .6,9,u,3,6,ch,1 ON 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u,3,6,ch,2 OFF 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,6,11 Channel blocking (all channels) 34. . . . . . . . . . . . . . . .6,9,u,3,6,11,1 ON 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,6,11,2 OFF 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,7 Signalling mode (channel associated) 35. . . . . . . . . . . . . .6,9,u,3,7,ch Signalling mode (single channel) 35. . . . . . . . . . . . . . .6,9,u,3,7,ch,1 Normal 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,7,ch,2 Hot line 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,7,11 Signalling mode (all channels) 35. . . . . . . . . . . . . . . . .6,9,u,3,7,11,1 Normal 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,7,11,2 Hot line 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u,3,8 Metering use (channel associated) 36. . . . . . . . . . . . . . . . .6,9,u,3,8,ch Metering use (single channel) 36. . . . . . . . . . . . . . . . . .

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    73/130

    C33561005SE_A0 ECopyright Nokia Networks Oy vii

    6,9,u,3,8,ch,1 Enabled 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,8,ch,2 Disabled 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,3,8,11 Metering use (all channels) 36. . . . . . . . . . . . . . . . . . . .6,9,u,3,8,11,1 Enabled 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u,3,8,11,2 Disabled 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,4 Fault consequences 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,4,1 Fault consequences (AIS in one channel) 37. . . . . . . . . . . .6,9,u,4,1,1 No alarms 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,4,1,2 B-alarm 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,4,3 Fault consequences (Blocking) 38. . . . . . . . . . . . . . . . . . . .6,9,u,4,3,1 No alarms 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,4,3,2 B-alarm 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,4,4 Fault consequences (Analog line state) 38. . . . . . . . . . . . .6,9,u,4,4,1 Open 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,4,4,2 Reversed polarity 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,6 Time constants 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6,9,u,6,1 Controls timeout 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,6,1,1 Modify 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,6,1,1,s Setting of permanent time constant 39. . . . . . . . . . . . . .6,9,u,8 Read/load settings 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,8,0 Display setup ID 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,8,1 Read from unit 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,9,u,8,2,* Load to unit 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Chapter 6Measurements 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7,9,u Measurements 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7,9,u,0 Channel faults 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,1 Voltages 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,1,1 48 V 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,1,1,1 Calibrate 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,1,2 5 V 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,1,2,1 Calibrate 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,1,3 75 VAC 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,1,3,1 Calibrate 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,2 Line code 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,3 Signalling state 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,3,1 Mnemonic 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7,9,u,3,2 All states 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,4 Detections 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,5 Traffic 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,5,1 Reset 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,6 Alarms 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,6,1 Reset 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,7 Calibrate levels (channel-associated) 46. . . . . . . . . . . . . . . . .7,9,u,7,ch Calibrate levels 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,7,ch,1 2-wire receive 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7,9,u,7,ch,2 2-wire transmit 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    74/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oyviii

    Chapter 7Testing 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9,9,u Unit testing 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9,9,u,1 Production test 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9,9,u,1,1 Production test OFF 48. . . . . . . . . . . . . . . . . . . . . . . . . . . .9,9,u,1,2 SLIC state 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9,9,u,1,2,s Set SLIC test state (s) 48. . . . . . . . . . . . . . . . . . . . . . . . . .9,9,u,2 Read memory 8 byte 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . .9,9,u,2,add Memory contents 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    75/130

    About this document

    C33561005SE_A0 ECopyright Nokia Networks Oy 1

    Chapter 1

    About this document

    This document lists and details the menus used for controlling Channel UnitSUB / SUB. The menus are described as they appear in the Service Terminal orMacro STE.

    The document covers the following topics:

    D service menu diagrams of the unit (Chapter 2).D descriptions of the SUB/SUB unit menus (Chapters 3 7) for:

    S setting and reading identificationsS setting temporary controlsS setting and modifying permanent setting parametersS reading measurement results

    S production line testing.

    Related documents

    The general principles for accessing and controlling the unit are given in theCommissioning and Maintenance document of this manual, DM 2-MUXOperating HandbookandDM 2+ Operating Manual.

    The general operation principles of the Service Terminal are found in theOperating Manual for Service Terminal TC 21700.

    The abbreviations used in this document are explained in the Glossary of thismanual.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    76/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oy2

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    77/130

    Service menus

    C33561005SE_A0 ECopyright Nokia Networks Oy 3

    Chapter 2

    Service menus

    This chapter shows the service menu diagrams of the SUB/SUB unit. Thediagrams consist of rectangular boxes (representing Service Terminal displays)that have been arranged in hierarchical fashion: the main menu is shown on the topof the page and the submenus proceed downwards and to the right of the mainmenu.

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    78/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oy4

    Select Operation:

    1 Fault display2 Local alarm cancel3 Reset local cancel4 Identifications5 Controls (temporary)6 Settings (permanent)7 Measurements8 Statistics9 Testing

    10 User privileges11 Miscellaneous

    TOPSee:

    MAIN LEVEL MENU (MUX)

    2 Eq name7 Modify eq name9 Unit IDs

    1 Eq type

    Controls:

    0 Display MUX controls1 Eq. to normal state2 2M loops3 Sig. to meas. conn.9 Unit controls

    Settings:

    1 Service options2 HW config.

    Measurements:

    Give main level:4 ... 9 9 Unit settings

    4

    5

    6

    7

    9

    Identifications:

    9 Unit measurements

    Testing:

    9 Unit tests

    1) Not yet implemented

    Options in bold type indicate access to SUB/SUBunit menus

    Statistics:

    8

    Page 5

    Page 6

    Page 11

    Page 12

    The following abbreviations

    are used in the menu

    commands:

    b byte

    ch channel

    dir direction

    led lightemitting diode

    u unit

    v voltage

    9 Unit statistics1)

    Page 7

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    79/130

    Service menus

    C33561005SE_A0 ECopyright Nokia Networks Oy 5

    Identifications:1 Eq type2 Eq name7 Modify eq name

    1 NameIdentifier

    Hardware IDProgram version

    2

    56

    4,9

    1...20

    4

    IDENTIFICATIONS: Unit IDs

    Give new identifier:

    9 Unit IDsSUB/SUB 6 channels

    TS 25060.00 01B

    3 User manual

    C33561005SE_A

    1...20

    Unit ?

    u

    4,9,u

    4,9,u,1

    4,9,u,2

    4,9,u,7,2,0

    4,9,u,7,2,1

    4,9,u,3

    4,9,u,5

    4,9,u,6

    4,9,u,7,5,0

    4,9,u,7,5,1

    SUB/SUB identifications:

    Modify IDs7

    000000000000000

    TU 21206 03A

    2 Identifier5 Hardware ID

    4,9,u,7

    Modify IDs:

    0 Display1 Modify

    Identifier:

    0 Display1 Modify

    Hardware ID:

    4,9,u,7,2

    4,9,u,7,5

    000000000000000

    TU 21206 01A

    115 characters ?

    Give new hardware ID:115 characters ?

    2)

    2)

    2)

    2)

    1) Default identification

    2) Example

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    80/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oy6

    5,9

    1...20

    CONTROLS: Unit Controls

    1...6

    5

    Controls:0 Display MUX controls1 Eq. state2 2M loops3 Sig. to meas. conn.9 Unit controls

    0 Display act. contr.1 Controls to normal2 Loop to equipment3 Forced indication

    channel

    Select led:1 Red2 Yellow3 Green

    0 Display2 D>D>loop1...6

    normalto

    Unit ?1...20

    5,9,u

    u

    5,9,u,2

    5,9,u,3

    ch

    5,9,u,2,ch

    SUB/SUB controls: Select channel:

    Loop to equipment:

    3 Loop off

    0 Display state1 Forced state2 Free state

    5,9,u,3,led

    Forced indication:

    1 Forced ON2 Forced OFF

    5,9,u,3,led,1

    Forced state:

    led1,2,3

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    81/130

    Service menus

    C33561005SE_A0 ECopyright Nokia Networks Oy 7

    6,9

    Unit ?1...20

    1...20

    SETTINGS: Unit Settings

    1

    148 V2 5 V3 75 VAC

    0 Display1 ON2 OFF

    Settings:1 Service options2 HW9 Unit settings

    6

    config.

    0 Display settings1 Default settings2 Voltage3 Channel46 Time

    supervisionsettings

    Fault consequencesconstants

    Default settings:

    1 Set def. settings

    1 Channel use3 Wire levels5 2-w balance imped.

    1 AIS in one channel3 Blocking

    Controls timeout

    Are you sure ?29

    0 Display1 No2 B-alarm

    alarms

    0 Display1 Modify

    1...65534 sec65535 no timeout

    CancelSet def. settings

    u6,9,u

    6,9,u,1

    6,9,u,2

    6,9,u,3

    6,9,u,4

    6,9,u,6

    6,9,u,1,1

    6,9,u,2,v

    6,9,u,4,1

    6,9,u,6,1

    6,9,u,6,1,1

    0 Display setup IDRead from Unit,* Load to Unit

    12

    6,9,u,8

    SUB/SUB settings:

    8 Copy settings

    Select voltage: Voltage supervision:

    6 Channel blocking

    Channel settings:

    Fault consequences:

    123

    Time constants:

    Read/load Settings:

    Controls timeout

    v

    4 Analog line statewhen block/fault

    0 Display1 Open2 Reversed polarity

    6,9,u,4,4

    Analog line state:

    AIS in one channel:

    0 Display1 No2 B-alarm

    alarms

    6,9,u,4,3

    Blocking:

    (*=)

    Pages 8 and 9

    1) Default setting

    Signalling mode7

    1)

    1)

    1)

    1)

    8 Metering use

    1)

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    82/130

    TU 21206 / TS 25060.00 Service Menu Reference

    C33561005SE_A0ECopyright Nokia Networks Oy8

    6,9,u,3

    6,9,u,3,16,9,u,3,1,11

    6,9,u,3,1,11,3

    1 Channel3 Wire levels5 2-wire balance imped.

    use

    Channel settings:

    0 Display1 ON2 OFF3 Modify timeslot

    115 & 1726 ?Give first timeslot:

    SETTINGS: Channel Settings

    6 Channel blocking

    Select channel:

    11 All channels

    Channel use:

    6,9,u,3,1,ch6,9,u,3,1,ch,3

    0 Display1 ON2 OFF3 Modify timeslot

    115 or 1731 ?Give timeslot:

    Channel use:ch1...6

    1...6 channel

    7 Signalling mode

    ch

    6,9,u,3,3 6,9,u,3,3,ch

    1...6,1 Receive2 Transmit

    6,9,u,3,3,ch,1

    Give new level (dBr) ?

    1...6 channel

    Select channel:

    11 All channels11

    Modify levels:

    0 Display

    1) Default setting

    1)

    6,9,u,3,7

    6,9,u,3,6 see page 10

    see page 10

    8 Metering use

    0 ...12.0

    6,9,u,3,3,ch,2

    Give new level (dBr) ?6.0 ...6.0

    6,9,u,3,5 see next page

    6,9,u,3,8 see page 10

  • 7/30/2019 21206 (C33561.20 B0) User Manual

    83/130

    Service menus

    C33561005SE_A0 ECopyright Nokia Networks Oy 9

    6,9,u,3

    1 Channel use

    3 Wire levels5 2-wire balance imped.

    Channel settings:

    SETTINGS: Channel Settings

    6 Channel blocking7 Signalling mode

    1 600, 600

    2 600, 390+(620//100nF)600, 270+(1200//120nF)270+(750//150nF),4

    5 270+(750//150nF),

    6,9,u,3,5

    6,9,u,3,5,0

    6,9,u,3,5,1

    6,9,u,3,5,3

    0 Display used imped.123

    Display imped. param.Select new imped.Modify coeffic. param.

    Which byte 1...3 ? Give new value 0255 ?

    2-w balance imped.:

    Select channel:

    11 All channels

    Select impedance:

    3

    ch

    1...6,11

    1..3

    b6,9,u,3,5,3,b

    1...6 channel

    1) Default setting

    1)

    8 Metering use

    6 270+