2.07_I9FP0151_E.pdf

Embed Size (px)

Citation preview

  • 7/28/2019 2.07_I9FP0151_E.pdf

    1/6

    1

    Abstract-- The fault current distribution among various paths,

    such as shield wires, neutral wires, cable sheaths, electric line

    structure grounds, and substation or power plant grounding

    systems, is computed and analyzed for several scenarios. A

    parametric analysis of the effects of several key variables on the

    fault current distribution is carried out. The variables include:

    cross section of power lines, length of power lines, tower footing

    resistance, grounding system resistance, type of static wires, and

    soil resistivity. In this paper, the fault current distribution andelectromagnetic interference levels have been studied and

    evaluated for a typical electrical network with overhead and

    underground cable lines. Furthermore, a measure has been

    provided to effectively reduce interference to acceptable levels.

    Index TermsElectromagnetic interference, fault currents,

    grounding, power cables, power distribution lines, transmission

    lines

    I. INTRODUCTION

    LECTRICAL engineers are often faced with the necessity

    of having to design grounding systems and

    electromagnetic interference mitigation measures to meetspecific criteria concerning personnel safety or integrity of

    equipment. In grounding design, during single phase-to-ground

    fault conditions, a portion of the fault current will discharge

    into the soil through the grounding network and cause a

    potential rise in the grounding system and induce voltages in

    neighboring conductors. A high potential can result in

    dangerous step and touch voltages and transferred potentials at

    remote locations as well.

    On the other hand, when high voltage transmission and

    distribution lines share a common corridor with other utility

    lines such as pipelines and rail tracks, electromagnetic

    interference caused by the power lines on the non-energized

    utility lines during single phase-to-ground faults occurring at

    any location along the entire power lines is a serious concern

    because it can result in electric shocks and can threaten the

    integrity of the neighboring utility lines.

    The fault current distribution among various paths, such as

    This work was supported by Safe Engineering Services & technologies

    ltd.

    The authors are with Safe Engineering Services & technologies ltd, 3055

    Blvd. Des Oiseaux, Laval, Quebec, Canada H7L 6E8 (e-mail:

    [email protected]).

    shield wires, neutral wires, cable sheaths, electric line structure

    grounds, and substation or power plant grounding systems, is

    an important factor that affects the design of the grounding

    system, the induced electromagnetic interference levels along

    the utility lines, and mitigation measures, if necessary. Several

    studies of fault current distribution for various situations have

    been analyzed in recent years [1-2].

    The fault current distribution is difficult to determine

    accurately since it is not easy to account for the large number

    of variables such as complex electric line networks and

    grounding systems. Detailed computer methods are usually

    used to obtain accurate results. IEEE STD 80-2000 [3]

    suggests a graphical method for determining the maximum

    fault current injected into the grounding system. The method

    attempts to correlate the substation zero sequence fault current

    obtained from a standard short circuit study to the actual

    current flowing between the grounding systems and

    surrounding earth. This provides a quick and simple method to

    estimate the current division, avoid complex computations and

    give acceptable results for a few simple examples compared

    with the computer method. However, it is an approximatemethod that focuses on a few typical line configurations that

    may not apply in many cases.

    This paper presents a parametric analysis in which the fault

    current distribution among various paths is accurately

    computed during single phase-to-ground fault conditions. The

    effects of the following variables on the fault current

    distribution are studied: cross section of power lines, length of

    power lines, tower footing resistance, grounding system

    resistance, type of static wires, and soil resistivity.

    Moreover, this paper presents the results of a recent

    electromagnetic interference study in a shared corridor

    occupied by 345 kV transmission lines, railroad tracks and gas

    pipelines which are parallel to the electric lines along the

    corridor that consists of a 37 km long underground 345 kV

    power cable network and a 74 km long overhead transmission

    line network. The fault current distribution and

    electromagnetic interference levels are studied and evaluated

    for the overhead lines and underground power cables

    respectively. Furthermore, a measure to effectively reduce

    interference to acceptable levels is presented and discussed in

    detail.

    Fault Current Distribution in Transmission and

    Distribution Systems with Shield Wires, Neutral

    Wires and Cable SheathsJ. Liu, F. P. Dawalibi Senior Member, IEEE, J. Ma, Senior Member, IEEE,

    and S. Fortin,Member, IEEE

    E

    The International Conference on Electrical Engineering 2009

  • 7/28/2019 2.07_I9FP0151_E.pdf

    2/6

    2

    II. COMPUTATION METHOD

    A circuit approach and a frequency domain method are

    used to carry out the fault current distribution and

    electromagnetic interference computations through accurate

    simulation of the electric network. The circuit approach used

    in this paper accounts for all the key elements necessary to

    calculate the fault current distribution accurately during

    normal conditions, imbalance conditions, and fault conditions.

    The circuit and frequency domain methods together take

    induction effects fully into account and the computation results

    contain the combined effects of the inductive, conductive, and

    capacitive interference. All simulations have been carried out

    by using the CDEGS software package [4].

    III. COMPUTER MODEL

    Fig. 1 shows the parameter settings that are considered in

    the computer models for this study.

    Fig. 1. Structure of the parametric fault current distribution study

    The reference case consists of a 10 km long 230 kV

    transmission line with a span length of 250 m. At one end of

    the line, a generating station feeds a substation located at the

    other end. We assume that a 10 kA single phase-to-ground

    fault occurs at the substation. The cross section of the line is

    shown in Fig. 2.

    Fig. 2. Overhead T/L cross section for the reference case

    The phase conductors are 2156 kcmil ACSR (bluebird).

    The static wires are Alumoweld 19 No. 7 395.6 kcmil. A

    uniform soil with a 100 ohm-m resistivity is used in the model.

    The tower footing resistance is 15 ohms. The substation

    grounding resistance is 1 ohm and the generating station

    grounding resistance is assumed to be 0.1 ohm. The computed

    fault current split factor, i.e. the ratio of the fault current

    injected into the substation grounding system to the total fault

    current is 34.9% for this reference case.

    This study is based on the reference computer model, fromwhich many computer simulations of representative

    transmission and distribution lines are created by varying one

    parameter at a time. It is not possible to present all the results

    obtained for each analyzed case. However, a number of typical

    cases have been selected and presented here in detail.

    IV. COMPUTER RESULTS

    A. Length of T/L

    The computation results for transmission lines of different

    lengths are shown in Fig. 3. Little change in the fault current

    split factor is observed when the length of the transmission lineis greater than 2.5 km. This shows that the impact on the fault

    current distribution of the transmission line length is small

    when the length exceeds 10 spans.

    Fault Current Split Factors

    0

    5

    10

    15

    20

    25

    30

    35

    40

    0 5 10 15 20 25 30 35 40 45 50

    Length of the Transmission Line (km)

    FaultCurrentSplitFactor(%)

    Fig. 3. Fault current distribution for different T/L lengths

    B. Transmission Line Cross Section

    Different transmission line cross sections are shown in Fig.

    4.

    Fig. 4. Different transmission line cross sections

  • 7/28/2019 2.07_I9FP0151_E.pdf

    3/6

    3

    It can be seen from the computation results shown in Fig. 5

    that some transmission line configurations produce higher fault

    current split factors than other configurations. Clearly, the

    main factor governing the fault current distribution is always

    the geometry distance between the faulted phase wire and the

    static wires rather than the overall configuration of the

    transmission lines. When the faulted phase wire is close to the

    static wires, the mutual coupling between the phase and static

    wires is stronger. As a result, more current flows along thestatic wires back to its source and less current is injected into

    the grounding grid.

    Fault Current Split Factors

    10

    20

    30

    40

    Horizontal (Fault is on

    Phase A)

    Wide Horizontal (Fault

    is on Phase A)

    Vertical (Fault is on

    Phase A)

    Vertical (Fault is on

    Phase C)

    Transmission Line Cross Section

    FaultCurrentSplitFactor(%)

    Fig. 5. Fault current distribution for different transmission line cross sections

    C. Type of Static (Ground) Wire

    The computation results for different types of static wires

    are shown in Fig. 6. As we can see, the materials of the static

    wires can significantly affect the fault current split factor.

    More current returns to its source via the static wires when the

    static wires are more conductive. As a result, less current is

    discharged by the grounding system at the faulted substation.

    Fault Current Split Factors

    10

    20

    30

    40

    50

    60

    Steel Aluminum Copper

    Type of Static Wire

    FaultCurrentSplitFactor(%)

    Fig. 6. Fault current distribution for different types of static wires

    D. Tower Resistance

    The computation results for different tower resistances

    along the transmission line are shown in Fig. 7. The resultsindicate that the fault current split factor is increasing with the

    increase of the tower resistance. This can be easily explained

    by the fact that less current will come back through the path

    consisting of the static wires and tower footings when the

    tower resistance is high. However, this effect will be small

    when the tower resistance is about 20 ohms or more.

    E. Soil Resistivitiy

    Four soil resistivities, 10, 100, 1000 and 10000 ohm-m are

    used to compute the self impedance of the static wire and the

    mutual impedance of the phase conductor and the static wire.

    The fault current distribution has been studied as shown in Fig.

    8. It has been found that the fault current distribution is slightly

    influenced by the soil resistivity. The fault current has a

    tendency to go back to the source through the static wires

    when the soil resistivity is high and therefore less current is

    injected into the grounding grid.

    F. Substation Ground Resistance

    Fig. 9 shows what happens when the faulted substation ground

    resistance changes. As expected, the fault current split factor

    decreases when the faulted substation ground resistance is

    high. Most of the fault current will return to the source through

    the static wires once the faulted substation ground resistance

    reaches a high value (on the order of 5 ohms in this case).

    Fault Current Split Factors

    0

    5

    10

    15

    20

    25

    30

    35

    40

    45

    50

    0 20 40 60 80 100

    Tower Resistance (ohms)

    FaultCurrentSp

    litFactor(%)

    Fig. 7. Fault current distribution for different tower resistances

    Fault Current Split Factors

    0

    5

    10

    15

    20

    25

    30

    35

    40

    1 10 100 1000 10000

    Soil Resistivity (ohm-m)

    FaultCurrentSplitFac

    tor(%)

    Fig. 8. Fault current distribution for different soil resistivies

    Fault Current Split Factors

    0

    10

    20

    30

    40

    50

    60

    0 5 10 15 20

    Substation Ground Resistance (ohms)

    FaultCurrentSplitFactor(%

    )

    Fig. 9. Fault current distribution for different faulted substation resistances

  • 7/28/2019 2.07_I9FP0151_E.pdf

    4/6

    4

    G. Generating Station Ground Resistance

    Fig. 10 shows the computation results with respect to

    different generating station ground resistances.

    Fault Current Split Factors

    20

    25

    30

    35

    40

    45

    50

    55

    0 1 2 3 4 5 6 7 8 9 10Generating Station Ground Resistance (ohms)

    FaultCurrentSplitFactor(%)

    Tower Resistance-5 ohms

    Tower Resistance-15 ohms

    Tower Resistance-50 ohms

    Tower Resistance-100 ohms

    Fig. 10. Fault current distribution for different generating station ground

    resistances

    It is interesting to observe that the fault current split factor

    varies by following different patterns when the generating

    station ground resistances have different values. The

    complexity of the relationship between the fault current split

    factor and the generating station ground resistance have been

    discovered. When the tower resistance is small, the fault

    current split factor will remain practically constant or increase

    slightly. On the other hand, the fault current split factor will

    gradually decline with the increase of the generating station

    ground resistance when the tower resistance is about 100 ohms

    or more.

    H. Underground Power Cable Configuration

    Two typical cables have been modeled to demonstrate the

    fault current distribution. The horizontal and mixed

    configurations are shown in Fig. 11.

    Fig. 11. Different configurations of the underground cable

    The length of the underground cables is 3 km. The

    underground cables are modeled as a stranded conductor core

    surrounded by a lead sheath. The equivalent relative resistivity

    and the relative permeability of the sheaths were derived based

    on typical values. The cable is a XLPE insulated cable and the

    characteristics used to perform the calculation are as follows:

    Cable core: 3500 kcmil copper conductor

    Cable overall diameter: 12.8 cm

    Copper core diameter: 5.2 cm

    Lead sheath: extruded lead, inner diameter = 9.4 cm, and

    outer diameter: = 10.5 cm

    Lead sheath equivalent relative resistivity (with respect to

    copper) and permeability(with respect to free space): 12 and 1

    Two ground wires are installed with the underground

    cables. The radius of the ground wire is 0.8 cm. The

    underground cables are divided into sections (from one vault

    location to another). Two ground rods are installed per cable

    vault (i.e., every 600 m). The ground resistance is 15 ohms.The computed fault current split factors are 1.6% and 2.2%

    for the horizontal and vertical configurations, respectively.

    Little change is observed when the overall configurations are

    different. This is due to the fact that the mutual coupling

    between the sheath and cable core is very strong because of the

    small distance between the two conductors. In the case of an

    underground cable, the mutual coupling plays a very important

    role in the current distribution, as expected.

    V. TYPICAL AC INTERFERENCE STUDY

    A typical AC interference study that involves an electric

    network consisting of overhead lines and underground cablesis presented in this section.

    A. Network Description and Computer Model

    Fig. 12 shows the plan view of the electrical network under

    study.

    Fig. 12. Plan view of the electrical network under study

    The underground power cables between Substation #1 and

    Substation #3 consist of two 345-kV circuits utilizing XLPE

    insulated cables. The total length of the underground cables is

    37 km and a railroad roughly follows the underground cables

    for about 21 km. The overhead portion of the 345-kV

    transmission lines between Substation #3 and Substation #7 is

    approximately 74 km. A gas pipeline and a railroad share the

    same corridor with the 345-kV overhead transmission line for

    about 6.4 km, respectively.

    The 345-kV transmission line can cause AC interference to

  • 7/28/2019 2.07_I9FP0151_E.pdf

    5/6

    5

    the railway system and pipelines. Especially, the induced

    voltages and currents on the railway and pipeline facilities can

    result in a shock hazard and threaten the integrity of both

    facilities during single phase-to-ground fault conditions.

    The complete model consists of the transmission line phase

    conductors, static wires, underground cables, rails, rail ballast

    resistances, insulating joints, track arresters, rail track circuits,

    and railroad equipment house grounds. Various soil structures

    have been modeled along the entire common-corridor. In thispaper, the electromagnetic interference under fault conditions

    has been analyzed and presented.

    The data and characteristics used in the simulations are as

    follows:

    The overhead line consists of the ACSR phase wires and

    Aluminum 7#8 static wires

    The underground cable characteristics are the same as in

    the previous section

    The maximum load current is 1.5 kA per phase for the

    new 345 kV line and 1.2 kA per phase for the existing

    345 kV line

    A 130 lb steel rail was selected and the separationdistance between rails is 1.5 m

    The pipeline has a radius of 30 cm and is covered with

    coal tar coating

    Figs. 13 and 14 show the typical cross sections of the

    overhead lines and underground cables.

    Fig. 13. Cross section of the underground cable conduit

    Fig. 14. Cross section of overhead transmission lines

    The touch voltage is one of the important quantities that

    should be computed and examined. In this paper, the touch

    voltages when a person contacts a rail track or a pipeline when

    standing 1 m away on both sides of the rail track or pipeline

    are calculated to ensure that safety concerns are addressed.

    B. Computation Results

    The computation results are summarized here. The worst

    rail touch voltage under fault conditions for the underground

    cable portion is 94 V only which is below the IEEE Standard

    80 safe limit of 519 V based on a 800 ohm-m native soil, as

    shown in Fig. 15. The low touch voltage is caused by theproximity of the lead sheath to the underground cable core that

    results in a very strong mutual coupling between them. As a

    result, most of the fault current is going back to the remote

    source through the sheath. As a result, the induced EMF on the

    rail is small due to the cancellation effect of the core current

    by the sheath current. The induced EMF caused by the ground

    conductors paralleling the cable sheath is also small because

    little current is flowing into the ground conductors.

    Rail Touch Voltages

    0

    100

    200

    300

    400

    500

    600

    700

    0 5000 10000 15000 20000 25000

    Distance along Railway in Parallel with the Underground Cable (m)

    TouchVoltages(V)

    Rail Touch Voltages

    Touch Voltage Limit

    Fig. 15. Rail touch voltages along the underground cable

    The worst rail and pipe touch voltages under fault

    conditions for the overhead portion are 2244 V and 1010 V,

    respectively. Both of them are above the IEEE Standard 80

    safe limit based on various soils along the entire length of the

    railway and pipeline. The computation results for the touch

    voltages along the rail are shown in Fig. 16. In contrast to the

    underground cable situation, a large amount of the fault

    current is injected into the tower grounds along the common-

    corridor due to the high fault current split factor in the case of

    an overhead line with two Aluminum 7#8 static wires.

    Maximum Rail Touch Voltages

    0

    500

    1000

    1500

    2000

    2500

    0 1000 2000 3000 4000 5000 6000 7000

    Distance along Railway in Parallel with the Overhead T/L (m)

    TouchVoltages(V)

    Rail Touch Voltages

    Touch Voltage Limit

    Fig. 16. Rail touch voltages along the overhead transmission lines

    Therefore, mitigation measures are required on the railway

    and pipelines facilities which parallel the overhead

    transmission lines.

  • 7/28/2019 2.07_I9FP0151_E.pdf

    6/6

    6

    C. Mitigation Measure

    A mitigation measure consisting of three continuous

    mitigation wires along the railway and pipeline is presented.

    Two continuous mitigation wires bonded to the railway

    through track arresters at regular intervals and buried 1 m

    away from the edge of the railway are installed along the

    exposed railway zone on both sides of the railway. Similarly, a

    zinc mitigation wire along the exposed pipeline located about

    1 m away from the edge of the pipeline is installed. Themitigation wire is connected to the pipeline through PCR

    (Polarization Cell Replacement) or solid-state decoupler

    devices. In case of a fault, the continuous mitigation wires

    provide additional grounding for the railway and pipeline and

    furthermore, act as screening conductors, thus decreasing the

    induced pipe and rail potential rise. This measure reduces

    interference levels considerably, as can be seen in Fig. 17 for

    the rail touch voltages. As a result, the computed rail and pipe

    touch voltages have been reduced to less than 250 V and 300

    V, respectively, which satisfy the safety design limits.

    Maximum Rail Touch Voltages with Mitigation Wires

    0

    100

    200

    300

    400

    500

    0 1000 2000 3000 4000 5000 6000 7000

    Distance along Railway in Parallel with the Overhead T/L (m)

    TouchVoltages(V)

    Rail Touch Voltages

    Touch Voltage Limit

    Fig. 17. Rail touch voltages along the overhead transmission lines with

    mitigation wires

    VI. CONCLUSIONS

    A parametric analysis of the fault current distribution along

    electric power transmission network has been conducted.

    Effects of the various parameters which influence the fault

    current split factor have been studied. The parameters include

    power line cross section, length of power lines, tower footing

    resistance, station grounding system resistance, types of static

    wires, and soil resistivity. All charts, observations, and

    computation results offer useful clues to better understanding

    of the fault current distribution. Furthermore, a typical study of

    electromagnetic interference on railways and pipelines caused

    by electrical overhead transmission lines and undergroundcables under fault conditions has been carried out as an

    example. This real case study shows how modern

    computational approaches can be used to analyze complex

    electromagnetic interference issues and produce accurate

    results.

    VII. REFERENCES

    [1] S. Tee, F. P. Dawalibi, and J. Liu, "Influence of current distribution in

    enclosed underground power cables on the overheating of the steel

    casing enclosure," The International Conference on Electrical

    Engineering (ICEE), Kunming, China, July 10 - 14, 2005.

    [2] W. K. Daily and F. P. Dawalibi, "Cost reduction and minimization of

    land based on an accurate determination of fault current distribution in

    neutral conductors,"IEEE Trans. Power Delivery, vol. 8, no. 1, pp. 97-

    103, January 1993.

    [3] IEEE Guide for Safety in AC Substation Grounding, IEEE Standard 80-

    2000.

    [4] CDEGS Software Package, Safe Engineering Services & technologies

    ltd., Montreal, Quebec, Canada, 2006.

    VIII. BIOGRAPHIES

    Ms. J. Liu received the B.Eng. and the M. Eng. degree in Electrical

    Engineering in 1985 and 1990, respectively. She is presently serving as

    scientific researcher at Safe Engineering Services & technologies ltd. Her

    research interests are electrical grounding systems, EMC, and various aspects

    of electrical power system analysis, modeling, control, and management.

    She is the author of more than 30 papers on electrical power system

    safety, power quality, EMC, and computer applications.

    Dr. F. P. Dawalibi (M'72, SM'82) was born in Lebanon in November

    1947. He received a Bachelor of Engineering degree from St. Joseph's

    University, affiliated with the University of Lyon, and the M.Sc. and Ph.D.

    degrees from Ecole Polytechnique of the University of Montreal. From 1971

    to 1976, he worked as a consulting engineer with the Shawinigan Engineering

    Company, in Montreal. He worked on numerous projects involving power

    system analysis and design, railway electrification studies and specialized

    computer software code development.

    In 1976, he joined Montel-Sprecher & Schuh, a manufacturer of high

    voltage equipment in Montreal, as Manager of Technical Services and was

    involved in power system design, equipment selection and testing for systems

    ranging from a few to several hundred kV.

    In 1979, he founded Safe Engineering Services & technologies, a

    company specializing in soil effects on power networks. Since then he has

    been responsible for the engineering activities of the company including the

    development of computer software related to power system applications.

    He is the author of more than 200 papers on power system grounding,

    lightning, inductive interference and electromagnetic field analysis. He has

    written several research reports for CEA and EPRI.

    Dr. Jinxi Ma (M'91, SM'00) was born in Shandong, P. R. China in

    December 1956. He received the B.Sc. degree from Shandong University, P.

    R. China, and the M.Sc. degree from Beijing University of Aeronautics and

    Astronautics, both in electrical engineering, in 1982 and 1984, respectively.

    He received the Ph.D. degree in electrical and computer engineering from theUniversity of Manitoba, Winnipeg, Canada in 1991. From 1984 to 1986, he

    was a faculty member with the Department of Electrical Engineering, Beijing

    University of Aeronautics and Astronautics. He worked on projects involving

    design and analysis of reflector antennas and calculations of radar cross

    sections of aircraft.

    Since September 1990, he has been with the R & D Dept. of Safe

    Engineering Services & technologies in Montreal, where he is presently

    serving as manager of the Analytical R & D Department. His research

    interests are in transient electromagnetic scattering, EMI and EMC, and

    analysis of grounding systems in various soil structures.

    Dr. Ma has authored and coauthored more than one hundred papers on

    transient electromagnetic scattering, analysis and design of reflector antennas,

    power system grounding, lightning and electromagnetic interference analysis.

    He is a senior member of the IEEE Power Engineering Society, a member of

    the IEEE Standards Association, and a corresponding member of the IEEE

    Substations Committee and is active on Working Groups D7 and D9Dr. S. Fortin was born in 1962. He received a B. Sc. degree (1985) in

    Physics from Laval University, Quebec and a Ph. D. degree (1991) in Physics

    from the University of British Columbia, Vancouver. His area of

    specialization was in the theoretical aspects of high-energy particle physics.

    In 1992-1993, he was a research assistant with the Nuclear Physics

    Department at the University of Montreal, again specializing in particle

    physics.

    He joined Safe Engineering Services & Technologies Ltd. as a research

    scientist in 1994. His research interests include the computation of

    electromagnetic fields at various frequencies and transient phenomena. Dr.

    Simon Fortin has published about 40 papers on lighting, grounding and

    electromagnetic fields compatibility related problems.