Upload
carlos-lino-rojas-agueero
View
215
Download
0
Embed Size (px)
Citation preview
7/28/2019 2.07_I9FP0151_E.pdf
1/6
1
Abstract-- The fault current distribution among various paths,
such as shield wires, neutral wires, cable sheaths, electric line
structure grounds, and substation or power plant grounding
systems, is computed and analyzed for several scenarios. A
parametric analysis of the effects of several key variables on the
fault current distribution is carried out. The variables include:
cross section of power lines, length of power lines, tower footing
resistance, grounding system resistance, type of static wires, and
soil resistivity. In this paper, the fault current distribution andelectromagnetic interference levels have been studied and
evaluated for a typical electrical network with overhead and
underground cable lines. Furthermore, a measure has been
provided to effectively reduce interference to acceptable levels.
Index TermsElectromagnetic interference, fault currents,
grounding, power cables, power distribution lines, transmission
lines
I. INTRODUCTION
LECTRICAL engineers are often faced with the necessity
of having to design grounding systems and
electromagnetic interference mitigation measures to meetspecific criteria concerning personnel safety or integrity of
equipment. In grounding design, during single phase-to-ground
fault conditions, a portion of the fault current will discharge
into the soil through the grounding network and cause a
potential rise in the grounding system and induce voltages in
neighboring conductors. A high potential can result in
dangerous step and touch voltages and transferred potentials at
remote locations as well.
On the other hand, when high voltage transmission and
distribution lines share a common corridor with other utility
lines such as pipelines and rail tracks, electromagnetic
interference caused by the power lines on the non-energized
utility lines during single phase-to-ground faults occurring at
any location along the entire power lines is a serious concern
because it can result in electric shocks and can threaten the
integrity of the neighboring utility lines.
The fault current distribution among various paths, such as
This work was supported by Safe Engineering Services & technologies
ltd.
The authors are with Safe Engineering Services & technologies ltd, 3055
Blvd. Des Oiseaux, Laval, Quebec, Canada H7L 6E8 (e-mail:
shield wires, neutral wires, cable sheaths, electric line structure
grounds, and substation or power plant grounding systems, is
an important factor that affects the design of the grounding
system, the induced electromagnetic interference levels along
the utility lines, and mitigation measures, if necessary. Several
studies of fault current distribution for various situations have
been analyzed in recent years [1-2].
The fault current distribution is difficult to determine
accurately since it is not easy to account for the large number
of variables such as complex electric line networks and
grounding systems. Detailed computer methods are usually
used to obtain accurate results. IEEE STD 80-2000 [3]
suggests a graphical method for determining the maximum
fault current injected into the grounding system. The method
attempts to correlate the substation zero sequence fault current
obtained from a standard short circuit study to the actual
current flowing between the grounding systems and
surrounding earth. This provides a quick and simple method to
estimate the current division, avoid complex computations and
give acceptable results for a few simple examples compared
with the computer method. However, it is an approximatemethod that focuses on a few typical line configurations that
may not apply in many cases.
This paper presents a parametric analysis in which the fault
current distribution among various paths is accurately
computed during single phase-to-ground fault conditions. The
effects of the following variables on the fault current
distribution are studied: cross section of power lines, length of
power lines, tower footing resistance, grounding system
resistance, type of static wires, and soil resistivity.
Moreover, this paper presents the results of a recent
electromagnetic interference study in a shared corridor
occupied by 345 kV transmission lines, railroad tracks and gas
pipelines which are parallel to the electric lines along the
corridor that consists of a 37 km long underground 345 kV
power cable network and a 74 km long overhead transmission
line network. The fault current distribution and
electromagnetic interference levels are studied and evaluated
for the overhead lines and underground power cables
respectively. Furthermore, a measure to effectively reduce
interference to acceptable levels is presented and discussed in
detail.
Fault Current Distribution in Transmission and
Distribution Systems with Shield Wires, Neutral
Wires and Cable SheathsJ. Liu, F. P. Dawalibi Senior Member, IEEE, J. Ma, Senior Member, IEEE,
and S. Fortin,Member, IEEE
E
The International Conference on Electrical Engineering 2009
7/28/2019 2.07_I9FP0151_E.pdf
2/6
2
II. COMPUTATION METHOD
A circuit approach and a frequency domain method are
used to carry out the fault current distribution and
electromagnetic interference computations through accurate
simulation of the electric network. The circuit approach used
in this paper accounts for all the key elements necessary to
calculate the fault current distribution accurately during
normal conditions, imbalance conditions, and fault conditions.
The circuit and frequency domain methods together take
induction effects fully into account and the computation results
contain the combined effects of the inductive, conductive, and
capacitive interference. All simulations have been carried out
by using the CDEGS software package [4].
III. COMPUTER MODEL
Fig. 1 shows the parameter settings that are considered in
the computer models for this study.
Fig. 1. Structure of the parametric fault current distribution study
The reference case consists of a 10 km long 230 kV
transmission line with a span length of 250 m. At one end of
the line, a generating station feeds a substation located at the
other end. We assume that a 10 kA single phase-to-ground
fault occurs at the substation. The cross section of the line is
shown in Fig. 2.
Fig. 2. Overhead T/L cross section for the reference case
The phase conductors are 2156 kcmil ACSR (bluebird).
The static wires are Alumoweld 19 No. 7 395.6 kcmil. A
uniform soil with a 100 ohm-m resistivity is used in the model.
The tower footing resistance is 15 ohms. The substation
grounding resistance is 1 ohm and the generating station
grounding resistance is assumed to be 0.1 ohm. The computed
fault current split factor, i.e. the ratio of the fault current
injected into the substation grounding system to the total fault
current is 34.9% for this reference case.
This study is based on the reference computer model, fromwhich many computer simulations of representative
transmission and distribution lines are created by varying one
parameter at a time. It is not possible to present all the results
obtained for each analyzed case. However, a number of typical
cases have been selected and presented here in detail.
IV. COMPUTER RESULTS
A. Length of T/L
The computation results for transmission lines of different
lengths are shown in Fig. 3. Little change in the fault current
split factor is observed when the length of the transmission lineis greater than 2.5 km. This shows that the impact on the fault
current distribution of the transmission line length is small
when the length exceeds 10 spans.
Fault Current Split Factors
0
5
10
15
20
25
30
35
40
0 5 10 15 20 25 30 35 40 45 50
Length of the Transmission Line (km)
FaultCurrentSplitFactor(%)
Fig. 3. Fault current distribution for different T/L lengths
B. Transmission Line Cross Section
Different transmission line cross sections are shown in Fig.
4.
Fig. 4. Different transmission line cross sections
7/28/2019 2.07_I9FP0151_E.pdf
3/6
3
It can be seen from the computation results shown in Fig. 5
that some transmission line configurations produce higher fault
current split factors than other configurations. Clearly, the
main factor governing the fault current distribution is always
the geometry distance between the faulted phase wire and the
static wires rather than the overall configuration of the
transmission lines. When the faulted phase wire is close to the
static wires, the mutual coupling between the phase and static
wires is stronger. As a result, more current flows along thestatic wires back to its source and less current is injected into
the grounding grid.
Fault Current Split Factors
10
20
30
40
Horizontal (Fault is on
Phase A)
Wide Horizontal (Fault
is on Phase A)
Vertical (Fault is on
Phase A)
Vertical (Fault is on
Phase C)
Transmission Line Cross Section
FaultCurrentSplitFactor(%)
Fig. 5. Fault current distribution for different transmission line cross sections
C. Type of Static (Ground) Wire
The computation results for different types of static wires
are shown in Fig. 6. As we can see, the materials of the static
wires can significantly affect the fault current split factor.
More current returns to its source via the static wires when the
static wires are more conductive. As a result, less current is
discharged by the grounding system at the faulted substation.
Fault Current Split Factors
10
20
30
40
50
60
Steel Aluminum Copper
Type of Static Wire
FaultCurrentSplitFactor(%)
Fig. 6. Fault current distribution for different types of static wires
D. Tower Resistance
The computation results for different tower resistances
along the transmission line are shown in Fig. 7. The resultsindicate that the fault current split factor is increasing with the
increase of the tower resistance. This can be easily explained
by the fact that less current will come back through the path
consisting of the static wires and tower footings when the
tower resistance is high. However, this effect will be small
when the tower resistance is about 20 ohms or more.
E. Soil Resistivitiy
Four soil resistivities, 10, 100, 1000 and 10000 ohm-m are
used to compute the self impedance of the static wire and the
mutual impedance of the phase conductor and the static wire.
The fault current distribution has been studied as shown in Fig.
8. It has been found that the fault current distribution is slightly
influenced by the soil resistivity. The fault current has a
tendency to go back to the source through the static wires
when the soil resistivity is high and therefore less current is
injected into the grounding grid.
F. Substation Ground Resistance
Fig. 9 shows what happens when the faulted substation ground
resistance changes. As expected, the fault current split factor
decreases when the faulted substation ground resistance is
high. Most of the fault current will return to the source through
the static wires once the faulted substation ground resistance
reaches a high value (on the order of 5 ohms in this case).
Fault Current Split Factors
0
5
10
15
20
25
30
35
40
45
50
0 20 40 60 80 100
Tower Resistance (ohms)
FaultCurrentSp
litFactor(%)
Fig. 7. Fault current distribution for different tower resistances
Fault Current Split Factors
0
5
10
15
20
25
30
35
40
1 10 100 1000 10000
Soil Resistivity (ohm-m)
FaultCurrentSplitFac
tor(%)
Fig. 8. Fault current distribution for different soil resistivies
Fault Current Split Factors
0
10
20
30
40
50
60
0 5 10 15 20
Substation Ground Resistance (ohms)
FaultCurrentSplitFactor(%
)
Fig. 9. Fault current distribution for different faulted substation resistances
7/28/2019 2.07_I9FP0151_E.pdf
4/6
4
G. Generating Station Ground Resistance
Fig. 10 shows the computation results with respect to
different generating station ground resistances.
Fault Current Split Factors
20
25
30
35
40
45
50
55
0 1 2 3 4 5 6 7 8 9 10Generating Station Ground Resistance (ohms)
FaultCurrentSplitFactor(%)
Tower Resistance-5 ohms
Tower Resistance-15 ohms
Tower Resistance-50 ohms
Tower Resistance-100 ohms
Fig. 10. Fault current distribution for different generating station ground
resistances
It is interesting to observe that the fault current split factor
varies by following different patterns when the generating
station ground resistances have different values. The
complexity of the relationship between the fault current split
factor and the generating station ground resistance have been
discovered. When the tower resistance is small, the fault
current split factor will remain practically constant or increase
slightly. On the other hand, the fault current split factor will
gradually decline with the increase of the generating station
ground resistance when the tower resistance is about 100 ohms
or more.
H. Underground Power Cable Configuration
Two typical cables have been modeled to demonstrate the
fault current distribution. The horizontal and mixed
configurations are shown in Fig. 11.
Fig. 11. Different configurations of the underground cable
The length of the underground cables is 3 km. The
underground cables are modeled as a stranded conductor core
surrounded by a lead sheath. The equivalent relative resistivity
and the relative permeability of the sheaths were derived based
on typical values. The cable is a XLPE insulated cable and the
characteristics used to perform the calculation are as follows:
Cable core: 3500 kcmil copper conductor
Cable overall diameter: 12.8 cm
Copper core diameter: 5.2 cm
Lead sheath: extruded lead, inner diameter = 9.4 cm, and
outer diameter: = 10.5 cm
Lead sheath equivalent relative resistivity (with respect to
copper) and permeability(with respect to free space): 12 and 1
Two ground wires are installed with the underground
cables. The radius of the ground wire is 0.8 cm. The
underground cables are divided into sections (from one vault
location to another). Two ground rods are installed per cable
vault (i.e., every 600 m). The ground resistance is 15 ohms.The computed fault current split factors are 1.6% and 2.2%
for the horizontal and vertical configurations, respectively.
Little change is observed when the overall configurations are
different. This is due to the fact that the mutual coupling
between the sheath and cable core is very strong because of the
small distance between the two conductors. In the case of an
underground cable, the mutual coupling plays a very important
role in the current distribution, as expected.
V. TYPICAL AC INTERFERENCE STUDY
A typical AC interference study that involves an electric
network consisting of overhead lines and underground cablesis presented in this section.
A. Network Description and Computer Model
Fig. 12 shows the plan view of the electrical network under
study.
Fig. 12. Plan view of the electrical network under study
The underground power cables between Substation #1 and
Substation #3 consist of two 345-kV circuits utilizing XLPE
insulated cables. The total length of the underground cables is
37 km and a railroad roughly follows the underground cables
for about 21 km. The overhead portion of the 345-kV
transmission lines between Substation #3 and Substation #7 is
approximately 74 km. A gas pipeline and a railroad share the
same corridor with the 345-kV overhead transmission line for
about 6.4 km, respectively.
The 345-kV transmission line can cause AC interference to
7/28/2019 2.07_I9FP0151_E.pdf
5/6
5
the railway system and pipelines. Especially, the induced
voltages and currents on the railway and pipeline facilities can
result in a shock hazard and threaten the integrity of both
facilities during single phase-to-ground fault conditions.
The complete model consists of the transmission line phase
conductors, static wires, underground cables, rails, rail ballast
resistances, insulating joints, track arresters, rail track circuits,
and railroad equipment house grounds. Various soil structures
have been modeled along the entire common-corridor. In thispaper, the electromagnetic interference under fault conditions
has been analyzed and presented.
The data and characteristics used in the simulations are as
follows:
The overhead line consists of the ACSR phase wires and
Aluminum 7#8 static wires
The underground cable characteristics are the same as in
the previous section
The maximum load current is 1.5 kA per phase for the
new 345 kV line and 1.2 kA per phase for the existing
345 kV line
A 130 lb steel rail was selected and the separationdistance between rails is 1.5 m
The pipeline has a radius of 30 cm and is covered with
coal tar coating
Figs. 13 and 14 show the typical cross sections of the
overhead lines and underground cables.
Fig. 13. Cross section of the underground cable conduit
Fig. 14. Cross section of overhead transmission lines
The touch voltage is one of the important quantities that
should be computed and examined. In this paper, the touch
voltages when a person contacts a rail track or a pipeline when
standing 1 m away on both sides of the rail track or pipeline
are calculated to ensure that safety concerns are addressed.
B. Computation Results
The computation results are summarized here. The worst
rail touch voltage under fault conditions for the underground
cable portion is 94 V only which is below the IEEE Standard
80 safe limit of 519 V based on a 800 ohm-m native soil, as
shown in Fig. 15. The low touch voltage is caused by theproximity of the lead sheath to the underground cable core that
results in a very strong mutual coupling between them. As a
result, most of the fault current is going back to the remote
source through the sheath. As a result, the induced EMF on the
rail is small due to the cancellation effect of the core current
by the sheath current. The induced EMF caused by the ground
conductors paralleling the cable sheath is also small because
little current is flowing into the ground conductors.
Rail Touch Voltages
0
100
200
300
400
500
600
700
0 5000 10000 15000 20000 25000
Distance along Railway in Parallel with the Underground Cable (m)
TouchVoltages(V)
Rail Touch Voltages
Touch Voltage Limit
Fig. 15. Rail touch voltages along the underground cable
The worst rail and pipe touch voltages under fault
conditions for the overhead portion are 2244 V and 1010 V,
respectively. Both of them are above the IEEE Standard 80
safe limit based on various soils along the entire length of the
railway and pipeline. The computation results for the touch
voltages along the rail are shown in Fig. 16. In contrast to the
underground cable situation, a large amount of the fault
current is injected into the tower grounds along the common-
corridor due to the high fault current split factor in the case of
an overhead line with two Aluminum 7#8 static wires.
Maximum Rail Touch Voltages
0
500
1000
1500
2000
2500
0 1000 2000 3000 4000 5000 6000 7000
Distance along Railway in Parallel with the Overhead T/L (m)
TouchVoltages(V)
Rail Touch Voltages
Touch Voltage Limit
Fig. 16. Rail touch voltages along the overhead transmission lines
Therefore, mitigation measures are required on the railway
and pipelines facilities which parallel the overhead
transmission lines.
7/28/2019 2.07_I9FP0151_E.pdf
6/6
6
C. Mitigation Measure
A mitigation measure consisting of three continuous
mitigation wires along the railway and pipeline is presented.
Two continuous mitigation wires bonded to the railway
through track arresters at regular intervals and buried 1 m
away from the edge of the railway are installed along the
exposed railway zone on both sides of the railway. Similarly, a
zinc mitigation wire along the exposed pipeline located about
1 m away from the edge of the pipeline is installed. Themitigation wire is connected to the pipeline through PCR
(Polarization Cell Replacement) or solid-state decoupler
devices. In case of a fault, the continuous mitigation wires
provide additional grounding for the railway and pipeline and
furthermore, act as screening conductors, thus decreasing the
induced pipe and rail potential rise. This measure reduces
interference levels considerably, as can be seen in Fig. 17 for
the rail touch voltages. As a result, the computed rail and pipe
touch voltages have been reduced to less than 250 V and 300
V, respectively, which satisfy the safety design limits.
Maximum Rail Touch Voltages with Mitigation Wires
0
100
200
300
400
500
0 1000 2000 3000 4000 5000 6000 7000
Distance along Railway in Parallel with the Overhead T/L (m)
TouchVoltages(V)
Rail Touch Voltages
Touch Voltage Limit
Fig. 17. Rail touch voltages along the overhead transmission lines with
mitigation wires
VI. CONCLUSIONS
A parametric analysis of the fault current distribution along
electric power transmission network has been conducted.
Effects of the various parameters which influence the fault
current split factor have been studied. The parameters include
power line cross section, length of power lines, tower footing
resistance, station grounding system resistance, types of static
wires, and soil resistivity. All charts, observations, and
computation results offer useful clues to better understanding
of the fault current distribution. Furthermore, a typical study of
electromagnetic interference on railways and pipelines caused
by electrical overhead transmission lines and undergroundcables under fault conditions has been carried out as an
example. This real case study shows how modern
computational approaches can be used to analyze complex
electromagnetic interference issues and produce accurate
results.
VII. REFERENCES
[1] S. Tee, F. P. Dawalibi, and J. Liu, "Influence of current distribution in
enclosed underground power cables on the overheating of the steel
casing enclosure," The International Conference on Electrical
Engineering (ICEE), Kunming, China, July 10 - 14, 2005.
[2] W. K. Daily and F. P. Dawalibi, "Cost reduction and minimization of
land based on an accurate determination of fault current distribution in
neutral conductors,"IEEE Trans. Power Delivery, vol. 8, no. 1, pp. 97-
103, January 1993.
[3] IEEE Guide for Safety in AC Substation Grounding, IEEE Standard 80-
2000.
[4] CDEGS Software Package, Safe Engineering Services & technologies
ltd., Montreal, Quebec, Canada, 2006.
VIII. BIOGRAPHIES
Ms. J. Liu received the B.Eng. and the M. Eng. degree in Electrical
Engineering in 1985 and 1990, respectively. She is presently serving as
scientific researcher at Safe Engineering Services & technologies ltd. Her
research interests are electrical grounding systems, EMC, and various aspects
of electrical power system analysis, modeling, control, and management.
She is the author of more than 30 papers on electrical power system
safety, power quality, EMC, and computer applications.
Dr. F. P. Dawalibi (M'72, SM'82) was born in Lebanon in November
1947. He received a Bachelor of Engineering degree from St. Joseph's
University, affiliated with the University of Lyon, and the M.Sc. and Ph.D.
degrees from Ecole Polytechnique of the University of Montreal. From 1971
to 1976, he worked as a consulting engineer with the Shawinigan Engineering
Company, in Montreal. He worked on numerous projects involving power
system analysis and design, railway electrification studies and specialized
computer software code development.
In 1976, he joined Montel-Sprecher & Schuh, a manufacturer of high
voltage equipment in Montreal, as Manager of Technical Services and was
involved in power system design, equipment selection and testing for systems
ranging from a few to several hundred kV.
In 1979, he founded Safe Engineering Services & technologies, a
company specializing in soil effects on power networks. Since then he has
been responsible for the engineering activities of the company including the
development of computer software related to power system applications.
He is the author of more than 200 papers on power system grounding,
lightning, inductive interference and electromagnetic field analysis. He has
written several research reports for CEA and EPRI.
Dr. Jinxi Ma (M'91, SM'00) was born in Shandong, P. R. China in
December 1956. He received the B.Sc. degree from Shandong University, P.
R. China, and the M.Sc. degree from Beijing University of Aeronautics and
Astronautics, both in electrical engineering, in 1982 and 1984, respectively.
He received the Ph.D. degree in electrical and computer engineering from theUniversity of Manitoba, Winnipeg, Canada in 1991. From 1984 to 1986, he
was a faculty member with the Department of Electrical Engineering, Beijing
University of Aeronautics and Astronautics. He worked on projects involving
design and analysis of reflector antennas and calculations of radar cross
sections of aircraft.
Since September 1990, he has been with the R & D Dept. of Safe
Engineering Services & technologies in Montreal, where he is presently
serving as manager of the Analytical R & D Department. His research
interests are in transient electromagnetic scattering, EMI and EMC, and
analysis of grounding systems in various soil structures.
Dr. Ma has authored and coauthored more than one hundred papers on
transient electromagnetic scattering, analysis and design of reflector antennas,
power system grounding, lightning and electromagnetic interference analysis.
He is a senior member of the IEEE Power Engineering Society, a member of
the IEEE Standards Association, and a corresponding member of the IEEE
Substations Committee and is active on Working Groups D7 and D9Dr. S. Fortin was born in 1962. He received a B. Sc. degree (1985) in
Physics from Laval University, Quebec and a Ph. D. degree (1991) in Physics
from the University of British Columbia, Vancouver. His area of
specialization was in the theoretical aspects of high-energy particle physics.
In 1992-1993, he was a research assistant with the Nuclear Physics
Department at the University of Montreal, again specializing in particle
physics.
He joined Safe Engineering Services & Technologies Ltd. as a research
scientist in 1994. His research interests include the computation of
electromagnetic fields at various frequencies and transient phenomena. Dr.
Simon Fortin has published about 40 papers on lighting, grounding and
electromagnetic fields compatibility related problems.