For detailed material and finish descriptions, see page 6. For other products that fit Itray specifications, look for the Itray Compatible logo on pages 40 thru 57.
raiL
heig
hT (i
N.)
Load
dep
Th (i
N.)
raiL
FLaN
ge (i
N.)
Nema
cLa
SS
cSa c
LaSS
Seri
eSTray SySTem Number amp raTiNg
][—][
87 3
20c+ e, 6m
S2 4823 2000
6 2 1/2 S2 4812 2000
10 8 4 S2 4904 2000
SupporT SpaN (FT.)
20 22 24 26 28 30 34 36 40
SaFe Load daTa (LbS./FT.) / deFLecTioN (iN.) / SaFeTy FacTor 1.5
270 1.88 218 2.22 179 2.58 150 2.98 127 3.39 108 3.81 76 4.44 64 4.70 48 5.31
292 2.00 236 2.37 194 2.75 162 3.17 137 3.60 117 4.05 82 4.69 69 4.97 52 5.70
400 1.15 331 1.39 278 1.66 237 1.94 204 2.25 178 2.59 138 3.32 123 3.73 100 4.60
Trays for extremely heavy loads and long spans have i-beam side rails and are available in lengths up to 50'.
tray system numBer
This identifies the specific tray design and is used as a product number prefix for straight sections.
length0020 – 20'-0"0024 – 24'-0"0030 – 30'-0"0040 – 40'-0"0050 – 50'-0"
Width12 – 12"18 – 18"24 – 24"30 – 30"36 – 36"
Bottom typevented
09 – 9" Rung spacing*12 – 12" Rung spacing18 – 18" Rung spacing* standard rung spacing
long-sPAn sTRAIghT secTIon cATAlog numbeRIng exAmPle:
0 9 - 4 8 2 3 - 0 0 2 0 - 3 6
long-sPAna aLuminum
G hoT-dip gaLvanized STeeL
WIDThs (W) Inches
12 18 24 30 36
RAIl heIghTs (h) Inches
8 10
lengThs (l) FeeT
20 24 30 40 50
raiL
heig
hT (i
N.)
Load
dep
Th (i
N.)
raiL
FLaN
ge (i
N.)
Nema
cLaS
S
cSa c
LaSS
Seri
eS
Tray SySTem Number amp raTiNg
][—][
8 62 1/4
20c+ –
S2 1952 600
4 S2 1953 600
10 5 4 S2 1954† 600
SupporT SpaN (FT.)
20 22 24 26 28 30 32 34 36 38 40 45 50
SaFe Load daTa (LbS./FT.) / deFLecTioN (iN.) / SaFeTy FacTor 1.5
203 0.88 167 1.06 141 1.27 120 1.49 103 1.72 90 1.98 81 2.22 68 2.47 60 2.72 54 3.06 48 3.31
360 0.98 298 1.18 250 1.41 213 1.65 184 1.92 160 2.20 139 2.47 121 2.74 107 3.05 95 3.35 85 3.69 66 4.00 51 5.37
900 1.04 744 1.26 625 1.50 533 1.77 459 2.05 400 2.35 347 2.64 304 2.95 268 3.26 238 3.60 212 3.94 164 4.87 124 5.62
† Fittings not available
connecToRs & FITTIngs:necessary connectors and fasteners are supplied with all trays and fittings. extra connectors for field cuts or spares must be ordered separately.
sAFe loAD:allowable cable load in pounds per linear foot uniformly distributed. based on tray with standard rung on 9" centers and supported on simple beam with safety factor of 1.5 per neMa Ve1.
concenTRATeD loAD:all ladders with solid rungs and trays with corrugated bottoms will support a 200 lb. concentrated load applied at the center of the tray in addition to the neMa-rated cable load without collapse.
SERIES2
fitting side rails have 5" tangents at the end of each fitting, to accommodate splice plates with eight holes.
Ladder
all legrand aluminum and steel cable trays are Classified by ul as equipment grounding conductors per neC 392.60. (ul file no. e60796)
legrand trays marked with Csa load class have been tested (loading, finish and electrical) by ul to Csa standard 126 22.2 .
sPlIces
MeT
all
iC s
TRa
iGH
T se
CTi
on
s –
lon
G-s
Pan
MeT
all
iC s
TRa
iGH
T se
CTi
on
s –
lon
G-s
Pan
PW CABLE TRAYLAddER, TRough
And soLid BoTTom
www.leGRand.us/Cablofil
26
Pw Cable TRayladdeR, TRouGH
and solid boTToM
www.leGRand.us/Cablofil
27
For detailed material and finish descriptions, see page 6. For other products that fit Itray specifications, look for the Itray Compatible logo on pages 40 thru 57.
raiL
heig
hT (i
N.)
Load
dep
Th (i
N.)
raiL
FLaN
ge (i
N.)
Nema
cLaS
S
cSa c
LaSS
Seri
eS
Tray SySTem Number amp raTiNg
[—] ]—[
4 3
1 12c, 16a d, 3m S1 A457 – 100
1 3/4
20a, 16b - S2 1D80 1D81 200
20b, 16c d, 6m S2 1D82 1D83 400
20c e, 6m S2 1D69* 1D70 400
5 4
1 12c, 16a d, 3m S1 1e72 – 100
1 3/420b, 16c - S2 1e45 1e46 400
20c d, 6m S2 1e53* 1e54 400
6 5
1 12c, 16a d, 3m S1 A639 – 100
1 3/420b, 16c e, 6m S2 1F45* 1F46 400
20c e, 6m S2 1F53* 1F54 400
7 6
1 12c, 16a d, 3m S1 1772 – 100
1 3/420b, 16c e, 6m S2 1755* 1756 400
20c e, 6m S2 1753 1754 400
WIDThs (W) Inches
6 9 12 18 24 30 36
RAIl heIghTs (h) Inches
4 5 6 7
lengThs (l) FeeT
10 12 20 24
* 1D69, 1F45, and 1F53 corrugated bottom tray systems have a CSA load class D,6M rating. 1E53 and 1755 corrugated bottom tray systems do not have CSA load class ratings.
connecToRs & FITTIngs:necessary connectors and fasteners are supplied with all trays and fittings. extra connectors for field cuts or spares must be ordered separately.
sAFe loAD:allowable cable load in pounds per linear foot uniformly distributed. based on tray with standard rung on 9" centers and supported on simple beam with safety factor of 1.5 per neMa Ve1.
concenTRATeD loAD:all ladders with solid rungs and trays with corrugated bottoms will support a 200 lb. concentrated load applied at the center of the tray in addition to the neMa-rated cable load without collapse.
tray system numBer
This identifies the specific tray design and is used as a product number prefix for straight sections.
length0010 – 10'-0"0012* – 12'-0"0020† – 20'-0"0024 – 24'-0"* standard for
SERIES 1
† standard for SERIES 2
Width06 – 6"09 – 9"12 – 12"18 – 18"24 – 24"30 – 30"36 – 36"
rung optionadd suffix for non-standard rung. see page 63 for details and other rung options.
Bottom type
sTeel sTRAIghT secTIon cATAlog numbeRIng exAmPle:
0 9 - a 4 5 7 - 0 0 1 2 - 3 6 -producT No.SySTem No.
non-vented
sC† – solid Corrugated* standard rung spacing† not available for
flange out tray
vented06 – 6" Rung spacing09 – 9" Rung spacing*12 – 12" Rung spacing18 – 18" Rung spacing**vC† – Vented Corrugated
sTeelG hoT-dip
gaLvanized STeeL
SupporT SpaN (FT.)
6 8 10 12 14 16 18 20 22 24
SaFe Load daTa (LbS./FT.) / deFLecTioN (iN.) / SaFeTy FacTor 1.5
439 0.31 250 0.55 160 0.86 111 1.24 78 1.61 58 2.06
439 0.20 338 0.51 216 0.79 150 1.14 110 1.55 84 2.02 67 2.56 54 3.16 44 3.74 34 4.07
439 0.16 439 0.50 312 0.88 217 1.26 159 1.72 122 2.25 96 2.84 78 3.51 63 4.18 52 4.87
439 0.39 400 0.87 278 1.25 204 1.70 156 2.21 123 2.80 100 3.46 81 4.09 66 4.77
400 0.21 225 0.38 144 0.59 100 0.85 71 1.13 52 1.40
439 0.11 439 0.37 304 0.62 211 0.90 155 1.22 119 1.59 94 2.02 76 2.49 61 2.92 50 3.38
439 0.34 400 0.75 278 1.08 204 1.47 156 1.92 123 2.43 100 3.00 81 3.54 60 4.13
420 0.13 236 0.22 151 0.35 105 0.50 74 0.65 55 0.83
439 0.08 439 0.25 336 0.47 233 0.68 171 0.92 131 1.20 104 1.52 84 1.88 68 2.24 53 2.47
439 0.20 439 0.50 319 0.75 235 1.02 180 1.34 142 1.69 115 2.09 93 2.48 73 2.75
400 0.10 225 0.18 144 0.28 100 0.40 71 0.53 52 0.66
439 0.07 439 0.22 300 0.38 208 0.54 153 0.73 117 0.96 93 1.22 75 1.50 61 1.79 50 2.08
439 .017 439 0.42 319 0.63 235 0.86 180 1.12 142 1.42 115 1.75 93 2.11 76 2.52
SERIES1
fitting side rails have 2" tangents (flat portion beyond curvature) at the end of each fitting, to accommodate splice plates with four holes.
SERIES2
fitting side rails have 5" tangents at the end of each fitting, to accommodate splice plates with eight holes.
sPlIces Match above to determine the connectors you need.
all legrand steel cable trays are Classified by ul as equipment grounding conductors per neC 392.60. (ul file no. e60796)
legrand trays marked with Csa load class have been tested (loading, finish and electrical) by ul to Csa standard 126 22.2 .
Ladder venTed CorrugaTed SoLid CorrugaTed
MeT
all
iC s
TRa
iGH
T se
CTi
on
s –
sTee
l
MeT
all
iC s
TRa
iGH
T se
CTi
on
s –
sTee
l
PW CABLE TRAYLAddER, TRough
And soLid BoTTom
www.leGRand.us/Cablofil
28
Pw Cable TRayladdeR, TRouGH
and solid boTToM
www.leGRand.us/Cablofil
29
For detailed material and finish descriptions, see page 6. For other products that fit Itray specifications, look for the Itray Compatible logo on pages 40 thru 57.
raiL
heig
hT
(iN.)
Load
dep
Th
(iN.)
raiL
FLaN
ge
(iN.)
Nema
cLaS
S
Seri
eSTray SySTem Number
[—] [—] ]—[ ]—[
4 3
112b S1 3408 3416 – –
12c, 16a S1 3409 3417 – –
1 3/4
20a, 16b S2 3476 3D85 3D63 3D82
20b, 16c S2 3456 3D92 3D93 3D58
20c S2 3406 3445 3407 3446
5 4
112b S1 3504 3514 – –
12c, 16a S1 3505 3515 – –
1 3/420b, 16c S2 3551 3594 3550 3582
20c S2 3587 3593 3592 3583
6 5
112b S1 3603 3620 – –
12c, 16a S1 3604 3621 – –
1 3/420b, 16c S2 3F67 3F85 3F68 3F66
20c S2 3645 3F35 3F58 3F61
7 6
112b S1 3734 3738 – –
12c, 16a S1 3735 3739 – –
1 3/420b, 16c S2 3701 3723 3754 3756
20c S2 3714 3724 3722 3760
SupporT SpaN (FT.)
6 8 10 12 14 16 18 20 22 24
SaFe Load daTa (LbS./FT.) / deFLecTioN (iN.) / SaFeTy FacTor 1.5
300 0.30 169 0.54 108 0.85 75 1.22
400 0.32 225 0.57 144 0.90 100 1.29 71 1.71 52 2.13
556 0.31 313 0.55 200 0.86 139 1.24 102 1.69 78 2.20 62 2.79 50 3.44
564 0.24 469 0.62 300 0.97 208 1.39 153 1.89 117 2.47 93 3.13 75 3.70 86 4.60 48 5.13
564 0.54 400 0.94 278 1.36 204 1.85 156 2.41 123 3.05 100 3.77 81 4.45 63 4.96
300 0.20 169 0.35 108 0.55 75 0.79
400 0.23 225 0.41 144 0.64 100 0.93 71 1.23 52 1.53
564 0.16 469 0.42 300 0.66 208 0.95 153 1.29 117 1.69 93 2.14 75 2.64 61 3.14 48 3.51
564 0.46 400 0.80 278 1.16 204 1.57 156 2.05 123 2.60 100 3.21 81 3.79 63 4.22
300 0.11 169 0.20 108 0.31 75 0.45
400 0.14 225 0.24 144 0.38 100 0.54 71 0.71 52 0.89
564 0.12 469 0.32 300 0.51 208 0.73 153 0.99 117 1.30 93 1.64 75 2.03 61 2.42 48 2.70
564 0.31 400 0.54 278 0.77 204 1.05 156 1.38 123 1.74 100 2.15 81 2.54 63 2.83
300 0.10 169 0.17 108 0.27 75 0.39
400 0.11 225 0.19 144 0.30 100 0.43 71 0.57 52 0.71
564 0.10 469 0.26 300 0.41 208 0.58 153 0.79 117 1.04 93 1.31 75 1.62 61 1.93 48 2.15
564 0.28 400 0.48 278 0.69 204 0.93 156 1.22 123 1.55 100 1.91 81 2.05 63 2.28
tray system numBer
This identifies the specific tray design and is used as a product number prefix for straight sections.
length0010 – 10'-0"0012* – 12'-0"0020† – 20'-0"0024 – 24'-0"* standard for
SERIES 1
† standard for SERIES 2
Width06 – 6"09 – 9"12 – 12"18 – 18"24 – 24"30 – 30"36 – 36"
rung optionadd suffix for non-standard rung. see page 63 for details and other rung options.
Bottom typevented
06 – 6" Rung spacing09 – 9" Rung spacing*12 – 12" Rung spacing18 – 18" Rung spacing
non-ventedsf† – solid flat bottom* standard rung spacing† not available with
flange out tray
sTAInless sTeel sTRAIghT secTIon cATAlog numbeRIng exAmPle:
0 9 - 3 6 2 0 - 0 0 1 2 - 1 8 -
WIDThs (W) Inches
6 9 12 18 24 30 36
RAIl heIghTs (h) Inches
4 5 6 7
lengThs (l) FeeT
10 12 20 24
connecToRs & FITTIngs:necessary connectors and fasteners are supplied with all trays and fittings. extra connectors for field cuts or spares must be ordered separately.
sAFe loAD:allowable cable load in pounds per linear foot uniformly distributed. based on tray with standard rung on 9" centers and supported on simple beam with safety factor of 1.5 per neMa Ve1.
concenTRATeD loAD:all ladders with solid rungs and trays with corrugated bottoms will support a 200 lb. concentrated load applied at the center of the tray in addition to the neMa-rated cable load without collapse.
sTAInlesssTeel
l STainLeSS STeeLaIsI Type 304l
t STainLeSS STeeLaIsI Type 316l
SERIES1
fitting side rails have 2" tangents (flat portion beyond curvature) at the end of each fitting, to accommodate splice plates with four holes.
SERIES2
fitting side rails have 5" tangents at the end of each fitting, to accommodate splice plates with eight holes.
sPlIces Match above to determine the connectors you need.
SoLid BoTTomLadder
MeT
all
iC s
TRa
iGH
T se
CTi
on
s –
sTa
inle
ss s
Teel
MeT
all
iC s
TRa
iGH
T se
CTi
on
s –
sTa
inle
ss s
Teel
PW CABLE TRAYLAddER, TRough
And soLid BoTTom
www.leGRand.us/Cablofil
30
Pw Cable TRayladdeR, TRouGH
and solid boTToM
www.leGRand.us/Cablofil
31