A-1
Western Area Power Administration Sierra Nevada Region
2011 Annual Ten-Year Transmission Plan Assessment
Report
Report Attachment 4 NERC Planning Standard TPL-002
November 11, 2011
For information or questions regarding this Transmission Assessment Report, please contact Larry Tobias via (916) 353-4766 or email at [email protected]
A-2
Attachment 4: Category B (NERC Planning Standard TPL-002): Single Element Outage, (N-1) Includes Power Flow, Post-Transient and Dynamic Stability Plots)
A-3
Figure 4-1 2012 Summer Peak One Shasta-Cottonwood 230 kV Line Outage
One Shasta Bus
A-4
Figure 4-2 2012 Summer Peak One Shasta-Cottonwood 230 kV Line Outage Split Shasta Bus
A-5
Figure 4-3 2012 Summer Peak One Shasta-Flanagan 230 kV Line Outage One Shasta Bus – Normal Rating
A-6
Figure 4-4 2012 Summer Peak One Shasta-Flanagan 230 kV Line Outage
One Shasta Bus – Emergency Rating
A-7
Figure 4-5 2012 Summer Peak One Shasta-Flanagan 230 kV Line Outage
One Shasta Bus – Cottonwood Jumpers Replaced – Normal Rating
A-8
Figure 4-6 2012 Summer Peak Captain Jack-Olinda 500 kV Outage
Max. Northern Calif. Hydro Gen
A-9
Figure 4-7 2012 Summer Peak Captain Jack-Olinda 500 kV Outage
70% Northern Calif. Hydro Gen
A-10
Figure 4-8 2012 Summer Peak Sutter Power Plant out – B1 Outage
A-11
Figure 4-9 2012 Summer Peak Keswick-Olinda 230 kV out – B2 Outage
A-12
Figure 4-10 2012 Summer Peak Tracy 500/230 kV Bank out – B3 Outage
A-13
Figure 4-11 2016-17 Winter Peak Sutter PP out – B1 Outage
A-14
Figure 4-12 2016-17 Winter Peak Keswick-O’Banion 230 kV B2 Outage
A-15
Figure 4-13 2016-17 Winter Peak Tracy 500/230 kV Bank B3 Outage
A-16
Figure 4-14 2016 Summer Peak Sutter PP Unit Outage B1 Outage
0.8
0.85
0.9
0.95
1
1.05
‐600 ‐500 ‐400 ‐300 ‐200 ‐100 0 100
2016 Summer PeakElverta 230 kV Bus Voltage ‐ Sutter PP Outage
Elverta 230 kV Bus Voltage ‐ Sutter PP Outage
A-17
Figure 4-15 2016 Summer Peak Keswick_O’Banion 230 kV line Outage – B2 Outage
0.82
0.84
0.86
0.88
0.9
0.92
0.94
0.96
0.98
1
1.02
‐600 ‐500 ‐400 ‐300 ‐200 ‐100 0
2016 Summer Peak Keswick‐O'Banion 230 kV Line Outage
2016 Summer Peak Keswick‐O'Banion 230 kV Outage
A-18
Figure 4-16 2016 Summer Peak Tracy 500/230 kV Transformer bank Outage – B3 Outage
0.8
0.85
0.9
0.95
1
1.05
‐700 ‐600 ‐500 ‐400 ‐300 ‐200 ‐100 0
2016 Summer PeakElverta 230 kV Bus Voltage ‐ Tracy 500/230 kV Bank Outage
Elverta 230 kV Bus Voltage ‐ Tracy 500/230 kV Bank Outage
A-19
Figure 4-17 2021 Summer Peak Sutter PP Unit Outage B1 Outage
0.85
0.86
0.87
0.88
0.89
0.9
0.91
0.92
0.93
0.94
0.95
0.96
‐80 ‐70 ‐60 ‐50 ‐40 ‐30 ‐20 ‐10 0
2021 Summer PeakElverta 230 kV Bus Voltage ‐ Sutter PP Outage
Elverta 230 kV Bus Voltage ‐Sutter PP Outage
A-20
Figure 4-18 2021 Summer Peak Keswick_O’Banion 230 kV line Outage – B2 Outage
0.84
0.86
0.88
0.9
0.92
0.94
0.96
0.98
‐180 ‐160 ‐140 ‐120 ‐100 ‐80 ‐60 ‐40 ‐20 0
2021 Summer PeakKeswick‐O'Banion 230 kV Line Outage
2021 Summer Peak Keswick‐O'Banion 230 kV Line Outage
A-21
Figure 4-19 2021 Summer Peak Tracy 500/230 kV Transformer bank Outage – B3 Outage
0.84
0.86
0.88
0.9
0.92
0.94
0.96
0.98
1
‐250 ‐200 ‐150 ‐100 ‐50 0 50
2021 Summer PeakElverta 230 kV Bus Voltage Tracy 500/230 kV Bank Outage
2021 Summer Peak Elverta 230 kV Bus Voltage Tracy 500/230 kV Bank Outage
A-22
Figure 4-20 2016 Light Autumn Sutter PP Unit Outage B1 Outage
0.6
0.7
0.8
0.9
1
1.1
‐1200 ‐1000 ‐800 ‐600 ‐400 ‐200 0 200
2016 Light Autumn Elverta 230 kV Voltage ‐ Sutter PP Unit Outage
2016 Light Autumn Elverta 230 kV Voltage ‐Sutter PP Unit Outage
A-23
Figure 4-21 2016 Light Autumn Keswick-O’Banion 230 kV Line Outage B2 Outage
0.6
0.7
0.8
0.9
1
1.1
‐1400 ‐1200 ‐1000 ‐800 ‐600 ‐400 ‐200 0
2016 Light Autumn Keswick‐O'Banion 230 kV Line Outage
2016 Light Autumn Keswick‐O'Banion 230 kV Line Outage
A-24
Figure 4-22 2016 Light Autumn Tracy 500/230 kV Bank Outage B3 Outage
0.6
0.7
0.8
0.9
1
1.1
‐1400 ‐1200 ‐1000 ‐800 ‐600 ‐400 ‐200 0
2016 Light Autumn Elverta 230 kV Bus Voltage Tracy 500/230 kV Bank Outage
2016 Light Autumn Elverta 230 kV Bus Voltage Tracy 500/230 kV …
A-25
Figure 4-23 2016 Summer Peak Sutter PP Unit Outage B1 Outage
A-26
Figure 4-24 2016 Summer Peak Keswick_O’Banion 230 kV line Outage – B2 Outage
A-27
Figure 4-25 2016 Summer Peak Tracy 500/230 kV Transformer bank Outage – B3 Outage
A-28
Figure 4-26 2021 Summer Peak Sutter PP Unit Outage B1 Outage
A-29
Figure 4-27 2021 Summer Peak Keswick_O’Banion 230 kV line Outage – B2 Outage
A-30
Figure 4-28 2021 Summer Peak Tracy 500/230 kV Transformer bank Outage – B3 Outage
A-31
Figure 4-29 2016 Light Autumn Sutter PP Unit Outage B1 Outage
A-32
Figure 4-30 2016 Light Autumn Keswick-O’Banion 230 kV Line Outage B2 Outage
A-33
Figure 4-31 2016 Light Autumn Tracy 500/230 kV Transformer Bank Outage B3 Outage