2006.02.08 Fault Localization

  • Upload
    vda

  • View
    218

  • Download
    0

Embed Size (px)

Citation preview

  • 8/22/2019 2006.02.08 Fault Localization

    1/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Fault Localization in High Voltage Cable with

    VLF Power SupplyMaster Thesis

    Beat Schwaller

    Telecommunications, Networks and Security

    Department of Computer ScienceUniversity of Fribourgand PDTech AG Neuenhof

    7.2.2006

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

  • 8/22/2019 2006.02.08 Fault Localization

    2/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Outline

    1 Introduction

    2 Physics

    3 Development

    4

    Schedule

    5 Conclusion

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

  • 8/22/2019 2006.02.08 Fault Localization

    3/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Topic

    The goal of this master thesis is to produce a softwarebased portable (low cost) measurement instrument for

    localizing weak spot of high power cable insulation.

    Supported by PDTech AG

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

  • 8/22/2019 2006.02.08 Fault Localization

    4/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Motivation

    Replacement of underground cables is expensive

    Detecting weak spot in cable insulation allows local

    reparation

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

  • 8/22/2019 2006.02.08 Fault Localization

    5/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    What is PD?

    Partial discharges are caused by local irregularity/defect of

    insulation material

    The capacitance in such locations is much less than of the

    surrounding insulation

    Applying high voltage, partial discharges appear

    Figure: Partial Discharge Pattern. Source: [1]

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    I d i

  • 8/22/2019 2006.02.08 Fault Localization

    6/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Why VLF 0,1 Hz?

    For field-test, the power supply should be portableA very low frequency (0,1Hz) power supply offers a

    compact portable design of test equipment

    Low power requirement I= U 2 f C

    (500 times less power than a regular 50Hz power supply)

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    I t d ti

  • 8/22/2019 2006.02.08 Fault Localization

    7/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    How to localize fault location?

    Analyze the PD reflections against the velocity of

    propagation of the signals and cable length

    Figure: Reflectometry. Source: [1]

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    Introduction

  • 8/22/2019 2006.02.08 Fault Localization

    8/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Workflow

    Development of a base application (I/O handling,calibration, etc)

    Module for manual fault location detection (prototype)

    Module for automatic detection (signal analyzing)

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    Introduction

  • 8/22/2019 2006.02.08 Fault Localization

    9/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Development

    Picoscope (USB Oscilloscope)

    LabView 7.1 (Graphical programming language)

    Coupling capacitors

    VLF power supply

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    Introduction

  • 8/22/2019 2006.02.08 Fault Localization

    10/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Screenshot PD Analyzer

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    Introduction

  • 8/22/2019 2006.02.08 Fault Localization

    11/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Schedule

    first draft for a timeschedule

    20.2. - 25.2. Testmeasurement in Ludwigshafen (AVISO)

    3 weeks development of base application for manual

    measurement

    5 weeks development and implementation of automatic

    signal detection

    Testing and debugging

    Documentation

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    Introduction

  • 8/22/2019 2006.02.08 Fault Localization

    12/13

    Introduction

    Physics

    Development

    Schedule

    Conclusion

    Conclusion

    In a first draft, the system should detect weak spots in

    cable insulation

    Problems may arise when multiple discharges are detected

    at the same time

    The feasibility of detecting weak spots in a composite

    cable system is not ensured

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply

    Introduction

  • 8/22/2019 2006.02.08 Fault Localization

    13/13

    Physics

    Development

    Schedule

    Conclusion

    Bibliography

    [1] M. de Nigris; G. Rizzi, et al. : CABLEDIAGNOSIS BASED ON DEFECT LOCATION

    AND CHARACTERIZATION THROUGH PARTIAL

    DISCHARGE MEASUREMENTS, Cesi (Cigre

    15-109 session 2002).

    Beat Schwaller Fault Localization in High Voltage Cable with VLF Power Supply