2001, 20022001, 2002& 3012 Series& 3012 Series
OperationOperation(See Installation and Operation Manual for detailed instructions)
2
WaterTank
WaterPump
MultipleDischarges
2000 Series
Line Strainer
FoamTank
Electronic DirectElectronic DirectInjection ProportionerInjection Proportioner
Check Valves
FlowMeter
3
WaterTank
WaterPump
Flowmeter
Line Strainer
FoamTank
Electronic DirectElectronic DirectInjection ProportionerInjection Proportioner
Check Valves
MultipleDischarges
3012 Model
4
• Digital display reads “Hypro” upon initial power-up
• System then enters flow mode in standby– Operates as flowmeter
Digital Display OperationDigital Display Operation
5
• Push red “FOAM” button to arm system– “ON” light illuminates
• Open foam discharge– Displays solution volume– “ON” light blinks when foam
pump runs
Digital Display OperationDigital Display Operation
6
• Water flow display
• Push “SELECT” button and total volume of water discharged is displayed– Gallons, liters, imperial
gallons
Digital Display OperationDigital Display Operation
7
• Push “SELECT” button to enter “%” mode– Displays default injection
percentage– “PA” Single tank system
– “PC” Remote start/stop
(“UP” or “DOWN” button will override default setting)
Digital Display OperationDigital Display Operation
8
Digital Display OperationDigital Display Operation
• Push “SELECT” button to enter “TOTAL FOAM”– Displays total concentrate
injected
• Dual-tank mode– Totals for each tank– Display corresponds to tank
chosen by dual-tank valve
9
Digital Display OperationDigital Display Operation
• Enter “INJECTION PERCENTAGE” from any mode– Press either “UP” or “DOWN”
button momentarily to display current percentage setting
– Hold either button for two seconds to change setting accordingly
10
Operating Instructions Operating Instructions System ResetSystem Reset
Total Water %(Percent) Total Foam
• Reset these modes to 0 or % to default setting• Push both the up and down buttons in desired mode
11
Size Max Accuracy Max OperatingTee Flow Range Flow Range1-1/2x1" 5 - 110 gpm 3 - 145 gpm
1-1/2" 10 - 320 gpm 3 - 380 gpm
2" 15 - 520 gpm 5 - 625 gpm
2-1/2" 20 - 750 gpm 8 - 900 gpm
3" 30 -1150 gpm 12-1380 gpm
4" 55 -1980 gpm 20 -2380 gpm
FlowmeterFlowmeter
• No flow restrictions• Wide operating range
13
• When Lo con is Displayed
– Selected foam concentrate tank is getting low
– If foam concentrate is added within 2 minutes Lo con goes out
– If no foam concentrate is added within 2 minutes no con is displayed
• When no con is Displayed
– Foam concentrate pump will not run
– Add foam concentrate until no con display goes out then push Red Foam button to start the foam pump
Low Foam DisplayLow Foam Display
14
Exceeding Foam Injection RateExceeding Foam Injection Rate
• Hi Flo display– Occurs when the water flow and
selected foam concentrate injection percentage exceeds the foam pump capabilities
– Informs pump operator when this situation occurs
– Lower the foam concentrate injection percentage or water flow to stop the flashing Hi Flo display
15
Motor DriverMotor Driver
• Module controls pump motor
• Totally enclosed environmentally sealed
• Incorporates system circuit breaker
16
Digital Display OperationDigital Display Operation
• Simulated flow– While in “FLOW” mode, push
both lower buttons simultaneously
– Three bars on left indicate manual mode
– Pushing red “FOAM” button will turn foam pump on/off
– Pump injects to simulated flow default setting
17
System Air PurgeSystem Air Purge
• Enter “SIMULATED FLOW”
• Turn injection valve from “INJECT” to “CAL/FLUSH”
• Push red “FOAM” button on display to start foam pump
18
System Air Purge System Air Purge (cont.)(cont.)
• Run until concentrate flows steady out of dump line
• Push red “FOAM” button to stop pump
• Turn injection valve to “INJECT”
• Exit “SIMULATED FLOW”
20
2000 Series Foam Pump2000 Series Foam Pump
• Totally enclosed environmentally sealed motor
• Housing incorporates speed sensor
• Positive displacement plunger pump– Components made of
corrosion resistant materials
– Max operating pressure is 400 psi
21
3012 Foam Pump3012 Foam Pump
• Hydraulic motor• Housing incorporates
speed sensor• Positive displacement
plunger pump– Components made of
corrosion resistant materials
– Max operating pressure is 400 psi
22
System MaintenanceSystem Maintenance
• Clean strainer(s) regularly– Purge pump to remove
air pockets afterwards
• Check oil level– Dip stick reading
or– Sight glass
26
Digital Display OperationDigital Display Operation
• Dual-tank function– Dual-tank valve in “A”– Displays “PA” and default
setting
– Dual-tank valve in “B”– Displays “Pb” and default
setting
• Default settings from 0.1 to 6.0%
28
Dual-Tank FlushDual-Tank Flush
• System does not require flushing after Class A foam use– Turn off and flush hose
• Flush after using Class B foam– Flow water and engage
foam system– Turn manual valve to
“FLUSH” or electric valve to “OFF”
(“Off” position is a constant flush)