20
20 + years experience Innovative distributor engineering - metering flow with cost effective Danfoss support in design and sourcing Al aluminum distributors Engineering for today’s needs - superior resistance to corrosion and 66% lighter than copper Product Catalog Go with the advanced flow Value-added engineering expertise Danfoss high quality distributors and flow controls, type RD MAKING MODERN LIVING POSSIBLE

20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

Embed Size (px)

Citation preview

Page 1: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

20+years experience

Innovative distributor engineering - metering flow with cost effective Danfoss support in design and sourcing

Alaluminum distributors

Engineering for today’s needs - superior resistance to corrosion and 66% lighter than copper

Product Catalog

Go with the advanced flow Value-added engineering expertiseDanfoss high quality distributors and flow controls, type RD

MAKING MODERN LIVING POSSIBLE

Page 2: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

2 DKRCC.PK.FF0.A1.22 / 520H6635

Product Catalog Danfoss Distributor Product Program

Page 3: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

DKRCC.PK.FF0.A1.22 / 520H6635 3

Product Catalog Danfoss Distributor Product Program

RD 3863 Series Copper-Brass Distributor with Brass Piston................................................................... 4

Features ................................................................................................................................................................... 4

Ordering options .................................................................................................................................................. 5

RD 3863 Series Aluminum Distributor with Brass Piston. ....................................................................... 6

Features ................................................................................................................................................................... 6

Ordering options .................................................................................................................................................. 7

RD 5271 Series TXV Style Copper-Brass Distributor .................................................................................. 8

Features ................................................................................................................................................................... 8

Ordering options .................................................................................................................................................. 9

RD 5271 Series TXV Style Aluminum Distributor ................................................................................... 10

Features ................................................................................................................................................................ 10

Ordering options ............................................................................................................................................... 11

RD 5500 Series Venturi Style Copper-Brass Distributor ....................................................................... 12

Features ................................................................................................................................................................ 12

Ordering options ............................................................................................................................................... 13

RD 5500 Series Nozzle Distributor ............................................................................................................... 14

Features ................................................................................................................................................................ 14

Ordering options ............................................................................................................................................... 15

RD 6500 Series Hot Gas Bypass Style Distributor .................................................................................. 16

Features ................................................................................................................................................................. 16

Ordering options ............................................................................................................................................... 17

Piston Orifice Selection Chart ........................................................................................................................ 18

Contents Page

Page 4: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

4 DKRCC.PK.FF0.A1.22 / 520H6635

Product Catalog RD 3863 Series Copper-Brass Distributor with Brass Piston

Introduction

Features

Applications

Technical Data

The Danfoss Eliminator-Distributor with the Chatleff Omni-Direct closure is the market leading cost effective distribution solution for HVAC. The Chatleff Omni-Direct Closure allows easy interchange of piston and/or expansion valve. In use, the Danfoss

Special Orifice piston allows metered flow in the cooling cycle. In the heating cycle for heat pumps, the refrigerant by-passes the metering by flowing around the piston using the flutes.

y Chatleff Omni-Direct Closure to insure 5 – 10 years of reliability on the mechanical connection, with a replaceable Teflon seal

y Precise metering for Eliminator-Distributors, thru the unique piston with teflon seal permitting superior seating during both heat pump and cooling cycles obtaining extremely repeatable and predictable expansion and distribution from cycle to cycle

y Designed and engineered to work with any size system

y Piston may be replaced to adjust flow and pressure drop

y This distributor also designed for use with a Thermostatic Expansion Valve (TXV) or Electronic Expansion Valve (EEV)

y Qualified for use with Danfoss TR6 TXV mechanical connection with long-tail fitting

y Low unit mass reduces tube fatigue from vibration

y U.L. listed. file No. SA 3449

y The Danfoss Eliminator-Distributor is designed to retrofit from piston expansion to TXV/EEV expansion or vice-versa

RD 3863 Series RD 3863 Series Internal detail

For all multi-circuited HVAC and refrigeration heat exchangers used in residential and light commercial applications.

Construction

Body: Brass

Feeder Tubes: Copper

Piston:Extruded Brass

Teflon seated

Inlet tube: Copper

Nut: Brass

Seal: Teflon

Static Pressure

Burst: 2500 psi

Rated Working Pressure: 500 psi

Max Operating Temp: 450 °F (232 °C)

Refrigerant compatibility

Standard refrigerants:

R134a, R22, R404A / R507, R407C, and R410A

Page 5: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

A

B

C

D

E

DKRCC.PK.FF0.A1.22 / 520H6635 5

Product Catalog RD 3863 Series Copper-Brass Distributor with Brass Piston

Ordering To order, indicate option choices for the following:

y Inlet option (Brass/Copper) (see fig. A)

y Piston Orifice Size

y Feeder Tube OD (Outside Diameter)

y Number of Circuits

y Feeder Tube Length

y Feeder Tube End Form

Ordering options

Straight Expanded Bell

Brazed on Bell

Fig. E

Please make your selections in the column or space provided and fax or email your sales representative.

Contact your Danfoss sales representative for custom options.

Fig. A

Inlet option liquid line connection Indicate

Choice:ODM 3/8 ODF 3/8 Tube Length3.875 in 3.375 in Long

3.375 in 3.0 in Medium

2.5 in 2.5 in Standard

N/A 1.125 in Short

Filter/strainer option available

Fig. B

Piston Orifice Size Indicate Choice:

see chart on page 18 Orifice No.

Fig. C

Feeder Tube ength Indicate Choice:

Available from 8 – 44 in (in increments of 2 in) Length:

Fig. D

Feeder Tube OD – Number of Circuits

Indicate Choice:

0.144 in x 0.028 in Wall – 2 to 14 circuits

0.157 in x 0.028 inWall – 2 to 12 circuits

0.188 in x 0.028 in Wall – 2 to 12 circuits

0.250 in x 0.028 in Wall – 2 to 6 circuits

Feeder Tube End Form Indicate Choice:

0.144 in – straight no end form

0.144 in – expanded Bell – 0.310 in OD

0.144 in – brazed on Bell – 0.375 in OD

0.157 in – straight no end form

0.157 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.375 in OD

0.188 in – straight no end form

0.250 in – straight no end form

Name Job Title:

Company: Phone:

Email:

Address:

Quantity:

Comments:

Contact Information:

OD – Outside Diameter

Page 6: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

6 DKRCC.PK.FF0.A1.22 / 520H6635

Product Catalog RD 3863 Series Aluminum Distributor with Brass Piston

Introduction

Features

Applications

Technical Data

The Danfoss Eliminator-Distributor with the Chatleff Omni-Direct closure is the market leading cost effective distribution solution for HVAC. The Chatleff Omni-Direct Closure allows easy interchange of piston and/or expansion valve.In use, the Danfoss Special Orifice piston allows metered flow in the cooling cycle.In the heating cycle

for heat pumps, the refrigerant by-passes the metering by flowing around the piston using the flutes. Additionally, the aluminum alloy eliminates leaks caused by formicary corrosion. The Danfoss Aluminum RD 3863 aligns well with the industry trend to convert into all aluminum indoor coils.

y Copper inlet tube for easy field connection and service

y Chatleff Omni-Direct Closure to insure 5 – 10 years of reliability on the mechanical connection, with a replaceable Teflon seal

y Precise metering for Eliminator-Distributors, thru the unique piston with teflon seal permitting superior seating during both heat pump and cooling cycles obtaining extremely repeatable and predictable expansion and distribution from cycle to cycle

y Aluminum Body and feeder tubes to provide excellent resistance against formicary corrosion (ant nest corrosion)

y Designed and engineered to work with any size system

y Piston may be replaced to adjust flow and pressure drop

y This distributor can be used with a Thermostatic Expansion Valve (TXV) or Electronic Expansion Valve (EEV)

y Qualified for use with Danfoss TR6 TXV mechanical connection with long-tail fitting.

y Reduced weight compared to the Copper-Brass distributors

y U.L. listed. file No. SA 3449

y The Danfoss Eliminator-Distributor is designed to retrofit from piston expansion to TXV/EEV expansion or vice-versa

RD 3863 Series RD 3683 Series Internal detail

For all multi-circuited HVAC and refrigeration heat exchangers used in residential and light commercial applications.

Construction

Body: Aluminum

Feeder Tubes: Aluminum

Piston:Extruded Brass

Teflon seated

Inlet tube: Copper

Nut: Brass

Seal: Teflon

Static Pressure

Burst: 2500 psi

Rated Working Pressure: 500 psi

Max Operating Temp: 450 °F (232 °C)

Refrigerant compatibility

Standard refrigerants:

R134a, R22, R404A / R507, R407C, and R410A

Page 7: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

A

B

C

D

E

DKRCC.PK.FF0.A1.22 / 520H6635 7

Product Catalog RD 3863 Series Aluminum Distributor with Brass Piston

Ordering To order, indicate option choices for the following:

y Inlet option (Brass/Copper) (see fig. A)

y Piston Orifice Size

y Number of Circuits

y Feeder Tube Length

y Feeder Tube End Form

Ordering options

Straight Expanded Bell

Please make your selections in the column or space provided and fax or email your sales representative.

Contact your Danfoss sales representative for custom options.

Fig. A

Inlet option liquid line connection Indicate

Choice:ODM 3/8 ODF 3/8 Tube Length

3.875 in 3.375 in Long

3.375 in 3.0 in Medium

2.5 in 2.5 in Standard

N/A 1.125 in Short

Filter/strainer option available

Fig. D

Feeder Tube OD – Number of Circuits

Indicate Choice:

0.188 in x 0.038 in Wall – 2 to 10 circuits

0.188 in x 0.050 in Wall – 2 to 10 circuits

Fig. E

Feeder Tube End Form Indicate Choice:

0.188 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.375 in OD

0.188 in – straight no end form

Contact Information:

OD – Outside Diameter

Fig. B

Fig. C

Name Job Title:

Company: Phone:

Email:

Address:

Quantity:

Comments:

Feeder Tube ength Indicate Choice:

Available from 8 – 44 in (in increments of 2 in) Length:

Piston Orifice Size Indicate Choice:

see chart on page 18 Orifice No.

Page 8: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

8 DKRCC.PK.FF0.A1.22 / 520H6635

Product Catalog RD 5271 Series TXV Style Copper-Brass Distributor

Introduction

Features

Applications

Technical Data

The Thermostatic Expansion Valve (TXV) Style Copper-Brass Distributor is designed with an industry unique chamber enhancing active turbulence and improving even distribution of two phase refrigerants to each circuit.

Designed with the Chatleff Omni-Direct Closure for easy installation and service of TXV’s.

y Chatleff Omni-Direct Closure to insure 5 – 10 years of reliability on the mechanical connection, with a replaceable Teflon seal

y Designed and engineered to work with any size refrigeration system

y Can be mounted in any direction

y Operates effectively in both high andlow pressure systems

y Available with full assemblies with Thermostatic Expansion Valve (TXV) or Electronic Expansion Valve (EEV)

y Qualified for use with Danfoss TR6 valve mechanical connection with short-tail fitting

y UL Listed, File no. SA 3449

RD 5271 Series RD 5271 Series Internal detail

For all multi-circuited HVAC and refrigeration heat exchangers used in residential and light commercial applications.

Construction

Body: Brass

Feeder Tubes: Copper

Threads: UNF 3/4-20

To be used with approved Teflon Seal

Static Pressure

Burst: 2500 psi

Rated Working Pressure: 500 psi

Max Operating Temp: 450 °F (232 °C)

Refrigerant compatibility

Standard refrigerants:

R134a, R22, R404A / R507, R407C, and R410A

Page 9: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

A

B

C

D

E

DKRCC.PK.FF0.A1.22 / 520H6635 9

Product Catalog RD 5271 Series TXV Style Copper-Brass Distributor

Ordering To order, indicate option choices for the following:

y Inlet option (Brass/Copper) (see fig. A)

y Feeder Tube OD (Outside Diameter)

y Number of Circuits

y Feeder Tube Length

y Feeder Tube End Form

Ordering options

Fig. E

Please make your selections in the column or space provided and fax or email your sales representative.

Contact your Danfoss sales representative for custom options.

Fig. A

Inlet option liquid line connection Indicate

Choice:ODM 3/8 ODF 3/8 Tube Length

3.875 in 3.375 in Long

3.375 in 3.0 in Medium

2.5 in 2.5 in Standard

N/A 1.125 in Short

Screen option available

Fig. B

Distributor Connection

Omni Direct Mechanical Connection

Fig. D

Feeder Tube OD – Number of Circuits

Indicate Choice:

0.144 in x 0.028 in Wall – 2 to 10 circuits

0.188 in x 0.028 in Wall – 2 to 8 circuits

Feeder Tube End Form Indicate Choice:

0.144 in – straight no end form

0.144 in – expanded Bell – 0.310 in OD

0.144 in – brazed on Bell – 0.375 in OD

0.188 in – straight no end form

0.188 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.375 in OD

Contact Information:

OD – Outside Diameter

Straight Expanded Bell

Brazed on Bell

Fig. C

Name Job Title:

Company: Phone:

Email:

Address:

Quantity:

Comments:

Feeder Tube ength Indicate Choice:

Available from 8 – 44 in (in increments of 2 in) Length:

Page 10: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

10 DKRCC.PK.FF0.A1.22 / 520H6635

Product Catalog RD 5271 Series TXV Style Aluminum Distributor

Introduction

Features

Applications

Technical Data

The RD 5271 Series Thermostatic Expansion Valve (TXV) Style Aluminum Distributor is designed with an industry unique chamber enhancing active turbulence and improving even distribution of each circuit.

Designed with the Chatleff Omni-Direct Closure for easy installation and service of TXV’s.

y Chatleff Omni-Direct Closure to insure 5 – 10 years of reliability on the mechanical connection, with a replaceable Teflon seal

y Designed and engineered to work with any size residential system

y Can be mounted in any direction

y Operates effectively in both high and low pressure systems

y Aluminum Body and feeder tubes to provide excellent resistance against formicary corrosion

y Available with full assemblies with TXV or EEV

y Qualified for use with Danfoss TR6 TXV mechanical connection with short-tail fitting

y UL Listed, File no. SA 3449

RD 5271 TXV Series RD 5271 TXV Series Internal detail

For all multi-circuited HVAC and refrigeration heat exchangers used in residential and light commercial applications.

Construction

Body: Aluminum

Feeder Tubes: Aluminum

Threads: UNF 3/4-20

To be used with approved Teflon Seal

Static Pressure

Burst: 2500 psi

Rated Working Pressure: 500 psi

Max Operating Temp: 450 °F (232 °C)

Refrigerant compatibility

Standard refrigerants:

R134a, R22, R404A / R507, R407C, and R410A

Page 11: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

A

B

C

D

E

Straight Expanded Bell

DKRCC.PK.FF0.A1.22 / 520H6635 11

Product Catalog RD 5271 Series TXV Style Aluminum Distributor

Ordering To order, indicate option choices for the following:

y Inlet option

y Feeder Tube OD (Outside Diameter) and wall thickness

y Number of Circuits

y Tube Length

y End Form

Ordering options

Fig. E

Please make your selections in the column or space provided and fax or email your sales representative.

Contact your Danfoss sales representative for custom options.

Fig. A

Inlet option liquid line connection Indicate

Choice:ODM 3/8 ODF 3/8 Tube Length

3.875 in 3.375 in Long

3.375 in 3.0 in Medium

2.5 in 2.5 in Standard

N/A 1.125 in Short

Filter/strainer option available

Fig. B

Distributor Connection

Omni Direct Mechanical Connection

Fig. D

Feeder Tube OD – Number of Circuits

Indicate Choice:

0.188 in x 0.038 in Wall – 2 to 10 circuits

0.188 in x 0.050 in Wall – 2 to 10 circuits

Feeder Tube End Form Indicate Choice:

0.188 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.375 in OD

0.188 in – straight no end form

Contact Information:

OD – Outside Diameter

Fig. C

Name Job Title:

Company: Phone:

Email:

Address:

Quantity:

Comments:

Feeder Tube ength Indicate Choice:

Available from 8 – 44 in (in increments of 2 in) Length:

Page 12: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

12 DKRCC.PK.FF0.A1.22 / 520H6635

Venturi area

Product Catalog RD 5500 Series Venturi Style Copper-Brass Distributort

Introduction

Features

Applications

Ordering To order, indicate option choices for the following (descriptions on following page):

y Inlet Options

y Feeder Tube OD (Outside Diameter)

y Number of Circuits

y Feeder Tube Length

y Feeder Tube End Form

y Available with sweat/braze inlets only

The Venturi Style Copper-Brass Distributor is designed for brazed connections. The RD 5500 Venturi series distributor can work in conjunction with an external expansion device for metering and distribution of the refrigerant.

y Designed and engineered to work with any size system

y Operates effectively in both high and low pressure systems

y Full assembly available with Thermostatic Expansion Valve (TXV) or Electronic Expansion Valve (EEV)

RD 5500 Series Venturi RD 5500 Series Venturi Internal detail

For all multi-circuited HVAC and refrigeration heat exchangers used in residential and light commercial applications.

Page 13: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

A

B

C

D

E

DKRCC.PK.FF0.A1.22 / 520H6635 13

Product Catalog RD 5500 Series Venturi Style Copper-Brass Distributor

Ordering options Please make your selections in the column or space provided and fax or email your sales representative.

Contact your Danfoss sales representative for custom options.

Fig. A

Tail Options Length Indicate Choice:

0.375 in ODF 2.5 in

0.5 in ODM 2.5 in

0.625 in ODM 2.5 in

Fig. B

Distributor Body Neck Size Option (no inlet tube)

Indicate Choice:

0.375 in

0.500 in

0.625 in

0.875 in

Fig. D

Feeder Tube OD – Number of Circuits

Indicate Choice:

0.144 in x 0.028 in Wall – 2 to 14 circuits

0.157 in x 0.028 in Wall – 2 to 12 circuits

0.188 in x 0.028 in Wall – 2 to 12 circuits

0.250 in x 0.028 in Wall – 2 to 6 circuits

Name Job Title:

Company: Phone:

Email:

Address:

Quantity:

Comments:

Contact Information:

Fig. E

Feeder Tube End Form Indicate Choice:

0.144 in – straight no end form

0.144 in – expanded Bell – 0.310 in OD

0.144 in – brazed on Bell – 0.375 in OD

0.157 in – straight no end form

0.157 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.375 in OD

0.188 in – straight no end form

0.250 in – straight no end form

OD – Outside Diameter

Straight Expanded Bell

Brazed on Bell

Fig. C

Feeder Tube ength Indicate Choice:

Available from 8 – 44 in (in increments of 2 in) Length:

Page 14: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

14 DKRCC.PK.FF0.A1.22 / 520H6635

Product Catalog RD 5500 Series Nozzle Style Distributor

Introduction

Features

Applications

Ordering To order, indicate option choices for the following (descriptions on following page):

y Inlet Options

y Nozzle Orifice Size

y Feeder Tube OD (Outside Diameter)

y Number of Circuits

y Feeder Tube Length

y Feeder Tube End Form

y Available with sweat/braze inlets only

The Nozzle Style Copper-Brass Distributor is designed for brazed connections. The nozzle allows for customizing of refrigerant flow to provide the desire performance of the system.

The RD 5500 Nozzle series distributor can work in conjunction with an external expansion device for metering and distribution of the refrigerant.

y Designed and engineered to work with any size system

y Operates effectively in both high and low pressure systems

y Full assembly available with Thermostatic Expansion Valve (TXV) or Electronic Expansion Valve (EEV)

RD 5500 Nozzle Style Series RD 5500 Nozzle Style Series Internal detail

For all multi-circuited HVAC and refrigeration heat exchangers used in residential and light commercial applications.

Nozzle

Page 15: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

A

B

C

F

E

D

DKRCC.PK.FF0.A1.22 / 520H6635 15

Product Catalog RD 5500 Series Nozzle Style Distributor

Ordering options Please make your selections in the column or space provided and fax or email your sales representative.

Fig. A

Tail Options Length Indicate Choice:

0.375 in ODF 2.5 in

0.5 in ODM 2.5 in

0.625 in ODM 2.5 in

Fig. B

Distributor Body Neck Size Option (no inlet tube)

Indicate Choice:

0.375 in

0.500 in

0.625 in

0.875 in

Fig. D

Feeder Tube OD – Number of Circuits

Indicate Choice:

0.144 in x 0.028 in Wall – 2 to 14 circuits

0.157 in x 0.028 in Wall – 2 to 12 circuits

0.188 in x 0.028 in Wall – 2 to 12 circuits

0.250 in x 0.028 in Wall – 2 to 6 circuits

Fig. F

Feeder Tube End Form Indicate Choice:

0.144 in – straight no end form

0.144 in – expanded Bell – 0.310 in OD

0.144 in – brazed on Bell – 0.375 in OD

0.157 in – straight no end form

0.157 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.375 in OD

0.188 in – straight no end form

0.250 in – straight no end form

OD – Outside Diameter

Straight Expanded Bell

Brazed on Bell

Fig. E

Feeder Tube ength Indicate Choice:

Available from 8 – 44 in (in increments of 2 in) Length:

Fig. C

Nozzle Orifice Size

Indicate Choice:

0.099 in

0.120 in

0.141 in

0.157 in

0.172 in

0.180 in

Nozzle Orifice Size

Indicate Choice:

0.199 in

0.219 in

0.221 in

0.242 in

0.266 in

0.281 in

Contact your Danfoss sales representative for custom options.

Name Job Title:

Company: Phone:

Email:

Address:

Quantity:

Comments:

Contact Information:

Page 16: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

16 DKRCC.PK.FF0.A1.22 / 520H6635

Product Catalog RD 6500 Series Hot Gas Bypass Style Distributor

Introduction

Features

Applications

Ordering To order, indicate option choices for the following (descriptions on following page):

y Inlet options

y HGBP options

y Nozzle Orifice size

y Feeder Tube OD (Outside Diameter)

y Number of Circuits

The Hot Gas Bypass Style Distributor is the largest distributor body allowing up to 22 circuits with 0.144 OD tubing (other tube size options are available).

Can be used for heat pump and Hot Gas ByPass applications (HGBP).

y Available with or without HGBP port

y The HGBP is available for those applications where the load of the evaporator varies and the return air is lower than 72 °F / 50% RH

y Different nozzle sizes available for proper refrigerant mixing

y Full assembly available with Thermostatic Expansion Valve (TXV) or Electronic Expansion Valve (EEV)

RD 6500 Hot Gas Bypass Series RD 6500 Hot Gas Bypass Series Piston detail

For all multi-circuited HVAC and refrigeration heat exchangers used in residential and light commercial applications.

y Feeder Tube Length

y Feeder Tube End Form

y Available with sweat/braze inlets only

Page 17: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

A

B

C

D

E

F

G

Straight Expanded Bell

Brazed on Bell

DKRCC.PK.FF0.A1.22 / 520H6635 17

Product Catalog RD 6500 Series Hot Gas Bypass Style Distributor

Ordering options Please make your selections in the column or space provided and fax or email your sales representative.

Fig. A

Inlet Option Liquid Line Indicate Choice:

Body Size Connection Size

0.875 in 0.50 in ODM

1.250 in 0.625 in ODM

1.625 in 0.625 in ODM

Fig. B

Distributor Body Neck Size Option Indicate

Choice:Body Size Connection Size

0.875 in 0.625 in

1.250 in 0.875 in

1.625 in 1.125 in

Fig. E

Feeder Tube Length Indicate Choice:

Available from 8 – 44 in (in increments of 2 in) Length:

Fig. F

Feeder Tube OD – Number of Circuits

Indicate Choice:

0.144 in x 0.028 in Wall – 2 to 22 circuits

0.157 in x 0.028 in Wall – 2 to 18 circuits

0.188 in x 0.028 in Wall – 2 to 18 circuits

0.250 in x 0.028 in Wall – 2 to 8 circuits

Fig. D

Nozzle Orifice Size

Indicate Choice:

0.120 in

0.141 in

0.157 in

0.172 in

0.199 in

Nozzle Orifice Size

Indicate Choice:

0.242 in

0.219 in

0.221 in

0.266 in

0.281 in

Fig. C

Side Port / Gas Port Indicate Choice:

Elbow 0.50 in ODF

Straigth 0.50 in ODF

Contact your Danfoss sales representative for custom options.

Name Job Title:

Company: Phone:

Email:

Address:

Quantity:

Comments:

Contact Information:

Fig. G

Feeder Tube End Form Indicate Choice:

0.144 in – straight no end form

0.144 in – expanded Bell – 0.310 in OD

0.144 in – brazed on Bell – 0.375 in OD

0.157 in – straight no end form

0.157 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.310 in OD

0.188 in – expanded Bell – 0.375 in OD

0.188 in – straight no end form

0.250 in – straight no end form

OD – Outside Diameter

Page 18: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

18 DKRCC.PK.FF0.A1.22 / 520H6635 © Danfoss A/S (AC-MC/rds), 2012-10

Product Catalog Pistons

1) Orifice diameter has tolerance ± 0.001

Piston Orifice Selection Chart

Top View

Orifice diameter

Length

Teflon seal

Orifice No. Orifice [in] ± 0.0005

Length [in] ± 0.005

033 0.0330 0.500

035 0.0350 0.500

036 0.0360 0.500

037 0.0370 0.500

038 0.0380 0.500

039 0.0390 0.500

040 0.0400 0.500

041 0.0410 0.500

042 0.0420 0.500

043 0.0430 0.500

045 0.0453 0.500

046 0.0465 0.500

047 0.0469 0.500

048 0.0480 0.500

049 0.0492 0.500

051 0.0512 0.500

052 0.0520 0.500

053 0.0531 0.500

055 0.0550 0.500

057 0.0571 0.500

059 0.0591 0.500

060 0.0600 0.500

061 0.0610 0.500

062 0.0625 0.500

063 0.0630 0.500

064 0.0640 0.500

065 0.0650 0.500

067 0.0670 0.500

068 0.0680 0.500

070 0.0700 0.500

071 0.0709 0.500

072 0.0720 0.500

073 0.0730 0.500

074 0.0740 0.500

075 0.0748 0.500

076 0.0760 0.500

Orifice No. Orifice [in] ± 0.0005

Length [in] ± 0.005

077 0.0770 0.480

078 0.0781 0.480

079 0.0787 0.480

080 0.0807 0.480

081 0.0810 0.480

082 0.0820 0.480

083 0.0830 0.480

084 0.0846 0.480

086 0.0860 0.480

087 0.0866 0.480

088 0.0886 0.480

089 0.0890 0.480

090 0.0906 0.480

091 0.0910 0.480

092 0.0925 0.480

093 0.0938 0.480

094 0.0945 0.480

096 0.0960 0.480

098 0.0980 0.480

099 0.0995 0.480

101 0.1015 0.480

102 0.1024 0.480

104 0.1040 0.480

106 0.1065 0.480

108 0.1083 0.480

109 0.1093 0.480

110 0.1100 0.480

113 0.1130 0.480

116 0.1160 0.480

118 0.1181 0.480

120 0.12001) 0.470

125 0.12501) 0.470

128 0.12801) 0.470

Page 19: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in

DKRCC.PK.FF0.A1.22 / 520H6635 19

Product Catalog Danfoss Distributor Product Program

Page 20: 20 Al - files.danfoss.comfiles.danfoss.com/technicalinfo/dila/01/DKRCC.PK.FF0.A1.22.pdf · Al aluminum ... 0.144 in – straight no end form 0.144 in – expanded Bell – 0.310 in