® N2 BLAST® Datasheet Preaction double interlock, Electric/Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
1 of 14 FM-076D-0-120C
(System shown with integrated control panel)
FireFlex® N2 Blast® description The FIREFLEX® N2 Blast® integrated system consists of an integrated double interlock Electric/Pneulectric release preaction automatic sprinkler system combined with a Nitrogen generating system, factory-assembled in a single cabinet. All the necessary components are integrated. The FIREFLEX® N2 Blast® is fully tested at factory. The FIREFLEX® N2 Blast® System uses the N2 Blast® Nitrogen generator system Type 1 FPS-250 or FPS-750 system, made by South-Tek Systems.
All the deluge valves are rated up to a maximum of 250 psi WWP (1724 kPa) max. and are available in the following diameters:
1½" (40 mm) 2" (50 mm) 3" (80 mm) 4" (100 mm) 6" (150 mm)
Warning: 6" (150 mm) available with N2 Blast® Type 1 FPS-750 only.
Features Inhibits corrosion with 98%+ pure Nitrogen Trouble-free design for safe and easy application Available in 2 cabinet sizes Uses South-Tek N2 Blast® Best value in nitrogen generation technology Limits the liability of early pipe replacement Uses the Viking deluge valve Trim is fully assembled and tested at the factory All trims are galvanized steel, Listed and Approved
for 250 psi (17.2 bar) service maximum Quick connections to water supply and drain on
left side, and sprinkler riser on top of unit, all available with grooved end or flanged fittings
No open drain cup inside unit Separate unlocked access hatch to emergency
manual release Compact, aesthetic and easy to move User-friendly standardized owner's manual with
every unit Unique serial number on every unit Uses UL, ULC and/or FM Approved components Designed in accordance with NFPA Standards Sturdy 14 gauge steel cabinet painted fire red with
oven baked polyester powder on phosphate base Textured rust proof finish Neoprene gasket on all doors to eliminate
vibrations Manufactured under ISO-9001 quality control
procedures Prewired to a terminals block.
® N2 BLAST® Datasheet Preaction double interlock, Electric/ Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
FM-076D-0-120C 2 of 14
System configurations
□ Double Interlock Preaction combined with N2 Blast® Type 1 FPS-250 (250 gallons system)
□ Double Interlock Preaction combined with N2 Blast® Type 1 FPS-750 (750 gallons system) Systems hydraulic limitations The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer. Designers should refer to the appropriate NFPA Standards and any other applicable codes for their final design. Also refer to FireFlex Systems Inc. appropriate user manuals and to manufacturer's data sheets for additional details. Systems limitations indicated below are nominal flow limitations.
System size (in.)
Usage Range (gpm)
Piping Equivalent Lengths w/o shut off valve
Piping Equivalent Lengths c/w shut off valve
Drain flow @ 250 PSIG w.p.
(m.) (ft.) (m.) (ft.) GPM 1½ 0 – 210 8.3 27.2 8.5 27.9 272 2 0 – 360 11.65 38.2 11.85 38.9 272 3 100 - 700 16.8 55.1 20.33 66.7 762 4 200 – 1400 21.89 71.8 25.33 83.1 1597 6 400 - 3500 33.28 109.15 37.28 122.3 1597
Sequence of operation Preaction operation
1. The activation of the detection condition AND the opening of an automatic sprinkler are necessary to cause the deluge valve actuation.
2. Detection condition: Single zone (the operation of one detector
in the protected area is required to fulfill the detection condition).
3. The activation of the detection condition alone will activate the solenoid valve (F1) open, but the deluge valve will not open.
4. Activation of the detection condition AND the opening of an automatic sprinkler will activate the solenoid valve (F1) and the Low air alarm switch (E4), causing the deluge valve to open and water will flow out of any open sprinklers. The alarm pressure switch (C1) will activate
5. The opening of an automatic sprinkler OR damage to system piping without the detection condition satisfied will activate the low air supervisory (E4) switch contact but will not allow the water to enter the system piping.
6. Operation of the emergency manual release will depressurize the priming chamber, causing the deluge valve to open and allowing water to enter the system piping and water will discharge through any open sprinklers.The alarm pressure switch (C1) will activate.
N2 Blast® Nitrogen generator system operation 1. The initial air supply fill of the piping system within
30 minutes as per NFPA 13 is accomplished using the “initial fill” air compressor. This compressor is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the sprinkler system piping. It is factory-set at 10 and 20 psi for the cut-in and cut-out pressures respectively. There is a "low air" supervisory pressure switch which monitors system piping air/nitrogen pressure at all times. It is factory-set at 12 psi to provide a "low air" supervisory signal.
2. The nitrogen generation/maintenance air compressor is supplied as an integral part of the STS N2-Blast® Nitrogen Generation System. It is equipped with a factory-adjusted ON/OFF pressure switch which is tied into the nitrogen storage tank. It is factory-set at 65 psi and 75 psi for the cut-in and cut-out pressures respectively. The Viking D-2 Air Pressure Maintenance Device is installed and factory-adjusted to 20 psi (normal system air/nitrogen pressure) downstream of the nitrogen storage tank. As the system continually purges with Nitrogen, the APMD will continually draw from the Nitrogen storage tank to maintain supervisory pressure (20 psi). Should the N2-Blast® generator run for more than 6 hours consecutively, the Leak Detection System (LDS) will automatically shut it down and activate a trouble contact.
3. The air and nitrogen supply systems are fully integrated and fully automatic in the FireFlex - N2-Blast®. No shut-off or bypass valve is required. The nitrogen generator is equipped with a BlastOff® Leak Detection System (LDS). Should the nitrogen generator compressor fail or a leak occur that can not be compensated by the nitrogen generating system, the preaction system air compressor will act as a back-up and start-up at 10 psi system pressure.
® N2 BLAST® Datasheet Preaction double interlock, Electric/Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
3 of 14 FM-076D-0-120C
Standard equipment Deluge valve
The Viking Model F-1 Deluge Valve is a quick-opening, differential diaphragm flood valve with one moving mechanism. The deluge valve is used to control water flow in preaction sprinkler systems. The valve is held closed by system water pressure trapped in the priming chamber, keeping the outlet chamber and system piping dry. In fire conditions, when the releasing system operates, pressure is released from the priming chamber. The deluge valve clapper opens to allow water to flow into the system
Water supply control valve The water inlet control valve is a supervised, indicating butterfly valve. Purpose of this vale is to manually shutoff the preaction system.
Preaction riser check valve
The Viking 1-½” and 2” spring loaded In-Line check valve is a general purpose rubber-faced check valve approved for use in fire-service systems. The Spring Loaded In-Line check valve is manufactured with a brass body, brass seat, and a rubber-faced clapper assembly. The Viking 3”, 4” and 6” Easy Riser® Swing check valve is a general purpose rubber-faced check valve approved for use in fire service systems. The valve is for use in preaction system risers.
Solenoid valve The high pressure solenoid valve is a two-way type with one inlet and one outlet. It is a packless, internal pilot operated valve, suitable for use in releasing water pressure from the priming chamber of Viking Deluge Valves. The solenoid valve has floating diaphragm construction, which requires a minimum pressure drop across the valve to operate properly.
IN OUT
® N2 BLAST® Datasheet Preaction double interlock, Electric/ Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
FM-076D-0-120C 4 of 14
Low air supervisory switch
The low pressure switches monitors the pressure within the sprinkler piping should a loss pressure of the air below 12Psi occurs, the pressure switch contacts transfer indicating low air supervisory signal. Should a loss pressure of the air below 10Psi occurs, the pressure switch contacts transfer indicating low air alarm signal.
POTTERPS40-2A
Alarm pressure switch
The alarm pressure switch monitors the water flow within the sprinkler piping. Should the Deluge Valve clapper opens to allow water to flow into the sprinkler piping. The alarm pressure switch will activate, indicating a water flow signal
POTTERPS10-1A
Releasing circuit disconnect switch
The releasing circuit disconnect switch is used to disable the releasing solenoid. When the key is set to “Disable”, the releasing solenoid will be disconnected from the control panel’s releasing circuit, causing a trouble signal and preventing accidental discharge during maintenance or inspection.
N2 Blast® Nitrogen generator
South-Tek Systems utilizes Membrane technology in the N2-Blast® Corrosion Inhibiting Systems in order to efficiently separate Nitrogen molecules from the air we breathe. Membrane technology, used in our smaller applications, has a simple air flow design, is wall-mounted and easy to service. PSA technology is more cost effective and energy efficient in larger Fire Protection Systems, those requiring more Nitrogen to compensate for the NFPA “acceptable leak rate”.
BlastOff™ Leak detection system
Unless the leak rate is catastrophic, the supervisory low pressure alarm on the BlastOff™ will not activate. Minor leaks cause the air compressor and N2-Blast® to run excessively in order to maintain supervisory pressure. The unnecessary additional run-time decreases the lifespan of the equipment. The Patent Pending BlastOff™ - Leak Detection System is designed to detect significant leaks before they compromise the FPS and the Nitrogen Generation System. It has an internal audible alarm and dry contact that’s is wired on the Sprinkler Low Air Supervisory Zone.
Nitrogen generator storage cylinder
Type 1 Nitrogen Generation Systems include a 16 gallon Nitrogen receiver tank (12.2”dia x 44.8”H). Nitrogen generated by the N2-Blast® is stored in the tank, and then sent to the sprinkler system through the Nitrogen air pressure maintenance device.
N2 Blast® AutoPurge System™
High purity Nitrogen must be equally distributed throughout the entire sprinkler piping system in order to effectively inhibit corrosion. The Patent Pending AutoPurge System™ provides a low volume, constant purge of Nitrogen within sprinkler piping. The rate in which gas is evacuated from the sprinkler piping is within NFPA guidelines and allows breathing to occur. The AutoPurge System™ also assists in drying out the residual water from a hydro test. Computational Fluid Dynamics modeling proves that this is the most effective way to ensure that high purity Nitrogen reaches all branches within the sprinkler piping. Install one AutoPurge System™ per system at a high point .
There is a Label on one side of the housing that lists the proper setting for a variety of zone sizes. The Label list: Gallons in Zone, and APS Flow Setting. The Flow Setting is labeled from A-E and has three Settings in between each letter.
Nitrogen generator air pressure maintenance device
FIREFLEX® N2 Blast® use the Viking Model D-2 Air Pressure Maintenance Device (APMD) which is a pressure regulator that automatically reduces the supply air pressure to a preset requirement when connected to a constantly maintained air supply.
The APMD is used to regulate the nitrogen pressure to 20Psi in the sprinkler piping at the specified system pressure for FIREFLEX N2 Blast® Double interlock preaction system.
® N2 BLAST® Datasheet Preaction double interlock, Electric/Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
5 of 14 FM-076D-0-120C
Optional preaction equipment Shut-off valve & sight glass (optional)
The Shut-off Valve & Sight Glass Option is intended to be used for applications where testing of the system operation without filling the sprinkler piping network is desirable and where it is critical that all functions of the preaction system be tested under actual discharge conditions.
Mainwater supplycontrol valve
Deluge valve
Shut-off valve
Riser check valve
Main drain valve
Sight glassassembly
Point flashlightHERE
FM-076Z-0-4B-1
Anti-column device option The model LD-1 anti-column device is an optional trim component designed for use with preaction sprinkler systems. The anti-column device automatically prevents an unwanted water column from establishing within the system riser. On preaction sprinkler systems the anti-column device prevents water from columning downstream of the easy riser check valve.
From Sprinkler Riser
FM-061H-0-146ATo Drain Collector
Semi-flange inlet / outlet (optional) When required by the user, FIREFLEX N2 Blast® units can be provided in a semi-flanged configuration. The semi flanged option provides flanged fittings only on the water inlet pipe (left side) and on the system riser outlet. The drain manifold is provided with a threaded connection (left side). The rest of the fittings are the same as usual with the main components being provided in the standard flanged / grooved configuration.
Deluge valve
Flange fittingoutside cabinet
Flange fittingoutside cabinet
Riser check valve
Threadeddrain output
FM-076Z-0-4B-2
Mainwater supplycontrol valve
® N2 BLAST® Datasheet Preaction double interlock, Electric/ Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
FM-076D-0-120C 6 of 14
Preaction system - Air supply
Direct air compressor (Style “A”) Used only for the sprinkler piping network of the preaction system. Air supply style "A" includes the air compressor mounted inside the FIREFLEX N2 Blast® cabinets with its supervisory trim and options. Compressors are of the tankless, oiless piston type and are factory piped to the sprinkler system riser, all within the FIREFLEX N2 Blast® cabinets.
Compressors are available in four (4) sizes: 1/6HP 1/2HP 1/3HP 1HP
FM-061H-0-118C
1
CONTRACTOR'SHYDROSTATIC TEST PORT(system side)
2 TO DRAIN COLLECTOR
TO SPRINKLER RISER
Copper tubing
This section replacedby Dehydrator option(when used)
TO OPTIONAL ACCELERATOR(plugged when not used)
3TO PNEUMATIC ACTUATOR(plugged when not used)
E4(plugged withSureFire trim)
Pressure relief valve
Air Pressure Maintenance Device (Style “B”)
Used only for the sprinkler piping network of the preaction system, when an external air supply is provided by others (tank mounted compressor, plant air or dry nitrogen cylinders) and piped to the air inlet port of the unit. Air supply style "B" provides an Air Pressure Maintenance Device (APMD) trim, factory mounted in the FIREFLEX N2 Blast® cabinets.
FM-061H-0-119B
1
CONTRACTOR'SHYDROSTATIC TEST PORT(system side)
TO SPRINKLER RISER
TO OPTIONAL ACCELERATOR(plugged when not used)
E4(plugged with SureFire trim)
This section replacedby Dehydrator option(when used)
Contractor external Airor Nitrogen connection
3TO PNEUMATICACTUATOR(plugged whennot used)
Compressor Service Factor Amp (S.F.A) rating Compressor
Size (HP) 115Vac / 60Hz 230Vac / 60Hz
1/6 5.0 Amp. 2.5 Amp. 1/3 7.4 Amp. 3.7 Amp. 1/2 10.0 Amp. 5.0 Amp. 1 18.0 Amp. 9.0 Amp.
115 / 220 Vac – 60Hz Compressor selection Table:
H.P CFM
@ 40 PSI
System capacity to fill system to 35 PSI
in 30 minutes *
System capacity to fill system to 55 PSI in 30
minutes ** 1/6 1.33 142 gal. 90 gal. 1/3 2.61 285 gal. 181 gal. 1/2 4.06 417 gal. 265 gal. 1 7.40 702 gal. 447 gal.
* For systems with maximum water supply pressure of 175 PSI (1206 kPa)
** For systems with water supply pressure between 175 PSI (1207 kPa) and 250 PSI (1724 kPa)
WARNING The information contained herewith is for estimation and evaluation purposes only. Its use remains the responsibility of the designer.
® N2 BLAST® Datasheet Preaction double interlock, Electric/Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
7 of 14 FM-076D-0-120C
Details & field wiring diagrams P & ID
Tank Providedwith brackets and Strap
Riser towards the nozzles
N2 Blast
Compressor
Air Maintenance Device/s(AMD/s) Supplied by Fireflex
PreactionCompressor
PreactionAir Kit
PreactionSystem
Low AirPressure Switch
Autopurge System
Sprinkler
NitrogenAir
® N2 BLAST® Datasheet Preaction double interlock, Electric/ Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
FM-076D-0-120C 8 of 14
Details & field wiring diagrams Cabinet with main components, shown without door(s)
FM-06LM-0-1A-1FM-06LM-0-1A-1
® N2 BLAST® Datasheet Preaction double interlock, Electric/Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
9 of 14 FM-076D-0-120C
Trim diagram
FM-076Z-0-61A
FIELD CONNECTIONTO OPEN DRAIN
(left side only)
FIELD CONNECTIONTO WATER SUPPLY
(left side only)
D1
C1
D3
B6
B5
B7
F1
B9
B1
B2
B4B3
D2
B13
A1
C2B11
B12
B10
2
CONTRACTOR'SHYDROSTATICTEST PORT(water supply side)
1To Air Supply System Trim
FIELD CONNECTION TOSPRINKLER PIPING NETWORK
TotalPac Base(shown without enclosure)
To Air SupplySystem Trim
B8
Trim Components:
A1 Deluge valve B1 Priming valve B2 Strainer B3 1/16" Restricted orifice B4 Spring loaded check valve B5 Alarm test valve B6 Flow test valve B7 Drip check valve B8 Drain check valve B9 Pressure operated relief valve (PORV) B10 Emergency release valve B11 Prime pressure water gauge & valve B12 Water supply pressure gauge & valve B13 Clapper check valve
C1 Alarm pressure switch C2 Connection to water motor gong (strainer supplied
by contractor) D1 Water supply control valve D2 Riser check valve D3 Main drain valve F1 24Vdc N.C. Solenoid valve
® N2 BLAST® Datasheet Preaction double interlock, Electric/ Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
FM-076D-0-120C 10 of 14
Wiring diagram
PR
EA
CTI
ON
LOW
AIR
PR
ES
SU
RE
SW
ITC
H
PR
EA
CTI
ON
LOW
AIR
PR
ES
SU
RE
SU
PE
RV
ISO
RY
EO
L
EO
L
EO
L
MA
IN V
ALV
E S
UP
V S
WIT
CH
MA
IN V
ALV
E
EOL devices (not included) must be compatible with the Release Control Panel used.
All devices are factory wired.
21 22 23 24
EO
L
SH
UT-
OFF
VA
LVE
SU
PV
SW
ITC
HS
HU
T-O
FF V
ALV
E
OPTIONAL
17 18 19 20
S
N.C
. SO
LEN
OID
VA
LVE
(see
tabl
ebe
low
for r
atin
gs)
SO
LEN
OID
VA
LVE
1
TBC
2 3 4 5 6
C NO
NC
MA
IN V
ALV
E
C NO
NC
SH
UT-
OFF
VA
LVE
Contacts provided for connection tothe building's central Fire Alarm Panel.
OPTIONAL
LOS ANGELES OPTION
CHICAGO OPTION
NOTE:
MA
IN V
ALV
E S
UP
V S
WIT
CH
SH
UT-
OFF
VA
LVE
SU
PV
SW
ITC
H
EO
L
BY
BA
SS
SW
ITC
HS
UP
ER
VIS
OR
Y
LED
PO
WER
RELEASING CIRCUITDISCONNECTSWITCH
25 26
1234
TBB
56
LINENEUTRALGROUNDGROUNDNEUTRALLINE
N2BLAST NITROGEN GENERATING SYSTEM20A MAX
WIRING OF INPUT POWER SOURCE
Branch circuit for air compressor shall not be the sameas the N2Blast Nitrogen Generating System.
Refer to Local Electrical Codes for wiring size.
PREACTIONAIR COMPRESSOR1HP MAX
WITH AIR OPTION "A" ONLY
120VAC, 60Hz
EO
L
N2B
LAS
TLO
W A
IR P
RE
SS
UR
ER
ELA
Y
N2B
LAS
TLO
W A
IR P
RE
SS
UR
ES
UP
ER
VIS
OR
Y
5 6 7 8
PR
EA
CTI
ON
LOW
AIR
PR
ES
SU
RE
SW
ITC
H
PR
EA
CTI
ON
LOW
AIR
PR
ES
SU
RE
ALA
RM
EO
L
29 3027 28 31 32 33 34
24 V
DC
**
Nee
ded
for k
eysw
itch
LE
Ds
oper
atio
n.
FM-061H-0-215B
1
TBA
2 3 4 9 10 11 12 13 14 15 16
WA
TER
FLO
W
All devices are shown in their normal supervisory state.
NOTES:
Use dry contacts with power limited circuits only.
Contacts are rated:Pressure switches: 2A, 30VDC 10A, 125/250VACSupervisory switches: 0.5A, 125VDC 0.25A, 250VDC 5A, 1/6HP, 125/250VACRelay module: 0.45A 125VDC 0.35A, 250VDC 16A, 30VDC 16A, 250VAC
WA
TER
FLO
WS
WIT
CH
SOLENOID VALVE ELECTRICAL RATINGS
Viking P/N Description (De-energized) Voltage Watts DC Amps Pressure
Rating
11591 NC 24 VDC 10.0 DC 416 mA 300 psi (2 068 kPa)
Notes: 1. Solenoid Valve is UL Listed as Fire Protection Special System Water Control Release Service (UL 429A Product category VLTR). 2. Voltage Drop: For proper operation, make sure that voltage at the solenoid valve is at least 85% of nameplate rating.
® N2 BLAST® Datasheet Preaction double interlock, Electric/Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
11 of 14 FM-076D-0-120C
Cabinet The FIREFLEX N2 Blast® cabinet is made of sturdy 14 gauge steel. Refer to figure 4 for dimensions. All surfaces are rust proof coated, inside and outside, with fire red, oven baked polyester powder on phosphate base. Cabinet is provided with two doors, all provided with a neoprene gasket to avoid vibrations, giving the access to the pressure gauges reading and the manual emergency release. The cabinet assembly is pre-assembled, pre-wired, and factory tested under ISO-9001 conditions. Refer to figures 2 & 3 for installation and clearances details. Electrical junction boxes are integrated inside the cabinet for connection of the supervisory and alarm devices contacts. Knockouts are pre-punched for the installing contractor as indicated on figure 1.
Figure 1 - knockouts details
3"
8½"
Top of Cabinet
FM-061H-0-68B-12
2½" Typ.3¾"
2½"
High voltage
Low voltage
Figure 2 - Floor anchoring template
5''
E
G
Ø3/4"
F
FM-061H-1-49B-6
Size E F G 46" 15" 48" 25"
54" 21" 56" 27"
Figure 3 - Required clearance
FM-061H-1-49B-7
12''MIN
12''MIN
22''MIN
Size A 46" 24"
54" 32"
® N2 BLAST® Datasheet Preaction double interlock, Electric/ Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
FM-076D-0-120C 12 of 14
Figure 4 - Cabinet dimensions
WATER INLETSCH.40 GROOVED OUTLET
DRAIN - SCH.40 GROOVED OUTLET
SP
RIN
KLE
R R
ISE
RS
CH
.40
GR
OO
VE
D O
UTL
ET
TBB TBA & TBC
CONTROLPANEL
(except for RemoteControlled Unit)
SP
RIN
KLE
R R
ISE
RS
CH
.40
GR
OO
VE
D O
UTL
ET
T
R
G
M
D
P
F
S
FM-06LM-0-2A
OPTIONALSHUT-OFF VALVE
CO
NTR
OL
PA
NE
L
TBA, TBB & TBC
N
Q
ØC
ØA
ØB
System Size A B C D E F G H J K L M N P Q R S T 1½" 2" 1½" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37½" 44¾" 50"
2" 2" 2" 2" 46" 25" 77¼" 4" 8¾" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 37¾" 45" 50"
3" 4" 3" 2" 46" 25" 77¼" 4" 10" 11½" 13¾" 3¾" 2¾" 2¾" 15" 11½" 44" 47¾" 50"
4" 4" 4" 2" 54" 31" 81¼" 4" 10" 11½" 13¾" 3¾" 2½" 2½" 23¾" 11½" 48½" 53" 58"
6" 6" 6" 2" 54" 31" 81¼" 4" 11" 13" 13¾" 5¼" 2¾" 2¾" 25" 13" 59¼" 65¼” 58"
Dimensions are nominal and may vary by ¼”
® N2 BLAST® Datasheet Preaction double interlock, Electric/Pneulectric c/w N2 Blast® Nitrogen generating system Remote controlled unit
13 of 14 FM-076D-0-120C
FM-076D-0-120C 14 of 14
1935, Lionel-Bertrand Blvd. Boisbriand QC Canada J7H 1N8 Tel.: 450-437-3473 • Fax: 450-437-1930 Toll Free: 866-347-3353 Email: [email protected] • Web: www.fireflex.com