12
GENERAL SPECIFICATION AND DATA SHEETS FOR GENERATOR RELAY PANEL Ref: GPSPL/GRP /2001/01 Page : 1 of 12 Rev No : 03 Date : 27.11.10 GREENESOL POWER SYSTEMS COPYWRIGHT AND CONFIDENTIAL COPYWRIGHT AND CONFIDENTIAL This information on this documents is the property of : GREENESOL POWER SYSTEMS PVT. LTD. PREPARED BY APPROVED BY P.AMMAIAHCHOWDARY K.DHANANJAYA Sign: Sign: 1. SCOPE: Scope of supply shall include design, engineering, manufacturing, testing, inspection, packing and transport of equipment to site in accordance with the stipulations mentioned hereunder and in data sheet. 2. CODES AND STANDARDS: The design, manufacturing and performance of equipment covered by this specification shall confirm to the relevant Indian standards and codes of practices. Where Indian standards are not available, they shall confirm to relevant British, IEC and American standards. Sl . No . Description Standards 01 Code of practice for climate proofing of electrical equipment IS 3202 02 Marking and arrangement of switchgear, bus- bar, main connection and aux. Wiring IS 5578 & 1353 03 Direct acting electrical indicating instruments IS 1248 04 HRC fuses IS 2206, IEC 269 05 Control switches and push buttons IS 6875 06 Current transformer IS 2705/ IEC 185 07 Potential transformer IS 3156/ IEC 186 08 Electrical relay for power system protection IS 3231 09 AC electricity meters IS 722 10 Degree of protection IS 2147&IEC 144 PROJECT: 2 X 150 MW THERMAL POWER PLANT. (PHASE -II) OWNER: M/s. SIMHAPURI ENERGY PRIVATE L.IMITED-HYD. OWNER’S ENGINEER: M/s. DEVELOPMENT CONSULTANTS PVT. LTD. KOLKATA. EPC CONTRACTOR: M/s. MADHUCON PROJECTS LIMITED-HYDERBAD. ORGINATOR ENGINEER: M/s. M.N.DASTUR & COMPANY (P) LTD-KOLKATA.

19.R3 - GRP Specification Sheet

Embed Size (px)

DESCRIPTION

sdfsfsfdfwe

Citation preview

Excitation Panel

1. SCOPE:

1. SCOPE:

Scope of supply shall include design, engineering, manufacturing, testing, inspection, packing and transport of equipment to site in accordance with the stipulations mentioned hereunder and in data sheet.

2. CODES AND STANDARDS:The design, manufacturing and performance of equipment covered by this specification shall confirm to the relevant Indian standards and codes of practices. Where Indian standards are not available, they shall confirm to relevant British, IEC and American standards.

Sl. No.DescriptionStandards

01Code of practice for climate proofing of electrical equipmentIS 3202

02Marking and arrangement of switchgear, bus-bar, main connection and aux. WiringIS 5578 & 1353

03Direct acting electrical indicating instrumentsIS 1248

04HRC fusesIS 2206, IEC 269

05Control switches and push buttonsIS 6875

06Current transformerIS 2705/ IEC 185

07Potential transformerIS 3156/ IEC 186

08Electrical relay for power system protectionIS 3231

09AC electricity metersIS 722

10Degree of protectionIS 2147&IEC 144

11Phosphate treatment of iron & steelIS 6005

12Bus-bar conductor materialIS 5082

13Static metersIEC 1036

14Instrument transformerIEC 44

15Electrical RelaysIEC 255

16LV switchgear and control gearIS 13947

17Code of practice for earthingIS 3043

3. PROJECT INFORMATION:

The equipment covered in this specification is used for Protection of a steam turbine driven Alternator. Location: Tamminapatnam and Momidi villages, Nellore District, AP

Ambient Air Temp 39.6 C

Ambient Max Humidity - 84 %

Altitude 4.0 Meters above MSL, Zone III

Design Temp.for Electrical Equip. -50C

Design Humidity for ESGIN Electrical Equip. -100 %

4. DESIGN REQUIREMENT:

4.1 Constructional Features: The panel shall be designed, fabricated and fitted with the components as specified in the data sheet and whichever applicable hereunder, necessary for satisfactory functioning of the Control and protection system.

Cubicle shall be of Simplex type, sheet steel enclosed, dust moisture and vermin proof. The degree of protection shall be as specified in the data sheet.

Cubicle shall be floor mounting, free standing, formed on a framework of standard sections. The enclosure shall be fabricated from cold rolled sheet steel of thickness not less than 3.0 mm for the front, back, equipment bearing surface and 2.5 mm for the rest. The supporting structure shall be so designed to form a rigid structure.

The panel shall be free from dents and flaws. It shall be sufficiently reinforced to provide level surfaces, resistance to vibration and rigidity during transportation and installation.

The perimeter of all doors, removable cover plates shall be having neoprene gasket all around. All doors shall be fitted with concealed type hinges and shall have handles with locking facility.

The cubicle shall be suitable to be installed on a base frame supplied in one piece along with foundation bolts. Amply dimensioned oblong holes shall be provided at the bottom of the cubicle for their installation on base frame, in addition the cubicle shall have an additional base channel at the bottom with smooth surface. Anti vibration pad of 15 mm thick shall be provided between base frame and panel through its entire width on the front and rear side.

Lifting hooks shall be provided for each transportable section of the cubicle. All hardware shall be zinc plated and passivated.

A suitable removable undrilled gland plate of 3mm thickness shall be provided for cable entry. Cable entry position shall be as specified in the data sheet.

The dimension and finish of the panel shall be as specified in the data sheet in order to match with other cubicles in purchasers scope.

Cubicle shall be provided with fluorescent lamps for each section working on Aux. AC supply as specified in data sheet. It shall be operated automatically by door limit switch.

A single phase, 15 Amps, 5 pin socket shall be provided in the panel interior of each cubicle with on-off switch.

Panel space heater complete with MCB and thermostat shall be provided in the panel. The thermostat shall maintain the internal temperature above the ambient temperature to prevent moisture condensation.

All the protective relays shall be numerical type with serial interface facility to communicate with DCS. The no. of numerical relays to be provided shall consider that all generator protection functions are to be duplicated. The controller shall establish the serial communication between the protective relays and DCS system.

Type of relays shall be Numerical that meet the protection philosophy described and the various performance requirements / characteristics required for fully protecting the Intended equipment is to be considered.

SUPPLIER shall furnish recommended relay settings with back up calculations for entire station.Adequate number of wipe out timers having time delayed opening contacts shall be provided to enable reset of Generator Trip relays (86 G), wherever required. The setting range of above timers shall approximately be in the range of 1-10 seconds. It shall have adequate number of contacts as required by the scheme.

5. SPECIFIC REQUIREMENTS:Discrete relays shall be provided for 60G11, 60G12, 60G21, 60G22, 60G31, and 60G 32, 61B and shall not be part of composite numerical relays.

Two Nos. of DC supply sources shall be arranged by the purchaser for the GRP from two different sections of DCDB. These supplies shall be taken through a contactor changeover arrangement i.e, In case of failure of any one source contactor shall be changed over to the other source and complete DC supply requirement of GRP shall be fed from the other source. Third DC supply for dead machine protection shall be provided from station DCDB. In addition, dead machine protection scheme shall be electrically and physically separated from other protections.

DC auxiliary supply shall be supervised by supply supervising relays. The NC contact of the relays shall be delayed on drop off by approximately 100 to 200 msec. For annunciation GCP/DCS. The relay shall be provided with flag indicator wherever required. White colour supervision lamps of clustered LED type shall be provided for DC supply monitoring on GRP.

The relay panels shall be provided with supervisory system facilities to indicate the location of the failed component when pre-engineered protection system is offered. On-line testing facility In-Built in the relay panel shall be provided.

Either hand reset mechanically operated operation indicator or LED with reset push button shall be provided for protective relays. They shall be arranged to operate only when tripping current passes through output circuit of the relay.

In addition to the contact required as per schemes, Supplier shall wire out to the terminal block spare contacts of the necessary relays.

The protection scheme shall include all the necessary contacts to achieve the schemes required, alarms / Trip conditions / Abnormal conditions of individual relays in DCS/GCP, annunciation windows, Sequence event recorder and for switchyard control panel (SCP) annunciation wherever required.

The protection philosophy of all equipment shall be divided into two groups. Complete protection of the respective equipment shall be fully available even if either of the groups is not available. Hence, both groups of protections shall be mechanically, physically and electrically separated into two separate and independent systems. Each group shall be receiving all ac and dc signals from dedicated set of devices. Similarly these two groups shall be provided with DC supply from two separate feeders. However the relays in both the groups shall be tripping the respective circuit breaker through both trip coils I&II. Suitable programming, testing & calibration facilities with necessary software, program unit/laptop etc., shall also be provided. Automatic changeover of DC supply source from one source to other shall be provided.6. EQUIPMENT MOUNTING AND LOCATION:The cubicle shall be of simplex type and shall consist of vertical front panels with mounted equipment and rear wiring access. All equipment shall be flush or semi-flush type.

Checking and removal of components shall be possible without disturbing the adjacent equipment. The mounting of terminal blocks and other auxiliary equipment such as transducers, interposing CTs, PTs, etc. shall be done in such a way so that it is readily accessible but without impending the access to internal wiring and components.

The centerline of switches, push buttons and indicating lamps shall be not less than 750 mm from the bottom of the cubicle. The centerline of the relays and meters shall not be less than 450 mm from the bottom of the cubicle. All switches, push buttons, indicating lamps, meters, relays etc. shall be arranged neatly to give a good aesthetic look.

Relay & Control Panels shall be supplied with anti vibration pads. A clearance of 300 mm shall be maintained between terminal blocks and gland plate and 150 mm between two rows of terminal blocks.

7. PANEL WIRING:All wiring shall be done with PVC insulated 650 / 1100 volt grade, single core multi strand annealed copper conductor. For CT & PT, control and alarm circuit 2.5-sq.mm size cables with color identification. Panel wiring shall be securely supported, neatly installed by lacing in the wiring channels. Flame retardant plastic channels / troughs with strap on wiring cover shall be used.

Each wire shall be identified at both ends with wire numbers by means of PVC \ferrules.

Ferrules shall fit tightly on the wire and shall not fall off when the wire is disconnected.

Wire termination shall be made with solderless crimping type tinned copper lugs, which

Firmly grip the conductor and insulation. Insulation sleeves shall be provided at all the wire termination. More than one cable should not be crimped on a same lug. All spare contacts of breaker switches, push buttons, and relays shall be wired to the terminal block.

8. TERMINAL BLOCK:Terminal block for control cable shall be of stud type CAT M4, 650/1100 V grade rated for 10 amps complete with insulated barriers, washers, nuts, and identification strips.The terminal block board shall be set at 45 Deg to the side panels for easy access. Minimum 20% spare terminal blocks shall be provided on the cubicle. These spare terminals shall be uniformly distributed on all rows of terminal block.

The terminal shall be suitable to receive crimped wires to give positive connection. All terminals shall be properly shrouded against accidental contact. Sufficient terminals shall be provided so that not more than one wire is connected in each terminal.

Moulding material of the terminal shall be self-extinguishing type or resistive to flame propagation, substantially non-hydroscopic and shall not carbonize when tested for tracking. The terminal and framework shall withstand 2 kV RMS for one minute.

Terminal blocks for CT and PT secondary shall be provided with test links and isolation facility. Also CT secondary leads shall be provided with shorting and earthing links.

There shall be minimum clearance of 250 mm between the first row of terminal block and associated cable gland plate. The clearance between two rows of terminal block shall be minimum 150 mm.9. LABELS:All equipment mounted on front of the panel as well as equipment inside the panel shall be provided with individual labels with equipment designation engraved. The label shall be mounted so that they are clearly visible.

The name plates bearing respective circuit designation of 50mm width etched in 40mm high letters shall be mounted on the top front and back side of each cubicle shall be supplied and fixed in such a way that these can be removed and refitted when desired.

Danger plates, warning plates, and other statutory notes will be provided as per the relevant standards.

Reverse engraved name plate at least 10mm wide bearing suitable identification shall be fixed in the interior of the switchboard, at the test blocks/MCB blocks and at the cable terminals. Similar plates shall be fixed on the panel for control switches, Push buttons, lamps, mimic indicating the functions associated. Labels shall be made of non-rusting metal or 3 ply lamicoid. Labels shall have white letters on black background. Labels shall be fastened using screws. Use of adhesive is not permitted.

10. EARTHING:The panel shall be fitted with the continuous earth bus of size as specified in the data sheet which shall be securely fixed along the inside base of the panel and running along the full length of the cubicle.

Suitable earthing studs shall be provided at the rear bottom of the panel at two ends for connection to the plant earth grid.

All metallic cases of panel-mounted equipment shall be connected to the earth bus by independent insulated copper wire colored green.

PT and CT secondary neutral or common lead shall be earthed at one place only at the terminal block where they enter the panel.

Insulation between the live terminals and earth prior to connection of earth to the plant earth grid shall withstand a test voltage of 500 volts for one minute or have resistance of not less than one mega ohm at 500 V.

11. PAINTING:All metal surfaces shall be chemically cleaned, degreased and pickled in acid to produce a smooth clean surface, free of scale, grease and rust. The panel shall be powder coated to shade as specified in the data sheet. The minimum thickness of paint finish shall not be less than 60 - 80 microns.

Panel finish shall be free from imperfections like pin holes, orange peels, run off paint etc. A small quantity of finishing paint shall be included in the supply for minor paint touchup at site after installation.

All unpainted steel parts shall be cadmium plated or suitably treated to prevent rust corrosion. If these parts are moving element then these shall be greased.

12. INSPECTION AND TESTING:We/our clients representative will visit works during manufacturing to assess the progress of work/ final inspection as to ascertain the quality as per approved quality approval plan.

All equipment and accessories shall be tested at works prior to dispatch and certified test report shall be submitted. Testing shall be done in accordance with the relevant standards.

Any defects noticed during inspection shall be rectified subsequently and a compliance report shall be submitted before dispatch.

Following minimum tests shall be carried out on the completed panel in the presence of the purchaser/ his representative.

Checking of correctness of wiring of circuits and continuity.

Electrical control, interlock and sequential operation test.

Functional tests

High voltage tests 2000 V to earth for one minute.

Insulation resistance will be before & after HV test and complete wiring with all equipment mounted on the cubicles.

Routine tests according to the standards followed by the manufacturer on the instruments, relays and other devices.

Physical & dimensional checks.

DC tests.

Test Certificates of all brought out items/components shall be submitted for verification.

13. DRAWING AND DOCUMENTATION SCHEDULE:The supplier shall furnish all the data/ drawings/ documents specified in the list for review/ approval.

The general arrangement drawings drawn to scale showing front, rear, side views with component mounting details, interconnection and wiring diagram as well as other drawings, which may be deemed necessary by the purchaser shall be submitted. Approval of GA drawing is required before fabrication of the panel. Approval of wiring and interconnection drawings is required before the panel wiring.

Bill of material shall correlate components to GA and schematic drawings. Components may be identified by the manufacturers catalogue number.

The diagram shall show clearly any connections to be made in field (because of shipping section). The vendor shall show all external cabling information contained in purchasers control wiring diagrams.

Number of copies of various documents required is listed below.

Sl NoDESCRIPTIONAfter Order

Till Final ApprovalFinal

1General Arrangement drawing with sectional views of panel, foundation details, Terminal arrangement details1212

2Schematic / wiring diagram 1212

3Rotor Earth fault capacitor Mounting box GA & wiring1212

4Relay setting recommendations1212

5Illustrative & descriptive literature of major components mounted in panel1212

6Quality assurance plan12-

7Test certificates of major bought out items1212

8Guarantee certificate1212

9Soft copies of final drawings in (.dwg format) in compact disc-4 Sets

1. GENERAL DATA:Quantity: TWO Set. (PER UNIT -1 No.) Each set consisting of 2 panels for Main-1, Main-2 protection groups separately. Exterior Paint shade Light admiralty grey shade no. 697, powder coated, Texture Finish Only.

Interior Paint shade Brilliant White

Degree of protection - IP 52.

Earth Bus size shall be 50 x 6 mm2 Tinned copper. (Separate Earth bus for Inst.)

Panel shall be suitable for Bottom Cable Entry

Tentative panel dimensions: (W x D x H) (Above height includes the base channel of 85mm plus 15mm thick anti vibration pad)

2. SYSTEM DETAILS:Generator voltage15.75 kV ( 10 %

Rated current8000 Amps

Rated frequency50 ( 5%

No of phaseThree

Fault level80 kA for 3 Sec.

Generator Neutral earthingNGTR

Auxiliary AC supply240 Volts, 50 Hz ( 10%

Auxiliary DC supply220 Volts, unearthed ( 10%

UPS240V AC, 50Hz ( 10%

CT Ratio8000 / 5 Amps

PT Ratio15750/3 / 110/3 Volts

Insulation Ratio17.5/38/95kV

Bus bar MaterialAluminum

Generator Protection & Metering SLD: 2001-01-01-01, REV-04, DATED 17.07.10

Generator Trip Logic: 2001-01-01-02, REV-02, DATED 12.07.10Note: For Detailed BOM, Please refer attached BOM.

Separate panel shall be provided for Group -1 & Group-2

PROJECT: 2 X 150 MW THERMAL POWER PLANT. (PHASE -II)

OWNER:M/s. SIMHAPURI ENERGY PRIVATE L.IMITED-HYD.

OWNERS ENGINEER: M/s. DEVELOPMENT CONSULTANTS PVT. LTD. KOLKATA.

EPC CONTRACTOR: M/s. MADHUCON PROJECTS LIMITED-HYDERBAD.

ORGINATOR ENGINEER: M/s. M.N.DASTUR & COMPANY (P) LTD-KOLKATA.